Cashco HP User Manual

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM)
12-13
MODEL HP
PRESSURE RE DUC ING REGULATOR
SECTION I
I. DESCRIPTION AND SCOPE
The Model HP is a heavy duty, high pressure reducing regulator used to control downstream (outlet or P2) pres sure. Sizes are 1/2", 3/4", 1" and 1-1/2" (DN15, 20, 25 and 40). With proper trim utilization, the unit is suit able for liquid and gaseous service. Refer to Technical Bulletin HP-TB for design conditions and selection rec om men da tions. NOT FOR
STEAM SERVICE.
SECTION II
II. INSTALLATION
CAUTION
IOM-HP
Installation of adequate overpressure pro tec tion is recommended to pro tect the reg u la tor from overpres­sure and all down stream equip ment from damage in the event of regulator failure.
CAUTION
For welded installations, all internal trim parts, seals and diaphragm(s) must be removed from reg u la tor body prior to welding into pipeline. The heat of fusion welding will dam age non-metallic parts if not re moved. NOTE: This does not apply to units equipped with extended pipe nip ples.
1. An inlet block valve should always be installed.
2. If service application is continuous such that shut down is not readily accomplished, it is rec ommended that an inlet block valve, outlet block valve, and a manual bypass valve be installed.
3. Pipe unions should be installed to allow removal from piping.
4. An outlet pressure gauge should be located ap prox­i mately ten pipe diameters downstream, and within sight.
outlet pressure rating of the unit.
6. Clean the pip ing of all foreign material including chips, welding scale, oil, grease and dirt before installing the regulator. Strainers are rec om mend ed.
7. In plac ing thread seal ant on pipe ends pri or to en­ gage ment, ensure that excess material is re moved and not allowed to enter the regulator upon startup.
8. Flow Direction: Install so the fl ow direction match es the arrow cast on the main regulator body.
9. Basic Regulator - (Refer to Figure 1): Regulator may be rotated around the pipe axis 360°. Rec om mend ed position is with spring chamber ver ti cal upwards. Orient such that the spring chamber vent hole does not collect rainwater or debris.
10. Regulators are not to be direct buried un der ground.
5. All installations should include a downstream re lief de vice if the inlet pressure could exceed the pres sure rating of any downstream equip ment or the maximum
11. For insulated piping systems, recommendation is to not insulate regulator.
SECTION III
III. PRINCIPLE OF OPERATION
1. Movement occurs as pressure variations register on the diaphragm. The registering pressure is the outlet, P2, or downstream pressure. The range spring op­poses di a phragm movement. As outlet pressure drops, the range spring pushes the dia phragm down, opening the port; as outlet pres sure in creas es, the diaphragm pushes up and the port opening closes.
2. A complete diaphragm failure will cause the reg u la tor to fail open.
SECTION IV
* NOTE: Systems sequencing operations at startup,
normal operation, failure mode(s), and shutdown must as­sure that the pressure (P does not exceed the pressure registering on the wetted side of the diaphragm. Should this "pressure reversal" oc­cur, particularly to metal diaphragms, the diaphragm may be permanently damaged and cause improper operation.
P1 > P2 > P
Pressure reversal is normally caused by the inlet pressure to a regulator being interrupted (automatically or manually).
IV. STARTUP
) on the spring chamber
Load
Load
CAUTION
The maximum outlet pressure is list ed on the name­ plate as the upper range spring pres sure level, and is the rec om mend ed "upper operative limit" for the sens ing diaphragm. Higher press ures could dam age the di a phragm. Refer to HP-TB, Table 5, for “emergency over-pressure level”. NOTE: Inlet pres sure and outlet pressure ratings are at different levels. (Field hydro static tests fre quent ly de stroy dia phragms. DO NOT HYDRO STATIC TEST THRU AN IN STALLED UNIT; ISO LATE FROM TEST.).
4. Crack open the outlet (downstream) block valve.
5. Slowly open the inlet (upstream) block valve ob serv ing the outlet (downstream) pressure gauge. De ter mine if the regulator is fl owing. If not, slowly rotate the regulator adjusting screw clockwise (CW) until fl ow begins.
6. Continue to slowly open the inlet (upstream) block valve until fully open.
7. Continue to slowly open the outlet (downstream) block valve, especially when the downstream pip ing system isn't pressurized. If the outlet (down stream) pressure exceeds the desired pres sure, close the block valve and go to Step 2, then return to Step 4.
1. Start with the block valves closed. A by pass valve may be used to maintain out let pres sure in the down stream sys tem without changing the fol low ing steps.
2. Relax the range spring by turning the adjusting screw counter clockwise (CCW) a minimum of three (3) full revolutions. This reduces the outlet (down stream) pres­ sure set point.
3. If it is a “hot” piping system, and equipped with a by­pass valve, slowly open the bypass valve to pre-heat the system piping and to allow slow ex pan sion of the piping. Closely monitor outlet (down stream) pres sure via gauge to ensure not over-pressurizing. NOTE: If no
bypass valve is in stalled, extra caution should be used in starting up a cold system; i.e. do everything slowly.
V. SHUTDOWN
1. On systems with a bypass valve, and where sys tem pressure is to be maintained as the reg u la tor is shut down, slowly open the bypass valve while closing the inlet (up stream) block valve. Fully close the inlet (upstream) block valve. (When on bypass, the system pressure must be constantly observed and manually regulated. Close the outlet (downstream) block valve.
8. When fl ow is established steady enough that the outlet (downstream) block valve is fully open, be gin to slowly close the bypass valve if installed.
9. Develop system fl ow to a level near its expected nor- mal rate, and reset the regulator set point by turning the adjusting screw CW to increase outlet pressure, or CCW to reduce outlet pressure.
10. Reduce system fl ow to a minimum level and ob serve set point. Outlet pressure will rise from the set point of Step
9. The maximum rise in outlet pressure on decreasing ow should not exceed the stated upper limit of the range spring by greater than 10%; i.e. 400–750 psig (27.5 –51.7 Barg) range spring, at low fl ow the outlet pressure should not exceed 825 psig (56.8 Barg), if it does, consult factory.
SECTION V
CAUTION
Do not walk away and leave a bypassed reg u la tor unattended.
2. If the regulator and system are to both be shut down, slowly close the inlet (upstream) block valve. Close the outlet (downstream) valve only if reg u la tor re mov al is required.
IOM-HP2
SECTION VI
VI. MAINTENANCE
WARNING
SYSTEM UN DER PRES SURE. Prior to performing any maintenance, isolate the reg u la tor from the system and relieve all pres sure. Failure to do so could result in personal injury.
A. General:
1. Maintenance procedures hereinafter are based upon re mov al of the regulator unit from the pipe­line where in stalled.
2. Owner should refer to owner's procedures for removal, handling, cleaning and disposal of non­reusable parts, i.e. gaskets, etc.
3. Refer to Figure 1 for the basic regulator and Figure 2 for a blowup of the balanced trim.
B. Diaphragm Replacement:
1. Securely install the body (1) in a vise with the spring chamber (2) directed upwards.
WARNING
If apparent, recommend trim re mov al and inspec­tion; go to Sub-sec tion C or D following. Reinstall pusher plate (11).
7. Inspect pressure plate (3) to ensure no de for ma tion due to over-pressurization. If de formed, replace.
8. Clean body (1) and diaphragm fl ange. NOTE: On
reg u la tors originally sup plied as “oxygen clean”, Option-55, main te nance must include a level of clean li ness equal to Cashco's clean ing stan dard #S-1134. Con tact factory for details.
9. Place diaphragm gasket (13) on body (1) fl ange. Position diaphragm(s) (12) into place. NOTE: Re-
fer to the quantity of diaphragms (12) incorporated in the bill of materials list ing. Depending on the outlet pressure lev el; mul ti ple metal diaphragms may be “stacked”. Visually center pressure plate
(3) on diaphragm(s) (12), and set range spring (14) onto retainer hub of pressure plate (3).
10. Place multi-purpose, high temperature grease into depression of spring button (4) where adjust­ing screw bears. Set spring but ton (4) onto range spring (14); ensure spring button is laying fl at.
NOTE: For units with range springs 120-225 psig (8.27-15.5 Barg) and higher, position spring button (4), thrust bearing (21) and bearing washer (22) on top of range spring (14).
SPRING UNDER COMPRESSION. Prior to re mov ing diaphragm fl ange bolts, relieve spring com pres sion by back ing out the adjusting screw. Fail ure to so so may result in fl ying parts that could cause per- sonal injury.
2. Relax range spring (14) by turning adjusting screw (6) CCW until removed from spring cham ber (2).
3. Draw or embed a match mark between body casting (1) and spring chamber casting (2) along anged area.
4. Remove all diaphragm fl ange nuts (9) and bolts (8, 23).
5. Remove spring chamber (2), range spring (14), spring button (4), pressure plate (3), diaphragm(s) (12), and di a phragm gas ket (13), for metal dia­phragm (no diaphragm gas ket (13) for composition diaphragm). NOTE: For units with spring ranges
120-225 psig (8.27 - 15.5 Barg) and higher, also remove the thrust bearing (21) and bearing washer (22).
6. Remove pusher plate (11) and inspect for a fi t which limits its travel to a vertical direction. Wear will show as excessive wobble in push er plate (11).
11. Aligning matchmarks, place spring chamber (2) over the above stacked parts. Install all bolts (8), (23) and nuts (9) by hand tightening. Mechani­cally tightening bolting in a cross pattern that al­lows spring chamber (2) to be pulled down evenly. Recommended torque values are as follows:
Regulator Size Bolt Size Metal Diaph. Comp. Diaph.
1/2", 3/4" & 1"
(DN15, 20 & 25)
1-1/2" (DN40) 7/16-20 50 Ft-lbs 30 Ft-lbs
NOTE: Never replace bolting (8 & 9) (23) with just
any bolting if lost. Bolt heads and nuts are marked with specifi cation identifi cation mark ings. Use only proper grades as re place ments.
12. Reinstall ad just ing screw (6) with locknut (7).
13. Pressurize with air and soap so lu tion test around bolting (8 & 9) (23), body (1) and spring cham ber (2) for leakage. Ensure that an outlet pressure is maintained during this leak test of at least mid­range spring level; i.e. 120-255 psig (8.27-15.5 Barg) range spring, 173 psig (11.9 Barg) test pres sure minimum.
3/8-24 30 Ft-lbs 25 Ft-lbs
IOM-HP
3
Loading...
+ 5 hidden pages