5.
5.1
COMMISSIONING -OPEN VENTED SYSTEMS
Gas Installation
5.5 Adjusting the by-pass
The whole of the gas installation, including the meter
should be inspected and tested for soundness and purged in accordance with the recommendations of
CP 331 :3.
5.2
Water circulation system Open vented system only
The whole of the system should be filled and thoroughly
flushed out with cold water without the pump in posi-
tion. Ensure that all valves are open.
With the pump fitted the system should be filled and air
locks cleared. Vent all radiators and check for water
soundness.
Light the boiler as detailed in 5.3.
The water system should be heated to maximum wor-
king temperature and examined for water soundness.
Both gas and water should then be turned off and the
water system rapidly drained while still hot.
The system should again be filled, cleared of air locks and
examined for water soundness and inhibitor added to
the system if required in the specification (See section
3.9).
5.3 Lighting the boiler
a) Check that the gas service tap is open.
b) Switch controls to a demand mode, ensuring that
pump is running.
c) Push the button marked ‘on’ fully in and hold for 10
seconds.
d) Check that pilot is alight and release button slowly.
e) If the pilot extinguishes press red button and repeat
from (b). (The pilot should be about 13 mm (l/2”) long
and impinge on the tip of the thermocouple).
f) If the pilot extinguishes, wait 3 minutes and repeat b)
above.
g) After 30 seconds the main burner will light.
h) Check for gas soundness around the boiler gas corn-
ponents using sense of smell and leak detection fluid.
i) Check and adjust gas rate as detailled in 5.4.
5.4
Gas rate adjustment
(TO be carried out be-
fore adjusting by-pass.)
NB : The boiler is supplied rated at the highest output.
The boiler is fitted with a gas rate adjuster.
a) Switch boiler to off by pressing OFF button.
b) Remove the pressure test point screw C (8.5) and
connect a suitable pressure gauge.
c) Remove the hexagonal cap from gas volume adjuster,
D (7.5) exposing the adjustment screw.
d) Turn boiler on by pressing ON button (see lighting boi-
ler 5.3).
e) Adjust pressure after boiler has been running for 10
minutes and then check the gas rate. Setting pressures are given in graph relative to required output. The
pressure will be reduced by clockwise movement of
screw, increased by anti-clockwise movement.
f) Turn boiler to OFF and refit pressure test point screw
and volume regulator cap. Test for gas leakage
around pressure test point.
g) Mark the data badge to indicate output to which boi-
ler has been set.
h) Replace case. Particular attention must be given to
ensuring that the case seal is sound when the casing
is replaced.
NB : The by-pass valve should be of the lock shield pattern.
Set the pump to achieve the system requirements
but ensure that the minimum flow rate through the
boiler is achieved (See 1.4 - page 3). This is equivalent
to a temperature rise across the boi!er of 15” C. Set
boiler thermostat to maximum.
Fit the boiler with the by-pass fully closed and the
system on full load, i.e. central heating and domestic
hot water (indicator valve fully open).
Adjust the system to minimum load. This will normally
be central heating only with one radiator operating.
Open the by-pass gradually until the boiler operates
quietly at all flow temperatures and the boiler thermostat turns off the gas.
6
SEALED SYSTEMS
6.1
Safety valve
A safety valve shall be fitted close to the appliance on
the flow pipe. Only safety valves set to operate at 3 bar
shall be used ; they shall be so positioned or any discharge pipe so arranged, that discharge of water or steam
from the valve cannot create a hazard to occupants of
the premises or cause damage to electrical components
and wiring.
6.2 Pressure Gauge
A pressure gauge covering the range O-4 bar (O-60 Ib/in2)
shall be fitted to the system adjacent to, and visible
from, the filling point.
6.3 Expansion vessel
0) A diaphragm type expansion vessel shall be fitted by
a connection to the inlet side of the circulating pump,
in a manner laid down in the vessel makers’ instructions (see page 14 for illustration of recommended
system layouts). The expansion vessel shall be capable
of accepting water up to at least 62.5 % of its volume
without damage.
(ii) The nitrogen or air charge pressure of the expansion
vessel shall not be less than the hydro-static head
(height of the top point of the system above the expansion vessel).
(iii) The expansion vessel shall be sized in accordance with
the Table on page 14.
3
boil: output kW
9 ?
51 I I I I I I I I
i
5
40 E.F
5
I
B
e
30 BF
-6 t
=,
m
E
outputBtu/h
13