1.1 - General .................................................................................................................................................................................4
2 - GENERAL DESCRIPTION ......................................................................................................................................................5
2.1 - General .................................................................................................................................................................................5
2.2 - Abbreviations used ...............................................................................................................................................................5
3.1 - General .................................................................................................................................................................................6
3.2.3 - The user interface.........................................................................................................................................................7
3.2.4 - Connections between boards .......................................................................................................................................7
3.2.6 - Power supply to the boards ..........................................................................................................................................7
3.2.7 - Light emitting diodes on boards ..................................................................................................................................7
3.3 - The controls ..........................................................................................................................................................................7
3.3.2 - The head pressure controls ..........................................................................................................................................7
3.3.3 - The evaporator pumps .................................................................................................................................................8
3.3.4 - The condenser pump....................................................................................................................................................8
3.4 - User connections ..................................................................................................................................................................9
4 - SETTING UP PRO-DIALOG PLUS CONTROL .................................................................................................................10
4.1 - Local interface general features..........................................................................................................................................10
4.2 - Unit start/stop control .........................................................................................................................................................11
4.2.2 - Stopping the unit in local mode ................................................................................................................................. 11
4.2.3 - Starting unit and selecting an operating type.............................................................................................................11
4.3.1 - Selecting a menu ........................................................................................................................................................12
4.3.2 - Selecting a menu item................................................................................................................................................12
4.3.3 - Modifying the value of a parameter/access to a sub-menu........................................................................................12
4.4 - General menu structure.......................................................................................................................................................13
4.5 - Menu tree structure.............................................................................................................................................................14
4.5.1 - Description of the Information menu.........................................................................................................................15
4.5.2 - Description of the Temperatures menu......................................................................................................................16
4.5.3 - Description of the Pressures menu.............................................................................................................................16
4.5.4 - Description of the Setpoints menu.............................................................................................................................17
4.5.5 - Description of the Inputs menu..................................................................................................................................18
4.5.6 - Description of the Outputs/Tests menu .....................................................................................................................18
4.5.7 - Description of the Configuration menu .....................................................................................................................20
4.5.8 - Description of the Alarms menu ................................................................................................................................25
4.5.9 - Description of the Alarms History menu ...................................................................................................................25
4.5.10 - Runtime menu description .......................................................................................................................................26
The cover photograph is solely for illustration, and forms no part of any offer for sale or any sale contract. The
manufacturer reserves the right to change the design at any time without notice.
2
5 - PRO-DIALOG PLUS CONTROL OPERATION .................................................................................................................27
5.1 - Start/stop control ................................................................................................................................................................27
5.3 - Evaporator water pump control ..........................................................................................................................................28
5.4 - Condenser water pump control...........................................................................................................................................28
5.5 - Control interlock contact ....................................................................................................................................................28
5.6 - Evaporator heater control ...................................................................................................................................................28
5.7 - Control point......................................................................................................................................................................28
5.7.1 - Active setpoint ...........................................................................................................................................................28
5.9 - Capacity control ................................................................................................................................................................29
5.10 - Determining the lead circuit............................................................................................................................................29
5.13 - Controlling the EXV ........................................................................................................................................................30
5.14 - Head pressure control on air-cooled units .......................................................................................................................30
5.15 - Head pressure control on water-cooled units...................................................................................................................30
5.16 - Active setpoint selection ..................................................................................................................................................30
5.17 - High pressure load shedding function..............................................................................................................................31
5.20 - Controlling Pro-Dialog Plus units with a System Manager.............................................................................................31
6.1 - General ...............................................................................................................................................................................32
Installation, start-up and servicing of equipment can be hazardous if factors particular to the installation are not considered:
operating pressures, electrical components, voltages and the
installation site itself (elevated plinths, rooftops and built-up
structures).
IMPORTANT:
Risk of electrocution: Even when the main power isolator or
circuit breaker is off, it is still possible for certain components such as crankcase heaters and trace heaters to be
energised, since they are connected to a separate power source.
Even when the unit is switched off, the power circuit remains
energised, as long as the unit or circuit disconnect is not open.
Refer to the wiring diagram for details.
Only highly trained and qualified installation engineers and
technicians, who are fully trained on the product, are authorised
to install and start up this equipment.
During all servicing operations, it is important to read, understand and follow all the recommendations and instructions
given in the installation and service instructions for the product,
including the tags and labels affixed to the equipment, components and any parts supplied separately, and to comply with all
other relevant safety regulations.
•Apply all safety codes and practices.
•Wear safety glasses and gloves.
•Use the proper tools to move heavy objects. Move units
carefully and set them down gently.
1.2 - Avoiding electrocution
Only personnel qualified in accordance with the recommendations of the IEC (International Electrotechnical Commission)
may be permitted access to electrical components. It is particularly recommended that all sources of electricity to the unit
be shut off before any work is begun. Shut off the main power
supply at the main circuit breaker or isolator.
Attach appropriate safety labels.
Risk of burns: Electrical currents cause components to get
hot either temporarily or permanently. Handle power cables,
electrical cables and conduits, terminal box covers and motor
frames with very great care.
IMPORTANT: This equipment uses and emits electromagnetic
signals. The tests carried out on this product have shown that
it complies with all applicable codes regarding electromagnetic
compatibility.
IMPORTANT : If the boards need to be handled wear antistatic gloves to avoid exposing the electronic components to a
destructive voltage. Only unpack the boards from their antistatic bag when they need to be installed.
4
2 - GENERAL DESCRIPTION
2.2 - Abbreviations used
2.1 - General
PRO-DIALOG Plus is a system for controlling units which use
reciprocating compressors*:
•Single or dual circuit
•Air or water-cooled condensers
•Non-reversible heat pumps
•Split systems
* At present only air-cooled models are available.
PRO-DIALOG Plus controls compressor start-up and demand
limits needed to maintain the desired entering or leaving temperature setpoint for water. It automatically sets the position of
the electronic expansion valve (if used) to optimise the evaporator charge. It controls operation of the fans (on air-cooled
units) or water valves (on water-cooled units) to maintain the
correct head pressure in each circuit.
Safety circuits are constantly monitored by PRO-DIALOG
Plus to ensure safe operation of the unit. PRO-DIALOG Plus
also gives access to a Quick Test program covering all inputs
and outputs.
All PRO-DIALOG Plus controls can work in accordance with
three independent modes:
•Local mode: the machine is controlled by commands from
the user interface.
•Remote mode: the machine is controlled by remote
contacts (volt-free contacts, analogue signals).
•CCN mode: the machine is controlled by commands from
the Carrier Comfort Network (CCN). In this case a data
communication cable is used to connect the unit to the
CCN communication bus.
In this manual the circuits are called circuit A and circuit B.
The compressors in circuit A are labelled A1, A2, A3 and A4.
Those in circuit B are labelled B1, B2, B3 and B4. A1 and B1
are the lead compressors.
The following abbreviations are frequently used:
AI- Analogue Input
AO- Analogue Output
CCn- Operating type: CCN
CCN- Carrier Comfort Network.
This is the Carrier communication network
DI- Discrete Input
DO- Discrete Output
EXV- Electronic Expansion Device
LED- Light Emitting Diode
LOFF - Operating type: Local off
L-ON - Operating type: Local operation
MASt - Master unit operating type (master/slave assembly)
RCPM - Reciprocating Compressor Protection Module
rEM- Operating type: by remote control contacts
SCT- Saturated disCharge Temperature
SIO- Standard Input/Output - internal communication bus
linking the basic board to the slave boards
SST- Saturated Suction Temperature
The operating mode must be chosen with the Operating Type
selection button described in section 4.2.1.
When the PRO-DIALOG Plus system operates autonomously
(Local or Remote mode) it retains all of its own control capabilities but does not offer any of the features of the CCN network.
5
3 - HARDWARE DESCRIPTION
3.1 - General
Control board
9
8
Legend
1CCN connector
2Red LED, status of the board
3Green LED, communication bus SIO
4Orange LED, communication bus CCN
5Remote master board customer control connection contacts
6Remote master board customer control connection signal
7Remote master board customer report connection contacts
8Master PD4 basic board
9CCN/clock board
1
7
2
3
4
5
6
The control system consists of at least a PD4 basic board, a
user interface, a PD4-EXV slave board and, depending on the
application, one or more RCPM compressor boards, 4xDO
boards or 4xAI-2xAO boards and an NRCP-BASE slave board.
Slave boards are connected to the basic board via an internal
communication bus (SIO).
The CCN/clock board is connected and screwed to the master
basic board. It permits communication with elements of the
Carrier Comfort Network via the CCN bus.
The various control components are arranged in modules
within the control cabinet:
•Control module: This comprises the basic board, the
user interface, the EXV control board and option boards,
as well as the customer’s terminal block.
•Start-up module: This consists of the start-up boards,
compressor protection boards, as well as the compressor
circuit breakers and contactors.
•Fan module (air-cooled unit): Consists of one or two
4xDO boards together with the fan circuit breakers and
contactors.
3.2 - Electronic boards
3.2.1 - The basic board
It can be used alone or in conjunction with slave boards. It
holds the program that controls the machine. It continuously
manages the information coming in from the various pressure
and temperature sensors, and communicates with the slave
boards via the SIO bus. It can also communicate with elements
of the Carrier Comfort Network via the CCN bus.
NOTE: After a power cut the unit restarts in the same
operating mode as before the power cut.
3.2.2 - Slave boards
•Compressor board RCPM: This board is used to control
a compressor. Up to eight RCPM boards can be connected
to the basic board.
•4xDO board: This board can be used to control fan stages.
•PD4-EXV board: This board can control two EXV valves
and two suction temperature sensors.
•4xAI-2xAO board: This optional board can be used to
read sensors (oil pressure), or to control variable speed
fans (air-cooled units) or the condenser valve (water-cooled
units).
•NRCP-BASE board: This optional board is used to control
the inputs and outputs of the heat reclaim option.
3Compressor start-up module
4Control system
5User interface
6
3.2.3 - The user interface
The user interface is in two parts:
•The main interface: This gives access to all of the
control parameters for the unit. It consists of a 2-digit
primary display block and a secondary 4-digit display
block with 10 LEDs and 5 buttons.
•The summary interface: This gives quick access to just
the main control parameters for the unit. It comprises 12
buttons and 16 LEDs, and includes a schematic diagram
of the unit.
3.2.4 - Connections between boards
The basic board and slave boards communicate with each other
over an internal three-wire RS485 communication bus (SIO
bus). These three wires link all the boards in parallel.
Terminals 1, 2 and 3 on connector J9 (A, B, C are connected
internally) of the basic board are connected to terminals 1, 2
and 3 of terminal J9 of the NRCP-BASE board, terminal J4 of
the PD4-EXV board respectively, except for terminal J3 of the
4xDO and 4xAI-2xAO boards where terminals 2 and 3 are
reversed.
Incorrect connection will render the system inoperative.
3.2.5 - Slave board addresses
Every slave board (except the NRCP-BASE board) has a
unique address controlled by 8 DIP switches. The switch is
disabled when it is in the open position (OPEN or OFF). On
RCPM boards SIO address switch is labelled 'ADDR'.
3.2.7 - Light emitting diodes on boards
All boards continuously check and indicate the proper
operation of their electronic circuits. A light emitting diode
(LED) lights on each board when it is operating properly.
Red LED
•The MAIN red LED flashes at about 2 second intervals to
show that the module is working properly.
•Irregular flashing or no flashing is a sign of a defective
board.
Green LED
(item SIO on the board)
•This LED flashes continuously to show that the board is
communicating correctly over its internal bus.
•If this LED is not flashing, check the wiring of the SIO
bus and the address of the board (slave board only). If the
basic board is not linked to any slave boards, this LED
should not flash.
•If all slave boards indicate a communication fault, check
the SIO bus connection on the basic board. If this
connection is correct and the fault persists, replace the
basic board.
Orange LED - CCN/clock board
•This LED flashes to show that the basic board is communicating via the CCN bus.
NOTE: Any incorrect address will prevent the unit from
starting. Turn off the power before amending the address of
any auxiliary board.
All boards are supplied by a 24 V source, ref erred to earth. In the
event of a power supply interrupt, the unit restarts automatically
without the need for an external command. However, any faults
active when the supply is interrupted are saved and may in
certain cases prevent a circuit or unit from restarting.
NOTE: When connecting the power supply for the boards,
maintain polarity.
3.3 - The controls
3.3.1 - Electronic expansion valve (EXV)
The EXV is used to adjust the refrigerant flow to changes in
the operating conditions of the machine. For this purpose, a
series of calibrated orifices are machined into the wall of the
refrigerant inlet port. As the refrigerant passes through these
orifices, it expands and becomes a bi-phase mixture (liquid and
gas).
T o adjust the refriger ant flow to changes in operating conditions,
a piston moves constantly up or down to vary the cross-section
of the refrigerant path. This piston is driven by an electronically
controlled linear stepper motor. The high degree of accuracy
with which the piston is positioned ensures that the flow of
refrigerant is precisely controlled.
NOTE: The external connector of the EXV must be cleaned
and coated with silicone grease (Part No. 397 EE) to keep out
condensation and prevent corrosion.
3.3.2 - The head pressure controls
The controller can deal with the following:
•in the case of air-cooled units, for each circuit, fan stages
together with, if necessary, a variable speed fan (controlled
by an optional 4xAI-2xAO board)
•in the case of water-cooled units, a water valve. This valve
is controlled by an optional 4xAI-2xAO board which can
deliver a 0-10 V d.c. or 4-20 mA signal, depending on the
configuration.
7
3.3.3 - The evaporator pumps
The controller can regulate one or two evaporator pumps, with
automatic changeover between the two pumps.
3.3.4 - The condenser pump
In appropriate cases the controller can regulate a condenser
pump (for water-cooled units or air-cooled units with heat
reclaim option). This control does not require an additional
board.
3.3.5 - Pressure sensors
These are used to measure the following pressures in each
circuit:
•Discharge gas pressure (high pressure type)
•Suction pressure (low pressure type)
•Oil pressure (option)
These electronic sensors deliver 0 to 5 V d.c. to the main board
or to a 4xAI-2xAO slave board. Two sensor versions are used;
one is calibrated for high pressure and the other for low
pressure and oil pressure.
Discharge pressure sensors
These are on the high pressure side of the lead compressor in
each circuit. They replace the usual discharge gas pressure
gauges and can be used to control head pressure or by the high
pressure load shedding option.
Oil pressure sensors
If installed, these sensors are used to measure the compressor
oil pressure on the oil pressure discharge side. The suction
pressure is subtracted from the oil pressure value to arrive at
the differential oil pressure.
Suction pressure sensors
They are located in the low-pressure side of the unit on the lead
compressor of each circuit. The suction pressure sensor reading
is used to control the electronic expansion devices EXV. They
permit replacement of the low-pressure switches, low-pressure
gauges and possibly of the oil pressure safety switch.
3.3.6 - Thermistors
These all have similar characteristics.
Evaporator entering water temperature sensor
The evaporator entering water temperature sensor is installed in
the evaporator wall in the free space at the side of the tube
bundle.
Evaporator leaving water temperature sensor
The evaporator leaving water temperature sensor is installed in
evaporator leaving water piping: The sensor bulb is directly
immersed in the water.
Compressor suction sensor
This is located in the lead compressor of each circuit in the
suction gas line situated between the motor and the cylinders
above the oil pump.
Condenser entering and leaving water temperature sensors
These are used to control the heating capacity on heat pumps.
In cooling only units they have no control function. They are
installed in the common condenser entering and leaving line.
Heat reclaim condenser entering/leaving water temperatures
These sensors measure the entering and leaving water temperatures of heat reclaim condensers and are used on air-cooled
units equipped with the heat reclaim option. If not, they may be
fitted as options. In this case they only have informative
character.
Temperature setpoint reset sensor
This is an optional 0-10 V sensor which can be installed
remotely from the unit. It is used to reset the cooling and
heating setpoint on the unit as a function of either the outdoor
air temperature or ambient room temperature. The sensor is not
supplied by Carrier, and must be configured by the User Menu.
Outdoor temperature sensor
Mounted on the control box. It is used for start-up, setpoint
temperature reset and frost protection control.
Master/slave assembly temperature control
The optional water temperature sensor can be used for master/
slave assembly control.
8
3.4 - User connections
The connections below are available at the customer’s terminal
block. Some of them can only be used in special operating
modes. For further details see the sections that describe the
functions (section 5) and the configurations (section 4.2.1).
NOTE: The bridge between terminals 32, 63 and 65 on the
customer’s terminal block must not be removed.
CONNECTION BLOCK
DESCRIPTION
Alarm relay output, circuit A
Alarm relay output, circuit B
User safety loop and chilled water
pump interlock
Remote start/stop
Remote cooling setpoint selection
Remote heating/cooling control
or
remote heat reclaim control
Demand limit command
0-10 V d.c. setpoint reset or
demand limit entry
Connection to CCN
CONNECTOR/CHANNEL
J3 / CH24
J3 / CH25
J4 / CH15a
J4 / CH11
J4 / CH12
J4 / CH13
J4 / CH13
J4 / CH14
J8 / CH10
J12
TERMINAL
30A - 31A
30B - 31B
34 - 35
32 - 33
65 - 66
63 - 64
63 - 64
73 - 74
71 - 72
1 - 2 - 3
DESCRIPTION
Indicates alarms in circuit A
Indicates alarms in circuit B
This contact is mounted in series with the water flow
control contact. It can be used for any user safety loop
that requires that the unit is shut down, if it is open. The
chilled water pump operation auxiliary contact is
connected between these two terminals.
The remote start/stop command is only used if the unit is
under remote operation control (rEM). See section 4.2.1.
The remote cooling setpoint selection command is only
used if the unit is under remote operation control (rEM).
See section 4.2.1.
The remote heating/cooling control command is only used
if the unit is under remote operation control (rEM). See
section 4.2.1.
The command allows selection of the second condensing
setpoint or of the heat reclaim mode. It is only used if the
unit is under remote operation control (rEM). See section
4.2.1.
This contact permits activating the unit demand limit
function. See section 5.8. This contact is active, whate v er
the operating type.
This 0-10 V d.c. input is used for setpoint reset or unit
demand limit. It is active, whatev er the unit operating type .
This 0-10 V signal can be supplied by a user command or
a 0-10 V temperature sensor.
A RS-485 bus is used for connection to the CCN.
The CCN connector is located on the CCN/clock board
(inserted on the PD4 Basic Board)
- Pin 1: signal +
- Pin 2: ground
- Pin 3: signal -
REMARKS
Volt-free contacts 24 V a.c. 48
V d.c. max, 20 V a.c. or V
d.c., 3 A max, 80 mA min,
external power supply .
Connector: 6 pin WA GO
231-306/026000 pitch 5.08.
24 V a.c., 20 mA
Connector: 10 pin WAGO
734-110, pitch 3.5
Connector: 2 pin WAGO 231302/026000 pitch 5.08
Use of a shielded cable (max.
length: 1000 m)
Shielding: braiding on 95% 100% of the cable surface.
Shielding connection at the
two cable ends.
AVAILABLE TERMINALS
Description
Condenser water flow
switch input
Evaporator 1 and 2 pump
operation input
Evaporator 1 control
Evaporator 2 control
Condenser pump control
Legend
*Associated functions, if selected: automatic changeover, pump 1 and 2; manual or CCN selection; periodical; by default.
Connector/
channel
J5/CH17
J5/CH18
J2/CH19
J2/CH20
J2/CH21
TerminalDescription
This contact is used to detect lack of condenser water flow and
shuts down the unit.
This contact is used to detect an evaporator pump operation
fault and switches over to the other evaporator pump*.
This contact permits control of evaporator 1 pump by the unit*.
This contact permits control of evaporator 2 pump by the unit*.
This contact permits control of condenser pump by the unit*.
Remarks
24 V a.c - 20mA
24 V a.c. internal supply.
Max. consumption
- each output: 20 VA/10W
- for all 3: 40 VA/20 W if all are used
9
4 - SETTING UP PRO-DIALOG PLUS CONTROL
4.1 - Local interface general features
MAIN INTERFACESUMMARY INTERFACE
DUAL-CIRCUIT AIR-COOLED
MENU BLOCK
CHILLER INTERFACE
The local interface enables a number of operating parameters to
be displayed and modified.
The interface consists of two distinct parts: the main interface
(left hand section) and the summary interface (right hand
section).
MAIN INTERFACESUMMARY INTERFACE
DUAL-CIRCUIT WATER-COOLED
MENU BLOCK
CHILLER INTERFACE
Main interface
It gives access to all PRO-DIALOG PLUS data and operating
functions. It consists of:
•A two-digit display showing the number of the item
selected.
•A four-digit display showing the contents of the item
selected.
•LEDs and buttons for unit start/stop, menu selection,
menu item selection and value adjustment.
MAIN INTERFACE
BUTTON NAMEDESCRIPTION
MenuPermits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.
Up arrowPermits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises
Down arrowPermits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises
EnterGives access to the modification mode, validates a modification or displays expanded item description.
Start/stopAuthorises start or stop of the chiller in local mode or modification of its operating type.
MAIN INTERFACE MENU LEDS
LEDNAMEDESCRIPTION
INFORMA TIONS men uDisplays the general operating parameters for the unit.
TEMPERATURES menuDisplays the unit operating temperatures.
kPa
PRESSURES menuDisplays the unit operating pressures.
SETPOINTS menuDisplays the unit setpoints and enables them to be modified.
INPUTS menuDisplays the status of the unit digital and analogue inputs.
OUTPUTS/TESTS menuDisplays the status of the unit outputs and enables them to be tested.
increase of the value of any parameter.
decrease of the value of any parameter.
10
CONFIGURATIONS menuDisplays the unit configuration and enables it to be modified.
ALARMS menuDisplays active alarms.
ALARMS HISTORY menuDisplays the history of the alarms.
OPERATING LOG menuDisplays the operating times and number of starts for the unit and the compressors.
The summary interface (right hand section) includes a mimic
diagram of the unit, together with push-buttons and LEDs. It
gives quick access to the main operating parameters of the unit.
SUMMARY INTERFACE LEDS
LEDINDICATION WHEN LIT
Green LED:
The unit is authorised to start or is already running
Red LED:
- Lit: circuit A or unit shut down by alarm
- Flashing: circuit A or unit running with alarm present
Red LED:
- Lit: circuit B or unit shut down by alarm
- Flashing: circuit B or unit running with alarm present
Red LED:
Water flow switch default or user safety lock open.
Green LED:
The evaporator pump is running.
Yellow LEDs:
From top to bottom - start/stop status of compressors A1, A2, A3 and A4
or B1, B2, B3 and B4. Flashing LED indicates that the circuit is in the
protection or defrost mode (A or B).
Green LED:
The unit operates in heating mode.
Green LED:
The unit operates in cooling mode.
The following operating types can be selected using the
Start/Stop button:
OPERATING TYPES
4-DIGIT DISPLA Y DESCRIPTION
LOFFLocal Off. The unit is halted in local mode.
L-OnLocal On. The unit is in local control mode and is authorised
to start.
L-Sc*Local On - timer control. The unit is in local control mode. It
is authorised to start if the period is occupied. If the timer
program for unit operation is unoccupied, the unit remains
shut down until the period next becomes occupied.
CCN*CCN. The unit is controlled by CCN commands.
rEM*Remote. The unit is controlled by remote control contacts.
MAST*Master Unit. The unit runs as a master in a two unit lead/lag
arrangement. This is displayed if the unit is configured for
master/slave control. See section 5.19.
Legend
*Displayed if the configuration requires it.
Section 5.1 gives a more detailed description of the commands to start/stop
the unit, analysed by operating type.
4.2.2 - Stopping the unit in local mode
The unit can be stopped in local mode at any time by pressing
the Start/Stop button.
SUMMARY INTERF A CE PUSH BUTTONS
BUTTON DISPLAY
Blue button: evaporator leaving or entering water temperature in °C
Gray button: outdoor air temperature in °C
Control point (setpoint + reset) in °C
kPa
Press 1: circuit A/B discharge pressure in kPa
Press 2: circuit A/B saturated condensing temperature in °C
kPa
Press 1: circuit A/B suction pressure in kPa
Press 2: circuit A/B saturated suction temperature in °C
Press 1: compressor A1/B1 operating hours in h/10 or h/100
Press 2: compressor A2/B2 operating hours in h/10 or h/100
4.2 - Unit start/stop control
4.2.1 - Description
The unit start/stop can be controlled by one of the following
methods:
•Locally on the actual unit (Local control type)
•By remote control with the aid of user contacts (remote
control type)
•By CCN control with the aid of the CCN (CCN control
type)
The main interface includes a Start/Stop button which can be
used to stop or start the unit in the local operating type or to
select the remote or CCN operating type.
The available operating types are described in the following
table.
TO STOP THE UNIT
BUTTON ACTION2-DIGIT DISPLAY 4-DIGIT DISPLAY
Press the Start/StopCLOFF
button for less than
4 seconds (one short
press is enough).
If the button istLOFF
released, the unit stops
without the need for
further action.
4.2.3 - Starting unit and selecting an operating type
The unit can be started in local mode, or unit operating type
can be changed at any time using the Start/Stop button. In the
example that follows, the unit is stopped (LOFF) and the user
wants to start the unit in local mode.
CHANGING THE OPERATING TYPE
BUTTON ACTION
Continually press the operating type selection
button for more than 4 seconds.
Hold down the Start/Stop button.
The available operating types are displayed
one by one until the button is released.
Release the Start/Stop button if the operating
type you want is displayed (in this example LOn). "C" flashes in the 2-digit display to show
that the controller is awaiting confirmation.
Press the Enter button to confirm the
operating type selected (in this example: LOn). "t" is displayed in the 2-digit display to
indicate the operating type selected. If the
Enter button is not pressed soon enough, the
controller will cancel the change and continue
to use the previous operating type.
2-DIGIT4-DIGIT
DISPLAYDISPLAY
CLOFF
L-On
L-Sc
rEM
L-On
tL-On
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.