Chaffoteaux & Maury Calydra green 24, Calydra green 30 Installation And Operating Instructions Manual

Page 1
CONDENSING WALL HUNG COMBINATION BOILER
Heating and Instantaneous Domestic Hot Water with TSS
®
Fanned Flue System
Installation and Operating
Instructions
Calydra green 24 Calydra green 30
Manufactures N° Model Type Gas Council N°
200906823037.31
Calydra green 24 Nat 47-980-25
200906826037.31 Calydra green 30 Nat 47-980-26
GB
IE
Page 2
2
These instructions are suitable for the CALYDRA GREEN boilers : Do not forget the Log
Book
Chaffoteaux & Maury supports Benchmark, the heating industry code to ensure the correct installation, commissioning and servicing of domestic central heating systems.
To The Householder Make sure you have a completed Log Book for your boiler.
This provides a record of the commissioning of your boiler.
It contains important information about your particular installation that may be required by service engineers. The Log Book will also provide contact details for the installer should you need guidance in the use of this appliance or if there are any problems.
As with your car, your boiler will work more reliably and efficiently if regularly serviced. We recommend an annual service check. The service history of the appliance will be recorded on the Log Book.
In the unlikely event of any problems with your boiler or system you should first contact your installer. If your installer cannot resolve the problem he should telephone our national service helpline.
A charge may be made if Chaffoteaux & Maury Service is called out to resolve a non-product related fault.
Your statutory rights are not affected.
CUSTOMER CARE
Chaffoteaux & Maury Ltd., as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products and a high quality after sales service. If it is necessary to contact an engineer, then telephone the national warranty helpline 0870 600 9888.
Advice on installation or servicing can also be obtained by contacting the Technical Department.on:
Tel: 0870 241 8180 Fax: 01494 459775 GUARANTEE The manufacturer’s guarantee is for 12 months from the date of purchase. The guarantee is invalidated if the appliance is not
installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an efficient after sales service, please return the guarantee registration card enclosed with the boiler without delay.
STATUTORY REQUIREMENTS The installation of this appliance must be carried out by a CORGI Registered person or other competent person and in
accordance with the requirements of the Gas Safety (Installation and Use) Regulations. In addition, the installation must also comply with the current bylaws of Local Water Undertakings, Building Regulations, IEE
Wiring Regulations, Local Authority Building Standards (Scotland) Regulations and the Safety Document 635 The Electricity at work Regulation. The appliance named below does not contain any asbestos or asbestos products, or mercury
derivatives. Additional CFC’s have not been used in this product. The appliance does not contain any potential hazard in relation to the COSHH regulations. It should also be carried out in accordance with current editions of the following British Standards Codes of practice: BS 6891,
BS 5440 parts 1 and 2, BS 5449 part 1, BS 7593, BS 6798, BS 5546, BS 4814, BS 7074 part 1 and 2, BS 7671 and BG DM2. If there is a possibility of the incoming mains water pressure exceeding 10 bar then a suitable pressure limiting valve must be
fitted where pressures exceed 6 bars a pressure limiting is preferred. Precautions: During servicing, keep the dust generation to a minimum and avoid inhaling any dust and contact with the skin
and eyes. Normal handling and use will not present any discomfort, although some people with a history of skin complaints may be susceptible to irritation. When disposing of the ceramic lining, ensure that it is securely wrapped and wash hands after contact.
TO CONTACT C&M SERVICE, PLEASE CALL THE NATIONAL WARRANTY HELPLINE ON:
0 870 600 9888
To The Installer
As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder. Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history. Please ensure that your customer is aware of the correct operation of the system, boiler and controls.
Page 3
3
CUSTOMER CARE
Page
Guarantee ............................................................................................................................................................2
Statutory Requirements .......................................................................................................................................2
Contents ...............................................................................................................................................................3
INTRODUCTION ..................................................................................................................................................4
INSTALLER’S INSTRUCTION.............................................................................................................................5
1 DESCRIPTION.................................................................................................................................................5
2 DIMENSIONS .................................................................................................................................................6
3 HYDRAULIC DATA .........................................................................................................................................6
4 INSTALLATION REQUIREMENTS .................................................................................................................7
Location ...................................................................................................................................................7
Flue..........................................................................................................................................................7
Ventilation ................................................................................................................................................7
Gas Supply .............................................................................................................................................7
Electrical Supply ....................................................................................................................................7
Showers...................................................................................................................................................7
Flushing and Water Treatment ...............................................................................................................7
System Controls ......................................................................................................................................7
5 INSTALLING THE BOILER .............................................................................................................................8
Method of positioning the boiler on th wall...............................................................................................8
Connecting the boiler to the system.........................................................................................................8
Safety valve and condensats drains ........................................................................................................8
Fitting the horizontal flue .........................................................................................................................8
6 ELECTRICAL CONNECTIONS ....................................................................................................................10
Making the Electrical Connections ........................................................................................................10
7 COMMISSIONING AND TESTING................................................................................................................10
Pre-commissioning ................................................................................................................................10
DHW ......................................................................................................................................................10
Central Heating .....................................................................................................................................10
Lighting the boiler...................................................................................................................................10
By pass and pump .................................................................................................................................11
Post Commissioning ..............................................................................................................................11
Handing over to the Householder
.......................................................................................................
11
8 FITTING THE CASING ..................................................................................................................................11
9 ADJUSTEMENTS AND SETTINGS ..............................................................................................................12
10 INCORRECT FUNCTION .............................................................................................................................17
11 GAS CONVERSION .....................................................................................................................................17
Contents
Page 4
4
USER’S INSTRUCTIONS
Page
12- CONTROL PANEL ......................................................................................................................................18
13- HOW TO USE ..............................................................................................................................................19
Switching on ........................................................................................................................................19
Switching on Central heating ................................................................................................................19
Switching on the Domestic Hot water ...................................................................................................19
Switching on the Domestic Hot water and Central Heating together ....................................................19
Stand by mode
......................................................................................................................................20
Turn off the boiler ..................................................................................................................................20
14 MAINTENANCE
............................................................................................................................................20
15 GUARANTEE ................................................................................................................................................20
16 PRACTICAL INFORMATION ........................................................................................................................20
17 GAS CONVERSION .....................................................................................................................................21
18 INCORRECT FUNCTION .............................................................................................................................21
19 TECHNICAL DATA .......................................................................................................................................22
This instruction booklet is especially designed for appliances installed in the United Kingdom and the
Republic of Ireland
INTRODUCTION
The CALYDRA GREEN is a fully automatic, wall mounted, low water content condensing combination boiler. It is a room sealed, fan assisted, balanced flued appliance providing central heating and mains pressure domestic hot water on demand. It has electronic ignition and is suitable for all modern electrical control systems. The boiler is designed for sealed systems only and a circulating pump, expansion vessel together with a pressure gauge and safety valve are included within the boiler. The standard horizontal flue kit is suitable for lengths 300 mm minimum to 600 mm maximum and includes an elbow adapter that can be rotated through 360° . The horizontal flue can extend up to 3 metres using 1 metre flue extension kits. 45° and 90° flue bends are also available as accessories.
Page 5
5
1.-
Steel chassis complete with expansion vessel
2.- Sealed chamber
3.- Burner and heat exchanger assembly
4.-
Air / gas connection
5.- 24 V modulating fan
6.- Gas valve
7.-
Ignition electrode
8.- Ionisation probe
9.- Ignitor
10.-
Combustion products manifold
11.- 24 V transformer
12.- Siphon
13.- Electrical box
14.- Pump
15.- Secondary heat exchanger
16.- Pressure gauge
17.- Three way valve
18.- Automatic air separator and automatic vent 19 - Central Heating flow switch
20.- Domestic Hot Water flow switch
21.- Central heating control thermistor
22.- Hot water control thermistor
23.- TSS Control thermistor 24 - Overheat sensor 25 - TSS ®(mini cylinder) 26 - DHW pressure relief valve 49 - Silencer.
1
INSTALLER’S INSTRUCTIONS
27.- Display
28.- Domestic Hot Water switch
29.- Green indicator – Domestic Hot Water mode
ON
30.- D.H.W. temperature reducing key
31.- D.H.W. temperature increasing key DHW
mode indicator
32.- Central Heating switch
33.- Green indicator – Central Heating mode ON
34.- Central Heating temperature reducing key
35.- Central Heating temperature increasing key
36.- Green indicator – Power ON
37.- Orange indicator - Burner ON
38.- Red indicator - Lock out / flame failure
39.- Reset key
1
2
3
4
5
6
8
11
12
13
14
7
Fig. 1
15
10
9
16
20
21
17
Fig. 2
19
22
23
24
25
26
38
33
27
29
30
28
37
31
Fig 3
36 39
3435
32
18
49
Description
Page 6
6
0
4
3
2
1
5
6
100
200
800
700
600
500
400
300
900
1000
1100 l/h
mCE
Débit mini (robinets thermostatiques fermés)
Hauteur manométrique
GVF
GVO
PVF
PVO
20 40 60 80 100 120Pf140 160 180 200 220 240
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
80°C
70°C
60°C
50°C
40°C
260
Pression à froid pour le circuit chauffage (en bar)
C liter
2
3
Fig. 5
Fig. 6
4
40
4
50 mini pour entretien
With packaging :
24
48,5 kg
30
51 kg
54 54 54 54
JKLMN
I
88
JKLMN
2
32
235
32
Safety valve center line
All dimensions in mm
Fig. 4
Pump head chart available at the outlet of the boiler
System capacity chart
The boiler comprises a double speed pump and an adjustable by-pass.
The chart (fig. 5) shows the pump head available regarding the flow rate. GVF means high speed by-pass closed, PVF means low speed by-pass closed, GVO means high speed by-pass fully open, PVO means low speed by-pass fully open.
For adjustment procedure, please refer to Section 8. The minimum flow rate to ensure the correct functioning of
the boiler should be over 300 l/h (with thermostatic valves fully closed).
Maximum water capacity of Central Heating system : The expansion vessel is pre-charged to 0.7 bar (10 lb/in
2
). The vessel is suitable for systems up to 145 litres capacity. For systems of a greater capacity an additional expansion
vessel will be required. Refer to the chart (Fig. 6) and BS 7074 pt 1 or BS 5449.
The minimum initial pressure of the system should be over
0.7 bar (1 to 1.5 bar is recommended).
I Safety valve C/H and condensate
J
Heating flow
K
D.H.W. flow
L
Gas supply
M
Cold water inlet
N
Heating return
minimum space required 450
Pump head available
Minimum flow rate (with all heating thermostatic valves closed)
Central heating initial pressure when cold (in bar)
Outer case dimensions :
- Width :
440 (minimum space required 450)
- Height :
850
- Depth : 380
Minimum clearances :
- Both sides 5 mm
- Above casing 170 mm
- Below casing 200 mm
- Front ( for servicing) 500 mm
- Front (in operation) 5 mm
212
360
67
737
850
24 : 380 30 : 405
50
Ø 100
206
143
Ø 125
Ø 80
120
Ø 80
250
Ø 80
250
Ø 125
Ø
80
120
Ø 80
250
Ø 80
2
50
Type C 13
Type C 33
Ø 80
120
Ø 80
250
Type C 53
The boiler is suitable for the flue types:
• type C 13
• type C 33
• type C 53
170
225
Dimensions
Hydraulic Data
Page 7
7
4
Location
The boiler can be installed on any suitable internal wall. Provision must be made to allow the correct routing of the flue and siting of the terminal to allow the safe and efficient removal of the flue products. A compartment or cupboard may be used provided that it has been purpose-built or modified for the purpose. It is not necessary to provide permanent ventilation for cooling purposes. Detailed recommendations are given in BS 5440 pt 2. If it is proposed that it is installed in a timber framed building then reference must be made to British Gas Document DM2, or advice sought from CORGI. Avoid installing the boiler where the air inlet can be polluted by chemical products such as chlorine (swimming pool area), or ammonia (hair dresser), or alcalin products (launderette).
Flue
Detailed information on the flue assembly is contained in the appropriate starter pack. The boiler must be installed so that the flue terminal is exposed to the free passage of external air at all times. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to. The minimum acceptable clearances are shown below:
- A Directly below an opening, window, etc 300 mm
- B Above an opening, window, etc 300 mm
- C Horizontally to an opening, window, etc 300 mm
- D Below gutters, soils pipes or drain pipes 75 mm
- E Below eaves 200 mm
- F Below balconies or car port roof 200 mm
- G From a vertical drain pipe or soil pipe 150 mm
- H From an internal or external corner 300 mm
- I Above ground roof or balcony level 300 mm
- J From a surface facing the terminal 600 mm
- K From a terminal facing the terminal 1200 mm
- L From an opening in the car port into the dwelling 1200 mm
- M Vertically from a terminal on the same wall 1500 mm
- N Horizontally from a terminal on the same wall 300 mm
- Q Fixed by Ubbink Rolux 4 GM flue terminal It may be necessary to protect the terminal with a guard. Reference should be made to the Building Regulations for guidance. Suitable guards may be obtained from the following manufacturer:
Quinnel Barret & Quinnel Wireworks Old Kent Road London SE15 1NL Tel: 0171 639 1357
Ventilation
The room in which the boiler is installed does not require specific ventilation.
If it is installed in a cupboard or compartment
permanent ventilation is not required for cooling purposes
.
Gas Supply
The gas installation and soundness testing must be in accordance with the requirements of BS 6891.The boiler requires a 22 mm supply. Ensure that the pipe size is adequate for demand including other gas appliances on the same supply. Combustion system protection The sulphur level contained in the gas should comply with the European Standards which are :
- maximum 150 mg/m
3
for a short period in a year
- average level of 30 mg/m
3
during one year
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and must be in accordance with current I.E.E. regulations. It must also be possible to be able to completely isolate the
appliance electrically. Connection should be via a 3 amp
fused double-pole isolating switch with contact separation of at least 3 mm on both poles. Alternatively, a fused 3 Amp. 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower. It should only supply the appliance.
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 10 bar. All fittings and pipework connected to the appliance should be of the same standard. If there is a possibility of the incoming mains pressure exceeding 10 bar, particularly at night, then a suitable pressure limiting valve must be fitted. The boiler is designed to provide hot water on demand to multiple outlets within the property. If there is a requirement for greater demands, for example if the property has several bathrooms and cloakrooms, a vented or unvented hot water storage system may be used.
Showers
Any shower valves used with the appliance should be of a thermostatic or pressure balanced type. Refer to the shower manufacturer for performance guidance and suitability.
Flushing and Water Treatment
The performance of the appliance could be impaired by system debris or the effects of corrosion. The system must be flushed thoroughly to remove metal filings, solder, machining oils and other fluxes and greases before connecting the boiler. If it is an existing system, an appropriate flushing and descaling agent should be used. Refer to BS 7593 (1992) for guidance. For more information on the use of corrosion inhibitors, flushing and descaling agents, advice can be sought from the manufacturers of water treatment products such as:
Betz Dearborn Ltd Foundry Lane Widnes Cheshire WA8 8UD Tel: 0151 424 5351 Fernox Manufacturing Britannica Works Clavering Essex CB11 4QZ Tel: 01799 550811
System Controls
The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls. The addition of such external controls can be beneficial to the efficient operation of the system. The boiler connections for external controls are 24V and so only controls of 24V or that have voltage free contacts should be used.
Fig. 7
A
B
G
H
J
C
L
M
N
K
I
D,E
F
Q
H
N
M
Q
Q
I
Installation Requirements
Page 8
8
5
Please check that you are familiar with the installation requirements before commencing work (section 6).
The installation accessories described in the following list are included in the boiler packaging.
- Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clearances, fitting instructions and commissioning instructions)
- Connection tails
- Screws and wall plugs
- Connection washers and filters
- Installation manual
Method of positioning the boiler on the wall.
The paper template can be used to ensure the correct positioning of kitchen cabinets etc. It also details the commissioning instructions.
The paper template has to be fixed to the wall and used to locate the position of the hanging bracket and the centre for the flue hole.
Drill and plug the wall and secure the hanging bracket using the screws provided. Remove the boiler from its packaging as shown
(Fig. 8) and unscrew the 4 screws A and remove the casing (Fig. 9).
Place the boiler on the wall on the hanging bracket
(Fig. 11).
If required, there is space for all piping to pass behind the boiler. Using
(Fig. 11) for reference, connect the gas and water
pipes and the valves to the base of the appliance using the tails provided. There is a 190 mm space between the valves and the wall to make these connections.
Connecting the boiler to the system
- Push in the tabs “P” (Fig. 13) on either side of the boiler and pivot the electrical box forward to gain access to the valve connections
- Remove the yellow caps and connect the boiler to the taps using the washers provided in the plastic bag. 4 x fibre washers for the C.H. flow and return, hot water outlet and cold water inlet connections 1 x rubber washer “
R” for gas connection.
Provision must be made to fill and recharge the system pressure. This can be achieved using a filling loop or other methods approved by the local water authority. Before fitting the tails onto the connecting bracket, please check the correct location of the flow restrictor
L (Fig.10) on the
main inlet.
Safety valve and condensate drains
The pressure relief valve tube is clear silicone. It should terminate below the boiler over a tundish or 22 mm pipe (see I Fig. 4) which should in turn discharge safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.
External termination via condensate siphon The condensate drainage pipe should have a minimum diameter of 22 mm and the external pipe length should not be more than 3m. The external length should be kept as short as possible to minimize the effect of freezing.
Please refer to
BS 6798 : 2000
The system should be carefully checked for leaks, as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger. The pipe from the siphon 12 (fig. 1) should be connected to a drain in the conditions described in the relevant Brittish regulations.
Pay special attention to not bend the condensates silicone drain pipe in such a way as to cause the flow to be interrupted. Please use only drain pipe material compatible with condensate products. (refer to
BS 6798 : 2000)
The condensate flow can reach 2 litres/hour; because of the acidity of the condensate products (Ph close to 2), take care before operation.
Fitting the Horizontal Flue Important!! Before starting the boiler, the siphon 12 (Fig. 1) must be filled with water. Before fitting the flue terminal
onto the boiler, please pour
1/4 litre of water in the exhaust pipe as shown (Fig. 12).
The instructions for the vertical and biflux (twin pipe) flue options are included with the relevant adapter kits. The standard flue supplied with the appliance is suitable for lengths from 300 mm minimum to 720 mm maximum. This means for rear flueing, the standard kit will accommodate a maximum wall thickness of 600 mm, and for side flueing a
maximum wall thickness of 587 mm. This takes into account the minimum appliance side clearances of 5 mm. If the flue is a side exit installation, then calculate the position of the hole with a slope of 5 mm / metre towards
the boiler from the terminal. The flue should rise up slightly to the terminal in order to let the condensate come back into the boiler.
Attention ! Use only specific condensation flue kit.
Installing the Boiler
Page 9
9
5
A
Fig.11
A
A
A
Fig. 9
Fig. 10
L
Fig. 8
Fig.12
Installing the Boiler (continued)
Page 10
10
Making the Electrical Connections
Hinge down the electrical box to gain access to the electrical connections. Push in the tabs P (Fig. 13) on either side of the boiler and pivot the box forward. Undo the two retaining screws V, remove the cover and remove the cable clamp C (Fig. 14).
Connect the live and neutral wires to the multipin plug leaving sufficient earth wire to connect to the earthing point T (Fig. 14). Note: The connections should be made so that should the lead be pulled from its anchorage, the current carrying wires
become taut before the earth wire.
If using a room thermostat or other external control, they can be connected in place of the link
S on the multipin plug (see Fig.
14).
Note: Use only controls designed for voltage free switching or a 24V supply. Do not connect to a 230V supply. Connect the multipin plug into the socket on the printed circuit board. Secure the cable using the cable clamp and
replace the cover.
NB: The room thermostat options setting can be made before replacing the electrical box cover J1 (Fig.
14).
All necessary settings for room thermostat operations are described in
Section 9 ADJUSTMENTS AND SETTINGS.
TR
COM
REP
8
M/A
VITESSE
1
1
1
1
1
1
BUS
1
CALYDRA
OFF
ON
11
12
2
1.23
OFF ON
11
12 1
SW2
PROG
SW1
TA
1
T
2A
1
MCD
1
230V
MOTEUR
RL6
R133
C28
T15
R36
R35
C80
C79
T16
R34
T12
T11
R107
R33
R130
R129
D43
U9
Z7A
R132
R16
R
15
R14
C84
C83
R6a
Z4A
C78
RL13
C73
Z6
R7a
Z7
Z
4
D46
T10
T9
RL8
RL7A
R
L7
RL10
RL2A
RL2
RL9
R119
R118
R113
R9
R8
R7
R6
R31
R32
R29
R27
R25
R24
R23
R19
R18
R17
R140
R137
TH4
R13
R12
R11
R115
C82
C81
T14
T13
R136
TH3
U11
R64
R10
R63
R59
R128
R112
J9
J
6
J7
J4
J3
J2
J1
F1
D5
D31
D30
D32
D42
D41
D40
D35
D36A
D36
D17
D16
D15
D
14
J11
C34
J5
C52
C51
C75
C
74
C31
C38
C27
C26
C25
C1
J12
U12
+5V
J
T
S
J 1
Fig. 14
6
J
T
C
S
7
Pre-commissioning
Ensure that the system has been adequately flushed. Purge gas supply of air and test for soundness. Carry out final electrical tests to ensure the correct polarity and earthing continuity.
DHW
Open the main cold feed valve 43. Open all hot taps to purge the DHW system. Check for water soundness. Check flow rate at the bath tap is set correctly (see technical data).
Central Heating Open the flow and return valves on the boiler 40 and 44
(Fig. 15)
Open the automatic air vent 18
(Fig. 2)
Fill the system and vent radiators. Set the system pressure and remove the filling loop. Check for leaks. Manually check pump is free to turn. Switch on electrical supply. Press on Central Heating switch 29
(Fig. 3)
to switch on the heating
mode. Press the + key 32
(Fig. 3)
to set the heating temperature to
maximum. Allow the pump to run for several minutes. Isolate the electrical supply. Drain boiler and check water filter for installation debris. Replace filter and recharge system.
Lighting the Boiler
Connect gas pressure gauge to test point 42 (Fig. 15). Turn on the gas supply and boiler gas tap 42 (Fig. 15). Ensure the electrical supply is on. Ensure all the external controls are calling for heat. Press on Central Heating switch 29
(Fig. 3)
to switch on heating
mode. Press on + key 32 (fig 3) to set heating temperature to maximum. The boiler will light. Allow the boiler to heat the system. Check the inlet gas pressure (working pressure) while boiler is operating in hot water mode. (Refer to technical data). Check the operation of the boiler controls and safety devices. (see separate servicing leaflet for details). Set the by-pass (refer to the paragraph Page 11). Re-flush the system to remove any dissolved oils and fluxes. Recharge the system pressure and introduce any water treatment as required.
Fig. 13
P
V
P
Electrical Connections
Commissioning and Testing
Page 11
11
7
By-Pass and Pump
The boiler is fitted with a pre-adjusted by pass. Although adjustment is not normally necessary, the by-pass can be reset by turning screw
D (Fig. 15) anti-clockwise to open the by-pass using
the chart
(Page 6, Fig. 5) for guidance. If used on a system with
thermostatic radiator valves, the flow rate with the thermostatic valves closed should be adjusted to at least 300 l/hr. The aforementioned chart indicates the residual head of the pump available for the system. The pump fitted on the boiler is a double speed model. (GV = High speed and PV = low speed). The speed setting is described in
Section 10. Speed selection is only
available in C.H. mode.
Post Commissioning
Ensure system pressure has been set correctly. Set all parameters of the boilers as shown in Section 9
ADJUSTMENTS AND SETTINGS
. Set boiler thermostat and controls. Set programmer to householder’s requirements. Set external controls. Ensure the Log Book is fully completed with your contact details and required readings and details of the installation.
Handing Over to the Householder
Demonstrate the lighting and operation of the boiler. Demonstrate how to maintain the system pressure. Demonstrate the operation and setting of the built-in clock. Explain the benefits of annual maintenance by a competent person. Explain how to register guarantee. Ensure the Householder countersigns the Log Book to confirm that these demonstrations have been carried out and understood.
T
T
1
2
Fig. 17
Fitting the casing
Remove the protecting film from the casing :
- Position the casing as shown
(Fig. 17)
- Slide down the casing and put the casing holes on the plastic pins
located on the top of the chassis
- Check the correct position of the casing onto the boiler
- Tighten the 4 screws located at the bottom as shown in (
Fig. 16).
8
A
A
A
A
Fig.16
b
a
r
0
1
3
4
Fig. 15
D
16
40
42
43
44
Commissioning and Testing (continued)
Fitting the Casing
Page 12
12
The boiler is delivered with pre-set values described in menus 3 and 4. All settings can be changed by the installer or a qualified person. To gain access to the setting keys, open the front door
P
(Fig. 18)
DISPLAY
1st digit
2nd digit
3rd digit
Menu key
Setting key
To gain access to the setting menus press both the and keys on the D.H.W. side for 5 seconds. (Fig. 18). Menu 1 is
displayed.
Changing the menu :
Press the Menu key ( key on C.H. side) (Fig.18). The menu number is displayed for 3 seconds. Press the menu key to change to the next menu.
Changing section in a menu (available only for menu 3 and 4) :
Press either the or key on the DHW side to change from one section to the previous or the next one in a menu.
Note : When you arrive at the last section of a menu, pressing the key will change to the the 1st section. When you
are at the first section, pressing the key will change to the last section of the menu.
Setting a parameter in a section:
Press the setting key ( key of the C.H. side) to enter the modification mode. The 2nd and 3rd digits will flash. Press the
or keys on the DHW side to select the correct value then press the Setting key to accept this modification and to exit
the setting mode. The 2nd and 3rd digits will stop flashing.
Recalling the basic configuration:
Select menu 3 or 4 then press both the
key on the DHW side and the setting key for more than 5 seconds. The digits
will flash
CM for a while to indicate that the operation is completed.
Erasing the default register :
Select menu 1 then press both the key DHW side and setting key for more than 5 seconds. The digits will flash CM
for a while to indicate that the operation is completed. Note: To exit from the setting mode, leave the boiler for
approx. 1 minute, the boiler will then revert to the user mode.
DISPLAY
Fig. 18
P
D.H.W keys
C.H keys
9
Adjustments and Settings
Page 13
13
5 ”
Menu - 1 - Default register
Records the last 10 defaults
Section Digit 1 Digits 2 and 3
Last default occured 0
code from 01 to 99
Last but one default occurred
1
code from 01 to 99
... ... code from 01 to 99
Last default occurred before the previous one 9
code from 01 to 99
DISPLAY
ACTION CONFIGURATION
once
x times
x times
Note -- is displayed if no default is recorded.
Menu - 2 - Boiler conditions
Indicates the conditions or the configurations of the boiler
Section Digit 1 Digits 2 and 3
Software version of display PCB 0
10 to 99
Flue type 2
1 : FF
variable speed
Room thermostat is calling for heat 3
0 : no
3
1 : yes
Theoretical position of the 3 way valve 4
0 : DHW
4
1 : CH
DHW flow temperature in Celsius degrees 5
from 00 to 99
TSS
®
temperature in Celsius degrees
6
from 00 to 99
CH flow temperature in Celsius degrees 7
from 00 to 99
Software version of main PCB 9
10 to 99
Page 14
14
Menu - 3 - Boiler options
DISPLAY
ACTION CONFIGURATION
Section Digit Digits
1 2 and 3
Under floor heating system 0 0 : no
1 : yes
DHW Delay 5
0 to 5 mn by step 0.5mn
(time before CH relights after a DHW cycle)
DHW flow swith Delay 6 0 to 20 1/10 seconds
(time before DHW flow detection to override pressure peak problem)
Factory
setting
Menu - 4 - Boiler settings
Section Digit Digits
1 2 and 3
Room thermostat operation 0 0 : Burner only
0 1 : Burner and pump
Pump speed 1 0 : High speed
1 1 : Low speed
Pump post circulation duration 2 0.0 min
From 0 to 5 minutes by step of 0.5 min. 2 0.5 min
2 1.0 min
2 5.0 min
Maximum Central Heating flow temperature 4 50°C
4 80°C
CH anti cycling delay 8 0.0 min
From 0 to 7 minutes by step of 0.5 min. 8 0.5 min
8 2.5 min
8 5.0 min
CH maximum output limitation Model 24 From step 0 (P. min.) 8 kW Value from
to step 10 (P. max.) 24 kW
9 0 to 10 Model 30 From step 0 (P. min.) 9 kW Value from
to step 10 (P. max.) 28 kW
9 0 to 10
Factory
setting
DISPLAY
ACTION CONFIGURATION
once
x times
once
x times
Page 15
15
Menu - 5 - Combustion rate control mode
X X
X X
DISPLAY
ACTION CONFIGURATION
wait 5 ”
Combustion rate control mode OFF
Switching on the combustion rate control mode. Central heating output reach the maximum power set in menu 4 section 9.
Central heating temperature is displayed in celsius degrees. The 3 dots indicate that the combustion rate control is ON at maximum output.
Switching the combustion rate down to minimum power.
Central heating temperature is displayed in celsius degrees. The dot indicates that the combustion rate control is ON at minimum output.
Switching on the combustion rate to maximum output set in menu 4 section 9.
Central heating temperature is displayed in celsius degrees. The 3 dots indicate that the combustion rate control is ON at maximum output.
X X
Switching off the combustion rate control mode.
press once
press once
press once
press once
Effect Display
Locking conditions of the combustion rate control mode :
- boiler in stand by mode
- D.H.W. draw off
- room thermostat is not calling for heat
- room thermostat is calling for heat but the maximum temperature is reached
- boiler in lockout mode
- after a reset or if the main supply fails
- end of the mode if the operator leaves menu 5
- after 15 minutes if there is no keys are pressed
Note :
As soon as the combustion rate control mode is on, the Central Heating and Domestic Hot Water keys become inactive.
press once
Page 16
16
CH heat output setting :
If you would like to change the setting of the C.H. heat output, please proceed as follows :
(Note: the factory setting is 18 kW and the following explanation refer to menu 4 section 9)
- Switch to the installer mode, press both the and keys on the DHW side for 5 seconds. The display shows :
-1- then 0•-- if there is no default in the default register.
- press the menu key 3 times (on CH side ) to gain access to menu
-4-,
The display shows :
-4- then the value set for section 0 ( 00
or 01 respectively Action on burner only or pump and burner)
- change to Section 9 (Adjustment of C.H. heat output). Press the key on the DHW side times. The display shows : (
906 which corresponds to 18 kW
which is the factory setting) 9 = section 9 06 = 18 kW
- press the setting key (on CH side) once, the 2nd and 3rd digits flash together. Then press the
or
key on the DHW side to change the C.H. heat output step between
00 and
10.
Press the setting key to confirm the value. The display stops flashing. The setting procedure is finished. To exit from the setting mode, leave the boiler for approx. 1 minute, the boiler will then revert to the user mode. After programming please close the door
P (Fig. 18)
1
Display
2
x 3
1
2
or
3
3
x 9
4
4
5 ”
9
Adjustments and Settings (continued)
Page 17
17
10
In case of problem, or when the boiler has to display a message, the display flashes 2 digits. Please refer to the table below to diagnose the default.
For default 01 and 03, the red indicator
38 will light (Fig.19)
38
Fig. 19
Overheat lock out
FAULT
Code
display Fault description Information on functioning
01 Overheat lock out 03 No flame detection 05 Anti freezing system, pump on 06 Anti freezing system, pump and burner on 07 No water circulation in primary circuit 08 No water in the primary circuit 09 Domestic Hot Water thermistor faulty (open circuit) 10
Domestic Hot Water thermistor faulty (short circuit) 11 Central Heating thermistor faulty (open circuit) 12 Central Heating thermistor faulty (open circuit) 18 Attempt to re ignite 20 Wiring problem 23 Fan speed too low 24
Fan control system defective 25 Thermistor cylinder open 26
Thermistor cylinder bypassed 29 Three way valve blocked in CH mode 31 Communication problem with the display PCB 32 Communication problem with the main PCB
If the boiler is not set for the required gas type, conversion kits are available. To convert the boiler, please use only Chaffoteaux & Maury parts and proceed as is mentioned in the instructions provided with the conversion kit.
11
Incorrect Function
Gas Conversion
Page 18
18
USER’S INSTRUCTIONS
Control panel (fig. 20)
16.- Pressure gauge
27.- Display
28.- Switch for Domestic Hot Water mode
29.- Green indicator Heating / Domestic Hot Water mode ON
30.- Key to reduce the Domestic Hot Water temperature
31.- Key to rise up the Domestic Hot Water temperature
32.- Switch for Central Heating (Winter) mode
33.- Green indicator Central Heating mode ON RESET Reset
button
34.- Key to decrease the Central Heating temperature
35.- Key to increase the Central Heating temperature
36.- Green indicator - Power ON
37.- Orange indicator - Burner ON
38.- Red indicator - Lock out / flame failure
39.- Reset button
12
Connecting bracket Taps shown in Open position (Fig. 21)
40 : Central Heating flow isolating valve 41 :
Domestic Hot Water outlet
42 : Gas service tap
43 : Water service tap 44 : Central Heating return isolating valve 46 : Central Heating pressure relief valve 48 : D.H.W. drain screw
STOP
+
+
+
+
Fig. 21
40 44
43
42
46
41
48
16
27
30
29
28
32
31
33
34
35
37
38
39
36
Fig. 20
Control Panel
Page 19
19
Switching on
1. Check that pressure in central heating system is above 0.7 bar and below 1.5 bar with the pressure gauge 16.
2. Check that the gas service tap is opened at the gasmeter and main power is on. Green indicator Power ON
36.
3. Open the gas tap
42 (Fig.21).
The boiler is now ready to use.
Attention ! If the boiler stays a long time without working, some air in the gas pipe can hinder the first lightings. (please refer to
Section 18 Incorrect Function).
Switching on the Central Heating
Press on key 32 , the green indicator 33 will light and the display will show the Heating
flow temperature.
Keys
34 and 35 allow the adjustment of the temperature required in the Central
Heating system dependent on the weather conditions.
• press to increase the temperature when the weather is cold
• press to decrease the temperature when the weather is fair
During the temperature setting operation the display will flash. If the room thermostat is calling for heat, a dot will be displayed at the bottom of the 3rd digit
Switching on the Domestic Hot Water
Press key 28 , the green indicator 29 will light :
If there is no water demand
the display will show the following graphic
In case of draw off
a square made of 4 digits will move clockwise on the display
Keys
30 and 31 allow the adjustment of the temperature required for the Domestic Hot Water flow. During the
temperature setting operation the display will flash.
Note : The configuration of the C.H. system can generate some gravity effect when the boiler is set in DHW mode only. It may result in a temperature rise of the heating pipes close to the boiler (or eventually a radiator). To avoid this it is possible during the summer period (Central Heating switched off) To close the Central Heating flow isolating tap
(40 Fig. 21). Don’t forget to
open it before switching on the Central Heating mode again.
13
Switching on the Domestic Hot water and Central Heating together
Press key 32 the green indicator 33 will light. Press key
28 the green indicator 29 will light.
If there is no water demand
the display will show the heating flow temperature
In case of draw off
a square made of 4 digits will move clockwise on the display
How to Use
Page 20
20
As with your car, your boiler will work more reliably and efficiently if regularly serviced. We recommend an annual service check. The service history of the appliance will be marked on the Log Book.
14
Turn off the boiler
- Press on key 32 and 28
,
to switch off both DHW and CH mode. The green indicators
33 and 29 will go out
- Switch off the main electrical supply
- Shut off the gas service tap
42 (Fig. 21)
Note :
In this condition, the anti-freeze system is inoperative.
Stand by mode A fixed digit at the centre of the display and the green indicator 36 on
Putting the boiler in stand by mode and anti freeze system. :
Press key 32 and 28
,
to switch off both DHW and C.H. mode. The green indicators
39 and 29 will stop. During the duration of the stand-by mode, an automatic anti-sticking system will switch on the pump for 1 minute and activate the 3 way valve every 23 hours. The stand-by mode will disable the anti-freeze function of the room thermostat (if fitted). To leave the room thermostat anti-freeze system operative, please leave the Central Heating mode on.
The boiler is equipped with an automatic anti-freeze system which is permanently on. If the Central Heating temperature falls below 7°C, the pump will start. If the Central Heating temperature falls below 4
°C, the pump and the burner will start.
13
15
The manufacturer`s guarantee is for 12 months from the date of purchase. The guarantee is voidable if the appliance is not installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an efficient after sales service, please return the guarantee registration card enclosed with the boiler with­out delay.
16
Pump anti-sticking device
When the boiler is switched on, an automatic anti-sticking system will switch on the pump for 1 minute and make a movement of the 3 way valve every 23 hours. This is a normal function.
Precaution to avoid freezing
We recommend you contact your installer or local service centre to take precautions adapted to your system.
• DHW system
Turn off the main cold water supply and drain the boiler :
- Open a hot water tap
- Unscrew the cold water inlet tail
- Drain the water out the boiler with the drain valve
48 (Fig. 21)
• C.H.
system
Chose one of the following solutions :
- 1) Drain the Central Heating system completely
- 2) Protect the Central Heating system with anti-freeze chemical products and verify periodically the concentration
- 3) Leave the Heating mode switched on and set the room thermostat to anti-freeze mode (between 5 and 10
°
C)
- 4) Leave your boiler in stand-by mode, the anti-freeze device will switch on the pump and the burner if necessary.
How to Use (continued)
Maintenance
Guarantee
Practical Information
Page 21
21
This appliance is suitable for Natural Gas or L.P.G. A gas conversion must be made by a competent person.
17
18
If these solutions do not cure the fault, call a qualified professional
Fault
The boiler doesn’t start
Red indicator lit
Noises in CH system
Radiators rise in temperature during summer season
Cause
No gas, no water or no electricity
Air in the gas pipe
Room thermostat switched off
Air presence in C.H. system or. Insufficient pressure
Gravity effect in the C.H. system
Solution
Control gas, water and electrical supply, fuses…
Follow the procedure in Section 8
Set up the room thermostat
Wait for a few minutes Press the reset button
39
(Fig.21)
the red led will go out and the boiler will attempt to re-light.
If red the indicator lights too frequently, please call your local service centre.
Purge the system of air and increase the system pressure (Section 8)
Close the Central Heating flow isolating valve
37. Don’t forget to open it again
before starting the heating.
Gas Conversion
Incorrect Function
Page 22
22
19
Model Calydra green 24 Calydra green 30
Appliance category
........................................... II 2H3P II 2H3P
Heat gross input C/H maxi ............................... 27.8 kW 94534 Btu/h 31.6 kW 107843 Btu/h
Heat gross input DHW maxi............................. 27.8 kW 94534 Btu/h 31.6 kW 107843 Btu/h
Heat output C/H 50
°/30° maxi.......................... 26 kW 88732 Btu/h 30 kW 102383 Btu/h
Heat output C/H 80°/60° maxi.......................... 24 kW 81907 Btu/h 28 kW 95557 Btu/h
Heat output DHW maxi .................................... 24 kW 81907 Bth/h 30 kW 102383 Btu/h
C/H operating temperature............................... 80°C max 25°C min 80°C max 25°C min
C/H circuit pressures Min operating................. 0.7 bar 10 Ib/in
2
0.7 bar 10 Ib/in
2
C/H circuit pressures Max operating................ 2.5 bar 36.3 Ib/in
2
2.5 bar 36.3 Ib/in
2
DHW flow rates 30°C ....................................... 12.5 l/min 2.77 gal/min 14.5 l 3.21 gal/min
DHW flow rates 35°C ...................................... 10.7 l/min 2.38 gal/min 12.4 l 2.76 gal/min
Cold water mains pressures Min operating...... 0.5 bar 7.25 Ib/in
2
0.5 bar 7.25 Ib/in
2
Cold water mains pressures Max operating..... 10 bar 145 Ib/in
2
10 bar 145 Ib/in
2
Flow limiter rate................................................ 8 l/min 10 l/min
Compartment ventilation .................................. not required not required
Natural gas G20
Gas rate C/H max ............................................ 2.64 m3/h 93 ft3/h 3,01 m3/h 106 ft3/h
Gas rate DHW max.......................................... 2.64 m
3
/h 93 ft3/h 3,01 m3/h 106 ft3/h
Gas rate C/H & DHW mini................................ 0.87 m
3
/h 31 ft3/h 1 m3/h 35 ft3/h
Gas valve restrictor diameter ........................... without without
Propane L.P.G G31
Gas rate C/H max. ........................................... 1.94 kg/h 36 ft3/h 2.21 kg/h 41 ft3/h
Gas rate DHW max.......................................... 1.94 kg/h 36 ft
3
/h 2.21 kg/h 41 ft3/h
Gas rate C/H & DHW mini................................ 0.64 kg/h 12 ft
3
/h 0.73 kg/h 13 ft3/h
Gas valve restrictor diameter ........................... 4.40 mm 4.8 mm
Safety discharge .............................................. 3 bar 43.5 Ib/in
2
3 bar 43.5 Ib/in
2
Expansion vessel - Pre-charge pressure ......... 0.7 bar 9.4Ib/in
2
0.7 bar 9.4Ib/in
2
Net capacity at 3 bar in liter.............................. 5.44 5.44
Adjustable by-pass Electrical characteristicis
Supply .............................................................. 230 v 230 v
Consumption.................................................... 150 w 150 w
Protection......................................................... IP 44 IP 44
Fuse F1............................................................ 2 A 2 A
Fuse F2............................................................ 1.25 A 1.25 A
Fuse F3............................................................ 0.315 A 0.315 A
Fuse F4
............................................................ 0.250 A 0.250 A
External controls .............................................. 24 v 24 v
Technical Data
Page 23
23
Page 24
1311238a - 09/2003
Chaffoteaux & Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
Manufacturer: Chaffoteaux & Maury - France
Commercial subsidiary: MTS
(GB) Limited
MTS
Building Hughenden Avenue High Wycombe Bucks HP13 5FT
Telephone:
(01494) 755600 Fax: (01494) 459775 Internet: www.chaffoteaux.co.uk E-mail:
info@uk.mtsgroup.com
Technical Support Help Line: 0870 241 8180 Customer Service Help Desk: 0870 600 9888
This appliance is suitable for Natural gas or LPG. A gas conversion must be made by a competent person.
Page 25
MAINTENANCE AND
SERVICE GUIDE
Fanned Flue Condensing
Combination Boiler
Heating and Storage Domestic Hot
Water with TSS
®
Dimensions
Flue types: C 13: - C 33 - C 53
54 54 54 54
JKLMN
I
88
JKLMN
232
235
32
Safety valve center line
All dimensions in mm
Outer case dimensions :
- Width : 440 (minimum space required 450)
- Height :
850
- Depth :
24 kw : 380
30 kW : 405
212
360
67
737
850
50
I Safety valve outlet J Heating flow K D.H.W. flow L Gas supply M Cold water inlet N Heating return
24 kW : 380 30 kW : 405
Technical data
Natural gas G20
Gas rate C.H. max .................. 2.64 m3/h 3.01 m3/h
Gas rate D.H.W. max .............. 2.64 m
3
/h 3.01 m3/h
Gas rate C.H. & D.H.W. min
...
0.87 m
3
/h
1 m
3
/h
Gas valve restrictor diameter
..
without
without
Propane L.P.G G31
Gas rate C.H. max.
.................
1.94 kg/h
2.21 kg/h
Gas rate D.H.W. max.
.............
1.94 kg/h
2.21 kg/h Gas rate C.H. & D.H.W. min ... 0.64 kg/h 0.73 kg/h Gas valve restrictor diameter
..
4.40 mm
4.8 mm
24 kW
30 kW
24 kW
30 kW
Heat gross input C.H. max ............................ 9.2-27.8 kW 10.4-31.6 kW
Heat gross input D.H.W. max
........................
9.2-27.8 kW 10.4-31.6 kW
Heat output C.H. 50°/30° max....................... 9-26 kW 10-30 kW
Heat output C.H. 80
°/60° max....................... 8-24 kW 9-28 kW
Heat output DHW maxi ................................. 8-24 kW 9-30 kW
C.H. operating temperature
...........................
80
°C max 80°C max
C.H. circuit pressures Min operating ............. 0.7 bar 0.7 bar
C.H. circuit pressures Max operating ............ 2.5 bar 2.5 bar
D.H.W. flow rates 30°C ................................. 12.5 l/min 14.5 l/min
D.H.W. flow rates 35°C ................................ 10.7 l/min 12.4 l/min
Cold water mains pressures Min operating
...
0.5 bar
0.5 bar Cold water mains pressures Max operating.. 10 bar 10 bar
Flow limiter rate............................................. 8 l/min 10 l/min
Safety discharge
........................................... 3 bar 3 bar
Expansion vessel - Pre-charge pressure
......
0.7 bar 0.7 bar
Net capacity at 3 bar in litres......................... 5.44 5.44
Supply
...........................................................
230 v
230 v
Consumption
.................................................
150 w
150 w
Protection ...................................................... IP 44 IP 44
Fuse F1/F2/F3/F4
.........................................
2 A/1.25 A/0.315 A/0.250 A
External controls ........................................... 24 v 24 v
Page 26
2
Pump and expansion vessel characteristics
Components location
Note : The system initial pressure should be over the following value :
System static height (in metre) + 0.7 = Initial pressure (in bar)
10
GV
F= high speed by-pass closed GVO = high speed by-pass open PV F= low speed by-pass closed PVO = low speed by-pass open
2
0 40 60 80 100 120
P
f
1
40 160 180 200 220 240
0
,7
0
,8
0
,9
1
,0
1,1
1,2
1,3
1,4
1,5
1
,6
1,7
1,8
1,9
2,0
80°C
70°C
60°C
50°C
40°C
2
60
P
ression à froid pour le circuit chauffage (en bar)
C liter
System capacity chart
Central heating initial pressure when cold (in bar)
0
4
3
2
1
5
6
100
200
800
700
600
500
400
300
900
1000
1100 l/h
mCE
Débit mini (robinets thermostatiques fermés)
Hauteur manométrique
GVF
GV
O
PVF
PVO
Pump head available
Minimum flow rate (with all heating thermostatic valves closed)
bar
0
1
3
4
42
43
44
41
40
45
46
47
1
2
3
4
5
6
8
11
12
13
14
7
15
10
9
16
1.- Steel chassis complete with expansion vessel
2.- Sealed chamber
3.-
Burner and heat exchanger assembly
4.- Air / gas connection
5.- 24 V modulating fan
6.- Gas valve
7.- Ignition electrode
8.- Ionisation probe
9.- Ignitor
10.- Combustion products manifold
11.- 24 V transformer
12.- Siphon
13.- Electrical box
14.- Pump
15.- Secondary heat exchanger
16.- Pressure gauge
17.- Three way valve
18.- Automatic air separator and automatic vent 19 - Central heating flowswitch
20.- Domestic hot water flowswitch
21.- Central heating control thermistor
22.- Hot water control thermistor
23.-
TSS Control thermistor
24 - Overheat sensor 25 - TSS ®(mini cylinder) 26 - DHW pressure relief valve.
40.- Central heating fl
ow isolating valve
41.- Domestic Hot Water outlet
42.- Gas service tap
43.- Water service tap
44.- Central heating return isolating valve
45.- Central heating pressure relief valve
46.- User’s guide
47.- Connecting tails (x 5)
48.- Adjustable by-pass 49 - Silencer
20
21
17
19
22
23
24
25
26
18
49
48
Page 27
3
FUNCTIONING
Control panel
38
33
27
32
30
28
37
31
36 39
3435
29
27 - Display
28.- Domestic Hot water switch
29.- Green indicator – Domestic Hot Water mode ON
30.- D.H.W. temperature reducing key
31.- D.H.W. temperature increasing key DHW mode indicator
32.- Central Heating switch
33.- Green indicator – Central Heating mode ON
34.- Central Heating temperature reducing key
35.- Central Heating temperature increasing key
36.- Green indicator – Power ON
37.- Orange indicator - Burner ON
38.- Red indicator - Lock out / flame failure
39.- Reset key
Switching on
1. Check that the pressure in the Central Heating system is above 0.7 bar and below 1.5 bar with the pressure gauge 16.
2. Check that the gas service tap is opened at the gas meter and the main power is on. Green indicator Power ON
36.
3. Open the gas tap
42.
The boiler is now ready to use.
Attention ! If the boiler remains off for a prolonged period of time, air may collect in the gas pipes and can hinder the boilers initial
attempts to light. (please refer to section 18 Incorrect Function)
Switching on the Central Heating
Press key 29 , the green indicator 33 will light and the display will show the Heating
flow temperature.
Keys
34 and 35 allow the adjustment of the temperature required in the Central Heating
system depending on the weather conditions.
• press
to increase temperature when the weather is cold
• press
to reduce temperature when the weather is fair
During the temperature setting operation the display will flash.
If the room thermostat is calling for heat, a dot will be displayed at the bottom of the 3rd digit
Page 28
4
Switching on the Domestic Hot water and Central Heating together
Press key 29 the green indicator 33 will light. Press key
28 the green indicator 32 will light.
If there is no water demand
the display will show the heating flow temperature
If the tank is heating up
the digit will move clockwise on the display
In case of draw off
a square made of 4 digits will move clockwise on the display
Turn off the boiler
- Press keys 29 and 28
,
to switch off both D.H.W. and C.H. mode. The green indicators
33 and 32 will stop
- Switch off the main electrical supply
- Shut off the gas service tap 42
Note :
In this condition, the anti-freeze system is inoperative
Stand by mode A fixed digit at the centre of the display and the green indicator 36 on
Putting the boiler in stand by mode and anti-freeze system. :
Press keys 29 and 28
,
to switch off both DHW and CH mode. The green indicators
33 and 32 will stop. During the duration of the stand-by mode, an automatic anti-sticking system will switch on the pump for 1 minute and make a movement of the 3 way valve every 23 hours. The stand-by mode will disable the anti-freeze function of the room thermostat (if fi
tted). To leave the room thermo
-
stat anti-freeze system operative, please leave the Central Heating mode on.
The boiler is equipped with an automatic anti-freeze system which is permanently on.
If the Central Heating temperature decreases below 7
°
C, the pump will start.
If the Central Heating temperature decreases below 4
°
C, the pump and the burner will start.
Switching on the Domestic Hot Water
Press key 28 , the green indicator 32 will light :
If there is no water demand
the display will show the following graphic
If the tank is heating up
the digit will move clockwise on the display
In case of draw off
a square made of 4 digits will move clockwise on the display
Keys
30 and 31 allow the adjustment of the temperature required for the Domestic Hot Water flow. During the tempera-
ture setting operation the display will flash.
Note : The configuration of the C.H. system can generate some gravity effect when the boiler is set in D.H.W. mode only. It may result in a temperature rise of the heating pipes close to the boiler (or eventually a radiator). To avoid this, it is possible to close dur­ing the summer period (Central Heating switched off) the heating flow isolating tap (
40). Don’t forget to open it before switching on
the Central Heating mode again.
Page 29
5
Domestic Hot Water Mode
To be able to supply hot water, the DHW mode should be ON. Press on key 28
, the green indicator 32 will light.
If there is no water demand, the display will show the following graphic
if the TSS®is cold, the burner will light immediately.
In case of draw off,
a square made of 4 digits will move
clockwise on the display
.
Keys
30 and 31 allow the adjust-
ment of the temperature required for D.H.W., fl
ow. During the temperature setting operation, the display will flash. When a tap or a shower is turned on, the flow of mains water, above 2 litres per min., will activate the DHW fl
ow switch
20 or if the TSS®thermistor is calling for heat and allow the 3 way valve
17 to
move to the DHW position. The pump can now circulate primary water heated by the main exchanger through the sec
­ondary heat exchanger and TSS®coil. The primary fl
ow switch checks that this flow rate is over 4lt./min. before allowing the lighting sequence to begin. The fan on the gas valve assembly starts and when the lighting speed is reached (detected by a hall effect sensor) the 2 safety solenoids open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected, the orange indicator led
34
will light and the regulation system will be able to adjust the gas rate regarding the heat load. If the TSS®thermistor is
calling for heat, the burner will stay in minimum output. If a fl
ame is not detect­ed, after 10 seconds, the security sole­noids close together and shut off the gas. The red lockout indicator led
38 will
light. Press the reset button to re-light the burner. For flow rates of less than 2 l/min, the domestic hot water temperature is con­trolled by TSS®thermistor
23 and heat-
ing thermistor 21. For fl
ow rates over 2 l/min , the domestic hot water tempera­ture is controlled by hot water control thermistor
22 and the central heating
control thermistor 21. This system antici
­pates the changes of temperature in the secondary heat exchanger and ensures accurate temperature regulation. When the tap is closed the burner may stay alight until the TSS®cylinder is up to temperature. Then the burner is extin­guished and the pump stops. The boiler will now stay in the hot water mode for 3 minutes to maintain temperature to ensure a fast response in the event of a subsequent hot water demand. Priority will be given to a demand for hot water or re-heating of the TSS®cylinder. This will interrupt the central heating for the duration of hot water supply.
Central Heating Mode
To be able to supply heating, the mode should be switched ON. Press key
29
, the green indicator 33 will light, and
the display will show the Heating Flow temperature.
Keys
34 and 35 allow the adjust-
ment of the temperature required for the
Central Heating system regarding the weather conditions. During the setting operation, the display will flash. When there is a demand for heating, (either from the room thermostat or the clock) the pump starts. If the boiler tem­perature control is calling for heat and the primary flow rate is over 4 lt./min., the central heating flow switch operates, allowing the ignition sequence to begin. The fan on the gas valve assembly starts and when the lighting speed is reached (detected by a hall effect sensor) the 2 safety solenoids open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a fl
ame
is detected, the orange indicator LED
37
will light and the regulation system will be able to adjust the gas rate regarding the heat load. If a flame is not detected, after 10 seconds, the security solenoids close together and shut off the gas. The red lockout indicator LED
38 will light.
Press the reset button to re-light the burner. The Central Heating flow temperature is controlled by the Central Heating control thermistor
21. The boiler has been
designed to minimise cycling and will not attempt to re-light for at least 3 min. after the boiler thermostat has been satisfied. When the room thermostat is satisfied , the burner will switch off and the pump will remain running for a further 3 min­utes before it too stops. Note: It is possible to override the 3 minute delay by pressing the Reset key
39.
Page 30
6
Lockout procedure
Flame disappearance : When the ionisation electrode 8 does not detect flame presence. The orange indi­cator led
37 extinguishes. A lighting
cycle starts. If a flame is not detected, before 10 seconds, the safety solenoids will close. The lockout red indicator
38
lights and the display shows the error
code. The pump runs and the 3 way valve
17 stays in its position. After a few
seconds, it will become possible to reset the boiler by pressing the reset key
39.
Overheat detection :
If an overheat (over 100°C) is detected in the primary circuit by the sensor
23, the
safety solenoids close and the fan stops.
The orange LED
37 extinguishes and the
pump remains running for 3 minutes. The reset will only be possible once the primary temperature has dropped below 76°C.
CALYDRA GREEN FUNCTIONAL DIAGRAM
17
1
8
1
9
20
21
23
2
4
26
27
28 29 30 31
33
32
34
36
37 38
3
9
1
2
3
4
5
6
7
8
9
1
0
11
12
13
1
4
15
16
22
25
3
5
1
7
18
19 2
0
2
1
23
24
26
27
2
8 29 30 31
33
3
2
34
36
37 38
39
1
2
3
4
5
6
7
8
9
10
11
12
1
3
14
15
1
6
22
25
35
Heating mode
Hot Water mode
DIAGRAM
ELECTRICAL WIRING
Page 31
7
5 ”
Menu - 1 - Default register
Record the last 10 defaults
Section Digit 1 Digit 2 and 3
Last default occured 0
code from 01 to 99
Last but one default occurred 1
code from 01 to 99
... ... code from 01 to 99
Last default occurred before the previous one 9
code from 01 to 99
Menu - 2 - Boiler conditions
Indicates the conditions or the configurations of the boiler
Section Digit 1 Digit 2 and 3
Software version of display PCB 0
10 to 99
Flue type 2
1 : FF
variable speed
Room thermostat is calling for heat 3
0 : no
3
1 : yes
Theoretical position of the 3 way valve 4
0 : DHW
4
1 : CH
DHW fl
ow temperature in Celsius degrees
5
from 00 to 99
TSS
®
temperature in Celsius degrees
6
from 00 to 99
CH flow temperature in Celsius degrees 7
from 00 to 99
Software version of main PCB
9
10 to 99
DISPLAY
ACTION CONFIGURATION
once
x times
x times
Note -- is displayed if no default is recorded.
Page 32
8
Menu - 3 - Boiler options
DISPLAY
ACTION CONFIGURATION
Section Digit Digit
1 2 and 3
Under floor heating system 0 0 : no
1 : yes
DHW Delay 5 0 to 5 mn by step 0.5mn
(time before CH relight after a DHW cycle)
DHW flow swith Delay 6 0 to 20 1/10 seconde
(time before DHW flow detection to override pressure peak problem)
Factory
setting
once
x times
Menu - 4 - Boiler settings
Section Digit Digit
1 2 and 3
Room thermostat operation 0 0 : Burner only
0 1 : Burner and pump
Pump speed 1 0 : High speed
1 1 : Low speed
Pump post circulation duration 2 0.0 min
From 0 to 5 minutes by step of 0.5 min. 2 0,5 min
2 1.0 min
2 5.0 min
Maximum Central Heating flow temperature 4 50°C
4 80°C
C.H. anti-cycling delay 8 0.0 min
From 0 to 7 minutes by step of 0.5 min. 8 0.5 min
8 2.5 min
8 5.0 min
C.H. maximum output limitation Model 24 From step 0 (P. min.) 8 kW
Value from
to step 10 (P. max.) 24 kW
9
0 to 10 Model 30 From step 0 (P. min.) 9 kW
Value from
to step 10 (P. max.) 28 kW
9
0 to 10
Factory
setting
DISPLAY
ACTION CONFIGURATION
once
x times
Page 33
9
Menu - 5 - Combustion rate control mode
X X
X X
DISPLAY
ACTION CONFIGURATION
wait 5 ”
Combustion rate control mode OFF
Switching on the combustion rate control mode. Central heating out put reaches the maximum power set in menu 4 section 9.
Central heating temperature is dis­played in celsius degrees. The 3 dots indicate that the combus­tion rate control is ON at maximum output.
Switching the combustion rate down to minimum power.
Central heating temperature is dis­played in celsius degrees. The dot indicates that the combus­tion rate control is ON at minimum output.
Switching on the combustion rate to maximum output set in menu 4 sec­tion 9.
Central heating temperature is dis­played in celsius degrees. The 3 dots indicate that the combus­tion rate control is ON at maximum output.
X X
Switching off the combustion rate control mode.
press once
press once
press once
press once
press once
Effect
Display
Locking conditions of the combustion rate control mode :
- boiler in stand by mode
- D.H.W. draw off
- room thermostat is not calling for heat
- room thermostat is calling for heat but the maximum temperature is reached
- boiler in lockout mode
- after a reset or if the main supply fails
- end of the mode if operator leave menu 5
- after 15 minutes if there is no actions on keyboard
Note :
As soon as the combustion rate control mode is on, Central Heating and Domestic Hot Water keys are inactive.
Page 34
10
C.H. heat output setting :
If you would like to change the setting of the C.H. heat output, please proceed as follows: (note: the factory setting is 18 kW and the following explanation refers to menu 4 section 9)
- Switch to installer mode, press key and
on DHW side for 5 sec­onds. The display shows :
-1- then 0•-- if there is no default in the default register.
- press 3 times on menu key
(on
C.H. side) to gain access to menu
-4-,
The display shows :
-4- then the value set for section 0 ( 00
or 01 respectively Action on burner only or pump and burner)
- change to section 9 (Adjustment of C.H. heat output). Press key on D.H.W. side 9 times. The display shows: 906 (which corresponds to the 18 kW which is the factory setting) 9 = section 9 06 = 18 kW
- press setting key (on CH side) once, the 2nd and 3rd digits flash together. Then press the
or key on the D.H.W. side to change the C.H. heat output step between
00 and
10.
Press the setting key to confirm the value. The display stops flashing. Setting procedure is fi
nished. To exit from setting mode, leave the boiler for approx. 1 minute, the comput­er will switch back to user mode. After programming please close the door
P.
1
Display
2
x 3
1
2
or
3
3
x 9
4
4
5 ”
Page 35
11
REGULATION
FLOW SWITCHES
Temperature regulation for both C.H., TSS®and D.H.W. circuits are con­trolled by 3 thermistors. The C.H. knob allows the adjustment of temperature between 35 and 85°C. The D.H.W. temperature is limited to 60°C. TSS®, D.H.W. and C.H. thermistors are identical and interchangeable.
Resistance value are
- 5000 Ω at 25 °C
- 2631
at 40°C
- 620 at 80°C
- 255 at 110°C
Flow in both D.H.W. and Heating cir­cuits are detected by 2 fl
ow switches. A piston with a magnet at the top operates a REED switch. The piston is lifted by flow rates listed below :
Flow rate threshold : D.H.W.
120 l/h ±20 l/h
C.H. 250 l/h ±20 l/h
ROUTINE SERVICING
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at reg­ulars intervals. The frequency of servicing will depend upon the particular installation condition and usage, but in general, once a year should be adequate.
It is the law that any service work must be carried out by a competent person such as your local Chaffoteaux Service Centre, British Gas or other CORGI registered personnel in accordance with the current Gas Safety (Installation and Use) regulation.
Attention ! the air/gas connection pipe between the gas valve and the burner should never open. The seal can be checked only in the factory.
The service schedule should include the following operations :
- Check the pressure in the system
- Check the correct operation of the appliance
- Check the correct operation of the gas controls
- Check the functions of safety controls
- Clean the electronic board of the fan located on the gas valve assembly and the different transformers in the sealed chamber.
- Check combustion chamber insulation panels for damage
- Check the lighting and ionisation electrodes condition
- Clean the burner (Never use a metallic brush as this can damage the stainless steel)
- Clean the heat exchanger (Never use a metallic brush as this can damage the stainless steel)
- Clean the siphon and pay attention to the acidity of its contents
- Check the correct seal of the drain system
- Clean gas and water filters
- Check expansion vessel charge pressure
- Clean and check the operation of the safety valve
- Check the correct seal of the flue system.
Additional procedures that may be necessary :
- Check the burner pressure and the gas fl
ow rates
- Check, clean or replace components as necessary
- Carry out combustion test utilising the test points in the fl
ue turret
Suggested sequence for servicing :
Before disconnecting or removing any part, isolate the gas and electricity supplies. Ensure that the appliance is cool, and take care about the condensate products content in the siphon which are acid.
(For detail, please see section on Parts Removal and Replacement)
Preliminary checks
- Remove outer case
- Check the system pressure is at least 0.7 bar cold
- Check the modulation of the gas valve in DHW mode by reducing progressively the flow rate at a tap.
- Check that the burner is extinguished fully when both solenoids are closed and fan is off.
- Test ionisation functions and check that lockout occurs by turning off gas tap.
- Whilst the boiler is operating, check the operation of the primary fl
ow switch by closing the Central Heating flow valve and by-
pass screw (turn clockwise ) noting the number of turns so that it may be reset correctly.
- Check the correct fl
ood of condensate into the siphon which is transparent.
Page 36
12
REMOVAL AND REPLACEMENT OF PARTS
Before removing the appliance case, isolate the gas and electrical supplies. Isolate the boiler from the system and drain before removing any component in the waterways. Ensure that the appli­ance is cool.
1. Outer Case
Remove the four screws A in the bottom of the case and lift free. When replacing,
carefully locate on lugs T on the top edge of the chassis.
2. Sealed chamber front panel
Unscrew the four self tapping screws securing the sealed chamber front panel and lift over the top corner locating lugs. Reassemble in reverse order.
3. Combustion Chamber front panel and air/gas connection
Carry out steps 1 and 2 as above. Unscrew the three screws securing the air/gas connection pipe onto the gas valve assembly. Disconnect the ionisa
­tion and lighting electrodes from their wiring. Unscrew the six nuts to release the combustion chamber front panel and pull the assembly towards you. Reassemble in reverse order.
4. Ionisation electrode
Carry out steps 1 and 2 as above. Disconnect the ionisation electrode from its wiring. Loosen the 2 screws and pull it out from the combustion chamber front panel. Replace the ionisation gasket provided. Reassemble in reverse order.
5. Lighting electrode
Carry out steps 1 and 2. Disconnect the lighting electrode from its wiring. Loosen the 2 screws and pull it out from the combustion chamber front panel. Replace the ionisation gasket provided. Reassemble in reverse order.
6. Burner
Carry out steps 1, 2 and 3. Remove the 4 Philips screw retaining the burner onto the combustion chamber. Pull it out with care to avoid any damage to the ceramic panel protecting the combustion cham­ber front panel. Replace the burner gas­ket. Reassemble in reverse order.
7. Gas vale assembly
Carry out steps 1 and 2 Unscrew the three screws securing the air/gas con­nection pipe onto the gas valve assem­bly. Disconnect the connectors from the gas solenoids and fan. Loosen the gas pipe nut. Unscrew the six nuts to release the combustion chamber front panel and pull the assembly towards you. Replace the gas filter before fitting the full assembly back into the boiler.
8. Fan assembly
Carry out all the operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. Reassemble in reverse order and replace all necessary gaskets.
9. Gas section
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. The venturi and the gas section can be separated by loosening the 2 screws located at the top of the gas valve. Replace all necessary gaskets before reassemble in reverse order.
10. Venturi in the gas section
Carry out all operations mentioned in step 7. Unscrew the three screws secur­ing the air/gas connection pipe onto the gas valve assembly. Separate the gas valve assembly and the venturi from the fan assembly by loosening the two hexagonal head screws. The venturi and the gas section can be separated by loosening the 2 screws located at the top of the gas valve. Replace all necessary gaskets before reassembling in reverse order.
11. Drain down
2 drain points are located on the boiler.
1 = DHW circuit drain point 2 = Heating circuit drain point
12. Water filters ( DHW and Heating) The DHW filter ensures a seal between the connecting bracket and the pipe to the DHW flow switch. Drain the boiler as in step 11. Unscrew the pipe nut and remove the clip on the hydraulic assy. Pull the pipe toward you and remove the water filter from its location. The C.H. filter is located in the right hydraulic assembly. Remove the return pipe as described previously and with­draw the filter. Reassemble in reverse order.
13. Flow switches
Drain boiler as in step 12. Disconnect the electrical plug, turn the top cover anti-clockwise, remove the O-ring and the brass piston. Reassemble in reverse order.
14. 3-Way valve
Drain boiler as in step 12. Remove the 3 clips on the 3 way valve. Remove the clip on the exchanger flow pipe. Pull the pipe down then pull it out of the 3 way valve. Disconnect the plug from the motor. Unscrew the nut on the pipe between the connecting bracket and the 3 way valve and pull it toward you. Rotate the 3 way valve body anti-clock­wise to unclip it from the left hydraulic assembly.
15. Secondary heat exchanger
Drain both circuits of the boiler as in step
12. Unscrew the 2 fixing screws D and remove the DHW exchanger from the front. Prior to reassembly, check that the 4 gaskets are correctly positioned. The heat exchanger is so designed that it
A
A
A
A
T
T
1
2
1
2
air separator
D
Page 37
13
cannot be remounted incorrectly.
16. Main heat exchanger
Carry out steps 1 and 2. Drain down the boiler as in step 12. Unscrew the three screws securing the air/gas connection pipe onto the gas valve assembly. Disconnect the ionisation and lighting electrodes from their wiring. Unscrew the six nuts to release the combustion chamber front panel and pull the assem­bly towards you. Undo the two clips of the pipes to the main exchanger and pull down the pipes. Unscrew the three screws located at the bottom, top left and the right with the retaining system to be able to pull the main heat exchanger towards you. Reassemble in reverse order taking care about the location of the gasket on the
fumes collector and replace all neces­sary gaskets.
17. Pump
Drain boiler as in step 12. Pivot the elec­tical box downwards. Open the electrical box cover removing the 2 screws. Remove the pump plug from the power board and the earth plug from the earth socket. Unscrew the nut
F of the return
pipe from the volute. Remove the clip
G
on the pump volute and pull the pump
toward you. Reassemble in reverse order.
18. Pressure relief valve
The pressure relief valve can be ser­viced from the front of the appliance. Drain the boiler first, undo the retaining
screw and pull out the valve. Reassemble in reverse order.
19. Thermistors
Drain the boiler as step 12. Disconnect
the plug, remove the retaining clip pull the thermistor out. Reassemble in reverse order.
22 = DHW thermistor 21 = Heating thermistor
20. Safety thermostat
Remove the casing as step 1 and hinge down the electrical box as step 5.
Disconnect the 2 cables, pull out the sensor with the clip (13). Reassemble in reverse order.
21. Spark generator
Carry out steps 1 and 2. Unplug the con­nector from the spark generator located on the right hand side of the main heat exchanger. Loosen the two screws to remove the igniter. Reassemble in reverse order.
22. Main control board
Carry out step 1 as above and hinge down the electrical box by pressing the retaining tabs
P on either side. Remove
wiring cover
C. Undo the 4 screws of the
electrical rear panel and remove it. Unplug all cables from the PCB, remove
the earth plug from the earth socket. Hang out the main PCB. Reassemble in
reverse order.
23. Display PCB
Carry out step 1 and hinge down electri
-
cal box by pressing the retaining tabs P on either side. Remove the pressure gauge clip. Rotate the electrical box back into the upper position. Undo the 2 screws retaining the front panel, put your two hands at the bottom of the front panel and pull it down to release it from the 2 clips. Hinge down again the electri­cal box. Undo the 4 screws of the electri­cal rear panel and remove it. Unplug the display board cables from the main PCB. Reassemble in reverse order.
24. Expansion vessel
Remove the casing as step 1 and drain the boiler as step 12 above. Unscrew the connecting tails nuts and lift out the boiler from the wall. Place it on a side on the floor. Remove the expansion vessel bracket retaining screws, disconnect the pipe from the vessel and pull it toward you. Reassemble in reverse order.
25. Pressure gauge
Carry out step 1 and drain the boiler as step 12. Hinge down the electrical box by pressing the retaining tabs
P on either
side. Press on the clip to remove it and pull it out. Remove the clip which holds the connection of the capillary onto the pump hose. Hang out the pressure gauge with its capillary. Reassemble in reverse order.
26. TSS
®
Drain both circuits of the boiler as in step 11. Unscrew all nuts from the con­necting bracket and remove the gas pipe from the gas section. Remove the main exchanger flow pipe to the 3 way valve. Remove the pump as in step 17. Unplug all thermistors, 3 way valve, flow switch­es. Unscrew the 2 retaining screws of the hydraulic section to the chassis. Pull the hydraulic assembly toward you. Reassemble in reverse order and check the gas section for soundness and the water circuits for leakages.
F
G
21
22
24
P
P
C
Page 38
14
FAULT FINDING CHART Part 1
Switch on the main electrical supply
Does the green LED
alight ?
- Check mains electrical
connection
- Check internal fuses
- Check connection between
the 2 PCBs
Replace control PCB or
display PCB
Replace control PCB
Replace DHW flow switch
Switch Domestic Hot Water
mode ON
Release pump rotor
Replace pump
Replace fan assembly
Replace heating fl
ow switch
Does the red LED
light ?
Does the display
show a - XX code ?
Does the fan run ?
Check heating fl
ow switch
Check voltage on
the fan
Check the 24 V at
the transformer
Press the reset button
Please refer to the list of error
codes and solve the problem
Does the pump run ?
Check that the
pump spins freely
Check voltage in the
pump electrical box
Replace control PCB
Could you see the
spark generation?
Does the spark
generator energize ?
Does the -24 error
display ?
Replace spark generator or
ignition electrods assembly
Replace transformer or the rel-
evant fuse
- Check pressure probes
or
- Check flue duct condition
or
- Replace pressure switch
Yes
Yes
Yes
Yes
No
No
No
No
Ok
Ok
No
Check or replace main or sec-
ondary heat exchangers. They
could be fully scaled.
Check flow in the
boiler primary circuit
Ok
No
Replace heating thermistor
Check heating
thermistor
Ok
No
No
No
No
Yes
Yes
Yes
No
No
No
Ok
Ok
Ok
Ok
means a test or a choice
means an action
means a group of actions
error code displayed
PLEASE CHECK THE FOLLOWING POINTS CAREFULLY
BEFORE GOING THROUGH THE FAULT FINDING CHART
-Gas pressure
-Electric mains
-Minimum water pressure in the heating circuit (over 0.8 bar)
-All isolating valves have been opened
-Boiler air vented
-Minimum domestic hot water flow of 2 l/min
-Check that the heating filter is clear.
- Remove the front panel of the sealed chamber
-7
Yes
Check or replace the DHW fow
switch
Draw off Domestic Hot Water
at a tap
Does the pump run ?
No
Check DHW flow
switch operation
No
No
Ok
-7
-7
-11
-12
Ok
Ok
No
No
-3
Wait for 4 seconds
-3
Error code Description
1 Overheating LockOut
3 No flame detection
5 Anti-frost mode on
6 Anti-frost mode on
7 No water circulation
8 Faulty water circulation in the primary circuit
9 DHW thermistor faulty, Opened circuit
10 DHW thermistor faulty, Short circuit
11 Central heating thermistor faulty, Opened circuit
12 Central heating thermistor faulty, Short circuit
18 Ignition test
20 Faulty connexion
23 Low speed fan
24 Faulty control functionning fan
25 TSS
®
thermistor faulty opened circuit
26 TSS
®
thermistor faulty short circuit
29 3 ways valve locked in Heating position
31 Error communication with EEPROM
32 Error communication with the main PCB
Page 39
15
FAULT FINDING CHART Part 2
Replace control PCB
Can you see the
ame on the burner ?
Replace gas section assembly
Do you feel air
drawing in at the air
Do the gas
solenoïds energise ?
Check that air inlet pipe, ven
-
turi, fan, air/gas pipe or burner
are free of dust and not blocked
Purge the gas pipe and press
on reset button
Does the DHW tem-
perature rise?
Does the burner still
alight ?
Does the red LED
light and -3 displayed ?
Does the orange
LED light ?
Replace control PCB
Replace DHW
thermistor
Replace control PCB
Replace display PCB or control the
connection between the 2 PCBs
- Adjust the DHW flow rate to
3 l/min at a tap.
- Wait until the temperature
becomes stable.
No
No
No
No
No
Yes
No
No
Does the orange
LED light ?
No
Yes
Replace the DHW heat
exchanger
Yes
Yes
Yes
Yes
No
-3
Replace display PCB or control the
connection between the 2 PCBs
Is the combution
chamber full of conden
-
sates ?
Yes
Check ionisation
probe
No
Ok
Drain and clean combustion cham-
ber, siphon and drain pipes
Yes
Replace the ionisation probe
No
Stop water draw off
Does DHW temper-
ature rise over 70
°
C ?
Check DHW ther-
mistor
No
Ok
- Press on DHW key to switch
off DHW mode.
- Press on CH key to switch on
CH mode and set CH tempera-
ture to maximum.
- Press the RESET button to
cancel the 3 min. delay.
- Ensure that external controls
are calling for heat.
Does the heating
outlet pipe temperature rise
?
Wait until the return pipe
become hot then reduce CH
temperature to minimum
Does the orange
LED light ?
Replace the 3 way valve
Replace control PCB
No
No
The boiler is OK
Yes
Does the heating
outlet pipe temperature
rise ?
Replace the 3 way valve
Yes
-29
No
Yes
Yes
Yes
- Switch off the boiler.
- Draw off DHW at a tap until the
temperature becomes cold.
- Close the tap
- Press on key 28
Does the orange
LED Alight
No
Check the TSS
®
thermistor
Ok
Replace the TSS
®
thermistor
No
25
26
Boiler is OK
Yes
Page 40
1311267d - 03/2003
SHORT LIST
110 ELECTRODE KIT 1309624
..
401 GAS VALVE (24 kW) 1308957
.
GAS VALVE (30 kW)
1310129
.
407 FAN ASSY 1307585
..
505 THREE-WAY VALVE E23510 81839
..
507 OVERHEAT THERMOSTAT 100°C 277783 1010572
..
510 THERMISTANCE 277834 1000733
..
514 WATER/WATER HEAT EXCHANGER 1302409
..
532 WATER THROTTLE 277846 81471
..
572 PUMP + AIR SEPARATOR 15/50 1301964
..
PUMP + AIR SEPARATOR 15/60 1303461
..
588 AIR SEPARATOR HEAD ASSEMBLY 1304608
..
607 IGNITER 1002105.20
..
615 PRINTED CIRCUIT BOARD 1310357
..
627 FUSE 250V 2A - TEMPORIZED 277883 1003456
..
628 FUSE 250V 1A - TEMPORIZED 1003634
..
629 FUSE 250V 1.25A - TEMPORIZED 277884 1003635
..
630 FUSE 250V 0.315A - TEMPORIZED 1307845
..
640 TRANSFORMER 1308149
..
805 PRESSURE GAUGE 1303158
..
938 PRESSURE RELIEF VALVE 1020933
..
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
Manf. date
CALYDRA GREEN 24
CALYDRA
GREEN 30
from to
110
407
401
532
505
640
514
510
507
R
4
1
R
37
R
31
R
3
0
R
2
9
J
7
C
3
8
R
102
1
+
+
+
+
+
+
+
+
8
C
68
R
2
8
S
T
2
F
T
1A
C
1
9
Z
11A
Z
1
0
A
Z
9A
Z
8
A
R
1
3
5
D
L1
T
H
1A
Z
7
A
Z
6A
R
132
U
5
Z
5A
Z
4A
T
E
R
R
E
-
1
T
H
1
R
4
8
R
2
7
R
9
1
R
8
9
R
4
7
C
83
C
78
C
80
C
7
9
S
T
1
R
87
Z
1
0
Z
9
Z
6
Z
7
Z
5
Z
4
Z
3
Z
2
Z
11
Z
1
U
3
U
10
U
9
U
7
U
6
U
4
T
R
1
T
H
2
T
E
R
R
E
T
8
T
7
T
5
T
4
T
3
R
4
6
T
2
T
6A
T
6
T
12
T
11
T
10
T
1
S
W
1
R
L8
R
L7A
R
L7
R
L6
R
L10
R
L5A
R
L5
R
L4A
R
L4
R
L
3
A
R
L3
R
L2A
R
L1A
R
L9
R
L1
R
A
D
1
R
118
R
114
R
113 R
111
R
112
R
1
1
0
R
1
0
9
R
108
R
107
R
106
R
9
R
105
R
101
R
1
0
0 R
9
9
R
9
8
R
97 R
96
R
8
R
95
R
94
R
93
R
9
2
R
90
R
88
R
6
6
R
6
5
R
6
4
R
62
R
7
R
58
R
59
R
57
R
2
4
R
52
R
53
R
51
R
6
R
5
0
R
4
9
R
55
R
5
R
2
2
R
7
9
R
78
R
77
R
4
5
R
4
3
R
4
4
R
4
2
R
4
R
39
R
3
8
R
35
R
34
R
3
R
33
R
32
R
19
R
1
8
R
2
R
1
6
R
2
0
R
2
1
R
15
R
1
4
R
2
6
R
25
R
2
3
R
13
R
131
R
1
3
0
C
82
C
8
1
T
14
T
13
D
4
5
D
4
4
R
L12
R
76
R
1
2
R
75
R
7
4
R
7
3
R
7
2
R
71
R
70
R
6
9
R
6
8
R
67
R
1
2
9
R
1
1
R
1
2
8
R
127
R
116
R
115
R
1
2
2 R
1
2
1
R
1
2
0
R
119
R
1
1
7
R
10
R
1
Q
1
P
2
P
1
M
O
V
1
L1
J
9
J
10A
J
8
J
6
J
4
J
3
J
2
J
1
F
T
1
F
3A
F
3
F
2A
F
2
F
1A
D
9 D
7
D
6
D
5
D
34
D
31
D
3
0
D
32
D
4
D
42
D
41
D
40
D
39
D
3
8 D
3
7
D
3
6
A
D
36
D
3
3
D
43
D
3
D
29
D
2
8
D
2
7
D
26
D
23
D
2
5
D
2
4
D
22
D
2
1
D
20
D
2
D
19
D
1
8
D
17
D
1
6
D
15
D
1
4
D
13
D
12
D
11
D
1
C
T
P
1
C
8
C
13
C
49
R
54
R
L11
C
3
4
C
35
C
3
2
C
7
J
5
C 5 3
C
6
C
52
C
51
C
77
C
76
C
75
C
74
C
72 C
71 C
70 C
69
C
5
C
50
C
48
C
47
C
46
C
45
C
4
4
C
43
C
42
C
6
7
C
4
C
6
6
C
6
5
C
6
4
C
6
3
C
6
2
C
61
C
60
C
59
C
22
C
56
C
55
C
54
C
3
3
C
31
C
41
C
39
C
3
7
C
2
C
3
6
C
29
C
3
0
C
28
C
27
C
26
C
2
5
C
1
0
C
11
C
9
C
3
C
24
C
23
C
2
1
C
20
C
18
C
17
C
1
6
C
1
5
C
14
C
12
C
1
K
VD
M/
A
VI
TESSE
K
1
1
1
1
1
EXT
1
P4
P3
P2
P1
BU
S
1
PR
O
G
TA
K
K
KC
D
1
K
K
2
3
0
V
+
5
V
TR
CO
M
REP
8
1
2
3
4
0 
N
628
627
629 630
607
805
938
615
588
572
Manufacturer: Chaffoteaux & Maury - France
Commercial subsidiary: MTS
(GB) Limited
MTS
Building Hughenden Avenue High Wycombe Bucks HP13 5FT
Telephone: (01494) 755600 Fax: (01494) 459775 Internet:
www.chaffoteaux.co.uk
E-mail:
info@uk.mtsgroup.com
Technical Support Help Line: 0870 241 8180 Customer Service Help Desk:
0870 600 9888
Chaffoteaux & Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
Page 41
CALYDRA GREEN
DOMESTIC BOILERS
CALYDRA GREEN 24 CALYDRA GREEN 30
B
CALYDRA GREEN
1
Réf. 82026.28c - 07/03 - GB
Page 42
2
B
CALYDRA GREEN
82072.44
200 FAN 300 SEALED CASE
100 BURNER
213
117
112
114
116
314
311
305 228
304
313
212
222
109 115
108
102
110
104
227
107
231
315
229
118
121
123 116
122 119
119
205
303
101
304
309
639
308
202
313
230 203
Page 43
B
CALYDRA GREEN
3
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
100 BURNER ASSEMBLY
101 BURNER 1306074
.
BURNER 61309327
.
102 DOOR ASSY 24KW 1308492
.
DOOR ASSY 30KW 61308491
.
104 GASKET D:110-75-2 1309658
..
107 FIXING BRACKET 1306181
.
FIXING BRACKET 61309237
.
108 FIXING BRACKET 1306180
.
FIXING BRACKET 61309238
.
109 HOOKING BRACKET
1306448
..
110 ELECTRODES 1309624
..
112 WASHER D:65-59-2.6 1307588
..
114 TRAP 1306078
..
115 TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
..
116 SILICONE TUBE D: 21x2.5 L: 1M 277636 81265.02
..
117 DUCT FIRST SECTION 1306026
..
118 CLIP 1306070
..
119 SCREW HX M 5-12 277797 1010131
..
121 "O" RING D: 17.76-1.78 1308092
..
122 SCREW D: 5-14
61308782
..
123 BARBED NIPLE 90 1309373
..
200 FAN ASSEMBLY
202
FLUE ADAPTOR 61309242
..
203 GASKET D:66-58.4-9 61310088
..
205
GASKET D:66.6 1306029
..
212 GASKET 1300262
..
213
PLUG KIT 1306698
..
222 OUTGOING FLUE BOX 1306028
..
227
TAPPING SCREW CBLSX D:4.2-12.5 1010847
..
228 TAPPING SCREW CBLSX D: 6.3-13 277865 1010648
..
229
TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
..
230 GASKET (/ Flue bend turret) 1300258
..
231 GASKET D:129.4 1306030
..
300 SEALED CASE
303
TOP PANEL BOX 1305438
..
304 FOAM SEAL 12.5x5 L: 2.5M 264425 81273
..
305
CASE 1310355
..
308 SPIRE CLIP 366787 57488
..
309 BASE - BOX 1307613
..
311
CASE COVER E23478 81851
.
CASE COVER 61400102
.
313 TAPPING SCREW CBLSX D:4.2-12.5 1010847
..
314 GROMMET 277819 1010109
..
315
GROMMET 366877 39017
..
24 30
Page 44
4
B
CALYDRA GREEN
82072.45
400 GAS SECTION
407
411
401
404
436
412
406
418
408
442 403
610
410
404
Page 45
B
CALYDRA GREEN
5
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
400 GAS SECTION
401 GAS SECTION ASSY 61307584 GZ20
.
GAS SECTION ASSY 61310129 GZ20
.
403 SCREW CLXS M 4-30 61310333
..
404 SCREW HX M 5-12 277797 1010131
..
406 GASKET 1308335
..
407 FAN ASSY 1307585
..
408 SCREW CLSX M 5-12 1308327
..
410 GASKET 1306072
..
411 GASKET 1307587
..
412 SILENCER
61310121
..
418 CONNECTION 1012649
..
436 "O" RING D: 22-2.6 E23502 21061.40
..
442 SCREW CBLSX M 4-12 1015222
..
24 30
Page 46
575
101
516
6
B
CALYDRA GREEN
82072.46
530
599
598
530
530
504 529
530
502
522
571 511
526
501
575
586
591 537
585
510
504
502
561
504
531
502
595
592 593
543
516
518
404
582
521
526
586
507
511
569
584
506
504
502
590
520
597 596
553 552
589
583
587
542
594 522
540
564
504
404
504
500 HYDRAULIC BLOCK
572
574
588
567
805
571
573
550
558
6006
532
6007
6002
514
505
6003
510
570
548
551
548
418
535
101
Page 47
B
CALYDRA GREEN
7
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
500 HYDRAULIC BLOCK
501 TUBE-EXCHAN TO 3-WAY VALVE 61310175
..
502 HEATING CONNECTION PIN E23507 1002399
..
504 "O" RING D: 17-4 E00604 24164.51
..
505 THREE-WAY VALVE E23510 81839
..
506 CLIP 277782 1010050
..
507 OVERHEAT THERMOSTAT 100C 277783 1010572
..
510 THERMISTOR TEMP. SENSOR 277834 1000733
..
511 TEMPERATURE SENSOR CLIP 277835 1002083
..
514 WATER / WATER HEAT EXCHANGER 1302409
..
516 CLIP
1307589
..
518 TOP INTERFACE SYSTEM E23512 1014228
..
520 FLEXIBLE PIPE E23513 1012952
..
521 TAPPING SCREW CBLSX D: 6.3-13 277865 1010648
..
522 CLIP 277841 1010005
..
526 "O" RING D: 8.9-2.7 E00605 1009834.14
..
529 HEATING FLOW TUBE E23515 1014220
..
530 SHEET GASKET D: 24-17-1.5 265389 61855.19
..
531 HYDRAULIC PLATE E23516 1014214
..
532 WATER THROTTLE 277846 81471
..
535 TAP BODY
1012963
..
537 "O" RING D: 13.6-2.7 366048 24164.18
..
540
SPINDLE E23519 1012946
..
542 CLIP 277851 79845
..
543
TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
..
548 SHEET GASKET D: 24-18.2-1.5 265091 22835.01
..
550
HEATING RETURN TUBE E23520 1014218
..
551 GAS TUBE 1307590
.
GAS TUBE
61309556
.
552 PLUG E23521 1015245
..
553
"O" RING D: 8.9-1.9 264374 24164.13
..
558 PUMP LEAD (2 SPEEDS) 1306995
..
561
BOTTOM INTERFACE SYSTEM E23522 1014172
..
564 "O" RING D: 24.6-3.6 1009834.30
..
565 HEATING FILTER 1305560
..
567 CLIP 366887 30898.03
..
569 LIP SEAL 277860 1002249
..
570
HEATING RETURN TUBE 61310176
..
571 "O" RING D: 16-1.9 E00615 1009833.37
..
572
PUMP + AIR SEPARATOR 15/50 1301964
..
PUMP + AIR SEPARATOR 15/60 1303461
..
573 CAPACITOR E00616 1000652.10
..
574
GASKET KIT 1304618
..
575 "O" RING D: 17.86-2.62 1308091
..
582 CYLINDER 6L E23527 1012790
..
583 LINKING TUBE E23528 1012808
..
584
NUT 1012886
..
585 PIN 1012909.02
..
586 CLIP E23531 1012983
..
587 WASHER D: 12.5-5.2-5 E23532 1015757
..
588 AIR SEPARATOR HEAD ASSEMBLY 1304608
..
589 STOPPED WATER THROTTLE BODY E23540 1012743
..
590 COLD WATER TUBE E23542 1014983
..
591
PLUG E23554 1002490
..
592
WASHER D: 12-6.2-1.2 366808 7059.03
..
593 NUT H M 6-1 366758 26501.03
..
594 "O" RING D: 2.7-10.5 E23557 1009834.15
..
595 SHEET GASKET D: 10.5-6.2-1.5 E23563 22831.07
..
596 PRESSURE RELIEF VALVE DRAIN 61014984
..
597 SHEET GASKET D: 13.9-10.4-1.5 E23568 61853.02
..
598 TUBE PVC D: 9x12 L: 1M E00634 81266
..
599 CONNECTION 1020242
..
24 30
Page 48
8
B
CALYDRA GREEN
82072.47
600 ELECTRICAL BOX
609 602
614
612
602
604
632
602
610
610
639
631
607
640
605
617
615
618
621
622 623
613
605
601
110
641
C
6
8
R67
F
T
1
A
C
1
9
Z
1
1
A
Z
1
0
A
Z
9
A
R
9
9
C
3
7
D
L
1
T
H
1
A
R
9
8
C36
R
1
3
2
R85
S
W
2
S
W
1
U
5
R
16
R
15
R
14
C
8
4
C
8
3
R6a
Z
4A
T
H
1
R78
R
66
R76
R100
R
1
3
4
R
8
8
Z
1
0
Z
9
Z
6
R
7
a
Z
5
Z
4
Z
3
Z
1
1
Z
1
U
1
0
U
9
U
8
U
7
U
6
U
2
U
4
T
8
T
7
T
5
T
4
T
3
T
2
T
6
R
5
1
R
L
8
R
L
10
R
L
5
A
R
L
5
R
L
4
A
R
L
4
R
L
3
A
R
L
3
R
1
08
R
12
4
R
1
23
R
122
R
121
R119
R118
R
11
6
R
1
17
R
113
R
9
R
106
R
107
R
9
7
R96
R95 R94
R
9
3
R
9
2
R
8
R
9
1
R
9
0
R
8
9
R79
R77
R
75
R54
R
5
3
R
5
2
R
5
0
R
7
R
4
9
R
4
8
R
4
6
R
4
7
R
4
5
R
65
R40
R
4
1
R
3
9
R6
R38
R
3
7
R
4
3
R87
R86
R84
R83
R82
R
5
R81
R80
R
7
0
R
72
R30
R
4
R
2
7
R26
R
24
R
2
3
R22
R
3
R
2
1
R
2
0
R
1
4
0
R
1
3
7
T
H
4
R
2
R
1
3
R
1
2
R
7
1
R
1
1
R
1
1
5
R
1
2
7
C
8
2
C81
T
14
T
1
3
R
136
U
1
1
R
64
R
1
0
R
63
R
61
R62
R
60
R
5
9
R
126
R
12
5
R120
R114
R
1
1
0
R
11
1
R109
R
1
Q
1
M
O
V
1
L
1
J
9
J6
J
4
J
3
J
2
F
T
1
F
3
F
2
F
1
D
9
D
8
D
7
D5
D
3
4
D
3
1
D
3
0
D
3
2
D
4
D
3
9
D
3
8
D
3
7
D36A
D
36
D
3
3
D
3
D
2
9
D
2
8
D
2
7
D
2
6
D
2
3
D
2
5
D
2
4
D
2
2
D
2
1
D
2
0
D
2
D
1
9
D18
D
1
3
D
1
2
D
1
1
D
1
0
D
1
C
T
P
1
+
C
8
C
4
9
R42
J
1
1
C
3
4
+
C
7
J5
C
53
C
6
C52
C
5
1
C
76
C
7
5
C
74
C
7
2
C
7
1
C
7
0
C
6
9
C
5
C
4
8
C
4
7
C
4
6
+
C
4
5
C44
+
C
4
3
+
C
4
2
C67
C
4
C66
C65
C64
C63
C62
C61
C58
C57
C
2
2
C
5
6
C
54
C
3
3
C
3
1
C
3
9
C
4
0
C
2
C
2
7
C
26
C
2
5
C
1
0
C
11
C
9
C
3
C
24
C
2
3
C
2
1
C
2
0
C
1
8
C
1
7
C
1
6
C
1
5
C
1
4
C
1
2
U
1
2
M/A
VITESSE
1
1
1
1
BUS
1
1
.
2
3
1
1
1
2
2
1
S
W
2
S
W
1
3
.
2
3
O
F
F
O
N
11
12
2
2
.
2
3
O
F
F
O
N
11
1
2
T
Y
P
E
D
E
C
H
A
U
D
IE
R
E
P
O
S
I
T
I
O
N
S
W
1
,
S
W
2
1
S
W
2
2
1
S
W
2
S
W
1
1
T1,25A
1
S
W
1
T315m
A
230V
MOTEUR
610
610
558
558
610
638
628
627
629
630
611
634
Page 49
B
CALYDRA GREEN
9
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
600 ELECTRICAL BOX
601 ELECTRICAL BOX 1311319
..
602 SCREW FX90 L:16 1020510
..
604 INSTRUCTIONS SUPPORT 1309315
..
605 TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
..
607 IGNITER 379075 1002105.20
..
609 CONNECTOR COVER 277874 1010014
..
610 FAN-IGNITER CABLE 1309837
..
611 WIRE ASSEMBLY 61309454
..
612 CONNECTION STRIP 277877 1010152
..
613 TAPPING SCREW CBLSX L:10
1020509
..
614 ELECTRICAL BOX COVER 277879 1010007
..
615 PRINTED CIRCUIT BOARDS 1310357
..
617 ELECTRIC BOX PLATE 277882 1010006
..
618 PLUG E00269 1011316
..
621 TRANSMITTER OF LEDS 1306012
..
622 CONTROL PANEL 1306019
..
623 SIGHT GLASS 1303830
..
627 FUSE 250V 2A - TEMPORIZED 277883 1003456
..
628 FUSE 250V 1A - TEMPORIZED 1003634
..
629 FUSE 250V 1.25A - TEMPORIZED
277884 1003635
..
630 FUSE 250V 0.315A - TEMPORIZED 1307845
..
631
EARTH WIRE 1309966
..
632 CLOSURE PLATE 1304599
..
634
FEEDER 1308031
..
638 CABLE THREE WAY VALVE 1305893
..
639
ELECTRODE CABLE 1308086
..
640 TRANSFORMER 1308149
..
641
SPACER 61308945
.
24 30
Page 50
10
B
CALYDRA GREEN
82072.48
700 CHASSIS 800 FRONT CASE
714
713
712
709
706
703
704
706
701
705
801
711 805
710
806
813
802
815
807
Page 51
B
CALYDRA GREEN
11
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
700 CHASSIS
701 TOP STAY PLATE 277864 1010029
..
703 EXPANSION VESSEL 366979 56676.06
..
704 CHASSIS 277866 1010028
.
CHASSIS 61310119
.
705 EXPANSION VESSEL AIR HOSE 277867 1010170
..
706 TAPPING SCREW CBLSX D: 6.3-19 1014516
..
709 FLEXIBLE PIPE KIT E23589 81824
..
710 CLIP 277848 1002406
..
711 "O" RING D: 5.7-1.9 E00621 1009834.10
..
712 SHEET GASKET D: 12-8.1-2
1308868
..
713 CLIP 277841 1010005
..
714 "O" RING D: 8.9-2.7 E00605 1009834.14
..
800 FRONT CASE
801 TAPPING SCREW CBLSX D: 4.2-9.5 277792 1010125
..
802 CASE E00622 1010016
.
CASE 61309874
.
805 PRESSURE GAUGE 1303158
..
806 DOOR 1306020
..
807 SERIGRA. STRIP (WITHOUT PROG.)
61310207
..
813 SPACER 1015797
..
815
SCREW FX90 L:16 1020510
..
24 30
Page 52
12
B
CALYDRA GREEN
82072.49
900 JIG PLATE & PIPE FITTING
907
908 909
901
902 904 906903 905
927
931
939 940
941
937
910
943
939
921
922 925
919
918917
920
918
939
920
917
918
936
923
947
938
Page 53
B
CALYDRA GREEN
13
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
900 JIG PLATE & PIPE FITTING
901 PREFABRICATION E00627 1012448
..
902 WATER FLOW SERVICE TAP 1020388
..
903 HOT WATER CONNECTION 1020916
..
904 GAS SERVICE TAP 1020389
..
905 COLD WATER TAP 1302612
..
906 WATER RETURN SERVICE TAP 1312122
..
907 HOOKING BRACKET E23593 1012457
..
908 WASHER D: 14.2-7.2-1.2 366764 5369.03
..
909 WOOD SCREW 366017 25617.03
..
910 BOTTOM STAY PLATE
E00630 1011683
..
917 SHEET GASKET D: 24-17-1.5 265389 61855.19
..
918 LOCK NUT 277909 31140
..
919 FLOW REGUL. 7L/MIN(DARK GREEN) 277911 1002775.07
..
FLOW REGULATORE 8L/MIN (WHITE) E23605 1002775.08
..
FLOW REGULATOR 10L/MIN (BLUE) E00631 1002775.10
..
FLOW REGULATORE 12L/MIN (RED) E23606 1002775.12
..
FLOW REGULATOR 14L/MIN (PINK) 277911 1002775.14
..
FLOW REGUL 15L/MIN(PALE GREEN) E23607 1002775.15
..
920 LOCK NUT H 1/2" 277910 31139
..
921 SHEET GASKET D: 24-18.2-1.5
265091 22835.01
..
922 HAND LEVER BLACK 1302611
..
923
HAND LEVER YELLOW 1302610
..
925 DRAIN SCREW ASSY 266043 81028
..
927
PRESSURE TEST POINT SCREW 1016378
..
931 GRUB SCREW 1304327
..
936
"O" RING D: 13.6-2.7 E00633 1009834.18
..
937 TUBE PVC D: 13x17 L: 1M 277912 81266.02
..
938
PRESSURE RELIEF VALVE 1020933
..
939 WASHER D: 18.4-12.2-1.5 265432 61855.14
..
940
NUT 1/2" THICK: 10 262584 20747.38
..
941 CONNECTING PIPE 277913 1010375
..
943
ACCESSORY KIT 1309329
..
947 CLIP E23616 1012927
..
24 30
Page 54
D80-125VERTICAL FLUE KIT
14
B
CALYDRA GREEN
82072.50
1005
1000 FLUE CONNECTION
1001
1002
D80-80
V./HORIZONTAL FLUE KIT
DOUBLE-FLOW FLUE KIT
D60-100
D60-100
HORIZONTAL FLUE KIT
1003
1011
1018
1012
1014
1013
1017
1016
1015
1011
1011
1015
1020
1011
1022 1019
Page 55
B
CALYDRA GREEN
15
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
1000 FLUE CONNECTION
1001 HORZ. FLUE KIT D60-100 L:800 1309947
..
1002 V./HORIZONTAL FLUE KIT D60-100 1309694
..
1003 VERTICAL FLUE KIT D80-125 1309693
..
1005 DOUBLE-FLOW FLUE KIT D80-80 1309715
..
1011 GASKET (/ Flue bend turret) 1300258
..
1012 FLUE BEND 90 1309692
..
1016 SEALING RING TRIM 366995 62079
..
1017 HORZ. TERMINAL D:60/100 L:800 61310156
..
1018 SCREW CBLXS D:5-16 61310811
..
24 30
Page 56
16
82072.51
B
CALYDRA GREEN
5000 ACCESSORIES
5040
6000 MAINTENANCE
5020
5022
5021
5023
5030 5033 5035
ACOUSTIC
KIT
5045
6002 6003
Simulating
Descaling
6006
Spanner
6007
5002
GZ20 > GZ31
5015
5014
Connection
FIRST FITTING
Connection
REPLACEMENT
Page 57
B
CALYDRA GREEN
17
DescriptionKey N°
Manf. Pt. N°
Type
G.C N°
CALYDRA GREEN
CALYDRA GREEN
Manf. date
from to
5000 ACCESSORIES
5002 CONVERSION KIT G20 > G31 1311759
.
CONVERSION KIT G20 > G31 1311760
.
5014 CONNECTION - FIRST FITTING 277922 1010429
..
5015 CONNECT. ELM E00648 1010182
..
CONNECT. VAILLANT E00649 1010183
..
CONNECT. CELTIC E00650 1010517
..
CONNECT. JUNKER E00652 1011063
..
CONNECT. SAULNIER DUVAL FF 1303293
..
5020 SLEEVE 1018789
.
SLEEVE 61309802
.
5021 EXTREMITY CHOCK DRAUG DIV SIDE 1014400
.
EXTREMITY CHOCK DRAUG DIV SIDE 61311303
.
5022 CHOCK - DRAUGHT DIVERTER SIDE E00655 1010080
.
CHOCK - DRAUGHT DIVERTER SIDE 61309804
.
5023 SIDE CHOCK E00656 1010081
..
5030 JIG PLATE 1309325
..
5033 ROD PLATE E23679 1010932
..
5035 SOUNDPROOFING KIT 1305676
..
5040 USERS' INSTRUCTIONS 1311238
..
5045 WALL SPACER KIT
E23683 1016144
..
6000
MAINTENANCE
6002 DESCALING INTERFACE/WATER EXCH 1011075
..
6003
SIMULATING BOX 3 WAY VALVE E23686 1012597
..
6006 SPANNER 1302650
..
6007
STOPPED W/THROT. CONNECTOR KIT 1306970
..
24 30
Page 58
18
Loading...