Improper installation, adjustment, alteration, service, maintenance,
or use can cause fire, electrical shock, or other conditions which
may cause personal injury or property damage. Consult a qualified
installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or
accessories when installing.
Follow all safety codes and wear safety glasses. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
and state building codes and Sheet Metal and Air Conditioning
National Association (SMACNA) for special installation requirements.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit or in instructions and
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
INSTALLATION CONSIDERATIONS
1. Install in a non-condensing area with ambients between 32°F
and 120°F.
2:45
A93208
.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1144
Tab 3a 5a 2a 5a
PC 101Catalog No. 809-568Printed in U.S.A.Form ZONEKIT4-1SIPg 17-95Replaces: 920415-3SI
2. Use vibration isolators (flex connectors) on zone dampers and
duct work to minimize noise.
3. Place dampers away from areas that may be noise sensitive.
4. TXV is required in air conditioning and heat pump applications.
5. Use separate isolated transformer to supply power to Comfort
Zone System (50 va minimum, class 2, field supplied).
6. Load calculations must be performed to determine equipment
size. Equipment selection is matched to block load. It is
imperative equipment is not oversized.
7. Duct work must be designed based off the sum of peaks plus
25 percent oversize. It is imperative duct work is not undersized.
INTRODUCTION
This installation guide pertains to revision 1.6 or greater. The
Comfort Zone System allows air conditioning and heating equipment to control temperatures in up to 4 distinct spaces or Zones
within a building. Each zone has independent temperature settings.
The comfort temperature settings can change automatically
through the use of schedules. This allows Comfort Zone to change
temperature settings in zones to reflect occupancy or usage. For
example, you can condition the bedrooms in a home from 5:00 PM
through 7:00 AM or the kitchen from 3:00 PM through 6:00 PM.
The Comfort Zone System uses motorized air volume control
dampers (also called zone dampers) to regulate flow of conditioned air into zones. In this manner Comfort Zone can selectively
heat or cool certain portions of a building depending upon space
temperature requirements.
INSTALLATION
Step 1—Check Equipment and Jobsite
INSPECT EQUIPMENT — File claim with shipping company,
prior to installation, if shipment is damaged or incomplete.
Step 2—Wiring
Shielding For A Single Comfort Zone System
1. Fig. 16 Shows a Comfort Zone System with all possible
options. The shield from all devices should be tied together at
I/O board and terminated at shield ground at lower right hand
corner of board. Be sure shielding does not touch any other
wiring on board.
NOTE: Do not connect shield wire at device end. Cut end and
tape up to avoid shorting.
Shielding For Multiple Comfort Zone Systems
1. If more than 1 Comfort Zone System resides on 1 job, they
may be tied together for communication purposes. If no
communication is required, then Comfort Zone System should
be wired separate and shielded as previously stated.
2. When 2 to 4 systems are on 1 job and require communication,
they should be daisy chained together through 3-wire communication bus at COM BUS HAM terminal.The shielding
should only be grounded at 1 point on end of communication
bus as shown in Fig. 2.
SHIELD DRAIN WIRE
Comfort
Zone
I/O
NOTES:
1. Use butt splices, or solder, for shield connections. Then tape up shield.
2. Do not connect the shield drain wire at the end of Communication Bus.
Cut and tape up to avoid shorting.
Comfort
Zone
I/O
Comfort
Zone
I/O
SHIELD DRAIN WIRE
Comfort
Zone
I/O
NOTE 2NOTE 1
A93251
Fig. 2—Daisy-Chained Comfort Zone Systems
To prevent personal injury or possible equipment damage
disconnect power supply before routing wire.
All wiring must comply with local and state codes.
NOTE: A remote room sensor requires a 2-wire cable, however,
it is recommended that a 5-wire cable be installed to allow for a
possible smart sensor upgrade. Connect white wire to terminal
labeled B- if a 5-wire cable is used. Connect red wire to R+.
Shielded cable is recommended to reduce noise interference.
NOTE: Use No. 22 AWG color-coded, insulated (35°C min)
wire. If thermostats are to be located more than 100 ft from
Comfort Zone Center as measured along control voltage wires, use
18 AWG colored-coded wires to avoid excessive voltage drop.
All wiring is run back to Comfort Zone Center. Keep wires a
minimum of 12 in. from any AC voltage. Do not tie-wrap wires
together. When wiring to COM BUS, a 3-wire cable must be
separate from the 5-wire cable. The thermostats should be located
approximately 5 ft above floor and must be located within 200 ft
of Comfort Zone Center.
SHIELDED CABLE
General
1. All wiring should be shielded (except damper wiring) with 18
or 22 gage. The 3-wire, 5-wire, and Remote Sensor wire must
be in separate jacketed cable.
2. All system wiring must be within 1 building. Never connect
devices between 2 or more buildings.
3. If more than 4 systems are used on 1 job, multiple device
buses must be used. Each device bus must be separated by an
ISOSAT-01. A typical arrangement is shown in Fig. 3.
Communication Bus Guidelines for Maximum Number of
Devices
1. The maximum number of Comfort Zone Systems allowed on
1 device bus is 4.
2. Four Zone Controllers must be addressed 4 addresses apart,
example 4, 8, 12, 16 for a device bus with 4 Comfort Zone
Systems.
3. Home Access Module (optional) will scan a maximum of 4
Comfort Zone Systems.
4. Multiple device buses can be tied together for communication
via ISOSAT-01. An ISOSAT-02 is required for remote or
direct communications via personal computer or modem. (See
Fig. 4.)
5. Comfort Zone Systems may reside on a bus with VVT system
devices. They may receive or broadcast time to these devices
accordingly by toggling T5 enable broadcast on or off.
NOTE: If multiple 4-zone controllers are on 1 bus, only 1 can
broadcast time. Turn all others off (T5).
2
NOTE 2
PORT #1
PORT #2
ISOSAT-01
NOTE 2
PORT #1
PORT #2
ISOSAT-01
Comfort
Zone
I/O
ISOSAT BUS
PORT #1
PORT #2
SHIELD DRAIN WIRE (TYP)
PORT #1
PORT #2
PORT #1
PORT #2
ISOSAT-01
DEVICE BUS (TYP)
ISOSAT-01
ISOSAT-01
BUILDING GROUND
Fig. 3—Typical Communications Network
Comfort
Zone
I/O
SHIELD DRAIN WIRE (TYP)
NOTES:
1.Use butt splices, or solder,
for shield connections. Then
tape up shield.
2.Do not connect the shield
drain wire at the end of
Communication Bus. Cut
and tape up to avoid shorting.
Comfort
Zone
I/O
NOTE 2NOTE 1
A93249
Table 1—Wiring Requirements
FROM
COMFORT ZONE
CENTER TO
Four Zone Controller
Remote Room Sen-
sors
NO.
OF WIRES
GAGE
3‡18/22200/100
5‡18/22200/100
2‡18/22200/100
Remote Duct Sensors2‡18/22200/100
Dx Coil Sensor2‡18/22200/100
Home Access
Module
3‡18/221000/100
ISOSAT*3‡18/221000/100
Transformer†21875
* When using ISOSATS in interfacing multiple buses together, the length of
wiring between ISOSATS cannot exceed 4000 ft with 18 gage.
† 24 vac, 50-75 va
‡ Shielded cable recommended to reduce noise interference.
Step 3—Install Comfort Zone Center
NOTE: The Comfort Zone System is approved for indoor use
only and should never be installed with any of its components
exposed to the elements. The enclosure must be installed with
center cover to help prevent damage from other sources. Do not
mount Comfort Zone Center where it will be accessible to
children. Do not locate center in areas of the home that are noise
sensitive since relays are energized and de-energized during
operation and may be an annoyance. Install Comfort Zone in an
area with a temperature range between 32°F and 120° F.
Install Comfort Zone Center in either a vertical or horizontal
position. Locate in an area that is easily accessible in case
servicing should be required.
NOTE: Four vent plugs and 2 bushings have been supplied. Snap
bushings in the 1-in. diameter holes that are to be used for wiring
and place plugs in remaining holes.
MAX.
LENGTH
(FT)
Comfort
Zone
I/O
ISOSAT BUS
PORT #1
PORT #2
SHIELD DRAIN WIRE (TYP)
PORT #1
PORT #2
PORT #1
PORT #2
PORT #1
PORT #2
BUILDING GROUND
ISOSAT-01
DEVICE BUS (TYP)
ISOSAT-01
ISOSAT-01
TO PERSONAL COMPUTER OR MODEM
ISOSAT-02
Fig. 4—Communication Network With
Comfort
Zone
I/O
SHIELD DRAIN WIRE (TYP)
NOTES:
1.Use butt splices, or solder,
for shield connections. Then
tape up shield.
2.Do not connect the shield
drain wire at the end of
Communication Bus. Cut
and tape up to avoid shorting.
Comfort
Zone
I/O
NOTE 2NOTE 1
A93250
An ISOSAT-02
To prevent possible damage to Comfort Zone Center, do not
mount on plenum, duct work, or flush against furnace.
1. Separate Comfort Zone Center cover. (See Fig. 5)
2. Mount back plate of center cover to wall using screws and
wall anchors provided.
3. Level back plate and tighten screws.
Step 4—Install Zone Dampers
IMPORTANT: If conditions exist for possible condensing, motor
must be positioned for adequate draining. (See Fig. 6.)
NOTE: If a multi-damper enabler is used to link dampers
together, add 5va per damper to the transformer power supply
rating. Reference multi-damper enabler Installation Instructions.
Zone dampers may be installed in any direction.
Install dampers so that actuator is visible for inspection and
accessible in the event it would ever need to be serviced. The black
mark on the end of damper shaft represents the position of damper
blade.
NOTE: Insulate damper using 1-1/2 in. insulation (check local
codes). In areas where excessive condensing may occur, carefully
insulate over the actuator assembly. Make sure insulation does not
interfere with operation of actuator.
3
COMFORT ZONE CENTER
BACK PLATE
INTERCHANGEABLE
HOLE PLUGS AND
BUSHINGS
MOUNTING
HUB
AIRFLOW
AIRFLOW
POSITION
INDICATOR
COMFORT ZONE
CENTER COVER
Fig. 5—Comfort Zone Center
Comfort Zone
Center
DAMPERMOUNTING
BRACKET
A93247
ACTUATOR
HOUSING
QUICK BLADE
RELEASE
BUTTON
(RED)
FIELD
INSTALLED
POWER WIRING
Fig. 7—Damper 24-vac Connections
SUPPLY
Fig. 8—Round Metal Duct Work
CLS
FLEX
CONNECTOR
COM
OPN
90
45
0
ZONE DAMPER
ANGULAR
ROTATION
STOPS
MOUNTING
BRACKET
A95096
A95129
1
/ ″ STEEL STRAP
2
ACTUATOR
Fig. 6—Damper Motor Positioning
A95128
Before insulating the duct work, check for proper damper operation. Apply the 24vac between COM and OPN to open the damper
and COM and CLS to close the damper. (See Fig. 7.) The damper
will modulate counter-clockwise to open and clockwise to close.
If in an emergency it becomes necessary to force a damper open,
manually press in the red quick blade release button with one hand
and turn the mounting hub to reposition the damper shaft. Release
the button to hold the damper shaft in the new position.
To avoid noise and vibration, do not hard mount dampers to any
solid structure such as joists.
ROUND METAL DUCT WORK
IMPORTANT: If application exists with all metal duct work
without insulation, flex connectors must be used on each end of
zone dampers to avoid noise and vibration.
1. Crimp end of branch duct.
2. Slip end of zone damper over end of duct work. Use
self-tapping sheet metal screw to secure. (See Fig. 8.)
3. Properly seal joint using duct tape, mastic, or other approved
method. Do not allow mastic to come in contact with actuator.
4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.)
Fig. 9—Insulated Round Metal Duct Work
NOTE: All zone dampers and duct work must be properly
supported according to local codes or SMACNA standards.
RECTANGULAR METAL DUCT WORK
1. Make connections using S-lock and drives. (See Fig. 10.)
2. Properly seal joint using duct tape, mastic, or other approved
method. Do not allow mastic to come in contact with actuator.
3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.)
NOTE: All zone dampers and duct work must be properly
supported according to local codes or SMACNA standards.
NOTE: There should be a minimum of 4 ft between zone damper
and first branch duct if more than 1 branch duct is downstream of
zone damper.
ROUND FLEXIBLE DUCT WORK
1. Slip 1 end of flexible duct work over 1 end of zone damper.
(See Fig. 12.)
4
A95130
S-LOCK
1
2
/ ″ STEEL STRAP
SUPPLY
AIR DUCT
DRIVE
Fig. 10—Rectangular Metal Duct Work
1
2
1 / " TO 2"
INSULATION
ZONE
DAMPER
A92478
A95131
Fig. 11—Insulated Rectangular Metal Duct Work
FLEXIBLE
DUCT
Fig 12—Round Flexible Duct Work
ZONE
DAMPER
A95132
A95133
Fig. 13—Insulated Round Flexible Duct Work
FIBROUS
GLASS
DUCTWORK
2″ TO 3″
FIELD
SUPPLIED
SCREWS
ZONE
DAMPER
A92480
Fig. 14—Rectangular Fibrous Glass Duct Work
1
2
1 / ″ TO 2″
INSULATION
A95134
Fig. 15—Insulated Rectangular Fibrous Glass Duct
Work
Step 5—Install Barometric Bypass Damper
NOTE: The barometric bypass damper is a critical part of
Comfort Zone System for control of minimum airflow and noise
reduction. It is recommended that the bypass be installed.
The bypass should be installed according to local codes and
SMACNA standards. Be sure bypass is properly supported.
For proper installation, refer to Installation Instructions packaged
with barometric bypass.
2. Secure flexible duct to zone damper using SMACNA or other
approved method.
3. Properly seal joint using duct tape, mastic, or other approved
method. Do not allow mastic to come in contact with actuator.
4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.)
NOTE: All zone dampers and duct work must be properly
supported according to local codes or SMACNA standards.
RECTANGULAR FIBROUS GLASS DUCT WORK
1. Insert 1 end of zone damper into 1 end of fibrous glass duct
work approximately 2- to 3-in. (See Fig. 14.)
2. Screw field-supplied screws and tabs into zone damper.
3. Properly seal joint using duct tape, mastic, or other approved
method. Do not allow mastic to come in contact with actuator.
4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.)
Failure to properly install bypass damper can cause permanent damage to the HVAC equipment. For single speed
furnace applications bypass air must never exceed 25 percent.
Step 6—Install Duct Temperature Sensor
Locate duct temperature sensor in main supply trunk after heating
and cooling coil and before bypass damper and first branch. The
duct temperature sensor must be radiant shielded to prevent heat
from affecting correct air temperature.
1. Drill a 7/8-in. hole at location in unit where sensor will be
installed.
2. Remove cover and insert sensor probe through 7/8-in. hole.
3. Drill two 1/16-in. holes to accept No. 6 screws through
pre-drilled holes in duct temperature sensor back plate.
4. Use two No. 6 sheet metal screws included with sensor to
mount duct temperature sensor back plate to unit.
5
5. Insert 2-conductor wiring through 1 of pre-drilled holes in side
of back plate.
6. Connect sensor to 2-wire conductor using provided wire nuts.
(See Fig. 16 for connection to Comfort Zone Center.)
Step 7—Install Dx Coil Sensor
The Dx coil temperature sensor is recommended for use in heat
pump with fan coil applications only. The sensor should be
installed between Dx coil and electric heaters. It measures Dx coil
temperature and adds extra protection for high/low temperature
limits. The range is from 30°F to 180°F. The Dx coil sensor
interfaces to Comfort Zone Center on terminal TB-1. (See Fig. 16.)
To activate Dx coil temperature sensor turn T-27 on. When
activated, the Dx coil sensor has built-in LAT setpoints of 50°F
and 45°F in the cooling mode, and 105°F and 110°F in the heating
mode. This is non-adjustable.
Step 8—Install Four Zone Controller
The Four Zone Controller is the zone 1 thermostat. It is recommended to locate this in the zone occupied as the living room or
family room for maximum comfort.
DO NOT locate controller where supply air can blow directly on
it. Avoid locating controller where heat from any lamps, appliances, or direct sunlight will affect temperature sensor on controller. Do not locate on an outside wall or next to a return air grill.
1. Separate base plate from main body of controller.
2. Pull 3-wire cable for communication bus and 5-wire cable for
controller through 3/4-in. round hole on base plate. Three-wire
cable and 5-wire cable must be separate jacketed wiring. Do
not use one 8-wire cable. (See Fig. 17.)
NOTE: Insulate or seal field wiring feed through hole to reduce
draft.
3. Mount base plate using provided screws, starting screw in
round hole first then second screw in slotted hole. On drywall
it is recommended to use provided plastic wall anchors.
NOTE: If mounting controller using an electrical box, mount base
plate using pair of horizontal holes.
4. Level base plate and tighten screw in slotted hole first, then
the screw in round hole.
5. Connect the 3 wires for communication bus and the 5 wires for
controller to base plate terminal screws. (See Fig. 16.) Ensure
that there are no excess or bare wires exposed.
6. Plug base plate connector into back of main body and ensure
it is secure into connector located on back of 4 zone
controller’s main body. Ensure connectors and main body are
secure.
7. Align main body with base plate and snap into place.
Step 9—Install Remote Room Sensors or
Smart Sensors (Optional)
Comfort Zone may have up to 4 zones. The 4 zone controller
controls zone 1. Remote room sensors or smart sensors control the
other 3 zones. If using a smart sensor, a smart sensor power pack
must be used. The remote sensors should be located 5 ft above the
floor and must be less than 200 ft away from Comfort Zone Center.
DO NOT locate sensors where supply air can blow directly on
them. Avoid locating sensors where heat from any lamps, appliances, or direct sunlight will affect temperature sensor on room
sensors. Do not locate on an outside wall or next to a return air
grill.
1. Separate the 2 parts of sensor and mount back plate with
provided flat-head screw.
2. Pull a 2-wire conductor through hole on right-hand side.
3. Connect black or white wire to terminal labeled B- and
connect red wire to terminal labeled R+.
4. Align sensor case with base plate then press firmly until cover
snaps into place.
Step 10—Sequence of Operation
TEMPERATURE SETPOINTS
The Comfort Zone System uses 2 temperature setpoints. The
setpoints are displayed in the left-hand window on the 4 zone
controller. (See Fig. 18.)
In display window, cooling setpoint is shown on upper left and
heating setpoint is shown on lower right.
The temperature setpoints for any of the 4 zones can be displayed
by the 4 zone controller. When the 4 zone controller rotary switch
points to zone 1, setpoints for zone 1 at the 4 zone controller are
displayed. Selecting zone 2, zone 3, or zone 4 will display
setpoints for each of these zones which use either remote room
sensors or smart sensors. The system is not required to have all 4
zones installed.
HEATING AND COOLING COMFORT SETPOINTS
If space temperature is between heating and cooling setpoints for
the zone, then the zone is said to be "satisfied" with respect to
temperatures. When a zone is "satisfied" no heating or cooling
equipment will turn on to condition the space. For example, if
cooling setpoint is 76°F and heating setpoint is 72°F, then a space
temperature of 73°F is assumed to be satisfactory and no heating
or cooling of zone is required.
If space temperature in a zone falls below heating setpoint, then
that zone needs to have heat added to zone which will raise space
temperature back to heating setpoint. For example, if heating
setpoint is 72°F and space temperature is 70°F, then space
temperature must be raised 2 degrees in order for zone to be
satisfied. In this case, temperature "heating demand" for zone is
2°F. (72°F minus 70°F.)
Otherwise, if space temperature in a zone rises above cooling
setpoint, then that zone needs to have heat removed from zone
which will lower space temperature back to cooling setpoint. For
example, if cooling setpoint is 76°F and space temperature is 77°F,
space temperature must be lowered 1° in order for zone to be
satisfied. In this case, "cooling demand" for zone is 1°F. (77°F
minus 76°F.)
Comfort Zone allows owner or installer to set ranges for comfort
setpoints along with maximum and minimum temperatures which
can be used by system.
Comfort Zone allows both heating and cooling comfort setpoints
to operate in a 14° span. The heating and cooling temperature
"spans" can be set to allow for a selected range of operation.
Rotary switch position 9 sets base temperatures for both heating
and cooling spans.
When switch is set to 9, both heating and cooling base temperatures are displayed and each can be modified by using up/down
setpoint buttons. The base temperatures are the same for all 4
zones.
If cooling base temperature is set to 68°F, then cooling comfort
range will be 68°F to 82°F. If heating base temperature is set to
54°F, then heating comfort range will be 54°F to 68°F.
6
Zone Dampers
ZN4
BYPASS
CL OP COM CL OP COM CL OP COM CL OP COM CL OP COM
COMFORT ZONE I/O
COMM
BUS HAM
ZN3 ZN2 ZN1
COMM BUS
CONTROLLER
G
R
W
WR
G
RWRWRWRWRWR
DX
OAT
LAT
ZT4
ZT3
ZT2
W
PWR. 24VAC
SHIELD
GROUND
24 VAC Transformer
(Field Supplied)
50 VAC req. for basic
4 damper system. Please
see Page 1, Electrical
Rating for details.
#16 AWG to
Grounded to Water Pipe
or Solid Electrical Ground
PWR
CHR06
RELAY
CHR06
R
Y
B
WG
SYSTEM CONTROLLER
Zone 2*
Zone 3*
Power
To
HVAC
System
FAN (G)
RV COOL (0)
RV HEAT (B)
72
68
HEAT 2 (W2)
OR
4-Zone Controller
COOL 2 (Y2)
HEAT 1 (W1)
COOL 1 (Y1)
UNIT 24 VAC (R)
CHR-06
2:45
Dx Coil
Sensor
(optional)
Outside Air
(optional)
Custom Cable
CALLOUT TO PHONECOMM BUSPOWER PHONE LINE
Home Access Module
(optional)
Sensor
Duct
Sensor
Remote Room
Sensors
* It is recommended that a 5 wire cable be used to install
Remote Room Sensors to allow
for future upgrade to Smart Sensors.
Fig. 16—Comfort Zone System Wiring Diagram
Zone 4*
Zone 1
Communication Bus
B Y G W RB Y G W RB Y G W R
Smart Sensor Power Pack
(optional)
Smart Sensor
(optional)
A94311
7
5 WIRE CONDUCTOR
(INTERFACE BOARD)
3 WIRE CONDUCTOR
(COMM BUS)
COMM BUS
FIELD WIRING
(FEED THRU)
I/O BOARD
Fig. 17—Wiring Four Zone Controller
GRN
RED
WHT
RED
YEL
BLU
GRN
WHT
GREEN
RED
WHITE
RED
YELLOW
BLUE
GREEN
WHITE
A93231
Changing the base temperatures will change the Comfort
Temperature Setpoints used in the system schedules. Always
set the Base Temperatures prior to programming the system
schedules.
Comfort Zone also uses a minimum temperature and a maximum
temperature for comfort setpoints. The minimum and maximum
temperatures are the same for all 4 zones.
The Maximum Temperature is only used for cooling. It is set by
selecting Rotary Switch Position S-2. The Maximum Temperature
setting is used when a temperature above the 14° span is selected.
If Cooling Base Temperature is set to 68°F and cooling setpoint is
82°F, any attempt to raise cooling setpoint will select Maximum
Temperature.
The Minimum Temperature is only used for heating. It is set by
selecting Rotary Switch Position S-3. The Minimum Temperature
setting is used when a temperature below the 14 ° span is selected.
If Heating Base Temperature is set to 54°F, any attempt to lower
heating setpoint below 54°F will select Minimum Temperature.
Both Maximum and Minimum Temperatures are intended for use
with schedules or setpoints which are extreme compared to normal
building temperatures.
Comfort Zone also has one additional set of temperature settings.
These are Vacation Setpoints. The Vacation Setpoints are heating
and cooling setpoints to be used in all 4 zones whenever 4 zone
controller rotary switch is turned to "Vacation." The Vacation
option is used to place entire building in setback during long
unoccupied periods without danger of freezing or extreme
heat/humidity.
SEQUENCE OF EVENTS FOR A NORMAL HEATING OR
COOLING CYCLE
Given Comfort Setpoints and space temperature for zones within
system, Comfort Zone will determine if active heating or cooling
is required. If so, Comfort Zone will perform the following:
1. Select a reference zone.
2. Make sure all zone dampers are fully open.
3. Energize HVAC equipment fan.
4. Energize heating or cooling equipment. The equipment may
be a compressor, furnace, strip heater, etc.
5. Set the zone damper positions based upon zone demand.
6. Energize additional stages of heating or cooling if demand
warrants.
7. Continue to adjust zone dampers as conditions within zones
change.
8. Turn off heating or cooling equipment when all zones are
within 0.5°F of desired comfort setpoint.
9. Open all zone dampers when equipment is turned off.
This is the basic Sequence of Operation for the Comfort Zone
system. The actual control of dampers, HVAC equipment, and
system fan will change with configuration of system. Depending
upon configuration, Comfort Zone can control heat pumps, furnaces, and dual fuel applications.
SELECTION OF A REFERENCE ZONE IN THE SYSTEM
The first step in any heating or cooling cycle requires Comfort
Zone to evaluate zones, determine if heating or cooling is needed,
and select a Reference Zone.
The Comfort Zone system actively looks at Comfort Setpoints and
space temperature in all zones. If any zone in system has a demand
of 1.5°F or more, then Comfort Zone will prepare to operate
heating or cooling equipment to reduce demand.
First, Comfort Zone will select a reference zone in the system. The
reference zone will be zone with greatest demand. The zone
damper serving reference zone will be forced fully open and will
remain fully open as long as that zone is used as reference.
As long as any zone in system has a demand greater than or equal
to 1.5°F, then Reference Zone will be selected by zone with
greatest demand. Once all zones have a demand less than 1.5
Reference Zone selection will not change until demand in that
zone is below 0.5°F. At this point Comfort Zone will re-select
Reference Zone and position that particular zone damper fully
open.
The objective of Reference Zone is to ensure that zone with
greatest demand is receiving as much conditioned air as system
will allow. It also gives Comfort Zone system a point of reference
in observing response of zones to equipment operation.
PRE-POSITIONING DAMPERS AND STARTING
THE SYSTEM FAN
In order to minimize noise and enhance system operation, Comfort
Zone maintains all zone dampers full open prior to starting system
fan or heating or cooling equipment. The intent is to provide
HVAC equipment with unrestricted duct work and reduce pressure
surges. Comfort Zone also fully opens dampers whenever a
heating or cooling cycle is completed and system fan is shutting
down. If Fan Switch on 4 zone controller is set to Auto, then all
zone dampers will remain fully open until next heating or cooling
cycle.
The other reason for opening dampers is to provide unrestricted
duct work to other equipment which is not directly controlled by
Comfort Zone. One example may be Heat Recovery Ventilator. If
Comfort Zone is not actively controlling HVAC system, then it
must not impose any control influences (i.e., closed zone dampers)
on system and prevent proper operation of other devices.
For Fan operation, switch settings on 4 zone controller and system
configuration can change actual operation.
If Auto Fan Off For Heating option (Rotary switch position
number T-9) is ON, then Comfort Zone will only energize fan for
cooling cycles. This option is intended for furnaces which will
control their own fan internally.
8
o
F,
If Fan Switch on 4 zone controller is set to ON instead of Auto,
then system fan will run continuously. Any time Comfort Zone is
operating fan, it will be in active control of system.
NOTE: If Auto Fan Off For Heating option (rotary switch
position T-9) is ON, and Fan Switch on the 4 zone controller is
ON, Comfort Zone will operate fan full time.
Operating fan continuously will place Comfort Zone in a FloatMode any time no active heating or cooling is taking place. During
Float Mode, Comfort Zone will position zone dampers based upon
demand in each zone. Comfort Zone will check air temperature in
duct work and allow air into zones if it will help zones reduce their
individual demands. For example, if temperature of air in duct
work is 65°F, cooling comfort setpoint for a zone is 72°F, and
space temperature is 73°F, then Comfort Zone will open damper
servicing that zone and allow cooler air into space.
Ventilation Mode is only in effect when temperature of supply air
is between 65°F and 80°F. Ventilation Mode establishes minimum
position of zone dampers and is intended to help air movement
throughout zones and reduce chance of having areas which are
stagnant or have high humidities with respect to rest of system.
The changes to dampers are detailed in the next section "Controlling the Zone Dampers."
CONTROLLING THE ZONE DAMPERS
The zone dampers have a total of 16 possible positions or
increments which are numbered 0 (zero) through 15. Position
number 0 is fully closed and position number 15 is fully open.
While damper servicing reference zone remains fully open, all
other zone dampers are positioned by selecting a position equal to
demand of space in tenths of a degree. (See Table 2.)
For example, a zone which has a 1.0°F demand will have damper
set to position number 10 while a zone which has a demand of
0.5°F will have damper set to position number 5. A demand of 0
(zero) will fully close zone damper. Any zone which has a demand
greater than 1.5°F will remain fully open.
Notice that positions are based upon tenths of a degree Fahrenheit.
If Comfort Zone has Celsius Temperature Display option (rotary
position T-2) turned on, the damper control is still based upon
Fahrenheit scale.
DEMAND °FDEMAND °C
00
1.50.83
The damper positions in table are also used during a Float Mode.
A zone with a demand of 0.5°F will be set to position number 5.
The actual control of zone dampers by Comfort Zone system can
be modified using 3 configurable options. These are Maximum
Damper Position, Minimum Damper Position, and Ventilation
Mode.
These options apply to all zone dampers simultaneously. Any
dampers servicing Zone 1 cannot be configured differently than
those servicing Zone 2. The options are as follows:
1. The Maximum Damper Position (rotary position number
S-4) sets maximum open damper position for all 4 zones. The
allowable range for this option is damper positions number 8
through number 15 (fully open). The factory default is 15. The
only time zone dampers will exceed this position is if system
fan is off or zone dampers are being calibrated.
2. The Minimum Damper Position (rotary position number
S-5) sets minimum open damper position for all 4 zones. The
allowable range for this option is damper positions number 0
through number 7. The factory default is number 0 (fully
closed). If Ventilation Mode (rotary position T-25) is turned
OFF, then minimum damper position will be an absolute
minimum regardless of operating mode. If Ventilation Mode
is turned ON, then minimum damper position will be minimum position during a Ventilation Mode only and dampers
will be allowed to fully close at any other time.
3. Ventilation Mode (rotary position T-25). If Ventilation Mode
is turned ON, then any time air inside supply air duct work is
between 65°F and 80°F, system will be in a "Ventilation
Mode". During a Ventilation Mode all zone dampers will have
a minimum position which is set by Minimum Damper
Position (rotary position S-5). The zone dampers are not
allowed to fully close as long as supply air temperature
remains within the 65°F-80°F range. If supply air temperature
falls outside the 65°F-80°F range, then zone dampers may
fully close.
NOTE: If Ventilation Mode option (rotary position T-25) is
turned ON, and Minimum Damper Position (rotary position S-5) is
set to position 0, there is no difference between Float Mode andVentilation Mode. In other words, Ventilation Mode option has
no effect on system.
OPERATING THE HEATING AND COOLING EQUIPMENT
Before any heating or cooling equipment is started, Comfort Zone
must first choose between heating or cooling. For most of the year
there is little question as to the need for heat or cooling. But for
portions of the year, particularly during mid-season, a building
may have simultaneous needs for both heating and cooling.
The first step in selecting heating or cooling is the determination of
a Reference Zone. If there is a single zone which has greatest
demand, then it will become the Reference Zone and Comfort
Zone will start equipment based upon needs of that zone. If 2 zones
have same "greatest demand" but in different modes (1 needs
heating and the other needs cooling), then Comfort Zone will
select mode which has greatest number of zones which require
same mode.
CONTROL STRATEGY FOR HEATING / COOLING STAGES
The Comfort Zone system will attempt to minimize use of
additional stages of heating or cooling equipment. In an ideal case,
building conditioning needs can be supplied by first stage cooling
or first stage heating alone.
For most heat pump applications, there may be only 2 or 3 stages
of heat depending upon type of emergency heater present. For a
heat pump, secondary heat source will generally be an electric strip
9
Table 3—Heating System Option Vs. Type of Heater Used
HEATER TYPE USED
IN SYSTEM
Single-Stage Heat PumpOnOff0
Two-Stage Heat PumpOnOn0
Heat Pump/Furnace Dual
Two-Stage Heat Pump,
* Refer to 2-speed heat pump Installation and Start-Up Instructions for details regarding 2-speed heat pump operation. It is recommended that heat pump control board
controls operation of this equipment and not Comfort Zone.
Fuel
Furnace Dual Fuel*
Furnace Heat OnlyOffOff0
Strip Heater OnlyOffOff0
HEAT PUMP
SYSTEM TOGGLE:
T-6
OnOff10 to 60
OnOn0°FOff
TWO STAGE
HEAT PUMP
TOGGLE: T-26
DUAL FUEL
SYSTEM SWITCH:
S-7
o
F (off)Off
o
F (off)Off
o
FOff
o
F (off)On or Off
o
F (off)Off
FAN ON
FOR COOLING ONLY
TOGGLE:
T-9
Table 4—Available Heating and Cooling Stages Vs. System Type
TYPE OF HVAC
EQUIPMENT USED
Cooling Only, any Heater TypeY1Y2W1W2----
Single-Stage Heat PumpY1--Y1W1W2--
Two-Stage Heat PumpY1Y2Y1Y2W1W2
For cooling applications, the second stage of an air conditioner is not necessarily more expensive to operate than first stage. But additional cooling can drive down the
efficiency of a 2-speed air conditioner and longer use of first stage alone tends to deliver better humidity control in moist climates. Again, because of these advantages,
Comfort Zone will attempt to minimize use of second stage cooling. This is not as great of a concern for a heating application, because the majority of small air
conditioning systems sold today (5 tons and below) are single-stage cooling only.
heater. The electric strip heat is much more expensive to operate
when comparing cost per unit of heat. Because auxiliary stages of
heating tend to be more expensive to operate, Comfort Zone
attempts to keep number of stages at a minimum.
CONFIGURATION OPTIONS FOR EQUIPMENT
OPERATION
Comfort Zone has several configurable options which allow it to
control different types of HVAC equipment and change the
manner in which the equipment is controlled. This first group must
be set given the type of HVAC equipment installed. These include:
1. Heat Pump Operation (Rotary Position T-6).
2. Two-Stage Heat Pump (Rotary Position T-26).
3. Dual Fuel trip temperature (Rotary Position S-7).
4. Auto Fan Off For Heat (Rotary Position T-9).
The second group modifies the way the HVAC equipment is
controlled. These include:
1. Comfort Trend Staging (Rotary Position T-8).
2. System Mode Reselect (Rotary Position T-22).
3. High/Low Temperature Limits Enabled (Rotary Position
T-10).
4. High Temperature Trip Limit (Rotary Position S-6).
The first options which must be set are based upon the type heater
or heaters used. These are shown in Table 3. The only option
which appears to impact cooling operation is Two-Stage Heat
Pump which implies the availability of 2 stages of cooling. In
reality there are no changes to cooling control scheme.
Comfort Zone assumes that there are always 2 stages of cooling
present. These are connected to the Comfort Zone Relay Pack on
the Y1 and Y2 contacts.
RELAY PACK TO HVAC EQUIPMENT CONNECTIONS
Given system configuration, Comfort Zone can determine number
of heating stages that it will actually control and which relay
outputs will be used to control each stage of heat. Comfort Zone
can control up to 4 stages of heat depending upon system
configuration.
For cooling only applications with any type of heater, Comfort
Zone will only control 2 stages of heat. If system uses a heat pump,
then Comfort Zone will control 3 stages of heat. The additional
stage is heat pump compressor contact. The auxiliary heat is still
2 stages. If system uses a 2 stage heat pump, then Comfort Zone
will control 4 stages of heat, 2 stages for heat pump and 2 stages
for auxiliary heat.
The Comfort Zone Relay Pack outputs are shown in Table 4. The
Y1 and Y2 contacts are used for compressor contacts only.
Comfort Zone operates heat pumps by energizing compressor
contacts and controlling reversing valve through Reversing Valve
(RV) relay output. The W1 and W2 contacts are always used for
heat sources. These are heating only units such as furnaces, strip
heaters, etc. The relay outputs for Comfort Zone 1.4 are shown in
Table 4.
Under no circumstances may the W1 and Y1 contacts on the
relay pack be jumpered together. This is a common practice
for many heat pump installations but will cause improper
operation of the Comfort Zone (1.4 or greater) system.
STARTING THE HVAC EQUIPMENT
Once Comfort Zone selects a mode, controller will use configu-
ration options to modify control of HVAC equipment. The
controller first selects number of stages of heating and cooling that
may be applied to building load. The "available" stages are
determined by Reference Zone temperature demand and are shown
in Table 5.
Using Table 5, if Reference Zone has a 2.3°F demand, then
Comfort Zone may use 2 stages of cooling or 2 stages of heating.
The HVAC equipment may not have 3 stages of heat or even 2
stages of cooling. The table is only used to determine what
equipment Comfort Zone is allowed to turn on at any given time
during a heating or cooling cycle. Actual operation of stages
depends on other variables as well.
Normally Comfort Zone will start equipment operation when it has
a demand of 1.5°F or greater. In some cases, Comfort Zone will be
facing a demand greater than 1.5°F when a mode is starting. This
can occur when user changes setpoints in a zone or if a schedule
change has reset the Comfort Setpoints.
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.