Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (elevated structures, mechanical rooms,
etc.). Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment, and any other safety precautions that apply. Follow
all safety codes. Wear safety glasses and work gloves. Use
care in handling, rigging, and setting this equipment, and in
handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE
(American National Standards Institute/American Society
of Heating, Refrigerating and Air Conditioning Engineers)
15 (Safety Code for Mechanical Refrigeration). The
accumulation of refrigerant in an enclosed space can
displace oxygen and cause asphyxiation. Provide adequate
ventilation in enclosed or low overhead areas. Inhalation of
high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness or death. Misuse can
be fatal. Vapor is heavier than air and reduces the amount
of oxygen available for breathing. Product causes eye and
skin irritation. Decomposition products are hazardous.
CAUTION
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the electronic
modules or electrical components.
CAUTION
To prevent potential damage to heat exchanger, always run
fluid through heat exchanger when adding or removing
refrigerant charge. Use appropriate brine solutions in cooler
fluid loop to prevent the freezing of brazed plate heat
exchanger when the equipment is exposed to temperatures
below 32 F (0° C). Proof of flow switch is factory installed
on all models. Do NOT remove power from this chiller during winter shutdown periods without taking precaution to
remove all water from heat exchanger and optional
hydronic system. Failure to properly protect the system
from freezing may constitute abuse and may void warranty.
CAUTION
Compressors require specific rotation. Monitor control
alarms during first compressor start up for reverse rotation
protection. Damage to unit may result.
CAUTION
Refrigerant charge must be removed slowly to prevent loss
of compressor oil that could result in compressor failure.
CAUTION
WARNING
DO NOT attempt to unbraze factory joints when servicing
this equipment. Compressor oil is flammable and there is
no way to detect how much oil may be in any of the
refrigerant lines. Cut lines with a tubing cutter as required
when performing service. Use a pan to catch any oil that
may come out of the lines and as a gage for how much oil
to add to system. DO NOT re-use compressor oil. Damage
to equipment or personal injury may result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300053-01Printed in U.S.A.Form 30MP-1TPg 11-10Replaces: New
Puron® refrigerant (R-410A) systems operate at higher
pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment. If service equipment is not rated for Puron
refrigerant, equipment damage or personal injury may
result.
This publication contains Start-Up, Service, Controls, Oper-
ation, and Troubleshooting information for the 30MPW watercooled chillers and the 30MPA air-cooled chillers. See Table 1.
These liquid chillers are equipped with ComfortLink controls
and conventional thermostatic expansion valves (TXVs). The
30MPA units and the 30MPW units with optional medium
temperature brine are also equipped with liquid line solenoid
valves (LLSVs).
CAUTION
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out or
bypass components or otherwise depart from recommended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the board or
electrical component.
Table 1 — Unit Sizes
UNIT MODELNOMINAL TONS
30MPA,MPW01515
30MPA,MPW02020
30MPA,MPW03030
30MPA,MPW04040
30MPA,MPW04545
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the
local display (scrolling marquee or Navigator™ accessory)
will be used in this manual.
Point names will be written with the mode name first, then
any sub-modes, then the point name, each separated by an
arrow symbol (. Names will also be shown in bold
and italics. As an example, the Minimum Load Valve Select
Point, which is located in the Configuration mode, Option 1
sub-mode, would be written as ConfigurationOPT1MLV.S.
This path name will show the user how to navigate through
the local display to reach the desired configuration. The user
would scroll through the modes and sub-modes using the
and keys. The arrow symbol in the path name
represents pressing to move into the next level of the
menu structure.
2
ESCAPE
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 1 — Scrolling Marquee Display
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
When a value is included as part of the path name, it will be
shown at the end of the path name after an equals sign. If the
value represents a configuration setting, an explanation will
be shown in parenthesis after the value. As an example,
ConfigurationOPT1MLV.S= 1 (Minimum Load Valve
Select).
Pressing the and keys simultaneously
will scroll an expanded text description of the point name or
value across the display. The expanded description is shown in
the local display tables but will not be shown with the path
names in text.
The CCN (Carrier Comfort Network
®
) point names are also
referenced in the local display tables for users configuring the
unit with CCN software instead of the local display. The CCN
tables are located in Appendix B of the manual.
Basic Control Usage
SCROLLING MARQUEE DISPLAY — The scrolling marquee display is the standard interface display to the ComfortLink
Control System for 30MP units. The display has up and down
arrow keys, an key, and an key. These
keys are used to navigate through the different levels of the
display structure. Press the key until the highest
operating level is displayed to move through the top 11 mode
levels indicated by LEDs (light emitting diodes) on the left side
of the display. See Fig. 1 and Tables 2-14.
Once within a mode or sub-mode, pressing the
and keys simultaneously will put the scrolling
marquee display into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed
for the current selection. Press the and
keys to return the scrolling marquee display to its default menu
of rotating display items (those items in Run Status
In addition, the password will be disabled, requiring that it be
entered again before changes can be made to password protected items. Press the key to exit out of the expanded
text mode.
NOTE: When the Language Selection (ConfigurationDISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name alternates
with the value. Press the key at a changeable item
and the value will be displayed. Press again and the
value will begin to flash indicating that the value can be
changed. Use the up and down arrow keys to change the value,
and confirm the value by pressing the key.
VIEW).
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are password protected. The words ‘PASS’ and ‘WORD’ will alternate
on the display when required. The default password is 0111.
Press and the 1111 password will be displayed. Press
again and the first digit will begin to flash. Use the
arrow keys to change the number and press to accept
the digit. Continue with the remaining digits of the password.
The password can only be changed through CCN operator interface software such as ComfortWORKS
®
, ComfortVIEW™
and Service Tool.
See Tables 2-14 and Appendix A for further details.
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
The Navigator module provides a mobile user interface to the
ComfortLink™ control system, which is only available as a
field-installed accessory. The display has up and down arrow
keys, an key, and an key. These keys are
used to navigate through the different levels of the display
structure. Press the key until ‘Select a Menu Item’
is displayed to move through the top 11 mode levels indicated
by LEDs on the left side of the display. See Fig. 2.
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
and keys simultaneously will put the Navigator module into expanded text mode where the full meaning
of all sub-modes, items and their values can be displayed. Pressing the and keys when the display says
‘Select Menu Item’ (Mode LED level) will return the Navigator
module to its default menu of rotating display items (those items
in Run Status
VIEW). In addition, the password will be disabled, requiring that it be entered again before changes can be
made to password protected items. Press the key to
exit out of the expanded text mode.
NOTE: When the Language Selection (ConfigurationDISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name appears on the
left of the display, the value will appear near the middle of the
display and the units (if any) will appear on the far right of the
display. Press the key at a changeable item and the value will begin to flash. Use the up and down arrow keys to change
the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are password protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The default
password is 1111. Use the arrow keys to change the number
3
and press to enter the digit. Continue with the re-
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
Fig. 2 — Accessory Navigator™ Display Module
maining digits of the password. The password can only be
changed through CCN operator interface software such as
ComfortWORKS, ComfortVIEW and Service Tool.
Adjusting the Contrast
— The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
the Navigator module, press the key until the display reads, “Select a menu item.” Using the arrow keys move
to the Configuration mode. Press to obtain access to
this mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the view
screen. Pressing and simultaneously
allows the user to adjust the display contrast. Use the up or
down arrows to adjust the contrast. The screen’s contrast will
change with the adjustment. Press to accept the
change. The Navigator module will keep this setting as long as
it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
— The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust the backlight of the
Navigator module, press the key until the display
reads, “Select a menu item.” Using the arrow keys move to the
Table 2 — Scrolling Marquee Display Menu Structure*
MODE
SUB-MODE
LEGEND
Ckt — Circuit
*Throughout this text, the location of items in the menu structure will be
described in the following format:
Item Expansion (Mode Name
RUN
STATUS
Auto
View of
Run Status
(VIEW)
Unit Run
Hour and
Start
(RUN)
Circuit and
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Preventive
Maintenance
(PM)
Software
Ver si on
(VERS)
SERVICE
TEST
Service
Te s t M o d e
(TEST)
Outputs
and Pumps
(OUTS)
Ciruit A Comp
Te st
(CMPA)
TEMPERATURES PRESSURES
Unit Temperatures
Temperatures
Sub-mode NameITEM)
(UNIT)
Circuit A
(CIR.A)
Pressures
Circuit A
(PRC.A)
SET
POINTS
Cooling
Setpoints
(COOL)
Head
Pressure
Setpoint
(HEAD)
Brine
Free ze
Setpoint
(FRZ)
Configuration mode. Press to obtain access to this
mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the
view screen. Pressing the up and down arrow keys simultaneously allows the user to adjust the display brightness. Use the
up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will
keep this setting as long as it is plugged in to the LEN bus.
Comfort
Link
MODE
Alarm Status
Run S
tatus
Service Test
Temperatures
P
ressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
ESC
Operating Modes
Alarm
s
ENTER
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit
Inputs
(CRCT)
4-20mA
Inputs
(4-20)
General
Outputs
(GEN.O)
Outputs
Circuit A
(CIR.A)
For example, using the language selection item:
Language Selection (Configuration
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Unit Options 1
Hardware
(OPT1)
Unit Options 2
Controls
(OPT2)
CCN Network
Configuration
(CCN)
Reset Cool Temp
(RSET)
Set Point and
Ramp Load
(SLCT)
Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
Date, Day,
Schedules
Schedule
Schedule
Schedule
DISPLANG)
TIME
CLOCK
Time of
(TIME)
Month,
and Year
(DATE)
Daylight
Savings
Time
(DST)
Local
Holiday
(HOL.L)
Number
(SCH.N)
Local
Occupancy
(SCH.L)
Override
(OVR)
Day
OPERATING
MODES
Modes
(MODE)
ALARMS
Current
(CRNT)
Reset
Alarms
(RCRN)
Alarm
History
(HIST)
4
Table 3 — Run Status Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
VIEWEWTXXX.X FENTERING FLUID TEMP
LWTXXX.X FLEAVING FLUID TEMP
SETPXXX.X FACTIVE SETPOINT
CTPTXXX.X FCONTROL POINT
LOD.FXXXLOAD/UNLOAD FACTOR
STATXCONTROL MODE0 = Service Test
OCCYES/NOOCCUPIED
MODEYES/NOOVERRIDE MODES IN EFFECT
CAPXXX %PERCENT TOTAL CAPACITY
STGEXREQUESTED STAGE
ALRMXXXCURRENT ALARMS & ALERTS
TIMEXX.XXTIME OF DAY00.00-23.59
MNTHXXMONTH OF YEAR1 = January, 2 = February, etc.
DATEXXDAY OF MONTH01- 31
ITEM
EXPANSION
COMMENT
1 = Off Local
2 = Off CCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On CCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
YEARXXYEAR OF CENTURY
RUNHRS.U XXXX HRSMACHINE OPERATING HOURS
STR.UXXXXMACHINE STARTS
HR.P1XXXX.XPUMP 1 RUN HOURS
HR.P2XXXX.XPUMP 2 RUN HOURS
HOURHR.A1 XXXX HRSCOMPRESSOR A1 RUN HOURS
HR.A2 XXXX HRSCOMPRESSOR A2 RUN HOURS
HR.A3 XXXX HRSCOMPRESSOR A3 RUN HOURS
STRTST.A1XXXXCOMPRESSOR A1 STARTS
ST.A2XXXXCOMPRESSOR A2 STARTS
ST.A3XXXXCOMPRESSOR A3 STARTS
PM
STRNSTRAINER MAINTENANCE
SI.STXXXX HRSSTRAINER SRVC INTERVAL
S.T.DNXXXX HRSSTRAINER SRVC COUNTDOWN
S.T.MNYES/NOSTRAINER MAINT. DONEUser Entry
ST.DTSTRAINER MAINT. DATES
S.T.M0MM/DD/YY HH:MM
S.T.M1MM/DD/YY HH:MM
S.T.M2MM/DD/YY HH:MM
S.T.M3MM/DD/YY HH:MM
S.T.M4MM/DD/YY HH:MM
5
Table 3 — Run Status Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
VERSAUXCESR131333-xx-xxxx-xx is Version number*
MBBCESR131279-xx-xxxx-xx is Version number*
EMMCESR131174-xx-xxxx-xx is Version number*
MARQCESR131171-xx-xxxx-xx is Version number*
NAVICESR130227-xx-xxxx-xx is Version number*
*Pressandsimultaneously to obtain version number.
ITEM
EXPANSION
COMMENT
Table 4 — Service Test Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
TESTON/OFFSERVICE TEST MODETo Enable Service Test Mode,
OUTSOUTPUTS AND PUMPS
CLR.PON/OFFCOOLER PUMP RELAY
CND.PON/OFFCONDENSER PUMP
UL.TM0 to 15COMP A1 UNLOAD TIME
CC.HON/OFFCRANKCASE HEATER
CW.VOON/OFFCONDENSER VALVE OPEN
ITEM
EXPANSION
COMMENT
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
CW.VCON/OFFCONDENSER VALVE CLOSE
LL.SVON/OFFLIQUID LINE SOLENOID
RMT.AON/OFFREMOTE ALARM RELAY
CMPACIRCUIT A COMPRESSOR TEST
CC.A1ON/OFFCOMPRESSOR A1 RELAY
UL.TM0 to 15COMP A1 UNLOAD TIME
CC.A2ON/OFFCOMPRESSOR A2 RELAY
CC.A3ON/OFFCOMPRESSOR A3 RELAY
MLVON/OFFMINIMUM LOAD VALVE RELAY
Table 5 — Temperature Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITENT AND LEAVE UNIT TEMPS
CEWTXXX.X FCOOLER ENTERING FLUID
CLWTXXX.X FCOOLER LEAVING FLUID
CDETXXX.X FCONDENSER ENTERING FLUID
CDLTXXX.X FCONDENSER LEAVING FLUID
OATXXX.X FOUTSIDE AIR TEMPERATURE
SPTXXX.X FSPACE TEMPERATURE
ITEM
EXPANSION
COMMENT
DLWTXXX.X FLEAD/LAG LEAVING FLUID
6
Table 5 — Temperature Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
CIR.ATEMPERATURES CIRCUIT A
SCT.AXXX.X FSATURATED CONDENSING TMP
SST.AXXX.X FSATURATED SUCTION TEMP
RGT.AXXX.X FCOMPR RETURN GAS TEMP
D.G ASXXX.X FDISCHARGE GAS TEMP
SH.AXXX.X ^F SUCTION SUPERHEAT TEMP
ITEM
EXPANSION
Table 6 — Pressure Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
PRC.APRESSURES CIRCUIT A
DP.AXXX.X PSIGDISCHARGE PRESSURE
SP.AXXX.X PSIGSUCTION PRESSURE
ITEM
EXPANSION
Table 7 — Set Points Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
COOLCOOLING SETPOINTS
CSP.1XXX.X FCOOLING SETPOINT 1Default: 44 F
CSP.2XXX.X FCOOLING SETPOINT 2Default: 44 F
CSP.3XXX.X FICE SETPOINTDefault: 32 F
HEADHEAD PRESSURE SETPOINTS
H.DPXXX.X FHEAD SETPOINTDefault: 95 F
FRZBRINE FREEZE SETPOINT
BR.FZXXX.X FBRINE FREEZE POINTDefault: 34 F
ITEM
EXPANSION
COMMENT
COMMENT
COMMENT
Table 8 — Inputs Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
GEN.IGENERAL INPUTS
STST STRT/STOPSTART/STOP SWITCH
FLOWON/OFFCOOLER FLOW SWITCH
CD.FLOPEN/CLSECONDENSER FLOW SWITCH
DLS1ON/OFFDEMAND LIMIT SWITCH 1
DLS2ON/OFFDEMAND LIMIT SWITCH 2
ICEDON/OFFICE DONE
DUALON/OFFDUAL SETPOINT SWITCH
CRCTCIRCUITS INPUTS
FKA1ON/OFFCOMPRESSOR A1 FEEDBACK
FKA2ON/OFFCOMPRESSOR A2 FEEDBACK
FKA3ON/OFFCOMPRESSOR A3 FEEDBACK
4-20
DMNDXX.X MA4-20 MA DEMAND SIGNAL
RSETXX.X MA4-20 MA RESET SIGNAL
CSPXX.X MA4-20 MA COOLING SETPOINT
ITEM
EXPANSION
4-20 MA INPUTS
COMMENT
7
Table 9 — Outputs Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
GEN.OGENERAL OUTPUTS
CIR.AOUTPUTS CIRCUIT A
KEYPAD
ENTRY
ITEM DISPLAY
C.LWPON/OFFCOOLER PUMP RELAY
C.DWPON/OFFCONDENSER PUMP
ALRMON/OFFALARM RELAY
CDWOON/OFFCONDENSER VALVE OPEN
CDWCON/OFFCONDENSER VALVE CLOSE
CC.A1ON/OFFCOMPRESSOR A1 RELAY
D.SOLON/OFFDIGITAL SCROLL SOLENOID
CC.A2ON/OFFCOMPRESSOR A2 RELAY
CC.A3ON/OFFCOMPRESSOR A3 RELAY
CCHON/OFFCRANKCASE HEATER RELAY
LLSVON/OFFLIQUID LINE SOLENOID
MLV.RON/OFFMINIMUM LOAD VALVE RELAY
EXPANSION
Table 10 — Configuration Mode and Sub-Mode Directory
UNC.1XX.XXPERIOD UNOCCUPIED TIMEMilitar y (00:00 – 23:59)
MON.1YES/NOMONDAY IN PERIOD
TUE.1YES/NOTUESDAY IN PERIOD
WED.1YES/NOWEDNESDAY IN PERIOD
THU.1YES/NOTHURSDAY IN PERIOD
FRI.1YES/NOFRIDAY IN PERIOD
SAT.1YES/NOSATURDAY IN PERIOD
SUN.1YES/NOSUNDAY IN PERIOD
HOL.1YES/NOHOLIDAY IN PERIOD
OVRSCHEDULE OVERRIDE
OVR.TXTIMED OVERRIDE HOURSDefault: 0, Range 0-4 hours
OVR.LXOVERRIDE TIME LIMITDefault: 0, Range 0-4 hours
T.OVRYES/NOTIMED OVERRIDEUser Entry
* Repeats for Occupancy Periods 2 through 8.
11
Table 12 — Operating Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
MODEMODES CONTROLLING UNIT
MD01ON/OFFCSM CONTROLLING CHILLER
MD03ON/OFFMASTER/SLAVE CONTROL
MD05ON/OFFRAMP LOAD LIMITED
MD06ON/OFFTIMED OVERRIDE IN EFFECT
MD07ON/OFFLOW COOLER SUCTION TEMPA
MD09ON/OFFSLOW CHANGE OVERRIDE
MD10ON/OFFMINIMUM OFF TIME ACTIVE
MD13ON/OFFDUAL SETPOINT
MD14ON/OFFTEMPERATURE RESET
MD15ON/OFFDEMAND LIMITED
MD16ON/OFFCOOLER FREEZE PROTECTION
MD17ON/OFFLOW TEMPERATURE COOLING
MD18ON/OFFHIGH TEMPERATURE COOLING
MD19ON/OFFMAKING ICE
MD20ON/OFFSTORING ICE
ITEM
EXPANSION
COMMENT
MD21ON/OFFHIGH SCT CIRCUIT A
MD23ON/OFFMINIMUM COMP ON TIME
MD24ON/OFFPUMP OFF DELAY TIME
LEGEND
CSM— Chillervisor System Manager
SCT— Saturated Condensing Temperature
WSM — Water System Manager
Table 13 — Alarms Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM
CRNTAXXX OR TXXXCURRENTLY ACTIVE ALARMS
RCRNYES/NORESET ALL CURRENT ALARMS
HISTAXXX OR TXXXALARM HISTORY
ITEM
EXPANSION
COMMENT
Alarms are shown as AXXX.
Alerts are shown as TXXX.
Alarms are shown as AXXX.
Alerts are shown as TXXX.
12
Table 14 — Operating Modes
MODE
NO.
01CSM CONTROLLING CHILLERChillervisor System Manager (CSM) is controlling the chiller.
03MASTER/SLAVE CONTROLDual Chiller control is enabled.
05
06
07
09
10MINIMUM OFF TIME ACTIVEChiller is being held off by Minutes Off Time (Configuration
13
14
15
16
17
18
19
20
21
23
24
ITEM EXPANSION DESCRIPTION
RAMP LOAD LIMITEDRamp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature
TIMED OVERRIDE IN EFFECTTimed override is in effect. This is a 1 to 4 hour temporary override of the programmed
LOW COOLER SUCTION TEMPACircuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
SLOW CHANGE OVERRIDESlow change override is in effect. The leaving fluid temperature is close to and moving
DUAL SETPOINTDual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set Points
TEMPERATURE RESETTemperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-
DEMAND LIMITEDDemand limit is in effect. This indicates that the capacity of the chiller is being limited by
COOLER FREEZE PROTECTIONCooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section
LOW TEMPERATURE COOLINGChiller is in Cooling mode and the rate of change of the leaving fluid is negative and
HIGH TEMPERATURE COOLINGChiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.
MAKING ICEChiller is in an unoccupied mode and is using Cooling Set Point 3 (Set Points
STORING ICEChiller is in an unoccupied mode and is controlling to Cooling Set Point 2 (Set Points
HIGH SCT CIRCUIT AChiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
MINIMUM COMP ON TIMECooling load may be satisfied, however control continues to operate compressor to ensure
PUMP OFF DELAY TIMECooling load is satisfied, however cooler pump continues to run for the number of minutes set
is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling
Ramp Loading (Configuration
desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
schedule, forcing unit to Occupied mode. Override can be implemented with unit under
Local (Enable) or CCN (Carrier Comfort Network
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If
the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the saturated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to
decrease capacity as long as either condition exists.
towards the control point.
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2)
during unoccupied periods.
ing fluid set point upward and is currently controlling to the modified set point. The set point
can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to
20 mA signal.
demand limit control option. Because of this limitation, the chiller may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs
or a 4 to 20 mA signal.
for definition). The chiller will be shut down when either fluid temperature falls below the
Freeze point.
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point
exceeds fixed amount. Control will automatically unload the chiller if necessary.
Error between leaving fluid and control point exceeds fixed amount. Control will automatically
load the chiller if necessary to better match the increasing load.
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing condensing temperature.
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop
volume.
by the configuration variable Cooler Pump Shutdown Delay (Configuration
PM.DY).
SLCTCRMP). The pull-down limit can be modified, if
®
) control. Override expires after each use.
OPT2DELY).
COOL
OPT1
FRZ
COOL
COOL
13
CONTROLS
General —
ComfortLink™ electronic control system that controls and
monitors all operations of the chiller.
The control system is composed of several components as
listed in the sections below. See Fig. 3 for a typical control box
drawing. See Fig. 4 and 5 for control schematics.
The 30MP liquid scroll chillers contain the
Main Base Board (MBB) — See Fig. 6. The MBB is
the heart of the ComfortLink control system. It contains the
major portion of operating software and controls the operation
of the machine. The MBB continuously monitors input/output
channel information received from its inputs and from all other
modules. The MBB receives inputs from the discharge and
suction pressure transducers and thermistors. See Table 15. The
MBB also receives the feedback inputs from each compressor
current sensor board and other status switches. See Table 16.
The MBB also controls several outputs. Relay outputs controlled by the MBB are shown in Table 17. Information is
transmitted between modules via a 3-wire communication bus
or LEN (Local Equipment Network). The CCN (Carrier Comfort Network) bus is also supported. Connections to both LEN
and CCN buses are made at the LVT (low voltage terminal).
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a fieldinstalled accessory. The EMM module receives 4 to 20 mA
inputs for the leaving fluid temperature reset, cooling set point
and demand limit functions. The EMM module also receives
the switch inputs for the field-installed 2-stage demand limit
and ice done functions. The EMM module communicates the
status of all inputs with the MBB, and the MBB adjusts the
control point, capacity limit, and other functions according to
the inputs received.
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and
providing an analog input to the main base board (MBB).
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to
control the chiller. When switched to the Enable position the
chiller is under its own control. Move the switch to the Off
position to shut the chiller down. Move the switch to the
Remote Contact position and a field-installed dry contact can
be used to start the chiller. The contacts must be capable of
handling a 24 vac, 50-mA load. In the Enable and Remote
Contact (dry contacts closed) positions, the chiller is allowed to
operate and respond to the scheduling configuration, CCN
configuration and set point data. See Fig. 7.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the
chiller off immediately. Power to the MBB, EMM, and
marquee display is interrupted when this switch is off and all
outputs from these modules will be turned off. See Fig. 7.
Board Addresses — The main base board (MBB) has a
3-position instance jumper that must be set to ‘1.’ The EMM
board has 4-position DIP switches. All switches are set to ‘On’
for all boards except the AUX2 board. The AUX2 board DIP
switch settings are shown on the wiring schematic.
Control Module Communication
RED LED — Proper operation of the control boards can be
visually checked by looking at the red status LEDs
(light-emitting diodes). When operating correctly, the red status
LEDs should be blinking in unison at a rate of once every
2 seconds. If the red LEDs are not blinking in unison, verify
that correct power is being supplied to all modules. Be sure that
the main base board (MBB) is supplied with the current software. If necessary, reload current software. If the problem still
persists, replace the MBB. A red LED that is lit continuously or
blinking at a rate of once per second or faster indicates that the
board should be replaced.
GREEN LED — The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED
which should be blinking whenever power is on. Check LEN
connections for potential communication errors at the board J3
and/or J4 connectors. Communication between modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module. The J4 connector on the MBB
provides both power and communication directly to the
marquee display only.
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
Carrier Comfort Network® (CCN) Interface —
The 30MP chiller units can be connected to the CCN if
desired. The communication bus wiring is a shielded,
3-conductor cable with drain wire and is supplied and installed
in the field. See Table 18. The system elements are connected
to the communication bus in a daisy chain arrangement. The
positive pin of each system element communication connector
must be wired to the positive pins of the system elements on
either side of it. This is also required for the negative and
signal ground pins of each system element. Wiring connections
for CCN should be made at LVT. Consult the CCN Contractor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. Wire manufactured by Alpha (2413
or 5463), American (A22503), Belden (8772), or Columbia
(02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication
bus that a color coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.)
3. Connect the red wire to (+) terminal on LVT of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
4. The RJ14 CCN connector on LVT can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Service Tool).
14
LEGEND FOR FIG. 3-5
ALMR— Alarm Relay
AUX— Auxilliary
C—Contactor, Compressor
CB— Circuit Breaker
CCB— Compressor Circuit Breaker
CH— Crankcase Heater
CCH— Crankcase Heater Relay
COMP— Compressor
CR— Control Relay
CSB— Current Sensor Board
CWFS— Chilled Water Flow Switch
CWP— Chilled Water Pump
DGS— Digital Scroll Compressor
DPT— Discharge Pressure Transducer
DTT— Discharge Temperature Thermistor
DUS— Digital Unloader Solenoid
EMM— Energy Management
EWT— Entering Water Temperature
FB— Fuse Block
FIOP— factory Installed Option
FU— Fuse
GND— Ground
HPS— High-Pressure Switch
LLSV— Liquid Line Solenoid Valve
LON— Local Operating Network
LV T— Low Voltage Terminal
LWT— Leaving Water Temperature
MBB— Main Base Board
MLV— Minimum Load Valve
MP— Modular Motor Protection
NEC— National Electrical Code
OAT— Outdoor-Air Thermistor
PL— Plug
RLY— Relay
SPT— Suction Pressure Transducer
SW— Switch
TB— Terminal Block
TRAN— Transformer
UPC— Unitary Protocol Converter
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
Accessory or Option Wiring
To indicate common potential only; not to represent wiring.
15
EQUIP
Fig. 3 — Typical Control Box — 30MP015-045 Units
a30-4963
GND
TB3
UPC LON
OPTION
UPC
DISCONNECT
OPTION CB1A/TB1A
L1
L2
L3
2
4
TRAN1
23
25
24
21
22
15
10
14
16
17
12
13
18
19
20
7
11
9
8
1
5
6
2
3
4
LVT
CCB-1
CCB-2
CCB-3
EMM
CSB-A1
CSB-A2
CSB-A3
6
CCH
CA1CA2
CA3
MBB
FB1
16
LOCATED OVER EMM
CB1
CB2
REMOTE
CONTROL
OFF
SW1
ENABLE
CB3
OFF
SW2
ON
COMP A2
TRAN1
H2
H3
H4
SECONDARY 24V
RED
3
3
2
2
1
1
J2
BRN
VIO
2
2
1
J1
1
3
3
FU3
SW2
C1
A1
B1
H1
X3
CONNECT FOR
APPROPRIATE
PRIMARY VOLTAGE
SEE TABLE 1
2
4
6
CB1A
11
12
13
TO FUSED
DISCONNECT
PER NEC
OPTIONAL
DISCONNECT
3.2 AMPS
CB3
1
2
3
T3
T1
T2
T3
T1
T2
3
2
1
GRN/YEL
GRN/YEL
XF
RED
11
21
12
22
13
23
CA1
BLK
YEL
BLU
11
21
12
22
1323
CA2
11
12
13
21
22
23
CCB-1
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLU BLK
YEL
BLU
BLK
11
12
13
21
22
23
CCB-2
BLK
YEL
BLK
015,020,040: 380V,460V,575V ONLY
030,045: 460V,575V ONLY
BLU
YEL
BLU
T3
T1
T2
3
2
1
GRN/YEL
11
21
12
22
13
23
CA3
BLK
YEL
BLU
11
12
13
21
22
23
CCB-3
BLK
YEL
BLU
YEL
BLU
BLK
BLU
BLU
BLU
YEL
YEL
YEL
BLK
BLK
BLK
BLK
YEL
CH-A1
BLK
BLK
BLK
YEL
L1T1
L2T2
BLK
YEL
CH-A2
BLK
BLK
BLK
YEL
CH-A3
BLK
BLK
YEL
BLK
015,020,040: 208/230V ONLY
030,045: 202/230V,380V ONLY
MBB
BRN
VIO
2
1
UPC FIOP
UPC
GND
HOT
24VAC
BRN
VIO
12
2
11
1
J1
DGS FIOP
AUX2
BRN
RED
3
3
2
2
1
1
J2
2
J1
1
3
FIOP/ACCESSORY
EMM
FU1
BLK
FU2
YEL
GRN/YEL
RED
VIO
VIO
BRN
BRN
PRIMARY
WHT
11
X2
380V
UNITS ONLY
NOT USED ON
380V UNITS
FB1
BLK
YEL
NOTES:
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN
COMPLIANCE WITH ALL APPLICABLE CODES.
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED--
THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE
PHASE CONDITIONS.
5. TERMINALS 14
& 15 OF LVT ARE FOR FIELD CONNECTION
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC
1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
8. MP-A1 NOT USED IN THE FOLLOWING UNITS:
015,020: ALL UNITS
9. MP-A2 NOT USED IN THE FOLLOWING UNITS:
015,020: ALL UNITS
10. MP-A3 NOT USED IN THE FOLLOWING UNITS:
11. JUMPER PLUG REQUIRED WHEN MP NOT USED
WHT
(040,045 ONLY)
VOLTAGESERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60100H1 & H5
380-3-60200H1 & H2
230-3-60500H2 & H4
208-3-60500H3 & H4
460-3-60600H1 & H4
TABLE 1
7. MAX LOAD: 5VA SEALED, 10VA INRUSH
(040,045 ONLY)
BLK
YEL
(MPA ONLY)
(MPA ONLY)
WHT
BLK
YEL
FU4
FU5
UNIT VOLTAGE
REPLACE
WITH
FNQ-R-3
FU1 & FU2
FUSE
NUMBER
380-3-60
TRAN
SIZE
200VA
FNQ-R-2
208/230-3-60
FNQ-R-10
FU3 (24V)
380-3-60,460-3-60,575-3-60
250VA
208/230-3-60
460-3-60
575-3-60
FNQ-R-1.5
FNQ-R-1.5
FU4 & FU5
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
(040,045 ONLY)(040,045 ONLY)
12. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 16 TO 17 AND
WIRE INTERLOCK CONTACT ACROSS TERMINALS 16 & 17.
030-045: 460V UNITS WITHOUT DIGITAL SCROLL
030-045: 460V UNITS
040,045: 460V UNITS
FNQ-R-3
1
2
3
TB3
X1
380V ONLY
PL11-2
PL11-1
PL12-2
PL12-1
CCH
PL13-2
PL13-1
STANDARD
TERMINAL
BLOCK
PER NEC
TO FUSED DISCONNECT
21
22
23
TB1A
EQUIP GND
COMP A1
COMP A3
21
380V UNITS ONLY
NEUTRAL
CSB-A1
CSB-A2
CSB-A3
L1
L2
L3
L1
L2
L3
Fig. 4 — Typical Power Wiring Schematic — 30MP015-045 Units
a30-4965
17
J10A
Fig. 5 — Typical Control Wiring Schematic — 30MP015-045 Units
a30-4966
J10B
CWPI
(SEE
NOTE
12)
REMOTE
ON-OFF
SWITCH
(SEE
NOTE 5)
DUAL
SETPOINT
CNPI
CNFS
RED
WHT
BLK
RED
BLK
WHT
RLY 11
RLY 9
RLY 10
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
MBB
17
16
15
14
13
12
11
LEN CCN
J1
LVT
LVT
(COM)
SHIELD
PORT 2
1
2
3
4
5
PORT 1A
1
2
3
(+)
(-)
UPC
NET +
NET -
N/C
N/C
SIGNAL
NET +
NET 2
SHIELD
CB2
3.2 AMPS
1
ORN
1
2
2
ORN
3
3
4
4
5
5
ORN
6
6
7
7
8
8
ORN
9
9
1
10
2
11
3
12
ORN
4
13
5
14
6
15
ORN
7
16
8
17
9
18
10
19
11
BLK
20
12
21
13
22
BLK
14
23
15
24
16
25
17
26
18
27
BLK
6
C1
2
ENABLE
6
5
5
4
4
3
3
2
2
RED
1
1
10
10
WHT
9
9
8
8
SW1
7
RED
7
6
6
5
5
4
BLU
4
3
BLU
3
2
VIO
2
1
1
10
BRN
10
9
RED
9
8
8
7
BLK
7
6
WHT
6
5
RED
5
4
4
3
BLK
3
2
WHT
2
1
RED
1
J11
2
3
4
CWFS
4
BLK
5
VIO
6
RED
7
8
9
10
11
12
13
14
J13
1
2
3
4
5
6
7
8
BLK
WHT
RED
BRN
RED
BLK
WHT
RED
OPTION
J3
UPC OPT
A1
OFF
B1
ORN
LON
GND
NET
J4
1
2
A2
SW2
RED
C2
ORN
B2
CB1
ORN
3.2 AMPS
PNK
GRA
PNK
PNK
BLU
ORN
PNK
XF
RED
LVT
J12
25
1
2
24
J12
20
6
7
19
J11
18
1
RED
BLU
HPS-A
BLK
BLK
ORN
GRA
VIO
PNK
SEE NOTE 11
SEE NOTE 11
SEE NOTE 11
MP-A1
VIO
M1
M2
VIO
MP-A2
VIO
M1
M2
VIO
MP-A3
VIO
M2
M1
VIO
GRA
PNK
J6
2
CSB
3
A2
1
2
CSB
3
A3
1
2
CSB
3
A1
1
B
C
A
B
C
A
1
RED
2
WHT
3
BLK
4
5
RED
6
BRN
(040,045 ONLY)
CONDENSER EWT
ACCESSORY
CONDENSER LWT
ACCESSORY
RGTA
ACCESSORY
COOLER ENTERING
FLUID TEMP
COOLER LEAVING
FLUID TEMP
+
DPTA
-
+
SPTA
-
1
2
3
4
5
6
MARQUEE
DISPLAY
LVT
J12 T55
3
4
5
23
22
21
J7
BOARD
J5
MAIN
BASE
J8
J4
J3
J9
1
RED
1
2
WHT
2
3
BLK
3
4
4
5
BRN
5
6
RED
6
1
RED
1
2
WHT
2
3
BLK
3
4
4
1
1
2
2
3
3
4
4
RED
5
5
ORN
6
6
BRN
7
7
RED
8
8
ORN
9
9
BRN
10
10
RED
11
11
ORN
12
12
BRN
1
1
2
2
3
3
4
4
5
BLU
5
6
VIO
6
1
RED
7
2
8
3
9
4
10
1
RED
11
2
12
BLK
3
RED
13
4
14
BLK
1
15
2
16
3
17
4
18
5
19
6
20
7
RED
21
8
22
GRN
9
BLK
23
10
RED
24
11
25
GRN
12
BLK
26
TRAN1
SECONDARY 24V
X1
FU3
ALMR
ALARM RELAY
SEE NOTE 7
CR
CWP RELAY
SEE NOTE 7
CR
CONDENSER FAN/PUMP RELAY
SEE NOTE 7
CONDENSER
WATER
VALVE
(MPB ONLY)
RED
GRA
(MPA AND BRINE ONLY)
BLU
PL1-2PL1-1
VIO
ORN
PL2-2PL2-1
VIO
GRA
PL3-2PL3-1
VIO
VIO
(040,045 ONLY)
GRA
GRA
PNK
BRN
PL1-3
PNK
RED
PL2-3
PNK
RED
PL3-3
PNK
RED
T-55
SEN
ACCSY
OAT ACCESSORY OR
DUAL CHILLER LWT
LLSV-A
CCH
(MPA ONLY)
CA1
CA2
CA3
MLV-A
MLV FIOP
CWFS
SEE NOTE 8
T2T1MP-A1
SEE NOTE 9
T2T1MP-A2
SEE NOTE 10
T2T1MP-A3
X2
GRN/YEL
1
BRN
TB3
TB3
1
X2
TRAN1
BRN
2
3
BRN
C2C1
C2C1
C2C1
C2C1
BRN
31
BRN
BLU
PL1-4
BRN
PL2-4
BRN
PL3-4
BRN
6
5
4
3
BLK
2
WHT
1
RED
4
3
BLK
2
WHT
1
RED
4
3
BLK
2
WHT
1
RED
BRN
BRN
3
BRN
BRN
C2
BRN
BRN
BRN
BRN
BRN
BRN
C2
BRN
BRN
BRN
C2
BRN
2
BRN
C2
BRN
C2
BRN
C2
BRN
C2
BRN
C2
BRN
AUX2
-
3
G
2
+
1
J9
-
3
G
2
DGS
+
1
FIOP
12345678
DARK = SWITCH LOCATION
4
EMM
3
J3
2
1
4
3
J4
2
1
FIOP/
ACCESSORY
CWFS-3
LLSV-A
TB3
MLV-A
CA3
MLV-A
PL1-4
PL2-4
PL2-4
PL3-4
CCH
PL3-4
LLSV-A
CCH
TB3
CA1
CA1
CA2
CA2
CA3
OFF
7
-
7
8
J2
CH1
8
1
CH11
1
2
J6
-
2
ON
1
1
GRA
2
2
GRA
3
3
RED
4
4
RED
5
5
BLU
6
6
BLU
7
7
8
J7
8
9
9
10
10
11
11
12
12
13
13
14
14
1
1
2
2
VIO
3
3
BRN
4
4
5
5
ORN
6
6
7
J6
7
8
8
PNK
9
9
10
10
11
11
12
12
DUS
VIO
BRN
RED
BLK
DTT
LVT
J10
1
17
16
2
ICE DONE
3
15
14
4
DLS STEP 1
5
13
12
6
DLS STEP 2
11
10
DEMAND
9
+
7
LIMIT
-
8
8
4-20mA
7
6
TEMP
5
+
9
RESET
4
-
4-20mA
3
COOLING
2
+
10
SETPOINT
-
1
4-20mA
18
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector. If
conditions return to normal, check the CCN connector and
cable. Run new cable if necessary. A short in one section of
the bus can cause problems with all system elements on the
bus.
Sensors — The electronic control uses 2 to 7 thermistors to
sense temperatures for controlling chiller operation. See
Table 15. These sensors are outlined below. Thermistors
RGTA, CNDE, CNDL, EWT, LWT, and OAT are identical in
temperature versus resistance and voltage drop performance.
The dual chiller thermistor (DLWT) is 5 k at 77 F (25 C)
thermistor. Space temperature thermistor (SPT) is a 10 kat
77 F (25 C). See Thermistors section for temperature-resistance-voltage drop characteristics.
COOLER LEAVING FLUID SENSOR (LWT) — The thermistor is installed in a well in the factory-installed leaving fluid
piping coming from the bottom of the brazed-plate heat
exchanger.
COOLER ENTERING FLUID SENSOR (EWT) — The thermistor is installed in a well in the factory-installed entering fluid
piping coming from the top of the brazed-plate heat exchanger.
CONDENSER LEAVING FLUID SENSOR (CNDL) — The
thermistor is installed in a well in the factory-installed leaving
fluid piping coming from the bottom of the brazed-plate heat
exchanger.
COOLER ENTERING FLUID SENSOR (CNDE) — The thermistor is installed in a well in the factory-installed entering fluid
piping coming from the top of the brazed-plate heat exchanger.
COMPRESSOR RETURN GAS TEMPERATURE SENSOR (RGTA) — This accessory thermistor can be installed in
a well located in the suction line.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —
This sensor is an accessory that is remotely mounted and used
for outdoor air temperature reset. See Table 15.
DUAL LEAVING WATER TEMPERATURE SENSOR
(DLWT) — This input can be connected to the LVT. See Table 15. For dual chiller applications (parallel only are supported), connect the dual chiller leaving fluid temperature sensor
(5 kthermistor, Carrier part no. HH79NZ029) to the outside
air temperature input of the Master chiller. If outside air temperature is required for reset applications, connect the sensor to
the Slave chiller and configure the slave chiller to broadcast the
value to the Master chiller.
REMOTE SPACE TEMPERATURE SENSOR (SPT) —
The sensor (part no. 33ZCT55SPT) is an accessory sensor that
is remotely mounted in the controlled space and used for space
temperature reset. The sensor should be installed as a wallmounted thermostat would be (in the conditioned space where
it will not be subjected to either a cooling or heating source or
direct exposure to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to
terminals in the unit main control box. The space temperature
sensor includes a terminal block (SEN) and a RJ11 female
connector. The RJ11 connector is used access into the Carrier
Comfort Network
®
(CCN) at the sensor.
To connect the space temperature sensor (Fig. 8):
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect 1 wire of the twisted pair to one
SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.
2. Connect the other ends of the wires to terminals 3 and 4
on LVT located in the unit control box.
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN (Fig. 9):
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 18 for
acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (–) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
Fig. 9 — CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector
a30-4967
a30-4968
20
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the
space temperature sensor.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
Energy Management Module (Fig. 10) — This
factory-installed option (FIOP) or field-installed accessory is
used for the following types of temperature reset, demand
limit, and/or ice features:
•4 to 20 mA leaving fluid temperature reset (requires
field-supplied 4 to 20 mA generator)
•4 to 20 mA cooling set point reset (requires fieldsupplied 4 to 20 mA generator)
•Discrete inputs for 2-step demand limit (requires fieldsupplied dry contacts capable of handling a 24 vac,
50 mA load)
•4 to 20 mA demand limit (requires field-supplied 4 to
20 mA generator)
•Discrete input for Ice Done switch (requires fieldsupplied dry contacts capable of handling a 24 vac,
50 mA load)
See Demand Limit and Temperature Reset sections on
pages 27 and 31 for further details.
CAUTION
Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink™ controls use half wave rectification. A
signal isolation device should be utilized if a full wave
bridge signal generating device is used.
Loss-of-Cooler Flow Protection — A proof-of-
cooler flow device is factory installed in all chillers.
Condenser Flow Protection — A proof-of-condens-
er flow protection accessory can be field installed in the condenser water piping of all chillers. The unit must be configured
for the input to be enabled.
Thermostatic Expansion Valves (TXV) — All
units are equipped from the factory with conventional TXVs.
The 30MPA units and 30MPW units with medium temperature
brine also have factory-installed liquid line solenoids. The liquid line solenoid valves are not intended to be a mechanical
shut-off. For 30MPW units, when service is required, reclaim
the refrigerant from the system.
For 30MPA units when service is required, the compressor
and evaporator can be serviced by closing the factory-installed
liquid line service valve and field-installed discharge line service valve. After the valves are closed, reclaim the refrigerant
from the system.
The TXV is set at the factory to maintain approximately 8 to
12° F (4.4 to 6.7° C) suction superheat leaving the cooler by
monitoring the proper amount of refrigerant into the cooler. All
TXVs are adjustable, but should not be adjusted unless abso-lutely necessary.
Capacity Control — The control system cycles com-
pressors, digital scroll modulting solenoid (if equipped), and
minimum load valve solenoids (if equipped) to maintain the
user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the main base board (MBB)
to determine the temperature drop across the cooler and is used
in determining the optimum time to add or subtract capacity
stages. The chilled fluid temperature set point can be automatically reset by the return fluid temperature, space, or outdoor-air
temperature reset features. It can also be reset from an external
4 to 20-mA signal (requires energy management module FIOP
or accessory).
The capacity control algorithm runs every 30 seconds. The
algorithm attempts to maintain the Control Point at the desired
set point. Each time it runs, the control reads the entering and
leaving fluid temperatures. The control determines the rate at
which conditions are changing and calculates 2 variables based
on these conditions. Next, a capacity ratio is calculated using
the 2 variables to determine whether or not to make any
changes to the current stages of capacity. This ratio value
ranges from –100 to +100%. If the next stage of capacity is a
compressor, the control starts (stops) a compressor when the
ratio reaches +100% (–100%). If installed, the minimum load
valve solenoid will be energized with the first stage of capacity.
Minimum load valve value is a fixed 30% in the total capacity
calculation. The control will also use the minimum load valve
solenoid as the last stage of capacity before turning off the last
compressor. A delay of 90 seconds occurs after each capacity
step change. Refer to Table 19.
MINUTES LEFT FOR START — This value is displayed
only in the network display tables (using Service Tool,
ComfortVIEW™ or ComfortWORKS
represents the amount of time to elapse before the unit will start
its initialization routine. This value can be zero without the
machine running in many situations. This can include being
unoccupied, ENABLE/OFF/REMOTE CONTACT switch in
the OFF position, CCN not allowing unit to start, Demand
Limit in effect, no call for cooling due to no load, and alarm or
alert conditions present. If the machine should be running and
none of the above are true, a minimum off time (DELY, see
below) may be in effect. The machine should start normally
once the time limit has expired.
MINUTES OFF TIME (ConfigurationDELY) — This user-configurable time period is used by the
control to determine how long unit operation is delayed after
power is applied/restored to the unit. Typically, this time period
is configured when multiple machines are located on a single
site. For example, this gives the user the ability to prevent all
the units from restarting at once after a power failure. A value
of zero for this variable does not mean that the unit should be
running.
LEAD/LAG DETERMINATION — This is a configurable
choice and is factory set to be automatic for all units unless the
unit is equipped with minimum load, then circuit A is lead
(Configuration
to Circuit A or Circuit B leading as desired. Set at automatic,
the control will sum the current number of logged circuit starts
and one-quarter of the current operating hours for each circuit.
The circuit with the lowest sum is started first. Changes to
which circuit is the lead circuit and which is the lag are also
made when total machine capacity is at 100% or when there is
a change in the direction of capacity (increase or decrease) and
each circuit’s capacity is equal.
CAPACITY CONTROL OVERRIDES — The following overrides will modify the normal operation of the routine.
Deadband Multiplier
Multiplier (Configuration
value of 1.0. The range is from 1.0 to 4.0. When set to other
than 1.0, this factor is applied to the capacity Load/Unload
Factor. The larger this value is set, the longer the control will
delay between adding or removing stages of capacity. Figure
11 shows how compressor starts can be reduced over time if
the leaving water temperature is allowed to drift a larger
amount above and below the set point. This value should be set
in the range of 3.0 to 4.0 for systems with small loop volumes.
Figure 12 shows the operating envelope for the compressor.
OPT2 LLCS). The value can be changed
— The user configurable Deadband
SLCTZ.GN) has a default
®
software) and
OPT2
21
First Stage Override
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH
Fig. 10 — Energy Management Module
— If the current capacity stage is zero,
the control will modify the routine with a 1.2 factor on adding
the first stage to reduce cycling. This factor is also applied
when the control is attempting to remove the last stage of
capacity.
Slow Change Override
— The control prevents the capacity
stages from being changed when the leaving fluid temperature
is close to the set point (within an adjustable deadband) and
moving towards the set point.
*Hot gas bypass (minimum load) valve energized.NOTE: These capacity steps may vary due to different capacity
Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
30MP UNIT SIZE
015
020
030
040
045
CONTROL
STEPS
1
2
3
1
2
3
1
2
3
1
2
3
4
1
2
3
4
staging sequences.
CAPACITY STEPS
(% Displacement)
18*
50
100
25*
50
100
34*
50
100
21*
33
67
100
22*
33
67
100
22
47
46
45
44
43
42
41
02004006008001000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED
DEADBAND
STANDARD
DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water Temperature
Fig. 11 — Deadband Multiplier
1
170
140
150
160
110
120
130
80
90
100
50
60
70
30
40
-30-20-1001020304050607080
SCT (F)
SST (F)
LEGEND
Fig. 12 — Operating Envelope for R-410A Compressor
SCT —
Saturated Condensing Temperature
SST —
Saturated Suction Temperature
a30-4969
Ramp Loading
tion
SLCTCRMP) limits the rate of change of leaving
fluid temperature. If the unit is in a Cooling mode and configured for Ramp Loading, the control makes 2 comparisons before deciding to change stages of capacity. The control calculates a temperature difference between the control point and
leaving fluid temperature. If the difference is greater than 4° F
(2.2° C) and the rate of change (°F or °C per minute) is more
than the configured Cooling Ramp Loading value (CRMP),
the control does not allow any changes to the current stage of
capacity.
Low Entering Fluid Temperature Unloading
entering fluid temperature is below the control point, the
control will attempt to remove 25% of the current stages being
used. If exactly 25% cannot be removed, the control removes
an amount greater than 25% but no more than necessary. The
lowest stage will not be removed.
Hot Gas Bypass
energized only when one compressor is running on circuit A. If
the close control feature is enabled the hot gas bypass valve
— Ramp loading (Configura-
may be used as needed to obtain leaving fluid temperature
close to set point.
Cooler Freeze Protection
shutting the chiller down on a Cooler Freeze Protection alarm
by removing stages of capacity. If the cooler fluid selected
is Water, the freeze point is 34 F (1.1 C). If the cooler fluid
selected is Brine, the freeze point is the Brine Freeze Point (Set
Points
references leaving fluid temperature and NOT Brine Freeze
point. If the cooler leaving fluid temperature is less than the
freeze point plus 2.0° F (1.1° C), the control will immediately
— When the
remove one stage of capacity. This can be repeated once every
30 seconds.
Low Saturated Suction Protection
prevent shutting a circuit down due to low saturated suction
conditions by removing stages of capacity. The circuit alert
condition (T116) compares saturated suction temperature to the
— If equipped, the hot gas bypass valve is
configured Brine Freeze Point (Set Points
The Brine Freeze point is a user-configurable value that must
be left at 34 F (1.1 C) for 100% water systems. A lower value
23
— The control will try to prevent
FRZBR.FZ). This alarm condition (A207) only
— The control will try to
FRZBR.FZ).
may be entered for systems with brine solutions, but this value
ENTER
ENTER
ESCAPE
should be set according to the freeze protection level of the
brine mixture. Failure to properly set this brine freeze point value may permanently damage the brazed plate heat exchanger.
The control will initiate Mode 7 (Circuit A) to indicate a circuit’s capacity is limited and that eventually the circuit may
shut down.
Operation of Machine Based on Control
Method and Cooling Set Point Selection Settings —
configuration of the Control Method (Configuration
OPT2CTRL) and Cooling Set Point Select
(ConfigurationSLCTCLSP) variables. All units are factory configured with Cooling Set Point Select set to 0 (single
set point). With the control method set to 0, simply switching
the Enable/Off/Remote Contact switch to the Enable or
Remote Contact position (external contacts closed) will put the
chiller in an occupied state. The control mode (Run
Status
switch is Off and will be 5 (ON LOCAL) when in the Enable
position or Remote Contact position with external contacts
closed.
Two other control methods are available for Machine On/
Off control:
OCCUPANCY SCHEDULE (Configuration
CTRL= 1) — The main base board will use the operating
schedules as defined under the Time Clock mode in the scrolling marquee display. These schedules are identical. The schedule number must be set to 1 for local schedule.
The schedule number can be set anywhere from 65 to 99
for operation under a CCN global schedule. The Enable/Off/
Remote Contact must be in the Enable or Remote Contact position. The control mode (Run Status
1 when the switch is Off. The control mode will be 3 when the
Enable/Off/Remote Contact switch input is On and the time of
day is during an unoccupied period. Similarly, the control
mode will be 7 when the time of day is during an occupied
period.
CCN SCHEDULE (Configuration
2) — An external CCN device such as Chillervisor System
Manager controls the On/Off state of the machine. This CCN
device forces the variable ‘CHIL_S_S’ between Start/Stop to
control the chiller. The control mode (Run Status
VIEWSTAT) will be 1 when the switch is Off. The con-
trol mode will be 2 when the Enable/Off/Remote Contact
switch input is On and the CHIL_S_S variable is ‘Stop.’
Similarly, the control mode will be 6 when the CHIL_S_S variable is ‘Start.’
Table 20 illustrates how the control method and cooling set
point select variables direct the operation of the chiller and the
set point to which it controls. The illustration also shows the
ON/OFF state of the machine for the given combinations.
Machine On/Off control is determined by the
VIEWSTAT) will be 1 (OFF LOCAL) when the
VIEWSTAT) will be
OPT2CTRL =
OPT2
Cooling Set Point Select
SINGLE — Unit operation is based on Cooling Set Point 1
(Set Points
COOLCSP.1).
DUAL SWITCH — Unit operation is based on Cooling Set
Point 1 (Set Points
COOLCSP.1) when the Dual Set
Point switch contacts are open and Cooling Set Point 2 (Set
Points
COOLCSP.2) when they are closed.
DUAL CCN OCCUPIED — Unit operation is based on
Cooling Set Point 1 (Set Points
COOLCSP.1) during the
Occupied mode and Cooling Set Point 2 (Set
Points
COOLCSP.2) during the Unoccupied mode as
configured under the local occupancy schedule accessible only
from CCN. Schedule Number in Table SCHEDOVR (See Appendix B) must be configured to 1. If the Schedule Number is
set to 0, the unit will operate in a continuous 24-hr Occupied
mode. Control method must be configured to 0 (switch). See
Table 20.
4 TO 20 mA INPUT — Unit operation is based on an external
4 to 20 mA signal input to the Energy Management Module
(EMM).
Cooler Pump Control — The AquaSnap® 30MP ma-
chines are configured with the Cooler Pump Control (Configuration
OPT1CPC) = ON.
The maximum load allowed for the Chilled Water Pump
Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil
is powered from the chiller control system. The starter should
be wired between LVT 24 and TB3-1. If equipped, the field-installed chilled water pump starter auxiliary contacts should be
connected in series with the chilled water flow switch between
LVT 16 and LVT 17.
Ice Mode — When Ice Mode is enabled Cooling Setpoint
Select must be set to Dual Switch, Dual 7 day or Dual CCN
Occupied and the Energy Management Module (EMM) must
be installed. Unit operation is based on Cooling Setpoint 1
(CSP.1) during the Occupied mode, Ice Setpoint (CSP.3) dur-
ing the Unoccupied mode with the Ice Done contacts open and
Cooling Setpoint 2 (CSP.2) during the Unoccupied mode with
the Ice Done contacts closed. These 3 set points can be utilized
to develop your specific control strategy.
Service Test (See Table 4) — Both main power and
control circuit power must be on.
The Service Test function should be used to verify proper
operation of condenser output, compressors, minimum load
valve solenoid (if installed), cooler pump, and remote alarm relay. To use the Service Test mode, the Enable/Off/Remote Contact switch must be in the OFF position. Use the display keys
and Table 4 to enter the mode and display TEST. Press
twice so that OFF flashes. Enter the password if required. Use either arrow key to change the TEST value to the
ON position and press . Press and the
button to enter the OUTS or COMP sub-mode.
Table 20 — Control Methods and Cooling Set Points
CONTROL
TYPE
(CTRL)
0 (switch)
2 (Occupancy)
3 (CCN)
*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.
†Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.