2.3 Water Circulation Systems
2.5
Flue System
Open or sealed type central heating systems (see Section
5) should be in accordance with the relevant recommendations given in BS 5376:2, BS 5449:l (for smallbore or
microbore systems) and the British Gas Specifications
for Domestic Wet Central Heating Systems.
Hot water systems should be in accordance with the relevant recommendations given in CP 342:l and the above mentioned British Gas publication and BS 5546.
2.4 Air supply - Open Flue Version
2Al
Room air supply
Where a boiler is to be installed in a room or internal space, the boiler requires the room or internal space containing it to have a permanent air vent. This vent must be
either direct to outside air or to an adjacent room or internal space which must itself have a permanent air vent
of at least the same size direct to outside air.
The minimum effective area of the permanent air
vent(s) is related to the maximum rated input of the boiler and should be not less than :
CHALLENGER 30 OF
21.15 cm2 (3.27 ins21
CHALLENGER 50 OF 53.73
cm2 (8.32 ins?
2A.2
Compartment air supply
If an open flued boiler is installed in a cupboard or compartment permanent air vents are reauired in accordan-
The boiler should be sited such that the maximum possible length of the flue system can be contained within the
building and that the route of the flue rises continuously
to the terminal and is as direct as practicable.
The first 600 mm (2ft) of flue pipe should rise vertically
from the draught diverter connection before the use of
any bends of elbows.
Horizontal or shallow angle runs, right angled bends or
mitred elbows should be avoided.
Where an existing brick chimney is to be used it should
be swept thoroughly before connection of the new boiler, and the chimney should be lined.
An approved British Gas terminal must be fitted and the
terminal sited at the.adjacent roof edge and, where possible, above the ridge line. The flue must not be terminated at or adjacent to a wall face.
The cross sectional area of the flue must not be less
than the area of the flue. outlet serving the boiler. The
point of termination must not be within 600 mm (2 ft) of
an openable window, air vent or other ventilation opening.
Before installing the boiler to an existing flue system,
the flue system must be checked by applying a smoke
match to the opening at the base of the flue system.
The flue pipe must not be closer than 25 mm (I ins) to
combustible material. For twin walled flue. pipe the
25 mm (I in) distance is measured from the internal pipe.
ce with the following table.
same room or internal space. and must both be on the
same wall to outside air.
Note that both air vents must communicate with the
Where cupboard or compartment vents communicate
with a room or internal space the room or internal space
must itself have a permanent air vent(s) as specified in
BS5440 pt2.
An open flued appliance must not be installed in a
bathroom bedroom or bedsitting room or in a compartment communicating with a bathroom, bedroom or bed
sitting room. An open flued boiler must not be installed
in a garage.
This appliance must be earthed. All wiring must conform
to the I.E.E. Regulations. The CHALLENGER requires a
2.6 Electrical Supply
240 V single phase, 50 Hz
supply.
A means of isolation
must be provided adjacent to the boiler, this should preferably be an unswtiched plug and socket. Alternatively a
double pole isolator having a contact separation of at
least 3 mm on both poles must be used. The fuse rating
should be 3 amp. The supply cord must be 0.74 m2 three
core heat resisting cable.
Cupboard or compartment air supply
30
OF
Low level
211 cm2 106 cm2
32 ins2 16 ins2
50
OF
Position of
Air from room Air direct
air vents
or internal space from outside
2A3 Effect of an extract fan
If there is any type of extract fan fitted in the premises
there is the possibility that if adequate air inlet area
from the outside is not provided, spillage of the products from the boiler flue could occur when the extract
fan is operating. Where such installations occur a spillage
test as detailed in BS5440:l must be carried out and any
necessary action taken.
2.7 Gas Supply
The
CHALLENGER
30 requires 1.09 m3/h 38.67 ft3/h.
CHALLENGER
50 requires 1.77 m3/h 62.53 ft3/h
of natural gas. The meter and supply pipes must be capable of delivering this quantity of gas in addition to the
demand from any other appliances in the house.
The complete installation must be tested for soundness
as described in CP 331:3
Fig. 2
5