Centurion Auto-Mate, Maxi-Mate Installation Manual

Page 1
Latest Revision: 08.03.04
Document Ref.: 1068.D.01.0052_4
SWING GATE OPERATORS
INSTALLATION
MANUAL
A
uo Mae
t
Ma i
-
e
x
M
at
Page 2
Page 3
11
INTRODUCTION
BASIC KIT
RECOMMENDED TOOLS
SITE PREPARATION
- TABLE 1 - CRITICAL DIMENSIONS
- TABLE 2 - CABLE REQUIREMENTS
MOUNTING CONTROL BOX
STANDARD PEDESTAL POSITIONING
- TABLE 3 - STANDARD PEDESTAL POSITIONING
OUTWARD SWING PEDESTAL POSITIONING
WALL MOUNT PEDESTAL
ELECTRICAL CONNECTIONS
COMMISSIONING
COLLISION SENSING ADJUSTMENT
SIMPLIFIED PEDESTAL MOUNTING POSITION
Page 2
Page 2
Page 3
Page 3
Page 3
Page 4
Page 5
Page 6
Page 6 - 13
Page 8
Page 14
Page 14 - 17
Page 18 - 26
Page 27 - 31
Page 32
TT
T
able of Contents
SS
S
wing Gate Installation Manual
Page 4
22
B
B
asic Kit
I
ntroduction
A CENTURION GATE AUTOMATION system is a quality product designed to give many years of trouble free service.
This MANUAL has been compiled to assist you, the customer, with a trouble free installation.
The swing gate kit comprises of components shown in the identification list below.
PLEASE READ THE INSTRUCTIONS CAREFULLY
PLUG IN
TRANSFORMER
ELECTRONICS
ENCLOSURES
FASTENERS PEDESTALS
BATTERIES
M10 x 20
SET SCREW
M8 x 40 SET SCREW
WALL MOUNT PEDESTAL
SHORT PEDESTAL STANDARD PEDESTAL
M12 CAP SCREW
M8 NYLOC
NUTS
M8 FLAT WASHER
PADLOCK
35AH
BATTERY
++
--
6.5AH
BATTERY
CP77 CONTROLLER
CP87 SINGLE CONTROLLER
MAXI-MATE GEARBOX
AUTO-MATE GEARBOX
UT
O
-
M
A
T
A
E
X
E
A
A
M
I-
T
M
CONNECTING ARMSGEARBOXES
LONG CONNECTING ARM
SHORT CONNECTING ARM
CP6 BATTERY
ENCLOSURE
GATE BRACKET
ADAPTOR PIECE
BALL JOINT
DRIVE ARMS with ADAPTOR PIECE
500mm DRIVE ARM
400mm DRIVE ARM
250mm DRIVE ARM
CP7
I
Page 5
R
C
Recommended Tools
Critical Dimensions
33
MASONRY BITS - 6mm
20mm FOR WALL MOUNT PEDESTAL
STEEL BITS 8,5mm/4,0mm/5,0mm
SPANNERS
22mm 19mm 17mm
2 x 13mm
10mm
SCREW DRIVERS
3,5mm FLAT
No 1 PHILLIPS
CRIMPING TOOL
AND PIN LUGS
PLIERS/SIDE
CUTTER
HAMMER
G-CLAMP
ELECTRIC
DRILLING MACHINE
TAPE MEASURE
No 8 ALLEN KEY
HACKSAW
SOLDERING IRON
WELDING MACHINE
LEVEL
PICKSPADE
PLUMB BOB
CRITICAL DIMENSIONS
STANDARD DRIVE ARM
LENGTHS AVAILABLE
(See page 11, Fig. 2)
ABSOLUTE MINIMUM FOR "A" IS: - 220mm FOR AUTO-MATE
- 260mm FOR MAXI-MATE
250mm 400mm 500mm
FOR:
Standard
Maxi-Mate
or single
Auto-Mate
kits
FOR:
Standard
double
Auto-Mate
kits
FOR:
Limited
space or
outward opening
applications
AA
400
315 150 430 365 530 515
240 635 560 790 760
AA AABB BB BB
RECOMMENDED
(See page 10)
MIN. NORMAL
OPERATION
(See page 11, Fig. 1)
B
"B" MUST BE
LESS THAN
VALUE
SHOWN IN
TABLE
DRIVE
ARM
HINGE
CENTRE
LINE
A
- DIMENSIONS
- MUNICIPAL BYLAWS
- WATER, SEWERAGE, ELECTRICAL CABLES
CHECK:
}
"A" MUST BE GREATER
THAN VALUE
SHOWN IN TABLE
Page 6
C
Cable Requirements
44
A MASTER MOTOR (MOTOR) and G.P. IN CONDUIT OR NORSK
INTERCOM/CABTYRE/ G.P. IN CONDUIT
INTERCOM/CABTYRE/ G.P. IN CONDUIT
INTERCOM/CABTYRE/ G.P. IN CONDUIT INTERCOM/CABTYRE/ G.P. IN CONDUIT
INTERCOM/CABTYRE/ G.P. IN CONDUIT
INTERCOM IN CONDUIT
CABTYRE OR G.P. IN CONDUIT
CABTYRE OR G.P. IN CONDUIT
INTERCOM IN CONDUIT
NORSK IN CONDUIT OR S.W.A.
NORSK IN CONDUIT OR S.W.A.
3 CORE CABTYRE IN CONDUIT
G.P. IN CONDUIT OR NORSK
3 2,5
2,5 X
X
X
X
X
X
X
X
0,2
0,2
0,5
0,2
0,5
1,5
0,5
1,5
0,2
0,2
0,2
0,2
3
3
3
2 + E
2 + E
n
n
1 + 6
2
2 + E
2
2
2
3
3
MASTER MOTOR (LIMIT SWITCH)
SLAVE MOTOR (MOTOR) and
SLAVE MOTOR (LIMIT SWITCH)
EITHER: 220V AC SUPPLY CABLE
OR: 15V AC TRANSFORMER SECONDARY
INTERCOM IN HOUSE & STATUS SIGNALLING
INTERCOM-CONTROL BOX TO GOOSENECK
PILLAR LIGHTS
REMOTE RECEIVER
PEDESTRIAN KEYSWITCH
INFRA RED BEAM
SOLENOID STRIKE (not shown)
SOLAR PANEL (not shown)
G.P. = GENERAL PURPOSE HOUSE WIRING OR PANEL FLEX
S.W.A. = STEEL WIRE ARMOURED
n1 = CONSULT INTERCOM SUPPLIER FOR REQUIRED NO. OF CORES
n2 = CONSULT INTERCOM SUPPLIER FOR REQUIRED NO. OF CORES
= FOR OPTIMUM LIGHTNING PROTECTION USE SCREENED CABLE EARTHED AT BOTH ENDS
= CABLE TYPE IS MINIMUM RECOMMENDATION
TABLE 2 - CABLE REQUIREMENTS
B
C
D
E
F
G
H
I
J
K
NO
NO OF OPTIONAL CABLE TYPE
SIZE
mm
CORES
DESCRIPTION
2
INTERCOM TO HOUSE
220V MAINS
F
G
A
B
D
E
I
C
**
H
INTERCOM
GOOSENECK
Page 7
THESE TABLES CAN BE USED AS A QUICK
ALTERNATIVE TO THE SETUP PROCEDURES
SHOWN ON PAGES 6 - 10
A
B
140mm
SEE NOTE 4
C
HINGE POINT
GATE BRACKET
GATE CLOSED
GATE OPEN
40mm
(See notes)
PILLAR
PEDESTAL
DRIVE ARM
OUTLINE OF
GEARBOX
COVER
GATE OPEN
ANGLE
1. All dimensions shown in millimetres.
2. All dimensions referenced to hinge point.
3. Gate thickness assumed to be 40mm.
4. Distance depends on pillar size. Check
carefully before installation.
NOTES:
O
GATE OPEN ANGLE = 110
ARM LENGTH
250mm ARM
400mm ARM
500mm ARM
A
360
540
670
B
265
525
700
C
305
488
610
O
GATE OPEN ANGLE = 90
ARM LENGTH
250mm ARM
400mm ARM
500mm ARM
A
235
340
410
B
385
700
915
C
354
566
707
S
Simplified Pedestal Mounting Position
55
Page 8
S
Standard Pedestal Positioning (Gate Inward Opening)
66
(See Page 14 for Wall Mount Pedestals)
M
Mounting Control Box
Page 9
XX
S2
XX
XX
S1
Standard Pedestal Positioning cont'd .....
77
xx
zz
S1S1
xx
S2S2
STEP 3
- MEASURE DISTANCE, Z, BETWEEN S1 & S2 IN mm.
- USING Z, LOOK UP GATE OPENING ANGLE AND DIMENSION C FOR SIZE OF DRIVE ARM SUPPLIED (See Table Overleaf).
STEP 2
- SWING GATE TO DESIRED OPEN POSITION (70 - 120 DEGREES).
- MAKE SECOND MARK "S2" ON THE GROUND.
e.g. SAY Z IS MEASURED AS 1482mm CLOSEST Z VALUE IN TABLE = 1486mm DIMENSION "C" FOR A 400mm DRIVE ARM IS THEREFORE 538mm.
Page 10
Z
(IN mm)
(mm) (Degrees) (mm) (mm) (mm)
250mm LONG 400mm LONG 500mm LONG
DIMENSION C FOR DRIVE ARMS:-
GATE OPENING
ANGLE
1147 1161 1176 1190 1204 1218 1231 1245 1259 1272 1286 1299 1312 1325 1338 1351 1364 1377 1389 1402 1414 1426 1439 1451 1463 1475 1486 1498 1509 1521 1532 1543 1554 1565 1576 1587 1597 1608 1618 1628 1638 1648 1658 1668 1677 1687 1696 1705 1714 1723 1732
436 431 425 420 415 411 406 402 397 393 389 385 381 377 374 370 367 363 360 357 354 351 348 345 342 339 336 334 331 329 326 324 322 319 317 315 313 311 309 307 305 303 302 300 298 296 295 293 292 290 289
697 689 681 672 665 657 650 643 636 629 622 616 610 604 598 592 587 581 576 571 566 561 556 551 547 543 538 534 530 526 522 518 515 511 508 504 501 498 494 491 488 485 482 480 477 474 472 469 467 464 462
872 861 851 841 831 821 812 803 795 786 778 770 762 755 747 740 733 726 720 713 707 701 695 689 684 678 673 668 663 658 653 648 643 639 635 630 626 622 618 614 610 607 603 600 596 593 590 586 583 580 577
70.0
71.0
72.0
73.0
74.0
75.0
76.0
77.0
78.0
79.0
80.0
81.0
82.0
83.0
84.0
85.0
86.0
87.0
88.0
89.0
90.0
91.0
92.0
93.0
94.0
95.0
96.0
97.0
98.0
99.0
100.0
101.0
102.0
103.0
104.0
105.0
106.0
107.0
108.0
109.0
110.0
111.0
112.0
113.0
114.0
115.0
116.0
117.0
118.0
119.0
120.0
88
T
T
able 3 - Pedestal Positioning
- SELECT VALUE OF Z IN TABLE CLOSEST TO THAT MEASURED
(Gate Inward Opening)
250mm - Limited space or outward opening applications 400mm - Standard double Auto-Mate kits 500mm - Standard Maxi-Mate or single Auto-Mate kits
DRIVE ARM LENGTH
APPLICATION
Page 11
XX
S4
CC
GATE BRACKET
GATE SHOWN
CLOSED
CC
HINGE
CENTRELINE
Standard Pedestal Positioning cont'd.....
99
XX
XX
SETUP LINE
S4
S5
STEP 4
- MARK "S4" ON GROUND (GATE CLOSED).
- WELD OR BOLT BRACKET TO GATE.
- POSITION GATE BRACKET AT DIMENSION "C"
STEP 5
- MAKE MARK "S5" ON GROUND.
- SWING GATE TO OPEN POSITION, SAME POSITION AS STEP 2.
- DRAW SETUP LINE THROUGH "S4" & "S5" AND EXTEND AWAY FROM DRIVEWAY.
Positioning Gate Bracket
Marking Setup Line
Page 12
60mm
WALL
PLAN VIEW
PILLAR
"S5"
SETUP LINE
"S4"
RECOMMENDED POSITION
DRIVE ARM END JUST
TOUCHES GATE
(See Step 7)
Standard Pedestal Positioning cont'd.....
Locate position of pedestal
1010
GATE SHOWN
OPEN
60mm
GATE BRACKET
SETUP
LINE
DRIVE ARM
S5
- PEDESTALS CAN BE MOUNTED "ANYWHERE" ALONG A LINE 60mm AWAY FROM SETUP LINE TOWARDS THE PILLAR.
STEP 6
RECOMMENDED LOCATION OF PEDESTAL
- LIE DRIVE ARM OVER SETUP LINE SUCH THAT END OF DRIVE ARM LIES DIRECTLY OVER MARK "S5".
- PEDESTAL POSITION LIES 60mm CLOSER TO THE WALL FROM CENTRE LINE OF DRIVE ARM MOUNTING HOLE.
STEP 7
PEDESTAL
ISOMETRIC VIEW
Page 13
"S4"
Figure 1
Figure 2
+/- 180mm
"S5"
NOTE: GEARBOX JUST CLEARS
THE GATE IN THE FULLY OPEN
POSITION
PILLAR
W
A L L
Standard Pedestal Positioning cont'd.....
PILLAR
"S4"
"S5"
SEE SITE PREPARATION
DRAWING (PAGE 3)
1111
CONSULT CENTURION FOR
CORRECT POSITION OF
PEDESTAL
PLAN VIEW OF GEARBOX & PEDESTAL
POSITIONING
NOTE:
THIS SHOWS AN ALTERNATIVE POSITION OF THE PEDESTAL IF SPACE IS LIMITED.
NOTE:
ALTERNATIVE POSITION WHEN THERE IS ABSOLUTE MINIMUM SPACE BETWEEN WALL AND GATE IN OPEN POSITION.
LIMITED SPACE
PLAN VIEW OF GEARBOX & PEDESTAL POSITIONING (CONSULT CENTURION)
ABSOLUTE LIMIT
(NOT RECOMMENDED)
W
A L L
Page 14
GATE SHOWN
CLOSED
1212
STEPS 9 & 10
- WHEN CONCRETE IS DRY, BOLT GEARBOX ONTO PEDESTAL WITH 4 BOLTS M10 x 20, AND WASHERS.
- LOOSELY FIT DRIVE ARM TO OUTPUT SHAFT
(USING M12 x 25 CAP SCREW) .
- CUT CONNECTING ARM TO FIT INSIDE ADAPTOR PIECE, DEEPER THAN THE FIXING HOLE.
CONNECTING
ARM
DRIVE ARM
FIXING HOLE
M12 x 25 CAP SCREW
M10 x 20
BOLTS
MOUNT GEARBOX ONTO
PEDESTAL AND BOLT
INTO PLACE
108 - 120mm
CONCRETE
BEND OUT
TABS
CONDUIT FOR MOTOR & LIMIT SWITCH CABLES
500mm
MIN
300mm
MIN
Standard Pedestal Positioning cont'd.....
- DIG HOLE FOR PEDESTAL.
- INSTALL CONDUIT TO PEDESTAL FROM CONTROL BOX.
- CONCRETE PEDESTAL IN PLACE AS SHOWN.
- ENSURE PEDESTAL IS VERTICAL.
STEP 8
GATE BRACKET
CONTROL
BOX
CUT HERE
Install pedestal and determine correct height.
Mount gearbox and connecting hardware
LEVEL
CONTROL
BOX
Page 15
NUT
FIXING
HOLE
M8 x 40 SET SCREW
ADAPTOR
PIECE
CONNECTING
ARM
SETUP
LINE
SETUP
LINE
ROTATE CONNECTING ARMS
AND ADAPTOR PIECES TO GET
GATE END POINTS TO ALIGN
MOTOR
ALIGN GATE END POINTS
180
o
180
o
THE CORRECT ARC
FOR LHS DRIVE ARM
THE CORRECT ARC
FOR RHS DRIVE ARM
CONNECTING
ARM
ADAPTOR PIECE
BALL JOINT
LOCK NUT
DRIVE ARM
MOTOR
1313
STEP 12
- ALIGN GATE END POINTS.
- LOCK ADAPTOR PIECE TO BALL JOINT WITH LOCK NUTS.
STEP 11
- DRILL FIXING HOLE HORIZONTALLY THROUGH CONNECTING ARM (8,5mm).
- FIT BOLT AND NUT.
Mount gearbox and connecting hardware cont'd....
Page 16
O
Outward Swing, Pedestal Positioning
GATE OPENS
OUTWARDS
Positioning Gate Bracket
W
Wall Mount Pedestals
(Gate Inward Opening)
GATE BRACKET
HINGE
CENTRE LINE
743mm
84mm
743mm
O
NOTE: DIMENSIONS CRITICAL
- GATE OPENS OUTWARDS BUT MOTOR REMAINS INSIDE PROPERTY.
- 250mm DRIVE ARM MUST BE USED.
- LONG CONNECTING ARM REQUIRED.
DRIVE ARM
SHOWN IN GATE
CLOSED POSITION
1414
STEP 4
- AFFIX GATE BRACKET TO GATE USING DIMENSION "C" FROM HINGE CENTRE LINE.
- MARK S4 ON GROUND USING A PLUMB BOB.
STEPS 1 - 3
TO DETERMINE GATE OPENING ANGLE AND DIMENSION "C" FOR POSITIONING THE GATE BRACKET, REFER TO PAGE 6-7, STEPS 1-3
Page 17
XX
S5
XX
SETUP LINE
GATE SHOWN
OPEN
PLUMB BOB
S4
Wall Mount Pedestal cont'd .....
1515
GATE SHOWN
OPEN
HORIZONTAL
LINE "L1"
100mm
STEP 6
- MARK HORIZONTAL LINE SHOWN ON PILLAR 100mm BELOW TOP OF GATE BRACKET.
STEP 5
- MARK POINT "S5" ON THE GROUND USING A PLUMB BOB.
Marking Set-up Line
Determine Height of Pedestal
Page 18
CONTROL
BOX
STEP 8
- INSTALL CABLE.
- BOLT WALL BRACKET TO WALL USING AT LEAST M12 RAWL BOLTS.
GATE SHOWN
CLOSED
1616
GATE SHOWN
CLOSED
- MOVE WALL BRACKET LEFT OR RIGHT ALONG LINE L1 UNTIL PLUM-BOB IS 60mm BACK FROM SETUP LINE.
STEP 7
90
L1L1
o
USE M12
RAWLBOLTS
97mm
74.5mm
60mm
PLUMB-BOB
59mm
L1
T
N
SE
U
P
LI E
S4
S5
XX
XX
Wall Mount Pedestal cont'd .....
PILLAR
O
90
60mm
GATE OPEN
GATE CLOSED
E
TUP LI
N
S E
PLAN VIEW
Locate Pedestal
Mount Pedestal
Page 19
Wall Mount Pedestal cont'd .....
1717
GATE SHOWN
CLOSED
FIXING HOLE
FOR STEPS 11 - 12 REFER TO "STANDARD PEDESTAL POSITIONING" ON PAGE 13.
CUT HERE
STEP 10
- BOLT GEARBOX IN PLACE.
- LOOSELY FIT DRIVE ARM TO OUTPUT SHAFT.
- CUT CONNECTING ARM TO FIT INSIDE ADAPTOR PIECE, DEEPER THAN FIXING HOLE.
CONTROL
BOX
STEP 9
- BOLT PEDESTAL ADAPTOR ON TO WALL BRACKET
BOLT
PEDESTAL
ADAPTOR
WALL BRACKET
FLAT WASHER
SPRING WASHER
NUT
Mount Gearbox and Connecting Hardware
Page 20
1818
E
Electrical Connections
N.B.
Two controllers are available. Select the correct controller drawing from those shown below:
CP77 CONTROLLER -
DOUBLE/SINGLE SWING CONTROLLER WITH MULTIPLE FEATURES
PEDESTRIAN INPUT
NORMAL TRIGGER
PILLAR LIGHT OVER-RIDE
REMOTE STATUS LED
INFRA-RED BEAM
MASTER LIMIT SW OPEN
MASTER LIMIT SW CLOSED
SLAVE LIMIT SW OPEN
SLAVE LIMIT SW CLOSED
+ 12V DC, 3A AUX SUPPLY
SOLENOID STRIKE
15V AC SUPPLY
15V AC SUPPLY
AUTO CLOSE CONTROL
FREE EXIT LOOP
HOLIDAY LOCKOUT
SLAVE MOTOR
BATTERY
MASTER MOTOR
SIGNAL COMMONS (NEG)
PILLAR LIGHT CONTACT
(Potential Free)
1
2
3
4
5
6
7
8
9
10
11 121314
15
16
+
-
}}
}}
}}
}}
}}
A
7 953
1
4
6 8
1210
14
16
11 13 15
2
C
C
D
E
F
G
I
B
H
CP77 CONTROL CARD
CP87 CONTROLLER -
PEDESTRIAN
COMMON (NEG)
LIMIT SWITCH (OPEN)
LIMIT SWITCH (CLOSE)
+ 12V 1A AUX SUPPLY
15V AC INPUT
15V AC INPUT
COMMON (NEG)
TRIGGER
MOTOR
BATTERY
1
2
3
4
5
6
7
8
9
}
}
7 953
4
6 8
CP87 CONTROL CARD
SINGLE MOTOR CONTROLLER WITH BASIC FEATURES
+
--
A B
C
D
1
2
Page 21
Electrical Connections cont'd.....
RADIO CONNECTIONS - (REFER TO CENTURION FOR CODING DETAILS)
MOTOR AND LIMIT SWITCH CONNECTIONS
1919
TO
E
AU MAT
TO
E
AU MAT
MOTOR 2
(SLAVE)
MOTOR 1
(MASTER)
(ORANGE)
(PURPLE)
(BLACK)
(GREEN)
(BLACK)
EARTH WIRE
Motor 1
Motor 1
(ORANGE)
(PURPLE)
(BLACK)
(GREEN)
(BLACK)
EARTH WIRE
Motor 2
0,2mm CABLE
2
Motor 2
9
10
4 5 6
C D
D
C C E11 12H
I
EARTH
2,5mm CABLE
CP77
CP87
EARTH N/A N/A N/A N/A N/A N/A
EARTH
FOR EARTHING DETAILS REFER TO PAGE 26.
2
CONTROLLER
MODEL
MOTOR FUSE RATING
AUTO-MATE MAXI-MATE
8A Slow Blow 16A Slow Blow
0,2mm² CABLE
121
CONTROLLER
MODEL
RECEIVER
FOR DETAILS OF SETTING CODE
SWITCHES REFER TO
RADIO MANUFACTURER
CODE SWITCHES
CP77
CP87
13
7
C
2
3
3
+12V
COM
TRG
COM
COM
+12V
OPTIONAL EXTERNAL LINK
IF NOT INTERNALLY FITTED
+12V
NC
COM
POWER
SUPPLY
COM
NC
LEARN
NO CODING
SWITCHES
ERASE
NO
-+
12-24V
AC/DC
NO
+12V
1
COM
2
3
4 5
CODE SWITCHES
TYPICAL
TRANSMITTER
(REMOTE)
TX
TYPICAL RADIO RECEIVER
CENTURION
SMART
RX
EXAMPLE 2
EXAMPLE 1
TRG
TRG
+12V
}}
}}
}}
Page 22
Electrical Connections cont'd.....
2020
NOTE:
- Many different intercom types are available.
- Only signals necessary to interface intercom to Centurion's controller are shown.
- Consult intercom manufacturer for full wiring diagrams.
0,5mm
CABLE
INTERCOM
2
CONTROLLER
MODEL
CP77
CP87
C
2
3
3
NEG
TRG
INTERCOM CONNECTIONS
NOTE: SOLENOID LOCK, OR MAGNET, IS USED TYPICALLY ON SINGLE SWING GATES
OPTION 1
SOLENOID
LOCK
MAGNETIC
LOCK
OR
OPTION 2
0,5mm
CABLE
2
CONTROLLER
MODEL
CP77
MAGNET SUPPLY
(Could be +12V from gate motor battery
depending on type of magnetic lock used)
14 13
N/AN/A
CP87
SOLENOID LOCK/MAGNETIC LOCK
SOL
+12V
SOL
12V RELAY
COIL
COM
N.C.
SOL
+12V
+12V
N
S
}}
Page 23
Electrical Connections cont'd.....
CONTROL BOX
0,2mm² CABLE
0,2mm² CABLE
SIGNAL COMMON
CONTROLLER
MODEL
CONTROLLER
MODEL
INFRA-RED BEAM
CP77
CP77
13
1 C
1
2
N/A N/A N/A
C 8
CP87
CP87
+12V
NEG
N/O
INFRA-RED BEAMS
PEDESTRIAN KEYSWITCH
2121
SPRING RETURN SWITCH
NEG
PED
BEAM
N/O
+12V
LINK
NOTE - TYPICAL SAFETY BEAM IS SHOWN. REFER TO MANUFACTURER FOR DETAILS
NOTE - THE INFRA-RED BEAM INPUT ONTO THE STANDARD CP77 IS NORMALLY OPEN
12V DC
POWER
SUPPLY
POWER
SUPPLY
N/C
N/O
NEG
TRANSMITTER RECEIVER
common
Page 24
Electrical Connections Cont'd.....
PROCON LD100 INDUCTIVE LOOP DETECTOR IS SHOWN BELOW. MODIFY WIRING IF OTHER MAKES OF DETECTORS ARE USED.
0,2mm CABLE
0,2mm CABLE
2
2
CONTROLLER
MODEL
2 POSITION SWITCH
CONTROLLER
MODEL
CP77
CP77
13
4 C
N/AN/A
N/A N/A N/A
2 C
CP87
CP87
HOLIDAY LOCKOUT
OR
OR
FREE EXIT LOOP -
2222
CONTROL BOX
UNDERGROUND
LOOP
PUSHBUTTON
KEYPAD
1
4
7 8 9
5 6
2 3
+12V
NEG
COM
N.O.
NEG
LOCK
LATCH TYPE
RADIO
RECEIVER
RELAY MUST HAVE
LATCHING CONTACT
3
TWISTED WIRES FROM LOOP
+
-
12V AC/DC
SUPPLY
11 PIN PLUG
IN RELAY BASE
OUT
NEG
**
5
2
1
6
8
7
LD101 - 12V DC
DETECTOR
UNIT
LOCK
NEG
+12V
**
ELECTRONICS
**
LOCK
NEG
+12V
ELECTRONICS
NEG
COM
N.O.
Page 25
Electrical Connections cont'd.....
AUTO CLOSE
TOGGLE
TO MOTOR
CONTROLLER
SIGNAL COMMON
TOGGLE SWITCH IS
SHOWN FITTED TO
AN INTERCOM
TELEPHONE
0,2mm CABLE
2
CONTROLLER
MODEL
CP77
N/A N/A
5
C
CP87
REMOTE AUTOCLOSE SWITCH
2323
A/C
NEG
SIGNAL COMMON
0,2mm² CABLE
CONTROLLER
MODEL
CP77
CP87
7
N/A
C
N/A
NEG
LED
FITTED TO HANDSET BASE SEPARATELY
STATUS LED
ANODE +
CATHODE -
GATE STATUS LED INDICATION
BATTERY LOW 3 FLASHES / 2 sec
GATE CLOSED OFF
GATE OPENING SLOW EVEN FLASH
MAINS LOSS 2 FLASHES / 2 sec
COLLISION
DETECTION
4 FLASHES / 2 sec
GATE OPEN ON
GATE CLOSING FAST EVEN FLASH
Page 26
Electrical Connections cont'd.....
TO MOTOR
CONTROLLER
SIGNAL COMMON
TOGGLE SWITCH IS
SHOWN FITTED TO
AN INTERCOM
TELEPHONE
0,2mm CABLE
0,5mm NORSK
CABLE OR (S.W.A.)
2
2
E N L
CONTROLLER
MODEL
CONTROLLER
MODEL
CP77
CP77
220V AC SUPPLY
(OR OTHER VOLTAGE TO
SUIT TYPE OF GLOBES USED)
AUTOCLOSE
TOGGLE
C
A
6
B
N/A
N/A
N/A
N/A
CP87
CP87
PILLAR LIGHT(S)
REMOTE PILLAR LIGHT CONTROL
2424
LIGHT
LIVE
LIGHT
}
NEG
Page 27
Electrical Connections cont'd.....
BATTERY CHARGER TRANSFORMER SUPPLY
PSU 1/2 POWER SUPPLY
2525
PLUG IN TRANSFORMER IN HOUSE
ENCLOSURE MOUNTED CHARGER TRANSFORMER MOUNTED AT GATE
OPTION 1
AC
AC
CONTROL BOX
CONTROL BOX
OPTION 2
1,5mm ²
CABLE
BROWN
BROWN
CONTROLLER
MODEL
CP77
CP87
15
8
16
9
CONTROLLER
MODEL
NOTE: CP77 CONTROLLER CARD MUST BE MODIFIED FOR PSU SUPPLY, REFERENCE CP77PSU
CP77PSU
CP87
15 F
N/A N/A
16
G
N/A N/A
AC
AC
AC
AC
220V AC
PLUG IN OR
ENCLOSURE
MOUNTED
L
N
E
L
N
E
220V AC SUPPLY
PLUG IN
CONNECTOR
CP53
CP13E
L N
2
V
2
A
C
0
S
P
Y
A
IN SU L
M
P
BT
E
R
A
T Y
A
)
( P
T
I
NO
O
L
PSU 2
W
P Y
T
P
1
/ O
E
R
S
U
L U
N
P I
R D
E
R ED
B L C A
K
BL A
C K
E
BATT - BATT +
Page 28
Electrical Connections cont'd.....
2626
SOLAR PANEL
RECOMMENDED EARTHING FOR LIGHTNING PROTECTION
SLAVE MOTOR 2
MASTER MOTOR 1
1,5M
EARTH
ROD
SEE SABS 1063 FOR ROD
ELECTRODE DETAILS
TO ESCOM or MAINS SUPPLY.
- EARTH SYSTEM AT THE GATE USING A COPPER EARTH SPIKE.
- ENSURE THAT SYSTEM IS CONNECTED TO ESCOM OR MAIN EARTH.
- CABLING FROM EARTH ROD TO PSU MUST BE AS HEAVY AS POSSIBLE (± 4mm)
CP77
CONNECT GREEN/YELLOW
EARTH WIRE TO EARTH
STUD ON TRANSFORMER
L
N
E
- USE ONE OF THE STUDS THAT SECURE THE TRANSFORMER IN POSITION
GREEN /YELLOW WIRE OF CONTROL CARD
SCREEN OF
INTERCOM CABLE
(EARTH SCREEN AT
HOUSE AS WELL)
EARTH ROD
TO ESCOM EARTH
SOLAR PANEL
TO SECOND
SOLAR PANEL
(IF FITTED)
NOTE 2
NOTE 2
TO MOTOR
LOAD e.g. FLUORESCENT
LIGHT 12V DC
e.g. PDI 120505L-3.5DC
2
1
X (NOTE1)
BLACK
SENSE CABLE 0.2mm²
SENSE CABLE 0.2mm²
POWER CABLE 2.5mm²
POWER CABLE 2.5mm² MINIMUM
RED
BATTERY
DEEP CYCLE
SOLAR REGULATOR
(WITH LOAD SHED)
TYPE WITH LOAD SHED
--
+
0,5mm²
CABLE MIN
ANGLE, X °
LOCATION
30°
JOHANNESBURG
40°
PE & EAST LONDON
CAPE TOWN45°
NOTE:
1. TO PREVENT THE STATUS LED ON THE CP77 CONTROLLER FROM INDICATING "MAINS FAILURE", IT IS NECESSARY TO CONNECT TERMINAL 13 TO TERMINAL 15.
2. CONNECT MOTOR DIRECTLY TO BATTERY (UNLESS LOAD SHED FUSE IS SUITABLY RATED)
Page 29
C
Commissioning
2727
CP77
1
1
1
2 3 4
0
0
0
0 0
1
1
1
1
1 16
1
0
0
0
1 1
0
0
1
0
1
0
0
1
0
1
1
0
0
0
1
0
1
0
0 0
0
0
0
1
0
2
SWITCH NO
3 4 DESCRIPTION OF OPERATION (MODE)
GREEN POWER ON LED
(ON WITH MAINS POWER PRESENT)
GATE STATUS
LED (RED)
SINGLE MOTOR SYSTEM WITHOUT AUTOCLOSE
SINGLE MOTOR SYSTEM WITH AUTOCLOSE
DOUBLE MOTOR SYSTEM WITHOUT AUTOCLOSE DOUBLE MOTOR SYSTEM WITH AUTOCLOSE
CONDOMINIUM MODE (SINGLE MOTOR)
PIRAC MODE (SINGLE MOTOR) CONDOMINIUM MODE (DOUBLE MOTOR)
PIRAC MODE (DOUBLE MOTOR) LINEAR MOTOR(S) WITHOUT AUTOCLOSE LINEAR MOTOR(S) WITH AUTOCLOSE
5 SECS
OPEN
45 SECS
CLOSE
LED
GATE STATUS
CP77 AND CP87
GATE CLOSEDLED OFF
LED ON FAST FLASH SLOW FLASH 2 FLASH/2 SECS 3 FLASH/2 SECS
NOTE: MAINS FAILURE DOES NOT APPLY TO CP87 CONTROL CARD.
MAINS FAILURE BATTERY LOW
OPENING
CLOSING
GATE OPEN
AUTOCLOSE TIMER
COLLISION SENSITIVITY
CONTROL CARD SETUP
NOTE: LIMIT SWITCH LEDS ONLY ON VERSION 1.1 CARDS AND ABOVE
(SEE NOTE)
xx
x
xx
xx xx xx
CP77 V1.X
CP87
AUTOCLOSE
SELECT
GATE STATUS
LED (RED)
XX
1 9
COLLISION SENSITIVITY
MINMAX
AUTOCLOSE
"OFF"
AUTOCLOSE
"ON"
x
GREEN POWER ON LED
(ON WITH MAINS
POWER PRESENT)
- IDENTIFY STATUS LED WHICH WILL GIVE INFORMATION ON GATE STATUS (e.g. WHETHER GATE SHOULD BE OPEN OR CLOSED).
- SELECT DIP SWITCH SETTINGS TO GIVE REQUIRED MODE OF OPERATION (CP77 ONLY).
- SELECT "AUTOCLOSE" IF REQUIRED (e.g. USING SW1 ON CP77, JUMPER ON CP87).
- SET AUTOCLOSE TIMER POTENTIOMETERS TO MINIMUM INITIALLY AND ADJUST TIME TO SUIT AFTER COMMISSIONING.
- SET COLLISION SENSITIVITY POTENTIOMETERS TO MID POSITION (SEE PAGE 32 FOR CORRECT FINAL ADJUSTMENT).
COMMISSIONING INSTRUCTIONS
Page 30
Commissioning cont'd .....
2828
x
APPLYING MAINS POWER
CONNECTING BATTERY
OPTION 1 220V AC SUPPLY TO GATE
- APPLY 220V AC POWER
- CHECK POWER ON INDICATION
OPTION 2
LOW VOLTAGE SUPPLY TO GATE
- PLUG IN TRANSFORMER AND SWITCH ON CIRCUIT
- CHECK POWER ON INDICATION
15V AC TO CONTROLLER
15V AC TO CONTROLLER
xx
CP77/CP87
CONTROLLER
GREEN = POWER SUPPLY
CONNECTED
AND SWITCHED ON
xx
CP77/CP87
CONTROLLER
GREEN = POWER SUPPLY
CONNECTED
AND SWITCHED ON
L
N
E
L
N
E
220V AC SUPPLY
PLUG IN
CONNECTOR
CP13E
POWER SUPPLY
4mm
CABLE
2
CONTROLLER
MODEL
CP77
CP87
F
A
G
B
+
-
-
BATTERY
12V
NOTE: IF A LARGE BATTERY IS USED, THE CABLES CONNECTING THE BATTERY TO THE CP80 CARD
SHOULD BE BETWEEN 6 & 10 mm² FOR CABLE LENGTHS LESS THAN 5 METRES.
+
CP4 BATTERY
CP77
- APPLY 220V AC POWER
- CHECK POWER ON INDICATOR
- LOOSEN OR REMOVE DRIVE ARMS
- CONNECT BATTERY
Page 31
Commissioning cont'd .....
2929
ARROW SHOWS
CORRECT DIRECTION(S)
TO CLOSE GATE(S)
(VIEWED FROM INSIDE
THE PROPERTY)
L.H.S. GATE MOTOR R.H.S. GATE MOTOR
}
PE
N
O
OPE
N
CLOSED
S
CLO ED
COMMON
COMMON
SWOP MOTOR POLARITY TO CHANGE MOTOR DIRECTION
MOTOR
MOTOR
EARTH WIRE
EARTH WIRE
TRIGGER CONTROL CARD
MAKE SURE MOTOR DIRECTION(S) CORRESPOND(S) WITH STATUS LED. (COMPARE FIG 1 AND FIG 2 BELOW).
SWOP MOTOR WIRES TO GIVE CORRECT MOTOR ROTATION (IF NECESSARY). (SEE FIG 3a BELOW).
TEST THAT MOTOR STOPS WHEN IT HITS THE LIMIT SWITCH.
SWOP LIMIT SWITCH WIRES IF MOTOR DOES NOT STOP ON LIMIT SWITCH (SEE FIG 3b BELOW).
SWOP TO STOP MOTOR(S) ON LIMIT(S) (IF NECESSARY)
--
--
--
--
--
}
}
SET MOTOR AND LIMIT SWITCH POLARITY
FIG 1
FIG 2
FIG 3a
CONNECTOR BLOCK
IN MOTOR
FIG 3b
xx xx
CP77
CONTROLLER
CP87
CONTROLLER
FAST FLASH SLOW FLASH LED ON LED OFF
CLOSING OPENING GATE OPEN GATE CLOSED
STATUS STATUS
Page 32
Commissioning cont'd .....
SETUP LINE
TIGHTEN
USING
ALLEN KEY
3030
--
--
--
FIXED PIN
ADJUSTABLE L/S STRIKER
MOTOR SHOWN
CLOSING
GATE "CLOSED"
MICROSWITCH
SHOWN ACTIVATED
GATE "OPEN"
MICROSWITCH
NOTE: LHS MOTOR SHOWN
LIMIT SWITCH ADJUSTMENT
DISCONNECT COMMON, IF NECESSARY
TO SET UP (SEE DESCRIPTION ABOVE)
ARRANGE FOR FIXED PIN TO STOP MOTOR IN THE GATE "CLOSED" POSITION (SEE FIG 1 BELOW).
IF ADJUSTABLE L/S STRIKER ARM CAUSES GATE TO STOP, THEN DISCONNECT L/S COMMON (SEE FIG 2 BELOW) AND ALLOW MOTOR TO DRIVE PAST LIMIT SWITCH SPRING.
WHEN L/S STRIKER ARM IS CLEAR, RECONNECT WIRE.
L/
S OPE
N
L/S
CLOS
E
D
/
S
M
O
N
L
CO
M
}
}
}
TO MICRO-
SWITCHES
TO
MOTORTOEARTH
--
--
--
WITH LIMIT SWITCHES SET FOR THE CORRECT "GATE CLOSED" POSITION, REFIT DRIVE ARM AND CONNECTING ARM ENSURING THAT THEY ARE IN A COMPLETELY STRAIGHT LINE.
TIGHTEN DRIVE ARM SECURELY USING ALLEN KEY.
DRIVE ARM, BALL JOINT AND CONNECTING ARM MUST LIE DIRECTLY OVER, AND IN LINE WITH, THE SETUP LINE.
FIG 1
FIG 2
Page 33
Commissioning cont'd .....
--
OPEN GATE AND ADJUST THE "ADJUSTABLE" LIMIT SWITCH STRIKER ARM SUCH THAT DRIVE ARM DESCRIBES 180 DEGREE ARC.
NOTE: L.H.S. MOTOR SHOWN
3131
DRIVE ARM POSITION
WITH GATE CLOSED
DRIVE ARM POSITION FOR
GATE FULLY OPEN
180° ARC
O
DIRECTION OF ROTATION
FOR L.H.S. TO OPEN
ADJUST ADJUSTABLE LIMIT
SWITCH STRIKER PLATE
USING 10 SPANNER.
Page 34
CP77
CONTROLLER
CP87
CONTROLLER
MINMIN
MAXMAX
SETS SENSITIVITY
FOR BOTH OPENING
AND CLOSING
C
Collision Sensing Adjustment
3232
GATE CLOSING
GATE OPENING
MOTOR STOPS AND
REVERSES ON HITTING
AN OBSTRUCTION
MOTOR STOPS
(DOES NOT REVERSE)
ON HITTING AN OBSTRUCTION
OPENING CLOSING
SETS SENSITIVITY FOR MASTER AND SLAVE GATE WHILE:-
--
--
ADJUST SETTING(S) ON CONTROL CARD (SEE FIGURE 2) SUCH THAT GATE(S) WILL OPEN AND CLOSE RELIABILY, BUT NOT CAUSE DAMAGE TO PERSONS OR OBJECTS IN THE PATH OF THE GATE.
NOTE DIFFERENCE DURING CLOSING (FIG 1) AND OPENING (FIG 3) DIRECTIONS.
FIG 1
FIG 2
FIG 3
Page 35
Page 36
CENTURION
THE AUTOMATIC CHOICE
CENTURION SYSTEMS (PTY) LTD HEAD OFFICE:
TEL: +27 (0)11 699-2400, FAX: +27 (0)11 704-3412 or 462-6669
148 EPSOM AVENUE, NORTH RIDING
P.O. BOX 506, CRAMERVIEW, 2060
SOUTH AFRICA
WEB: http://www.centsys.co.za General information e-mail: info@centsys.co.za
FOR TECHNICAL SUPPORT CONTACT:
ECHO-LINE, NAMIBIA.............................................................Tel: (61) 220-8309
MOLECULAR CONSULTANTS, NIGERIA...............................................Tel: 803-3123182
SECURITY DISTRIBUTORS, ZIMBABWE................................................Tel: (4) 795-873
SEKANYOLYA TIMBER WORKS, UGANDA...............................................Tel: (41) 231-40
AUTOMATISME BATIMENT, FRANCE.................................................Tel: (1) 697-93120
CROWN AXXESS LTD U.K. UNITED KINGDOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tel: (1483) 450-011
NESTOR, BELGIUM ...............................................................Tel: (9) 380-4020
BILLY GATES, CANADA ..........................................................Tel: (250) 334-1553
ABA GATES, WESTERN AUSTRALIA.................................................Tel: (8) 933-03061
DOMINATOR SYSTEMS, NEW ZEALAND ..............................................Tel: (3) 384-5145
ICBT, VICTORIA..................................................................Tel: (3) 933-54213
ROTECH, QUEENSLAND..........................................................Tel: (7) 326-47330
SA GATES, SOUTHERN AUSTRALIA.................................................Tel: (8) 826-64235
SECURITE DU PACIFIQUE, NEW CALEDONIA..............................................Tel: 283-760
SECULOGIX LTD, MAURITIUS..........................................................Tel: 467-8509
SECURITE AUTOMATISMES REUNION, REUNION ..........................................Tel: 280-368
VAST VIDEO, MALAYSIA...........................................................Tel: (3) 214-34931
BLT ASSOCIATES, THAILAND .......................................................Tel: (2) 691-6793
EAST RAND. . . . . . . . . . . . . . . (011) 397-6401
DURBAN .................(031) 701-9583
NELSPRUIT . . . . . . . . . . . . . . . (013) 752-8074/5
PRETORIA . . . . . . . . . . . . . . . . (012) 348-2610/1
CAPE TOWN . . . . . . . . . . . . . . (021) 447-1295
PORT ELIZABETH. . . . . . . . . . . (041) 581-6994/5
EAST LONDON . . . . . . . . . . . . . . (043) 743-4923
BLOEMFONTEIN . . . . . . . . . . . . . (051) 448-1714
KIMBERLEY . . . . . . . . . . . . . . . . . (053) 832-3231
VEREENIGING . . . . . . . . . . . . . . . (016) 422-5667
SOUTH AFRICA
AFRICA
EUROPE
NORTH AMERICA
AUSTRALASIA
INDIAN OCEAN
ASIA & PACIFIC
Loading...