Centurion 04791-0, 3500 Owner's Manual And Installation Instructions

Page 1
®
Owner’s Manual and
Installation Instructions
CENTURION 3500
Air-cooled, Prepackaged
Automatic Standby Generator
• Model: 04791-0
3.4kW LP
or in life-support applications.
!
!
This manual should
remain with the unit.
DEADLY EXHAUST FUMES. OUTDOOR INTALLATION ONLY!!
DANGER
Page 2
Generac®Power Systems, Inc.

INTRODUCTION

Thank you for purchasing this model of the CENTU­RION product line by Generac Power Systems Inc. This model is designed and manufactured to supply electrical power for residences.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is misunderstood, con­tact the nearest Generac Authorized Service Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAU­TION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
After this heading, read instructions that, if not strictly complied with, will result in serious person­al injury, including death, as well as property dam­age.
After this heading, read instructions that, if not strictly complied with, may result in serious person­al injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety infor­mation that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion haz­ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts for generator model numbers 04791-0. In addition, the latter portion of this manual contains information necessary for the proper installation of these generators.
OPERATION AND MAINTENANCE
It is the owner's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Generac Authorized Service Dealer. Normal maintenance ser­vice and replacement of parts are the responsibility of the owner and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage con­tribute to the need for maintenance service.
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum.
HOW TO OBTAIN SERVICE
When your generator requires servicing or repairs, simply contact a Generac Authorized Service Dealer for assistance. Service technicians are factory trained and are capable of handling all service needs.
When contacting a Generac Authorized Service Dealer about parts and service, always supply the complete model number and serial number of the unit as given on its data decal, which is located on the generator.
Model No. ____________ Serial No. ______________
AUTHORIZED SERVICE
DEALER LOCATION
To locate the nearest GENERAC AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
ONLY DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
DANGER
!
Page 3

Table of Contents

CENTURION 3500 Home Standby Generator
Generac®Power Systems, Inc. 1
Part I – Owner’s Manual
Introduction ........................................Inside Front Cover
Read This Manual Thoroughly ....................................IFC
Contents ......................................................................IFC
Operation and Maintenance ........................................IFC
How to Obtain Service..................................................IFC
Authorized Service Dealer Locator Number ................IFC
Safety Rules ........................................................................2
Section 1 - General Information ....................................4
1.1 Generator Identification ........................................4
1.2 Unpacking/Inspection ............................................5
1.3 Safety ....................................................................6
1.4 Protection Systems................................................6
1.5 Location ................................................................6
1.6 Specifications ........................................................6
Section 2 - Operation........................................................7
2.1 Generator Control Panel........................................7
2.2 Before Starting the Engine ....................................8
2.3 Battery Connection................................................8
2.4 The Battery ..........................................................9
2.5 Before Initial Start-up............................................9
2.6 Stopping the Generator ......................................10
2.7 Applying Loads to Generator ..............................10
2.8 Do Not Overload the Generator ..........................10
2.9 Protection Systems..............................................10
2.10 Additional Information ........................................12
Section 3 - Maintenance ................................................12
3.1 Checking the Engine Oil Level ............................12
3.2 Changing the Engine Oil and/or Oil Filter ..........12
3.3 Maintaining the Engine Air Cleaner ....................13
3.4 Clean Air Intake ..................................................14
3.5 Checking the Engine Spark Plug ........................14
3.6 Clean Spark Arrestor ..........................................14
3.7 Cleaning the Generator ......................................15
3.8 Battery Maintenance............................................15
3.9 Exercising the Generator ....................................16
3.10 Out of Service Procedure ....................................16
3.11 Adjusting Valve Clearance ..................................17
3.12 Generator Service Interval ..................................17
Part II – Installation Instructions
Safety Rules ......................................................................19
Section 1 - General Information ..................................21
1.1 Tools Required....................................................21
1.2 Items That Must Be Purchased ..........................21
1.3 Plan the Location of the Generator......................21
Section 2 - Installation ..................................................22
2.1 Site Preparation and Generator Placement ........22
2.2 Power Cord Installation ......................................22
2.3 Mount Power Transfer Motor ..............................23
2.4 Install Propane Tanks ........................................23
2.5 Set System for Automatic Operation ..................25
2.6 How to Keep the Regulator Operating
Efficiently & Safely ..............................................25
2.7 What is Regulator Freeze Up?..............................25
Appendix 1 - Troubleshooting ......................................26
Appendix 2 - Notes..........................................................27
Appendix 3 - Electrical Data ........................................30
Appendix 4 - Exploded Views and Parts Lists..........34
Appendix 5 - Warranty ..................................................48
Page 4
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this manual and with the unit. The generator can operate safely, efficiently and reli­ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possibility that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit, are, therefore, not all-inclusive. If using a procedure, work method or operating technique Generac does not specifically recommend, satisfy yourself that it is safe for others. Also make sure the procedure, work method or operating technique chosen does not ren­der the generator unsafe.
Despite the safe design of this generator, oper­ating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsi­ble and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GEN
ERAL HAZARDS
• For safety reasons, Generac recommends that the
maintenance of this equipment is carried out by a Generac Authorized Service Dealer.
• The generator engine releases DEADLY carbon
monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concentra­tions, can cause unconsciousness or even death. Never operate the generator inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOXIDE POISONING ARE (a) inability to think coherently, (b) nausea, (c) vomit­ing, (d) twitching muscles, (e) throbbing temples, (f) dizziness, (g) headaches, (h) weakness, and (i) sleepiness. IF EXPERIENCING ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDI­ATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. Shut down the generator and do not operate it until it has been inspected and repaired.
• The engine exhaust fumes contain carbon monox-
ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compli­ance with applicable codes and standards. Following installation, do nothing that might ren­der the system unsafe or in noncompliance with such codes and standards. Never operate this equipment with a leaking or defective exhaust sys­tem.
• Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti-
lating air is critical to correct generator operation and is required to expel toxic fumes and fuel vapors from the generator. Without sufficient cooling air­flow, the engine/generator overheats, which causes serious damage to the generator. Do not alter the installation or permit even partial blockage of ven­tilation provisions, as this can seriously affect safe operation of the generator.
!
!
!

Safety Rules

CENTURION 3500 Home Standby Generator
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas of the recreational vehicle. Safety should be stressed to all operators and potential operators of this equipment.
!
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
!
!
!
!
!
!
DANGER
!
Page 5
Generac®Power Systems, Inc. 3
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and contact the nearest Generac Authorized Service Dealer immedi­ately for parts needing repair or replacement.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
• The generator covered by this manual produces dangerous electrical voltages and can cause fatal electrical shock. Avoid contact with bare wires, ter­minals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• During installation, have the generator properly grounded (bonded) by means of an approved bonding conductor. DO NOT disconnect the bond­ing conductor. DO NOT reconnect the bonding conductor to any generator part that might be removed or disassembled during routine mainte­nance. If the grounding conductor must be replaced, use only a flexible conductor that is of No. 12 American Wire Gauge (AWG) copper wire minimum.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a dry rope or board, to free the vic­tim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
EXP
LOSION HAZ
ARDS
• Do not smoke around the generator. Wipe up any oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the genera­tor clean and free from debris.
Safety Rules
CENTURION 3500 Home Standby Generator
Page 6
4 Generac®Power Systems, Inc.
1. Generator Air Intake
2. Engine AUTO/OFF/MANUAL Switch
3. Fuse
4. LED Indicator
5. Demand Regulator (Inside Compartment)
6. Change-over Regulator
7. Circuit Breakers
8. Starter Contactor
9. Fuel Inlet
10. Tank Hook-ups.
11. Battery (In Compartment)
12. Oil Filter
13. Oil Drain (From Underside)
14. Oil Dipstick
15. Air Filter (Behind Access Panel)
16. Oil Fill
17. Spark Plug
18. Tank Hold Down Brace
19. Exhaust Hood (Tailpipe and Spark Arrestor Inside)
20. Ground Lug
21. Data Decal (Located inside compartment)

Section 1 – General Information

CENTURION 3500 Home Standby Generator
Please record the following information from the generator DATA DECAL or information decal.
1. Model Number ____________________ 2. Serial Number __________________
3. kW Rating__________________________ 4. Rated Voltage __________________
072347
QT
RATO
R
T
OR
R
USE
.5A
1.1 GENERATOR IDENTIFICATION
Model: 004700-0 — QUIETPACT 40G
21
18
10
19
13
14, 16
12
8
17
4
3
7
2
15
1
9
6
5
1
11
20
GENERAT
F
POWE
7
PUSH TO RESE
R POWE
0.8L/0.84
Page 7
Generac®Power Systems, Inc. 5
Section 1 – General Information
CENTURION 3500 Home Standby Generator
1.1.1 POWER TRANSFER MONITOR
The Power Transfer Monitor controls the automatic function of the Centurion 3500 generator set. It’s six foot utility sensing cord monitors the utility line when it is plugged into a standard household 120 volt out­let.
NOTE:
Automatic start-up upon utility power outage will not occur if six foot sensing cord is not plugged into a utility powered 120 volt outlet.
Figure 1.2 — Power Transfer Monitor
1. Generator Power Conduit (15 foot)
2. Circuit Breaker Reset (2)
3. Generator Power Indicator Lamp
4. Utility Power Indicator Lamp
5. Generator Exercise Switch
6. Switched GFCI Outlet
7. Standby GFCI Outlet
8. Utility Sensing Cord (6 foot)
1.1.1.1 Generator Power Conduit
This conduit connects the Power Transfer Monitor, which is located inside the home, to the generator outside.
1.1.1.2 Circuit Breaker Reset
If the generator should experience an overload for any reason, the circuit breaker(s) will trip. The cir­cuit breaker reset(s) should be pushed to reset after overload condition has been corrected.
1.1.1.3 Generator Power Indicator Lamp
This lamp will illuminate when the generator has started and is supplying power to the Power Transfer Monitor’s GFCI outlets.
1.1.1.4 Utility Power Indicator Lamp
This lamp will be illuminated when normal utility power is available.
1.1.1.5 Generator Exercise Switch
This switch activates the exercise cycle of the genera­tor. Make sure the combined loads do not exceed gen­erator capacity.
1.1.1.6 Switched GFCI Outlet
This outlet is powered by the utility and by the gen­erator. When utility power is present is acts as anoth­er normal household outlet. When the generator is supplying power this outlet is then being supplied with power from the generator.
NOTE:
There will be a momentary “No Power” period between the time of utility failure and the genera­tor start up.
1.1.1.7 Standby GFCI Outlet
This outlet is ONLY powered by the generator. Use it for additional items during a utility power outage when the generator is providing backup electricity for the home.
1.1.1.8 Utility Sensing Cord
When plugged into a standard grounded 120 volt out­let this cord allows the Power Transfer Monitor to sense the utility line condition and react to a power outage.
1.2 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
• This standby generator set has been factory sup­plied with a weather protective enclosure that is intended for outdoor installation only.
• This standby generator set is prepackaged with an automatic power transfer monitor. The power transfer monitor is prewired with 15 foot conduit and six foot utility sensing cord with plug. The Power Transfer Monitor is for indoor installation only.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix his or her signature under the consignor’s memo of loss or damage.
If loss or damage is found after delivery, separate the damaged materials and contact the carrier for claim procedures if applicable.
Use this generator to supply electrical power for operating 120-volt, single-phase, 60 Hertz, AC elec­trical loads. These loads can require up to 3,400 watts (3.4 kW) of power, but cannot exceed 28.3 AC amperes of current at 120 volts.
1
2
3
4
5
6
7
8
Page 8
6 Generac®Power Systems, Inc.
Section 1 – General Information
CENTURION 3500 Home Standby Generator
Do not overload the generator. Some installa­tions may require that electrical loads be alter­nated to avoid overloading. Applying exces­sively high electrical loads may damage the generator and may shorten its life. Add up the rated watts of all electrical lighting, appliance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capacity of the generator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.
1.3 SAFETY
Before attempting to use the generator set, carefully read the “Safety Rules” section of this manual. Comply strictly with these rules to prevent accidents and damage to equipment and/or property. We sug­gest copying and posting the “Safety Rules” in poten­tial hazard near the generator. Stress safety to all operators and potential operators of this equipment.
1.4 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for long periods of time with no operator pre­sent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging condi­tions:
1. Overcrank
2. Overspeed
3. Low Oil Pressure Sensor
4. High Temperature Sensor
5. Underspeed There is an LED readout on the control panel to noti-
fy personnel that one of these faults has occurred. Detail of of the protection systems can be found in Section 2.9.
1.5 LOCATION
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available. Consider these factors:
• Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift­ing, consider using a windbreak to protect the unit.
• Install the generator on high ground where water levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator for maintenance and servicing. A good rule is to allow three feet of space on all sides.
• Where strong prevailing winds blow from one direction, face the generator air inlet openings to the prevailing winds.
1.6 SPECIFICATIONS
1.6.1 FUEL REQUIREMENTS AND RECOM­MENDATIONS
With LP gas, use only the LP vapor withdrawal sys­tem. This type of system uses the vapors formed above the liquid fuel in the storage tank.
Recommended fuel should have a BTU content of at least 2,520 BTU's per cubic foot. Ask the LP fuel sup­plier for the BTU content of the fuel.
This generator has been designed for a specific type of tank. Acceptable tank types are DOT-4BA240 and DOT-4BW240. Any deviation in tank type may not allow the tank to fit in the LP enclosure.
Gaseous fuels such as liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. LP gas, which is heavier than air tends to settle in low areas.
1.6.2 FUEL CONSUMPTION
Fuel consumption is in gal/hr.
1.6.3 ENGINE OIL REQUIREMENTS
Use only high quality detergent oil rated with American Petroleum Institute (API) Service Classification SF, SG or SH. The recommended oil weights include the following:
• During summer months: SAE 30. An acceptable substitute is SAE 10W-30.
• During winter months: SAE 5W-30. DO NOT USE SAE 10-W40.
Crankcase and oil filter capacity is approximately 800 mL or .84 U.S. quarts. Do NOT use special addi­tives. See Sections 3.1 and 3.2 for oil level check and fill procedures.
!
!
Model 1/2 Load Full Load
Centurion 3500 0.55 0.73 (04791-0)
DANGER
Page 9
Generac®Power Systems, Inc. 7

Section 2 – Operation

CENTURION 3500 Home Standby Generator
1.6.4 ENGINE
Type of Engine ............................GN-220, Single-cylinder
Cooling Method..................................................Air-cooled
Rated Horsepower ..................................7.8 @ 4,200 rpm
Displacement............................................................220cc
Cylinder Block ....................Aluminum w/Cast Iron Sleeve
Type of Governor ........................Mechanical, Fixed Speed
Air Cleaner ..................Paper Element w/Foam Precleaner
Starter ................................................12-volt DC Electric
Ignition System ................Solid-state w/Flywheel Magneto
Recommended Spark Plug
Champion ..........................................................RC12YC
AC ..........................................................................R45S
Fram Autolite ..............................................................65
Spark Plug Gap ..................................0.03. inch (76 mm)
Recommended Minimum
Battery ......................................235cc Amperes @ 32°F/
195cc Amperes @ 0° F
1.6.5 GENERATOR
Rated Maximum Continuous
AC Output (LP)................................3,400 Watts (3.4kW)
Rated Voltage ................................................120 Volts AC
Rated Maximum Continuous
AC Current (LP) ........................................28.3 Amperes
Phase ......................................................................Single
Rotor RPM................................................................3,600
Number of Rotor Poles ....................................................2
Engine RPM..............................................................3,600
Rated AC Frequency ................................................60 Hz
Battery Charge Voltage ....................................14 Volts DC
Battery Charge Current ..........................2 Amperes (max)
Length ..................................................843 mm (33.2 in.)
Width ....................................................504 mm (19.8 in.)
Height ......................................................966 mm (38 in.)
Weight ......................................................90 kg (275 lbs.)
2.1 GENERATOR CONTROL PANEL
The following features are mounted on the generator control panel (Figure 2.1):
Figure 2.1 — Generator Control Panel
2.1.1 SHUT DOWN INDICATOR
This LED will flash a specific number of times to indi­cate a specific failure. Shutdowns and their failure codes follow in Section 2.9, Protection Systems. These codes can also be referenced on the decal located on the air filter cover, located below the control panel.
2.1.2 AUTO/OFF/MANUAL SWITCH
2.1.2.1 Auto Position
Selecting this switch position activates fully automat­ic system operation. It also allows the user the abili­ty to start and exercise the generator from the remote Power Transfer Monitor.
2.1.2.2 Off Position
This switch position shuts down the engine. This position also prevents the engine from starting.
2.1.2.3 Manual Position
Selecting this switch position will crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.
With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre­set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuse before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.
2.1.3 FUSE
The generator panel's 7.5 amp fuse protects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, the engine cannot crank or start. The same fuse also protects the bat­tery charge circuit against overload. If the fuse ele­ment has melted open, battery charging will not be possible. Replace the fuse using only an identical 7.5 amp fuse.
2.1.4 MAIN BREAKERS
The main breakers protect the generator’s AC output circuit against overload and provide a method of turning OFF the generator’s 120-volt AC output to the Power Transfer Monitor’s outlets. The CENTURION 3500 has two (2) 15-amp breakers.
!
FUSE
7.5A
SHUT
DOWN
GENERATOR
POWER
GREEN BAR INDICATES TRIP
PUSH TO RESET
15 15
PULL TO DISCONNECT
GENERATOR POWER
INDICATOR
SEE CHART BELOW FOR DETAILS
CONTROL CENTER
AUTO
OFF
MAN.
Page 10
8 Generac®Power Systems, Inc.
Section 2 – Operation
CENTURION 3500 Home Standby Generator
2.2 BEFORE STARTING THE ENGINE
NOTE:
Instructions and information in this manual assume the generator has been properly installed and connected.
2.2.1 ENGINE LUBRICATION
Have the engine crankcase properly serviced with the recommended oil before starting. Refer to Section
1.6.2 and Sections 3.1 and 3.2, for oil servicing pro­cedures and recommendations.
Any attempt to crank or start the engine before it has been properly serviced with the recom­mended oil may result in an engine failure.
2.2.2 FUEL SUPPLY
The engine must have an adequate supply of proper fuel to operate. Before starting it, check that sufficient fuel is available.
2.2.3 COOLING AND VENTILATING AIR
Air inlet and outlet openings in the generator com­partment must be open and unobstructed for contin­ued proper operation. Without sufficient cooling and ventilating airflow, the engine/generator overheats, which causes it to shut down and may damage the generator.
2.2.4 ENGINE EXHAUST GAS
Before starting the generator engine, be sure there is no way for exhaust gases to endanger people or ani­mals. Close windows, doors near the generator that, if open, might permit exhaust gases to do so.
The generator engine releases DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concen­trations, can cause unconsciousness or even death. Never operate the generator set inside any enclosed area. make sure THE EXHAUST SYSTEM IS not LEAKING AND HAS NOT BEEN DAMAGED. SYMPTOMS OF CARBON MONOX­IDE POISONING ARE (a) inability to think coher­ently, (b) nausea, (c) vomiting, (d) twitching muscles, (e) throbbing temples, (f) dizziness, (g) headaches, (h) weakness, and (i) sleepiness. IF EXPERIENCING ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMP­TOMS PERSIST, GET MEDICAL HELP. Shut down the generator and do not operate it until it has been inspected and repaired.
2.3 BATTERY CONNECTION
Before connecting the battery, complete the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Make sure the Power Transfer Monitor’s sensing cord (6 foot) is not plugged into an electrical out­let.
If the AUTO/OFF/MANUAL switch is not set to its OFF position, the generator can crank and start as soon as the battery cables are connect­ed. If the utility power supply is not disabled by unplugging the 6 foot sensing cord from electrical outlet, sparking can occur at the bat­tery posts and cause an explosion.
Battery cables were factory connected at the genera­tor (Figure 2.2). Connect the cables to the battery posts using the hardware supplied in the manual bag as follows:
3. Slide the red battery terminal boot over the bat­tery cable, then connect the cable (from the starter contactor) to the battery post indicated by a positive, POS or (+).
4. Connect the black battery cable (from frame ground) and the two green grounding wires (from the control panel) to the battery post indicated by a negative, NEG or (-).
NOTE:
Damage will result if battery connections are made in reverse.
Figure 2.2 — Battery Cable Connections
!
DANGER
DANGER
!
Page 11
Generac®Power Systems, Inc. 9
Section 2 – Operation
CENTURION 3500 Home Standby Generator
2.4 THE BATTERY
Servicing of the battery is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
When replacing the battery, use the following type of battery, Group U1 12-volt battery with a rating of 235 cold-cranking amps at 0° C (32° F); 195 cold-crank­ing amps at -17.8º C (0º F) minimum. When using a maintenance-free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connect­ed and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
Do not dispose of the battery in a fire. The bat­tery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. The following precau­tions are to be observed when working on bat­teries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the bat­tery; and
• Disconnect charging source prior to connecting or disconnecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following proce­dures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek med­ical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon­ate of soda to one gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) as ceased. The resulting liquid is to be flushed with water and
the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. The fol­lowing procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
2.5 BEFORE INITIAL START-UP
Before starting the generator, complete the fol­lowing:
1. Set the generator's main circuit breakers (located
in generator’s control panel) to their OFF or OPEN positions by pulling the reset buttons out­ward. A visible GREEN stripe should appear.
2. Set the generator's AUTO/OFF/MANUAL Switch to
the OFF position.
3. Turn OFF all loads connected to the Power
Transfer Monitor through the GFCI outlets.
4. Check the engine crankcase oil level and, if nec-
essary, fill to the dipstick full mark with the rec­ommended oil. Do not fill above the oil FULL mark.
5. Check the fuel supply. Both tanks should be full.
6. The changeover valve tank indicator should be
GREEN.
2.5.1 INITIAL START UP - PURGING THE FUEL SYSTEM
To purge the air that is in the lines of the fuel system, perform the following:
1. Connect the LP tanks and open both tank valves. Make sure that the selector lever on the changeover regulator is pointing at one of the two tanks. Also verify that the Full/Empty indicator on top of the changeover regulator is GREEN.
2. Set the generator's main circuit breakers to their OFF or OPEN positions by pulling the reset but­tons outward. A visible Green stripe should appear.
3. Move the AUTO/OFF/MANUAL switch to the MAN­UAL position.
!
DANGER
!
!
Page 12
10 Generac®Power Systems, Inc.
Section 2 – Operation
CENTURION 3500 Home Standby Generator
4. The engine will crank and attempt to start for approximately 15 seconds. Due to the air that will be in the fuel lines, the engine may not start dur­ing the first 15 second cranking cycle. If the engine does not start during the first crank cycle, it will rest for approximately 15 seconds and then attempt to start again. The complete starting cycle is as follows:
• 15 seconds ON
• 15 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds, Approximately 90 sec­onds total. The engine should start during the first or second attempt.
5. If the unit does not start during this crank cycle, verify that all fuel connections are tight and that the tank valves are open. Turn the AUTO/OFF/MANUAL switch to the OFF position, wait 3-5 seconds, then repeat steps 3-4.
6. If the engine does not start after repeating steps 3-4, contact the nearest Generac Authorized Service Dealer for assistance.
2.5.2 CHECKING AUTOMATIC OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Set the generator's main circuit breakers to their OFF or OPEN positions by pulling the reset but­tons outward. A visible GREEN stripe should appear.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn ON the utility power supply to the Power Transfer Monitor by plugging the 6-foot sensing cord into a standard household outlet.
4. Set the generator's main circuit breakers to their ON or CLOSED position by pressing in the reset buttons.
5. Set the AUTO/OFF/MANUAL switch to AUTO, the system is now ready for automatic operation.
6. Turn off the utility power supply to the Power Transfer Monitor by unplugging it’s 6-foot power cord from the household outlet.
Once the Power Transfer Monitor senses the utility source power is turned OFF, and after an approxi­mate five second delay, the engine should crank and start. After starting, the Power Transfer Monitor should connect load circuits to the standby or gener­ator side. Both sets of GFCI outlets on the Power Transfer Monitor should have power. Confirm trans­fer of power by depressing the test buttons on both GFCI outlets. Each one should trip and the indicator will illuminate.
With the generator running and power is available to the GFCI outlets, turn the utility power supply ON once again by plugging the six foot power cord into a standard household outlet. The following should occur.
• The Power Transfer Monitor should sense the return of utility power and transfer the loads plugged into the SWITCHED GFCI back to the util­ity source. Any loads connected to the STANDBY GFCI will remain powered by the generator until it shuts down. In the event of a real outage, these loads would be reconnected to the utility.
• About two minutes after re-transfer, the engine should shut down. However, if the engine was not run for it's minimum run time based on starting time, it may run for a longer period of time before shutting down. (20 minutes max.)
• The minimum run time is pre-programmed into the generator micro processor and is provided to ensure that the starting battery is fully charged before the engine shuts down. The minimum run time is based on the time it takes for the engine to crank and start. For every one second of cranking, the generator will run for 1.5 minutes.
2.6 STOPPING THE GENERATOR
1. Turn OFF all electrical loads using the means
provided (such as the generator fs main circuit breakers).
2. Let generator run at no-load for a few minutes, to
stabilize internal engine generator temperatures.
3. Place the AUTO/OFF/MANUAL switch in its OFF
position.
2.7 APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator, observe these guidelines:
Before applying electrical loads, let the generator stabilize and warm up for a minute or two.
DO NOT overload the generator.
2.8 DO NOT OVERLOAD THE
GENERATOR
Read the rated wattage/amperage capacity of the gen­erator in GENERATOR data, (see Section 1.6.5). Applying electrical loads in excess of the unit’s rated capacity will cause the engine/generator to automati­cally shut down.
To avoid overloading, add up the wattage of all con­nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the gen­erator’s rated wattage capacity.
Page 13
Generac®Power Systems, Inc. 11

Section 3 – Maintenance

CENTURION 3500 Home Standby Generator
• Most lighting, appliance, tool and motor loads indi­cate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.
• If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain WATTS.
• Induction type motors (such as those that run a furnace fan, refrigerator, window air conditioner, etc.) need about 2-1/2 time more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when con­necting electrical loads to the generator. First, fig­ure the watts needed to start electric motors in the system. To that figure, add the running wattages of other items that will be operated by the generator.
• Do not apply heavy electrical loads for the first two or three hours of operation.
2.9 PROTECTION SYSTEMS
2.9.1 OVERCRANK — 2 FLASHES OF LED
This feature prevents the generator from damaging itself when it continually attempts to start and anoth­er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The AUTO/OFF/ MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature will continue to activate.
2.9.1.1 Approximate Crank Cycle Times
• 15 seconds ON
• 15 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total
2.9.2 OVERSPEED — 3 FLASHES OF LED
This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gener­ator from supplying an output that could potentially damage appliances connected to the generator cir­cuit. Please reference Appendix 1, Troubleshooting, if this fault occurs.
2.3.3 LOW OIL PRESSURE SWITCH — 4 FLASHES OF LED
This switch (Figure 2.2) has normally closed (N.C.) contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below a preset level, switch contacts close, and the engine automatically shuts down. The unit should not be restarted until oil is added. Please reference Appendix 1, Troubleshooting, if this fault occurs.
2.9.4 HIGH TEMPERATURE SWITCH — 5 FLASHES OF LED
This switch (Figure 2.2), which has normally open (N.O.) contacts, is mounted near the oil filter. The contacts close if the temperature should exceed approximately 284° F (140° C), initiating an engine shutdown. Please reference Appendix 1, Troubleshooting, if this fault occurs.
Figure 2.3 — Low Oil Pressure and High
Temperature Switches
2.9.5 UNDERSPEED — 6 FLASHES OF LED
This feature protects the generator from damage by shutting down if it happens to run slower than the preset limit. Please reference Appendix 1, Troubleshooting, if this fault occurs.
2.9.6 FIELD BOOST
The Controller Circuit Board houses a field boost diode and resistor. These two components are part of a “field boost” circuit (Figure 2.4). During engine cranking only, a positive DC (battery) voltage is deliv­ered through the diode, resistor, brushes and slip rings, to the generator rotor. Application of this volt­age to the rotor “flashes the field” whenever it is start­ed. Flashing of the field each time the generator starts makes sure that a sufficiently strong magnetic field is available to produce “pickup” voltage in the stator windings.
High Temperature Switch
Low Oil Pressure Switch
Page 14
12 Generac®Power Systems, Inc.
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
Figure 2.4 — Field Boost Circuit
2.9.7 OVERVOLTAGE PROTECTION
A solid-state voltage regulator (Figure 2.5) controls the generator’s AC output voltage. This regulator sup­plies an excitation current to the rotor. By regulating the rotor’s excitation current, the strength of its mag­netic field is regulated and, in turn, the voltage deliv­ered to connected electrical loads is controlled. When the AC frequency is 60 Hertz, voltage is regulated at 120 volts (voltage-to-frequency ratio is 2-to-1).
Figure 2.5 — Solid State Voltage Regulator
The voltage regulator also incorporates a “voltage surge protection circuit”. This circuit prevents trou­blesome surges in the generator AC output voltage. Voltage surge is a common cause of damage to elec­tronic equipment.
2.10 ADDITIONAL INFORMATION
2.10.1 BREAK-IN PERIOD
The first few hours of operation is the break-in peri­od for the generator. Properly breaking in the genera­tor is essential to minimize fuel consumption and provide maximum engine performance. During this break-in period, follow this procedure:
• Run the unit at different electrical loads by plug­ging items into the Power Transfer Monitor’s out­lets. This will help seat the engine piston rings properly.
• Check the engine oil level frequently. Add oil if needed. It is normal for the generator engine to consume more oil than is normal until the piston rings have properly seated.
• After operating the unit for the break-in period, complete the tasks recommended under Section
2.10.2.
2.10.2 POST BREAK-IN CHECK-UP
After the break-in period, the owner should perform the following maintenance items:
• Change the engine crankcase oil and oil filter.
• Check the oil level.
• Inspect the cooling and ventilation openings.
• Check the engine ignition system.
• Inspect the entire electrical system.
• Inspect the engine exhaust system.
2.10.3 ATTENTION REQUIRED AFTER SUBMERSION
If the generator has been submerged in water, it MUST NOT be started and operated. Following any submersion in water, have a Generac/Centurion Authorized Service Dealer thoroughly clean and dry the generator.
2.10.4 OPERATION IN HIGH GRASS OR BRUSH
Never operate the generator while it is in contact with high grass, weeds, brush, leaves or any other com­bustible substance. Such materials can ignite and burn from the heat of the exhaust system. The gener­ator exhaust system becomes extremely hot during operation and remains hot for a long time after it has shut down.
2.10.5 EFFECTS OF MOISTURE AND DIRT
Keep the generator set as clean and dry as possible. Protect the unit against excessive dust, dirt, corrosive vapors, etc. Permitting dirt and moisture to accumu­late on generator windings will have an adverse effect on the insulation resistance of those windings.
When moisture is allowed to remain in contact with windings, some of the moisture will be retained in voids and cracks in the insulation. This causes a reduced insulation resistance and will eventually cause problems. Dirt will make the problem worse, since dirt tends to hold moisture in contact with windings. Salt (as from sea air) also will worsen the problem since it tends to absorb moisture from the air. Salt and moisture, when combined, form an elec­trical conductor which is detrimental to the genera­tor.
CONTROLLER CIRCUIT BOARD
4
O
GRND
F
CLOSEST TO BEARING
FIELD
Page 15
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
3.1 CHECKING THE ENGINE OIL LEVEL
For oil capacities and requirements, see “Engine Oil Requirements,” Section 1.6.3. Check the engine crankcase oil level weekly. To check the engine oil level, proceed as follows (see Figure 3.1):
1. Remove the oil fill/dipstick cap and wipe the dip-
stick dry with a clean, lint-free cloth.
2. Install and tighten the oil fill/dipstick cap; then,
remove it again. The oil level should be at the dip­stick “Full” mark.
3. If necessary, slowly add oil until it reaches the
dipstick “FULL” mark. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
4. Install and tighten the oil fill/dipstick cap before
operating the engine.
3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER
• Change the engine oil after the break-in period,
(see Section 2.10.1). Thereafter, change oil every twelve months. Change the oil more frequently if unit operates during extended power outages of several days at a time, in dusty conditions or at high ambient temperatures.
• Change the engine oil filter after the break-in peri-
od, and every twelve months thereafter.
To change the oil and/or oil filter, proceed as follows (see Figure 3.1):
1. Run the engine until it is thoroughly warmed up (at least five minutes) then shut OFF the engine.
2. Immediately after the engine shuts OFF, remove the plug from the tube with a 5/16” allen wrench and drain the oil into a suitable container. Loosening the oil fill/dipstick cap will allow the crankcase to drain faster.
3. After the oil has drained, replace the plug onto the end of the oil drain tube.
4. With the oil drained, remove the old oil filter by turning it counterclockwise. Place a towel under­neath to catch excess oil.
5. Apply a light coating of clean engine oil to the gas­ket of the new filter. Fill the filter until saturated with clean oil.
6. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tight­en the filter an additional 3/4 to one turn.
7. Remove the oil fill/dipstick cap and wipe the dip­stick dry with a clean, lint-free cloth. This will be used later to check the oil level.
8. Slowly add the proper type and amount of rec­ommended oil (see Section 1.6.3). Periodically use the dipstick to check the oil level and contin­ue to fill the crankcase until the oil reaches the dipstick “Full” mark. DO NOT FILL ABOVE THE “FULL” MARK.
9. Install and tighten the oil fill/dipstick cap before operating the engine.
10. Start the engine and check for leaks.
NOTE:
Check the oil level and fill to the “FULL” mark after checking for leaks. The filter will retain some oil.
!
Generac®Power Systems, Inc. 13
Figure 3.1 – Oil Maintenance Features
Dipstick & Oil Fill
Oil Drain
(Underneath)
Oil Filter
GENERATOR
FUSE
POWER
7.5A GREEN BAR INDICATES TRIP
PUSH TO RESET
PULL TO DISCONNECT
GENERATOR POWER
SHUT DOWN
INDICATOR
SEE CHART BELOW FOR
MAN.
AUTO
OFF
DETAILS
CONTROL CENTER
SERVICEACCESS PANEL
GENERATOR SHUTDOWN
S
O
E
N
O
L
INFORMATION SYSTEM
FAULTSIGNAL
2 FLASHES =
OVERCRANK
3 FLASHES =
OVERSPEED LOW OIL PRESSURE
4 FLASHES = 5 FLASHES =
HIGH OIL TEMP
6 FLASHES = UNDERSPEED
MAINTENANCE SCHEDULE
OIL LEVEL:
AIR FILTER:
LOCATED BEHIND PANEL
*
OIL & OIL FILTER:
SPARK PLUGS:
REPLACEMENT INFORMATION
PREFILTER P/N: AIR FILTER P/N: OIL FILTER P/N: SPARK PLUG P/N:
OIL CAPACITY WITH FILTER:
TEMPERATURE
40˚F AND HIGHER
-20˚F TO 40˚F
API SERVICE CLASSIFICATION SF, SG OR SH WHEN SERVICE OR PARTS ARE NEEDED IN
THE USA OR CANADA, CONTACT THE GENERAC
SERVICE LOCATOR AT 1-800-333-1322.
CHECK DAILY
CLEAN PREFILTER EVERY 100 HOURS. REPLACE ELEMENT EVERY 250 HOURS.
CHANGE EVERY 100 HOURS. (OR ANNUALLY)
PERFORM MORE OFTEN IN DUSTY CONDITIONS
*
INSPECT & CLEAN PLUGS EVERY 500 HOURS. REPLACE PLUGS IF NECESSARY
SAE VISCOSITY
SAE 30 OR 10W-30
5W-30 OR 5W-20
SEE OWNERS MANUAL FOR FURTHER EXPLANATION
}
*
*
*
0D4511 0D9723 070185 072347
0.8L/0.84QT
Page 16
14 Generac®Power Systems, Inc.
3.3 MAINTAINING THE ENGINE AIR CLEANER
3.3.1 CLEANING THE FOAM PRECLEANER
Clean and re-oil the foam precleaner every six months. Service the foam precleaner more frequent­ly if operating the generator in extremely dusty or dirty conditions. Use the following procedure (Figure
3.2):
Figure 3.2 — Engine Air Cleaner
1. Turn the two screws counterclockwise to loosen.
2. Remove the cover, foam precleaner and paper fil-
ter.
3. Remove the foam precleaner from the cover.
4. Wash the foam precleaner in liquid detergent and
water.
5. Wrap the foam precleaner in a clean cloth and
gently squeeze it dry.
6. Saturate the foam precleaner in clean engine oil.
Gently squeeze it in a clean cloth to remove excess oil and to distribute oil (DO NOT TWIST).
7. Install the foam precleaner into the cover, fol-
lowed by the paper filter.
8. Install the cover, foam precleaner and paper filter.
9. Tighten the two screws to retain the filter in place.
3.3.2 CLEANING OR REPLACING THE PAPER FILTER
Once each year or more frequently if operating in dirty or dusty conditions, clean or replace the paper filter. The new replacement filter must be flame retar­dant. Service the paper filter more frequently if oper­ating the generator in extremely dusty or dirty condi­tions. Use the following procedure (Figure 3.2):
1. Follow steps 1-3 in Section 3.3.1; service the foam precleaner if necessary.
2. Remove the paper filter.
3. Clean the air filter by tapping it gently on a solid surface. If the filter is too dirty, replace it with a new one. Dispose of the old filter properly.
4. Clean the air cleaner cover then reassemble fol­lowing steps 7-9 in Section 3.3.1.
3.4 CLEAN AIR INTAKE
Clean all foreign material from the air intake (Figure
3.3) at least once every six months. Clean more often if necessary.
Inspect the area around the generator periodically and remove all grass, leaves, etc., from area.
Figure 3.3 — Cleaning Air Intake
3.5 CHECKING THE ENGINE SPARK PLUG
Clean the spark plug and reset the spark plug gap annually. Replace spark plug when the electrodes have worn to the point where the proper gap cannot accurately be set, or if the insulation is cracked.
1. Clean the area around the base of the spark plug
to keep dirt and debris out of the engine. Remove the spark plug and check the condition. Replace the spark plug if worn or if reuse is questionable.
2. Clean spark plug by scraping or washing using a
wire brush and commercial solvent. Do not blast the spark plug to clean.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.030 inch (0.76 mm) by carefully bending the ground electrode (Figure
3.4).
Figure 3.4 — Setting the Spark Plug Gap
USTC
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
USTC
Page 17
Generac®Power Systems, Inc. 15
Sparking can occur if the wire terminal does not fit firmly on the spark plug terminal end. If necessary, re-form the wire terminal to obtain a tight fit.
3.6 CLEAN SPARK ARRESTOR
The engine exhaust muffler has a spark arrestor screen. Inspect and clean the screen at least once each year.
NOTE:
If using the generator on any brush-covered or grass-covered unimproved land, it must equipped with a spark arrestor. The spark arrestor must be maintained in good condition by the owner.
Clean and inspect the spark arrestor as follows:
• Remove the screen retaining bracket by removing the screw (Figure 3.5).
• Slide the spark arrestor screen out from the exhaust pipe.
• Inspect screen and replace if torn, perforated or otherwise damaged. DO NOT USE a defective screen. If screen is not damaged, clean it with com­mercial solvent.
• Replace the screen and the retaining bracket. Reinstall screw.
Figure 3.5 — Spark Arrestor
3.7 CLEANING THE GENERATOR
Keep the generator set as clean and dry as possible. Protect the unit against excessive dust, dirt, corrosive vapors, etc. Permitting dirt and moisture to accumu­late on generator enclosure reduces the effectivity of the power-coat paint to maintain color and appear­ance.
Do NOT use a forceful spray of water to clean the generator. Water will enter the generator interior and cause problems, and may also cause corrosion of brackets and linkage on the generator.
3.7.1 CORROSION PROTECTION
Periodically wash and wax the generator enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine linkage, steel brackets and fasteners with a light oil such as WD-40®.
3.8 BATTERY MAINTENANCE
All lead-acid batteries will discharge when not in use. The generator battery should be inspected as follows:
3.8.1 EVERY SIX MONTHS
• Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
• Check the battery fluid level of unsealed batteries and, if necessary, fill with Distilled Water Only. Do
not use tap water in batteries.
• Have the state of charge and condition checked. This should be done with an automotive-type bat­tery hydrometer if battery is not a maintenance free type.
NOTE:
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batter­ies and the required precautions. Keep unautho­rized personnel away from batteries. Damage will result if the battery connections are made in reverse.
Do not dispose of the battery in a fire. The bat­tery is capable of exploding. Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explo­sion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks, or any spark producing tools or equip­ment near the battery. Discharge static electrici­ty from body before touching the battery by first touching a grounded metal surface.
A battery presents a risk of electrical shock and high short circuit current. The following precau­tions are to be observed when working on bat­teries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the bat­tery;
!
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
!
EXHAUST PIPE
P/N 0E2138
SPARK ARRRESTOR SCREEN P/N 089680
RETAINING SCREW P/N 056892
DANGER
Page 18
16 Generac®Power Systems, Inc.
• Disconnect any charging source prior to connecting or disconnecting battery terminals; and
• Do not use any jumper cables or booster battery to crank and start the generator engine. If any bat­tery has discharged, remove it for recharging.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following proce­dures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek med­ical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to one gallon (4 liters) or water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
3.9 EXERCISING THE GENERATOR
Generac recommends that this unit be exercised at least once every seven days. This generator system does not have an automatic exerciser or a utility fed battery charger. The unit must be manually started and run in order to charge the starting battery and fully lubricate the engine. It is imperative that the bat­tery be fully charged in the event of a power outage to ensure that the generator starts automatically. Couple the exercising of the generator along with another task or activity that is done once a week.
3.9.1 TO EXERCISE THE GENERATOR:
• Make sure the AUTO/OFF/MANUAL switch located on the generator control panel is set in the AUTO position, and then depress and hold the EXER­CISE switch located on the Power Transfer Monitor for about ten seconds.
• The engine will start to crank and the unit will then start.
• The unit will exercise for an amount of time that is predetermined by the time that it takes for the gen­erator to crank and start. The unit will exercise approximately 1.5 minutes for every second that the starter motor cranks during engine start-up. The unit will run for a minimum of two minutes and a maximum of 20 minutes based on the crank time.
IMPORTANT: The generator power outlet located on the Power Transfer Monitor will be "LIVE" during this exercise cycle.
• After the generator completes its predetermined exercise cycle, the unit will enter a cool down cycle that will last approximately two minutes.
• The generator will then shut down, and the unit will return to automatic operation.
3.10 OUT OF SERVICE PROCEDURE
3.10.1 REMOVAL FROM SERVICE
If unable exercise the generator every seven days, or do not require the generator's services for an extend­ed period of time, please prepare the generator as fol­lows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valves on both propane
tanks and allow the unit to shut down.
3. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with SAE 10W-30 oil having API classification “For Service SF.”
4. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
5. Remove the spark plug and pour two or three
tablespoons of clean, fresh engine oil into the spark plug threaded openings. Reinstall and tighten the spark plug.
6. Disconnect battery cables (negative NEG or (—)
first). Remove the battery and store it in a cool, dry room on a wooden board. Never store the bat­tery on any concrete or earthen floor.
7. Clean and wipe the entire generator.
3.10.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommend­ed oil is used in the engine (see Section 1.6.3). If necessary, drain and refill with the proper oil.
2. Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with dis­tilled water. DO NOT USE TAP WATER IN THE BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery.
3. Clean and wipe the entire generator.
4. Reconnect the battery (positive POS or (+) first).
Observe battery polarity. Damage may occur if the battery is connected incorrectly.
5. Unplug any items plugged into the Power
Transfer Monitor’s GFCI outlets.
!
!
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
Page 19
Generac®Power Systems, Inc. 17
6. Start the unit by depressing and holding the EXERCISE switch on the Power Transfer Monitor for about ten seconds. Allow the unit to run for exercise cycle.
7. Re-plug items needing protection back into the Power Transfer Monitor’s switched GFCI outlet.
8. The generator is now ready for service.
3.11 ADJUSTING VALVE CLEARANCE
After the first six months, adjust the valve clearance in the engine.
When adjusting valve clearance, the engine should be at outdoor ambient temperature and the piston should be at Top Dead Center (TDC) of its compres­sion stroke (both valves closed). Correct clearance is
0.001-0.003 inch (0.03-0.07mm). Adjust valve clear-
ance as follows:
1. Loosen the rocker arm jam nut. Use an allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge (Figure 3.6).
Figure 3.6 — Adjusting Valve Clearance
2. When valve clearance is correct, hold the pivot ball stud with the allen wrench and tighten the rocker arm jam nut with a crows foot. Tighten the jam nut to 65-85 inch-pounds torque. After tight­ening the jam nut, recheck valve clearance to make sure it did not change (Figure 3.7).
Figure 3.7 — Tightening Jam Nut
3.12 GENERATOR SERVICE INTERVAL
CENTURION 3500
Annually ................................Clean Spark Arrestor
Annually..............................Change Engine Oil/filter
Every Six Months........................Clean Air Pre-filter
Annually....................................Inspect Spark Plugs
Annually................Replace Paper Air Filter Element
As Needed ................................Replace Spark Plugs
1st Six Months
Annually ..............................Adjust Valve Clearance
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
Page 20
18 Generac®Power Systems, Inc.
PART II –
INSTALLATION
INSTRUCTIONS
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION!!
DANGER
Page 21
Generac®Power Systems, Inc. 19

IMPORTANT SAFETY INSTRUCTIONS

CENTURION 3500 Home Standby Generator
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this manual and with the unit. The generator can operate safely, efficiently and reli­ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possible circumstance that might involve a hazard. The warn­ings in th is manual, and on tags and decals affixed to the unit, are, therefore, not all-inclusive. If using a procedure, work method or operating technique Generac does not specifically recommend, satisfy yourself that it is safe for others. Also make sure the procedure, work method or operating technique that chosen does not render the generator unsafe.
Despite the safe design of this generator, oper­ating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsi­ble and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GEN
ERAL HAZARDS
• For safety reasons, Generac recommends that the maintenance of this equipment is carried out by a Generac Authorized Service Dealer.
• The generator engine releases DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concentra­tions, can cause unconsciousness or even death. Never operate the generator inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOXIDE POISONING ARE (a) inability to think coherently, (b) nausea, (c) vomit­ing, (d) twitching muscles, (e) throbbing temples, (f) dizziness, (g) headaches, (h) weakness, and (i) sleepiness. IF EXPERIENCING ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDI­ATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. Shut down the generator and do not operate it until it has been inspected and repaired.
• The engine exhaust fumes contain carbon monox­ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compliance with applicable codes and standards. Following installation, do nothing that might render the sys­tem unsafe or in noncompliance with such codes and standards. Never operate this equipment with a leaking or defective exhaust system.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti­lating air is critical to correct generator operation and is required to expel toxic fumes and fuel vapors from the generator. Without sufficient cool­ing airflow, the engine/generator overheats, which causes serious damage to the generator. Do not alter the installation or permit even partial block­age of ventilation provisions, as this can seriously affect safe operation of the generator.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and contact the nearest Generac Authorized Service Dealer imme­diately for parts needing repair or replacement.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
!!!
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be fol­lowed during installation and maintenance of the generator and batteries.
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas near the generator set. Safety should be stressed to all operators and potential operators of this equipment.
!
!
!
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
!
!
!
!
DANGER
!
Page 22
20 Generac®Power Systems, Inc.
IMPORTANT SAFETY INSTRUCTIONS
CENTURION 3500 Home Standby Generator
• Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start-up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
• All generators covered by this manual produce dan­gerous electrical voltages and can cause fatal elec­trical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as well as the standby generator. Avoid contact with bare wires, terminals, connections, etc., on the gen­erator as well as the transfer switch, if applicable. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• If people must stand on metal or concrete while installing, operating, servicing, adjusting or repair­ing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
• The National Electrical Code (NEC), Article 250 requires the frame and external electrically con­ductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous elec­trical shock that might be caused by a ground fault condition in the generator set or by static electric­ity. Never disconnect the ground wire.
• Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maxi­mum electrical current (ampacity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make sure that all power voltage sup­plies are positively turned off at their source. Failure to do so will result in hazardous and pos­sibly fatal electrical shock.
• Connecting this unit to an electrical system nor­mally supplied by an electric utility shall be by means of a transfer switch so as to isolate the gen­erator electric system from the electric utility dis­tribution system when the generator is operating. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in
injury or death to utility power workers due to backfeed of electrical energy.
• Generators installed with an automatic transfer switch will crank and start automatically when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per­sonnel, disable the generator’s automatic start cir­cuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a noncon­ducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
• Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extinguish­er properly charged and be familiar with its use. Consult the local fire department for any questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
• Provide adequate ventilation around the generator to prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• Generac generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks imme­diately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equip­ment into service.
• Gaseous fluids such as liquid propane (LP) gas are extremely EXPLOSIVE. LP gas is heavier than air and settles in low areas; install leak detectors accordingly.
Page 23
Generac®Power Systems, Inc. 21

Section 1 – General Information

CENTURION 3500 Home Standby Generator
NOTE:
THE INSTALLATION SECTION OF THIS MANUAL SHOULD NOT BE USED EXCLUSIVELY FOR ALL ASPECTS OF INSTALLATION AND OPERATION OF THE CENTURION UNIT. FAMILIARIZE YOUR­SELF WITH ALL FEATURES AND OPERATION OF THE UNIT TO ENSURE SAFE USE. PLEASE READ ALL INFORMATION PRIOR TO INSTALLATION AND OPERATION OF THE CENTURION EMER­GENCY AUTOMATIC SYSTEM.
1.1 TOOLS REQUIRED
Drill, Drill Bits, Hole Saw (type and length will be determined by the materials that need drilling and cutting), Open-End Wrenches or Adjustable Wrenches, Socket Wrenches or Nut Drivers, Standard and Phillips Screwdrivers, Level, Sledge Hammer, Channel-lock Pliers, Spade Shovel, and Safety Goggles.
1.2 ITEMS THAT MUST BE
PURCHASED
• (2) 20 pound propane tanks. Acceptable tank types are DOT-4BA240 and DOT-4BW240.
• Grounding rod with grounding strap.
• Crushed stone or pea gravel (approximately 8-10 cubic feet).
• Black polyfilm or other vegetation blocking fabric (5-1/2 feet x 3-1/2 feet).
• Silicone caulk.
• Fasteners (To mount Power Transfer Monitor).
1.3 PLAN THE LOCATION OF THE
GENERATOR
Select an area outside of the home near the room that the Power Transfer Monitor will be located. It must be within two cords combined length (21”) of an inside outlet.
NOTE:
Do not place the generator directly under or next to a window.
4a
3 ft.
1
2
3
Page 24
22 Generac®Power Systems, Inc.

Section 2 – Installation

CENTURION 3500 Home Standby Generator
2.1 SITE PREPARATION AND GENERATOR PLACEMENT
2.1.1 SITE PREPARATION
1. Clear an area 5-1/2 feet by 3-1/2 feet of grass and
vegetation to a depth of five inches. This includes the distance the generator should be set away from a structure (three feet) and six inches beyond the width and length of the generator mounting pad (30" L x 24" W).
2. Lay black poly-film to cover the area.
3. Fill the area to ground level with pea gravel or
crushed stone.
2.1.2 ATTACH GENERATOR TO MOUNTING PAD
Place the mounting pad in the exact desired location. Bring the generator, still attached to the shipping pal­let, to the prepared area and place it along side of the mounting pad. Remove and discard the two (2) lag screws that hold the generator to the shipping pallet. Using a minimum of two adults, hold the mounting pad in place, gently slide the generator off of the ship­ping pallet and onto the mounting pad. Align the holes in the generator base with the holes in the mounting pad. Use the supplied fasteners to attach generator to base (Figure 2.1).
Four Each: 1” long hex head cap screw, lock washer and flat washer.
Figure 2.1 — Attach Generator To Pad
4. Drive an 8-foot grounding rod into the ground to grade.
A. Attach one end of the grounding strap (No. 12
AWG stranded copper wire) to grounding rod and the other end to the grounding lug (located at rear of unit). Make sure grounding rod and strap are not exposed above ground level. (NEC code applies to grounding method.)
Figure 2.2 — Grounding Lug
2.2 POWER CORD INSTALLATION
2.2.1 DRILL PASS THROUGH HOLE
The power transfer monitor needs to be located in a position that is appealing to the homeowner. Recommended locations are underneath or inside a kitchen or utility room cabinet, or in a basement where access is convenient. The homeowner should test multiple positions to find the most appealing one. It is not recommended that the power transfer monitor be located where water may be present, such as under a sink.
Determine where the flexible watertight conduit (power cord) will pass through the house from inside to outside (Figure 2.3). When certain there is clear­ance on each side of the wall and within the wall, mark the location. Drill a small pilot hole to aid loca­tion of hole saw. Drill 1-1/4 inch diameter hole through the wall with hole saw.
Figure 2.3 — Pass Through Hole
2.2.2 FEED POWER CORD OUT TO GENERATOR
From the room inside the home where the Power Transfer Monitor will be located, feed the end of the power cord through to outside of exterior wall (Figure
2.4). DO NOT connect power cord to generator at this time.
030795 SC
"
0
6"
0
3/8"
Grounding Lug
REW HHV 5/16"-18 X 1
22129 WASHER LOCK 5/1
22145 WASHER FLAT
Page 25
Generac®Power Systems, Inc. 23
Section 2 – Installation
CENTURION 3500 Home Standby Generator
Figure 2.4 — Feed Power Cord
2.2.3 GENERATOR CONNECTION
The power cord contains five wires with spade termi­nals. These wires are color coded and and labeled for accurate connection to the generator’s terminal strip.
NOTE:
Generator mode switch should be placed in the OFF position. Generator main circuit breakers should be placed in the OFF or OPEN position by pulling the reset buttons outward. A visible GREEN stripe should appear.
1. Remove the four screws that hold the cover plate in place at rear of generator. Remove cover plate.
2. Remove lock ring from the coupler on end of power cord. Feed wires through cover plate, Slip lock ring over wires and reattach lock ring to cou­pler. Tighten lock ring securely to assure that the coupler will not loosen during generator opera­tion.
3. Match the wires by color or by label to the match­ing terminal positions on the generator. Place the appropriate spade connectors under the match­ing terminal screws. (See Figure 2.5). Tighten the the terminal screws securely to prevent arcing.
4. Align cover plate over threaded holes. Reinstall and tighten the four screws that hold the cover plate to back of generator compartment.
Figure 2.5 — Generator Terminal Strip
Connection
2.3 MOUNT POWER TRANSFER MONITOR
Hold the Power Transfer Monitor in desired location and mark the mounting holes. The mounting holes are 1/4 inch in diameter. Drill pilot holes. Use two fasteners which are appropriate for the area for mounting the Power Transfer Monitor (Figure 2.6).
NOTE:
If mounting on drywall, it is suggested to use a fas­tener that spreads behind the hole for added rigid­ity. This is necessary because of the force that will be applied when plugging in and unplugging items from the GFCI outlets.
Figure 2.6 — Mount Power Transfer Monitor
NOTE:
DO NOT plug the six foot sensing cord into stan­dard household outlet at this time.
2.4 INSTALL PROPANE TANKS
This generator has been designed for a specific type of tank. Acceptable tank types are DOT-4BA240 and DOT-4BW240. Any deviation in tank type may not allow the tank to fit in the LP enclosure.
Slide the latches on the top of the mesh panel down­ward. Tilt the panel toward you and lift out The tank hold down brace is held in place by a large wingnut. Loosen the wingnut to allow the brace to face per­pendicular to the opening of the tank enclosure.
Tilt the top of the first tank toward you so the bottom of the tank enters the compartment first. Set the ring on the bottom of the tank into the recessed area of the tank tray. Place tank in upright position in the tank compartment. Repeat this process for second tank.
Position tanks so that the tank hold down brace can be brought down on top of tank flanges and flanges slip into grooved areas of brace.
17 0
N
L2
L1
RED
WHITE
BLACK
BLUE
GREEN
Page 26
24 Generac®Power Systems, Inc.
Section 2 – Installation
CENTURION 3500 Home Standby Generator
The changeover regulator needs to be placed at a height such that the inlet hoses are located even with or above the cylinder valves on the LP tanks. This will prevent LP vapor from condensing in the LP changeover regulator and possibly damaging the fuel system.
Tighten the wingnut securely to prevent vibration when the generator is running.
Connect the fuel lines by carefully threading the OPD (Overflow Protection Device) valves onto the tanks. Make sure the valve is not cross-threaded which will cause leaking. Open the valves on both tanks and swab connections with soapy water to detect any leaks. Be careful not to crimp the power cord when the power transfer monitor is in it’s final position.
If a leak is detected in the system near the green swiv­el connector, there is a possibility that the flare fitting inside the tank valve has been damaged during the tank filling process. To inspect the fitting, turn off the tank valve and visually inspect the flare fitting to make sure that there are no scratches, dents or mars on the surface of the flare. If there are visible defects in the flare fitting of the tank, a new tank must be used.
To assure that the hose does not kink, rub against the tanks or the enclosure, it is important to note the ori­entation of the valve on the tank. It should always be pointing towards the front of the cabinet. Do not allow the hose to kink or rub on the tank (Figure 2.7).
Figure 2.7 — Overhead View of LP Tank
On the propane tank changeover valve, move the black selector lever to the left or to the right to desig­nate which tank will be the primary or service cylin­der (tank). That tank will supply fuel to the generator first. When the lever is moved to a position an indi­cator will show green. When that tank empties during generator operation the indicator will show red sig­nalling the need to refill the tank. The generator will start drawing from the reserve cylinder. The changeover feature allows gives the benefit of unin­terrupted fuel flow to the generator.
Prior to disconnecting the service cylinder, rotate the black lever all the way over towards the reserve cylin­der. (Figure 2.8). DO NOT ATTEMPT TO CHANGE
THE LP TANK WITHOUT ROTATING THIS LEVER. The full-empty indicator will turn green and
the reserve cylinder becomes the service cylinder. Refill and reinstall the empty cylinder to maintain interruption free back up power.
For model 254-00, two-stage changeover regu­lator, failure to rotate the black lever all the way over towards the reserve cylinder will allow propane to leak from the disconnect pig­tail. Leaking propane, if ignited, will result in a fire that may cause property damage, bodily injury or death. REMEMBER: NEVER disconnect a pigtail if the indicator is RED.
IMPORTANT: Only qualified persons should install, adjust or service LP ga regulators. If service is need­ed, contact a qualified LP dealer. Always make sure cylinders are properly filled and never accept cylin­ders that are over filled. When replacing newly filled cylinders to the regulator, check all connections for leaks with an approved leak detector solution or a mixture of non-ammonia soap and water. Never use matches or an open flame.
NOTE:
Low pressure regulators are designed to regulate LP vapor only.
Figure 2.8 – LP Tank Changeover Valve
Selector Lever
Full/Empty Indicator Window
Green - Full
Red - Empty
DANGER
Page 27
Generac®Power Systems, Inc. 25
2.5 SET SYSTEM FOR AUTOMATIC OPERATION
Make sure the valves on both of the filled propane cylinders are open.
At this time, plug the six foot sensing cord into a stan­dard 120V household outlet. This will allow the Power Transfer Monitor to sense the utility power feed. Plug desired items into the SWITCHED GFCI outlet on the Power Transfer Monitor. This outlet is powered when utility power is available and when the generator is operating during a utility power outage.
Place the generator main circuit breakers to their ON or CLOSED position by pressing in the reset buttons. The GREEN indicator stripe should no longer be evi­dent.
Place the generator mode switch, which is located on the generator control panel, in the AUTO position.
The system is now set for automatic operation.
2.6 HOW TO KEEP THE REGULATOR OPERATING EFFICIENTLY & SAFELY
The regulator is equipped with a vent which allows the diaphragm to “breathe”. The diaphragm of the regulator moves down and draws air into the bonnet of adjustment spring housing. When the diaphragm moves up, air is expelled through the vent. In the event that excess pressure builds up in the lower housing or body of the regulator, a relief mechanism vents it to the atmosphere. It is imperative to check the vent frequently to be sure it is clean and free of water, corrosion or obstruction, as clogging is a potential cause of regulator malfunction. Great care has been taken in the manufacture of the regulator and it has been thoroughly tested and UL listed.
However, even a small piece of dirt, corrosion, pipe dope or other foreign material which finds its way into the regulator can result in higher than normal pressure (high lockup) and/or loss of fuel.
If the vent does become clogged it can easily be cleaned with a toothbrush. In addition, the regulator should be checked periodically by a competent LP serviceman to be sure it is properly adjusted and in safe working condition. By following these simple precautions, the regulator should give you years of trouble-free service.
2.7 WHAT IS REGULATOR FREEZE UP?
A regulator will not freeze, nor will LP gas under nor­mal atmospheric conditions. However, as the gas passes through the regulator it expands and cools and moisture in the gas or in the regulator may turn to ice. This ice can build up and totally or partially block the orifice and thus partially or totally block the fuel supply. There are a number of things that can be done to prevent this type of freeze up.
1. Be sure the LP cylinder is totally free of moisture before it is filled.
2. Be sure the cylinder is not over filled. This is par­ticularly important if you have a permanently mounted ASME tank.
3. Keep the valves on empty cylinders closed.
4. Have the LP gas dealer purge the cylinder if freeze up occurs.
5. Have the LP gas dealer inject methyl alcohol in the cylinder.
Section 2 – Installation
CENTURION 3500 Home Standby Generator
Page 28
26 Generac®Power Systems, Inc.

Appendix 1 – Troubleshooting

CENTURION 3500 Home Standby Generator
TROUBLESHOOTING GUIDE
SYMPTOM CAUSE CORRECTION
The engine will not crank. 1. Fuse blown 1. Replace fuse.
2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary.
3. Defective starter contactor 3. Replace contactor.
4. Defective starter motor 4. Replace starter motor.
5. Low or defective battery 5. Charge or replace battery.
OVERCRANK – 2 flashes of LED 1. No fuel to the engine. 1. Make sure that the tanks are full and
the valves are opened.
2. Crimped fuel hose or hoses. 2. Check all fuel hoses to ensure that
there is no crimping and fuel is being allowed to flow freely.
3. Defective fuel solenoid. 3. *
4. Open #14 wire from engine 4. * control board.
5. Defective spark plug/plug wire 5. Clean, re-gap, or replace plug/ not connected. connect plug wire.
OVERSPEED - 3 flashes of LED 1. Governor spring is disconnected. 1. Reconnect spring. Spring should be in
the second hole from the bottom (shaft end) of the governor arm.
2. Governor spring is broken. 2. Replace spring. *
3. Governor arm or linkages are 3. * loose or broken.
LOW OIL PRESSURE - 1. Engine oil is low. 1. Check and fill engine oil. Check 4 flashes of LED generator compartment for leaks.
2. Oil Pressure switch is defective. 2. *
3. Oil is contaminated with dirt. 3. Change oil and oil filter.
HIGH TEMPERATURE - 1. Engine oil is low. 1. Check and fill engine oil. 5 Flashes of LED 2. Air flow is restricted. 2. Check airflow openings for blockage.
3. Spark arrestor is plugged. 3. Clean or replace the spark arrestor.
4. Oil is contaminated with dirt. 4. Change oil and oil filter.
UNDERSPEED - 6 flashes of LED 1. Fuel supply is low. 1. Check and replenish fuel supply.
2. Speed adjust linkage is damaged 2. * or control nut is loose.
The engine starts hard 1. Air cleaner plugged or damaged 1. Check, clean or replace air cleaner. and runs rough.
2. Defective spark plug 2. Clean, re-gap or replace plug.
The engine starts, but shuts 1. Engine oil level low 1. Check oil and add oil as needed. down immediately. 2. Defective low oil pressure switch 2. *
3. Defective high temperature switch 3. *
4. Defective engine control board 4. *
5. Overheated engine 5. Check that the airflow openings are
adequate. The AUTO/OFF/MANUAL switch 1. Defective switch 1. * is set to OFF, but the engine 2. AUTO/OFF/MANUAL switch 2. * continues to run. is wired incorrectly
3. Defective engine control board 3. * There is no AC output from 1. Main line circuit breaker(s) 1. Reset circuit breaker(s) the generator. open to ON (or closed).
2. Generator internal failure 2. * There is no transfer to utility. Defective transfer relay *
* Contact the nearest Generac Authorized Service Dealer for assistance.
Page 29
Generac®Power Systems, Inc. 27
Appendix 2 – Notes
CENTURION 3500 Home Standby Generator
Page 30
28 Generac®Power Systems, Inc.
Appendix 2 – Notes
CENTURION 3500 Home Standby Generator
Page 31
Generac®Power Systems, Inc. 29
Appendix 2 – Notes
CENTURION 3500 Home Standby Generator
Page 32
CK
CUSTO
D
OP
O
86
85
D
CO
OL
SM
6
SC
8A
3
0
56
85
86
8A
85
J1
3891053
6
8
8A
56
3
0
G
0
S
0
5
C
R
3
3
5
86
5
0
0
5
3
5
66766
5
85
86
85
85
86
8A
56
0
0
0
0
0
0
0
0
8A
SP
C
0
0
8
0
0
0
0
8
0
8
SW1
5
0
0
0
0
0
0
0
0
0
0
0
0
86
0
0
0
0
0
000
0
0
0
Y
D
P
T
S
A
A
A
S
OR
SC
OR
SSU
CH
D
GRD3
D
A
GFC
T
G
D
C
R
N
CB 3
R
D
E
E
CH
OR
OR
OR
OR
S
UG
.
CIC
C
R
CB 5
R
L
S
30 Generac®Power Systems, Inc.

Appendix 3 – Electrical Data

CENTURION 3500 Home Standby Generator
Wiring Diagram - Drawing No. 0E4263-A
LEGEN
BA - BRUSH ASSEMBL
CB 1 - 2A CIRCUIT BREAKER, AUTO RESET, ALT. EXCITATIO
B 2 - 15A 1 POLE CIRCUIT BREAKE
- 15A 1 POLE CIRCUIT BREAKE
B 4 - 15A 1 POLE CIRCUIT BREAKE
- 15A 1 POLE CIRCUIT BREAKE D - DIOD F1 - FUSE, 7.5 FS - FUEL SOLENOI
I - GROUND FAULT CIRCUIT INTERUP
RD1 - CONTROL PANEL GROUN
GRD2 - CONTROL PANEL GROUND, ISOLATE
- POWER STRIP GROUN
HTO - HIGH OIL TEMPERATURE SWIT IC - INLINE CONNECT IM - IGNITION MODUL L1 - UTILITY PRESENT INDICAT L2 - GENERATOR RUNNING INDICAT
LED - ALARM INDICAT LOP - LOW OIL PRE
- STARTER CONTACT M - STARTER MOT
P - SPARK PL
SR - REMOTE START RELAY, SPST, 120V COIL, 250V 5A CONTACT OPEN = UTILITY PRESENT, CLOSED = UTILITY NOT PRESEN SW1 - AUTO-OFF-MANUAL SWITCH, ON-OFF, 125V, 15 SW2 - POWER SWITCH, ON-OFF, 125V, 15 SW3 - EXCERCISE SWITCH, (ON)-OFF, 250V, 5
TB1 - TERMINAL STRIP, GEN. TO POWER STRI TB2 - TERMINAL STRIP, POWER STRIP TO GEN
TB3 - TERMINAL STRIP, STATOR TO CONTROL PANE
TR - TRANSFER RELAY, SPDT, 120V COIL, 250V 20A CONTACT
RE SWIT
ENGINE WIRIN
I
HARGE
1
1
F
7
1
1
HT
1
L
1
BLA
1
1
NTR
PRINTED CIRCUIT BOAR
1
1
1
17
1
1
I
1
1
1
1
1
1
17
MER SUPPLIE
1
Page 33
Generac®Power Systems, Inc. 31
CLOSES
G
GE
OR
62
0
6
4
66
62
6
G
2
6
0
CO
OX
66
66
CB1
62
6
S
OR
000
0
0
0
0
0
0
D
3
5
D
OT
OT 5
6
5
0
0
0
0
0
0
0
0
U
Y
G
OR
SR
SW3
0
0
0
0
CB2
CB3
0
66
C
P
G
0
GFCI
GFCI
0
G
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
S
D
0
G
G
0
0
0
0
0
0
0
0
0
0
DLOAD
G
3
CB4
CB5
G
CO
OX
R
3
CUSTOMER
CO
ON
C
C
G
G
G
G
)
)
)
)
)
.
Appendix 2 – Electrical Data
CENTURION 3500 Home Standby Generator
Wiring Diagram - Drawing No. 0E4263-A
VOLTA
REGULAT
NTROL PANEL B
1
TB
6
1
1
RD
T TO BEARIN
TAT
WITCHE
LOA
H
LOA
HITE
H
CUSTOME
NNECT B
11
RD
11
RD
15 FT
POWER STRI
RED (L1
WHITE (N
BLACK (L2
BLUE (17
GREEN (0
TILIT
ENERAT
LOA
WIRIN
11
11
11
11
NNECTI
Page 34
GE
C
R
C
R
BATTERY
T
A
D
5
CO
OL
86
8
0
56
56
5
5
5
8
85
56
56
5
8
8
86
86
85
8
8
0
8A
8A
8586018A
E
CB 3
R
N
C
R
CH
E
A
OR
D
OR
0
6
62
3
66
5
0
SW1
913
0
6
8
5
J1
3
0
0
0
0
6
3
56
CB 1
5
85
86
8A
0
0
0
6
6
OR
SSU
CH
SC
OR
S
OR
A
A
S
S
D
Y
CO
OL
0
0
CB 4
CB 5
C
R
CB 5
R
32 Generac®Power Systems, Inc.
Appendix 3 – Electrical Data
CENTURION 3500 Home Standby Generator
Wiring Diagram - Drawing No. 0E6560
LEGEN
BA - BRUSH ASSEMBL
CB 1 - 2A CIRCUIT BREAKER, AUTO RESET, ALT. EXCITATIO
B 2 - 15A 1 POLE CIRCUIT BREAKE
- 15A 1 POLE CIRCUIT BREAKE
B 4 - 15A 1 POLE CIRCUIT BREAKE
- 15A 1 POLE CIRCUIT BREAKE D - DIOD F1 - FUSE, 7.5 FS - FUEL SOLENOI HTO - HIGH OIL TEMPERATURE SWIT IM - IGNITION MODUL
L1 - UTILITY PRESENT INDICAT L2 - GENERATOR RUNNING INDICAT
LED - ALARM INDICAT LOP - LOW OIL PRE
- STARTER CONTACT
M - STARTER MOT
SR - REMOTE START RELAY, DPDT, 120V COIL, 250V 5A CONTACT SW1 - AUTO-OFF-MANUAL SWITCH, DPDT, ON-OFF-ON, 125V, 15 SW2 - EXCERCISE SWITCH, (ON)-OFF, 250V, 5
TR - TRANSFER RELAY, SPDT DM-DB, 120V COIL, 250V 20A CONTACT
RE SWIT
HARGE
1
1
1
ELECTRONI
VOLTA
REGULATO
NTR
1
1
1
17
1
1
17
1
1
1
NTR
PRINTED CIRCUI
BOAR
1
17
18
1
1
1
1
Page 35
Generac®Power Systems, Inc. 33
Appendix 3 – Electrical Data
CENTURION 3500 Home Standby Generator
Wiring Diagram - Drawing No. 0E6560
SP
0
SC
SC
SM
S
0
0
0
0
0
O
OP
G
C
GE
E
G
UN
G
0
6
S
OR
6
66
66
66
66
66
3
6
8A
8A
56
6
0
0
0
6
86
85
0
0
3
D
OR
000
0
5
CB 2
0
L
A
C
C
O
C
ONLY
G
OR
T
0
0
0
G
OR
T
U
Y
OR
0
C
7
2
0
2
0
C
0
CB 3
0
2
0
0
1
0
CH
R
/
R
SR
3
4
7
G
ENGINE AN
HAR
WINDIN
ALTERNAT
1
1
L
HT
1
F
1
1
DPE WINDIN
TAT
ENGIN
R
WINDIN
11
4
NN 1-4
NN 1-
N
N
NEUTRA
NN 1-1
NN 1-2
NN 1-
11
11
11
11
2
1
1
11
2
11
1
1
2
POWE
TRIP
TRANSFE
WIT
OUTLE
ENERAT
OUTLE
TILIT
ENERAT
Page 36
34 Generac®Power Systems, Inc.
5

Appendix 4 – Exploded Views & Parts Lists

CENTURION 3500 Home Standby Generator
Enclosure - Drawing No. 0E2150
4
1
7
8
4
9
2
2
1
2
Page 37
Generac®Power Systems, Inc. 35
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Enclosure - Drawing No. 0E2150
ITEM PART NO. QTY. DESCRIPTION
1 0D3037 1 LATCH, QUARTER TURN LOCKING 2 0E2046 1 PANEL, GENERATOR ENCLOSURE DOOR 3 0E5686 1 FOAM, DOOR 4 0C7781 1 PAWL, DOOR 5 0E6551 1 PANEL AIR BOX COVER 6 064113 1 SCREW, M6-1.00 X 20MM WING 7 0A2115 1 WASHER NYLON .250" 8 0E2108 1 COMPARTMENT, AIR INTAKE
9 0E2109 1 PANEL, FRONT DIVIDER 10 0A7215 20 SCREW SW ¼"-20 X 5/8" WITH NYLON WASHER 11 0D3700 18 NUT FLANGE M6-1.0 NYLOK 12 029451 2.5 TAPE FOAM 1/8" X ½" 13 075763A 2 BOOT BATTERY CABLE 14 022127 2 NUT HEX ¼"-20 15 022097 2 WASHER LOCK M6-1/4" 16 0742600144 1 CABLE, STARTER 17 388040AL0 1 CABLE, BATTERY CONNECTION 18 086729 1 CONTACTOR, STARTER 19 029451A 8.75' FOAM TAPE 1/16" X ½" 20 0E2047 1 PANEL, GENERATOR ENCLOSURE ROOF 21 0E5685A 1 FOAM, ROOF FAN COMPARTMENT 22 0E5685 1 FOAM, ROOF 23 0E2049 1 PANEL, GENERATOR ENCLOSURE SIDE & BACK 24 0C2506A 3 MESH, DOOR PANEL 25 0D7176 12 WASHER SELF LOCKING 1"DIA 12GA 26 0D8254 1 SHIELD, MUFFLER 27 0E2099 1 PANEL, REAR DIVIDER 28 0E5685C 1 FOAM, ENGINE COMPARTMENT FRONT 29 0E5685B 2 FOAM, FAN COMPARTMENT FRONT & BACK 30 0E2048 1 PANEL, GENERATOR ENCLOSURE SIDE 31 0E3926 2 SCREW, SHOULDER M6-1.0 32 0E5685F 1 FOAM, EXHAUST DUCT RIGHT SIDE 33 0E5685D 1 FOAM, EXHAUST DUCT BACK PANEL 34 0E5685E 1 FOAM, EXHAUST DUCT LEFT SIDE 35 0E1789 1 DUCT, AIR OUT 36 0E2050 1 TRAY, GENERATOR ENCLOSURE 37 082121C 1 CLIP-J VINYL COAT 0.625" ID 38 0E0361 1 DIPSTICK 39 0E0724A 1 ASSEMBLY OIL DRAIN 40 0E2039 1 COVER, CONNECTION ACCESS PANL 41 0E2045 1 BOX, ELEC CONNECTION 42 096021 2 GROMMET 0.75" X 0.06" X 0.50" 43 075476 2 SCREW PPHM M4-0.7 X 16MM 44 0E2110 1 BLOCK TERM 15A 6 X 5 X 1100V 45 022264 4 WASHER LOCK #8-M4 46 051715 2 NUT HEX M4-0.7 47 090388 7 SCREW HHTT M6-1.0 X 12 48 023484S 1 BUSHING SNAP 49 0A9973 2 RIVET POP 0.125" X 0.337" 50 0E4854 1 BRACKET, DOOR LATCH 51 022471 2 NUT HEX #8-32 52 0E6451 1 GASKET, CONTROL PNL ACCESS 53 0E1330 1 GROMMET, 38.1 DIA. CROSS SLIT 54 0E2043 1 POWER STRIP 55 0E7088 1 LED, GREEN 56 0E7088A 1 LED, WHITE
Page 38
36 Generac®Power Systems, Inc.
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Generator - Drawing No. 0E2151-A
4
1
2
7
Page 39
Generac®Power Systems, Inc. 37
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Generator - Drawing No. 0E2151-A
ITEM PART NO. QTY. DESCRIPTION
1 050322 1 SCREW IHHC 5/16"-24 X 9-3/4"
2 022129 16 WASHER LOCK M8-5/16"
3 049451 1 WASHER FLAT .406" I.D. X 1.62" O.D.
4 0C8096A 1 FAN, 8" CURVE BLADE, 16.5MM I.D.
5 0D8120 4 SCREW IHHC M8-1.25 X 260MM
6 066849 2 SCREW HHTT M5-0.8 X 16MM
7 066386 1 ASSEMBLY, BRUSH HOLDER
8 0D4217 1 CARRIER, REAR BEARING
9 073159 1 BEARING 10 0E2089H 1 ROTOR 11 0E2101H 1 STATOR 12 0D4216 1 ADAPTOR, ENGINE 13 048614 4 SCREW HHC 5/16"-24 X 3/4" 14 0D2588A 1 GASKET, FRONT DIVIDER 15 089476 1 GASKET, EXHAUST 16 027028 4 NUT LOCK HEX 5/16"-18 NYLON INSERT 17 0D6832 1 BRACKET, ENGINE MOUNTING 18 022145 19 WASHER FLAT 5/16" 19 030231 3 SCREW HHC 5/16"-18 X 1-1/2" 20 0C3168 4 5/16" SPECIAL LOCK WASHER 21 022259 8 NUT HEX 5/16"-18 22 0C8565 1 SCREW SHC M8-1.25 X 18MM 23 0D8048 4 VIBRATION MOUNT 24 083512 6 SCREW HHTT M8-1.2 X 16MM 25 0D6831 1 BRACKET, ALTERNATOR MOUNTING 26 029451 2.14' TAPE ELEC. UL FOAM 1/8" X 1/2" 27 0E2098 1 DUCT, ALTERNATOR AIR IN 28 0D2558 1 GASKET, ALTERNATOR DUCT 29 087680 2 NUT WING M6-1.0 30 0D7530 1 STUD, M6-1.0 OFFSET 31 0D9723 1 ELEMENT, AIR FILTER 32 0D4511 1 PRECLEANER, AIR 33 0D8451 1 WASHER FLAT .281" I.D. X 1.50" O.D. 34 022097 1 WASHER LOCK M6-1/4" 35 0E2044 1 MUFFLER 36 090388 2 SCREW HHTT M6-1.0 X 12MM 37 045771 1 NUT, HEX M8-1.25 38 022531 1 SCREW HHC 5/16"-18 X 1-3/4" 39 0C2417A 1 EARTH STRAP 3/8" X 3/8" 40 025145 1 BOLT U 5/16"-18 X 1.25" WITH SADDLE 41 0E2138 1 TAILPIPE 42 022142 4 SCREW HHC 5/16"-18 X 3/4" 43 0D8981 1 FILTER GASKET
Page 40
38 Generac®Power Systems, Inc.
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Control Panel - Drawing No. 0E2152-A
Page 41
Generac®Power Systems, Inc. 39
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Control Panel - Drawing No. 0E2152-A
ITEM PART NO. QTY. DESCRIPTION
1 0E4914 1 PCB CONTROL ASSEMBLY 2 0E8331 1 BATTERY CHARGER ASSEMBLY 3 083049 1 VOLTAGE REGULATOR 4 049226 6 WASHER LOCK M5 5 075235 6 SCREW HHC M5-0.8 X 30MM 6 049813 4 NUT HEX M6 X 1.0 7 022097 2 WASHER LOCK M6-1/4" 8 022473 2 WASHER FLAT 1/4"-M6
9 0A1658 1 WASHER LOCK SPECIAL 1/4" 10 075476 2 SCREW PPHM M4-0.7 X 16MM 11 048766 1 TERMINAL STRIP, 2 POSITION 12 0E5840 2 CIRCUIT BREAKER 15A PUSH/PULL MAIN RESET 13 0E2042 1 INDICATOR LIGHT 14 0A9611 1 FUSE AGC-7.5A 15 032300 1 FUSE HOLDER 16 0E4494 1 SWITCH ROC DPDT ON-OFF-ON 17 0E5103 1 CONTROL PANEL FRONT 18 057159 1 CIRCUIT BREAKER, DPE 19 031879 2 WASHER FLAT #4 20 043182 2 WASHER LOCK M3 21 051714 2 NUT HEX M3-0.5 22 0D3700 3 NUT FLANGE M6-1.0 NYLOK 23 0E4584 1 BAFFLE, ENGINE INTAKE 24 023484R 2 SNAP BUSHING, 1.25" 25 022264 2 WASHER LOCK #8-M4 26 0D5303 1 WASHER FLAT 0.25" I.D. X 1.00" O.D.ZINC 27 049721 2 SCREW HHC M6-1.0 X 35MM 28 090388 4 SCREW HHTT M6-1.0 X 12MM 29 051715 2 NUT HEX M4-0.7 30 0E6553 1 ISOLATOR/SHOULDER WASHER NYLON 31 0E6553A 1 WASHER NYLON 0.50" X 0.32" X 0.12"
Page 42
40 Generac®Power Systems, Inc.
1
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Gn-220 H/SH Engine - Drawing No. 0E2153-A Part 1
1
7
4
2
4
Page 43
Generac®Power Systems, Inc. 41
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Gn-220 H/SH Engine - Drawing No. 0E2153-A Part 1
ITEM PART NO. QTY. DESCRIPTION
1 0D8433 1 GUARD, FAN
2 0C1069 10 SCREW, HHTT M6-1.0 X 8MM
3 090695F 1 BLOWER HOUSING
4 081810 1 NUT, HEX M16-1.5
5 083312 1 WASHER, M16 CONICAL
6 0E2091 1 BRACKET, GOV SPEED ADJUST
7 0C8917D 1 FLYWHEEL, WITH RING GEAR
8 0C8798A 1 BACKPLATE, ELECTRIC START
9 045756 9 SCREW HHTT M6-1.0 X 10MM 10 082774 1 KEY, WOODRUFF 4 X 19D 11 022129 2 5/16"-M8 LOCK WASHER 12 081990 2 SCREW SHC M8-1.25 X 40MM 13 0D9004A 1 STARTER ASSEMBLY 14 072347 1 SPARKPLUG 15 022097 2 LOCKWASHER, ¼"- M6 16 082981 2 TAPTITE, M6-1.0 X 30MM 17 081675 1 ASSEMBLY, IGNITION COIL 18 0C2018 2 WASHER 19 0D7666 1 BREATHER TUBE 20 090051 1 GASKET, MANIFOLD/ HEAD 21 080316 2 SCREW HHFC M6-1.0 X 30MM 22 090948 1 INTAKE MANIFOLD 23 078631 1 GASKET CARBURETOR/MANIFOLD 24 0E2094 1 CARBURETOR 25 091846 1 GASKET, CARB/ ADAPTOR 26 0D7558 1 ADAPTOR, CARB 27 078643 2 BOLT, CARB MOUNT M6-1.0 X 75MM 28 0D8372 1 GASKET, CARB TO AIRBOX 29 0C2756 1 ASSEMBLY, GOVERNOR LEVER 30 0D7458 1 ROD, GOVERNOR 31 0C3979 1 SPRING, ANTI LASH 32 085953 1 WASHER, CARB WEAR 33 0D8739A 1 ASSEMBLY BRACKET GOVERNOR ADJUST 34 0D9689 1 ELBOW 90D STREET 1/8NPT 35 0E7019 1 SPRING, GOVERNOR 36 083512 1 SCREW HHTT M8-1.2 X 16MM 37 082025 1 NUT HEX LOCK M5-0.8 NYLOCK 38 092984 1 TOP WRAPPER 39 094820 1 PLUG, EXPANSION 40 089739 1 LOWER WRAPPER 41 091848 1 GASKET, OIL PSI PAD 42 0D8778 1 ADAPTER, OIL FILTER 43 0D8803 2 SCREW SHC M6-1.0 X 22MM 44 0A8584 1 SWITCH, OIL- 10 PSI 45 070185 1 FILTER, OIL 52 075281 1 SWITCH, THERMAL 284F 53 043182 2 WASHER LOCK M3 54 0C1085 2 SCREW PPHM M3-0.5 X 8MM
Page 44
42 Generac®Power Systems, Inc.
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Gn-220 H/SH Engine - Drawing No. 0E2153-A Part 2
1
2
7
2
1
Page 45
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Gn-220 H/SH Engine - Drawing No. 0E2153-A Part 2
Generac®Power Systems, Inc. 43
ITEM PART NO. QTY. DESCRIPTION
N/A 0E7400 1 LONG BLOCK ASSEMBLY
1 078621 1 CONNECTING ROD ASSEMBLY
2 076389 1 PISTON PIN
3 088411 1 PISTON RING SET
4 0A8897B 1 GEAR COVER ASSEMBLY
5 077168 5 M8 X 56MM HEAD BOLT
6 088057 1 PISTON
7 076390 2 PIN RETAINER RING
8 083337A 1 TAPERED CRANKSHAFT ASSEMBLY
9 078658 1 GOVERNOR "R" PIN 10 078659 1 GOVERNOR ARM THRUST WASHER 11 089213E 1 CRANKCASE ASSEMBLY 12 0A7637 1 GOVERNOR ARM 13 0E3811 2 OIL SEAL 14 0D1303 1 GOVERNOR GEAR ASSEMBLY 15 078645 1 GOVERNOR GEAR C-RING 16 0A7811 1 GOVERNOR SPOOL 17 072683A 1 1/8" NPT PIPE PLUG 18 0A9878 1 CAMSHAFT ASSEMBLY 19 089096 1 CRANKCASE GASKET 20 088156 1 VALVE STEM SEAL 21 0A8822 1 CYLINDER HEAD GASKET 22 078691 1 OIL PRESSURE RELIEF COVER 23 0A5772 1 OIL PRESSURE SPRING 24 0A5776 1 11/32" BALL 25 074908 1 M5 FORM SCREW 26 078606 4 M6-1.0 X 12MM SCREW 27 076361 1 GOVERNOR GEAR THRUST WASHER 28 0D2414 6 SCREW, HHFC M8-1.25 X 35MM 29 099922 1 SPRING WASHER 30 0C3733 2 VALVE RETAINER 31 0C4390 2 VALVE SPRING 32 084186 2 V ALVE SPRING WEAR WASHER 33 083192 1 GEROTER SET 34 0E0057 1 "O" RING 35 078699B 4 SLEEVE, SEAM DWL 36 021705B 1 CYLINDER HEAD ASSEMBLY 37 0C3590 1 EXHAUST VALVE 38 0C3591 1 INTAKE VALVE 39 0D9853A 2 PUSH ROD 40 083235 2 TAPPET 41 080336 1 OIL PICK-UP ASSEMBLY 42 0C8754 1 ROCKER COVER GASKET 43 077161 2 PIVOT BALL STUD 44 077160 2 GN- 191/220 ROCKER ARM 45 076307 2 ROCKER ARM JAM NUT 46 088403 1 PUSH ROD GUIDE PLATE 47 026073A 1 1/4" NPT PIPE PLUG 48 088412C 1 ROCKER COVER ASSEMBLY 49 076329 1 PLASTIC OIL FILL PLUG 50 0C3592 4 VALVE SPRING KEEPER 51 049340A 1 BARBED ELBOW 90 1/4" NPT X 3/8" 52 045761A 1 STUD M8-1.25 / 10MM X 30MM
Page 46
44 Generac®Power Systems, Inc.
GU
O
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Tank Enclosure - Drawing No. 0E2154-A
1
2
1
R
7
4
LAT
2
E
Page 47
Generac®Power Systems, Inc. 45
ITEM PART NO. QTY. DESCRIPTION
1 0A6111 1 HOLD DOWN SPIN WITH NUT
2 0E2132 1 BRACKET, REGULATOR ASSEMBLY
3 022774 2 SCREW PPH #8-32 X 3/8"
4 0E4112 2 FUEL LINE (TANK TO REGULATOR)
5 0A6101 1 REGULATOR ASSEMBLY
6 0E4113 1 FUEL LINE (REGULATOR TO REGULATOR)
7 0A6110 1 DUAL TANK HOLD DOWN
8 0E2040 1 RETAINING ROD
9 022241 4 NUT HEX 3/8"-16 10 022237 4 WASHER LOCK 3/8" 11 022131 7 WASHER FLAT 3/8" 12 0E2061 1 DOOR, TANK ENCLOSURE 13 0C5644 2 SLIDE LATCH, FLUSH 14 0E2041A 1 MOUNTING PAD 15 030795 4 SCREW HHC 5/16"-18 X 1" 16 022287 2 SCREW HHC ¼"-20 X ¾" 17 0E2090 1 BATTERY 18 0388040AL0 1 BATTERY CABLE (POSITIVE) 19 0388050AG0 1 BATTERY CABLE (NEGATIVE) 20 022473 6 WASHER FLAT ¼"- M6 21 022097 6 WASHER LOCK M6-1/4" 22 022127 2 NUT HEX ¼"-20 23 023484D 2 BUSHING SNAP 24 0E1330 1 GROMMET 25 0E3199 1 TOP RAIL, FUEL ENCLOSURE 26 0E1788 2 MOUNTING FRAME ASSEMBLY LP ENCLOSURE 27 0E3163 1 BOX, BATTERY & REGULATOR 28 0C8285 1 BRACKET, BATTERY HOLD DOWN 29 0E2038 1 PANEL, TANK ENCLOSURE BACK 30 0E3164 1 COVER, BATTERY & REG BOX 31 0E1805 1 TRAY, TANK ENCLOSURE 32 022142 16 SCREW HHC 5/16"-18 X 3/4" 33 047411 4 SCREW HHC M6-1.0 X 16MM 34 045764 4 SCREW HHTT M4-0.7 X 8MM 35 090388 9 SCREW HHTT M6-1.0 X 12MM 36 0E2066 2 PANEL, TANK ENCLOSURE SIDE 37 027028 16 NUT LOCK HEX 5/16-18 38 075763 1 BOOT BATTERY CABLE 39 0A9973 16 RIVET POP 0.125" X 0.337" 40 029451 2 FT FOAM TAPE 41 0D3167 1 GASKET, BATTERY HOLD DOWN 42 082121C 1 CLIP-J VINYL COAT 0.625" I.D. 43 0C7649 2 CLAMP HOSE 0.38"-0.87" 44 092079 1 SCREW HHTT M6-1.0 X 25MM 45 055414 1 LUG SLDLSS #2-#8 X 17/64" 46 0A1658 1 WASHER LOCK SPECIAL 1/4" 47 0D3700 2 NUT FLANGE M6-1.0 NYLOK 48 0E4170 1 CONN 3/4"NPT - 3/8" 45D BRASS 49 047290 2.3 FT HOSE 3/8" I.D. 50 022129 4 WASHER LOCK M8-5/16 51 022145 4 WASHER FLAT 5/16-M8 52 0C7649 1 CLAMP HOSE 0.38"-0.87"
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Tank Enclosure - Drawing No. 0E2154-A
Page 48
46 Generac®Power Systems, Inc.
5
6
3
8
0
9
315
9
3
5
616
8
0
8
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Gas Regulator - Drawing No. 0E3924
1
2
1
1
1
2
2
2
2
Page 49
Generac®Power Systems, Inc. 47
ITEM PART NO. QTY. DESCRIPTION
1 0D5694 1 CASTING, TWIN REGULATOR HOUSING
2 075475 4 SCREW PPHM M4-0.7 X 10
3 022264 4 WASHER LOCK #8-M4
4 043180 4 WASHER FLAT M4
5 0C5765 1 SOLENOID, TWIN REGULATOR
6 0C6070 1 SPRING-SOLENOID PLUNGER
7 0C4680 1 PLUNGER LP REG. ASSY
8 0C4647 1 GASKET, SOLENOID
9 0C4643 1 INLET, TWIN REGULATOR NO HOLE 10 0D3973 1 PLUG, EXPANSION 16MM TWINREG 11 0D7020A 1 BARBED STR 1/2NPT X 3/8" W/VS 12 026073 2 PLUG STD PIPE 1/8 STEEL SQ HD 13 0D3308 2 WASHER FLAT 3.2MM ID X 10MM OD 14 070728 2 SCREW PFILHM M3-0.5 X 5 15 0C5764A 1 SPRING, REGULATOR 16 0C4643A 1 INLET, TWIN REG 11.11 DIA. 17 0C6066 1 SEAL, INLET REGULATOR 18 0C5968 1 SUPPORT, INLET SEAL 19 0C5759 1 PIN, PIVOT ARM 20 0C5761 1 LEVER, REGULATOR 21 0C6069 1 GASKET, DIAPHRAGM 22 0C6731 1 RIVET .118 X .125 ALUMINUM 23 0C6067 1 SUPPORT, DIAPHRAGM 24 0C4706 1 DIAPHRAGM, TWIN REGULATOR 25 0C6068 1 CAP, DIAPHRAGM SUPPORT 26 0C5762 1 COVER,TWIN REGULATOR 27 045764 8 SCREW HHTT M4-0.7 X 8 BP 28 0C5760 1 JET LP
Appendix 4 – Exploded Views & Parts Lists
CENTURION 3500 Home Standby Generator
Gas Regulator - Drawing No. 0E3924
Page 50
48 Generac®Power Systems, Inc.
CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and the United States Environmental Protection Agency (EPA), together with Generac Power Systems, Inc. (Generac), are pleased to explain the Emission Control System Warranty on your new engine.* New utility, and lawn and garden equipment engines must be designed, built and equipped to meet stringent anti-smog stan­dards for the state of California and the federal government. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improp­er maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition and exhaust systems. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1997 and later model year engines are warranted for two years as hereinafter noted. If, dur­ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely because of the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect, improper maintenance or unap­proved modifications, or the use of counterfeit and/or ‘grey market’ parts not made, supplied or approved by Generac.
You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a prob­lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility. To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California and federal law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser­vice, evidence must be presented showing the date of the sale to the original purchaser/owner. The purchaser/owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the inspection or repair facilities. The purchaser/owner also shall be responsible for any and/or all damages or losses incurred while the engine is being transported/shipped for inspection or warranty repairs.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol­lowing address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Part 1

Appendix 5 – Warranty

CENTURION 3500 Home Standby Generator
Page 51
Generac®Power Systems, Inc. 49
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1997 and later model year engines:
(a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall contin­ue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment, and to each subsequent purchaser/owner, that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the EPA and CARB pursuant
to their respective authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine manu­facturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-
ble for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the purchaser/owner. Such use shall not reduce Generac’s ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or ‘grey market’ parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or ‘grey market’ part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
*Generac engine types covered by this warranty statement include the following:
1) Utility
2) Lawn and Garden Equipment
3) Recreational Vehicle (RV) Generator
4) Industrial Mobile (IM) Generator
Part 2
Appendix 5 – Warranty
CENTURION 3500 Home Standby Generator
1) Fuel Metering System:
1.1) Gasoline carburetor assembly and its internal components (if so equipped).
a) Fuel filter (if so equipped) b) Carburetor gaskets c) Fuel pump (if so equipped)
1.2) LPG carburetion assembly and its internal components (if so equipped).
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including: a) Intake pipe/manifold b) Air cleaner
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
Page 52
Part No. 0E2096 Revision B (09/12/03) Printed in U.S.A.
Appendix 5 – Warranty
CENTURION 3500 Home Standby Generator
GENERAC POWER SYSTEMS "TWO YEAR" STANDARD WARRANTY FOR
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equip­ment that the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. This warranty applies only to Generac prepackaged emergency automatic standby generators sold and rated for use in "Standby" applications.
WARRANTY SCHEDULE
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
• Engine - All Components
• Alternator - All Components
• Transfer System - All Components All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate
Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Generac/Centurion generators that utilize non-Generac/Centurion replacement parts.
• Generac/Centurion generators utilizing non-Generac/Centurion transfer switches.
• Any Generac/Centurion generators used as rental or trailer mounted applications.
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent or insect infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e., cranes, hoists, lifts, etc,)
• Overnight freight costs for replacement part(s).
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES
NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC®POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Loading...