Cashco 135 User Manual

Page 1
INSTALLATION, OPERATION, & MAINTENANCE
MANUAL IOM
IOM-135
12/13
MODEL 135
PNEUMATIC CONTROLLER
LOW TEMPERATURE SHUTOFF
SECTION I
I. DESCRIPTION AND SCOPE
The Model 135 thermal probe is a low temperature shutoff device with an integral, rigid insertion bulb used to protect downstream piping systems and equipment from experiencing temperature excursions below desired minimum operating temperature due to equipment malfunction or customer overdraw of system capacity. This is NOT a
SAFETY DEVICE.
The Model 135 is not a stand-alone device. Primarily installed with a pressure loaded reducing regulator with fail-close action upon the loss of loading pressure. It is used with any compatible fl uid that can be vented to atmo- sphere in an environmentally acceptable method. This combination of equipment is known as a PRESSURE/LOW TEMPERATURE CONTROL MODULE (PTCM). It typically consists of a Model 135 thermal probe, an unloading backpressure valve, fl ow restricting orifi ces and a main regulator.
II. PRINCIPLES OF OPERATION
As the Model 135 thermal probe external sheath is exposed to lower temperatures, it contracts in length. The internal Invar rod remains unchanged in length, pushing a ball/plug away from its seat, allowing the inlet gas pressure to be "vented".
The PTCM low temperature protection is provided through the Model 135 thermal probe. When the fl uid
III. INSTALLATION
1. Inspect the SST tag on the Model 135 and note the Calibration and Re-Calibration dates. If the Re-Calibration date has expired, return the Model 135 to Cashco. Inc, for recalibration. If the tag is missing do not install the unit, return it to Cashco. Inc,. Each probe is factory cali brated per customer's order and set point speci cations.
2. Prior to installation, check that the Model 135 operates within the desired window for the set point. If it does not operate correctly, return it to Cashco. Inc,.
SECTION II
is approximately 8°F (4.5°C) above the setpoint, the Model 135 thermal probe will begin to open, lowering the loading pressure and thereby the delivery pres­sures. The delivery flow rate is reduced by this action. When the fluid is at the setpoint, the Model135 thermal probe will reduce the loading pressure to 5 psig (.34 Barg),essentially closing the main regulator. When the fluid is slightly below setpoint the main regulator will close tight.
SECTION III
CAUTION
Setpoint for the probe can shift if it is mis-handled prior to installation.
3. Apply a compatible sealant to the 1/2" (DN15) NPT threads and insert the Model 135 probe into the upstream pipe line requiring control. With a wrench, secure the fl at surfaces on the body and rotate the probe clockwise (CW) until probe is tight. See Figure 1.
Page 2
SECTION IV
IV. MAINTENANCE
1. The Model 135 is shipped from the factory preset per the customer's order specifi cations. All main- tenance should be preformed at the factory.
WARNING
SYSTEM UNDER PRESSURE. Relieve all pressure prior to removing the Model 135 from the piping system or performing any maintenance on the PTCM. Failure to do so could result in personal injury.
Figure 1
2
IOM- 135
Page 3
SECTION V
V. CALIBRATION
All Model 135 thermal probes should be re-calibrated annually if the unit has been in service. Refer to Section IV
for instructions to remove and replace the Model 135 thermal probe. Write the main valve serial number on an adhesive label and apply to the probe. Return all used thermal probes to the factory for examination and calibration.
SEC TION VI
VI. TROUBLE SHOOTING GUIDE
1. No/Low Flow or Pressure at Normal Operating Temperatures
Possible Causes Remedies
A. No supply pressure to PTCM. A Check gauges.
B. Lockout valves closed. B. Open valves.
C. Unloading valve incorrectly set. C. Reset.
D. Model 135 thermal probe vent leaking. D. Under normal operating conditions, there should be no fl ow
coming from the outlet vent. If there is fl ow and the temperature of the gas is not suspect then replace the Model 135 thermal probe.
E. Upstream fi lter/orifi ce blocked. E. Inspect and replace if necessary.
F. Unloading valve malfunction. F. Inspect and replace if necessary.
G. Leaking or broken fi tting. G. Inspect and replace if necessary.
H. Main regulator stuck closed. H. Verify dome pressure.
I. Strainer blocked. I. Inspect and replace if necessary.
2. Poor Pressure Control
Possible Causes Remedies
A. Back Pressure valve failed A Inspect and replace if necessary.
B. Upstream fi lter/orifi ce blocked. B. Inspect and replace if necessary.
C. Leaking or broken fi tting. C. Inspect and replace if necessary.
D. Diaphragm in main regulator failed. D. Inspect and replace if necessary.
3. Delivery Pressure Rise at No/Low Flow
Possible Causes Remedies
A. Main regulator seat leakage. A Inspect and replace if necessary.
B. By-pass valve leaking. B. Inspect and replace if necessary.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be con­strued as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifi cations of such product at any time without notice. Cashco, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Cashco, Inc. product remains solely with the purchaser.
IOM-135
3
Page 4
Cashco, Inc. P.O. Box 6 Ellsworth, KS 67439-0006 PH (785) 472-4461 Fax. # (785) 472-3539 www.cashco.com email: sales@cashco.com
Printed in U.S.A. 135-IOM
Cashco GmbH Handwerkerstrasse 15 15366 Hoppegarten, Germany PH +49 3342 4243135 Fax. No. +49 3342 4243136 www.cashco.com Email: germany@cashco.com
Cashco do Brasil, Ltda. Al.Venus, 340 Indaiatuba - Sao Paulo, Brazil PH +55 11 99677 7177 Fax. No. www.cashco.com Email: brazil@cashco.com
Loading...