Centurion 04791-0, 3500 Owner's Manual And Installation Instructions

®
Owner’s Manual and
Installation Instructions
CENTURION 3500
Air-cooled, Prepackaged
Automatic Standby Generator
• Model: 04791-0
3.4kW LP
or in life-support applications.
!
!
This manual should
remain with the unit.
DEADLY EXHAUST FUMES. OUTDOOR INTALLATION ONLY!!
DANGER
Generac®Power Systems, Inc.

INTRODUCTION

Thank you for purchasing this model of the CENTU­RION product line by Generac Power Systems Inc. This model is designed and manufactured to supply electrical power for residences.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is misunderstood, con­tact the nearest Generac Authorized Service Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAU­TION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
After this heading, read instructions that, if not strictly complied with, will result in serious person­al injury, including death, as well as property dam­age.
After this heading, read instructions that, if not strictly complied with, may result in serious person­al injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety infor­mation that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion haz­ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts for generator model numbers 04791-0. In addition, the latter portion of this manual contains information necessary for the proper installation of these generators.
OPERATION AND MAINTENANCE
It is the owner's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Generac Authorized Service Dealer. Normal maintenance ser­vice and replacement of parts are the responsibility of the owner and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage con­tribute to the need for maintenance service.
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum.
HOW TO OBTAIN SERVICE
When your generator requires servicing or repairs, simply contact a Generac Authorized Service Dealer for assistance. Service technicians are factory trained and are capable of handling all service needs.
When contacting a Generac Authorized Service Dealer about parts and service, always supply the complete model number and serial number of the unit as given on its data decal, which is located on the generator.
Model No. ____________ Serial No. ______________
AUTHORIZED SERVICE
DEALER LOCATION
To locate the nearest GENERAC AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
ONLY DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
DANGER
!

Table of Contents

CENTURION 3500 Home Standby Generator
Generac®Power Systems, Inc. 1
Part I – Owner’s Manual
Introduction ........................................Inside Front Cover
Read This Manual Thoroughly ....................................IFC
Contents ......................................................................IFC
Operation and Maintenance ........................................IFC
How to Obtain Service..................................................IFC
Authorized Service Dealer Locator Number ................IFC
Safety Rules ........................................................................2
Section 1 - General Information ....................................4
1.1 Generator Identification ........................................4
1.2 Unpacking/Inspection ............................................5
1.3 Safety ....................................................................6
1.4 Protection Systems................................................6
1.5 Location ................................................................6
1.6 Specifications ........................................................6
Section 2 - Operation........................................................7
2.1 Generator Control Panel........................................7
2.2 Before Starting the Engine ....................................8
2.3 Battery Connection................................................8
2.4 The Battery ..........................................................9
2.5 Before Initial Start-up............................................9
2.6 Stopping the Generator ......................................10
2.7 Applying Loads to Generator ..............................10
2.8 Do Not Overload the Generator ..........................10
2.9 Protection Systems..............................................10
2.10 Additional Information ........................................12
Section 3 - Maintenance ................................................12
3.1 Checking the Engine Oil Level ............................12
3.2 Changing the Engine Oil and/or Oil Filter ..........12
3.3 Maintaining the Engine Air Cleaner ....................13
3.4 Clean Air Intake ..................................................14
3.5 Checking the Engine Spark Plug ........................14
3.6 Clean Spark Arrestor ..........................................14
3.7 Cleaning the Generator ......................................15
3.8 Battery Maintenance............................................15
3.9 Exercising the Generator ....................................16
3.10 Out of Service Procedure ....................................16
3.11 Adjusting Valve Clearance ..................................17
3.12 Generator Service Interval ..................................17
Part II – Installation Instructions
Safety Rules ......................................................................19
Section 1 - General Information ..................................21
1.1 Tools Required....................................................21
1.2 Items That Must Be Purchased ..........................21
1.3 Plan the Location of the Generator......................21
Section 2 - Installation ..................................................22
2.1 Site Preparation and Generator Placement ........22
2.2 Power Cord Installation ......................................22
2.3 Mount Power Transfer Motor ..............................23
2.4 Install Propane Tanks ........................................23
2.5 Set System for Automatic Operation ..................25
2.6 How to Keep the Regulator Operating
Efficiently & Safely ..............................................25
2.7 What is Regulator Freeze Up?..............................25
Appendix 1 - Troubleshooting ......................................26
Appendix 2 - Notes..........................................................27
Appendix 3 - Electrical Data ........................................30
Appendix 4 - Exploded Views and Parts Lists..........34
Appendix 5 - Warranty ..................................................48
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this manual and with the unit. The generator can operate safely, efficiently and reli­ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possibility that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit, are, therefore, not all-inclusive. If using a procedure, work method or operating technique Generac does not specifically recommend, satisfy yourself that it is safe for others. Also make sure the procedure, work method or operating technique chosen does not ren­der the generator unsafe.
Despite the safe design of this generator, oper­ating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsi­ble and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GEN
ERAL HAZARDS
• For safety reasons, Generac recommends that the
maintenance of this equipment is carried out by a Generac Authorized Service Dealer.
• The generator engine releases DEADLY carbon
monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concentra­tions, can cause unconsciousness or even death. Never operate the generator inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOXIDE POISONING ARE (a) inability to think coherently, (b) nausea, (c) vomit­ing, (d) twitching muscles, (e) throbbing temples, (f) dizziness, (g) headaches, (h) weakness, and (i) sleepiness. IF EXPERIENCING ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDI­ATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. Shut down the generator and do not operate it until it has been inspected and repaired.
• The engine exhaust fumes contain carbon monox-
ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compli­ance with applicable codes and standards. Following installation, do nothing that might ren­der the system unsafe or in noncompliance with such codes and standards. Never operate this equipment with a leaking or defective exhaust sys­tem.
• Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti-
lating air is critical to correct generator operation and is required to expel toxic fumes and fuel vapors from the generator. Without sufficient cooling air­flow, the engine/generator overheats, which causes serious damage to the generator. Do not alter the installation or permit even partial blockage of ven­tilation provisions, as this can seriously affect safe operation of the generator.
!
!
!

Safety Rules

CENTURION 3500 Home Standby Generator
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas of the recreational vehicle. Safety should be stressed to all operators and potential operators of this equipment.
!
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
!
!
!
!
!
!
DANGER
!
Generac®Power Systems, Inc. 3
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and contact the nearest Generac Authorized Service Dealer immedi­ately for parts needing repair or replacement.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
• The generator covered by this manual produces dangerous electrical voltages and can cause fatal electrical shock. Avoid contact with bare wires, ter­minals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• During installation, have the generator properly grounded (bonded) by means of an approved bonding conductor. DO NOT disconnect the bond­ing conductor. DO NOT reconnect the bonding conductor to any generator part that might be removed or disassembled during routine mainte­nance. If the grounding conductor must be replaced, use only a flexible conductor that is of No. 12 American Wire Gauge (AWG) copper wire minimum.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a dry rope or board, to free the vic­tim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
EXP
LOSION HAZ
ARDS
• Do not smoke around the generator. Wipe up any oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the genera­tor clean and free from debris.
Safety Rules
CENTURION 3500 Home Standby Generator
4 Generac®Power Systems, Inc.
1. Generator Air Intake
2. Engine AUTO/OFF/MANUAL Switch
3. Fuse
4. LED Indicator
5. Demand Regulator (Inside Compartment)
6. Change-over Regulator
7. Circuit Breakers
8. Starter Contactor
9. Fuel Inlet
10. Tank Hook-ups.
11. Battery (In Compartment)
12. Oil Filter
13. Oil Drain (From Underside)
14. Oil Dipstick
15. Air Filter (Behind Access Panel)
16. Oil Fill
17. Spark Plug
18. Tank Hold Down Brace
19. Exhaust Hood (Tailpipe and Spark Arrestor Inside)
20. Ground Lug
21. Data Decal (Located inside compartment)

Section 1 – General Information

CENTURION 3500 Home Standby Generator
Please record the following information from the generator DATA DECAL or information decal.
1. Model Number ____________________ 2. Serial Number __________________
3. kW Rating__________________________ 4. Rated Voltage __________________
072347
QT
RATO
R
T
OR
R
USE
.5A
1.1 GENERATOR IDENTIFICATION
Model: 004700-0 — QUIETPACT 40G
21
18
10
19
13
14, 16
12
8
17
4
3
7
2
15
1
9
6
5
1
11
20
GENERAT
F
POWE
7
PUSH TO RESE
R POWE
0.8L/0.84
Generac®Power Systems, Inc. 5
Section 1 – General Information
CENTURION 3500 Home Standby Generator
1.1.1 POWER TRANSFER MONITOR
The Power Transfer Monitor controls the automatic function of the Centurion 3500 generator set. It’s six foot utility sensing cord monitors the utility line when it is plugged into a standard household 120 volt out­let.
NOTE:
Automatic start-up upon utility power outage will not occur if six foot sensing cord is not plugged into a utility powered 120 volt outlet.
Figure 1.2 — Power Transfer Monitor
1. Generator Power Conduit (15 foot)
2. Circuit Breaker Reset (2)
3. Generator Power Indicator Lamp
4. Utility Power Indicator Lamp
5. Generator Exercise Switch
6. Switched GFCI Outlet
7. Standby GFCI Outlet
8. Utility Sensing Cord (6 foot)
1.1.1.1 Generator Power Conduit
This conduit connects the Power Transfer Monitor, which is located inside the home, to the generator outside.
1.1.1.2 Circuit Breaker Reset
If the generator should experience an overload for any reason, the circuit breaker(s) will trip. The cir­cuit breaker reset(s) should be pushed to reset after overload condition has been corrected.
1.1.1.3 Generator Power Indicator Lamp
This lamp will illuminate when the generator has started and is supplying power to the Power Transfer Monitor’s GFCI outlets.
1.1.1.4 Utility Power Indicator Lamp
This lamp will be illuminated when normal utility power is available.
1.1.1.5 Generator Exercise Switch
This switch activates the exercise cycle of the genera­tor. Make sure the combined loads do not exceed gen­erator capacity.
1.1.1.6 Switched GFCI Outlet
This outlet is powered by the utility and by the gen­erator. When utility power is present is acts as anoth­er normal household outlet. When the generator is supplying power this outlet is then being supplied with power from the generator.
NOTE:
There will be a momentary “No Power” period between the time of utility failure and the genera­tor start up.
1.1.1.7 Standby GFCI Outlet
This outlet is ONLY powered by the generator. Use it for additional items during a utility power outage when the generator is providing backup electricity for the home.
1.1.1.8 Utility Sensing Cord
When plugged into a standard grounded 120 volt out­let this cord allows the Power Transfer Monitor to sense the utility line condition and react to a power outage.
1.2 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
• This standby generator set has been factory sup­plied with a weather protective enclosure that is intended for outdoor installation only.
• This standby generator set is prepackaged with an automatic power transfer monitor. The power transfer monitor is prewired with 15 foot conduit and six foot utility sensing cord with plug. The Power Transfer Monitor is for indoor installation only.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix his or her signature under the consignor’s memo of loss or damage.
If loss or damage is found after delivery, separate the damaged materials and contact the carrier for claim procedures if applicable.
Use this generator to supply electrical power for operating 120-volt, single-phase, 60 Hertz, AC elec­trical loads. These loads can require up to 3,400 watts (3.4 kW) of power, but cannot exceed 28.3 AC amperes of current at 120 volts.
1
2
3
4
5
6
7
8
6 Generac®Power Systems, Inc.
Section 1 – General Information
CENTURION 3500 Home Standby Generator
Do not overload the generator. Some installa­tions may require that electrical loads be alter­nated to avoid overloading. Applying exces­sively high electrical loads may damage the generator and may shorten its life. Add up the rated watts of all electrical lighting, appliance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capacity of the generator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.
1.3 SAFETY
Before attempting to use the generator set, carefully read the “Safety Rules” section of this manual. Comply strictly with these rules to prevent accidents and damage to equipment and/or property. We sug­gest copying and posting the “Safety Rules” in poten­tial hazard near the generator. Stress safety to all operators and potential operators of this equipment.
1.4 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for long periods of time with no operator pre­sent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging condi­tions:
1. Overcrank
2. Overspeed
3. Low Oil Pressure Sensor
4. High Temperature Sensor
5. Underspeed There is an LED readout on the control panel to noti-
fy personnel that one of these faults has occurred. Detail of of the protection systems can be found in Section 2.9.
1.5 LOCATION
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available. Consider these factors:
• Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift­ing, consider using a windbreak to protect the unit.
• Install the generator on high ground where water levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator for maintenance and servicing. A good rule is to allow three feet of space on all sides.
• Where strong prevailing winds blow from one direction, face the generator air inlet openings to the prevailing winds.
1.6 SPECIFICATIONS
1.6.1 FUEL REQUIREMENTS AND RECOM­MENDATIONS
With LP gas, use only the LP vapor withdrawal sys­tem. This type of system uses the vapors formed above the liquid fuel in the storage tank.
Recommended fuel should have a BTU content of at least 2,520 BTU's per cubic foot. Ask the LP fuel sup­plier for the BTU content of the fuel.
This generator has been designed for a specific type of tank. Acceptable tank types are DOT-4BA240 and DOT-4BW240. Any deviation in tank type may not allow the tank to fit in the LP enclosure.
Gaseous fuels such as liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. LP gas, which is heavier than air tends to settle in low areas.
1.6.2 FUEL CONSUMPTION
Fuel consumption is in gal/hr.
1.6.3 ENGINE OIL REQUIREMENTS
Use only high quality detergent oil rated with American Petroleum Institute (API) Service Classification SF, SG or SH. The recommended oil weights include the following:
• During summer months: SAE 30. An acceptable substitute is SAE 10W-30.
• During winter months: SAE 5W-30. DO NOT USE SAE 10-W40.
Crankcase and oil filter capacity is approximately 800 mL or .84 U.S. quarts. Do NOT use special addi­tives. See Sections 3.1 and 3.2 for oil level check and fill procedures.
!
!
Model 1/2 Load Full Load
Centurion 3500 0.55 0.73 (04791-0)
DANGER
Generac®Power Systems, Inc. 7

Section 2 – Operation

CENTURION 3500 Home Standby Generator
1.6.4 ENGINE
Type of Engine ............................GN-220, Single-cylinder
Cooling Method..................................................Air-cooled
Rated Horsepower ..................................7.8 @ 4,200 rpm
Displacement............................................................220cc
Cylinder Block ....................Aluminum w/Cast Iron Sleeve
Type of Governor ........................Mechanical, Fixed Speed
Air Cleaner ..................Paper Element w/Foam Precleaner
Starter ................................................12-volt DC Electric
Ignition System ................Solid-state w/Flywheel Magneto
Recommended Spark Plug
Champion ..........................................................RC12YC
AC ..........................................................................R45S
Fram Autolite ..............................................................65
Spark Plug Gap ..................................0.03. inch (76 mm)
Recommended Minimum
Battery ......................................235cc Amperes @ 32°F/
195cc Amperes @ 0° F
1.6.5 GENERATOR
Rated Maximum Continuous
AC Output (LP)................................3,400 Watts (3.4kW)
Rated Voltage ................................................120 Volts AC
Rated Maximum Continuous
AC Current (LP) ........................................28.3 Amperes
Phase ......................................................................Single
Rotor RPM................................................................3,600
Number of Rotor Poles ....................................................2
Engine RPM..............................................................3,600
Rated AC Frequency ................................................60 Hz
Battery Charge Voltage ....................................14 Volts DC
Battery Charge Current ..........................2 Amperes (max)
Length ..................................................843 mm (33.2 in.)
Width ....................................................504 mm (19.8 in.)
Height ......................................................966 mm (38 in.)
Weight ......................................................90 kg (275 lbs.)
2.1 GENERATOR CONTROL PANEL
The following features are mounted on the generator control panel (Figure 2.1):
Figure 2.1 — Generator Control Panel
2.1.1 SHUT DOWN INDICATOR
This LED will flash a specific number of times to indi­cate a specific failure. Shutdowns and their failure codes follow in Section 2.9, Protection Systems. These codes can also be referenced on the decal located on the air filter cover, located below the control panel.
2.1.2 AUTO/OFF/MANUAL SWITCH
2.1.2.1 Auto Position
Selecting this switch position activates fully automat­ic system operation. It also allows the user the abili­ty to start and exercise the generator from the remote Power Transfer Monitor.
2.1.2.2 Off Position
This switch position shuts down the engine. This position also prevents the engine from starting.
2.1.2.3 Manual Position
Selecting this switch position will crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.
With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre­set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuse before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.
2.1.3 FUSE
The generator panel's 7.5 amp fuse protects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, the engine cannot crank or start. The same fuse also protects the bat­tery charge circuit against overload. If the fuse ele­ment has melted open, battery charging will not be possible. Replace the fuse using only an identical 7.5 amp fuse.
2.1.4 MAIN BREAKERS
The main breakers protect the generator’s AC output circuit against overload and provide a method of turning OFF the generator’s 120-volt AC output to the Power Transfer Monitor’s outlets. The CENTURION 3500 has two (2) 15-amp breakers.
!
FUSE
7.5A
SHUT
DOWN
GENERATOR
POWER
GREEN BAR INDICATES TRIP
PUSH TO RESET
15 15
PULL TO DISCONNECT
GENERATOR POWER
INDICATOR
SEE CHART BELOW FOR DETAILS
CONTROL CENTER
AUTO
OFF
MAN.
8 Generac®Power Systems, Inc.
Section 2 – Operation
CENTURION 3500 Home Standby Generator
2.2 BEFORE STARTING THE ENGINE
NOTE:
Instructions and information in this manual assume the generator has been properly installed and connected.
2.2.1 ENGINE LUBRICATION
Have the engine crankcase properly serviced with the recommended oil before starting. Refer to Section
1.6.2 and Sections 3.1 and 3.2, for oil servicing pro­cedures and recommendations.
Any attempt to crank or start the engine before it has been properly serviced with the recom­mended oil may result in an engine failure.
2.2.2 FUEL SUPPLY
The engine must have an adequate supply of proper fuel to operate. Before starting it, check that sufficient fuel is available.
2.2.3 COOLING AND VENTILATING AIR
Air inlet and outlet openings in the generator com­partment must be open and unobstructed for contin­ued proper operation. Without sufficient cooling and ventilating airflow, the engine/generator overheats, which causes it to shut down and may damage the generator.
2.2.4 ENGINE EXHAUST GAS
Before starting the generator engine, be sure there is no way for exhaust gases to endanger people or ani­mals. Close windows, doors near the generator that, if open, might permit exhaust gases to do so.
The generator engine releases DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concen­trations, can cause unconsciousness or even death. Never operate the generator set inside any enclosed area. make sure THE EXHAUST SYSTEM IS not LEAKING AND HAS NOT BEEN DAMAGED. SYMPTOMS OF CARBON MONOX­IDE POISONING ARE (a) inability to think coher­ently, (b) nausea, (c) vomiting, (d) twitching muscles, (e) throbbing temples, (f) dizziness, (g) headaches, (h) weakness, and (i) sleepiness. IF EXPERIENCING ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMP­TOMS PERSIST, GET MEDICAL HELP. Shut down the generator and do not operate it until it has been inspected and repaired.
2.3 BATTERY CONNECTION
Before connecting the battery, complete the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Make sure the Power Transfer Monitor’s sensing cord (6 foot) is not plugged into an electrical out­let.
If the AUTO/OFF/MANUAL switch is not set to its OFF position, the generator can crank and start as soon as the battery cables are connect­ed. If the utility power supply is not disabled by unplugging the 6 foot sensing cord from electrical outlet, sparking can occur at the bat­tery posts and cause an explosion.
Battery cables were factory connected at the genera­tor (Figure 2.2). Connect the cables to the battery posts using the hardware supplied in the manual bag as follows:
3. Slide the red battery terminal boot over the bat­tery cable, then connect the cable (from the starter contactor) to the battery post indicated by a positive, POS or (+).
4. Connect the black battery cable (from frame ground) and the two green grounding wires (from the control panel) to the battery post indicated by a negative, NEG or (-).
NOTE:
Damage will result if battery connections are made in reverse.
Figure 2.2 — Battery Cable Connections
!
DANGER
DANGER
!
Generac®Power Systems, Inc. 9
Section 2 – Operation
CENTURION 3500 Home Standby Generator
2.4 THE BATTERY
Servicing of the battery is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
When replacing the battery, use the following type of battery, Group U1 12-volt battery with a rating of 235 cold-cranking amps at 0° C (32° F); 195 cold-crank­ing amps at -17.8º C (0º F) minimum. When using a maintenance-free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connect­ed and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
Do not dispose of the battery in a fire. The bat­tery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. The following precau­tions are to be observed when working on bat­teries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the bat­tery; and
• Disconnect charging source prior to connecting or disconnecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following proce­dures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek med­ical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon­ate of soda to one gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) as ceased. The resulting liquid is to be flushed with water and
the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. The fol­lowing procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
2.5 BEFORE INITIAL START-UP
Before starting the generator, complete the fol­lowing:
1. Set the generator's main circuit breakers (located
in generator’s control panel) to their OFF or OPEN positions by pulling the reset buttons out­ward. A visible GREEN stripe should appear.
2. Set the generator's AUTO/OFF/MANUAL Switch to
the OFF position.
3. Turn OFF all loads connected to the Power
Transfer Monitor through the GFCI outlets.
4. Check the engine crankcase oil level and, if nec-
essary, fill to the dipstick full mark with the rec­ommended oil. Do not fill above the oil FULL mark.
5. Check the fuel supply. Both tanks should be full.
6. The changeover valve tank indicator should be
GREEN.
2.5.1 INITIAL START UP - PURGING THE FUEL SYSTEM
To purge the air that is in the lines of the fuel system, perform the following:
1. Connect the LP tanks and open both tank valves. Make sure that the selector lever on the changeover regulator is pointing at one of the two tanks. Also verify that the Full/Empty indicator on top of the changeover regulator is GREEN.
2. Set the generator's main circuit breakers to their OFF or OPEN positions by pulling the reset but­tons outward. A visible Green stripe should appear.
3. Move the AUTO/OFF/MANUAL switch to the MAN­UAL position.
!
DANGER
!
!
10 Generac®Power Systems, Inc.
Section 2 – Operation
CENTURION 3500 Home Standby Generator
4. The engine will crank and attempt to start for approximately 15 seconds. Due to the air that will be in the fuel lines, the engine may not start dur­ing the first 15 second cranking cycle. If the engine does not start during the first crank cycle, it will rest for approximately 15 seconds and then attempt to start again. The complete starting cycle is as follows:
• 15 seconds ON
• 15 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds, Approximately 90 sec­onds total. The engine should start during the first or second attempt.
5. If the unit does not start during this crank cycle, verify that all fuel connections are tight and that the tank valves are open. Turn the AUTO/OFF/MANUAL switch to the OFF position, wait 3-5 seconds, then repeat steps 3-4.
6. If the engine does not start after repeating steps 3-4, contact the nearest Generac Authorized Service Dealer for assistance.
2.5.2 CHECKING AUTOMATIC OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Set the generator's main circuit breakers to their OFF or OPEN positions by pulling the reset but­tons outward. A visible GREEN stripe should appear.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn ON the utility power supply to the Power Transfer Monitor by plugging the 6-foot sensing cord into a standard household outlet.
4. Set the generator's main circuit breakers to their ON or CLOSED position by pressing in the reset buttons.
5. Set the AUTO/OFF/MANUAL switch to AUTO, the system is now ready for automatic operation.
6. Turn off the utility power supply to the Power Transfer Monitor by unplugging it’s 6-foot power cord from the household outlet.
Once the Power Transfer Monitor senses the utility source power is turned OFF, and after an approxi­mate five second delay, the engine should crank and start. After starting, the Power Transfer Monitor should connect load circuits to the standby or gener­ator side. Both sets of GFCI outlets on the Power Transfer Monitor should have power. Confirm trans­fer of power by depressing the test buttons on both GFCI outlets. Each one should trip and the indicator will illuminate.
With the generator running and power is available to the GFCI outlets, turn the utility power supply ON once again by plugging the six foot power cord into a standard household outlet. The following should occur.
• The Power Transfer Monitor should sense the return of utility power and transfer the loads plugged into the SWITCHED GFCI back to the util­ity source. Any loads connected to the STANDBY GFCI will remain powered by the generator until it shuts down. In the event of a real outage, these loads would be reconnected to the utility.
• About two minutes after re-transfer, the engine should shut down. However, if the engine was not run for it's minimum run time based on starting time, it may run for a longer period of time before shutting down. (20 minutes max.)
• The minimum run time is pre-programmed into the generator micro processor and is provided to ensure that the starting battery is fully charged before the engine shuts down. The minimum run time is based on the time it takes for the engine to crank and start. For every one second of cranking, the generator will run for 1.5 minutes.
2.6 STOPPING THE GENERATOR
1. Turn OFF all electrical loads using the means
provided (such as the generator fs main circuit breakers).
2. Let generator run at no-load for a few minutes, to
stabilize internal engine generator temperatures.
3. Place the AUTO/OFF/MANUAL switch in its OFF
position.
2.7 APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator, observe these guidelines:
Before applying electrical loads, let the generator stabilize and warm up for a minute or two.
DO NOT overload the generator.
2.8 DO NOT OVERLOAD THE
GENERATOR
Read the rated wattage/amperage capacity of the gen­erator in GENERATOR data, (see Section 1.6.5). Applying electrical loads in excess of the unit’s rated capacity will cause the engine/generator to automati­cally shut down.
To avoid overloading, add up the wattage of all con­nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the gen­erator’s rated wattage capacity.
Generac®Power Systems, Inc. 11

Section 3 – Maintenance

CENTURION 3500 Home Standby Generator
• Most lighting, appliance, tool and motor loads indi­cate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.
• If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain WATTS.
• Induction type motors (such as those that run a furnace fan, refrigerator, window air conditioner, etc.) need about 2-1/2 time more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when con­necting electrical loads to the generator. First, fig­ure the watts needed to start electric motors in the system. To that figure, add the running wattages of other items that will be operated by the generator.
• Do not apply heavy electrical loads for the first two or three hours of operation.
2.9 PROTECTION SYSTEMS
2.9.1 OVERCRANK — 2 FLASHES OF LED
This feature prevents the generator from damaging itself when it continually attempts to start and anoth­er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The AUTO/OFF/ MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature will continue to activate.
2.9.1.1 Approximate Crank Cycle Times
• 15 seconds ON
• 15 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total
2.9.2 OVERSPEED — 3 FLASHES OF LED
This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gener­ator from supplying an output that could potentially damage appliances connected to the generator cir­cuit. Please reference Appendix 1, Troubleshooting, if this fault occurs.
2.3.3 LOW OIL PRESSURE SWITCH — 4 FLASHES OF LED
This switch (Figure 2.2) has normally closed (N.C.) contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below a preset level, switch contacts close, and the engine automatically shuts down. The unit should not be restarted until oil is added. Please reference Appendix 1, Troubleshooting, if this fault occurs.
2.9.4 HIGH TEMPERATURE SWITCH — 5 FLASHES OF LED
This switch (Figure 2.2), which has normally open (N.O.) contacts, is mounted near the oil filter. The contacts close if the temperature should exceed approximately 284° F (140° C), initiating an engine shutdown. Please reference Appendix 1, Troubleshooting, if this fault occurs.
Figure 2.3 — Low Oil Pressure and High
Temperature Switches
2.9.5 UNDERSPEED — 6 FLASHES OF LED
This feature protects the generator from damage by shutting down if it happens to run slower than the preset limit. Please reference Appendix 1, Troubleshooting, if this fault occurs.
2.9.6 FIELD BOOST
The Controller Circuit Board houses a field boost diode and resistor. These two components are part of a “field boost” circuit (Figure 2.4). During engine cranking only, a positive DC (battery) voltage is deliv­ered through the diode, resistor, brushes and slip rings, to the generator rotor. Application of this volt­age to the rotor “flashes the field” whenever it is start­ed. Flashing of the field each time the generator starts makes sure that a sufficiently strong magnetic field is available to produce “pickup” voltage in the stator windings.
High Temperature Switch
Low Oil Pressure Switch
12 Generac®Power Systems, Inc.
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
Figure 2.4 — Field Boost Circuit
2.9.7 OVERVOLTAGE PROTECTION
A solid-state voltage regulator (Figure 2.5) controls the generator’s AC output voltage. This regulator sup­plies an excitation current to the rotor. By regulating the rotor’s excitation current, the strength of its mag­netic field is regulated and, in turn, the voltage deliv­ered to connected electrical loads is controlled. When the AC frequency is 60 Hertz, voltage is regulated at 120 volts (voltage-to-frequency ratio is 2-to-1).
Figure 2.5 — Solid State Voltage Regulator
The voltage regulator also incorporates a “voltage surge protection circuit”. This circuit prevents trou­blesome surges in the generator AC output voltage. Voltage surge is a common cause of damage to elec­tronic equipment.
2.10 ADDITIONAL INFORMATION
2.10.1 BREAK-IN PERIOD
The first few hours of operation is the break-in peri­od for the generator. Properly breaking in the genera­tor is essential to minimize fuel consumption and provide maximum engine performance. During this break-in period, follow this procedure:
• Run the unit at different electrical loads by plug­ging items into the Power Transfer Monitor’s out­lets. This will help seat the engine piston rings properly.
• Check the engine oil level frequently. Add oil if needed. It is normal for the generator engine to consume more oil than is normal until the piston rings have properly seated.
• After operating the unit for the break-in period, complete the tasks recommended under Section
2.10.2.
2.10.2 POST BREAK-IN CHECK-UP
After the break-in period, the owner should perform the following maintenance items:
• Change the engine crankcase oil and oil filter.
• Check the oil level.
• Inspect the cooling and ventilation openings.
• Check the engine ignition system.
• Inspect the entire electrical system.
• Inspect the engine exhaust system.
2.10.3 ATTENTION REQUIRED AFTER SUBMERSION
If the generator has been submerged in water, it MUST NOT be started and operated. Following any submersion in water, have a Generac/Centurion Authorized Service Dealer thoroughly clean and dry the generator.
2.10.4 OPERATION IN HIGH GRASS OR BRUSH
Never operate the generator while it is in contact with high grass, weeds, brush, leaves or any other com­bustible substance. Such materials can ignite and burn from the heat of the exhaust system. The gener­ator exhaust system becomes extremely hot during operation and remains hot for a long time after it has shut down.
2.10.5 EFFECTS OF MOISTURE AND DIRT
Keep the generator set as clean and dry as possible. Protect the unit against excessive dust, dirt, corrosive vapors, etc. Permitting dirt and moisture to accumu­late on generator windings will have an adverse effect on the insulation resistance of those windings.
When moisture is allowed to remain in contact with windings, some of the moisture will be retained in voids and cracks in the insulation. This causes a reduced insulation resistance and will eventually cause problems. Dirt will make the problem worse, since dirt tends to hold moisture in contact with windings. Salt (as from sea air) also will worsen the problem since it tends to absorb moisture from the air. Salt and moisture, when combined, form an elec­trical conductor which is detrimental to the genera­tor.
CONTROLLER CIRCUIT BOARD
4
O
GRND
F
CLOSEST TO BEARING
FIELD
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
3.1 CHECKING THE ENGINE OIL LEVEL
For oil capacities and requirements, see “Engine Oil Requirements,” Section 1.6.3. Check the engine crankcase oil level weekly. To check the engine oil level, proceed as follows (see Figure 3.1):
1. Remove the oil fill/dipstick cap and wipe the dip-
stick dry with a clean, lint-free cloth.
2. Install and tighten the oil fill/dipstick cap; then,
remove it again. The oil level should be at the dip­stick “Full” mark.
3. If necessary, slowly add oil until it reaches the
dipstick “FULL” mark. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
4. Install and tighten the oil fill/dipstick cap before
operating the engine.
3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER
• Change the engine oil after the break-in period,
(see Section 2.10.1). Thereafter, change oil every twelve months. Change the oil more frequently if unit operates during extended power outages of several days at a time, in dusty conditions or at high ambient temperatures.
• Change the engine oil filter after the break-in peri-
od, and every twelve months thereafter.
To change the oil and/or oil filter, proceed as follows (see Figure 3.1):
1. Run the engine until it is thoroughly warmed up (at least five minutes) then shut OFF the engine.
2. Immediately after the engine shuts OFF, remove the plug from the tube with a 5/16” allen wrench and drain the oil into a suitable container. Loosening the oil fill/dipstick cap will allow the crankcase to drain faster.
3. After the oil has drained, replace the plug onto the end of the oil drain tube.
4. With the oil drained, remove the old oil filter by turning it counterclockwise. Place a towel under­neath to catch excess oil.
5. Apply a light coating of clean engine oil to the gas­ket of the new filter. Fill the filter until saturated with clean oil.
6. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tight­en the filter an additional 3/4 to one turn.
7. Remove the oil fill/dipstick cap and wipe the dip­stick dry with a clean, lint-free cloth. This will be used later to check the oil level.
8. Slowly add the proper type and amount of rec­ommended oil (see Section 1.6.3). Periodically use the dipstick to check the oil level and contin­ue to fill the crankcase until the oil reaches the dipstick “Full” mark. DO NOT FILL ABOVE THE “FULL” MARK.
9. Install and tighten the oil fill/dipstick cap before operating the engine.
10. Start the engine and check for leaks.
NOTE:
Check the oil level and fill to the “FULL” mark after checking for leaks. The filter will retain some oil.
!
Generac®Power Systems, Inc. 13
Figure 3.1 – Oil Maintenance Features
Dipstick & Oil Fill
Oil Drain
(Underneath)
Oil Filter
GENERATOR
FUSE
POWER
7.5A GREEN BAR INDICATES TRIP
PUSH TO RESET
PULL TO DISCONNECT
GENERATOR POWER
SHUT DOWN
INDICATOR
SEE CHART BELOW FOR
MAN.
AUTO
OFF
DETAILS
CONTROL CENTER
SERVICEACCESS PANEL
GENERATOR SHUTDOWN
S
O
E
N
O
L
INFORMATION SYSTEM
FAULTSIGNAL
2 FLASHES =
OVERCRANK
3 FLASHES =
OVERSPEED LOW OIL PRESSURE
4 FLASHES = 5 FLASHES =
HIGH OIL TEMP
6 FLASHES = UNDERSPEED
MAINTENANCE SCHEDULE
OIL LEVEL:
AIR FILTER:
LOCATED BEHIND PANEL
*
OIL & OIL FILTER:
SPARK PLUGS:
REPLACEMENT INFORMATION
PREFILTER P/N: AIR FILTER P/N: OIL FILTER P/N: SPARK PLUG P/N:
OIL CAPACITY WITH FILTER:
TEMPERATURE
40˚F AND HIGHER
-20˚F TO 40˚F
API SERVICE CLASSIFICATION SF, SG OR SH WHEN SERVICE OR PARTS ARE NEEDED IN
THE USA OR CANADA, CONTACT THE GENERAC
SERVICE LOCATOR AT 1-800-333-1322.
CHECK DAILY
CLEAN PREFILTER EVERY 100 HOURS. REPLACE ELEMENT EVERY 250 HOURS.
CHANGE EVERY 100 HOURS. (OR ANNUALLY)
PERFORM MORE OFTEN IN DUSTY CONDITIONS
*
INSPECT & CLEAN PLUGS EVERY 500 HOURS. REPLACE PLUGS IF NECESSARY
SAE VISCOSITY
SAE 30 OR 10W-30
5W-30 OR 5W-20
SEE OWNERS MANUAL FOR FURTHER EXPLANATION
}
*
*
*
0D4511 0D9723 070185 072347
0.8L/0.84QT
14 Generac®Power Systems, Inc.
3.3 MAINTAINING THE ENGINE AIR CLEANER
3.3.1 CLEANING THE FOAM PRECLEANER
Clean and re-oil the foam precleaner every six months. Service the foam precleaner more frequent­ly if operating the generator in extremely dusty or dirty conditions. Use the following procedure (Figure
3.2):
Figure 3.2 — Engine Air Cleaner
1. Turn the two screws counterclockwise to loosen.
2. Remove the cover, foam precleaner and paper fil-
ter.
3. Remove the foam precleaner from the cover.
4. Wash the foam precleaner in liquid detergent and
water.
5. Wrap the foam precleaner in a clean cloth and
gently squeeze it dry.
6. Saturate the foam precleaner in clean engine oil.
Gently squeeze it in a clean cloth to remove excess oil and to distribute oil (DO NOT TWIST).
7. Install the foam precleaner into the cover, fol-
lowed by the paper filter.
8. Install the cover, foam precleaner and paper filter.
9. Tighten the two screws to retain the filter in place.
3.3.2 CLEANING OR REPLACING THE PAPER FILTER
Once each year or more frequently if operating in dirty or dusty conditions, clean or replace the paper filter. The new replacement filter must be flame retar­dant. Service the paper filter more frequently if oper­ating the generator in extremely dusty or dirty condi­tions. Use the following procedure (Figure 3.2):
1. Follow steps 1-3 in Section 3.3.1; service the foam precleaner if necessary.
2. Remove the paper filter.
3. Clean the air filter by tapping it gently on a solid surface. If the filter is too dirty, replace it with a new one. Dispose of the old filter properly.
4. Clean the air cleaner cover then reassemble fol­lowing steps 7-9 in Section 3.3.1.
3.4 CLEAN AIR INTAKE
Clean all foreign material from the air intake (Figure
3.3) at least once every six months. Clean more often if necessary.
Inspect the area around the generator periodically and remove all grass, leaves, etc., from area.
Figure 3.3 — Cleaning Air Intake
3.5 CHECKING THE ENGINE SPARK PLUG
Clean the spark plug and reset the spark plug gap annually. Replace spark plug when the electrodes have worn to the point where the proper gap cannot accurately be set, or if the insulation is cracked.
1. Clean the area around the base of the spark plug
to keep dirt and debris out of the engine. Remove the spark plug and check the condition. Replace the spark plug if worn or if reuse is questionable.
2. Clean spark plug by scraping or washing using a
wire brush and commercial solvent. Do not blast the spark plug to clean.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.030 inch (0.76 mm) by carefully bending the ground electrode (Figure
3.4).
Figure 3.4 — Setting the Spark Plug Gap
USTC
Section 3 – Maintenance
CENTURION 3500 Home Standby Generator
USTC
Loading...
+ 36 hidden pages