Chaffoteaux & Maury Centora green 18, Centora green 24 Installation And Operating Instructions Manual

CONDENSING WALL-HUNG COMBINATION BOILER
Central Heating and Instantaneous Domestic Hot Water - Fanned Flue system
Installation and Operating
Instructions
C
Centora green 18-24
G.C.N: 47-980-21
2
These instructions are suitable for ‘CENTORA GREEN’ boilers : Do not forget the Log Book!
Chaffoteaux & Maury supports Benchmark, the heating industry code to ensure the correct installation, commissioning and servicing of domestic central heating systems.
To The End User Make sure you have a completed Log Book for your boiler.
This provides a record of the commissioning of your boiler.
It contains important information about your particular installation that may be required by service engineers. The Log Book will also provide contact details for the installer should you need guidance in the use of this appliance or if there are any problems.
As with a car, your boiler will work more reliably and efficiently if regularly serviced. We recommend an annual service check. The service history of the appliance will be recorded in the Log Book.
In the unlikely event of any problems with your boiler or system you should first contact your installer. If your installer cannot resolve the problem he should telephone our national service helpline.
A charge may be made if Chaffoteaux & Maury Service is called out to resolve a non-product related fault.
Your statutory rights are not affected.
CUSTOMER CARE
Chaffoteaux & Maury, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products and a high quality after sales service. If it is necessary to contact an engineer, then telephone the national warranty helpline 0870 243 0224.
Advice on installation or servicing can also be obtained by contacting the C&M Services Department at Telford. CUSTOMER SERVICES DEPARTMENT Tel: 01952 222288 Fax: 01952 260915 GUARANTEE The manufacturer’s guarantee is for 12 months from the date of purchase. The guarantee is invalidated if the appliance is not
installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an efficient after sales service, please return the guarantee registration card enclosed with the boiler without delay.
STATUTORY REQUIREMENTS The installation of this appliance must be carried out by a CORGI Registered person or other competent person and in
accordance with the requirements of the Gas Safety (Installation and Use) Regulations. In addition, the installation must also comply with the current Water Regulations, Water Byelaws Building Regulations, IEE
Wiring Regulations, Local Authority Building Standards (Scotland) Regulations and the Safety Document 635 The Electricity at work Regulation. The appliance named below does not contain any asbestos or asbestos products, or mercury derivatives. Additional CFC’s have not been used in this product.
The appliance does not contain any potential hazard in relation to the COSHH regulations. It should also be carried out in accordance with current editions of the following British Standards Codes of practice: BS 6891,
BS 5440 parts 1 and 2, BS 5449 part 1, BS 7593, BS 6798, BS 5546, BS 4814, BS 7074 part 1 and 2, BS 7671 and BG DM2. If there is a possibility of the incoming mains water pressure exceeding 10 bar then a suitable pressure limiting valve must be
fitted where pressures exceed 6 bars a pressure limiting is preferred. Precautions: During servicing, keep the dust generation to a minimum and avoid inhaling any dust and contact with the skin
and eyes. Normal handling and use will not present any discomfort, although some people with a history of skin complaints may be susceptible to irritation. When disposing of the ceramic lining, ensure that it is securely wrapped and wash hands after contact.
TO CONTACT C&M SERVICE, PLEASE CALL THE NATIONAL WARRANTY HELPLINE ON:
0870 243 0224
To The Installer
As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the End User. Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history.
Please ensure that your customer is aware of the correct operation of the system, boiler and controls.
3
Contents
CUSTOMER CARE
Page
Guarantee ............................................................................................................................................................2
Statutory Requirements .......................................................................................................................................2
Contents ...............................................................................................................................................................3
INTRODUCTION ..................................................................................................................................................4
INSTALLATION INSTRUCTIONS........................................................................................................................5
1 DESCRIPTION.................................................................................................................................................5
2 DIMENSIONS .................................................................................................................................................6
3 HYDRAULIC DATA .........................................................................................................................................6
4 INSTALLATION REQUIREMENTS .................................................................................................................7
Location ...................................................................................................................................................7
Flue..........................................................................................................................................................7
Ventilation ................................................................................................................................................7
Gas Supply .............................................................................................................................................7
Electrical Supply ....................................................................................................................................7
Showers...................................................................................................................................................7
Flushing and Water Treatment ...............................................................................................................7
System Controls ......................................................................................................................................7
5 INSTALLING THE BOILER .............................................................................................................................8
Method of Positioning the Boiler On the Wall ..........................................................................................8
Connecting the Boiler to the System........................................................................................................8
Safety Valve and Condensate Drains......................................................................................................8
Fitting the Horizontal Flue .......................................................................................................................8
6 ELECTRICAL CONNECTIONS ....................................................................................................................10
Making the Electrical Connections ........................................................................................................10
7 COMMISSIONING AND TESTING................................................................................................................10
Pre-Commissioning................................................................................................................................10
D.H.W. ...................................................................................................................................................10
Central Heating .....................................................................................................................................10
Lighting the Boiler ..................................................................................................................................10
By-pass and Pump.................................................................................................................................11
Post Commissioning ..............................................................................................................................11
Handing Over to the End User ............................................................................................................11
8 FITTING THE CASING ..................................................................................................................................11
9 ADJUSTMENTS AND SETTINGS ................................................................................................................12
10 INCORRECT OPERATION............................................................................................................................17
11 GAS CONVERSION .....................................................................................................................................17
4
USER INSTRUCTIONS
Page
12- CONTROL PANEL ......................................................................................................................................18
13- HOW TO USE ..............................................................................................................................................19
Switching On ........................................................................................................................................19
Switching On the Central Heating .........................................................................................................19
Switching On the Domestic Hot Water .................................................................................................19
Switching On the Domestic Hot Water and Central Heating Together .................................................19
Stand-by Mode .....................................................................................................................................20
Turn Off the Boiler ................................................................................................................................20
14 MAINTENANCE ............................................................................................................................................20
15 GUARANTEE ................................................................................................................................................20
16 PRACTICAL INFORMATION ........................................................................................................................20
17 GAS CONVERSION .....................................................................................................................................21
18 INCORRECT OPERATION ...........................................................................................................................21
19 TECHNICAL DATA .......................................................................................................................................22
This instruction booklet is specifically designed for appliances installed in the United Kingdom
INTRODUCTION
The CENTORA GREENis a fully automatic, wall mounted, low water content condensing combination boiler. It is a room sealed, fan assisted, balanced flued appliance providing central heating and mains pressure domestic hot water on demand. It has electronic ignition and is suitable for all modern electrical control systems. The boiler is designed for sealed systems only. A circulating pump, expansion vessel, pressure gauge and safety valve are included within the boiler. The standard horizontal flue kit is suitable for lengths 300 mm minimum to 600 mm maximum and includes an elbow adapter that can be rotated through 360° . The horizontal flue can be extended up to 3 metres using 1 metre flue extension kits, 45° and 90° flue bends are also available as accessories.
5
1 - Steel chassis complete with expansion vessel 2 - Sealed chamber 3 - Burner and heat exchanger assembly 4 - Air/gas connection 5 - 24 V modulating fan 6 - Gas valve 7 - Ignition electrode 8 - Ionisation probe
9 - Ignitor 10 - Combustion products manifold 11 - 24 V transformer 12 - Siphon trap 13 - Electrical box 14 - Pump 15 - Secondary heat exchanger 16 - Pressure gauge 17 - Three way valve 18 - Automatic air separator and automatic vent 19 - Central heating flow switch 20 - Domestic hot water flow switch 21 - Central heating control thermistor 22 - Hot water control thermistor 23 - Overheat sensor
1
2
3
4
5
6
8
11
12
13
14
35
30
24
26
27
25
34
28
1 Description
INSTALLATION INSTRUCTIONS
7
Fig. 1
Fig 3
15
20
21
10
17
9
Fig. 2
33 36
3132
19
18
22
23
16
29
24 - Display 25 - Domestic Hot Water switch 26 - Green indicator – Domestic Hot Water mode ON 27 - D.H.W. temperature reducing key 28 - D.H.W. temperature increasing key D.H.W. mode
indicator
29 - Central Heating switch 30 - Green indicator – Central Heating mode ON 31 - Central Heating temperature reducing key 32 - Central Heating temperature increasing key 33 - Green indicator – Power ON 34 - Orange indicator - Burner ON 35 - Red indicator - Lock out/flame failure 36 - Reset key
6
0
4
3
2
1
5
6
100
200
800
700
600
500
400
300
900
1000
1100 l/h
mCE
Débit mini (robinets thermostatiques fermés)
Hauteur manométrique
GVF
G
VO
PVF
PVO
20 40 60 80 100 120Pf140 160 180 200 220 240
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
80°C
70°C
60°C
50°C
40°C
260
Pression à froid pour le circuit chauffage (en bar)
l
3
2
Dimensions
3 Hydraulic Data
Fig. 5
Fig. 6
450
500 min for servicing
With packaging : 43 kg
105
Type C12, C42 or C22
155
54 54 54 54
JKLMN
I
88
JKLMN
232
235
32
Safety valve center line
All dimensions in mm
Fig. 4
Type C 13 ou C 42
Pump head chart measured at the outlet of the boiler
System capacity chart
The boiler comprises a double speed pump and an adjustable by-pass.
The chart (fig. 5) shows the pump head available relating to the flow rate. GVF means high speed by-pass closed, PVF means low speed by-pass closed, GVO means high speed by-pass fully open, PVO means low speed by-pass fully open.
For adjustment procedure, please refer to section 9.
The minimum flow rate to ensure the correct function of the pump, should be over 300 l/h (with all heating thermostatic valves fully closed)
Maximum water capacity of Central Heating system :
The expansion vessel is pre-charged to 0.7 bar (10 lb/in 2 ).
The vessel is suitable for systems up to 145 litres capacity.
For systems of greater capacity an additional expansion vessel will be required. Refer to the chart below and BS 7074 pt 1 or BS 5449.
The minimum initial pressure of the system should be over
0.7 bar (1 to 1.5 bar is recommended).
I Safety valve C.H. and condensate
J Central
Heating flow
K
D.H.W. outlet
L
Gas supply
M
Cold water inlet
N Central
Heating return
Pump head available
Minimum flow rate (with all heating thermostatic valves closed)
Central heating initial pressure when cold (in bar)
157
177
Outer case dimensions :
- Width : 440 (minimum space required 450)
- Height : 850
- Depth : 380
Minimum clearances :
- Both sides 5 mm
- Above casing 170 mm
- Below casing 200 mm
- Front (for servicing) 500 mm
- Front (in operation) 5 mm
212
360
67
737
850
380
50
7
4
Installation Requirements
Location
The boiler can be installed on any suitable internal wall. Provision must be made to allow the correct routing of the flue and siting of the terminal to allow the safe and efficient removal of the flue products. A compartment or cupboard may be used provided that it has been purpose-built or modified for the purpose. It is not necessary to provide permanent ventilation for cooling purposes. Detailed recommendations are given in BS 5440 pt 2. If it is proposed that it is installed in a timber framed building then reference must be made to British Gas Document DM2, or advice sought from CORGI. Avoid installing the boiler where the air inlet can be polluted by chemical products such as chlorine (swimming pool aera), or ammonia (hair dresser), or alcaline products (launderette)
Flue
Detailed information on flue assembly is contained in the appropriate starter pack. The boiler must be installed so that the flue terminal is exposed to the free passage of external air at all times. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to. The minimum acceptable clearances are shown below:
- A Directly below an opening, window, etc 300 mm
- B Above an opening, window, etc 300 mm
- C Horizontally to an opening, window, etc 300 mm
- D Below gutters, soils pipes or drain pipes 75 mm
- E Below eaves 200 mm
- F Below balconies or car port roof 200 mm
- G From a vertical drain pipe or soil pipe 150 mm
- H From an internal or external corner 300 mm
- I Above ground roof or balcony level 300 mm
- J From a surface facing the terminal 600 mm
- K From a terminal facing the terminal 1200 mm
- L From an opening in the car port into the dwelling 1200 mm
- M Vertically from a terminal on the same wall 1500 mm
- N Horizontally from a terminal on the same wall 300 mm
- Q Fixed by Ubbink Rolux 4 GM flue terminal It may be necessary to protect the terminal with a guard. Reference should be made to the Building Regulations for guidance. Suitable guards may be obtained from the following manufacturer:
Quinnel Barret & Quinnel Wireworks Old Kent Road London SE15 1NL Tel: (020) 7639 1357
Ventilation
The room in which the boiler is installed does not require specific ventilation. If it is installed in a cupboard or compartment
permanent ventilation is not required for cooling purposes. Gas Supply
The gas installation and soundness testing must be in accordance with the requirements of BS 6891.The boiler requires a 22 mm supply. Ensure that the pipe size is adequate for demand including other gas appliances on the same supply. Combustion system protection The sulphur level contained in the gas should comply with the european Standards which are :
- maximum 150 mg/m3 for a short period in a year
- average level of 30 mg/m3 during one year
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and must be in accordance with current I.E.E. Regulations. It must also be possible to be able to completely isolate the
appliance electrically. Connection should be via a 3 Amp
fused double-pole isolating switch with a contact separation of at least 3 mm on both poles. Alternatively, a fused 3 Amp. 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower. It should only supply the appliance.
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 10 bar. All fittings and pipework connected to the appliance should be of the same standard. If there is a possibility of the incoming mains pressure exceeding 10 bar, particularly at night, then a suitable pressure limiting valve must be fitted. The boiler is designed to provide hot water on demand to multiple outlets within the property. If there is a requirement for greater demands, for example if the property has several bathrooms and cloakrooms, a vented or unvented hot water storage system may be used.
Showers
Any shower valves used with the appliance should be of a thermostatic or pressure balanced type. Refer to the shower manufacturer for performance guidance and suitability.
Flushing and Water Treatment
The performance of the appliance could be impaired by system debris or the effects of corrosion. The system must be flushed thoroughly to remove metal filings, solder, machining oils and other fluxes and greases before connecting the boiler. If it is an existing system, an appropriate flushing and descaling agent should be used. Refer to BS 7593 (1992) for guidance. For more information on the use of corrosion inhibitors, flushing and descaling agents, advice can be sought from the manufacturers of water treatment products such as:
Betz Dearborn Ltd Foundry Lane Widnes Cheshire WA8 8UD Tel: 0151 424 5351 Fernox Manufacturing Britannica Works Clavering Essex CB11 4QZ Tel: 01799 550811
System Controls
The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls. The addition of such external controls can be beneficial to the efficient operation of the system. The boiler connections for external controls are 24V and so only controls of 24V or that have voltage free contacts should be used.
Fig. 7
A
B
G
H
J
C
L
M
N
K
I
D,E
F
Q
H
N
M
Q
Q
I
8
5
Installing the Boiler
Please check that you are familiar with the installation requirements before commencing work.(section 4)
The installation accessories described in the following list are included in the boiler packaging.
- Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clearances, fitting instructions and commissioning instructions)
- Connection tails
- Screws and wall plugs
- Connection washers and filters
- Installation manual
Method of positioning the boiler on the wall.
The paper template can be used to ensure the correct positioning of kitchen cabinets etc. It also details the commissioning instructions.
The paper template has to be fixed to the wall and used to locate the position of the hanging bracket and the centre for the flue hole.
Drill and plug the wall and secure the hanging bracket using the screws provided. Remove the boiler from its packaging as shown in fig. 8 and unscrew the 4 screws
A and remove the casing (Fig. 9).
Place the boiler on the wall on the hanging bracket (Fig. 11). If required, there is space for all piping to pass behind the boiler. Using Fig. 11 for reference, connect the gas and water pipes and the valves to the base of the appliance using the tails provided. There is a 190 mm space between the valves and the wall to make these connections.
Connecting the boiler to the system
- Push in the tabs P(Fig. 13) on either side of the boiler and pivot the electrical box forward to gain access to the valve
connections
- Remove the yellow caps and connect the boiler to the taps using the washers provided in the plastic bag.
4 x fibre washers for the C/H flow and return, hot water outlet and cold water inlet connections 1 x rubber washer
R” for gas connection.
Provision must be made to fill and recharge the system pressure. This can be achieved using a filling loop or other methods approved by the local water authority. Before fitting the tails onto the connecting bracket, please check the correct location of the flow restrictor
L (Fig.10) on the
main inlet.
Safety valve and condensate drains
The pressure relief valve tube is clear silicone. It should terminate below the boiler over a tundish or 22 mm pipe (see I Fig. 4) which should in turn discharge safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.
External termination via condensate siphon The condensate drainage pipe should have a minimum diameter of 22 mm and the external pipe length should not be more than 3m. The external length should be kept as short as possible to minimize the effect of freezing.
Please refer to
BS 6798:2000
The system should be carefully checked for leaks, as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger. The pipe from the siphon 12 (Fig. 1) should be connected to a drain as described in the relevant Brittish regulations.
Pay a special attention to not bend the condensate drain pipe as the flow will be interrupted. Please use exclusively drain pipe material compatible with condensate products. (refer to
BS 6798:2000)
The condensate flow can reach 2 l/hr; because of the acidity of the condensate products (Approx. Ph2), take care before operation.
Fitting the Horizontal Flue Attention ! Before starting the boiler, the siphon (12 Fig. 1) must be filled with water. Before fitting the flue terminal
onto the boiler, please pour 1/4 litre of water into the exhaust pipe as shown in (Fig. 12).
The instructions for the vertical and biflux (twin pipe) flue options are included with the relevant adapter kits. The standard flue supplied with the appliance is suitable for lengths from 300 mm minimum to 720 mm maximum. This means for rear flueing, the standard kit will accommodate a maximum wall thickness of 600 mm, and for side flueing a
maximum wall thickness of 587 mm. This takes into account the minimum appliance side clearances of 5 mm. If the flue is a side exit installation, then calculate the position of the hole with a slope of 5 mm / metre towards
the boiler from the terminal. The flue should rise up slightly to the terminal in order to allow the condensate back into the boiler.
Attention ! Use only a C&M condensation flue kit.
9
5
Installing the Boiler
(continued)
A
Fig.11
A
A
A
Fig. 9
Fig. 10
L
Fig. 8
Fig.12
10
Making the Electrical Connections
Lower the electrical box to gain access to the electrical connections. Push in the tabs P (Fig. 13) on either side of the boiler and pivot the box forward. Undo the two retaining screws
V , remove the cover and remove the cable clamp. C (Fig. 14)
Connect the live and neutral wires to the multipin plug
J1 (Fig. 14) leaving sufficient earth wire to connect to the earthing point
T (Fig. 14).
Note: The connections should be made so that should the lead be pulled from its anchorage, the current carrying wires become taut before the earth wire.
If using a room thermostat or other external control, they can be connected in place of the link
S (Fig. 14) on the multipin
Plug. Note: Use only controls designed for voltage free switching or 24V supply. Do not connect to a 230V supply. Connect the multipin plug into the socket on the printed circuit board. Secure the cable using the cable clamp and
replace the cover. NB The room thermostat options setting can be made before replacing the electrical box cover
1 (Fig.14).
All necessary settings for room thermostat operations are described in Section 9 ADJUSTMENTS AND SETTINGS.
TR
COM
REP
8
M/A
VITESSE
1
1
1
1
1
1
BUS
1
CALYDRA
OFF
ON
11
12
2
1.23
OFF ON
11
12 1
SW2
PROG
SW1
TA
1
T2A
1
MCD
1
230V
MOTEUR
RL6
R133
C28
T15
R36
R35
C80
C79
T16
R34
T12
T11
R107
R33
R130
R129
D43
U9
Z7A
R132
R16
R15
R14
C84
C83
R6a
Z4A
C78
RL13
C73
Z6
R7a
Z7
Z4
D46
T10
T9
RL8
RL7A
RL7
RL10
RL2A
RL2
RL9
R119
R118
R113
R9
R8
R7
R6
R31
R32
R29
R27
R25
R24
R23
R19
R18
R17
R140
R137
TH4
R13
R12
R11
R115
C82
C81
T14
T13
R136
TH3
U11
R64
R10
R63
R59
R128
R112
J9
J6
J7
J4
J3
J2
J1
F1
D5
D31
D30
D32
D42
D41
D40
D35
D36A
D36
D17
D16
D15
D14
J11
C34
J5
C52
C51
C75
C74
C31
C38
C27
C26
C25
C1
J12
U12
+5V
J
T
S
J 1
Fig. 14
6
Electrical Connections
J
T
C
S
7 Commissioning and Testing
Pre-commissioning
Ensure that the system has been adequately flushed. Purge the gas supply of air and test for soundness. Carry out final electrical tests to ensure the correct polarity and earthing continuity.
D.H.W.
Open the main cold feed valve 40 (Fig. 15). Open all hot taps to purge the D.H.W. system. Check for water soundness. Check the flow rate at the bath tap is set correctly (see technical data).
Central Heating
Open the flow and return valves on the boiler 37 and 41 (Fig. 15) Open the automatic air vent 18 (Fig. 2) Fill the system and vent the radiators. Set the system pressure and remove the filling loop. Check for leaks. Manually check the pump is free to turn. Switch on the electrical supply. Press the Central Heating switch 29 (Fig. 3) to switch on the heating mode. Press the +’ key 32 (Fig. 3) to set the heating temperature to
maximum. Allow the pump to run for several minutes. Isolate the electrical supply. Drain the boiler and check the water filter for installation debris. Replace the filter and recharge system.
Lighting the Boiler
Connect a gas pressure gauge to the test point 39 (Fig. 21). Turn on the gas supply and boiler gas tap 39 (Fig. 21). Ensure the electrical supply is on. Ensure all external controls are calling for heat. Press the Central Heating switch 29 (Fig. 3) to switch on the heating mode. Press the +’ key 32 (Fig. 3) to set heating temperature to maximum. The boiler will light. Allow the boiler to heat the system. Check the inlet gas pressure (working pressure) while the boiler is operating in D.H.W. mode. (Refer to technical data). Check the operation of the boiler controls and safety devices. (see the servicing leaflet for details). Set the by-pass (refer to the page
12). Re-flush the system to remove any dissolved oils and fluxes. Recharge system pressure and introduce any water treatment as required.
P
V
P
Fig. 13
11
7
Commissioning and Testing
(continued)
By-pass and Pump
The boiler is fitted with a pre-adjusted by-pass. Although adjustment is not normally necessary, the by-pass can be reset by turning screw D (Fig. 15 ) anticlockwise to open the by-pass using the chart below for guidance. If used on a system with thermostatic radiator valves, the flow rate with the thermostatic valves closed should be adjusted to at least 300 l/hr. The enclosed charts indicate the residual head of the pump available for the system. The pump fitted on the boiler is a double speed model. (GV = High speed and PV = low speed). The speed setting is described in Section 9. Speed selection is only available in C.H. mode.
Post Commissioning
Ensure the system pressure has been set correctly. Set all the parameters of the boilers as shown in Section 9 ADJUSTMENTS AND SETTINGS. Set the boiler thermostat and controls. Set the programmer to the requirements of the End User. Set the external controls. Ensure the Log Book is fully completed with your contact details and all the required details of the installation.
Handing Over to the Householder
Demonstrate the lighting and operation of the boiler. Demonstrate how to maintain the system pressure. Demonstrate the operation and setting of the built-in clock. Explain the benefits of annual maintenance by a competent person. Explain how to register the guarantee. Ensure the End User countersigns the Log Book to confirm that these demonstrations have been carried out and understood.
T
T
1
2
Fig. 17
Fitting the casing
Remove the protective film from the casing :
- Position the casing as shown fig. 17
- Slide down the casing and locate the casing holes on the plastic pins on top of the chassis
- Ensure the correct positioning of the casing onto the boiler
- Tighten the 4 screws located at the bottom as shown in Fiig. 16.
8 Fitting the Casing
A
A
A
A
Fig.16
b
a
r
0
1
3
4
Fig. 15
D
16
37
39
40
41
12
The boiler is delivered with pre-set values described in menus 3 and 4. All settings can be changed by the installer or a qualified person. To gain access to the setting keys please, open the front door
P. (Fig. 18)
DISPLAY
1st digit
2nd digit
3rd digit
Menu key
Setting key
To gain access to the setting menus press both the and keys on the D.H.W. side for 5 seconds. (Fig. 18). Menu 1 is displayed.
Changing the menu :
Press the key (C.H. side) (Fig.18). The menu number is displayed for 3 seconds. Press the + key (C.H. side) again to show the next menu.
Changing section in a menu
(available only for menus 3 and 4)
:
Press the or key (D.H.W. side) to change from one section to the next in a menu. Note : When you arrive at the last section of a menu, pressing the key will change to the 1st section. When you are at the first section, pressing the key will change to the last section of the menu.
Setting a parameter in a section:
Press the key (C.H. side) to enter the modification mode. The 2nd and 3rd digits will flash. Press the or key (D.H.W. side) to select the correct value then press the key (C.H. side) to validate the modification and to exit the setting mode. The 2nd and 3rd digits will stop flashing.
Recalling the basic configuration:
Select menu 3 or 4 then press the key (D.H.W. side) and the key (C.H. side) for more than 5 seconds. The digits will flash
CM for a while to indicate that the operation is completed.
Erasing the default register :
Select menu 1 then press both the key (D.H.W. side) and the key (C.H. side) for more than 5 seconds. The digits will flash
CM for a while to indicate that the operation is completed.
Note : To exit the setting mode, leave the boiler for approx. 1 minute, the computer will then switch back to user mode.
DISPLAY
Fig. 18
P
D.H.W. keys
C.H. keys
9
Adjustments and Settings
13
5
Menu - 1 - Default register
Records the last 10 defaults
Section Digit 1 Digit 2 and 3
Last default occured 0
code from 01 to 99
Last but one default occurred 1
code from 01 to 99
... ... code from 01 to 99
Last default occurred before the previous one 9
code from 01 to 99
Menu - 2 - Boiler conditions
Indicates the conditions or the configurations of the boiler
Section Digit 1 Digit 2 and 3
Software version of display P.C.B. 0
10 to 99
Nominal Power of the boiler (type 18 or 24 kW) 1
24
Flue type 2
1 : FF
variable speed
Room thermostat is calling for heat 3
0 : no
3
1 : yes
Theoretical position of the 3 way valve 4
0 : D.H.W.
4
1 : C.H.
DHW flow temperature in oC 5
from 00 to 99
CH flow temperature in oC 7
from 00 to 99
Software version of main P.C.B. 9
10 to 99
DISPLAY
ACTION CONFIGURATION
once
x times
x times
Note -- is displayed if no default is recorded.
14
Menu - 3 - Boiler options
DISPLAY
ACTION CONFIGURATION
Section Digit Digit
1 2 and 3
Under floor heating system 0 0 : no
1 : yes
Factory
setting
Menu - 4 - Boiler settings
Section Digit Digit
1 2 and 3
Room thermostat operation 0 0 : Burner only
0 1 : Burner and pump
Pump speed 1 0 : High speed
1 1 : Low speed
Pump post circulation duration 2 0,0 min
From 0 to 5 minutes by step of 0.5 min. 2 0,5 min
2 1,0 min
2 5,0 min
Maximum Central Heating flow temperature 4 50°C
C.H. anti cycling delay 4 80°C
TAC 8 0,0 min
From 0 to 5 minutes by step of 0.5 min. 8 0,5 min
8 2,5 min
8 5,0 min
C.H. maximum output limitation Power by step of 1 kW value
For a 24 kW model 9 8 to 18
Factory
setting
DISPLAY
ACTION CONFIGURATION
once
x times
once
x times
15
Menu - 5 - Combustion rate control mode
X X
X X
DISPLAY
ACTION CONFIGURATION
wait 5
Combustion rate control mode OFF
Switching on the combustion rate control mode. Central heating output reaches the maximum power set in menu 4 section 9.
Central heating temperature is displayed in oC. The 3 dots indicate that the combustion rate control is ON at maximum output.
Switching the combustion rate down to minimum power.
Central heating temperature is displayed in oC. The dot indicates that the combustion rate control is ON at minimum output.
Switching on the combustion rate to maximum output set in menu 4 section 9.
Central heating temperature is displayed in oC. The 3 dots indicate that the combustion rate control is ON at maximum output.
X X
Switching off the combustion rate control mode.
press once
press once
press once
press once
press once
Effect Display
Locking conditions of the combustion rate control mode :
- boiler in stand by mode
- D.H.W. draw off
- room thermostat is not calling for heat
- room thermostat is calling for heat but the maximum temperature is reached
- boiler in lockout mode
- after a reset or if the main supply fails
- end of the mode if the operator exits menu 5
- after 15 minutes if no keys are pressed.
Note : As soon as the combustion rate control mode is on, the Central Heating and Domestic Hot Water keys
will become inactive.
16
C.H. power output setting :
If you would like to change the setting of C.H. power output to 12 kW, please proceed as follows : (Note: the factory setting is 18 kW and the following explanation refers to menu 4 section 9)
- Switch to installer mode, press the and keys on the D.H.W. side
for 5 seconds. The display shows :
-1- then 0•-- if there is no default in the
default register.
- press the key (C.H. side ) 3 times
to gain access to menu
-4-,
The display shows :
-4- then the value set for section 0 ( 00
or 01 respectively (action on burner only or pump and burner)
- Select section 9 (Adjustment of C.H.
heat output). Press the key (D.H.W. side) 9 times. The display shows : 918 (this corresponds to 18 kW which is the factory setting) 9 = section 9 18 = 18 kW
- press the key (C.H. side) once,
the 2nd and 3rd digits will flash together. Then press the key (D.H.W. side) to change to 3.0 on the 2nd and 3rd digits. The display shows : 912 press the - key (C.H. side) to confirm this value. The display will stop flashing. The setting procedure is finished. To exit from the setting mode, leave the boiler for approx. 1 minute the computer will then return to the user mode. After programming is completed
please close the door.
P (fig. 17)
1
Display
2
x 3
1
2
or
3
3
x 9
4
4
5
9
Adjustments and Settings (continued)
17
10
Incorrect Operation
In case of a problem, or when the boiler displays a message, the 2 digits will flash.. Please refer to the table below to diagnose the default.
For default 01 and 03, the red indicator
35 will light (Fig.19)
35
Fig. 19
Overheat lock-out
FAULT
Code
display Fault description Operation Information
01 Overheat lock-out 03 No flame detection 05 Anti freezing system, pump on 06 Anti freezing system, pump and burner on 07 No water circulation in primary circuit 08 No water in the primary circuit 09 Domestic Hot Water thermistor faulty (open circuit) 10 Domestic Hot Water thermistor faulty (short circuit) 11 Central Heating thermistor faulty (open circuit) 12 Central Heating thermistor faulty (open circuit) 18 Attempt to re-light 20 Wiring problem 23 Fan speed too low 24 Fan control system defective 29 Three way valve blocked in C.H. mode 31 Communication problem with the display P.C.B. 32 Communication problem with the main P.C.B.
If the boiler is not set for the gas type, conversion kits are available. To convert the boiler, please use originally Chaffoteaux & Maury parts and proceed as is mentioned in the instruction manual provided with the conversion kit.
11
Gas Conversion
18
USER INSTRUCTIONS
Control panel (Fig. 20)
16.- Pressure gauge
24.- Display
25.- Switch for Domestic Hot Water mode
26.- Green indicator Heating Domestic Hot Water mode ON
27.- Key to reduce the Domestic Hot Water temperature
28.- Key to rise up the Domestic Hot Water temperature
29.- Switch for Central Heating mode
30.- Green indicator: Central Heating mode ON and RESET (
Reset button)
31.- Key to reduce the Central Heating temperature
32.- Key to increase the Central Heating temperature
33.- Green indicator - Power ON
34.- Orange indicator - Burner ON
35.- Red indicator - Lock out/flame failure
36.- Reset button
12
Control Panel
Connecting bracket (Taps shown in the open posi-
tion) (Fig. 21)
37 : Central heating flow isolating valve 38 : Domestic Hot Water outlet 39 : Gas service tap
40 : Water service tap 41 : Central Heating return isolating valve 43 : Central Heating pressure relief valve 45 : D.H.W. drain screw
16
24
27
26
25
29
28
30
31
32
34
35
36
33
Fig. 20
STOP
+
+
+
+
Fig. 21
37 41
40
39
43
38
45
19
Switching on
1. Check that the pressure in the central heating system is above 0.7 bar and below 1.5 bar with the pressure gauge 16
(Fig.20)
2. Check that the gas service tap is opened at the gas meter and the main power is on. Green indicator (Power ON )
33 (Fig.20).
3. Open the gas tap
39 (Fig.21).
The boiler is now ready to use.
Attention ! If the boiler has been off for a long period of time without working, some air in the gas pipe can hinder the first
attempts to ignite. (please refer to section 18 (Incorrect Operation)
Switching on the Central heating
Press the key 29, the green indicator 30 (Fig.20) light and the display will show the
Heating flow temperature.
Keys
31 and 32 (Fig.20) allow the temperature to be adjusted as required in the
Central Heating system depending on the weather conditions.
press to increase the temperature when the weather is cold
press to reduce the temperature when the weather is fair
During the temperature setting operation the display will flash.
If the room thermostat is calling for heat, a dot will be displayed at the bottom of the 3rd digit
Switching on the Domestic Hot water
Press the key 25, the green indicator 26 (Fig.20) will light :
If there is no water demand
the display will show the following graphic
During
draw off
a square made of 4 digits will move clockwise on the display
Keys
27 and 28 (Fig.20) allow the temperature to be adjusted as required for the Domestic Hot Water flow. During the
temperature setting operation the display will flash.
Note : The configuration of the C.H. system can generate some gravity effect when the boiler is set to the D.H.W. mode only. It may result in a temperature rise of the heating pipes close to the boiler (or eventually a radiator). To avoid this, it is possible to close the heating flow isolating tap
37 (Fig.21) during the summer period (Central Heating switched off) Dont forget to open
it before switching on the Central Heating mode again.
13
How to Use
Switching on the Domestic Hot Water and the Central Heating together
Press the key 29 the green indicator 30 (Fig.20) will light. Press the key
25 the green indicator 26 (Fig.20) will light.
If there is no water demand
the display will show the heating flow temperature
During draw off
a square made of 4 digits will move clockwise on the display
20
As with a car, your boiler will work more reliably and efficiently if regularly serviced. We recommend an annual service check. The service history of the appliance will be marked in the Log Book.
14
Maintenance
Turn off the boiler
- Press the and keys, 25 and 29 to (Fig.20) switch off both the D.H.W. and the C.H. mode. The green indicators 30 and 26 (Fig.20) will go out.
- Switch off the main electrical supply
- Shut off the gas service tap
39 (Fig. 21)
Note : In this condition, the anti-freeze system is inoperative.
Stand by mode A fixed digit at the centre of the display and the green indicator 33
(
Fig.20) will light.
Putting the boiler in stand-by mode and anti-freeze system. :
Press the and keys, 25 and 29 (Fig.20) to switch off both the D.H.W. and the C.H. mode. The green indicators 30 and 26 (Fig.20) will go out.
During the duration of the stand by mode, an automatic anti-sticking system will activate the pump for 1 minute and operate the 3 way valve every 23 hours. The stand-by mode will disable the anti-freeze function of the room thermostat (if fitted). To leave the room thermostat anti-freeze system operative, please leave the Central Heating mode on.
The boiler is equipped with an automatic anti freeze system which is permanently on.
If the Central Heating temperature decreases below 7
o
C, the pump will start.
If the Central Heating temperature decreases below 4
o
C, the pump and the burner will start.
13
How to Use (
continued
)
15
Guarantee
The manufacturers guarantee is valid for 12 months from the date of installation. The guarantee is voidable if the appliance is not installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an efficient after sales service, please return the guarantee registration card enclosed with the boiler without delay.
16
Practical Information
Pump anti-sticking device
When the boiler is switched on, an automatic anti-sticking system will activate the pump for 1 minute and operate the 3 way valve every 23 hours. This is a normal function.
Precaution to avoid freezing
We recommend you to contact your installer or local service centre for further information.
D.H.W. system
Turn off the mains cold water supply and drain the boiler :
- Open a hot water tap
- Unscrew the cold water inlet tail
- Drain the water from the boiler with the D.H.W. drain screw
45 (Fig. 21)
C.H. system
Chose one of the following solution :
- 1) Drain the Central Heating system completely.
- 2) Protect the Central Heating system with anti freeze chemical products and periodically check the concentration
- 3) Leave the Central Heating mode switched on and set the room thermostat to its anti-freeze mode (between 5 and 10
o
C)
- 4) Leave the boiler in stand-by mode, the anti-freeze device will activate the pump and the burner if necessary.
21
This appliance is suitable for Natural gas or L.P.G. Any gas conversion must be made by a competent person.
17
Gas Conversion
18
Incorrect Operation
If these solutions do not cure the fault, call a qualified professional
Fault
The boiler doesnt start
Red indicator illuminates
Noises in the C.H. system
Radiators rise in temperature During summer season
Cause
No gas, no water or no electricity
Air in the gas pipe
Room thermostat switched off
Air is present in the C.H. system or. system pressure is insufficient.
Gravity effect in the C.H. system
Solution
Control gas, water and electrical supply, fuses
Follow the procedure in section 7
Set up the room thermostat
Wait for a few minutes Press the reset button
36 (Fig.21) the
red L.E.D. goes out and the boiler attempts to re-light.
If the red indicator illuminates frequently, please call your localfaîtes service centre.
Purge the system of air and increase the system pressure (section 7)
Close the C.H. flow isolating valve. Dont forget to open it again before you switch on the Central Heating.
22
19
Technical Data
Model Centora green 18-24
Appliance category........................................... II 2H3P
Gross heat input C.H. max.............................. 20.9 kW 71,290 Btu/h
Gross heat input D.H.W. max .......................... 27.8 kW 94,800 Btu/h
Heat output C.H. 50°/30° max.......................... 19.5 kW 66,550 Btu/h
Heat output C.H. 80°/60° max.......................... 18 kW 61,430 Btu/h
Heat output D.H.W. max .................................. 24 kW 80,910 Bth/h
C.H. operating temperature.............................. 80°C max 25°C min
C.H. circuit pressure min operating.................. 0.7 bar 10 Ib/in
2
C.H. circuit pressure max operating................. 2.5 bar 36.3 Ib/in
2
D.H.W. flow rate ∆T30°C................................. 12 l/min 2.66 gal/min
D.H.W. flow rate
T35°C ................................ 10.3 l/min 2.29 gal/min
Cold water mains pressure min operating........ 0.5 bar 7.25 Ib/in
2
Cold water mains pressure max operating....... 10 bar 145 Ib/in
2
Flow limiter rate................................................ 8 l/min
Compartment ventilation .................................. not required
Natural gas G20
Gas rate C.H. max ........................................... 1.98 m3/h 70 ft3/h
Gas rate D.H.W. max....................................... 2.65 m
3
/h 93 ft3/h
Gas rate C.H. & D.H.W. min ............................ 0.87 m
3
/h 31 ft3/h
Gas valve restrictor diameter ........................... 5.55 mm
Propane L.P.G. G31
Gas rate C.H. max. .......................................... 1.46 kg/h 27 ft3/h
Gas rate D.H.W. max....................................... 1.94 kg/h 36 ft
3
/h
Gas rate C.H. & D.H.W. min ............................ 0.64 kg/h 12 ft
3
/h
Gas valve restrictor diameter ........................... 4.15 mm
Safety discharge .............................................. 3 bar 43.5 Ib/in
2
Expansion vessel - Pre-charge pressure ......... 0.7 bar 9.4 Ib/in
2
Net capacity at 3 bar in litres............................ 5.44
Adjustable by-pass Electrical characteristics
Supply .............................................................. 230V~
Consumption.................................................... 150W
Protection......................................................... IP4 XD
Fuse F1............................................................ 2 A
Fuse F2............................................................ 1.25 A
Fuse F3............................................................ 0.315 A
Fuse F4............................................................ 0.250 A
External controls .............................................. 24V~
23
1309033a - 02/2002
Chaffoteaux & Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
Manufacturer: Chaffoteaux & Maury - France
Commercial subsidiary: MTS (GB) Limited
MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax: (01494) 459775 internet: www.chaffoteaux.co.uk E-mail: info@mtsgb.ltd.uk
Technical Support Help Line: (01952) 222288
MAINTENANCE AND
SERVICE GUIDE
Fanned Flue Condensing Wall Hung
Combination Boiler
Central Heating and Instantaneous
Domestic Hot Water
Dimensions
Technical Data
Flue types: C 13: horizontal
C
54 54 54 54
JKLMN
I
88
JKLMN
232
235
32
Safety valve centre line
All dimensions in mm
Outer case dimensions :
- Width : 440 (minimum space required 450)
- Height : 850
- Depth : 380
212
360
67
737
850
380
50
I Safety valve outlet J Heating flow K D.H.W. flow L Gas supply M Cold water inlet N Heating return
Gross heat input C.H. max............................ 9.2 to 20,9 kW
Gross heat input D.H.W. max ....................... 9.2 to 27.8 kW
Heat output C.H. 50°C/30°C max.................. 8.3 to 19.5 kW
Heat output C.H. 80°C/60°C max.................. 8 to 18 kW
Heat output D.H.W. max ............................... 8.3 to 24 kW
C.H. operating temperature........................... 80°C max
C.H. circuit pressures Min operating ............. 0.7 bar
C.H. circuit pressures Max operating ............ 2.5 bar
D.H.W. flow rates
T30°C............................. 12 l/min
D.H.W. flow rates
T35°C ............................ 10.3 l/min
Cold water mains pressures Min operating... 0.5 bar Cold water mains pressures Max operating.. 10 bar
Flow limiter rate............................................. 8 l/min
Safety discharge ........................................... 3 bar
Expansion vessel - Pre-charge pressure ...... 0.7 bar
Nett capacity at 3 bar in litres........................ 5.44
Supply ........................................................... 230 V~
Consumption ................................................. 150 W
Protection ...................................................... IPX4D
Fuse F1/F2/F3/F4 ......................................... 2 A/1.25 A/0.315 A/0.250 A
External controls ........................................... 24 V~
Natural Gas G20
Gas rate C.H. max .......................... 1.98 m3/h
Gas rate D.H.W. max...................... 2.65 m
3
/h
Gas rate C.H. & D.H.W. min ........... 0.87 m
3
/h
Gas valve restrictor diameter.......... 5.55 mm
Propane L.P.G. G31
Gas rate C.H. max. ......................... 1.46 kg/h
Gas rate D.H.W. max...................... 1.94 kg/h
Gas rate C.H. & D.H.W. min ........... 0.64 kg/h
Gas valve restrictor diameter.......... 4.15 mm
2
Pump and Expansion Vessel Characteristics
Components Location
Note : The system initial pressure should be over the following value :
System static height (in metre) + 0.7 = Initial pressure (in bar)
10
GV F= high speed by-pass closed GVO = high speed by-pass open PV F= low speed by-pass closed PVO = low speed by-pass open
20 40 60 80 100 120Pf140 160 180 200 220 240
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
80°C
70°C
60°C
50°C
40°C
260
Pression à froid pour le circuit chauffage (en bar)
C litre
System capacity chart
Central heating initial pressure when cold (in bar)
0
4
3
2
1
5
6
100
200
800
700
600
500
400
300
900
1000
1100 l/h
mCE
Débit mini (robinets thermostatiques fermés)
Hauteur manométrique
GVF
GVO
PVF
P
VO
Pump head available
Minimum flow rate (with all heating thermostatic valves closed)
b
a
r
0
1
3
4
1
2
3
4
5
6
8
11
12
13
14
7
15
10
9
16
1.- Steel chassis complete with expansion vessel (not visible)
2.- Sealed chamber
3.- Burner and heat exchanger assembly
4.- Air/gas connection
5.- 24 V modulating fan
6.- Gas valve
7.- Ignition electrode
8.- Ionisation probe
9.- Ignitor
10.- Combustion products manifold
11.- 24 V transformer
12.- Siphon
13.- Electrical box
14.- Pump
15.- Secondary heat exchanger
16.- Pressure gauge
17.- Three way valve
18.- Automatic air separator and automatic vent 19 - Central Heating flow switch
20.- Domestic Hot Water flow switch
21.- Central Heating control thermistor
22.- Domestic Hot Water control thermistor
23.- Overheat sensor
37.- Central Heating flow isolating valve
38.- Domestic Hot Water outlet
39.- Gas service tap
40.- Water service tap
41.- Central Heating return isolating valve
43.- Central Heating pressure relief valve
46.- User instructions
47.- Connecting tails (x5)
48.- Condensate drain
49.- Adjustable by-pass
50.- Right hydraulic assy
51.- Left hydraulic assy
23
20
21
17
19
18
22
23
39
40
41
38
37
43
46
47
48
49
50
51
3
FUNCTIONING
Control Panel
35
30
24
26
27
25
34
28
33 36
3132
29
24.- Display
25.- Domestic Hot Water switch
26.- Green indicator – Domestic Hot Water mode ON
27.- D.H.W. temperature reducing key
28.- D.H.W. temperature increasing key D.H.W. mode indica-
tor
29.- Central Heating switch
30.- Green indicator – Central Heating mode ON
31.- Central Heating temperature reducing key
32.- Central Heating temperature increasing key
33.- Green indicator – Power ON
34.- Orange indicator - Burner ON
35.- Red indicator - Lock out / flame failure
36.- Reset key
Switching On
1. Check that the pressure in the Central Heating system is above 0.7 bar and below 1.5 bar with the pressure gauge 16.
2. Check that the gas service tap is open at the gas meter and the main power is on. Green indicator Power ON
33.
3. Open the gas tap
39 (Fig.21).
The boiler is now ready to use.
Attention ! If the boiler has been off for a long period of time, some air in the gas pipe can hinder the first attempts to ignite.
(please refer to Section 19 Incorrect Operation).
Switching on Central Heating
Press the key 29, the green indicator 30 will light and the display will show the Central
Heating flow temperature.
Keys
31 and 32 allow the temperature to be adjusted as required for the Central Heating
system depending on the weather conditions.
press to increase the temperature when the weather is cold
press to reduce the temperature when the weather is fair
During the temperature setting operation the display will flash.
If the room thermostat is calling for heat, a dot will be displayed at the bottom of the 3rd digit
Switching on the Domestic Hot water
Press the key 25 the green indicator 26 will light :
If there is no water demand
the display will show the following graphic
During
draw off
a square made of 4 digits will move clockwise on the display
Keys
27 and 28 allow the temperature to be adjusted as required for the Domestic Hot Water flow. During the tempera-
ture setting operation the display will flash.
Note : The configuration of C.H. system can generate some gravity effect when the boiler is set in D.H.W. mode only. It may result in a temperature rise of the heating pipes close to the boiler (or eventually a radiator). To avoid this, it is possible to close the heat­ing flow isolating tap
37 (Fig. 21) during the summer period (Central Heating switched off). Don’t forget to open it again before you
switch on the Central Heating mode again.
4
Switching On the Domestic Hot Water and Central Heating Together
Press the key 29, the green indicator 30 will light. Press the key
25, the green indicator 26 will light.
If there is no water demand
the display will show the heating flow temperature
During
draw off a square made of 4 digits will move clockwise on the display
Turn Off the Boiler
- Press the key 29 and the key 25, to switch off both the D.H.W. and C.H. mode. The green indicators 30 and 26 will go off.
- Switch off the main electrical supply
- Shut off the gas service tap
39 (Fig. 21)
Note : In this condition, the anti-freeze system is inoperative.
Stand-by Mode A fixed digit at the centre of the display and the green indicator 33 will illumi
nate.
Putting the boiler in stand-by mode and anti-freeze system. :
Press the key 29 and the key 25, to switch off both the D.H.W. and C.H. mode. The green indicators 30 and 26 will go off.
During the duration of the stand by mode, an automatic anti-sticking system will activate the pump and 3 way valve for 1 minute every 23 hours. The stand by mode will disable the anti-freeze function of the room thermostat (if fitted). To leave the room thermo­stat anti-freeze system operative, leave the Central Heating mode on.
The boiler is equipped with an automatic anti-freeze system which is permanently on.
If the Central Heating temperature falls below 7°C, the pump will start. If the Central Heating temperature falls below 4°C, the pump and the burner will start.
Domestic Hot Water Mode
To be able to supply Hot Water, the D.H.W. mode should be ON. Press the
key
25, the green indicator 26 will
illuminate. If there is no water demand, the display
will show the following graphic During draw off, a square made of 4 dig­its will move clockwise on the display
.
Keys
27 and 28 allow the tem-
perature to be adjusted as required for D.H.W. flow. During the temperature set­ting operation, the display will flash. When a tap or a shower is turned on, a flow of mains water above 2 l/min, will activate the D.H.W. flow switch
20, the 3
way valve 17 will move to the D.H.W. position. The pump can now circulate pri­mary water heated by the main exchang­er through the secondary heat exchanger. The C.H. flow switch checks that the flow rate is over 4 l/min to allow the ignition sequence to begin. The fan on the gas valve assembly starts and when the lighting speed is reached (detected by a hall effect sensor) the 2 safety solenoids open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected, the orange indicator bulb
34
will light and the regulation system will be able to adjust the gas rate according
to the heat load. If a flame is not detect­ed, after 10 seconds, the security sole­noids close together and shut off the gas. The red lockout indicator bulb 35 will light. Press the reset button to re­attempt ignition. The Domestic Hot Water temperature is controlled by the Hot Water control ther­mistor
22 and the Central Heating control
thermistor 21. The system anticipates changes of temperature in the secondary heat exchanger and ensures accurate temperature regulation. When the tap is closed, the burner is extinguished and the pump stops. The boiler will now stay in the Hot Water mode for 3 minutes to maintain temper­ature and to ensure a fast response in the event of a subsequent Hot Water demand. Priority will be given to a demand for Hot Water. This will interrupt the Central Heating for the duration of Hot Water delivery.
Central Heating Mode
To be able to supply Central Heating, the C.H. mode should be switched ON.
Press the key
29, the green indicator
30 will light, and the display will show the
Heating Flow temperature. Keys
31 and 32 allow the tem-
perature to be adjusted as required for the Central Heating system relating to the weather conditions. During the set­ting operation, the display will flash.
When there is a demand for heating, (either from the room thermostat or the clock) the pump starts. If the boiler tem­perature control is calling for heat and the Central Heating flow rate is over 4 l/min, the Central Heating flow switch operates, allowing the ignition sequence to begin. The fan on the gas valve assembly starts and when the lighting speed is reached (detected by a hall effect sensor) the 2 safety solenoids open together to allow gas to the burner. The ignition sequence begins and a con­tinuous high speed spark ignites the gas. As soon as a flame is detected, the orange indicator bulb
34 will light and the
regulation system will be able to adjust the gas rate according to the heat load. If a flame is not detected after 10 seconds, the security solenoids close together and shut off the gas. The red lockout indica­tor bulb
35 will light. Press the reset but-
ton to re-attempt ignition. The Central Heating flow temperature is controlled by the Central Heating control thermistor
21. The boiler has been
designed to minimise cycling and will not attempt to re-light for at least 3 min. after the boiler thermostat has been satisfied. When the room thermostat is satisfied, the burner will switch off and the pump will run for a further 3 minutes before stopping.
Note:
It is possible to override the 3 minute delay by pressing the reset button 36.
5
Lockout Procedure
Flame extinguishes: When the ionisation probe 8 fails to detect flame presence. The orange indi­cator bulb
34 will go off and a lighting
cycle starts. If a flame is not detected, within 10 seconds, the safety solenoids will close. The red lockout indicator
35
illuminates and the display shows the
error code. The pump runs and the 3 way valve
17 stays in its position. After a
few seconds, it will become possible to reset the boiler by pressing the reset but­ton
36.
Overheat Detection :
If a temperature over 100°C is detected in the primary circuit by the sensor 23,
the safety solenoids close and the fan stops. The orange bulb
34 will go off and
the pump will run for a further 3 minutes. It is possible to reset the boiler when the primary circuit temperature falls below 76°C.
CENTORA GREEN FUNCTIONAL DIAGRAM
Heating mode
Hot water mode
40
49
48
43
41
19
39
38
37
22
20
21
23
18
17
16
14
13
12
6
3
8
15
5
7
DIAGRAM
ELECTRICAL WIRING
6
5
Menu - 1 - Default Register
Records the last 10 defaults
Section Digit 1 Digits 2 and 3
Last default occured 0
code from 01 to 99
Last but one default occurred 1
code from 01 to 99
... ... code from 01 to 99
Last default occurred before the previous one 9
code from 01 to 99
Menu - 2 - Boiler Conditions
Indicates the conditions or the configurations of the boiler
Section Digit 1 Digit 2 and 3
Software version of display P.C.B. 0
10 to 99
Nominal Power of the boiler (type 18 or 24 kW) 1
24
Flue type 2
1 : FF
variable speed
Room thermostat is calling for heat 3
0 : no
3
1 : yes
Theoretical position of the 3 way valve 4
0 : D.H.W.
4
1 : C.H.
D.H.W. flow temperature in oC5
from 00 to 99
C.H. flow temperature in oC7
from 00 to 99
Software version of main P.C.B. 9
10 to 99
DISPLAY
ACTION CONFIGURATION
once
x times
x times
Note -- is displayed if no default is recorded.
7
Menu - 3 - Boiler Options
DISPLAY
ACTION CONFIGURATION
Section Digit 1 Digits 2 and 3
Under floor heating system 0 0 : no
1 : yes
Factory
setting
Menu - 4 - Boiler Settings
Section Digit 1 Digits 2 and 3
Room thermostat operation 0 0 : Burner only
0 1 : Burner and pump
Pump speed 1 0 : High speed
1 1 : Low speed
Pump post circulation duration 2 0.0 min
From 0 to 5 minutes by step of 0.5 min. 2 0.5 min
2 1.0 min
2 5.0 min
Maximum Central Heating flow temperature 4 50°C
C.H. anti cycling delay 4 80°C
TAC 8 0.0 min
From 0 to 5 minutes by step of 0.5 min. 8 0.5 min
8 2.5 min
8 5.0 min
C.H. maximum output limitation Power by step of 1 kW value
For a 24 kW model 9 8 to 18
Factory
setting
DISPLAY
ACTION CONFIGURATION
once
x times
once
x times
8
Menu - 5 - Combustion Rate Control Mode
X X
X X
DISPLAY
ACTION CONFIGURATION
wait 5
Combustion rate control mode OFF
Switching on the combustion rate control mode. Central Heating out­put reaches the maximum power set in menu 4 section 9.
Central Heating temperature is dis­played in oC. The 3 dots indicate that the combus­tion rate control is ON at maximum output.
Switching the combustion rate down to minimum power.
Central Heating temperature is dis­played in oC. The dot indicates that the combus­tion rate control is ON at minimum output.
Switching on the combustion rate to maximum output set in menu 4 sec­tion 9.
Central Heating temperature is dis­played in oC. The 3 dots indicate that the combus­tion rate control is ON at maximum output.
X X
Switching off the combustion rate
control mode.
press once
press once
press
press once
press once
Effect Display
Locking conditions of the combustion rate control mode :
- boiler in stand by mode
- D.H.W. draw off
- room thermostat is not calling for heat
- room thermostat is calling for heat but the maximum temperature is reached
- boiler in lockout mode
- after a reset or if the main supply fails
- end of the mode (if operator leaves menu 5)
- after 15 minutes if no keys are pressed.
Note: As soon as the combustion rate control mode is on, the Central Heating and Domestic Hot Water
keys will become inactive.
9
C.H. Power Output Setting :
If you would like to change the setting of the C.H. power output to 12 kW, please proceed as follows : Note: the factory setting is 18 kW and the following explanation refers to menu 4 section 9)
- Switch to installer mode, press both the and keys (D.H.W. side) for 5 seconds. The display shows :
-1- then 0•-- if there is no default in the default register.
- press the menu key (C.H. side ) 3 times to gain access to menu
-4-,
The display shows :
-4- then the value set for section 0 ( 00
or 01 respectively action on burner only or pump and burner)
- change to section 9 (Adjustment of C.H. Power Output). Press the (D.H.W. side) 9 times. The display shows : 918 (which corresponds to the 18 kW which is the factory setting) 9 = section 9 18 = 18 kW
- press the key (C.H. side) once, the 2nd and 3rd digits flash together. Press the key (D.H.W. side) to change to 3.0 on the 2nd and 3rd digits. The display shows : 912 press the setting key to confirm this value. The display stops flashing. Setting procedure is finished. To exit the setting mode, leave the boil­er for approx. 1 minute, the computer will revert to the user mode. After programming is completed please close the door
P (fig. 17)
1
Display
2
x 3
1
2
or
3
3
x 9
4
4
5
10
REGULATION
FLOW SWITCHES
Temperature regulation for both C.H. and D.H.W. circuits are controlled by 2 thermistors. The C.H. knob allows the temperature to be adjusted between 35
o
C and 85°C. The D.H.W. temperature is limited to 60°C. The D.H.W. and
C.H. thermistors are identical and interchangeable.
Resistance value are
- 5000 at 25°C
- 2631 at 40°C
- 620 at 80°C
- 255 at 110°C
Flow in both D.H.W. and Central Heating circuits are detected by 2 flow switches. A piston with a magnet at the top operates a REED switch. The piston is lifted by the flow rates listed below :
Flow rate threshold : D.H.W. 120 l/h ±20 l/h C.H. 250 l/h ±20 l/h
ROUTINE SERVICING
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at reg­ular intervals. The frequency of servicing will depend upon the particular installation, condition and usage. In general, once a year should be adequate.
It is the law that any service work must be carried out by a competent person such as your local Chaffoteaux Service Centre, British Gas or other CORGI registered personnel in accordance with the current Gas Safety (Installation and Use) regulations.
Attention! The air/gas connection pipe between the gas valve and the burner should never be opened. The seal can only be checked in the factory.
The service schedule should include the following operations :
- Check the pressure in the system
- Check the correct operation of the appliance
- Check the correct operation of the gas controls
- Check the functions of the safety controls
- Clean the electronic board of the fan located on the gas valve assembly and the different transformers in the sealed chamber.
- Check combustion chamber insulation panels for damage
- Check the condition of the lighting and ionisation electrodes
- Clean the burner (Never use a metallic brush which can damage the stainless steel)
- Clean the heat exchanger (Never use a metallic brush which can damage the stainless steel)
- Clean the siphon and pay attention to the acidity of its contents
- Check the correct seal of the drain system
- Clean the gas and water filters
- Check the expansion vessel charge pressure
- Clean and check the operation of the safety valve
- Check the correct seal of the flue system.
Additional procedures that may be necessary :
- Check the burner pressure and the gas flow rates
- Check, clean and replace components as necessary
- Carry out combustion test utilising the test points in the flue turret
Suggested sequence for servicing :
Before disconnecting or removing any part, isolate the gas and electricity supplies. Ensure that the appliance is cool, and be careful of the condensate products content in the siphon which are acid.
(For detail, please see section on Parts Removal and Replacement)
Preliminary checks
- Remove the outer case
- Check the system pressure is at least 0.7 bar when cold
- Check the modulation of the gas valve in D.H.W. mode by progressively reducing the flow rate at a tap.
- Check that the burner is extinguished fully when both solenoids are closed and the fan is off.
- Test ionisation functions and check that lockout occurs by turning off the gas tap.
- Whilst the boiler is operating, check the operation of the Central Heating flow switch by closing the Central Heating flow valve and the by-pass screw (turn clockwise) noting the number of turns so that it may be reset correctly.
- Check the correct flood of condensate in the siphon which is transparent.
11
REMOVAL AND REPLACEMENT OF PARTS
Before removing the appliances case, isolate the gas and electrical supplies. Isolate the boiler from the system and drain before removing any component in the waterways. Ensure that the appli­ance is cool.
1. Outer Case
Remove the four screws in the base of the boiler and lift free. When replacing,
carefully place the casing on lugs T located on the top edge of chassis.
2. Sealed Chamber Front Panel
Unscrew the four self tapping screws securing the sealed chamber front panel and lift off of the corner locating lugs. Reassemble in reverse order.
3. Combustion Chamber Front Panel and Air/Gas Connection
Carry out steps 1 and 2 as above. Unscrew the three screws securing the air/gas connection pipe onto the gas valve assembly. Disconnect both the ionisation and lighting electrodes from their wiring. Unscrew the six nuts to release the combustion chamber front panel and pull the assembly towards you. Reassemble in reverse order.
4. Ionisation Probe
Carry out steps 1 and 2 as above. Disconnect the ionisation probe from its wiring. Loosen the 2 screws and pull it out from the combustion chamber front panel. Replace the gasket provided. Reassemble in reverse order.
5. Ignition Electrode
Carry out steps 1 and 2 as above. Disconnect the ignition electrode from its wiring. Loosen the 2 screws and pull it out from the combustion chamber front panel. Replace the gasket provided. Reassemble in reverse order.
6. Burner
Carry out steps 1, 2 and 3 as above. Remove the four Philips screws retain­ing the burner. Pull it out with care to avoid any damage to the ceramic panel protecting the combustion chamber front panel. Replace the burner gasket. Reassemble in reverse order.
7. Gas Vale Assembly
Carry out steps 1 and 2 as above. Unscrew the three screws securing the air/gas connection pipe onto the gas valve assembly. Disconnect the connec­tors from the gas solenoids and fan. Loosen the gas pipe nut. Unscrew the six nuts to release the combustion chamber front panel and pull the assem­bly towards you. Replace the gas filter before fitting the full assembly back into the boiler.
8. Fan Assembly
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. Reassemble in reverse order and replace the necessary gaskets.
9. Gas Section
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. The venturi and the gas section can be separated by loosening the two screws located at the top of the gas valve. Replace all neces­sary gaskets before reassembling in reverse order.
10. Venturi in the Gas Section
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. The venturi and the gas section can be separated by loosening the two screws located at the top of the gas valve. Replace all neces­sary gaskets before reassembling in reverse order.
11. Drain Down
2 drain points are located on the boiler.
1 = D.H.W. circuit drain point 2 = Central Heating circuit drain point
12. Water Filters (D.H.W. and C.H.) The D.H.W. filter ensures a seal between the connecting bracket and the pipe to the D.H.W. flow switch. Drain the boiler as in step 12. Unscrew the pipe nut and remove the clip on the hydraulic assy. Pull the pipe toward you and remove the water filter from its location. The C.H. filter is located in the right hydraulic assembly. Remove the return pipe as described previously and remove the filter. Reassemble in reverse order.
13. Flow Switches
Drain boiler as in step 12. Disconnect the electrical plug, turn the top cover anti-clockwise, remove the O-ring and the brass piston. Reassemble in reverse order.
14. 3-Way Valve
Drain boiler as in step 12. Remove the three clips on the 3-way valve. Remove the clip on the exchanger flow pipe. Pull the pipe down then pull it out of the 3­way valve. Disconnect the plug from the motor. Unscrew the nut on the pipe between the connecting bracket and the 3-way valve and pull it toward you. Rotate the 3-way valve body anti-clock­wise to unclip it from the left hydraulic assembly.
15. Secondary Heat Exchanger
Drain both circuits of the boiler as in step
12. Unscrew the 2 fixing screws D and remove the D.H.W. exchanger from the front. Prior to reassembly, check that the 4 gaskets are correctly positioned. The heat exchanger is designed so that it cannot be remounted incorrectly.
A
A
A
A
T
T
1
2
1
2
Air Separator
D
12
16. Main Heat Exchanger
Carry out steps 1 and 2 as above. Drain down the boiler as in step 12. Unscrew three screws securing the air/gas con­nection pipe onto the gas valve assem­bly. Disconnect the ionisation and ignition electrodes from their wiring. Unscrew the six nuts to release the com­bustion chamber front panel and pull the assembly towards you. Remove the two clips for the pipes to the main exchanger and pull down the pipes. Unscrew the three screws located at the bottom, top left and at the right with the retaining system to be able to pull the main heat exchanger towards you. Reassemble in reverse order taking care about the location of the gasket on the fumes collector and replace the neces­sary gaskets.
17. Pump
Drain the boiler as in step 12. Pivot the electical box downwards. Open the elec­trical box cover removing the 2 screws. Remove the pump plug from the power board and earth plug from earth socket. Unscrew nut
F on the return pipe from
the volute. Remove the clip G on the pump volute and pull the pump toward you. Reassemble in reverse order.
18. Pressure Relief Valve
The pressure relief valve can be ser­viced from the front of the appliance. Drain the boiler first, undo the retaining screw and pull out the valve. Reassemble in reverse order.
19. Thermistors
Drain the boiler as step 12. Disconnect the plug, remove the retaining clip pull the thermistor out. Reassemble in reverse order.
22 = D.H.W. thermistor 21 = Central Heating thermistor
20. Safety Thermostat
Remove the casing as step 1 and pivot the electrical box downwards. Disconnect the 2 cables, pull out the sensor with the clip
23. Reassemble in
reverse order.
21. Spark Generator
Carry out steps 1 and 2 as above. Unplug the connector from the spark generator located on the right hand side of the main heat exchanger. Loosen the two screws to remove the igniter. Reassemble in reverse order.
22. Main Control Board
Carry out step 1 as above and pivot the electrical box downwards by pressing the retaining tabs
P on either side.
Remove the wiring cover
C. Undo the
four screws of the electrical rear panel and remove it. Unplug all cables from the P.C.B., remove the earth plug from earth socket. Remove the Main P.C.B. Reassemble in reverse order.
23. Display P.C.B.
Carry out step 1 as above and pivot the electrical box downwards by pressing the retaining tabs
P on either side.
Remove the pressure gauge clip. Rotate the electrical box back to the upper posi­tion. Undo the 2 screws retaining the front panel, put your two hands at the bottom of the front panel and pull it down to release it from the 2 clips. Pivot the electrical box downwards. Undo the four screws of the electrical rear panel and remove it. Unplug the display board cables from the Main P.C.B. Reassemble in reverse order.
24. Expansion Vessel
Remove the casing as step 1 and drain the boiler as step 12 above. Unscrew the connecting tails nuts and lift out the boil­er from the wall. Place it on its side on the floor. Remove the expansion vessel bracket retaining screws, disconnect the pipe from the vessel and pull it toward you. Reassemble in reverse order.
25. Pressure Gauge
Carry out step 1 as above and drain the boiler as step 12. Pivot the electrical box downwards by pressing the retaining tabs
P on either sides. Press the clip to
remove it and pull it out. Remove the clip which holds the connection of the capil­lary on the pump hose. Pull out the pres­sure gauge with its capillary. Reassemble in reverse order.
F
G
21
22
23
P
P
C
13
FAULT FINDING CHART Part 1
Switch on the main electrical supply
Does the green
L.E.D. light ?
- Check mains electrical
connection
- Check internal fuses
- Check connection between
the 2 P.C.B.s
Replace control P.C.B. or
display P.C.B.
Replace control P.C.B.
Replace D.H.W. flow switch
Switch Domestic Hot Water
mode ON
Release pump rotor
Replace pump
Replace fan assembly
Replace the Central Heating
flow switch
Does the red L.E.D.
light ?
Does the display
show a - XX code ?
Does the fan run ?
Check Central Heating
flow switch
Check voltage on
the fan
Check the 24 V at
the transformer
Press the reset button
Please refer to the list of error
codes and solve the problem
Does the pump run ?
Check that the
pump spins freely
Check voltage in the
pump electrical box
Replace control P.C.B.
Could you see the
spark generation?
Does the spark
generator energize ?
Does the -24 error
display ?
Replace spark generator or
ignition electrods assembly
Replace transformer or the rel-
evant fuse
- Check pressure probes
or
- Check flue duct condition
or
- Replace pressure switch
Yes
Yes
Yes
Yes
No
No
No
No
Ok
Ok
No
Check or replace main or sec-
ondary heat exchangers. They
could be fully scaled.
Check flow in the
boiler primary circuit
Ok
No
Replace heating thermistor
Check heating
thermistor
Ok
No
No
No
No
Yes
Yes
Yes
No
No
No
Ok
Ok
Ok
Ok
means a test or a choice
means an action
means a group of actions
error code displayed
PLEASE CHECK THE FOLLOWING POINTS CAREFULLY
BEFORE GOING THROUGH THE FAULT FINDING CHART
-Gas pressure
-Electric mains
-Minimum water pressure in the heating circuit (over 0.8 bar)
-All isolating valves have been opened
-Boiler air vented
-Minimum domestic hot water flow of 2 l/min
-Check that the heating filter is clear.
- Remove the front panel of the sealed chamber
-7
Yes
Check or replace the D.H.W.
flow switch
Draw off Domestic Hot Water
at a tap
Does the pump run ?
No
Check D.H.W. flow
switch operation
No
No
Ok
-7
-7
-11
-12
Ok
Ok
No
No
-3
Wait for 4 seconds
-3
Error code Description
1 Overheat Lock Out
3 No flame detection
5 Anti-frost mode on
6 Anti-frost mode on
7 No water circulation
8 Faulty water circulation in the primary circuit
9 DHW thermistor faulty, Open circuit
10 DHW thermistor faulty, Short circuit
11 Central heating thermistor faulty, Open circuit
12 Central heating thermistor faulty, Short circuit
18 Ignition test
20 Faulty connection
23 Low speed fan
24 Faulty control functionning fan
29 3 ways valve locked in Heating position
31 Error communication with EEPROM
32 Error communication with the Main P.C.B.
14
FAULT FINDING CHART Part 2
Replace control P.C.B.
Can you see the
flame on the burner ?
Replace gas section assembly
Do you feel air
drawing in at the air inlet ?
Do the gas
solenoïds energise ?
Check that air inlet pipe, ven-
turi, fan, air/gas pipe and burn-
er are free of dust and not
blocked
Purge the gas pipe and press
on reset button
Does the D.H.W.
temperature rise?
Does the burner still
light ?
Does the red L.E.D.
light and -3 displayed ?
Does the orange
L.E.D. light ?
Replace control P.C.B.
Replace D.H.W. thermistor
Replace control P.C.B.
Replace display P.C.B. or check
the connection between the 2 P.C.B.s
- Adjust the D.H.W. flow rate to
3 l/min at a tap.
- Wait until the temperature
becomes stable.
No
No
No
No
No
Yes
No
No
Does the orange
L.E.D. light ?
No
Yes
Replace the D.H.W. heat
exchanger
Yes
Yes
Yes
Yes
No
-3
Replace display P.C.B. or check the
connection between the 2 P.C.B.s
Is the combution
chamber full of conden-
sates ?
Yes
Check ionisation
probe
No
Ok
Drain and clean combustion cham-
ber, siphon and drain pipes
Yes
Replace the ionisation probe
No
Stop water draw off
Does D.H.W. tem-
perature rise above 70°C ?
Check D.H.W. ther-
mistor
No
Ok
- Press the D.H.W. key to switch
off D.H.W. mode.
- Press the C.H. key to switch on
C.H. mode and set CH tempera-
ture to maximum.
- Press the RESET button to
cancel the 3 min. delay.
- Ensure that external controls
are calling for heat.
Does the heating
outlet pipe temperature rise
?
Wait until the return pipe
become hot then reduce the
C.H. temperature to minimum
Does the orange
L.E.D. light ?
Replace the 3 way valve
Replace control P.C.B.
No
Yes
The boiler is O.K.
No
Does the heating
outlet pipe temperature
rise ?
Replace the 3 way valve
Yes
-29
No
Yes
Yes
Yes
15
SHORT LIST
102 ELECTRODE KIT 1309624 . 401 GAS VALVE 1308957 . 407 FAN ASSY 1307585 . 505 3-WAY VALVE 1010000 . 507 OVERHEAT THERMOSTAT 100°C 1010572 . 510 THERMISTOR 1000733 . 514 WATER/WATER HEAT EXCHANGER 1011164 . 532 WATER THROTTLE 81471 . 560 AIR SEPARATOR HEAD ASSEMBLY 1002653 . 572 PUMP UP 15/50 230V 1010612 . 606 TRANSFORMER 1308149 . 607 IGNITER 1002105.20 . 615 PRINTED CIRCUIT BOARD 1307645 . 616 PRINTED CIRCUIT BOARD 1307647 . 627 FUSE 250V 2A - TEMPORIZED 1003456 . 628 FUSE 250V 1A - TEMPORIZED 1003634 . 629 FUSE 250V 1.25A - TEMPORIZED 1003635 . 630 FUSE 250V 0.315A - TEMPORIZED 1307845 . 805 PRESSURE GAUGE 1303158 . 938 PRESSURE RELIEF VALVE 1020933 .
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
FF
Manf. date
CENTORA GREEN
from to
102
407
401
532
572
505
606
514
510
507
R41
R
37
R
3
1
R
30
R29
J
7
C38
R
1
0
2
1
+
+
+
++
+
+
+
8
C
6
8
R28
S
T
2
F
T
1
A
C19
Z
1
1
A
Z10A
Z
9
A
Z8A
R
1
3
5
D
L1
T
H
1
A
Z7A
Z
6
A
R
1
3
2
U
5
Z
5
A
Z
4
A
T
E
R
R
E
-1
T
H
1
R48
R27
R91
R89
R47
C
8
3
C
7
8
C
8
0
C7
9
ST
1
R
8
7
Z10
Z
9
Z
6
Z7
Z
5
Z
4
Z3
Z
2
Z
1
1
Z
1
U
3
U
1
0
U
9
U
7
U
6
U
4
T
R
1
T
H
2
T
E
R
R
E
T
8
T
7
T
5
T
4
T
3
R46
T
2
T
6A
T
6
T
1
2
T
1
1
T
10
T
1
S
W
1
R
L8
R
L
7
A
R
L
7
R
L6
R
L
1
0
R
L
5A
R
L5
R
L
4
A
RL
4
RL3A
R
L
3
R
L
2
A
R
L
1A
R
L
9
R
L
1
R
A
D
1
R
11
8
R1
1
4
R
1
1
3
R
11
1
R
11
2
R110
R109
R1
0
8
R
10
7
R
1
0
6
R9
R
1
0
5
R
1
0
1
R
100
R99 R
98
R
9
7 R
96
R
8
R
9
5
R
9
4
R
9
3
R
92
R
9
0
R
88
R66
R65
R64
R
6
2
R7
R
5
8
R
5
9
R
5
7
R24
R
5
2
R
5
3
R
51
R6
R50
R49
R
5
5
R
5
R22
R79
R
7
8
R
7
7
R45
R43
R44
R42
R
4
R
3
9
R38
R
35
R3
4
R
3
R3
3
R3
2
R
1
9
R18
R
2
R16
R20
R21
R
1
5
R
14
R26
R
2
5
R23
R
1
3
R1
3
1
R130
C
82
C81
T
1
4
T
1
3
D45
D
44
R
L
12
R
7
6
R1
2
R
7
5
R74
R73
R72
R
7
1
R
70
R6
9
R68
R
6
7
R
129
R1
1
R128
R
12
7
R1
1
6
R
1
1
5
R1
22 R1
21
R120
R
1
1
9
R117
R
1
0
R
1
Q
1
P
2
P
1
M
O
V
1
L1
J
9
J
1
0
A
J
8
J
6
J
4
J
3
J
2
J
1
F
T
1
F
3
A
F
3
F
2
A
F
2
F
1A
D
9 D
7
D
6
D
5
D
3
4
D
31
D30
D
32
D
4
D
42
D
41
D
4
0
D
3
9
D38
D37
D36A
D
3
6
D3
3
D
4
3
D
3
D
2
9
D28
D27
D
2
6
D
2
3
D25
D24
D
2
2
D21
D
2
0
D
2
D
1
9
D18
D
1
7
D1
6
D
15
D14
D
1
3
D
1
2
D
1
1
D
1
C
T
P1
C
8
C
13
C
4
9
R
5
4
R
L
1
1
C34
C3
5
C32
C
7
J
5
C 5
3
C
6
C
5
2
C
5
1
C7
7
C
7
6
C
7
5
C
7
4
C
72
C
7
1
C
7
0 C
69
C
5
C
5
0
C
4
8
C
47
C
46
C
4
5
C44
C
4
3
C
4
2
C67
C
4
C6
6
C65
C
64
C
63
C
62
C
61
C
60
C
5
9
C
2
2
C
5
6
C
5
5
C
5
4
C3
3
C
3
1
C
4
1
C
3
9
C37
C
2
C3
6
C
2
9
C30
C
2
8
C
2
7
C
2
6
C2
5
C
1
0
C
1
1
C
9
C
3
C
24
C
2
3
C21
C
2
0
C
18
C
17
C16
C15
C
1
4
C
12
C
1
K
V
D
M
/A
V
ITES
SE
K
1
1
1
1
1
EX
T
1
P4 P3
P2
P1
B
U
S
1
PR
OG
TA
K
K
KC
D
1
K
K
230
V
+
5
V
T
R
C
O
M
R
E
P
8
1
2
3
4
0
N
616
628
627
629 630
607
805
938
560
615
1309456 - 03/2002
Chaffoteaux & Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
Manufacturer: Chaffoteaux & Maury - France
Commercial subsidiary: MTS (GB) Limited
MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax: (01494) 459775 internet: www.chaffoteaux.co.uk E-mail: info@mtsgb.ltd.uk
Technical Support Help Line: (01952) 222288
CENTORA GREEN
DOMESTIC BOILERS
CENTORA GREEN SYSTEM 24 CENTORA GREEN 24 CENTORA GREEN SYSTEM 30 CENTORA GREEN 30
B
CENTORA GREEN
1
Réf. 82025.98d - 07/03 - GB
124
2
B
CENTORA GREEN
82071.85
200 FAN 300 SEALED CASE
100 BURNER
213
117
112
114
314
311
305 228
304
313
212
222
109 115
108
102
110
104
227
107
231
315
229
118
121
123 116
122 119
119
205
303
101
304
309
639
308
230
203
202
313
B
CENTORA GREEN
3
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
100 BURNER ASSEMBLY
101 BURNER 1306074
..
BURNER 61309327
..
102 DOOR ASSY 24KW 1308492
..
DOOR ASSY 30KW 61308491
..
104 GASKET D:110-75-2 1309658
....
107 FIXING BRACKET 1306181
..
FIXING BRACKET 61309237
..
108 FIXING BRACKET 1306180
..
FIXING BRACKET 61309238
..
109 HOOKING BRACKET 1306448
....
110 ELECTRODES 1309624
....
112 WASHER D:65-59-2.6 1307588
....
114 TRAP 1306078
....
115 TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
....
116 SILICONE TUBE D: 21x2.5 L: 1M 277636 81265.02
....
117 DUCT FIRST SECTION
1306026
....
118 CLIP 1306070
....
119 SCREW HX M 5-12 277797 1010131
....
121 "O" RING D: 17.76-1.78 1308092
....
122 SCREW D: 5-14 61308782
....
123 BARBED NIPLE 90° 1309373
....
124 TUBE PVC D:19 L:500 61311628
....
200 FAN ASSEMBLY
202 FLUE ADAPTOR 1306168
..
... 10/02
FLUE ADAPTOR 61309242
....
11/02 ...
203
GASKET D:66-60-7.5
61309786
..
... 10/02
GASKET D:66-58.4-9 61310088
....
11/02 ...
205
GASKET D:66.6
1306029
....
212 GASKET 1300262
....
213 PLUG KIT
1306698
....
222 OUTGOING FLUE BOX 1306028
....
227 TAPPING SCREW CBLSX D:4.2-12.5
1010847
....
228 TAPPING SCREW CBLSX D: 6.3-13 277865 1010648
....
229 TAPPING SCREW CBLSX D: 4.2-9.5
277792 1010125
....
230 GASKET (/ Flue bend turret) 1300258
....
231 GASKET D:129.4 1306030
....
300 SEALED CASE
303 TOP PANEL BOX 1305438
....
304 FOAM SEAL 12.5x5 L: 2.5M 264425 81273
....
305 CASE 1310355
....
308 SPIRE CLIP 366787 57488
....
309 BASE - BOX 1307613
....
311
CASE COVER E23478 81851
..
CASE COVER 61400102
..
313 TAPPING SCREW CBLSX D:4.2-12.5 1010847
....
314
GROMMET 277819 1010109
....
315
GROMMET 366877 39017
....
4
B
CENTORA GREEN
82071.86
400 GAS SECTION
407
402
411
401
404
437
436
412
406
418
408
442 403
610
410
404
B
CENTORA GREEN
5
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
400 GAS SECTION
401 GAS SECTION ASSY 61312986
B/P
..
GAS SECTION ASSY 61312987 B/P
..
GAS SECTION ASSY 61307584 NAT
..
GAS SECTION ASSY 61310129 NAT
..
402 VENTURI D:20 1307649
..
... 11/02
VENTURI D:22 61310128
..
... 11/02
403
SCREW CLXS M 4-30 61310333
....
404 SCREW HX M 5-12 277797 1010131
....
406 GASKET 1308335
....
407 FAN ASSY 1307585
....
408 SCREW CLSX M 5-12 1308327
....
410 GASKET 1306072
....
411 GASKET 1307587
....
412 SILENCER 61310121
....
418 CONNECTION 1012649
....
436 "O" RING D: 22-2.6
E23502 21061.40
....
437 RESTRICTOR D: 4.4 61310495 B/P
..
RESTRICTOR D: 4.8 61310370 B/P
..
RESTRICTOR D: 5.55 1308519 NAT
..
... 11/02
442
SCREW CBLSX M 4-12 1015222
....
6
B
CENTORA GREEN
82071.87
500 HYDRAULIC BLOCK
542
531
502
510
515
514
539 540
550
504
504
532
550
564
509
561
567
575
570
571
572
574
502
502
520
537
535
511
538
565
521
521
558
504
528
526
522
502
504
522
518
573
543
553
530
560
559
6006
548
530
530
6002
101
101
504
509 510
511
529
502
503
530
526 504
569
575
6003
505
516
516
551
548
418
6007
501
611
611
638
611
611
514
SYSTEM
581 507
B
CENTORA GREEN
7
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
500 HYDRAULIC BLOCK
501 TUBE-EXCHAN TO THREE-WAY VALVE 1307591
....
502 CLIP 277830 1010012
....
503 "O" RING D: 18.4-2.7 277831 24164.22
....
504 "O" RING D: 17-4 E00604 24164.51
....
505 VALVE BLOCK ASSY 1010436
..
THREE-WAY VALVE 277833 1010000
..
507 OVERHEAT THERMOSTAT 100°C 277783 1010572
....
509 DRAIN SCREW ASSY 266043 81028
....
510 THERMISTOR TEMP. SENSOR 277834 1000733
....
511 TEMPERATURE SENSOR CLIP 277835 1002083
....
514 JOINING PLATE 1010439
..
WATER/WATER HEAT EXCHANGER E00612 1011164
..
515 SCREW CBLSX M 5-40 277837 1010129
....
516 CLIP 1307589
....
518 LEFT HAND HYDRAULIC BLOCK 277839 1010003
....
520 BYPASS TUBE
277840 1010044
....
521 TAPPING SCREW CBLSX D: 6.3-19 277785 1010127
....
522 CLIP 277841 1010005
....
526 "O" RING D: 8.9-2.7 E00605 1009834.14
....
528 HOT WATER BEND 277842 1010056
..
529 HEATING FLOW BEND 277843 1010057
....
530 SHEET GASKET D: 24-17-1.5 265389 61855.19
....
531 HYDRAULIC PLATE 277845 1010042
....
532 WATER THROTTLE 277846 81471
....
535 BYPASS BODY 1016387
....
537 "O" RING D: 13.6-2.7 366048 24164.18
....
538 CLIP
277830 1010112
....
539 "O" RING D: 1.9-8 277849 1009833.34
....
540 ADJUSTING SCREW OF BY-PASS
277850 1010111
....
542 CLIP 277851 79845
....
543 TAPPING SCREW CBLSX D: 4.2-9.5
277792 1010125
....
548 SHEET GASKET D: 24-18.2-1.5 265091 22835.01
....
550 BEND RETURN
277852 1010055
....
551 GAS TUBE 1307590
..
GAS TUBE 61309556
..
553 WATER FILTER 277854 1007727
....
558 PUMP LEAD (2 SPEEDS) 277855 1004115
....
559 "O" RING D: 45-3.5 E00613 1009833.46
....
560 AIR SEPARATOR HEAD ASSEMBLY 277857 1002653
....
561 RIGHT HAND HYDRAULIC BLOCK 277858 1010167
....
564 "O" RING D: 24.6-3.6 1009834.30
....
565 HEATING FILTER 1305560
....
567 CLIP 366887 30898.03
....
569 LIP SEAL 277860 1002249
....
570
HEATING RETURN TUBE 1307592
....
571 "O" RING D: 16-1.9 E00615 1009833.37
....
572 PUMP UP 15/50 230V E11662 1010612
....
573
CAPACITOR E00616 1000652.10
....
574
PLUG M 10-100 277508 15709
....
575 "O" RING D: 17.86-2.62 1308091
....
581 CLIP 277782 1010050
....
8
B
CENTORA GREEN
82071.88
600 ELECTRICAL BOX
609 602
614
612
602
604
632
602
610
610
639
631
607
640
605
617
615
621
622 623
613
605
110
609 602
SYSTEM
627
625
613
606
626
601
618
641
C68
R67
F
T
1
A
C
1
9
Z
1
1
A
Z
1
0
A
Z
9
A
R
9
9
C
3
7
D
L
1
T
H
1
A
R
9
8
C36
R
1
3
2
R85
S
W
2
S
W
1
U
5
R
1
6
R
15
R
14
C
8
4
C
8
3
R6a
Z
4A
TH1
R78
R
6
6
R76
R100
R
1
3
4
R
8
8
Z
1
0
Z
9
Z
6
R
7
a
Z
5
Z4
Z
3
Z
1
1
Z
1
U
1
0
U
9
U
8
U
7
U
6
U
2
U
4
T
8
T7
T
5
T
4
T
3
T
2
T
6
R
5
1
R
L8
R
L10
R
L
5
A
R
L
5
R
L
4
A
R
L
4
R
L
3
A
R
L
3
R
10
8
R
12
4
R
1
23
R
12
2
R
1
21
R119
R118
R
11
6
R
11
7
R
113
R
9
R
10
6
R
10
7
R
9
7
R96
R95 R94
R
9
3
R
9
2
R
8
R91
R90
R89
R79
R77
R
75
R54
R
5
3
R
5
2
R
5
0
R
7
R
4
9
R
4
8
R
4
6
R
4
7
R
4
5
R
65
R40
R
4
1
R
3
9
R6
R38
R
37
R
4
3
R87
R86
R84
R83
R82
R
5
R81
R80
R
7
0
R
7
2
R30
R
4
R
2
7
R26
R
24
R
2
3
R22
R
3
R
21
R
20
R
1
4
0
R
1
3
7
T
H
4
R
2
R
1
3
R
1
2
R
7
1
R11
R
1
1
5
R
1
2
7
C
8
2
C81
T
14
T
1
3
R
136
U
1
1
R
64
R
10
R
63
R
6
1
R62
R
6
0
R
5
9
R
1
2
6
R
12
5
R120
R114
R
1
1
0
R
1
1
1
R109
R
1
Q
1
M
O
V
1
L
1
J
9
J6
J
4
J
3
J
2
F
T
1
F
3
F
2
F
1
D
9
D
8
D
7
D5
D
3
4
D
3
1
D
3
0
D
3
2
D
4
D
39
D
3
8
D
3
7
D36A
D
3
6
D33
D
3
D
2
9
D
2
8
D
2
7
D
2
6
D
2
3
D
2
5
D
2
4
D
2
2
D
2
1
D
2
0
D
2
D
1
9
D18
D
1
3
D
1
2
D
1
1
D
1
0
D
1
C
T
P
1
+
C
8
C
49
R42
J
1
1
C
3
4
+
C
7
J5
C
53
C
6
C52
C
5
1
C
76
C
75
C
7
4
C
72
C71
C70 C69
C
5
C
4
8
C
4
7
C
4
6
+
C
4
5
C44
+
C
4
3
+
C
4
2
C67
C
4
C66
C65
C64
C63
C62
C61
C58
C57
C
2
2
C
56
C
54
C
3
3
C
3
1
C
3
9
C
4
0
C
2
C
27
C
26
C
2
5
C
10
C
1
1
C
9
C
3
C
2
4
C
2
3
C
2
1
C
2
0
C
18
C
1
7
C
1
6
C
1
5
C
1
4
C
1
2
U
1
2
M/A
VITESSE
1
1
1
1
BUS
1
1
.2
3
1
1
1
2
2
1
SW
2
S
W
1
3
.2
3
O
FF
O
N
11
1
2
2
2
.2
3
O
FF
O
N
11
12
TY
P
E D
E
C
H
A
U
D
IER
E
POSITION SW1,SW2
1
SW
2
2
1
S
W
2
S
W
1
1
T1,25A
1
S
W
1
T315mA
230V
MOTEUR
610
610
558
558
610
638
628
627
629
630
611
634
B
CENTORA GREEN
9
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
600 ELECTRICAL BOX
601 ELECTRICAL BOX 1311320
..
ELECTRICAL BOX 1311319
..
602 SCREW FX90 L:16 1020510
....
604 INSTRUCTIONS SUPPORT 1309315
....
605 TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
....
606 CONNECTOR 1011046
..
607 IGNITER 379075 1002105.20
....
609 CONNECTOR COVER 277874 1010014
....
610 FAN-IGNITER CABLE 1309837
....
611 WIRE ASSEMBLY 61310189
..
WIRE ASSEMBLY 1308085
..
612 CONNECTION STRIP 277877 1010152
....
613 TAPPING SCREW CBLSX L:10 1020509
....
614 ELECTRICAL BOX COVER 277879 1010007
....
615 PRINTED CIRCUIT BOARDS 1310357
....
617 ELECTRIC BOX PLATE
277882 1010006
....
618 PLUG E00269 1011316
....
621 TRANSMITTER OF LEDS 1306012
....
622 CONTROL PANEL 61310292
..
CONTROL PANEL 1306019
..
623 SIGHT GLASS 1303830
....
625 PRINTED CIRCUIT BOARD T.A. 1011846
..
626 PRINTED CIRCUIT BOARD LEAD 61310366
..
627 FUSE 250V 2A - TEMPORIZED 277883 1003456
....
628 FUSE 250V 1A - TEMPORIZED 1003634
....
629 FUSE 250V 1.25A - TEMPORIZED 277884 1003635
....
630 FUSE 250V 0.315A - TEMPORIZED
1307845
....
631 EARTH WIRE 1309966
....
632 CLOSURE PLATE
1304599
....
634 CONNECTING TERMINAL 1308032
....
638 CABLE THREE WAY VALVE
1305893
..
639 ELECTRODE CABLE 1308086
....
640 TRANSFORMER
1308149
....
641 SPACER 61308945
..
10
B
CENTORA GREEN
82071.89
700 CHASSIS 800 FRONT CASE
714
713
712
709
706
703
704
706
701
705
801
711 805
710
806
813
802
815
807
B
CENTORA GREEN
11
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
700 CHASSIS
701 TOP STAY PLATE 277864 1010029
....
703 EXPANSION VESSEL 366979 56676.06
....
704 CHASSIS 277866 1010028
..
CHASSIS 61310119
..
705 EXPANSION VESSEL AIR HOSE 277867 1010170
....
706 TAPPING SCREW CBLSX D: 6.3-19 1014516
....
709 FLEXIBLE PIPE KIT E23589 81824
....
710 CLIP 277848 1002406
....
711 "O" RING D: 5.7-1.9 E00621 1009834.10
....
712 SHEET GASKET D: 12-8.1-2 1308868
....
713 CLIP 277841 1010005
....
714 "O" RING D: 8.9-2.7 E00605 1009834.14
....
800 FRONT CASE
801 TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
....
802 CASE
E00622 1010016
..
CASE 61309874
..
805 PRESSURE GAUGE 1303158
....
806 DOOR 1306020
....
807 SERIGRA. STRIP (WITHOUT PROG.) 1307650
....
813 SPACER 1015797
....
815 SCREW FX90 L:16 1020510
....
12
B
CENTORA GREEN
82071.90
900 JIG PLATE & PIPE FITTING
907
908 909
901
902 904 906903 905
927
931
939 940
941
937
910
943
939
921
922 925
919
918917
920
918
939
920
917
918
936
923
947
938
SYSTEM 24 - 30
24 - 30
901
902 904 906
B
CENTORA GREEN
13
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
900 JIG PLATE & PIPE FITTING
901 PREFABRICATION 1312381
..
PREFABRICATION E00627 1012448
..
902 WATER FLOW SERVICE TAP 1020388
....
903 HOT WATER CONNECTION 1020916
..
904 GAS SERVICE TAP 1020389
....
905 COLD WATER TAP 1302612
..
906 WATER RETURN SERVICE TAP 1312122
....
907 HOOKING BRACKET E23593 1012457
....
908 WASHER D: 14.2-7.2-1.2 366764 5369.03
....
909 WOOD SCREW 366017 25617.03
....
910 BOTTOM STAY PLATE E00630 1011683
....
917 SHEET GASKET D: 24-17-1.5 265389 61855.19
....
918 LOCK NUT 277909 31140
....
919 FLOW REGUL. 7L/MIN(DARK GREEN) 277911 1002775.07
..
FLOW REGULATORE 8L/MIN (WHITE) E23605 1002775.08
..
FLOW REGULATOR 10L/MIN (BLUE) E00631 1002775.10
..
FLOW REGULATORE 12L/MIN (RED) E23606 1002775.12
..
FLOW REGULATOR 14L/MIN (PINK) 277911 1002775.14
..
FLOW REGUL 15L/MIN(PALE GREEN) E23607 1002775.15
..
920 LOCK NUT H 1/2" 277910 31139
..
921 SHEET GASKET D: 24-18.2-1.5 265091 22835.01
....
922 HAND LEVER BLACK 1302611
....
923 HAND LEVER YELLOW 1302610
....
925 DRAIN SCREW ASSY 266043 81028
..
927 PRESSURE TEST POINT SCREW 1016378
....
931 GRUB SCREW 1304327
....
936 "O" RING D: 13.6-2.7
E00633 1009834.18
....
937 TUBE PVC D: 13x17 L: 1M 277912 81266.02
....
938 PRESSURE RELIEF VALVE
1020933
....
939 WASHER D: 18.4-12.2-1.5 265432 61855.14
....
940 NUT 1/2" THICK: 10
262584 20747.38
....
941 CONNECTING PIPE 277913 1010375
....
943 ACCESSORY KIT
1309329
....
947 CLIP E23616 1012927
....
14
B
CENTORA GREEN
82071.91
1000 FLUE CONNECTION
D80-125VERTICAL FLUE KIT
from ... to 10/02
1005
1001 1002
D80-80
V./HORIZONTAL FLUE KIT
DOUBLE-FLOW FLUE KIT
D60-100
D60-100
HORIZONTAL FLUE KIT
1003
1011
1018
1012
1022
1014
1013
1017
1016
1015
1011
1022
1011
1022
1015
1020
1011
1022
1022
1019
D80-125VERTICAL FLUE KIT
from 11/02 to ...
1005
1001 1002
D80-80
V./HORIZONTAL FLUE KIT
DOUBLE-FLOW FLUE KIT
D60-100
D60-100
HORIZONTAL FLUE KIT
1003
1011
1012
1014
1013
1017
1016
1015
1011
1011
1015
1020
1011
1022 1019
B
CENTORA GREEN
15
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
1000 FLUE CONNECTION
1001 HORZ. FLUE KIT D60-100 L:800 1309941
..
... 10/02
HORZ. FLUE KIT D60-100 L:800 1309947
....
11/02 ...
1002 V./HORIZONTAL FLUE KIT D60-100 1309948
..
... 10/02
V./HORIZONTAL FLUE KIT D60-100 1309694
....
11/02 ...
1003
VERTICAL FLUE KIT D80-125 1309162
..
... 10/02
VERTICAL FLUE KIT D80-125 1309693
....
11/02 ...
1005
DOUBLE-FLOW FLUE KIT D80-80 1309175
..
... 10/02
DOUBLE-FLOW FLUE KIT D80-80 1309715
....
11/02 ...
1011
GASKET (/ Flue bend turret) 1300258
....
1012 FLUE BEND 90° 1307942
..
... 10/02
FLUE BEND 90° 1309692
....
11/02 ...
1013
GASKET D:106-100-5 61310157
....
1014 GASKET D:60 61310150
....
1015 GASKET D:88-80-12 61310152
....
1016 SEALING RING TRIM 366995 62079
....
1017 HORZ. TERMINAL D:60/100 L:800
61310156
....
1018 SCREW CLX M 5-20 1017600
....
1019 GASKET D:106.5-100-12 61310151
....
1020 GASKET D:133.5-125-12.5 61310153
....
1022 GASKET D:66-60-7.5 61309786
....
16
82071.92
B
CENTORA GREEN
5000 ACCESSORIES
5040
6000 MAINTENANCE
5015
5014
Connection
FIRST FITTING
Connection
REPLACEMENT
5020
5022
5021
5023
5030 5033 5035
ACOUSTIC
KIT
5045
6002 6003
Simulating
Descaling
6006
Spanner
6007
5001
G20 > G25
5002
G20 > G31
B
CENTORA GREEN
17
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Centora green system 24
Centora green 24
Centora green system 30
Centora green 30
Manf. date
from to
5000 ACCESSORIES
5001 CONVERSION KIT > G25 1310865
..
... 10/02
5002
CONVERSION KIT > G31 1310866
..
... 10/02
CONVERSION KIT G20 > G31 1311759
..
11/02 ...
CONVERSION KIT G20 > G31 1311760
..
5014 CONNECTION - FIRST FITTING 1313069
..
CONNECTION - FIRST FITTING 277922 1010429
..
5015 CONNECT. ELM E00648 1010182
....
CONNECT. VAILLANT E00649 1010183
....
CONNECT. CELTIC E00650 1010517
....
CONNECT. JUNKER E00652 1011063
....
CONNECT. SAULNIER DUVAL FF 1303293
....
5020 SLEEVE 1018789
..
SLEEVE 61309802
..
5021 CHOCK - BOTTOM SIDE E00654 1010655
..
CHOCK - BOTTOM SIDE 61309803
..
5022 CHOCK - DRAUGHT DIVERTER SIDE
E00655 1010080
..
CHOCK - DRAUGHT DIVERTER SIDE 61309804
..
5023 SIDE CHOCK E00656 1010081
....
5030 JIG PLATE 1309325
....
5033 ROD PLATE E23679 1010932
....
5035 SOUNDPROOFING KIT 1305676
....
5040 USERS' INSTRUCTIONS 1309033
..
USERS' INSTRUCTIONS 1310360
..
5045 WALL SPACER KIT E23683 1016144
....
6000 MAINTENANCE
6002 DESCALING INTERFACE/WATER EXCH
1011075
..
6003 SIMULATING BOX 3 WAY VALVE E23686 1012597
..
6006 SPANNER
1302650
....
6007 STOPPED W/THROT. CONNECTOR KIT 1306970
....
18
Loading...