Carrier NP034-074 User Manual

48DJ,DK,NP034-074
50DJ,DK,DW,DY,NB,NP034-074
Single Package Heating and Cooling Units
Installation, Start-Up and
Service Instructions
CONTENTS
Page
GENERAL ...................................2
SAFETY CONSIDERATIONS ...................2
INSTALLATION .............................2-37
Rigging and Unit Placement ..................2
Roof Curb ...................................2
Roof Mount ..................................2
Slab Mount ..................................2
Positioning ..................................3
Field-Fabricated Ductwork ....................6
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
Outdoor-Air Inlet Adjustments ...............10
• MANUAL OUTDOOR-AIR DAMPER
• ECONOMIZER SETTINGS
Field Wire Routing ..........................17
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
Field Electrical Connections .................17
• POWER WIRING
• CONTROL WIRING
Gas Piping (48 Series Units Only) ............36
Installing Flue/Inlet Hoods (48 Series Units
Only) ......................................36
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
PRE-START-UP ............................38-41
Evaporator-Fan Shipping Brackets ...........38
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
Refrigerant Service Valves ...................38
Crankcase Heaters ..........................38
Gas Manifold Pressure (48 Series
Units Only) ................................39
Unit Voltage ................................39
Leak Test and Dehydration ..................39
Evaporator-Fan Belts, Pulleys, and Sheaves ..39
Return-Air Filters ...........................40
Economizer Inlet Screens ...................40
Economizer Dampers .......................40
25% Outdoor-Air Damper ....................40
START-UP .................................41,42
Operating Sequences .......................41
• COOLING, UNITS WITHOUT ECONOMIZER
• HEATING, UNITS WITHOUT ECONOMIZER
• COOLING, UNITS WITH ECONOMIZER
Page
• HEATING, UNITS WITH ECONOMIZER
• VENTILATION AIR CIRCULATION (Continuous Fan)
• AUTOMATIC CHANGEOVER USING AUTOMATIC CHANGEOVER THERMOSTAT
Head Pressure Control ......................42
SERVICE ..................................42-53
Service Access .............................42
• COMPRESSORS
• LIQUID SERVICE VALVES, FILTER DRIERS, AND SIGHT GLASSES
• EVAPORATOR-FAN MOTORS, PULLEYS, AND BELTS
• POWER EXHAUST MOTORS, PULLEYS, AND BELTS
• UNIT CONTROL BOX
• GAS HEAT SECTION (48 Series Units Only)
• MAIN AND PILOT BURNERS (48 Series Units Only)
• FLUE GAS PASSAGEWAYS (48 Series Units Only)
• COMBUSTION AIR BLOWER (48 Series Units Only)
• ECONOMIZER DAMPER MOTOR
• ELECTRIC HEATER CONTROL BOX (50 Series Units Only)
• HEATER BOX (50 Series Units Only)
• 25% OUTDOOR-AIR DAMPER
• MODULATING POWER EXHAUST DAMPER MOTOR
• RETURN-AIR FILTERS
• CONDENSER FANS AND FAN MOTORS
• INLET GUIDE VANE MOTOR
Cleaning ....................................45
Lubrication .................................45
• COMPRESSORS
• FAN SHAFT BEARINGS
• INLET GUIDE VANE BEARINGS (Units With Optional Inlet Guide Vanes)
• FAN MOTOR BEARINGS
• DOOR HINGES
Adjustments ................................46
• EVAPORATOR FAN AND POWER EXHAUST MOTOR PLATE
• MODULATING POWER EXHAUST DIFFERENTIAL PRESSURE SWITCH
• INLET GUIDE VANE DIFFERENTIAL PRESSURE SWITCH (Units With Optional Inlet Guide Vanes and Static Pressure Control)
• BELT INSTALLATION AND TENSIONING
• PULLEY ALIGNMENT
• INSTALLING ALTERNATE MOTOR PULLEY (Evaporator Fan Only)
• CONDENSER FAN ADJUSTMENT
• 25% OUTDOOR-AIR DAMPER
• REFRIGERANT CHARGE
• PILOT LIGHT OFF (48 Series Units Only)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 Tab 1a 1b
PC 111 Catalog No. 564-818 Printed in U.S.A. Form 48/50D,N-9SI Pg 1 3-96 Replaces: 48DJ,DK-3SI;
48/50NB,NP-1SI; 50DJ,DK-9SI
CONTENTS (cont)
• AUTOMATIC PILOT ADJUSTMENT (48 Series Units Only)
• GAS VALVE ADJUSTMENT (48 Series Units Only)
• MAIN BURNER ADJUSTMENT (48 Series Units Only)
Main Burner Removal (48 Series Units Only) ..50
Refrigerant Feed Components ...............50
Thermostatic Expansion Valve (TXV) .........50
Liquid Line Service Valve ....................51
Compressor Discharge Service Valve ........51
Compressor Suction Service Valve ...........51
Protective Devices ..........................51
• COMPRESSOR PROTECTION
• EVAPORATOR-FAN MOTOR PROTECTION
• CONDENSER-FAN MOTOR PROTECTION
• HIGH- AND LOW-PRESSURE SWITCHES
Relief Devices ..............................51
Control Circuit, 115 V .......................52
Control Circuit, 24 v .........................52
Electric Heat (50 Series Units Only) ..........52
• OVERCURRENT
• OVERTEMPERATURE
Gas Heat (48 Series Units Only) ..............52
• LIMIT SWITCHES
• ROLLOUT SWITCH
TROUBLESHOOTING ......................52-69
• ECONOMIZER MOTOR CHECKOUT
• ECONOMIZER CONTROL BOARD CHECKOUT
• BASIC CHECK
• DETAILED CHECK
START-UP CHECKLIST .....................CL-1
Before performing service or maintenance operations on unit, turn offmain power switch to unit. Electrical shock could cause personal injury.
Do not try to light any appliance. Do not touch any elec­trical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you can­not reach your gas supplier, call the fire department.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Re­fer to this manual. For assistance or additional infor­mation, consult a qualified installer, service agency, or the gas supplier.
Disconnect gas piping from 48 Series units when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pres­sure greater than 0.5 psig, it must be replaced. When pressure testing field-supplied gas piping at pressures of
0.5 psig or less, the unit connected to such piping must be isolated by manually closing the gas valve.
GENERAL
This installation instruction contains base unit installa­tion, start-up, and service instructions only. For complete in­formation on PIC (Product Integrated Controls) and variable­air volume (VAV) controls and troubleshooting, refer to appropriate Controls and Troubleshooting literature also en­closed in this literature packet.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American Na­tional Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
INSTALLATION
Riggingand UnitPlacement —
portation damage. File claim with transportation agency. Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Sheets of plywood placed along the condenser coils will provide additional protection. All lifting lugs MUST be used when lifting unit. Level by using unit frame as a reference. See Fig. 1 for information. Unit and accessory weights are shown in Tables 1A, 1B, and 2. Weight distribution and center of gravity can be found in Fig. 2.
Inspect unit for trans-
Roof Curb — Assemble and install as described in in-
structions shipped with the accessory. Accessory roof curb and information required to field fabricate a roof curb is shown in Fig. 3A-3C. Install insulation, cant strips, roofing and counter flashing as required. For unit condensate drains to function properly, curb must be level or within tolerances shown in Fig. 3A-3C.
Roof Mount — Check building codes for weight distri-
bution requirements. Unit weight is shown in Tables 1A and 1B. Unit may be mounted on class A, B, or C roofing material.
Slab Mount — Provide a level concrete slab that ex-
tends beyond unit cabinet at least 6 inches. Make a slab 8 in. thick with 4 in. above grade. Use gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob­structing airflow.
2
NOTES:
1. Sizes 034,044:Rigwith4 cables and spread with two 95 in. (2413 mm) and 2 8A 1 A8 long spreader bars. Sizes 054-074:Rigwith 4 cables and spread withfour 95 in. (2413 mm) and 2 8A 1 B 1 A8 long spreader bars.
2. Center of gravity includes economizer.
RIGGING WEIGHTS AND DIMENSIONS
1. All panels must be in place when rigging.
2. Unit is not designed for handling by forklift truck.
UNIT
48DJD,DKD,NPD034 5941 2694.8
48DJE,NPE034 6070 2753.4 110.4 2804
48DJD,DKD,NPD044 6841 3103.1
48DJE,NPE044 6970 3161.6 128.6 3267
48DJD,DKD,NPD054 9230 4186.7
48DJE,NPE054 9350 4241.2
48DJD,DKD,NPD064 9530 4322.8
48DJE,NPE064 9650 4377.2
48DJD,DKD,NPD074 9950 4513.3
48DJE,NPE074 10,080 4572.3
50DJ,DK,NP034 5700 2585.5 84.8 2153 120.8 3067
50DW,DY,NB034 6270 2844.1 76.4 1940 102.5 2604
50DJ,DK,NP044 6350 2880.4 92.6 2353 126.6 3216
50DW,DY,NB044 6920 3138.9 86.0 2185 108.4 2753
50DJ,DK,NP054 8230 3733.1 120.8 3066 126.8 3221
50DW,DY,NB054 8780 3982.6 109.0 2769 109.0 2769
50DJ,DK,NP064 8530 3869.2 120.9 3071 120.9 3071
50DW,DY,NB064 9080 4119.7 120.8 3066 126.8 3221
50DJ,DK,NP074 8960 4064.3 131.7 3345 137.6 3495
50DW,DY,NB074 9500 4309.2 109.0 2769 109.0 2769
*Includes optional economizer.
UNIT WEIGHT* A B
Lb Kg in. mm in. mm
86.0 2185
92.6 2353
121.5 3086 126.8 3221
134.7 3421 134.7 3421
Fig. 1 — Rigging Label
109.4 2780
127.6 3240
If roof curb is not used, support unit with steel beams along
its entire length and then support steel as required.As a mini­mum, unit must be supported across its width at each lifting lug location.
Positioning — Provideclearance around and above unit
for airflow,safety,and service access. Do not restrict top (area above condenser fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
On units equipped with or power exhaust option, high ve­locity air is exhausted out the hoods. Unit should be posi­tioned with at least 10 ft clearance between the exhaust hoods and any obstruction. Although unit is weatherproof, guard against water from higher level runoff and overhangs.
3
Table 1A — Physical Data; 034, 044 Units
BASE UNIT* 034 044 NOMINAL CAPACITY (tons) 30 40 OPERATING WEIGHT (lb)
Base Unit
48 Series, Low Heat 5641 6541 48 Series, High Heat 50 Series, Horizontal Discharge 5970 6620 50 Series, Vertical Discharge 5400 6050
With Economizer
48 Series, Low Heat 5941 6841 48 Series, High Heat 6070 6970 50 Series, Horizontal Discharge 6270 6920 50 Series, Vertical Discharge 5700 6350
COMPRESSORS
Quantity...Type 2...06D 2...06E Capacity Steps (%) 17, 33, 50, 66, 83, 100 25, 50, 75, 100 Number of Refrigerant Circuits 22
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
Without Hot Gas Bypass With Hot Gas Bypass 31.0/29.0 42.0/40.0
CONDENSER COILS
Quantity 22 Rows...Fins/in.
Aluminum Copper (Optional) 3...13.7 3...13.7
Total Face Area (sq ft) 37.5 50.0
EVAPORATOR COILS
Quantity Rows...Fins/in. 3...15.0 3...15.0 Total Face Area (sq ft) 32.1 45.5 Refrigerant Feed Device...No. per Circuit TXV...1 TXV...2
HEATING SECTION (48 Series Units Only) Low Heat High Heat Low Heat High Heat
Number of Heat Exchangers Input (MBtuh) 264 529 264 529 Output (MBtuh) 211 423 211 423 Temperature Rise Range (F) 0-30 15-45 0-30 15-45 Efficiency (%) 79 79 79 79 Burner Orifice Diameter
Quantity (in. ...drill no.) 6 (.1285...30) 12 (.1285...30) 6 (.1285...30) 12 (.1285...30)
Pilot Orifice Diameter
Quantity (in. ...drill no.) 1 (.076...48) 2 (.076...48) 1 (.076...48) 2 (.076...48)
Firing Stages 2222 Number of Gas Valves
CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 2...30 3...30 Nominal Cfm 18,600 26,000 Motor Hp...Rpm 1.0...1140 1.0...1140
EVAPORATOR FAN Centrifugal 25 x 25 in.
Nominal Cfm 10,500 14,000 Maximum Allowable Cfm 15,000 20,000 Maximum Allowable Rpm 900 900 Shaft Diameter at Pulley (in.) 1
EVAPORATOR-FAN MOTOR AND DRIVE (Any motor available on any unit)
Motor Hp 7.5 10.0 15.0 20.0 Motor Frame Size 213T 215T 254T 256T Efficiency at Full Load (%)
Standard Efficiency 82.9 85.6 84.5 87.5
High Efficiency† 89.5 90.0 91.0 Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 13.7 Motor Pulley Pitch Diameter (in.) 34.4 4.3 4.9 5.5 Resulting Fan Rpm 405 510 580 660 Belts Quantity...Model No.
48 Series and 50 Series, Horizontal Discharge 2...BX60 2...5VX630 2...5VX630 2...5VX630
50 Series, Vertical Discharge 2...BX60 2...5VX630 2...5VX630 2...5VX630 Center Distance Range (in.)
48 Series and 50 Series, Horizontal Discharge 17.74...14.30 17.74...14.30 17.63...14.01 17.63...14.01
50 Series, Vertical Discharge 19.86...15.87 19.86...15.87 19.04...15.00 19.04...15.00
OPTIONAL POWER EXHAUST Centrifugal, 15 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp 2...3.0 2...5.0 2...7.5 Motor Frame Size 56HZ 184T 213T Efficiency at Full Load (%) 81.0 84.0 82.9 Fan Pulley Pitch Diameter (in.) 6.9 6.9 6.9 Motor Pulley Pitch Diameter (in.) 3.35 4.12 5.0 Shaft Diameter at Pulley (in.) 1 Resulting Fan Rpm 843 1040 1264 Maximum Allowable Rpm 1300 1300 1300 Belts Quantity...No. 2...3VX670 2...3VX670 2...3VX710
FILTERS
Standard Efficiency Throwaway (Standard) 12...20 x 25 x 2 12...20 x 25 x 2
Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 Medium Efficiency (30%) Pleated (Optional) 12...20 x 25 x 2 12...20 x 25 x 2
Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 High Efficiency (90%) Bag Filters with Prefilters (Optional) 6...20 x 24 x 22 6...20 x 24 x 22
Quantity...Size (in.) 6...20 x 20 x 22 6...20 x 20 x 22
612612
1212
3
TXV — Thermostatic Expansion Valve *Data is for all 48 and 50 Series units of the size listed unless otherwise specified.
†Not available on 575-v units.
5770 6670
Semi-Hermetic
29.0/29.0 40.0/40.0
3
⁄8-in. Tube Diameter
3...15.0 3...15.0
1
12
11
16
16
⁄2-in. Tube Diameter
13⁄
16
111⁄
16
13⁄
16
4
Table 1B — Physical Data; 054-074 Units
BASE UNIT* 054 064 074 NOMINAL CAPACITY (tons) 50 60 75 OPERATING WEIGHT (lb)
Base Unit
48 Series, Low Heat 8700 9000 9420 48 Series, High Heat 8820 9120 9550 50 Series, Horizontal Discharge 8250 8550 8970 50 Series, Vertical Discharge 7700 8000 8430
With Economizer
48 Series, Low Heat 9230 9530 9950 48 Series, High Heat 9350 9650 10,080 50 Series, Horizontal Discharge 8780 9080 9500 50 Series, Vertical Discharge 8230 8530 8960
COMPRESSORS Semi-Hermetic
Quantity...Type 2...06E 2...06E 2...06E Capacity Steps (%) 20, 40, 60, 80, 100 17, 33, 50, 66, 83, 100 14, 28, 43, 71, 85, 100 Number of Refrigerant Circuits 222
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
Without Hot Gas Bypass 59.0/44.5 61.0/61.0 70.5/64.5 With Hot Gas Bypass 62.0/44.5 64.0/61.0 73.5/64.5
CONDENSER COILS
Quantity 444 Rows...Fins/in.
Aluminum 2...17.0, 3...17.0 3...17.0 3...17.0 Copper (Optional) 2...15.7, 3...15.7 3...15.7 3...15.7
Total Face Area (sq ft) 72.4 72.4 108.4
EVAPORATOR COILS
Quantity 222 Rows...Fins/in. 3...17.0 4...17.0 4...17.0 Total Face Area (sq ft) 61.5 61.5 61.5 Refrigerant Feed Device...
No. per Circuit
HEATING SECTION (48 Series Units Only) Low Heat High Heat Low Heat High Heat Low Heat High Heat
Number of Heat Exchangers 12 18 12 18 12 18 Input (MBtuh) 540 810 540 810 540 810 Output (MBtuh) 432 648 432 648 432 648 Temperature Rise Range (F) 5-35 15-45 5-35 15-45 5-35 15-45 Efficiency (%) 80 80 80 80 80 80 Burner Orifice Diameter
Quantity (in. ...drill no.) 12 (.1285...30) 18 (.1285...30) 12 (.1285...30) 18 (.1285...30) 12 (.1285...30) 18 (.1285...30)
Pilot Orifice Diameter
Quantity (in. ...drill no.) 2 (.076...48) 3 (.076...48) 2 (.076...48) 3 (.076...48) 2 (.076...48) 3 (.076...48)
Firing Stages 222222 Number of Gas Valves 232323
CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 4...30 4...30 5...30 Nominal Cfm 40,000 40,000 50,000 Motor Hp...Rpm 1.0...1140 1.0...1140 1.0...1140
EVAPORATOR FAN Centrifugal 30 x 27 in.
Nominal Cfm 17,500 21,000 24,500 Maximum Allowable Cfm 25,000 30,000 30,000 Maximum Allowable Rpm 750 750 750 Shaft Diameter at Pulley (in.) 1
EVAPORATOR-FAN MOTOR AND DRIVE (Any motor available on any unit)
Motor Hp 15.0 20.0 25.0 30.0 Motor Frame Size 254T 256T 284T 286T Efficiency at Full Load (%)
Standard Efficiency 84.5 87.5 87.1 88.3
High Efficiency† 90.0 91.0 91.7 92.4 Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 15.5 Motor Pulley Pitch Diameter (in.) 4.5 5.1 5.5 5.9 Resulting Fan Rpm 555 625 660 700 Belts Quantity...Model No.
48 Series and 50 Series, Horizontal Discharge 2...5VX1120 2...5VX1150 2...5VX1150 2...5VX1180
50 Series, Vertical Discharge 2...5VX1230 2...5VX1230 2...5VX1230 2...5VX1230 Center Distance Range (in.)
48 Series and 50 Series, Horizontal Discharge 48.25...44.00 48.25...44.00 48.50...44.25 48.50...44.25
50 Series, Vertical Discharge 44.25...39.75 44.25...39.75 44.00...40.00 44.00...40.00
OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp 2...5.0 2...7.5 2...10.0 Motor Frame Size 184T 213T 215T Efficiency at Full Load (%) 84.0 82.9 85.6 Fan Pulley Pitch Diameter (in.) 10.6 10.6 10.6 Motor Pulley Pitch Diameter (in.) 4.5 5.0 5.6 Shaft Diameter at Pulley (in.) 1 Resulting Fan Rpm 740 820 920 Maximum Allowable Rpm 925 925 925
FILTERS
Standard Efficiency Throwaway (Standard) 15...20 x 25 x 2 15...20 x 25 x 2 15...20 x 25 x 2
Quantity...Size (in.) 5...16 x 20 x 2 5...16 x 20 x 2 5...16 x 20 x 2 Medium Efficiency (30%) Pleated (Optional) 15...20 x 25 x 2 15...20 x 25 x 2 15...20 x 25 x 2
Quantity...Size (in.) 5...16 x 20 x 2 5...16 x 20 x 2 5...16 x 20 x 2 High Efficiency (90%) Bag Filters with Prefilters (Optional) 6...20 x 24 x 22 6...20 x 24 x 22 6...20 x 24 x 22
Quantity...Size (in.) 6...24 x 24 x 22 6...24 x 24 x 22 6...24 x 24 x 22
TXV...2 TXV...2 TXV..2
11
16
7
16
TXV — Thermostatic Expansion Valve *Data is for all 48 and 50 Series units of the size listed unless otherwise specified.
†Not available on 575-v units.
3
⁄8-in. Tube Diameter
1
⁄2-in. Tube Diameter
111⁄
16
17⁄
16
111⁄
17⁄
16
16
5
Table 2 — Operating Weights of Options and Accessories
OPTION OR ACCESSORY
Roof Curb
Condenser Section Roof Curb 540 540 625 Economizer 300* 300* 530* 530* 530* Power Exhaust 600* 600* 710* 710* 710* Barometric Relief 200 200 200 200 200 High-Efficiency Filters 20 20 20 20 20 Bag filters 35 35 40 40 40 Hail Guard 120 150 145 145 210 Copper Condenser Coil Fins 180 235 235 235 420 Electric Heat† 150 150 150 150 150 Inlet Guide Vanes 95 95 115 115 115
*Includes hood.
†50 Series vertical discharge units.
48DJ,DK,NP 50DW,DY,NB 50DJ,DK,NP
034 044 054 064 074
450 450 380
480 480 465
UNIT SIZE
515 560 515
515 560 515
515 560 515
UNIT
034 1754 1213 1216 1758 14- 9 3- 8 044 2035 1382 1385 2039 17- 3 3- 8
48DJD,DKD,NPD
48DJE,NPE
50DW,DY,NB
50DJ,DK,NP
NOTE: Weights include economizer.
054 2334 2276 2281 2339 19- 7 3-10 064 2431 2328 2334 2437 19- 7 3-10 074 2452 2518 2523 2457 21- 0 3-10 034 1781 1251 1253 1785 14- 8 3-10 044 2057 1424 1428 2061 17- 2 3-10 054 2375 2295 2300 2380 19- 7 3-10 064 2393 2373 2378 2506 19- 7 3-10 074 2494 2541 2546 2499 21- 0 3-10 034 1864 1268 1271 1867 13- 3 3-10 044 2070 1387 1389 2074 15-10 3-10 054 2381 2005 2009 2385 19-10 3-10 064 2461 2074 2078 2467 19-10 3-10 074 2551 2194 2199 2556 21- 3 3-10 034 1674 1173 1175 1678 13- 9 3-10 044 1879 1292 1295 1884 16- 3 3-10 054 2090 2021 2025 2094 18- 2 3-10 064 2188 2073 2077 2192 18- 2 3-10 074 2212 2263 2269 2216 21- 3 3-10
UNIT CENTER OF GRAVITYAND CORNER WEIGHTS
CORNER WEIGHT (lb) DIMENSIONS (Ft-in.)
1234 A B
Fig.2—Weight Distribution and Center of Gravity
Field-FabricatedDuctwork — Units are designed for
vertical supply/return only.Field-fabricated ductwork should be attached to the roof curb. Supply and return duct dimen­sions are shown in Fig. 3A-3C.
To attach ductwork to roof curb, insert duct approxi­mately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside of the duct.
Secure all ducts to the building structure, using flexible duct connectors between roof curb and ducts as required. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge. The return duct must have a 90-degree elbow before opening into the building space if unit is equipped with power exhaust.
Design supply duct strong enough to handle expected static
pressures.
6
UNIT
MODEL
48DJ,DK,NP 034
50DW,DY,NB 034
UNIT SIZE
mm ft-in. mm ft-in.
6606 21-8
50DJ,DK,NP 034 6131 20-1 48DJ,DK,NP 044
50DW,DY,NB 044
7825 25-8
50DJ,DK,NP 044 7344 24-1
UNIT LEVELING TOLERANCES
DIMENSIONS*
(degrees and inches)
AB
Deg in. Deg in.
1.0 2.0 .50 .75
*From edge of unit to horizontal.
XY
1
16
3
8
1
16
1
8
4056 13- 311⁄ 3311 10-103⁄ 4893 16- 05⁄ 4141 13- 71⁄
16
8
8
16
NOTES:
1. Roof curb is shipped unassembled.
2. Roof curb: 14 gage (VA03-56) steel.
3. Dimensions in [ ] are millimeters.
NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor-air section, unit can only be pitched as shown.
Fig. 3A — Roof Curb; 034, 044 Units
7
UNIT
MODEL
48DJ,DK,NP 054,064
50DW,DY,NB 054,064
UNIT SIZE
mm ft-in. mm ft-in. mm ft-in.
2474 8-1
50DJ,DK,NP 054,064 2458 8-0 48DJ,DK,NP 074
50DW,DY,NB 074
3383 11-1
50DJ,DK,NP 074 3367 11-0
UNIT LEVELING TOLERANCES
DIMENSIONS*
(degrees and inches)
AB
Deg in. Deg in.
1.0 2.0 .50 .75
*From edge of unit to horizontal.
XY Z
3
⁄88476 27-911⁄166965 22-103⁄
3
⁄47444 24-51⁄
3
⁄168476 27-911⁄166965 22-103⁄
9
⁄167444 24-51⁄
16
16
5933 19- 59⁄
5933 19- 59⁄
16
16
16
16
NOTES:
1. Roof curb is shipped unassembled.
2. Roof curb: 14 gage (VA03-56) steel.
3. Dimensions in [ ] are millimeters.
4. Suggested hole location for field wiring through roof curb (holes to be field drilled).
NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor-air section, unit can only be pitched as shown.
Fig. 3B — Roof Curb; 054-074 Units
8
UNIT
SIZE
DIMENSION X
mm Ft-in.
054,064 270 0-10
074 255 0-101⁄
UNIT LEVELING TOLERANCES
DIMENSIONS*
5
8 16
Deg in. Deg in.
(degrees and inches)
AB
1.0 2.0 .50 .75
*From edge of unit to horizontal. NOTE: To prevent the hazard of stagnant water
build-up in the drain pan of the indoor-air section, unit can only be pitched as shown.
Fig. 3C — Condenser Section Roof Curb (054-074 Units Only)
9
Condensate Drains — See Fig. 4A-4D and Fig. 5 for
drain locations. The drain assemblies, each consisting of a 10-gage plate with a 11⁄4-in. half coupling welded to it, are shipped in the unit fan section. Also included are 16-gage seal plates to cover the drain holes not being used. Open the access door marked FANSECTION to find the drain assem­blies, seal plates, and 4 screws for each mounting taped to the unit basepan.
After the unit has been set in place on the roof:
1. Select the appropriate drain locations. The 034 units have 6 drain holes (3 per side), and the 044-074 units have 8 drain holes (4 per side). Two holes on each side must be selected for condensate drains as shown in Fig. 5, and the remaining holes must be sealed.
2. Remove the drain assemblies and attach them to the bot­tom of the unit base rails at the preferred drain locations using the screws provided. See Fig. 6.
NOTE: Use a trap at least 4-in. deep.
3. Cover the remaining drain holes with the seal plates and screws provided. See Fig. 7.
4. Apply a bead of RTV or similar sealant around the drain assemblies and seal plates where they attach to the base rail. See Fig. 8.
NOTE: If unit is slab mounted, holes will need to be drilled in the side of the base rail and the holes factory-drilled in the bottom of the base rail will need to be plugged.
Install Outdoor Hoods
UNIT SIZES 034 AND 044 25% Outdoor-Air Hoods (Units Without Economizer
Option)
1. Outdoor-air hoods are shipped bolted to the unit in a ship­ping position. Remove the 6 screws holding each 25% air hood shipping cover in place.
2. Replace the 6 screws.
3. Remove the holddown screw from each upper corner of each hood.
4. Pivot hoods outward (2 hoods total).
5. Install 17 screws around outside of each hood. (Screws are in the fastener package taped to the basepan inside the fan section.)
6. Apply a bead of RTV or similar sealant to corner of each hood at pivot point to prevent water leaks. See Fig. 9.
Economizer Hoods (Units WithEconomizer Option) — Fol­low the same procedure described in 25% Outdoor-Air Hoods section above.
UNIT SIZES 054-074 25% Outdoor-Air Hoods — The outdoor-air hoods are fac-
tory installed on the 054-074 units. Economizer Hoods (Units With Economizer Option)
1. Remove the 6 screws holding each of the 4 economizer shipping covers in place.
2. Replace the screws.
3. Remove the holddown screw from each upper corner of each economizer hood.
4. Pivot hoods outward. (There is a total of 4 hoods.)
5. Install 18 screws, (5 each side, 6 top, and 2 bottom), around the outside of each hood. (Screws are in the fastener pack­age taped to the basepan inside the fan section.)
6. Apply a bead of RTV or similar sealant to corner of econo­mizer hood at pivot point to prevent water leaks. (See Fig. 9.)
Outdoor-Air Inlet Adjustments
MANUALOUTDOOR-AIRDAMPER (Units WithoutEcono­mizer Option) —All units except those equipped with a factory­installed economizer have a manual outdoor-air damper to provide ventilation air. This damper can be preset to admit up to 25% outdoor air into the return-air compartment. To adjust, loosen the blade limiter screws as shown in Fig. 10 and move the damper to the desired position. Then retighten the blade limiter screws to secure the damper. See Fig. 10. (T omake this adjustment, it is necessary to remove the screens covering the hood opening and make adjustments from in­side the hood.)
ECONOMIZER SETTINGS Enthalpy Sensor (See Fig. 11.) — This sensor is located be-
hind the filters in the end economizer hood (the upper hood on sizes 054-074). See Fig. 12. For maximum benefit of out­door air, set enthalpy sensor control to the A setting. At this setting, when the relative humidity is 50%, and the outdoor air is below 74 F, the sensor’s relay contacts will be closed. See Fig. 13 and 14.
NOTE: Enthalpy control setting dial is on the economizer motor.
Mixed-Air Thermistor (MAT) — This control set point ad­justment is on the top of the economizer motor. This motor is located in the return-air section, and is accessed by open­ing the access panel marked FILTER SECTION. See Fig. 15. Set MAT set point adjustment dial to the desired setting. The factory setting is 55F±5°F;range is 40 to 90 F. The MAT is located on the filter rack.
Damper Vent Position — The position setting adjustment is located on the cover of the economizer motor. See Fig. 15. Adjust by setting the fan switch at ON position (continuous fan operation), and setting the system selector switch to OFF position. Then turn adjustment screw slowly until the damp­ers assume the desired vent position. Do not manually op­erate the damper motor; damage to the motor may result.
Economizer Damper Linkage Adjustment — When replac­ing economizer damper motors, or if the linkage has come loose, it is critical that the linkages be adjusted correctly. They are sensitive, and incorrect adjustment can cause the motor to stall.
NB,NPUnitMinimum Position Set Point — Minimum econo­mizer position is set using the keypad and display module. Refer to Control and Troubleshooting literature for more details.
10
UNIT SIZE
48DJD,DKD,NPD 48DJE,NPE 5770 2617 4474 14-81⁄
WEIGHT A B C D E F G H J
lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
5641 2559 4498 14-9
034
50DW,DY,NB 5970 2708 4044 13-31⁄ 48DJD,DKD,NPD 48DJE,NPE 6670 2708 5229 17-17⁄
6541 2967 5255 17-27⁄
044
50DW,DY,NB 6620 3003 4823 15-97⁄
UNIT SIZE
KL
mm ft-in. mm ft-in. 48DJD,DKD,NPD 48DJE,NPE
034 4741 15-6 6797 22-3
50DW,DY,NB 48DJD,DKD,NPD 48DJE,NPE
044 5576 8-3
1
⁄28015 26-39⁄
50DW,DY,NB
1
8
3662 12-03⁄167278 23-109⁄161709 5-75⁄162216 7- 31⁄44228 13-107⁄162746 9-01⁄8— 3626 12-109⁄
8
4
8
4497 14-91⁄168496 27-101⁄22328 7-75⁄82091 6-105⁄164706 15-5 3363 11-03⁄83769 12-43⁄84762 15-71⁄
8
8
LEGEND
CONN — Connection DIM Dimension
NOTES:
1. Dimensions in [ ] are in millimeters.
5
8
2. Center ofGravity includeseconomizer.Unit weightdoes not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans
16
Control Box End — 68-09 Sides — 68-09 Economizer End — 68-09 (except power exhaustunits 108-09)
Forsmaller service and operational clearances, con­tact Carrier Product Engineering Department.
4. Vertical discharge ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, support the ducts using cross bracesas doneon the accessory roof curb.
5. When unit is slab mounted, locate the condensate drain as low as possible on vertical face of base rail atthe samelocation asthe standard condensatedrain (usingfactory suppliedfitting). Plugfactory drilled con­densate hole.
16
2
Fig. 4A — Base Unit Dimensional Drawing; 48DJ,DK,NP/50DW,DY,NB034,044 Units
11
UNIT SIZE
50DJ,DK,NP
UNIT SIZE
50DJ,DK,NP
WEIGHT A B C D E F G H
lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
034 5400 2449 4198 13-9 044 6050 2744 4948 16-2
JK
mm ft-in. mm ft-in.
034 4168 13-8
1
044 4999 16-413⁄167534 24-85⁄
1
⁄42916 9-613⁄166802 22-313⁄161711 5-73⁄82216 7- 31⁄44428 9-01⁄83762 12-43⁄8——
13
⁄163746 12-31⁄28015 26-39⁄162247 7-47⁄162091 6-105⁄163363 11-03⁄84306 14-11⁄23769 12-43⁄
⁄166321 20-87⁄
LEGEND
CONN — Connection DIM Dimension
NOTES:
8
1. Dimensions in [ ] are in millimeters.
8
2. Center of Gravity includes economizer. Unit weight does not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans Control Box End — 68-09 Sides — 68-09 EconomizerEnd —68-09 (except power exhaust units 108-09)
Forsmaller service and operational clearances, con­tact Carrier Product Engineering Department.
4. Vertical discharge ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, support the ducts using cross bracesas doneon the accessory roof curb.
5. When unit is slab mounted, locate the condensate drain as low as possible on vertical face of base rail atthe samelocation asthe standard condensatedrain (usingfactory suppliedfitting). Plugfactory drilled con­densate hole.
8
Fig. 4B — Base Unit Dimensional Drawing; 50DJ,DK,NP034,044 Units
12
UNIT SIZE
48DJD,DKD,NPD 48DJE,NPE 8820 4000 50DW,DY,NB 8250 3742 6045 19-10 7676 25-2 48DJD,DKD,NPD 48DJE,NPE 9120 4137 50DW,DY,NB 8550 3878 6045 19-10 7676 25-2 48DJD,DKD,NPD 48DJE,NPE 9550 4332 50DW,DY,NB 8970 4069 6477 21-3 7676 25-2
LEGEND
CONN — Connection DIM Dimension
*Dimension shown is for 48 series units. On 50 series units, dimension given is measured from
economizer end of unit to drain connection closest to condenser fans.
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity includes economizer. Unit weight does not include economizer.
3. Unit clearances: Top — Do not restrict condenser fans Control Box End — 68-09 Sides — 68-09 (except power exhaust units 108-09)
WEIGHT A B C D E F G
lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
054
064
074
8700 3946
9000 4082
9420 4273
5969 19-7 6717 22-0
5969 19-7 6717 22-0
6401 21-0 6717 22-0
7
16
1163 3-913⁄1611,524 37-911⁄
3
16
7
16
1163 3-913⁄1611,524 37-911⁄
3
16
7
16
1163 3-913⁄1612,433 40-91⁄
3
16
2718 8-11 6541 21-51⁄
16
2
11,140 36-69⁄
16
2830 9-33⁄46427 21-1 2718 8-11 6541 21-51⁄
16
2
11,140 36-69⁄
16
2830 9-33⁄46427 21-1 3543 11-71⁄25715 18-9
2
12,049 39-6
3
8
3694 12-13⁄45563 18-3
Economizer End — 68-09 (except power exhaust units 108-09) For smaller service and operational clearances, contact Carrier Product Engineering Department.
4. Verticaldischarge ductsdesigned tobe attachedto accessoryroof curb.If unitis mounted on dunnage, support the ducts using cross braces as done on the accessory roof curb.
5. When unit is slab mounted, locate the condensate drain as low as possible on vertical face of base rail at the same location as the standard condensate drain (using factory supplied fitting). Plug factory drilled condensate hole.
Fig. 4C — Base Unit Dimensional Drawing; 48DJ,DK,NP/50DW,DY,NB054-074 Units
13
UNIT SIZE
50DJ,DK,NP
054 7700 3493 064 8000 3629
Weight A B C D E F
Lb Kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
5537 18-2 1163 3-9
074 8430 3824 5969 21-3 1163 3-9
LEGEND
CONN — Connection DIM Dimension
*Dimension shown is for 48 series units. On 50 series units, dimension given is measured from economizer end of unit to drain connection closest to con­denser fans. NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity includes economizer. Unit weight does not include
3. Unit clearances:
economizer.
Top — Do not restrict condenser fans Control Box End — 68-09 Sides — 68-09 (except power exhaust units 108-09)
13
⁄1610,476 34-47⁄162864 9-43⁄410,092 33-15⁄165347 17-61⁄
13
⁄1611,385 37-41⁄43727 12-23⁄411,001 36-11⁄84483 14-81⁄
Economizer End — 68-09 (except power exhaust units 108-09) For smallerservice and operational clearances, contactCarrier Product En­gineering Department.
4. Verticaldischarge ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, support the ducts using cross braces as done on the accessory roof curb.
5. When unit is slab mounted, locate the condensate drain as low as possible on vertical face of base rail at the same location as the standard conden­sate drain (using factory supplied fitting). Plug factory drilled condensate hole.
2
2
Fig. 4D — Base Unit Dimensional Drawing; 50DJ,DK,NP054-074 Units
14
034 UNITS
044-074 UNITS
Fig. 5 — Drain Location Selection
Fig. 6 — Condensate Drain Location
ROOF MOUNT DRAIN
SLAB MOUNT DRAIN
Fig. 8 — Condensate Drain Piping Details
Fig. 7 — Seal Plate Location
Fig. 9 — Outdoor-Air Hood
15
Fig. 12 — Enthalpy Sensor Location
Fig. 10 — Outdoor-Air Damper Adjustments
(Inside of Hood Shown)
ENTHALPY SENSOR
O
CONTROL
CURVE
A 73 B 68 C 63 D 58
CONTROL
POINT
(Approx Deg)
AT 50% RH
Fig. 13 — Psychrometric Chart for
Enthalpy Control
Fig. 11 — Enthalpy Sensor
16
NOTES:
1. Switches shown in high enthalpy state. Terminals 2 and 3 close on enthalpy decrease.
2. When standard economizer is used with accessory differential en­thalpy sensor, set enthalpy control to ‘‘D’’ setting.
Fig. 14 — Wiring Connections for Solid-State
Enthalpy Sensor (HH57AC077)
Fig. 15 — Mixed-Air Thermistor and Economizer
Position Setting Adjustments
(Top of Economizer Motor)
Field Wire Routing
UNIT SIZES 034 AND 044 — Field wiring can be brought into the unit through the basepan and roof curb or through the corner post in the side of the unit next to the control box.
A 3-1/2 in. NPT coupling for field power and a 3/4-in. NPT coupling for 24 v control wiring are provided in the basepan. There are two 4-5/8 in. knockouts in the corner post for field power wiring.
If field power wiring is brought through the roof curb, route wiring out through one of the 4-5/8 in. knockouts to the field­supplied disconnect and then back into the unit through the other knockout. See Fig. 16 for recommended disconnect location.
If power wiring is brought through the side of the unit, route wiring from field-supplied disconnect through top 4-5/8 in. knockouts into unit.
If control wiring is to be brought in through the side of the unit, a 7/8-in. diameter hole must be drilled in the corner post next to the control box.
UNIT SIZES 054-074 — Field wiring is brought into the unit through the bottom of the control box. Wiring can be brought through the roof curb through field-supplied water­tight connections. See Fig. 17.
A 4-5/32 in. hole for field power wiring and a 7/8-in. hole for 24 v control wiring are provided in the bottom of the control box. Field-supplied couplings must be used when rout­ing wiring into the control box.
See Fig. 17 for recommended disconnect location.
Field Electrical Connections
IMPORTANT: The 48/50DK,DY,NB,NP units gener­ate, use, and can radiate radio frequency energy. If units are not installed and used in accordance with these instructions, they may cause radio interference. They have been tested and found to comply with limits of a Class A computing device as defined by FCC (Federal Communications Commission) regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
Use care when drilling into corner post to avoid damage to con­denser coil.
Fig. 16 — Disconnect Location, 034 and 044 Units
(50 Series Vertical Discharge Unit Shown)
17
Use care when drilling into corner post to avoid damage to con­denser coil.
Fig. 17 — Disconnect Location, 054-074 Units
(50 Series Horizontal Discharge Shown)
POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate. The main terminal block is suitable for use with aluminum or copper wires. Maximum wire size is 3/0 AWG (American Wire Gage).
When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (MOCP [Maxi­mum Overcurrent Protection] of unit is on the informative plate). All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 18 for power wiring connections to the unit power terminal block and equipment ground.
Operating voltage to the compressor must be within the voltage range indicated on the unit nameplate. Voltages be­tween phases must be balanced within 2%, and the current must be balanced within 10%. See Tables 3-7 for unit elec­trical data.
LEGEND
EQUIP — Equipment GND Ground NEC National Electrical Code TB Terminal Block
Fig. 18 — Field Power Wiring Connections
Use the following formula to determine the percent
voltage imbalance. % Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
452 1 464 1 455
3
1371
=
3
457
=
Determine maximum deviation from average voltage:
(AB) 457 – 452=5v (BC) 464 – 457=7v
(AC) 457 – 455=2v Maximum deviation is 7 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is be­low the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact local utility immediately.
Unit failure as a result of operation on improper line volt­age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
18
Table 3 — Electrical Data, 034 Units
COMPR
VOLTAGE
RANGE
187-254 53.2 266.0 53.2 266.0 10.8
CV Constant Volume ETL ETL Testing Laboratory FLA Full Load Amps Hp Nominal Horsepower IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps (for wire sizing) MOCP — Maximum Overcurrent Protection OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Electric heat available on 50 Series vertical discharge units.
†108 kW available on CV applications only.
NO. 1
RLA LRA RLA LRA
LEGEND
COMPR
NO. 2
OFM IFM
Total
FLA
10.0
15.0
20.0
208/230-3-60 (V-Ph-Hz)
BASE UNIT
ONLY
Hp FLA MCA MOCP
24.2/
7.5
22.0
30.8/
28.0
46.2/
42.0
59.4/
54.0
154.7/
152.5
161.3/
158.5
176.7/
172.5
191.4/
184.7
200/
200
200/
200
225/
225
250/
225
EXHAUST
FAN
TotalHpTotal
10.0 33.4/30.0 188.1/182.5 225/225
15.0 48.4/44.0 203.1/196.5 250/225
10.0 33.4/30.0 29/ 36 78.9/ 91.0 188.1/182.5 225/225
10.0 33.4/30.0 59/ 72 157.7/182.0 227.4/255.0 250/300
10.0 33.4/30.0 88/108† 236.6/273.0 326.0/368.8 350/400
15.0 48.4/44.0 29/ 36 78.9/ 91.0 203.1/196.5 250/225
15.0 48.4/44.0 59/ 72 157.7/182.0 227.4/255.0 250/300
15.0 48.4/44.0 88/108† 236.6/273.0 326.0/368.8 350/400
10.0 33.4/30.0 194.7/188.5 225/225
15.0 48.4/44.0 209.7/202.5 250/250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 194.7/188.5 225/225
10.0 33.4/30.0 59/ 72 157.7/182.0 235.6/262.5 250/300
10.0 33.4/30.0 88/108 236.6/273.0 334.2/376.3 350/400
15.0 48.4/44.0 29/ 36 78.9/ 91.0 209.7/202.5 250/250
15.0 48.4/44.0 59/ 72 157.7/182.0 235.6/262.5 250/300
15.0 48.4/44.0 88/108† 236.6/273.0 334.2/376.3 350/400
10.0 33.4/30.0 210.1/202.5 250/250
15.0 48.4/44.0 225.1/216.5 250/250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 210.1/202.5 250/250
10.0 33.4/30.0 59/ 72 157.7/182.0 254.9/280.0 300/350
10.0 33.4/30.0 88/108 236.6/273.0 353.5/393.8 400/400
15.0 48.4/44.0 29/ 36 78.9/ 91.0 225.1/216.5 250/250
15.0 48.4/44.0 59/ 72 157.7/182.0 254.9/280.0 300/350
15.0 48.4/44.0 88/108† 236.6/273.0 353.5/393.8 400/400
10.0 33.4/30.0 224.8/214.7 250/250
15.0 48.4/44.0 239.9/228.7 250/250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 224.8/214.7 300/300
10.0 33.4/30.0 59/ 72 157.7/182.0 271.4/295.0 350/350
10.0 33.4/30.0 88/108† 236.6/273.0 370.0/408.8 450/450
15.0 48.4/44.0 29/ 36 78.9/ 91.0 239.9/228.7 300/300
15.0 48.4/44.0 59/ 72 157.7/182.0 271.4/295.0 350/350
15.0 48.4/44.0 88/108† 236.6/273.0 370.0/408.8 450/450
NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To determine heater capacity (kW) at unit operating voltage, multiply 240 v, 480 v, or 575 v capacity by appropriate multiplier below.
2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series units only.
FLA
6.0 21.2/20.0 175.9/172.5 225/225
29/ 36 78.9/ 91.0 154.7/152.5 200/200 — 59/ 72 157.7/182.0 227.4/255.0 250/300 — 88/108† 236.6/273.0 326.0/368.8 350/400
6.0 21.2/20.0 29/ 36 78.9/ 91.0 175.9/172.5 225/225
6.0 21.2/20.0 59/ 72 157.7/182.0 227.4/255.0 250/300
6.0 21.2/20.0 88/108† 236.6/ 273.0 326.0/368.8 350/400
6.0 21.2/20.0 182.5/178.5 225/225
29/ 36 78.9/ 91.0 161.3/158.5 200/200 — 59/ 72 157.7/182.0 235.6/262.5 250/300 — 88/108† 236.6/273.0 334.2/376.3 350/400
6.0 21.2/20.0 29/ 36 78.9/ 91.0 182.5/178.5 225/225
6.0 21.2/20.0 59/ 72 157.7/182.0 235.6/262.5 250/300
6.0 21.2/20.0 88/108† 236.6/273.0 334.2/376.3 350/400
6.0 21.2/20.0 197.9/192.5 250/225
29/ 36 78.9/ 91.0 176.7/172.5 250/250 — 59/ 72 157.7/182.0 254.9/280.0 300/350 — 88/108† 236.6/273.0 353.5/393.8 400/400
6.0 21.2/20.0 29/ 36 78.9/ 91.0 197.9/192.5 250/250
6.0 21.2/20.0 59/ 72 157.7/182.0 254.9/280.0 300/350
6.0 21.2/20.0 88/108† 236.6/273.0 353.5/393.8 400/400
6.0 21.2/20.0 212.6/204.7 250/250
29/ 36 78.9/ 91.0 191.4/184.7 300/300 — 59/ 72 157.7/182.0 271.4/295.0 350/350 — 88/108† 236.6/273.0 370.0/408.8 450/450
6.0 21.2/20.0 29/ 36 78.9/ 91.0 212.6/204.7 300/300
6.0 21.2/20.0 59/ 72 157.7/182.0 271.4/295.0 350/350
6.0 21.2/20.0 88/108† 236.6/273.0 370.0/408.8 450/450
HEATER kW
RATING
240
480
575
Electric heaters are tested and ETL approved at maximum total external static pressure of 1.9 in. wg.
ELECTRIC
HEAT*
kW FLA MCA MOCP
MULTIPLICATION FACTORS
VOLTAGE
DISTRIBUTION
V-3-60
200 208 230 240
440 460 480
550 575 600
BASE UNIT WITH
EXHAUST FAN
AND/OR
ELECTRIC HEAT*
MULTIPLICATION
FACTOR
0.694
0.751
0.918
1.000
0.840
0.918
1.000
0.915
1.000
1.089
19
Table 3 — Electrical Data, 034 Units (cont)
460-3-60 (V-Ph-Hz)
COMPR
VOLTAGE
RANGE
414-508 28.8 120.0 28.8 120.0 5.4
NO. 1
RLA LRA RLA LRA
COMPR
NO. 2
OFM IFM
Total
Hp FLA MCA MOCP
FLA
7.5 11.0 81.2 100
10.0 14.0 84.2 110
15.0 21.0 91.2 110
20.0 27.0 97.2 125
BASE UNIT
ONLY
EXHAUST
FAN
TotalHpTotal
FLA
6.0 9.6 90.8 110
10.0 15.2 96.4 125
15.0 22.0 103.2 125
36 46.3 81.2 100 — 72 93.0 130.0 150 — 108† 139.0 187.5 200
6.0 9.6 36 46.3 90.8 110
6.0 9.6 72 93.0 130.0 150
6.0 9.6 108† 139.0 187.5 200
10.0 15.2 36 46.3 96.4 125
10.0 15.2 72 93.0 130.0 150
10.0 15.2 108† 139.0 187.5 200
15.0 22.0 36 46.3 103.2 125
15.0 22.0 72 93.0 130.0 150
15.0 22.0 108† 139.0 187.5 200
6.0 9.6 93.8 110
10.0 15.2 99.4 125
15.0 22.0 106.2 125
36 46.3 84.2 110 — 72 93.0 133.7 150 — 108† 139.0 191.2 200
6.0 9.6 36 46.3 93.8 110
6.0 9.6 72 93.0 133.7 150
6.0 9.6 108† 139.0 191.2 200
10.0 15.2 36 46.3 99.4 125
10.0 15.2 72 93.0 133.7 150
10.0 15.2 108† 139.0 191.2 200
15.0 22.0 36 46.3 106.2 125
15.0 22.0 72 93.0 133.7 150
15.0 22.0 108† 139.0 191.2 200
6.0 9.6 100.8 125
10.0 15.2 106.4 125
15.0 22.0 113.2 125
36 46.3 91.2 125 — 72 93.0 142.5 175 — 108† 139.0 200.0 200
6.0 9.6 36 46.3 100.8 125
6.0 9.6 72 93.0 142.5 175
6.0 9.6 108† 139.0 200.0 200
10.0 15.2 36 46.3 106.4 125
10.0 15.2 72 93.0 142.5 175
10.0 15.2 108† 139.0 200.0 200
15.0 22.0 36 46.3 113.2 125
15.0 22.0 72 93.0 142.5 175
15.0 22.0 108† 139.0 200.0 200
6.0 9.6 106.8 125
10.0 15.2 112.4 125
15.0 22.0 119.2 125
36 46.3 97.2 150 — 72 93.0 150.0 200 — 108† 139.0 207.5 225
6.0 9.6 36 46.3 106.8 150
6.0 9.6 72 93.0 150.0 200
6.0 9.6 108† 139.0 207.5 225
10.0 15.2 36 46.3 112.4 150
10.0 15.2 72 93.0 150.0 200
10.0 15.2 108† 139.0 207.5 225
15.0 22.0 36 46.3 119.2 150
15.0 22.0 72 93.0 150.0 200
15.0 22.0 108† 139.0 207.5 225
ELECTRIC
HEAT*
kW FLA MCA MOCP
BASE UNIT WITH
EXHAUST FAN
AND/OR
ELECTRIC HEAT*
20
Table 3 — Electrical Data, 034 Units (cont)
575-3-60 (V-Ph-Hz)
COMPR
VOLTAGE
RANGE
518-632 23.1 96.0 23.1 96.0 4.8
CV Constant Volume ETL ETL Testing Laboratory FLA Full Load Amps Hp Nominal Horsepower IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps (for wire sizing) MOCP — Maximum Overcurrent Protection OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Electric heat available on 50 Series vertical discharge units.
†108 kW available on CV applications only.
NO. 1
RLA LRA RLA LRA
LEGEND
COMPR
NO. 2
OFM IFM
Total
FLA
BASE UNIT
ONLY
Hp FLA MCA MOCP
7.5 9.0 65.8 80
10.0 11.0 67.8 90
15.0 17.0 73.8 90
20.0 22.0 78.8 100
NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To determine heater capacity (kW) at unit operating voltage, multiply 240 v, 480 v, or 575 v capacity by appropriate multiplier below.
2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series units only.
EXHAUST
FAN
TotalHpTotal
10.0 12.2 78.0 100
15.0 18.0 83.8 100
10.0 12.2 36 36.0 78.0 100
10.0 12.2 72 72.0 101.3 110
10.0 12.2 108† 108.0 146.2 150
15.0 18.0 36 36.0 83.8 100
15.0 18.0 72 72.0 101.3 110
15.0 18.0 108† 108.0 146.2 150
10.0 12.2 80.0 100
15.0 18.0 85.8 100
10.0 12.2 36 36.0 80.0 100
10.0 12.2 72 72.0 103.7 110
10.0 12.2 108† 108.0 148.7 150
15.0 18.0 36 36.0 85.8 100
15.0 18.0 72 72.0 103.7 110
15.0 18.0 108† 108.0 148.7 150
10.0 12.2 86.0 100
15.0 18.0 91.8 110
10.0 12.2 36 36.0 86.0 100
10.0 12.2 72 72.0 111.2 125
10.0 12.2 108† 108.0 156.2 175
15.0 18.0 36 36.0 91.8 110
15.0 18.0 72 72.0 111.2 125
15.0 18.0 108† 108.0 156.2 175
10.0 12.2 91.0 110
15.0 18.0 96.8 110
10.0 12.2 36 36.0 91.0 110
10.0 12.2 72 72.0 117.5 150
10.0 12.2 108† 108.0 162.5 175
15.0 18.0 36 36.0 96.8 110
15.0 18.0 72 72.0 117.5 150
15.0 18.0 108† 108.0 162.5 175
HEATER kW
RATING
Electric heaters are tested and ETL approved at maximum total external static pressure of 1.9 in. wg.
FLA
6.0 7.8 73.6 90
36 36.0 65.8 80 — 72 72.0 101.3 110 — 108† 108.0 146.2 150
6.0 7.8 36 36.0 73.6 90
6.0 7.8 72 72.0 101.3 110
6.0 7.8 108† 108.0 146.2 150
6.0 7.8 75.6 90
36 36.0 67.8 90 — 72 72.0 103.7 110 — 108† 108.0 148.7 150
6.0 7.8 36 36.0 75.6 90
6.0 7.8 72 72.0 103.7 110
6.0 7.8 108† 108.0 148.7 150
6.0 7.8 81.6 100
36 36.0 73.8 100 — 72 72.0 111.2 125 — 108† 108.0 156.2 175
6.0 7.8 36 36.0 81.6 100
6.0 7.8 72 72.0 111.2 125
6.0 7.8 108† 108.0 156.2 175
6.0 7.8 86.6 100
36 36.0 78.8 110 — 72 72.0 117.5 150 — 108† 108.0 162.5 175
6.0 7.8 36 36.0 86.6 110
6.0 7.8 72 72.0 117.5 150
6.0 7.8 108† 108.0 162.5 175
MULTIPLICATION FACTORS
240
480
575
ELECTRIC
HEAT*
kW FLA MCA MOCP
VOLTAGE
DISTRIBUTION
V-3-60
200 208 230 240
440 460 480
550 575 600
BASE UNIT WITH
EXHAUST FAN
AND/OR
ELECTRIC HEAT*
MULTIPLICATION
FACTOR
0.694
0.751
0.918
1.000
0.840
0.918
1.000
0.915
1.000
1.089
21
Table 4 — Electrical Data, 044 Units
208/230-3-60 (V-Ph-Hz)
COMPR
VOLTAGE
RANGE
187-254 69.2 345.0 69.2 345.0 16.2
NO. 1
RLA LRA RLA LRA
COMPR
NO. 2
OFM IFM
Total
Hp FLA MCA MOCP
FLA
24.2/
7.5
22.0
30.8/
10.0
28.0
46.2/
15.0
42.0
59.4/
20.0
54.0
BASE UNIT
ONLY
196.1/
193.9
202.7/
199.9
218.1/
213.9
231.3/
225.9
EXHAUST
FAN
TotalHpTotal
10.0 33.4/30.0 229.5/223.9 250/250
15.0 48.4/44.0 244.5/237.9 300/300
250/ 250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 229.5/223.9 250/250
10.0 33.4/30.0 59/ 72 157.7/182.0 229.5/255.0 250/300
10.0 33.4/30.0 88/108† 236.6/273.0 326.0/368.8 350/400
15.0 48.4/44.0 29/ 36 78.9/ 91.0 244.5/237.9 300/300
15.0 48.4/44.0 59/ 72 157.7/182.0 244.5/255.0 300/300
15.0 48.4/44.0 88/108† 236.6/273.0 326.0/368.8 350/400
10.0 33.4/30.0 236.1/229.9 300/250
15.0 48.4/44.0 251.1/243.9 300/300
250/ 250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 236.1/229.9 300/250
10.0 33.4/30.0 59/ 72 157.7/182.0 236.1/262.5 300/300
10.0 33.4/30.0 88/108† 236.6/273.0 334.2/376.3 350/400
15.0 48.4/44.0 29/ 36 78.9/ 91.0 251.1/243.9 300/300
15.0 48.4/44.0 59/ 72 157.7/182.0 251.1/262.5 300/300
15.0 48.4/44.0 88/108† 236.6/273.0 334.2/376.3 350/400
10.0 33.4/30.0 251.5/243.9 300/300
15.0 48.4/44.0 266.5/257.9 300/300
250/ 250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 251.5/243.9 300/300
10.0 33.4/30.0 59/ 72 157.7/182.0 254.9/280.0 300/350
10.0 33.4/30.0 88/108† 236.6/273.0 353.5/393.8 400/400
15.0 48.4/44.0 29/ 36 78.9/ 91.0 266.5/257.9 300/300
15.0 48.4/44.0 59/ 72 157.7/182.0 266.5/280.0 300/350
15.0 48.4/44.0 88/108† 236.6/273.0 353.5/393.8 400/400
10.0 33.4/30.0 264.7/255.9 300/300
15.0 48.4/44.0 279.7/269.9 300/300
300/ 250
10.0 33.4/30.0 29/ 36 78.9/ 91.0 264.7/255.9 300/300
10.0 33.4/30.0 59/ 72 157.7/182.0 271.4/295.0 350/350
10.0 33.4/30.0 88/108† 236.6/273.0 370.0/408.8 450/450
15.0 48.4/44.0 29/ 36 78.9/ 91.0 279.7/269.9 300/300
15.0 48.4/44.0 59/ 72 157.7/182.0 279.7/295.0 350/350
15.0 48.4/44.0 88/108† 236.6/273.0 370.0/408.8 450/450
FLA
6.0 21.2/20.0 217.3/213.9 250/250
29/ 35 78.9/ 91.0 196.1/193.9 250/250 — 59/ 72 157.7/182.0 227.4/255.0 250/300 — 88/108† 236.6/273.0 326.0/368.8 350/400
6.0 21.2/20.0 29/ 36 78.9/ 91.0 217.3/213.9 250/250
6.0 21.2/20.0 59/ 72 157.7/182.0 227.4/255.0 250/300
6.0 21.2/20.0 88/108† 236.6/273.0 326.0/368.8 350/400
6.0 21.2/20.0 223.9/219.9 250/250
29/ 36 78.9/ 91.0 202.7/199.9 250/250 — 59/ 72 157.7/182.0 235.6/262.5 250/300 — 88/108† 236.6/273.0 334.2/376.3 350/400
6.0 21.2/20.0 29/ 36 78.9/ 91.0 223.9/219.9 250/250
6.0 21.2/20.0 59/ 72 157.7/182.0 235.6/262.5 250/300
6.0 21.2/20.0 88/108† 236.6/273.0 334.2/376.3 350/400
6.0 21.2/20.0 239.3/233.9 300/300
29/ 36 78.9/ 91.0 218.1/213.9 250/250 — 59/ 72 157.7/182.0 254.9/280.0 300/350 — 88/108† 236.6/273.0 353.5/393.8 400/400
6.0 21.2/20.0 29/ 36 78.9/ 91.0 239.3/233.9 300/300
6.0 21.2/20.0 59/ 72 157.7/182.0 254.9/280.0 300/350
6.0 21.2/20.0 88/108† 236.6/273.0 353.5/393.8 400/400
6.0 21.2/20.0 252.5/245.9 300/300
29/ 36 78.9/ 91.0 231.3/225.9 300/300 — 59/ 72 157.7/182.0 271.4/295.0 350/350 — 88/108† 236.6/273.0 370.0/408.8 450/450
6.0 21.2/20.0 29/ 36 78.9/ 91.0 252.5/245.9 300/300
6.0 21.2/20.0 59/ 72 157.7/182.0 271.4/295.0 350/350
6.0 21.2/20.0 88/108† 236.6/273.0 370.0/408.8 450/450
ELECTRIC
HEAT*
kW FLA MCA MOCP
BASE UNIT WITH
EXHAUST FAN
AND/OR
ELECTRIC HEAT*
22
Loading...
+ 50 hidden pages