Carrier Transicold Supra 550, Transicold Supra 850, Transicold Supra 950, Transicold Supra 650, Transicold Supra 750 Operator's Manual

MANUAL
OPERATOR’S
Supra 550, 650,
750, 850 & 950
TRUCK
REFRIGERATION
CONTENTS
Page
Unit Identification 2..........................
Safety 3....................................
Pre-Trip Inspection 4.........................
Unit Operation 6............................
Starting the Unit -- Road Operation 6...........
Starting the Unit -- Standby Operation 7........
Starting the Unit -- Manual Operation 8.........
Pretrip Check 9.............................
Changing Setpoint 10........................
Start/Stop Operation 12......................
Continuous Run Operation 14.................
Manual Defrost 15...........................
City Speed 16...............................
Function Change 17.........................
Unit Data 19................................
Alarm Display and Reset 21..................
Stopping Unit 23............................
Product Loading 24..........................
Recommended Transport Temperatures 26.....
Problems 27................................
Troubleshooting 28..........................
Relay Board 30.............................
Unit Maintenance 32.........................
Unit Maintenance Schedule 34................
Standby Operation Guidelines 39..............
Emergency Road Service 40..................
1
SUPRA OPERATOR’S MANUAL
This guide has been prepared for the operator of Carrier Transicold diesel truck refrigeration units. It contains basic instructions for the daily operation of the refrigeration unit as well as safety information, troubleshooting tips, and other information that will help you to de­liver the load in the best possible condition. Please take the time to read the information contained in this booklet and refer to it when­ever you have a question about the operation of your Carrier Tran­sicold Supra unit.
Your refrigeration unit has been engineered to provide long, trouble-free performance when it is properly operated and main­tained. The checks outlined in this guide will help to minimize over­the-road problems. In addition, a comprehensive maintenance pro­gram will help to insure that the unit continues to operate reliably. Such a maintenance program will also help to control operating costs, increase the unit’s working life, and improve performance.
This guide is intended as an introduction to your unit and to provide general assistance when needed. More comprehensive informa­tion can be found in the Operation and Service Manual for your unit. This manual can be obtained from your local Carrier Transicold dealer.
When having your unit serviced, be sure to specify genuine Carrier Transicold replacement parts for the highest quality and best reli­ability.
At Carrier Transicold, we are continually working to improve the products that we build for our customers. As a result, unit specifica­tions may change without notice.
2
UNIT IDENTIFICATION
Each Supra 50 Series unit is identified by a nameplate attached to the frame near the accumulator. This nameplate identifies the complete model number of the unit, the serial number, the refrigerant charge and quantity, and the date the unit was placed in service.
If a problem occurs, please refer to the information on this plate, and make a note of the model and serial number before calling for assistance. This information will be needed when you contact a technician or Carrier Transicold Service Engineer so that he or she may properly assist you.
NAMEPLATE
3
SAFETY
Your Carrier Transicold refrigeration unit has been designed with the safety of the operator in mind. During normal operation, all moving parts are fully guarded to help prevent injury. During all pre-trip inspections, daily inspections, and problem troubleshooting, you may be exposed to moving parts; please stay clear of all moving parts when the unit is in operation and when the unit main power switch is in the RUN position.
AUTO-START/STOP
Your refrigeration unit is equipped with Auto-Start/Stop, a valuable fuel saving feature. When the unit is set for Auto-Start/Stop operation it may start at any time and without warning. When performing any check of the refrigeration unit (e.g., checking the belts, checking the oil), make certain that the main power switch is in the OFF position.
ENGINE COOLANT
The engine is equipped with a pressurized cooling system. Under normal operating conditions, the coolant in the engine and radiator is under high pressure and is very hot. Contact with hot coolant can cause severe burns. Do not remove the cap from a hot radiator. If the cap must be removed, do so very slowly in order to release the pressure without spray.
REFRIGERANTS
The refrigerant contained in the refrigeration system of your unit can cause frostbite, severe burns, or blindness when in direct contact with the skin or eyes. For this reason, and because of legislation regarding the handling of refrigerants during system service, we recommend that whenever your unit requires service of the refrigeration system, you contact your nearest Carrier Transicold authorized repair facility for service.
BATTERY
This unit utilizes a lead-acid type battery. The battery normally vents small amounts of flammable hydrogen gas. Do not smoke when checking the battery. A battery explosion can cause serious physical harm and/or blindness.
4
PRE-TRIP INSPECTION
The pre-trip inspection should be performed before picking up any load. This inspection is essential to anticipate and help minimize the possibility of “over-the-road” problems. These checks take only a few minutes.
1. Place the unit’s main switch in the STOP (0) position.
2. Fuel -- drain any water and impurities from the sump of the refrigeration unit fuel tank by opening the drain-cock located on the bottom of the tank (if so equipped). Close the valve when only pure fuel emerges. Check the fuel level in the tank, ensuring that the fuel supply is adequate for unit operation. Refuel if necessary.
3. Belts -- Check the belt tension by depressing the belt with your thumb, near the center of the longest free run of each belt. Under moderate pressure each belt should deflect approximately 6 mm to 13mm (1/4 inch to 1/2 inch). If the belts deflect more than this they should be tightened (loose belts may slip, generating heat and reducing belt life). If the belts are too tight they should be loosened; tight belts can reduce bearing life.
3. Battery -- on units equipped with serviceable batteries, the level of the electrolyte in each of the cells should be checked. If the level is low, distilled water should be added to the correct level. Most units, however, are equipped with low or no--maintenance batteries. These should be inspected to ensure that the connections are clean and tight, and the battery hold--down should be checked for tightness.
MARKS ONLY NO WORDING
5
5. Engine Oil -- the engine oil should be checked last since it is necessary for oil to drain from the block and into the oil pan to obtain a correct reading. Remove the dipstick, wipe it off and re-insert it fully into the engine block. Once again, remove the dip-stick and observe the oil level; it should be somewhere between the full and add marks. If it is below the add mark, add oil until the level is correct.
6. Over-all Unit -- visually inspect the entire unit for leaks, loose bolts, frayed, loose, or broken wires, etc. The radiator and condenser coils of the unit should be free of dirt, bugs, cardboard, or any other debris that may obstruct airflow across the coils. The evaporator (located inside the body) should be free of debris also, especially stretch-wrap, which is often used during transport to prevent cargo shifting.
7. Truck body -- The body should be inspected prior to loading. Check the door and vent seals for damage and wear. Inspect the entire interior and exterior of the body for damage; check for damage to the inner and outer skins of the body. Damage to the insulation may compromise the unit’s ability to maintain the product temperature by increasing the amount of heat gain across the truck body.
6
UNIT OPERATION
STARTING THE UNIT -- ROAD OPERATION
WARNING
Under no circumstances should ether or any other starting aids be used to start engine.
BOX TEMPERATURE
AUTO START/STOP
I
UNIT DATA
PRETRIP
ALARM/FAULT
STANDBYBUZZER OFF
MAN
DEFROST
CITY
SPEED
ROAD
FUNCTION
ENTER
SETPOINT
O
i
-20 35° F
1. Place the I/O switch in the “I” position.
2. If unit was previously used in Standby
Mode, press the ROAD key.
Under normal circumstances this is all that is required to start the unit. The unit will then perform a complete diagnostic check on the microprocessor controller, pre-heat for the required amount of time based on the engine temperature and start automatically.
Complete the Pre-Trip Inspection described in the previous section.
7
STARTING THE UNIT -- STANDBY OPERATION
WARNING
Make sure the power plug is clean and dry before con­necting to any power source.
Do not attempt to connect or remove power plug or perform service and/or maintenance before ensuring the unit RUN/STOP Switch is in the STOP position and the I/O switch is in the “O” position.
BOX TEMPERATURE
AUTO START/STOP
I
UNIT DATA
PRETRIP
ALARM/FAULT
STANDBYBUZZER OFF
MAN
DEFROST
CITY
SPEED
ROAD
FUNCTION
ENTER
SETPOINT
O
i
-20 35° F
2. Connect unit to appropriate power source. (See table on page 39)
4. Press Standby key.
1. Place the unit RUN/STOP switch in the
“STOP” position and the I/O switch in the “O” position.
3. Place the unit RUN/STOP switch in the “RUN” position and the I/O switch in the “I” position.
Under normal circumstances this is all that is required to run the unit in standby power. The unit will then perform a complete diagnostic check on the microprocessor controller and start automatically.
Complete the Pre-Trip Inspection described in the previous section.
8
STARTING THE UNIT -- MANUAL OPERATION
BOX TEMPERATURE
AUTO START/STOP
I
UNIT DATA
PRETRIP
ALARM/FAULT
STANDBYBUZZER OFF
MAN
DEFROST
CITY
SPEED
ROAD
FUNCTION
ENTER
SETPOINT
O
i
MAN OP
1. Place unit RUN/STOP switch in RUN and I/O switch in “I” position. (Manual Operation will only function if unit is in Continuous Mode. If AUTO START/STOP indictor is illuminated, press AUTO START/STOP toggle key to place unit in Continuous Mode.)
2. Press FUNCTION key until AUTO OP or MAN OP is displayed. If MAN OP appears, unit is already in Manual Start Mode.
3. If AUTO OP appears, first press ENTER key, then UP or DOWN arrow key until MAN OP appears. Press ENTER key to lock in Manual Mode.
4. Place manual GLOW/CRANK switch in GLOW and hold for 5 to 15 seconds. Then place switch in CRANK position to crank and start.
Control Box
9
PRETRIP CHECK
BOX TEMPERATURE
AUTO START/STOP
I
UNIT DATA
PRETRIP
ALARM/FAULT
STANDBYBUZZER OFF
MAN
DEFROST
CITY
SPEED
ROAD
FUNCTION
ENTER
SETPOINT
O
i
PPPP
1. Start and run unit until box temperature is 40_±5°F(4.4_±2.8°C).
2. Press PRETRIP CHECK key.
The PRETRIP key initiates a check of all normal operating modes. Upon initiation, the unit will cycle through all operating modes at 30 second intervals. The display will show “PPPP” at the beginning and will show various unit data during the pre-trip cycle. The final PRETRIP mode is Defrost. When Defrost ends, PRETRIP will be complete.
This is not a self-diagnosing pretrip test. No specific pretrip alarms will be generated. Pretrip must be monitored by the user to verify that the unit operates through all cycles.
10
CHANGING SETPOINT
BOX TEMPERATURE
AUTO START/STOP
I
UNIT DATA
PRETRIP
ALARM/FAULT
STANDBYBUZZER OFF
MAN
DEFROST
CITY
SPEED
ROAD
FUNCTION
ENTER
SETPOINT
O
i
Press ENTER key when desired setpoint is
displayed to lock in new setpoint.
New setpoint will flash and then return to original
setpoint if ENTER key is not pressed within 5 seconds.
Press UP or DOWN arrow key to increase or
decrease displayed setpoint.
-20 35° F
11
Setpoints of -22°Fto+89°F (-30°Cto+32°C) may be entered via the keypad. The controller always retains the last entered setpoint in memory. If no setpoint is in memory (i.e. on initial startup), the controller will lock out the run relay and flash “SP” on the left hand display until a valid setpoint is entered. The setpoint may be changed up or down in 1° increments by pressing and releasing either the UP ARROW or DOWN ARROW key .
You cannot change setpoint when unit is in Pretrip or when viewing Unit Data or Functional Parameters.
Loading...
+ 30 hidden pages