• MODULATING POWER EXHAUST DIFFERENTIAL
PRESSURE SWITCH
• INLET GUIDE VANE DIFFERENTIAL PRESSURE
SWITCH (Units With Optional Inlet Guide Vanes and
Static Pressure Control)
• BELT INSTALLATION AND TENSIONING
• PULLEY ALIGNMENT
• INSTALLING ALTERNATE MOTOR PULLEY
(Evaporator Fan Only)
• CONDENSER FAN ADJUSTMENT
• 25% OUTDOOR-AIR DAMPER
• REFRIGERANT CHARGE
• PILOT LIGHT OFF (48 Series Units Only)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1
Tab 1a 1b
PC 111Catalog No. 564-818Printed in U.S.A.Form 48/50D,N-9SIPg 13-96Replaces: 48DJ,DK-3SI;
48/50NB,NP-1SI; 50DJ,DK-9SI
CONTENTS (cont)
• AUTOMATIC PILOT ADJUSTMENT (48 Series
Units Only)
• GAS VALVE ADJUSTMENT (48 Series Units Only)
• MAIN BURNER ADJUSTMENT (48 Series
Units Only)
Main Burner Removal (48 Series Units Only) ..50
Switch Adjustment.........................50
Refrigerant Feed Components ...............50
Thermostatic Expansion Valve (TXV) .........50
Moisture/Liquid Indicator ....................51
Filter Drier ..................................51
Liquid Line Service Valve ....................51
Compressor Discharge Service Valve ........51
Compressor Suction Service Valve ...........51
Protective Devices ..........................51
• COMPRESSOR PROTECTION
• EVAPORATOR-FAN MOTOR PROTECTION
• CONDENSER-FAN MOTOR PROTECTION
• HIGH- AND LOW-PRESSURE SWITCHES
Relief Devices ..............................51
Control Circuit, 115 V .......................52
Control Circuit, 24 v .........................52
Electric Heat (50 Series Units Only) ..........52
• OVERCURRENT
• OVERTEMPERATURE
Gas Heat (48 Series Units Only) ..............52
• LIMIT SWITCHES
• ROLLOUT SWITCH
TROUBLESHOOTING ......................52-69
Economizer .................................52
• ECONOMIZER MOTOR CHECKOUT
• ECONOMIZER CONTROL BOARD CHECKOUT
Unit Control Board Checkout ................53
• BASIC CHECK
• DETAILED CHECK
START-UP CHECKLIST .....................CL-1
Before performing service or maintenance operations on
unit, turn offmain power switch to unit. Electrical shock
could cause personal injury.
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department.
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, or
the gas supplier.
Disconnect gas piping from 48 Series units when leak
testing at pressures greater than 0.5 psig. Pressures greater
than 0.5 psig will cause gas valve damage resulting in
a hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced. When
pressure testing field-supplied gas piping at pressures of
0.5 psig or less, the unit connected to such piping must
be isolated by manually closing the gas valve.
GENERAL
This installation instruction contains base unit installation, start-up, and service instructions only. For complete information on PIC (Product Integrated Controls) and variableair volume (VAV) controls and troubleshooting, refer to
appropriate Controls and Troubleshooting literature also enclosed in this literature packet.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and
work gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing operations.
INSTALLATION
Riggingand UnitPlacement —
portation damage. File claim with transportation agency. Do
not drop unit; keep upright. Use spreader bars over unit to
prevent sling or cable damage. Sheets of plywood placed along
the condenser coils will provide additional protection. All
lifting lugs MUST be used when lifting unit. Level by using
unit frame as a reference. See Fig. 1 for information. Unit
and accessory weights are shown in Tables 1A, 1B, and 2.
Weight distribution and center of gravity can be found in
Fig. 2.
Inspect unit for trans-
Roof Curb — Assemble and install as described in in-
structions shipped with the accessory. Accessory roof curb
and information required to field fabricate a roof curb is shown
in Fig. 3A-3C. Install insulation, cant strips, roofing and counter
flashing as required. For unit condensate drains to function
properly, curb must be level or within tolerances shown in
Fig. 3A-3C.
Roof Mount — Check building codes for weight distri-
bution requirements. Unit weight is shown in Tables 1A and
1B. Unit may be mounted on class A, B, or C roofing
material.
Slab Mount — Provide a level concrete slab that ex-
tends beyond unit cabinet at least 6 inches. Make a slab 8 in.
thick with 4 in. above grade. Use gravel apron in front of
condenser coil air inlet to prevent grass and foliage from obstructing airflow.
2
NOTES:
1. Sizes 034,044:Rigwith4 cables and spread with two 95 in. (2413 mm) and
2 8A 1 A8 long spreader bars.
Sizes 054-074:Rigwith 4 cables and spread withfour 95 in. (2413 mm) and
2 8A 1 B 1 A8 long spreader bars.
2. Center of gravity includes economizer.
RIGGING WEIGHTS AND DIMENSIONS
1. All panels must be in place when rigging.
2. Unit is not designed for handling by forklift truck.
UNIT
48DJD,DKD,NPD03459412694.8
48DJE,NPE03460702753.4110.42804
48DJD,DKD,NPD04468413103.1
48DJE,NPE04469703161.6128.63267
48DJD,DKD,NPD05492304186.7
48DJE,NPE05493504241.2
48DJD,DKD,NPD06495304322.8
48DJE,NPE06496504377.2
48DJD,DKD,NPD07499504513.3
48DJE,NPE07410,0804572.3
50DJ,DK,NP03457002585.584.82153120.83067
50DW,DY,NB03462702844.176.41940102.52604
50DJ,DK,NP04463502880.492.62353126.63216
50DW,DY,NB04469203138.986.02185108.42753
50DJ,DK,NP05482303733.1120.83066126.83221
50DW,DY,NB05487803982.6109.02769109.02769
50DJ,DK,NP06485303869.2120.93071120.93071
50DW,DY,NB06490804119.7120.83066126.83221
50DJ,DK,NP07489604064.3131.73345137.63495
50DW,DY,NB07495004309.2109.02769109.02769
*Includes optional economizer.
UNIT WEIGHT*AB
LbKgin.mmin.mm
86.02185
92.62353
121.53086126.83221
134.73421134.73421
Fig. 1 — Rigging Label
109.42780
127.63240
If roof curb is not used, support unit with steel beams along
its entire length and then support steel as required.As a minimum, unit must be supported across its width at each lifting
lug location.
Positioning — Provideclearance around and above unit
for airflow,safety,and service access. Do not restrict top (area
above condenser fans) in any way. Allow at least 6 ft on all
sides for rated performance, code compliance, and service.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
On units equipped with or power exhaust option, high velocity air is exhausted out the hoods. Unit should be positioned with at least 10 ft clearance between the exhaust hoods
and any obstruction. Although unit is weatherproof, guard
against water from higher level runoff and overhangs.
3
Table 1A — Physical Data; 034, 044 Units
BASE UNIT*034044
NOMINAL CAPACITY (tons)3040
OPERATING WEIGHT (lb)
Quantity...Type2...06D2...06E
Capacity Steps (%)17, 33, 50, 66, 83, 10025, 50, 75, 100
Number of Refrigerant Circuits22
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
Without Hot Gas Bypass
With Hot Gas Bypass31.0/29.042.0/40.0
CONDENSER COILS
Quantity22
Rows...Fins/in.
Aluminum
Copper (Optional)3...13.73...13.7
Total Face Area (sq ft)37.550.0
EVAPORATOR COILS
Quantity
Rows...Fins/in.3...15.03...15.0
Total Face Area (sq ft)32.145.5
Refrigerant Feed Device...No. per CircuitTXV...1TXV...2
HEATING SECTION (48 Series Units Only)Low HeatHigh HeatLow HeatHigh Heat
Number of Heat Exchangers
Input (MBtuh)264529264529
Output (MBtuh)211423211423
Temperature Rise Range (F)0-3015-450-3015-45
Efficiency (%)79797979
Burner Orifice Diameter
Quantity...Diameter (in.)2...303...30
Nominal Cfm18,60026,000
Motor Hp...Rpm1.0...11401.0...1140
EVAPORATOR FANCentrifugal 25 x 25 in.
Nominal Cfm10,50014,000
Maximum Allowable Cfm15,00020,000
Maximum Allowable Rpm900900
Shaft Diameter at Pulley (in.)1
EVAPORATOR-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp7.510.015.020.0
Motor Frame Size213T215T254T256T
Efficiency at Full Load (%)
Standard Efficiency82.985.684.587.5
High Efficiency†—89.590.091.0
Fan Pulley Pitch Diameter (in.)13.713.713.713.7
Motor Pulley Pitch Diameter (in.)34.44.34.95.5
Resulting Fan Rpm405510580660
Belts Quantity...Model No.
48 Series and 50 Series, Horizontal Discharge2...BX602...5VX6302...5VX6302...5VX630
50 Series, Vertical Discharge2...BX602...5VX6302...5VX6302...5VX630
Center Distance Range (in.)
48 Series and 50 Series, Horizontal Discharge17.74...14.3017.74...14.3017.63...14.0117.63...14.01
OPTIONAL POWER EXHAUSTCentrifugal, 15 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp2...3.02...5.02...7.5
Motor Frame Size56HZ184T213T
Efficiency at Full Load (%)81.084.082.9
Fan Pulley Pitch Diameter (in.)6.96.96.9
Motor Pulley Pitch Diameter (in.)3.354.125.0
Shaft Diameter at Pulley (in.)1
Resulting Fan Rpm84310401264
Maximum Allowable Rpm130013001300
Belts Quantity...No.2...3VX6702...3VX6702...3VX710
FILTERS
Standard Efficiency Throwaway (Standard)12...20 x 25 x 212...20 x 25 x 2
Quantity...Size (in.)4...16 x 20 x 24...16 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)12...20 x 25 x 212...20 x 25 x 2
Quantity...Size (in.)4...16 x 20 x 24...16 x 20 x 2
High Efficiency (90%) Bag Filters with Prefilters (Optional)6...20 x 24 x 226...20 x 24 x 22
Quantity...Size (in.)6...20 x 20 x 226...20 x 20 x 22
612612
1212
3
TXV — Thermostatic Expansion Valve
*Data is for all 48 and 50 Series units of the size listed unless otherwise specified.
†Not available on 575-v units.
57706670
Semi-Hermetic
29.0/29.040.0/40.0
3
⁄8-in. Tube Diameter
3...15.03...15.0
1
12
11
⁄
16
⁄
16
⁄2-in. Tube Diameter
13⁄
16
111⁄
16
13⁄
16
4
Table 1B — Physical Data; 054-074 Units
BASE UNIT*054064074
NOMINAL CAPACITY (tons)506075
OPERATING WEIGHT (lb)
Quantity222
Rows...Fins/in.3...17.04...17.04...17.0
Total Face Area (sq ft)61.561.561.5
Refrigerant Feed Device...
No. per Circuit
HEATING SECTION (48 Series Units Only)Low HeatHigh HeatLow HeatHigh HeatLow HeatHigh Heat
Number of Heat Exchangers121812181218
Input (MBtuh)540810540810540810
Output (MBtuh)432648432648432648
Temperature Rise Range (F)5-3515-455-3515-455-3515-45
Efficiency (%)808080808080
Burner Orifice Diameter
Quantity...Diameter (in.)4...304...305...30
Nominal Cfm40,00040,00050,000
Motor Hp...Rpm1.0...11401.0...11401.0...1140
EVAPORATOR FANCentrifugal 30 x 27 in.
Nominal Cfm17,50021,00024,500
Maximum Allowable Cfm25,00030,00030,000
Maximum Allowable Rpm750750750
Shaft Diameter at Pulley (in.)1
EVAPORATOR-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp15.020.025.030.0
Motor Frame Size254T256T284T286T
Efficiency at Full Load (%)
Standard Efficiency84.587.587.188.3
High Efficiency†90.091.091.792.4
Fan Pulley Pitch Diameter (in.)13.713.713.715.5
Motor Pulley Pitch Diameter (in.)4.55.15.55.9
Resulting Fan Rpm555625660700
Belts Quantity...Model No.
48 Series and 50 Series, Horizontal Discharge2...5VX11202...5VX11502...5VX11502...5VX1180
50 Series, Vertical Discharge2...5VX12302...5VX12302...5VX12302...5VX1230
Center Distance Range (in.)
48 Series and 50 Series, Horizontal Discharge48.25...44.0048.25...44.0048.50...44.2548.50...44.25
OPTIONAL POWER EXHAUSTCentrifugal, 18 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp2...5.02...7.52...10.0
Motor Frame Size184T213T215T
Efficiency at Full Load (%)84.082.985.6
Fan Pulley Pitch Diameter (in.)10.610.610.6
Motor Pulley Pitch Diameter (in.)4.55.05.6
Shaft Diameter at Pulley (in.)1
Resulting Fan Rpm740820920
Maximum Allowable Rpm925925925
FILTERS
Standard Efficiency
Throwaway (Standard)15...20 x 25 x 215...20 x 25 x 215...20 x 25 x 2
Quantity...Size (in.)5...16 x 20 x 25...16 x 20 x 25...16 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)15...20 x 25 x 215...20 x 25 x 215...20 x 25 x 2
Quantity...Size (in.)5...16 x 20 x 25...16 x 20 x 25...16 x 20 x 2
High Efficiency (90%) Bag Filters
with Prefilters (Optional)6...20 x 24 x 226...20 x 24 x 226...20 x 24 x 22
Quantity...Size (in.)6...24 x 24 x 226...24 x 24 x 226...24 x 24 x 22
TXV...2TXV...2TXV..2
11
⁄
16
7
⁄
16
TXV — Thermostatic Expansion Valve
*Data is for all 48 and 50 Series units of the size listed unless otherwise specified.
†Not available on 575-v units.
3
⁄8-in. Tube Diameter
1
⁄2-in. Tube Diameter
111⁄
16
17⁄
16
111⁄
17⁄
16
16
5
Table 2 — Operating Weights of Options and Accessories
OPTION OR ACCESSORY
Roof Curb
Condenser Section Roof Curb——540540625
Economizer300*300*530*530*530*
Power Exhaust600*600*710*710*710*
Barometric Relief200200200200200
High-Efficiency Filters2020202020
Bag filters3535404040
Hail Guard120150145145210
Copper Condenser Coil Fins180235235235420
Electric Heat†150150150150150
Inlet Guide Vanes9595115115115
vertical supply/return only.Field-fabricated ductwork should
be attached to the roof curb. Supply and return duct dimensions are shown in Fig. 3A-3C.
To attach ductwork to roof curb, insert duct approximately 10 to 11 in. up into roof curb. Connect ductwork to
14-gage roof curb material with sheet metal screws driven
from inside of the duct.
Secure all ducts to the building structure, using flexible
duct connectors between roof curb and ducts as required. Ducts
passing through an unconditioned space must be insulated
and covered with a vapor barrier. Outlet grilles must not lie
directly below unit discharge. The return duct must have a
90-degree elbow before opening into the building space if
unit is equipped with power exhaust.
Design supply duct strong enough to handle expected static
pressures.
6
UNIT
MODEL
48DJ,DK,NP034
50DW,DY,NB034
UNIT
SIZE
mmft-in.mmft-in.
660621-8
50DJ,DK,NP034613120-1
48DJ,DK,NP044
50DW,DY,NB044
782525-8
50DJ,DK,NP044734424-1
UNIT LEVELING TOLERANCES
DIMENSIONS*
(degrees and inches)
AB
Degin.Degin.
1.02.0.50.75
*From edge of unit to horizontal.
XY
1
⁄
16
3
⁄
8
1
⁄
16
1
⁄
8
405613- 311⁄
331110-103⁄
489316- 05⁄
414113- 71⁄
16
8
8
16
NOTES:
1. Roof curb is shipped unassembled.
2. Roof curb: 14 gage (VA03-56) steel.
3. Dimensions in [ ] are millimeters.
NOTE: To prevent the hazard of stagnant water build-up in the
drain pan of the indoor-air section, unit can only be pitched as
shown.
Fig. 3A — Roof Curb; 034, 044 Units
7
UNIT
MODEL
48DJ,DK,NP054,064
50DW,DY,NB054,064
UNIT
SIZE
mmft-in.mmft-in.mmft-in.
24748-1
50DJ,DK,NP054,06424588-0
48DJ,DK,NP074
50DW,DY,NB074
338311-1
50DJ,DK,NP074336711-0
UNIT LEVELING TOLERANCES
DIMENSIONS*
(degrees and inches)
AB
Degin.Degin.
1.02.0.50.75
*From edge of unit to horizontal.
XY Z
3
⁄8847627-911⁄16696522-103⁄
3
⁄4744424-51⁄
3
⁄16847627-911⁄16696522-103⁄
9
⁄16744424-51⁄
16
16
593319- 59⁄
593319- 59⁄
16
16
16
16
NOTES:
1. Roof curb is shipped unassembled.
2. Roof curb: 14 gage (VA03-56) steel.
3. Dimensions in [ ] are millimeters.
4. Suggested hole location for field wiring
through roof curb (holes to be field drilled).
NOTE: To prevent the hazard of stagnant water build-up in the
drain pan of the indoor-air section, unit can only be pitched as
shown.
Fig. 3B — Roof Curb; 054-074 Units
8
UNIT
SIZE
DIMENSION X
mmFt-in.
054,0642700-10
0742550-101⁄
UNIT LEVELING TOLERANCES
DIMENSIONS*
5
⁄
8
16
Degin.Degin.
(degrees and inches)
AB
1.02.0.50.75
*From edge of unit to horizontal.
NOTE: To prevent the hazard of stagnant water
build-up in the drain pan of the indoor-air section,
unit can only be pitched as shown.
Fig. 3C — Condenser Section Roof Curb (054-074 Units Only)
9
Condensate Drains — See Fig. 4A-4D and Fig. 5 for
drain locations. The drain assemblies, each consisting of a
10-gage plate with a 11⁄4-in. half coupling welded to it, are
shipped in the unit fan section. Also included are 16-gage
seal plates to cover the drain holes not being used. Open the
access door marked FANSECTION to find the drain assemblies, seal plates, and 4 screws for each mounting taped to
the unit basepan.
After the unit has been set in place on the roof:
1. Select the appropriate drain locations. The 034 units have
6 drain holes (3 per side), and the 044-074 units have 8
drain holes (4 per side). Two holes on each side must be
selected for condensate drains as shown in Fig. 5, and the
remaining holes must be sealed.
2. Remove the drain assemblies and attach them to the bottom of the unit base rails at the preferred drain locations
using the screws provided. See Fig. 6.
NOTE: Use a trap at least 4-in. deep.
3. Cover the remaining drain holes with the seal plates and
screws provided. See Fig. 7.
4. Apply a bead of RTV or similar sealant around the drain
assemblies and seal plates where they attach to the base
rail. See Fig. 8.
NOTE: If unit is slab mounted, holes will need to be drilled
in the side of the base rail and the holes factory-drilled in the
bottom of the base rail will need to be plugged.
Install Outdoor Hoods
UNIT SIZES 034 AND 044
25% Outdoor-Air Hoods (Units Without Economizer
Option)
1. Outdoor-air hoods are shipped bolted to the unit in a shipping position. Remove the 6 screws holding each 25% air
hood shipping cover in place.
2. Replace the 6 screws.
3. Remove the holddown screw from each upper corner of
each hood.
4. Pivot hoods outward (2 hoods total).
5. Install 17 screws around outside of each hood. (Screws
are in the fastener package taped to the basepan inside
the fan section.)
6. Apply a bead of RTV or similar sealant to corner of each
hood at pivot point to prevent water leaks. See Fig. 9.
Economizer Hoods (Units WithEconomizer Option) — Follow the same procedure described in 25% Outdoor-Air Hoods
section above.
UNIT SIZES 054-074
25% Outdoor-Air Hoods — The outdoor-air hoods are fac-
tory installed on the 054-074 units.
Economizer Hoods (Units With Economizer Option)
1. Remove the 6 screws holding each of the 4 economizer
shipping covers in place.
2. Replace the screws.
3. Remove the holddown screw from each upper corner of
each economizer hood.
4. Pivot hoods outward. (There is a total of 4 hoods.)
5. Install 18 screws, (5 each side, 6 top, and 2 bottom), around
the outside of each hood. (Screws are in the fastener package taped to the basepan inside the fan section.)
6. Apply a bead of RTV or similar sealant to corner of economizer hood at pivot point to prevent water leaks. (See
Fig. 9.)
Outdoor-Air Inlet Adjustments
MANUALOUTDOOR-AIRDAMPER (Units WithoutEconomizer Option) —All units except those equipped with a factoryinstalled economizer have a manual outdoor-air damper to
provide ventilation air. This damper can be preset to admit
up to 25% outdoor air into the return-air compartment. To
adjust, loosen the blade limiter screws as shown in Fig. 10
and move the damper to the desired position. Then retighten
the blade limiter screws to secure the damper. See Fig. 10.
(T omake this adjustment, it is necessary to remove the screens
covering the hood opening and make adjustments from inside the hood.)
ECONOMIZER SETTINGS
Enthalpy Sensor (See Fig. 11.) — This sensor is located be-
hind the filters in the end economizer hood (the upper hood
on sizes 054-074). See Fig. 12. For maximum benefit of outdoor air, set enthalpy sensor control to the A setting. At this
setting, when the relative humidity is 50%, and the outdoor
air is below 74 F, the sensor’s relay contacts will be closed.
See Fig. 13 and 14.
NOTE: Enthalpy control setting dial is on the economizer
motor.
Mixed-Air Thermistor (MAT) — This control set point adjustment is on the top of the economizer motor. This motor
is located in the return-air section, and is accessed by opening the access panel marked FILTER SECTION. See
Fig. 15. Set MAT set point adjustment dial to the desired
setting. The factory setting is 55F±5°F;range is 40 to
90 F. The MAT is located on the filter rack.
Damper Vent Position — The position setting adjustment is
located on the cover of the economizer motor. See Fig. 15.
Adjust by setting the fan switch at ON position (continuous
fan operation), and setting the system selector switch to OFF
position. Then turn adjustment screw slowly until the dampers assume the desired vent position. Do not manually operate the damper motor; damage to the motor may result.
Economizer Damper Linkage Adjustment — When replacing economizer damper motors, or if the linkage has come
loose, it is critical that the linkages be adjusted correctly.
They are sensitive, and incorrect adjustment can cause the
motor to stall.
NB,NPUnitMinimum Position Set Point — Minimum economizer position is set using the keypad and display module.
Refer to Control and Troubleshooting literature for more
details.
10
UNITSIZE
48DJD,DKD,NPD
48DJE,NPE5770 2617 4474 14-81⁄
WEIGHTABCDEFGHJ
lbkg mmft-in. mmft-in.mmft-in.mm ft-in. mmft-in.mmft-in.mm ft-in. mm ft-in. mmft-in.
2.Center ofGravity includeseconomizer.Unit weightdoes
not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans
16
Control Box End — 68-09
Sides — 68-09
Economizer End — 68-09 (except power exhaustunits 108-09)
Forsmaller service and operational clearances, contact Carrier Product Engineering Department.
4. Vertical discharge ducts designed to be attached to
accessory roof curb. If unit is mounted on dunnage,
support the ducts using cross bracesas doneon the
accessory roof curb.
5. When unit is slab mounted, locate the condensate
drain as low as possible on vertical face of base rail
atthe samelocation asthe standard condensatedrain
(usingfactory suppliedfitting). Plugfactory drilled condensate hole.
16
2
Fig. 4A — Base Unit Dimensional Drawing; 48DJ,DK,NP/50DW,DY,NB034,044 Units
2.Center of Gravity includes economizer. Unit
weight does not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans
Control Box End — 68-09
Sides — 68-09
EconomizerEnd —68-09 (except power exhaust units
108-09)
Forsmaller service and operational clearances, contact Carrier Product Engineering Department.
4. Vertical discharge ducts designed to be attached to
accessory roof curb. If unit is mounted on dunnage,
support the ducts using cross bracesas doneon the
accessory roof curb.
5. When unit is slab mounted, locate the condensate
drain as low as possible on vertical face of base rail
atthe samelocation asthe standard condensatedrain
(usingfactory suppliedfitting). Plugfactory drilled condensate hole.
8
Fig. 4B — Base Unit Dimensional Drawing; 50DJ,DK,NP034,044 Units
Economizer End — 68-09 (except power exhaust units 108-09)
For smaller service and operational clearances, contact Carrier Product Engineering
Department.
4. Verticaldischarge ductsdesigned tobe attachedto accessoryroof curb.If unitis mounted
on dunnage, support the ducts using cross braces as done on the accessory roof curb.
5. When unit is slab mounted, locate the condensate drain as low as possible on vertical
face of base rail at the same location as the standard condensate drain (using factory
supplied fitting). Plug factory drilled condensate hole.
Fig. 4C — Base Unit Dimensional Drawing; 48DJ,DK,NP/50DW,DY,NB054-074 Units
*Dimension shown is for 48 series units. On 50 series units, dimension given
is measured from economizer end of unit to drain connection closest to condenser fans.
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of Gravity includes economizer. Unit weight does not include
3. Unit clearances:
economizer.
Top — Do not restrict condenser fans
Control Box End — 68-09
Sides — 68-09 (except power exhaust units 108-09)
Economizer End — 68-09 (except power exhaust units 108-09)
For smallerservice and operational clearances, contactCarrier Product Engineering Department.
4. Verticaldischarge ducts designed to be attached to accessory roof curb. If
unit is mounted on dunnage, support the ducts using cross braces as done
on the accessory roof curb.
5. When unit is slab mounted, locate the condensate drain as low as possible
on vertical face of base rail at the same location as the standard condensate drain (using factory supplied fitting). Plug factory drilled condensate
hole.
2
2
Fig. 4D — Base Unit Dimensional Drawing; 50DJ,DK,NP054-074 Units
14
034 UNITS
044-074 UNITS
Fig. 5 — Drain Location Selection
Fig. 6 — Condensate Drain Location
ROOF MOUNT DRAIN
SLAB MOUNT DRAIN
Fig. 8 — Condensate Drain Piping Details
Fig. 7 — Seal Plate Location
Fig. 9 — Outdoor-Air Hood
15
Fig. 12 — Enthalpy Sensor Location
Fig. 10 — Outdoor-Air Damper Adjustments
(Inside of Hood Shown)
ENTHALPY
SENSOR
O
CONTROL
CURVE
A73
B68
C63
D58
CONTROL
POINT
(Approx Deg)
AT 50% RH
Fig. 13 — Psychrometric Chart for
Enthalpy Control
Fig. 11 — Enthalpy Sensor
16
NOTES:
1. Switches shown in high enthalpy state. Terminals 2 and 3 close
on enthalpy decrease.
2. When standard economizer is used with accessory differential enthalpy sensor, set enthalpy control to ‘‘D’’ setting.
Fig. 14 — Wiring Connections for Solid-State
Enthalpy Sensor (HH57AC077)
Fig. 15 — Mixed-Air Thermistor and Economizer
Position Setting Adjustments
(Top of Economizer Motor)
Field Wire Routing
UNIT SIZES 034 AND 044 — Field wiring can be brought
into the unit through the basepan and roof curb or through
the corner post in the side of the unit next to the control box.
A 3-1/2 in. NPT coupling for field power and a 3/4-in.
NPT coupling for 24 v control wiring are provided in the
basepan. There are two 4-5/8 in. knockouts in the corner post
for field power wiring.
If field power wiring is brought through the roof curb, route
wiring out through one of the 4-5/8 in. knockouts to the fieldsupplied disconnect and then back into the unit through the
other knockout. See Fig. 16 for recommended disconnect
location.
If power wiring is brought through the side of the unit,
route wiring from field-supplied disconnect through top
4-5/8 in. knockouts into unit.
If control wiring is to be brought in through the side of the
unit, a 7/8-in. diameter hole must be drilled in the corner
post next to the control box.
UNIT SIZES 054-074 — Field wiring is brought into the
unit through the bottom of the control box. Wiring can be
brought through the roof curb through field-supplied watertight connections. See Fig. 17.
A 4-5/32 in. hole for field power wiring and a 7/8-in. hole
for 24 v control wiring are provided in the bottom of the
control box. Field-supplied couplings must be used when routing wiring into the control box.
See Fig. 17 for recommended disconnect location.
Field Electrical Connections
IMPORTANT: The 48/50DK,DY,NB,NP units generate, use, and can radiate radio frequency energy. If units
are not installed and used in accordance with these
instructions, they may cause radio interference. They
have been tested and found to comply with limits of a
Class A computing device as defined by FCC (Federal
Communications Commission) regulations, Subpart J
of Part 15, which are designed to provide reasonable
protection against such interference when operated in
a commercial environment.
Use care when drilling into corner post to avoid damage to condenser coil.
Fig. 16 — Disconnect Location, 034 and 044 Units
(50 Series Vertical Discharge Unit Shown)
17
Use care when drilling into corner post to avoid damage to condenser coil.
Fig. 17 — Disconnect Location, 054-074 Units
(50 Series Horizontal Discharge Shown)
POWER WIRING — Units are factory wired for the voltage
shown on the unit nameplate. The main terminal block is
suitable for use with aluminum or copper wires. Maximum
wire size is 3/0 AWG (American Wire Gage).
When installing units, provide a disconnect per NEC
(National Electrical Code) of adequate size (MOCP [Maximum Overcurrent Protection] of unit is on the informative
plate). All field wiring must comply with NEC and all local
codes. Size wire based on MCA (Minimum Circuit Amps)
on the unit informative plate. See Fig. 18 for power wiring
connections to the unit power terminal block and equipment
ground.
Operating voltage to the compressor must be within the
voltage range indicated on the unit nameplate. Voltages between phases must be balanced within 2%, and the current
must be balanced within 10%. See Tables 3-7 for unit electrical data.
Use the following formula to determine the percent
voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 1 464 1 455
3
1371
=
3
457
=
Determine maximum deviation from average voltage:
(AB) 457 – 452=5v
(BC) 464 – 457=7v
(AC) 457 – 455=2v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact local utility immediately.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may
cause damage to electrical components.
18
Table 3 — Electrical Data, 034 Units
COMPR
VOLTAGE
RANGE
187-25453.2266.053.2266.010.8
CV— Constant Volume
ETL— ETL Testing Laboratory
FLA— Full Load Amps
Hp— Nominal Horsepower
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps (for wire sizing)
MOCP — Maximum Overcurrent Protection
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Electric heat available on 50 Series vertical discharge units.
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit operating voltage, multiply 240 v,
480 v, or 575 v capacity by appropriate multiplier below.
2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series
units only.
CV— Constant Volume
ETL— ETL Testing Laboratory
FLA— Full Load Amps
Hp— Nominal Horsepower
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps (for wire sizing)
MOCP — Maximum Overcurrent Protection
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Electric heat available on 50 Series vertical discharge units.
†108 kW available on CV applications only.
NO. 1
RLALRARLALRA
LEGEND
COMPR
NO. 2
OFMIFM
Total
FLA
BASE UNIT
ONLY
HpFLAMCAMOCP
7.59.065.880
10.011.067.890
15.017.073.890
20.022.078.8100
NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit operating voltage, multiply 240 v,
480 v, or 575 v capacity by appropriate multiplier below.
2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series
units only.
EXHAUST
FAN
TotalHpTotal
10.012.2——78.0100
15.018.0——83.8100
10.012.23636.078.0100
10.012.27272.0101.3110
10.012.2108† 108.0146.2150
15.018.03636.083.8100
15.018.07272.0101.3110
15.018.0108† 108.0146.2150
10.012.2——80.0100
15.018.0——85.8100
10.012.23636.080.0100
10.012.27272.0103.7110
10.012.2108† 108.0148.7150
15.018.03636.085.8100
15.018.07272.0103.7110
15.018.0108† 108.0148.7150
10.012.2——86.0100
15.018.0——91.8110
10.012.23636.086.0100
10.012.27272.0111.2125
10.012.2108† 108.0156.2175
15.018.03636.091.8110
15.018.07272.0111.2125
15.018.0108† 108.0156.2175
10.012.2——91.0110
15.018.0——96.8110
10.012.23636.091.0110
10.012.27272.0117.5150
10.012.2108† 108.0162.5175
15.018.03636.096.8110
15.018.07272.0117.5150
15.018.0108† 108.0162.5175
HEATER kW
RATING
Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.