Carrier Infinity SYSTXCCITW01, YSTXCCITN01, Infinity SYSTXCCITN01 Installation Instructions Manual

Page 1
SYSTXCCITW01 & SYSTXCCITN01 Infinityr Touch Control
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
US Patents: Carrierr U.S. Pat No. 7,243,004, Carrierr U.S. Pat No. 7,775,452, pointSETt U.S. Pat No. 7,415,102
Page 2
Page 3
TABLE OF CONTENTS
PAGE
1.Safety Considerations 1.............................................
2.Introduction 1.....................................................
3.Quick Start 2......................................................
3.1. Set Time and Date 2............................................
3.2. Set Dealer Information 3........................................
4.Installation 4......................................................
4.1. Overview 4...................................................
4.2. Check Equipment 4............................................
4.3. Location 5....................................................
4.3.1. Wall Control 5...........................................
4.3.2. Remote Room Sensors 6...................................
4.3.2.1.Remote Room Sensor Averaging 6...........................
4.3.3. Smart Sensors (for zoning applications) 7......................
4.4. Wiring Considerations 7.........................................
4.4.1. Shielded Wire 10.........................................
4.4.2. Damper Control Module 11.................................
4.5. Mounting 11..................................................
4.5.1. Decorative Backplate 12...................................
4.6. Humidifier Connections 13......................................
Page 4
TABLE OF CONTENTS (cont.)
PAGE
4.6.1. Bypass Humidifier 13......................................
4.6.2. Fan Powered Humidifiers 13................................
5.Commissioning 14.................................................
5.1. Searching for Indoor Unit 14.....................................
5.2. Searching for Outdoor Unit 15....................................
5.3. Indoor Evaporator Selection 16...................................
5.4. Electric Heater Selection 16......................................
5.4.1. Hydronic Heat Application 17...............................
5.5. Searching SAM Module (If Applicable) 18..........................
5.6. Searching for Zones (If Applicable) 18.............................
5.7. Filter T ype Selection 19.........................................
5.8. Humidifier Installation 19........................................
5.9. Ultraviolet Lights Installation 19..................................
5.10.Equipment Summary 29........................................
5.11.Static Pressure Check 20........................................
5.12.Duct Assessment (zoning applications only) 20......................
6.Service Menu 22...................................................
6.1. Equipment Summary 22.........................................
6.2. Installation 23.................................................
6.3. Set up 24.....................................................
Page 5
TABLE OF CONTENTS (cont.)
PAGE
6.3.1. Thermostat 25............................................
6.3.1.1.Auto Mode set up 25......................................
6.3.1.2.Heat/Cool Deadband 26...................................
6.3.1.3.Offsets 26..............................................
6.3.1.4.Reset factory defaults 26...................................
6.3.1.5.Scheduling Enable 26.....................................
6.3.1.6.Smart Recovery Enable 27.................................
6.3.1.7.Temperature Units Display 27...............................
6.3.2. Fan Coil 27..............................................
6.3.2.1.Airflow 28..............................................
6.3.2.2.Altitude 28.............................................
6.3.2.3.Fan Coil Dehumidification 29...............................
6.3.2.4.Fan Coil G--Terminal 29...................................
6.3.3. Furnace 30..............................................
6.3.3.1.Furnace Airflow 30.......................................
6.3.3.2.AC/HP Air Flow 31.......................................
6.3.3.3.Furnace Staging 32.......................................
6.3.3.4.Furnace Airflow Limits (modulating furnace only) 32............
6.3.3.5.Furnace Off Delay 32.....................................
6.3.3.6.Altitude 33.............................................
Page 6
TABLE OF CONTENTS (cont.)
PAGE
6.3.3.7.Furnace Dehumidifier Drain 33.............................
6.3.3.8.Furnace G Terminal 33....................................
6.3.4. AC/Heat Pump 34........................................
6.3.4.1.Cooling Lockout 35......................................
6.3.4.2.Defrost Interval 35.......................................
6.3.4.3.Low Ambient Cooling 36..................................
6.3.4.4.Quiet Shift 36...........................................
6.3.4.5.AC/Heat Pump RPM Max 36...............................
6.3.4.6.Defrost Fan Delay 36.....................................
6.3.4.7.Brownout Disable 37.....................................
6.3.4.8.Energy Efficiency 37......................................
6.3.5. Heat Source Lockout 37....................................
6.3.6. Zoning (If Applicable) 38...................................
6.3.6.1.Zoning Disable 39........................................
6.3.6.2.Zone Offsets 39..........................................
6.3.6.3.Zone Airflow Limits 39....................................
6.3.6.4.Duct Assessment Time 40..................................
Page 7
TABLE OF CONTENTS (cont.)
PAGE
6.3.7. Accessories 40...........................................
6.3.7.1.Filter 41................................................
6.3.7.2.Humidifier 41...........................................
6.3.7.3.Ultraviolet Lights 42......................................
6.3.7.4.Ventilator 42............................................
6.3.8. Utility Curtailment 42......................................
6.3.9. Hydronic Airflow 43......................................
6.4. Check out 44.................................................
6.4.1. Electric Heat 44..........................................
6.4.2. Furnace 45..............................................
6.4.3. Hydronic 45.............................................
6.4.4. Air Conditioning 45.......................................
6.4.5. Heat Pump Heating 46.....................................
6.4.6. Heat Pump Cooling 47.....................................
6.4.7. Humidifier 47............................................
6.4.8. Ventilator 48.............................................
6.4.9. Zoning (If Applicable) 48...................................
6.4.9.1.Airflow Limits 48........................................
6.4.9.2.Damper/Sensor Check 48..................................
Page 8
TABLE OF CONTENTS (cont.)
PAGE
6.4.9.3.Zone Duct Assessment 49..................................
6.4.9.4.Sensor Type 49..........................................
6.5. Service Information 49..........................................
6.5.1. Fan Coil Status 50........................................
6.5.2. Furnace Status 50.........................................
6.5.3. AC Status 51.............................................
6.5.4. Heat Pump Status 51......................................
6.5.5. Zoning Status 52..........................................
6.5.6. Last 10 System Faults 52...................................
6.5.7. Run/Fault History 53......................................
6.5.8. Model/Serial Numbers 54...................................
6.5.9. Service Phone Number 54..................................
6.5.10. Energy Tracking Watt Meter 54..............................
6.6. Refrigerant Charging 55.........................................
6.6.1. Charging 55.............................................
6.6.2. Pump down 56...........................................
6.6.3. Evacuation 5 7............................................
6.7. Dealer Logo 57................................................
7.Wireless Setup 58..................................................
8.Appendix A -- Wiring Diagrams 65....................................
Page 9
1
1. Safety Considerations
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol
on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING ,andCAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury o r death. WARNING signifies hazards, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
2. Introduction
The Infinityr System consists of several intelligent communicating components which includes the Infinityr Touch Control (or User Interface), variable speed furnace or FE fan coil, and 2--stage AC or HP, which continually communicate with each other via a four--wire connection called the ABCD bus. Commands, operating
Page 10
2
conditions, and other data are passed continually between components over the ABCD bus. The result is a new level of comfort, versatility, and simplicity.
All Infinityr furnaces or fan coils are variable--speed and multi stage for maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Infinityr (communicating), or a standard single--stage 24VAC controlled outdoor unit may be used.
When using conventional single--stage outdoor units, the Infinity furnace or fan coil provides the 24 volt signals needed to control them. Also, the Infinityr Network Interface Module (P/N SYSTXCCNIM01) allows connection of a Carrier HRV or ERV without the need for separate wall control.
When using a Carrier HRV or ERV with a zoned system, the Infinityr Zone board allows connection of a Carrier HRV or ERV without the need for separate wall control.
All system components are controlled through the wall mounted Infinity Touch Control, which replaces the conventional thermostat and provides the homeowner with a single wall control for all features of the system.
3. Quick Start
3.1. Set Time and Date
From the main screen, touch MENU, on the bottom of the control. The TIME/DATE icon allows you to set the time and date for the Infinityr Touch
Control.
d To se t the HOUR, MINUTE, MONTH, DAY, or YEAR touch the feature
you wish to change.
d Use the Up (Y) and Down (B) buttons to make the appropriate changes.
d When you have completed all of the settings touch SA VE.
Page 11
3
d If you make a mistake you may touch CANCEL and begin again.
A12175
3.2. Set Dealer Information
From the main screen, touch MENU, on the bottom of the control. The SERVICE icon allows you to upload your contact information into the Infinity Touch Control.
A12176
S Format your contact information and logo (if applicable) using the PC/MAC
application, save it to a standard USB drive. See Section 6.7.
S Touch the SERVICE icon for about 10 seconds, then touch DEALER LOGO
UPLOAD.
S Place the USB drive into the USB port on the bottom of the Infinity Touch
Control and follow the on screen prompts.
Page 12
4
S More detailed information can be found on HVACPartners.com under the
Product tab> Thermostats & Controls> SYSTXCCITW01> Documents & Downloads> Marketing/Miscellaneous> Infinity Touch Control Dealer Logo Application -- Instructions.
4. Installation
4.1. Overview
This instruction covers installation of the Infinityr Touch Control and the Infinityr Wireless Access Point only. Physical installation instructions for the indoor and outdoor equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the Infinityr System are covered only in this installation instruction. It is the guide to connecting the system components and commissioning the system once all physical components are installed. Special screen prompts and start--up capabilities are provided in the Infinityr System to simplify and automate the initial commissioning of the system.
S Install the Infinity Touch Control according to this instruction. S Install indoor unit, outdoor unit, and accessories according to their instructions. S Wire complete system according to this instruction. S Setup, commission, and operate system according to this instruction to assure a
smooth and trouble free start--up.
4.2. Check Equipment
Inspect equipment. File a claim with shipping company prior to installation if shipment is damaged or incomplete.
Page 13
5
4.3. Location
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect power before routing control wiring.
!
WARNING
All wiring must comply with national, local, and state codes.
4.3.1. Wall Control
The Infinity Touch Control is the command center for the Infinity System. It should be located where it is easily accessible and visible to the adult homeowner or end user. For accurate temperature measurement, the following guidelines should be followed:
The Infinity Touch Control and Remote Room Sensors SHOULD be mounted:
S Approximately 5--ft (1.5 m) from the floor. S Close to or in a frequently used room, preferably on an inside partitioning wall. S On a section of wall without pipes or ductwork.
The Infinity Touch Control and Remote Room Sensors SHOULD NOT be mounted:
S Close to a window, on an outside wall, or next to a door leading to the outside. S Exposed to direct light or heat from a lamp, sun, fireplace, or other
temperature--radiating objects which could cause a false reading.
Page 14
6
S Close to or in direct airflow from supply registers. S In areas with poor air circulation, such as behind a door or in an alcove.
4.3.2. Remote Room Sensors
A Remote Room Sensor can be used with the Infinity Touch Control to take the place of the control’s internal temperature sensor. This allows the Infinity Touch Control to be mounted in areas with less than optimal airflow (such as near an exterior door, window or in a closet). The remote sensor can be wired to the terminal block connectors labeled S1 and S2 at the control’s backplate, or the ZS1 and ZS1C connection at the Damper Control Module. In either case, the Infinity Touch Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor.
4.3.2.1. Remote Room Sensor Averaging
Typically, one remote sensor is used but, multiple sensors may be used and averaged in some applications. Averaging requires a special series --parallel wiring method with a specific number of sensors. See figure below. It is also important to note the humidity sensor cannot be remotely located, so do not locate the Infinity Control in an area where humidity sensing may not be accurate.
Page 15
7
Sensor 1 Sensor 2
Sensor 3 Sensor 4
Damper Control
Module
ZS_
Damper Control
Module
ZS_C
A03233
4.3.3. Smart Sensors (for zoning applications)
Any zone may use a Smart Sensor. It provides a temperature display and buttons to adjust the desired temperature in that zone only. It also displays outdoor temperature and indoor humidity sensed at the control. Only one Smart Sensor may be used per zone. They cannot be averaged like Remote Room Sensors. If a Smart Sensor is used in a zone, a Remote Room Sensor may also be used in the same zone. The Remote Room Sensor has priority over the Smart Sensor. The Smart Sensor will display the Remote Room Sensor temperature.
NOTE: Smart Sensors must be addressed to identify which zone it will control. See Smart Sensor Installation Instructions for details.
4.4. Wiring Considerations
Ordinary thermostat wire is recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or larger.
Page 16
8
NOTE: ABCD bus wiring only requires a four--wire connection; however, it is
good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during installation.
Each communicating device in the Infinityr Zone System has a four --pin connector labeled ABCD. It is recommended that the following color code be used when wiring each device:
A — Green = Data A B — Yellow = Data B C — White = 24VAC (Com) D — Red = 24VAC (Hot)
ABCD
A03193
It is not mandatory that the above color code be used, but each ABCD connector in the system MUST be wired consistently.
NOTE: Some outdoor units provide their own low--voltage power source and do not require the “C” (24VAC common) and “D” (24VAC power) connections. See the outdoor unit installation instructions for more information.
Page 17
9
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
WARNING
S Turn off all power to equipment. S If an existing Infinityr Control or other control is being replaced:
d Remove existing control from wall.
d Disconnect wires from existing control.
d Discard or recycle old control.
S NOTE: Mercury is a hazardous waste, if existing control contains any
mercury, it MUST be disposed of properly. The Infinity Touch Control does not contain mercury.
S Select Infinity Control mounting plastic (backplate and decorative backplate if
desired).
S Route wires through large hole in mounting plastic. Level rear plastic against
wall (for aesthetic value only; Infinity Touch Control need not be level to operate properly) and mark wall through two mounting holes.
S Drill two 3/16--in (4.8 mm) mounting holes in wall where marked. S Secure mounting plastic to wall using two screws and anchors provided.
Page 18
10
S Adjust length and routing of each wire to reach each wire entry on the
connector backplate. Strip 1/4--in (6.4 mm) of insulation from each wire.
S Match and connect thermostat wires to proper terminals on control backplate.
d See wiring diagrams in Appendix A.
S Push any excess wire into the wall. Seal hole in wall to prevent any air leaks.
Leaks can affect operation.
S Attach Infinity Control to the mounting plastic by lining up the plastic guides
on the back of the control with the opening on the mounting plastic and push on.
S Perform installation of all other system equipment (i.e. dampers, humidifier,
ventilator, UV lights, etc.).
S Turn on power to equipment.
4.4.1. Shielded Wire
If the thermostat wiring will be located near or in parallel with high voltage wiring, radio, TV or Ethernet wiring, then four conductor, twisted--pair, shielded cable can be used to reduce or eliminate potential interference. The shield wire should be connected to the C terminal, or ground, at the indoor unit. The shield wire should NOT be connected to any terminal at the user interface. Connecting the shield to ground at both ends can cause current loops in the shield, reducing shield effectiveness.
Connect one pair of the two--pair (minimum) cable to the A and B communication terminals, and another pair to the C and D terminals at both ends of the cable. The shield wire should ONLY be connected at the indoor equipment ground or C terminal. Note that some outdoor units only require the A and B connections. See the outdoor unit installation instructions for more information.
Page 19
11
4.4.2. Damper Control Module (zoning systems only)
All wiring is run back to the Damper Control Module. Select a location near the furnace or fan coil where wiring from the control, each Remote Room Sensor or Smart Sensor, each damper actuator, and the equipment itself can come together easily. The Damper Control Module is approved for indoor use only and should never be installed with any of its components exposed to the elements. The Damper Control Module (and zone dampers) may be installed in any area where the temperature remains between --4_F to 158_F(--20_Cto70_C), and there is no condensation. The cover must be installed to prevent damage from o ther sources. Do not locate where it will be accessible to children. It may be mounted in either vertical or horizontal position. Remember that wiring access is likely the most important consideration.
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
To prevent possible damage to the Damper Control Module, DO NOT mount on plenum, ductwork, or flush against furnace or fan coil.
CAUTION
!
4.5. Mounting
First become familiar with all plastic assembly pieces shown on the following page. The Infinity Touch Control will snap together with the backplate. A backplate is supplied. Attach backplate using only a small hole in the wall allowing a four wire connection to pass through. Mount the assembly to the backplate.
Page 20
12
A12214
A12215
NOTE: Once Infinity Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing.
4.5.1. Decorative Backplate
Sold separately, a thin decorative backplate is available to hide any marks/screw holes left from the previous thermostat. This decorative backplate (or beauty ring) is used by snapping it onto the back of the mounting plate before securing the plate to the wall.
Page 21
13
A12213
NOTE: Once the Infinity Touch Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing.
4.6. Humidifier Connections
A 24VAC bypass or fan powered humidifier may be installed.
NOTE: Do NOT use a traditional humidistat to control humidifier operation. If a humidifier is installed, let the Infinity Touch Control operate humidifier.
4.6.1. Bypass Humidifier
A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24VAC COM terminals. The Infinity Control Touch will automatically energize the HUM output during a call for humidification.
4.6.2. Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in order to energize upon a switch or contact closure. For this application, a 24VAC N.O. Isolation Relay (DPST) MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer. Applying 24VAC isolation relay coil to furnace or fan coil HUM and COM terminals will allow the Infinity Touch Control to
Page 22
14
automatically energize the HUM output during a call for humidification. The N.O. relay contacts will be used to energize the humidifier. See fan powered humidifier installation instructions for more details.
5. Commissioning
This section addresses initial power up (or commissioning) of a new Infinityr Touch Control. The control will communicate and identify all components in the Infinityr System. The following is a typical example for a communicating variable-- speed furnace / fan coil with a 2--stage air --conditioner / heat pump (including HYBRIDHEATr dual fuel system).
5.1. Searching for Indoor Unit
The Infinity Touch Control will light up and begin the commissioning process by displaying “Searching for indoor unit”. This includes Infinityr small packaged products (SPP), with UI Version 8.0 software or later.
A12177
NOTE: If the Infinity--compatible indoor equipment (furnace or fan coil) cannot be found, the control will display “Indoor unit not found”. This MUST be corrected before the initial power up sequence can continue. Proceed to the next section, Searching for outdoor unit. If it is not corrected, the Infinity Touch Control will go into its DEMO operating mode.
Page 23
15
A12178
5.2. Searching for Outdoor Unit
The Infinity Touch Control will then proceed to communicate with the outdoor unit by displaying “Searching for outdoor unit”. This includes Infinityr small packaged products (SPP), with UI Version 8.0 software or later.
NOTE: If the outdoor unit cannot be found, the control will display “Outdoor unit not found”.
S Select the appropriate unit installed; then, touch NEXT.
d AC1Stage – 1-- stage air conditioner
d *AC2Stage – 2 --stage air conditioner
d *HP1Stage – 1 --stage heat pump
d *HP2Stage – 2 --stage heat pump
d None – No outdoor unit installed
NOTE: For small p ackaged products (SPP), the selection screen is not needed and will not appear.
S The installer will first be instructed to select the appropriate size of the outdoor
unit; then, touch SELECT.
*Network Interference Module (NIM) may be required for these selections to be displayed.
Page 24
16
A13118
5.3. Indoor Evaporator Selection
If a furnace is installed with a variable capacity heat pump, a screen will appear to select the installed indoor evaporator coil. This selection is used to adequately calculate the refrigerant charge required while in the heat pump charging screens under the Heat Pump Checkout menu (See page 44). Select “other” for non --Carrier evaporators.
5.4. Electric Heater Selection
If the indoor equipment is a fan coil, the control will display “Searching for heater” until one is found. If the electric heater is not self--identifying, the select heater screen will appear. Touch the appropriate heater size; then, touch SELECT.
Page 25
17
A13119
5.4.1. Hydronic Heat Application
The Infinity Touch Control supports 2 types of Hydronic Heat applications:
1. Hot water coil in combination with an FE fan coil and heat pump, or hot water coil as sole heat source with an FE fan coil.
2. Non--zoned FE fan coil combined with radiant hot water heat.
In either application, a Hydronic Heat kit should be installed in place of an electric heater. See FE fan coil Product Data for accessory part number. The system will self--identify that hydronic heat has been installed during electric heater selection. The system will treat the hot water coil as either auxiliary heat in a heat pump application, or the sole heat source. Setup options for Hydronic Heat applications are described in the setup section of this instruction.
Page 26
18
A13117
5.5. Searching for SAM Module (If Applicable)
“Searching for SAM Module” will appear on the screen to determine if a System Access Module, used for home automation only, is connected to the system.
NOTE: For more information regarding the SAM Module, reference the latest version of the application specification entitled “Carrier Communicating HVAC System” (Version 2 or later), available on HVACpartners.com, or the System Access Module Installation Instructions.
5.6. Searching for Zones (If Applicable)
“Zoning -- Searching” will appear on the screen to determine if any zones are present. The screen will show Zone 1, Zone 2, etc. and indicate all zones having either a Remote Room Sensor, or smart sensors associated with them. If the system contains smart sensors, they must be assigned a zone number before continuing. See the Smart Sensor Installation Instructions on how to assign Smart Sensors to their respective zones. After each zone has been identified, touch NEXT.
Page 27
19
A12185
5.7. Filter Type Selection
The installer will next be prompted to select the air filter type installed with the Infinity System. After the selection is made, touch NEXT.
S Air Filter: 1--in. to 4 --in. media filter S EAC: high voltage electronic air cleaner S Air Purifier: Infinityr or Performancet Air Purifier
5.8. Humidifier Installation
Next, the installer will be prompted to select whether a humidifier is installed in the system. Select YES or NO, then touch NEXT.
5.9. Ultraviolet Lights Installation
Next, the installer will be prompted to select whether ultraviolet lights are installed in the system. Select YES or NO, then touch NEXT.
5.10. Equipment Summary
The equipment summary screen will appear after accessories have been selected. This screen will give a summary of all equipment automatically found or manually
Page 28
20
selected. If an incorrect selection was made, touch RE--INSTALL to restart the installation process.
Example: SPP Equipment Summary Screen
A13120
5.11. Static Pressure Check
The static pressure check screen will appear next. The system will perform a static pressure check. This process will take about 1--1/2 minutes to complete. When completed, a screen will appear displaying the static pressure (in inches) across the equipment at the expected highest delivered airflow. If the blower RPM is greater than 1200, then a warning will appear, but equipment operation and the TrueSenset dirty filter detection operation will not be affected. When the static pressure check is complete, touch NEXT.
NOTE: The static pressure check occurs only at initial installation, or when INSTALL isrunintheINSTALL/SERVICE menu.
5.12. Duct Assessment (zoning applications only)
The duct assessment screen will be displayed n ext for zoning applications. Touch NEXT to start Duct Assessment. Duct Assessment will measure the relative size of the ductwork, up to and through the dampers. These measurements are u sed to control the correct amount of airflow in the zoned system. Status messages will appear on the screen to indicate what the system is doing. The process will take
Page 29
21
approximately one minute per zone. The duct assessment will override a call for heat or cool.
A duct assessment will automatically occur each day at a user selectable time. The factory default time is 1:00 p.m. but, may be changed by entering the Zoning Setup menu (see pages 36 -- 37). If there is an active call for heating or cooling, the system will wait until the call is satisfied before it performs the duct assessment. The system will first open all zones and drive the blower to 175 CFM/ton of cooling (or the minimum indoor unit’s airflow, whichever is greater). It will then take a static pressure measurement. The system will then close all zones and open one zone at a time, taking a static pressure measurement for each zone.
The system will then close all zones and take a pressure measurement, getting a value for the duct leakage up to and through the dampers. With these static pressure measurements, the system will calculate the relative size of each zone as well as the percent leakage through the dampers At the end of the process, the display will show the relative size of each zone duct.
If the Infinity Touch Control detects an error (damper not moving or damper wired backwards), it will perform the duct assessment again. If it still detects a damper problem, it will default the measurements into equal sizes, with 10% leakage, and display the zone number for the suspected zone damper.
After the duct assessment is complete, touch NEXT.
A12186
Page 30
22
6. Service Menu
The Service menus contain a set of vital information. This information enables the installer or service person to view a summary of what has been installed, etc. This information is not covered in the Owner’s Manual.
To enter service menus, touch menu, then touch and hold the SERVICE icon for at least ten seconds. The following screens are available in installation and service. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12145
6.1. Equipment Summary
Touch EQUIPMENT SUMMARY to show indoor unit type and model number, outdoor unit type (and model number if a 2--stage unit), filter type, any accessories that are installed, and the number of zones in the system. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Page 31
23
Example: SPP Equipment Summary Screen
A13121
6.2. Installation
Touch INSTALLATION to perform the start--up process in order to learn all equipment in system. Press right side button to initiate the process. Touch NEXT to begin the process.
Touch Duct Assessment to perform a duct assessment. This can be done if duct modifications have been made since installation of the UI. Duct assessment can be performed without performing a full system install.
A12146
Page 32
24
NOTE: For Small Packaged Products (SPP), please use the following instructions
for Set --up (Section 6.3), Checkout (Section 6.4), and Service (Section 6.5):
--For PAC AC Indoor and OAC HP Indoor, follow Fan Coil instructions.
--For Gas PAC Indoor and Gas PHP Indoor, follow Furnace instructions.
--For all PAC Outdoor, follow AC/Heat Pump instructions.
6.3. Set up
A13130
NOTE: Depending upon the equipment installed, the following options will be displayed.
S Indoor:
d Furnace
d Fan coil
d PAC AC Indoor
d PAC HP Indoor
d GAS PAC Indoor
d GAS PHP Indoor
Page 33
25
S Outdoor:
d AC/Heat pump
d PAC AC outdoor
d PAC HP outdoor
d GAS PAC outdoor
d GAS PHP outdoor
Once the equipment has been selected, the appropriate menus will be displayed.
6.3.1. Thermostat
First touch SETUP, then touch THERMOSTAT to set up the parameters for the Infinityr Touch Control.
A12187
6.3.1.1. Auto Mode set up
Once the auto changeover option has been selected, touch SAVE.
S Enable or Disable: Choose to enable or disable auto changeover mode
d Default = Enable
S Auto changeover time: Adjustable from 5 to 120 minutes
d Default = 30 minutes
Page 34
26
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired temperatures. This can allow one setting to “push” the other to maintain this difference. When the correct deadband is set, touch SAVE.
S Deadband: Adjustable from 0 to 6_F(0to2_C)
d Default = 2_F
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and humidity sensors. These offsets are added to the actual temperature/humidity values. When the correct offsets are made, touch SAVE.
S Outdoor temperature: Adjustable from --5 to 5_F(--3to3_C)
d Default = 0_F
S Humidity: Adjustable from --10 – 10%
d Default = 0%
6.3.1.4. Reset fac tory defaults
This option allows the installer to reset certain factory parameters. After the selections are made, touch SAVE.
S Program Schedule: Reset back to pre --programmed time and temperature. S User Settings: Reset user settings back to pre--programmed values. S Install Settings: Reset installation settings back to pre --programmed values. S Last 10 Faults: Reset the last 10 system faults under the Service menu.
6.3.1.5. Scheduling Enable
This option lets the installer allow programming features. After the selection is made, touch SAVE.
S Scheduling: On or Off
Page 35
27
d Default = On
6.3.1.6. Smart Rec overy Enable
Applies to programmable operation only. Will start recovery 90 minutes prior to schedule change in both heating and cooling mode. After the selection is made, touch SAVE.
S Smart Recovery: On or Off
d Default = On
6.3.1.7. Temperature Units Display
This option allows the installer to choose between Fahrenheit and Celsius display. After the selection is made, touch SAVE.
S Display Option: Selectable between _Fand_C
d Default = _F
6.3.2. Fan Coil
First touch SETUP, then touch FA N C O IL to set up the parameters for the fan coil unit.
A12188
Page 36
28
6.3.2.1. Airflow
This option allows the installer to select the appropriate air flow based on the needs of the installation. The QUIET airflow means the minimum cooling airflow that the system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note that duct sweating in high humidity environments could become an issue at low airflows. The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings. This selection enables the full dehumidify and comfort capabilities of the system. The EFF325 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2--stage outdoor unit is used. The EFF350 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 350 CFM/ton, but will vary if a 2 --stage outdoor unit is used. The MAX airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is performed.
The dehumidify airflow, when set to NORMAL,isallowedtoadjusttoaminimum to satisfy the dehumidification call. When set to HIGH, the minimum airflow during the dehumidify mode is increased to reduce duct and register sweating. Also the airflow increases minimum airflow during normal cooling operation to help reduce duct sweating.
After the selections are made, touch SAVE.
S Cooling Airflow: Quiet, Comfort, EFF325, EFF350, or Max
d Default = Comfort
S Dehumidify Airflow: Normal or High
d Default = Normal
6.3.2.2. Altitude
S Static Pressure selection: 0 to 10,000 feet. This is used to correct the static
pressure readings the system performs.
Page 37
29
6.3.2.3. Fan Coil Dehumidification
The Dehum Drain Time option turns off the continuous fan at the end of cooling for five minutes in order to drain the indoor coil of water. The fan will only be turned off if a dehumidify d emand existed at the start of or during the cooling cycle.
The Electric Reheat option enables the electric heat to be used while cool--to --dehumidify is running. This will allow the cool--to--dehumidify function to run longer, greatly improving humidity control in cooling mode. Accumulated electrical energy used while reheating (in kilowatt--hours) is shown on the Fan Coil Run Hours screen and can be reset there. This option is only available with fan coil systems.
After the selections are made, touch SAVE.
S Dehum Dra in Time: Adjustable from 5 to 60 minutes or OFF
d Default = 15 minutes
S Electric Reheat: Ye s o r N o
d Default = No
6.3.2.4. Fan Coil G--Terminal
This setup option selects desired operation when the R-- G circuit changes state on the fan coil control board depending on setup.
Under the function option, FA N turns on fan to selected fan speed when G terminal is energized. SHUTDOWN shuts off fan and equipment when initiated. After the selections are made, touch SAVE.
S Function: Disabled, Fan or Shutdown
d Default = Disabled
S Fan Speed: Low, Med, or High
d Default = Low
S Shutdown:
Page 38
30
d Normally Open
d Normally Closed
6.3.3. Furnace
First touch SETUP, then touch FURNACE to set up the parameters for the furnace unit.
A12189
6.3.3.1. Furnace Airflow
Selects the airflow of the furnace when heating. EFFICIENCY is the airflow used to meet specified ratings, COMFORT is a decreased airflow used to increase the output air temperature and provide increased comfort.
For the Low heat rise option, set to ON if the system contains a bypass humidifier. The ON setting will increase the furnace low heat airflow.
After the selections are made, touch SAVE.
S Furnace Air Flow: Comfort or Efficiency
d Default = Comfort
S Low Heat Rise: On or Off
d Default = Off
Page 39
31
6.3.3.2. AC/HP Air Flow
This option elects the airflow of the furnace when cooling, heat pump heating, and dehumidification.
The QUIET airflow means the minimum cooling airflow that the system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note that duct sweating in high humidity environments could become an issue at low airflows. The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings. This selection enables the full dehumidify and comfort capabilities of the system. The EFF325 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2--stage outdoor unit is used. The EFF350 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 350 CFM/ton, but will vary if a 2--stage outdoor unit is used. The MAX airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is performed.
The dehumidify airflow, when set to NORMAL, the airflow is allowed to adjust to a minimum to satisfy the dehumidification call. When set to HIGH, the minimum airflow during the dehumidify mode is increased to reduce duct and register sweating. Also the airflow increases minimum airflow during normal cooling operation to help reduce duct sweating.
After the selections are made, touch SAVE.
S Cool: Quiet, Comfort, EFF325, EFF350, or Max
d Default = Comfort
S HP Heat: Comfort or EFF350
d Default = Comfort
S Dehumidify: Normal or High
d Default = Normal
Page 40
32
6.3.3.3. Furnace Staging
This option controls the staging of the furnace and selects the minimum amount of time low stage must operate before high stage is activated. SYSTEM setting will allow the Infinityr Zone Control to determine furnace staging. LOW will only run the low stage of furnace heat. LOW--MED will run the low and medium stages (2 stages of heat). MED will only run the medium stage of heat. MED-- HIGH will run the medium and high stages (2 stages of heat). HIGH will only run the high stage of furnace heat.
NOTE: Two--stage furnace has LOW and HIGH selections only.
S Stages: System, Low, Low-- Med, Med, Med--High, or High
d Default = System
6.3.3.4. Furnace Airflow Limits (modulating furnace only)
The following settings allow the installer to restrict the furnace within certain minimum and maximum airflows. These airflows are converted to capacities. The Min and Max limits are determined by the equipment size. These settings are not the same as the zoning airflow limits.
S Min. modulating limits: Minimum CFM to run a modulating furnace. This will
increase the minimum operating capacity of the furnace.
d Default value is the furnace air flow for the lowest heat capacity.
S Max. modulating limits: Maximum CFM to run a modulating furnace. This
will increase the maximum operating capacity of the furnace.
d Default value is the furnace air flow for the highest heat capacity
6.3.3.5. Furnace Off Delay
This option denotes the amount of time the blower will continue to run after heating has shut off. After the selection is made, touch SAVE.
S Furnace Off Delay: 90, 120, 150 or 180 seconds
Page 41
33
d Default = 120 seconds
6.3.3.6. Altitude
For gas de --rating, this setting will adjust the furnace’s airflow to compensate for altitude. Altitude adjustment is not available with older furnaces. Please see furnace instructions for further details. After the selection is made, touch SAVE.
S Altitude: 0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000,
US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 – 9000, and US > 9000.
d Default = US 2001 --3000
S Static Pressure selection: 0 to 10,000 feet. This v alue is used to correct the
static pressure readings the system performs.
6.3.3.7. Furnace Dehumidifier Drain
This option selects the time the continuous fan turns off at the end of cooling in order to drain the indoor coil of water. The fan will only be turned off if a dehumidify demand existed at the start of or during the cooling cycle.
S Dehumidify Drain Time: Adjustable from 5 to 60 minutes
d Default = 15 minutes
6.3.3.8. Furnace G Terminal
This setup option selects desired operation when the R-- G circuit changes state on the furnace control board depending on setup.
Under the function option, FA N turns on fan to selected fan speed when G terminal is energized. SHUTDOWN shuts off fan and equipment when initiated.
After the selections are made, touch SAVE.
S Function: Disabled, Fan or Shutdown
d Default = Disabled
Page 42
34
S Fan Speed:Low,Med,orHigh
d Default = Low
S Shutdown:
d Normally Open
d Normally Closed\
d The shutdown function may not be immediate. Blower off delays, etc., will
still be used. The shutdown is not intended for commercial applications. If immediate shutdown is required, provision must be made to remove power to indoor unit.
6.3.4. AC/Heat Pump
First touch SETUP, then touch AC/HEAT PUMP to set up the parameters for the AC/Heat Pump unit.
Page 43
35
A12190
6.3.4.1. Cooling Lockout
Outside temperature below which cooling will not be provided. After the selection is made, touch SAVE.
S Cooling Lockout Temp: None, 45, 50 or 55 (_F)
d Default = None
6.3.4.2. Defrost Interval
Time interval at which defrost cycles can occur on a heat pump. AUTO means the defrost interval is optimized by the outdoor control. After the selection is made, touch SAVE.
S Set Defrost Interval: 30, 60, 90, 120 minutes or AUTO
Page 44
36
d Default = 30 minutes
6.3.4.3. Low Ambient Cooling
Selecting YES will enable the low ambient cooling operation in the outdoor unit. This setting is only available with communicating outdoor units and with Cooling Lockout set to NONE. Low ambient kits are not needed with communicating outdoor units. After the selection is made, touch SAVE.
S Low Ambient Cooling: Yes or No
d Default = No
6.3.4.4. Quiet Shift
This option turns on Quiet Shift function in 1--stage or 2 --stage communicating heat pumps. After the selection is made, touch SAVE.
NOTE: This option is not available with variable speed heat pumps.
S Quiet Shift:OnorOff
d Default = Off
6.3.4.5. AC/Heat Pump RPM Max
Used with variable capacity heat pumps, this option clamps the operating speed
of the heat pump to this maximum. Used to reduce operating noise while in high heating capacity. Reducing this value will reduce the heating capacity of the heat pump. After the selection is made, touch SAVE.
S AC Heat Pump Max RPM: Adjustable from 4500 – 7000
d Default = 4500 RPM
6.3.4.6. Defrost Fan Delay
Turns on the outdoor unit fan at the end of a defrost cycle for approximately 12 seconds. This helps to reduce any nuisance refrigerant noise caused by the
Page 45
37
switching reversing valve. This setup is only available on communicating heat pumps. After the selection is made, touch SAVE.
S Defrost Fan Delay: Ye s or No
d Default = No
6.3.4.7. Brownout Disable
This option turns off the high voltage brownout detection function in the outdoor unit control. After the selection is made, touch SA VE.
S Brownout Disable: On or Off
d Default = Off
6.3.4.8. Energy Efficiency
This option is used to input the published ratings of the installed air conditioner or heat pump as part of the energy tracking calculation. After the ratings are entered, touch SAVE.
6.3.5. Heat Source Lockout
First touch SETUP, then touch HEAT SOURCE LOCKOUTS to set up the parameters for the AC/Heat Pump unit.
For hydronic heat applications, this option allows the installer to set the lockout temperatures below the which only the hydronic coil will operate, and the lockout temperature above which the hydronic coil will not operate. After the selections are made, touch SAVE.
Page 46
38
A12149
S HP Lockout: Adjustable from 5 to 55_F(--15to13_C) or None
d Default = None
S Furnace, Electric Heat or Hydronic Lockout: Adjustable from 5 to 55_F
(--15to13_C) or None
d Default = None
S Defrost with Furnace, Electric Heat or Hydronic: Yes o r N o
d Default = Yes
6.3.6. Zoning (If Applicable)
First touch SETUP, then touch ZONING to set up the parameters for the zoning system (if applicable).
Page 47
39
A12191
6.3.6.1. Zoning Disable
This option allows the installer to enable or disable zoning. After the selection is made, touch SAVE.
S Disable Zoning: Yes o r N o
d Default = No
6.3.6.2. Zone Offsets
This option allows actual temperature offset for each zone, allowing calibration (or deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to change the zone. After the selection is made, touch SAVE.
S Temperature Offset: Adjustable between --5 to 5_F(--3to3_C)
d Default = 0_F
6.3.6.3. Zone Airf low Limits
Since a bypass damper is prohibited in this system, this setting is used to select the maximum allowable noise/airflow relationship into each zone based on air noise and comfort requirements. LOW means 100% of maximum assessed airflow; MED--LOW means 138% of maximum assessed airflow; MEDIUM means 176% of m a ximum assessed a irflow; MED--HIGH means 214% of maximum assessed
Page 48
40
airflow; HIGH means 250% of maximum assessed airflow; and NO LIMIT means the equipment does not stage down.
CFM associated for each limit is shown on the screen. Compare this value with the equipment’s low stage CFM value to ensure that equipment will run for each zone. Assessed airflow is determined as de scribed in DUCT ASSESSMENT.
After the selections are made, touch SAVE.
S Touch the zone name that you wish to change S Select the zone to adjust airflow: Low, Med--Low, Medium, Med--High, High,
or No Limit
d Default = High
6.3.6.4. Duct Assessment Time
This option allows the installer to select the time in which the duct assessment will be performed. After the selection is made, touch SAVE.
S Duct Assessment Time: Selectable between 12 AM and 11PM
d Default = 1 PM
6.3.7. Accessories
First touch SETUP, then touch ACCESSORIES to set up the parame te rs for the accessories installed with the system.
Page 49
41
A12192
6.3.7.1. Filter
With this option, the installer has the option of selecting pressure monitoring, the type of filter installed, and the time interval for cleaning. After the selections are made, touch SAVE.
S Pressure Monitoring (not available with Electric Air Cleaner): Enable or
Disable
d Default = Enable
S Clean Interval: Selectable from 1 to 18 months
d Default = 3 months
S Filter Type: Air Filter, Electric Air Cleaner or Air Purifier
d Filter type is selected during installation; otherwise default = air filter
6.3.7.2. Humidifier
With this option, the installer has the option of selecting whether a humidifier is installed, to humidify with the fan in low speed, and the time interval for changing the humidifier pad. After the selections are made, touch SA VE.
S Humidifier Installed: Yes or No
d Humidifier selection made during installation; otherwise default = no
Page 50
42
S Change Pad: Selectable from 1 to 24 months
d Default = 12 months
S Humidify with Fan: Ye s o r N o
d Default = No
6.3.7.3. Ultraviolet Lights
With this option, the installer has the option of selecting whether ultraviolet lights are installed, and the time interval for changing the ultraviolet lights. After the selections are made, touch SAVE.
S UV Lights Installed: Yes or No
d UV Lights selection made during installation; otherwise default = no
S Change Interval: Selectable from 1 to 48 months
d Default = 12 months
6.3.7.4. Ventilator
When a ventilator is installed, the installer has the option of selecting the time interval for cleaning the ventilator. After the selections are made, touch SAVE.
S Clean Interval: Selectable from 60, 90, 120, 150 or 180 days
d Default = 90 days
6.3.8. Utility Curtailment
Utility Saver is used to force the equipment to a lower stage (low or off) when activated by the utility company, typically during peak load times. This setup is available only if the equipment has a utility saver input (refer to outdoor equipment Installation Instructions). This setup controls the response of the equipment when the utility saver input is active. DI SABLED means that the curtailment function is not active. TURN OFF means the outdoor unit is to be turned off when the curtailment function is active. LOW STAGE means the outdoor unit will run in
Page 51
43
lows stage when the curtailment function is active. After the selections are made, touch SAVE.
A12193
S Cooling: Disabled, Low Stage or Turn off
d Default = Disabled
S Heat Pump: Disabled, Low Stage or Turn off
d Default = Disabled
6.3.9. Hydronic Airflow
This option allows the installer to select the airflow for the fan coil when paired with a hydronic coil. After the selections are made, touch SAVE.
A12194
Page 52
44
S Airflow: Selectable between Off to Max in 50 CFM increments
d Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)
d Default = Off
S Blower On Delay: Selectable from 0 to 240 seconds
d Default = 30 seconds
S Blower Off Delay: Selectable from 0 to 240 seconds
d Default = 0 seconds
6.4. Check out
Touch CHECKOUT to view the equipment installed in the system. Perform checkout test to make sure each piece of equipment is operating p roperly.
A13122
6.4.1. Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the heaters to be exercised. With self--identifying electric h eaters, three stages of electric heat are available to be exercised in any combination. Non--identifying heaters will only provide one stage of heat. After the selections are made, touch START.
S Low Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
Page 53
45
S Medium Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Hea t: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.2. Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time and high heat run time are selected. The furnace will execute its ignition start--up sequence. This sequence will be displayed on the screen. After the gas valve and blower motor turn on, the screen will show the current operating status of the furnace. After the selections are made, touch ST ART.
S Low Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Hea t: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.3. Hydronic
This option allows the hydronic heat relay to be exercised. First, it will energize the relay and turns on the blower. This sequence will be displayed on the screen. After the selections are made, touch ST ART.
S Hydronic heater check: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.4. Air Conditioning
This option allows the air conditioner to be exercised. With a 2--stage AC unit, a low cool and a high cool run time are independently selectable to exercise. The
Page 54
46
display will change to show the AC operating status. After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings. To view airflows for normal air conditioning cooling mode, exit the CHECKOUT screen and apply a heating demand to the system.
S Low Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.5. Heat Pump Heating
The heat pump heating mode can be exercised with this menu option. With a 2--stage heat pump, a Low Heat and a High Heat Run Time are independently selectable to exercise.
For variable speed heat pumps, you can select the speed at which the heat pump will exercise.
After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings. To view airflows for normal air conditioning cooling mode, exit the CHECKOUT screen and apply a heating demand to the system.
S Low Heat Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Heat Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S Speed (variable speed heat pump only): Selectable from lowest available to
Page 55
47
100%
d Default = lowest available as specified by variable speed heat pump
S Defrost: Ye s o r N o
d Default = No
6.4.6. Heat Pump Cooling
The heat pump cooling mode can be exercised with this menu option. With a 2--stage heat pump, a Low Cool Run Time and a High Cool Run Time are independently selectable to exercise.
For variable speed heat pumps, you can select the speed at which the heat pump will exercise.
After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings. To view airflows for normal air conditioning cooling mode, exit the CHECKOUT screen and apply a heating demand to the system.
S Low Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S Speed (variable speed heat pump only): Selectable from lowest available to
100%
d Default = lowest available as specified by variable speed heat pump
6.4.7. Humidifier
The humidifier can be exercised On and Off with this menu option. To end the humidifier checkout, touch STOP.
S Humidifier Check: On or Off
Page 56
48
6.4.8. Ventilator
The ventilator can be exercised through all of its operating speeds with this menu option. To end the ventilator checkout, touch STOP.
S Humidifier Check: High, Low or Off
6.4.9. Zoning (If Applicable)
6.4.9.1. Airflow Limits
Because there is no bypass damper, the zone airflow limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amount of airflow to each zone. Touch AIRFLOW LIMITS:When START is touched, the selected zone’s damper will fully open, all others will close, and the indoor unit will provide the maximum airflow for that zone (as selected in SETUP — ZONING, Airflow Limits). If the airflow noise is objectionable, the installer can select a lower airflow noise limit. If the noise is not objectionable, the installer should leave HIGH selected, or even NO LIMIT.
NOTE: Selecting a lower airflow noise limit may decrease the homeowner’s comfort in that zone.
Touch the Left (<) or Right (>) buttons to change the desired zones. Once the proper airflow limits are set, touch SAVE,toseeZONING CHECKOUT menu.
6.4.9.2. Damper/Sensor Check
The Sensor/Damper Check allows the installer to check each zone damper for operation, as well as insure the zone sensor corresponds to that particular zone. When first initiated, the Zone 1 damper will fully open, and all other zones will close. Using the Left (<) or Right (>) buttons, the installer can select each zone and verify the damper is fully open while all other dampers remain closed.
Page 57
49
After proper damper operation has been verified, the installer can now check and verify that each Remote Room Sensor corresponds to the proper zone damper in the same zone. For systems with remote room sensor, temporarily disconnect any other zone Remote Room Sensor (at sensor location). That zone damper will now open, while the Zone 1 damper will close.
For systems using Smart Sensors, the installer may press and hold the Hold and Mode buttons simultaneously for 3 seconds to change the zone under test. This should be done with each zone to verify that the zone sensor corresponds to that particular zone.
Once each zone has been checked, touch DONE to return to the ZONING
CHECKOUT menu.
6.4.9.3. Zone Duct Assessment
This screen shows the results from the previous duct assessment. The duct assessment is performed at initial start--up and at 1 P.M. or the installer selected time each day. If another duct assessment is desired, the service technician should perform a re--install of the system.
NOTE: A Duct Assessment will automatically occur every 24 hours at selected time to check system static and calibrate dampers.
Once the duct assessment is complete, touch DONE to return to the ZONING
CHECKOUT menu.
6.4.9.4. Sensor Type
This option shows a list of all zones with corresponding sensor types.
6.5. Service Information
The Service Info menu will only show the equipment installed in the system. To enter this menu of options, touch SERVICE INFORMATION.
Page 58
50
A13123
6.5.1. Fan Coil Status
The fan coil status screen displays relevant information about the fan coil operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12197
6.5.2. Furnace Status
The furnace status screen displays relevant information about the furnace operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Page 59
51
A12198
6.5.3. AC Status
The AC status screen displays relevant information about the AC operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12199
6.5.4. Heat Pump Status
The heat pump status screen displays relevant information about the heat pump operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Page 60
52
A12200
6.5.5. Zoning Status
The zoning status screen displays relevant information about the zoning operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12201
6.5.6. Last 10 System Faults
This screen will show the last 10 events that occurred throughout the system. Each entry has the time and date incident recorded. These events are stored in the memory of the control and are resettable in the THERMOSTAT SETUP screen under the RESET FACTORY DEFAULT selection. Each entry shows the
Page 61
53
equipment that generated the event. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12151
6.5.7. Run/Fault History
This information is stored in the equipment circuit boards (if communicating) and displayed on the control. The indoor unit and outdoor unit (if communicating) have the following histories. To return to the previous screen, touch BACK.Toexitthe Service menus, touch DONE.
S Resettable Faults: Fault counters for each piece of equipment that can be reset. S Cycle Counters: Number of heat/cool/power cycles the unit has performed. S Run Times: Lifetime hours of operation in heating, cooling, and how long the
unit has been powered.
Page 62
54
A12202
6.5.8. Model/Serial Numbers
This menu item allows the installer to view the model number and serial number (if available) of all communicating pieces of equipment in the system, including the wall control. This information resides in the original equipment circuit board(s) from the factory. If an equipment circuit board has been replaced, the model and serial number will no longer be displayed. To return to the previous screen, touch
BACK. To exit the Service menus, touch DONE.
6.5.9. Service Phone Number
This menu item allows the installer to view the name and phone number that the homeowner can call for future service of the system. This n ame and phone number will appear to the homeowner whenever a service reminder pop--up message is displayed (i.e. Change Filter, etc.). To return to the previous screen, touch BACK. To exit, touch DONE. See Section 6.7.
6.5.10. Energy Tracking Watt Meter
This menu item allows the installer to view the energy usage of each piece of equipment connected to the system. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Page 63
55
A12203
6.6. Refrigerant Charging
For variable speed heat pumps, a refrigerant charging menu is available to aid in the proper charging of the system. Enter the menu from the service screens by touching REFRIGERANT CHARGING.
A12204
6.6.1. Charging
Within the CHARGING screens, the installer will have the ability to enter the LINESET length and the VA P O R LI N E diameter. After the selections are made, touch NEXT.
S Lineset: Selectable from 5 to 200 feet
Page 64
56
S Vapor line: Selectable with various diameters by using the up and down
buttons
Next, the installer will enter the WEIGH IN screen to verify the curre nt total charge is accurate. Once the installer has confirmed, touch DONE.
Next, the installer will enter the SERVICE VALVE SUBCOOL screen. This screen will show the current liquid line subcool target (in _F). To begin the charging, touch START. If the outdoor temperatures are not in the required range, Service Valve Subcool may not be available.
Next, the installer will enter the SERVICE VALVE INFORMATION screen. The current liquid line subcool target, stabilization time, mode and speed in rpm, EXV position in percent, indoor airflow in CFM, outdoor coil temperature in _F, indoor temperature in _F, outdoor temperature in _F, compressor discharge pressure in psig, and accumulator suction pressure in psig are displayed on this screen. Once the stabilization time has expired, touch DONE.
6.6.2. Pump down
Because this system has an inverter controlled compressor, suction pressure transducer and EXV, conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit. The control has provisions to assist in performing this function.
S Select mode to pump down in (COOL or HEAT). COOL mode allows
refrigerant to be isolated in outdoor unit. HEAT mode allows the refrigerant to be isolated in indoor coil and lineset. Set desired time period.
d Default time period for procedure is 120 minutes.
S Touch START to begin the pump down process. Unit will begin running in
selected mode after a brief delay.
Page 65
57
6.6.3. Evacuation
Because this system has an EXV for the heating expansion device, additional steps must be taken to open the EXV if the heat pump unit must be evacuated for service reasons. If the EXV is not open when pulling a vacuum or recovering refrigerant from the heat pump unit, extended evacuation time may be required and/or inadequate vacuum obtained. The control has provisions to open the EXV for refrigerant recovery and/or evacuation.
S Set desired time period.
d Default time period for procedure is 120 minutes.
S Touch START on UI to open the valve. S Begin evacuation or refrigerant recovery as required for the procedure after
control indicates the EXV is open. Power may be removed from heat pump after the control indicates “READY TO EVACUATE.”
6.7. Dealer Logo
Touch DEALER LOGO to upload the dealer logo and contact information from a standard USB memory device connected to the Infinityr Touch Control. The “Dealer Logo Application” PC/MAC software download available at www.MyInfinityTouch.Carrier.com/Infinity/downloads
is required to properly
format the dealer logo and contact information for use on the wall control.
Along with the dealer logo (if any), three lines of dealer information are provided on the wall control:
Dealer name (50 characters, max)
Dealer phone number (20 characters, max)
Dealer URL (50 characters, max)
The wall control dealer information display is 30 characters wide. Dealer names and URLs over 30 characters will be split into two lines on the display.
Page 66
58
The PC/MAC software application to format the dealer logo and contact information can be found at:
www.MyInfinityTouch.Carrier
.com/Infinity/downloads
Download the program and follow the program instructions.
Once the dealer logo and contact information have been properly loaded onto the USB memory device, insert the USB device into the bottom edge of the Infinityr Touch Control. The control will prompt you whether or not to upload the dealer logo. Once complete, you will receive a confirmation that your upload was successful. If the information was not stored properly on the USB device, you will receive an error message that the dealer logo was not found. Refer back to the PC/MAC software application instructions and try again. Once the upload is complete, touch NEXT.
If you have problems, contact your distributor service manager for support.
A12205
7. Wireless and Remote Access Setup (Wi-- Fi Option, only)
The Infinityr Touch Control, when supplied with the Wi-- Fi option, may be accessed by consumers through the www.MyInfinityTouch.Carrier.com
website, or
by dealers through www.HVACpartners.com
. The Infinity Touch Control connects
to a home Internet connection through an existing home Local Area Network
Page 67
59
(LAN). An Infinityr Wireless Access Point is provided in the Infinity Touch Control Wi--Fi bundle to ease connection of the Infinityr System to a home LAN.
If you or the homeowner encounter problems with Wi-- Fi or network connections, please call 1 --800--CARRIER for support with the installation and setup of the Wireless Access Point, connection of the Infinityr Control to the Wireless Access Point, or connection of the Infinity System to the web applications. Verify that Internet connections to other d evices in the home are operating properly before calling for support for Internet problems. If other devices in the home do not have Internet connection, disconnect the Wireless Access Point from the home LAN. If the Internet problems persist with other devices in the home, the homeowner should contact their Internet Service Provider.
The ability to remotely access and adjust the settings of the Infinityr Touch Control with the MyInfinity web and mobile applications is dependent on the compatibility of the user’s computer/network or mobile device, the Infinity Touch Control, and/or the MyInfinity web server with, and the availability of, the user’s internet service provider or mobile device carrier service. Carrier Corporation makes no representations or warranties, express or implied, including, to the extent permitted by applicable law, any implied warranty of merchantability or fitness for a particular purpose or use, about the compatibility of the user’s computer/network, or mobile device, with the Infinity Touch Control, and/or the MyInfinity web server, with, and the availability of, the user’s internet service provider or mobile device carrier service, or that the ability to remotely access and adjust the settings of the Infinity Touch Control will not be negatively affected by the network --related modifications, upgrades, or similar activity of the user’s internet service provider or mobile device carrier service.
7.1. Connect Wireless Access Point ot Home LAN
The Wireless Access Point may be located anywhere there is an Ethernet cable connected to the home LAN router, including next to the router itself. To install Wi--Fi connectivity to the Infinity Touch Control, connect the WAN connection
Page 68
60
(BLUE port) of the TP--LINKr Wireless Access Point (supplied with the Infinity Touch Control Wi-- Fi Bundle) to an open LAN port on the homeowner’s existing router using the provided Ethernet cable.
If there are no open LAN ports available on the homeowner’s existing router, the home router’s LAN ports may be expanded by use of an Ethernet Network Switch, available from a local electronics store. Consult the information supplied with the network switch for instructions on applying and using the network switch.
The LAN ports on the back of the TP--LINK Wireless Access Point should not be used for other devices. The TP--LINK Wireless Access Point should only be used for connection of the Infinity Touch Control and is not intended to be used, wired or wirelessly, with any other devices.
Once the Ethernet cable is connected, install the power supply to the Wireless Access Point, plug the power supply into a household receptacle, and press the power button on the back of the Wireless Access Point. The power light on the front of the Wireless Access Point should light and after a few minutes three other indicator lights will begin to blink (LAN Activity, Wi--Fi Activity and WAN/Internet Activity).
Verify the signal strength of the wireless access point radio signal at the desired location of the Infinity Touch Control with a wireless laptop computer. Use the Scan for Wireless Networks utility and verify that the signal for “MyHVACxxxxxx” is “Strong” or better. If not, reposition the wireless access point to provide a strong signal at the wall control location.
7.2. Connect the Infinity Touch Control to the Wireless Access Point
Touch the WIRELESS icon from the second page of the Infinity Touch Control MENU screen. First, enable the Wi-- Fi connection by touching the ENABLE
button.
Page 69
61
A12206
S Verify that the Wi--Fi connection is enabled, by noting that ENABLED is
highlighted in green.
S Touch SETUP A WI-- FI CONNECTION to begin the process. S Next, touch SCAN FOR AVAILABLE ACCESS POINTS.
A12115
S Select the myHVACxxxxxx connection from the list, then touch NEXT
d Note that “myHVAC” is followed by the last 6 digits of your Wireless Ac -
cess Point’s MAC address
d This is the “SSID” of the Wireless Access Point
d The SSID for the Wireless Access Point may also be found on a label on
the bottom of the Wireless Access Point
Page 70
62
d You may have to use the down arrow to scan to the next screen to find the
“myHVACxxxxxx”SSID
A12162
S Use the on--screen keyboard to enter the Wi--Fi security key, then touch NEXT
d The security key can be found on the label on the bottom of the Wireless
Access Point
d Touch in the security key area, and the keyboard will appear
d Begin typing and the ENTER TEXT label will disappear
A12163
S The control will inform you if the connection is successful. If so, touch DONE.
Page 71
63
d If the connection is unsuccessful, verify the Wireless Access Point SSID
and Security Key from the label on the bottom of the Wireless Access Point.
d A message of “Security Mis--match” indicates that the security has been
entered incorrectly.
d Touch RETRY and the wall control will go through the process again
d If you continue to have problems, call 1 --800--CARRIER for support
A12165
S Verify the status of the Wi--Fi connection by touching VIEW REMOTE
ACCESS STATUS on the WI--FI SETUP screen
d “Connected” should appear next to Network Status
d If the Network Status is “not connected”, repeat the process in section 7.2
d The MyInfinity Server status may take up to 15 minutes to show “Connec -
ted” due to Internet traffic
d If the MyInfinity Server status fails to show “Connected” after 15 minutes,
check Internet connectivity with other devices in the home. The homeowner should contact their Internet Service provider to diagnose general Internet problems in the home
d If you continue to have problems, call 1 --800--CARRIER for support
Page 72
64
Once Internet connectivity is established, the weather forecast should appear on the HOME screen and on the WEATHER button/screen, found on the second page under the MENU option.
7.3. Connect to MyInfinity Web Server
After connection to the Internet is established, the Infinity Touch Control must register with the web server database in order to enable the web applications. To do this, touch the WIRELESS icon from the second page of the MENU screen. In the WI--FI SETUP screen, touch MyInfinity REGISTRATION INFO. Write down the Infinity Touch Control Serial Number, MAC Address, and PIN that are displayed on this screen. This is the information that the consumer will need to register on the www.MyInfinityTouch.Carrier.com
website. It is also the information that you may need to identify the system through www.HVACpartners.com
, if the homeowner allows you access to their system.
NOTE: DO NOT use the MAC address, serial number or security key from the Wireless Access Point label to register on the MyInfinity website. It will NOT work. Use the Infinity Touch control information from the MyInfinity Registration Info screen to register the system on the MyInfinity website.
The consumer may follow the information provided on www.MyInfinityTouch.Carrier.com
to register their system. This must be done
BEFORE you attempt to access the system through www.HVACpartners.com
.
If you or the consumer have problems, contact 1--800--CARRIER for support.
Page 73
65
8. Appendix A -- Wiring Diagrams
A
B
C
D
A
B
C
D
User Interface
Green - Data A
Yellow - Data B
White - COM
Red - 24VAC
OAT
Optional Remote
Room Sensor
HUM
COM 24V
Humidifier
Connection
S2
S1
A
B
C
D
ABCD
Connections
Communicating
AC or HP*
Green
Yellow
White
Red
OAT
Sensor
(Optional)
Variable-Speed
Furnace/ Fan Coil
*NOTE: Some outdoor units do not require the “C” and “D” connections. See outdoor unit Installation Instructions.
*NOTE: For SPP products, ABCD connection between Indoor and Outdoor control boards are pre-wired at the factory.
*NOTE: For new SPP installations in which the OAT Sensor is required, please refer to the SPP Installation Instructions.
A13124
Universal Four--Wire Connection
Page 74
66
A
B
C
D
A
B
C
D
C
Y
ABCD
Connection
User Interface
1-Spd. Non-Communicating AC
Green - Data A
Yellow - Data B
White - COM
Red - 24VAC
Optional Remote
Room Sensor
HUM
COM
24V
Humidifier
Connection
Y/Y2
S2
S1
OAT
OAT
Sensor
Variable-Speed
Furnace/Fan Coil
A12354
Connection Diagram for Furnace or FE Fan Coil with
1--Stage Air Conditioning
Page 75
67
A
B
C
D
A
B
C
D
ABCD
Connection
User Interface
1-Spd. Non-communicating HP
Green - Data A
Yellow - Data B
White - COM
Red - 24VAC
Optional Remote
Room Sensor
HUM
C
Humidifier
Connection
Y
S2
S1
W2
Y
O
C
R
O
R
W
OAT
OAT
Sensor
Variable-Speed
Fan Coil
G
A12355
Connection Diagram for FE Fan Coil with Non--communication
1--Stage Heat Pump
Page 76
68
A
B
C
D
Zone Control
User Interface &
Smart Sensor(s)
Green
Yellow
White
Red
OAT
HUM
COM 24V
Humidifier Connection
A
B
C
D
OAT
Sensor
(Optional)
A B C D A B C D
Damper
Control module
A B C D
Indoor
Unit
Communicating
AC or HP
A04018
Zoning Connection for Communicating Indoor Unit with
2--Stage Communicating Outdoor Unit
Page 77
69
A
B
C
D
Zone Control
User Interface &
Smart Sensor(s)
Green
Yellow
White
Red
OAT
HUM
COM 24V
Humidifier
Connection
OAT
Sensor
A B C D A B C D
Damper
Control
module
A B C D
Indoor
Unit
C
Y
1-Stage AC.
Y/Y2
A04019
Zoning Connection Diagram for Furnace or FE Fan Coil with
Non--Communicating 1-- Stage Air Conditioning
Page 78
70
A
B
C
D
Zone Control
User Interface &
Smart Sensor(s)
Green
Yellow
White
Red
A B C D A B C D
Damper
Control module
A B C D
Variable-Speed
Fan Coil
1-Spd. HP
HUM
C
Y
W2
Y
O
C
R
O
R
W
OAT
OAT
Sensor
Humidifier Connection
G
A07149
Zoning Connection diagram for FE Fan Coil with
Non--communicating 1--Stage Heat Pump
Page 79
71
R
G
FE Fan Coil or Variable Speed Furnace
A07114
G Input Wiring for Blower Operation
Page 80
72
R
G
FE Fan Coil or Variable Speed Furnace
A07115
G Input Wiring for System Shutdown
Page 81
73
NOTES:
Page 82
74
NOTES:
Page 83
Page 84
Infinity and HYBRIDHEAT are trademarks or registered trademarks of Carrier Corporation in the United States and other countries. Other brands and product names are trademarks of their respective holders.