Carrier PC211 User Manual

Page 1
19XL
50/60 Hz
Hermetic Centrifugal Liquid Chillers
®
with HCFC–22 and HFC–134a
Start-Up, Operation, and Maintenance Instructions
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 211 Catalog No. 531-94512-94 Form 19XL-3SS Replaces: 19XL- 2SS
Carrier Corpor ation 1994
©

Safety Considerations

Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgement and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and safety precautions contained in the machine instructions as well as those listed in this guide.
Page 2
DANGER
DO NOT VENT refrigerant relief devices within a building. Outlet from rupture disc or re lie f v al ve mu st be vent e d ou t doo rs in a c co rd an ce with the la tes t e dit i on of ANS I/ASHRAE 15 (Ameri can Nat io nal Sta nd ards In st itute /American Society of Heating, Refrigeration, and Air Conditioning Engineers). The accumulation of ref rigerant in an enclosed spa ce can dis pl ace ox ygen and cause asphyxiation .
PROVIDE a dequ a te vent il a ti on in a c cordance with ANSI/ASHRAE 1 5 , es peciall y for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fata l. Va po r is heavi er than air and reduces the amount o f oxygen available for breathing. Product causes eye and skin irritation. Decomposition pro ducts are haza rdous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures. VERIFY the allowable test pressure by che cking the instruct io n literature and the design press ures on th e equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen. DO NO T VALVE O FF any safe t y device. BE SURE that all pressure relief devices are properly installed and functioning
befor e ope r ati ng an y mac hine.
!
DANGER
Page 3
WARNING
DO NOT WELD OR FLAM E CUT any refri gerant li ne or vessel un t il all refrigerant (
liquid and vapor
placed with dry air or nitrogen and the work area should be well ventilated.
Refr ig erant in con t act with an open flame pr od uces toxic gases.
DO NOT US E eyebol t s or eyebolt ho les to rig machin e sections or the entire assemb ly.
DO NOT work on high-voltage equipment unless you are a qualified electrician. DO NOT WORK ON electrical components, including control panels, switches,
sta rte r s, or oil heate r until you a r e sur e AL L P OW E R I S OFF and no re si du al v ol t ­age can le ak f rom ca pacitors or sol id-st at e components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTER­RUPTE D, confi rm t hat all ci rcuit s are deenergized before resuming work.
DO NOT siphon refrigerant . AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE
SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a ph y sician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous over pressu re can result. Wh en it is ne cessar y t o he at ref rigerant , u se only warm (110 F [43 C]) water.
!
) has been removed from chiller. Traces of vapor should be dis-
WARNING
Page 4
WAR NING
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND IL LEGAL. W hen cylinder is emptie d, evacuat e remaining gas pressure, loosen th e collar , an d unscr ew and discard t he valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the machine. The introduction of the wrong refrigerant can cause machine damage or malfunction to this machine. Operation of this equipment with refrigerants other than those cited herein shou ld comp ly with ANS I/ASHRAE - 15 (latest ed ition). Con t act Car­rier for further information on use of this machine with other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before breakin g an y refrigeran t connec t io n.
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT L E AS T ONCE A YEAR. If machine op erates i n a co rrosive atmo sphere, in spect th e devices at mor e f requen t in t ervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corro­sion or build-up of foreign material (rust, dirt, scale, etc.) is found within the val ve body o r mechani sm. Re pl ace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring. Sudden
release of t he spri ng can cause it and o bj ects in its path to act as proj ect iles.
!
WARNING
Page 5
CAUTION
DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.
DO NOT climb over a machine. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection cov ers or ot her heavy component s. Even if compon ents ar e li ght, us e mecha ni ­cal equipment when there is a risk of slipping or losing your balance.
BE AWARE tha t cert ain au t omati c st art arrangem ents CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect tower fan, and pumps.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NO T VE N T OR DR A IN wa te rb ox es c on t ai nin g industr ia l brine s, liq uid, gas e s, or semisolids without the permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items hav e been removed b ef ore rot at ing any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut has a posi­tive thread engagement.
!
CAUTION
ahead of
the st arter,
Page 6
CAUTION
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks , o r damage.
PROV IDE A DRAIN conne ct ion in the vent lin e near each pressure rel ief de vice to prevent a build-up of condensate or rain water.
!
CAUTION
Page 7

Contents

List of Tables List of Figures Safety Considerations Introduction Abbreviations and Explanations Machine Familiarization
Machine Information Plate System Components Cooler Condenser Moto r-Co m pr e ss o r Control Center Factory-Mounte d Starte r (O ptional) Storage Vessel (Optional)
Page 8
Contents
Refrigeration Cycle Motor/Oil Ref r ige r ati on Co oling Cyc le Lubrication Cycle
Summary Details Oil Reclaim System
During Normal Machine Operation During Light Load Conditions
Starting Equipment
Unit Mounted Solid-State S tarter (Optional) Unit Mounted Wye-Delta Starter (Optional)
Controls
Definitions
Analog Signal
Page 9
Digit al Signal Volatile Memory
General PIC System Components
Pr ocessor Modu le (PSIO) Starter Management Module (SMM) Local I nter f ace Devi ce (LID) 6-Pack Relay Board 8-Input Modules Oil Heater Contactor (1C) Oil Pump Contactor (2C) Hot Gas Bypa ss Contactor Relay (3C) (Optional ) Control Transformers (T1-T4)
Contents
Control and Oil Heater Volt age Sel ecto r (S1)
LID Operation and Menus
General Alarm and Alerts
Page 10
Menu Structure To View Point Sta tus Override Operations Time Schedule Operation To View and C hange Set Point s Service Operation
PIC System Funct ions
Capacity Control Enteri ng Chilled Water Control Deadband Proportional Bands and Gain Dema nd Limiting Machine Timers
Contents
Occupancy Schedule
Safety Controls
Shunt Trip
Page 11
Contents
Def a u lt Scr een Fr eeze Motor Cooling Control Ramp Loading Control Capacity Ov erride High Discharge Temperature Cont r ol Oil Sump Temperature Control
PSIO Softwa r e Vers ions 08 and Lower PSIO Software Versions 09 and Hi gher
Oil Cooler Remote Start/ St op Contr ol s Spare Safety Inputs
Spare Alarm C ont acts
Condenser Pump Control Condenser Freeze Pr ote ction
Page 12
Contents
Tower Fan Relay Auto. Restart After Power Failur e Water/Br ine Reset Demand Limit Control, Option (Requires Optional 8- Input Module) Surge Prevention Algor ithm Surge Protection Lead/Lag Control
Common Point Sensor Installation Machi ne Communication Wiri ng Lead/Lag Operation Faulted Chiller Operation Load Balancing Auto Restart After Power Failure
Ice Build Control
Ice Build Initiation
Page 13
Contents
Start-Up/Recycle Operation Tempe rature Control During Ice Build Termination of Ice Build Retu rn to Non-i ce Build Operati ons
Attach to Network De vi ce Control
Changing Refrigerant Types Attachi ng to Other CC N Modul es
Service Operation
To Log On To Log Off Holida y Scheduling
Start-Up/Shutdown/Recycle Sequence
Local Start-Up Shutdown Sequence Automatic Soft-S top Am ps Threshold (PSIO Sof tw are Version 09 and
Higher)
Page 14
Chilled Water Recycle Mode Safety Shutdown
Before Initial Start-Up
Job Data Required Equipment Requi r ed Using the Optional Storage Ta nk and Pumpout System Remove Shipping Packaging Open Oil Circuit Valves Torque All Gasketed Joints Check Machine Tightness Ref rigerant T racer
Contents
Leak Test Machine Standing Vacuum Te st
Page 15
Contents
Machine Dehydration Inspect Water Piping Check Optional Pumpout Compre ssor Water Piping Check Relief Devices Inspect Wiring Carrie r Comfort Network Interface Check Starter
Mechanical-Type Starters Benshaw, Inc. Solid-State Starter Cutler-Hammer® Solid-State Starters
Oil Charge Power Up the Controls and Check the Oil Heater
Softwa re Ver sio n
Set Up Machine Control Configurat ion Input the Design Set P oi n ts
Page 16
Contents
Input the Local Occupied Schedule (OCCPC01S) Selecting Refrigerant Type
To Confirm Refrigerant Type To Chang e Re frigerant Type
Input Service Configurations
Password Input Time and Date Change LID Configuration If Necessary Modify Controller Identificati on If Necessary Input Equipment Service Par ameters If Necessary Modify Equipment Configuration If Necessary Check V oltage Supply Perform an Automated Control Test
Check Optional Pumpout System Controls and Compressor High Altitude Loca ti ons
Page 17
Charg e Refrig er ant into Mach ine
19XL Mach ine E quali z at ion without Pumpout Uni t 19XL Mach ine E quali z at ion with Pumpout Unit Trimmi ng Refrigerant Charge
Initial Start-Up
Preparation Manual Operation of th e Guid e Vane s Dry Run to Test Start-Up Sequence Check Rotation
If Rotation Is Proper If the Motor Rotation Is Not Clockwise Notes o n Solid- State Starter s (Bens haw, Inc.)
Contents
Check Oil Pressure and Compressor Stop Calibrate Motor Current Demand Setting To Prevent Accidental Start-Up
Page 18
Contents
Check Machine Operating Condition Instruct the Customer Operator
Cool er-Condenser Option al Stor age Tank and Pumpout System Motor Compressor Assembly Motor Compressor Lubrication Sys te m Control System Auxiliary Equ ipment Describe Machine Cycles Review Maintenance Safety Devices and Procedures Check Operator Know ledge Review the Start-Up, Operation, and Maintenance Manual
Operating Ins tr uc t ion s
Operator Duties
Page 19
Contents
Prepare the Machine for Start-Up To Star t th e M achine Check the Runni ng System To Stop the Machine After Limited Shutdow n Extended Shutdown After Extende d Shut down Cold Weather Operation Manual Guide Vane Operation Refrigera ti on Log
Pump out and Ref rigerant Transf er Procedures
Pr eparation Operating the Optional Pumpout Compressor
To Read Re frige ran t Pressur es
Page 20
Machines with Storage Tanks
Transfer Refri gerant from Storag e Tank to Mach ine Transfer the Refrigerant from Machine to Storage Tank
Machines with Isolation Valves
Transfer All Refrigerant to Condenser Vessel Transfer All Refrigerant to Cooler/Compressor Vessel
Retu rn Refrigeran t to Normal Operating Conditions
Genera l Mai nt e na nc e
Refrigeran t Pro perties Adding Refri gera n t Removing Refrigerant Adjustin g the Refr igeran t Charge
Contents
Ref rigeran t Leak T est in g Le ak Ra te
Page 21
Test After Service, Repair, or Major Le ak
Ref rigerant Tracer To Pres surize w ith Dry Nitr ogen
Repair the Leak, Retest, and Apply S tanding Vacuum Test Checking Guide Vane Link age
Checki ng the Auxiliary S witch on Gu ide Vane Actua t or
Trim Refrigerant Charge
Weekly Maintenance
Check the Lubrication System
Sched ule d Mai nt e na nc e
Service Ontime Inspect th e Co ntro l Cen ter
Contents
Check Safety and O perating Controls Monthly Changing Oil Filter Oil Specification
Page 22
Contents
Oil Changes
To Change the Oil
Refrigeran t F ilter Oil Reclaim Filters Inspect Refrigerant Float System Inspect Relief Valves and Piping Com pr e sso r Be aring and Gear Ma in t en ance Inspect the Hea t Exchanger Tubes
Cooler Condenser
Water Leaks Water Tre atment Inspect the Starting Equipment Check Pressure Transducers
Page 23
Optional Pumpout System Maintenance
Optional Pumpout Compressor Oil Charge Option al Pu mp out S af ety Control Settings
Ordering Replacement Chiller Parts
Troub le sh ooting Gui de
Overvi ew Checking the Display Messages Checking Tem per a t ur e Sen sor s
Resistance Check Voltage Drop Check Sensor Ac cura cy Dual Tempe r ature Sensors
Contents
Checking Pressure Transducers
Transducer Replacement
Control Algori thms Checkout Procedure
Page 24
Contents
Control Test Control Modu les
Red LED Green LE Ds
Notes on Module Operation Processor Module (PSIO)
Inputs Outputs
Starter Management Modul e ( SM M)
Inputs Outputs
Options Modules (8-Input) Replacing Defective Processor Modules
Installation
Page 25
Solid-State Starters
Testing Silicon Control Rectifiers in Benshaw, Inc. Solid-State Starters
Contents
Testing Silicon Control Rectifiers (SCRs) in Cutler-Hammer® Solid-State Starters
Electronic Protection Relay (EPR)
Physical Data
Initial Start-Up Checklist for 19XL Hermetic Centrifugal Liquid Chiller
Page 26

List of Tables

Table 1 — Major PIC Components and Panel Locations Table 2 — LID Screens
Example 1 — Status01 Disp lay Scr een Example 2 — Status02 Disp lay Scr een Example 3 — Status03 Disp lay Scr een Example 4 — Setpoint Display Screen Example 5 — Confi gur ation (Config) Dis p l ay Scr ee n Example 6 — Le ad/Lag Confi guration Display Screen Example 7 — Service1 Display Screen Example 8 — Service2 Display Screen Example 9 — Service3 Display Screen Example 10 — Mainten ance (Maint0 1) Display Scr een
Contents
Example 11 — Mainten ance (Maint0 2) Display Scr een Example 12 — Mainten ance (Maint0 3) Display Scr een Example 13 — Mainten ance (Maint0 4) Display Scr een
Page 27
Contents
Table 3
Protective Safety Li m it s and Control Settings
Table 4 — Capacity O ver rides Table 5A — HCFC-22 Pressure — Temperature (F) Table 5B — HCFC-22 Pressure — Temperature (C) Table 5C — H FC-134a Pressure Table 5D — H FC-134a Pressure
Te m p e r a ture (F )
Te m p e r a ture (C)
Table 6 — Potentiometer Adjustme nt Table 7 — Amps Corre ction Fa ctors for 19XL Motors Table 8 — Control Test Menu Functions Table 9 — Refrigerant (HCFC-22 or HFC-134a) Charges Table 10 — LID Primar y an d Seconda r y Messages and Custom Alarm/
Alert Messages with Troublesho oting Guides
A. Shutdown with On/Off/Reset-Off B. Timing Out or Ti m ed Out C. In Recycle Shutdown
Page 28
Contents
Table 10 — LID Primary an d Seconda r y Messages and Custom Alarm/
Alert Messages with Troublesho oting Guides (Continued)
D. Pre-Start Alerts E. Normal or Auto.-Restart F. Sta r t-Up Failures G. Compressor Jumpstart and Refrigerant Protection H. Nor mal Run with Reset, Tempe r ature, or Demand I. Normal Run Overrides Active (Alerts) J. Out-Of-R ange Sensor Failures K. Machine Pr otect Limit Faults L. Machine Alerts M. Spare Sensor Alert Messages N. Other Problems/Malfunctions
Table 11A—Thermi stor Temperature (F) v s Resistance/Volta ge Drop Table 11B—Thermi stor Temperature (C) vs Re sistance/Voltage Drop Table 12 — Benshaw, Inc. Solid-State Starter Tr oubl es hooting Guide
Page 29
Contents
Table 13 — Cutler- Hamme r® S olid-State Starter Troubl eshooting
Guide Table 14 — Heat Exchanger Data Table 15 — Additional Data for Marine Waterboxes Table 16 — Compressor Wei ghts Table 17 — Compressor/Motor Weights Table 18 — Waterbox Cove r We ights Table 19 — Optional Pum pout System Electr ica l D ata
Page 30

List of Figures

Figure 1 — 19XL Iden tification Figure 2A— Typi cal 19XL Components — Design I Figure 2B— Typi ca l 19 XL Components — Design II Figure 3 — Refrigera nt Moto r Cooling an d Oil Cooling Cycles Figure 4 — Lubricat i on System Figure 5 — Cutler-Hammer Soli d -State Starter, Internal Vi ew Figure 6 — Benshaw, Inc. Solid-State Starter, Internal View Figure 7 — Typical St arte r Fr ont View (Solid-S ta te Starter Shown) Figure 8 — 19XL Contr ols and Sensor Locations Figure 9 — Control Sensors (Temperature)
Contents
Figure 10— Control Senso rs (Pr essure Tr ans ducer, Typical) Figure 11— Control Panel (Front View), with Options Module Figure 12— Power Panel with Options
Page 31
Contents
Figure 13— LID Defa ult Screen Figure 14— LID Service Screen Figure 15— Example of Point Status Screen (Status01) Figure 16— 19XL Menu Structur e Figure 17— 19XL Service Menu Structure Figure 18— Example of Time Schedule Operation Screen Figure 19— Exam pl e of Set Poi nt Screen Figure 20— 19XL Hot Gas Bypass/Surge Preve nti on Figure 21— 19XL with Default Metric Settings Figure 22— Example of Att ach to Net wo rk D evice Screen Figure 23— Example of Holiday Period Screen Figure 24— Control Seque nce Figure 25— Typical Wet-Bulb Ty pe Vacuum Indicator Figure 26— 19XL Leak Test Proce dur es
Page 32
Contents
Figure 27— Typical Opti onal P ump out S ys te m Pipi ng Schematic with
Storage Tank Figure 28— Typical Opti onal P ump out S ys te m Pipi ng Schematic with-
out Storage Tank Figure 29— Dehydration Cold Trap Figure 30— Benshaw, I nc. Solid-State Starter Power St ack Figure 31— Ramp Up and Starting Torque Potentiometers Figure 32— Typical Potent iometer Adjustment Figure 33— Typ ica l Cut le r-Hammer® Sol id-State St arter Figure 34— Cor rect Motor Ro tat ion Figure 35— Refrigerat ion Log Figure 36— 19XL Pumpout Unit W iring S che m at ic Figure 37— Optional Pumpout System Figure 38— Guide Vane Actua tor Li nka ge Figure 39— 19XL Float Val ve Des igns
Page 33
Contents
Figure 40— Optional Pumpout System Controls Figure 41— PSIO Module Address Selector Switch Locations and LED
Locations Figure 42— LID Module (Rear View) and LED Locations Figure 43— Processor (PS IO) Module Figure 44— Starter Manage ment Module (SSM) Figure 45— Options Module Figure 46— Typical Benshaw, Inc. Solid-State Starter (Internal View) Figure 47— Resistance Check Figure 48— SCR and Power Poles Figure 49— Typ ica l Cut le r-Hammer® Sol id-State St arter (Intern al
View) Figure 50— Cutler-Hammer Terminal Functions Figure 51— Solid-State Starter, General Operation Tr oubl eshooting
Guide (Typi cal)
Page 34
Contents
Figure 52— Solid-State Sta rter, S tarter F ault (Mo tor Will Not Start)
Troubleshooting Guide (Typical ) Figure 53— Compressor Fi ts and Clearances Figure 54— Compressor Fits and Clearances (Continue d) Figure 55— Compressor Fits and Clearances (Continue d) Figure 56— Electronic PIC Controls Wiring Schematic Figure 57— Machine Power Panel, Starter Assembly, and Motor Wir-
ing Schemat i c Figure 58— Typical Wye-D elta Uni t Mounted Starter Wiring Schem at ic
Page 35

Introduction

Prior to initial star t-up of the 19XL unit, tho s e inv olved in the s tart-up , opera tion, and maintenance should be thoroughly familiar with these instructions and other necessary job data. This book is outlined so that you may b ecome familiar w ith the control system be fore performing start-up procedures. Procedures in this manual are arranged in the sequence required for proper m ac hine start- up and operation.
Page 36
WARNING
This unit us es a m ic r opr oc e ss or co nt r ol sy s tem . Do not short or jumper betwe en terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside con t rol center.
Use extreme care when handling tools near boards and when connecting or dis­connecting terminal plugs. Circuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiat e, radi o freq uency en ergy. If n ot inst alled and used in accordance with the instruction manual, it may cause interference to rad io co mm un ic ations. I t ha s be en te ste d a nd fou nd to com ply wi t h the limits f or a Clas s A computing device pursuan t to S ub part J o f Part 15 of FCC Rul es, which are designed to provide reasonable protection against such interference when o perated in a commercial envi ronmen t . O perati on of thi s equip ment in a residential area is likely to cause interference, in which case the user, at his own expe nse, wi ll be required to ta ke whate ver meas ures may be requi red to correct the in t erference.
Alw ays stor e and transport replacement or defe ct ive boa rds in ant i-stat ic ship­ping ba g.
!
WARNING
Page 37

Abbreviations and Explanations

Frequently us ed abb r ev iatio ns in this manual inc lude:
CCN — Carrier Comfort Network LID — Local Interface Device CCW — Countercloc kwi se LCW — Leaving Chill ed Water CW — Clockwise OLTA — Overload Trip Amps ECW — Entering Chi ll ed W ate r PIC — Product Integr at ed Cont r ol ECDW — En teri ng Condenser Water PSIO — Processor Sensor Input/Out put Module EMS — Energy Manag eme nt Sys tem RLA — Rated Load Amps HGBP — Hot Gas Bypass SCR — Silicon Control Rectifier I/O — I nput/Output SI — Inter nat ional System of Units LCD — Liquid Crystal Display SMM — Starter Management Module LCDW — Leaving Condenser Water TXV — Thermal Expansion Valve LED — Light-E m itti ng Di ode
The 19XL machines use HCFC-2 2 and HFC - 134a ref r igerant. Whe n r eferen c ing refrigerant charg es in this manual , t he HCFC - 22 c harge will be lis ted fir s t and the HF C- 134a va lue will be show n nex t to it in [ ].
Words printed in all capital letters or in italics may be viewed on the LID.
The PSIO s oftwar e v er s ion nu mb er of your 19X L unit will be lo c ated on the front cover.
Page 38

Machine Familiarization

Figure 1
(

Machin e Information Plate

The infor m ati on plate is loc ate d on the rig ht side of the machine control ce nter panel.
Click here for Figure 1 — 19XL Identification

System Components

The components include the cooler and condenser heat exchangers in separate vessels, motor-compressor, lubrication package, control center, and motor starter. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.

Cooler

This ves s el (als o k nown as th e ev aporator) is locat ed underneath the compress or . The cool er is m aintained at lower temperat ur e/pr es s ur e so tha t evaporating r efrig er ant can remove
, Figur e 2A ( Front View) (Rear View), and Figure 2B (Front View) (Rear View)
heat fr om water f lowing through its internal tubes.

Condenser

The condenser operates at a highe r temperat ur e/pr es s ur e tha n the cool er , and has water
Page 39
flowing through its internal tubes in order to remove heat from th e r efrigerant.

Moto r-Co m pr essor

This component maintains system temperature/pressure differences and moves the heat carrying refrigerant from the cooler to the condenser.

Control Center

The control center is the user interface for controlling the machine. It regulates the machine’s capac ity as re quired t o m aintain pr oper leaving chilled water tem per atu r e. The control center :
registers cooler, condenser, and lubricating system pressures
shows machine operating condition and alarm shutdown conditions
recor ds the tot al machine ope r ating hour s
sequences machine start, stop, and recycle under microprocessor control
provides access to other CCN (Carrier Comfort Network) devices

Factory-Mounte d Starte r (O ptional)

The sta r ter allows for the proper starting and disconnecting of t he elect r ic al energy for t he compressor-motor, oil pump, oil heater, and control panels.

Storage Vessel (Optional)

There are 2 sizes of storage vessels available. The vessels have double relief valves, a magnetically coupled dial-type refr igerant leve l gage, a one- inch FPT dra in v alve, and a 1/2-in. male flare vapor connecti on for th e pum pout unit. A 30- in.-0 - 400 psi (–101- 0-2750 kP a) gage
Page 40
also is su pplied with each unit. Note: If a storage vessel is not used at the jobsite, factory-installed isolation valves on the
chil ler m ay be used t o is olate the machine charge in either t he c ooler or c onden s er . An optional pumpout compressor system is used to transfer refrigerant from vessel to ves­sel.

Refrig eration Cycle

The compressor continuously draws refrigerant vapor from the cooler, at a rate set by the amount of guide vane opening. As the compressor suction reduces the pressure in the cooler, the remaining refr igerant boils at a fairly low temperatur e (typically 38 to 42 F [ 3 to 6 C]). Th e energy r equired for bo iling is obtained fro m the water flowi ng throu gh the cooler tubes. With heat en er gy r em oved, the wat er becomes c old enough for us e in an air conditioning circ uit or process liquid cooling.
After taking heat from the water, the refrigerant vapor is compressed. Compression adds still more heat energy and the refrigerant is quite warm (typically 98 to 102 F [37 to 40 C]) when it is discharged from the compressor into the condenser.
Relativel y co ol ( typically 65 t o 90 F [18 to 32 C]) water flowin g into the conden s er tubes removes heat from the re frigerant and the vap or c ondenses to li quid.
The liq uid refrigerant pass es through orific es into the FL A S C ( Flash Subcooler) cham ber
Page 41
(Figure 3). Since the FLASC chamber is at a lower pressure, part of the liquid refrigerant flashes to vapor, thereby cooling the remaining liquid. The FLASC vapor is recondensed on the tubes whic h are c oo led by ent ering condense r wat er. The liquid dra ins in to a flo at ch amber bet wee n the FLASC chamber and cooler. Here a float valve forms a liquid seal to keep FLASC chamber vapor from ente r ing the co oler. When liquid refr igerant pas s es throug h the valve, some of it flashes to vapor in the reduced pressure on the cooler side. In flashing, it removes heat from the remaining liquid . T he r efrigeran t is now at a temperature and pr essur e at whi c h the cycle began.

Motor/Oil Refrigeration Cooling Cycle

The motor and the lubricating oil are cooled by liquid refrigerant taken from the bottom of the condenser vessel (Figure 3). Flow of refrigerant is maintained by the pressure differential that exist s due to compress or oper ation. After the refrigerant flows past an isolation valve, an in-line filter, and a sight glass/moisture indicator, the flow is split between motor cooling and oil cooling systems.
Flow t o th e m otor fl ows throug h an orifi c e and int o the motor . Ther e is als o another orifice and a solenoid valve which wi ll open if additional mot or c ooling is required . O nc e past t he orific e, the refrig er ant is direct ed ov er the mo tor by a spr ay noz z le. The refri ger ant co llects in the bottom of the motor casing and then is drained back into the cooler through the motor refrigerant drain line. A back pressure valve or an orifice in this line maintains a higher pressure
Page 42
in the motor shell than in the c ooler/ oil sump. The mo tor is protected by a temperatur e s ensor imbedded in t he s tator windings. Higher motor te m per atur es ( above 125 F [51 C] ) ener gize a solenoid to pr ov ide add itional m otor coolin g. A furt her increas e in tem per atur e pas t the m otor override set point will over r ide the temperatur e c apacit y co ntrol to hold, and if the motor temperatu r e r is es 10° F (5.5° C) ab ov e this set point , will close the inlet guide vanes. If the temperatu r e r is es above t he s afety lim it, th e c om pr essor will shut down.
Refrigerant that flows to the oil cooling system is regulated by a thermostatic expansion valve . T her e is always a mi nim um flo w by pass ing the TXV , which flows th r ough an orifice. The TXV valve regulates flow into the oil/refrigerant plate an d frame-type he at exchanger. The bulb for the expansion valve controls oil temperature to the bearings. The refrigerant leaving the heat exchanger then returns to the cooler.
Click here for Figure 2A (Front and Rear Views) — Typical 19XL Components — Design I
Click here for Figure 2B (Front and Rear Views) — Typical 19XL Components — Design II
Page 43
Click here for Figure 3 — Refrigerant Motor Coolin g and Oil Co oling Cycles

Lubr ic ati on Cy c le

Su mma ry

The oil pump, oil filter, and oil cooler make up a package located partially in the transmission casting of the compressor-motor assembly. The oil is pumped into a filter assembly to remove foreign part ic les, and is then forc ed into an oil cooler he at exchanger where t he oil is cooled to proper operational temperatures. After the oil cooler, part of the flow is directed to the gears and the hig h s peed shaft bearings; the rem ainin g flow is direct ed to the motor shaft bearings. Oil drains into the transmission oil sump to complete the cycle (Figure 4).

Details

Oil is charged into the lubrication system through a hand valve. Two sight glasses in the oil reserv oir perm it oil lev el observation. Normal oil level is bet ween the m iddle of t he upper sight glass and the top of the lower sight glas s when the c om pr ess or is s hut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump temperature is displayed on the LID default screen. Oil sump temperature ranges during compressor operation betwe en 100 to 120 F (37 to 49 C) [120 to 140 F (49 to 60 C) ].
Page 44
The oil pu m p s uc tion is fed from the oil r es er v oir. An oil pr es s ure r elief va lv e m aintains 18 to 25 psid (124 to 172 kPad) differential pressure in the system at the pump discharge. This differential pressure can be read directly from the Local Interface Device (LID) default screen. The oil pump discharges oil to the oil filter assembly. This filter is capable of being valved closed to permit removal of the filter without draining the entire oil system (see Maintenance sections for details). The oil is then piped to the oil cooler. This heat exchanger uses refrigerant from the condenser as the coolant. The refrigerant cools the oil to a temperature between 100 and 120 F (37 to 49 C) .
As the oi l leav es the oi l co oler, it pas s es the oil pre s s ur e transducer and the therm al bulb for the refrigerant expansion valve on the oil cooler. The oil is then divided, with a portion flowing to the thr us t bearing, fo r war d pini on bearing, and gear spr ay . The balance then lubricates the motor s haft bearings and the r ear pinio n bearing. The oil temper atur e is m eas ured as the oil leaves the thr us t and forward journal beari ngs with in the bear ing hou s ing. The oil then dr ains into the oil reservoir at the base of the compressor. The PIC (Product Integrated Control) measures the temperature of the oil in the sump and maintains the temperature during shutdown (see Oil Sump Temperature Control sec tion ) . T his tempe r ature is r ead on the LID default screen.
Duri ng the machine star t-up, the PIC will energize t he oil pump and pro v ide 15 sec onds of prel ubr icat ion to the bearings after press ur e is ve r ified before st ar ting the compres s or. Du r ing shutdown, the oil pump will run for 60 seconds after the compressor shuts down for the purpose
Page 45
of post-lubrication. The oil pump can also be energized for testing purposes in the Control Test.
Ramp loading can slow the rate of guide vane opening to minimize oil foam ing at star t-up. If the guide vanes open quickly, the sudden drop in suction pressure can cause any refrigerant in the oil to f las h. The r es ulting oil foam c annot be pumped efficiently , therefore oil pre s s ur e falls off and lubric ation is poor . If oil pressur e falls below 15 psid (103 kPad) differ ential, the PIC will shut down the compressor.
Clic k here for Figure 4 — Lubr ication System

Oil Reclaim System

The oil reclaim system operates to return oil back to the oil reservoir by recovering it from 2 areas on the machine. The primary ar ea of recovery is from the guide vane housing. Oil als o is recovered, along wi th refrigera nt, from the cooler.
Any refrige r ant that enters the oil re s er v oir /trans m iss ion area is flash ed into gas . The demister line at the top of the casing will vent this refrigerant into the suction of the compressor. Oil ent r ained in the refr igerant is eli m inated by the demister filter.
During Normal Machine Operation
compressor pulls th e r efrigerant into the guide va ne housing to be com pr ess ed, the oil will normally drop out at this point and fall to the bottom of the housing where it accumulates. Using
, oil is entra ined with the ref r igerant. As the
Page 46
disch ar ge gas pr es s ure to power an educto r , t he oil is vac uumed f r om the hou s ing by the eductor and is discharged into the oil reservoir. Oil and refrigerant are also recovered from the top of the cooler refrigera nt level and are dis c harged into the guide v ane hou s ing. The oil wil l drop to the bottom of the guide vane housing and be recovered by the eductor system.
Duri ng Lig ht Load Conditions
enough velocity to r eturn oil, which is flo ating in the cool er bac k to the com pr ess or . In addit ion, the edu c tor may not have en ough pow er to pull the oil from the guide v ane hou s ing back into the oil re s er v oir due to extr em ely low pr essur e at the guide vanes. Two solen oids, located on the oil re c laim piping, ar e operated so that the ed uc tor can pull oi l and refrigerant direc tly fr om the cooler and discharge t he m ix ture into the oil reser v oir. The oil reclaim s olenoi ds ar e operated by an auxil iar y c ontac t integr al to the guide va ne ac tua tor. This s witch ov er of the solenoids oc c ur s when the guide vanes are open ed beyond 30 deg r ees from th e c los ed posi tion.
, the suction gas into the compres s or does not hav e
Page 47

Starting Equipment

The 19XL requires a motor starter to operate the centrifugal hermetic compressor motor, the oil pump, and va r ious auxiliary equipment. The star ter serv es as the main f ield wiring interfa c e for the contractor.
Three t y pes of sta r ters are av ailab le from Car r ier Corporation: solid-state, wye-delta, and across-the-line starters. See Carrier Specification Z-375 for specific starter requirements. All starters mu s t meet these specifications in order to properly start and s atisfy m ec hanical saf ety requir em ent s . Starter s m ay be s upplied as separate, fre e- s tanding units , or may be m ounted direc tly on th e c hiller (unit mounted ) for low-volta ge units only .
Inside the star ter are 3 separate ci r c uit brea ke r s . Circuit br eaker CB 1 is the compress or motor circuit breaker. The disconnect switch on the starter front cover is connected to this breaker. Circuit breaker CB1 supplies power to the compressor motor.
WARNING
The main circuit br eaker (CB1) on t he front of t he starter disconn ects the main motor current only. Power is still energized f or the other circuits. Two more cir­cuit breakers inside the starter must be turned off to disconnect power to the oil pump, PIC controls, and oil heater.
!
WARNING
Page 48
Circu it breaker CB2 su pplies power t o the contr ol center, oil heater , and po r tions of the starter controls. Cir c uit break er CB 3 s upplie s power to oi l pum p. Bot h of these c ir c uit br eak ers are wi r ed in parallel with CB1 so that power is s upplie d to them if t he CB 1 disconnect is ope n.
All starters are shipped with a Carrier control module called the Starter Management Module (SMM). This module controls and monitors all aspects of the starter. See the Controls section for additional SMM information. All starter replacement parts are supplied by the starter manufacturer.

Unit-Mounted S olid-State Starter (Optiona l)

The 19XL may be equipped with a solid-state, reduced-voltage starter (Figu r e 5, Figure 6,
Figure 7). This starter provides on-off control of the compressor motor as its primary function.
Using this type of starter reduces the peak starting torque, reduces the motor inrush current, and decr eases m ec hanical shock. This is s um m ed up by th e phr ase ‘‘soft s tarting.’’
Two var ieties of solid-state s tarter s ar e av aila ble as a 19X L option ( factor y s upplied and installed ) . W hen a unit- m ounted, optional , solid-s tate start er is pur c hased with th e 19X L, ei th er a Bensh aw, Inc . or Cutler - Hamm er ® so lid-s tate starter wi ll be shipped wi th the unit . See
Figure 5 and Figure 6. The solid-state starter’s manufacturer name will be located inside the
starter access door. See Figure 7.
These starte r s oper ate by reducin g the start ing volt age. The start ing torq ue of a motor at full voltage is typically 125% to 175% of the running torque. When the voltage and the current are
Page 49
reduc ed at sta r t-up, the start ing tor que is reduc ed as well. The objec t is to redu c e the sta r ting voltage to jus t the voltage nec es s ary to develo p the torque required t o get the motor mov ing. The voltage and current are then ramped up in a desired period of time. The voltage is reduced through the use of silicon controlled rectifiers (SCR). Once full voltage is reached, a bypass contac tor is energi z ed to bypass the SC Rs .
WARNING
When voltage is supplied to the solid-state circuitry, the heat sinks within the start er are at line voltag e. Do not to uch the he at sinks wh ile volt age is pr esent o r serious injury will result.
There are a number of LEDs (light - em itting dio des ) that ar e us eful in troub les hoot ing and starter chec k out on Be ns haw, Inc. solid-st ate sta r te r s . T hes e are us ed to indic ate:
voltage to the SCRs
SCR contro l v oltage
pow er indicat ion
proper phasing for rotation
start circuit energized
overtemperature
grou nd faul t
!
WARNING
Page 50
curr ent unbalance
run state
These LEDs are further explained in the Check Starter and Troubleshooting Guide sections.

Unit-Mounted Wy e-Delta Start er (Optional)

The 19XL machine may be equipped with a wye-delta starter mounted on the unit. This starter is intended for use with low- v oltage m otors ( under 600 v). It reduc es the starting curr ent inrus h by c onnecting eac h phase of the mot or windin gs into a wye co nfigu r ation. T his oc c urs duri ng the star ting per iod when the motor is acc elerating up to spee d. After a time del ay , once the mot or is up to speed, the star ter automatical ly c onnects the phas e wind ings into a delta configurat ion.
Click here for Figure 5 — Cutler-Hammer® Solid-State Starter, Internal View
Click here for Figure 6 — Benshaw, Inc. Solid-State Starter, Internal View
Click here for Figure 7 — Typical Starter Front View (Solid-State Starter Shown)
Page 51

Definitions

Analog Signal

Controls

An ana log signal
operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proporti on to the te m per atu r e, gener ating ma ny v alues.)

Digit al Signal

A digital (discrete) signal
(Example: A switch is a digital device because it only indicates whether a value is above or below a s et point or boun dar y by generating an on/off, high/low, or open/closed signal.)

Volatile Memory

Vola tile memory
restored.
CAUTI ON CAUTION
The memory of the PSIO and LID modules are volatile. If the battery in a module is removed or damaged, all programming will be lost.
varie s in pr oportion to t he m onit or ed sourc e. It qua ntifies v alues bet ween
is a 2-position representation of the value of a monitored source.
is memory inc apabl e of bein g s us tained if power is los t and su bs equen tly
!
Page 52

General

The 19XL hermetic centri fu gal liquid chil ler c onta ins a m ic r oprocessor - based c ontro l c enter that monitors and controls all operations of the machine. The microprocessor control system matc hes the coo ling capacity of the machine to the co oling load while pr oviding st ate-of- the-art machine protection. The system controls cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature, and regulating the inlet guide vane via a mecha nic ally linked actuator motor. The guid e v ane is a var iable flow prewhirl ass embly that contr ols the re frigeration effect in the cooler by r egulating the am ount of refrig er ant vap or flow into t he c om press or . An increase in guid e v ane open ing increases c apacit y . A dec r ease in guide vane opening decreases capacity. Machine protection is provided by the processor which moni to r s the digi tal and analog in puts and execut es c apacit y ov er r ides or s afety s hutdo wns , if requir ed.

PIC System Components

The Product Integrated C ontrol (PIC) is the control system on the machine. See Table 1. The PIC controls the oper atio n of the mac hine by monito r ing all op er ating c ondit ions. The P IC can diagnose a problem and let th e operator know what the prob lem is and wha t t o c hec k . It promp tly positions the gui de v anes to ma intain leaving chilled water temp er ature. It can interface with auxiliary equipment such as pumps and cooling tower fans to turn them on only when required. It continually checks all safeties to prevent any unsafe operating condition. It
Page 53
also regulates the oil heater while the compressor is off, and the hot gas bypass valve, if installed.
The PIC ca n be inte r faced wi th the Carr ier Comfort Network (CCN) if desired. It can communicat e with other PIC-equ ipped chille r s and other CCN devices .
The PIC consists of 3 modules housed inside the 3 major components. The component names and the contr ol v oltage cont ained in each compon ent are listed below (als o s ee Table 1):
control center – all extra low-voltage wiring (24 v or less)
pow er panel – 230 or 115 v control voltage (per job requirement)
up t o 600 v for oil pump power
starter cabinet – mac hine power wi r ing (per job requirement)
Click here for Table 1 — Major PIC Components and Panel Locations

Pr ocessor Modu le (PSIO)

The PSIO is the brain of the PIC. This mo dule contains all of the operating softwar e need ed
Page 54
to cont r ol the machine . T he 19XL uses 3 pr ess ur e transducers and 8 ther m is tors t o s ens e pressures and temp er atures. These are connected to th e P S IO m odule. The PSIO als o provides ou tputs to t he: gui de v ane act uator; oil pump; oil heater; hot gas bypass (optio nal); motor cooling solenoid; and alarm contact. The PSIO communicates with the LID, the SMM, and the optional 8-input modules for user interface and starter management.

Starter Management Module (SMM)

This module is loc ated withi n th e s tarte r ca binet. T his m odule initia tes PSIO co m m ands for starter functions such as start/stop of the compressor, start/stop of the condenser and chilled water pumps, start/stop of the tower fan, spare alarm contacts, and the shunt trip. The SMM moni to r s star ter inputs s uc h as flow sw itches, line volt age, re m ote star t contac t, s par e safety, condens er high press ur e, oil pum p int er lock, motor cur r ent si gnal, star ter 1M and run contac ts, and kW t ransducer input (optional). The SMM co ntains logic ca pable of safely shutting d own t he machine if communications with the PSIO are lost.

Local I nter f ace Devi ce (LID)

The LID is mounted to the control center and allows the operator to interface with the PSIO or other CCN devices. It is the inpu t center for all local machine set point s , sc hedul es , set-u p funct ions, and options. The LID has a STO P button, an alarm light, 4 button s for logic inputs , and a display. The function of the 4 buttons or ‘‘softkeys’’ are menu driven and are shown on the display direc tly abo v e the key.
Page 55

6-Pack Relay Board

This device is a c lus ter of 6 pilot relays located in the control c enter. It is energiz ed by th e PSIO fo r the oil pu m p, oil heater, alar m , optional hot gas bypass re lay , and mo tor cooling solenoid.

8-Input Modules

One optional module is factory installed in the control center panel when ordered. There can be up to 2 of these module s per c hiller with 8 sp ar e inputs eac h. They ar e used whene v er chilled water reset, demand reset, or reading a spare sensor is required. The sensors or 4 to 20 mA signals are field- installed.
The spare temperature sensors must have the same temperature/resistance curve as the other tempe r ature sensors on this un it. These sensor s ar e 5,000 ohm at 75 F (25 C) .

Oil Heater Contactor (1C)

This contactor is located in the power panel and operates the heater at either 115 or 230 v. It is cont r olled by the PIC to maintain oil te m per atur e dur ing mac hine sh utdown.

Oil Pump Contactor (2C)

This contact or is locat ed in the power panel. It oper ates all 200 to 575- v oil pumps . The PIC energiz es the contac tor to turn on th e oil pump as necess ar y .
Page 56

Hot Gas Bypa ss Contactor Relay (3C) (Optional )

This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC energizes the rel ay dur ing low load, high lift con ditions .

Control Transformers (T1-T4)

These t r ans formers con v er t incoming control v oltag e to either 21 vac power for the PSI O module and opt ions modules, or 24 vac power f or 3 power panel contactor relay s , 3 contr ol solenoid valv es, an d the gui de v ane act uator. They are locat ed in the power panel.
Clic k here for Figure 8 — 19XL C ontrols and Sensor Loc ati ons
Clic k here for Figure 9 — Cont r ol S ensors (Tempe rature)
Click here for Figure 10 — Control Sensors (Pressure Transducer, Typical)
Click here for Figure 11 — Control Panel (Front View), with Options Module
Page 57
Click here for Figure 12 — Power Panel with Options

Control and Oil Heater Volt age Sel ecto r (S1)

It is poss ible to use either 115 v or 230 v inc oming cont ro l power in t he power panel . T he switc h is s et to the vo ltage us ed at the job site .
LID Operation and Menus (
17, F igure 18

General

The LID display will automatically revert to the default screen after 15 minutes if no softkey activity takes plac e and if the machine is not in the Pu m pdown mode (Figur e
13).
When not in the default screen, the upper right-hand corner of the LID always dis­plays the name of the screen that you have enter ed ( Figur e 14).
The LI D m ay be c onfi gur ed in English or SI units, throug h the LID config ur ation screen.
Loca l Operat ion — By pressing the LOCAL sof tkey, t he P IC is now in the LOCAL operation mode and the control will accept modification to programming from the LID only . T he P IC will us e the Loc al Time Sc hedul e to determ ine mac hine st ar t and st op times.
CCN Operation — By pressing the CCN softkey, the PIC is now in the CCN operation
, and
Figure 19
Figure 13, Figure 14, Figure 15, Figure 16, Figure
)
Page 58
mode, and the c ontrol will acc ept modi fications from any CCN interface or m odule (with the pro per author ity), as well as the LID. The P IC wil l us e the CCN time sched­ule to determine start and stop times.

Alar m s and Alerts

Alarm ( *) and alert ( !) s tatus ar e indicated on the Status ta bles. An alarm ( *) will shut down the compressor. An alert (!) notifies the operator that an unusual condition has occurred. The machine will c ontinue to op er ate when an alert is s hown.
Clic k here for Figure 13 — LI D D efault Screen
Click here fo r Figure 14 — LID Service Scr een
Alarms are indicated when the control center alarm light (!) flashes. The primary alarm message is viewed on the default screen and an additional, secondary, message and troubleshooting infor m ation ar e s ent to th e A lar m History tab le.
When an alarm is detected, the LID default screen will free z e ( s top upd ating) at t he time of alarm. The freeze enables the operator to view the machine conditions at the time of alarm. The Status tables will show the updated information. Once all alarms have been cleared (by pressing the RESET softkey), the default LID screen will return to normal operation.
Page 59

Menu Structure

To perform any of the operations described below, the PIC must be powered up and h av e successfully completed its self test.
Press QUIT to leave the selected decision or field without saving any changes. INCREASE DECREASE QUIT ENTER
Pres s E NTER to leav e the se lec ted dec is ion or field and sav e c hanges. INCREASE DECREASE QUIT ENTER
Page 60
Press NEXT to scroll the cursor bar down in order to highlight a point or to view more
points below the current screen.
NEXT PREVIOUS SELECT EXIT
Press PREVIOUS to scroll the cursor bar up in order to highlight a point or to view
points above the cur r ent scr een.
NEXT PREVIOUS SELECT EXIT
Press SELECT to view the next screen level (highlighted with the cursor bar), or to
override (if allowa ble) the highlighted point v alue.
NEXT PREVIOUS SELECT EXIT
Page 61
Press EXIT to return to the previous screen level. NEXT PREVIOUS SELECT EXIT
Press INCREASE or DECREASE to change the highlighted point value. INCREASE DECREASE QUIT ENTER
To View Point Status (
Point Status is the actual value of all of the temperat ur es, pressures , relays , and ac tuators
sense d and controll ed by the PI C.
1.
On the Menu screen, press STATUS to view the list of Point Status tables.
Figure 15
STATUS SCHEDULE SETPOINT SERVICE
)
Page 62
2. Press NE X T or PREV IOUS to highlight the desired status table. The lis t of tabl es is :
Status01 — Status of control points and sensors
Status02 — Status of relays and contacts
Status03 — Status of both optional 8-input modules and sensors NEXT PREVIOUS SELECT ENTER
3. Press SELECT to view the desired Point Status table desired. NEXT PREVIOUS SELECT ENTER
4. On the Point Status table press NEXT or PREVIOUS until desired point is displayed on the
screen.
NEXT PREVIOUS SELECT ENTER
Page 63

Override Operations

To Override a Value or Status
1.
On the P oint St atus table press NE X T or PRE V IO US to highlight the desi r ed point.
NEXT PREVIOUS SELECT EXIT
2.
Press S E LE CT to select the highlighted point. Then:
NEXT PREVIOUS SELECT EXIT
Click here for Figure 15 — Example of Point Status Screen (Status 01)
Click here for Figure 16 — 19XL Menu Structure
Page 64
Click here for Figure 17 — 19XL Service Menu Structur e
For Discrete Points
For Analog Points
3. Press ENTER to register new value.
Note: When overriding or changing metric values, it is necessary to hold the softkey down for a
— Press START or STOP to select the desired state.
START STOP R ELEASE ENTER
— Press INCREASE or DECREASE to select the desired value.
INCREASE DECREASE RELEASE ENTER
NEXT PREVIOUS SEL ECT EXIT
Page 65
few seconds in or der to se e a v alue change, es pecially on kilopa s c al v alues.
To Rem ov e an Override
1. On th e P oint Status table pres s NE X T or PREV IO US to highlight the desi r ed point.
NEXT PREVIOUS SELECT EXIT
2. Press S E LE CT to acc es s the hi ghligh ted point. NEXT PREVIOUS SELECT EXIT
3. Press RELEASE to remove the override and return the point to the PIC’s automatic control. INCREASE DECREASE RELEASE ENTER
Overr id e Indi cat ion
An override value is indicated by ‘‘SUPVSR,’’ ‘‘SERVC,’’ or ‘‘BEST’’ flashing next to the point
value on the St atus table.
Page 66
Time Schedule Operation (
1.
On the Menu screen, press SCHEDULE.
STATUS SCHEDULE SETPOINT SERVICE
2.
Press NEXT or PREVIOUS to highlight the desired schedule. PSIO Software Version 08 and lower:
OCCPC01S — LOCAL Time Schedule OCCPC02S — CCN Time Schedule
PSI O Software Vers ion 09 and higher:
OCCPC01S — LOCAL Time Schedule OCCPC02S — ICE B UILD Time Sch edule OCCPC03-99S — CCN Time Schedule (Actual number is defined in Config table.)
NEXT PREVIOUS SELECT EXIT
Figure 18
)
Page 67
3. Press SELECT to access and view the time schedule.
NEXT PREVIOUS SELECT EXIT
4. Press NE X T or PREV IOUS to highlight the desired period or overr ide th at you wish to
change.
NEXT PREVIOUS SELECT EXIT
5. Press S E LE CT to acc es s the hi ghligh ted peri od or ov err ide. NEXT PREVIOUS SELECT EXIT
Page 68
6.
a. Pre ss INCREASE or DECREASE to change the time values. Override values are in one-
hour inc r em ent s , up to 4 hours .
INCREASE DECREASE ENTER EXIT
b. Press ENABLE to select days in the day-of-week fields. Press DISABLE to eliminate
days f r om th e per iod.
ENABLE DISABLE ENTER EXIT
7. Press ENTER to register the values and to move horizontally (left to right) within a period. ENABLE DISABLE EN TER EXIT
Page 69
8. Press E X IT to lea v e the peri od or ov err ide. NEXT PREVIOUS SELECT EXIT
9. Either return to Step 4 to select another period or override, or press EXIT again to leave the
current time schedule screen and save the changes.
NEXT PREVIOUS SELECT EXIT
Click here for Figure 18 — Example of Time Schedule Operation Screen
10. Holid ay Des igna tion (HO LIDEF table) ma y be found in the Service Operation section. You must as s ign the m onth, day, and dur ation for the holiday. The Br oadcast func tion in the Brod efs tab le also mus t be ena bled for holiday period s to f unc tio n.
Page 70
To View and C hange Set Point s (
1.
To view the Set Point table, at the Menu screen press SETPOINT.
STATUS SCHEDULE SETPOINT SERVICE
2.
There are 4 set points on this screen: Base Demand Limit; LCW Set Point (leaving chilled wate r se t point) ; ECW Set Po int (ent er ing chilled water set point); an d ICE BUILD se t point (PSIO Software Version 09 and higher only). Only one of the chilled water set points can be activ e at one time, and the ty pe of set point is act iv ate d in the Service menu. ICE B UILD is als o ac tivated and configur ed in the S er v ice menu.
3.
Press NEXT or PREVIOUS to highlight the desired set point entry.
NEXT PREVIOUS SELECT EXIT
Figure 19
)
Page 71
4. Press S E LE CT to modify t he highl ighted s et poin t.
NEXT PREVIOUS SELECT EXIT
5. Press INCREASE or DECREASE to change the selected set point value. INCREASE DECREASE QUIT ENTER
6. Press ENTER to save the changes and return to the previous screen. INCREASE DECREASE QUIT ENTER
Click here for Figure 19 — Example of Set Point Screen
Page 72

Service Operation

To view t he m enu-dr iv en programs av ailab le for Serv ic e Ope r ation, see Service Operation
section. For examples of LID display screens, see Table 2 (begins on this page).
Table 2 — LID Screens
Note:
1.
Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to highlight a point or to view points below or above the current screen.
2.
The LID may be configured in English or SI units, as required, through the LID configuration screen.
3.
Data appearing in the Refer enc e Point Name s co lum n is used for CCN opera tions on ly .
4.
All options associated with ICE BUILD, Lead/Lag, CCN Occupancy Configuration, and Soft Stopping are only available on PSIO Software Version 9 and higher.
Click on an example to view:
Example 1 — Status01 Display Screen Example 2 — Status02 Display Screen Example 3 — Status03 Display Screen Ex ample 4 — Setpoint D i splay Scr een Example 5 — Configuration (Config) Display Screen
Page 73
Table 2 — LID Screens (Continued) Click on an example to view:
Example 6 — Lead/Lag Configuration Display Screen Example 7 — Service1 Display Screen Example 8 — Service2 Display Screen Example 9 — Service3 Display Screen Example 10 — Maintenance (Maint01) Display Screen Example 11 — Maintenance (Maint02) Display Screen Example 12 — Maintenance (Maint03) Display Screen Example 13 — Maintenance (Maint04) Display Screen
Page 74

PIC System Funct ions

Note:
Throughout this manual, words printed in capital letters and italics are values that may be view ed on the LID. See Table 2 for ex am ples of LID sc r eens. Point nam es ar e list ed in the Description column. An overview of LID operation and menus is given in Figure 13,
Figur e 14, Figure 15, Figure 16, Figur e 17, Figure 18, and Fig ure 19 .

Capacity Control

The PIC co ntrols the machine capac ity by m odulating th e inlet guide vanes in res ponse t o chil led water temperatur e c hanges away fro m the may be change d by a CCN networ k devic e, or is det er m ined by the PIC ad ding any active chilled water reset to the chilled water (
Increase) BAND, PROPORTIONAL DEC (Decrease) BAND
(
Enter ing Chi lled Wa te r) GAIN
may be viewed/overridden on the Status table, Status01 selection.
to determine how fast or slow to respond.
SET POINT
CO NTRO L P OI N T
. The PIC uses the
, and the
. The
CONT ROL POINT
PROP OR TIO NAL INC
PROPORTIONAL ECW
CONT ROL POINT

Enteri ng Chilled Water Control

If this optio n is enable d, the PIC uses modulate the vanes instead of
WATER
control opt ion may be v iewed /modif ied on the E quipment Configur atio n table, Config
LEAVING CHILLED WATER
EN TERING CHI LLED WATER
temperature.
temperat ur e to
ENTERING CHILLED
table .
Page 75

Deadband

This is the tolerance on the chilled water/ brine temperature temperatu r e goes out s ide of the response until it is within tolerance. The PIC may be configured with a 0.5 to 2 F (0.3 to 1.1 C) deadband.
For exam ple, a 1° F (0.6° C) deadband setting contro ls the water temperat ur e within ±0.5° F (0.3° C) of the control poi nt. This m ay c aus e frequ ent gui de v ane movem ent if the chi lled wat er load fl uc tuates frequ ently. A va lue of 1° F (0. 6° C) is the default sett ing.
DEADBAND
may be viewed or mo dified on the Equ ipm ent Se r v ic e1 table.
DEADBAND
, the P IC open s or cl os es the guide vanes in
CONT ROL POINT
. If the wate r

Proportional Bands and Gain

Propo r tiona l band is th e r ate at whic h the guide vane position is c or r ec ted in pr oporti on to how far the chi lled water /brine temperature is f r om the contr ol point. Proporti onal gain determ ines how quic k ly the gui de v anes reac t to how quickly the temperat ur e is m ov ing f r om CONT ROL POINT .
The proport ional ba nd one for t em perature response above the control po int, the other for response below the c ontro l point.
The fir s t t y pe is c alled
can be v iewed/ m odified on the LID. There are t wo r es ponse modes,
PROP OR TI ON A L INC BA ND
, and it c an s low or quicken v ane respo ns e to chilled water/ br ine tem per atur e above setting of 2 to 10; the def ault set ting is 6.5.
PROPORTIONAL DEC BAND
DEADBAND
. It can be adjusted from a
can sl ow or quick en
Page 76
vane response to chilled water temperature below deadband plus control point. It can be adjus ted on the LID from a s etting of 2 to 10, and the defaul t setting is 6.0. I nc r easing either of these settings will cause the van es to respond slower than a lower setting.
The
PROP OR TI ON A L EC W GAIN
3.0, with a default sett ing of 2.0 . I nc r ease this set ting to inc r ease guide va ne r es ponse to a change in ent er ing chilled water te m per atur e. The proportional bands and gain ma y be v iewed/ modified on the Equipment Service3 table.
can be adjusted at the LID display from a setting of 1.0 to

Dema nd Limiting

The PIC will respond to the
guide vanes. It will compare the set point to either
COMPRESSOR MOTOR CURRENT
for the setting is current limiting.
DEMAND LIMIT SOURCE
ACTIVE DEMAND LIMIT
(percentage), depending on how the control is configured
which is accessed on the SERVICE1 table. The default
set point by lim iting the ope ning of the
COMPRESSOR MOTOR LOAD
or

Machine Timers

The PIC maintains 2 runtime clocks, known as
ONTIME. COMPRESSOR ONTIME
can register up to 500,000 hours before the clock turns back to zero. The a resettable timer that can be used to indicate the hours since the last service visit or any other reason. The time can be changed through the LID to whatever value is desired. This timer can
indicates the total lifetime comp ressor run hours. Thi s timer
COMPRESSOR ONTIME
and
SERVICE
SERVICE ONTIME
is
Page 77
register up to 32,767 hours before it rolls over to zero.
The chiller also maint ains a s tart-to- s tart timer and a stop- to-sta r t t im er . Thes e timers limit how soon the machine ca n be s tart ed. See the Start-Up/Shutdown/Recycle Sequence section for operational information.

Occupancy Schedule

This sc hedule determ ines when the c hiller is eithe r occ upied or unoccupied.
Each sc hedul e c ons ists of from one to 8 occupied/unoccupie d time periods, se t by the operator. These time per iods can be enabled to be in ef fect, or not in effect, on each day of the week and for holidays. The day begins with 0000 hours and ends with 2400 hours. The machine is in OCCUPIED mode un les s an unocc upie d time period is in effect .
The machine will shut down when the sc hedule goes to UNO CCUPI E D. These s c hedules can be se t up to follow the building sch edule or t o be 100% OCCUPIED if the operat or wishes. The schedules also can be bypassed by forcing the Start/S top command on the PIC Status screen to star t. The schedules also can be overridden to k eep the unit in an OCCUPIE D m ode for up to 4 hour s , on a on e- time ba s is .
Fig u re 18 shows a schedule for a typical office building time schedule, with a 3-hour, off-peak
cool down period from midnight to 3 a.m., following a weekend shutdown. Example: Holiday peri ods ar e unoccupie d 24 hours per day. T he build ing operates Mo nday through Friday, 7:00 a.m. to 6:00 p.m., with a Saturday schedule of 6:00 a.m. to 1:00 p.m., and includes the Monday
Page 78
midnight to 3:00 a.m. weekend coo l- down schedule. Note: This schedule is for illustration only, and is not intended to be a recommended schedule
for chiller operation.
PSIO Software Version 08 and Lower
Whene v er the chiller is in t he LOCAL mode, the machine wi ll s tart when the Occ upancy Schedule 01 indicates OCCUPIED. When in the CCN mode, Occupancy Schedule 02 is used.
PSIO S oft ware V ersion 09 and Hig her
The Local Time Schedule is still the Occupancy Schedule 01. The Ice Build Time Schedule is Schedule 02 and the CCN Default Time Schedule is Schedule 03. The CCN schedule number is defined on the Config table in the Eq uipment Configur ati on table. The sch edule number can change to any value fr om 03 to 99. If this schedule num ber is ch anged on the Config table, the operator mus t use the A tt ac h to Network Dev ice ta ble to up load the new number int o th e Schedule screen. See Figure 17.
Page 79

Safety Controls

The PIC mo nitors all safe ty c ontro l input s , and if required, s huts down the mac hine or limit s the gui de v anes to protec t the mac hine from possible da m age from any of the following condition s :
high bearing temp er ature
high m otor winding temperatur e
high dis c harge temp er ature
low oil pressure
low cooler refrigerant temperature/pressure
condenser high pressure or low pressure
inadequate water/brine cooler and condenser flow
high, low, or los s of voltage
excessive motor acceleration time
excessive starter transition time
lack of motor current signal
excessive motor amps
excessive compressor surge
temper atu r e and tran s duc er fau lts
Starter faults or optional protective devices within the starter can shut down the machine. These devices are dependent on what has been purchased as options.
Page 80
CAUTI ON
If comp ressor motor overload occ urs, che ck t he mot or for grounded o r op en phases befo re at t empt in g a restart.
If the controller in itiates a s afety s hutdown, it dis plays the fault on the LID display with a prima r y and a s ec ondary mes s age, and energiz es an alarm relay in the star ter an d blinks the alarm light on the contr ol c enter . T he alarm is s tored in me m or y and can be viewed in the PIC alarm table al ong with a m es s age for troubleshoo ting.
To give a better warning as to the operating condition of the machine, the operator also can defin e alert limits on v ar ious m onitor ed inputs . Safe ty c ontac t and aler t limit s are defin ed in
Table 3. Alarm and alert messages are lis ted in th e Troubleshooting Guide section.
Click here for Table 3 — Protective Safety Limits and Control Settings (and figure following table)
!
CAUTION
Page 81

Shunt Trip

The shunt trip function of the PIC is a safety trip. The shunt trip is wired from an output on the SMM to the motor circuit breaker. If the PIC tries to shut down the compressor through normal shutdown procedu r e but is unsucces s ful for 30 s ec onds, the shunt trip outp ut is energized and cause s the circ uit brea k er to trip off . If ground fault protec tio n has been ap plied t o th e s tarte r , the ground fault trip will also ene r giz e the sh unt tri p to trip the circuit breaker.

Def a u lt Scr een Fr eeze

Whenever an alarm occurs, the LID default screen will freeze displaying the condition of the machine at th e time of alar m . Knowledge of the operat ing state of the chiller at the ti m e an alarm occurs is useful when troubleshooting. Current machine information can be viewed on the Status tables. Once all existing alarms are cleared (by pressing the RESET softkey), the defaul t LID will retur n normal operation.

Motor Cooling Control

Motor te m per atu r e is re duc ed by refrige r ant enter ing the m otor shell an d ev aporat ing. The refrigerant is regulated by the motor cooling relay. This relay will energize when the compressor is runn ing and motor tem perature is above 12 5 F (51.7 C) . T he r elay will close when mo tor temperature is below 100 F (37.8 C). Note that there is always a minimum flow of refrigerant when th e c om pr ess or is operat ing for mot or c ooling; the re lay only controls addi tiona l refrigerant to the motor.
Page 82

Ramp Loading Control

The ramp loading control slows down the rate at which the compressor loads up. This control can pre v ent the c om pr essor from loading up dur ing the s hort pe r iod of tim e when the m ac hine is star ted, and the chi lled wat er loop ha s to be broug ht down to normal design condi tions. This helps reduce electrical demand charges by slowly bringing the chilled water to control point. Howev er , the to tal power dr aw during this per iod remains almost uncha nged.
There are 2 methods of r am p loadi ng with the PIC. Ram p loading can be bas ed on chi lled water tempe r ature or on moto r load.
1.
Temperat ur e r am p load ing chilled water temperature decreases by an operator-configured rate. The lowest temperat ur e r am p table will be used the first time the ma c hine is started (a t commissioning ) . T he lowest temper ature ra m p r ate wil l als o be used if mach ine powe r has been of f for 3 ho ur s or m or e ( ev en if the motor ra m p load is s electe d) .
2.
Motor load ramp load ing compressor motor load increases by an operator-configured rate.
limits th e r ate at whic h either leaving chilled water or ent er ing
limits the rate at which the compressor motor current or
The
TEMP (Temperature) PULL DOWN, LOA D P ULL DO WN
may be viewed /modified on t he LID Equ ipm ent Config ur ation table, Config table ( s ee Table 2). Motor load is th e default type .
, and
SELECT RAMP TYPE
Page 83
Capacity Ov erride (Table 4)
These can prevent some safety shutdowns caused by exceeding motor amperage limit, refrigerant low temperature safety limit, motor high temperature safety limit, and condenser high pressure limit. In all cases there are 2 stages of compressor vane control.
1.
The vanes are held from opening further, and the status line on the LID indicates the reason for th e ov er r ide.
2.
The vanes are c losed until c ondition decreases below the first step set point, and then the vanes are released to normal capacity control.
Whene v er the mot or c ur r ent dema nd limit set point is reached, it activ ates a capacit y override, again with a 2-step process. Exceeding 110% of the rated load amps for more than 30 secon ds will initiat e a s afety sh utdown.
The compressor high lift (surge prevention) set point will cause a capacity override as well. When t he s ur ge prevention set po int is reac hed, the cont r oller normally will only ho ld the guide vanes from opening. If s o equipped, th e hot gas bypass v alv e will open inst ead of ho lding the vanes .
Click here for Table 4 — Capacity Overrides
Page 84

High Discharge Temperature Cont r ol

If the discharge temperature increases above 160 F (71.1 C) (PSIO Software Version 09 and higher) or 180 F (82 C) (PSIO Software Version 08 or lower), the guide vanes ar e proportionally opened to increase gas flow through the compressor. If the leaving chilled water temperature is then brough t 5° F (2.8° C) below the c ontro l s et poin t t em perat ur e, the controls will br ing the machine into the recycle mode.

Oil Sump Temperature Control

The oil sump temperature control is regulated by the PIC which uses the oil heater relay when th e m ac hine is s hut down.
As part of the pre-start checks executed by the controls, oil sump temperature is compared against evaporator r efrigeran t t em perat ur e. If th e difference bet ween t hes e 2 temp er ature s is 50 F (27. 8 C) or les s , the s tart-u p will be de lay ed unt il the oil tempe r ature is 50 F (27.8 C) or more. On c e this te m per atur e is c onfirmed, the start- up cont inues.

PSIO Softwa r e Vers ion 08 and Lower

The oil heater relay is energiz ed when ev er the chi ller co m pr es s or is off , and the oil sump temperatu r e is les s than 140 F (60 C) or s um p temperatur e is less tha n the cooler ref r igerant temperatu r e plus 60° F (33.3° C) . The heat er is then turned off when the oil sump temp er ature is: 1) more than 160 F (71.1 C); or 2) the sump temperature is more than 145 F (62.8 C) and more than the cooler refrigerant temperature plus 65° F (36.1° C). The heater is always off duri ng s tart- up or when the c om pres s or is r unnin g.
Page 85

PSIO Software Version 09 and Highe r

The oil heater relay is energiz ed when ev er the chi ller co m pr es s or is off and the oil s um p temperatu r e is les s than 150 F (65.6 C) or the oil su m p temperature is les s than the coole r refr igerant temperatur e plus 70° F (39° C). The oil heater is tu rn ed off when the oil sump temperatu r e is either 1) mo r e than 160 F (71.1 C) ; or 2) the oil s um p tempe r ature is m or e than 155 F (68. 3 C) and mor e than the coole r re frigerant temperat ur e plus 75° F (41.6° C) . Th e oil heate r is always off dur ing st ar t-up or when the c om press or is r unnin g.
When a po wer fail ur e to the PS IO m odule has occur r ed for more than 3 hour s ( i.e., initial start-up), the oil sump is heated to 100° F (56° C) above the evaporator refrigerant temperature or 190 F (88 C) , whi c hev er is lower. O nc e this tem perat ur e is r eached, the oil pump will be energiz ed fo r 1 to 2 minutes or until the oil sump temperature c ools to below 145 F (63 C). The norma l heati ng algorithm is now followed once ramp loadin g has been complet ed.
After a 3- hour power failure, the oil temper ature mus t rise t o the hig her oil tem per atur e. The contr ols will delay the start of the com pr es s or unt il this t em perat ur e is m et.

Oil Cooler

The oil mu s t be cooled when the compresso r is ru nning. This is acc om plished thr ough a small, plat e- type he at exchanger located behind the oil pump. The hea t exc hang er us es liqui d condenser refrigerant as the cooling liquid. A refrigerant thermal expansion valve (TXV) regulates refrigerant flow to control oil temperature entering the bearings. There is always a flow
Page 86
regulates refrigerant flow to control oil temperature entering the bearings. There is always a flow of refrigerant bypassing the thermal expansion valve (TXV). The bulb for the expansion valve is strapped to the oil supply line leaving the heat exchanger and the valve is set to maintain 110 F (43 C).
Note: The expansion valve is not adjustable. Oil sump temperature may be at a lower tempera-
ture.

Remote Start/ St op Contr ol s

A remote device, such as a time clock which uses a set of contacts, may be used to start and stop th e m ac hine. However, the dev ice should no t be programmed to star t and sto p the machine in excess of 2 or 3 times every 12 hours. If more than 8 starts in 12 hours occur, then an Excessive Starts alarm is displayed, preventing the machine from starting. The operator must reset the alarm at the LID in order to override the starts counter and start the machine. If Autom atic Re s tart After a Power Fail ur e is not activ ate d when a pow er failur e oc c ur s , and the remot e c ontac t is c losed, the machine wi ll indicate an alarm bec ause of the loss of voltage.
The cont ac ts fo r Rem ote Star t are wired into the star ter at ter m inal st r ip TB5, term inals 8A and 8B. See the ce r tified drawin gs for furt her det ails on contact r atings . T he c ontac ts m us t be dry (no power).

Spare Safety Inputs

Norma lly c los ed (NC) digital inputs for additional f ield-supplied safeties ma y be wir ed to the
Page 87
spare pr otect iv e limit s input channel in place of the fac tory-ins talled jumper. (W ir e m ulti ple input s in s er ies.) The opening of any c ontac t will result in a s afety sh utdown and LID dis play. Refer to the cer tified drawings for s afety co ntact ra tings.
Anal og tempe r ature sensors ma y als o be add ed to the opt ions m odules, if installed. These may be programmed to cause an alert on the CCN network, but will not shut the machine down.

Spare Alarm C ont acts

Two spar e sets of alarm con tacts are provided wi thin the s tarter . The contact ra tings are provided in the cert ified dr awings. The contac ts are locat ed on terminal str ip TB6, terminals 5A and 5B, and terminals 5C and 5D.

Condenser Pump Control

The machine will moni tor the
CONDENSER PRESSURE
and may turn on t his pump if the
pressure becomes too high whenever the compressor is shut down.
PRESSURE OVERRIDE
Equipment Service1 LID table and has a default value (Table 4). If the
PRESSURE
is greater than or equal to the
ENTERING CONDENSER WATER TEMP (Temperature
condens er pum p will en er gize to try to decrease th e pr es s ure. The pump will turn off when the condenser pressure is less than the pressure override less 5 psi (34 kPa), or the
REFRIG (Refrigerant) TEMP
temperature.
is used to determine this pr ess ur e point. This va lue is found on the
CONDENSER PRESSURE OVERRIDE
) is less than 115 F (46 C), then the
is within 3° F (2° C) of the
ENTERING CONDENSER WATER
CONDENSER
CONDENSER
, and the
CONDENSER
Page 88

Condenser Freeze Pr evention

This control algorithm helps prevent condenser tube freeze-up by energizing the condenser pump relay. If the pump is controlled by the PIC, starting the pump will help prevent the water in the condenser from freezing. Condenser freeze prevention can occur whenever the machine is not running ex c ept when it is either ac tively in pu m pdown or in Pumpdown Lo c k out with the freeze prevention disabled (refer to Control Test table, Pumpdown/Terminate Lockout tables).
When the CONDENSER REFRIG TEMP is less than or equal to the CONDENSER FREEZE POINT , or the EN TERING CO NDENS E R WATER temperat ur e is les s than or eq ual to the CONDENSER FREEZE POINT, then the CONDENSER WATER PUMP shall be energized until the CONDENSER REFRIG TEMP is greater than the CONDENSER FREEZE POINT plus 5° F (2.7° C). An alarm will be generated if the machine is in PUMPDOWN mode and the pump is ener giz ed. An aler t will be generated if the mac hine is not in P UM P DOWN m ode and the pump is ener gized. If in re c y c le s hutdown, the m ode shall trans itio n to a non-recycle s hutd own.

Tower-Fan R el ay

Low condenser water temperature can cause the chiller to shut down on low refrigerant temperature. The tower fan relay, located in the starter, is controlled by the PIC to energize and deenergize as the pressure differential between cooler and condenser vessels changes in order to prevent low condenser water temperature and to maximize machine efficiency. The tower-fan
Page 89
relay ca n only ac c om plish t his if the r elay has been add ed to the cooling tower temperatur e contr oller. The is runn ing, flow is ver ified , an d the differen c e betwe en c ooler and cond ens er pres s ur e is mo r e than 45 ps id ( 310 kP ad) ( 30 psid [ 207 kPad] for HFC- 134a ) or enterin g c ondenser wat er temperatu r e is gr eater than 85 F (29 C) . The condens er pum p is off, flow is los t, the evapora tor refrigerant temperat ur e is less than the override tem perat ur e, or th e differential pr ess ur e is less than 40 psid (279 kPad) (28 psid [1 93 kPad] fo r HFC-134a) and enterin g c ondensing wa ter is les s th an 80 F (27 C).
IMPORTANT: A f ield-su ppli ed water t emper at ure con t rol system for co ndens er water should be installed. The system should maintain the leaving condenser water tempera­ture at a t emperat ure that is 20° F (11° C) above the leaving chi lled wat er temperat ure.
The tower-fan relay control is not a substitute for a condenser water temperature control. Wh en used with a Wat er Temperatur e Control system, t he tower f an relay control can be used to help prevent low condenser water temperatures.
TOWER FAN RELAY
CAUTI ON
!
is turned on wheneve r the
TOWER FAN RELAY
CAUTION
CONDENSER WATER PUMP
is deenergized when the
Page 90

Auto. Restart After Power Failur e

This opt ion may be enabl ed or disabled, and may be v iewed/ m odified in the Config table of Equipment Configuration. If enabled, the chiller will start up automatically after a single cycle dropout, low, high, or loss of voltage has occurred, and the power is within ±10% of normal. The 15- and 3- m inut e inhibi t t im er s ar e igno r ed during this type of star t-up.
When power is restored after the power failure, and if the compressor had been running, the oil pump will be energ iz ed for on e m inute pr ior to the evaporat or pump energizing. A uto restart will th en c onti nue like a normal s tart- up.
If pow er to the PSIO mo dule has been off for more than 3 hours, t he P IC will ra is e the oil temperatu r e 100° F (56° C) above the ev aporat or temperatur e. Refrigerant normally migr ates into t he oil whe n the oil heater is left of f f or ex tended periods of tim e. The PIC operates the oil pump for 1 to 2 minutes to ensure that the oil is free of excess refrigerant. Once this algorithm is completed, the REST A RT of the chille r will cont inue.

Water/Br ine Reset

Three types of chilled water or brine reset are available and can be viewed or modified on the Equipment Configuration table Config selection.
The LID default screen status message indicates when the chilled water reset is active. The Control Point temperat ur e on the Status0 1 table indicates the m ac hine’s curr ent reset temperatu r e.
Page 91
To acti v ate a reset type, inpu t all configurat ion inf or m ation for that reset t y pe in the Config table. Then input the reset type number in the SELECT/ENABLE RESET TYPE input line.
1. Reset Ty p e 1 rese t based on a 4 to 20 mA in put sign al. This type permits up to ±30° F (±16° C) of automatic reset to the chilled water or brine temperature set point, based on the input from a 4 to 20 mA s ignal. This signal is hardwi r ed into the numbe r one 8- input module.
If the 4- 20 mA si gnal is externally po wer ed fro m the 8-inp ut module, the si gnal is wir ed to terminals J1-5(+) and J1- 6(–). If the signal is to be internally powered by the 8-input module (for ex am ple, when using variable re s is tance ) , t he s ignal is wired t o J 1- 7( + ) and J1-6( –). The PIC must now be configured on the Service2 table to ensure that the appropriate power sour c e is ident ified.
2. Reset Ty p e 2 reset based on a remote temperature sensor input. This type permits ±30° F (±16° C) of auto m atic res et to the se t point based on a t em perat ur e s ensor wir ed to the numbe r one 8­input m odule (s ee wiring diagr am s or c er tified drawings).
The t em perat ur e s ensor m us t be wired to terminal J1 - 19 and J1- 20. To configur e Reset Type 2, enter the temperat ur e of the rem ote se ns or at the point where no temperature reset will occur. Next, enter the temperature at which the full amount of
(Requir es opti onal 8-input m odule) — A utomatic c hilled water temperatur e
(Requir es opti onal 8-input m odule) — A utomatic c hilled water temperatur e
reset will occur. The n, enter the maxi mum amount of re set required t o oper ate the machine.
Page 92
Reset Type 2 ca n now be act iv ated.
3. Reset Ty p e 3 diff er ence. This typ e of reset will add ±30 ° F (±16° C) bas ed on the temperatur e difference betw een ent er ing and leav ing chille d water tem perature. This is th e only type of reset available without the ne ed of the num ber one 8-inp ut module. No wiring is r equired for this type as it alre ady us es the co oler wat er s ens ors .
To configur e Reset Type 3, enter the ch illed wa ter temp er ature diffe r enc e (the differ enc e betw een ent er ing and leav ing chille d water) at which no tempe r ature reset occurs. T his chi lled water tempe r ature difference is usually the full design load tempe r ature difference. The difference in ch illed water temperat ur e at whic h the full amount of res et will oc c ur is now ent er ed on t he next in put line. Next , t he am ount of reset is enter ed. Res et Type 3 can now be activated.
— Automatic chilled water temperature reset based on cooler temperature
Page 93

Demand Limit Control, Option — (Requires Optiona l 8-Input Module)

The demand limit may be externally controlled with a 4 to 20 mA signal from an energy management system (EMS). The option is set up on the Config table. When enabled, the contr ol is set f or 100% demand wi th 4 mA and an operator c onfi gur ed minimum demand set point at 20 mA.
The Demand Reset input from an energy management system is hardwired into the number one, 8-input module. The signal may be internally powered by the module or externally powered. If the signal is externally powered, the signal is wired to terminals J1-1(+) and J1-2(–). If the signal is inter nally powered, the signal is wir ed to term inals J1- 3(+ ) and J 1- 2(–). When enabled, the contr ol is s et for 100% demand with 4 m A and an ope r ator configur ed minimum demand s et poi nt at 20 mA.

Surge Prevention Algor ithm

This is an operator configurable feature which can determine if lift conditions are too high for the compr ess or and then take corr ec tive action. Lift is defined as th e differ ence bet ween the pressure at the impel ler ey e and t he im pell er dis c harge. The max imum lift tha t a parti c ular impeller wheel can perfor m va r ies with the gas flow ac r oss the impeller, and the si z e of the wheel.
The alg or ithm f ir s t determ ines if cor r ecti v e ac tion is nec es s ary . T his is done by checking 2 sets of operator configured data points, which are the MINIMUM and the MAXIMUM Load
Page 94
Points, (T1/P1;T2/P2). These points have default settings for each type of refrigerant, HCFC-22 or HFC-134a, as defined on the Service1 table, or on Table 4. These settings and the algorithm function are graphically displayed in Figu re 2 0. The two sets of load points on this graph (default settings are shown) describe a line which the algorithm uses to determine the maximum lift of the compressor. Whenever the actual differential pressure between the cooler and condenser, and the temperature differenc e bet ween the enteri ng and leaving ch illed wa ter are above th e line on the graph (as defined by the MINIMUM and MAXIMUM Load Points) the algorithm will go into a co r r ec tive action m ode. If the ac tua l v alues are below the line , t he algorithm takes no action. Modification of the default set points of the MINIMUM and MAXIMUM load points is described in Figu r e 21.
Corre c tive action can be taken by making one of 2 c hoices . If a hot gas by pass line is present, and the hot gas is configured on the Service1 table, then the hot gas bypass valve can be energized. If a hot gas bypass if not present, then the action taken is to hold the guide vanes. See Tabl e 4, Capac ity Overr ides. B oth of the s e c or r ec tive actions will reduce t he lift exper ienced by the compress or and hel p to prevent a surge cond ition. Sur ge is a c ondition when the lift becomes so high that the gas flow across the impeller reverses. This condition can eventuall y ca us e m ac hine dam age. The surge pr event ion alg or ithm is intended to notify the operator th at machine oper ating co nditions ar e marginal, and to take ac tio n to help prev ent machine dam age such as lowering enter ing conden s er water tem perat ur e.
Page 95

Surge Protection

Surging of th e c om pr essor c an be det er m ined by t he P IC through operator co nfigur ed settings. S ur ge will ca us e am perage fluc tuations of the compres s or motor. The P IC moni tors these amperage swings, and if the swing is greater than the configurable setting in one second, then one surge count has occurred. The SURGE DELTA PERCENT AMPS setting is displayed and configured on the Service1 screen. It has a default setting of 25% amps, SURGE PROTECTIO N COUNTS c an be monitore d on the Mai nt03 table.
A surge prote c tion shu tdown of t he m ac hine will occur when ev er the surge prot ec tion counter reaches 12 counts within an operator specified time, known as the SURGE TIME PERIOD. The SURGE TIME PERIOD is displayed and configured on the Service1 screen. It has a default of 5 minutes .
Click here fo r Figure 20 — 19XL Hot Gas Bypass/Surge Prevention
Click here for Figure 21 — 19XL with Default Metric Settings
Page 96

Lead/Lag Control

Note:
chiller in a 2-chiller water system. Refer to Figure 16 and Figure 17 for menu, table, and screen selec tion in format ion. On m ac hines t hat have PSI O software wit h Lead/Lag capabil ity, it is possible to ut ilize t he P IC cont r ols to pe r form the lead/l ag function on 2 mac hine s . A third machine can be added to the lead/lag system as a standby chiller to start up in case the lead or lag chiller in the system has shut down during an alarm condition and additional cooling is required.
Note:
Lead/ lag control is only availab le on machines with PSI O Software Ver s ion 09 or higher.
Lead/lag is a control system process that automatically starts and stops a lag or second
Lead/lag configuration is viewed and edited under Lead/Lag in the Equipment Configura­tion t able (located in the Serv ice menu). Le ad/la g s tatus dur ing machine operation is viewed in the MAINT04 table in the Control Algorithm Status table. See Table 2.
Lead/Lag System Requirements:
all mac hines m us t have PSIO software ca pable of per forming the lead/lag fu nc tion
water pumps M US T be ener giz ed fro m the PIC controls
water flows sh ould be consta nt
CCN Time Schedules f or all mac hines mus t be identical
Page 97
Operat ion Fe atures:
2 chiller le ad/lag
addition of a t hir d chiller for bac k up
manu al r otation of lead chiller
load balancing if c onfig ur ed
staggered restart of the chillers after a power failure
chillers may be pipe d in parallel or in series c hilled water flow

Common Point Sensor Installation

Lead/ lag operation does not r equire a c om m on chilled water poin t sensor. Common poin t sensors can be added to the 8-input option module, if desired. Refer to the certified drawings for termination of sensor leads.
Note:
senso r is not used, the leav ing chilled wa ter sensor of the upstream chiller must be moved into the lea v ing chilled wa ter pipe of t he downstrea m ch iller.
If the common point sensor option is chosen on a chilled water system, both machines should have their ow n 8- input option m odule an d c om m on poin t sensor ins talled. Each machine will us e its ow n c om m on point sens or for cont r ol, whe n th at machine is desig­nated as the lead chiller. The PIC cannot read the value of common point sensors installed on other machines in the chilled water system.
When installing chillers in s er ies, a comm on point se ns or s hould be used. If a common poin t
If ret ur n c hille d water control is re quired on chill er s piped in series, the com m on point return
Page 98
chil led water s ens or should be installed. If this sens or is not ins talled, the return chilled water senso r of t he downstrea m ch iller mus t be relocated to the r eturn chilled water pipe of th e upstream machine.
To properly c ontrol the common s upply point temperature se ns or when chille r s ar e piped in parallel, the water flow thr ough the s hutdown chillers m us t be isol ated so t hat no water bypass around the operating chiller occurs. The common point sensor option must not be used if water bypas s ar ound th e operat ing chiller is oc c ur r ing.

Machi ne Communication Wiri ng

Refer to the machine’s Installation Instructions, Carrier Comfort Network Interface section for inform ation on machine com m unicat ion wiring.

Lead/Lag Operation

The PIC co ntrol provides the ability t o operat e 2 c hillers in the LE A D/LAG mo de. It also provides the additional ability to star t a designated standby c hiller when either the lead or lag chil ler is faulted and ca pac ity requirements ar e not met . The lead/lag option operat es in CCN mode only . If any other ch iller c onfigur ed for le ad/la g is s et to the LOCA L or OFF modes, it will be unavailable for lead/ lag operation.
Note:
Lead/lag configuration is viewed and edited in Lead/Lag, under the Equipment Configu­ration table of the Service menu. Lead/lag status during machine operation is viewed in the MAINT04 table in the Control Algorit hm S tatus table.
Page 99
Lead/Lag Chiller Configuration and Operation
The conf igured lead chiller is identified when the LEAD/LAG SE LE CT valu e for tha t chiller is configured to the value of ‘‘1.’’ The configured lag chiller is identified when the LEAD/LAG SELECT for that chiller is co nfigur ed to the value of ‘‘2.’’ The standby c hiller is configur ed to a value of ‘‘3.’’ A value of ‘‘0 ’’ disables the lead/ lag in that chill er .
To configure the LAG ADDRESS value on the LEAD/LAG Configuration table, always use the address of the other chiller on the system for this value. Using this address will make it easier to rotate the lead and lag machines.
If the address assignments placed into the LAG ADDRESS and STANDBY ADDRESS values conflict, the lead/lag will be disabled and an alert (!) message will occur. For example, if the LAG ADDRESS matches the lead machine’s address, the lead/lag will be disabled and an alert (!) message will occur. The lead/lag maintenance screen (MAINT04) will display the message ‘INV A LID CONF IG’ in the LEAD/ LA G CONFIGUR A TI ON and CURRE NT MO DE field s .
The lea d c hiller r es pond s to normal start/s top con trols s uc h as oc c upan c y schedule, forc ed start/ s top, and remote sta r t contac t inputs. After c om pleting start up and ram p loadi ng, the PIC evaluates the need for additional capacity. If additional capacity is needed, the PIC initiates the start up of the chiller configured at the LAG ADDRESS. If the lag chiller is faulted (in alarm) or is in the OFF or LOCAL modes, then the chiller at the STANDBY ADDRESS (if configured) is
Page 100
requested to start. After the second chiller is started and is running, the lead chiller shall monitor conditions and evaluate whether the capacity has reduced enough for the lead chiller to sustain the system alone. I f the capacity is re duced enough for the lead chiller to sustai n the CONTROL POINT te m per atu r es alone, then the operat ing lag ch iller is s toppe d.
If the lead chiller is stopp ed in CCN mode for any re as on other than an alar m ( *) c ondition, then the lag and standby c hille r s ar e s toppe d. If the co nfigur ed lead chille r stops for and ala r m condition, then the configured lag chiller takes the lead chiller’s place as the lead chiller and the standby chiller ser v es as the la g c hiller.
If the config ur ed lead ch iller does not co m plete the start- up bef or e the PRESTART FAULT TIMER (user configured value) elapses, then the lag chiller shall be started and the lead chiller will s hut down. The lead chiller then m onitor s the sta r t request from the ac ting le ad c hille r to start. The PRESTART FAULT TIMER is initiated at the time of a start request. The PRESTART FAULT TIMER’s function is to provide a timeout in the event that the r e is a pr es tart alert condition pr ev enting the machine from s tarting in a ti m ely m anner. The timer is c onfig ur ed under Lead/ Lag, found in the E quipment Conf iguration table of t he S er v ice m enu.
If the lag chiller doe s not achie v e s tart-up before the PR E S TART FAU LT TIMER elapses , then the lag chiller shall be stopped and the s tand by c hiller will be re quested to start, if configured and ready.
Loading...