Carrier Pro-Dialog CONTROL 4 User Manual

USER'S GUIDE
TITLE: PRO-DIALOG CONTROL 4 FOR AIR & WATER COOLED
CHILLERS SERIES 30 GX & HXC VERSION 2
REV: original
Property of CARRIER S.A. Montluel. Not to be disclosed to persons outside the organization without Written authorization
SYNOPTIQUE CARRIER - AIR-COOLED BI CIRCUIT - ABC PARTNERS 08/06/98
SPECIFICATION
COPY N°
ECG CARRIER S.A.
ECG-UG-00-001
06/12/00
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
Carrier Carrier Service1
COMPANYNAMECOPY #
Ba-Tung PHAM
ORIGINATOR
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: /98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
1 - INTRODUCTION ...................................4
1.1 - About This Manual .............................4
1.2 - Manual Structure and contents ..................4
2 - GENERAL DESCRIPTION
...........................4
2.1 - Generalities ...................................4
2.1 - Software Reference Number ....................7
2.3 - Abbreviations Used ............................ 7
3 - HARDWARE DESCRIPTION
........................8
3.1 - Produc Component ............................ 8
3.1.1 - Basic Board ............................. 10
3.1.2 - CCN/Clock Option Board ................. 10
3.1.3 - Screw Compressor Protection Module .....11
3.1.3.1 - Screw Compressor Module Layout 11
3.1.3.2 - Compressor Part Number/MTA Header
Configuration ....................12
3.1.4 - 4 xDO Board ............................12
3.1.4.1 - General ........................ 12
3.1.4..2 - Terminal J4 Description ........12
3.1.5 - AUX Boards ............................. 13
3.1.5.1 - General ........................ 13
3.1.6 - EXV Driver Board ........................14
3.1.7 - 4 x AI - 2 x AO Board ....................14
3.1.8 - Aquasnap Basic Board ..................16
3.2 - Pressure Sensors .............................. 17
3.2.1 - High Pressure Side Sensors .............17
3.2.2 - Large Band Pressure Sensors ........... 17
3.2.3 - Suction and economizer Pressure Sensors 18
3.3 - Thermistors ................................... 18
3.3.1 - Discharge Gas temperature .............. 18
3.3.2 - 5K Resistor : Resistance vs Temperature
Curve ................................. 19
4 - CONTROL DESCRIPTION
..........................20
4.1 - General ...................................... 20
4.2 - Configuration ................................. 20
4.2.1 - General ................................ 20
4.2.2 - Main Interface Configuration sub menu
structure ............................... 20
4.2.3 - Factory Configuration ................... 21
4.2.3.1 - Factory configuration from Service
Tool ............................ 21
4.2.3.2 - Factory configuration from Main
Interface ........................ 23
4.2.3.3 - Economizer TQ valve Feedback
Signal Wiring ....................24
4.2.4 - Service Configuration ................... 25
4.2.4.1 - Service 1 configuration from Service
Tool ............................ 25
4.2.4.2 - Service 1 configuration from Main
Interface ........................ 27
4.2.4.3 - Service 2 configuration from Service
Tool ............................ 28
4.2.4.4 - Service 2 configuration from Main
Interface ........................ 29
4.2.4.5 - Service 3 configuration from Service
Tool ............................ 30
4.2.4.6 - Service 3 configuration from Main
Interface ........................ 31
4.2.4.7 - Service 4 configuration from Service
Tool ............................ 31
4.2.4.8 - Service 4 configuration from Main
Interface, runtime sub menu ......31
4.2.5 - User Configuration ...................... 32
4.2.6 - Network Configuration ..................32
4.2.6.1 - General .......................32
4.2.6.2 - Configuring a Control as a
Broadcast Acknowledger ........ 32
4.2.6.3 - Setting Time and Date .......... 32
4.2.6.4 - Alarm Configuration Table ...... 33
4.2.6.5 - Master/Slave Configuration .....35
4.3 - Cooler Interlock Contact ........................36
4.4 - Cooler heater control ........................... 36
4.5 - Oil heater control .......................... 36
4.6 - Motor cooling control without plate exchanger
economizer ....................................36
4.7 - Motor cooling control without sub cooling plate
exchanger economizer ..........................37
4.7.1 - Motor cooling with TQ feedback Signal Control 37
4.8 - Capacity Control ...............................38
4.8.1 - Logic Description ....................... 38
4.8.1.1 - Basic Logic ................... 38
4.8.1.2 - Z Multiplier Calculation ........ 38
4.8.1.3 - Overrides .................... 39
4.9 - Compressors & loaders loading sequence ....... 40
4.9.1 - General Description ..................... 40
4.9.2 - Compressor capacity determination ...... 41
4.9.3 - Staged Loading Increasing Capacity Logic 41
4.9.4 - Equal Loading Increasing Capacity Logic
with close control = NO ................. 41
4.9.5 - Equal Loading Increasing Capacity Logic
with close control = YES ................ 42
4.9.6 - Equal Loading Decreasing Capacity Logic
with close control = YES ................ 42
4.9.7 - Equal Loading Decreasing Capacity Logic
with close control = NO ................. 43
4.9.8 - Staged Loading Decreasing Capacity Logic
with close control = NO ................. 43
4.9.9 - Staged Loading Decreasing Capacity Logic
with close control = YES ................ 44
4.10 - EXV Control .................................. 45
4.10.1 - General ...............................45
4.10.2 - Overrides ............................. 45
4.11 - Air Cooled Condensing Pressure Control ....... 46
4.12.1 - Air Cooled Condensing Pressure Control -
Fan staging with AUX board ................. 46
4.12.2 - Air Cooled Condensing Pressure Control -
Fan staging ................................ 46
4.13 - Water Cooled Condensing Pressure Control .... 47
4.14 - High Pressure Override .......................48
4.15 - High Current Override ......................... 48
CONTENTS
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page:2 /98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.16 - Stopping Function ............................ 48
4.16.1 - Stopping a compressor by capacity
unloading ............................. 48
4.16.2 - Stopping the unit by manual command
(OFF) ................................. 48
4.16.3 - Stopping a circuit by failure ............. 48
4.17 - Oil pressure control ........................... 49
4.17.1 - Oil pressure setpoint determination .....49
4.17.2 - Oil pump control ....................... 49
4.17.3 - Low oil pressure alarm determination .... 49
4.17.4 - Differential Oil Pressure Setpoint 1
alarm condition summary ............... 50
4.18 - Reclaim Operation ............................51
4.18.1 - General Description ...................51
4.18.2 - Reclaim to Air Cooled Changeover
Initiation ............................... 51
4.18.3 - Air Cooled To Reclaim Changeover
Initiation ............................... 52
4.18.4 - Reclaim Operation hr_status
Description ............................ 52
4.18.5 - Reclaim Operation Using Air Cooled
Exchanger ............................ 52
4.18.6 - Reclaim Condenser Water Valve Control 52
4.18.7 - Reclaim Condenser Heater Control ..... 52
4.19 - Two Units Master/Slave Control ................ 53
4.19.1 - General ...............................53
4.19.2 - Abnormal Conditions .................. 55
5 - CCN
ALARM MESSAGES ........................... 57
6 - CCN
COMPATIBILITY .............................. 60
7 - PRO_DIALOG
4 DOWNLOADER ADDENDUM
INFORMATION .................................... 60
Appendix A - CCN DIPSLAY, SETPOINT, MAINTENANCE,
CONFIGURATION TABLE SCREENS ....... 61
Appendix B - CCN Variables ............................ 76
Appendix C - Wiring Schemes ..........................
83
Appendix D - JBUS memory with GX& HX
default configuration ........................ 96
Appendix E - SAM Screen ..............................97
Appendix F - CCN Network Example ..................... 98
CONTENTS
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page:3 /98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
1 - INTRODUCTION
1.1 - ABOUT THIS MANUAL
This manual is intended to be used as an additional guide for using and configuring the Pro-Dialog control for the 30GX & HX chillers. The use of this document does not substitute the IOM.
This manual is intended for use by Service organizations inside the Carrier corporation. It is delivered on the express condition that it is not to be disclosed, reproduced in whole or in part, or used for manufacture by anyone other than Carrier Corporation.
1.2 - MANUAL STRUCTURE AND CONTENTS
This manual includes the following sections:
v Introduction v Product general description v Hardware description v Control description v Appendixes
The introduction and product general description sections contain information about this manual as an overview of the 30GX&HX Pro-Dialog Plus controls.
The hardware section provides complete information on boards, devices and connections used by the product. The control description section is divided in several subsections. First provides a main description of hardware
configuration. This subsection provides sufficient information to runs the control in the most operating cases. For more complete information, use the remaining sections and also IOM. Second subsection describes all the unit configuration and the methods to modify it. The last subsections describe the unit control logic’s.
2 - GENERAL DESCRIPTION
2.1 - GENERALITIES
PRO-DIALOG is a system for controlling units which use screw compressors:
w Dual circuits w Air cooled and water cooled chillers w Non reversible heat machines
PRO-DIALOG controls compressors and loaders needed to maintain the desired leaving or entering water control point. It automatically sets the position of the electronic expansion valve to maintain a correct refrigerant flow in the cooler. For air cooled units it controls the operation of the fans to maintain the correct condensing pressure in each circuit.
Safety circuits in the unit are constantly monitored by PRO-DIALOG to ensure its safe operation. PRO-DIALOG
also gives access to a Quick Test program covering all inputs and outputs excepted compressors outputs. The control features of the 30GX&HX Pro-Dialog Plus are divided into standard features and options
(additional board needed):
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 4/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Standard features:
w Local control w Remote control (external contacts) w CCN control w Compressor & loader sequence control (up to 4 compressors - two loaders per compressor) w Cooler leaving or entering fluid temperature control w Ramp loading w Delay at startup w Circuit & Compressors loading sequence optimization w Heat machine condenser entering or leaving fluid control w Head pressure control w Cooling dual setpoints control w Temperature reset w Outdoor temperature monitoring w Demand limit control w High pressure and high current override w Cooler and Condenser pump control w Oil temperature control w Motor temperature control w Safety lock control w Quick test function w Diagnostics function w Local Interface Display with Metric units w Digital pressure gauges through the main interface w Display of all I/O and other data w CCN Network compatibility w Occupancy and dual setpoint schedules w SAM (LID 1B) compatibility w Alarm POC w System Manager compatibility w Integrated two chillers master/slave control
Available options With optional board:
w Varifan control w Condenser water valve control w Reclaim sensors w Cooler heater control
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 5/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
xx Condenser Varifan or Water Valve 0-10 Vdc 10-0 Vdc 4-20 mA 20-4 mA
No confi
g
uration required Oil Transducers On all compressors
xx Reclaim Condenser Water Valve
xx Heat Reclaim Sensors
xx Condenser Sensors
x Dela
y
at startu
p
x Cooling and heating Capacity Adjustment
(
z multiplier
)
x Ramp Loading (Heat & Cool
)
No configuration required Setpoint Control (single or dual
)
x Reset Type Select (Heat & Cool
)
x Demand Limit Type Select
x Loading Sequence Equal Sta
g
ed
XCondenser Pum
p
Control Select
XEnterin
g
Fluid Control
xCooler
pump
#1 and # 2 control sequence
xx**Water
pump p
eriodical quick start sequence
xx**Time and OAT broadcast ca
p
abilit
y
xx**Night capacity limitation mode
xx**Ni
g
ht head pressure control mode
xx**Unit on/off schedule control
x Com
p
ressor Number (1 to 4) & Capacit
y
xEconomizer Motor cooling TQ valve feedback
si
g
nal
xxxCooler Heater Select
xx Fans
2 Separate Circuits with 1 to 8 fans per circuit
x
EXV 1500 steps = Mueller, unipolar, 33 steps/s
No confi
g
uration required Loader ( 2 per compressor
)
x Compressor Number (1 to 4) & Capacit
y
xLarge Band Oil Transducer Select
xEconomizer Select
x Cooler Fluid Type Water Medium Brine Low Tem
p
erature Brine
xx
x Heat Reclaim Option
No confi
g
uration required Refrigerant R134
x Chiller Type Air Cooled Water Cooled Heat Machine
USER
CONFIG
SERVICE
CONFIG
FACTORY
CONFIG
HARDWARE
OPTION
FUNCTIONS
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 6/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
xTwo units Master/Slave Control
x FSM & CSM II Control
x Close Control Select
x Maximum Current Override
x Maximum Condensin
g
Temperature Override
USER
CONFIG
SERVICE
CONFIG
FACTORY
CONFIG
HARDWARE
OPTION
FUNCTIONS
** : require a CCN/Clock board All Pro-Dialog controls can work either autonomously or they can be interfaced with the Carrier Comfort Network (CCN). In the later case a communication data cable is used to connect the unit to the CCN communication bus. When Pro-Dialog system operates autonomously it retains all of its own control capabilities but does not offer the functionality of the CCN network.
2.2 - SOFTWARE REFERENCE NUMBER
This software is referenced under the 15 digits software reference number:
CSA-SR-208410XX The two last digits (XX) provides the software version (e.g. 2.0). 15 digits reference number can be displayed in the CCN configuration Ctrl_ID table through the Building
Supervisor, the Network Service Tool or the 30GX&HX Downloader. Unit Main Interface Configuration Menu allows to display the software version: item #13, user 1 menu.
2.2 - Abbreviations Used
In this manual, the refrigeration circuits are called circuit A and circuit B. The compressors in circuit A are labeled A1, and A2. Those in circuit B are B1 and B2.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 7/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3 - HARDWARE DESCRIPTION
3.1 - PRODUCT COMPONENT
This control shall employ the following electronic modules:
Basic Board 32 GB 500 182 EE NRCP Board 32 GB 500 052 EE CCN and RTC Board 32 GB 500 062 EE 4 x DO Board (087) OP 12AS 004 EE 4xAI - 2xAO Board OP 12AS 005 EE 8 x DO Board (Auxiliary 2) 32 GB 500 312 EE 8xDO - 4xAI - 2xAO Board (Auxiliary 1) 32 GB 500 322 EE EXV Board 32 GB 500 192 EE Screw Compressor Protection Module 32 GB 500 232 EE Local Interface Device 30GX dual circuits 32 GB 500 092 EE Local Interface Device 30HX dual circuits 32 GB 500 112 EE Local Interface Device 30GX single circuit 32 GB 500 082 EE Local Interface Device 30HX single circuit 32 GB 500 102 EE
This control shall employ the following sensors modules:
Thermistors HH79NZ047C (small size)
HH79NZ059C (large size) Low Pressure Transducer OP12DA040 EE High Pressure Transducer OP12DA039 EE Large Band Oil transducer OP12DA057 (for unit operating in low ambient)
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 8/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
COMPONENT USAGE
1[1
]1[1]1[1]1[1]
AUX 1 BOARD
1
[1]1[1]1[1]1[1]
4 x AI-2xAO BOARD
2
[2]2[2]2[2]
1PD4 - EXV BOARD
4321PD4 - SCPM BOARD
1111PD4 - BASIC BOARD
4321
NUMBER OF COMPRESSORS
COMPONENTS
UNIT TYPE : WATER COOLED
2[1
]2[1]2[1]1[1]
AUX 1 BOARD
1
[1]1[1]1[1]1[1]
4 x AI-2xAO BOARD
1
[4]1[4]1[4] 1[4]
NRCP BASIC BOARD
1
[3]1[3]1[3]1[3]
AUX 2 BOARD (8xDO
)
1[3
]1[3]1[3]2[3]
4x DO BOARD
2
[2]2[2]2[2]
1PD4 - EXV BOARD
4321PD4 - SCPM BOARD
1111PD4 - BASIC BOARD
4321
NUMBER OF COMPRESSORS
COMPONENTS
UNIT TYPE : AIR COOLED - 2 FAN STAGES PER CIRCUIT MAX
1[1
]1[1]1[1]1[1]
AUX 1 BOARD
1
[1]1[1]1[1]1[1]
4 x AI-2xAO BOARD
1
[4]1[4]1[4]
0NRCP BASIC BOARD
1
[3]1[3]1[3]1[3]
AUX 2 BOARD (8xDO
)2[3]2[3]2[3]2[3]
4x DO BOARD
2
[2]2[2]2[2]
1PD4 - EXV BOARD
4321PD4 - SCPM BOARD
1111PD4 - BASIC BOARD
4321
NUMBER OF COMPRESSORS
COMPONENTS
UNIT TYPE : AIR COOLED - MORE THAN 2 FAN STAGES (if no AUX board) or MORE
THAN 4 FAN STAGES
(
AUX BOARD) PER CIRCUIT
1 - additional 4 x AI - 2 x AO board or 8xD0-4xAI-2xAO board required for varifan or reclaim sensors or water valve option 2 - Second EXV board is required for motor cooling using EXV valve on economizer units 3- 4xDO board or 8xDO board is required to control fans. 4xDO is also used to control hot gas bypass valve on units with single compressor. 4-additional NRCP board is required for reclaim option or cooler heater option.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 9/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.2 - Basic Board The PD4 - Basic board is 24VAC power supplied. It contains 8 Discrete Inputs (Switch type), 8 Digital Outputs (5
triacs and 3 relays), 10 Analog Inputs (five thermistors and four pressure transducers) and 1 analog input (0-10 Vdc) . See the schemes in Appendix E. The software is contained in a Flash EPROM (downloadable only with Downloader). All the setpoints, runtime and configuration parameters are contained in an EEPROM (data storage at power down).
AllSafety Critical Signal (for Contactor Failure)26J3
AllAlarm Circuit B25J3
AllAlarm Circuit A24J3
Air cooledOil Heater Circuit B23J2
Air cooledOil Heater Circuit A22J2
All excepted air cooled without reclaim option
Condenser Pump21J2
AllCooler Pump #220J2
AllCooler Pump #119J2
AllCooler pump default18J5
All excepted air cooled without reclaim option
Condenser flow switch17J5
AllElectrical box thermostat & network power reverse
phase detection
16 a & 16 bJ5
AllCooler flow switch & customer interlock (lock_1)15 a & 15 bJ4 & J5
AllDemand limit switch14J4
All excepted heat machineHeat Reclaim switch 13J4
Heat machineHeat Cool switch 13J4
AllDual setpoint switch12J4
AllRemote Control switch status11J4
All0-10 VDC setpoint reset signal or demand limit signal10J8
AllCircuit B suction pressure9J7D
AllCircuit B discharge pressure8J7C
AllCircuit A suction pressure7J7B
AllCircuit A discharge pressure6J7A
Water cooled and heat pumpCondenser entering water temperature
5
J6
Water cooled and heat pumpCondenser leaving water temperature
4
J6
Ai
r coole
d
Outside Temperature 4J6
Master/SlaveMaster/Slave common piping fluid temperature3J6
AllCooling entering water temperature2J6
AllCooling leaving water temperature1J6
UNIT TYPEFUNCTIONCHANNELTERMINAL
3.2 - CCN/Clock Option Board
(factory installed)
The PD4 - Global chiller controller has a small option board that can be connected to the Basic Board via a single 10 pin header and 4 metal standoff. This option board contains one RS-485 driver for CCN communication, a real time clock and super cap for two weeks backup. There are two connectors for CCN. One is a 3 pin screw connector ( 1= + signal, 2 = ground signal, 3 = - signal) and the other is a 6 pins phone jack.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 10/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.3 - Screw Compressor Protection Module This board shall monitor compressor pressure transducer, temperature sensors, oil level, high pressure switch,
motor cooling solenoids, oil pumps, motor current, compressor wye-delta startup and compressor protection.
3.3.1 Screw Compressor Module Layout
N.B :Only Y
✁✁✁✁
dip switch of the 4 is used to configure start-delta startup procedure (when in ON
position), the 3 others shall remain OFF ! If not, MTA header configuration alarm will occur.
Oil pressure0-5V pressure transducer 44J10B
Economizer
p
ressure0-5V pressure transducer33J10A
Dischar
g
e Gas Temperature 5K thermistor 22J9
Com
p
ressor temperature5K thermistor 11J9
Usual FunctionsTypeChannel#AI #*Connector
Current Phase #3Current sensor 3-3J8
Current Phase #2Current sensor 2-2J8
Current Phase #1Current sensor 1-1J8
Usual FunctionsTypeChannel#CT #*Connector
Oil levelDry contact62J6
Hi
g
h PressureDry contact51J7
Main FunctionsTypeChannel#DI #*Connector
Loader #2
24VAC, 10VA
Triac118J2
Loader #1
24VAC, 10VA
Triac107J2
Motor cooling #2 or economizer valve for circuit which has 2 com
p
ressors
24VAC, 10VA
Triac146J2
Motor coolin
g
#1
24VAC, 26 VA
Triac135J2
Oil solenoid
24VAC ,10VA
Triac124J2
Oil
pump
115VAC,145VA,-
Triac93J4
Com
p
ressor output “Y”
115VAC, 70VA,
Relay/TRiac82J3
Com
p
ressor output “D”
115VAC, 250VA
Relay/Triac71J3
Main FunctionsLoad max
(
Voltage,power
)
TypeChannel#DO #*Connector
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 11/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.3.2- Compressor Part Number / MTA header configuration
0 0 0 1 0 1 0 1
92 39
06NW2146S7N
0 0 0 1 1 1 1 1
112 46
06NW2174S7N
0 0 1 0 1 0 1 1
136 56
06NW2209S7N
0 1 0 0 1 0 1 0
198 80
06NW2300S7N
0 0 1 0 0 0 0 0
114 39
06NA2146S7N
0 0 1 1 1 0 0 1
164 66
06NW2250S7N
0 0 1 0 1 1 1 0
142 46
06NA2174S7N
0 0 1 1 1 1 0 0
170 56
06NA2209S7N
0 1 0 1 0 1 0 0
218 80
06NW2300S5E
0 1 0 0 1 1 0 1
204 66
06NA2250S7N
0 1 0 1 1 1 1 1
240 80
06NA2300S5N
0 1 1 1 1 1 0 0
298 80
06NA2300S5E
Compressor MTA Header Config
MSB(8 . . . . . . . 1) LSB
MTA
(for 400V)
TonsCompressor phase 3 Part Number
3.1.4 - 4xDO BOARD
The 4xDO board has 4 digital outputs capable of switching 24 VAC at 1 amp numbered from 1 to 4 on connector J4. They have a common point numbered 12 on connector J4. D0 #1 and Do # 2 shall support 1 fan D0 #3 shall support 1 fan if circuit has less than 5 fans. It shall support 2 fans if circuit has more than 4 fans. D0 #4 shall support 1 fan if circuit has less than 6 fans. It shall support
2 fans if circuit has 6 fans. 3 fans if circuit has 7 fans. 4 fans if circuit has 8 fans.
3.1.4.2 - Terminal J4 Description
12
1212
12 12
1212
1211
1111
11
DO #4
DO #4DO #4
DO #4
DO #3
DO #3DO #3
DO #3
DO #2
DO #2DO #2
DO #2
DO #1
DO #1DO #1
DO #1
24 VAC DO
24 VAC DO24 VAC DO
24 VAC DO
POWER SUPPLY
POWER SUPPLYPOWER SUPPLY
POWER SUPPLY
TRIAC
TRIACTRIAC
TRIAC TRIAC
TRIACTRIAC
TRIAC
TRIAC
TRIACTRIAC
TRIAC
TRIAC
TRIACTRIAC
TRIAC
TO CONTACTOR # 1
TO CONTACTOR # 1TO CONTACTOR # 1
TO CONTACTOR # 1
TO CONTACTOR # 2
TO CONTACTOR # 2TO CONTACTOR # 2
TO CONTACTOR # 2
TO CONTACTOR #3 (or and #4)
TO CONTACTOR #3 (or and #4)TO CONTACTOR #3 (or and #4)
TO CONTACTOR #3 (or and #4)
TO OTHER CONTACTORS
TO OTHER CONTACTORSTO OTHER CONTACTORS
TO OTHER CONTACTORS
pins 12 are connected together
pins 12 are connected togetherpins 12 are connected together
pins 12 are connected together
4444
33332222
1111
TERMINAL J4
TERMINAL J4TERMINAL J4
TERMINAL J4
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 12/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.1.5 - AUX Boards
3.1.5.1 - General
R S V
CH 4
J7
CH 1
--
R S V
--
J2
--
CH13
75 mm (2.95 in)
CH 3
J4
CH 2
PD4-AUX1
--
------
32GB 500 322 EE
-- G +
12
STATUS
--
T P V
CH13
CEPL130487-01
J3
CH 12
J1
24VAC
--
------
SIO
J9
143 mm ( 5.60 in )
SIO
CH 11
--
11
CH
10
--
J5
T P V
CH14
l
3 2 1
--
3 2 1
CH 8
--
-- G +
CH 7
--
J6
CH14
CH 6
l
--
J8
CH 5
CH 9
The
AUX1
board shall allow:
wthe control of 1 to 8 fan stages; wthe monitoring of 4 temperatures or 2 temperatures and 2 pressures. wthe control of 2 Varifan or two water valves
The AUX2 board shall allow:
wthe control of 1 to 8 fan stages.
Discrete outputs requirements
: AUX1 and AUX2
Fan 8 - circuit A , 4 or 8 circuit B88
Fan 7 - circuit A , 3 or 7 circuit B/Reclaim option, condenser heater
77
Fan 6 - circuit A
,
2 or 6 circuit B66
Fan 5 - circuit A
,
1 or 5 circuit B/ Reclaim valve B55
J3
Fan 4 - circuit A or circuit B/ Pum
p
down valve B44
Fan 3 - circuit A or circuit B33
Fan 2 - circuit A or circuit B/ Reclaim valve A 22
Fan 1 - circuit A or circuit B/ Pum
p
down valve A 11
J2
AUX1
&
AUX2
Main FunctionsChannel#DO #ConnectorBoard
All are standard 24 VAC/±10%. All 24Vac common ground must be connected together on board and to 24Vac ground pin of J1. All DO’s total consomption = 115VA
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 13/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.1.6 - EXV BOARD
The EXV board shall be able to control 2 EXV’s and 2 thermistors.
Analog inputs requirements
Economizer Motor Cooling TQ Valve Feedback Signal Circuit B5/10 K thermistor2J3 (TH B
)
Economizer Motor Cooling TQ Valve Feedback Signal Circuit A5/10 K thermistor1J3 (TH A
)
Usual FunctionsTypeAI
#*
Connector
Discrete output requirements The EXV board shall be able to drive both unipolar and bipolar stepper motors via a common connector. The
default configuration shall be unipolar, 30 steps/s step rates and 1500 steps range such as to allow easy retrofit with Pro-Dialog phase 1, 2 and 3 units fitted with Mueller Brass EXV’s. It shall be able to handle 12V @ 0.5 A per coil and maintain a step rate of at least 200 steps per second (unipolar or bipolar).
Note: board shall be able to handle a total coil load of 1 Amp for unipolar and 2 Amps for bipolar. Connection to the EXV shall be done through two Molex, 5 pin, 3.91 pitch (one per EXV) [J2A & J2B].
12VDC (for unipolar stepper motor)Coil 4Coil 3Coil 2Coil 1
54321
Connector J2A & J2B - Pins description
3.1.7 - 4xAI-2xAO BOARD
This board provides 4 analog inputs (labeled AI #1, AI #2, AI #3, and AI #4 on the terminal J2) and 2 analog outputs (labeled AO #1 and AO #2 on the terminal J1). It allows to use the following features:
w Optional reclaim thermistors when reclaim option is not used w Remote discharge transducer on remote condenser on split units. w Optional varifan on air cooled units or water valve on water cooled units
Each input can be independently configured with a bridge allowing to close 3 pair of pins named T,C or V.
V: Transducers 5 Volts power supply 1: Signal R: -
V - 1 - RPressure transducer (remote discharge pressure circuit B)
V
Carrier thermistor: HH 79NZ 047, 5K@ 25°C1 - RunusedT,C
AI #2
V: Transducers 5 Volts power supply 1: Signal R: -
V - 1 - RPressure transducer (remote discharge pressure circuit A)
V
unused1 - RunusedT,C
AI #1
REMARKSPINSFUNCTIONBRIDGE
POSITION
ANALOG
INPUT
J2
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 14/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
1: + R: -
1 - RunusedC
V: Transducers 5 Volts power supply 1: Signal R: -
V - 1 - Rnot usedV
Carrier thermistor: HH 79NZ 047, 5K@ 25°C1 - RReclaim entering
thermistor
T
AI #4
1: + R: -
1 - RunusedC
V: Transducers 5 Volts power supply 1: Signal R: -
V - 1 - Rnot usedV
Carrier thermistor: HH 79NZ 047, 5K@ 25°C1 - RReclaim leaving
thermistor
T
AI #3
REMARKSPINSFUNCTIONBRIDGE
POSITION
ANALOG
INPUT
J2
Each output can be independently configured with a bridge allowing to close 2 pair of pins named C or V.
6: + R: -
6 - R4 - 20 mA Varifan
circuit B
C
6: + R: -
6 - R0-10 Vdc Varifan circuit
B
V
AO #2
5: + R: -
5 - R4 - 20 mA Varifan
circuit A or water valve
C
5: + R: -
5 - R0- 10 Vdc Varifan circuit
A or water valve
V
AO #1
REMARKSPINSFUNCTIONBRIDGE
POSITION
ANALOG OUTPUT
J1
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 15/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.1.8 - Aquasnap Basic Board
This board is used on global chiller as slave board for air cooled units with reclaim option or cooler heater option. It contains 8 Discrete Inputs (switch type), 10 Digital Outputs (8 triacs and 2 relays), 6 Analog Inputs (four 5K or 10K thermistors and two active pressure transducer types) and 1 analog output (0-10 Vdc).
Cooler heater option, condenser and cooler refri
g
erant isolation solenoid circuit B
Relay outputDO_1025
Cooler heater option, condenser and cooler refri
g
erant isolation solenoid circuit A
Relay outputDO_924
Cooler heater out
p
utTriacDO 823
unusedTriacDO
_
722
Reclaim o
p
tion, pumpdown solenoids circuit BTriacDO 621
Reclaim o
p
tion, pumpdown solenoids circuit ATriacDO_520
Reclaim o
p
tion, condenser heater TriacDO 419
unusedTriacDO 318
reclaim option or cooler heater option, circuit B, refriger ant c onde ns er ent eri ng so len oid
TriacDO_2
4
17
reclaim option or cooler heater option, circuit A, refri
g
erant condenser entering solenoid
TriacDO_1
3
0
unusedRela
y
inputDI’s 08 to 15
Reclaim o
p
tion, condenser water valve0 - 10 VdcAO_1 07
Reclaim o
p
tion pumpdown pressure circuit B Pressure transducer 0 - 5 VdcAI 6 06
Reclaim o
p
tion pumpdown pressure circuit APressure transducer 0 - 5 VdcAI_5 05
unusedThermistor 5K or 10KAI 3 03
,
04
Reclaim o
p
tion entering temperatureThermistor 5K or 10KAI 2 02
Reclaim o
p
tion leaving temperatureThermistor 5K or 10KAI_1 01
FUNCTIONTypeI/OChannel Number
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 16/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3.2 - Pressure sensors
They are used to measure in each circuit :
w Discharge gas pressure w Suction pressure w Economizer pressure
and in each compressor :
w Oil pressure w Economizer pressure on first compressor and also in the second compressor if unit is not equipped
with economizer
They are electronic sensors which linearise the output signal and deliver a 0 to 5 Vdc to either the basic board or to an analog board. Three types of sensors are used.
3.2.1 - High pressure side sensors
They are used to measure discharge pressure and oil pressures when large band oil pressure transducer is not selected. Carrier part: OP12DA039
High pressure side transducer curve
3.2.2 - Large band pressure sensors
They are used to measure oil pressures for unit operating with low ambient (when large band oil pressure transducer is selected).
Carrier part:
OP12DA057
Large band oil pressure transducer curve
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 17/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
50 100
150
200
250
450
500
689
2068
2414
3103
2758
4
2
0
Voltage (VDC)
Voltage (VDC)Voltage (VDC)
Voltage (VDC)
kPa
PSI
3
1
5
3447
1724
345
1034
Pressure
PressurePressure
Pressure
1379
350
300 400
-6.6
100
155
420
500
1904
2252
2895
2670
4
2
Voltage (VDC)
Voltage (VDC)Voltage (VDC)
Voltage (VDC)
kPa
PSI
3
1
5
3447
1484
-45
689
Pressure
PressurePressure
Pressure
1068
327
276 387
50 345
215
3.2.3 - Suction Pressure and Economizer Pressure sensors
These are in the low pressure side. Suction pressure transducer takes the place of the low pressure switches, low pressure gauges and the low pressure safety switch (where these are usually fitted). Economizer pressure is used to measure the intermediary pressure between low and high pressure. The oil pressure is subtracted from
this pressure to determine the oil differential pressure for oil pressure safety purpose.
Carrier part: OP12DA040
Low pressure transducer curve
3.3 - THERMISTORS
All thermistor, excepted the reset sensor, have similar characteristics (see next page). They have Carrier Part No. HH 79 NZ 047
3.3.1 - Discharge gas temperature
This is installed on the discharge pipe of each compressor. It is used to control the discharge superheat. The discharge gas temperature (lowest discharge compressor temperature or average discharge temperature of both compressors) is subtracted to the saturated condensing temperature to determine the discharge superheat.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 18/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
20 40
60
80
100
180
200
276
828
965
1241
1103
4
2
0
Voltage (VDC)
Voltage (VDC)Voltage (VDC)
Voltage (VDC)
kPa
PSI
3
1
5
1379
689
138
414
Pressure
PressurePressure
Pressure
552
140
120 160
5K Resistor: Resistance vs Temperature Curve
602,480,01 694,0
52,0
5 203,
224
,020 075,9-4,0
612,679,51 725,151,55 321,223,520 606,4-4,5
2
85,2107,0
623,279,0
1 7
56,8
51,0
5
442,22
3,0
21 152
,6-5,0
292,1106,5634,078,51 789,150,55 566,422,521 715,7-5,5
2
98,6106,0
645,278,01 822,150,0
5 693,922,0
22 2
95,6-6,0
305,3105,5656,877,51 855,749,55 824,621,522 893,2-6,5
311,6105,0
668,677,01 890,149,0
5 958,
721
,023 509,0-7,0
317,9104,5680,876,51 925,148,56 096,320,524 143,6-7,5
323,8104,0
693,376,01 960,948,0
6 237,520,0
24 797
,8-8,0
329,7103,5706,175,51 997,447,56 382,319,525 472,2-8,5
335,3103,0719,275,02 034,
747
,0
6 530,919,026 167,5-9,0
341,1102,5732,674,52 072,846,56 683,418,526 884,4-9,5
346,3102,0746,574,0
2 111,74
6,0
6 839,818,0
27 62
3,8-10,0
351,5101,5760,673,52 151,545,57 000,317,528 386,3-10,5
356,7101,0775,073,0
2 192,24
5,0
7164.917
,029
172,7-11
,0
361,6100,5789,872,52 233,844,57 333,916,529 984,0-11,5
366,5100,0
804,872,0
2 27
6,344,07 507,216,0
30 821,0
-12
,0
371,199,5820,271,52 319,943,57 685,115,531 684,6-12,5
375,8
99,0
836,071,02 364,443,07 867,715,0
32 575,6-13,0
380,398,5952,070,52 410,042,58 055,014,533 495,2-13,5
384,798,0
868,470,0
2 4
56,642,0
8
247,214
,0
3
4 444,2-14
,0
389,097,5885,169,52 504,441,58 444,513,535 423,7-14,5
393,3
97,0
902,169,02 553,341,0
8 469,913,0
36 434,
7-1
5,0
397,696,5919,468,52 603,440,5 8854.712,537 478,4-15,5
4
01,8
96,0
937,168,02 654,740,0
9068.012
,0
38 555,9-16,0
406,095,5955,167,52 707,239,5 9287.011,539 668,3-16,5
41
0,3
95,0
973,467,0
2 761,1
39,0
9 511,
711
,040 816,9
-17
,0
414,594,5992,166,52 816,238,5 9742.510,542 002,9-17,5
41
8,8
94,01 011,0
66,02 872,8
38,0
9979.31
0,043
227
,6-18,0
423,093,51 030,365,52 930,737,510 222,6 9.544 492,4-18,5
427
,493,01 050,0
65,02 990,137,010
472
,3
9.045 7
98,6-19,0
431,892,51 069,964,53 051,036,510 728,88,547 147,7-19,5
4
36,3
92,01 090,264,0
3
113,4
36,010 992,18,048 541,
1-2
0,0
440,991,51 110,963,53 177,535,511 262,77,549 980,4-20,5
44
5,791,0
1 131
,8
63,0
3
243,1
35,0
11 54
0,5
7.0
5
1 467
,0
-21
,0
450,690,51 153,262,53 310,434,511 826,0 6.553 002,7-21,5
4
55,6
90,0
1 174
,8
62,0
3 379,434,0
12 119,2
6,0
54 589,
1-22
,0
460,889,51 196,961,53 450,233,512 420,55,556 227,9-22,5
4
66,189,0
1 21
9,3
61,0
3 522,9
33,0
12 7
30,15,0
57 920,9-23,0
571,688,51 242,160,53 597,332,513 048,3 4.559 670,0-23,5
477
,488,0
1 2
65,260,0
3 673,732,013 375,34,0
6
1 47
6,9
-24
,0
483,287,51 288,759,53 752,131,513 711,43,563 343,7-24,5
4
89,487,01 312,6
59,0
3 832,5
31,0
14
056,9 3.0
65
272,4-2
5,0
495,786,51 336,958,53 915,030,514 412,2 2.567 265,0-25,5
502,3
86,01 361,6
58,0
3 999,6
30,0
14 777
,52,0
69 323,
7-2
6,0
509,285,51 386,857,54 086,329,515 153,1 1.571 450,6-26,5
516,285,0
1 412
,3
57,0
4 175,42
9,015 539,51,073 648,0
-27
,0
523,684,51 438,356,54 266,728,515 936,90,575 918,3-27,5
531,284,0
1 464,7
56,04 630,428,016 345,70,078 263,9-28,0
539,183,51 491,655,54 456,627,516 766,3-0,580 687,1-28,5
547,283,01 519,0
55,04 555,
227
,0
17 1
99,
1-1
,0
83 190,
7-2
9,0
555,782,51 546,954,54 656,426,517 644,5-1,585 777,0-29,5
564,482,01 575,254,0
4 7
60,226,018 102,9-2,0
88
44
9,0
-
30,0
573,481,51 604,153,54 866,825,518 574,8-2,591 209,3-30,5
582,8
81,01 633,5
53,04 976,025,019 060,6-3,0
94 060,8
-31
,0
592,480,51 663,552,55 088,124,519 560,8-3,597 006,4-31,5
602,480,01 694,0
52,0
5 203,
224
,020 075,9-3,5100 049,0
-32
,0
(
OHMS
)
(°C)
(
OHMS
)
(°C)
(
OHMS
)
(°C)
(
OHMS
)
(°C)
(
OHMS
)
(°C)
Resistanc
Temp.Resistanc
Temp.Resistanc
Temp.Resistanc
Temp.Resistanc
Temp.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 19/98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.2 - CONFIGURATION
4.2.1 - General
Four types of configuration are available:
wThe factory configuration. It describes the "hardware" structure of the unit (e.g. the number of compressors,
valve...). This configuration is accessible through the Main Interface Factory menu Menus or the Network Service Tool and can be done by Carrier factory or service only.
wThe Service configuration. It allows to modify operating parameters. This configuration is accessible
through the Main Interface Service Menus or the Network Service Tool and can be done by Carrier factory or service only.
wThe User configuration. It allows to modify a limited number of simple parameters (i.e. loading sequence,
start-up delay, cooler pumps control, reset select...). This configuration can be done through the Main Interface or through the Network Service Tool. This configuration can be modified by the customer.
wThe network configuration. It allows to modify parameters used by network functions (i.e. Alarm POC,
Broadcast ...). This is accessible through the Building Supervisor or the Network Service Tool.
4.2.2 -Main interface configuration sub menu tree structure
‘broAdCASt’’
7
S
‘’HoLidAY’’
6
M
‘’SCHEduLE 2’’
5
E
‘’MAStEr SLAvE’’‘’SCHEduLE 1’’
4
T
‘’SErViCE 3’’‘’dAtE’’
3
I
"FACtorY 2 MEnu"‘’SErViCE 2’’‘’USEr 2’’
2
"FACtorY 1 MEnu"‘’SErViCE 1’’‘’USEr 1’’
1
"FACtorY MEnu"‘’SErViCE MEnu’’‘’USEr MEnu’’
0
FACTORYSERVICEUSER
CONFIGURATION SUB MENUS
MAIN INTERFACE FACTORY CONFIGURATION SUB MENU TREE STRUCTURE
TQ_r_fbk (TQ valve feeddback
)
19
pd4_
aux (aux board select
)
18
exvb max (1500
)
17
exva max (1500
)
16
heat sel (idem version 1.x
)
15
cira lwt (idem version 1.x
)
14
eva
p_p
as (idem version 1.x
)
13
recl_opt (idem version 1.x
)
12
hr temp (idem version 1.x
)
11
cpb2 mta (idem version 1.x
)
10
cpb1 mta (idem version 1.x
)
9
cpa2 mta (idem version 1.x
)
8
cpa1_mta (idem version 1.x
)
7
S
oil_sel (idem version 1.x
)
6
M
econ sel (idem version 1.x
)
5
E
hd selec (idem version 1.x
)
4
T
nb fan b (idem version 1.x
)
3
I
nb fan a (idem version 1.x
)
2
fac_passunit_typ (idem version 1.x
)
1
"FACtorY2 MEnu""FACtorY1 MEnu"
0
FACTORY 2FACTORY 1
FACTORY CONFIGURATION SUB-SUB MEN
US
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 20 /98
4.2.3 - Factory configuration
4.2.3.1 - Factory configuration from Service Tool
The Network Service tool allows to view and modify the factory configuration (table FACTORY in 'Modify Controller').
TABLE NAME: FACTORY PIC TABLE TYPE : 10H, instance 1
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 Chiller Type 1,2,3
1
1 - unit_typ
2 Circuit A Fan Stages Num 0 to 8
2
0 - nb_fan_a
3 Circuit B Fan Stages Num 0 to 8
2
0 - nb_fan_b 4 Varifan or W. Valves Sel 0/1/2/3/4 0 - hd_selec 5 Economizer Select Yes/No
3
No - econ_sel 6 Large Bd Oil Transducers Yes/No
4
No - oil_sel 7 Comp A1 Must Trip Amps 0 to 560
5
0 - mta_cpa1 8 Comp A2 Must Trip Amps 0 to 560
5
0 - mta_cpa2 9 Comp B1 Must Trip Amps 0 to 560
5
0 - mta_cpb1 10 Comp B2 Must Trip Amps 0 to 560
5
0 - mta_cpb2 11 Reclaim Sensor Select Yes/No
6
No - hr_tmp 12 Air Cooled Reclaim Sel Yes/No
7
No - recl_opt 13 Evaporator Number Pass 1 to 3
8
3 - evap_pas 14 Cooler LWT On Circuit A Yes/No
9
Yes - cira_lwt 15 Cooler Heater Select Yes/No
10
No - heat_sel 16 Factory Password 0 to 150
11
113 - fac_pass 17 EXV A Maximum Steps Numb 1500/15000
12
1500 - exva_max
18 EXV B Maximum Steps Numb 1500/15000
12
1500 - exvb_max
19 Motor Cool. TQ Feedback Yes/No
13
No - TQ_r_fbk
20 PD4 Aux Boards Select Yes/No
14
No - pd4_aux
Parameters from 1 to 16 in version 1.x are the same than those in the new version 2.X.
For Retrofit from verson 1.x to the new 2.x, it is better to write down in a paper, configuration item s from 1 to 16. Use Service Tool to upload all the configuration f rom version 1 (example address 1). Then use address search f unction to change the address to 2 before downloading the new software version 2.x. Use Service T ool to add a new controller with a dif fer ent address e (exam ple addres s 1 f or version 1 and address 2 for version 2). Once Upload conf iguration is done, fill factory configuration in FACTORY table and then download this.
1. 1 = air cooled. 2 = water cooled . 3 = heat machine
2. 0 = no fan
<
4 = each DO output of the 4xDO board support 1 fan .
>
5 = DO # 1 and DO # 2 support 1 fan each. DO # 3 support 2 fans DO # 4 support 1 fan if circuit has 5 fans max
DO # 4 support 2 fans if circuit has 6 fans max DO # 4 support 3 fans if circuit has 7 fans max DO # 4 support 4 fans if circuit has 8 fans max
nb : these fans are not controlled by a varifan. For pro_dialog 4 Auxiliary board select, each DO output of the Auxiliary board support 1 fan
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 21 /98
13. Yes = Use Pro_dialog 4 auxiliary boards instead of old 4xAO-2xAO board and 4xDO board No = Use old 4xAO-2xAO board & 4x DO board (shall be set to no for version 1 retrofit)
3. W hen this item is selected, both compressor use the common economizer transducer in the economizer. Otherwise, each compressor uses it own economizer transducer, located in the refrigerant injection pipe line, near the motor cooling valve. Economizer pressure represents the intermediary pressure between high pressure and low pressure. It is used to determine the oil differential pressure (oil pressure ­economizer pressure).
4. The use of large band oil pressure transducer is required for low ambient application and is only applied on oil pressure transducers since high pressure range transducer can not read pressure lower than 2.4 bars, Calibration is automatically determined each time the control is in OFF mode and both suction and discharge pressures are equalized. Differences between oil pressures and suction pressure are then stored as offset (if less than 0.4 bar).
5. MTA configuration is required for capacity calculation, motor current measurement and protection. This value shall match the one read from MTA header configuration on screw compressor board, if not an alarm will be generated.
6. If only reclaim sensor is selected and reclaim option is not, an 4xAI-2xAO board is required, and reclaim temperature sensor are used for information only.
7. Reclaim option requires an Aquasnap Basic board for reclaim entering and leaving temperatures, solenoids, an analogue output to control the reclaim condenser water valve, 2 transducers for reclaim pumpdown injection pressure.
8. This items indicates the number of pass the cooler fluid goes through the cooler. For example, if cooler enters from circuit A and goes out by circuit A and only 1 time, then a number of 2 shall be entered. This item is used for exv control when caculating cooler pinch.
9. This items indicates if cooler leaving temperature sensor is in the circuit A or not. If cooler leaving pipe line is on side A, then Yes shall be entered, otherwise, no shall be required. This item is used for exv control when caculating cooler pinch.
10. Cooler heater option requires an Aquasnap Basic board for refrigerant isolation solenoids and heater output.
11. Factory password is required when accessing the main interface factory menu. Factory password can be used to access to service and user configuration sub menus.
12. 1500 = For Muller valve, Unipolar, 1500 steps, 33 steps/s (1500 steps shall be kept !!!) 15000 = For Muller valve phase 3, Bipolar, 15300 steps, 300 steps/s (for future use,)
Note: schemes are described in appendix C.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 22 /98
4.2.3.2- Factory configuration from main interface
Economizer units with TQ feedback signal sensor-
y
es/notqr fbk19
Pro dialo
g
4 Aux boards select -
y
es/no
p
d4 aux18
EXV A Maximum Ste
p
s Number (Shall be left 1500
)
-1500 to 15000exva_max17
EXV A Maximum Ste
p
s Number (Shall be left 1500
)
-1500 to 15000exva_max16
Cooler heater select dis
play
ed on air cooled chiller onl
y-y
es/noheat sel15[1
]
Cooler leaving sensor on circuit A select-
y
es/nocira lwt14
Cooler number of
p
ass select-1 to 3eva
p
p
as13
Heat reclaim o
p
tion select-
y
es/norecl opt12[1
]
Reclaim sensors select-
y
es/nohr_tem
p
11[1
]
Compressor B2 Must Trip Amps. amps0 to 560cpb2_mta10[1
]
Compressor B1 Must Trip Amps. amps0 to 560cpb1 mta9[1
]
Compressor A2 Must Trip Amps. amps0 to 560cpa2 mta8[1
]
Compressor A1 Must Trip Amps amps0 to 560cpa1 mta7
Lar
g
e Band Oil transducer select-
y
es/nooil sel6
Economizer select-
y
es/noecon_sel5
Varifan or Water valve select-0,1,2,3,4hd
_
selec4
Number of fans on circuit B not controlled b
y
a varifan -0 to 8nb fan b3[1
]
Number of fans on circuit A not controlled by a varifan -0 to 8nb fan a2[1
]
Chiller type select-1/2,3,4unit t
yp
1
When selected t his item shall allow to return to the Configuration main menu.
-"FACTORY
MEnu"
-0
COMMENTSUNITSFORMATVARIABLEITEM #
Factory password-0 to 150fac_pass1
When selected t his item shall allow to return to the Configuration main menu.
-"FACTORY 2
MEnu"
-0
COMMENTSUNITSFORMATVARIABLEITEM #
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 23 /98
Economizer Tq valve Feedback Signal Control Wiring
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 24 /98
TQ output (done)
TQ output (done)
SCPM A1
SCPM B1
THA
THB
EXV BOARD
Connexion to be done (tq_r_fbk = yes)
4.2.4 - Service configuration
4.2.4.1 - Service1 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table SERVICE1. Unit shall be stopped and under CCN Operating Type control.
TABLE NAME: SERVICE1 PIC TABLE TYPE : 13H, instance 1
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 Cooler Fluid Type 1/2/3
1
1 - flui_typ
2 Head Pressure Diff Timer 10 to 120
2
90 sec head_tim
3 Head Pressure Diff 3.8 to 22
3
5 ^C head_dif
4 Prop PID Gain Varifan/Wv -20.0 to 20.0
4
1.0 - hd_pg
5 Int PID Gain Varifan/Wv -5.0 to 5.0
4
1.0 - hd_ig
6 Deri PID Gain Varifan/Wv -20.0 to 20.0
4
1.0 - hd_dg
7 Cir A Superheat Setpoint 8.3 to 22
5
11 ^C dsh_sp_a
8 Cir B Superheat Setpoint 8.3 to 22
5
11 ^C dsh_sp_b
9 Cir A Cooler Pinch Setpt 0.5 to 2.6
6
1.0 ^C pinc_p_a
10 Cir B Cooler Pinch Setpt 0.5 to 2.6
6
1.0 ^C pinc_p_b
11 Maximum Condensing Temp 48.8 to 71.1
7
68 °C mct_sp
12 Max Condensing Temp Diff 5.5 to 11
7
6.7 ^C mct_diff
13 Maximum Current Setpoint 50 to 85
8
80 % curr_max
14 Maximum Current Diff 5 to 20
8
10 % curr_dif
15 Close Capacity Ctrl Sel Dsable/Enable
9
Dsable - cls_ctrl
16 Auto Z Multiplier Setpt 4 to 6
10
6 - zm_spt
17 Maximum Z Multiplier 1.0 to 6.0
11
6.0 - hc_zm
18 Entering Fluid Control Yes/No
12
No - ewt_opt
Note: this table canl be downloadable at any time. However, modified value shall not be used by tasks until the unit is in off state . This shall not apply to the Varifan/water valves gains that shall be modified at any time and used immediately by the head pressure control tasks even if the unit is in operation.
1. > 1 = Water
2 = Brine 3 = Low Brine
Warning: This decision affects the freeze protection threshold.
w water: 1.1°C
w brine & low brine: coldest setpoint - 4.4°C
2. Used to set fan cycling. Decreasing this value will increase fan cycling. This timer can be reduced since the unit is fitted with an important number of fan stages, as to increase the condensing control accuracy. But in certain cases, notably on units with few fan stages, at too small value can causes superheat hunting problems.
3. Used to set fan cycling. Default value is 5 ^C, 11.1^C or higher value are recommanded if unit has varifan. This value can be increased on units with few fan stages to avoid superheat hunting problems.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 25 /98
4. This configuration applies to varifan or water valve upon unit type. It is used to adjust the head pressure control PID loop. Normally this decision has not to be modified for Varifan. For water valve it can be adjusted upon water valve type and installation.
0.4hd_sp_dgDerivative PID Gain:
0.4hd_sp_igIntegral PID Gain:
2.7 hd_sp_pgProportional PID Gain:
Recommanded for air
cooled
PDI GAINS
2.0hd_sp_dgDerivative PID Gain:
0.2hd_sp_igIntegral PID Gain:
2.0 hd_sp_pgProportional PID Gain:
Recommanded for
water cooled
PDI GAINS
5. Upon the operating capacity, the discharge superheat is adjusted as follows :
discharge superheat control point = setpoint + 3.8^C (7^F) if no loader ON. discharge superheat control point =setpoint + 1.7^C (3^F) if one loader ON. discharge superheat control point =setpoint if both loaders ON.
6. This setpoint is used by the EXV control in order to maintain an optimal cooIer exchange delta temperature between leaving temperature and saturated suction temperature. This is done in compensation with discharge superheat temperature which has higher priority.
7. This decision allows to set the high pressure override threshold:
wIf the saturated condensing temperature is greater than [the maximum condensing temperature override
threshold minus the maximum condensing temperature override differential] but less than the [maximum condensing temperature threshold] then the capacity increase shall be inhibited.
wIf the saturated condensing temperature is greater than the [maximum condensing temperature override
threshold] then one stage capacity of the corresponding circuit shall be removed (doesn't apply to the last stage).
8. This decision allows to set the high current override threshold:
wIf the compressor current is greater than [the maximum current setpoint threshold minus the maximum
current override differential] but less than the [the maximum current setpoint threshold] then the capacity increase shall be inhibited.
wIf the compressor current is greater than [the maximum current setpoint threshold] then a loader of the
circuit or the compressor will be stopped.
wcurr_max and curr_dif are in percent of MTA (Must Trip Amps). curr_max shall not exceed 85% as the
screw compressor board shall stop the compressor for alarm when current reaches 85% of MTA.
9. The Global chillers use compressors which have better performance at full load than at part load. Therefore the loading sequence strategy will be different from the one for flotronic II or pro-dialog 30 G & H control. When compressor is on, it will try to avoid the compressor operate at low capacity (no loader ON). If this item is enable, the control will use any stage of capacity in order to keep the exchanger leaving temperature as closed at possible to the control point what ever the compressor performance. When the circuit is in capacity override (compressor status LEDs in the synopsis are blinking), the control will force the close control capacity variable to enable until the circuit is no more in override.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 26 /98
10. This decision allows to set the setpoint which is used for auto Z Multiplier calculation. The Z Multiplier calculation tries to maintain, for each compressor, a maximum number of starts per hour equal to [zm_spt]. Thus, decreasing the setpoint shall increase the reactivity of the auto Z Multiplier to compressors cycling.
11. The Z Multiplier parameter allows to adjust the on/off time delay between compressors staging. It doesn't affect loaders staging. Increasing this value shall increase the on/off time delay but shall reduce the accuracy on the leaving temperature control.
wTthe current Z Multiplier is the result of calculation based on the number of starts of compressors.
However, the maximum Z multiplier calculation will be limited to the value entered in this decision.
12. This item allows the entering fluid control. Default is leaving fluid control. Entering fluid control can be used for small charge.
4.2.4.2 - Service1 configuration table from main interface
The main interface allows to view and modify the service configuration table SERVICE1. Unit shall be stopped and service password or factory password are required.
Entering fluid temperature control selectewt opt18
Coolin
g
and Heating Z multiplier.hc_zm17
Auto z multi
p
lier setpoint.zm_spt16
Close ca
p
acity control selectcls ctrl15
Maximum Current differential in
p
ercent of MTA.curr dif14
Maximum Current set
p
oint in percent of MTAcurr max13
Maximum Condensin
g
Temperature differential.mct diff12
Maximum Condensin
g
Temperature setpointmct_s
p
11
Cooler pinch T setpoint Circuit B (lwt - sst setpoint displayed only if cap_b1 > 0).pinc_p_b10 [2]
Cooler pinch setpoint Circuit A (lwt - sst setpoint) pinc_p_a9
Discharge superheat setpoint circuit B (displayed only if cap_b1 > 0).dsh_sp_b8 [2]
Discharge superheat setpoint circuit A.dsh_sp_a7
Setpoint head press ure control - Derivat ive gain for Varifan or water valve control. Masked if the Varifan or the water valve is not selected (hd_selec = 0).
hd_sp_dg 6 [2]
Setpoint head pressure control - Integral gain for Varifan or water valve control. Masked if the Varifan or the water valve is not selected (hd_selec = 0).
hd_sp_ig 5 [2]
Setpoint head pressure cont rol - Proportional gain for Varifan or water valve control. Masked if the Varifan or the water valve is not selected (hd_selec = 0).
hd_sp_pg 4 [2]
Fan control - head pressure differentialhead_dif 3[2]
Fan control - head pressure differential timer. head_tim 2 [2]
Fluid type select.flui_typ1
When selected this item shall allow to return to main menu.-0
COMMENTSVARIABLEITEM #
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 27 /98
4.2.4.3 - Service 2 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table SERVICE2. Unit shall be stopped and under CCN Operating Type control.
TABLE NAME: SERVICE2 PIC TABLE TYPE : 13H, instance 2
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 Condenser Pump Ctrl Type 0/1/2
1
0 - cond_ctr
2 Condenser Fluid Type 1/2/3
2
1 - cond_typ
3 Cooler Lowest Setpoint - 20 to 101
3
14 ^F low_setp
4 Cooler Heater Delta Spt 0.6 to 3.3
4
1.1 ^C heatersp
5 CCN/Clock Functions Enable/Disable
5
Enable - ccnclock
6 Auto Start When SM Lost Enable/Disable
6
Disable - auto_sm
7 8 RECLAIM PARAMETERS 9 Reclaim to Reclaim Delay 5 to 20
7
15 mn recl_del
10 Heat Reclaim Deadband 2.7 to 11.1
8
4.4 ^F recl_db
11 Recl Valve Min Position 0 to 50
9
20 %- min_3w
12 Recl Valve Max Position 20 to 100
10
100 % max_3w
10 Cir A SCT Ctrl Pt Coef a 1.1 to 11.1
11
4.4 ^C rsp_a_a
11 Cir B SCT Ctrl Pt Coef a 1.1 to 11.1
11
4.4 ^C rsp_a_b
12 Cir A SCT Ctrl Pt Offs b 0 .0to 5.5
12
1.7 ^C rsp_b_a
13 Cir B SCT Ctrl Pt Offs b 0.0 to 5.5
12
1.7 ^C rsp_b_b
14 15 User Password 0 to 150
13
11 - use_pass
16 Service Password 0 to 150
13
88 - ser_pass
1. This decision is only used for the water cooled chillers.
w0 - no control w1 - condenser pump is based on the unit on/off status. w2 - condenser pump is ON when unit is ON (compressors are ON )
2. This decision is only used for the water cooled chillers.
w1 = water, 2 = medium brine, 3 = low brine wIf condenser fluid type is brine, condenser pump will not be turned on for condenser freeze protection
function
3. This decision allows to limit the setpoint of the customer (control point shall be higher than this value). It is mostly used for brine application, as freezing condition depends on ratio on glycol and water.
4. Used for cooler heater operation, this item is applied to outside temperature to determine the freeze conditions (see cooler heater operation section).
5. This item allows to use capabilities and functions based on CCN and clock..
6. If enable, when chiller looses communication with the System Manager, it shall force the its CHIL_S_S variable to «enable» and auto all other variables. Chiller restarts in stand alone mode with default setpoint .
7. This decision allows to enter the entering temperature dead band for reclaim operation mode. See reclaim operation description.
8. This decision allows to enter the delay between two air cooled to reclaim injection sessions. See reclaim operation description.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 28 /98
9. This decision allows to set the minimum position in percent of the reclaim condenser water valve. See reclaim operation description.
10. This decision allows to set the maximum position in percent of the reclaim condenser water valve. See reclaim operation. See reclaim operation description.
11. coefficient A in delta F / percent for circuit. This decision allows to set the coefficient A of the saturated condensing temperature control point determination (rsp_a, for circuit A or rsp_b for circuit B) for each circuit when reclaim operation is active. See the items description below and reclaim operation description.
12. offset B in delta F. This decision allows to set the offset B of the saturated condensing temperature control point determination (rsp_a, for circuit A or rsp_b for circuit B) for each circuit when reclaim operation is active.
Thus each circuit will have its control point as follows :
rsp_x = (hr_ewt + hr_lwt )/ 2 + rsp_x_a * cap_t_x / 100 + rsp_x_b: cap_t_x = current capacity in percent of the circuit x = circuit A or circuit B
13. User and service passwords used on main interface.
4.2.4.4 - Service 2 configuration table from main interface
The main interface allows to view and modify the service configuration table SERVICE2. Unit shall be stopped and service password or factory password are required.
reclaim SCT control point determination, offset B, circuit B ^Crspbb16[2
]
reclaim SCT control point determination, offset B, circuit A ^Crspba15[2
]
reclaim SCT control point determination, coef A , circuit B ^C%rspab14[2
]
reclaim SCT control point determination, coef A , circuit A ^C%rsp_a_a13[2
]
reclaim water valve maximum position%max_3w12[2
]
reclaim water valve minimum position%min_3w11[2]
reclaim to reclaim delay minuterecl_del10[2]
reclaim enterin
g
temperature deadband^Chr deadb9[2
]
Service password.-serpass8
User password.-use_pass7
Auto restart when loss of com munication with SM. Not dislayed if the control is not fitted with the o
p
tional CCN/clock board (ccnclock = yes).
-auto_sm6[1]
Clock capabilities select. Not displayed if the c ontrol is not fitted with the optional CCN/clock board (RTC_CHIP_P RESENT = no). Always displ ayed when ccncloc k =
y
es.
-ccnclock5[1]
Cooler lowest setpoint°Clow set
p
4[1
]
Cooler heater delta setpoint.^Cheaters
p
5[1
]
Condenser fluid type.-cond t
yp
2
Condenser control t
yp
e.-cond_ctr1
When selected this item shall allow to return to main menu.--0
COMMENTSUNITSVARIABLEITEM #
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 29 /98
4.2.4.5 - Service 3 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table MAINCFG. Unit should be stopped and under CCN Operating Type control.
TABLE NAME: MAINTCFG PIC TABLE TYPE : 13H, instance 4
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 MAINTENANCE CONFIG 2 3 Servicing Alert Enable/Disable Disable - s_alert 4 5 Refrigerant Charge Ctrl Enable/Disable Disable - charge_c 6 Water Loop Control Enable/Disable Disable - wloop_c 7 Air Exchanger Control Enable/Disable Disable - aexch_c 8 9 CPump 1 Ctl Delay (days) 0 to 1000 0 - cpump1_c 10 CPump 2 Ctl Delay (days) 0 to 1000 0 - cpump2_c 11 HPump Ctrl Delay (days) 0 to 1000 0 hpump_c 12 Water Filter Ctrl (days) 0 to 1000 0 - wfilte_c 13 A1 Oil Filter Ctl (days) 0 to 1000 0 ofila1_c 14 A2 Oil Filter Ctl (days) 0 to 1000 0 ofila2_c 15 B1 Oil Filter Ctl (days) 0 to 1000 0 ofilb1_c 16 B2 Oil Filter Ctl (days) 0 to 1000 0 ofilb2_c
4.2.4.6 - Service 3 configuration table from main interface
The main interface allows to view and modify the service configuration table MAINCFG. Unit should be stopped and service password or factory password are required.
Oil filer b2 next service in days (displayed only capb2 > 0
)
-ofilb2 m12[1
]
Oil filer b1 next service in days (displayed only cap_b1> 0
)
-ofilb1_m11[1
]
Oil filer a2 next service in days (displayed only cap_a2 > 0
)
-ofila2_m10[1
]
Oil filer a1 next service in days.-ofila1 m9[1
]
Water filter next service in days.-wfilte m8[1
]
Condenser water pump next service in days, (displ ayed only if recl _opt = yes or unit t
yp
= 2 or 3 and cond tr > 0
)
-hpump_m7[1]
Cooler water
pump
#2 next service in days (displayed only if pump_seq > 1
)-cpump2_m6[1]
Cooler water pump #1 next service in days (displayed only if pum
p
_seq
> 0
)-cpump1_m5[1]
Air exchanger control select -aexch m4[1
]
Water loop size control select -wloopm3[1
]
Refrigerant charge control select -chargem2[1
]
Reset maintenance select.-s reset1
When selected this item shall allow to return to the main menu.-0
COMMENTSUNITSVARIABLEITEM #
This table is used for service maintenance alert and not available today.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 30 /98
4.2.4.7 - Service 4 configuration table from Service Tool
The Network Service tool allows to view and modify the service configuration table UPDTHOUR. Unit should be stopped and under CCN Operating Type control.
TABLE NAME: UPDTHOUR PIC TABLE TYPE : 13H, instance 3
DESCRIPTION
STATUS UNITS POINT
1 TABLE TO BE USED FOR RUN 2 TIMES & STARTS UPDATE IN 3 CASE OF CONTROL RETROFIT 4 5 Machine Operating Hours nnnnn hours hr_mach 6 Machine Starts nnnnn - st_mach 7 Compressor A1 Hours nnnnn hours hr_cp_a1 8 Compressor A2 Hours nnnnn hours hr_cp_a2 9 Compressor A1 Starts nnnnn - st_cp_a1 10 Compressor A2 Starts nnnnn - st_cp_a2 11 Compressor B1 Hours nnnnn hours hr_cp_b1 12 Compressor B2 Hours nnnnn hours hr_cp_b2 13 Compressor B1 Starts nnnnn - st_cp_b1 14 Compressor B2 Starts nnnnn - st_cp_b2 15 Cooler Pump #1 Hours nnnnn hours hr_cpum1 16 Cooler Pump #2 Hours nnnnn hours hr_cpum2 17 Condenser Pump Hours nnnnn hours hr_hpump
Note
: this table shall be used for purposes of transplanting the devices on time or starts number in the event of a module hardware failure or software upgrade via downloading. It shall be usable only if all items are still nul. Afterwards, its access shall be denied.
4.2.4.8 - Service 4 configuration table from main interface, runtime sub menu
The main interface allows to view and modify the service configuration table UPDTHOUR. Unit shalld be stopped and service password or factory password are required.
Condenser Pump operating hours. Not displayed if cond_ct r = 0 or recl o
p
t =0 and uni t
y
p
=1 or 4
hrs/10 or 100hr_hpump15 [1]
Cooler Pum
p
#2 operating hours. Only if pump_seq > 1.hrs/10 or 100hr_cpum214 [1
]
Cooler Pump #1 operating hours. Only if pumpseq > 0.hrs/10 or 100hr cpum113 [1
]
Average of Maximum number of compressors starts/hour durin
g
last 24 hours
-st_cp_av12
Maximum number of com
p
ressors starts during last hour-st cpmx11
Com
p
ressor B2 starts (only if cap_b2 > 0
)
-/10 or 100st_cp_b210 [1
]
Compressor B1 starts (only if cap_b1 > 0
)
-/10 or 100st_cp_b19 [1
]
Compressor A2 starts (only if capa2 > 0
)
-/10 or 100st cpa28 [1
]
Compressor A1 starts-/10 or 100st cpa17
Machine starts-/10 or 100st mach6
Com
p
ressor B2 operating hours (only if capb2 > 0
)
hrs/10 or 100hr cpb25 [1
]
Compressor B1 operating hours (only if cap_b1 > 0
)
hrs/10 or 100hr_cp_b14 [1
]
Compressor A2 operating hours (only if cap_a2 > 0
)
hrs/10 or 100hr_cp_a23 [1
]
Compressor A1 operating hourshrs/10 or 100hr cpa12
Machine o
p
erating hourshrs/10 or 100hr mach1
When selected this item shall allow to return to the main menu.
-0
COMMENTSUNITSVARIABLEITEM #
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 31 /98
4.2.5 - User configuration
This configuration is accessible by the customer. Parameters can be modified either through the unit main interface (see iom manual), the Network Service Tool (see appendix).
4.2.6 - Network configuration
4.2.6.1 - General
This configuration is used to set network functions. It can be done through the Building Supervisor or the Network Service Tool.
Two network configurations can be implemented on Pro-Dialog control:
wSetting controller time and date wConfiguring alarm configuration table wConfiguring the master/slave function
4.2.6.2 - Configuring a control as a broadcast acknowledger In order for CCN functions to operate properly, one and only one Broadcast Acknowledger is required per bus.
wVerify that no other controller on the bus is configured as a broadcast
acknowledger.
wTo configure an element as a Broadcast Acknowledger:
ˆ Use function (8) of the NETWORK SERVICE TOOL: Addres s Search ˆ Establish connection with the module chosen to be the Broadcast Acknowledger. ˆPosition the cursor on driver type and Enter 3. ˆ Press F2 to transmit the configuration. This element is now the bus broadcast aknowledger
4.2.6.3 - Setting time and date
The modification of the time and date of a Pro-dialog controller can be done through the network. Setting the correct date and time is necessary for units connected on a network which collects alarms.
Two methods are available:
wThrough the Network Service Tool in Carrier Control:
ˆ Select Building-Time. This allows to send time of day, date, day of week to all
controllers
connected to the network.
ˆ When Building-Time is selected, the Service Tool clock is displayed: ˆ Press F2 to transmit this data to the network. If the displayed time is incorrect, modify your PC
time or set the correct time and date on screen.
Note
: If no broadcast aknowledger has been configured on the bus, a communication error will be
displayed. However, controller connected on the network will be set to the date displayed on screen.
wThrough the Network Service Tool in Carrier Control/Select:
ˆ Use the Select function to select a controller. ˆ Once selected choose Ctrl-Time function ˆ Controller-time allows you to view and set the clock functions in the selected device. The clock of
the selected device is read and displayed as shown in the following screen:
ˆ Type over any incorrect data and press F2 to send the information to the controller.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 32 /98
4.2.6.4 - Pro-Dialog alarm configuration table
The Pro-Dialog control has an alarm configuration table associated with it: ALARMDEF. This table can be accessed through the Modify Controller menu of the Network Service Tool. This table needs to be configured only if the unit is network connected to a Building Supervisor, an Autodial Gateway or a Dataport 2, and only if these options are configured to receive network alarms.
The parameters which are configured in this table determine the handling of alarms. TABLE NAME: ALARMDEF PIC TABLE TYPE : 14H, instance 4
DESCRIPTION
STATUS DEFAULT POINT
1 Alarm Routing Control 0-11111111 00000000 ALRM_CNT 2 Alarm Equipment Priority 0 - 7 4 EQP_TYP 3 Comm Failure Retry Time 1 - 240 min 10 RETRY_TM 4 Realarm Time 1 - 255 min 30 RE_ALARM 5 Alarm System Name 8 chars PD4_GXHX ALRM_NAM
ALARMDEF Decisions description:
ALARM ROUTING CONTROL
This decision determines which CCN system elements will receive and process alarms sent by the Pro-Dialog. Input for the decision consists of eight digits, each of which can be set to either 0 or 1. Setting a digit to 1 specifies that alarm will be sent to the system element that correspond to that digit. Setting all digits to 0 disables alarm processing. Digits in this decision correspond to CCN elements in the following manners:
Note
: If the CCN network does not contain a Building Supervisor, Autodial Gateway, or Dataport 2 to
serve as an alarm acknowledger, all digits in this decision shall be set to 0 in order to prevent unnecessary activity on the CCN communication bus.
Allowable Entries 0 = Disabled
1 = Enabled
Default 00000000
ALARM EQUIPMENT PRIORITY
A Building Supervisor uses the value in this decision when sorting alarms by level. Within any group of alarms that all have the same level, the Building Supervisor sorts alarms according to Alarm Equipment Priority.
Allowable Entries 0 to 7 (priority numbers) Default 4
COMM
FAILURE RETRY TIME
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 33 /98
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 00 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Local Building Supervisor(s)
Autodial Gateway(s)
Data
p
ort 2
This decision specifies the amount of time that will be allowed to elapse between alarm retries. Retries occur when an alarm is not acknowledged by a network alarm acknowledger, which may be either a Building Supervisor, an Autodial Gateway, or a Dataport 2. If the acknowledgement is not received, the alarm will be retransmitted after the number of minutes specified in this decision.
Allowable Entries 1 to 240 minutes Default 10 minutes
REALARM
TIME
This decision specifies the amount of time that will be allowed to elapse between re-alarms. A re-alarm occurs when the condition that caused the initial alarm continues to persist for the number of minutes specified in this decision. Re-alarming will continue to occur at the specified interval until the condition causing the alarm is corrected.
Allowable Entries 1 to 254 minutes Default 30 minutes
ALARM SYSTEM NAME
This decision specifies the system element name that will appear in alarms generated by the Pro-Dialog control.
Allowable Entries Up to 8 alphanumeric characters Default PRO_30GX
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 34 /98
4.2.6.5 - Master/Slave configuration table
The MST_SLV table can be accessed through the Modify Controller menu of the Network Service Tool or the main interface. This table needs to be configured if the master/slave function is used. Master/slave function allows the Pro-Dialog unit to operate as master or a slave in a two chillers plant. See section 4.20.
TABLE NAME: MST_SLV PIC TABLE TYPE : 10H, instance 3
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 MASTER/SLAVE CONTROL 2 3 Master/Slave Select: 0/1/2
1
0 - ms_sel 4 0 = Disable 5 1 = Master 6 2 = Slave 7 Master Control Type: 1/2/3 1 - ms_ctrl 8 1 = Local Control 9 2 = Remote Control 10 3 = CCN Control 11 Slave Address 1 to 236 1 - slv_addr 12 Lag Start Timer 2 to 30
2
10 min lstr_tim 13 Lead/Lag Balance Yes/No
3
No - ll_bal 14 Lead/Lag Balance Delta 40 to 400
4
168 hours ll_bal_d 15
Lag Unit Pump Control 0/1 0 - lag_pump 16 0 = Stop if Unit Stops 17 1 = Run if Unit Stops 18 Lead Pulldown Time 0 to 60
5
0 minutes lead_pul
Decisions description:
1. This decision allows the unit to operate as master or a slave in a two chillers master/slave. The master
chiller monitors all external commands as start/stop, demand limiting, setpoint select or reset via CCN bus.
Control of the slave chiller is done through commands (start/stop, demand limit, setpoint, heat cool)
emitted by the master chiller. The slave will not be allowed to operate as a slave if its CHIL_S_S,
CTRL_PNT or DEM_LIM, HC_SEL variables has a force priority higher than a control force.
2. This timer is started when all conditions to start the lag chiller are satisfied. Lag chiller shall not be started
until this timer is elapsed. To be set in the master unit table only.
3. This decision allows to activate two chillers lead/lag balance function. It is used for master/slave chiller
running time equalization. When this function is active, once per day or each time the master chiller is
switched from the off to the on state the control determines the lead chiller based on both chillers run hours
delta. When the run hours delta is greater than the configured lead/lag balance delta then a changeover
will occur and the unit with the smallest operating hours value will become the lead. This function cannot
operate if the master chiller demand limit is less than 100%. In that case, the master chiller will always be
the lead. To be set in the master unit table only.
4. This function allows to set the lead/lag balance delta used for master/slave chiller running time
equalization. Lead/lag changeover occurs when the lead/lag operating time delta overlaps the configured
balance value and provided that master unit is not under demand limit control.
5. This decision allows to set the lead chiller pull down duration before the lag chiller starts.
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 35 /98
4.3 - Cooler Interlock contact
A contact to check the status of a safety loop is provided (cooler flow switch and customer interlock are wired internally in series). Its function is to prevent the unit from starting if the contact is open while the delay at startup has expired. The contact must also stay closed as long as the unit is not stopped through Local, Remote or CCN control.
If the cooler pump is controlled by the pro-dialog and if the cooler contact is closed after 2 minutes the cooler pump is turned OFF provided that the contact is failed CLOSED, the alarm 75 shall be active and the unit can't no more start until manual reset.
4.4 - Cooler heater control
This function is applied only for air cooled units and is related to the cooler pump function when the unit state is OFF or when unit operates as a lag chiller in master/slave operation and in standby mode. This is provided on outdoor unit as a safeguard against the cooler freezing. The cooler heater is associated with refrigerant isolation solenoids, one output per circuit whose goal is to prevent the refrigerant from migrating into the condenser when chiller is stopped.
The following logic shall be used:
wIf the outdoor air temperature is below the cooler heater trip point and if either the saturated suction temperature
of circuit A or saturated suction temperature of circuit B are lower than the cooler heater trip point plus 3.3 ^C, the cooler heater shall be activated.
wNormally the isolation valves shall prevent refrigerant in the cooler from migrating into the condenser. For this
case, cooler heater can ensure cooler protection efficiently without the need of using cooler pump.
wIf it is not the case (SST remain low), the pump shall be turned on every 7 minutes to check freezing conditions
and additional heat to the cooler : cooler fluid temp (< 3° - [SSTa + SSTb]/2). Pump shall be turned of if cooler fluid temp > (8°C - [SSTa + SSTb]/2).
wIf both saturated suction temperatures of circuit A and circuit B are greater than the cooler heater trip point plus
5.5 ^C, the cooler heater shall be turned off. The pump shall be allowed to stop.
heater trip point = freeze + heat_spt (heat_sp from SERVICE2 table)
freeze = 1.1 for water, coldest setpoint - 4.4^C for brine
4.5 - Oil heater control
Each circuit has its own oil separator fitted with an oil heater. Both circuit oil heater are controlled independently . Since there is no oil temperature sensor, the oil heater will be controlled based on the saturated condensing temperature as follows :
wOil heater ON when outside temperature is below 17°C. wOil heater OFF when outside temperature is above 25°C wOil heater OFF when circuit is in operation or oil level is low (oil_sw is OPEN).
4.6 - Motor Cooling Control without plate exchanger economizer
The screw compressor motors used in the Global Chiller control are refrigerant cooled. The control strategy for motor cooling relies on vapor at light loads, and supplementary liquid refrigerant at high loads. Each compressor will have its own cooling solenoid. An additional motor cooling solenoid is required when operating in high condensing temperature. It is automatically controlled by pro-dialog even if it is not mounted in the units. The motor cooling solenoids shall be cycled to allow liquid to cool the motor. The main motor cooling solenoid control is based on the motor temperature and its setpoint (83°C) using a quasi-fuzzy logic . The additional motor cooling solenoid control is just based on the discharge gas temperature.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 36/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.7 - Motor Cooling Control with sub cooling plate exchanger
The sub cooling plate exchanger replaces the old economizer for simple maintenance and cost reduction. Thus the screw compressor motors are cooled by refrigerant from the plate exchanger, located between condenser and exv (see scheme below). The refrigerant flow through this exchanger for motor cooling purpose is controlled by a thermal expansion valve. The opening of this valve is done by heating its internal resistor via 24 vac ouput signal from the screw compressor board, channel 13. For circuit which has 2 compressors, an additional solenoid (see scheme below, x=a for circuit A, x=b for circuit B) shall be controlled to balance motor temperatures. These solenoid output are located at channel 14 of the screw compressor board.
Evaporator
Condenser
EXV
motor cooling valve
sub-cooling
plate exchanger
compressor 1
compressor 2
cpx1_mc2
cpx2_mc2
4.7.1 Motor Cooling Control with TQ feedback Signal Control
(refer to factory configuration and wiring for retrofit, pages, 21, 23 and 24)
Tq valve opening position depends on the heat (resistor is the image) on the TQ valve and also the equali­sation pressure located at plate exchanger (in our application, quite the same than economiser pressure).
With the same economiser pressure, the higher heating signal is commanded (CPA1_PUL, or CPB1_PUL), the lower is the resistor and the more the valve is opened.
With sam e heating signal value, if the economiser pressure increases, the valve will tend to close. And vice versa
Based on this relation, if the feedback s ignal is enabled, the control will check all the time the relation TQ position = F (economis er pressure/T Q resistor) and shall m ake a k ind of override (absolutely required at the start-up, resistor is very high) When a value of 200 is sent on CPA1_PUL or CPB1_PUL (hardware SIO variable) some time, that means resistor value is a little above the minimum position, preheat is sent. This value is sent also when loading capacity.
When the econom iser pressure is steady, and TQ resistor is near to the pre-opening position, regular control (PID) is used.
TQ resistor sens or is connected to the EXV board. T he value read is in K Ohm s MTQ_RESA (for circuit A), MTQ_RESB (for circuit B). During regular operation, value read shall be from 0.7 k Ohm to 4 k Ohms.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 37/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.8 - CAPACITY CONTROL
This function adjusts the number of active compressors and loaders to keep the leaving water temperature at the setpoint. The precision with which this is achieved depends upon the capacity of the water loop, the water flow rate, the load and the number of capacity control steps available. The control continuously takes account of the temperature error with respect to the control point, the rate of change of the leaving fluid temperature and the delta of temperatures between the entering and leaving fluid in order to determine the optimum time to add or subtract steps of capacity.
Note: a too important number of starts of a particular compressor will automatically cause a limitation of the compressors starts. This will affect the precision of the water loop temperature control.
4.8.1 - Logic description
4.8.1.1 - Basic logic
To operate the capacity control task uses the following inputs:
w EWT Entering water temperature w LWT Leaving water temperature w CTRL_PNT Control point w Cooling z_multiplier Z Multiplier (range: 1.0 to 6.0) w Heating z_multiplier Z Multiplier (range: 1.0 to 6.0)
The control calculates the SMZ: load/unload factor. It is compared to the z_multiplier to determine when to add or remove stage:
w If (sum/z) > +z_multiplier -> stage = +1 (add a compressor) w
If (sum/z) > +0.6 and if a loader is available (loader is OFF) -> stage = +1 (add a loader)
w If (sum/z) < - z_multiplier -> stage = -1 (remove one compressor) w If sum/z) < -0.6 and loader is avaialble (loader is ON) -> stage = -1 (turn off one loader)
Note
: z_multiplier doesn't apply to loaders.
4.8.1.2 - Z Multiplier calculation
The z_multiplier factor allows to indirectly increase the compressor on/off time delay. In consequence, it can be adjusted (increased) to avoid compressors short cycling. This function requires the following Service configuration:
vAuto Z Multiplier sepoint (zm_spt). Default to 6. vCooling and heating Z Multiplier max value (hc_zm). default to 6.0.
This function adapts the z_multiplier to the unit compressor cycles number (the cycle number shall be based on the compressor which has been the most started during an hour). The significant period for compressors cycling shall be of one hour.
If the cycle counter exceeds the setpoint (zm_spt), then the z_multiplier value shall be increased based on the cycle number (PID loop). The function shall not take care of the loaders cycling.
The calculated value of the z_multiplier shall not exceed the configured hc_zm. If the unit returns to normal operating condition with a cycles counter going down then the calculated z_multiplier shall progressively return to its normal value (zm = 1.0). The rate at which the calculated z_multiplier returns to normal shall be lower than the rate at which it is increased.
The setpoint value shall allow to adapt the auto z multiplier calculation to the installation. The setpoint ranges from 4 to 6.
During normal operation, each modification of the unit capacity is followed by a dead time when no capacity modification is possible. The duration of this dead time is 90 seconds.
4.8.1.3 - Overrides
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 38/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
sum/z ratio will be overridden if any one of the following conditions is satisfied.
1 Cooler freeze protection 2,3 Very Low saturated suction temperature 4 Low source temperature protection 5,6 Low discharge superheat temperature 7, 8 Low temperature Cooling/High temperature heating 9 Demand limit 10 Cooler Lock 11 Slow change override 12 Ramp loading 13 Minimum ON/OFF delay 14 High temperature cooling and low temperature heating 15 System Manager control 16, 17 High pressure 18,19 High current 20, 21 Low saturated suction temperature 22,23,24,25 High condensing temperature
28 Compressor startup with loader 1 on due to low condensing temperature 26, 27 Low Oil Level when circuit is OFF 29,30 Stopping circuit due to low oil level (allowed thrice within 2 hours) before going to alarm 31,32 High motor temperature on economizer units (T° > 93°C) 33,34 Stopping compressor due high motor temperature (T° > 110°C, allowed thrice within 2 hours)
before going to alarm
35 Chiller current limit
Note : When overrides 2,3 , 5, 6, 16, 17, 18, 19, 20, 21 are active, the variable close control (cls_ctrl) shall be enabled whatever the configuration to allow unloading the last loader in the circuit.
Chiller Current Override (override #35) This function allows customer to limit the total current (it does not include current of fans, valves, heaters, oil pumps
...) of all the compressors during operation. The chiller current limit can be modified through USER configuration (USER table or User configuration by main interface). This function is similar to demand limit function.
wIf the chiller current is greater than the chiller current limit , then a stage of capacity will be removed. wIf chiller current plus the added current of selected compressor is greater than the chiller current limit, the
increase of capacity will not be allowed. If the compressors is OFF, its added current is 80% of its MTA. If the selected compressor is on but deos not reach 100% capacity, an added stage on the same compressor will add 40% of its current.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 39/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.9 - COMPRESSORS & LOADERS LOADING SEQUENCE
4.9.1 - General Description
The Global chillers uses compressors which have better performance at full load than at part load. Therefore, the loading sequence strategy will be different than for the flotronic II or for the Pro-dialog 30 G & H. The following list applies only to capacity control. For High Ambient Unloading, it can be overridden.
1. A compressor will not be started until all other running compressors are 100% loaded.
2. On units with 3 compressors, both circuits cannot have their loaders off at the same time once 3 or more of the compressors in the unit are on. Where possible, the circuit which is starting a compressor will be the one which is to be unloaded.
3. Any time a lag compressor in a circuit is starting, the loaders in the circuit shall be turned off (unloading all compressors in the circuit). This shall be done 15 seconds prior to starting the new compressor. 15 seconds after the new compressor has started, the loaders shall be set to their desired state. When a lead compressor is starting, all loaders shall be turned off when the compressor relay is turned on (+/- 2 seconds), and shall be set to their desired state 15 seconds after the compressor has been started.
4. There shall be a configuration decision for "close control", which (when selected) will cause the control to utilize all of the loading devices to achieve better leaving water temperature control.
5. Whenever any compressor in a circuit is going to be stopped normally, the circuit shall be fully unloaded for 15 seconds prior to shutting down the compressor. This shall not apply when the reason for a shutdown is due to an alarm condition.
7. For any shutdown, all compressors and loaders will be shut down at the same time.
For more than 2 compressors, two types of sequencing are available and configurable by the user through either the Main Interface or through the CCN network:
w Equal circuit loading: The control shall attempt to maintain equal capacity between the circuits as the machine
loads and unloads.
w Staged circuit loading: The control shall load the lead circuit completely before the lag circuit is started. When
the load is decreasing the lag circuit shall be unloaded first.
Circuit compressors sequence select shall try to equalize the compressor starts number. That means any compressor in the circuit can become the lead compressor if it has the lowest starts number, however, this shall be balanced with the operating hours.
Loaders in the same circuit are commanded simultaneously. Thus one loader variable is displayed. When a circuit is overridden (compressor status are blinking in the synopsis) because of low suction
temperature, low or high discharge temperature or high condensing temperature (high pressure), or high current then no capacity increase shall be allowed on the affected circuit. This circuit is selected to unload capacity first when unloading capacity condition is required.
4.9.2- Compressor capacity determination
Each compressor has three stages capacity. Simulation had been done to determine the average capacity corresponding to those stages as following :
No loader ON -> 40% Only loader_1 -> 70% Both loaders ON -> = 100%
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 40/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.9.3- Staged Loading Increasing Capacity Logic
ONON2ONON2
OFFON2ONON2
ONON1ONON2
OFFON1ONON2
OFFOFF0ONON2
OFFOFF0OFFON2
OFFOFF0ONON1
OFFOFF0OFFON1
OFFOFF0OFFOFF1
OFFOFF0OFFOFF0
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
4.9.4- Equal Loading Increasing Capacity Logic with close_control = NO
ONON2ONON2
OFFON2ONON2
ONON1ONON2
ONON1OFFON2
ONON1ONON1
OFFON1ONON1
OFFON1OFFON1
OFFOFF0ONON1
OFFOFF0OFFON1
OFFOFF0OFFOFF1
OFFOFF0OFFOFF0
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 41/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.9.5- Equal Loading Increasing Capacity Logic with close_control = YES
ONON2ONON2
OFFON2ONON2
ONON1ONON2
ONON1OFFON2
ONON1ONON1
OFFON1ONON1
OFFOFF1ONON1
OFFOFF1OFFON1
OFFOFF0ONON1
OFFOFF0OFFON1
OFFOFF0OFFOFF1
OFFOFF0OFFOFF0
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
4.9.6- Equal Loading Decreasing Capacity Logic with close_control = YES
OFFOFF0OFFOFF1
OFFOFF0OFFON1
OFFOFF0ONON1
OFFOFF1OFFON1
OFFON1OFFON1
OFFON1ONON1
OFFOFF1OFFON2
OFFON1OFFON2
OFFON1ONON2
OFFON2OFFON2
OFFON2ONON2
ONON2ONON2
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 42/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.9.7 - Equal Loading Decreasing Capacity Logic with close_control = NO
OFFOFF0OFFOFF0
OFFOFF0OFFOFF1
OFFOFF0OFFON1
OFFOFF0ONON1
OFFON1OFFON1
OFFON1ONON1
ONON1ONON1
OFFON1ONON2
ONON1ONON2
OFFON2ONON2
ONON2ONON2
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
4.9.8 - Staged Loading Decreasing Capacity Logic with close_control = NO
OFFOFF0OFFOFF0
OFFOFF0OFFOFF1
OFFOFF0OFFON1
OFFOFF0ONON1
OFFOFF0OFFON2
OFFOFF0ONON2
OFFON1ONON2
ONON1ONON2
OFFON2ONON2
ONON2ONON2
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 43/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.9.9 - Staged Loading Decreasing Capacity Logic with close_control = YES
OFFOFF0OFFOFF0
OFFOFF0OFFOFF1
OFFOFF0OFFON1
OFFOFF0ONON1
OFFOFF0OFFON2
OFFOFF1OFFON2
OFFOFF1ONON2
OFFON1ONON2
ONON1ONON2
OFFON2ONON2
ONON2ONON2
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LOADER
2
LOADER
1
NUMBER OF
COMPRESSORS
LAG CIRCUIT LEAD CIRCUIT
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 44/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.10 - EXV CONTROL
4.10.1 - General
The EXV is controlled to maintain minimum pinch for insuring the cooler exchange performance through the delta temperature between the cooler fluid and the saturated suction temperature. EXV opening movement will normally decrease the cooler pinch and thus increase the cooler exchange performance. But it shall not open too much provided a drop in discharge superheat , low oil pressure and refrigerant flow.
The EXV control shall deal with two goals : Smaller Cooler Pinch and Discharge Superheat Protection. Additional protection against excessive EXV opening is applied to ensure the condenser heat transfer (sub cooling).
It may happen when operating in high condensing temperature and indirectly high discharge superheat, exv would tend to open continuously to get the lower pinch due to the setpoint and unfortunately in certain conditions, this value has reached the limit, though it is higher than the setpoint. Therefore, EXV position limit shall be set when there is no more variation in cooler pinch for a variation of EXV position of 4 percent.
EXV position shall also be limited to avoid hunting problem due to low discharge superheat protection. It may occur when operating in a low condensing temperature, the discharge superheat protection can switch from enable to disable in few scans and so on.
This control uses a kind of auto adaptive method whose goal is to find out the optimal position of EXV for insuring an optimal pinch with a correct discharge superheat and sub cooling.
4.10.2 - Overrides over_exv Override Description with and priority precedence.
1 Low ambient startup 2 Low Saturated Suction Temperature 3 Very Low Saturated Suction Temperature 4 Very Low Discharge Superheat 5 Mop control (Closing EXV) 6 Cooler pinch regular control 7 Reclaim injection override 8 High Saturated Suction Temperature (no movement) 9 Low Saturated Suction with High Saturated Condensing Temperature 10,11 Capacity increase 12,13, 14 Capacity decrease 15 Reclaim pumpdown session 16,17 Discharge Superheat lower than control point 18, 20 Safeguard Discharge Superheat 19 Exv position limitation active 21,26 Safeguard optimal cooler pinch due high Discharge Superheat or lower exv
position 22 Closing EXV due to good pinch and high motor temperature for economizer unit 23 Exv position limitation active, and go back to previous position 24, 25 EXV limitation is reinitialized
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 45/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.11 - Air Cooled Condensing Pressure Control
Head pressure differential value and head pressure differential timer can be adjusted in the Service menu. Decreasing these values will increase fan cycling. This differential value and timer can be reduced since the unit is fitted with an important number of fan stages, as to increase the condensing control accuracy. But in certain cases, notably on units with few fan stages, at too small value can causes superheat hunting problems. Varifan PID gains can be modified in the Service menu (not recommended). See section 4.2.3.
SCT
control point without varifan
To avoid fan cycles and also to ensure a minimum expected SCT for oil pressure, SCT control shall be adjusted based on OAT, the same for SCT differential as
55°C (13°F1)
OAT
20°c
0°c
68°F
32°F
+ 1 fan
- 1 fan
SCT control point
35°C (95°F)
40°C (104°F)
35°C (95°F)
SCT Diff
4.12.1 - Air Cooled Condensing Pressure Control - Fan staging with Aux board
Each DO shall support only one fan. The first DO is not used if varifan is present to standardize the way of making connection and to avoid wiring mistake.
4.12.2 - Air Cooled Condensing Pressure Control - Fan staging
The combination described here below is for 4 fans configured maximum, each DO commands 1 fan
4fan_1 + fan_2 + fan_3 + fan_4onononon4
3fan_1 + fan_2+ fan_3 offononon3
2fan_1 + fan_2offoffonon2
1fan_1offoffoffon1
00offoffoffoff0
total fans
fans controlled
DO_4DO_3
DO_2DO_1stage
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 46/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The following combinations are used for a circuit with more than 4 fans configured
5fan_1 + fan_2 + fan_3 + fan_4 + fan_5onononon5
4fan_1 + fan_2 + fan_3 + fan_4offononon4
3fan_1 + - + fan_3 + fan_4offonoffon3
2fan_1 + fan_2offoffonon2
1fan_1offoffoffon1
00offoffoffoff0
total
fans
fans controlled
DO_4DO_3
DO_2DO_1stage
6fan_1+ fan_2 + fan_3 + fan_4 + fan_5 + fan_6onononon6
5fan_1+ - + fan_3 + fan_4+ fan_5 + fan_6 ononoffon5
4fan_1+ fan_2 + fan_3 + fan_4offononon4
3fan_1+ - + fan_3 + fan_4offonoffon3
2fan_1+ fan_2offoffonon2
1fan_1offoffoffon1
0-offoffoffoff0
total fans
fans controlled
DO_4DO_3
DO_2DO_1stage
7fan_1 + fan_2 + fan_3 + fan_4 + fan_5 + fan_6 + fan_7onononon7
6fan_1 + - + fan_3 + fan_4 + fan_5 + fan_6 + fan_7ononoffon6
5fan_1 + fan_2 + - + - + fan_5 + fan_6 + fan_7 onoffonon5
4fan_1 + fan_2 + fan_3 + fan_4offononon4
3fan_1 + - + fan_3 + fan_4offonoffon3
2fan_1 + fan_2offoffonon2
1fan_1offoffoffon1
0-offoffoffoff0
total fans
fans controlled
DO_4DO_3
DO_2DO_1stage
8fan_1 + fan_2 + fan_3 + fan_4 + fan_5 + fan_6 + fan_7 + fan_8onononon8
7fan_1 + - + fan_3 + fan_4 + fan_5 + fan_6 + fan_7 + fan_8ononoffon7
6fan_1 + fan_2 + - + - + fan_5 + fan_6 + fan_7 + fan_8onoffonon6
5fan_1 + - + - + - + fan_5 + fan_6 + fan_7 + fan_8onoffoffon5
4fan_1 + fan_2 + fan_3 + fan_4offononon4
3fan_1 + - + fan_3 + fan_4offonoffon3
2fan_1 + fan_2offoffonon2
1fan_1offoffoffon1
0-offoffoffoff0
total fans
fans controlled
DO_4DO_3
DO_2DO_1stage
4.13 - Water Cooled Condensing Pressure Control
The control of a common water valve for both circuits is required. The water valve control will be based on the highest saturated condensing temperature of both circuit or based on the operating circuit if the other is OFF.
Water valve PID gains can be modified in the Service menu (when unit is OFF). See section 4.2.3. They are accessible though the table SERVICE1 and can be modified during operation.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 47/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.14 - High Pressure (Maximum Condensing Temperature) Override
This function shall be used to avoid circuit high pressure trip while the condensing pressure reaches a configurable override threshold (Service 1 Configuration).
wIf the saturated condensing temperature is greater than the maximum condensing temperature (mct_sp) minus
the maximum condensing temperature override differential (mct_diff) but less than the maximum condensing temperature (mct_sp) then the circuit capacity increase shall be inhibited.
wIf the saturated condensing temperature is greater than the maximum condensing temperature (mct_sp) then the
circuit capacity shall be reduced. The first capacity stage shall never be turned off even if that causes a circuit high pressure trip.
wIf the circuit capacity has been reduced due to high condensing temperature override then the circuit capacity
increase will not be allowed for 5 minutes even if the saturated condensing temperature is below the maximum condensing temperature (mct_sp) minus the maximum condensing temperature override differential. This shall avoid compressor cycling.
4.15 - High Current Override
This function shall be used to avoid circuit high current trip while the motor current reaches a configurable override threshold (Service 1 Configuration).
wIf the current is greater than the maximum current threshold (curr_max) minus the maximum current override
differential (curr_diff) but less than the maximum current threshold (curr_max) then the circuit capacity increase shall be inhibited.
wIf the current is greater than the maximum current threshold (curr_max) then the circuit capacity shall be reduced
by removing a loader or the affected compressor.
wIf the circuit capacity has been reduced due to current override then the circuit capacity increase will not be
allowed for 5 minutes what ever current measured. This shall avoid compressor cycling.
4.16 - Stopping Function
4.16.1- Stopping a compressor by capacity unloading
If the selected compressor is operating with at least one loader ON, then all the loaders in the same circuit shall be de-energized for 15 seconds before stopping the compressor.
4.16.2- Stopping the unit by manual command (OFF)
Both circuit shall decrease its capacity progressively every 15 seconds. One loader is immediately de-energized. The last loader will be de-energized in 15 seconds later. Then all compressors, oil solenoids and oil pump will be de-energized in 15 seconds after the last loader is turned OFF. Here is an example of the stopping function with time indicator for a circuit with both loaders ON before receiving a STOP command.
t = t
0
loader_2 = OFF
t = t
0 + 15s
loader_1 = OFF,
t = t
0 + 30s
All the compressors, oil solenoids and oil pumps shall be de-energized
The exv shall be closed in one minute after the last compressor is de-energized or after the difference between discharge and suction pressure is lower than 58 psi
note : Both circuits can be stopped in different timing depending on the status of their loaders when the STOP command is received. Maximum duration for stopping the unit is 30 seconds. A circuit can be stopped immediately if no loader is ON before going to stopping procedure.
4.16.3- Stopping a circuit by failure
If the circuit or the hole unit are failed by alarms freeze, low sst, cooler flow, all the compressors are shut off immediately. Otherwise, it shall respect procedure above.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 48/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.17- Oil pressure control
4.17.1- Oil pressure Setpoint determination
The following algorithm applies to all unit types:
104 86 70
Oil setpoint 1
(kpa)
> 350240 < AND <350< 240Suction pressure (kpa)
Oil Setpoint2 is calculated as follows:
0.63645* (DP - SP) + 35
2* (DP - SP) - 1516
0.235* (DP - SP) + 4
Oil setpoint 2
(kpa)
> 1137861 < AND < 1137< 861DP - SP (kpa)
* DP = Discharge Pressure * SP = Suction pressure
4.17.2- Oil pump control
The oil pump is generally used to provide pre-lubrification of the compressor. Moreover, it is controlled to insure a correct oil pressure during capacity transition or during operation with low condensing temperature that cause a drop of oil pressure to avoid tripping in alarm.
Thus the oil pump is turned ON when the Differential Oil Pressure is lower than Oil Setpoint 1 plus 13 kpa. and remained ON until Differential Oil Pressure is greater than Oil Setpoint 1 plus 35 kpa AND difference between discharge and economizer pressure is greater than Oil Setpoint 1 plus 150 kpa to avoid oil pump cycles.
4.17.3- Low Oil pressure alarm determination
ALARM 68 for Compressor A1, ALARM 69 for Compressor A2, ALARM 70 for Compressor B1, ALARM 71 for Compressor B2.
Criteria For Trip
Tested only when the compressor is ON. DOP: Differential Oil Pressure for the appropriate compressor. DOP = Oil pressure - Economizer pressure. Economizer pressure is the common (econ_sel = YES) Economizer Pressure transducer reading for the
circuit involved or the appropriate economizer pressure transducer (econ_sel = NO) associated to the compressor.
A. Compressor has started with Normal Ambient (oat > 10 °C) or
or condenser temperature (temp > 18°C)
1. If the compressor has been running for less than 5 seconds then ignore the alarm.
2. If the compressor has been running for more than 5 seconds but less than 30 seconds and
DOP < (Oil Setpoint1/30)*(Comp. Running Time [in seconds]) for 3 continuous readings, then the alarm shall be tripped.
3. If the compressor has been running for 30 seconds or more, then if:
a). DOP < Oil pressure setpoint1 for 15 continuous seconds,
OR
b). (Poil - Psuction) < Oil pressure setpoint2 for 15 continuous seconds, then the alarm shall be tripped
B. Compressor has started with Low Ambient (oat < 10 °C) or low condenser temperature (temp < 18°C)
1. If the compressor has been running for less than 90 seconds then ignore the alarm.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 49/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
2. If the compressor has been running for more than 90 seconds but less than 180 seconds and
DOP < (Oil Setpoint1/90)*(Comp. Running Time [in seconds] - 90) for 3 continuous readings, then the alarm shall be tripped.
3. If the compressor has been running for 180 seconds or more, then if:
a). DOP < Oil pressure setpoint1 for 15 continuous seconds,
OR
b). (Poil - Psuction) < Oil pressure setpoint2 for 15 continuous seconds, then the alarm shall be tripped.
Action To Be Taken
1. If the alarm is tripped then the affected compressor shall be stopped. The other compressors shall
continue to run.
4.17.4- Differential Oil Pressure Setpoint 1 alarm condition summary.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 50/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
0
Differential Oil pressure required
180s
oil pressure trip
Oil pressure tr ip with low ambient or
90s
30s
5s
oil setpoint1
oil setpoint1oil setpoint1
oil setpoint1
3 continued
3 continued3 continued
3 continued
reading values
reading valuesreading values
reading values
3 continued
3 continued3 continued
3 continued
reading values
reading valuesreading values
reading values
15 s delay
15 s delay
time from start
low condensing temperature
4.18 - Reclaim Operation
4.18.1 - General Description This function shall control the air cooled to reclaim or the reclaim to air cooled changeover process. Reclaim changeover shall be caused either by:
wA manual reclaim select change due to a local, remote or CCN command on the unit wA heat reclaim temperature change while reclaim has been selected. This algorithm monitors the entering
reclaim sensor temperature and compares it with the reclaim setpoint to determine if the reclaim can be active or not.
If the reclaim function has been selected, the reclaim shall become active when the entering reclaim temperature comes below the reclaim setpoint minus the reclaim deadband and delay between the last air cooled to reclaim session is elapsed. It shall become inactive when the entering reclaim temperature comes over the reclaim setpoint plus the reclaim deadband.
Non-reclaim to reclaim Changeover shall follow this procedure:
wTurn on the reclaim condenser pump wVerify the condenser flow is established, if not after 1 minute delay has elapsed, reclaim operation shall be
aborted and an alarm shall be displayed.
wWait for 3 minutes after condenser pump is ON and until the saturated condensing temperature reaches (30
deg C) and superheat is greater than 8.6 ^C
w If saturated condensing temperature is greater than reclaim setpoint + 3.3^F, go to reclaim operation directly (it
is not necessary to make an pumpdown) otherwise, go through pumpdown (see below)
wStart the pumpdown sequence : reclaim discharge valve shall be closed and reclaim pumpdown injection valve
shall be open.
wClose EXV 6.67 or 3.33% upon the number of compressors on circuit every 10 seconds while pumpdown
pressure is greater than 300 kpa (44 psi), during first minute if EXV is less than 15 % opened.
wAfter a 10 minutes duration or as soon as pumpdown pressure is lower than 300 kpa (44 psi), reclaim injection
valve shall be closed, reclaim operation is effective. Open EXV 13.33% as avoid low saturated suction alarm.
wWhen reclaim operation is active, each circuit fan staging has its own saturated condensing control point
determined as follows:
sct_ctrl_x = (hr_ewt + hr_lwt)/ 2 + rsp_x_a * capacity_x + rsp_x_b (x for circuit), rsp_x_a and rsp_x_b are service parameters in table SERVICE2.
wPumpdown shall not be necessary if saturated condensing temperature is greater than reclaim setpoint + 6 ^C
Reclaim to non-reclaim Changeover shall follow this procedure:
wTurn off the condenser pump. wClose the reclaim pumpdown valve. wOpen the reclaim discharge valve if at least a compressor is ON. Otherwise, Close it.
During reclaim operation, if the pumpdown pressure is greater than 400 kpa (59 psi), the pumpdown procedure in non_reclaim to reclaim session shall be initiated. When the number of these abnormal sessions exceeds 2 times, the reclaim operation shall be aborted, the circuit shall return to air cooled mode and an alarm shall be displayed.
At power up or after reset or after the unit capacity goes down to 0%, the function shall return to air cooled mode.
4.18.2 - Reclaim To Air Cooled Changeover Initiation This shall determine whether the unit shall return to air cooled mode. This can be caused by the following:
Cause #1
: Reclaim operation active and reclaim select is no more active
Cause #2
: Reclaim mode is active and the entering reclaim temperature is above the range of the reclaim
setpoint + the reclaim dead band divided by 2 : HR_EWT >rsp + hr_deadb/2 Cause #3: Number of consecutive reclaim pumpdown sessions exceeds 2 times Cause #4
: entering reclaim temperature sensor failure
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 51/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.18.3 - Air Cooled To Reclaim Changeover Initiation A non-reclaim to reclaim injection session has been required and at least one compressor is on and the unit is not
failed and the entering reclaim temperature is not failed and this one is below the reclaim setpoint - half of configured reclaim deadband and delay between the last reclaim injection has elapsed.
4.18.4 - Reclaim Operation status
hr_status Description
Information on reclaim operation is available on table RECLAIM (hrstatus) or on INFORMATION menu (hr_status). hr_status parameter shall contain reclaim operation indicator of both circuit in two digits, one digit per circuit (left digit for circuit A, the other for circuit B) with the following description :
Reclaim failed due to flow switch 5
Reclaim pumpdown failed 4
Reclaim operation active3
Reclaim pumpdown mode2
Reclaim mode request 1
Air cooled operation0
Status descriptionreclaim operation
indicator
*note : in case of reclaim operation failure (alarm # 83 for circuit A, alarm # 84 for circuit B), hr_status will not be initialized until the manual reset on main interface is done.
4.18.5 - Reclaim Operation Using Air Cooled Exchanger To avoid high pressure problem, the remained condenser (hr_val_x) can be turned ON if SCT is above reclaim
setpoint + 8.3 deg C and all fans are ON provided that fans staging is not enough to avoid the risk of exceeding high pressure override threshold. When turning ON, the remained condenser (hr_val_a) is kept to ON for at least 3 minutes to let fans staging to be stabilized. This condenser can be turned OFF if it has been ON for more than 3 minutes and if saturated condensing temperature is below the reclaim setpoint (rsp) to ensure the reclaim operation performance.
4.18.6 - Reclaim Condenser Water Valve Control if unit is not in reclaim operation, then the reclaim condenser water valve remains in minimum position. In reclaim operation :
wIf reclaim entering temperature is below 20 deg C, then reclaim condenser valve is at minimum position. wIf reclaim entering temperature is above 40 deg C, then reclaim condenser valve is at maximum position. wIf entering temperature is within the range 20 degC and 40 deg C, then reclaim condenser water valve position
will be an interpolation between minimum and maximum position.
4.18.7 - Reclaim Condenser Heater Control Reclaim condenser heater is ON when entering or leaving fluid are lower than 3.0 deg C( 37.4 degF). It is turned
OFF when both temperatures are above 4.4 deg C (40.0 deg F).
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 52/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.19 - Two Units Master/Slave Control
4.19.1 - General
This function allows to perform master/slave plant control between two chillers linked by the CCN network. Master and slave chiller need to operate on the same bus. Master/slave operations shall operate in cooling or heating mode.
To operate properly, the master and the slave chillers must have an additional CHWS sensor located on the common chilled leaving piping when the water control is done on the outlet side. This CHWS sensor shall be connected on each chiller basic board. When the water system control is done on the inlet side no additional CHWS sensor is required.
Parallel chiller control with dedicated pumps is recommended. Chiller must start and stop its own water pump located on its own piping. If pumps are not dedicated for each chiller pimping, chiller isolation valves are required: each chiller must open and close its own isolation valve through the control (valve shall be connected to the pump outputs).
Water system control with no individual chiller pump control is feasible. It is not recommended when the system load is low or if the control point is close from the freeze water tripping point (because of system instability that can be caused by the freeze protection override). System flow is constant even if the master or the slave chiller is stopped. In that case, the system pump shall be controlled by the master chiller.
Series chillers with dedicated primary pumping and constant flow shall be feasible but not recommended. Pump start/stop must be controlled externally. Each series chiller must control its own isolation and bypass valves: stopped chiller must be isolated from water flow (chiller pump command shall be used for valves control. Each chiller must open and close its own chilled isolation valve).
The master chiller shall monitor all external commands as start/stop, demand limiting or setpoint select. It needs to be started in Master operating type. The slave chiller must operate in CCN mode. If the master chiller is turned off while the master/slave function is active then, the slave chiller shall be stopped.
The master/slave linkage shall not be allowed to operate if any one of the slave chiller CTRL_PNT, DEM_LIM, LAG_LIM, CTRL_PNT HC_SEL or LCW _STPT variables has a force priority higher than a control force. In that case, the master slave operations shall not be allowed or shall be disabled.
The control of the slave chiller shall be done through commands emitted by the master chiller. The slave chiller has no action in the master/slave operations: it shall only verify that CCN communication with its master is correct.
The master function shall provide the ability to select a lead chiller among the master and the slave. Selection shall be based on the delta between the master and the slave run hours and shall try to optimize the runtime hours. If this function is unused then, the lead chiller shall always the master. Lead/lag changeover between the master and the slave due to hour balance shall occur during chiller operations odd days at 12:00 a.m. or at startup.
The lead chiller shall always be started first and the lag chiller shall be maintained at zero percent capacity through master forcing the lag demand limit value (LAG_LIM) to 0%. The lag water pump shall be maintained off. When the lead chiller cannot be loaded anymore (because it is loaded at its full available capacity or at the master demand limit value) then the lag start timer is started. When the lag start timer is elapsed, if the error on the master controlled setpoint is greater than 3^F and if the pulldown time is elapsed then, the lag chiller water pump shall be turned on (if required by configuration) and the lag chiller shall be allowed to start through master forcing the lag chiller demand limit value (LAG_LIM) to its own demand limit value. To ensure that the lag chiller will be unloaded first in case of water load decrease then, the lead chiller setpoint error shall be reset of upwards 4^F provided that the lag capacity is not zero.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 53/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The lead pulldown time tells how long after starting the lead chiller (one time after the master chiller status has been manually started) before checking whether to start an additional chiller. This time delay gives the lead chiller a chance to pull down the loop temperature before starting another chiller.
If a communication failure is detected between the master and the slave then, all master/slave functions shall be disabled and chillers shall return to standalone operations until communication is reestablished.
Note: to ensure that no compressor is started before the flow rate is correctly established then, the water flow control is absolutely required on the lag chiller for master slave operations.
The figures below illustrate master/slave application for the most common plant layouts. Those figures are not exhaustive.
MASTER
CHWS temp sensors
COOL_EWT
COOL_EWT
SLAVE
LOAD
SLAVE PUMP
MASTER PUMP
COOL_LWT
COOL_LWT
Typical parallel Master/slave chillers, dedicated primary pumping, variable flow
Leaving water control
MASTER
CHWS temp sensors
COOL_EWT
COOL_EWT
SLAVE
LOAD
COMMON PRIMARY PUMP
COOL_LWT
COOL_LWT
Typical parallel Master/slave chillers, common primary pumping, constant flow
Leaving water control
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 54/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MASTER
COOL_EWT
COOL_EWT
SLAVE
LOAD
SLAVE PUMP
MASTER PUMP
COOL_LWT
COOL_LWT
Typical parallel Master/slave chillers, dedicated primary pumping, variable flow
Entering water control
MASTER
COOL_EWT
COOL_EWT
SLAVE
LOAD
COMMON PRIMARY PUMP
COOL_LWT
COOL_LWT
Typical parallel Master/slave chillers, common primary pumping, variable flow
Entering water control
COOL_EWT
SLAVE
LOAD
CHWS temp sensors
COOL_EWT
COOL_LWT
COOL_LWT
MASTER
PUMP (not contro lle d b y chillers)
ISOLATION (controlled by chillers)
VALVES
BYPASS (controlled by chillers) VALVES
Typical series Master/slave chillers, dedicated primary pumping, constant flow
Leaving water control option
4.19.2 - Abnormal conditions
If a communication failure is detected between the master and the slave then all master/slave functions shall be disabled and chillers shall return to standalone operations until communication is reestablished.
If any chiller is stopped due to failure then the other chiller will be allowed to start with no delay.
If master/slave configuration error occurs, master/slave shall be disable.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 55/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Master/Slave Error
The following error shall be updated in the M_MSTSLV Maintenance table (priority order):
master and slave heatcool status are not the same.x13
No communication with slave.xx12
The master chiller operating type is not Master: master_oper_typ ≠ master
x11
The slave chiller is down due to fault (chilstat = 5)xx10
The slave chiller is in local or remote control (chilstat = 3)xx9
There is a conflict between the master and the slave pump option: the master is not configured for lag pump control while the slave is configured for lag pump control.
x8
There is a conflict bet ween the master and the slave pum p option: the m aster is c onfigured for lag pump control while the slave is not configured for lag pump control.
x7
There is a conflict between the m aster and the s lave lwt option: the mas ter is c onfigured for lwt control while the slave is configured for ewt control.
x6
There is a conflict between the m aster and the s lave lwt option: the mas ter is c onfigured for ewt control while the slave is configured for lwt control.
x5
Slave pump_seq incorrect configurationx4
There is no slave configured at the slave addressx3
Master and slave units have the same network address.x2
The master or slave water pum p is not configured while the control of the lag uni t pump is required (lag_pump = 1)
xx1
Normalxx0
DescriptionSlaveMasterError
code
Master/Slave alarm code
Note
Master/slave sequence can be controlled through the Network Service Tool or PCDCT tools (see appendix, M_MSTSLV Maintenance Table)
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 56/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
5 - CCN ALARM MESSAGES
The Building Supervisor displays current alarms messages and their return to normal provided that the CCN table ALARMDEF has been correctly configured.
The Network Service Tool Diagnostic Menu allows to display 5 current alarms messages (even if the ALARDEF table is not configured).
The following gives the messages that shall be displayed by the Building Supervisor or from main interface.
Alarm 1 Cooler Entering Thermistor Alarm 2 Cooler Leaving Thermistor
Alarm 3 Condenser Entering Thermistor Alarm 4 Condenser Leaving Thermistor Alarm 5 Reclaim Condenser Entering Thermistor Alarm 6 Reclaim Condenser Leaving Thermistor Alarm 7 OAT Thermistor Alarm 8 MASTER/Slave Common Fluid Thermistor Alarm 9 Compressor A1 Discharge Gas Temperature Thermistor Alarm 10 Compressor A2 Discharge Gas Temperature Thermistor Alarm 11 Compressor B1 Discharge Gas Temperature Thermistor Alarm 12 Compressor B2 Discharge Gas Temperature Thermistor
Alarm 13 0-10V Reset/Limit Input Alarm 14 Circuit A Discharge Transducer
Alarm 15 Circuit B Discharge Transducer Alarm 16 Circuit A Suction Transducer Alarm 17 Circuit B Suction Transducer Alarm 18 Compressor A1 Oil Transducer Alarm 19 Compressor A2 Oil Transducer Alarm 20 Compressor B1 Oil Transducer Alarm 21 Compressor B2 Oil Transducer Alarm 22 Compressor A1 Economizer Transducer Alarm 23 Compressor A2 Economizer Transducer Alarm 24 Compressor B1 Economizer Transducer Alarm 25 Compressor B2 Economizer Transducer Alarm 26 Circuit A Remote Discharge Pressure Transducer Alarm 26 Circuit A Reclaim Pumpdown Pressure Transducer Alarm 27 Circuit B Reclaim Pumpdown Pressure Transducer
Alarm 28 Circuit A Motor Cooling TQ feedback Sensor Failure Alarm 29 Circuit B Motor Cooling TQ feedback Sensor Failure
Alarm 30 Loss of communication with Screw Compressor Board 1 Alarm 31 Loss of communication with Screw Compressor Board 2 Alarm 32 Loss of communication with Screw Compressor Board 3 Alarm 33 Loss of communication with Screw Compressor Board 4 Alarm 34 Loss of communication with EXV Board 1 Alarm 35 Loss of communication with Fans Board 1 Alarm 36 Loss of communication with Fans Board 2 Alarm 37 Loss of communication with 4xAI_2xAO
or Aux Type 1 Board
Alarm 38 Loss of communication with
Reclaim or Cooler Heater Board
Alarm 39 Loss of communication with CCN / Clock Board
Alarm 40 Electrical Box Thermostat or reverse phase detection Failure Alarm 41 Unit is in CCN emergency stop
Alarm 42 Initial factory configuration required Alarm 43 Illegal configuration
Alarm 44 Circuit A High Pressure Alarm 45 Circuit B High Pressure Alarm 46 Compressor A1 Oil Solenoid Failure
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 57/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Alarm 47 Compressor A2 Oil Solenoid Failure Alarm 48 Compressor B1 Oil Solenoid Failure Alarm 49 Compressor B2 Oil Solenoid Failure Alarm 50 Compressor A1 Prestart Low Oil Pressure Alarm 51 Compressor A2 Prestart Low Oil Pressure Alarm 52 Compressor B1 Prestart Low Oil Pressure Alarm 53 Compressor B2 Prestart Low Oil Pressure Alarm 54 Circuit A Low Oil Level Alarm 55 Circuit B Low Oil Level Alarm 56 Circuit A Low Suction Temperature Alarm 57 Circuit B Low Suction Temperature Alarm 58 Circuit A High Suction Temperature Alarm 59 Circuit B High Suction Temperature Alarm 60 Circuit A Low Discharge Superheat Alarm 61 Circuit B Low Discharge Superheat Alarm 62 Compressor A1 Maximum Delta Pressure Check Oil Line Alarm 63 Compressor A2 Maximum Delta Pressure Check Oil Line Alarm 64 Compressor B1 Maximum Delta Pressure Check Oil Line Alarm 65 Compressor B2 Maximum Delta Pressure Check Oil Line Alarm 66 Loss of communication with System Manager Alarm 67 Master/Slave communication Failure Alarm 68 Compressor A1 Low Oil Pressure Alarm 69 Compressor A2 Low Oil Pressure Alarm 70 Compressor B1 Low Oil Pressure Alarm 71 Compressor B2 Low Oil Pressure Alarm 72 Cooler Freeze Protection Alarm 73 Circuit A Condenser Freeze Alarm 74 Circuit B Condenser Freeze Alarm 75 Cooler Interlock Failure Alarm 76 Condenser Lock Failure Alarm 77 Compressor A1 High Current
Alarm 78 Compressor A2 High Current Alarm 79 Compressor B1 High Current Alarm 80 Compressor B2 High Current Alarm 81 Cooler Pump 1 Default
Alarm 82 Cooler Pump 2 Default Alarm 83 Circuit A Reclaim Pumpdown Failure
Alarm 84 Circuit B Reclaim Pumpdown Failure Alarm 85 Reclaim Operation Failed by Condenser Flow Switch Alarm 86 Master chiller configuration error Alarm 87 Service maintenance alert
Alarms compressor
Alarm 101 Compressor A1 Motor Temperature Too High Alarm 102 Compressor A1 Motor Temperaure Out of Range Alarm 103 Compressor A1 High Pressure Switch Alarm 104 Compressor A1 Over Current Alarm 105 Compressor A1 Lock Rotor Alarm 106 Compressor A1 Ground Fault Alarm 107 Compressor A1 Phase Loss L1 Alarm 108 Compressor A1 Phase Loss L2 Alarm 109 Compressor A1 Phase Loss L3 Alarm 110 Compressor A1 Unbalance > 14 % Alarm 111 Compressor A1 Unbalance > 18 % Alarm 112 Compressor A1 No Motor Current Alarm 113 Compressor A1 Star Delta Starter Failure Alarm 114 Compressor A1 Contactor Failure Alarm 115 Compressor A1 Unable To Stop Alarm 116 Compressor A1 Phase Reversal Alarm 117 Compressor A1 MTA Configuration Header Fault
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 58/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Alarm 201 Compressor A2 Motor Temperature Too High Alarm 202 Compressor A2 Motor Temperature Out of Range Alarm 203 Compressor A2 High Pressure Switch Alarm 204 Compressor A2 Over Current Alarm 205 Compressor A2 Lock Rotor Alarm 206 Compressor A2 Ground Fault Alarm 207 Compressor A2 Phase Loss L1 Alarm 208 Compressor A2 Phase Loss L2 Alarm 209 Compressor A2 Phase Loss L3 Alarm 210 Compressor A2 Unbalance > 14 % Alarm 211 Compressor A2 Unbalance > 18 % Alarm 212 Compressor A2 No Motor Current Alarm 213 Compressor A2 Star Delta Starter Failure Alarm 214 Compressor A2 Contactor Failure Alarm 215 Compressor A2 Unable To Stop Alarm 216 Compressor A2 Phase Reversal Alarm 217 Compressor A2 MTA Configuration Header Fault
Alarm 301 Compressor B1 Motor Temperature Too High Alarm 302 Compressor B1 Motor Temperature Out of Range Alarm 303 Compressor B1 High Pressure Switch Alarm 304 Compressor B1 Over Current Alarm 305 Compressor B1 Lock Rotor Alarm 306 Compressor B1 Ground Fault Alarm 307 Compressor B1 Phase Loss L1 Alarm 308 Compressor B1 Phase Loss L2 Alarm 309 Compressor B1 Phase Loss L3 Alarm 310 Compressor B1 Unbalance > 14 % Alarm 311 Compressor B1 Unbalance > 18 % Alarm 312 Compressor B1 No Motor Current Alarm 313 Compressor B1 Star Delta Starter Failure Alarm 314 Compressor B1 Contactor Failure Alarm 315 Compressor B1 Unable To Stop Alarm 316 Compressor B1 Phase Reversal Alarm 317 Compressor B1 MTA Configuration Header Fault
Alarm 401 Compressor B2 Motor Temperature Too High Alarm 402 Compressor B2 Motor Temperature Out of Range Alarm 403 Compressor B2 High Pressure Switch Alarm 404 Compressor B2 Over Current Alarm 405 Compressor B2 Lock Rotor Alarm 406 Compressor B2 Ground Fault Alarm 407 Compressor B2 Phase Loss L1 Alarm 408 Compressor B2 Phase Loss L2 Alarm 409 Compressor B2 Phase Loss L3 Alarm 410 Compressor B2 Unbalance > 14 % Alarm 411 Compressor B2 Unbalance > 18 % Alarm 412 Compressor B2 No Motor Current Alarm 413 Compressor B2 Star Delta Starter Failure Alarm 414 Compressor B2 Contactor Failure Alarm 415 Compressor B2 Unable To Stop Alarm 416 Compressor B2 Phase Reversal Alarm 417 Compressor B2 MTA Configuration Header Fault
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 59/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
6 - CCN COMPATIBILITY
30GX&HX Pro-Dialog 4 Control is compatible with:
wThe Building Supervisor wThe Network Service Tool
30GX&HX Pro-Dialog 4 Control is compatible with the following POCs:
wAlarm POC II wAutodial Gateway II wData Transfer/Collection History wDataport 1 wDataport 2 wSAM wNDS wCCN/JBUS Gateway wFlotronic System Manager wChiller SYstem Manager III
7 - PRO_DIALOG 4 DOWNLOADER ADDENDUM INFORMATION
The pro_dialog 4 control software shall be downloaded using the downloader version 3.0 or later. Here is the example of the downloader list (download.lis) which contains only pro_dialog 4 controls :
CESR208410-22 PD4 Global chiller GX & HXC SR 2.2 (1) CESR208400-22 PD4 Recip chiller 30 GK & 30HZ V2 SR 2.2 (1) CESRNRCP53-10 NRCP PD4 SLAVE ADDRESS 53 version 1.0 (2)
CESRSCPM10-60 PD4 SCPM board download SR 1.06 (2)
1. Software can be downloaded through CCN bus or through SIO bus
2. Software shall only be downloaded through SIO bus. Before downloading the software, use the reset command to erase the old software. Once F2 key is pressed, turn off and on quickly the power supply of the board, the message «Hard restart command successful !». Then go to the downloader , Select download, software and then press F2 to download the software as usual.
The «CESRNRCP53-10» shal be used for Aquasnap basic board download when cooler heater and reclaim option are selected.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 60/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
APPENDIX A - CCN DISPLAY, SETPOINT, MAINTENANCE TABLE SCREENS
...
DISPLAY SCREEN
TABLE NAME: GENUNIT PIC TABLE TYPE : 11H, instance 1
DESCRIPTION
STATUS UNITS POINTS FORCEABLE
1 GENERAL PARAMETERS 2 3 Control Type Local/CCN/Remote
1
- ctr_type N
4 Run Status running/Off/Stopping/Delay
2
- status N
5 CCN Chiller Start/Stop Enable/Dsable
3
- CHIL_S_S Y
6 Chiller Occupied? Yes/No
4
- CHIL_OCC Y 7 Minutes Left for Start 0-15 min MIN_LEFT N 8 Heat/Cool Select Heat/Cool
5
- HC_SEL Y 9 Heat Reclaim Select Yes/No
10
- RECL_SEL Y 10 11 Alarm State Normal
6
- ALM N 12 Current Alarm 1 nnn - alarm_1 N 13 Current Alarm 2 nnn - alarm_2 N 14 Current Alarm 3 nnn - alarm_3 N 15 Current Alarm 4 nnn - alarm_4 N 16 Current Alarm 5 nnn - alarm_5 N 17 18 Percent Total Capacity nnn % CAP_T N 19 Active Demand Limit Val nnn
7
% DEM_LIM Y 20 Lag Capacity Limit Value nnn % LAG_LIM N 21 Current Setpoint ±nnn.n °F SP N 22 Setpoint Occupied? Yes/No
4
- SP_OCC Y
23 Control Point ±nnn.n
8
°F CTRL_PNT Y 24 Controlled Water Temp ±nnn.n °F CTRL_WT N 25 External Temperature ±nnn.n °F OAT N 26 27 Emergency Stop Enable/Emstop
9
- EMSTOP Y
1 : Unit control type in effect as described in section 4.4.1.
2 : Unit current status as described in section 4.5.
wRunning means that the unit is started or allowed to start wOff means that the unit is stopped with all its outputs off wStopping means that the unit is required to stop but all its outputs (compressors) are not yet stopped. wDelay means that the unit is allowed to start but the delay at startup is not yet elapsed.
3 : Allows to Start/Stop the chiller only when unit under CCN control type. Forced value is displayed but unused
when the unit is not under CCN control.
4 : Occupied state. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead of the
real occupancy state. If the unit is not in CCN mode the forced value shall be unused and the regular time schedule shall be used. Forced value and force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
5: Heat/cool select. This item can be forced. If the unit is in CCN mode, the forced value shall be used whatever the
status of the remote heat/cool contacts. If the unit is not in CCN mode the forced value shall be unused. Forced value and force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 61/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
6 : Alarm status
wNormal (no alarm) wPartial (alarm but unit is not down) wShutdown (unit is down)
7: Active Demand Limit Value. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the external limit switch contact and whatever the value of the demand limit switch setpoint. If the unit is not in CCN mode the forced value shall be unused. Forced value and force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
8: Control Point. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead of the
real control point calculation. If the unit is not in CCN mode the forced value shall be unused. Forced value and
force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control. 9 : Active all the time even if the unit is not in CCN control type. 10: Heat Reclaim Select. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the remote reclaim switch. Forced value and force code shall appear in the GENUNIT
Points Display table only if the unit is under CCN control.
DISPLAY SCREEN
TABLE NAME: CIRCA_AN PIC TABLE TYPE : 11H, instance 2
DESCRIPTION
STATUS UNITS POINTS FORCEABLE
1 CIRCUIT A ANALOG VALUES
2. 3 Percent Total Capacity 0 - 100 % CAPA_T N 4 Discharge Pressure nnn.n psi DP_A N 5 Suction Pressure nnn.n psi SP_A N 6 Oil Pressure Cp1 nnn.n psi CPA1_OP N 7 Oil Pressure Cp2 nnn.n psi CPA2_OP N 8 Oil Press Difference Cp1 nnn.n psi DOP_A1 N 9 Oil Press Difference Cp2 nnn.n psi DOP_A2 N 10 Economizer Pressure Cp1 nnn.n psi CPA1_ECP N 11 Economizer Pressure Cp2 nnn.n psi CPA2_ECP N 12 Saturated Condensing Tmp ±nnn.n °F SCT_A N 13 Saturated Suction Temp ±nnn.n °F SST_A N 14 Discharge Gas Temp Cp 1 ±nnn.n °F CPA1_DGT N 15 Discharge Gas Temp Cp 2 ±nnn.n °F CPA2_DGT N 16 Average Discharge Gas Tp ±nnn.n °F dt_a N 17 Motor Temperature Comp 1 ±nnn.n °F CPA1_TMP N 18 Motor Temperature Comp 2 ±nnn.n °F CPA2_TMP N 19 Motor Current Comp 1 nnn.n AMPS CPA1_CUR N 20 Motor Current Comp 2 nnn.n AMPS CPA2_CUR N 21 EXV Position 0 - 100 % EXV_A N 22 Head Press Actuator Pos 0 - 100 % hd_pos_a N 23 Cooler Exchange Delta T n.n ^F PINCH_A N 24 Motor Cool TQ in Kohms nn.n MTQ_RESA N 25 Motor Cooling Puls Cycle nnn CPA1_PUL N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 62/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: CIRCA_D PIC TABLE TYPE : 11H, instance 3
DESCRIPTION
STATUS UNITS POINTS FORCIBLE
1 CIRCUIT A DISCRETE 2 3 Compressor 1 Output On/Off - CP_A1 N 4 Cp1 Mtr Cool Solenoid 1 On/Off - cpa1_mc1 N 5 Cp1 Mtr Cool Solenoid 2 On/Off - cpa1_mc2 N 6 Cp1, Oil Solenoid Out On/Off - cpa1_ols N 7 Compressor 2 Output On/Off - CP_A2 N 8 Cp2 Mtr Cool Solenoid 1 On/Off - cpa2_mc1 N 9 Cp2 Mtr Cool Solenoid 2 On/Off - cpa2_mc2 N 10 Cp2, Oil Solenoid Out On/Off - cpa2_ols N 11 Cir A, Loader 1 Output On/Off - ldr_1_a N 12 Cir A, Loader 2 Output On/Off - ldr_2_a N 13 Cir A, Oil Heater Output On/Off - oil_h_a N 14 Cir A, Oil Level Input Low/High - oil_l_a N 15 Cir A, Oil Pump Output On/Off - oilpmp_a N 16 Cir A Refrig Isolate Out On/Off - refa_iso N 17 18 FANS OUTPUT 19 Fan Output DO # 1 On/Off - fan_a1 N 20 Fan Output DO # 2 On/Off - fan_a2 N 21 Fan Output DO # 3 On/Off - fan_a3 N 22 Fan Output DO # 4 On/Off - fan_a4 N 23 Fan Output DO # 5 On/Off - fan_a5 N 24 Fan Output DO # 6 On/Off - fan_a6 N 25 Fan Output DO # 7 On/Off - fan_a7 N 26 Fan Output DO # 8 On/Off - fan_a8 N 27 Fan Staging Number 0 - 8 - FAN_ST_A N
DISPLAY SCREEN
TABLE NAME: CIRCB_AN PIC TABLE TYPE : 11H, instance 4
DESCRIPTION
STATUS UNITS POINTS FORCEABLE
1 CIRCUIT B ANALOG VALUES
2. 3 Percent Total Capacity 0 - 100 % CAPB_T N 4 Discharge Pressure nnn.n psi DP_B N 5 Suction Pressure nnn.n psi SP_B N 6 Oil Pressure Cp1 nnn.n psi CPB1_OP N 7 Oil Pressure Cp2 nnn.n psi CPB2_OP N 8 Oil Press Difference Cp1 nnn.n psi DOP_B1 N 9 Oil Press Difference Cp2 nnn.n psi DOP_B2 N 10 Economizer Pressure Cp1 nnn.n psi CPB1_ECP N 11 Economizer Pressure Cp2 nnn.n psi CPB2_ECP N 12 Saturated Condensing Tmp ±nnn.n °F SCT_B N 13 Saturated Suction Temp ±nnn.n °F SST_B N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 63/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
14 Discharge Gas Temp Cp 1 ±nnn.n °F CPB1_DGT N 15 Discharge Gas Temp Cp 2 ±nnn.n °F CPB2_DGT N 16 Average Discharge Gas Tp ±nnn.n °F dt_b N 17 Motor Temperature Comp 1 ±nnn.n °F CPB1_TMP N 18 Motor Temperature Comp 2 ±nnn.n °F CPB2_TMP N 19 Motor Current Comp 1 nnn.n AMPS CPB1_CUR N 20 Motor Current Comp 2 nnn.n AMPS CPB2_CUR N 21 EXV Position 0 - 100 % EXV_B N 22 Head Press Actuator Pos 0 - 100 % hd_pos_b N 23 Cooler Exchange Delta T n.n ^F PINCH_B N 24 Motor Cool TQ in Kohms nn.n MTQ_RESB N 25 Motor Cooling Puls Cycle nnn CPB1_PUL N
DISPLAY SCREEN
TABLE NAME: CIRCB_D PIC TABLE TYPE : 11H, instance 5
DESCRIPTION
STATUS UNITS POINTS FORCEABLE
1 CIRCUIT B DISCRETE 2 3 Compressor 1 Output On/Off - CP_B1 N 4 Cp1 Mtr Cool Solenoid 1 On/Off - cpb1_mc1 N 5 Cp1 Mtr Cool Solenoid 2 On/Off - cpb1_mc2 N 6 Cp1, Oil Solenoid Out On/Off - cpb1_ols N 7 Compressor 2 Output On/Off - CP_B2 N 8 Cp2 Mtr Cool Solenoid 1 On/Off - cpb2_mc1 N 9 Cp2 Mtr Cool Solenoid 2 On/Off - cpb2_mc2 N 10 Cp2, Oil Solenoid Out On/Off - cpb2_ols N 11 Cir B, Loader 1 Output On/Off - ldr_1_b N 12 Cir B, Loader 2 Output On/Off - ldr_2_b N 13 Cir B, Oil Heater Output On/Off - oil_h_b N 14 Cir B, Oil Level Input Low/High - oil_l_b N 15 Cir B, Oil Pump Output On/Off - oilpmp_b N 16 Cir B Refrig Isolate Out On/Off - refb_iso N 17 18 FANS OUTPUT 19 Fan Output DO # 1 On/Off - fan_b1 N 20 Fan Output DO # 2 On/Off - fan_b2 N 21 Fan Output DO # 3 On/Off - fan_b3 N 22 Fan Output DO # 4 On/Off - fan_b4 N 23 Fan Output DO # 5 On/Off - fan_b5 N 24 Fan Output DO # 6 On/Off - fan_b6 N 25 Fan Output DO # 7 On/Off - fan_b7 N 26 Fan Output DO # 8 On/Off - fan_b8 N 27 Fan Staging Number 0 - 8 - FAN_ST_B N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 64/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: OPTIONS PIC TABLE TYPE : 11H, instance 6
DESCRIPTION
STATUS UNITS POINTS FORCEABLE
1 UNIT DISCRETE IN 2 Remote On/Off Switch Open/Close - onoff_sw N 3 Remote Heat/Cool Switch Open/Close - hc_sw N 4 Remote Reclaim Switch Open/Close - recl_sw N
5 Remote Setpoint Switch Open/Close - setp_sw N 6 Limit Switch Status Open/Close - limit_sw N 7 Interlock Status Open/Close - lock_1 N 8 Pump Run status On/Off - pump_def N
9 Condenser Flow Status Open/Close - condflow N 10 Electrical Box Thermostat Open/Close
4
- elec_box N
11 12 UNIT DISCRETE OUT 13 Cooler Pump #1 Command On/Off
1
- CLPUMP_1 Y
14 Cooler Pump #2 Command On/Off
1
- CLPUMP_2 Y
15 Rotate Pumps Now? Yes/No
1
- ROT_PUMP Y
16 Condenser Pump Command On/Off
3
- COND_PMP Y
17 Cooler Heater Command On/Off - coolheat N 18 Critical Alarm Signal On/Off
5
- SAFE_ALM N
19 20 UNIT ANALOG
21 Cooler Entering Fluid ±nnn.n °F COOL_EWT N 22 Cooler Leaving Fluid ±nnn.n °F COOL_LWT N 23 Condenser Entering Fluid ±nnn.n °F COND_EWT N 24 Condenser Leaving Fluid ±nnn.n °F COND_LWT N 25 CHWS Temperature ±nnn.n °F CHWSTEMP N
26 External 0-10Vdc Signal ±nn.n Volts EXT_VDC N 27 Current Cond Setpoint nnn.n
2
°F COND_SP Y
28 Chiller Total Current nnn.n amps tot_curr N
1: Cooler pump control. This item can be forced On or Off if the unit is in CCN mode and if the CHIL_S_S is
disabled. If the unit is not in CCN mode the forced value shall be unused and the regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display table only if the unit is under CCN control and if CHIL_S_S is disabled.
If PUMP#1 is forced, no force shall be allowed on PUMP_2 and vice versa. 2: Condensing Setpoint. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead
of the real control point calculation. If the unit is not in CCN mode the forced value shall be unused and the regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display table only if the unit is under CCN control.
3: Condenser pumpcontrol. This item can be forced On but not Off
. If the unit is in CCN mode, the forced value shall be used instead of regular pump control point. If the unit is not in CCN mode the forced value shall be unused and the regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display table only if the unit is under CCN control.
4: Electrical box Thermostat. This item indicates the electrical box thermostat and network power reverse phase
detection status (wired internally in series 16a and 16b on PD4-BASIC BOARD). These contacts, when opened will prevent the unit from starting.
5: This output is energized when a contact failure is reported by any SCPM board
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 65/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: RECLAIM PIC TABLE TYPE : 11H, instance 7
DESCRIPTION
STATUS UNITS POINTS FORCEABLE
1 RECLAIM ANALOG PARAM 2 Reclaim Entering Fluid ±nnn.n °F HR_EWT N 3 Reclaim Leaving Fluid ±nnn.n °F HR_LWT N 4 Reclaim Fluid Setpoint ±nnn.n °F hr_sp N 5 Cir A SCT Control Point ±nnn.n °F sct_a_sp N 6 Cir B SCT Control Point ±nnn.n °F sct_b_sp N 7 Cir A Pumpdown Pressure ±nnn.n psi pmpd_p_a N 8 Cir B Pumpdown Pressure ±nnn.n psi pmpd_p_b N 9 A Saturated Pumpdown Tmp ±nnn.n °F pd_sat_a N 10 B Saturated Pumpdown Tmp ±nnn.n °F pd_sat_b N 11 HR Cond Valve Position ±nnn.n % hr_v_pos N 12 13 RECLAIM DISCRETE PARAM - N 14 Heat Reclaim Select Yes/No No RECL_SEL N
15 Condenser Flow Status Open/Close - condflow N 16 Cir A Reclaim Valve Stat On/Off - hr_val_a N 17 Cir B Reclaim Valve Stat On/Off - hr_val_b N 18 A Pumpdown Valve Status On/Off - pd_val_a N 19 B Pumpdown Valve Status On/Off - pd_val_b N 20 Circuit A Reclaim Status n hrstat_a N 21 Circuit B Reclaim Status n hrstat_b N 22 Reclaim Condenser Heater On/Off - cond_htr N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 66/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
TABLE NAME: MODES PIC TABLE TYPE : 11H, instance 8
DESCRIPTION STATUS UNITS POINTS FORCEABLE
1 OPERATING MODES 2 Startup Delay in Effect Yes/No - Mode[07] N 3 Second Setpoint in Use Yes/No - Mode[08] N 4 Reset in Effect Yes/No - Mode[09] N 5 Demand Limit Active Yes/No - Mode[10] N 6 Ramp Loading Active Yes/No - Mode[11] N 7 Low Source Protection Yes/No - Mode[12] N 8 Low Cooler Suction Cir A Yes/No - Mode[13] N 9 Low Cooler Suction Cir B Yes/No - Mode[14] N 10 Low Dis Superheat Cir A Yes/No - Mode[15] N 11 Low Dis Superheat Cir B Yes/No - Mode[16] N 12 High Pres Override Cir A Yes/No - Mode[17] N 13 High Pres Override Cir B Yes/No - Mode[18] N 14 High Current Over Cir A Yes/No - Mode[19] N 15 High Current Over Cir B Yes/No - Mode[20] N 16 Reclaim Active? Yes/No - Mode[21] N 17 Cooler Heater Active? Yes/No - Mode[22] N 18 Cooler Pumps Rotation? Yes/No - Mode[23] N 19 Pump Periodic Start? Yes/No - Mode[24] N 20 Night Capacity Active? Yes/No - Mode[25] N 21 System Manager Active? Yes/No - Mode[26] N 22 Master Slave Active? Yes/No - Mode[27] N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 67/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CONFIGURATION SCREEN
TABLE NAME: USER PIC TABLE TYPE : 10H, instance 2
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 USER CONFIGURATION 2 3 Circuit Loading Sequence 0/1/2 0 - lead_cir 4 0 = Auto 5 1 = Circuit A First 6 2 = Circuit B First 7 Loading Sequence 0/1 0 - seq_typ
8 9 Ramp Loading Select Yes/No No - ramp_sel 10 11 Unit Off to On Delay 1 to 15 1 min off_on_d 12 13 Cooler Pumps Sequence 0/1/2/3/4 0 - pump_seq 14 0 = No Pump 15 1 = One Pump Only 16 2 = Two Pumps Auto 17 3 = Pump#1 Manual 18 4 = Pump#2 Manual 19 Pump Auto Rotation Delay 24 to 3000 48 hours pump_del 20 Periodic Pumps Start Yes/No No - pump_per 21 22 Reset Type Select 0 to 3 0 - res_sel
23 0 = None 24 1 = Voltage Control 25 2 = Delta T Control 26 3 = OAT Control 27
28 Demand Limit Type Select 0 to 2 0 - lim_sel 29 0 = None
30 1 = Switch Control 31 2 = 0-10vdc Control 32 Vdc For 100% Demand Lim 0 to 10 0 volts lim_mx
33 Vdc For 0% Demand Limit 0 to 10 10 volts lim_ze 34
35 Night Control 36 Start Hour 00:00 to 24:00 00:00 - nh_start 37 End Hour 00:00 to 24:00 00:00 - nh_end 38 Capacity Limit 0 to 100 100 % nh_limit 39 Capacity Limit 0 to 100 100 % nh_limit 40 41 Chiller Comp Current Limit 90 to 1500
1
1500 amps curr_lim 42 Menu Description Select Yes/No Yes - menu_des 43 Pass For All User Config Yes/No No - all_pass
1. Refer to control capacity override #35, chiller current limit description
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 68/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
TABLE NAME: BRODEFS PIC TABLE TYPE : 14H, instance 1
DESCRIPTION STATUS DEFAULT UNITS POINT 1 Activate Yes/No No - ccnbroad
2 3 OAT Broadcast 4 Bus # 0 to 239 0 - oatbusnm 5 Element # 0 to 239 0 - oatlocad 6 7 DAYLIGHT SAVINGS START 8 Month 1 to 12 4 - startmon 9 Day 1 to 31 15 - startday 10 Time 00:00 to 24:00 02:00 - starttim 11 Minutes to Add 0 to 1440 60 - min_add 12 13 DAYLIGHT SAVINGS STOP 14 Month 1 to 12 10 - stopmon 15 Day 1 to 31 15 - stopday 16 Time 00:00 to 24:00 02:00 - stoptim 17 Minutes to Subtract 0 to 1440 60 - min_sub
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 69/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CONFIGURATION SCREEN
TABLE NAME: OCCDEFCS / OCCPC01S and OCCPC02S PIC TABLE TYPE : 14H, instance 2
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Timed Override Hours 0-4 0 - ovr_ext 2 Period 1 DOW (MTWTFSSH) 0/1 11111111 - dow1 3 Occupied From 0:00-24:00 0:00 - occtod1 4 Occupied To 0:00-24:00 24:00 - unoctod1 5 Period 2 DOW (MTWTFSSH) 0/1 00000000 - dow2 6 Occupied From 0:00-24:00 0:00 - occtod2 7 Occupied To 0:00-24:00 24:00 - unoctod2 8 Period 3 DOW (MTWTFSSH) 0/1 00000000 - dow3 9 Occupied From 0:00-24:00 0:00 - occtod3 10 Occupied To 0:00-24:00 24:00 - unoctod3 11 Period 4 DOW (MTWTFSSH) 0/1 00000000 - dow4 12 Occupied From 0:00-24:00 0:00 - occtod4 13 Occupied To 0:00-24:00 24:00 - unoctod4 14 Period 5 DOW (MTWTFSSH) 0/1 00000000 - dow5 15 Occupied From 0:00-24:00 0:00 - occtod5 16 Occupied To 0:00-24:00 24:00 - unoctod5 17 Period 6 DOW (MTWTFSSH) 0/1 00000000 - dow6 18 Occupied From 0:00-24:00 0:00 - occtod6 19 Occupied To 0:00-24:00 24:00 - unoctod6 20 Period 7 DOW (MTWTFSSH) 0/1 00000000 - dow7 21 Occupied From 0:00-24:00 0:00 - occtod7 22 Occupied To 0:00-24:00 24:00 - unoctod7 23 Period 8 DOW (MTWTFSSH) 0/1 00000000 - dow8 24 Occupied From 0:00-24:00 0:00 - occtod8 25 Occupied To 0:00-24:00 24:00 - unoctod8
TABLE NAME: HOLIDAY / HOLDY01S to HOLDY016S PIC TABLE TYPE : 14H, instance 3
DESCRIPTION STATUS DEFAULT UNITS POINT Holiday Start Month 0-12 0 - HOL_MON
Start Day 0-31 0 - HOL_DAY Duration (days) 0-99 0 - HOL_LEN
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 70/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
SETPOINT SCREEN
TABLE NAME: SETPOINT PIC TABLE TYPE : 17H, instance 1
DESCRIPTION
STATUS DEFAULT UNITS POINT
1 COOLING 2 Cooling Setpoint 1 - 20 to 101 44.0 °F csp1 3 Cooling Setpoint 2 - 20 to 101 44.0 °F csp2 4 Voltage No Reset Value 0 to 10 0.0 volts v_cr_no 5 Voltage Full Reset Value 0 to 10 0.0 volts v_cr_fu 6 Delta T No Reset Value 0 to 25 0.0 ^F dt_cr_no 7 Delta T Full Reset Value 0 to 25 0.0 ^F dt_cr_fu 8 OAT No Reset Value 14 to 125 0.0 °F oatcr_no 9 OAT Full Reset Value 14 to 125 0.0 °F oatcr_fu 10 Cooling Reset Deg. Value -30 to 30 0.0 ^F cr_deg 11 Cooling Ramp Loading 0.2 to 2.0 1.0 ^F cramp_sp 12 13 HEATING 14 Heating Setpoint 80 to 153 100.0 °F hsp 15 Voltage No Reset Value 0 to 10 0.0 volts v_hr_no 16 Voltage Full Reset Value 0 to 10 0.0 volts v_hr_fu 17 Delta T No Reset Value 0 to 25 0.0 ^F dt_hr_no 18 Delta T Full Reset Value 0 to 25 0.0 ^F dt_hr_fu 19 Heating Reset Deg. Value -30 to 30 0.0 ^F hr_deg 20 Heating Ramp Loading 0.2 to 2.0 1.0 ^F hramp_sp 21 22 HEAD PRESSURE 23 Sat Cond Temp Setpoint 95 to 140
1
104.0 °F headsp 24 Reclaim Setpoint 95 to 140 122.0 °F rsp 25 26 DEMAND LIMIT 27 Switch Demand Limit Setp 0 to 100 100 % lim_sp
1 : For water cooled, headsp low limit is 80°F (26.7 degC)
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 71/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MAINTENANCE SCREEN
TABLE NAME: LOADFACT PIC TABLE TYPE : 12H, instance 1
DESCRIPTION STATUS UNITS POINT
1 CAPACITY CONTROL 2 Average Ctrl Water Temp ±nnn.n °F ctrl_avg 3 Differential Water Temp ±nnn.n °F diff_wt 4 Water Delta T ±nnn.n ^F delta_t 5 Control Point ±nnn.n °F CTRL_PNT 6 Reset Amount ±nnn.n ^F reset 7 Controlled Temp Error ±nnn.n ^F tp_error 8 Actual Capacity nnn % cap_t 9 Actual Capacity Limit nnn % cap_lim 10 Current Z Multiplier Val ±n.n - zm
11 Load/Unload Factor ±nnn.n - smz 12 Active Capacity Override nn - over_cap 13 14 CIRCUIT A EXV CONTROL
15 EXV Position nnn.n % EXV_A 16 EXV Position Limit nnn.n % exvlim_a 17 Cooler Exchange Delta T n.n ^F PINCH_A 18 Discharge Superheat n.n °F DSH_A 19 Economizer pinch offset n.n ^F offset_a 20 EXV Override nn - ov_exv_a 21 22 CIRCUIT B EXV CONTROL
23 EXV Position nnn.n % EXV_B 24 EXV Position Limit nnn.n % exvlim_b 25 Cooler Exchange Delta T n.n ^F PINCH_B 26 Discharge Superheat n.n °F DSH_B 27 Economizer pinch offset n.n ^F offset_b 28 EXV Override nn - ov_exv_b
TABLE NAME: LAST_POR PIC TABLE TYPE : 12H, instance 6
1 PowerDown 1:day-mon-year nnnnnn ddmmyy date_of1 2 PowerDown 1:hour-minute nnnn hhmm time_of1 3 Power On 2: day-mon-year nnnnnn ddmmyy date_on1 4 Power On 2: hour-minute nnnn hhmm time_on1 5 PowerDown 2:day-mon-year nnnnnn ddmmyy date_of2 6 PowerDown 2:hour-minute nnnn hhmm time_of2 7 Power On 2: day-mon-year nnnnnn ddmmyy date_on2 8 Power On 2: hour-minute nnnn hhmm time_on2 9 PowerDown 3:day-mon-year nnnnnn ddmmyy date_of3 10 PowerDown 3:hour-minute nnnn hhmm time_of3 11 Power On 3: day-mon-year nnnnnn ddmmyy date_on3 12 Power On 3: hour-minute nnnn hhmm time_on3 13 PowerDown 4:day-mon-year nnnnnn ddmmyy date_of4 14 PowerDown 4:hour-minute nnnn hhmm time_of4 15 Power On 4: day-mon-year nnnnnn ddmmyy date_on4 16 Power On 4: hour-minute nnnn hhmm time_on4 17 PowerDown 5:day-mon-year nnnnnn ddmmyy date_of5 18 PowerDown 5:hour-minute nnnn hhmm time_of5 19 Power On 5: day-mon-year nnnnnn ddmmyy date_on5 20 Power On 5: hour-minute nnnn hhmm time_on5
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 72/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MAINTENANCE SCREEN
TABLE NAME: M_MSTSLV PIC TABLE TYPE : 12H, instance 3
DESCRIPTION
STATUS UNITS POINT
1 MASTER/SLAVE CONTROL 2 Unit is Master or Slave Disable/Master/Slave - mstslv 3 Master Control Type Local/Remote/CCN
3
- ms_ctrl 4 Master/Slave Ctrl Active True/False - ms_activ 5 Lead Unit is the: Master/Slave - lead_sel 6 Slave Chiller State 0/1/2/3/4/5
1
- slv_stat 7 Slave Chiller Total Cap 0-100 % slv_capt 8 Lag Start Delay 1 to 30
2
minutes l_strt_d
9 Lead/Lag Hours Delta ±nnnnn
3
hours ll_hr_d
10 Lead/Lag Changeover? Yes/No
4
- ll_chang 11 Lead Pulldown? Yes/No
4
- ll_pull 12 Master/Slave Error nn - ms_error 13 Max Available Capacity ? True/False
5
- cap_max
1: Slave chiller chilstat value 2: This decision is consistent for Master chiller only. It shall be set by default to 0 for the slave chiller. 3: Always CCN for the slave chiller. 4: This decision is consistent for Master chiller only. It shall be set by default to 'No' for the slave chiller. 5: This item is true when chiller has loaded its total unbroken capacity tonnage.
TABLE NAME: SERMAINT PIC TABLE TYPE : 12H, instance 5
DESCRIPTION
STATUS UNITS POINT FORCEABLE
1 Reset Maintenance Alert nn - S_RESET Y 2 1 - 11: reset individually 3 12 : reset all 4 5 OPERATION WARNINGS 6 1 - Refrigerant Charge Normal/Low - charge_m N 7 2 - Water Loop Size Normal/Low - wloop_m N 8 3 - Air Exchanger Normal/Dirty - aexch_m N 10 11 GENERAL SERVICING DELAYS 12 4 - CPump 1 (days) 0 to 1000/Alert - cpump1_m N 13 5 - CPump 2 (days) 0 to 1000/Alert - cpump2_m N 14 6 - HPump (days) 0 to 1000/Alert - hpump_m N 15 7 - Water Filter (days) 0 to 1000/Alert - wfilte_m N 16 8 - A1 Oil Filter (days) 0 to 1000/Alert ofila1_m N 17 9 - A2 Oil Filter (days) 0 to 1000/Alert ofila2_m N 18 10- B1 Oil Filter (day) 0 to 1000/Alert ofilb1_m N 19 11- B2 Oil Filter (days) 0 to 1000/Alert ofilb2_m N
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 73/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MAINTENANCE SCREEN
TABLE NAME: STRTHOUR PIC TABLE TYPE : 12, instance 3
DESCRIPTION
STATUS UNITS POINT
1 MACHINE 2 Total Operating Hours nnnnn hours HR_MACH 3 Starts Number nnnnn - st_mach 4 Compressor A1 Hours nnnnn hours HR_CP_A1 5 Compressor A2 Hours nnnnn hours HR_CP_A2 6 Compressor A1 Starts nnnnn - st_cp_a1 7 Compressor A2 Starts nnnnn - st_cp_a2 8 Compressor B1 Hours nnnnn hours HR_CP_B1 9 Compressor B2 Hours nnnnn hours HR_CP_B2 10 Compressor B1 Starts nnnnn - st_cp_b1 11 Compressor B2 Starts nnnnn - st_cp_b2 12 Starts Max During 1 Hour nn - st_cp_mx
13 Starts/hr From Last 24 h nn - st_cp_av 14 Cooler Pump #1 Hours nnnnn hours hr_cpum1
15 Cooler Pump #2 Hours nnnnn hours hr_cpum2 16 Condenser Pump Hours nnnnn hours hr_hpump
Note
: Table for display only.
TABLE NAME: MTA_SCHM PIC TABLE TYPE : 12H, instance 4
DESCRIPTION
STATUS DEFAULTUNITS POINT
1 SCPM A1 MTA Header Read 0 to 560 0 Amps cpa1_mta 2 SCPM A2 MTA Header Read 0 to 560 0 Amps cpa2_mta 3 SCPM B1 MTA Header Read 0 to 560 0 Amps cpb1_mta 4 SCPM B2 MTA Header Read 0 to 560 0 Amps cpb2_mta 5 6 Scheme Number 0 to 5 3 - scheme 7 SCPM A1 Software Version nnn.nn 0 cpa1_ver 8 SCPM A2 Software Version nnn.nn 0 cpa2_ver 9 SCPM B1 Software Version nnn.nn 0 cpb1_ver 10 SCPM B2 Software Version nnn.nn 0 cpb2_ver
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 74/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
TABLE NAME: OCCMAINT PIC TABLE TYPE : 15,
DESCRIPTION
STATUS UNITS POINT
1 Current Mode (1=occup.) 0/1 - MODE 2 Current Occup Period # 1 to 8 - PER_NO 3 Timed -Override in Effect Yes/No - OVERLAST 4 Timed-Override Duration 0 to 4 hours OVR_HRS 5 Current Occupied Time 00:00 to 23:59 - STRTTIME 6 Current Unoccupied Time 00:00 to 23:59 - ENDTIME 7 Next Occupied Day Mon to Sun - NXTOCDAY 8 Next Occupied Time 00:00 to 23:59 - NXTOCTIM 9 Next Unocupied Day Mon to Sun - NXTUNDAY 10 Next Unoccupied Time 00:00 to 23:59 - NXTUNTIM 11 Prev Unocupied Day Mon to Sun - PRVUNDAY 12 Prev Unoccupied Time 00:00 to 23:59 - PRVUNTIM
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 75/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
APPENDIX B
CCN Variables
The following variables can be used for trace functions (Network Service Tool-Trace, Data Collection).
CCN Variables: Hardware SIO Points
cpa2 _mta> 0H-DO-Compressor A2, CommandCP_A2
allH-AI-Compressor A1, status and MTA reading CPA1_STA
allH-AI°FCompressor A1, Motor Temperature CPA1_TMP
allH-AI°FCompressor A1, Discharge Gas TemperatureCPA1_DGT
allH-AIpsiCompressor A1, Economizer PressureCPA1_ECP
allH-AIpsiCompressor A1, Oil PressureCPA1_OP
allH-AIAmpsCompressor A1, Current CPA1_CUR
econ_sel = 1H-AO-Circuit A Motor cooling thermal valve outputCPA1_PUL
AllH-DO-Compressor A1, multiplexed DO's
b
5b4b3b2b1b0
b
0
: cpa1_mc1 Motor cooling 1
b
1
: cpa1_mc2 Motor cooling 2 or economizer valve b
2
: cpa1_ols Oil solenoid b
3
: cpa1_ld1 Loader 1 output b
4
: cpa1_ld2 Loader 2 output b
5
: oilpmp_a Oil pump output circuit A
CPA1_MUX
allH-DO-Compressor A1, CommandCP_A1
AllH-DOCondenser Water Pump , CommandCONDPUMP
pump_seq > 1H-DOCooler Water Pump # 2, CommandCPUMP_2
pump_seq > 0H-DOCooler Water Pump # 1, CommandCPUMP_1
allH-AI°FCooler leaving water temperatureCOOL_LWT
allH-AI°FCooler entering water temperatureCOOL_EWT
unit_typ = 2 or 3 H-AI°FCondenser leaving water temperatureCOND_LWT
unit_typ = 2 or 3H-AI°FCondenser entering water temperatureCOND_EWT
AllH-AI°FChiller Water System for Master / Slave ControlCHWSTEMP
cpb1_mta > 0H-DOCircuit B Alarm Relay, CommandALARM_B
allH-DOCircuit A Alarm Relay, CommandALARM_A
CONFIGURATIONTYPEUNITSDESCRIPTIONSPOINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 76/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
cb2_mta> 0H-AIpsiCompressor B2, Oil PressureCPB2_OP
cb2_mta> 0H-AIAmpsCompressor B2, Current CPB2_CUR
cb2_mta > 0H-DO-Compressor B2, multiplexed DO's
b
5b4b3b2b1b0
b
0
: cpb2_mc1 Motor cooling 1 b
1
: cpb2_mc2 Motor cooling 2 or economizer valve b
2
: cpb2_ols Oil solenoid b
3
: cpb2_ld1 Loader 1 output b
4
: cpb2_ld2 Loader 2 output b
5
: not used
CPB2_MUX
cpb2_mta> 0H-DO-Compressor B2, CommandCP_B2
cpb1_mta> 0H-AI-Compressor B1, status and MTA reading CPB1_STAT
cpb1_mta > 0H-AI°FCompressor B1, Motor Temperature CPB1_TMP
cpb1_mta> 0H-AI°FCompressor B1, Discharge Gas TemperatureCPB1_DGT
cpb1_mta > 0H-AIpsiCompressor B1, Economizer PressureCPB1_ECP
cpb1_mta > 0H-AIpsiCompressor B1, Oil PressureCPB1_OP
cpb1_mta > 0H-AIAmpsCompressor B1, Current CPB1_CUR
cpb1_mta> 0 and
econ_sel = 1
H-AO-Circuit B Motor cooling thermal valve outputCPB1_PUL
cpb1_mta > 0H-DO-Compressor B1, multiplexed DO's
b
5b4b3b2b1b0
b
0
: cpb1_mc1 Motor cooling 1 b
1
: cpb1_mc2 Motor cooling 2 or economizer valve b
2
: cpb1_ols Oil solenoid b
3
: cpb1_ld1 Loader 1 output b
4
: cpb1_ld2 Loader 2 output b
5
: oilpmp_b Oil pump output circuit B
CPB1_MUX
cpb1_mta> 0H-DO-Compressor B1, CommandCP_B1
cpa2_mta> 0H-AI-Compressor A2, status and MTA reading CPA2_STA
cpa2_mta> 0H-AI°FCompressor A2, Motor Temperature CPA2_TMP
cpa2_mta> 0H-AI°FCompressor A2, Discharge Gas TemperatureCPA2_DGT
cpa2_mta > 0 and
econ_sel = 0
H-AIpsiCompressor A2, Economizer PressureCPA2_ECP
cpa2_mta> 0H-AIpsiCompressor A2, Oil PressureCPA2_OP
cpa2_mta > 0H-AIAmpsCompressor A2, Current CPA2_CUR
cpa2_mta > 0H-DO-Compressor A2, multiplexed DO's
b
5b4b3b2b1b0
b
0
: cpa2_mc1 Motor cooling 1 b
1
: cpa2_mc2 Motor cooling 2 or economizer valve b
2
: cpa2_ols Oil solenoid b
3
: cpa2_ld1 Loader 1 output b
4
: cpa2_ld2 Loader 2 output b
5
: not used
CPA2_MUX
CONFIGURATIONTYPEUNITSDESCRIPTIONSPOINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 77/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
all
(all) (all)
(unit_typ = 3)
(unit_typ = 1 or 4)
(all) (all) (all) (all)
(uni_typ = 1 or 4)
H-DIM-Basic board multilexed DI's:
b
7b6b5b4b3b2b1b0
b0: onoff_sw Remote on/off switch b
1
: spt_sw Remote dual setpoint sw b
2
: hc_sw Remote heat/cool switch b
2
: recl_sw Remote reclaim swutch b
3
: limit_sw demand limit switch b
4
: lock_1 Cooler interlock b
5
: elec_box Electrical Box Thermostat b
6
: condflow Condenser flow switch b
7
: pump_def Pump default
MUX_DI
econ_sel and tq_r_fbk=
YES
H-AI-Motor Cooling Feedback Signal circuit B MTQ_RESB
econ_sel and tq_r_fbk=
YES
H-AI-Motor Cooling Feedback Signal circuit A MTQ_RESA
recl_opt = 1H-AO0 -
10Vdc
Reclaim Condenser Water ValveHR_WTRVL
hr_tmp = 1H-AI°FReclaim Entering Water TemperatureHR_LWT
hr_tmp = 1H-AI°FReclaim Entering Water TemperatureHR_EWT
hd_selec > 0H-AO4 - 20
mA
0 -
10Vdc
Varifan or Water Valve Circuit BHD_B
hd_selec > 0H-AO4 - 20
mA
0 -
10Vdc
Varifan or Water Valve Circuit AHD_A
cb2_mta> 0H-AIpsiDischarge Pressure Circuit BDP_B
allH-AIpsiDischarge Pressure Circuit ADP_A
allH-AIvoltsExternal 0 - 10 Vdc input sensor EXT_VDC
cb2_mta > 0H-AO%EXV Movement Circuit BEXV_ST_B
allH-AO%EXV Movement Circuit AEXV_ST_A
cb2_mta> 0H-AI-Compressor B2, status and MTA reading CPB2_STA
cb2_mta> 0H-AI°FCompressor B2, Motor Temperature CPB2_TMP
cb2_mta> 0H-AI°FCompressor B2, Discharge Gas TemperatureCPB2_DGT
cb2_mta > 0 and
econ_sel = 0
H-AIpsiCompressor B2, Economizer PressureCPB2_ECP
CONFIGURATIONTYPEUNITSDESCRIPTIONSPOINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 78/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
unit_typ = 1
nb_fan_b> 0
total comp > 6
H-DOFan Aux board , multiplexed DO's
b
7b6b5b4b3b2b1b0
b
0
: fan_b1 Fan output 1, circuit B b
1
: fan_b2 Fan output 2, circuit B b
2
: fan_b3 Fan output 3, circuit B b
3
: fan_b4 Fan output 4, circuit B b
4
: fan_b5 Fan output 5, circuit B b
5
: fan_b6 Fan output 6, circuit B b
6
: fan_b7 Fan output 7, circuit B b
7
: fan_b8 Fan output 8, circuit B
nbfan_a > 2 and
nbfan_b> 2
H-DO-Fan 4xDO board #2, multiplexed DO's
b
4b3b2b1b0
b
0
: fan_b1 Fan output 1, circuit B b
1
: fan_b2 Fan output 2, circuit B b
2
: fan_b3 Fan output 3, circuit B b
3
: fan_b4 Fan output 4, circuit B
MUX_FAN2
unit_typ = 1
nb_fan_a> 0
nb_fan_a > 0 and
nb_fantotal comp > 6
Total comp < 7
H-DOFan Aux board , multiplexed DO's
b
7b6b5b4b3b2b1b0
b
0
: fan_a1 Fan output 1, circuit A b
1
: fan_a2 Fan output 2, circuit A b
2
: fan_a3 Fan output 3, circuit A b
3
: fan_a4 Fan output 4, circuit A
b
4
: fan_a5 Fan output 5, circuit A b
5
: fan_a6 Fan output 6, circuit A b
6
: fan_a7 Fan output 7, circuit A b
7
: fan_a8 Fan output 8, circuit A
b
4
fan_b1 Fan output 1, circuit B b
5
fan_b2 Fan output 2, circuit B b
6
fan_b3 Fan output 3, circuit B b
7
fan_b4 Fan output 4, circuit B
unit_typ = 1
nbfan_a < 3 and nbfan_b
> 3
nbfan_a > 2 and
nbfan_b > 2
H-DO-Fan 4xDO board #1, multiplexed DO's
b
4b3b2b1b0
b
0
: fan_a1 Fan output 1, circuit A b
1
: fan_a2 Fan output 2, circuit A b
2
: fan_b1 Fan output 1, circuit B b
3
: fan_b2 Fan output 2, circuit B
b
0
: fan_a1 Fan output 1, circuit A b
1
: fan_a2 Fan output 2, circuit A b
2
: fan_a3 Fan output 3, circuit A b
3
: fan_a4 Fan output 4, circuit A
MUX_FAN1
CONFIGURATIONTYPEUNITSDESCRIPTIONSPOINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 79/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
alllH-DO-Critical Alarm Signal, CommandSAFE_ALM
allH-AIPSISuction pressure, circuit BSP_B
allH-AIPSISuction pressure, circuit ASP_A
recl_opt = yes and
cpb1_mta > 0
H-AIPSIReclaim Pumpdown Pressure circuit BPD_P_B
recl_opt = yesH-AIPSIReclaim Pumpdown Pressure circuit APD_P_A
unit_typ = 1 or 4 and
cpb1_mta > 0
H-DOOil Heater Circuit BOIL_HTRB
unit_typ = 1 or 4H-DOOil Heater Circuit AOIL_HTRA
unit_typ = 1 or 4H-AI°FOutside Air TemperatureOAT
heat_sel = yes or
recl_opt = yes recl_opt = yes recl_opt = yes
recl_opt = yes recl_opt = yes recl_opt = yes
(heat_sel = yes) (heat_sel = yes) (heat_sel = yes)
H-DOM-NRCP (AQUASNAP) Basic board multilexed DO's,
or AUX 1 Basic board multilexed DO's:
b
9b8b7b6b5b4b3b2b1b0
b0: hr_val_a reclaim valve circuit A b
1
: hr_val_b reclaim valve circuit B b
2
: unused b
3
: cond_htr reclaim condenser heater b
4
: pd_val_a pumpdown valve circuit A b
5
: pd_val_b pumpdown valve circuit B b
6
: unused b
7
: cool_htr cooler heater b
8
: refa_iso refriegerant solenoid A b
9
: refb_iso refriegerant solenoid B
MUX_HRDO
CONFIGURATIONTYPEUNITSDESCRIPTIONSPOINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 80/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CCN Variables: Software SIO Points
S-A°FLeaving Water TemperatureLWT
S-A°FCCN Leaving Chiller Water SetpointLCW_STPT
S-A%Master Slave Lag limitLAG_LIM
S-AHoursCompressor B2 Run time Operation HR_CP_B2
S-AHoursCompressor B1 Run time Operation HR_CP_B1
S-AHoursCompressor A2 Run time Operation HR_CP_A2
S-AHoursCompressor A1 Run time Operation HR_CP_A1
S-AHoursChiller Run time Operation HR_MACH
S-A-Heat/Cool Select ( 0=Cool 1= Heat )HC_SEL
S-AFan stages Circuit BFAN_ST_B
S-AFan stages Circuit AFAN_ST_A
S-A%EXV Position Circuit BEXV_B
S-A%EXV Position Circuit AEXV_A
S-A°FEntering Water TemperatureEWT
S-D-Emergency Stop Enable/Disable via CCN flagEMSTOP
S-ApsiCompressor B2, Oil Differential Pressure DOP_B2
S-ApsiCompressor B1, Oil Differential Pressure DOP_B1
S-ApsiCompressor A2, Oil Differential Pressure DOP_A2
S-ApsiCompressor A1, Oil Differential Pressure DOP_A1
S-A^FDischarge Superheat Circuit BDSH_B
S-A^FDischarge Superheat Circuit ADSH_A
S-APercentActive Demand Limit ValueDEM_LIM
S-A°FChiller Control Water CTRL_WT
S-A°FChille Control PointCTRL_PNT
S-D-Cooler heater outputCOOLHEAT
S-A°FConsensing SetpointCOND_SP
S-D-Condenser pump statusCOND_PMP
S-D-Cooler pump # 2 statusCL_PUMP2
S-D-Cooler pump # 1 statusCL_PUMP1
S-D-CCN Enable/Disable the start/Stop Chiller FlagCHIL_S_S
S-D-CCN Chiller Occupancy FlagCHIL_OCC
S-D-CCN Chiller status (for SM & Master/Slave operation )CHILSTAT
S-APercentChiller Available Percent Capacity (running or not)CAP_T_AV
S-APercentMachine Percent CapacityCAP_T
S-APercentCircuit B Percent CapacityCAPB_T
S-APercentCircuit A Percent CapacityCAPA_T
S-AI-Alarm Status (0=no alarm 1=partial alarm 2=total alarm) ALM
TYPEUNITSDESCRIPTIONSPOINT NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 81/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
S-A-Circuit A & B Oil level indicator : 3 = Circuit A & Circuit B oil level are both high 2 = Circuit A oil level is high, circuit B oil level is low 1 = Circuit A oil level is low, circuit B oil level is high 0 = Circuit A & Circuit B oil level are both low
TOT_OIL
S-A-Unit state information (int value):
1 = local operating type, off mode 2 = local operating type, on mode 3 = remote operating type, off mode 4 = remote operating type, on mode 5 = ccn operating type, off mode 6 = ccn operating type, on mode 7 = ccn operating type, off mode, system manager control 8 = ccn operating type, on mode, system manager control 9 = Master operating type, off mode 10 = Master operating type, on mode 11 = Master operating type, Master Slave Control, off mode 12 = Master operating type, Master Slave Control, on mode off mode = unit is commended to OFF or totally failed on mode = unit is commended to ON (status could also be delay)
STATE
S-A°FSaturated Suction Temperature, Circuit BSST_B
S-A°FSaturated Suction Temperature, Circuit ASST_A
S-D
Setpoint occupancy statusSP_OCC
S-A-
Sum/Z Value for capacity PID Loop ControlSMZ
S-A°FSaturated Condensing Temperature, Circuit BSCT_B
S-A°FSaturated Condensing Temperature, Circuit ASCT_A
S-D-Servicing alert ResetS RESET
S-D-Rotate pumps nowROT PUMP
S-D-Reclaim SelectRECL_SEL
S-A^FCooler Exchange Deltat T circuit BPINCH_B
S-A^FCooler Exchange Deltat T circuit APINCH_A
S-AminMinutes left for startMIN_LEFT
TYPEUNITSDESCRIPTIONSPOINT NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 82/98
©
C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
SCHEME 1 : Water Cooled Chillers 1 compressor, Aux Board
Channel 27-28: virtual
-AIChannel 38
-MTQ RESAAIChannel 37
-Channel 33
EXV ST AChannel 29
EXV BOARD #1
Address = 29
SAFE ALMDOChannel 26
DOChannel 25
ALARM ADOChannel 24
-DOChannel 23
-DOChannel 22
CONDPUMPDOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 94elec boxDI11 - bit 5
-AIChannel 93lock 1DI11 - bit 4
-AIChannel 55CPA1 STAAIChannel 92lim swDI11 - bit 3
-AIChannel 54CPA1 TMPAIChannel 91hc swDI11 - bit 2
-AIChannel 53CPA1 DGTAIChannel 90sptswDI11 - bit 1
-AIChannel 52CPA1 ECPAIChannel 89onoff swDI11- bit 0
AOChannel 51CPA1 OPAIChannel 88MUX DI
1
Channel 11
HD AAOChannel 50CPA1 CURAIChannel 87EXT VDCAIChannel 10
-DOCh 49 bit-7CPA1 PULDOChannel 86AIChannel 09
-DOCh 49 bit-6oilpmpaDO85 - bit 5AIChannel 08
-DOCh 49 bit-5a1 ldr 2DO85 - bit 4SP AAIChannel 07
-DOCh 49 bit-4a1 ldr 1DO85 - bit 3DP AAIChannel 06
-DOCh 49 bit-3cpa1 olsDO85 - bit 2COND EWTAIChannel 05
-DOCh 49 bit-2cpa1 mc2DO85 - bit 1COND LWTAIChannel 04
-DOCh 49 bit-1cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
-DOCh 49 bit-0CPA1 MUXChannel 85COOL EWTAIChannel 02
-Channel 49CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1
Address = 49
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 83 / 98
SCHEME 3 : Water Cooled Chillers 2 to 4 compressors, Aux board
Channel 27-28: virtual
-AIChannel 127-AIChannel 105
-AIChannel 126 -AIChannel 104
CPB2 STAAIChannel 125CPA2 STAAIChannel 103
CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
-DOChannel 119-DOChannel 97
-DO118 - bit 5-DO96 - bit 5EXV BOARD # 1
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3SAFE ALMDOChannel 26
cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
cpb2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cpb2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0-DOChannel 23
CPB2 MUXChannel 118CPA2 MUXChannel 96-DOChannel 22
CP B2DOChannel 117CP A2DOChannel 95CONDPUMPDOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
-AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
-AIChannel 55CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
-AIChannel 54CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91hc swDI11 - bit 2
-AIChannel 53CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90sptswDI11 - bit 1
-AIChannel 52CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
HD BAOChannel 51CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
HD AAOChannel 50CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
-DOCh 49 bit-7CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
-DOCh 49 bit-6oilpmpbDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
-DOCh 49 bit-5b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
-DOCh 49 bit-4b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
-DOCh 49 bit-3cpb1 olsDO107 - bit 2cpa1 olsDO85 - bit 2COND EWTAIChannel 05
-DOCh 49 bit-2cpb1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1COND LWTAIChannel 04
-DOCh 49 bit-1cpb1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
-DOCh 49 bit-0CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
-Channel 49CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1
Address = 49
SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 84 / 98
SCHEME 4 : Water Cooled Chillers 2 to 4 Compressors, no Aux Board
HD BAOChannel 52
-HD AAOChannel 51
-Channel 27-28: virtual -AIChannel 50
-AIChannel 49
-AIChannel 48
-AIChannel 47
-
-AIChan126-127 -AIChan104-105
4xAI - 2xAO BOARD
Address = 47
CPB2 STAAIChannel 125CPA2 STAAIChannel 103
CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
-DOChannel 119-DOChannel 97
-DO118 - bit 5-DO96 - bit 5
EXV BOARD # 1
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3SAFE ALMDOChannel 26
c
p
b2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
c
p
b2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
c
p
b2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0-DOChannel 23
CPB2 MUXChannel 118CPA2 MUXChannel 96-DOChannel 22
CP B2DOChannel 117CP A2DOChannel 95CONDPUMPDOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
SCPM BOARD
Address = 117
SCPM BOARD
Address = 40
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
--elec boxDI11 - bit 5
-AIChan 115-16 -AIChan 93-94lock 1DI11 - bit 4
CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91hc swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2COND EWTAIChannel 05
c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1COND LWTAIChannel 04
c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
SCPM BOARD
Address = 106
SCPM BOARD
Address = 84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 85 / 98
SCHEME 5 : Air Cooled Chillers
1 compressor, Aux Board, Varifan
Channel 27-28: virtual
-AIChannel 38
MTQ RESAAIChannel 37
Channel 33
EXV ST AChannel 29
EXV BOARD
Address = 29
SAFE ALMDOChannel 26
REFA ISODOChannel 25
ALARM ADOChannel 24
COOL HTRDOChannel 23
OIL HTRADOChannel 22
DOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 94elec boxDI11 - bit 5
-AIChannel 93lock 1DI11 - bit 4
-AIChannel 55CPA1 STAAIChannel 92lim swDI11 - bit 3
-AIChannel 54CPA1 TMPAIChannel 91hc swDI11 - bit 2
-AIChannel 53CPA1 DGTAIChannel 90sptswDI11 - bit 1
-AIChannel 52CPA1 ECPAIChannel 89onoff swDI11- bit 0
AOChannel 51CPA1 OPAIChannel 88MUX DI
1
Channel 11
HD AAOChannel 50CPA1 CURAIChannel 87EXT VDCAIChannel 10
-DOCh 49 bit-7CPA1 PULDOChannel 86AIChannel 09
-DOCh 49 bit-6oilpmpaDO85 - bit 5AIChannel 08
-DOCh 49 bit-5a1 ldr 2DO85 - bit 4SP AAIChannel 07
fan a4DOCh 49 bit-4a1 ldr 1DO85 - bit 3DP AAIChannel 06
fan a3DOCh 49 bit-3cpa1 olsDO85 - bit 2AIChannel 05
fan a2DOCh 49 bit-2cpa1 mc2DO85 - bit 1OATAIChannel 04
fan a1DOCh 49 bit-1cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
DOCh 49 bit-0CPA1 MUXChannel 85COOL EWTAIChannel 02
MUX FAN1Channel 49CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1
Address = 49
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 86 / 98
SCHEME 6 : Air Cooled Chillers
1 compressor, Aux Board, No Varifan
Channel 27-28: virtual
-AIChannel 38
MTQ RESAAIChannel 37
Channel 33
EXV ST AChannel 29
EXV BOARD
Address = 29
SAFE ALMDOChannel 26
REFA ISODOChannel 25
ALARM ADOChannel 24
COOL HTRDOChannel 23
OIL HTRADOChannel 22
DOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 94elec boxDI11 - bit 5
-AIChannel 93lock 1DI11 - bit 4
CPA1 STAAIChannel 92lim swDI11 - bit 3
CPA1 TMPAIChannel 91hc swDI11 - bit 2
CPA1 DGTAIChannel 90sptswDI11 - bit 1
CPA1 ECPAIChannel 89onoff swDI11- bit 0
CPA1 OPAIChannel 88MUX DI
1
Channel 11
CPA1 CURAIChannel 87EXT VDCAIChannel 10
-DOCh 49 bit-7CPA1 PULDOChannel 86AIChannel 09
-DOCh 49 bit-6oilpmpaDO85 - bit 5AIChannel 08
-DOCh 49 bit-5a1 ldr 2DO85 - bit 4SP AAIChannel 07
-DOCh 49 bit-4a1 ldr 1DO85 - bit 3DP AAIChannel 06
fan a4DOCh 49 bit-3cpa1 olsDO85 - bit 2AIChannel 05
fan a3DOCh 49 bit-2cpa1 mc2DO85 - bit 1OATAIChannel 04
fan a2DOCh 49 bit-1cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
fan a1DOCh 49 bit-0CPA1 MUXChannel 85COOL EWTAIChannel 02
MUX FAN1Channel 49CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1
Address = 49
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 87 / 98
SCHEME 8 : Air Cooled Chillers < 3 separate fan stages 2 to 4 compressors,
Cooler heater = NO, Reclaim option = no No Aux Board
HD_BAOChannel 52
Channel 27-28: virtual HD AAOChannel 51
HR EWTAIChannel 50
HR LWTAIChannel 49
AIChannel 48
AIChannel 47
-AIChannel 127-AIChannel 105
-AIChannel 126 -AIChannel 104
4xAI - 2xAO BOARD
Address = 47
fan b239 - bit 3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
fan b139 - bit 2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
fan a239 - bit 1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
fan a139 - bit 0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
MUX FAN1Channel 39CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
-DOChannel 119-DOChannel 97
4xDO BOARD #1Address = 39-DO118 - bit 5-DO96 - bit 5EXV BOARD
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3SAFE ALMDOChannel 26
cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
cpb2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cpb2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRBDOChannel 23
CPB2 MUXChannel 118CPA2 MUXChannel 96OIL HTRADOChannel 22
CP B2DOChannel 117CP A2DOChannel 95-DOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
-AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90sptswDI11 - bit 1
CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
oilpmpbDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
cpb1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
cpb1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
cpb1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 88 / 98
SCHEME 9 : Air Cooled < 5 separate fan stages 2 to 4 compressors, Aux Board, no varifan
AIChannel 69
AIChannel 68
HR EWTAIChannel 67Channel 27-28: virtual
HR LWTAIChannel 66
-AOChannel 65
AOChannel 64
cool htrDOCh 63 bit-7
cond htrDOCh 63 bit-6
refb isoDO
Ch 63 bit-5-AIChannel 127-AIChannel 105
hr val bDOCh 63 bit-4 -AIChannel 126 -AIChannel 104
p
d val bDOCh 63 bit-3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
refa isoDOCh 63 bit-2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
hr val aDOCh 63 bit-1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
p
d val aDOCh 63 bit-0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
MUX HRDOChannel 63CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
AUXILIARY BOARD # 3 Address = 63-DOChannel 119-DOChannel 97
-DO118 - bit 5-DO96 - bit 5EXV BOARD
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3SAFE ALMDOChannel 26
cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
cpb2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cpb2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRBDOChannel 23
CPB2 MUXChannel 118CPA2 MUXChannel 96OIL HTRADOChannel 22
CP B2DOChannel 117CP A2DOChannel 95CONDPUMPDOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
-AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
fan b4DOCh 49 bit-7CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
fan b3DOCh 49 bit-6oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
fan b2DO
Ch 49 bit-5b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
fan b1DOCh 49 bit-4b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
fan a4DOCh 49 bit-3c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
fan a3DOCh 49 bit-2c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
fan a2DOCh 49 bit-1c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
fan a1DOCh 49 bit-0CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
MUX FAN1
Channel 49CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1 Address = 49SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 89 / 98
SCHEME 10 : Air Cooled > 4 separate fan stages 2 to 4 compressors, Aux Board, no varifan
AIChannel 69
AIChannel 68
HR EWTAIChannel 67Channel 27-28: virtual
HR LWTAIChannel 66
-AOChannel 65
AOChannel 64
cool htrDOCh 63 bit-7
cond htrDOCh 63 bit-6
refb isoDO
Ch 63 bit-5-AIChannel 127-AIChannel 105
hr val bDOCh 63 bit-4 -AIChannel 126 -AIChannel 104
p
d val bDOCh 63 bit-3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
refa isoDOCh 63 bit-2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102-AIChannel 38
hr val aDOCh 63 bit-1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101-AIChannel 37
p
d val aDOCh 63 bit-0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
MUX HRDOChannel 63CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
AUXILIARY BOARD # 3 Address = 63-DOChannel 119-DOChannel 97
-DO118 - bit 5-DO96 - bit 5EXV BOARD
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3SAFE ALMDOChannel 26
cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
cpb2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cpb2_mc1DO118 - bit 0cpa2_mc1DO96 - bit 0OIL_HTRBDOChannel 23
fan b8DOCh 56 bit-7CPB2 MUXChannel 118CPA2 MUXChannel 96OIL HTRADOChannel 22
fan b7DOCh 56 bit-6CP B2DOChannel 117CP A2DOChannel 95CONDPUMPDOChannel 21
fan b6DO
Ch 56 bit-5CPUMP 2DOChannel 20
fan b5DOCh 56 bit-4CPUMP 1DOChannel 19
fan b4DOCh 56 bit-3
SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
fan b3DOCh 56 bit-2
cond_flow
DI11 - bit 6
fan b2DOCh 56 bit-1-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
fan b1DOCh 56 bit-0 -AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
MUX FAN2
Channel 56CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
AUXILIARY BOARD # 2 Address = 56CPB1_TMPAIChannel 113CPA1_TMPAIChannel 91recl_swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
fan a8DOCh 49 bit-7CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
fan a7DOCh 49 bit-6oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
fan a6DO
Ch 49 bit-5b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
fan a5DOCh 49 bit-4b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
fan a4DOCh 49 bit-3c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
fan a3DOCh 49 bit-2c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
fan a2DOCh 49 bit-1c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
fan a1DOCh 49 bit-0CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
MUX FAN1
Channel 49CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1 Address = 49SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 90 / 98
SCHEME 11: Air Cooled < 5 separate fan stages 2 to 4 compressors Aux Board, varifan
PD_P_BAIChannel 69
PDPAAIChannel 68Channel 27-28: virtual
HR EWTAIChannel 67
HR LWTAIChannel 66
-AOChannel 65
HR WTRVLAOChannel 64
cool htrDO
Ch 63 bit-7
cond htrDOCh 63 bit-6
refb isoDOCh 63 bit-5-AIChannel 127-AIChannel 105
hr val bDOCh 63 bit-4 -AIChannel 126 -AIChannel 104
p
d val bDOCh 63 bit-3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
refa isoDOCh 63 bit-2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
hr val aDOCh 63 bit-1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESA-AIChannel 37
p
d val aDOCh 63 bit-0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST B Channel 33
MUX HRDOChannel 63CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST B Channel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
AUXILIARY BOARD # 3 Address = 63-DOChannel 119-DOChannel 97EXV BOARD Address = 29
-DO118 - bit 5-DO96 - bit 5
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4SAFE ALMDOChannel 26
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3ALARM BDOChannel 25
cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM ADOChannel 24
c
p
b2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1OIL HTRBDOChannel 23
c
p
b2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRADOChannel 22
CPB2 MUXChannel 118CPA2 MUXChannel 96CONDPUMPDOChannel 21
CP B2DOChannel 117CP A2DOChannel 95CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
SCPM BOARD #4 Address = 117SCPM BOARD #2 Address = 95
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
-AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
-AIChan 52-54CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
HD BAOChannel 51CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
HD AAOChannel 50CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
fan b3DOCh 49 bit-7CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
fan b2DOCh 49 bit-6oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
fan b1DO
Ch 49 bit-5b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
-DOCh 49 bit-4b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
fan a3DOCh 49 bit-3c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
fan a2DOCh 49 bit-2c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
fan a1DOCh 49 bit-1c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
-DOCh 49 bit-0CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
MUX FAN1Channel 49CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1 Address = 49SCPM BOARD #3 Address =106SCPM BOARD #1 Address =84BASIC BOARDAddress = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 91 / 98
SCHEME 12 : Air Cooled > 4 separate fan stages 2 to 4 Compressors Aux Board, varifan
PD_P_BAIChannel 69
PDPAAIChannel 68Channel 27-28: virtual
HR EWTAIChannel 67
HR LWTAIChannel 66
-AOChannel 65
HR WTRVLAOChannel 64
cool htrDO
Ch 63 bit-7
cond htrDOCh 63 bit-6
refb isoDOCh 63 bit-5-AIChannel 127-AIChannel 105
hr val bDOCh 63 bit-4 -AIChannel 126 -AIChannel 104
p
d val bDOCh 63 bit-3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
refa isoDOCh 63 bit-2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
hr val aDOCh 63 bit-1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
p
d val aDOCh 63 bit-0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST B Channel 33
MUX HRDOChannel 63CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST B Channel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
AUXILIARY BOARD # 3 Address = 63-DOChannel 119-DOChannel 97EXV BOARD#1 Address = 29
-DO118 - bit 5-DO96 - bit 5
-AIChan 59-62b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4SAFE ALMDOChannel 26
AOChannel 58b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3ALARM BDOChannel 25
HD BAOChannel 57cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM ADOChannel 24
fan b7DOCh 56 bit-7c
p
b2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1OIL HTRBDOChannel 23
fan b6DO
Ch 56 bit-6cpb2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRADOChannel 22
fan b5DOCh 56 bit-5CPB2 MUXChannel 118CPA2 MUXChannel 96CONDPUMPDOChannel 21
fan b4DOCh 56 bit-4CP B2DOChannel 117CP A2DOChannel 95CPUMP 2DOChannel 20
fan b3DOCh 56 bit-3CPUMP 1DOChannel 19
fan b2DOCh 56 bit-2SCPM BOARD #4 Address = 117SCPM BOARD #2 Address = 95
pump_def
DI11 - bit 7
fan b1DOCh 56 bit-1
cond_flow
DI11 - bit 6
-DOCh 56 bit-0-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
MUX FAN1Channel 56 -AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
AUXILIARY BOARD # 2 Address = 56CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
-AIChan 52-54CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
AOChannel 51CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
HD AAOChannel 50CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
fan a7DOCh 49 bit-7CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
fan a6DOCh 49 bit-6oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
fan a5DO
Ch 49 bit-5b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
fan a4DOCh 49 bit-4b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
fan a3DOCh 49 bit-3c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
fan a2DOCh 49 bit-2c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
fan a1DOCh 49 bit-1c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
f-DOCh 49 bit-0CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
MUX FAN1Channel 49CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
AUXILIARY BOARD # 1 Address = 49SCPM BOARD #3 Address =106SCPM BOARD #1 Address =84BASIC BOARDAddress = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 92 / 98
SCHEME 13 : Air Cooled Chillers >2 separate fan stages, 2 to 4 Compressors, Cooler heater = NO, Reclaim option = no
,
No Aux Board
fan b443 - bit 3Channel 80 - 83 : freeHD BAOChannel 52
fan b343 - bit 2Channel 27-28: virtual HD AAOChannel 51
fan b243 - bit 1Channel 26 : DO unusedHR EWTAIChannel 50
fan b143 - bit 0HR LWTAIChannel 49
MUX FAN2Channel 43AIChannel 48
AIChannel 47
4xDO BOARD #2
Address = 43
-AIChannel 127-AIChannel 105
-AIChannel 126 -AIChannel 104
4xAI - 2xAO BOARD
Address = 47
fan a439 - bit 3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
fan a339 - bit 2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
fan a239 - bit 1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
fan a139 - bit 0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
MUX FAN1Channel 39CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
-DOChannel 119-DOChannel 97
4xDO BOARD #1
Address = 39
-DO118 - bit 5-DO96 - bit 5EXV BOARD
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3unusedDOCh 26-28
cpb2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
cpb2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cpb2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRBDOChannel 23
CPB2 MUXChannel 118CPA2 MUXChannel 96OIL HTRADOChannel 22
CP B2DOChannel 117CP A2DOChannel 95DOChannel 21
CPUMP 2DOChannel 20
CPUMP 1DOChannel 19
SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
cond_flow
DI11 - bit 6
-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
-AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90sptswDI11 - bit 1
CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
oilpmpbDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
cpb1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
cpb1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
cpb1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 93 / 98
SCHEME 14 : Air Cooled Chillers < 3 separate fan stages 2 to 4 Compressors, Cooler heater = YES or Reclaim option = YES, No Aux Board
Channel 80 - 83 : freeHD BAOChannel 52
Channel 27-28: virtual HD AAOChannel 51
Channel 26 : DO unused-AIChannel 50
-AIChannel 49
AIChannel 48
AIChannel 47
-AIChannel 127-AIChannel 105
-AIChannel 126 -AIChannel 104
4xAI - 2xAO BOARD
Address = 47
fan b239 - bit 3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
fan b139 - bit 2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
fan a239 - bit 1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
fan a139 - bit 0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
MUX FAN1Channel 39CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
-DOChannel 119-DOChannel 97
4xDO BOARD #1
Address = 39
-DO118 - bit 5-DO96 - bit 5EXV BOARD
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
virtual-unusedDOCh 78- 79b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3unusedDOCh 26-28
refb isoDO 68 bit 9c
p
b2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
refa isoDO 68 bit 8c
p
b2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cool htrDO 68 bit 7c
p
b2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRBDOChannel 23
-DO 68 bit 6CPB2 MUXChannel 118CPA2 MUXChannel 96OIL HTRADOChannel 22
p
d val bDO 68 bit 5CP B2DOChannel 117CP A2DOChannel 95HPUMPDOChannel 21
p
d val aDO 68 bit 4CPUMP 2DOChannel 20
cond htrDO 68 bit 3CPUMP 1DOChannel 19
-DO 68 bit 2SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
hr val bDO 68 bit 1
cond_flow
DI11 - bit 6
hr val aDO 68 bit 0-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
MUX NRCPMUXChannel 68 -AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
-DIChannel 67CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
-DIChannel 66CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
-DIChannel 65CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
-DIChannel 64CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
-DIChannel 63CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
-DIChannel 62CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
-DIChannel 61CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
-DIChannel 60oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
HR WTRVLAOChannel 59b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
PD P BAIChannel 58b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
PD P AAIChannel 57c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
-AIChannel 56c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
-AIChannel 55c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
HR EWTAIChannel 54CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
HR LWTAIChannel 53CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
NRCP BASIC BOARD
Address = 53
SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 94 / 98
SCHEME 15 : Air Cooled Chillers > 2 separate fan stages 2 to 4 Compressors, Cooler heater = YES or Reclaim option = YES, No Aux Board
fan b443 - bit 3Channel 80 - 83 : freeHD BAOChannel 52
fan b343 - bit 2Channel 27-28: virtual HD AAOChannel 51
fan b243 - bit 1Channel 26 : DO unused-AIChannel 50
fan b143 - bit 0-AIChannel 49
MUX FAN2Channel 43AIChannel 48
AIChannel 47
4xDO BOARD #2
Address = 43
-AIChannel 127-AIChannel 105
-AIChannel 126 -AIChannel 104
4xAI - 2xAO BOARD
Address = 47
fan a439 - bit 3CPB2 STAAIChannel 125CPA2 STAAIChannel 103
fan a339 - bit 2CPB2 TMPAIChannel 124CPA2 TMPAIChannel 102MTQ RESBAIChannel 38
fan a239 - bit 1CPB2 DGTAIChannel 123CPA2 DGTAIChannel 101MTQ RESAAIChannel 37
fan a139 - bit 0CPB2 ECPAIChannel 122CPA2 ECPAIChannel 100EXV ST BChannel 33
MUX FAN1Channel 39CPB2 OPAIChannel 121CPA2 OPAIChannel 99EXV ST AChannel 29
CPB2 CURAIChannel 120CPA2 CURAIChannel 98
-DOChannel 119-DOChannel 97
4xDO BOARD #1
Address = 39
-DO118 - bit 5-DO96 - bit 5EXV BOARD
Address = 29
b2 ldr 2DO118 - bit 4a2 ldr 2DO96 - bit 4
virtual-unusedDOCh 78- 79b2 ldr 1DO118 - bit 3a2 ldr 1DO96 - bit 3unusedDOCh 26-28
refb isoDO 68 bit 9c
p
b2 olsDO118 - bit 2cpa2 olsDO96 - bit 2ALARM BDOChannel 25
refa isoDO 68 bit 8c
p
b2 mc2DO118 - bit 1cpa2 mc2DO96 - bit 1ALARM ADOChannel 24
cool htrDO 68 bit 7c
p
b2 mc1DO118 - bit 0cpa2 mc1DO96 - bit 0OIL HTRBDOChannel 23
-DO 68 bit 6CPB2 MUXChannel 118CPA2 MUXChannel 96OIL HTRADOChannel 22
p
d val bDO 68 bit 5CP B2DOChannel 117CP A2DOChannel 95CONDPUMPDOChannel 21
p
d val aDO 68 bit 4CPUMP 2DOChannel 20
cond htrDO 68 bit 3CPUMP 1DOChannel 19
-DO 68 bit 2SCPM BOARD #4
Address = 117
SCPM BOARD #2
Address = 95
pump_def
DI11 - bit 7
hr val bDO 68 bit 1
cond_flow
DI11 - bit 6
hr val aDO 68 bit 0-AIChannel 116-AIChannel 94elec boxDI11 - bit 5
MUX NRCPMUXChannel 68 -AIChannel 115 -AIChannel 93lock 1DI11 - bit 4
-DIChannel 67CPB1 STAAIChannel 114CPA1 STAAIChannel 92lim swDI11 - bit 3
-DIChannel 66CPB1 TMPAIChannel 113CPA1 TMPAIChannel 91recl swDI11 - bit 2
-DIChannel 65CPB1 DGTAIChannel 112CPA1 DGTAIChannel 90s
p
tswDI11 - bit 1
-DIChannel 64CPB1 ECPAIChannel 111CPA1 ECPAIChannel 89onoff swDI11- bit 0
-DIChannel 63CPB1 OPAIChannel 110CPA1 OPAIChannel 88MUX DI
1
Channel 11
-DIChannel 62CPB1 CURAIChannel 109CPA1 CURAIChannel 87EXT VDCAIChannel 10
-DIChannel 61CPB1 PULDOChannel 108CPA1 PULDOChannel 86SP BAIChannel 09
-DIChannel 60oil
pmp
bDO107 - bit 5oilpmpaDO85 - bit 5DP BAIChannel 08
HR WTRVLAOChannel 59b1 ldr 2DO107 - bit 4a1 ldr 2DO85 - bit 4SP AAIChannel 07
PD P BAIChannel 58b1 ldr 1DO107 - bit 3a1 ldr 1DO85 - bit 3DP AAIChannel 06
PD P AAIChannel 57c
p
b1 olsDO107 - bit 2cpa1 olsDO85 - bit 2-AIChannel 05
-AIChannel 56c
p
b1 mc2DO107 - bit 1cpa1 mc2DO85 - bit 1OATAIChannel 04
-AIChannel 55c
p
b1 mc1DO107 - bit 0cpa1 mc1DO85 - bit 0CHWSTEMPAIChannel 03
HR EWTAIChannel 54CPB1 MUXChannel 107CPA1 MUXChannel 85COOL EWTAIChannel 02
HR LWTAIChannel 53CP B1DOChannel 106CP A1DOChannel 84COOL LWTAI
Channel 01
NRCP BASIC BOARD
Address = 53
SCPM BOARD #3
Address =106
SCPM BOARD #1
Address =84
BASIC BOARD
Address = 1
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 95 / 98
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 96 / 98
Default = 0, no parity and 1 stop bit
X
JBUS parity and stop bit
R/W114 [72h
]
Default = 1
X
JBUS address
R/W113 [71h
]
Default = 9600
X
JBUS baud rate
R/W112 [70h
]
X
Demand Limit Value
R/W109 [h6D
]
Write value must be multiplied by 10
X
Control Point
R/W108 [h6C
]
0 = Off 1 = On
X
Chiller Start/Stop ***
R/W107 [6Bh
]
Write value must be multiplied by 10
X
Heating Setpoint
R/W99 [h62
]
Write value must be multiplied by 10
X
Cooling Setpoint 2
R/W98 [h62
]
Write value must be multiplied by 10
X
Cooling Setpoint 1
R/W97 [h61
]
X
JBUS alarm code
R66 [h42
]
2 = CCN communication failure
X
Gateway current alarm code
R61 [h3D
]
X
Active alarm 5*
R45 [h2D]
X
Active alarm 4*
R44 [h2C
]
X
Active alarm 3*
R43 [h2B
]
X
Active alarm 2*
R42 [h2A
]
Provide the code of up to 5 active alarms. These are stored in arrival order. Alarms read from CCN/JBUS are alarm index but not alarms codes as follows from iom, alarm codes 101 to 117 , index = 88 (code 101) to 104 ( code 117) from iom, alarm codes 201 to 217 , index = 105 (code 201) to 121 (code 217)
- - - - - - - ­from iom, alarm codes 401 to 417 , index = 139
(
code 401) to 155 (code 417
)
X
Active alarm 1*
R41 [h29
]
X
Total Number of active alarms
R40 [h28
]
XR---
X
Com
p
ressor B2 Hours
R16 [h10
]
X
Com
p
ressor B1 Hours
R15 [h0F
]
X
Com
p
ressor A2 Hours
R14 [h0E
]
X
Com
p
ressor A1 Hours
R13 [h0D
]
X
Machine O
p
erating Hours
R12 [h0C
]
X
Condenser Pum
p
status
R11 [h0B
]
X
Cooler Pum
p
# 1 status
R10 [h0A
]
0
=
cool,
1 = h
eat
X
Heat Cool Select
R9 [h09
]
0 = Normal, 16 = Partial, 25 = Shutdown
X
Alarm State
R8 [h08
]
0 = Off, 1 = On, 6=dela
y
,
24=runnin
g
X
Chiller State
R7 [h07
]
X
Demand Limit
R6 [h06
]
X
Unit Percent Active Ca
p
acit
y
R5 [h05
]
Read value must be divided by 10
X
Control Point
R4 [h04
]
Read value must be divided by 10
X
Circuit B Discharge Pressure
R3 [h03
]
Read value must be divided by 10
X
Circuit A Discharge Pressure
R2 [h02
]
Read value must be divided by 10
X
Leaving Fluid Temperature
R1 [h01
]
Read value must be divided by 10
X
Entering Fluid Temperature
R0 [h00
]
FLOATINT
REMARK**TYPE**CONTENTJBUS
ACCESS
REGISTER
ADDRESS
APPENDIX E- JBUS
MEMORY MAPPING - 30GX&HX V2.X DEFAULT CONFIGURATION
CARRIER SA
USER’S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev : Original
Page: 96 / 98
COMFORT
NETWORK
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page:97 / 98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
PRO-DIALOG 30DQ
PRO-DIALOG 30GX & HX
REPEATER
REPEATER
CCN/JBUS
DATAPORT I
DATAPORT II
PRO-DIALOG 30GH
FLOTRONIC II
FLOTRONIC I
FSM
FLOTRONIC I
3200 MP
19XL
AUTODIAL
AUTODIAL
GATEWAY
GATEWAY
MODEM
MODEM
BUILDING
BUILDING
SUPERVISOR
SUPERVISOR
NETWORK
SERVICE
TOOL
PRIMARY CCN BUS
GW
WSM
39 L
CSM
GW
GW
TSM
39 L
39 L
DATA COLLECTION
NDS BRIDGE
DATA TRANSFERT
TSM SECONDARY BUS
SECONDARY
BUS
AIR TERMINAL
AIR TERMINAL
35
37
GATEWAY
J-BUS/RS-485
TO
TO
TO
BMS
BMS
BMS
LOCAL BUILDING SUPERVISOR
REMOTE BUILDING SUPERVISOR
SAM
RS-485
ASCII/RS-23 2
ASCII/RS-23 2
SERVICE WINDOW 2
APPENDIX F
SAM SCREEN FOR 30GX&HX PRO-DIALOG PLUS
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page:98 / 98
© C
ARRIER S.A
NOT
TO BE
DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
!
ON - COOLING 05-20-94 15:00 NORMAL 255 hours
ENTERING LEAVING OUTDOOR
12.5 6.7 12
CAPACITY HEATCOOL PUMP
50 0 0
CTRL PNT CTRL WT LIMIT
6.0 6.7 100
CCN LOCAL REMOTE MENU
LOCAL
CARRIER
CONFORT
NETWORK
OFF OFF - COOLER HEATER ACTIVE READY TO START IN XX MIN ON - COOLING ON - COOL-RECLAIM ON - COOL-RESET ACTIVE ON - COOL- RECL-RESET ON - HEATING ON - HEAT - RESET ACTIVE ON - MASTER AND LEAD UNIT ON - MASTER AND LAG UNIT ON - SLAVE AND LEAD UNIT ON - SLAVE AND LAG UNIT ON - UNDER SM CONTROL
NORMAL PARTIAL: ALARM XX SHUTDOWN: ALARM XX
Loading...