Carrier P, 52CE Series, 52CQ Series, 52PE Series, 52PQ Series User Manual

...
52C,P
52C,P
SERIES
SERIES
SERVICE TECHNICIAN GUIDE
PACKAGED TERMINAL AIR CONDITIONERS
AND HEAT PUMPS
CONTENTS
INTRODUCTION
SUMMARY OF DANGERS, WARNINGS,
AND CAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
UNIT DISASSEMBLY
TOOLS NEEDED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REMOVE FRONT P ANEL . . . . . . . . . . . . . . . . . . . . . . . 3
DISCONNECT POWER FOR
CORD-CONNECTED UNIT . . . . . . . . . . . . . . . . . . . . . 3
DISCONNECT POWER FOR PERMANE N TLY
CONNECTED (HARDWIRED) UNITS . . . . . . . . . . . . 3
OPEN THE CONTROL BOX. . . . . . . . . . . . . . . . . . . . . 4
REMOVE THE UNIT FROM THE W ALL SLEEVE . . 4
ACCESSING UNIT COMPONENTS
ACCESSING INDOOR-AIR SECTION COMPONENTS (UNITS WITH LATERAL
DUCT ACCESSORY). . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ACCESSING INDOOR-AIR SECTION COMPONENTS (UNI TS WIT HOU T L ATERAL
DUCT ACCESSORY). . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ACCESSING OUTDOOR-AIR SECTION
COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GENERAL CLEANING
CLEANING AND SAFETY . . . . . . . . . . . . . . . . . . . . . . 9
TOOLS NEEDED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MONTHLY CLEANING. . . . . . . . . . . . . . . . . . . . . . . . 10
SEASONAL CLEANING . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,3
. . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
. . . . . . . . . . . . . .5-8
. . . . . . . . . . . . . . . . . . . . . . . . .9-12
COMPRESSOR
COMPRESSOR TROUBLESHOOTING . . . . . . . . . . .14
BASIC HERMETIC COMPRESSOR
ELECTRICAL MEASUREMENTS. . . . . . . . . . . . . . . .14
COMPRESSOR REPLACEMENT . . . . . . . . . . . . . . . .15
HEATERS
COMMON CAUSES OF HEATER FAILURE. . . . . . .18
HEATER REMOVAL . . . . . . . . . . . . . . . . . . . . . . . . . . .18
OPERATING CONTROLS
DESCRIPTION OF SELECTOR
SWITCH SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . .22
NON-USER ADJUSTABLE CONTROLS . . . . . . . . . .22
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . .23
COMPONENT OPERATION AND
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . .23
ELECTRICAL COMPONENTS REMOVAL
AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . .26
FAN MOTOR
FAN MOTOR TROUBLESHOOTING. . . . . . . . . . . . .28
BASIC FAN MOTOR ELECTRICAL TESTS. . . . . . . . 28
FAN MOTOR REPLACEMENT. . . . . . . . . . . . . . . . . .30
WIRING DIAGRAMS MOST FREQUENT PTAC SERVICE
QUESTIONS ACCESSORIES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,19
. . . . . . . . . . . . . . . . . . . . . 20-27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-30
. . . . . . . . . . . . . . . . . . . . . . . . 31-35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
PTAC Customer Support Center
1•800•894•6449
Page
52C,P
CANADIAN INSTALLATION
SERIAL 3701X11520 DATE OF MFG. 09/12/2001 VOLT RANGE 187-253 VOLTS 230/208 PH 1
MODEL 52PQA312301AA
HZ
60
MIN CKT AMPACITY 19.3 R-22 OZ 34
DESIGN PSIG 350 HIGH SIDE, 150 LOW SIDE
COOLING
HEATING
BTU/HR 12,100/12,000 AMPS 4.8/5.3
WATTS 1100/1100 EER 11.0/10.9
MOTOR
FAN
COMP
HP
FLA
RLA LRA
6.1 29
0.75 1/8
BTU/HR 10,800/10,700 AMPS 15.6/14.5 WATTS 3570/2997 COP 3.2/3.2
HEATER
BTU/HR
AMPS 14.8/13.7 WATTS 3400/2850 WATER
STEAM
20
20
20
USE
TIME DELAY FUSE
OR HACR TYPE
CIRCUIT BREAKER
AMP
AMP AMP
MAX FUSE
MAX BREAKER
SERIES
INTRODUCTION
The focus of this manual is to provide basic information on service procedures, safety, troubleshooting, clean­ing, and component replacement for service techni­cians. It is intended for use only by HVAC service
technicians who have successfully completed instruction and received Type I Certification from the U.S. Environmental Protection Agency.
The instructions in this manual are general in nature and are not to be substituted for installation and ser­vice instructions shipped with the unit. No attempt to install, ope rate, adju st, re pair , or di smant le any equi p­ment should be made until the manufacturer’s i nstruc­tions are read and thoroughly understood by the service technician. Even equipment that seems famil­iar may have specific model diffe rences from year to year. Always review manufacturer’s instructions.
Model 52C,P packaged terminal air conditioner (PTAC) and heat pump units are self-contained for installation through the wall for individual room heat­ing and cooling. The Model 52C,P polymer and metal sleeves are permanently fastened to the wall; the unit chassis slides out of the sleeve to allow the service technician easy access. Many accessories are offered to complement the unit’s performance and comfort control.
Before beginning any service procedu res, it is impor­tant to check the unit model number. See Figure 1 and
2. Units that seem similar may have subtle differences that could affect service procedures. The following units are covered in this manual:
52CE — 60 Hz cooling with electric heat units 52CQ — 60 Hz cooling with electric heat and heat
52PE — 60 Hz cooling with electric heat units 52PQ — 60 Hz cooling with electric heat and heat
52PC — 60 Hz cooling only units Knowing which model is being serviced will help deter-
mine if the unit is performing at optimum levels. The model number is located on the data informatio n plate beneath the front panel of the unit. See Figure 1. The data information plate also lis ts voltage ranges and other important electric al information about the unit.
SUMMARY OF DANGERS, WARNINGS, AND CAUTIONS
The terms DANGER, WARNING, and CAUTION have specific meanings that identify the degree of hazard. Typically in the HVAC industry, these specific mean­ings are:
There is an immediate hazard which WILL result in severe personal injury or death.
pump units
pump units
Hazards or unsafe practices which COULD result in severe personal injury or death.
Potential hazards or unsafe practices which COULD result in minor personal injury or equip­ment damage.
FIGURE 1 — SAMPLE DATA INFORMATION PLATE
2
52 PQ A 3 12 3 0 1 AA
Series Designation
PTAC (Packaged Terminal Air Conditioner)
CE – Cooling with Electric Heat CQ – Heat Pump with Electric Heat PC – Cooling Only PE – Cooling with Electric Heat PQ – Heat Pump with Electric Heat
Latest Revision
A – Z
Electric Heater Size
0 – No Heating (Cooling Only Model) 2 – 2.3 kW 3 – 3.4 kW 5 – 5.0 kW
Cooling Capacity (nominal)
07 – 7,000 Btuh 09 – 9,000 Btuh 12 – 12,000 Btuh 15 – 15,000 Btuh
FIGURE 2 — MODEL NUMBER NOMENCLATURE
UNIT DISASSEMBLY
This section includes common procedures for disas­sembly and re-assembly of u nit.
IMPORTANT: Follow manufacturer’s instruc­tions when disassembling and re-assembling a unit for cleaning, maintenance, or part replace­ment. When disassembling wiring, it is strongly recommended that numbered stickers be attached to identify leads and terminals to aid in the re-assembly process. Always review safety procedures prior to the start of a job.
Prior to servicing electrical equipment, discon­nect all power to avoid electric shock! Tag all dis­connects. Never alter cord or plug and do not use extension cords.
TOOLS NEEDED
The following field-supplied items are recommended for general disassembly of the unit:
• Flat head screw driver
5
/16-in. nut driver
• Safety glasses
• Needle nose pliers
Chassis Options
Blank or AA – Standard
CP – Corrosion Protection RC – Wall Thermostat Control RP – Wall Thermostat Control with
Corrosion Protection
Packaging
1 – Domestic
Non-Performance
Changes 0-9
Electrical Data
3 – 230/208-v, 60 Hz 4 – 265-v, 60 Hz
See Figure 3. If a lateral duct accessory is installed, the plenum must be removed before removing the front panel. Refer to Remove Lateral Duct Extension section for removal instructions.
1. Grasp the front firmly ne ar bottom of both sides.
2. Pull the panel forward then upward to release magnetic latches and partition hooks . See Figure 4.
DISCONNECT POWER FOR CORD-CONNECTED UNIT
1. Turn selector switch to OFF position.
2. Open the disconne ct swit c h a t ma in po wer su pply. Use proper Lockout and Tag procedures.
3. Unplug the unit service cord.
DISCONNECT POWER FOR PERMANENTLY CONNECTED (HARDWIRED) UNITS
1. Turn selector switch to OFF position.
2. Open the disconne ct swit c h a t ma in po wer su pply. Use proper Lockout and Tag procedures.
3. Remove screw from access cover and remove access cover.
4. Pull out the plug assembly and disconnect. See Figure 5.
REMOVE FRONT PANEL
NOTE: Before removing front panel, remove 2 locking screws (if installed) located behind the filter handles.
3
52C,P
SERIES
OPEN THE CONTROL BOX
The control box is factory wired. To open the box, remove the 2 screws on the top of the control box and lower the front hinged panel. See Figure 6.
REMOVE THE UNIT FROM THE WALL SLEEVE
1. Remove the four moun tin g scr e ws tha t secu re th e PTAC unit to the wall sleeve (2 screws per side). See Figure 7.
2. Grasp the sides of the unit and slide it from the sleeve.
NOTE: The mounting screws ma y be in a differen t location depending on brand of wall sleeve attached.
REMOVABLE FILTER
LOCATION OF REMOVED FILTER
LOCKING SCREW (NOTE: 2nd LOCKING SCREW IS LOCATED BEHIND 2nd FILTER)
FIGURE 3 — LOCATION OF LOCKING SCREWS
BEHIND FILTERS
FIGURE 4 — REMOVING FRONT PANEL
Replacement Package Terminal Air Conditioner, CLASSIFIED BY UNDERWRITERS LABORATO­RIES INC., AS TO ELECTRIC SHOCK, FIRE AND CASUALTY HAZARDS ONLY. FOR FIELD INSTAL­LATION WITH EXISTING WALL SLEEVES, OUT­DOOR, LOUVERS, AND INDOOR PANELS AS SPECIFIED ON THE PRODUCT.
The chassis weighs between 110 and 150 lbs. Take proper safety precautions to avoid personal injury when lifting and moving the chassi s.
The unit basepan may have water in it. Tilt the unit back slightly whe n removing it fro m th e sl e eve to drain some of the water into the sleeve.
CONDUIT
ACCESS PANEL
MOLEX PLUGS
FIGURE 5 — PLUG ASSEMBLY ON
HARDWIRE UNITS
4
POWER
GE WALL SLEEVE HOLES
AMANA, TRANE (SLOTTED HOLES) WALL SLEEVE HOLES
VARIOUS ATTACHMENT
HOLE LOCATIONS
CARRIER, BRYANT WALL SLEEVE HOLES
CORD ACCESS COVER
POWER CORD
FIGURE 6 — CONTROL BOX COVER
CONTROL BOX SCREWS
FIGURE 7 — PTAC UNIT TO WALL
SLEEVE MOUNTING SCREWS
ACCESSING INDOOR-AIR SECTION COMPONENTS (UNITS WITH LA TERAL DUCT ACCESSORY)
REMOVE LATERAL DUCT EXTENSION
ACCESSORY ONLY ON UNITS EQUIPPED WITH THE LATERAL DUCT
1. Remove the 2 top screws that secure the lateral
2. Locate and remove the 2 bottom bracket screws
3. Carefully lift the plenum up and away from front
ACCESSING INDOOR-AIR SECTION COMPONENTS (UNITS WITHOUT LATERAL DUCT ACCESSORY)
REMOVE THE DISCHARGE DECK ASSEMBLY
1. Remove the front panel. Re fer to Remove Front
2. Remove discharge screen screw using a
ACCESSING UNIT COMPONENTS
duct plenum to the top of the lateral duct exten­sion. See Figure 8.
(located opposite extension duct) that secure the lateral duct plenum to the brac ket flange. See Figure 8.
panel and duct extension.
Panel section and Figure 4. driver. See Figure 9.
5
/16-in. nut
3. Remove th e disch arge dec k asse mbly scre ws usin g
5
a
/16-in. nut driver. See Figure 9.
4. Gently pull the deck/grille up and away f rom the unit.
5. Reassemble by reversing steps above.
ACCESSING THE HEATER ASSEMBLY
— Once the discharge deck assembly is removed, the Heater Assembly should now be accessible. See Figure 10.
1. Using pliers, carefully remove all wires connected to the heater assembl y. Label ea ch wire for ea se of re-assembly.
2. Gently pull the heater assembly up and away from scroll. See Figure 11.
3. Reassemble by reversing steps above.
ACCESSING OUTDOOR-AIR SECTION COMPONENTS
REMOVE THE GUSSETS (See Figure 12)
1. Remove the 2 screws on each side that secure the gussets to the partition.
2. Remove the 2 screws that secure the gussets to the plastic condenser orifice and remove the gussets.
5
52C,P
SERIES
END CAP
BRACKET SCREWS
PLENUM LATERAL DUCT
LEFT BRACKET
TOP SCREWS (2)
EXTENSION
RIGHT BRACKET
FIGURE 8 — PTAC UNIT WITH LATERAL
DUCT ACCESSORY INSTALLED
ATTACHMENT SCREWS
WALL
BRACKET SCREWS
HEATER ASSEMBLY
FIGURE 10 — ACCESSING HEATER
HEATER PLATE ASSEMBLY
PLATE ASSEMBLY
DISCHARGE SCREEN
DISCHARGE DECK
FIGURE 9 — LOCATION OF ATTACHMENT
SCREWS ON DISCHARGE DECK OF UNIT
DETACH THE CONDENSER ORIFICE FROM THE
CONDENSER COIL
1. Remove top half of condenser orifice. a. Unscrew the top half of the condens er orifi ce b y
removing the 4 captive screws. See Figure 13.
b. Using a flat head screwdriver, gently pry the
top half of the orifice from the tube sheets. See Figure 14.
c. Remove top of condenser orifice. See Figure 15.
2. Remove bottom half of condenser orifice. a. Using a flat head screwdriver, gently pry the
bottom half of the orifice from the tube sheets. See Figure 14.
b. Remove 2 outdoor coil tube sheet screws using a
Phillips head screwdriver. See Figure 16.
c. Carefully lift condenser up and away from con-
denser fan. Rest con d e nse r on bas epan . Se e Figure 17.
FIGURE 11 — REMOVAL OF HEATER
PLATE ASSEMBLY
d. Using Needle Nose Pliers remove co ndenser fan
hub clamp. See Figure 18. e. Pull condenser fan off fan motor shaft. f. Remove bottom half of condenser orifice.
3. Reassemble by reversing steps above.
REMOVE THE AIR DISCHARGE GRILLE
1. Remove the front panel from the unit, reference Remove Front Panel section.
2. Flip the panel front panel over to the backside. Remove the 2 screws on each end of the air dis­charge grille and remove grille. See Figure 19. The grille can be positioned to direct the discharge air up or out by simply rotating the grille 180 degrees.
6
GUSSET
GUSSET SCREWS
CONDENSER ORIFICE (PLASTIC)
PARTITION GUSSET
GUSSET SCREWS
FIGURE 12 — GUSS ET RE M O VAL
CONDENSER ORIFICE
CAPTIVE SCREWS (2)
CAPTIVE SCREWS (2)
FIGURE 13 — LOCATION OF CAPTIVE SCREWS
ON CONDENSER ORIFICE
FIGURE 14 — PRYING CONDENSER ORIFICE
AWAY FROM TUBE SHEET
FIGURE 15 — REMOVING TOP OF
CONDENSER ORIFICE
7
52C,P
SERIES
OUTDOOR COIL TUBE SHEET SCREWS
FIGURE 16 — LOCATION OF OUTDOOR
COIL TUBE SHEET SCREWS
CONDENSER FAN
HUB CLAMP
FIGURE 18 — REMOVING CONDENSER
FAN HUB CLAMP
CONTROL DOOR HINGE PINS
FRONT PANEL (BACK VIEW)
SCREW SCREW
DISCHARGE GRILLE
FIGURE 19 — LOCATION OF SCREWS ON
DISCHARGE GRILLE
FIGURE 17 — REMOVING OUTDOOR COIL
FROM CONDENSER FAN
8
GENERAL CLEANING
Maintaining proper performance of 52C,P systems requires conscientious cleaning and care of compo­nents. See Figure 20. Specific components require periodic cleaning and/or replacement, including the following:
COMPONENT CLEANING SCHEDULE
Indoor Air Filter
Vent Air Filter
Indoor Coil Indoor Fan
Outdoor Coil
Monthly
Monthly Seasonally Seasonally Seasonally
CLEANING AND SAFETY
Before starting to clean a unit, read the instructions thoroughly and gather the necessary tools for the job. Review all safety information on unit and in literature.
Before cleaning, servicing, performing maintenance, or removing the chassis from the wall sleeve, discon­nect all power to the unit to avoid the possibility of electrical shock and personal injury. Only trained and qualified service personnel should perform installation and service procedures on these units. Untrained personnel may perform basic mainte­nance tasks such as cleaning and replacing filters. Refer to General Disassembly section of this ma nual for proper procedures to disconnect power to 52C,P units.
Consider the following safety issues before beginning:
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as safety glasses and work gloves, should be used.
• The floor around the work area shoul d be clea n and free of debris.
• The 52C,P unit weighs up to 150 pounds. Use a lift­ing device or ask for assistance if the unit must be moved.
• Make sure tools are the correct tools for the job, and that they are working properly and in good condi­tion.
FRONT PANEL (STANDARD)
CHASSIS (STANDARD)
FIGURE 20 — STANDARD 52C UNIT
EXTERIOR GRILLE (ACCESSORY)
WALL SLEEVE (ACCESSORY)
9
52C,P
SERIES
TOOLS NEEDED
The following list includes the recommended tools, devices, and cleaning solutions for use in cleaning the 52C,P unit and components.
Vacuum Cleaner with Crevice Tool Attachment,
Lifting Device (or another person for assistance)
Trigger Spray Extension Tube (Part No. P9029000)
Vent Air Filter Replacement (Part No. 52CQ500144)
Condenser Coil Cleaning Solution (Part No. P9020501)
Evaporator Coil Cleaning Solution (Part No. P90221001)
3% Solution of Hydrogen Peroxide in Spray Bottle
MONTHLY CLEANING
AIR FILTERS
should be cleaned once per month. F ilt ers that are not cleaned become clogged and will restrict airflow. This may lead to major component damage. If a filter becomes torn, has holes, or other damage, replace it with a new one. Replacement filters are available through Carrier Finished Goods and Carrier Replace­ment Component Division.
CLEANING THE INDOOR AIR FILTER
filters are located in the unit’s front panel. To remove each filter simply grasp each filter handle with both hands and gently pull the filter up and away from the unit. See Figure 21.
or Soft Plastic Bristle Brush
Mild Household Detergent Phillips Head Screwdriver
5
/16-in. Nut Driver
Flat Head Screw Driver
Needle Nose Pliers, 90° Bend
Tank Sprayer (Part No. P9021001) or
Compressed Air Tank
Clean Water Supply
Indoor Air Filter Replacement
(Part No. AIR-FILTER-10PAK)
10-in. by 29-in. Piece of Clean Cardboard
Clean Cloth
Safety Glasses
Protective Gloves
— The indoor and vent air filters
Two air
REPLACING THE INDOOR AIR FILTER
Remove the indoor air filter as detailed in Cleaning the Indoor Air Filter. If damaged, use a filter replace­ment with the Carrier Part No. AIR-FILTER-10PK, available through Carrier Finished Goods and Carrier Replacement Component Division.
NOTE: Both filters are completely interchangeable.
CLEANING THE OUTDOOR AIR VENT FILTER
1. Remove the unit chassis from wall sleeve as described in the General Disassembly section of this manual. Refer to Remove the Unit from the Wall Sleeve section.
2. Swing open vent door. The filter is located directly behind the vent door. See Figure 22.
3. Once the filter is accessed, it may be cleaned using either a vacuum cleaner, or a soft bristle brush and a small amount of mild dish detergent. If detergent is used, remove detergent residue with a gentle, clean water stream. Allow the filter to air dry.
REPLACING THE OUTDOOR AIR VENT FIL TER —
If vent filter requires replacement:
1. Open vent door to access vent filter.
2. Remove vent door from hinges.
3. Using needle nose pliers, remove vent cable from vent door.
4. Using a small flat head screwdriver, pry the filter from the partition.
5. Replace vent filter using Carrier Part No. 52CQ500144.
6. Reverse Steps 1-4 to re attach vent door and cable.
CHASSIS
Occasional cleaning of the e xterior surfaces of the PTAC unit optimizes the unit’s appearance and removes particles that may enter the air system. See Figure 23. Mild detergents clean and reduce electro­static charges on the plastic components of the PTAC unit.
Use a clean cloth or brush to gently wipe exterior s ur­faces. Be careful not to push dirt or other fibers into the unit’s interior components. Accessible wall sleeve surfaces should also be wiped clean.
10
SEASONAL CLEANING
VENT DOOR
OUTDOOR AIR FILTER
The indoor and outdoor coils should be cleaned at least once during every season. Refer to ACCESSING UNIT COMPONENTS section to prepare unit.
CLEANING THE INDOOR AND OUTDOOR
COILS
Coil fins are sharp and may cut hands. Wear heavy protective gloves when cleaning coils.
Use only cleaning solutions that meet local codes.
1. Use a vacuum cleaner or soft bristle brush to remove surface fibers and dirt from the interior surface of evaporator coil and both surfaces of con­denser coil. See Figure 24. It is important to apply the tool in the same direction of the fins, not against them. Applying the tool against the fins may cause damage (fin edges may bend over).
2. With a tank sprayer or a trigger spray extension tube, spray coil cleaning solution evenly across the coils, making sure coils are thoroughly saturated. See Figure 25. Refer to instructions on the clean­ing solution containers for best results.
use a high-pressure sprayer.
3. Rinse the coils thoroughly with low-velocity, clean warm water (less than 200 F).
4. Repeat steps 2 and 3 for each coil surface.
5. Drain water and cleaning solution that may have collected in the basepan during the cleaning pro­cess by carefully tilting the chassis. This allows excess water to flow out of the overflow notches.
Do not
Do not set unit on end to drain water from basepan, or at any other time. Oil will drain from the com­pressor sump, which could cause compressor failure.
6. Thoroughly cl ean the b asepan a nd drain p assages by rinsing with clean water. Be sure all debris is removed from the drain valve. See Figure 26.
7. Thoroughly cle an outdoor fan assembly and all other mechanical components located in outdoor coil area. Be sure to remove all dirt and debris.
8. Clean wall sleeve.
CLEANING THE INDOOR FAN AND FAN
SCROLL —
Dried debris and build-up on the blower wheel and fan scroll can reduce the efficiency of the unit.
ACCESS AND CLEAN INDOOR FAN AND
1.
FAN SCROLL
a. Reach behind the indoor coil and vacuum any
loose debris from the condensat e drai n pan, fan and other areas accessible to the fan scroll, being careful to avoid damage to the coil fins.
b. Use mild detergent and a damp cl oth to remov e
stubborn debris from surfaces around scroll and fan blades.
CLEAN HEATER ASSEMBLY
2.
— Use com­pressed air to blow off any dirt or dust that has accumulated on the heater coils.
NOTE: Do not direct air at the bi-metal discs on the temperature limiter switches.
FIGURE 21 — LOCATION OF
TWO-PIECE INDOOR FILTER
FIGURE 22 — LOCATION OF OUTDOOR AIR
VENT FILTER
11
52C,P
SERIES
FIGURE 23 — PTAC EXTERIOR SURFACES
FIGURE 25 — CLEANING COILS
FIGURE 24 — VACUUMING EVAPORATOR COIL
DRAIN VALVE
FIGURE 26 — BASEPAN SECTION
12
COMPRESSOR
A cutaway view of the rotary compressor with key components labeled is shown in Figure 27. The motor stator is rigidly attached to the compressor shell. The rotor is pressed onto the eccentric shaft, which is sup­ported by 2 bearings. Both the discharge valve and dis­charge muffler are attached to the motor bearing. The
DISCHARGE TUBE
SUCTION INLET
pump bearing provides a thrust surface for the shaft and the rolling piston. Compressed gas is separated from the suction gas by the vane. Discharge gas pres­sure and the vane spring keep the vane in contact with the rolling piston.
SHELL
STAT OR
SUCTION MUFFLER/ ACCUMULATOR
PISTON
VANE
OIL TUBE
ECCENTRIC SHAFT
ROTOR
MOTOR BEARING
DISCHARGE MUFFLER
DISCHARGE VALVE CYLINDER
PUMP BEARING
MOUNTING PLATE
FIGURE 27 — ROTARY COMPRESSOR COMPONENTS
13
52C,P
SERIES
The rotary compression process (Figure 28), starts at top dead center as shown in (1). Suction gas flows through the suction inlet and into the cylinder area. As the shaft rotates through 90 degrees, the rolling piston moves to positio n A as shown in (2). The su ction volume is now the area defined by point A and the tip of the vane. Gas in the remaining volume has been compressed above suction pressure. After another 90 degrees of shaft rotation, the rolling piston has moved to position B as shown in (3 ). Both the com­pressed gas and suction gas volumes are now equal. Another 90 degrees of shaft rotation is shown in (4 ). Compressed gas has reached a pressure sufficient to open the discharge valve, and flows from the cylinder into the compressor shell. After another 90 degrees of shaft rotation, the entire process begins again. Contin­uous suction and discharge allows for a smooth com­pression process.
The rolling piston is not in actual contact with the cyl­inder wall, vane, or bearing faces. Hydrodynamic seal­ing prevents leakage from the compressed gas volume to the suction volume via these paths. Precise control of machining tolerances, surfaces, finishes, and assem­bly clearances is critical to achieve high efficiency per­formance. In addition, the line contact between the vane tip and the rolling piston requires careful selec­tion and control of materials to provide wear resis­tance and reliable long-term operation.
BASIC HERMETIC COMPRESSOR ELECTRICAL MEASUREMENTS
There are 2 basic electrical te st s for herme tic compres ­sors that will determine the electrical state of the motor. The first test requires checking the electrical resistance of each of the electric al motor windin gs. The second test requires checking the electrical resistance of each of the electrical motor windings to ground. These tests may be accomplished by performing the following steps:
1. DISCONNECT ALL POWER TO THE UNIT.
2. Remove the unit chassis from the sleeve as detailed in the
3. Open the control box as detailed in the
DISASSEMBLY
remove the 3 compressor wires from the following locations: the RUN wire (BLACK) from the capac­itor, the START wire (BLUE) from the capacitor. The third wire, COMMON wire (YELLOW) may be connected to one of the following locations:
PC units for CE, PE Remote Control Units
on the RC Control Board,
Units
switch. outdoor frost thermostat.
the wire is located on the rotary selector
For ALL CQ, PQ Units
UNIT DISASSEMBLY
section, then locate, label, and
the wire is on the indoor thermostat,
for all other CE, PE
section.
UNIT
the wire is
the wire is on the
for
COMPRESSOR TROUBLESHOOTING
Refer to Figure 29 for a basic compressor troubleshoot­ing chart.
FIGURE 28 — ROTARY COMPRESSOR
COMPRESSION PROCESS
For compressors that are known to be dam­aged: Remove refrigerant prior to disconnecting
compressor wires. Damaged hermetic compressor terminals may become loose a nd eject f rom the com­pressor. Wear safety glasses and keep your face away from the area above the terminals when removing compressor wires.
4. Perform a shorted/open windings test to measure the resistance between the windings of the com­pressor motor. Use a volt-ohmmeter set to the low­est ohm reading level then read and record the resistance between the RUN and START, START and COMMON, and RUN and COMMON wires . See Figure 30. The typical resistance readings will be about 4, 3, and 1 ohms respectively. The smaller values should add to equal the larger value. If this is not true then the compressor is likely shorted winding to winding.
NOTE: The rotary compressor has the compressor overload located under the terminal cover. If the over­load is open it can show ohm readings that are infinite. The unit should be off for at least an hour to give this overload time to reset if it is open.
14
POSSIBLE CAUSE SYMPTOM
COILS/FILTERS DIRTY OR PLUGGED AIR OR NONCONDENSABLE GASES
SYSTEM REFRIGERANT OVERCHARGED
DISCHARGE LINE RESTRICTED
CAPILLARY TUBE OR STRAINER
RESTRICTED OR PLUGGED
FAN BLADE OR MOTOR DEFECTIVE
FAN BLADE OR BLOWER WHEEL STUCK
SYSTEM REFRIGERANT UNDERCHARGED
EVAPORATOR AIRFLOW RECIRCULATION
UNIT OVERSIZED FOR APPLICATION
COMPRESSOR REQUIRES START ASSIST
OVERLOAD PROTECTOR OPEN
OVERLOAD PROTECTOR INCORRECT
CAPACITOR INCORRECT OR DEFECTIVE
THERMOSTAT CONTACTS ARE OPEN
THERMOSTAT IS SET TOO HIGH OR LOW
SELECTOR SWITCH IS OPEN
WIRING IS INCORRECT OR DEFECTIVE SYSTEM PRESSURES NOT EQUALIZED
COMPRESSOR MOTOR OR
COMPRESSOR GROUNDED
IN SYSTEM
NO POWER TO UNIT
LOW VOLTAGE TO UNIT
OR DEFECTIVE
OR DEFECTIVE
MECHANISM DEFECTIVE
COMPRESSOR
STARTS AND
RUNS BUT
CYCLES ON THE
OVERL OAD
X
XX
X X XX
XX X
X X X X X X
XX X X
XXX
XX X X
XXXX
XX X XX
COMPRESSOR
STARTS AFTER
CYCLING THE
OVERLOAD
SEVERAL TIMES
XX
XX X
COMPRESSOR
WILL NOT
START. IT HUMS
AND CYCLES ON
THE OVERLOAD
X
COMPRESSOR
WILL NOT START
AND MAKES NO
NOISE
X
X
X X
X
COMPRESSOR
CYCLES OFF
(NOT ON
OVERLOAD)
X X
FIGURE 29 — BASIC COMPRESSOR TROUBLESHOOTING GUIDE
5. Next, perform a grounded windings test to test the resistance individually of each wire to the shell of the compressor. The paint on the compres­sor can prevent good contact between the probe and the metal. The paint should be removed from a small section of th e shell of the compressor to ensure good contact by the meter probe. The volt­ohmmeter should be set to at least the 100X ohm level. The measured resistance between each wire and ground should be infinite or O.L. on the readout. If there is measurable resistance one of the windings is likely shorted to ground. See Figure 31.
6. A compressor that has a winding to winding short or a winding to compressor shell short is electri­cally failed and needs to be replaced. See the
Compressor Replacement
section for details.
COMPRESSOR REPLACEMENT
Before working on the compressor, read the instruc­tions thoroughly and gather t he necessar y tools fo r the job. Review all safety information on unit and in liter­ature. Always turn off all power to unit to avoid the possibility of electrical shock.
Consider the following safety issues before beginning:
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as work gloves and safety glasses, should be worn.
• The floor around the work area should be clean and free of debris.
• Make sure tools are th e cor r ect to ol s for the jo b a nd that they are working properly and in good condition.
• Never replace a blown fuse without correcting the cause of the original fail u re. If thermally operated circuit breakers or overloads are tripping, make sure the trip is not due to excessi vely high tempera­tures or loose connections.
• When brazing suction and discharge lines, cool the lines with a damp, clean cloth to prevent injury.
• Oil may be present in the compressor accumulator and interconnecting tubing. Use caution when removing tubing.
15
52C,P
SERIES
FIGURE 30 — SHORTED/OPEN WINDINGS TEST
FIGURE 31 — GROUNDED WINDINGS TEST
REMOVING THE COMPRESSOR
Follow the
steps below to remove the compressor:
1. Disconnect all power to unit.
2. Remove unit from wall sleeve as detailed in the UNIT DISASSEMBLY section. The unit weighs up to 150 pounds. Seek assistance or use a lifting device when removing unit from wall sleeve.
If the unit is a heat pump:
3.
Disconnect the wire plug on the reversing valve solenoid and carefully remove the outdoor thermostat capillary from the outdoor coil. See Figure 32.
4. Attach the piercing valve to the suction side pro­cess tube below the crimps. Attach Carrier TOTALTEST® kit (Part No. TT1-001), to the piercing valve to verify acidity of the s ystem. After verifying the system acidity, remove the refriger­ant using a certified refrigerant recovery system.
5. When all the refrigerant has been recovered, remove the terminal cover from the compressor with a nut driver. Disconnect the 3 wires from the compressor and label the location of each. Once the wires are labeled, replace the terminal cover to protect the compressor terminals.
6. Remove the air system components by following the procedure detailed in the
COMPONENTS
section
ACCESSING UNIT
.
7. Remove the piercing valve and cut the crimped portion of both process tubes off with a small tub­ing cutter. Braze an access valve on each process tube. Using a torch, disconnect the suction and discharge tubes from the compressor connections.
8. Remove the compressor mounting bolts, and remove the compressor.
For compressors that are known to be dam­aged: Remove refrigerant prior to disconnecting
compressor wires. Damaged hermetic compressor terminals may become l oos e and eje ct f r om the com­pressor. Wear safety glasses and keep your face away from the area above the terminals when removing compressor wires.
TOOLS NEEDED
— The following list inclu des the recommended tools and devices for removing and replacing the compressor.
1
/2-in. and 3/8-in. Tube Benders
1
/2-in. Nut Driver
5
/16-in. Nut Driver Flat Head Screwdriver Piercing Valve 2 Parker Access Valves (Part No. AVUSE-5) Pinch Off Tool Filter Drier — All Units (Part No. P504-80845) Carrier TOTALTESTT Kit (Part No. TT1-001) Totalclaim® System Charging Cylinder or an Electronic Scale Refrigerant-22 Tubing Cutter To rch Nitrogen Cylinder with Regulator Stainers Capillary Tubes
The compressor may still be hot from the brazing process.
IMPORTANT. Any time the compressor is replaced, the strainer and capillary tubes must be removed and replaced also.
F or all units:
9.
Remove and replace the strainer and capillary tubes from the system. See Figure 32 for strainer and capillary tube location.
For Heat/Cool Units:
10.
Use an in-line filter drier (P/N P504-80845). The filter drier can be installed in any location in suction line. See Figure 33A for general installation location.
For Heat Pump Units: Use an in-line filter drier (P/N P504-80845)
and install between the
reversing valve and the compressor accumu­lator. There are several suction tube configura-
tions and the in-line filter drier will be field piped and brazed in to the su ction tube for your uni t. See Figure 33B for a general installation location.
11. Remove the grommets from the existing compres­sor and install them onto the new compressor.
16
12. Install the new compressor and the new capillary
IN-LINE FILTER DRIER
COMPRESSOR
IN-LINE FILTER DRIER
COMPRESSOR
assembly (the correct capillary and strainer may be obtained from Carrier RCD), into the unit.
13. Leak check the unit with 150 psi of nitrogen pressure.
14. For 52C,P units, the system should be evacuated from the high side to the low side to a minimum of 200 microns of mercury. This evacuation removes residual moisture from the system prior to charging.
For Heat Pump Units:
15.
Recharge unit to the nameplate refrigerant charge using a charging cylinder.
16. Pinch off each access valve o n the process t ubes , in 2 places, using a pinch off tool such as Imperial tool #105-FF or Robinair Tool #12294. Release any refrigerant pressure trapped in the access valve by depressing the valve core, then confirm that no R-22 is leaking past the pinch off tool location. Cut the access valve stem of the process tube above the top crimp and braze the top o f each process tube to ensure the system is sealed, (leave the pinch off tool in p lace until after the brazing pro­cess is complete).
17. Reassemble the unit by reversing steps 1-9.
18. Connect the compressor wires and energize the unit to verify operation.
REFRIGERANT CHARGING —
Every mechanical refrigeration system that is opened for servicing must be accurately charged before it is returned to service. Run the compressor ONLY after charging the system with refrigerant.
FIGURE 32 — STRAINER AND CAPILLARY TUBE LOCATION
IMPORTANT: The compressor should never be operated without refrigerant!
It is important to remember that recovered and/or recycled refrigerant may only be recharged into the system from which it was initially recovered, or another one owned by the same customer. Charge level is important. Charge units only as recommended by manufacturer.
FIGURE 33A — IN-LINE FILTER DRIER —
GENERAL INSTALLATION LOCATION
FOR HEAT/COOL UNIT
FIGURE 33B — IN-LINE FILTER DRIER —
GENERAL INSTALLATION LOCATION
FOR HEAT PUMP UNIT
17
52C,P
SERIES
HEATERS
The heater in 52C,P units is located directly behind the evaporator coil. The heater assembly includes the heater (2.3 kW, 3.4 kW or 5 kW), a primary limit switch, and a secondary limit switch. See Figure 34. The primary and secondary limit switches are safety switches that regulate heater operation. The primary limit switch disables current to the heater when the temperature exceeds t he setting on the switch.
For example, a 3.4 kW heater may have a primary limit switch setting of 150 F. If the temperature at the switch exceeds 150 F, the primary limit switch will electrically open and shut off power to the heater. Once the temperature drops below 110 F, the primary limit switch will automatically reset.
The secondary limit switch works in the same manner as the primary limit switch, except it is a one time switch and has a slightly higher temperature setting. Once this switch is thermally opened, it must be replaced. Together the primary and secondary switches help maintain safe temperature limits for unit operation.
COMMON CAUSES OF HEATER FAILURE
Heater failure may result from broken heater coils, primary limit switch failure, or an open secondary limit switch. These conditions are generally caused by low or no airflow.
HEATER REMOVAL
Before working on the heater, read the instructions thoroughly and gather the necessary tools for the job. Review all safety information on the unit and in the product literature.
Before performing any cleaning, servicing, or main­tenance to the unit, Disconnect All Power to avoid the possibility of electric shock and personal injury.
The manufacturer reserves the right to discontinue, or change at any time, specifications or desig ns without notice and without incurring obligations.
Consider the following safety issues:
• Prior to performing any service or maintenance on electrical equipment you must Disconnect All
Power.
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as safety glasses and work gloves, should be worn.
• The floor around the work area should be clean and free of debris.
• Make sure tools are the correct tools for the job, and that they are working properly and in good condition.
FIGURE 34 — LIMIT SWITCH LOCATION
18
TOOLS NEEDED
The following list includes rec­ommended tools and devi ces for worki ng on t he heater section of 52C,P units.
Phillips Head Screw Driver
Needle Nose Pliers
Volt-ohmmeter
Nut Driver
5
/16-in.
Perform the follo w in g ste ps to rem ove the Heater Assembly.
1. DISCONNECT ALL POWER TO UNIT.
2. Remove heater by follo wing instructions in
ACCESSING UNIT COMPONENTS
section.
After the heater is removed, examine the heater as follows to determine if it is operational:
Perform a visual inspection. The heater coil should be free of breaks. If there are any breaks in the coil, replacement of the heater assembly is necessary. See Figure 35.
Coil resistance must also be checked to verify the heater is operating correctly. The resistance of the heater coils must meet approximate levels for the heater to perform at its optimum effici ency. See Figure 36 for approximate resistance for heaters at 75 F. Before checking the heater coil resistance, be
sure all power to unit is off.
To check resistance, set the volt-ohmmeter selector switch to the lowest ohms value. Next connect the volt­ohmmeter leads to each side of the heater coil at the studs that hold the limit switches in place. Incorrect readings can be obtained if the wires are not removed from the limit switches on the heater assembly. If the resistive reading is infinite or zero, the heater is failed and replacement is necessary. Reinstall the heater assembly.
FIGURE 35 — HEATER COIL (Removed)
HEATER SIZE WATTS VOLTS
2.3 kW
3.4 kW
5.0 kW
2300 230 20-23 2300 265 28-31 3400 230 13-16 3400 265 19-21 5000 230 9-11 5000 265 13-15
FIGURE 36 — ACCEPTABLE HEATER
RESISTANCE VALUES
ACCEPTABLE RESISTANCE
(Ohms)
19
52C,P
SERIES
OPERATING CONTROLS
The controls and components used in the 52C,P cool­ing only or heat/cool units are as follows: the selec-
tor switch, the indoor thermostat, the dual capacitor, the temperature limiter, the vent lever, and the fan cycle switch.
The selector switch is used to determine the mode of operation: heat, cool, fan, or off. The indoor thermostat controls the room ambient temperature and cycles the heater or the compressor based on the selector switch setting. The dual capacitor aids in the start-up of the compressor and the fan motor. The temperature limiter is integrated into the control box top cover located under front panel. I t is a mecha n ica l dev i ce th at restricts the amount of rotation of the thermostat. The temperature limiter device may be adjusted by moving the plastic temperature selector tabs to another temper­ature location on the control box. The vent lever is located on the front left side of the chassis. It is a slide mechanism that opens and closes the vent door. The vent control may be accessed by removing the front panel of the unit. The f an cycle switch is used to provide 2 options of fan control. The first option, CON, causes the fan to run continuously. The second option, CYC, causes the fan to cycle on with the compressor or elec­tric heater and off when the thermostat is satisfied.
The 52C,P heat pump unit contains all the compo­nents of the heat/cool and cooling only unit, and the following additional ones: the outdoor frost thermostat and the reversing valve. The outdoor frost thermostat prevents operation of the unit in the heat pump mode when the outdoor coil temperature drops below 20 F, or at about 35 F outdoor ambient temperature. The unit automatically engages the electric heat strip under these conditions.
The outdoor fros t thermo stat has a manual overr ide to place the unit in electri c heat mode operation only. The override switch is located behin d the front pa n el on the front side of the unit control box door.
See Figures 40 and 41 for control wiring. See Figure 42 for unit control panel examples.
FIGURE 37 — NON-PROGRA MMABLE
THERMOSTAT
FIGURE 38 — MANUAL THERMOSTAT
IMPORTANT: Pla c ing th e over ri de sw it c h to elec ­tric heat mode operation will disable the compres-
sor for ALL heating or cooling operations (for all units except RC units). Placing the override swi tch
to electric heat mode operation on RC units will only disable the compressor in heating mode.
The reversing valve allows for operation in reverse cycle heat pump mode. The valve is located in the piping sys­tem and is controlled by the reversing valve solenoid coil. The coil is energized only during the heating mode.
For 52C,P remote control (RC, RP) units, all con­trols are located on the wall-mounted thermostat except the vent lever and outdoor thermostat. Remote control is a factory or field-installed option. There are 3 styles of thermostats qualified for use with 52C,P series Remote Control units. See Figures 37-39. For all other 52C,P units, room controls are located on the unit control panel. On remote control units, the fan cycle function is located on the wall thermostat. The rocker switch on control box door is used to set fan speed to high or low. Factory default is low.
FIGURE 39 — PROGRAMMABLE THERMOSTAT
TYPICAL
WALL
THERMOSTAT
TERMINAL
TERMINAL DESIGNATION
R
24 VAC
G
Fan
Y
Compressor
W
Electric Heat
O
Reversing Valve
C
Common
NOTES:
Use terminal “O” for heat pump con-
1.
nection only
2. See table at left for terminal descriptions.
3. Common wire “C” is typically used only for digital thermostats.
4. Power stealing is allowed. There must always be a hard common connection between unit and digital thermostat.
BLOCK
.
FIGURE 40 — WIRING CONNEC TIONS
20
R
G
Y
W
O
C
MASTER
PTAC
R
Y
W
G
O
C
R
Y
W
G
O
C
TSTAT
UNIT 1
UNIT 2
UNIT 3
R
Y
W
G
O
C
R
Y
W
G
O
C
R
Y
W
G
O
C
NOTES:
1. Do not daisy chain R (24 VAC).
2. Maximum of 4 PTAC units can be con­nected to one single wall thermostat.
All units must be connected to same ground source. To accomplish this, be sure to connect all units back to the same breaker box.
FIGURE 41 — TYPICAL WIRING FOR MULTIPLE 52C PTAC UNITS CONNECTED TO 1 WALL THERMOSTAT
21
52C,P
SERIES
DESCRIPTION OF SELECTOR SWITCH SETTINGS (Figure 42)
OFF MODE
operation.
FAN ONLY MODE
circulation without heating or cooling. Fan runs at high speed.
HIGH HEAT OR HIGH COOL MODE
selector and temperature control knobs to desired com­fort level. This function provides maximum heating or cooling, and is recommended to raise or lower the roo m temperature quickly.
LOW HEAT OR LOW COOL MODE
selector and temperature control knobs to desired com­fort level. This function provides minimum heating or cooling with maximum dehumidification duri ng cooling. This setting also allows for very quiet fan operation.
FINDING TEMPERATURE SETTING FOR COM-
FORT LEVEL
Select High Heat, Low Heat or Cool position and allow unit to run for 15 to 30 minutes. If room is not comfort­able, turn knob setting slowly to change setting. When room is comfortable, keep control knob at that position.
The OFF position terminates unit
Use fan only position for air
Position
Position
Set temperatu re knob in the middle.
NON-USER ADJUSTABLE CONTROLS
OUTSIDE OR VENT AIR
the fully open position for outside air or fully closed position for vented air.
FAN CYCLE
to operate in 2 modes: CON — Fan runs continuously, circulating air even
when the temperature setting has been satisfied. This helps to maintain the room temperature closer to the thermostat setting.
CYC —Fan cycles on and off with the compressor dur­ing heating or cooling . Fan stops when the tempera­ture setting is satisfied. This results in longer unit off­time and slightly larger variations in room tempera­ture and humidity.
OUTDOOR THERMOSTAT (52CQ, PQ Units Only)
The outdoor thermostat has 2 operating mode s. The heat pump mode (selector screw set fully clockwise), allows the unit to opera te normally in the re verse cycle mode. The electri c heat mode (selector screw set fu lly counterclockwise), disables all modes, both heating and cooling for units with mounted controls. For wall thermostat controlled mod­els the compressor is only disabled in heating and still allowed to run in cooling.
The fan cycle switch allows the fan
Slide the vent lever to
compressor
operating
TYPICAL 52C UNIT CONTROLS
FIGURE 42 — TYPICAL CONTROL PANEL (52C Unit Shown)
WALL THERMOSTAT CONTROLS (Blank Plate )
TYPICAL 52C UNIT WITH
22
SEQUENCE OF OPERATION
HEAT/COOL UNITS (Figure 43)
Fan Mode tacts L1 to HI and FCS1 to LS are made.
Cooling (Low) speed cooling contacts FCS2 to LO, COMP to FCS1, and COMP to IT3 are made.
Cooling (High) speed cool contacts FCS2 to HI, COMP to FCS1, and COMP to IT3 are made.
Heating (Low) speed heat contacts FCS2 to LO, IT1 to LS, L2 to HTR, and FCS1 to LS are made.
Heating (High) —
speed heat c o nta ct s FC S2 to H I , I T 1 to LS, L2 to HTR , and FCS1 to LS are made.
SWITCH
POSITION
OFF FAN LO HEAT HI HEAT LO COOL HI COOL
FIGURE 43 — SELECTOR SWITCH CONTACTS,
With the selector switch set to FAN con-
With the selector switch set to low
With the selector switch set to high
With the selector switch set to low
With the selector switch set to high
CONTACTS MADE
NONE L1 TO HI, FCS1 TO LS FCS2 TO LO, IT1 TO LS, L2 TO HTR, FCS1 TO LS FCS2 TO HI, IT1 TO LS, L2 TO HTR, FCS1 TO LS FCS2 TO LO, COMP TO FCS1, COMP TO IT3 FCS2 TO HI, COMP TO FCS1, COMP TO IT3
ALL 52CE, PE ELECTRIC HEAT/COOL UNITS
Heating (Low)
With the selector switch set to low heat contacts L1 to IT1, FCS to LO and L2 to HTR are made.
Heating (High)
With the selector switch set to high heat contacts L1 to IT1, FCS to HI, and L2 to HTR are made.
Defrost Cycle
When heat pump unit is operating in reverse cycle, the outdoor coil may begin to frost. As frost accumulates on the outdoor coil the unit may switch into defrost mode. The defrost mode is activated when the outdoor frost thermostat sensor detects a temperature below 20 F on the coil. At this point, the thermostat deenergizes the compressor and activates the electric heat. The unit will remain in electric heat mode until the outdoor thermostat senses 35 F coil temperature. The defrost mode is a passive operation and may take some time before the coil defrosts.
SWITCH
POSITION OFF FAN LO HEAT HI HEAT LO COOL HI COOL
NONE L1 TO HI L1 TO IT1, FCS TO LO, L2 TO HTR L1 TO IT1, FCS TO HI, L2 TO HTR L1 TO IT3, FCS TO LO L1 TO IT3, FCS TO HI
CONTACTS MADE
FIGURE 45 — SELECTOR SWITCH CONTACT,
ALL 52CQ, PQ HEAT PUMP UNITS
COOLING ONLY UNITS (Figure 44)
Fan Mode
With the selector switch set to FAN con-
tact L1 to LO is made.
Cooling (Low)
With the selector switch set to low speed cooling contacts FCS to LO and L1 to IT3 are made.
Cooling (High)
With the selector switch set to high
speed cool contacts FCS to HI, L1 to IT3 are made.
SWITCH
POSITION OFF FAN L O FAN HI LO COOL HI COOL
CONTACTS MADE
NONE L1 TO LO L1 TO HI L1 TO IT3, FCS TO LO L1 TO IT3, FCS TO HI
FIGURE 44 — SELECTOR SWITCH CONTACTS,
ALL 52CE, PE COOLING ONLY UNITS
HEAT PUMP UNITS (Figure 45)
Fan Mode
With the se lector switc h set to fan c ontact
L1 to HI is made.
Cooling (Low)
With the selector switch set to low
cool contacts L1 to IT3 and FCS to LO are made.
Cooling (High)
With the selector switch set to high
cool, contacts L1 to IT3 and FCS to HI are made.
COMPONENT OPERATION AND TROUBLESHOOTING
TOOLS NEEDED
Volt-Ohmmeter
Flat and Phillips Screw Drivers
5
/16-in. Nut Driver
Side Cutting Pliers
Before cleaning, servicing, performing maintenance or removing the chassis from the wall sleeve, discon­nect all power to the unit to avoid the possibility of electrical shock and personal injury. Only trained and qualified service personnel should perform installation and service procedures on these units. Untrained personnel may perform basic mainte­nance tasks such as cleaning and replacing filters. Refer to UNIT DISASSEMBLY section of this man­ual for proper procedures to disconnect power to 52C,P units.
23
52C,P
SERIES
The Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Consider the following safety issues:
• Prior to performing any service or maintenance on electrical eq ui pment you must Disconnect All
Power.
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as safety glasses and work gloves, should be worn.
• The floor around the work area shoul d be clean and free of debris.
• Make sure tools are the correct tools for job, and that they are working properly and in good condition.
• The 52C,P unit may weigh up to 150 pounds. Use a lifting device or ask for assistance if the unit must be moved.
INDOOR THERMOSTAT (Heat/Cool and Cool Only
Units) (Figure 46) —
The thermostat maintains the selected temperature by cycl ing the compressor on and off during cooling operat ion and the electric heater during heating operation.
The thermostat DOES NOT switch from heating to cooling, or cooling to heating.
If the switch is in the CYCLE position, then the fan will be cycled off when the thermostat satisfies.
To verify the operation of the thermos tat switch , a con­tinuity test may be performed as follows:
1. Turn off unit power as descri b e d i n UNIT DISASSEMBLY section.
2. Remove wire leads from thermostat. Note their locations to ease re-assembly.
FIGURE 46 — INDOOR THERMOSTAT (IT)
CONTACTS, ALL 52CE, PE MODELS
LEGEND (Figures 46-48)
COMP — HTR — IF — IT — OFT — OL — PLS — SLS
Compressor Heater Indoor Fan Indoor Thermostat Outdoor Frost Thermostat Overload Primary LImit Switch Secondary Limit Switch
3. Place one of the leads of the continuity tester on the terminal marked 2, and the other lead on either the terminal marked 1 or the terminal marked 3.
4. Adjust the thermostat up or down to verify the contacts of the switch open and close. When veri­fying continuity of a ing should be 0 ohms. An
closed
switch, the ohm read-
open
switch will show
OL on the meter.
5. When testing is complete, reconnect the leads .
INDOOR THERMOSTAT (Heat Pump Units)
(Figure 47) —
The heat pump indoor thermostat uses a two-stage switch for the heating mode. The first stage engages the compressor and reversing valve, and the unit operates in normal heat p u mp mode. The indoor thermostat maintains the selected temperature by cycling the compressor on and off in cooling mode. In the heating mode, the indoor thermostat will cycle the compressor or the heater, depending on the difference between the actual room temperature and the thermo­stat temperature setting.
When the room temperature is more than 4 F cooler than the indoor thermostat setting, the second hea ting stage of the indoor thermostat engages t he electric heat strip. This design feature allows the user to rap­idly warm the room with the electric heat strip by turning the thermostat to its highest setting. When room temperatures appro ach the desired temperatu re, the user may adjust the thermostat to a personal comfort setting, which allows for normal heat pump operation.
NOTE: For outdoor coil temperatures below approxi­mately 25 F, the outdoor frost thermostat prevents heat pump mode operation and immediately engages the electric heat strip upon a call for heating. The elec­tric heat strip is NEVER energized at the same time as the compressor.
To verify operation of th e heat pump indoor thermo­stat switch, a continuity test may be performed as follows:
1. Turn off unit power as described in UNIT DISASSEMBLY section.
2. Remove wire leads from thermostat. Note their locations to ease re-assembly.
3. To test stage A, place one lead of the continuity tester on the terminal marked 2, and the other lead on either the terminal marked 1 or the t ermi­nal marked 3.
4. Adjust the thermostat up or down to verify the contacts of the switch open and close. When veri­fying continuity of the on the meter should be 0 ohms. An
closed
switch, the reading
open
switch
will show OL on the meter.
5. To test stage B contacts, place one lead of the con­tinuity tester on contact 5 and the other lead on either contact 4 or contact 6.
6. Adjust the thermostat up or down to verify the contacts of the switch open and close as in Step 4.
7. When testing is complete, reconnect the leads .
24
1
BLK
2
ORN
5
3
4
6
IT
BLU
GRY
BRN
FIGURE 47 — INDOOR THERMOSTAT (IT)
CONTACTS, ALL 52CQ, PQ MODELS
OUTDOOR FROST THERMOSTAT (Heat Pump
Units) (Figure 48A and 48B) —
The Outdoor Frost Thermostat (OFT) is a thermostat that uses a single­pole switch with a manual override selector. The ther­mostat swit che s bet w ee n el ect r ic h e at and co mp res sor operation when the temperature of the outdoor coil falls below 20 F or rises above 35 F. Switching the override selector to electric heat disables the reverse cycle operation of the thermos ta t and is manually switched to electric heat operation.
IMPORTANT: Pla cin g the ove rr id e swit c h to el ec­tric heat mode operation will disable the compres-
sor for ALL heating or cooling operations (for all units except RC units). Placing the override swi tch
to electric heat mod e operation on RC units will only disable the compressor in heating mode.
FIGURE 48A — OUTDOOR FROST THERMOSTAT
(OFT) CONTACTS, ALL 52CQ, PQ UNITS WITH
MOUNTED CONTROLS
To verify the OFT is operational, a continuity test may be performed as follows:
1. Turn off unit power as described in UNIT DISASSEMBLY section.
2. Remove the leads from the OFT. Note their loca­tions to ease re-assembly.
3. Connect the continuity tester to the switch termi­nals marked 1 and 2.
4. Rotate the override switch to the electric heat set­ting and verify that there is continuity between terminals 1 and 2.
5. To check the other contacts, move the lead on ter­minal 1 to terminal 3. Rotate the override switch to the heat pump setting. There should now be continuity between terminals 2 and 3.
6. Once the test is complete, reconnect the leads.
CAPACITOR —
The 52C,P units use a
dual
capacitor. One part of the capacitor is used with the
fan motor. The other part of the capacitor is used by the compressor.
Run circuits on single-phase compressor motors use capacitors which dramatically affect the motor opera­tion. Run capacitors are connected to the motor circuit
at all times.
To evaluate the capacitor, perform a visual check first. A shorted capacitor may give a visual indication of its failure. For example, the pop-out hole at the top of a start capacitor may bulge or blow out. A run capacitor may bulge or leak. In these instances, the capacitor must be replaced with one recommended by the manu­facturer. If there are no visual signs of capacitor fail­ure, testing of the capacitor resistance may be done with a volt-ohmmeter as detailed below:
1. Turn off unit power as described in UNIT DISASSEMBLY section but do not unplug the service cord; it will supply ground connection for the unit chassis. Check to ensure power is off
and LOCKED OUT.
2. Connect one lead of a 20,000 ohm, 2-watt resistor to the center group of te rminal s on the dua l ca pac­itor. Attach the other lead from the resistor to an unpainted metal section of the unit chassis. This allows that section of the dual capacitor to dis­charge. Repeat this process between the other group of terminals.
Capacitors are capable of holding charge similar to a battery and may cause an electrical shock.
FIGURE 48B — OUTDOOR FROST THERMOSTAT
(OFT) CONTACTS, ALL 52CQ, PQ UNITS WITH
WALL THERMOSTAT CONTROL
3. Locate and disconnect the wires from the start and/or run capacitor to isolate them from the remainder of the circuit. Refer to the unit wiring diagram if you need assistance locating wires.
4. Perform capacitor test. Set up the volt-ohmmeter to measure resistance by connecting terminals C to FAN and C to HERM on the meter. See Figure 49.
25
52C,P
SERIES
FIGURE 49 — CAPACITOR TEST
5. The reading on the meter should first indicate zero, or a low resistance, then slowly rise toward infinity or some high value or measurable resis­tance. This indicates the capacitor is most likely good. If the reading goes to zero or a low resis­tance and stays there, the capacitor is likely shorted and needs replacement . If the reading immediately indicates infinity, the capacitor is likely open and must be replaced.
6. Replace the capacitor if failed and rewire accord­ing to the WIRING SCHEMATICS located in the control box of the unit.
FAN CYCLE SWITCH —
2 operating modes, cont inuous (CON) and cycle (CY C). To verify the fan cycle switch is oper ational, a continu­ity test may be performed as follows:
1. Turn off unit power as descri b e d i n UNIT DISASSEMBLY section.
2. Label and remove the leads connected to fan cycle switch. See Figure 50.
3. Connect the volt -ohmmeter for 1X o hms and c heck for continuity from terminal 2 to 1 then change the switch position and check for continuity from terminal 2 to 3.
4. Once test is complete, reconnect the leads.
The fan cycle switch has
7. Remove the 2 screws mounting the thermostat to the control box. Route thermostat bulb and cap il­lary out of control box.
8. Remove thermostat.
9. Reverse Steps 1-8 to reinstall.
OUTDOOR FROST THERMOSTAT (Heat Pump
Units)
To remove the outdoor frost thermostat
(OFT), perfor m th e fo llo w in g ste ps :
1. Turn off unit power as described in UNIT DISASSEMBLY secti on.
2. Remove front panel.
3. Remove the 2 screws mounting the thermostat to the bottom of the control box. See Figure 51.
FIGURE 50 — FAN CYCLE SWITCH (3 Terminal)
SELECT0R SWITCH
TEMPERATURE CONTROL STANDOFF PINS
FAN CYCLE SWITCH
80
85
CON
CYC
75
70
65
60
90
ELECTRICAL COMPONENTS REMOVAL AND REPLACEMENT
INDOOR THERMOSTAT
thermostat, perform the following steps:
1. Turn off unit power as descri b e d i n UNIT DISASSEMBLY section.
2. Remove front panel.
3. Remove thermostat knob to expose 2 Phillips head mounting screws.
4. Open the control box as described in the
DISASSEMBLY
5. Carefully remove the thermostat bulb from the clip by gently pressing it down and out of the clip.
6. Remove the leads from the indoor thermostat. Note the wire locations to ease re-assembly.
To remove the indoor
section of this manual.
UNIT
26
OFT MOUNTING SCREWS
OUTDOOR THERMOSTAT (HEAT PUMP UNITS ONLY)
FIGURE 51 — 52C,P OPERATING CONTROLS
4. Remove the thermostat ca pillary from t he outdoor
PLAIN WIRE (L1) TO ROTARY SWITCH
GROUND SCREW
FAN CYCLE SWITCH
INDOOR THERMOSTAT
SELECTOR SWITCH
CAPACITOR
OUTDOOR FROST THERMOSTAT
RIBBED WIRE (L2) TO CAPACITOR (C)
POWER CORD
POWER CORD
coil and clip any wire ties holding the capillary in place.
5. Disconnect the wires and carefully remove the thermostat and capillary from the unit, noting location of wires for easy re-assembly.
6. Reverse Steps 1-5 to reinstall.
CAPACITOR
T o remove the capacitor, perform
the following steps:
1. Turn off unit power as described in UNIT DISASSEMBLY section.
2. Open the control box as detailed in the
DISASSEMBLY
section of this manual.
UNIT
3. Properly discharge the capacitor as described in the Capacitor section under
Component Opera-
tion and Troubleshooting.
4. Remove the leads to the capacitor. Note the wire locations to ease re-assembly.
5. Remove the screw holding the capacitor.
6. Remove capacitor.
7. Reverse Steps 1-6 to reinstall.
FAN CYCLE SWITCH —
The fan cycle switch is located on the front of the control box. To remove the fan cycle switch, perform the following steps:
1. Turn off unit power as described in UNIT DISASSEMBLY section.
2. Open the control box as described in
DISASSEMBLY
section of this manual.
UNIT
3. Remove the 3 wires from the fan cycl e swit ch . See Figure 52 for location, noting location of wires for re-assembly.
4. Push the snaps of the switch housing toward the switch with a pair of pliers or small screwdriver. Gently push the switch out of the housing.
5. Reverse Steps 1-4 to reinstall.
SELECTOR SWITCH —
T o remove the selector
switch from the unit, perform the following steps:
1. Turn off unit power as described in UNIT DISASSEMBLY secti on.
2. Remove selector switch knob. See Figure 51.
3. Open control box as described in the
DISASSEMBLY
section of this manual.
UNIT
4. Remove all the wires to the selector switch. Label wires to simplify re-assembly. See Figure 52.
5. Remove the 2 screws mounting the switch and remove switch.
6. Reverse Steps 1-5 to reinstall.
FIGURE 52 — COMPONENT LOCATIONS
IN OPEN CONTROL BOX
27
52C,P
SERIES
FAN MOTOR
The fan motor is a permanent split capacitor (PSC) type motor. This motor is common in air-conditioning system applicatio ns. A PSC mo tor do es not requi re the use of a relay and always has a run capacitor con­nected between the run and start windings of the motor. See Figure 53.
The 52C,P series fan moto r has a motor shaft ex tended through both ends. It powers both the indoor and the outdoor fans. It has permanently sealed bearings that require no lubricati on. There are many different fan motor models, but they typically are 2-speed and in 2 voltage categories, 208/230 and 265 volts.
FAN MOTOR TROUBLESHOOTING
Refer to Figure 54 for a basic fan motor troubleshoot­ing chart.
TOOLS NEEDED
mended tools and de vices for working on the fa n motor of 52C,P units.
Before cleaning, servicing, performing maintenance or removing the chassis from the wall sleeve, discon­nect all power to the unit to avoid the possibility of electrical shock and personal injury. Only trained and qualified service personnel should perform installation and service procedures on these units. Untrained personnel may perfor m basic mainte­nance tasks such as cleaning and replacing filters. Refer to UNIT DISASSEMBLY section of this man­ual for proper procedures to disconnect power to 52C,P units.
The Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Regular and Phillips Head Screw Drivers
FIGURE 53 — TWO-SPEED, PERMANENT
SPLIT CAPACITOR MOTOR (PSC)
The following list includes recom-
Gloves
Safety Glasses
Small Adjustable Wrench
Channel Lock Pliers
Volt-ohmmeter
5
/16-in. Nut Driver
Consider the following safety issues:
• Prior to performing any service or maintenance on electrical equipment you must Disconnect All
Power.
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as safety glasses and work gloves, should be worn.
• The floor around the work area should be clean and free of debris.
• Make sure tools are the correct tools for the job, and that they are working properly and in good condition.
• The 52C,P unit may weigh up to 150 pounds. Us e a lifting device or ask for assistance if the unit must be moved.
BASIC FAN MOTOR ELECTRICAL TESTS
There are 2 basic electrical tests for PSC fan motors that will determine the electrical state of the motor. The first test requires checking the electrical resis­tance between the motor windings. The second test requires checking t he electrical resistan ce between the motor windings and ground. These tests may be accomplished by performing the following steps:
1. DISCONNECT ALL POWER TO UNIT.
2. Open the control box as detailed in the
DISASSEMBLY
3. Label and disconnect the fan motor wires from the selector switch and capacitor as shown in Figure 52. Two-speed motors have 2 wires on the capacitor and 2 wires on the push button switch.
4. Measure and record the resistance between the black wire and each of the other wires. Make sure the motor is cool before attempting to measure resistance. The internal thermostat of the motor may be electrically open and will not close until the motor cools. See Figure 55 for typical motor winding resistance measurements. The resistance values in the table are approximate. Values that are within 10% of those listed are acceptable. If the motor in your model is not listed, find a motor of similar horsepower an d voltage on the chart and compare it to the resistance measurements of your motor.
5. Measure the resistance of each of the motor wires to the motor casing. The resistance should be infi­nite. Make sure the motor is cool before attempt­ing to measure resistance. The internal thermostat of the motor may be electrically open and will not close unt il the motor cools. A motor that has measurable resistance to ground is shorted to ground and must be replaced.
section.
UNIT
28
POSSIBLE CAUSE SYMPTOM
DEFECTIVE BEARING
CAPACITOR DEFECTIVE
SWITCH DEFECTIVE LOW LINE VOLTAGE
SHORTED MOTOR WINDING
NO POWER TO UNIT
INTERNAL THERMOSTAT OPEN
MISWIRED
FAN STUCK
BROKEN MOTOR WIRE
MOTOR WINDING GROUNDED
OPEN MOTOR WINDING
FIGURE 54 — FAN MOTOR TROUBLESHOOTING CHART
UNIT 52C,P (BTUH) 7,000/9,000 12,000/15,000
CARRIER MOTOR PART NUMBER HC37GE237 HC37GE238
MANUFACTURER’S
PART NUMBER
MOTOR VOLTAGE
MOTOR HORSEPOWER
MOTOR SPEEDS
RESISTANCE (OHMS)
BLACK TO WHITE WIRE
RESISTANCE (OHMS)
BLACK TO BROWN WIRE
RESISTANCE (OHMS) BLACK TO RED WIRE
NOTE: Resistance values are approximate.
MOTOR HUMS
BUT DOES
NOT START
XXX XX
XXX XX X
XXX X X XXX X XX XXX X
MAKES NO NOISE
AND DOES NOT
START
XX
X X
STARTS BUT
STOPS AFTER
SHORT TIME
STARTS
BUT RUNS
SLOW
RUNS ON
ONE SPEED,
NOT ON OTHERS
TYPICAL 208/230 VOLT MOTORS
5KCP29ECA299A 5KCP29ECA301
208/230 208/230
.075 .125
22
101.4 90
45.8 71
38.8 32.9
UNIT 52C,P (BTUH) 7,000/9,000 12,000/15,000
CARRIER MOTOR PART NUMBER HC29GE236 HC33GE239
MANUFACTURER’S
PART NUMBER
MOTOR VOLTAGE
MOTOR HORSEPOWER
MOTOR SPEEDS
RESISTANCE (OHMS)
BLACK TO WHITE WIRE
RESISTANCE (OHMS)
BLACK TO BROWN WIRE
RESISTANCE (OHMS) BLACK TO RED WIRE
NOTE: Resistance values are approximate.
TYPICAL 265 VOLT MOTORS
5KCP29FCA315 5KCP29FCA316
265 265
.075 .125
22
144.0 83.7
29.3 39.1
82.1 45.2
FIGURE 55 — TYPICAL 52C,P FAN MOTORS
29
52C,P
SERIES
FAN MOTOR REPLACEMENT
1. DISCONNECT ALL POWER TO UNIT.
2. Remove the unit from the sleeve as detailed i n the
UNIT DISASSEMBLY
on a large flat surface.
3. Remove the discharge deck and grille as detailed in Remove The Discharge Deck Assembly section.
4. Remove heater plate assembly as detailed in Accessing The Heater Assembly section. The blower wheel should now be accessible.
Safety glasses should be worn to protect eyes in the event the spring clip breaks free from pliers.
5. Using adjustable pliers, carefully remove the spring clip that secures the blower wheel to the fan shaft. Remove the blower wheel.
6. Open the Control box as described in the
DISASSEMBLY Box
. Disconnect the fan motor wires from the rotary switch and capacitor. All units are equipped with two-speed motors, which have 2 wires on the capacitor and 2 wires on the rotary switch. Refer to the unit wiring schematic which is attached to the front panel of the control box. See Figure 56.
7. Carefully pull fan motor leads through the parti­tion hole, located in the back of the control box.
8. Remove the top gussets, as detailed in Remove the Gussets section.
section,
section and place the unit
UNIT
Open the Control
9. Remove the top half of the condenser orifice as detailed in Detach the Condenser Orifice From the Condenser Coil section.
10. Using a Phillips head screwdriver, remove the fan motor shield. The fan motor mounting screws should now be accessible. Remove the 3 mounting screws that secure the fan motor to the partition and remove the fan motor from the unit.
11. Using needle nose pliers, remove condenser fan hub clamp. Slide condenser fan off fan motor shaft.
12. Re-install the new fan motor by reversing Steps 1 through 11.
POWER CORD
FIGURE 56 — LOCA TION OF WIRING SCHEMATIC
ON FRONT PANEL OF CONTROL BOX
WIRING SCHEMATIC
30
WIRING DIAGRAMS
Refer to Figures 57-61 for Typical Wiring Schematics.
NOTE: Figures 57-61 should not be substituted for the schematic located on control box.
FIGURE 57 — 52CQ — TYPICAL WIRING SCHEMATIC FOR STANDARD HEAT PUMP UNITS
31
52C,P
SERIES
FIGURE 58 — 52CQ — TYPICAL WIRING SCHEMATIC FOR
WALL THERMOSTAT CONTROL HEAT PUMP UNITS
32
FIGURE 59 — 52CE — TYPICAL WIRING SCHEMATIC FOR STANDARD HEAT/COOL UNITS
33
52C,P
SERIES
FIGURE 60 — 52CE — TYPICAL WIRING SCHEMATIC FOR
WALL THERMOSTAT CONTROL HEAT/COOL UNITS
34
FIGURE 61 — 52PC — TYPICAL WIRING SCHEMATIC FOR
STAN DA R D CO OLING ONLY UNITS
35
52C,P
SERIES
MOST FREQUENT PTAC SERVICE QUESTIONS
1. Can remote wall therm o s tat s be use d on standard (AA) models?
2. Which remote thermostats are acceptable for use on 52C,P products?
3. How many 52C,P series units can be controlled by one
4. What is the vent capacity of the 52C,P products?
5. How do the 52C,P series models handle condensate
6. At what temperature will the outdoor (defrost) pumps only) into defrost (emergency heat) mode?
7. Can the PTAC unit be configured to allow continuous
8. Can the discharge air grille be changed to alter the
9. What does the outdoor thermostat switch do?
thermostat switch the unit (heat
direction of the airflow?
remote thermostat?
removal?
fan operation?
No, only for use on remote control (RC,RP) models. How­ever, accessory RC- Retrofit Ki t can be ordered to convert standard units to RC units.
HH01AD045 — Manual changeover thermostat TSTATCCBPC01-B (Heat/Cool) — Non-Progr ammable thermostat TSTATCCBPH01-B (Heat Pump) — Non-Programmable thermostat TSTATCCPAC01-B (Heat/Cool) — Digital Programmable thermostat TSTATCCPHP01-B (Heat Pump) — Digital Programmable thermostat
Maximum of 4. 50 cfm (standalone). Capacity can be increased with the
use of an external exhaust fan. By using a 2-stage condensate removal system. First
stage uses a slinger ring to pick up condensate and move it to the outdoor coil to be evaporated. In second stage, a vortex pump will suck condensate water int o the con­denser airstream where it will be blown onto the outdoor coil for evaporation.
When the outdoor coil temperature falls below 20 F (outdoor ambient temperature of approximately 35 F) and will stay in a passive defrost until outdoor coil is greater than 35 F.
Yes. A switch located on the front of the control box is used to toggle between continuous or cycle fan mode.
Yes. Remove the 2 screws and flip the grille over 180 degrees.
The selector screw, located on the front of the control box, prevents the compressor from energizing in heating mode during subfreezing conditions to ensure adequate heating capacity. For units with unit mounted controls, the switch must be returned to the ‘‘heat p ump’’ position for compressor operation during cooling modes.
36
ACCESSORIES
ACCESSORY FORM NUMBER PART NUMBER DESCRIPTION Wall Sleeves
Exterior Grilles†
Subbase
Subbase
Field-Installed
Kits
Electrical
Connections
Condensate
Drain Kit
Wall
Thermostats
Wall Thermostat
Interface
Retrofit Kit
Replacement
Filters
Energy
Management
Locking Security
Control Door
Lateral Duct Kit
Air/Curtain
Deflector
*Extended metal wall sleeve also available in 26 in. and 28 in. depth.
Custom colors are also available.
52S-48SI WALL-SLEEVE-1PK Non-Insulated Plastic Wall Sleeve, 1 per pack
52S-50SI SLEEVE-STEEL-1PK Insulated Metal Wall Sleeve, 1 per pack 52S-49SI* SLEEVE-EXT24-1PK Extended Metal Wall Sleeve for Deep Wall Applications (24 in. deep), 1 per pack 52C,P-12SI FR-SLEEVE-EXT Friedrich wall sleeve extension to retrofit Carrier PTAC unit into Friedrich 11
52S-59SI GRILLE-ALU-STAMP Stamped Aluminum Exterior Grille, Clear Finish 52S-58SI GRILLE-PLA-BROWN Plastic Architectural Rear Grille, Brown
52S-60SI GRILLE-ALU-CLEAR Aluminum Architectural Exterior Grille, Clear Finish
52C,P-1SI SUBBASE-NON-ELEC Non-electrical Subbase 52C,P-2SI SUBBASE-230V-15A Electrical subbase with factor y-installed 208/230V, 15 amp receptacle
52C,P-3SI SUBBASE-HARDWIRE Electrical subbase with factory-installed hardwire kit (230/208V and 265V) 52C,P-4SI SUBBASE-SWITCH Field-Installable Switch kit for an electrical subbase 52C,P-5SI SUBBASE-FUSE-15A Field-Installed Fuse Kit (15 amp) for electrical subbase
52C,P-11SI HARDWIRE-KIT-1PK Permanent power connection to the unit (includes 36" of flexible conduit and unit-mounted
52C,P-19SI CONDUIT-INTF-4PK Interface kit for field-supplied conduit to provide permanent power connection (230/208V and 265V) to
52S-53SI DRAIN-KIT-4PK Attaches to wall sleeve for controlled internal or external disposal of condensate 4 per pack
N/A HH01AD045 Electro-mechanical Wall Thermostat (Heat/Cool and Heat Pump)
52C,P-7SI RC-FIELDKIT230HC Field-installed wall thermostat retrofit kit to convert a standard 230V Heat/Cool unit to an
N/A TSTAT-COVER-6X7 Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for use with
N/A TSTAT-COVER-7X10 Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for use with
N/A AIR-FILTER-10PK Replacement air filters in package of 10
52C,P-10SI EM-KIT Allows unit to be turned on and off from a remote location (includes freeze guard protection)
52C,P-13SI SECURITY-DOOR Key-locking security door to prevent access to heating and cooling controls
52C,P-14SI LATERAL-DUCT Ductwork to allow one unit to heat and cool two rooms (plenum plus extension duct and registers) 52C,P-9SI DEFLECTOR-1PK Lateral air deflector, with individually adjustable louvers, to enhance air circulation, 1 per pack N/A CURTDFL-52CP-1PK Curtain deflector for 52C and 52P models prevents cur tains from blowing into discharge air stream.
WALL-SLEEVE-9PK Non-Insulated Plastic Wall Sleeve, 9 per pack SLEEVE-INSUL-1PK Insulated Plastic Wall Sleeve, 1 per pack
sleeve. 1 per pack
GRILLE-PLA-BEIGE Plastic Architectural Rear Grille, Beige
GRILLE-ALU-WHITE Aluminum Architectural Exterior Grille, White GRILLE-ALU-BRONZ Aluminum Architectural Exterior Grille, Light Bronze GRILLE-ALU-MBRNZ Aluminum Architectural Exterior Grille, Medium Bronze GRILLE-ALU-BROWN Aluminum Architectural Exterior Grille, Brown (Dark Bronze) GRILLE-ALU-BEIGE Aluminum Architectural Exterior Grille, Beige GRILLE-ALU-ALPIN Aluminum Architectural Exterior Grille, Alpine (matches Carrier Wall Sleeve) GRILLE-ALU-PEACH Aluminum Architectural Exterior Grille, Peach GRILLE-ALU-MELON Aluminum Architectural Exterior Grille, Melon GRILLE-ALU-LGREY Aluminum Architectural Exterior Grille, Light Grey GRILLE-ALU-SGREY Aluminum Architectural Exterior Grille, Slate Gray GRILLE-ALU-RDBRK Aluminum Architectural Exterior Grille, Red Brick GRILLE-ALU-BLUE Aluminum Architectural Exterior Grille, Blue GRILLE-ALU-GREEN Aluminum Architectural Exterior Grille, Green
SUBBASE-230V-20A Electrical subbase with factor y-installed 208/230V, 20 amp receptacle SUBBASE-230V-30A Electrical subbase with factor y-installed 208/230V, 30 amp receptacle SUBBASE-265V-15A Electrical subbase with factor y-installed 265V, 15 amp receptacle SUBBASE-265V-20A Electrical subbase with factor y-installed 265V, 20 amp receptacle SUBBASE-265V-30A Electrical subbase with factor y-installed 265V, 30 amp receptacle
SUBBASE-FUSE-20A Field-Installed Fuse Kit (20 amp) for electrical subbase SUBBASE-FUSE-30A Field-Installed Fuse Kit (30 amp) for electrical subbase
connector, 230/208V and 265V) 1 per pack
the unit. Kit includes Molex connector for easy connect/disconnect. 4 per pack
TSTATCCBPC01-B Value Series Electronic Thermostat w/Digital display (Heat/Cool Models) TSTATCCBPH01-B Value Series Electronic Thermostat w/Digital display (Heat Pump Models) TSTATCCPAC01-B 7-Day Programmable Electronic Thermostat (Heat/Cool Models) TSTATCCPHP01-B 7-Day Programmable Electronic Thermostat (Heat Pump Models)
RC-FIELDKIT230HP Field-installed wall thermostat retrofit kit to convert a standard 230V Heat Pump unit to an
RC-FIELDKIT265HC Field-installed wall thermostat retrofit kit to convert a standard 265V Heat/Cool unit to an
RC-FIELDKIT265HP Field-installed wall thermostat retrofit kit to convert a standard 265V Heat Pump unit to a
RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC).
RC unit. Wall thermostat sold separately.
RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC).
RC unit. Wall thermostat sold separately.
non-programmable and electro-mechanical thermostats. Outside dimensions: 6 1 per pack
programmable thermostats. Outside dimensions: 7
1 per pack. NOTE: Curtain deflector for previous models are also available. Contact Carrier Representative.
1
1
/4" x 93/4" x 33/8". 1 per pack
/2" deep (T Series) wall
1
/2" x 71/2" x 215/16".
37
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 9a 11a
PC 132 Catalog No. 535-20019 Printed in U.S.A. Form 52C,P-1SM Pg 40 1-02 Replaces: New
Loading...