CDVI Erone EACP106E, Erone EACP106, F0544000048, F0544000049 Installation Manual

ELECTRONIC CONTROL PANEL FOR TWO 24Vdc MOTORS APPARECCHIATURA DI COMANDO 2 MOTORI 24Vdc
ENGLISH
EN
EACP106E
ITALIANO
IT
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
2 erone.com
1] Product range
Important precautIons for the safety
The present document contains important precautions for the use and the operating safety. Read carefully the instructions before commencing the installation. Keep this document even after installation.
!
This product, if properly installed by specialized personnel, able to perform the necessary risk analysis, complies with the Regulations EN 12453 - EN 12445
These warnings are integral and essential parts of the product and must be delivered to the user. Read them carefully as they provide important information regarding installation, use and maintenance. This form must be kept and transmit it to any subsequent users in the use of the system. Incorrect installation or use improper use of the product can be a source of serious danger.
2] Dimensions
Part-name Part-Number Description
EACP106E F0544000048 2 MOTORS 24 Vdc control panel w/enclosure
EACP106 F0544000049 2 MOTORS 24 Vdc control panel card
319
223
100
285.4
195.4
Fig.1
3erone.com
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
4] Technical specications
Parameter Value
Power supply 230 Vac +/- 10% / 50 Hz
Motor power supply 24 Vdc
Switching power for courtesy light max 10A / 230 Vac
Switching power for ashing light
max 10A / 230 Vac
Power for accessories
33V - 24 Vdc - 250 mA
Automatic reclosing time 5 - 120 Sec.
Working time 3 - 120 Sec.
Courtesy light time 180 Sec.
Memory for S/N security codes
260
Security protocol Keeloq Hopping code
Frequency 433,92 MHz
Operating temperature -20 / +70°C
Enclosure protection IP55
1) Depending on the type of the gates, locate the best position for the appliance, close to the gate, safe from shocks and tampering, high enough from the ground, safe from water and easily accessible for maintenance operations.
2) Unscrew the 4 screws of the cover and verify the electronic card integrity. (Fig. 2).
3) Trace the 4 xing points using the container as template mark or making reference to the distances shown on
Fig. 1
4) Drill 4 holes Ø6 mm for the plugs and fasten the box with 4 x M4 screws.
5) Insert the cable holders ( if provided ) throught the pre-cuted holes and pass the cables, keeping the mains cables and low voltage cables seperated .
6) If not provided with the appliance, connect an all-pole 10A thermal breaker switch with contact opening distance of 3mm or greater.
Make sure that a differential switch with threshold of 0.03 A is tted upstream of the system.
7) Make the connections with reference to paragraph 7.
3] Installing
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
4 erone.com
5] Preliminary recommendations
Installation and testing must be carried out only by qualied personnel to guarantee the
correct and safe functionality of the automatic gate.
The manufacturer declines all responsibility for damages deriving from any incorrect installation due to incapacity and / or negligence.
Before proceeding with the installation of the automatiion, check that the door is fully functional and balanced.
6] Main board layout
Buzzer
P3
LV LR
JP1
T1
T2 T3
PG2
PG1
P2
1 2 3
4 5 6 7
8 9 10 11
25 26 27 28 29
12 13 14 15 16 17 18 19 20 21 22 23 24
34 35
30 31 32 33
FUSE 10A
FUSE 2A
L4 L5 L6 L7 L8 L9 L10
L3
P1
L2
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
5
erone.com
7] Connections
POWER SUPPLY & MOTOR CONNECTIONS
TERMINAL CONNECTIONS
32 33
8 9
L
N
230 V~
M1
4 5
2122 2324
Courtesy Lamp 230 V~
Power Accessories 33 Vdc 250 mA
1516 17
FTC OP
FTC CH
121314
FCC2
FCA2
181920
FCC1
FCA1
PED.
STOP
START
POWER SUPPLY ACCESSORIES / ELECTROLOCK / ANTENNA
25 26
26 27 28 29
12 V=
+ -
Electrolock
34 35
RG58
Antenna
POTENTIOMETERS
+
-
+
-
+
-
T1
T2
T3
T1 adjusts torque and
sensitivity in regular mode
T2 adjusts torque and sensitivity
in slow down mode
T3 adjusts the pause
time [3 - 120 sec.]
30 31
24 V~ Sec. TRF
10 11
M2
6 7
Power Accessories 24 Vdc 250 mA
Flashing Lamp 230 V~ 10A
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
6 erone.com
Terminals Type Description
1 - 2 - 3 230 V~ Input Line L- N - PE
4 - 5 230 V~ Output ashing lamp
6 - 7 230 V~ Output courtesy light
8 - 9 24 Vdc Input MOTOR 1
10 - 11 24 Vdc
Input MOTOR 2
12 - 14 NC Open limit switch Motor 2 (*)
13 - 14 NC
Close limit switch Motor 2 (*)
15 - 17 NC Contact safety Bar ( reopen photocell ) (*)
16 - 17 NC Contact Close photocell (*)
19 - 18 NC Close limit switch Motor 1 (*)
20 - 18 NC Open limit switch Motor 1 (*)
21 - 23 NC STOP Command (*)
22 - 23 NO Pedestrian Open
24 - 23 NO START Command ( open / stop / close / stop )
25 - 26 33 V= Power supply photocells + accessories 33 Vdc / 250 mA ( or battery
charger)
26 - 27 24 V= Power supply photocells + accessories 24 Vdc / 250 mA
28 - 29 12 V= Power supply Electrolock
34 - 35 50 Ohm Input antenna - Cable RG58 ( 34 GND, 35 SIGNAL)
(*) : short if not used
8] Legenda connections
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
erone.com 7
Function Dip-switch Pos Description
1
Automatic closing
ON Automatic closing activated
OFF Automatic closing disabled
2
Condominium / step-by-step
ON During opening does not accept further commands
OFF Command : OPEN/STOP/CLOSE/STOP
3
limit switches management
ON
During the self-calibrating the leaves don’t stop at the limit switch but keep on moving up to the next command
OFF During the self-calibrating the leaves stop at the limit switch
4 Opening Jolt
ON Opening jolt enabled
OFF Opening jolt disabled
5
Contact safety in opening
ON
NC contacts (15-17), stop & invert for 2 sec on opening, stop & invert the direction on closing
OFF
NC contacts (15-17) stop the movement on opening, stops & inverts on closing
6
Flashing function
ON Warning light blinking
OFF Warning light xed
7 Slow down
ON slow down mode at the end of each manouvre ( opening and closing )
OFF No slow down : full torque
8
Periodic closing command for security
ON
Every 180 min, the panel gives a closing command, avoiding any gate-opened situation
OFF Function disabled
9] Dip-switch settings
NOTES
Safety edge, connected on terminals 15-17 - This contact protects opening and closing.
DIP 5 ON: When there is an obstacle, the motors stop and reverse for 2 sec. DIP 5 OFF: When there is an obstacle motors STOP. In both cases after the disengagement resumes the opening.
Photocells, connected on terminals 16-17 - This contact protects only in closing : when there is an obstacle the motors STOP;
Emergency Stop connected on terminals 21-23 - The contact, if open, will cause the immediate stop of the automation in any situation.
FLASHING LIGHT
If Dip6=ON then: IN OPENING: blinking slow IN CLOSING: blinking fast IN PAUSE: steady light PHOTOCELL ENGAGED: Turn off
GALEO
Illuminated RF Keypad
INSTALLATION MANUEL
EACP106E
Electronic control panel for two 24 Vdc motors
INSTALLATION MANUAL
EN
8 erone.com
10a] Double gates programming
The programming starts with the gate closed. The rst operation must be the opening: if the gates close, invert
the connection of the motor wires on the terminals.The programming of the gates will be done using the buttons PG1 for gate 1 and PG2 for gate 2.To enter the programming press P2 for 2 sec LED L3 lights up.
PG1
PG2
P2
2 sec.
L3
Wait for leaves
staggering
Press PG2 : gate 2 starts
Press PG1 : gate 1 starts
1 - OPENING PROGRAMMING
PG1
Press PG1 : gate 1 starts the slow down (*)
PG2
Press PG2 : gate 2 starts the slow down (*)
PG1
Press PG1 : gate 1 stops
PG2
Press PG2 : gate 2 stops
Press PG2 : gate 2 starts closing
Wait for leaves
staggering
Press PG1 : gate 1 starts closing
PG2
Press PG2 : gate 2 starts the slow down (*)
PG1
Press PG1 : gate 1 starts the slow down (*)
Press PG2 : gate 2 stops
PG2
PG1
Press PG1 : gate 1 stops
2 - CLOSING PROGRAMMING
End of the procedure