Carrier 50PTH, PTV User Manual

AQUAZONE™
50PTH, PTV, PTD026-072
Two-Stage Water Source Heat Pumps
with PURON® Refrigerant (R-410A)
Installation, Start-Up, and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
•PROTECTION
•INSPECT UNIT
Step 3 — Locate Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• FIELD CONVERSION OF DISCHARGE AIR
• HORIZONTAL UNIT
• VERTICAL UNITS
Step 5 — Check Duct System . . . . . . . . . . . . . . . . . . . . 9
• SO U N D AT T E N U AT I ON
• EXISTING DUCT SYSTEM
Step 6 — Install Condensate Drain . . . . . . . . . . . . . . . 9
• HORIZONTAL UNIT
• VERTICAL UNITS
• VENTING
Step 7 — Pipe Connections . . . . . . . . . . . . . . . . . . . . . 10
• WATER LOOP APPLICATIONS
• GROUND-WATER APPLICATIONS
• GROUND-LOOP APPLICATIONS
• INSTALLATION OF SUPPLY AND RETURN HOSE KIT
• POWER CONNECTION
• SUPPLY VOLTAGE
• 208-VOLT OPERATION
• 460-VOLT OPERATION
• WSHP OPEN WIRING
Step 9 — Wire Field Controls. . . . . . . . . . . . . . . . . . . . 25
• THERMOSTAT CONNECTIONS
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
Step 10 — Operate ECM Interface Board . . . . . . . . 27
• STANDALONE — NO DDC CONTROLS
• WSHP OPEN CONTROLS
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29,30
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . . . 30-33
Complete C Control Jumper Settings. . . . . . . . . . . . 30
Complete C Control DIP Switches . . . . . . . . . . . . . . . 30
Deluxe D Control DIP Switches. . . . . . . . . . . . . . . . . . 30
Units with Modulating Hot Water Reheat
(HWR) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
• STANDALONE — NO DDC CONTROLS
• WSHP OPEN CONTROLS
• HWR APPLICATION CONSIDERATIONS
• HWR COMPONENT FUNCTIONS
Deluxe D Control Accessory
Relay Configurations. . . . . . . . . . . . . . . . . . . . . . . . . 32
Page
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-38
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 34
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 34
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 34
Unit Start-Up with WSHP Open Controls . . . . . . . . 36
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 38
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 38
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-42
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Units with Aquazone™ Complete C Control . . . . . 39
Units with Aquazone Deluxe D Control. . . . . . . . . . 39
Units with WSHP Open Multiple Protocol. . . . . . . . 39
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42,43
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
WSHP Open Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . 43
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Aquazone Deluxe D Control LED Indicators . . . . . 43
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44,45
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 44
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 45
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 45
Replacing the WSHP Open Controller’s
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 45-53
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Control Sensors
WSHP Open Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Thermostatic Expansion Valves . . . . . . . . . . . . . . . . . . 46
Stopped or Malfunctioned ECM Motor. . . . . . . . . . . . 50
Moisture Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
APPENDIX A — WSHP OPEN SCREEN
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 54-59
50PTH,PTV,PTD START-UP
CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before starting installation.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500079-01 Printed in U.S.A. Form 50PT-4SI Pg 1 7-10 Replaces: 50PT-3SI
components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Improper installation, adjustment, alteration, service, main­tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or a local distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individ­ual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal inju­ry or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury.
WARNING
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
GENERAL
This installation and start-up instructions literature is for Aquazone™ two-stage water source heat pump systems.
Water source heat pumps (WSHPs) are single-package hori­zontally and vertically mounted units with electronic controls designed for year-round cooling and heating. Aquazone WSHPs are available in the following unit configurations:
• 50PTH unit with horizontal airflow and right, left or back
discharge
• 50PTV unit with vertical airflow and top discharge
• 50PTD unit with vertical airflow and bottom discharge
(downflow)
IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi­bility of the installing contractor to determine and comply with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
maintenance instructions are provided with each unit. Before
Installation, operation and
unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Table 1 for unit physical data.
IMPORTANT: This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidity and corrosive water or air will adversely affect the unit performance, reliability and service life.
HORIZONTAL UNIT (50PTH) —
ed for indoor installation only. Be sure to allow adequate space around the unit for servicing. See Fig. 1 for overall unit dimen­sions. Refer to Fig. 2 for an illustration of a typical horizontal installation.
VERTICAL AND DOWNFLOW UNITS (50PTV, PTD) — Vertical units are designed for indoor installations. While verti­cal units are typically installed in a floor-level closet or a small mechanical room, the unit access guidelines for these units are very similar to those described for horizontal units. See Fig. 3 and 4 for overall dimensions. Refer to Fig. 5 for an example of a typical vertical installation. Refer to Fig. 6 for a sample downflow installation.
Horizontal units are design-
CAUTION
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction pro­cess. The mechanical components and filters used in these units quickly become clogged with construction dirt and debris which may cause system damage.
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the car­ton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.
1. Be sure that the location chosen for unit installation pro­vides ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing.
2. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.
NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces.
3. Check local codes to be sure a secondary drain pan is not required under the unit.
4. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropri­ate slope cannot be achieved, a field-supplied condensate pump may be required.
5. Provide sufficient space for duct connection. Do not allow the weight of the ductwork to rest on the unit.
6. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access.
7. Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils. Removal of the entire unit from the closet should not be necessary.
2
8. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary.
9. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.
10. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.
STORAGE — If the equipment is not needed immediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 high. Do not remove any equipment from its shipping package until it is needed for installation.
PROTECTION — Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl film, or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate­rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.
CAUTION
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com­plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Do not remove the packaging until the unit is ready for installation.
3. Verify that the unit’s refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Be sure connections are clean and tight at their terminations.
5. Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.
6. Remove the four
1
/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra­tion and sound alternation.
CAUTION
Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.
7. Remove any blower support cardboard from inlet of the blower.
8. Locate and verify any accessory kit located in compressor and/or blower section.
9. Remove any access panel screws that may be difficult to remove once unit is installed.
Table 1 — Physical Data — 50PTH, PTV, PTD026-072 Units
UNIT 50PTH, PTV, PTD 026 038 049 064 072 COMPRESSOR (1 each) Two- St a g e, Sc r oll FACTORY CHARGE R-410A (oz) 58 78 81 144 156 ECM FAN MOTOR AND BLOWER
Fan Motor Type VAR VAR VAR VA R VAR Fan Motor (Hp)
Blower Wheel Size (D x W) (in.) 9 x 7 11 x 10 11x10 11x10 11x10 COAXIAL COIL VOLUME (gal.) .76 .92 1.24 1.56 1.56 WATER CONNECTION SIZE (FPT) (in.) HWG CONNECTION SIZE (FPT) (in.) VERTICAL
Air Coil
Dimensions (H x W) (in.) 28 x 20 28 x 25 32 x 25 36 x 25 36 x 25 Filter Standard — 1-in. Throwaway
(Qty — Size) (in.)
Weight (lb)
Operating 266 327 416 443 443 Packag ed 276 337 426 453 453
HORIZONTAL
Air Coil
Dimensions (H x W) (in.) 18 x 31 20 x 25 20 x 40 20 x 45 20 x 45 Filter Standard — 1-in. Throwaway
(Qty — Size) (in.)
Weight (lb)
Operating 266 327 416 443 443 Packag ed 276 337 426 453 453
LEGEND
ECM — Electronically Commutated Motor HWG — Hot Water Generator VAR — Variable Speed
NOTE: All units have spring compressor mountings, TXV (thermostatic expan­sion valve) expansion devices, and
1
/2 and 3/4-in. electrical knockouts.
1
/
2
3
/
4
1
/
2
1 — 28 x 24 1 — 28 x 30 2 — 16 x 30
2 — 18 x 18
1
/
2
3
/
4
1
/
2
1 — 12 x 20 1 — 20 x 24
111
111
1
/
2
1 — 18 x 20 1 — 20 x 24
1
/
2
1 — 16 x 30 1 — 20 x 30
2 — 20 x 24 2 — 20 x 24
1 — 16 x 30 1 — 20 x 30
1
/
2
3
Y Configuration - Left Return/Back Discharge
W Configuration - Left Return/Right Discharge - Air Coil Opening
W Configuration - Left Return/Right Discharge - Air Coil Opening
P Configuration - Right Return/Back Discharge - Air Coil Opening
N Configuration - Right Return/Left Discharge - Air Coil Opening
N Configuration - Right Return/Left Discharge - Air Coil Opening
Left View
Right View
Size
Right View
ASP
BSP
Q
P
O
R
Blower Outlet
Air Coil Side
C
A
Y
Front
X
Z
C
P
A
R
O
Q
BSP
Left Discharge
Back Discharge
Condensate 3/4” FPT
H
CSP
Front
2 Service Access
Right Return
2 Service Access
3.25”
G
F
E
D
CAP
J
K
L
A
Powe r Supply 3/4” Knockout
1/2”
Knockout
Low Voltage
1/2” Knockout
Front
CSP
ASP
Left Return
Right Discharge
Back Discharge
Condensate 3/4” FPT
H
2 Service Access
2 Service Access
Air Coil Side
Blower Outlet
BSP
P
M
N
O
Blower Outlet
S
U
V
C
T
B
CSP
Front Front
Air Coil
1.1”
C
Air Coil
ASP
S
B
T
Front
CSP
M
BSP
Blower Outlet
O
P
N
3.25”
1.6”
, 072
NOTES:
1. Condensate connection is stainless steel
3
/4 in. female pipe thread (FPT).
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without additional suppor t.
3. Discharge flange is factory-installed.
4. Hanger kit is factory-installed.
5. Shaded areas are recommended service areas, not required.
6. Discharge can be modified in field. Return cannot be modified.
AIRFLOW CONFIGURATION
50PTH
UNIT
OVERALL CABINET
(in.)
WATER CONNECTIONS (in.)
WATER
CONNEC-
TIONS (in.)
- UNITS
WITH HWR
ELECTRICAL
KNOCKOUTS (in.)
DISCHARGE CONNECTIONS (in.)
DUCT FLANGE INSTALLED
( 0.10 in.)
RETURN CONNECTION
USING AIR COIL
OPENING (in.)
A
WidthBDepthCHeight
123 4 5
Loop
Wate r
FPT (in.)
HWG
FPT (in.)
12
J
1
/2-in.
Cond
K
1
/2-in.
Cond
L
3
/4-in.
Cond
M (LH rtn)
NOSupply
Height
P
Supply
Width
Q (RH rtn)
RSReturn
Width
T Return Height
UV
DInE
Out
F
HWG
In
G
HWG
Out
H Cond­ensate
Loop
in D
Loop out E
Low
Vol ta ge
Ext
Pump
Power
Supply
026 22.4 62.2 19.3 2.1 10.0 13.9 16.9 3.53/
4
1
/22.1 10.0 3.6 6.1 8.6 3.6 2.0 12.5 15.5 3.6 2.0 33.8 16.2 2.3 1.5
038 25.4 71.2 21.3 3.4 10.8 14.6 18.9 3.43/
4
1
/25.96 13.13 3.4 6.1 8.6 3.1 1.2 19.0 17.5 3.1 1.0 34.8 18.2 3.1 1.5
049 25.4 76.2 21.3 3.4 10.8 15.6 18.9 3.4 11/25.96 13.13 3.6 6.1 8.6 3.1 1.2 19.0 17.5 3.1 1.0 39.8 18.2 3.1 1.5
064,072 25.4 81.2 21.3 3.4 10.8 15.6 18.9 3.4 11/25.96 13.13 3.6 6.1 8.6 3.1 1.2 19.0 17.5 3.1 1.0 44.8 18.2 3.1 1.5
CODE RETURN DISCHARGE
N Right Left
P Right Back
W Left Right
Y Left Back
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HWG — Hot Water Generator HWR — Hot Water Reheat
Fig. 1 — 50PTH026-072 Dimensional Data
4
Field-Supplied Electric Heat (if applicable)
Filter Access
Integral hanger support­pre-attached in factory
Field-supplied transition to minimize pressure loss
3/8” threaded rods
(by others)
Return Air (Ductwork not shown)
Thermostat
Wiring
Power Wiring
Balancing Valve (field­installed accessory)
Stainless steel braid hose with integral “J” swivel
3/8” Threaded
Rod (by others)
Supply Air
Insulated supply duct with at least one 90 degree elbow to reduce air noise (field-supplied)
Flexible Connection
Vibration Isolator
(white-compressor end
and red-blower end)
Washer
(by others)
Double Hex Nuts
(by others)
Unit Power
Unit Power Disconnect (by others)
Unit Hanger (factory­supplied)
Low Pressure Drop Water Control Valve (optional) (field-installed accessory)
Ball Valve with optional integral P/T plug (typical for supply and return piping)
(field-installed accessory)
(field-installed accessory)
Aux Electric Heat Disconnect
Water In
Water Out
Building
Loop
Fig. 2 — Typical Installation — 50PTH Unit
UNIT HANGER ISOLATION DETAIL
5
Filter Bracket
NOTES:
1. Condensate connection is stainless steel 3/4 in. female pipe thread (FPT).
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without additional support.
3. Discharge flange is field-installed.
4. Shaded areas are recommended service areas, not required.
AIRFLOW CONFIGURATION
50PTV
UNIT
OVERALL CABINET
(in.)
WATER CONNECTIONS (in.)
WATER
CONNEC-
TIONS (in.)
- UNITS
WITH HWR
ELECTRICAL
KNOCKOUTS (in.)
DISCHARGE CONNECTIONS (in.)
DUCT FLANGE INSTALLED
( 0.10 in.)
RETURN CONNECTION
USING AIR COIL OPENING
(in.)
A
WidthBDepthCHeight
123 4 5
Loop
Wate r
FPT (in.)
HWG
FPT (in.)
12
J
1
/2-in.
Cond
K
1
/2-in.
Cond
L
3
/4-in.
Cond
M (LH rtn)
NOSupply
Width
P
Supply
Depth
Q (RH rtn)
RSReturn
Depth
T Return Height
U
DInE
Out
F
HWG
In
G
HWG
Out
H Cond­ensate
Loop
in D
Loop out E
Low
Vol ta ge
Ext
Pump
Power
Supply
026 22.4 25.6 48.5 2.1 10.0 13.9 16.9 7.8
3
/
4
1
/22.1 10.0 3.6 6.1 8.6 7.2 5.8 14.0 14.0 4.9 2.2 21.1 27.2 1.0
038 25.4 30.6 50.5 3.4 10.8 15.6 18.9 7.83/
4
1
/25.96 13.13 3.6 6.1 8.6 6.4 6.3 18.0 18.0 5.3 2.2 26.1 27.2 1.0
049 25.4 30.6 54.5 3.4 10.8 15.6 18.9 7.8 11/25.96 13.13 3.6 6.1 8.6 6.4 6.3 18.0 18.0 5.3 2.2 26.1 31.2 1.0
064, 072
25.4 30.6 58.5 3.4 10.8 15.6 18.9 7.8 11/25.96 13.13 3.6 6.1 8.6 6.4 6.3 18.0 18.0 5.3 2.2 26.1 35.2 1.0
CODE RETURN DISCHARGE
J Left Top
K Right Top
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HV — High Voltage HWG — Hot Water Generator HWR — Hot Water Reheat LV Low Voltage
Fig. 3 — 50PTV Dimensional Data
Field-Installed Discharge Flange (shipped loose inside blower section)
Access Panels
Front
O
Q
K - Configuration - Right Return
/Top Discharge
U
T
C
Front
K - Configuration - Right Return -
Air Coil Opening
(Right Side View)
P
Air Coil Side
(Top View)
S
ASP
B
N
R
N
J - Configuration - Left Return
R
P
Air Coil Side
/Top Discharge
(Top View)
S
Front
U
Air Coil
T
C
1.18”
CSP
Back Back Front
J - Configuration - Left Return -
Air Coil Opening
(Left Side View)
O
M
A
Air Coil
Air Coil
Power Supply 3/4” HV Knockout
1/2” Knockout
Low Voltage 1/2” LV Knockout
CSP
2ʼ Service Access
CSP
BSP
CAP
1.63”
J
K
Front View
Isometric View
CAP
L
ASP
ASP
1.00”
1.68”
D
Condensate 3/4” FPT
H
2ʼ Service Access
G
F
E
6
NOTES:
1. Condensate connection is stainless steel 3/4 in. female pipe thread (FPT).
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without additional support.
3. Downflow unit does not have discharge flange, and is rated for zero clearance installation.
4. Shaded areas are recommended service areas, not required.
AIRFLOW CONFIGURATION
50PTD
UNIT
OVERALL CABINET
(in.)
WATER CONNECTIONS (in.)
WATER
CONNEC-
TIONS (in.)
- UNITS
WITH HWR
ELECTRICAL
KNOCKOUTS (in.)
DISCHARGE CONNECTIONS (in.)
DUCT FLANGE INSTALLED
( 0.10 in.)
RETURN CONNECTION (in.)
USING AIR COIL OPENING
A
WidthBDepthCHeight
12 3 4 5
Loop
Wate r
FPT (in.)
HWG
FPT (in.)
12
J
1
/2-in.
Cond
K
1
/2-in.
Cond
L
3
/4-in.
Cond
M (LH rtn)
NOSupply
Width
P
Supply
Depth
Q (RH rtn)
RSReturn
Depth
T Return Height
U
DInE
Out
F
HWG
In
G
HWG
Out
H
Cond-
ensate
Loop
in D
Loop out E
Low
Vol t ag e
Ext
Pump
Power
Supply
026 22.4 25.6 52.5 2.1 10.0 13.9 16.9 3.63/
4
1
/22.1 10.0 3.6 6.1 8.6 6.7 8.4 10.1 9.1 10.8 2.2 21.1 27.2 1.0
038 25.4 30.6 54.5 3.4 10.8 15.6 18.9 3.63/
4
1
/25.96 13.13 3.6 6.1 8.6 7.2 9.0 13.4 12.9 10.4 2.2 26.1 27.2 1.0
049 25.4 30.6 58.5 3.4 10.8 15.6 18.9 3.6 11/25.96 13.13 3.6 6.1 8.6 7.2 9.0 13.4 12.9 10.4 2.2 26.1 31.4 1.0
064,072 25.4 30.6 62.5 3.4 10.8 15.6 18.9 3.6 11/25.96 13.13 3.6 6.1 8.6 7.2 9.0 13.4 12.9 10.4 2.2 26.1 35.2 1.0
CODE RETURN DISCHARGE
J Left Bottom
K Right Bottom
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HWG — Hot Water Generator HWR — Hot Water Reheat
Fig. 4 — 50PTD Dimensional Data
7
• Provide adequate clearance for filter replacement and
Return
Air
Power
Thermostat Wiring
Compressor Access Panel
Balancing Valve (field-installed accessory)
Low Pressure
Drop Water Control Valve (optional) (field-installed accessory)
Ball Valve with optional integral P/T plug (typical for supply and return piping) (field-Installed accessory)
Water Out
Water In
Building
Loop
Supply Air
Flexible Connection
Stainless steel braid hose with integral “J” swivel (field-installed accessory)
Return
Air
Power
Thermostat
Wiring
Compressor Access Panel
Balancing Valve
(field-installed
accessory)
Low Pressure Drop Water Control Valve (optional) (field-installed accessory)
Ball Valve with optional integral
P/T plug (typical for supply and return piping)(field-installed accessory)
Water Out
Water In
Building Loop
Supply Air
Flexible Connection
Flexible
Connection
Stainless steel braid hose with integral ”J” swivel(field­installed accessory)
NOTE: Ball valve with integral pressure temperature plug recommended.
Fig. 5 — Typical Vertical Installation — 50PTV Unit
NOTE: Ball valve with integral pressure temperature plug recommended.
Fig. 6 — Typical Downflow Installation —
50PTD Unit
Water
Connection End
Supply Duct
Return Air
Water
Connection End
Drain
Return Air
Discharge Air
Side Discharge
Back Discharge
Fig. 7 — Conversion Right Return, Side Discharge to Back Discharge
drain pan cleaning. Do not block filter access with pip­ing, conduit or other materials. Refer to Fig. 1, 3, and 4 for dimensional data.
• Provide access for fan and fan motor maintenance and for servicing the compressor and coils without removing the unit.
• Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of the unit, if necessary.
• In limited side access installations, pre-removal of the control box side mounting screws will allow control box removal for future servicing.
• Provide access to water valves and fittings and screw­driver access to the unit side panels, discharge collar and all electrical connections.
NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since duct­work is normally applied to these units, the unit can be placed so that the principal sound emission is outside the oc­cupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.
FIELD CONVERSION OF DISCHARGE AIR — The dis­charge air of the 50PTH horizontal units can be converted between side and back discharge in the field. The conversion process is the same for right and left return configurations. See Fig. 7 and 8.
NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.
Step 3 — Locate Unit — The following guidelines
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between 39 F and 102 F and relative humidity is no greater than 75%.
• Provide sufficient space for water, electrical and duct
• Locate unit in an area that allows easy access and removal
• Allow enough space for service personnel to perform
• Return air must be able to freely enter the space if unit needs
• Install the unit on a piece of rubber, neoprene or other
connections.
of filter and access panels.
maintenance.
to be installed in a confined area such as a closet.
mounting pad material for sound isolation. The pad should be at least
3
/8 in. [10 mm] to 1/2 in. [13 mm] in
thickness. Extend the pad beyond all four edges of the unit.
Preparation
— The unit should be on the ground in a well lit area. Hung units should be taken down to ground level before converting.
Side to Back Discharge Conversion
1. Remove screws to free the top and discharge panels. Set screws aside for later use. See Fig. 8.
2. Remove the access panel and set aside.
3. Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.
4. Check blower wire routing and connections for undue tension or contact with sheet metal edges. Re-route if necessary.
8
Fig. 9 — 50PTV Units Mounted With
Vibration Absorption Pad
Return Air
Remove Screws
Return Air
Rotate
Move to Side
Side Discharge
Return Air
Discharge Air
Drain
Back Discharge
Replace Screws
Water
Connection End
Water
Connection End
Water
Connection End
Fig. 8 — Conversion Left Return,
Side Discharge to Back Discharge
5. Check refrigerant tubing for contact with other compo­nents. Adjust if necessary.
6. Reinstall top panel using screws set aside in Step 1. NOTE: Location for some screws at bottom of discharge
panel may have to be changed.
7. Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.
8. Replace access panel.
Back to Side Discharge Conversion above for Side to Back Discharge Conversion, noting the panels would be reversed.
— Follow instructions
Step 4 — Mount the Unit
HORIZONTAL UNIT (50PTH) — Horizontal units should be mounted using the factory-installed hangers. Proper attach­ment of hanging rods to building structure is critical for safety. See Fig. 1. Rod attachments must be able to support the weight of the unit. See Table 1 for unit operating weights.
VERTICAL UNITS (50PTV,PTD) — Vertical and downflow units are available in left or right return air configurations. See Fig. 3 and 4. Mount the unit (except 50PTD) on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor. See Fig. 9.
NOTE: Some codes require the use of a secondary drain pan under vertical units. Check local codes for more information.
Step 5 — Check Duct System — Size the duct sys-
tem to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a ship­ping support installed at the factory. This must be removed before operating unit.
SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom­mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in­clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon­ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.
To reduce air noise, at least one 90-degree elbow could be included in the supply and return air ducts, provided system performance is not adversely impacted. The blower speed can also be changed in the field to reduce air noise or excessive air­flow, provided system performance is not adversely impacted.
EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small, install
larger ductwork.
• Check existing ductwork for leaks and repair as necessary.
NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation
may be required for the ventilating air supply. If hard
ducted ventilation is not required, be sure that a proper air
path is provided for ventilation air to unit to meet ventila-
tion requirement of the space.
Step 6 — Install Condensate Drain
HORIZONTAL UNIT (50PTH) — Slope the unit toward the drain at quired pitch, install a condensate at the unit to pump conden­sate to building drain.
ternal trap is necessary. Install each unit with its own individual trap and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent. See Fig. 11 for typical condensate connections.
NOTE: Never use a pipe size smaller than the connection.
VERTICAL UNITS (50PTV,PTD) — Each unit uses a con­densate hose inside all cabinets as a trapping loop, therefore an external trap is not necessary. See Fig. 12.
1
/4 in. See Fig. 10. If it is not possible to meet the re-
Horizontal units are not internally trapped, therefore an ex-
9
Each unit must be installed with its own individual vent and
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 11 — Trap Condensate Drain
Alternate Condensate Location
Vent
1/4 per foot slope to drain
3/4 Copper FPT/PVC
Water Connections
1/2
1/2
3/4 PVC
NOTE: Unit does not need to be sloped toward drain.
Fig. 12 — Vertical Condensate Connection
1/4 Pitch for Drainage
Drain Connection
Pitch Toward Drain
Fig. 10 — Horizontal Unit Pitch
means to flush or blow out the condensate drain line. Do not in­stall units with a common trap or vent.
VENTING — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line. Con­sider the following:
• Always install a vent where an application requires a long horizontal run.
• Always install a vent where large units are working against higher external static pressure and to allow proper drainage for multiple units connected to the same condensate main.
• Be sure to support the line where anticipated sagging from the condensate or when “double trapping” may occur.
• If condensate pump is present on unit, be sure drain connec­tions have a check valve to prevent back flow of condensate into other units.
Step 7 — Pipe Connections — Depending on the
application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for addi­tional information.
All WSHP units use low temperature soldered female pipe
thread fittings for water connections to prevent annealing and out-of-round leak problems which are typically associated with high temperature brazed connections. Refer to Table 1 for con­nection sizes. When making piping connections, consider the following:
• Use a backup wrench when making screw connections to unit to prevent internal damage to piping.
• Insulation may be required on piping to avoid condensation in the case where fluid in loop piping operates at tempera­tures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may be subject to galvanic corrosion. Dielectric fittings may be used to isolate the steel parts of the system to avoid galvanic corrosion.
WATER LOOP APPLICATIONS — Water loop applications usually include a number of units plumbed to a common pip­ing system. Maintenance to any of these units can introduce air into the piping system. Therefore, air elimination equipment comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.25 and 3.5 gpm per
ton of cooling capacity. For proper maintenance and servicing, pressure-temperature (P/T) ports are necessary for temperature and flow verification.
Cooling tower/boiler systems typically utilize a common
loop maintained at 60 to 95 F. The use of a closed circuit evap­orative cooling tower with a secondary heat exchange between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and fil­tering will be necessary.
In addition to complying with any applicable codes, consid-
er the following for system piping:
• Piping systems using water temperatures below 50 F
• Avoid all plastic to metal threaded fittings due to the poten-
• Teflon tape thread sealant is recommended to minimize
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Flush the piping system prior to operation to remove dirt
GROUND-WATER APPLICATIONS — Typical ground­water piping is shown in Fig. 13. In addition to complying with any applicable codes, consider the following for sys­tem piping:
• Install shut-off valves for servicing.
• Install pressure-temperature plugs to measure flow and
• Connect boiler drains and other valves using a “T” connec-
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material.
NOTE: PVC SCH40 should not be used due to system high pressure and temperature extremes.
10
1
require
/2-in. closed cell insulation on all piping surfaces to
eliminate condensation.
tial to leak. Use a flange fitted substitute.
internal fouling of the heat exchanger.
and foreign materials from the system.
temperature.
tor to allow acid flushing for the heat exchanger.
Water Supply and Quantity
Boiler Drains (field-installed)
Strainer (field-installed accessory) (16 to 20 mesh recommended for filter sediment)
Shut-Off Valve (field-installed accessory)
Water Control Valve (field-installed accessory)
Flow Regulator (field-installed accessory)
Pressure
Ta nk
Water Out
Water In From Pump
Fig. 13 — Typical Ground-Water Piping Installation
— Check water supply. Water supply should be plentiful and of good quality. See Table 2 for water quality guidelines.
IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed­system application design requirements may cause damage to the tube-in-tube heat exchanger. This damage is not the responsibility of the manufacturer.
In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat­ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.
GROUND-LOOP APPLICATIONS — Temperatures between 25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow per ton is recommended. In addition to complying with any applicable codes, consider the following for system piping:
• Limit piping materials to only polyethylene fusion in the
buried sections of the loop.
• Do not use galvanized or steel fittings at any time due to
corrosion.
• Avoid all plastic to metal threaded fittings due to the poten-
tial to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use pressure-temperature (P/T) plugs to measure flow of
pressure drop. INSTALLATION OF SUPPLY AND RETURN HOSE
KIT — Follow these piping guidelines.
1. Install a drain valve at the base of each supply and return riser to facilitate system flushing.
2. Install shutoff/balancing valves and unions at each unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system circulating pump.
4. Select the proper hose length to allow slack between con­nection points. Hoses may vary in length by +2% to –4% under pressure.
5. Refer to Table 3. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radi­us may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.
NOTE: Piping must comply with all applicable codes.
Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum ex­pected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point.
Do not bend or kink supply lines or hoses.
Pipe joint compound is not necessary when Teflon threaded tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the male pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint.
NOTE: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed.
Maximum allowable torque for brass fittings is 30 ft-lb. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.
Optional pressure-rated hose assemblies designed specifi­cally for use with Carrier units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kink­ing during installation.
Backup wrench is required when tightening water connec­tions to prevent water line damage.
Refer to Fig. 14 for an illustration of a supply/return hose kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life.
CAUTION
CAUTION
11
Table 2 — Water Quality Guidelines
Rib Crimped
Length
(2 ft Length Standard)
Swivel Brass Fitting
Brass Fitting
MPT
Fig. 14 — Supply/Return Hose Kit
CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
2+
(Ferrous)
Iron Fe (Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H
Ammonia Ion as Hydroxide, Chloride, Nitrate and Sulfate Compounds
Maximum Chloride Levels Maximum allowable at maximum water temperature.
Erosion and Clogging
Particulate Size and Erosion
Brackish
HWG — Hot Water Generator HX Heat Exchanger N/A — Design Limits Not Applicable Considering Recirculating
NR Application Not Recommended SS Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS
(stainless steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping
system.
**Recirculating open wells should observe the open recirculating design
considerations.
Pota ble Wate r
S)
2
LEGEND
HX
MATERIAL*
All N/A pH < 7.5 and Ca Hardness, <100 ppm
All N/A
All N/A
All N/A
All N/A
All
All N/A
All N/A
Copper N/A
Cupronickel N/A <150 ppm
304 SS N/A <400 ppm 316 SS N/A <1000 ppm
Titanium N/A >1000 ppm
All
All N/A
CLOSED RECIRCULATING† OPEN LOOP AND RECIRCULATING WELL**
6.0 - 7.5
–0.5 to +0.5
<0.2 ppm (Ferrous)
<0.5 ppm of Oxygen
6 - 8.5
<0.5 ppm
<0.5 ppm
75 F (24 C) 100 F (38 C)
NR NR
NR NR <250 ppm <150 ppm <550 ppm <375 ppm >550 ppm >375 ppm
6 - 8.5
Monitor/treat as needed.
<10 ppm of particles and a
maximum velocity of 6 fps.
Filtered for maximum
800 micron size.
If >7.5 minimize steel pipe use.
Based upon 150 F HWG and direct well, 85 F indirect well HX.
2+
If Fe
(ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
Minimize steel pipe below 7 and no open tanks with pH <8.
At H
S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.
2
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
50 F (10 C)
<20 ppm
<10 ppm (<1 ppm “sandfree for reinjection) of particles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not removed can potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium chlo­ride are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
††If the concentration of these corrosives exceeds the maximum allowable
level, then the potential for serious corrosion problems exists. Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acid­ity, basicity, or neutrality of the water supply. Below 7.0, the water is consid­ered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0. To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
If <–0.5 minimize steel pipe use.
Above this level deposition will occur.
Rotten egg smell appears at 0.5 ppm level.
Table 3 — Metal Hose Minimum Bend Radii
HOSE DIAMETER (in.) MINIMUM BEND RADII (in.)
1
/
2
3
/
4
15
21/
4
1
2
/
2
Step 8 — Wire Field Power Supply
WARNING
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION
Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must
12
conform to the Class II temperature limitations described in the NEC.
Refer to unit wiring diagrams Fig. 15-24 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. For Deluxe D with WSHP Open controls 3-phase units and Complete C with Open controls single-phase and 3-phase units contact Application Engineering. Refer to Table 4 for fuse sizes.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as shown in electrical data shown in Table 4.
Make all final electrical connections with a length of flexi­ble conduit to minimize vibration and sound transmission to the building.
POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the line side of the compressor contactor terminal as shown in Fig. 25. See Table 4 for amperage ratings to provide correct wire and maximum overcurrent protection sizing.
SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter­mine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 volts BC = 464 volts AC = 455 volts
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage: (AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri­cal components.
NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.
460-VOLT OPERATION — Units using 460-v and an ECM (electronically commutated motor) fan motor, modulating HWR, and/or internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.
Table 4 — 50PTH,PTV,PTD Electrical Data
50PTH,
PTV, PTD
UNITS
026 208/230-1-60 197/254 10.3 52.0 4.3 14.6 17.2 25 0.8 15.4 18.0 25
038
049
064
072 208/230-1-60 197/254 27.2 150.0 7.0 34.2 41.0 60 1.07 35.3 42.1 60
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps RLA Rated Load Amps HWR — Hot Water Reheat
V-P H- Hz *
208/230-1-60 197/254 16.7 82.0 4.3 21.0 25.2 40 0.8 21.8 26.0 40 208/230-3-60 197/254 11.2 58.0 4.3 15.5 18.3 25 0.8 16.3 19.1 30
460-3-60 414/506 4.5 29.0 4.1 8.6 9.7 15 0.7 9.3 10.4 15 208/230-1-60 197/254 21.2 96.0 7.0 28.2 33.5 50 1.07 29.3 34.6 50 208/230-3-60 197/254 13.5 88.0 7.0 20.5 23.9 35 1.07 21.6 24.9 35
460-3-60 414/506 6.4 41.0 6.9 13.3 14.9 20 1.07 14.4 16.0 20 208/230-1-60 197/254 25.6 118.0 7.0 32.6 39.0 60 1.07 33.7 40.1 60 208/230-3-60 197/254 17.6 123.0 7.0 24.6 29.0 45 1.07 25.7 30.1 45
460-3-60 414/506 9.0 62.0 6.9 15.9 18.2 25 1.07 17.7 19.2 25
LEGEND *The 460-v units using an ECM (electronically commutated motor) fan
VO LTAGE
MIN/MAX
COMPRESSOR
RLA LRA
FAN
MOTOR
FLA
TOTAL
UNIT FLA
MIN
CIRCUIT
AMPS
motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.
MAX FUSE/ HACR
REHEAT
PUMP
FLA
UNITS WITH HWR
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX FUSE/ HACR
13
ECM
Y
GGGGR
W
O
Y
2
Y
1
G
R
C
Y
2
Y
1
G
O
W
C
R
D
H
A
L
1
A
A
A
L
1
S
W1
S
W2
S
W3
S
W4
S
W5
S
W6
S
W7
S
W8
S
W9
OF
F
ON
G
D
E
HUM
C
F
M
T
B
1
J1
S
1
BM ECM
ECM
INTERFACE
BOARD
S
W
1
S
W
2
S
W
3
S
W
4
S
W
5
S
W
6
S
W
7
S
W
8
S
W
9
OF
F
ON
S
1
J1
BM ECM
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
DTS Discharge Temp Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HWG Hot Water Generator
JW1 Jumper, Alarm
LOC Loss of Charge Pressure Switch
MV Motorized Valve
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, dis-
connect RED lead at L1 and attach ORN lead to L1. Insulate open end of RED lead. Trans-
former for 220/240 v will be connected for 220 v operation. For 240 v operation, disconnect
RED lead at L1 and attach ORN lead to L1. Transformer is energy limiting or may have cir-
cuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut
JW3 jumper.
5. Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions
for wiring to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or
greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box.
(Ground available from top two standoffs as shown.)
8. Aquastat is field-supplied and must be wired in series with the hot leg to the pump. Aqua-
stat is rated for voltage up to 277 v.
9. Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
Fig. 15 — Wiring of 50PTH,PTV,PTD026-072 Units with Complete C Controller, Single Phase (208/230 V)
14
ECM INTERFACE BOARD LAYOUT
Y
GGGGR
W
O
Y2
Y1
G
R
C
Y2
Y1
G
O
W
C
R
DH
AL
1
A
A
AL
1
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
SW
7
SW
8
SW
9
OFF
ON
G
DEH
UM
C
FM
T
B1
J
1
S
1
BM (ECM)
ECM
INTERFACE
BOARD
SW1
S
W2
S
W3
S
W4
S
W5
S
W6
S
W7
S
W8
S
W9
OFF
O
N
BM
(ECM)
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
CAP Capacitor
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
COMPR — Compressor
DDC Direct Digital Control
DTS Discharge Temp Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HWG Hot Water Generator
JW1 Jumper, Alarm
NSB Digital Night Setback
LOC Loss of Charge Pressure Switch
MV Motorized Valve
NEC National Electrical Code
LEGEND
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, discon-
nect RED lead at L1 and attach ORN lead to L1. Insulate open end of RED lead. Transformer
for 220/240 v will be connected for 220 v operation. For 240 v operation, disconnect RED
lead at L1 and attach ORN lead to L1. Transformer is energy limiting or may have circuit
breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut
JW3 jumper.
5. Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions for
wiring to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater
than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut AL2 dr y jumper and dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box.
(Ground available from top two standoffs as shown.)
8. Aquastat is field-supplied and must be wired in series with the hot leg to the pump. Aquastat
is rated for voltage up to 277 v.
9. Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.
Fig. 16 — Wiring of 50PTH,PTV,PTD026-072 Units with Deluxe D Controller, Single Phase (208/230 V)
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
15
BM (ECM)
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
DTS Discharge Temp Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HWG Hot Water Generator
JW1 Jumper, Alarm
LOC Loss of Charge Pressure Switch
MV Motorized Valve
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, disconnect
RED lead at L1 and attach ORN lead to L1. Insulate open end of RED lead. Transformer for 220/
240 v will be connected for 220 v operation. For 240 v operation, disconnect RED lead at L1 and
attach ORN lead to L1. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3
jumper.
5. Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions for wir-
ing to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit
supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dr y contact will be available
between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box.
(Ground available from top two standoffs as shown.)
8. Aquastat is field-supplied and must be wired in series with the hot leg to the pump. Aquastat is
rated for voltage up to 277 v.
9. Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
Fig. 17 — Wiring of 50PTH,PTV,PTD026-072 Units with Complete C Controller, Three Phase (208/230 V)
ON 1 S
J1
Y
W8
W6
W9
W7
W4
W5
W3
W2
W1
S
S
S
S
S
S
S
S
S
M F C
2
O
W
Y
L1 A
F
HUM E
OF
D
A
G
A 1
L A
H D
R
C
W
O
G 1
Y 2
Y
1 B T
C
GGGGR
1
R
G
Y
ECM INTERFACE BOARD LAYOUT
BM
(ECM)
N O
F OF
W7
W9
W4
W6
W3
W5
W2
W8
SW1
S
S
S
S
S
S
S
S
ECM
INTERFACE
BOARD
16
ECM INTERFACE BOARD LAYOUT
Y
GGGGR
W
O
Y2
Y1
G
R
C
Y2
Y1
G
O
W
C
R
DH
AL
1
A
A
AL
1
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
SW
7
SW
8
SW
9
OFF
ON
G
DEH
UM
C
FM
T
B1
J
1
S
1
BM (ECM)
ECM
INTERFACE
BOARD
SW1
S
W2
S
W3
S
W4
S
W5
S
W6
S
W7
S
W8
S
W9
OFF
O
N
BM
(ECM)
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
COMPR — Compressor
DDC Direct Digital Control
DTS Discharge Temp Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HWG Hot Water Generator
JW1 Jumper, Alarm
NSB Digital Night Setback
LOC Loss of Charge Pressure Switch
MV Motorized Valve
NEC National Electrical Code
LEGEND
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, dis-
connect RED lead at L1 and attach ORN lead to L1. Insulate open end of RED lead. Trans-
former for 220/240 v will be connected for 220 v operation. For 240 v operation, disconnect
RED lead at L1 and attach ORN lead to L1. Transformer is energy limiting or may have cir-
cuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut
JW3 jumper.
5. Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions
for wiring to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or
greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut AL2 dry jumper and dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box.
(Ground available from top two standoffs as shown.)
8. Aquastat is field-supplied and must be wired in series with the hot leg to the pump.
Aquastat is rated for voltage up to 277 v.
9. Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.
Fig. 18 — Wiring of 50PTH,PTV,PTD026-072 Units with Deluxe D Controller, Three Phase (208/230 V)
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
17
ECM INTERFACE BOARD LAYOUT
Y
GGGGR
W
O
Y
2
Y
1
G
R
C
Y
2
Y
1
G
O
W
C
R
D
H
A
L
1
A
A
A
L
1
S
W1
S
W2
S
W3
S
W4
S
W5
S
W6
S
W7
S
W8
S
W9
OF
F
ON
G
D
E
HUM
C
F
M
T
B
1
J1
S
1
BM (ECM)
ECM
INTERFACE
BOARD
BM
(ECM)
SW1
S
W2
S
W3
S
W4
S
W5
S
W6
S
W7
S
W8
S
W9
OF
F
O
N
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
COMPR — Compressor
DTS Discharge Temp Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HWG Hot Water Generator
JW1 Jumper, Alarm
LOC Loss of Charge Pressure Switch
MV Motorized Valve
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3
jumper.
4. Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions for wir-
ing to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit
supply voltage.
5. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available
between AL1 and AL2.
6. Transformer secondary ground via Complete C board standoffs and screws to control box.
(Ground available from top two standoffs as shown.)
7. Aquastat is field-supplied and must be wired in series with the hot leg to the pump. Aquastat is
rated for voltage up to 277 v.
8. Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
Fig. 19 — Wiring of 50PTH,PTV,PTD026-072 Units with Complete C Controller, Three Phase (460 V)
18
ECM INTERFACE BOARD LAYOUT
Y
GGGGR
W
O
Y2
Y1
G
R
C
Y2
Y1
G
O
W
C
R
DH
AL
1
A
A
AL
1
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
SW
7
SW
8
SW
9
OFF
ON
G
DEH
UM
C
FM
T
B1
J
1
S
1
BM
(ECM)
ECM
INTERFACE
BOARD
BM
(ECM)
SW1
S
W2
S
W3
S
W4
S
W5
S
W6
S
W7
S
W8
S
W9
OFF
O
N
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
DDC Direct Digital Control
DTS Discharge Temp Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HWG Hot Water Generator
JW1 Jumper, Alarm
NSB Digital Night Setback
LOC Loss of Charge Pressure Switch
MV Motorized Valve
NEC National Electrical Code
LEGEND
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS — Transformer
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3
jumper.
4. Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions for wiring
to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply
voltage.
5. 24-v alarm signal shown. For dry alarm contact, cut AL2 dry jumper and dry contact will be available
between AL1 and AL2.
6. Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground
available from top two standoffs as shown.)
7. Fan motors are factory wired for medium speed. For high or low speed, remove BLU wire from fan
motor speed tap “M or “3 and connect to “H or “2 for high speed or “L” or “4” for low speed.
8. Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.
Fig. 20 — Wiring of 50PTH,PTV,PTD026-072 Units with Deluxe D Controller, Three Phase (460 V)
19
*Optional Wiring.
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
BMC Blower Motor Capacitor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
DTS Discharge Temperature Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HPWS High-Pressure Water Switch
HWG Hot Water Generator
JW1 Clippable Field Selection Jumper
LOC Loss of Charge Pressure Switch
LON Local Operating Network
MV Motorized Valve
MVES Motorized Valve End Switch
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v (BLK/RED) lead for 460/3/60 units. Transformer is energy limiting or may
have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5. Typical thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Ther-
mostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.
6. Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground
available from top two standoffs as shown.)
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated
for voltages up to 277-v.
9. Optional LON wires. Only connect if LON connection is desired at the wall sensor.
10. Fan motors are factory wired for medium speed. For high or low speed, remove BLU wire from fan motor
speed tap “M and connect to “H for high speed or “L” for low speed.
11. For low speed, remove BLK wire from BR “6 and replace with RED. Connect BLK and BRN wires
together.
12. For blower motors with leads. For medium or low speed, disconnect BLK wire from BR “6. Connect BLK
and ORG/PUR wire together. Connect RED for low or BLU for medium to BR “6”.
13. The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR, and/or an
internal secondary pump will require a neutral wire from the supply side in order to feed the accessory
with 265-v.
Complete C
a50-8363
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
Relay Contacts - N.C.
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
Fig. 21 — Wiring of 50PTH,PTV,PTD026-072 Units with Complete C and LON Controller, Three Phase (460 V)
20
Loading...
+ 44 hidden pages