Cashco PS2 I-P User Manual

SSSSIIIIPPPPAAAARRRRTTTTP
PSSSS22226
PP
6DDDDRRRR5555xxxxxxxxxxxx
66
MMMMaaaannnnuuuuaaaallll
EEEElllleeeeccccttttrrrrooooppppnnnneeeeuuuum LLLLiiiinnnneeeeaaaarrrra
annnnddddR
aa
maaaattttiiiiccccP
mm
RoooottttaaaarrrryyyyA
RR
EEEEddddiiiittttiiiioooonnnn00002222////00001111
Poooossssiiiittttiiiioooonnnneeeerrrrffffoooorrrr
PP
Accccttttuuuuaaaattttoooorrrrssss
AA
SIMATICr,SIPARTr,SIRECr, SITRANSr are registered trademarks of Siemens AG. All other product or system names are (registered) trademarks of their respective owners and must be treated accordingly.
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights created by the granting of patents or registration of a design are reserved.
Technical data subject to change without notice
Contents
0 Information for the Operator 5.............................................
0.1 General information 5...........................................
0.2 Meaning of safety instructions and warnings 6.....................
0.3 Qualified Personnel 7...........................................
0.4 Use as intended 8..............................................
0.5 Technical Documentation 8......................................
0.6 Warranty Information 9..........................................
0.7 Delivery Notes 9...............................................
0.8 Standards and Regulations 10....................................
1 Introduction 11............................................................
1.1 General information about the positioner 1 1.........................
2 Design and Method of Operation 15........................................
2.1 Overview 15....................................................
2.2 Instrument Components 16.......................................
2.2.1 Motherboard 17.................................................
2.2.2 Electrical Connections 17.........................................
2.2.3 Pneumatic Connections 18.......................................
2.2.4 Mounting Kit 21.................................................
2.2.5 Purge air switching (not in the explosion proof version) 21............
2.2.6 Restrictors 21...................................................
2.3 Method of Operation 22..........................................
2.4 State as supplied 25.............................................
2.5 Options modules 25.............................................
2.5.1 Options modules in normal and intrinsically safe versions 25..........
2.5.2 Options modules in explosion proof version 28......................
2.5.3 HART-function 29...............................................
2.5.4 Alarm module 30................................................
2.5.5 Jy-module 31...................................................
2.5.6 SIA module 31..................................................
2.5.7 Accessories 32.................................................
3 Preparing for Operation 33.................................................
3.1 Instrument identification (type key) 33..............................
3.2 Dimensional drawings 33.........................................
3.3 Assembly 35....................................................
3.3.1 Instructions for using positioners in a wet environment 36.............
3.3.2 Instructions for using positioners which are exposed to great accelerations
or vibrations 38.................................................
3.3.3 Mounting kit ”linear actuator” 6DR4004-8V and 6DR4004-8L 39.......
3.3.4 Assembly procedure (see figure 3-6, page 41) 39....................
SIPART PS2 Manual A5E00074631-- 01
3
3.3.5 Mounting kit ”Rotary actuator” 6DR4004-8D 42......................
3.3.6 Assembly procedure (see figure 3-7 and figure 3-8) 43...............
3.4 Electrical Connection 48..........................................
3.4.1 Connection variants 49...........................................
3.4.1.1 Connection variant: not intrinsically safe 49.........................
3.4.1.2 Connection variant: intrinsically safe 50............................
3.4.1.3 Connection variant: Options in positioner in non--intrinsically safe
and explosion proof version 52....................................
3.4.1.4 Connection variant: Options in the positioner in intrinsically safe
version 54......................................................
3.5 Pneumatic Connection 56........................................
3.6 Commissioning 57...............................................
3.6.1 Preparations for linear actuators 58................................
3.6.2 Automatic initialization of linear actuator 59.........................
3.6.3 Manual initialization of linear actuator 61............................
3.6.4 Preparations for rotary actuator 64.................................
3.6.5 Automatic initialization of rotary actuator 64.........................
3.6.6 Manual initialization of rotary actuators 66..........................
3.6.7 Automatic initialization (structograms) 67...........................
3.7 Copying initialization data (positioner exchange) 72..................
4 Operation 73.............................................................
4.1 Display 73......................................................
4.2 Input keys 73...................................................
4.3 Operating modes 76.............................................
4.4 Parameters 78..................................................
4.5 Diagnosis 90...................................................
4.5.1 Diagnostic display 90............................................
4.5.2 Meaning of the diagnostic values 91...............................
4.5.3 Online-Diagnosis 93.............................................
5 Service and Maintenance 99................................................
6 Technical Data 101.........................................................
7 Scope of Delivery 105.......................................................
7.1 Scope of delivery of standard controller 105..........................
7.2 Scope of delivery of options 106....................................
7.3 Scope of delivery of accessories 106................................
A Appendix 107..............................................................
A1 Index 107..........................................................
A2 Literature and Catalog 109...........................................
A3 Conformity 109.....................................................
SIPART PS2 Manual
4
A5E00074631-- 01
Information for the Operator

Information for the Operator

Dear customer,
Please read this manual before starting work!
It contains important information and data which, when observed, ensure full availability of the equipment and save service costs. This simplifies handling of this control instrument considerably and provides accurate measuring results.
You have purchased an instrument which can be installed in various configurations:
- SIPART PS2 without Ex-protection in a metal-- or plastic housing.
- SIPART PS2 with EEx ia/ib-protection in a metal-- or plastic
housing.
- SIPART PS2 EEx d in a pressurized explosion proof metal housing
This manual takes each of these possibilities into consideration. Any differences between the devices are indicated specially.
Scope of delivery, see chapter 7, page 105.
0

0.1 General information

The product described in this manual left the factory in a perfectly safe and tested condition. To maintain this condition and to achieve perfect and reliable operation of this product, it must only be used in the way described by the manufacturer. Successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance.
This manual contains the information required for use as intended of the product it describes. It is addressed to technically qualified personnel specially trained or having relevant knowledge of instrumen­tation and control technology, hereafter called automation technology.
Familiarity with and proper technical observance of the safety notes and warnings contained in this manual are essential for safe installation and commissioning and for safety in operation and maintenance of the product described. Only qualified personnel as defined in Chapter 0.3 has the necessary specialist knowledge to interpret the general safety notes and warnings given in this document in specific cases and to take the necessary action.
The documentation supplied with the instrument is listed in Chapter
0.5.
SIPART PS2 Manual A5E00074631-01
5
Information for the Operator
This manual is not a permanent part of the scope of supply. For reasons of clarity, it does not contain every detail about every version of the product described and cannot take every eventuality in installa­tion, operation, maintenance and use in systems into account. If you require further information or if problems occur that have not been dealt with in sufficient detail in this document, please request the required information from your local Siemens office or the office responsible for you.
Functionality, commissioning and operation are described in this manual.
Please pay special attention to the Warning and Note texts. These are separated from the remaining text by horizontal lines and specially marked with symbols (see Chapter 0.2).

0.2 Meaning of safety instructions and warnings

Safety information and warnings are intended to avert danger from the life and health of users and maintenance personnel and to prevent material damage. They are highlighted in this manual by the headings defined here. They are also marked by warning symbols next to where they appear. The headings used have the following meaning for the purposes of this manual and the product labels:
DANGER
!
!
!
indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
used with the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
used with the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
SIPART PS2 Manual
6
A5E00074631-01
Information for the Operator
NOTICE
NOTICE used without the safety alert symbol indicates a potential situation which, if not avoided, may result in an undesireable result or state.
.
NOTE
indicates a reference to a possible advantage when this recommendation is followed.

0.3 Qualified Personnel

The result of unqualified intervention in the instrument or nonobservance of the warnings given in this manual or on product labels can be severe personal injury and/or serious material damage. Therefore only properly qualified personnel must make changes and settings in the instrument.
For the purpose of the safety information in this manual and on the product labels, qualified personnel are those who
S if they are configuration personnel, are familiar with the safety
concepts of automation technology
S if they are operating personnel, have been instructed in the handling
of automation equipment and know the content of this manual relating to operation
S if they are commissioning and/or service personnel, are trained to
repair such automation equipment and authorized to energize, de-energize, clear ground and tag circuits and equipment according to safety engineering standards.
SIPART PS2 Manual A5E00074631-01
S and instructed additionally in first aid
S and, in the case of ex-proof equipment, are trained, instructed or
authorized to perform work on electrical circuits of equipment subject to explosion hazard.
7
Information for the Operator
WARNING
!
The instrument must only be installed and commissioned by qualified personnel.
The instrument is designed for connection to functional and safety extra low voltage.
Electrical safety depends only on the power supply equipment.
Pneumatic actuators exert considerable positioning forces. The safety precautions of the actuator used must therefore be scrupulously observed during installation and commissioning in order to prevent injuries.
We explicitly draw your attention to the necessity of observing safety regulations regarding operation in zones subject to explosion hazard, if applicable.

0.4 Use as intended

Use as intended for the purpose of this manual means that this product must only be used for the applications described in the technical description (see also Chapter 3 of this manual).
The product described in this manual has been developed, manufac­tured, tested and documented observing the relevant safety standards. If the handling rules and safety information for configuration, installa­tion, use as intended and maintenance are observed, there is normally no danger with regard to material damage or for the health of personnel. Extra low voltages that are connected must be fed in by safe isolation.

0.5 Technical Documentation

In addition to this manual, the following documentation is also supplied with the instrument:
- Leaflet “Operation -- Concise Overview”
explains in visualized form the principle of operation and parameterization and automatic commissioning.
- “Operating Instructions”
contains the information required for assembly, connection and commissioning.
SIPART PS2 Manual
8
A5E00074631-01
Information for the Operator
The following list contains all the documents available for these instruments:
Title Language Order No.
Operating Instructions
German/English French/Italian/Spanish
A5E00074600 A5E00074601
Manual German
Leaflet German

0.6 Warranty Information

We should like to point out that the content of this manual is not part of and does not modify a previous or current agreement, undertaking or legal relationship. Siemens is bound solely by the contract of sale, which also contains the complete and exclusive warranty. The contractual warranty conditions are neither extended nor restricted by this document.

0.7 Delivery Notes

English
English French Italien Spanish
A5E00074630 A5E00074631
A5E00074610 A5E00074611 A5E00074612 A5E00074613 A5E00074614
The scope of delivery is listed on the dispatch papers accompanying the delivery in accordance with the valid contract of sale.
When you open the packaging please observe the information on the packaging. Check that the delivery is complete and undamaged. If possible, compare the order number on the rating plates with the ordering data.
For the scope of delivery please see Chapter 7.
SIPART PS2 Manual A5E00074631-01
9
Information for the Operator

0.8 Standards and Regulations

As far as possible, the harmonized European standards were used to specify and manufacture this equipment. If harmonized European standards have not been applied, the standards and regulations of the Federal Republic of Germany apply (see also the Technical Data in Chapter 6, page 101).
If this product is used outside the area of applicability of these standards and regulations, please observe the standards and regulations in force in the country where the product is operated.
10
SIPART PS2 Manual
A5E00074631-01
Introduction

Introduction

1.1 General information about the positioner

The positioner is used to adjust and control pneumatic actuators. The controller operates electropneumatically with compressed air as an energy supply.
Purpose
For example, the positioner can be used to control valves as follows:
- with linear actuator (figure 1-1, page 13) or
- with rotary actuator VDI/VDE 3845 (figure 1-2, page 13)
Different mounting types are available for linear actuators:
- NAMUR or IEC 534
- integrated mounting to ARCA
1
Versions
Housing
- integrated mounting to SAMSON (non--explosion--proof version)
This means the positioner can be installed and operated on all common actuator systems.
The positioner is available for the following actuators:
- double--acting and
- single--acting
For following applications:
- potentially explosive or
- not potentially explosive applications.
The electronics with display, position feedback and valve block are integrated in the housing.
The housing is available in three versions:
- Plastic housing for single and double--acting actuators
- Metal housing for single--acting actuators
- Explosion proof metal housing for single and double--acting
actuators
SIPART PS2 Manual A5E00074631-01
11
Introduction
Degree of protection
Explosion Protection
Options
Accessories
The device is designed with IP65/NEMA4x degree of protection.
The intrinsically safe version can be used in hazardous areas in zone 1 or zone 2. The explosion proof version can be used in hazardous areas in zone 1 or zone 2.
The positioner can be expanded with various options modules (chapter
2.5, page 25). The following modules are available in all:
-module: Two--wire current output 4 to 20 mA for position feed-
- J
y
back
- Alarm module: 3 digital outputs and 1 digital input
- SIA module: one digital output for fault messages, two digital out-
puts for limit value alarms
- Manometer block: 2 or 3 manometers for single and double action positioners
- Add--on flange (NAMUR) for safety valve block
- Add--on sets for linear and rotary actuator
Environmental Protection
Only environmentally friendly materials have been used in the construction of the positioner.
The technical manual is printed on chlorine--free bleached paper.
12
SIPART PS2 Manual
A5E00074631-01
Introduction
1
2
3
1 Actuator 2 Positioner, single action in metal housing 3 Lantern 4 Manometer block, single action 5Valve
Figure 1-1 Positioner mounted on linear actuator (single action)
4
5
1
2
1 Positioner double action in plastic housing 2 Rotary actuator 3 Manometer block, double action
Figure 1-2 Positioner mounted on rotary actuator (double action)
3
SIPART PS2 Manual A5E00074631-01
13
Introduction
1
2
4
3
1 Actuator 2 Positioner, single action in metal housing 3 Lantern 4 Manometer block, single action
Figure 1-3 Explosion proof positioner mounted on linear actuator (single action)
1
3
2
1 Positioner double action in plastic housing 2 Rotary actuator 3 Manometer block, double action
Figure 1-4 Explosion proof positioner mounted on rotary actuator (double action)
14
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle

Design and Method of Operation

The following chapter describes the mechanical and electrical design, the instrument components and method of operation of the positioner.

2.1 Overview

Introduction
The electropneumatic positioner forms a control system in connection with an actuator. The current position of the actuator is detected by a servo potentiometer and fed back as actual value x. The setpoint and actual value are output simultaneously on the display.
The setpoint w is formed by a current fed to the positioner which at the same time serves to supply the positioner in two-wire operation. In 3 / 4-wire operation the supply comes from a 24 V voltage input.
The positioner operates as a predicative five--point switch by the output variable ±Dy of which the integrated actuating valves are controlled with pulse length modulation.
2
These actuating signals cause fluctuations in pressure in the actuator chamber(s) and thus adjustment of the actuator until the control error is zero.
Operation (manual) and configuration (structuring, initialization and pa­rameterization) is effected by three keys and a display with the housing cover removed.
The standard controller has one digital input (DI1). This can be configu­red individually and can be used for blocking the operating levels for example.
With the J as a two wire signal J
In addition the actuator can be monitored for two programmable limit values which respond on exceeding or dropping below the stroke or angle of rotation.
The limit value alarms are output by the alarm option module which can monitor and report the function of the positioner and the actuator addi­tionally through a fault message output. The value of the control diffe­rence dependent on the floating time is monitored in automatic mode. The fault signal is always set when the control error cannot be leveled after a certain time because for example the valve is blocked or the mains pressure is insufficient. The three digital outputs are implemen­ted as semiconductor outputs and are error self--reporting, i.e. the out-
-option module, the current actuator position can be output
y
=4to20mA.
y
SIPART PS2 Manual A5E00074631-01
15
Design and Functional Principle
1
puts respond even when the power supply fails or the electronics are defective.
The actuator can also be blocked or driven to its final positions depen­ding on the configuration for example by an external event via a digital input (DI2) on the alarm module.
If you require electrically independent limit value messages from the standard controller, you will have to use the SIA module with the slot initiators instead of the alarm module.
Communication with the controller is possible via the optional HART interface.

2.2 Instrument Components

314
15
90°
3/4 W2W
13
12
1 Input: Supply air 7 Silencer 2 Output: Actuating pressure Y1 8 Transmission ratio selector 3 Display 9 Adjusting wheel slip clutch 4 Output: Actuating pressure Y2 5 Operating keys 12 Dummy plug 6 Restrictor 13 Screw-- type cable gland
6.1 Restrictor Y1 14 Terminal plate on cover
6.2 Restrictor Y2
*)
in double-- acting actuators
*)
4...20 mA 0/4...20 mA
*)
O
33
O
DI1
90
33°
6.1 6.2
789101
10 Terminals options modules
15 Purging air switch
2
1
4
56
Figure 2-1 View of the positioner in normal version (cover open)
SIPART PS2 Manual
16
A5E00074631-01
Design and Functional Principle
9
1
10
3
---­++
10
1 Input: Supply air 7 Transmission ratio selector 2 Output: Actuating pressure Y1 (only possible with positioner open) 3 Display 8 Adjusting wheel slip clutch 4 Output: Actuating pressure Y2 5 Operating keys 10 Terminals options modules
6.1 Restrictor Y1 12 Safety catch
6.2 Restrictor Y2
*)
in double-- acting actuators
*)
*)
2121
6.1
138238 9
6.2
45
9 Terminals standard controller
7
8
Figure 2-2 View of the explosion proof version of the positioner

2.2.1 Motherboard

The motherboard contains all the electronic elements such as the CPU, memory, A/D converter . It also contains the display and the operating keys.
In addition, the terminal strips for connecting the options modules are also on the motherboard.

2.2.2 Electrical Connections

The terminals of the standard controller, the Jy- and alarm-option mo­dule are arranged at the left--hand front edges and offset against each other in staircase form.
A module cover protects the modules from being pulled out and pre­vents incorrect installation.
SIPART PS2 Manual A5E00074631-01
17
Design and Functional Principle

2.2.3 Pneumatic Connections

The pneumatic connections are on the right hand side of the positioner (figure 2-3 and figure 2-4).
1
2
3
4
5
1 Actuating pressure Y1 in single-- and double-- acting actuators 2 Feedback shaft 3 Supply air P 4 Actuating pressure Y2 in double--acting actuators 5 Exhaust air output E with silencer on the bottom of the instrument
z
Figure 2-3 Pneumatic connection in normal version
1
2
3
4
5
6
7
1 Restrictor Y2 *) 5 Actuating pressure Y1 2 Restrictor Y1 6 Exhaust air output E 3 Actuating pressure Y2 *) 7 Housing ventilation (2x) 4 Supply air PZ
*)
in double-- acting actuators
Figure 2-4 Pneumatic connection in explosion proof version
18
In addition, there are pneumatic connections on the back of the positio­ner for integrated installation in single--acting linear actuators.
- Actuating pressure Y1
- Exhaust air output E (not in explosion proof version)
In the ex--factory state, these connections are sealed by screws (see figure 3-1, page 33, figure 3-3, page 34 and figure 3-4, page 35).
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle
The exhaust air output E can be provided for supplying dry instrument air to the tapping chamber and spring chamber to prevent corrosion.
Figure 2-5, page 20 shows the pneumatic connection variants for the different actuator types, the positioning action and the safety position after power failure.
SIPART PS2 Manual A5E00074631-01
19
Design and Functional Principle
Positioning pressure Connection
Y1
Y1
Y2
Y1
Y1
Y2
Closed
Closed
Actuator type
Open
Open
OpenClosed
OpenClosed
Safety position after power failure
electrical pneumatic
Closed Closed
Open Open
Open
Last position
(before power
failure)
Closed
In rotary actuators the direction of rotation counterclockwise looking onto the actuating shaft of the valve is usually defined as ”Open”.
Open
Closed
Y1
up
Down Down
down
Y1
up
down
Up Up
Y2
Y1
up
down
Up
Y1
Y2
up
down
Down
Figure 2-5 Pneumatic connection positioning
Last position
(before power
failure)
up down
20
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle

2.2.4 Mounting Kit

The positioner can be mounted on almost all actuators with the appro­priate mounting kit.

2.2.5 Purge air switching (not in the explosion proof version)

The purge air switch is accessible above the pneumatic terminal strip with the housing open (figure 2-6). In the IN position the inside of the housing is purged with very small amounts of clean, dry instrument air. In the OUT position the purge air is fed directly to the outside air.
Figure 2-6 Purge air switch on the valve block, view of the positioner onto pneumatic connection side
with cover open

2.2.6 Restrictors

In order to achieve floating times of > 0.5 s in small actuators, the air rate can be reduced with the restrictors Y1 and Y2 (figure 2-7, in explosion proof version, see figure 2-4, page 18). By turning to the right the air rate is reduced up to shutting off. To set the restrictors it is advisable to close them and then open them slowly (see initialization RUN3).
Y1 Y2
Figure 2-7 Restrictors
SIPART PS2 Manual A5E00074631-01
21
Design and Functional Principle

2.3 Method of Operation

The electropneumatic positioner SIPART PS2 forms a control circuit with the pneumatic actuator in which the actual value x is the position of the actuator bar in linear actuators or the position of the actuator shaft in rotary actuators and the command variable w is the actuating current of a controller or a manual control station of 4 to 20 mA.
The stroke or rotary movement of the actuator is transferred by the appropriate mounting accessories, the feedback shaft and a play--free switchable gearwheel to a high quality conductive plastic potentiometer and to the analog input of the microcontroller .
This may correct the angle error of the stroke tap, compares the potemtiometer voltage as actual value x with the setpoint w fed in at the terminals 3 and 7 and calculates the manipulated variable increments Δy. Depending on the size and direction of the control error (x-w) the piezo--controlled supply air or exhaust air valve is opened. The volume of the actuator integrates the positioning increments to actuating pressure y open which moves the actuator bar or actuator shaft approximately proportionally. These positioning increments change the actuating pressure until the control error becomes zero.
The pneumatic actuators are available in single and double action versions. Only one pressure chamber is aerated or deaerated in the single action version. The resulting pressure operates against a spring. In the double action version, two pressure chambers are counteractive. In this case the one volume is deaerated when the other volume is aerated. See the block diagram figure 2-9, page 24.
The control algorithm is an adaptive predicative five--point switch (see figure 2-8, page 23).
The valves are controlled with continuous contact at large control errors (fast action zone). At medium control errors the valve is controlled by pulse length modulated pulses (slow action zone).
No actuating pulses are output in the small control error zone (adaptive dead zone). The dead zone adaptation and the continuous adaptation of the minimum pulse lengths in automatic operation cause the best possible control accuracy to be achieved at the lowest switching fre­quency. The start parameters are determined during the initialization phase and stored in a non--volatile memory. These are basically the real actuating path with the mechanical limit stops, the floating times, the size of the dead zone etc.
In addition the number of fault messages, changes in direction and the number of strokes are determined and stored every hour during operation. These parameters can be read out and documented by the communication programs such as PDM and AMS. Conclusions as to the wear on the fitting can be drawn (diagnostic function) especially by comparing the old value with the currently determined values.
22
Figure 2-9, page 24 shows the block diagrams for single-- and double-­acting actuators with the linear actuator as an example.
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle
.
Figure 2-8 Method of operation five--point switch
NOTE
The exhaust air valve is always open when there is no current.
SIPART PS2 Manual A5E00074631-01
23
Design and Functional Principle
1
BE1
I
W+
I
W-
y
0
+
x
3 V
W
+U
_
W
x
0
6
BE2
7
+5 V
A
A
2
+24 V
D
D
HART
_
Micro-
controller
A1 A2
II
A1 A2
3
_
y
y
+
+
U
U
I
5
4
Supply ai r
Zuluft
p
Z
Exhaust a i r
Abluft
p
1
p
p
p
2
Abluft
Exhaust
air
1
2
stroke
9
p
2
p
1
stroke
8
p
1
1 Motherboard with microcontroller and input circuit 2 Control panel with LC-display and momentary action switch 3 Piezo-- valve unit, always built--in 4 Valve unit with double action positioner always built--in 5 Iy-module for positioner SIPART PS2 6 Alarm module for three alarm outputs and one digital input 7 SIA-module (Slot Initiator-Alarm-module) 8 Spring--loaded pneumatic actuator (single action) 9 Spring--loaded pneumatic actuator (double action)
Figure 2-9 Block diagram of the electro--pneumatic positioner, functional diagram
.
NOTE
Alarm module (6) and SIA module (7) can only be used alternatively.
24
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle

2.4 State as supplied

There are no mechanical mounting accessories on the controller in the state as supplied These must be ordered and installed according to the “operating instructions” depending on the application.
The respective connections for single or double action versions are pre­pared at the factory as ordered.
The pneumatic connections on the rear are sealed.

2.5 Options modules

2.5.1 Options modules in normal and intrinsically safe versions

The options modules are protected and mechanically fixed by a module cover ((1), see figure 2-10, page 27 and figure 2-11, page 29).
.
Opening the instrument
.
NOTE
The housing must be opened to install the options modules. The degree of protection IP65 is not guaranteed as long as the positioner is open.
To open the positioner, the four screws of the housing cover must be loosened with a Phillips screwdriver.
Disconnect or isolate the power supply cables.
Remove the module cover (1). To do this, the two screws (1.1) must be removed with a screwdriver .
NOTE
To prevent premature wearing of the fixture by the self--tapping screws (1.1), the following method of mounting the module cover (1) has proven effective.
1. Turn the screws counterclockwise until you feel them snap into the thread
2. Tighten both screws carefully in clockwise direction
Jy-module Insert the Jy-module (3) in bottom pcb rails of the container, establish
the electrical connection with the enclosed ribbon cable (6).
SIPART PS2 Manual A5E00074631-01
25
Design and Functional Principle
Alarm module Insert the alarm module (4) in the top pcb rails of the container,
establish the electrical connection with the enclosed ribbon cable (5).
SIA-module (Slot Initiator Alarm module) Proceed as follows for installation:
1. Remove all the electrical connections from the basic electronics (2).
2. Loosen the two fixing screws (2.1) of the basic electronics.
3. Snap out the basic electronic board by carefully bending the four holders.
4. Insert the SIA-module (7) from above up to the top pcb rail of the container.
5. Push the SIA module in the pcb rail of the container about 3 mm to the right.
6. Screw the special screw (7.1) through the SIA module into the axle of the positioner, please observe the following note: The pins pressed into the actuating disc bearing must be adjusted to just before touching with the special screw. The actuating disc bearing and the special screw must then be turned simultaneously so that the pins slot into the special screw.
7. Place the insulating cover (10) over the SIA module underneath the surface of the basic electronics board at the container wall on one side. The recesses in the insulating cover must slot into the corresponding lugs on the container wall. Place the insulating cover on the SIA module by carefully bending the container walls.
8. Snap the basic electronics board into the four holders and screw it tight again with the two fixing screws (2.1).
9. Make all the electrical connections between the motherboard and the options with the ribbon cables provided and between the mo­therboard and potentiometers with the potentiometer cable.
10. Fix the enclosed module cover instead of the standard version with the two screws.
1 1. Select the plates which already exist on the standard version of the
module cover from the set of plates enclosed. Stick the selected plates according to the standard version to the mounted module cover.
12. Make the electrical connections.
Setting the two limit values:
13. Drive the actuator to the first desired mechanical position.
26
14. Adjust the top actuating disc (for output terminals 41--42) by hand until the output level changes.
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle
15. Drive the actuator to the second desired mechanical position.
16. Adjust the bottom actuating disc (for output terminals 51--52) by hand until the output level changes.
.
NOTE
If you turn the actuating disc beyond the switching point up to the next switching point, you can set a high-low or a low-high change.
6
1
1.1
5
2.1
1.1
2.1
2
11
10
4
7
3
1 Module cover 7 SIA-module 2 Motherboard 7.1 Special screw
2.1 Fixing screws 8 Adjusting wheel slip clutch 3J
-module with ribbon cable (6) 9 Transmission ratio selector
y
4 Alarm module with ribbon cable (5) 10 Insulating cover 5 Ribbon cable for alarm module 11 Actuating disk bearings 6 Ribbon cable for Jy-module
Figure 2-10 Installation of Options Modules
7.1
8
9
SIPART PS2 Manual A5E00074631-01
27
Design and Functional Principle

2.5.2 Options modules in explosion proof version

The options modules are protected and mechanically fixed by a module cover ((1), see figure 2-11, page 29).
.
!
Open the positio­ner
NOTE
The housing must be opened to install the options modules. The degree of protection IP65/NEMA4x is not guaranteed as long as the positioner is open.
WARNING
The explosion proof positioner may only be supplied with electrical power in areas in which the atmosphere may be potentially explosive when the housing is closed.
The feed--though openings for the electronic connections must be sealed with EEX-d certified cable glands or EEx-d certified plugs or an ignition lock must be mounted at a maximum distance of 46 cm (18 inches) when using the “conduit”--system.
Disconnect or isolate the power supply cables first.
To open the positioner, the safety catch (12) must be opened and the screw--on cover unscrewed.
.
After loosening the four fixing screws (13.1) the complete rack (13) can be removed. The actuator may have to be turned so that the clutch can be easily disengaged.
Remove the module cover (1). To do this, the two screws (1.1) must be removed with a screwdriver .
NOTE
To prevent premature wearing of the fixture by the self--tapping screw (1.1) next to the display, the following method of mounting the module cover (1) has proven effective.
1. Turn the screws counterclockwise until you feel them snap into the thread.
2. Tighten both screws carefully in clockwise direction.
28
SIPART PS2 Manual
A5E00074631-01
1.1
Design and Functional Principle
10
13.1
12
8
7
13.1
56
13
1
1.1
2
4
3
11
1 Module cover 7 Transmission ratio selector
1.1 Fixing screws 8 Adjusting wheel for slipping clutc 2 PA module 10 Housing 3J 4 Alarm module with ribbon cable 12 Safety catch 5 Ribbon cable for alarm module 13 Rack 6 Ribbon cable for J
module with ribbon cable 11 Screw-- on cover
y
module 13.1 Fixing screws
y
Figure 2-11 Installation of the options modules in the explosion proof version

2.5.3 HART-function

Function
SIPART PS2 Manual A5E00074631-01
The positioner is also available with built--in HART-functions. The HART protocol allows you to communicate with your instrument with a handheld communicatorR, PC or programming unit. This enables you to configure your instrument comfortably , save configurations, call dia­gnostic data, display online measured values and much more. Commu­nication takes place as frequency modulation over the existing signal lines for the command variable from 4 to 20 mA.
29
Design and Functional Principle
The SPART PS2 is integrated in the following parameterization tools:
- Handheld communicatorR
- PDM (Process Device Manager)
- AMS (Asset Management System; update in preparation)
- Cornerstone
.

2.5.4 Alarm module

Function
NOTE
Operation on the positioner has priority over the settings via the HART inetrface.
Communication is aborted by a power failure at the positioner.
The alarm module contains
- 3 digital outputs and
- 1 digital input
The digital outputs serve to output fault messages and alarms. The configuration is described in chapter 4.4, page 79, with the parameters 44 to 54.
By an external signal applied at digital input (DI2) the actuator can be blocked or driven to its limit positions for example depending on the configuration. The configuration is described in chapter 4.4, page 79, with the parameters 43.
30
The alarm module is available in two versions:
- explosion protected for connecting to switching amplifier DIN 19234
- non--explosion protected for connection to voltage sources with a
maximum 35 V
The semiconductor outputs of the alarm module report an alarm (signal state Low) by switching off with high resistance. They are conductive in the High state (without alarm). The dynamic control makes them error self--reporting.
The outputs are potentially isolated from the basic circuit and each other.
The digital input is double.
- one potential isolated for voltage level
- one not potential isolated for floating contacts
These two inputs are designed as logic OR links.
SIPART PS2 Manual
A5E00074631-01
Design and Functional Principle
Installation

2.5.5 Jy-module

Function
Installation

2.5.6 SIA module

The alarm module is pushed in underneath the motherboard into the module rack up to the stop and connected by the enclosed 8-wire rib­bon cable (5) to the motherboard (see figure 2-10, page 27).
With the Jy-option module, the current actuator position can be output as a two wire signal J standard controller. The dynamic control of the J
= 4 to 20 mA – potentially isolated from the
y
-module makes it also
y
error self--reporting.
- module is pushed in to the bottom compartment of the module
The J
y
rack up to the stop and connected by the enclosed 6-wire ribbon cable (6) to the motherboard (see figure 2-10, page 27).
The SIA module contains:
- a digital output for outputting a group fault message (see alarm module)
The floating digital output is implemented as a self error reporting semiconductor output.
- two digital outputs for reporting two mechanically adjustable limit values (L1, L2) by slot initiators.
These two outputs are electrically independent of the rest of the electronics.
SIPART PS2 Manual A5E00074631-01
31
Design and Functional Principle

2.5.7 Accessories

Y1
Y1
PZ
Figure 2-12 Manometer block (left for single--acting, right for double--acting actuators)
Manometer block
The manometer block for single--acting actuator contains two manometers which are screwed to the lateral pneumatic connection of the positioner with O--rings. The values for the input pressure (supply air PZ) and output pressure (actuating pressure Y1) are displayed.
The manometer block for double--acting actuators contains three manometers which are screwed to the lateral pneumatic connection of the positioner with O--rings. The values for the input pressure (supply air PZ) and output pressure (actuating pressure Y1 and Y2) are displayed.
PZ
Y2
32
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation

Preparing for Operation

This chapter describes all the preparations necessary for operating the positioner.

3.1 Instrument identification (type key)

The order number of the positioner is printed on the rating plate and on the packaging. Compare this with the order number in chapter 7.1, page 105.
Installation of any modules required is described in chapter 2.5, page 25 of this technical manual.

3.2 Dimensional drawings

3
60
50x4xM6
h9
7
9 deep
1
3729
48
M20 x 1.5 or NPT-adapter
15
14,5
95
2
Y1
65
80
13,5
96,6
23
88,5
E
58
33
M8, 9 deep
182
8
7
38,5
Y1
PZ
Y2
All air connections G 1/4 or 1/4” NPT
29,5
72
29,5
11, 2
Figure 3-1 Dimensional drawing version plastic housing 6DR5xx0
SIPART PS2 Manual A5E00074631-01
33
Preparing for Operation
14
25
12
10
5
3x G1/4or 1/4” NPT
9,5
90
79,5
2xM6
29,5
58,75
82
Thread depth 5.5
50
3,5
5,3
20,5
M4
9,5
9
5
Figure 3-2 Dimensional drawing terminal strip for plastic housing
50x4xM6
9 deep
2
Y1
65
E
M8, 9 deep
23
58
182
13,5
96,6
88,5
8
7
38,5
7
34,5
M20 x 1.5 or NPT-adapter
h9
1
14,5
84
29
27,5
All air connections G 1/4 or 1/4” NPT
15
12
29,5
11, 2
6,5
14
Y1
29,5
59
PZ
Figure 3-3 Dimensional drawing version metal housing 6DR5xx1
34
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
M8, 14 deep (4x)
43
65
M6, 11 deep (4x)
129,5
23
7,75
50
60
3,5
Æ
All air connections
1/
or1/4”NPT
G
4
25
34
4,5
M6, 8 deep (2x)
M20, M25 or
1/
”NPT (2x)
2
10,25
19,25
1)
7,5
25,7
1)
Connection 238/Y2 only in
E
12
87,2
14,3
33,5
7
33,5
double action version
158,5
82,5
Æ 136.5
235,3
Æ 8h9
Figure 3-4 Dimensional drawing for positioner with metal housing in explosion proof
version 6DR5xx5

3.3 Assembly

General
WARNING
!
To avoid injury or mechanical damage to the positioner/mounting kit, the following order must be observed for assembly:
1. Mechanical fitting of positioner this chapter
2. Connection of electric power supply see chapter 3.4, p. 48
3. Connection of pneumatic power supply see chapter 3.5, p. 56
4. Put into operation see chapter 3.6, p. 57
Please also observe the warning on page 48!
SIPART PS2 Manual A5E00074631-01
35
Preparing for Operation
.
!
NOTE
The positioner will be equipped at the factory and delivered complete with the necessary options at the customer’s request. Options modules may only be retrofitted by our service technicians.
The positioner must be assembled – especially in a moist environment – in such a way as to rule out freezing of the positioner axle at low ambient temperature.
The operating keys must be covered to prevent liquid getting in.
WARNING
In the combination of components it must be ensured that only positioners and options modules are combined which are approved for the respective area of application. This applies especially for safe operation of the positioner in areas in which the atmosphere is potentially explosive (zone 1 and 2). The instrument categories (2 and
3) of the instrument itself and those of its options must be observed.
In addition, you must always make sure that no water gets into an open housing or screw--type gland. This may be the case for example when the positioner cannot be finally assembled and connected immediately.
It generally applies that the positioner may only be operated with dry compressed air. Therefore use the normal water traps. An additional drying unit may even be necessary in extreme cases. This is particularly important when operating the positioner at low ambient temperatures. Please set the purge air switch (on the valve block above the pneumatic terminals) additionally to the “OUT” position.
Use a sufficiently rugged console (e.g. plate thickness > 4 mm with reinforcements) for rotary actuators and the mounting kit “linear actuator” or integrated connection for linear actuators.

3.3.1 Instructions for using positioners in a wet environment

This information gives you important instructions for the assembly and operation of the positioner in a wet environment (frequent, heavy rain and/or prolonged tropical condensation) in which the IP65 degree of protection is no longer sufficient and especially when there is a danger that water may freeze.
To prevent water getting into the instrument in normal operation (e.g. through the exhaust air openings) or the display being poorly legible, please avoid the unfavorable installation positions illustrated in figure 3-5.
36
SIPART PS2 Manual
A5E00074631-01
Figure 3-5 Favorable and unfavorable installation positions
If conditions oblige you to operate the positioner in a unfavorable installation position, you can take additional precautionary measures to prevent penetration by water.
Preparing for Operation
Procedure
.
NOTE
Never clean the positioner with a high pressure water jet because the IP65 degree of protection is inadequate protection for this.
The necessary additional measures to prevent penetration by water depend on the installation position chosen and you may additionally require:
- screw--type gland with sealing ring (e.g. FESTO: CK –1 / 4–PK–6)
- plastic hose approx. 20 to 30 cm (e.g. FESTO PUN-- 8X1,25 SW)
- cable straps (number and length depends on local conditions)
- Connect the pipes in such a way that rain water which runs along
the pipes can drip off before it reaches the terminal strip of the positioner.
- Check the electrical connections for perfect firm contact.
- Check the seal in the housing cover for damage and contamination.
Clean and replace if necessary.
- Mount the positioner if possible so that the sinter bronze silencer faces downwards on the underside of the housing (vertical installa­tion position). If this is not possible, the silencer should be replaced by a suitable screw--type gland with a plastic hose.
Assembly of the screw--type gland with plastic hose
- Unscrew the sinter bronze silencer from the exhaust air opening on the underside of the housing.
- Screw the screw--type gland mentioned above into the exhaust air opening.
SIPART PS2 Manual A5E00074631-01
37
Preparing for Operation
- Mount the above mentioned plastic hose on the screw--type gland and check the good fit.
- Fix the plastic hose with a cable strap to the fitting so that the opening faces downwards.
- Make sure that the hose has no kinks and the exhaust air can flow out unhindered.

3.3.2 Instructions for using positioners which are exposed to great accelerations or vibrations

Great acceleration forces which may be far beyond the specified data occur on fittings under great mechanical stress such as breaking flaps, heavily shaking or vibrating valves as well as “steam impacts”. This may lead to maladjustment of the slip clutch in extreme cases.
Please use the positioner with reinforced slip clutch for such applications.
External displacement measurement
The increased torque requires a much greater force to actuate the slip clutch.
Applications in which the measures described above are inadequate are also conceivable. This applies for instance with continuous and heavy vibration, increased or too low ambient temperatures and in the case of nuclear radiation.
The separate attachment of position displacement sensor and controller unit can help here. A universal component is available which is suitable both for linear and rotary actuators.
You require the following:
- The position displacement sensor unit (order no. C73451­A430-D78). This consists of a SIPART-PS2- housing with integrated slip clutch, built--in potentiometer and various dummy plugs and seals.
- The controller unit, any positioner version.
- The EMC filter plate, this is is a set together with cable clips and
M-20 screw--type cable gland and has the order number C73451-A430-D23. The EMC filter plate must be installed in the SIPART-PS2 positioner. The installation instructions enclosed with the EMC filter plate explain how to assemble the components.
38
- A 3-wire cable for connecting the components.
This retrofit kit should always be used for the controller unit when any actuator--mounted potentiometer (resistance 10 kohms) is to be used instead of the position displacement sensor unit C73451-A430-D78.
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
3.3.3 Mounting kit ”linear actuator” 6DR4004-8V and 6DR4004-8L
The scope of delivery of the mounting kit” linear actuator IEC 534 (3 mm to 35 mm)” are contained (ser. no. see figure 3-6, page 41):
Ser. no. pieces Designation Note
1 1 NAMUR mounting kit bracket
IEC 534
2 1 Pick--up bracket Guides the roller with carrier pin and turns lever
3 2 Clamping assembly Mounting of pick-- up bracket on actuator spindle
4 1 Carrier pin Assembly with roll (5) on lever (6)
5 1 Roll Assembly with pin (4) on lever (6)
6 1 Lever NAMUR Forstrokerange3mmto35mm
7 2 U bolt Only for actuators with columns
8 4 Hexagon head screw M8 x 20 DIN 933-A2
9 2 Hexagon head screw M8 x 16 DIN 933-A2
10 6 Lock washer A8 -- DIN 127-A2
11 6 Flat washer B 8,4 -- DIN 125-A2
12 2 Flat washer B 6,4 -- DIN 125-A2
13 1 Spring VD-115E 0.70 x 11.3 x 32.7 x 3.5
14 1 Spring washer A6 -- DIN 137A-A2
15 1 Lock washer 3.2 -- DIN 6799-A2
16 3 Spring washer A6 -- DIN 127-A2
17 3 Socket cap screw M6 x 25 DIN 7984-A2
18 1 Hexagon nut M6 -- DIN 934-A4
19 1 Square nut M6 -- DIN 557-A4
21 4 Hexagon nut M8 -- DIN 934-A4
22 1 Guide washer 6.2 x 9.9 x 15 x 3.5
Standardized connection for mounting console with ledge, column or plane surface
arm
For stroke ranges> 35 mm to 130 mm (special deli­very), lever 6DR4004-8L is required additionally

3.3.4 Assembly procedure (see figure 3-6, page 41)

1. Mount clamping assembly (3) with hexagon socket cap screws
(17) and lock washer (16) on the actuator spindle.
2. Insert the pick--up bracket (2) into the recesses of the clamping
assembly. Set the necessary length and tighten the screws so that the pick--up bracket can still be shifted.
3. Push the roll (5), spring (13) and guide washer (22) onto the pin (4).
4. Insert the pin in the lever (6) and assemble with nut (18), spring
washer (14) and washer (12).
5. The value of the stroke range specified on the actuator or if this
does not exist as a scaling value, the next greatest scaling value is set. The center of the pin must be in line with the scaling value. The same value can be set later under parameter 3.YWAY in commissioning to display the way in mm after initialization.
6. Assemble the hexagon socket cap screw (17), spring washer (16),
washer (12) and square nut (19) on the lever.
7. Push the premounted lever onto the positioner axis up to the stop
and fix with the hexagon socket cap screw (17).
SIPART PS2 Manual A5E00074631-01
39
Preparing for Operation
8. Fit the mounting bracket (1) with two hexagon head screws (9),
lock washer (10) and flat washer (11) on the rear of the positioner.
9. Selection of the row of holes depends on the width of the actuator
yoke. The roll (5) should engage in the pick--up bracket (2) as close as possible to the spindle but may not touch the clamping assembly.
10. Hold the positioner with the mounting bracket on the actuator so
that the pin (4) is guided within the pick--up bracket (2).
1 1. Tighten the pick--up bracket.
12. Position the mounting parts according to the type of actuator.
-- Actuator with ledge: Hexagon head screw (8), flat washer (11)
and lock washer (10).
-- Actuator with plane surface: Four hexagon head screws (8), flat
washer (11) and lock washer (10).
-- Actuator with columns: Two U bolts (7), four hexagon nuts (21)
with flat washer (11) and lock washer (10).
13. Secure positioner onto the yoke using the previously positioned
mounting parts.
.
NOTE
Set the height of the positioner so that the horizontal lever position is reached as close to the stroke center as possible. You can use the lever scale as orientation. It must be guaranteed that the horizontal lever position is passed through within the stroke range.
40
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
2
16
17
1)
3
Without explosion proof version
11
10
9
1
2) 4 15
17
16 12
19
18
14
12
6
22
13
5
3)
Explosion proof version:
11
10
9
1
3)
11
10
9
11
10
9
Figure 3-6 Assembly procedure (linear actuator)
SIPART PS2 Manual A5E00074631-01
41
Preparing for Operation
1
10
8
Mounting on yoke
11
with ledge
4)
11
Mounting on yoke with plane surface
11
Mounting on yoke with columns
10
8
10
7
21
as required
Figure 3-6 Assembly procedure (linear actuator) continued
3.3.5 Mounting kit ”Rotary actuator” 6DR4004-8D
The scope of delivery of the mounting kit ”Rotary actuator” contains (ser. no. see figures 3-7 and 3-8):
Ser. no. Pieces Designation Note
2 1 Coupling wheel Mounting on position feedback shaft of the
SIPART PS2 3 1 Carrier Mounting on end of actuator shaft
4 1 Multiple plate Indication of actuator position, comprising 4.1
and 4.2
4.1 8 Scales Different divisions
4.2 1 Pointer mark Reference point for scale
14 4 Hexagon head screw DIN 933 -- M6 x 12
15 4 Lock washer S6
16 1 Fillister head screw DIN 84 -- M6 x 12
17 1 Washer DIN125–6.4
18 1 Hexagon socket head screw Premounted with coupling wheel
19 1 Allen key For item 18
42
SIPART PS2 Manual
A5E00074631-01

3.3.6 Assembly procedure (see figure 3-7 and figure 3-8)

1. Attach VDI/VDE 3845 mounting console ((9), actuator--specific, scope of delivery actuator manufacturer) onto rear of positioner and secure using hexagon head screws (14) and lock washers (15).
2. Adhere pointer (4.2) onto mounting console in the center of the centering hole.
3. Push the coupling wheel (2) onto positioner axis, pull back by about 1 mm and tighten the hexagon socket head screw (18) with the Allen key provided.
4. Place the carrier (3) onto the end of the actuator and secure using Fillister head screw (16) and washer (17).
5. Carefully place positioner with mounting console onto the actuator such that the pin of the coupling wheel engages in the driver.
6. Align the positioner/mounting console assembly in the center of the actuator and screw tight. (Screws not included in delivery; they are part of the actuator mounting console!)
Preparing for Operation
7. Following startup as described in Chapter 3.6, page 57: Drive the actuator to the end position and adhere scale (4.1) on the coupling wheel (2) according to direction of rotation and rotary actuator. The
scale is self--adhesive!
SIPART PS2 Manual A5E00074631-01
43
Preparing for Operation
4.2
1)
3)
15
9
14
2
9
18
2)
16
17
3
2
3
4)
Figure 3-7 Assembly procedure (rotary actuator)
44
5)
2
4.1
0%20 40 60 80 100%
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
15
14
4.2
9
1)
3)
16
9
17
3
2)
18
2
2
3
5)
4)
Figure 3-8 Assembly procedure forexplosion proof version(rotary actuator)
SIPART PS2 Manual A5E00074631-01
2
4.1
0%20 40 60 80 100%
45
Preparing for Operation
15
14, 15
2
25
A
CUT A -- B
4.2 14, 15
positioner
G1/4
B
rotary actuator
3 16, 17 10 4.1 9
2 Coupling wheel 10 Feedback shaft 3 Carrier 14 Hexagon head screw M6 x 12 4 Multiple plate 15 Lock washer S6
4.1 Scale 16 Fillister head screw M6 x 12
4.2 Pointer mark 17 Washer 9 VDI/VDE 3845-mounting bracket 18 Hexagon socket head screw
Figure 3-9 Mounted positioner for rotary actuator
46
SIPART PS2 Manual
A5E00074631-01
Befestigungsebene
fastening level
Stellungsregler
positioner
Preparing for Operation
M6
Schwenkantrieb
rotary actuator
+0,1
4
35
F05-Lkr.- 50
Figure 3-10 Attachment of rotary actuator, mounting console (scope of delivery actuator manufacturer),
dimensions
SIPART PS2 Manual A5E00074631-01
47
Preparing for Operation

3.4 Electrical Connection

.
!
NOTE
Any necessary options modules must be installed before electrical connection (see chapter 2.5, page 25).
N.B.: The transmission ratio selector can only be set when the positioner is open. Therefore check this setting before sealing the controller.
WARNING
For the electrical installation, please observe the pertinent regulations, in hazardous areas particularly the rules and regulations for the installation and operation of systems in hazardous areas (e.g. in Germany: Elex V, VDE 0165)
The explosion proof positioner may only be supplied with electrical power in areas in which the atmosphere may be potentially explosive when the housing is closed.
The feed--though openings in the explosion proof version for the electronic connections must be sealed with EEX-d certified cable glands or EEx-d certified plugs or an ignition lock must be mounted at a maximum distance of 46 cm (18 inches) when using the “conduit”-system.
The plastic housing is metal lined to increase the electromagnetic compatibility (EMC) against high frequency radiation. This screen is connected electrically to the threaded bushes shown in figure 3-11, page 49.
Please bear in mind that this protection can only be effective if you con­nect at least one of these bushes with grounded fittings by electrically conductive (blank) mounting parts.
48
SIPART PS2 Manual
A5E00074631-01
Figure 3-11 Base plate

3.4.1 Connection variants

Preparing for Operation
Shield
3.4.1.1 Connection variant: not intrinsically safe
The electrical connection of the positioner can be made in the following ways:
+
4to20mA
J
HART Communicator
Figure 3-12 Two-- wire connection non Ex
.
NOTE
The current i
6 7 8
+3 V
9 10
must be 3.6 mA to maintain the power supply.
y
E
A
Only for:
6DR5110-xNxxx 6DR5120-xNxxx 6DR5111-xNxxx
Positioner
Digital inputs 1
6DR5010-xNxxx 6DR5020-xNxxx 6DR5011-xNxxx 6DR5110-xNxxx 6DR5120-xNxxx 6DR5111-xNxxx
Please also observe the warning on page 48!
SIPART PS2 Manual A5E00074631-01
49
Preparing for Operation
3.4.1.2 Connection variant: intrinsically safe
.
NOTE
Only certified intrinsically safe circuits may be connected as power supply, control and signal circuits.
Non-hazardous area
EEx
Intrinsically safe power source
Figure 3-13 Two--wire connection standard controller 6DR50xx-xExxx (power supply from s ignal current)
+
J
Hazardous area zone 1 or zone 2
4to20mA
6 7 8 9 10
+3 V
E
Positioner
A
Digital inputs 1
6DR5010-xExxx 6DR5020-xExxx 6DR5011-xExxx
.
NOTE
The current i
must be 3.6 mA to maintain the power supply.
y
50
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
Non-hazardous area
EEx
J
Intrinsically safe power source
Hazardous area zone 1 or zone 2
+
4to20mA
2 3 4 5
6 7 8
+3 V
9 10
HART Communicator
Positioner
E
A
Digital inputs 1
6DR5210-xExxx 6DR5220-xExxx 6DR5211-xExxx
Figure 3-14 Two--wire connection standard controller 6DR52xx-xExxx
Non-hazardous area
EEx
U
EEx
J
Intrinsically safe power sources
+
+
*)
Hazardous area zone 1 or zone 2
18 to 30 V
4to20mA
*)
2 3 4 5
6 7 8
+3 V
9 10
HART Communicator
Positioner
E
A
6DR5210-xExxx 6DR5220-xExxx 6DR5211-xExxx
Digital inputs 1
*) Only for three--wire connection
Figure 3-15 Three-/four--wire connection standard controller 6DR52xx-xExxx
SIPART PS2 Manual A5E00074631-01
51
Preparing for Operation
Split-range
Figure 3-16 Series circuit of two positioners, e.g. split range (separate power supply)
3.4.1.3 Connection variant: Options in positioner in non--intrinsically safe and explosion proof version
Current output
+
U
H
+
Figure 3-17 Jy-module 6DR4004-8J, non Ex
616261 62
52
E
J
Jy-module: 6DR4004-8J
SIPART PS2 Manual
A5E00074631-01
Digital inputs and outputs
Preparing for Operation
Alarm module 6DR4004-8A
+13 V
+
+4.5 V
+24 V
+24 V
+24 V
Figure 3-18 Alarm module non Ex
11 12
21 22
31 32
41 42
51 52
+3 V
1K
1K
1K
1
Fault message
Limit value A1
Limit value A2
Digital input 2
SIA module
+
+
+
Figure 3-19 SIA module, non Ex
SIA module: 6DR4004-8G
31
10K
32
41 42
51 52
2K1
Fault message
Limit value A1
Limit value A2
SIPART PS2 Manual A5E00074631-01
53
Preparing for Operation
3.4.1.4 Connection variant: Options in the positioner in intrinsically safe version
Current output
Non-- hazardous area
+
U
H
EEx
+
U
J
+
Intrinsically safe power sources
Figure 3-20 Jy-module 6DR4004-6J, Ex
Hazardous area zone 1 or zone 2
616261 62
E
J
Jy-module: 6DR4004-6J
54
SIPART PS2 Manual
A5E00074631-01
Digital inputs and outputs
EEx
Preparing for Operation
Alarm module 6DR4004-6A
+
11 12
1
Digital input 2
Intrinsically
+8.2 V
safe Switching
EEx
amplifier to EN 50227
+8.2 V
EEx
+8.2 V
EEx
Figure 3-21 Alarm module 6DR4004-6A, Ex
Current output
21
+3 V
22
2K1
31 32
41 42
51 52
10K
2K1
10K
2K1
10K
Fault message
Limit value A1
Limit value A2
Hazardous area zone 1 or zone 2Non-- hazardous area
Intrinsically safe Switching
+8.2 V
EEx
amplifier to EN 50227
+8.2 V
EEx
+8.2 V
EEx
Non-- hazardous area
Figure 3-22 SIA module 6DR4004-8G, Ex
SIPART PS2 Manual A5E00074631-01
SIA module: 6DR4004-6G
2K1
31
10K
32
2K1
41
10K
42
2K1
51
10K
52
Hazardous area zone 1 or zone 2
Fault message
Limit value A1
Limit value A2
55
Preparing for Operation

3.5 Pneumatic Connection

WARNING
!
For reasons of safety, the pneumatic power may only be supplied after assembly when the positioner is switched to operating level P manual operation with electrical signal applied (as--delivered state, see figure 4-4, page 76).
.
NOTE
Note the air quality! Oil--free industrial air, solid content < 30 μm, pressure dew point 20 K below the lowest ambient temperature.
- Connect a manometer block for supply air and actuating pressure if necessary.
- Connection by female thread G 1/4 DIN 45141 or 1/4” NPT:
P
Z
Y1 actuating pressure 1 for single-- and double--acting
Y2 actuating pressure 2 for double--acting actuators E exhaust air outlet (remove silencer if necessary) see figure 2-3 and 2-4, page 18.
- Safety position when the electric power supply fails:
single action: Y1 deaerated double action: Y1 Max. Actuating pressure
- Connect actuating pressure Y1 or Y2 (only in double--acting actuators) according to the desired safety position.
Supply air 1.4 to 7 bar
actuators
(supply air pressure)
Y2 deaerated
56
.
- Connect supply air to P
NOTE
In order for spring--loaded pneumatic actuators to be able to reliably exploit the maximum possible actuating path, the supply pressure must be sufficiently greater than the maximum required final pressure of the actuator.
.
Z
SIPART PS2 Manual
A5E00074631-01

3.6 Commissioning

Due to the wide range of application possibilities the positioner must be adapted (initialized) to the respective actuator individually after assem­bly. This initialization can be effected in three different ways:
- Automatic initialization
Initialization takes place automatically Hereby the positioner deter­mines the direction of action, the displacement path and the angle of rotation, the adjusting times of the actuator one after the other and adapts the control parameters to the dynamic behavior of the actua­tor.
- Manual initialization
The displacement path or angle of rotation of the actuator can be set manually, the otehr parameters are determined as in automatic initialization. This function is useful in actuators with soft limit stops.
- Copying initialization data (positioner exchange)
In the devices with HART function the initialization data of a positio­ner can be read out and copied to another positioner. This enables a defective device to be changed without having to interrupt an ongo­ing process by initialization.
Preparing for Operation
.
.
Only a few parameters need to be set in the positioner prior to initializa­tion. The others are defaulted so that they do not normally need to be adjusted. You will have no problems with commissioning if you observe the following points.
NOTE
You go to the previous parameter by pressing the operation mode key and the decrement key simultaneously.
Without initialization the positioner is in operating mode P manual operation (this may also be reached by ”PRST”) -- ”NOINI” flashes.
NOTE
N.B.: The operating pressure should be at least one bar greater than is necessary for closing/opening the valve during initialization.
N.B.: The gear transmission switch can only be set when the positioner is open. Therefore check this setting before sealing the housing.
SIPART PS2 Manual A5E00074631-01
57
Preparing for Operation

3.6.1 Preparations for linear actuators

1. Assemble the positioner with the appropriate mounting kit (see
chapter 3.3.3, page 39).
.
NOTE
Particularly important is the position of the gear transmission switch (8, figure 2-1, page 16) in the positioner:
Stroke Lever Position of the gear transmission
switch
5to20mm short 33° (i.e. down) 25 to 35 mm short 90° (i.e. up) 40 to 130 mm long 90° (i.e. up)
2. Push the carrier pin (4, figure 3-6 (page 41) 2) onto the lever (6,
figure 3-6, 2) to the scale position corresponding to the rated stroke or next highest position and screw the carrier pin tight with the nut (18, figure 3-6, 2).
3. Connect the actuator and the positioner with the pneumatic lines
and supply pneumatic power to the positioner (figure 2-3 and 2-4, page 18 ).
4. Connect a suitable current or voltage source (see figure 3-12,
page 49 and figure 3-13, page 50).
5. The positioner is now in the operating mode ”P-manual opera-
tion” The current potentiometer voltage (P) is displayed in percent in the top line of the display, e.g.: ”P12.3”, and ”NOINI” flashes in the bottom line:
58
.
6. Check the free running of the mechanics in the whole actuating
range by moving the actuator with the keys to the respective end position.
NOTE
You can move the actuator quickly by pressing the other direction key additionally whilst keeping the direction key selected first pressed.
7. Now move the actuator to the horizontal position of the lever. A
value between P48.0 and P52.0 should be visible in the display. If this is not the case, adjust the slip clutch (8, figure 2-10, page 27) until ”P50.0” is displayed with a horizontal lever. The more accurately you hit this value, the more exactly the positioner can determine the path.
and and driving
SIPART PS2 Manual
A5E00074631-01

3.6.2 Automatic initialization of linear actuator

If you can move the actuator correctly, leave it standing in a central po­sition and start automatic initialization:
Preparing for Operation
.
1. Press the operation mode key
you to the Configuration operating mode. Display:
2. Switch to the second parameter by pressing the operation mode
key Display:
NOTE
It is vital that this value corresponds to the setting of the transmission ratio selector (8, figure 2-1, page 16) (33° or 90°).
briefly.
for longer than 5 s. This brings
or
3. Switch on to the following display with the operation mode key :
You only need to set this parameter if you want to have the total stroke in mm displayed at the end of the initialization phase. To do this, select the same value in the display to which you have set the carrier pin to the scale on the lever.
4. Switch on to the following display with the operation mode key
:
SIPART PS2 Manual A5E00074631-01
59
Preparing for Operation
5. Start initialization by pressing the key for longer than 5 s.
Display:
During the initialization phase ”RUN1”to”RUN5” appear one after an- other in the bottom display (see also structograms figures 3-24, page 68 to figure 3-27, page 71).
.
NOTE
The initialization process may last up to 15 minutes depending on the actuator.
The initialization is complete when the following display appears:
The following display appears after pressing the operation mode key
briefly:
To e xit t he Configuration operating mode, press the
operation mode key played after about 5 s. The instrument is in manual operation after re­leasing the operation mode key.
for longer than 5 s. The software version is dis-
60
.
NOTE
You can abort an ongoing initialization at any time by pressing the operation mode key. Your previous settings are retained. All the para­meters are reset to the factory setting only after performing a “Preset”.
SIPART PS2 Manual
A5E00074631-01

3.6.3 Manual initialization of linear actuator

The positioner can be initialized with this function without the actuator being driven hard against the limit stop. The start and end positions of the displacement path are set manually. The other initialization steps (optimization of the control parameters) run automatically as in automa­tic initialization.
Preparing for Operation
Manual initializa­tion procedure in linear actuator
.
1. Make preparations as described in chapter 3.6.1, page 58 for
linear actuator. In particular, make sure by manuallydriving the whole displacement path that the displayed potentiometer setting moves in the permissible range between P5.0 and P95.0.
Press the operation mode key you to the Configuration operating mode. Display:
3. Switch to the second parameter by pressing the operation mode
key
NOTE
It is vital that this value corresponds to the setting of the transmission ratio selector (33_ or 90°).
briefly. One of the following displays appears:
for longer than 5 s. This brings
or
SIPART PS2 Manual A5E00074631-01
4. Switch on to the following display with the operation mode key:
You only need to set this parameter if you want to have the total stroke in mm displayed at the end of the initialization phase. To do this, select the same value in the display to which you have set the carrier pin to the scale on the lever or the next highest position in intermediate positions.
61
Preparing for Operation
5. Switch on to the following display by pressing the operation
mode key twice:
6. Start initialization by pressing the increment key for longer
than5s. Display:
7. After 5 s the display changes to:
.
(The display of the potentiometer setting is shown here and below as an example only). Now move the actuator to the position which you want to define as
the first of the two end positions with the increment
ment the current position as end position 1 and switches on to the next
position.
NOTE
If the message “RANGE” appears in the bottom line, the selected end position is outside the permissible measuring range. There are several ways to correct the error:
S Adjust the slip clutch until “OK” appears and press the operationmode
key again or
S move to another end position with the increment and decrement key
or
S abort initialization by pressing the operation mode key. You then have
to change to P manual operation and correct the displacement path and the displacement detection according to step 1.
key. Then press the operation mode key . This accepts
and decre-
62
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
8. If step 7 was successful, the following display appears:
Now move the actuator to the position which you want to define as the second end position with the increment
ment key. Then press the operation mode key . This enters the current position as end position 2.
and decre-
.
.
NOTE
If the message “RANGE” appears in the bottom line, the selected end position is outside the permissible measuring range. There are several ways to correct the error:
S move to another end position with the increment and decrement key
or
S abort initialization by pressing the operation mode key. You then have
to change to P manual operation and correct the displacement path and the displacement detection according to step 1.
NOTE
If the message “Set Middl” appears, the lever arm must be driven to horizontal position using the increment and decrement key and then the operation mode key pressed. This sets the reference point of the sine correction in linear actuators.
9. The rest of the initialization now runs automatically. “RUN1” to
“RUN5” appear one after another in the bottom line of the display. The following display appears on successful completion of initiali­zation:
SIPART PS2 Manual A5E00074631-01
The first line additionally contains the determined stroke in millimeters if the set lever length was specified with parameter 3 YWA Y.
5 INITM appears in the bottom line again after pressing the operation mode key operating mode.
To exit the Configuration mode, press the operation mode key longer than 5 seconds. The software version is displayed after about
5 seconds. The instrument is in manual operation after releasing the operation mode key.
briefly. This brings you back to the Configuration
for
63
Preparing for Operation

3.6.4 Preparations for rotary actuator

.
NOTE
Very important: Switch the transmission ratio selector in the
positioner (8, figure 2-1, page 16) to position 90° (normal angle for rotary actuator).
1. Mount the positioner with the appropriate mounting kit (see chapter
3.3.5, page 42).
2. Connect the actuator and the positioner with the pneumatic lines
and supply pneumatic power to the positioner (figure 2-3 and 2-4, page 18).
3. Connect a suitable current or voltage source (see figure 3-12,
page 49 and figure 3-13, page 50).
4. The positioner is now in the operating mode ”P-manual opera-
tion” The current potentiometer voltage (P) is displayed in % in the top line of the display , e.g.: ”P12.3”, and ”NOINI” flashes in the bot­tom line:
5. Check the free running of the mechanics in the whole actuating
range by moving the actuator with the keys to the respective end position.
and and driving
.
NOTE
You can move the actuator quickly by pressing the other direction key additionally whilst keeping the direction key selected first pressed.

3.6.5 Automatic initialization of rotary actuator

If you can move the actuator correctly through the actuating range, leave it standing in a central position and start automatic initialization:
1. Press the operation mode key
you to the Configuration operating mode. Display
for longer than 5 s. This brings
64
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
2. Set the parameter with the -key to ”turn”
Display:
3. Switch to the second parameter by pressing the operation mode
key Display:
4. Switch on to the following display with the operation mode key :
briefly. This has set automatically to 90°.
.
5. Start initialization by pressing the key for longer than 5 s.
Display:
During the initialization phase ”RUN1”to”RUN5” appear one after another in the bottom display (see also structograms in figure 3-24, page 68 to figure 3-27, page 71).
NOTE
The initialization process may last up to 15 minutes depending on the actuator.
The initialization is complete when the following display appears:
SIPART PS2 Manual A5E00074631-01
The top value indicates the total angle of rotation of the actuator (example 93.5°).
65
Preparing for Operation
The following display appears after pressing the operation mode key
briefly:
To e xit t he Configuration mode, press the operation mode key for longer than 5 s. The software version is displayed after about 5 s. The instrument is in manual operation after releasing the operation mode key.
.
NOTE
You can abort an ongoing initialization at any time by pressing the ope­ration mode key. Your previous settings are retained. All the parame­ters are set to the factory setting only after performing a “Preset”.

3.6.6 Manual initialization of rotary actuators

The positioner can be initialized with this function without the actuator being driven hard against the limit stop. The start and end positions of the displacement path are set manually. The other initialization steps (optimization of the control parameters) run automatically as in automa­tic initialization.
Manual initializa­tion procedure in rotary actuators
1. Make preparations as described in chapter 3.6.4, page 64 for
rotary actuators. In particular, make sure by manually driving the whole displacement path that the displayed potentiometer setting moves in the permissible range between P5.0 and P95.0.
2. Press the operation mode key
you to the Configuration mode. Display:
for longer than 5 s. This brings
66
3. Set the parameter YFCT to “turn” with the decrement key.
Display:
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
4. Switch to the second parameter by pressing the operation mode
key Display:
briefly.
.
NOTE
Make sure that the transmission ratio selector is in position 90 °!
5. Switch on to the following display by pressing the operation mode
key
The following steps are identical with the steps 6) to 9) for initiali­zation of linear actuators.
After successful initialization the determined rotary range appears in the top display.
“5.INITM” appears in the bottom line again after pressing the ope­ration mode key tion operating mode.
To exit the Configuration mode, press the operation mode key for longer than 5 seconds. The software version is displayed after
about 5 seconds. The instrument is in manual operation after re­leasing the operation mode key.
twice:
briefly. This brings you back to the Configura-

3.6.7 Automatic initialization (structograms)

Linear actuator
Up Down
Figure 3-23 Direction of action of the actuators
The initialization procedure should be taken from the following structo­gram (figure 3-24 to figure 3-27). The terms Open/Closed and up/down in the structogram refer to the direction of action of the actuators as illustrated in figure 3-23.
SIPART PS2 Manual A5E00074631-01
Rotary actuator
Closed
Open
67
Preparing for Operation
Figure 3-24 Automatic initialization, part 1
68
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
Figure 3-25 Automatic initialization part 2 (in rotary actuators)
SIPART PS2 Manual A5E00074631-01
69
Preparing for Operation
Figure 3-26 Automatic initialization part 2 (in rotary actuators)
70
SIPART PS2 Manual
A5E00074631-01
Preparing for Operation
Figure 3-27 Automatic initialization, part 3
SIPART PS2 Manual A5E00074631-01
71
Preparing for Operation

3.7 Copying initialization data (positioner exchange)

With this function you have the possibility of starting up a positioner without running the initialization routine. This allows for example a posi­tioner to be changed on a running system in which automatic or manual initialization cannot be performed without disturbing the process.
NOTICE
Initialization (automatic or manual) should be performed as soon as possible afterwards because only then can the positioner be optimally adapted to the mechanical and dynamic properties of the actuator.
Data are transmitted from the positioner to be replaced to the replacement instrument via the HARTÒ- communication interface.
The following steps must be performed to exchange a positioner:
1. Read in and save instrument parameters and initialization data
(determined in initialization) of the instrument to be replaced with PDM (Process Device Manager) or HARTÒ-Communicator. This step is unnecessary if the instrument has been parameterized with PDM and the data have already been stored.
2. Fix the actuator in its momentary position (mechanical or
pneumatic).
3. Read and note the current position actual value of the positioner to
be changed. If the electronics are defective, determine the current position by measuring on the actuator or valve.
4. Disassemble the positioner. Mount the lever arm of the positioner
on the replacement instrument. Mount the replacement instrument on the fitting. Move the gear switch to the same position as the defective instrument. Copy the instrument data and initialization data from the PDM or handheld.
5. If the displayed actual value does not match the noted value of the
defective positioner, set the correct value with the slip clutch.
6. The positioner is now ready to operate.
The accuracy and dynamic behavior may be restricted in relation to correct initialization. The position of the hard stops and the rela­ted maintenance data may show deviations in particular. Therefore initialization must be performed at the earliest opportunity.
72
SIPART PS2 Manual
A5E00074631-01
Operation

Operation

4.1 Display

.
4
The following chapter describes the operation of the positioner.
The LC display has two lines whereby the lines have different segmentation. The elements of the top line consist of 7, those of the bottom line of 14 segments. The display depends on the selected operating mode (see chapter 4.3, page 76)
NOTE
If the positioner is operated in ranges with temperatures below --10 °C the liquid crystal display becomes sluggish and the display refresh rate is reduced considerably.

4.2 Input keys

.
Figure 4-1 shows you the various display options.
The positioner is operated by three keys (figure 4-2) the function of which depends on the selected operating mode. In the explosion proof version of the positioner the input keys are underneath a key cover which can be lifted up after loosening the cover screw.
NOTE
The input keys of the explosion proof version must be covered to prevent liquid getting in. The IP65/NEMA4x degree of protection is not guaranteed when the housing is open or the key cover is open.
The housing cover must be removed to operate the keys in the normal and intrinsically safe versions of the positioners.
SIPART PS2 Manual A5E00074631-01
73
Operation
Figure 4-1 Meaning of the various display options
.
74
NOTE
The degree of protection IP 65/NEMA4x is not guaranteed as long as the positioner is open.
SIPART PS2 Manual
A5E00074631-01
1
23 4
1 Display 2 Operation mode key 3 Decrement key 4 Increment key
Figure 4-2 Display and input keys of the positioner
Explanations of the input keys
- The operation mode key (manual key) serves to switch over the operating mode and pass on parameters.
Operation
.
Firmware version
NOTE
By pressing and holding the operation mode key and additionally pressing the decrement key, you can select the parameters in reverse order.
- The decrement key serves to select parameter values in configuration and to move the actuator in manual operation.
- The increment key
serves to select parameter values in
configuration and to move the actuator in manual operation.
The current firmware state is displayed when you exit the configuration menu.
Figure 4-3 Firmware version
SIPART PS2 Manual A5E00074631-01
75
Operation

4.3 Operating modes

The positioner can be operated in five operating modes.
1. P-manual mode (ex--factory state)
2. Configuration and initialization
3. Manual mode (MAN)
4. Automatic (AUT)
5. Diagnostic display
Figure 4-4 gives you an overview of the possible operating modes and the change between them.
Figure 4-4 Change between the operating modes
76
SIPART PS2 Manual
A5E00074631-01
Operation
P-manual mode (ex--factory state)
Configuration and initialization
.
The display of the positioner shows you the current potentiometer setting in the top line and ”NOINIT” flashes in the second line. You can
move the actuator with the decrement and increment key . In order to adapt the positioner to your actuator, you have to change to the
Configuration menu. See also chapter 3.6, page 57 “Commissioning”.
Output of alarms and position feedback is possible after successful in­itialization.
To go to the Configuration menu, press the operation mode key
for
at least 5 seconds. In the Configuration menu you can adapt the positioner individually to your actuator and start initialization. Only a few parameters need to be set in the positioner prior to initialization. The others are defaulted so that they do not normally need to be adjusted. You can block the Configuration menu against manipulation by an appropriately parameterized and activated digital input. Which parameters you need to set and all other parameters are explained in chapter 4.4, page78Parameterization.
The configuration mode can be reported by outputting a parameterizable fault message, a position feedback or output of limit values A1 and A2 is not possible.
NOTE
If the electric power supply fails during configuration, the positioner switches back to the first parameter after recovering the power supply, values which have already been parameterized are retained. Without a power failure you re--enter the configuration menu at the point you exited it when you call the Configuration menu again.
to
Figure 4-5 Overview: Configuration
SIPART PS2 Manual A5E00074631-01
at the same time
at the same time
at the same time
at the same time
77
Operation
Manual mode (MAN)
.
.
Automatic (AUT)
In this operating mode you can move the actuator with the decrement
) and increment keys ( ) and the current position is held
( regardless of the setpoint current and any leakages.
NOTE
You can move the actuator quickly by pressing the other direction key additionally whilst keeping the direction key selected first pressed.
The manual mode can be reported by outputting a parameterizable fault message, a position feedback or output of limit values A1 and A2 is only possible in automatic mode.
NOTE
The positioner switches over to automatic mode automatically after an electrical power failure.
The automatic mode is the normal mode. In this mode the positioner compares the setpoint current with the current position and moves the actuator until the control deviation reaches the parameterizable dead zone. Error messages are output if this is not possible for various reasons.
Diagnostic display
.

4.4 Parameters

In this operating mode you can have the current operating data (such as number of strokes, number of changes in direction, number of faults messages, etc.) displayed (see table 3-1, page 91).
From the automatic or manual mode you go to the diagnostic display by simultaneously pressing all three keys for at least two seconds.
See chapter 4.5, page 90 for further information.
NOTE
The respective operating mode (MAN or AUT) of the positioner is retai­ned when you switch to the diagnostic display, i.e. in automatic opera­tion the specified setpoint is still used for controlling and in manual operation the position last reached is retained.
All the parameters of the positioner are listed in this chapter. Figure 4-6 shows an overview of the parameters.
The parameter name is shown once in plain text and once as it ap­pears in the display. The function of the parameter is described briefly in the ”Function” column. In addition, the possible parameter values, the physical unit and the factory setting of the parameters are shown.
78
SIPART PS2 Manual
A5E00074631-01
Operation
A
A
Paramet er name
1.YFCT
1)
2.YAGL
2)
3.YWAY
4.INITA
5.INITM
6.SCUR
7.SDIR
8.SPRA
9.SPRE
10.TSUP
11.T SD O
12.SFCT
13.SL0
14.SL1 usw. bis
32.SL19
33.SL20
34.DEBA
35.YA
36.YE
37.YNRM
38.YDIR
39.YCLS
40.YCDO
41.YCUP
4)
42.BIN1
4)
43.BIN2
5)
44.AFCT
45.A1
46.A2
5)
47. FCT
48. TIM
49. LIM
50. STRK
51. DCHG
52. ZERO
53. OPEN
54. DEBA
55.PRST
1)
1)
If "turn" is selected, you cannot set 33°
2)
2)
Parameter does no t appear if 1.YFCT=turn has been selected
3)
3)
Turning points only appear wih selection 12.SFCT = FrEE
4)
Alternatively "no" if initiali zation has not yet been carried out
Display
Type of actuator
Rated angle of rotation of feedback
Set tran smission ratio selector (7 ) approp riately (see view of device)
Stroke range (opt ional setting)
When used, the value must correspond with the set of the leverage ratio on the actuator
Driver pi n must be set to the va lue of the actua tor travel or, if this value is not scaled, to the next larger scale value.
Initi alization (aut omatically)
Initialization (manually)
Current range of setpoint
Setpoi nt direct ion
Setpoi nt for st art of spl it rang e
Setpoint for end of split range
Setpoi nt ramp u p
Setpoi nt ramp d own
Setpoint function
Equal-per centage 1:25, 1:33, 1: 50
Inverse eq ual-percenta ge
3) (example)
Setpoint turning point at 0%
Dead zone of controller
Start of manipulated variable limiting
End of man ipulated varia ble limiting
Standardization of manipulated variable
Direction of manipulated variabl e for display
Tight closing with manipulated variable
Value for tight closing, bottom
Value for tight closing, top
Function of BI 1
Function of BI 2
Alarm func tion Withou t
Response threshold of ala rm 1
Response threshold of ala rm 2
Function of alarm output
Monitoring time for fault message “control deviation”
Response threshold for fault message “control deviation”
Limit for stroke integral
Limit for di rection ch ange
Limit for end stop monitoring, bottom
Limit for end stop monitoring, top
Limit for dead z one monit oring
Preset (factory setting) "no" noth ing activat ed "Strt" start of factory setting after pressing key for 5 s "oCAY" display following successful factory setting CAUTION: preset results in "NO INIT"
Function Parameter v alues Unit
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear act uator
without sin e correction)
ncSt (part-t urn actuator with NCS)
0 to 20 mA 4 to 20 mA
rising
falling
Line ar
1:25, 1:3 3, 1:50
Freely ad justable
5%
to
95%
100%
To me ch . tr av el
To fl ow
Risin g
Falling
Without
Top only
Bottom only
Top and bottom
Only message
Block configuring
Block con figuring and man ual
Drive va lve to position u p
Drive va lve to position d own
Block movement
None
Only message
Drive valve to position up
Drive va lve to position d own
Block moveme nt
A1=min . A2=max A1=min . A2=min A1=max. A2=max
on fault
Fault + not automatic
Fault + not automatic + BI
("+" mean s logical OR oper ation)
5) NC contact means:
NO contact means:
6) Normal means: High level withou t fault
Inverted means: Low level without fault
-ncSt (ditto, i nv. direction of action
None
90° 33°
OFFOFF
5 | 10 | 15 | 20
(kurzer Hebel 33°)
25 | 30 | 35
(kurzer Hebel 90°)
40 | 50 | 60 | 70 | 90 | 110 | 130
(lange r Hebel 90° )
noini | no / ###.# | Strt
noini | no / ###.# | Strt
0 MA 4 MA
riSE
FALL
0,0 bis 100,0
0,0 bis 100,0
Auto
0 bis 400
0 bis 400
Lin
1 - 33
1- 25
n1 - 25
NO cont actNO contact
normalnormal
1 - 50
n1 - 33
n1 - 50
FrEE
0,0 bis 100,0
Auto
0,1 bis 10,0
0,0 bis 100,0
0,0 bis 100,0
MPOS FLOW
riSE
FALL
no
uP
do
uP do
0,0 bis 100,0
0,0 bis 100,0
OFFOFF
OFF
-on
on bLoc1 bLoc2
-uP
uP
-doWn
doWn
-StoP
Sto P
OFF
on
-on
-uP
uP doWn
-doWn
Sto P
-StoP
OFF
0,0 bis 100,0
0,0 bis 100,0
uto
0 bis 100
uto
0,0 bis 100,0
OFF
1 bis 1.00E9
OFF
1 bis 1.00E9
OFF
0,0 bis 100,0
OFF
0,0 bis 100,0
OFF
0,0 bis 10,0
no
Strt
oCAY
action with opene d switch or Low lev el action with closed s witch or High lev el
Degrees
invertedinverted NC contact NC contact
Factory setting Customer setting
WAY
33°
mm
%
%
s
s
%
%
%
%
%
%
%
%
s
%
%
%
%
OFF
no
no
4 MA
riSE
0,0
100
0
0
Lin
0.0
5.0
usw. bis
95.0
100.0
Auto
0,0
100,0
MPOS
riSE
no
0,5
99,5
OFF
OFF
OFF
10,0
90,0
Auto
Auto
OFF
OFF
OFF
OFF
OFF
Figure 4-6 Parameter table of the positioner
SIPART PS2 Manual A5E00074631-01
79
Operation
1.YFCT
2.Y AGL
Positioning actuator type
Selection of used actuator: Linear actuator (WAY), rotary actuator (turn). The unlinearity which exists in linear actuators due to the conversion of linear movement to rotational movement is compensated by the positioner when 1.YFCT = WAY is selected.
If an external, linear potentiometer is used for displacement measuring, “1.YFCT” is set to LWAY. However, no way is displayed after initialization.
Special case: Use this setting for rotary actuators with reverse direction of action as well.
When using a rotary actuator with NCS sensor for position detection, select 1.YFST = ncST or --ncST
Rated angle of rotation of the feedback shaft
In rotary actuators, an angle of 90° is preset automatically by 1.YFCT = turn (see above). In linear actuators (1.YFCT = WAY) a value of 33° or 90° can be selected depending on the stroke range:
- 33° for strokes £ 20 mm
- 90° for strokes > 20 mm
When using the lever up to 35 mm, both angles of rotation (33° and 90°) are possible.
3.YWAY
.
.
The long lever (> 35 mm stroke) is only designed for an angle of rotation setting of 90°. It is not part of the mounting kit set 6DR4004-8V but must be ordered separately under order number 6DR4004-8L.
NOTE
The setting of the transmission ratio selector on the positioner (see figure 2-1, page 16 and figure 2-2, page 17) must correspond to the angle value selected under “2.YAGL”.
Lever arm transmission
NOTE
The use of this parameter is optional. You only need to set this parameter if you want to have the way in mm displayed at the end of the initialization.
Selection of the lever arm range: serves to display the real stroke after initialization. This parameter is only relevant for linear actuator. If the parameter value ”oFF” is selected here, the real stroke is not displayed after initialization.
80
SIPART PS2 Manual
A5E00074631-01
Operation
4.INITA
5.INITM
.
NOTE
The specification “YWAY” must match the mechanical lever arm trans­mission. The carrier must be set to the value of the actuator stroke, if this is not scaled to the next highest scaled value.
Automatic initialization (see chapter 3.6, page 57)
By selecting “Strt” and pressing the increment key seconds, automatic initialization is started. The initialization process is
displayed by “RUN 1” to “RUN 5” (see figure 3-24, page 68 to figure 3-27, page 71).
If the positioner is already initialized, it can be switched over to the uninitialized status without changing the other parameters by pressing
the decrement key (
Manual initialization
By selecting “Strt” and pressing the increment key seconds, manual initialization is started. The manual initialization
process is described in chapter 3.6.6, page 66.
) for 5 seconds.
foratleast5
foratleast5
6.SCUR
7.SDIR
8.SPRA
9.SPRE
Current range of the setpoint
The selection of the current range depends on the connection type. ”0mA” (0 to 20 mA) is only possible in three-/four--wire connections (see figure 3-15, page 51).
Setpoint direction (see figure 4-7, page 82)
The setting of the setpoint direction serves to reverse the direction of action of the setpoint. It is used mainly for the split range mode and in single--acting actuators with the safety position “up”.
Split range start (see figure 4-7) and Split range end (see figure 4-7)
The parameters “8.SPRA” and “9.SPRE” in connection with the parameter “7.SDIR” serve to restrict the active setpoint range. In this way split range tasks can be solved with the following characteristics.
- rising / falling
- falling / rising
- falling / falling
SIPART PS2 Manual A5E00074631-01
- rising / rising
81
Operation
y=x
100 %
0%
Positioner 1
6.SDIR = FALL
Total setting range
100 %-- SPRE 100 %-- SPRA
Positioner 1 Positioner 2
Setting range 1
Positioner 2
6.SDIR = riSE
SPRA SPRE
Setting range 2
100 %
[0 % to 100 %]
J
W
Figure 4-7 Example: Split range-operation with two positioners
10.TSUP
Setpoint ramp UP and
11.TSDO
Setpoint ramp DOWN
The setpoint ramp is effective in automatic operation and limits the speed of alteration of the active setpoint. When switching over from manual operation to automatic the active setpoint is adjusted to the set­point on the positioner with the setpoint ramp.
This bumpless manual/automatic switchover avoids excessive pressure increases on long pipelines.
In the position TSUP = Auto the slower of the two travel times determi­ned during initialization is used for the setpoint ramp. TSDO is then in­effective.
12.SFCT
Setpoint function (see figure 4-8, page 83)
Non--linear valve characteristics can be linearized with this function and any flow characteristics simulated in linear valve characteristics.
Six valve characteristics are stored in the positioner
82
- equal percentage 1 : 25 (12.SFCT = 1 -- 25)
- equal percentage 1 : 33 (12.SFCT = 1 --33)
- equal percentage 1 : 50 (12.SFCT = 1 --50)
- inverse equal percentage 1 : 25 (12.SFCT = n1 -- 25)
SIPART PS2 Manual
A5E00074631-01
- inverse equal percentage 1 : 33 (12.SFCT = n1 --33)
- inverse equal percentage 1 : 50 (12.SFCT = n1 --50)
Operation
Figure 4-8 Setpoint characteristic, manipulated variable standardization and tight sealing function
SIPART PS2 Manual A5E00074631-01
83
Operation
13.SL0 to 33.SL20
34.DEBA
35.Y A
36.YE
Setpoint vertex points (see figure 4-8, page 83)
A flow parameter can be assigned to the respective setpoint vertex va­lue at an interval of 5%. These points lead to a polygon chain with 20 straight lines which therefore represents a projection of the valve cha­racteristic.
The setpoint vertex values can only be input at You may only enter a strictly monotonous characteristic, the vertex values of which differ by at least 0.2%. If the monotony condition has been infringed, an error message appears as soon as you want to exit ”Configuration”. If you need a falling characteristic you have to enter a rising characteristic and reverse the direction of action by entering 7.SDIR = fall.
Dead zone of the controller
At dEbA = AUto the dead zone in automatic operation is adapted conti­nuously to the requirements of the control circuit. The dead zone is gra­dually increased on detecting a control oscillation. The reverse adapta­tion takes place by a time criterion.
In the other discrete settings the fixed value is used for the dead zone.
Manipulated variable limiting start (see figure 4-8 and 4-9) and Manipulated variable limiting end (see figure 4-8 and 4-9)
37.YNRM
With the parameters “35.YA” and “36.YE” the mechanical actuating di­stance (from stop to stop) is limited to the set values. In this way the mechanical setting range of the actuator can be limited to the active flow and the integral saturation of the commanding controller avoided.
Manipulated variable standardization (see figure 4-8 and 4-9)
With limiting of the manipulated variable (by “35.YA” and “36.YE”) two different scalings are produced for the display and the position feed­back via the current output (MPOS or FLOW).
The MPOS scaling shows the mechanical position (0 to 100%) bet­ween the hard stops of the initialization. This is not affected by the pa­rameters “35.YA” and “36.YE”. The parameters “35.YA” and “36.YE” are displayed in the MPOS-scale.
The FLOW-scale is the standardization (0 to 100%) to the range bet­ween “35.YA” and “36.YE”. The setpoint w (0 to 100%) is always refer­red to this range. This gives (also by using valve characteristics) a quasi--flow--proportional display and position feedback Iy.
To calculate the control difference, the setpoint is also shown in the ap­propriate scale on the display.
84
SIPART PS2 Manual
A5E00074631-01
YNRM = MPOS or YNRM = FLOW Presetting: YA = 0% and YE = 100%
4mA 20mA7.2mA 10.4mA 13.6mA 16.8mA
0%
0mm
YA = 0%
20%
16mm
40%
32mm
Example: YNRM = MPOS with YA = 10 % and YE = 80 %
4mA 20mA7.2mA 10.4mA 13.6mA 16.8mA
0%
0mm
20%
16mm
YA = 10%
40%
32mm
50%
50%
60%
48mm
60%
48mm
80%
64mm
80%
64mm
YE = 80%
100%
80mm
YE = 100%
100%
80mm
Operation
Input current (setpoint)
X display W display
Mechan. Stroke (actual value)
Input current (setpoint)
X display W display
Mechan. Stroke (actual value)
Example: YNRM = FLOW with YA = 10 % and YE = 80 %
50%
Input current
80mm
(setpoint)
X display W display
Mechan. Stroke (actual value)
4mA 20mA7.2mA 10.4mA 13.6mA 16.8mA
0mm
0%
20%
16mm
YA = 10%
40%
32mm
60%
80%
48mm
100%
64mm
YE = 80%
Figure 4-9 Dependence on the stroke of standardization and on YA and YE in the example of an
80 mmlinear actuator
38.YDIR
Manipulated variable direction of action
The direction of action (rising or falling) of the display and the position feedback (Iy) can be set with this.
39.YCLS
Manipulated variable sealing (see figure 4-8, page 83)
With this function the valve can be driven to the seat with the maximum actuating force of the actuator (continuous contact of the piezo--val­ves). The sealing function can be activated on one side or for both limit positions. YCLS becomes active when the setpoint is below the value set with parameter “40.YCDO” or above that set with parameter “41.YCUP”.
SIPART PS2 Manual A5E00074631-01
85
Operation
40.YCDO
41.YCUP
42.BIN1
43.BIN2
Value for sealing bottom
When the sealing function bottom (see parameter“39.YCLS”is activa­ted, it can be set below which setpoint the bottom sealing is activated with this parameter.
Value for sealing top
When the sealing function top (see parameter“39.YCLS”is activated, it can be set above which setpoint the top sealing is activated with this parameter.
Function digital input 1 (see figure 4-6, page 79) and Function digital input 2 (see figure 4-6)
The parameters “42.BIN1” and “43.BIN2” can be set individually depen­ding on the purpose. The direction of action can be adapted to an NCC or an NOC.
- BIN1 or BIN2 = on or --on
Digital messages of the periphery (e.g. pressure or temperature switches) can be read out via the HART interface or lead to respon­ding of the fault message output by OR linking with other messages.
- BIN1 = bLc1
The Configuration operating level is locked to prevent it being adju­sted (e.g. by a wire jumper between terminals 9 and 10).
- BIN1 = bLc2
If digital input 1 has been activated, manual operation is also locked in addition to the Configuration operating level.
- BIN1 or BIN2 = uP or doWn (contact closes) or --uP or --doWn (con­tact opens).
The actuator drives the linear actuator to the upper or lower stop when the digital input is activated with continuous contact.
- BIN1 or BIN2 (contact closes) = StoP or --StoP (contact opens).
With activated digital input the piezo--valves are blocked and the actuator remains in the last position. Leakage messages can then be executed without initialization function.
- BIN1 or BIN2 = oFF (factory setting)
no function special function of DI1: If the digital input 1 is activated in P manual operation by a jumper between terminals 9 and 10, ”NOINI” or the 100times input current in mA is displayed alternately in the bottom line of the display.
86
If one of the above named functions is selected with the parameters “42.BIN1” and “43.BIN2” simultaneously, then “Blocking” has priority over “Up” and “Up” priority over “Down”.
SIPART PS2 Manual
A5E00074631-01
Operation
44.AFCT
45.A1
46.A2
47. FCT
Alarm function
The actuator can report the exceeding (max.) or dropping below (min) of a specified stroke or angle of rotation. The response of the alarms (limit contacts) is related to the MPOS-scaling (see figure 4-9, page
85). The alarms are reported by the alarm module (order no.
6DR4004-6A or -8A). In addition the alarms can be read out through the HART interface (optional).
The direction of action of the digital outputs can be adapted from high active to low active sequence systems.
Response threshold alarm 1 and Response threshold alarm 2
The alarm thresholds are related to the mechanical path (MPOS-scale).
Function of the fault message output
The fault message output serves as a group message for following faults:
- Control error (e.g. by actuator fault, valve fault, compressed air fai­lure) with the parameters “48.
TIM” and “49. LIM”
- Positioner not in automatic mode
48. TIM
49. LIM
- Digital input activated (see parameter “42.BIN1” and “43.BIN2”)
- Exceeding of a limit value (e.g. way integral or valve seat, see para-
meter50to54)
It also responds at:
- Power failure
- Processor fault
The direction of action of the digital outputs can be adapted from high active to low active sequence systems.
Monitoring time for setting the fault messages
The set value (s) serves as a specification for the time within which the positioner must have reached the controlled state. The corresponding response threshold is specified with “49.
LIM”.
The fault message output is set on exceeding the set time.
Response threshold of the fault message
Here a value (%) can be set for the permissible variable of control error for releasing the fault message.
If the parameters “48.
TIM” and “49. LIM” are both set to ”Auto”, the fault message is set if the short step zone is not reached within a certain time. This time is 5 times the initialization travel time within 5 to 95% of the actuating path and 10 times this time outside 10 to 90% of the actuating path.
SIPART PS2 Manual A5E00074631-01
87
Operation
50. STRK
51. DCHG
52. ZERO
Limit value for monitoring the way integral
A limit value for the way integral can be set here. If the way integral exceeds the limit value, the fault message output (optional) is activated.
This function enables a preventive maintenance of the fitting, see also chapter 4.5 “Diagnostics”, page 90.
This monitoring function can be deactivated with the OFF setting (factory setting).
Limit value for monitoring the change of direction
A limit value for the direction change counter can be set here. If this counter exceeds the limit value, the fault message output is activated.
This function enables a preventive maintenance of the fitting, see also chapter 4.5 “Diagnostics”, page 90.
This monitoring function can be deactivated with the OFF setting (factory setting).
Tolerance value for monitoring the bottom hard stop
With this value a limit value (in percent related to the total mechanical distance) can be preset for the monitoring of the bottom hard stop. If this tolerance value is exceeded or dropped below of, the fault message output (optional) is activated.
53. OPEN
This function detects when the bottom stop has changed by more then the specified tolerance related to its initialization value. Monitoring takes place when the valve is in sealing bottom. Activation of the sealing bottom function (parameter “39.YCLS”) is therefore a prerequisite.
The fault message remains activated until either a subsequent monitoring remains within the tolerance or a new initialization is performed.
This monitoring function can be deactivated with the OFF setting (factory setting). See also chapter 4.5 “Diagnostics”, page 90.
Tolerance value for monitoring the top hard stop
With this value a limit value (in percent related to the total mechanical distance) can be preset for the monitoring of the top hard stop. If this tolerance value is exceeded or dropped below of, the fault message output (optional) is activated.
This function detects when the top stop has changed by more then the specified tolerance related to its initialization value. Monitoring takes place when the valve is in sealing top. Activation of the sealing top function (parameter “39.YCLS”) is therefore a prerequisite.
The fault message remains activated until either a subsequent monitoring remains within the tolerance or a new initialization is performed.
88
This monitoring function can be deactivated with the OFF setting (factory setting).
SIPART PS2 Manual
A5E00074631-01
Operation
54. DEBA
55.PRST
.
.
NOTE
But the monitors of the bottom and top hard stop do not only react to valve errors. Adjustment of the position feedback is also detected as an error if the tolerance values are exceeded as a result.
Limit value for monitoring the dead zone adaptation
The automatic adaptation of the dead zone can be monitored with this value (%). If the dead zone exceeds the set value, the fault message output (optional) is activated.
Prerequisite for this function is the setting of the parameter“34.DEBA” = Auto. This monitoring function can be deactivated with the OFF setting (factory setting).
Preset
Establishing the factory setting and resetting the initialization.
NOTE
The positioner must be re--initialized after ”Preset”. All previously de­termined maintenance parameters are cleared.
SIPART PS2 Manual A5E00074631-01
89
Operation

4.5 Diagnosis

4.5.1 Diagnostic display

You go to the diagnostic display from automatic or manual operation by simultaneously pressing all three keys for at least two seconds.
Table 3-1, page 91 shows an overview of the displayable values. In the third column the corresponding English term from which the abbrevia­tion is derived is shown next to the German meaning unless this is self explanatory.
The diagnostic display has a similar structure to in the ”Configuration” operating mode. the top line shows the value of the diagnostic variable, the bottom line the number and abbreviation of the displayed variable.
The respective next diagnostic value can be selected with the operation mode key
additionally pressing the decrement key stic values in reverse order.
. By pressing and holding the operation mode key and
you can select the diagno-
Certain values can be set to zero by pressing the increment key at least 5 seconds. This is noted in the last column in the table.
Some diagnostic values may be greater than 99999. In this case the display switches to exponential display. Example: the value 1234567 is displayed as 1.23E6.
No. Abbrevia-
tion
1 STRKS Number of strokes (Strokes) 0to4.29E9 -- x
2 CHDIR Changes of direction (Changes of Direction) 0to4.29E9 -- x
3
CNT
4 A1CNT Alarm counter 1 (Alarm 1Counter) 0to4.29E9 -- x
5 A2CNT Alarm counter 2 (Alarm 2Counter) 0to4.29E9
6 HOURS Operating hours (Hours) 0to4.29E9 Hours
7 WAY Determined actuating path (Way) 0to130 mm or _
8 TUP Travel time up (T ravel Time Up) 0 to 1000 s
9 TDOWN Travel time down (Travel Time Down) 0 to 1000 s
10 LEAK Leakage (Leakage) 0.0 to 100.0 %
11 P0 Potentiometer value below stop (0%) 0.0 to 100.0 %
12 P100 Potentiometer value bottom stop (100%) 0.0 to 100.0 %
13 IMPUP Impulse length up (Impulse Length Up) 2to100 ms
14 IMPDN Impulse length down (Impulse Length Down) 2to100 ms
15 DBUP Dead zone up (Dead Band Up) 0.1 to 100.0 %
16 DBDN Dead zone down (Dead Band Down) 0.1 to 100.0 %
17 SSUP Short step zone up (Short Step Zone Up) 0.1 to 100.0 %
18 SSDN Short step zone down (Short Step Zone Down) 0.1 to 100.0 %
19 TEMP Current temperature --40 to 85 _C
20 TMIN Minimum temperature (”drag pointer”) --40 to 85 _C
21 TMAX Maximum temperature (”drag pointer”) --40 to 85 _C
22 T1 Number of operating hours in Temperature range 1 0to4.29E9 Hours
23 T2 Number of operating hours in Temperature range 2 0to4.29E9 Hours
24 T3 Number of operating hours in Temperature range 3 0to4.29E9 Hours
25 T4 Number of operating hours in Temperature range 4 0to4.29E9 Hours
26 T5 Number of operating hours in Temperature range 5 0to4.29E9 Hours
27 T6 Number of operating hours in Temperature range 6 0to4.29E9 Hours
Meaning Displayable
values
Fault counter (Counter ) 0to4.29E9 -- x
Unit Rest
for
poss.
90
SIPART PS2 Manual
A5E00074631-01
Operation
No. Rest
tion
28 T7 Number of operating hours in Temperature range 7 0to4.29E9 Hours
29 T8 Number of operating hours in Temperature range 8 0to4.29E9 Hours
30 T9 Number of operating hours in Temperature range 9 0to4.29E9 Hours
31 VENT1 Number of cycles pre--controlvalve 1 0to4.29E9 --
32 VENT2 Number of cycles pre--controlvalve 2 0to4.29E9 --
33 STORE Store current values as ”last maintenance”
Table 3-1 Overview diagnostic values
MeaningAbbrevia-
values
-- --
(press increment key for 5 s) (Store)
UnitDisplayable
poss.

4.5.2 Meaning of the diagnostic values

1 STRKS
2 CHDIR
Number of strokes
The actuator movements during operation are totaled and can be read here as number of strokes. Unit: 100% stokes The value is written every hour in a non--volatile memory. It can be reset to zero with the
increment key
.
Number of direction changes
3 CNT
4 A1CNT
5 A2CNT
6 HOURS
Every change in direction leaving the dead zone is noted in the controller and added to the number of changes of direction.
The value is written every hour in a non--volatile memory. It can be reset to zero with the increment key
.
Fault counter
Every fault is noted in the controller and added to the number of fault messages. The counter can be reset to zero with the increment key
Alarm counter 1 and Alarm counter 2
Responses of alarm 1 and alarm 2 are counted with these two counters. The prerequisite is the activation of the alarms with the parameter “44.AFCT”. The counters can be reset to zero with the increment key
.
Operating hours
The operating hours counter is updated every hour as soon as the positioner has been supplied with electrical power.
.
SIPART PS2 Manual A5E00074631-01
91
Operation
7WAY
8TUP
9TDOWN
10 LEAK
11 P0
12 P100
Determined actuating way
This value indicates the actuating way determined during initialization according to the display at the end of an initialization. Prerequisite in linear actuator: Specification of the lever arm with the parameter “3.YWAY”.
Travel time up and travel time down
These values show the travel times which have been determined du­ring initialization. The unit is seconds.
Leakage
If a leakage message has been output during initialization, the value of the leakage can be read here in %/min.
Potentiometer value bottom stop and Potentiometer value top stop
These two values indicate the measured values of displacement mea­surement (potentiometer) at the bottom and top hard stops as determi­ned in automatic initialization. In manual initialization the values of the manually reached limit positions are indicated here.
13 IMPUP
14 IMPDN
15 DBUP
16 DBDN
17 SSUP
18 SSDN
Impulse length up and Impulse length down
During initialization the smallest impulse lengths are determined with which a movement of the actuator can be achieved. They are determi­ned and displayed here for the “Up”-direction and the “Down”-direction.
Dead zone up and Dead zone down
Here the dead zone of the controller is displayed in “Up”-direction or in “Down”-direction. The values correspond either to the manually set va­lue of the parameter“34.DEBA” or the value adapted automatically by the instrument when “DEBA” has been set to ”Auto”.
Short step zone up and Short step zone down
The short step zone is the range of the controller in which pulse--sha­ped control signals are output. The impulse length here is proportional to the control error. If the control error is outside the short step zone, the valves are controlled in continuous contact.
92
SIPART PS2 Manual
A5E00074631-01
Operation
19 TEMP
20 TMIN
21 TMAX
22 T1 to 30 T9
Temperature range [_C]
Current temperature
Current temperature in the positioner housing The sensor is on the electronics board.
Minimum temperature (drag pointer) and Maximum temperature (drag pointer)
The minimum and maximum temperature inside the housing is determi­ned and stored continuously in a kind of drag pointer.
Number of operating hours in temperature range T1 to T9
Statistics how long operation takes place in which temperature ranges is kept in the instrument. To do this, the measured temperature over one hour respectively is averaged and incremented in the counter which is assigned to the corresponding temperature range every hour. This enables you to draw conclusions about the past operating condi­tions and thus the whole fitting.
The temperature ranges are divided up as follows:
T1 T2 T3 T4 T5 T6 T7 T8 T9
-- 3 0
-- 3 0
<--15
-- 1 5<0≥0
<15
15 <30
30 <45
45 <60
60 <75
75
31 VENT1
Number of cycles pre--control valve 1 and
32 VENT2
Number of cycles pre--control valve 2
These two counters add up the control processes of the pre--control valves.
33 STORE
Store maintenance data
A store function is triggered by pressing the increment key least 5 seconds. Here the diagnostic data 7 to 17 are stored in a non-­volatile memory as ”Data of the last maintenance”. These diagnostic
data are selected values, the changes of which can provide information on the mechanical wear of the valve.
Normally this function is operated via HART, e.g. with PDM, menu item Instrument!Store maintenance info. It is possible to compare the data of the last maintenance with the current data.

4.5.3 Online -Diagnosis

Some important variables and parameters are monitored continuously during operation. In the “Configuration” operating mode you can confi­gure this monitoring so that the fault message output is activated when a certain event such as exceeding a limit value occurs.
for at
SIPART PS2 Manual A5E00074631-01
93
Operation
Table 3-2, page 94 shows which events can activate the fault message output, how the parameters must be set for this event to be monitored, when the fault message disappears again and where the possible causes of the fault lie.
In automatic and manual operation response of the fault message output on the display shows which is the fault message trigger. The two digits at the bottom left indicate the corresponding error code. If several triggers occur at the same time, these are displayed cyclically. The instrument status which also contains all fault messages can be called via HART with the command #48.
Error code
1 Remaining con-
2 Instrument not
3 Digital input DI1
4 Limit value
5 Limit value
6 Limit value bot-
7 Limit value
8 Limit value
Table 3-2 Events which can activate the fault message output
Event Parameter
setting
always active ... the control error has
trol error
47. FCT= nA
in automatic mode
or DI2 active
Number of stro­kes exceeded
change of di­rection excee­ded
tom hard stop exceeded
top hard stop exceeded
dead zone adaptation ex­ceeded
or = nAB
47. FCT= nAB and digital function BIN1 or BIN2 to ”on”
50. STRK¸OFF ... the stroke counter is
51. DCHG¸OFF
52. ZERO¸OFF
39.YCLS = do or up do
53. OPEN¸OFF 39 YCLS = up or up do
53. OPEN¸OFF
34.DEBA = Auto
Fault message dis­appears when ...
disappeared again
... the instrument is brought into automatic mode
... the digital input is no longer activated
reset or the limit value increased
... the change of direction counter is reset or the limit value increased
... the deviation of the stop disappears or the instrument is re-- initialized
... the deviation of the stop disappears or the instrument is re-- initialized
... the limit value is dropped below again
Possible causes
Compressed air missing, actuator fault, valve fault (e.g. blockade).
The instrument is configured or is in manual operation.
The contact connected to the binary input has become active (e.g. stuffing box monitoring, excess pressure, temperature switch).
The total distance traveled by the actuator exceeded the set limit value.
The number of changes of direction exceeded the set limit value.
Wear of the valve seat, de­posits or foreign bodies in the valve seat, mechanical maladjustment, slip clutch maladjusted.
Wear of the valve seat, de­posits or foreign bodies in the valve seat, mechanical maladjustment, slip clutch maladjusted.
Increased stuffing box friction, mechanical lots of the position feedback
94
SIPART PS2 Manual
A5E00074631-01
Explanations of column “Error codes”:
1 Monitoring of control error
In automatic operation the error between setpoint and actual value is monitored continuously. The fault message is activated with unchanged control error according to the setting of the parameters 48. toring time for setting the fault messages and 49 hold of the fault message. As soon as the control error drops back be­low the response threshold, the fault message is reset.
2 Monitoring automatic operation
A fault message is generated when the instrument is not in the automa­tic mode at the appropriate parameter setting “47. control syst em can be warned for example when the instrument has been switched to manual operation or Configuration on site.
3 Digital input DI1 or DI2 active
A fault message is generated when the digital input is activated at the the corresponding setting of the parameter “47. fault message output and the parameter “42.BIN1”, function digital in­put 1. This may be a switch for stuffing box monitoring, a temperature switch or a limit value switch for example.
Operation
TIM, moni-
LIM, response thres-
FCT”. In this way the
FCT”, function of the
Digital input 2 (on the alarm module option) can be configured in the same way.
4 Monitoring of number of strokes 5 Monitoring of number of changes of direction
The two values number of strokes and number of changes of direction are compared continuously with the limit values which are specified with the parameters “50.
STRK” and “51. DCHG”. The fault message output responds when exceeded. Both functions can be deactivated with the parameter setting ”OFF”.
6 Monitoring of the bottom hard stop (valve seat) 7 Monitoring of the top hard stop
Monitoring of the bottom hard stop is activated when the parameter
ZERO” has a value¸OFF . Errors of the valve seat can be detected
“52. with this function for example. Exceeding of the limit value may hint at deposits or foreign bodies in the valve seat. Exceeding the limit value may be caused by wear of the valve seat. Mechanical maladjustment of the position feedback may also trigger this error message.
Monitoring takes place every time the valve is in sealing position. The current position is compared with the one determined during initializa­tion as a bottom end stop. Activation of the sealing bottom function (pa­rameter “39.YCLS”) is therefore a prerequisite.
SIPART PS2 Manual A5E00074631-01
Example: 3% is set as a value. Normally the setting 0% is adopted when sealed. If a value >3% or <--3% is determined instead, a fault is reported.
95
Operation
The fault message remains activated until either a subsequent monitoring remains within the tolerance or a new initialization is performed. The deactivation of the monitoring (“52. clears any existing fault message.
This monitoring function supplies no useful results when the stops have not been determined automatically in initialization but the limits set manually (manual initialization“5.INITM”).
An appropriate diagnosis is made for the top hard stop. The limit value for this is set with the parameter
. Activation of the sealing top function
(parameter “39.YCLS”) is therefore a prerequisite.
8 Monitoring of the dead zone adaptation
If the dead zone increases unproportionally in operation in automatic adaptation of the dead zone (parameter DEBA = Auto) this points to an error in the system (e.g. a marked increase in stuffing box friction, play in the displacement detection, leakage). Therefore a limit value can be specified for this value (”54.
DEBA”, limit value for dead zone monitoring) which activates the fault message output when it is exceeded.
ZERO”=OFF) also
96
SIPART PS2 Manual
A5E00074631-01
Operation
Figure 4-10 Configuration block diagram
SIPART PS2 Manual A5E00074631-01
97
Operation
98
SIPART PS2 Manual
A5E00074631-01
Care and Maintenance

Service a nd Maintenance

The positioner is largely maintenance--free. The positioners are fitted with filters in the pneumatic connections as protection against coarse particles of dirt. If the pneumatic energy supply contains particles of dirt, the filters may clog and impair the function of the positioner. In this case the filters can be cleaned as follows.
Positioner in metal housing and explosion proof version
1. Switch off the pneumatic power supply and remove the pipes.
2. Remove the metal filters carefully from the holes and clean (e.g.
with compressed air).
3. Insert the filters.
4. Re--connect the pipes and supply pneumatic energy.
Positioner in plastic housing
5
Removal
1. Switch off the pneumatic power supply and remove the pipes.
2. Unscrew the cover
3. Remove the three screws from the pneumatic connector strip.
4. Remove the filters and O-rings behind the connector strip.
5. Clean the filters (e.g. with compressed air).
Installation
6. First insert the filters in the recesses in the plastic housing and then
place the O-rings on the filters.
7. Align the pneumatic connector strip on the two lugs and screw tight
with the three self--tapping screws.
Important:
Make sure that the same thread is used. To do this turn the screws counterclockwise until they snap into the thread audibly. Only then should you tighten the screws.
SIPART PS2 Manual A5E00074631-01
99
Care and Maintenance
!
8. Replace the cover and screw it tight.
9. Re--connect the pipes and supply pneumatic energy.
DANGER
Electrostatic charging must be prevented in hazardous areas. These could be caused by example when cleaning the positioner in plastic housing with a dry cloth.
100
SIPART PS2 Manual
A5E00074631-01
Loading...