Chaffoteaux & Maury Calydra Green 24, Calydra Green 30 Maintenance And Service Manual

MAINTENANCE AND
54 54 54 54
JKLMN
I
88
JKLMN
232
235
32
C
Dimensions
SERVICE GUIDE
Fanned Flue Condensing
Combination Boiler
Heating and Storage Domestic Hot
®
67
212
Water with TSS
Outer case dimensions :
- Width : 440 (minimum space required 450)
- Height : 850
- Depth : 24 kw : 380 30 kW : 405
360
50
737
850
24 kW : 380 30 kW : 405
I Safety valve outlet J Heating flow
Technical data
Heat gross input C.H. max ............................ 9.2-27.8 kW 10.4-31.6 kW
Heat gross input D.H.W. max........................ 9.2-27.8 kW 10.4-31.6 kW
Heat output C.H. 50°/30° max....................... 9-26 kW 10-30 kW
Heat output C.H. 80°/60° max....................... 8-24 kW 9-28 kW
Heat output DHW maxi ................................. 8-24 kW 9-30 kW
C.H. operating temperature........................... 80°C max 80°C max
C.H. circuit pressures Min operating ............. 0.7 bar 0.7 bar
C.H. circuit pressures Max operating ............ 2.5 bar 2.5 bar
D.H.W. flow rates 30°C ................................. 12.5 l/min 14.5 l/min
D.H.W. flow rates 35°C ................................ 10.7 l/min 12.4 l/min
Cold water mains pressures Min operating... 0.5 bar 0.5 bar Cold water mains pressures Max operating.. 10 bar 10 bar
Flow limiter rate............................................. 8 l/min 10 l/min
Safety discharge ........................................... 3 bar 3 bar
Expansion vessel - Pre-charge pressure ...... 0.7 bar 0.7 bar
Net capacity at 3 bar in litres......................... 5.44 5.44
Supply ........................................................... 230 v 230 v
Consumption ................................................. 150 w 150 w
Protection ...................................................... IP 44 IP 44
Fuse F1/F2/F3/F4 ......................................... 2 A/1.25 A/0.315 A/0.250 A
External controls ........................................... 24 v 24 v
K D.H.W. flow L Gas supply M Cold water inlet N Heating return
24 kW
30 kW
Safety valve center line
All dimensions in mm
24 kW
Natural gas G20
Gas rate C.H. max .................. 2.64 m3/h 3.01 m3/h
Gas rate D.H.W. max .............. 2.64 m
Gas rate C.H. & D.H.W. min ... 0.87 m Gas valve restrictor diameter .. without without
Propane L.P.G G31
Gas rate C.H. max. ................. 1.94 kg/h 2.21 kg/h
Gas rate D.H.W. max. ............. 1.94 kg/h 2.21 kg/h
Gas rate C.H. & D.H.W. min ... 0.64 kg/h 0.73 kg/h Gas valve restrictor diameter .. 4.40 mm 4.8 mm
30 kW
3
/h 3.01 m3/h
3
/h 1 m3/h
Pump and expansion vessel characteristics
20 40 60 80 100 120Pf140 160 180 200 220 240
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
80°C
70°C
60°C
50°C
40°C
260
Pression à froid pour le circuit chauffage (en bar)
0
4
3
2
1
5
6
100
200
800
700
600
500
400
300
900
1000
1100 l/h
mCE
Débit mini (robinets thermostatiques fermés)
Hauteur manométrique
GVF
GVO
PVF
PVO
bar
0
1
3
4
Pump head available
Minimum flow rate (with all heating thermostatic valves closed)
GV F= high speed by-pass closed GVO = high speed by-pass open PV F= low speed by-pass closed PVO = low speed by-pass open
10
7
2
3
8
12
6
13
Central heating initial pressure when cold (in bar)
System capacity chart
Note : The system initial pressure should be over the following value :
System static height (in metre) + 0.7 = Initial pressure (in bar)
Components location
1.- Steel chassis complete with expansion vessel
2.- Sealed chamber
3.- Burner and heat exchanger assembly
4.- Air / gas connection
5.- 24 V modulating fan
11
9
1
4
5
49
15
18
14
6.- Gas valve
7.- Ignition electrode
8.- Ionisation probe
9.- Ignitor
10.- Combustion products manifold
11.- 24 V transformer
12.- Siphon
13.- Electrical box
14.- Pump
15.- Secondary heat exchanger
16.- Pressure gauge
17.- Three way valve
18.- Automatic air separator and automatic vent 19 - Central heating flowswitch
20.- Domestic hot water flowswitch
21.- Central heating control thermistor
22.- Hot water control thermistor
23.- TSS Control thermistor 24 - Overheat sensor 25 - TSS ®(mini cylinder) 26 - DHW pressure relief valve.
40.- Central heating flow isolating valve
41.- Domestic Hot Water outlet
42.- Gas service tap
43.- Water service tap
44.- Central heating return isolating valve
45.- Central heating pressure relief valve
46.- User’s guide
47.- Connecting tails (x 5)
48.- Adjustable by-pass 49 - Silencer
C liter
10
46
47
40
41
42
43
16
24
22
21
19
17
48
25
20
23
26
44
45
2
FUNCTIONING
Control panel
33
36 39
32
27
28
37
3435
29
Switching on
1. Check that the pressure in the Central Heating system is above 0.7 bar and below 1.5 bar with the pressure gauge 16.
2. Check that the gas service tap is opened at the gas meter and the main power is on. Green indicator Power ON
3. Open the gas tap The boiler is now ready to use.
Attention ! If the boiler remains off for a prolonged period of time, air may collect in the gas pipes and can hinder the boilers initial
attempts to light. (please refer to section 18 Incorrect Function)
42.
30
38
27 - Display
28.- Domestic Hot water switch
29.- Green indicator – Domestic Hot Water mode ON
30.- D.H.W. temperature reducing key
31.- D.H.W. temperature increasing key DHW mode indicator
32.- Central Heating switch
33.- Green indicator – Central Heating mode ON
34.- Central Heating temperature reducing key
35.- Central Heating temperature increasing key
36.- Green indicator – Power ON
37.- Orange indicator - Burner ON
38.- Red indicator - Lock out / flame failure
39.- Reset key
31
36.
Switching on the Central Heating
Press key 29 , the green indicator 33 will light and the display will show the Heating
flow temperature.
Keys
system depending on the weather conditions.
• press to increase temperature when the weather is cold
• press to reduce temperature when the weather is fair
During the temperature setting operation the display will flash.
If the room thermostat is calling for heat, a dot will be displayed at the bottom of the 3rd digit
34 and 35 allow the adjustment of the temperature required in the Central Heating
3
Switching on the Domestic Hot Water
Press key 28 , the green indicator 32 will light :
If there is no water demand
the display will show the following graphic
If the tank is heating up
the digit will move clockwise on the display
In case of draw off
a square made of 4 digits will move clockwise on the display
30 and 31 allow the adjustment of the temperature required for the Domestic Hot Water flow. During the tempera-
Keys ture setting operation the display will flash.
Note : The configuration of the C.H. system can generate some gravity effect when the boiler is set in D.H.W. mode only. It may result in a temperature rise of the heating pipes close to the boiler (or eventually a radiator). To avoid this, it is possible to close dur­ing the summer period (Central Heating switched off) the heating flow isolating tap ( the Central Heating mode again.
40). Don’t forget to open it before switching on
Switching on the Domestic Hot water and Central Heating together
Press key 29 the green indicator 33 will light. Press key
28 the green indicator 32 will light.
If there is no water demand
If the tank is heating up
In case of draw off
the display will show the heating flow temperature
the digit will move clockwise on the display
a square made of 4 digits will move clockwise on the display
Stand by mode A fixed digit at the centre of the display and the green indicator 36 on
Putting the boiler in stand by mode and anti-freeze system. :
Press keys 29 and 28
During the duration of the stand-by mode, an automatic anti-sticking system will switch on the pump for 1 minute and make a movement of the 3 way valve every 23 hours. The stand-by mode will disable the anti-freeze function of the room thermostat (if fitted). To leave the room thermo­stat anti-freeze system operative, please leave the Central Heating mode on.
The boiler is equipped with an automatic anti-freeze system which is permanently on.
If the Central Heating temperature decreases below 7°C, the pump will start. If the Central Heating temperature decreases below 4°C, the pump and the burner will start.
to switch off both DHW and CH mode. The green indicators
,
33 and 32 will stop.
Turn off the boiler
- Press keys 29 and 28
- Switch off the main electrical supply
- Shut off the gas service tap
In this condition, the anti-freeze system is inoperative
Note :
,
42
to switch off both D.H.W. and C.H. mode. The green indicators
4
33 and 32 will stop
Domestic Hot Water Mode
To be able to supply hot water, the DHW mode should be ON. Press on key
, the green indicator 32 will light.
If there is no water demand, the display will show the following graphic the TSS®is cold, the burner will light immediately.
a square made of 4 digits will move
clockwise on the display . Keys
30 and 31 allow the adjust-
ment of the temperature required for D.H.W., flow. During the temperature setting operation, the display will flash. When a tap or a shower is turned on, the flow of mains water, above 2 litres per min., will activate the DHW flow switch 20 or if the TSS®thermistor is calling for heat and allow the 3 way valve move to the DHW position. The pump can now circulate primary water heated by the main exchanger through the sec­ondary heat exchanger and TSS®coil. The primary flow switch checks that this flow rate is over 4lt./min. before allowing the lighting sequence to begin. The fan on the gas valve assembly starts and when the lighting speed is reached (detected by a hall effect sensor) the 2 safety solenoids open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected, the orange indicator led will light and the regulation system will be able to adjust the gas rate regarding the heat load. If the TSS®thermistor is
In case of draw off,
28
if
17 to
34
calling for heat, the burner will stay in minimum output. If a flame is not detect­ed, after 10 seconds, the security sole­noids close together and shut off the gas. The red lockout indicator led light. Press the reset button to re-light the burner. For flow rates of less than 2 l/min, the domestic hot water temperature is con­trolled by TSS®thermistor ing thermistor l/min , the domestic hot water tempera­ture is controlled by hot water control thermistor control thermistor pates the changes of temperature in the secondary heat exchanger and ensures accurate temperature regulation. When the tap is closed the burner may stay alight until the TSS®cylinder is up to temperature. Then the burner is extin­guished and the pump stops. The boiler will now stay in the hot water mode for 3 minutes to maintain temperature to ensure a fast response in the event of a subsequent hot water demand. Priority will be given to a demand for hot water or re-heating of the TSS®cylinder. This will interrupt the central heating for the duration of hot water supply.
Central Heating Mode
To be able to supply heating, the mode should be switched ON. Press key
, the green indicator 33 will light, and
the display will show the Heating Flow temperature.
Keys
34 and 35 allow the adjust-
ment of the temperature required for the
21. For flow rates over 2
22 and the central heating
21. This system antici-
38 will
23 and heat-
29
Central Heating system regarding the weather conditions. During the setting operation, the display will flash. When there is a demand for heating, (either from the room thermostat or the clock) the pump starts. If the boiler tem­perature control is calling for heat and the primary flow rate is over 4 lt./min., the central heating flow switch operates, allowing the ignition sequence to begin. The fan on the gas valve assembly starts and when the lighting speed is reached (detected by a hall effect sensor) the 2 safety solenoids open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected, the orange indicator LED will light and the regulation system will be able to adjust the gas rate regarding the heat load. If a flame is not detected, after 10 seconds, the security solenoids close together and shut off the gas. The red lockout indicator LED Press the reset button to re-light the burner. The Central Heating flow temperature is controlled by the Central Heating control thermistor designed to minimise cycling and will not attempt to re-light for at least 3 min. after the boiler thermostat has been satisfied. When the room thermostat is satisfied , the burner will switch off and the pump will remain running for a further 3 min­utes before it too stops. Note: It is possible to override the 3 minute delay by pressing the Reset key
39.
21. The boiler has been
38 will light.
37
5
Lockout procedure
17
18
19 20
21
23
24
26
27
28 29 30 31
33
32
34
36
37 38
39
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
22
25
35
17
18
19 20
21
23
24
26
27
28 29 30 31
33
32
34
36
37 38
39
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
22
25
35
Flame disappearance : When the ionisation electrode
8 does not
detect flame presence. The orange indi­cator led
37 extinguishes. A lighting
cycle starts. If a flame is not detected, before 10 seconds, the safety solenoids will close. The lockout red indicator
38
lights and the display shows the error
code. The pump runs and the 3 way valve
17 stays in its position. After a few
seconds, it will become possible to reset the boiler by pressing the reset key
Overheat detection :
If an overheat (over 100°C) is detected in the primary circuit by the sensor safety solenoids close and the fan stops.
CALYDRA GREEN FUNCTIONAL DIAGRAM
39.
23, the
The orange LED
37 extinguishes and the
pump remains running for 3 minutes. The reset will only be possible once the primary temperature has dropped below 76°C.
Heating mode
ELECTRICAL WIRING
DIAGRAM
Hot Water mode
6
ACTION CONFIGURATION
DISPLAY
5 ”
x times
once
Menu - 1 - Default register
Record the last 10 defaults
Section Digit 1 Digit 2 and 3
Last default occured 0
Last but one default occurred 1
code from 01 to 99
code from 01 to 99
... ... code from 01 to 99
Last default occurred before the previous one 9
code from 01 to 99
Note -- is displayed if no default is recorded.
Menu - 2 - Boiler conditions
Indicates the conditions or the configurations of the boiler
Section Digit 1 Digit 2 and 3
x times
Software version of display PCB 0
Flue type 2
Room thermostat is calling for heat 3
Theoretical position of the 3 way valve 4
DHW flow temperature in Celsius degrees 5
®
TSS
temperature in Celsius degrees 6
CH flow temperature in Celsius degrees 7
Software version of main PCB 9
10 to 99
1 : FF
variable speed
3
4
0 : no
1 : yes
0 : DHW
1 : CH
from 00 to 99
from 00 to 99
from 00 to 99
10 to 99
7
ACTION CONFIGURATION
Menu - 3 - Boiler options
DISPLAY
Section Digit Digit
once
1 2 and 3
Under floor heating system 0 0 : no
DHW Delay 5 0 to 5 mn by step 0.5mn
x times
(time before CH relight after a DHW cycle)
DHW flow swith Delay 6 0 to 20 1/10 seconde
(time before DHW flow detection to override pressure peak problem)
ACTION CONFIGURATION
Menu - 4 - Boiler settings
Section Digit Digit
once
Room thermostat operation 0 0 : Burner only
1 : yes
1 2 and 3
DISPLAY
Factory
Factory
setting
setting
x times
0
1 : Burner and pump
Pump speed 1 0 : High speed
1
1 : Low speed
Pump post circulation duration 2
0.0 min
From 0 to 5 minutes by step of 0.5 min. 2 0,5 min
2 1.0 min
2 5.0 min
Maximum Central Heating flow temperature 4 50°C
4 80°C
C.H. anti-cycling delay 8 0.0 min
From 0 to 7 minutes by step of 0.5 min. 8 0.5 min
8 2.5 min
8 5.0 min
C.H. maximum output limitation Model 24 From step 0 (P. min.) 8 kW Value from
to step 10 (P. max.) 24 kW 9 0 to 10 Model 30 From step 0 (P. min.) 9 kW Value from
to step 10 (P. max.) 28 kW 9 0 to 10
8
X X
X X
ACTION CONFIGURATION
X X
Menu - 5 - Combustion rate control mode
press once
Effect Display
DISPLAY
wait 5 ”
press once
press once
press once
Combustion rate control mode OFF
Switching on the combustion rate control mode. Central heating out put reaches the maximum power set in menu 4 section 9.
Switching the combustion rate down to minimum power.
Switching on the combustion rate to maximum output set in menu 4 sec­tion 9.
Central heating temperature is dis­played in celsius degrees. The 3 dots indicate that the combus­tion rate control is ON at maximum output.
Central heating temperature is dis­played in celsius degrees. The dot indicates that the combus­tion rate control is ON at minimum output.
Central heating temperature is dis­played in celsius degrees. The 3 dots indicate that the combus­tion rate control is ON at maximum output.
Switching off the combustion rate control mode.
press once
Locking conditions of the combustion rate control mode :
- boiler in stand by mode
- D.H.W. draw off
- room thermostat is not calling for heat
- room thermostat is calling for heat but the maximum temperature is reached
- boiler in lockout mode
- after a reset or if the main supply fails
- end of the mode if operator leave menu 5
- after 15 minutes if there is no actions on keyboard
Note : As soon as the combustion rate control mode is on, Central Heating and Domestic Hot Water keys
are inactive.
9
C.H. heat output setting :
If you would like to change the setting of the C.H. heat output, please proceed as follows: (note: the factory setting is 18 kW and the following explanation refers to menu 4 section 9)
Display
- Switch to installer mode, press key
1
and on DHW side for 5 sec­onds. The display shows :
-1- then 0•-- if there is no default in the default register.
- press 3 times on menu key (on
2
C.H. side) to gain access to menu The display shows :
-4- then the value set for section 0 ( 00
or 01 respectively Action on burner only or pump and burner)
3
- change to section 9 (Adjustment of C.H. heat output). Press key on D.H.W. side 9 times. The display shows: 906 (which corresponds to the 18 kW which is the factory setting)
9 = section 9 06 = 18 kW
-4-,
1
5 ”
2
x 3
or
3
x 9
4
- press setting key (on CH side) once, the 2nd and 3rd digits flash together. Then press the or key on the D.H.W. side to change the C.H. heat output step between
10. Press the setting key to confirm the value. The display stops flashing. Setting procedure is finished. To exit from setting mode, leave the boiler for approx. 1 minute, the comput­er will switch back to user mode. After programming please close the
P.
door
4
00 and
10
REGULATION
FLOW SWITCHES
Temperature regulation for both C.H., TSS®and D.H.W. circuits are con­trolled by 3 thermistors. The C.H. knob allows the adjustment of temperature between 35 and 85°C. The D.H.W. temperature is limited to 60°C. TSS®, D.H.W. and C.H. thermistors are identical and interchangeable.
Resistance value are
- 5000 Ω at 25 °C
- 2631 Ω at 40°C
- 620 at 80°C
- 255 at 110°C
Flow in both D.H.W. and Heating cir­cuits are detected by 2 flow switches. A piston with a magnet at the top operates a REED switch. The piston is lifted by flow rates listed below :
Flow rate threshold : D.H.W. 120 l/h ±20 l/h C.H. 250 l/h ±20 l/h
ROUTINE SERVICING
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at reg­ulars intervals. The frequency of servicing will depend upon the particular installation condition and usage, but in general, once a year should be adequate.
It is the law that any service work must be carried out by a competent person such as your local Chaffoteaux Service Centre, British Gas or other CORGI registered personnel in accordance with the current Gas Safety (Installation and Use) regulation.
Attention ! the air/gas connection pipe between the gas valve and the burner should never open. The seal can be checked only in the factory.
The service schedule should include the following operations :
- Check the pressure in the system
- Check the correct operation of the appliance
- Check the correct operation of the gas controls
- Check the functions of safety controls
- Clean the electronic board of the fan located on the gas valve assembly and the different transformers in the sealed chamber.
- Check combustion chamber insulation panels for damage
- Check the lighting and ionisation electrodes condition
- Clean the burner (Never use a metallic brush as this can damage the stainless steel)
- Clean the heat exchanger (Never use a metallic brush as this can damage the stainless steel)
- Clean the siphon and pay attention to the acidity of its contents
- Check the correct seal of the drain system
- Clean gas and water filters
- Check expansion vessel charge pressure
- Clean and check the operation of the safety valve
- Check the correct seal of the flue system.
Additional procedures that may be necessary :
- Check the burner pressure and the gas flow rates
- Check, clean or replace components as necessary
- Carry out combustion test utilising the test points in the flue turret
Suggested sequence for servicing :
Before disconnecting or removing any part, isolate the gas and electricity supplies. Ensure that the appliance is cool, and take care about the condensate products content in the siphon which are acid.
(For detail, please see section on Parts Removal and Replacement)
Preliminary checks
- Remove outer case
- Check the system pressure is at least 0.7 bar cold
- Check the modulation of the gas valve in DHW mode by reducing progressively the flow rate at a tap.
- Check that the burner is extinguished fully when both solenoids are closed and fan is off.
- Test ionisation functions and check that lockout occurs by turning off gas tap.
- Whilst the boiler is operating, check the operation of the primary flow switch by closing the Central Heating flow valve and by­pass screw (turn clockwise ) noting the number of turns so that it may be reset correctly.
- Check the correct flood of condensate into the siphon which is transparent.
11
REMOVAL AND REPLACEMENT OF PARTS
T
T
1
2
Before removing the appliance case, isolate the gas and electrical supplies. Isolate the boiler from the system and drain before removing any component in the waterways. Ensure that the appli­ance is cool.
1. Outer Case
Remove the four screws A in the bottom of the case and lift free. When replacing,
5. Lighting electrode
Carry out steps 1 and 2. Disconnect the lighting electrode from its wiring. Loosen the 2 screws and pull it out from the combustion chamber front panel. Replace the ionisation gasket provided. Reassemble in reverse order.
6. Burner
Carry out steps 1, 2 and 3. Remove the 4 Philips screw retaining the burner onto the combustion chamber. Pull it out with care to avoid any damage to the ceramic panel protecting the combustion cham­ber front panel. Replace the burner gas­ket. Reassemble in reverse order.
11. Drain down
2 drain points are located on the boiler.
air separator
1
2
A
A
carefully locate on lugs edge of the chassis.
2. Sealed chamber front panel
Unscrew the four self tapping screws securing the sealed chamber front panel and lift over the top corner locating lugs. Reassemble in reverse order.
3. Combustion Chamber front panel and air/gas connection
Carry out steps 1 and 2 as above. Unscrew the three screws securing the air/gas connection pipe onto the gas valve assembly. Disconnect the ionisa­tion and lighting electrodes from their wiring. Unscrew the six nuts to release the combustion chamber front panel and pull the assembly towards you. Reassemble in reverse order.
4. Ionisation electrode
Carry out steps 1 and 2 as above. Disconnect the ionisation electrode from its wiring. Loosen the 2 screws and pull it out from the combustion chamber front panel. Replace the ionisation gasket provided. Reassemble in reverse order.
T on the top
A
A
7. Gas vale assembly
Carry out steps 1 and 2 Unscrew the three screws securing the air/gas con­nection pipe onto the gas valve assem­bly. Disconnect the connectors from the gas solenoids and fan. Loosen the gas pipe nut. Unscrew the six nuts to release the combustion chamber front panel and pull the assembly towards you. Replace the gas filter before fitting the full assembly back into the boiler.
8. Fan assembly
Carry out all the operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. Reassemble in reverse order and replace all necessary gaskets.
9. Gas section
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. The venturi and the gas section can be separated by loosening the 2 screws located at the top of the gas valve. Replace all necessary gaskets before reassemble in reverse order.
10. Venturi in the gas section
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. The venturi and the gas section can be separated by loosening the 2 screws located at the top of the gas valve. Replace all necessary gaskets before reassembling in reverse order.
1 = DHW circuit drain point 2 = Heating circuit drain point
12. Water filters ( DHW and Heating) The DHW filter ensures a seal between the connecting bracket and the pipe to the DHW flow switch. Drain the boiler as in step 11. Unscrew the pipe nut and remove the clip on the hydraulic assy. Pull the pipe toward you and remove the water filter from its location. The C.H. filter is located in the right hydraulic assembly. Remove the return pipe as described previously and with­draw the filter. Reassemble in reverse order.
13. Flow switches
Drain boiler as in step 12. Disconnect the electrical plug, turn the top cover anti-clockwise, remove the O-ring and the brass piston. Reassemble in reverse order.
14. 3-Way valve
Drain boiler as in step 12. Remove the 3 clips on the 3 way valve. Remove the clip on the exchanger flow pipe. Pull the pipe down then pull it out of the 3 way valve. Disconnect the plug from the motor. Unscrew the nut on the pipe between the connecting bracket and the 3 way valve and pull it toward you. Rotate the 3 way valve body anti-clock­wise to unclip it from the left hydraulic assembly.
15. Secondary heat exchanger
Drain both circuits of the boiler as in step
12. Unscrew the 2 fixing screws D and remove the DHW exchanger from the front. Prior to reassembly, check that the 4 gaskets are correctly positioned. The heat exchanger is so designed that it
12
D
cannot be remounted incorrectly.
16. Main heat exchanger
Carry out steps 1 and 2. Drain down the boiler as in step 12. Unscrew the three screws securing the air/gas connection pipe onto the gas valve assembly. Disconnect the ionisation and lighting electrodes from their wiring. Unscrew the six nuts to release the combustion chamber front panel and pull the assem­bly towards you. Undo the two clips of the pipes to the main exchanger and pull down the pipes. Unscrew the three screws located at the bottom, top left and the right with the retaining system to be able to pull the main heat exchanger towards you. Reassemble in reverse order taking care about the location of the gasket on the
screw and pull out the valve. Reassemble in reverse order.
19. Thermistors
Drain the boiler as step 12. Disconnect
21
22
the plug, remove the retaining clip pull the thermistor out. Reassemble in reverse order.
22 = DHW thermistor 21 = Heating thermistor
20. Safety thermostat
Remove the casing as step 1 and hinge down the electrical box as step 5.
reverse order.
23. Display PCB
Carry out step 1 and hinge down electri­cal box by pressing the retaining tabs on either side. Remove the pressure gauge clip. Rotate the electrical box back into the upper position. Undo the 2 screws retaining the front panel, put your two hands at the bottom of the front panel and pull it down to release it from the 2 clips. Hinge down again the electri­cal box. Undo the 4 screws of the electri­cal rear panel and remove it. Unplug the display board cables from the main PCB. Reassemble in reverse order.
24. Expansion vessel
Remove the casing as step 1 and drain the boiler as step 12 above. Unscrew the connecting tails nuts and lift out the boiler from the wall. Place it on a side on the floor. Remove the expansion vessel bracket retaining screws, disconnect the pipe from the vessel and pull it toward you. Reassemble in reverse order.
P
fumes collector and replace all neces­sary gaskets.
17. Pump
Drain boiler as in step 12. Pivot the elec­tical box downwards. Open the electrical box cover removing the 2 screws. Remove the pump plug from the power board and the earth plug from the earth socket. Unscrew the nut pipe from the volute. Remove the clip on the pump volute and pull the pump
F of the return
G
24
Disconnect the 2 cables, pull out the sensor with the clip (13). Reassemble in reverse order.
21. Spark generator
Carry out steps 1 and 2. Unplug the con­nector from the spark generator located on the right hand side of the main heat exchanger. Loosen the two screws to remove the igniter. Reassemble in reverse order.
22. Main control board
G
Carry out step 1 as above and hinge down the electrical box by pressing the retaining tabs wiring cover electrical rear panel and remove it. Unplug all cables from the PCB, remove
P on either side. Remove
C. Undo the 4 screws of the
25. Pressure gauge
Carry out step 1 and drain the boiler as step 12. Hinge down the electrical box by pressing the retaining tabs side. Press on the clip to remove it and pull it out. Remove the clip which holds the connection of the capillary onto the pump hose. Hang out the pressure gauge with its capillary. Reassemble in reverse order.
26. TSS
Drain both circuits of the boiler as in step 11. Unscrew all nuts from the con­necting bracket and remove the gas pipe from the gas section. Remove the main exchanger flow pipe to the 3 way valve. Remove the pump as in step 17. Unplug all thermistors, 3 way valve, flow switch­es. Unscrew the 2 retaining screws of the hydraulic section to the chassis. Pull the hydraulic assembly toward you. Reassemble in reverse order and check the gas section for soundness and the water circuits for leakages.
®
P on either
toward you. Reassemble in reverse order.
18. Pressure relief valve
The pressure relief valve can be ser­viced from the front of the appliance. Drain the boiler first, undo the retaining
P
F
C
the earth plug from the earth socket. Hang out the main PCB. Reassemble in
13
P
Yes
1 Overheating LockOut
3 No flame detection
5 Anti-frost mode on
6 Anti-frost mode on
7 No water circulation
PLEASE CHECK THE FOLLOWING POINTS CAREFULLY
BEFORE GOING THROUGH THE FAULT FINDING CHART
-Gas pressure
-Electric mains
-Minimum water pressure in the heating circuit (over 0.8 bar)
-All isolating valves have been opened
-Boiler air vented
-Minimum domestic hot water flow of 2 l/min
means a test or a choice
means an action
means a group of actions
error code displayed
Error code Description
-Check that the heating filter is clear.
- Remove the front panel of the sealed chamber
-7
No
FAULT FINDING CHART Part 1
thermistor faulty opened circuit
thermistor faulty short circuit
®
®
8 Faulty water circulation in the primary circuit
9 DHW thermistor faulty, Opened circuit
10 DHW thermistor faulty, Short circuit
11 Central heating thermistor faulty, Opened circuit
12 Central heating thermistor faulty, Short circuit
18 Ignition test
20 Faulty connexion
No
Does the display
mode ON
show a - XX code ?
Switch Domestic Hot Water
26 TSS
29 3 ways valve locked in Heating position
31 Error communication with EEPROM
23 Low speed fan
24 Faulty control functionning fan
25 TSS
32 Error communication with the main PCB
No
at a tap
Does the pump run ?
Draw off Domestic Hot Water
No
spark generation?
Could you see the
Wait for 4 seconds
Yes
No
Does the fan run ?
Yes
Does the pump run ?
-3 Ok
display ?
Does the -24 error
No
or
or
- Check pressure probes
- Replace pressure switch
- Check flue duct condition
Ok
Check flow in the
Check heating flow switch
No
boiler primary circuit
No
-7
Replace heating flow switch
could be fully scaled.
Check or replace main or sec-
ondary heat exchangers. They
No
Does the spark
generator energize ?
Replace control PCB
Yes
-3
ignition electrods assembly
Replace spark generator or
Ok
Ok
thermistor
Check heating
No
-7
-11
-12
Replace heating thermistor
No
the fan
Check voltage on
Ok
Replace fan assembly
evant fuse
Replace transformer or the rel-
No
the transformer
Check the 24 V at
Ok
Yes
alight ?
Does the green LED
Switch on the main electrical supply
Ok
No
connection
- Check mains electrical
- Check connection between
- Check internal fuses
light ?
Ok
Does the red LED
Yes
No
the 2 PCBs
Yes
Press the reset button
codes and solve the problem
Please refer to the list of error
Replace control PCB or
Yes
switch
Check or replace the DHW fow
display PCB
No
switch operation
Check DHW flow
No
Replace DHW flow switch
Ok
No
Ok
Check that the
pump electrical box
Check voltage in the
No
Release pump rotor
Ok
Replace pump
pump spins freely
Replace control PCB
14
Stop water draw off
No
- Press on DHW key to switch
off DHW mode.
- Press on CH key to switch on
CH mode and set CH tempera-
are calling for heat.
ture to maximum.
- Press the RESET button to
cancel the 3 min. delay.
- Ensure that external controls
LED light ?
Does the orange
No
Yes
Yes
?
Does the heating
outlet pipe temperature rise
No
Yes
LED light ?
Does the orange
temperature to minimum
Wait until the return pipe
become hot then reduce CH
No
The boiler is OK
FAULT FINDING CHART Part 2
connection between the 2 PCBs
Replace display PCB or control the
Yes
connection between the 2 PCBs
Replace display PCB or control the
No
Drain and clean combustion cham-
Yes
-3
alight ?
No
Does the burner still
Yes
Does the red LED
Is the combution
light and -3 displayed ?
No
Yes
LED light ?
Does the orange
ber, siphon and drain pipes
Replace the ionisation probe
No
No
Check ionisation
probe
Ok
sates ?
chamber full of conden-
Does DHW temper-
ature rise over 70°C ?
Replace control PCB
- Adjust the DHW flow rate to
3 l/min at a tap.
- Wait until the temperature
Yes
perature rise?
Does the DHW tem-
Yes
becomes stable.
No
mistor
Check DHW ther-
No
Replace DHW thermistor
Ok
Replace control PCB
Replace the 3 way valve
Replace the 3 way valve
Yes
-29
No
rise ?
Does the heating
outlet pipe temperature
Replace control PCB
exchanger
Replace the DHW heat
Yes
No
Can you see the
flame on the burner ?
Yes
on reset button
Purge the gas pipe and press
Do the gas
solenoïds energise ?
No
Replace control PCB
Yes
Do you feel air
drawing in at the air
Replace gas section assembly
No
Check that air inlet pipe, ven-
turi, fan, air/gas pipe or burner
are free of dust and not blocked
28
- Switch off the boiler.
- Draw off DHW at a tap until the
temperature becomes cold.
- Close the tap
- Press on key
Yes
Boiler is OK
15
No
LED Alight
Does the orange
Ok
26
25
®
thermistor
Check the TSS
No
®
thermistor
Replace the TSS
507
R37
R31
J7
R102
1
+
+
+
8
C68
ST2
FT1A
Z11A
Z9A
R
DL1
TH1A
Z6A
R132
U5
Z5A
Z4A
TERRE1
TH1
C83
C78
C80
ST1
R87
Z9
Z6
Z5
Z4
Z3
Z2
Z11
Z1
U3
U10
U9
U7
U6
U4
TR1
TH2
TERRE
T8
T7
T5
T4
T3
T2
T6A
T6
T12
T11
T10
T1
SW1
RL8
RL7A
RL7
RL6
RL10
RL5A
RL5
RL4A
RL4
RL3
RL2A
RL1A
RL9
RL1
RAD1
R118
R114
R113
R111
R112
R108
R107
R106
R105
R101
R97
R96
R95
R94
R93
R90
R88
R62
R58
R59
R57
R52
R53
R51
R55
R5
R78
R77
R4
R39
R35
R34
R3
R33
R32
R19
R2
R15
R25
R13
R131
C82
T14
T13
RL12
R76
R75
R71
R70
R67
R127
R116
R115
R119
R10
R1
Q1
P2
P1
MOV1
L1
J9
J10A
J8
J6
J4
J3
J2
J1
FT1
F3A
F3
F2A
F2
F1A
D9 D7
D6
D5
D34
D31
D32
D4
D42
D41
D40
D39
D36
D43
D3
D29
D26
D23
D22
D20
D2
D19
D17
D15
D13
D12
D11
D1
CTP1
C8
C13
C49
R54
RL11
C35
C7
J5
C6
C52
C51
C77
C76
C75
C74
C72
C71 C70 C69
C5
C50
C48
C47
C46
C45
C43
C42
C4
C61
C60
C59
C22
C56
C55
C54
C31
C41
C39
C2
C29
C28
C27
C26
C
C11
C9
C3
C24
C23
C20
C18
C17
C14
C12
C1
K
MA
E E
K
1
1
1
1
1
EX
1
1
ROG A
K
K
KC
1
K
K
+5V
TR
COM
REP
8
0
N
SHORT LIST
110
401
407
505
510
532
588
572
514
640
607
627 628
629 630
805
938
615
DescriptionKey N°
G.C N°
Manf. Pt. N°
110 ELECTRODE KIT 1309624 401 GAS VALVE (24 kW) 1308957 407
FAN ASSY 1307585
505 THREE-WAY VALVE E23510 81839 507 OVERHEAT THERMOSTAT 100°C 277783 1010572 510 THERMISTANCE 277834 1000733 514 WATER/WATER HEAT EXCHANGER 1302409 532 WATER THROTTLE 277846 81471 572 PUMP + AIR SEPARATOR 15/50 1301964
PUMP + AIR SEPARATOR 15/60 1303461
588 AIR SEPARATOR HEAD ASSEMBLY 1304608 607 IGNITER 1002105.20 615 PRINTED CIRCUIT BOARD 1310357 627 FUSE 250V 2A - TEMPORIZED 277883 1003456 628 FUSE 250V 1A - TEMPORIZED 1003634 629 FUSE 250V 1.25A - TEMPORIZED 277884 1003635 630 FUSE 250V 0.315A - TEMPORIZED 1307845 640 TRANSFORMER 1308149 805 PRESSURE GAUGE 1303158 938 PRESSURE RELIEF VALVE 1020933
Chaffoteaux & Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
Manufacturer: Chaffoteaux & Maury - France
Type
.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
CALYDRA GREEN 30
CALYDRA GREEN 24
GAS VALVE (30 kW)
Manf. date
from to
1310129
Commercial subsidiary: MTS (GB) Limited
MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax: (01494) 459775 internet: www.chaffoteaux.co.uk E-mail: info@uk.mtsgroup.com
Technical Support Help Line: (01494) 539579
1311267d - 03/2003
Loading...