Cashco POSR-1 User Manual

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM)
IOM-POSR-1
12-13
MODEL POSR-1
PILOT OPERATED PRESSURE RE DUC ING REGULATOR
SECTION I
I. DESCRIPTION AND SCOPE
The POSR-1 is a pilot operated pressure reducing reg u la tor used to control downstream (P2) pressure. The
POSR-1-20 is a pressure loaded (no pilot) option. Sizes are 1/2", 3/4" and 1" (DN15, 20 and 25). The unit is suitable for steam service only. Refer to Technical Bulletin POSR-1-TB for design conditions and selection recommendations.
NOT RECOMMENDED FOR DEAD END SERVICE!
SECTION II
II. INSTALLATION
A. General:
WARNING
Do not dead end (no fl ow demand) downstream of POSR-1 if P1 - Inlet Pressure is greater than max i mum allowable outlet design pressure.
Max. Allowable Spring Range Out let Pressure
5-15 psig (0.34-1.03 Barg) 100 psig (6.9 Barg) 10-40 psig (0.69-2.8 Barg) 200 psig (13.8 Barg) 30-80 psig (2.1-5.5 Barg) 200 psig (13.8 Barg) 70-150 psig (4.8-10.3 Barg) 200 psig (13.8 Barg)
B. Piping the Valve:
1. An inlet block valve should always be in­ stalled.
2. If service application is continuous such that shut down is not readily accomplished, it is recommended that an inlet block valve, outlet block valve, and a manual bypass valve be installed.
3. Pipe unions are recommended for NPT screwed in stal la tions to allow removal from piping.
PI
Pilot
Valve
Main
TR
HP Cond.
Valve
MP/LP Cond.
TR
FIGURE 1
Recommended Piping Schematic for POSR-1
Airset or
Manual Loader
TR
HP Cond.
Main
Valve
Air
Supply
TR
MP/LP Cond.
PI
FIGURE 2
Recommended Piping Schematic for POSR-1-20
CAUTION
SRV
SRV
4. An outlet pressure gauge should be lo cat ed ap­ prox i mate ly ten pipe diameters down stream, and within sight.
Installation of adequate overpressure pro tec tion is recom­mended to pro tect the reg u la tor from overpressure and all down stream equip ment from damage in the event of regulator failure.
5. All installations should include a down stream re lief device if the inlet pressure could ex ceed the pressure rating of any downstream equip­ ment or the maximum allowable outlet pres sure rating of the unit.
6. Clean the piping of all foreign material in clud ing chips, welding scale, oil, grease and dirt before installing the regulator. Strainers are recom­mended.
use 1/4" OD metal tubing for dis tanc es 4 ft (1.2 m) or less, and 3/8" OD metal tubing (re­quires 1/4" x 3/8" tubing adapter) for distances greater than 4 ft. (1.2 m). The sensing line should always be sloped down ward so that condensation will drain away from the pilot. If regulator pipe line is ex pand ing to a larger pipe line, always connect sens ing line to the larger pipe line. NOTE: The POSR-1-20 does
not reguire a sensing line.
CAUTION
DO NOT HYDROSTATIC TEST THROUGH AN IN STALLED UNIT, INCLUDING PILOT; ISOLATE BOTH PILOT AND MAIN VALVE FROM TEST. The upper range spring pressure level listed on the nameplate is the rec om mend ed “upper op er a tive limit” for the sens ing diaphragm(s) in the pilot. Higher pres sures could cause internal dam age. In addition, note on the name plate that the Inlet and Outlet pressure and tem per a ture rat ings are at different levels.
7. In placing thread sealant on pipe ends prior to en gage ment, assure that excess material is removed and not allowed to enter the reg u ­la tor upon start-up.
8. Flow Direction. Install so the fl ow direction match es the arrow cast on the body.
9. The POSR-1 comes factory piped between the pilot supply and pilot loading. Install an external sensing line from the 1/4" NPT con­ nec tion opposite the factory piped pilot load ing port to a point downstream at gauge location;
10. For best per for mance Cashco rec om mends in stall ing regulator in a well drained horizontal pipe, prop er ly trapped.
11. Recommended installation is with pilot valve spring chamber vertical upwards. Orient such that the spring chamber vent hole does not collect rainwater or debris.
12. Regulators are not to be buried under­ground.
13. For insulated piping systems, rec om men da tion is to not insulate regulator.
CAUTION
For welded installations, all internal trim parts, seals and diaphragm(s) must be removed from reg u la tor body prior to welding into pipeline. The heat of fusion welding will dam age non-metallic parts if not re moved. NOTE: This does not apply to units equipped with extended pipe nip ples.
III. PRIN CI PLE OF OPERATION
A. General:
1. The POSR-1 pilot obtains its operating medium from the main valve body inlet. Down stream pressure (P2) registers on the un der side of the main valve’s diaphragm and the pilot valve’s diaphragm(s).
2. The loading pressure on the top side of the main valve’s diaphragm is an intermediate pressure higher than the downstream (P2) pres sure by the sum of the pressures re quired to overcome the main valve’s plug unbalance force and the piston spring’s force.
3. The pilot has a bleed orifi ce that continu- ously bleeds part of the loading medium down stream. In op er a tion, the pilot valve’s plug can fl ow more medium than is bleed-
SECTION III
ing down stream. This increases the loading pres sure on the main valve’s plug and opens valve. Partially closing the pilot valve’s plug will reduce its fl ow to less than the amount bleed ing downstream, and allows the loading pressure on the main valve’s diaphragm to de cay, allowing partial closing of the main valve’s plug. This continues until steady-state is de vel oped.
4. The pilot valve’s diaphragm(s) senses the down stream (P2) pressure and compares the force generated to the force developed by the pilot’s range spring.
5. If, during operation, the downstream (P2) pres­ sure falls below the pilot valve’s setpoint, the main valve’s diaphragm senses the reduced pres sure on its underside and instantly moves down, increasing the fl ow through the main valve. At the same time, the pilot valve
IOM-POSR-12
senses the reduced pressure and the pilot valve’s plug increases its opening, elevating the load ing pressure on the upper side of the main valve’s diaphragm.The combined actions increase fl ow enough to restore the down- stream (P2) pressure to the setpoint.
6. If the downstream (P2) pressure rises above the setpoint, the force developed by the in creased pressure on the underside of the diaphragm instantly moves it upward and partially closes the main valve’s plug. Si mul ta neous ly, the pilot valve’s plug partially clos es and al lows
SECTION IV
the loading pressure to decay through the bleed orifi ce. The reduced load ing pres sure on the upper side of the di a phragm closes the main valve’s plug enough to re store the down stream (P2) pressure to the setpoint.
7. Pressure setpoint is adjusted by changing the com pres sion of the pilot’s range spring by turning the adjusting screw either clockwise (CW) or counter-clock wise (CCW). Turning the adjusting screw clockwise (CW) will in crease the downstream (P2) pressure. Turn ing the adjusting screw counter-clockwise (CCW) will decrease the down stream (P2) pressure.
IV. START-UP
CAUTION
A. General
1. Start with the block valves closed.
2. Ensure that the needle valve(s) on the sens ing line is opened and downstream (P2) pres sure is in di cat ing on pressure gauge.
3. Relax the pilot valve range spring by turning the adjusting screw counter clockwise (CCW) (viewed from above) a minimum of three (3) full revolutions. This reduces the outlet (down­ stream) pressure setpoint.
For POSR-1-20 use manual loading valve to
set minimum loading pressure.
Outlet Pressure - P2
psig (Barg)
5 (0.34) 15 (1.03) 25 (1.7)
50 (3.45) 60 (4.1) 70 (4.8)
100 (6.90) 110 (7.6) 120 (8.3)
130 (8.97) 145 (10.0) 150 (10.3)
135 (9.31) 150 (10.3) – ( – )
Loading Pressure - P3, psig (Barg)
Minimum @ P1 Maximum
@ P
1
4. Slowly open the bypass valve to preheat the system piping and to allow slow ex pan sion of the piping. Assure proper steam trap op­ er a tion. Closely monitor outlet (down stream) pressure via gauge to assure not over-pres sur­ iz ing. NOTE: If no bypass valve is in stalled,
extra caution should be used in start ing up a cold system; i.e. do ev ery thing slowly.
5. Slowly open the outlet (downstream) block valve until fully open. Slightly close the by pass valve at same time.
IOM-POSR-1 3
Do not walk away and leave a bypassed reg u la tor unat­tended when on manual bypass!
6. Slowly open the inlet (upstream) block valve ob serv ing the outlet (downstream) pres sure gauge. De ter mine if the reg u la tor is fl owing.
If not, slightly close bypass valve, and then
slowly rotate the pilot valve adjusting screw clock wise (CW) (viewed from above) until fl ow begins.
For POSR-1-20 in crease load ing pres sure
until fl ow begins.
CAUTION
Do not exceed Maximum Loading Pressure limits for P2 set point.
7. Continue to alternate slow ly closing the bypass valve and then slowly opening the inlet (upstream) block valve, es pe cial ly when the down stream piping sys tem isn’t pressurized.If the outlet (downstream) pressure exceeds the desired pressure, close the bypass valve un­til fully closed. If outlet pres sure still re mains above desired level, rotate pilot’s ad just ing screw CCW (viewed from above) in 1/2 rev o lu tion in cre ments until out let pres sure reach es de sired level. If outlet pres sure is below de sired level, ro tate pilot’s ad just ing screw CW (viewed from above) until de sired level is reached.
For POSR-1-20 adjust manual loading valve
to either increase or decrease loading pres­ sure until desired set point is reached. Do not exceed limits.
8. When fl ow is established steady enough that the inlet (upstream) block valve is fully open, begin to slowly close the bypass valve and continue until fully closed.
9. Develop system fl ow to a level near its ex pect ed normal rate, and reset the reg u la tor setpoint by turning the pi lot valve ad just ing screw CW
SECTION V
(viewed from above) to in crease outlet pres­sure, or CCW to reduce outlet pres sure.
10. Reduce system fl ow to a minimum level and observe setpoint. Outlet pressure will rise from the set point of Step 9. There should be no more than a 10% vari a tion in outlet pres sure over the max i mum to min i mum fl ow range.
V. SHUTDOWN
A. General
1. On systems with a bypass valve, and where system pressure is to be main tained as the POSR-1 is shut down, slowly open the by pass valve while closing the inlet (up stream) block valve. Fully close the inlet (up stream) block valve. (When on by pass, the sys tem pres sure must be con stant ly ob served and man u al ly reg u lat ed.) Close the outlet (down stream) block valve. Close the nee dle valve on the pilot valve’s sensing line.
SECTION Vl
VI. MAINTENANCE
CAUTION
SYSTEM UNDER PRESSURE. Prior to performing any maintenance, isolate the regulator from the sys tem and relieve all pressure. Failure to do so could result in per­sonal injury.
CAUTION
Do not walk away and leave a bypassed reg u la tor unat­tended when on manual bypass!
2. If the regulator and system are to both be shut­ down, slowly close the inlet (up stream) block valve. Close the out let (down stream) valve only if reg u la tor re mov al is required. Close the needle valve on the pilot valve’s sensing line.
For POSR-1-20 close manual loading valve
and relieve loading pressure.
4. All indicated item numbers that are with respect to the Pilot Valve will be in pa ren ­the sis and underscored, i.e. (14), (PV). All item numbers that are with respect to the Main Valve will NOT be underscored, i.e. (1), (MV).
5. Refer to Figures 3 and 4 for item num ber callouts.
A. General:
1. Maintenance procedures hereinafter are based upon removal of the regulator unit from the pipeline where installed.
2. Owner should refer to owner’s procedures for re mov al, handling, cleaning and dis pos al of non-reuseable parts, i.e. gaskets, etc. Cash co recommends not reusing any gas kets, but re­placing with only new and fac to ry supplied
gaskets.
3. This regulator is supplied from the factory using a gasket sealing aid, Federal Pro cess Company, PLS 2, or equal. Such compatible sealing aids may be utilized by the Owner, if desired.
6. Most pilot-operated valve operation problems center around the pilot valve (PV). Cashco always rec om mends full maintenance on any POSR-1 pilot valve (PV) once a POSR-1 is removed from the pipeline.
B. Separation:
1. Observe position of pilot valve (PV) with respect to main valve (MV) before dis as ­sem bling.
2. Place main valve body (1) into a vise, oriented to allow rotation of pilot valve (PV) to geth er with in ter con nect ing pipe nipple (19).
3. Remove loading tubing (21) at both end fi t- tings (20) by rotating nut CCW (viewed from tube-end).
IOM-POSR-14
+ 8 hidden pages