N O T I C E D E M O N T A G E E T D ’ U T I L I S A T I O N
This device comes with a varistor.
The varistor must be connected to the strike terminal
(electromagnet…) operated by the device.
If this product works with many strikes, each of them
should have a varistor.
The varistor controls the overload produced by the strike
coil – self-effect.
If you are using a « Shear Lock » electromagnetic lock, it is recommended to
use a separate power supply than the one connected to the DG502U!
Warning
Do not use a switching power
supply because of the interference
radiation that may disturb the
reading of the badges
DG502U/A
DG502U/P
2-DOOR CONTROLLER
500 USERS

2 form C relays N/O and N/C 3A @ 125V
12-digit keypad with built-in buzzer (Audible feedback)
Distance between the
remote readers and the
controller
60 cm minimum,
50 meters maximum
(cable spec. 7 x 0.6 mm2)
Default Factory Values
Master Code: 12345
Door release time: 1 second
Key-in Keypad: 10 seconds
Enrollment unit: Built-in reader in controller
Power consumption
DG502 only: 160mA
DG502 with 1 remote reader: 240mA
DG502 with 2 remote readers: 320mA
Audible Feedback
Validation of data in programming mode: master code,
proximity badge or time delay.
Accessing the programming mode
or exit from the programming mode
Badge not programmed (invalid badge)
or incorrect master code or time delay entered
Request-to-Exit Inputs
The two request-to-exit inputs PB1 and PB2 operate relay RL1 and RL2.
The LED turns on green when the relay is activated by one of the two inputs.

Changing the Master Code
1. Enter the master code twice (for the first use the master code default value
is 12345). 2 beeps and the orange LED lights on confirming that you are in
programming mode.
2. Enter *3 then the 5-digit new master code. The LED goes off during 1 second
and an audible beep indicates that the new master code is memorised.
3. Press # to exit from the programming mode. 2 beeps confirm that you went
back to the reading mode.
4 beeps indicate a data computing error.
Time outputs, Enrolment Reader and Access Level
Enter the master code twice (for the first use the master code default value is
12345). 2 beeps and the orange LED lights on confirm the entry in programming
mode.
Enrolment reader
(* mag stripe must
be set as remote
enrolment reader)
Enter 0, then 00 to select the built-in reader of the controller as the
enrolment unit.
*Press 0, then 01 remote reader 1 as the enrollment unit.
The LED lights off during 1 second and an audible beep indicates
the validation of the enrolment reader.
In stand-by mode, if the enrolment reader is the controller
built-in reader all the readers can be used but if the enrolment
reader is the remote reader 1 then only the 2 remote reader can
be used.
Enter 1, then the time relay in second:
01 equal 1 second up to 99 for 99 seconds.
00 corresponds to a latched output.
The LED lights off during 1 second and an audible beep indicates
the validation of the time delay.
Enter 2, then the time relay in second:
01 equal 1 second up to 99 for 99 seconds.
00 corresponds to a latched output.
The LED lights off during 1 second and an audible beep indicates
the validation of the time delay.
Enter 4 , then 01 for door 1 and controller activates relay 1
02 for door 2 activates relay 2
03 door 1 and 2 activates relay 1 2
The LED lights off during 1 second and an audible beep indicates
the validation of the access level.
Press # to exit from the programming mode. 2 beeps confirm that you returned
to reading mode.
4 beeps indicate a data computing error.