Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (elevated structures, mechanical rooms,
etc.). Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment, and any other safety precautions that apply. Follow
all safety codes. Wear safety glasses and work gloves. Use
care in handling, rigging, and setting this equipment, and in
handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE
(American National Standards Institute/American Society
of Heating, Refrigerating and Air-Conditioning Engineers)
15 (Safety Code for Mechanical Refrigeration). The
accumulation of refrigerant in an enclosed space can
displace oxygen and cause asphyxiation. Provide adequate
ventilation in enclosed or low overhead areas. Inhalation of
high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness or death. Misuse can
be fatal. Vapor is heavier than air and reduces the amount
of oxygen available for breathing. Product causes eye and
skin irritation. Decomposition products are hazardous.
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these procedures may result in damage to equipment.
CAUTION
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the electronic
modules or electrical components.
CAUTION
To prevent potential damage to heat exchanger, always run
fluid through heat exchanger when adding or removing
refrigerant charge. Use appropriate brine solutions in cooler
fluid loop to prevent the freezing of brazed plate heat
exchanger when the equipment is exposed to temperatures
below 32 F (0° C). Proof of flow switch is factory installed
on all models. Do NOT remove power from this chiller
during winter shutdown periods without taking precaution
to remove all water from heat exchanger and optional
hydronic system. Failure to properly protect the system
from freezing may constitute abuse and may result in loss
of warranty coverage.
CAUTION
Compressors require specific rotation. Monitor control
alarms during first compressor start-up for reverse rotation
protection. Damage to unit may result.
2
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
CAUTION
Refrigerant charge must be removed slowly to prevent loss
of compressor oil that could result in compressor failure.
CAUTION
Puron® refrigerant (R-410A) systems operate at higher
pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment. If service equipment is not rated for Puron
refrigerant, equipment damage or personal injury may
result.
GENERAL
This publication contains Start-Up, Service, Controls, Operation, and Troubleshooting information for the 30MPW watercooled chillers and the 30MPA air-cooled chillers. For unit
sizes, see Table 1. These liquid chillers are equipped with Com-fortLink controls and conventional thermostatic expansion
valves (TXVs, units 30MP015-045) or electronic expansion
valves (EXVs, units 30MP050-071). The 30MPA units and the
30MPW units with optional medium temperature brine are also
equipped with liquid line solenoid valves (LLSVs).
CAUTION
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out or
bypass components or otherwise depart from recommended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the board or
electrical component.
ing conventions for discussing configuration points for the
local display (scrolling marquee or Navigator™ accessory)
will be used in this manual.
Point names will be written with the mode name first, then
any sub-modes, then the point name, each separated by an
arrow symbol (. Names will also be shown in bold
and italics. As an example, the Minimum Load Valve Select
Point, which is located in the Configuration mode, Option 1
sub-mode, would be written as ConfigurationOPT1MLV.S.
This path name will show the user how to navigate through
the local display to reach the desired configuration. The user
would scroll through the modes and sub-modes using the
and keys. The arrow symbol in the path name
represents pressing to move into the next level of the
menu structure.
When a value is included as part of the path name, it will be
shown at the end of the path name after an equals sign. If the
value represents a configuration setting, an explanation will
be shown in parenthesis after the value. As an example,
ConfigurationOPT1MLV.S= YES (Minimum Load
Valve Select).
Pressing the and keys simultaneously
will scroll an expanded text description of the point name or
value across the display. The expanded description is shown in
the local display tables but will not be shown with the path
names in text.
®
The CCN (Carrier Comfort Network
) point names are also
referenced in the local display tables for users configuring the
unit with CCN software instead of the local display. The CCN
tables are located in Appendix B of the manual.
Basic Control Usage
SCROLLING MARQUEE DISPLAY — Thisdevice is the
keypad interface used for accessing unit information, reading
sensor values, and testing the unit. The scrolling marquee display is a 4-key, 4-character, 16-segment LED (light-emitting
diode) display. Eleven mode LEDs are located on the display
as well as an Alarm Status LED. See Table 2. For further details,
see Appendix A—Local Display Tables on page 72.
The scrolling marquee display module provides the user interface to the ComfortLink control system. The display has up
and down arrow keys, an key, and an key.
These keys are used to navigate through the different levels of
the display structure. See Appendix A—Local Display Tables
on page 72. Press the key until the display is blank
to move through the top 11 mode levels indicated by LEDs on
the left side of the display.
Pressing the and keys simultaneously
will scroll a clear language text description across the display
indicating the full meaning of each display acronym. Clear language descriptions will be displayed in the language of choice.
Pressing the and keys when the display is
blank (Mode LED level) will return the scrolling marquee display to its default menu of rotating display items, found under
Run Status
requiring that it be entered again before changes can be made
to password protected items. After a period of time with no key
activity, the scrolling marquee will display its default menu of
rotating display items found under Run Status
When a specific item is located, the display will flash showing the operator, the item, the item value and then the item units
(if any). Press the key to stop the display at the item
value. Press the key again so that the item value
flashes. Use the arrow keys to change the value or state of an
item and press the key to accept it. Press the
sume. Repeat the process as required for other items.
NOTE: If a value has been forced, the lower right “.” will be
flashing.
See Table 3 and Appendix A for further details.
VIEW. In addition, the password will be disabled,
VIEW.
key and the item, value, or units display will re-
3
Table 2 — Scrolling Marquee Display Menu Structure*
MODE
SUB-MODE
*Throughout this text, the location of items in the menu structure will be
described in the following format:
RUN
STATUS
Auto
View of
Run Status
(VIEW)
Unit Run
Hour and
Start
(RUN)
Circuit and
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Preventive
Ma
intenance
(PM)
Software
Version
(VERS)
Item Expansion (Mode Name
For example, using the language selection item:
Language Selection (Configuration
SERVICE
TEST
Service
Test Mode
(TEST)
Outputs
and Pumps
(OUTS)
Circuit A
Comp
Test
(CMPA)
TEMPERATURES PRESSURES
Unit Temperatures
(UNIT)
Temperatures
Circuit A
(CIR.A)
Sub-mode NameITEM)
DISPLANG)
Pressures
Circuit A
(PRC.A)
SET
POINTS
Cooling
Setpoints
(COOL)
Head
Pressure
Setpoint
(HEAD)
Brine
Freeze
Setpoint
(FRZ)
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit
Inputs
(CRCT)
4-20mA
Inputs
(4-20)
General
Outputs
(GEN.O)
Outputs
Circuit A
(CIR.A)
Outputs
Circuit A
EXV
(A.EXV)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Unit Options 1
Hardware
(OPT1)
Unit Options 2
Controls
(OPT2)
Circuit A EXV
Configuration
(EXV.A)
CCN Network
Configuration
(CCN)
Reset Cool Temp
(RSET)
Set Point and
Ramp Load
(SLCT)
Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
TIME
CLOCK
Time of
Day
(TIME)
Month,
Date, Day,
and Year
(DATE)
Daylight
Savings
Time
(DST)
Local
Holiday
Schedules
(HOL.L)
Schedule
Number
(SCH.N)
Local
Occupancy
Schedule
(SCH.L)
Schedule
Override
(OVR)
OPERATING
MODES
Modes
(MODE)
ALARMS
Current
(CRNT)
Reset
Alarms
(RCRN)
Alarm
History
(HIST)
4
Table 3 — Operating Modes
MODE
NO.
01CSM CONTROLLING CHILLERChillervisor System Manager (CSM) is controlling the chiller.
02WSM CONTROLLING CHILLERWater System Manager (WSM) is controlling the chiller.
03MASTER/SLAVE CONTROLDual Chiller control is enabled.
05
06
07
09
10MINIMUM OFF TIME ACTIVEChiller is being held off by Minutes Off Time (Configuration
13
14
15
16
17
18
19
20
21
23
24
CSM — Chillervisor System Manager
SCT— Saturated Condensing Temperature
WSM — Water System Manager
ITEM EXPANSION DESCRIPTION
RAMP LOAD LIMITEDRamp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature
TIMED OVERRIDE IN EFFECTTimed override is in effect. This is a 1 to 4 hour temporary override of the programmed
LOW COOLER SUCTION TEMPACircuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
SLOW CHANGE OVERRIDESlow change override is in effect. The leaving fluid temperature is close to and moving
DUAL SETPOINTDual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set Points
TEMPERATURE RESETTemperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-
DEMAND LIMITEDDemand limit is in effect. This indicates that the capacity of the chiller is being limited by
COOLER FREEZE PROTECTIONCooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section
LOW TEMPERATURE COOLINGChiller is in Cooling mode and the rate of change of the leaving fluid is negative and
HIGH TEMPERATURE COOLINGChiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.
MAKING ICEChiller is in an unoccupied mode and is using Cooling Set Point 3 (Set Points
STORING ICEChiller is in an unoccupied mode and is controlling to Cooling Set Point 2 (Set Points
HIGH SCT CIRCUIT AChiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
MINIMUM COMP ON TIMECooling load may be satisfied, however control continues to operate compressor to ensure
PUMP OFF DELAY TIMECooling load is satisfied, however cooler pump continues to run for the number of minutes set
LEGEND
is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling
Ramp Loading (Configuration
desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
schedule, forcing unit to Occupied mode. Override can be implemented with unit under
Local (Enable) or CCN (Carrier Comfort Network
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If
the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the saturated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to
decrease capacity as long as either condition exists.
towards the control point.
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2)
during unoccupied periods.
ing fluid set point upward and is currently controlling to the modified set point. The set point
can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to
20 mA signal.
demand limit control option. Because of this limitation, the chiller may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs
or a 4 to 20 mA signal.
for definition). The chiller will be shut down when either fluid temperature falls below the
Freeze point.
decreasing faster than -0.5° F (-0.3° C) per minute. Error between leaving fluid and control
point exceeds fixed amount. Control will automatically unload the chiller if necessary.
Error between leaving fluid and control point exceeds fixed amount. Control will automatically
load the chiller if necessary to better match the increasing load.
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing condensing temperature.
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop
volume.
by the configuration variable Cooler Pump Shutdown Delay (Configuration
PM.DY).
SLCTCRMP). The pull-down limit can be modified, if
®
) control. Override expires after each use.
OPT2DELY).
COOL
OPT1
FRZ
COOL
COOL
5
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
Fig. 1 — Accessory Navigator™ Display Module
The Navigator module provides a mobile user interface to the
ComfortLink control system. The display has up and down
arrow keys, an key, and an key. These
keys are used to navigate through the different levels of the display structure. Press the key until ‘Select a Menu
Item’ is displayed to move through the top 11 mode levels
indicated by LEDs on the left side of the display. See Fig. 1.
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
and keys simultaneously will put the Navigator module into expanded text mode where the full meaning
of all sub-modes, items and their values can be displayed. Pressing the and keys when the display says
‘Select Menu Item’ (Mode LED level) will return the Navigator
module to its default menu of rotating display items (those items
in Run Status
VIEW). In addition, the password will be dis-
abled, requiring that it be entered again before changes can be
made to password protected items. Press the key to
exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name appears on the
left of the display, the value will appear near the middle of the
display and the units (if any) will appear on the far right of the
display. Press the key at a changeable item and the value will begin to flash. Use the up and down arrow keys to change
the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are password protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The default
password is 1111. Use the arrow keys to change the number
and press to enter the digit. Continue with the remaining digits of the password. The password can only be
changed through CCN operator interface software such as
ComfortWORKS, ComfortVIEW and Service Tool.
Adjusting the Contrast
— The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
the Navigator module, press the key until the display reads, “Select a menu item.” Using the arrow keys move
to the Configuration mode. Press to obtain access to
this mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
PAS.EENBL
Pressing will cause the “OFF” to flash. Use the up
or down arrow to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the view
screen. Pressing and simultaneously
allows the user to adjust the display contrast. Use the up or
down arrows to adjust the contrast. The screen’s contrast will
change with the adjustment. Press to accept the
change. The Navigator module will keep this setting as long as
it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
— The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust the backlight of the
Navigator module, press the key until the display
reads, “Select a menu item.” Using the arrow keys move to the
Configuration mode. Press to obtain access to this
mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
PAS.EENBL
Pressing will cause the “OFF” to flash. Use the up
or down arrow keys to change “OFF” to “ON.” Pressing
will illuminate all LEDs and display all pixels in the
view screen. Pressing the up and down arrow keys simultaneously allows the user to adjust the display brightness. Use the
up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will
keep this setting as long as it is plugged in to the LEN bus.
ComfortLink
MODE
Alarm Status
Run Status
Service Test
Temperatures
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
ESC
Operating M
odes
Alarms
ENTER
CHANGING THE DISPLAY LANGUAGE — The factory default language is English. Several other languages are
available, including Spanish, French, and Portugese.
Required Configurations
— Table 4 shows the required con-
figurations for Language Selection.
Table 4 — LANG (Language Selection)
Required Configurations
SUB-
MODE
DISPLANGXLanguage
ITEM DISPLAY
ITEM
DESCRIPTION
Selection
COMMENT
Default: 0
Range: 0 to 3
0=English
1=Espanol
2=Francais
3=Portugese
NOTE: When the Language Selection (Configuration
DISPLANG) variable is changed, all appropriate dis-
play expansions will immediately change to the new language.
No power-off or control reset is required when reconfiguring
Language Selection.
CHANGING THE UNITS OF MEASURE — The factory
default unit of measure is English (for example, °F, ^F, psi).
The display can be changed to metric units (for example, °C,
^C, kPa).
6
Required Configurations
ENTER
ENTER
— Table 5 shows the required con-
figurations for Metric Display.
Table 5 — METR (Metric Display)
Required Configurations
SUB-
MODE
DISPMETROFF/ON Metric DisplayDefault: OFF
ITEM DISPLAY
ITEM
DESCRIPTION
COMMENT
OFF=English
ON=Metric
NOTE: When the Metric Display (Configuration
DISPMETR) variable is changed, all appropriate dis-
play expansions will immediately change to the new units of
measure. No power-off or control reset is required when reconfiguring Metric Display.
CONFIGURATION AND SERVICE PASSWORD —
Items in the Configuration and Service Test modes are password protected. The words PASS and WORD will flash on the
scrolling marquee. Press for the digits 1111 to be
displayed. On the Navigator, press Enter Password and 1111
will be displayed. The default password is 1111. Use the arrow
keys to change each number if required and press to
accept the digit. Continue with the remaining digits of the password.
Changing Service Password
— The password can only be
changed through CCN operator interface software such as
ComfortWORKS™, ComfortVIEW™, and Service Tool.
Caution should be exercised when changing the password.
Once changed, the only way to determine the password is
through one of these devices. To view or change the password,
use the CCN Variable PASSWORD found in Service Configuration/Display.
CONTROLS
General —
ComfortLink electronic control system that controls and monitors all operations of the chiller.
The control system is composed of several components as
listed in the sections below. See Fig. 2 for a typical control box
drawing. See Fig. 3 and 4 for power and control schematics.
See Table 6 for drawing designation.
The 30MP liquid scroll chillers contain the
Main Base Board (MBB) — See Fig. 5. The MBB is
the heart of the ComfortLink control system. It contains the
major portion of operating software and controls the operation
of the machine. The MBB continuously monitors input/output
channel information received from its inputs and from all other
modules. The MBB receives inputs from the discharge and
suction pressure transducers and thermistors. See Table 7. The
MBB also receives the feedback inputs from each compressor
current sensor board and other status switches. See Table 8.
The MBB also controls several outputs. Relay outputs controlled by the MBB are shown in Table 9. Information is transmitted between modules via a 3-wire communication bus or
LEN (Local Equipment Network). The CCN (Carrier Comfort
Network) bus is also supported. Connections to both LEN and
CCN buses are made at the LVT (low voltage terminal).
The Instance Jumper must be on “1.”
AUX Board (AUX) — The AUX board is used with the
digital scroll option (020-045 only). It provides additional inputs and outputs for digital scroll control. See Fig. 6.
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a fieldinstalled accessory. The EMM module receives 4 to 20 mA
inputs for the leaving fluid temperature reset, cooling set point
and demand limit functions. The EMM module also receives
the switch inputs for the field-installed 2-stage demand limit
and ice done functions. The EMM module communicates the
status of all inputs with the MBB, and the MBB adjusts the
control point, capacity limit, and other functions according to
the inputs received.
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and
providing an analog input to the main base board (MBB).
Expansion Valve (EXV) Board (050-071
only) —
directly controls the expansion valves to maintain the correct
compressor superheat.
The EXV board communicates with the MBB and
Enable/Off/Remote Control Switch — The Enable/
Off/Remote Control switch is a 3-position switch used to
control the chiller. When switched to the Enable position the
chiller is under its own control. Move the switch to the Off
position to shut the chiller down. Move the switch to the
Remote Control position and a field-installed dry contact can
be used to start the chiller. The contacts must be capable of
handling a 24 vac, 50-mA load. In the Enable and Remote
Control (dry contacts closed) positions, the chiller is allowed to
operate and respond to the scheduling configuration, CCN
configuration and set point data. See Fig. 7.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the
chiller off immediately. Power to the MBB, EMM, EXV,
AUX, and marquee display is interrupted when this switch is
off and all outputs from these modules will be turned off. See
Fig. 7.
Board Addresses — The main base board (MBB) has a
3-position instance jumper that must be set to 1. The EMM and
EXV board has 4-position DIP switches. All switches are set to
ON for all boards except the AUX board. The AUX board DIP
switch settings are shown on the wiring schematic.
Control Module Communication
RED LED — Proper operation of the control boards can be
visually checked by looking at the red status LEDs. During initial power-up the LED will signal a
followed by a pause. This indicates that the processor is booting. If this pattern repeats, it is an indication that the control
board is in a continuous reboot loop and the board should be replaced. When operating correctly, the red status LEDs should
be blinking in unison at a rate of once every 2 seconds. If the
red LEDs are not blinking in unison, verify that correct power
is being supplied to all modules. Be sure that the main control
is supplied with the current software. If necessary, reload current software. If the problem still persists, replace the control
board. A red LED that is lit continuously or blinking at a rate of
once per second or faster indicates that the control board
should be replaced.
GREEN LED — The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED
which should be blinking whenever power is on. Check LEN
connections for potential communication errors at the board J3
and/or J4 connectors. Communication between modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module. The J4 connector on the MBB
provides both power and communication directly to the
marquee display only.
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
1
/2-second blink 3 times,
7
Table 6 — Component, Power, and Control Drawings
30MPA,MPW UNITDESCRIPTIONLOCATION
Component ArrangementFig. 2, page 9
015
020
030
040
045
050
055
060
065
071
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
Component ArrangementFig. 2, page 9
Power Wiring SchematicFig. 3, page 10
Control Wiring SchematicFig. 4, page 11
LEGEND FOR FIG. 3-5
ALMR— Alarm Relay
AUX— Auxilliary
C—Contactor, Compressor
CB— Circuit Breaker
CCB— Compressor Circuit Breaker
CCH— Crankcase Heater Relay
CNFS— Condenser Water Flow Switch
CNPI— Condenser Pump Interlock
COMP— Compressor
CR— Control Relay
CSB— Current Sensing Board
CWFS— Chilled Water Flow Switch
DGS— Digital Scroll Compressor
DPT— Discharge Pressure Transducer
DTT— Discharge Temperature Thermistor
DUS— Digital Unloader Solenoid
EMM— Energy Management
EXV— Expansion Valve Board/Electronic Expansion Valve
FB— Fuse Block
FIOP— Factory-Installed Option
FU— Fuse
GND— Ground
HPS— High-Pressure Switch
LLSV— Liquid Line Solenoid Valve
LON— Local Operating Network
LVT— Low Voltage Terminal
LWT— Leaving Water Temperature
MBB— Main Base Board
MLV— Minimum Load Valve
MP— Modular Motor Protection
MTT— Motor Temperature Thermistor
NEC— National Electrical Code
OAT— Outdoor-Air Thermistor
OPT— Option
PL— Plug
RGT— Return Gas Temperature
SPT— Suction Pressure Transducer
SW— Switch
TB— Terminal Block
TRAN— Transformer
UPC— Unitary Protocol Converter
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
Accessory or Option Wiring
To indicate common potential only; not to represent
wiring.
8
Fig. 2 — Typical Control Box — 30MP015-071 Units
a30-5984
9
10
Fig. 3 — Typical Power Wiring Schematic — 30MP015-071 Units
Fig. 4 — Typical Control Wiring Schematic — 30MP015-071 Units
ACCESSORY
ALARM RELAY
AUXILIARY
CONTACTOR, COMPRESSOR
CIRCUIT BREAKER
COMPRESSOR CIRCUIT BREAKER
CARRIER COMFORT NETWORK
CRANKCASE HEATER
CRANKCASE HEATER RELAY
COOLER ENTERING FLUID TEMP
COOLER LEAVING FLUID TEMP
CONDENSER FLOW SWITCH
CONDENSER PUMP INTERLOCK
COMPRESSOR
CONTROL RELAY
CURRENT SENSING BOARD
CHILLED WATER TEMP
CHILLED WATER FLOW SWITCH
CHILLED WATER PUMP INTERLOCK
DIGITAL SCROLL
DEMAND LIMIT SWITCH
DISCHARGE PRESSURE TRANSDUCER
DISCHARGE TEMPERATURE THERMISTOR
DIGITAL UNLOADER SOLENOID
ENTERING FLUID TEMPERATURE
ENERGY MANAGEMENT
ENTERING WATER TEMPERATURE
FUSE BLOCK
FACTORY INSTALLED OPTION
FUSE
GROUND
HIGH PRESSURE SWITCH
LOCAL EQUIPMENT NETWORK
LEAVING FLUID TEMPERATURE
LIQUID LINE SOLENOID VALVE
LOW VOLTAGE TERMINAL
LEAVING WATER TEMPERATURE
MAIN BASE BOARD
MINIMUM LOAD VALVE
MODULAR MOTOR PROTECTOR
MOTOR TEMPERATURE THERMISTOR
OUTDOOR AIR THERMISTOR
OUTDOOR FAN MOTOR
OPTION
PLUG
RELAY
RETURN GAS TEMPERATURE
SENSOR
SUCTION PRESSURE TRANSDUCER
SWITCH
TERMINAL BLOCK
TRANSFORMER
UNITARY PROTOCOL CONVERTER
ACCSY
ALMR
AUX
C
CB
CCB
CCN
CH
CCH
CEFT
CLFT
CNFS
CNPI
COMP
CR
CSB
CWP
CWFS
CWPI
DGS
DLS
DPT
DTT
DUS
EFT
EMM
EWT
FB
FIOP
FU
GND
HPS
LEN
LFT
LLSV
LVT
LWT
MBB
MLV
MP
MTT
OAT
OFM
OPT
PL
R
RGT
SEN
SPT
SW
TB
TRAN
UPC
TERMINAL BLOCK
TERMINAL (UNMARKED)
TERMINAL (MARKED)
SPLICE
FACTORY WIRING
FIELD WIRING
ACCESSORY OR OPTION WIRING
TO INDICATE COMMON POTENTIAL
ONLY, NOT TO REPRESENT WIRING
LEGEND
TO MULTI-CHILLER
CONTROLLER ACCESSORY
PANEL IN A DAISY CHAIN
CONFIGURATION (IF APPLICABLE)
11
CEPL130346-01
STATU S
LEN
J1
J2
J4
J3
J5
J6
J7
J8
J9
J10
CCN
RED LED - STATU SGREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
K11
K10K9
K8
K7
K6
K5
K4
K3K2
K1
2 1
Fig. 5 — Main Base Board
NOTE: Not to scale.
1
2
3
4
5
6
7
8
ON
100K
100K
100K
CH1
CH2CH3
CH4CH5CH6CH7CH8
TR1TR2TR3TR4TR5TR6TR7TR8
STAT USSIO (LEN)
LOCATION OF
SERIAL NUMBER
24 VAC
CH13 CH14
J9
J1
CH9
CH10
CH11
CH12
JP2
C61
CH13
D12
JP1
L3
L5
U21
L2
D6
D5
Q5
Y1
D7
D8
S1
D3
U1
Q1
U5
U6
U7
U8
U9
Q10
Q11
U10
J4
J3
J2
U4
U2
Q12
Q60
3 2 1
– G +
3 2 1
– G +
DIP SWITCH
J5
J6
J7J8
CEPL130567-03
32GB500 442 EE
Fig. 6 — AUX Board
NOTE: Not to scale.
12
Carrier Comfort Network® (CCN) Interface —
Fig. 7 — Scrolling Marquee, Enable/Off/Remote Contact Switch, and
Emergency On/Off Switch Locations
LEGEND
CB — Circuit Breaker
SW — Switch
Fig. 8 — CCN Wiring Diagram
The 30MP chiller units can be connected to the CCN if
desired. The communication bus wiring is a shielded,
3-conductor cable with drain wire and is supplied and installed
in the field. See Table 10. The system elements are connected
to the communication bus in a daisy chain arrangement. The
positive pin of each system element communication connector
must be wired to the positive pins of the system elements on
either side of it. This is also required for the negative and
signal ground pins of each system element. Wiring connections
for CCN should be made at LVT See Fig. 8 and consult the
CCN Contractor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon*, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. Wire manufactured by Alpha (2413
or 5463), American (A22503), Belden (8772), or Columbia
(02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication
bus that a color coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.)
3. Connect the red wire to (+) terminal on LVT of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
4. The RJ14 CCN connector on LVT can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Service Tool).
SCROLLING MARQUEE
ENABLE/OFF/REMOTE
CONTROL SWITCH
DISPLAY
CB1
SW1OFF
CB2CB3
REMOTE
CONTROL
ENABLE
EMERGENCY
ON-OFF SWITCH
OFF
SW2
ON
* Teflon is a registered trademark of DuPont.
13
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector. If
conditions return to normal, check the CCN connector and
cable. Run new cable if necessary. A short in one section of
the bus can cause problems with all system elements on the
bus.
CURRENT SENSING BOARD (CSB) — The CSB is used
to monitor the status of each compressor by measuring current
and providing an analog input to the main base board (MBB)
or compressor expansion module (CXB).
ENABLE/OFF/REMOTE CONTACT SWITCH — The
Enable/Off/Remote Control switch is a 3-position switch used
to control the unit. When switched to the Enable position, the
unit is under its own control. Move the switch to the Off position to shut the unit down. Move the switch to the Remote Control position and a field-installed dry contact can be used to
start the unit. The contacts must be capable of handling a
24 vac, 50 mA load. In the Enable and Remote Control (dry
contacts closed) positions, the unit is allowed to operate and respond to the scheduling configuration, CCN configuration and
set point data. See Fig. 7.
EMERGENCY ON/OFF SWITCH — The Emergency On/
Off switch should only be used when it is required to shut the
unit off immediately. Power to the MBB, CXB, AUX, EMM,
and scrolling marquee display is interrupted when this switch is
off and all outputs from these modules will be turned off. See
Fig. 7.
HIGH PRESSURE SWITCH (HPS) — Each unit is protected with a high pressure switch to prevent excessive condensing
pressure. See Table 11 for switch details.
Table 11 — High Pressure Switch
CARRIER PART
NUMBER
HK02ZZ001*
HK02ZZ003
* Available for 30MPA,MPW015-045, 30MPA050-071, 30MPW050071 high condensing option.
OPENS ATCLOSES AT
650 ± 10 psig
(4482 ± 69 kPa)
558 ± 15 psig
(384 ± 103 kPa)
500 ± 15 psig
(3447 ± 103 kPa)
435 ± 29 psig
(2999 ± 200 kPa)
PRESSURE TRANSDUCERS — Each refrigerant circuit is
equipped with a suction and discharge pressure transducer. The
suction pressure transducers have a yellow body with a pressure range of –6.7 to 420 psig (–46 to 2896 kPa) while the discharge transducers have a red body with a pressure range of
14.5 to 667 psig (100 to 4599 kPa). These inputs connect to the
MBB (main base board) and are used to monitor the status of
the unit and to ensure the unit operates within the compressor
envelope. The transducers are used to protect the compressor
from operating at too low or too high of a pressure condition. In
some cases, the unit may not be able to run at full capacity. The
MBB will automatically reduce the capacity of a circuit as
needed to maintain specified maximum/minimum operating
pressures. Table 12 summarizes pressure transducer
characteristics.
14
Table 12 — Pressure Transducer Identification
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Fig. 9 — Space Temperature Sensor
Typical Wiring (33ZCT55SPT)
TRANSDUCER
DischargeHK05ZZ001Red
SuctionHK05SZ003Yellow
CARRIER
PART NUMBER
BODY
COLOR
PRESSURE
RANGE,
psi (kPa)
14.5 to 667
(100 to 4599)
–6.7 to 420
(–46 to 2896)
Sensors — The electronic control uses 2 to 8 thermistors to
sense temperatures for controlling chiller operation. See
Table 7. These sensors are outlined below. Thermistors cooler
leaving fluid, cooler entering fluid, discharge temperature, circuit A return gas temperature, outdoor-air temperature sensor
or dual LWT sensor, accessory remote space temperature sensor, condenser entering fluid temperature sensor, and condenser leaving fluid temperature sensor are identical in temperature
versus resistance and voltage drop performance. All thermistors are 5,000 ohmsat 77 F (25 C) except the space temperature thermistor which is 10,000 ohms. Space temperature
thermistor (SPT) is 10,000 ohms at 77 F (25 C). See
Thermistors section on page 46 for temperature-resistancevoltage drop characteristics.
COOLER LEAVING FLUID SENSOR (LWT) — The thermistor is installed in a well in the factory-installed leaving fluid
piping connecting to the bottom of the brazed-plate heat
exchanger.
COOLER ENTERING FLUID SENSOR (EWT) — The thermistor is installed in a well in the factory-installed entering fluid
piping connecting to the top of the brazed-plate heat exchanger.
CONDENSER LEAVING FLUID SENSOR (CDLT)
(30MPW Only) — The thermistor is installed in a well in the
field-installed leaving fluid piping connecting to the bottom of
the brazed-plate heat exchanger. The thermistor and well are a
field-installed accessory. The thermistor and well are a fieldinstalled accessory. See Table 13 for thermistor and well part
numbers. This sensor must be enabled, Configura-
tion
OPT1CDWS= ENBL.
CONDENSER ENTERING FLUID SENSOR (CDET)
(30MPW Only) — The thermistor is installed in a well in the
field-installed entering fluid piping connecting to the top of the
brazed-plate heat exchanger. See Table 13 for thermistor and
well part numbers.
Table 13 — Thermistors and Wells
THERMISTOR
PART NO.
HH79NZ014
HH79NZ029
00PPG0000B105A
COMPRESSOR RETURN GAS TEMPERATURE SENSOR (RGT.A) — This accessory thermistor can be installed
in a well located in the suction line. Use Carrier part number
HH79NZ029. This thermistor is standard for unit sizes 050-
071. For 015-045 this accessory must be enabled, Configura-
tion
OPT1RG.EN = ENBL.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —
This sensor is an accessory that is remotely mounted and used
for outdoor air temperature reset. See Table 7. Use Carrier part
number HH79NZ023. If sensor is attached, it must be enabled,
(Configuration
cast information.
Outside Air Temperature can be forced to a value at the
scrolling marquee or Navigator device. To force the value, access the parameter Temperatures
to view the current value. Press again and
use the up and down arrow keys to display the desired value;
DESCRIPTIONWELL PART NO.
3 in., 5,000 ohm
Thermistor
4 in., 5,000 ohm
Thermistor
1-1/2 in.,5,000 ohm
Thermistor
10HB50106801
10HB50106802
00PPG00000B000A
OPT1OAT.E=ENBL) and include broad-
UNITOAT. Press
then press to accept the value. On the scrolling marquee, the “.” in the lower right corner will flash. On the Navigator device, a flashing “f” will be displayed next to the value.
To clear the forced value, press followed by the up
and down arrow keys simultaneously. The value will revert to
the actual reading and the flashing “.” or “f” will be removed.
DUAL LEAVING WATER TEMPERATURE SENSOR
(DLWT) — This input can be connected to the LVT. See Table 7. For dual chiller applications (parallel only are supported), connect the dual chiller leaving fluid temperature sensor
(see Table 13 for thermistor and well part numbers) to the outside air temperature input of the Master chiller. If outside-air
temperature is required for reset applications, connect the sensor to the Slave chiller and configure the slave chiller to broadcast the value to the Master chiller. The broadcast must be enabled, (Configuration
BCSTOAT.B=ON). If there are
only two units, the master chiller must be configured to acknowledge the broadcast (Configuration
BCSTBC.AK
=ON). If there are more than two units, at least one unit must
be configured to acknowledge the broadcast (Configura-
tion
BCSTBC.AK =ON).
DISCHARGE TEMPERATURE THERMISTOR
(DTT) — This sensor is only used on units with a digital
compressor. The sensor is mounted on the discharge line close
to the discharge of the digital compressor. It attaches to the discharge line using a spring clip and protects the system from
high discharge gas temperature when the digital compressor is
used. This sensor is a connected to the AUX board.
SPACE TEMPERATURE SENSOR — Space temperature
sensors are used to measure the interior temperature of a
building.
Space Temperature can be forced to a value at the scrolling
marquee or Navigator device. To force the value, access the
parameter Temperatures
UNITSPT. Press to
view the current value. Press again and use the up
and down arrow keys to display the desired value; then press
to accept the value. On the scrolling marquee, the “.”
in the lower right corner will flash. On the Navigator device, a
flashing “f” will be displayed next to the value. To clear the
forced value, press followed by the up and down arrow keys simultaneously. The value will revert to the actual
reading and the flashing “.” or “f” will be removed.
The following type of SPT sensor is available:
• Space temperature sensor (33ZCT55SPT) with timed
override button (see Fig. 9)
TIMED OVERRIDE
BUTTON (SW1)
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
15
All of the above sensors are 10,000 ohms at 77 F (25 C),
SPT (T10) PART NO. 33ZCT55SPT
SENSOR
SEN
SEN
LVT
22
23
Fig. 10 — Typical Space Temperature
Sensor Wiring
T-55 SPACE
SENSOR
CCN+
CCN GND
CCN-
TO CCN
COMM 1
BUS (PLUG)
AT UNIT
1
2
3
4
5
6
Fig. 11 — CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector
Type II thermistors and are connected to the low voltage terminal (LVT). The sensor should be mounted approximately 5 ft
(1.5 m) from the floor in an area representing the average temperature in the space. Allow at least 4 ft (1.2 m) between the
sensor and any corner. Mount the sensor at least 2 ft (0.6 m)
from an open doorway.
Space temperature sensor wires are to be connected to
terminals in the unit main control box. The space temperature
sensor includes a terminal block (SEN) and a RJ11 female
connector. The RJ11 connector is used for access into the Carrier Comfort Network
®
(CCN) at the sensor.
To connect the space temperature sensor (Fig. 10):
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect 1 wire of the twisted pair to one
SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.
2. Connect the other ends of the wires to terminals 3 and 4
on LVT located in the unit control box.
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN (Fig. 11):
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 10 for
acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (–) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the
space temperature sensor.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
In lieu of a single sensor providing space temperature, an averaging sensor array of either 4 or 9 sensors may be employed to
provide a space temperature as shown in Fig. 12. With this
control scheme, only T55 space temperature sensors (P/N
33ZCT55SPT) can be used. Total sensor wiring must not
exceed 1,000 ft (305 m).
NOTE: The Timed Override feature from a space temperature
sensor requires a single space temperature sensor connected to
the unit. This feature does not function when used with
averaging space temperature sensor arrays.
Energy Management Module (Fig. 13) — This
factory-installed option (FIOP) or field-installed accessory is
used for the following types of temperature reset, demand
limit, and/or ice features:
• 4 to 20 mA leaving fluid temperature reset (requires
field-supplied 4 to 20 mA generator)
• 4 to 20 mA cooling set point (requires field-supplied 4 to
20 mA generator)
• Discrete inputs for 2-step demand limit (requires fieldsupplied dry contacts capable of handling a 24 vac,
50 mA load)
• 4 to 20 mA demand limit (requires field-supplied 4 to
20 mA generator)
• Discrete input for Ice Done switch (requires fieldsupplied dry contacts capable of handling a 24 vac,
50 mA load)
See the Temperature Reset and Demand Limit sections on
pages 31 and 34 for further details.
CAUTION
Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink controls use half wave rectification. A signal
isolation device should be utilized if a full wave bridge signal generating device is used.
Loss-of-Cooler Flow Protection — A proof-of-
cooler flow device is factory installed in all chillers.
Condenser Flow Protection — A proof-of-condens-
er flow protection accessory can be field installed in the condenser water piping of all chillers. The unit must be configured
for the input to be enabled, Configuration
OPT1
D.FL.S=ENBL.
Thermostatic Expansion Valves (TXV) — All
30MP015-045 units are equipped from the factory with conventional TXVs. Two styles of TXVs are employed. The
30MPA units utilize a 15% bleed port type valve. The 30MPW
units do not require a bleed port type valve. The 30MPA units
and 30MPW units with medium temperature brine also have
factory-installed liquid line solenoids. The liquid line solenoid
valves are not intended to be a mechanical shut-off.
16
The TXV is set at the factory to maintain approximately 8 to
12° F (4.4 to 6.7° C) suction superheat leaving the cooler by
monitoring the proper amount of refrigerant into the cooler. All
TXVs are adjustable, but should not be adjusted unless abso-lutely necessary.
Electronic Expansion Valves (EXV) — All
J6
6
7
RED
BLK
RED
RED
BLK
BLK
BLK
RED
BLK
RED
SENSOR 1SENSOR 2SENSOR 3SENSOR 4
J6
6
7
RED
BLK
RED
BLK
SENSOR 2
SENSOR 1
RED
RED
BLK
SENSOR 3
SENSOR 4
BLK
BLK
RED
RED
RED
BLK
BLK
SENSOR 8
SENSOR 9
SENSOR 5
RED
BLK
SENSOR 6
SENSOR 7
BLK
RED
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
Fig. 12 — Space Temperature Averaging
LEGEND
Factory Wiring
Field Wiring
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
30MP050-071 units are equipped from the factory with EXVs.
The 30MPA and 30MPW units with medium brine temperature brine also have the EXV set at the factory to maintain
9°F (5° C) suction superheat leaving the cooler by metering the
proper amount of refrigerant into the cooler.
The EXV is designed to limit the cooler saturated suction
temperature to 50 F (12.8 C). This makes it possible for the unit
to start at high cooler fluid temperatures without overloading
the compressor.
Capacity Control — Capacity control is determined by
the difference between the leaving fluid temperature and the
Control Point (Run Status
change. The Control Point (CTPT) is the current set point modified by a temperature reset command. This can be from the
temperature reset function or the dual chiller routine. The capacity control routine runs every 30 seconds. The algorithm attempts to maintain the Control Point at the desired set point.
Additionally, the control calculates a rise per stage knowing
which compressor is on, its capacity and the temperature difference across the cooler (entering fluid temperature minus leaving fluid temperature) to determine the best time to turn on or
off the next compressor, institute Minimum Load Control, or
change the digital response, if equipped. Entering and Leaving
fluid temperatures can be monitored at the unit's interface device Run StatusLWT. With this information, a capacity ratio is calculated to determine whether to make any changes to the current stage of
capacity. This ratio, Capacity Load/Unload Factor (Run Sta-
tus
VIEWLOD.F) value ranges from –100% to +100%
times Deadband Multiplier (Configuration
VIEWEWT and Run StatusVIEW
VIEWCTPT) and its rate of
SLCTZ.GN).
See Deadband Multiplier on this page for more information. If
the next stage of capacity is a compressor, the control starts
(stops) a compressor when the ratio reaches +100% (–100%)
times Deadband Multiplier (Z.GN). Once a change in capacity
occurs, a 90-second time delay is initiated and the capacity
stage is held during this time delay.
When the unit is at stage zero (Requested Stage Run Sta-
tus
VIEWSTGE=0) as part of the capacity control routine,
the control adds a 1.2 factor on adding the first stage to reduce
cycling.
If the unit is equipped with a digital compressor, it is normally the first compressor started. If the lead compressor is a
digital compressor, and is enabled and available (not in alarm),
the compressor will start fully loaded for 90 seconds prior to
starting to cycle between loaded and unloaded. Once the digital
compressor is on, positive changes in LOD.F will cause the
compressor to load. Negative changes to LOD.F will cause the
compressor to unload. This process can occur every 30 seconds. Changes to the digital loading are not subject to the 90second delay. See Digital Scroll Option on page 36 for additional information.
If the unit is equipped with Minimum Load Control, it will
not be active until the unit is on its last stage of capacity. It too
is treated as a stage of compression. As a result, Minimum
Load Control will be activated when capacity is decreasing,
Requested Stage STGE=1, and Capacity Load/Unload Factor
LOD.F= -100% times Deadband Multiplier (Z.GN). See Table
14 for capacity step information.
MINUTES LEFT FOR START — This value is displayed
only in the network display tables (using Service Tool,
ComfortVIEW™ or ComfortWORKS™ software) and
17
represents the amount of time to elapse before the unit will start
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4J3
J5
J6
J7
LEN
STATU S
RED LED - STATU S
GREEN LED LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH
Fig. 13 — Energy Management Module
its initialization routine. This value can be zero without the
machine running in many situations. These can include being
unoccupied, ENABLE/OFF/REMOTE CONTROL switch in
the OFF position, CCN not allowing unit to start, Demand
Limit in effect, no call for cooling due to no load, and alarm or
alert conditions present. If the machine should be running and
none of the above are true, a minimum off time (DELY, see
below) may be in effect. The machine should start normally
once the time limit has expired.
MINUTES OFF TIME — The Minutes Off Time feature
(Configuration
OPT2DELY) is a user-configurable time
period used by the control to determine how long unit operation is delayed after the unit has been enabled. This delay is
initiated following the Enable-Off-Remote Switch being
placed in “Enable” position or “Remote” with remote contacts
closed, or if power is applied/restored to the unit with the Enable-Off-Remote Switch in a position that would allow the unit
to operate. Typically, this time period is configured when multiple machines are located on a single site. For example, this
gives the user the ability to prevent all the units from restarting
at once after a power failure. A value of zero for this variable
does not mean that the unit should be running.
If Minutes Off Time is active, the control will indicate Op-
erating Mode, Minutes Off Time Active (Operating
Modes
MODEMD10 will indicate YES).
CAPACITY CONTROL OVERRIDES — The following
overrides will modify the normal operation of the routine.
Deadband Multiplier
Multiplier (Configuration
— The user configurable Deadband
SLCTZ.GN) has a default
value of 1.0. The range is from 1.0 to 4.0. When set to other
than 1.0, this factor is applied to the capacity Load/Unload
Factor. The larger this value is set, the longer the control will
delay between adding or removing stages of capacity. Figure
14 shows how compressor starts can be reduced over time if
the leaving water temperature is allowed to drift a larger
amount above and below the set point. This value should be set
in the range of 3.0 to 4.0 for systems with small loop volumes.
First Stage Override
— If the current capacity stage is zero,
the control will modify the routine with a 1.2 factor on adding
the first stage to reduce cycling. This factor is also applied
when the control is attempting to remove the last stage of
capacity.
Slow Change Override
— The control prevents the capacity
stages from being changed when the leaving fluid temperature
is close to the set point (within an adjustable deadband) and
moving towards the set point.
18
Table 14 — Part Load Data Percent Displacement, Standard Units
47
46
45
44
43
42
41
02004006008001000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED
DEADBAND
STANDARD
DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water Temperature
Fig. 14 — Deadband Multiplier
30MP UNIT SIZE
015
020
030
040
045
050
055
060
065
071
*Minimum Load Valve energized. Minimum load valve will only be
energized with decreasing capacity. Minimum load valve cannot be
enabled with digital compressor operation on 30MP020-045 units.
NOTE: The capacity steps listed for the 30MP055-071 may vary
from what is depicted due to the different size compressors used in
the circuit.
CAPACITY
(% Displacement)
WITH MINIMUM LOAD VALVE
Ramp Loading — Ramp loading (Configuration
SLCTCRMP) limits the rate of change of leaving fluid tem-
perature. If the unit is in a Cooling mode and configured for
Ramp Loading, the control makes 2 comparisons before deciding to change stages of capacity. The control calculates a temperature difference between the control point and leaving fluid
temperature. If the difference is greater than 4° F (2.2° C) and
the rate of change (°F or °C per minute) is more than the configured Cooling Ramp Loading value (CRMP), the control
does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading
entering fluid temperature is below the control point, the
control will attempt to remove 25% of the current stages being
used. If exactly 25% cannot be removed, the control removes
an amount greater than 25% but no more than necessary. The
lowest stage will not be removed.
Minimum Load Control
control is energized only when one compressor is running on
the circuit and capacity is decreasing.
Cooler Freeze Protection
shutting the chiller down on a Cooler Freeze Protection alarm
— When the
— If equipped, the minimum load
— The control will try to prevent
by removing stages of capacity. If the cooler fluid selected
is Water, the freeze point is 34 F (1.1 C). If the cooler fluid
selected is Brine, the freeze point is the Brine Freeze Point (Set
Points
FRZBR.FZ). This alarm condition (A207) only
references leaving fluid temperature and NOT Brine Freeze
point. If the cooler leaving fluid temperature is less than the
freeze point plus 2.0° F (1.1° C), the control will immediately
remove one stage of capacity. This can be repeated once every
30 seconds.
Low Saturated Suction Protection
prevent shutting a circuit down due to low saturated suction
conditions by removing stages of capacity. The circuit alert
— The control will try to
condition (T116) compares saturated suction temperature to the
configured Brine Freeze Point (Set Points
FRZBR.FZ).
The Brine Freeze point is a user-configurable value that must
be left at 34 F (1.1 C) for fresh water systems. A lower value
may be entered for systems with brine solutions, but this value
should be set according to the freeze protection level of the
brine mixture. Failure to properly set this brine freeze point value may permanently damage the brazed plate heat exchanger.
The control will initiate Mode 7 (Circuit A) to indicate a
19
circuit’s capacity is limited and that eventually the circuit may
shut down.
Time, Day, and Date — Many features of the 30MP
controls require that the time, day and date be properly set.
This is especially helpful when troubleshooting alarms, as they
are reported with a time and date stamp. ComfortLink controls
also have the ability to automatically adjust for daylight savings time, when configured. The unit time and date is set at the
factory based in the Eastern Time Zone.
To set the time, Time Clock
Minute) is the item. The time clock is programmed in a 24hour format, 00.00 to 23.59. See Table 15.
To set the month, Time Clock
is the item. This item follows the standard convention, 1=January, 2=February, etc.
To set the day of the month, Time Clock
(Day of Month) is the item.
To set the day of the week, Time Clock
(Day of Week) is the item. This item uses the following convention: 1=Monday, 2=Tuesday, 3=Wednesday, etc. This setting is important if using the internal schedule.
To set the year, Time Clock
tury) is the item. This item follows the convention of a 4-digit
year, such as 2014.
TIMEHH.MM (Hour and
DATEMNTH (Month)
DATEDOM
DATEDAY
DATEYEAR (Year of Cen-
Table 16 lists the required configurations for these settings.
TIME/DATE BROADCAST — The 30MP unit controls
have the ability to broadcast the time and date on the network.
If the CCN Time/Date Broadcast configuration Configura-
tion
BCSTT.D.BC=ON, the control will send the time and
date out onto the CCN bus once a minute. If this device is on a
CCN network, it is important to make sure that only one
device on the bus has this configuration set to ON. If more
than one time broadcaster is present, problems with the time
will occur. If the unit is installed on a network, another unit
must be configured to be Broadcast Acknowledger, Configu-
ration
BCSTBC.AK. Only one unit can be the Broadcast
Acknowledger. See Table 17 for required configurations.
DAYLIGHT SAVINGS TIME — The 30MP controls have
the ability to automatically adjust the time for daylight savings
time. To utilize this feature, several items must be configured,
including a start date and time to add as well as an end date.
All items are found in the Daylight Saving Time sub-mode,
Time Clock
tion
DST and the Broadcast sub-mode, Configura-
BCST. See Table 18 for required configurations.
NOTE: Only the time and date broadcaster can perform daylight savings time adjustments. Even if the unit is stand-alone,
the user may want to set Configuration
BCSTT.D.BC to
ON to accomplish the daylight savings function. To disable the
daylight savings time feature, set T.D.BC to OFF.
Table 15 — Time Required Configuration
TIME CLOCK MODE
SUBMODEITEMDISPLAYITEM DESCRIPTIONCOMMENT
TIMEHH.MMXX.XXHour and Minute
24-hour format
Range: 00.00 to 23.59
Table 16 — Day and Date Required Configurations
TIME CLOCK MODE
SUBMODEITEMDISPLAYITEM DESCRIPTIONCOMMENT
Range: 1-12
(1=January, 2=February, etc.)
Range: 1-7
(1=Monday, 2=Tuesday, etc.)
DATE
MNTHXXMonth of Year
DOMXXDay of MonthRange: 1-31
DAYXDay of Week
YEARXXXXYear of Century
Table 17 — Broadcast Required Configurations
CONFIGURATION MODE
SUBMODEITEMDISPLAYITEM DESCRIPTIONCOMMENT
T.D.BCON/OFFCCN Time/Date Broadcast
BCST
BC.AKON/OFFCCN Broadcast Ack'er
*Only the time and date broadcaster can perform daylight savings
time adjustments. Even if the unit is stand-alone, the user may want
to set this to ON to accomplish the daylight savings function.
Default: Off
Must be set to ON to enable automatic
Daylight Savings Time correction.*
Default: Off
One unit on the network must be set to
ON. The broadcast unit cannot be the
acknowledger.
Operation of Machine Based on Control
Method — This term refers to how the machine is started
and stopped. Several control methods are available to enable
and disable the unit. Machine On/Off control is determined by
the configuration of the Control Method, Configura-
tion
OPT2CTRL.
ENABLE-OFF-REMOTE CONTROL — With the control
method set to Enable-Off-Remote Contact, CTRL=0 (Switch),
simply switching the Enable/Off/Remote Control switch to the
Enable or Remote Control position with external contacts
closed will place the unit in an occupied state.
Under normal operation, the Control Mode (Run Sta-
tus
VIEWSTAT ) will be 1 (Off Local) when the switch is
in the Off position or in the Remote Control position with external contacts open, and will be 5 (On Local) when in the Enable position or Remote Control position with external contacts
closed.
OCCUPANCY SCHEDULE — With the control method set
to Occupancy, CTRL=2 (Occupancy), the Main Base Board
will use the operating schedules as defined under the Time
Clock mode in the scrolling marquee display. If Time
Clock
SCH.N (Schedule Number) is set to 0, the unit will
remain in an occupied mode continuously.
In either case, and whether operating under a Local Sched-
ule or under a CCN Schedule, under normal operation, Run
Status
VIEWSTAT (Control Mode) will be 1 (Off Local)
when the Enable/Off/Remote Control switch is Off or in Remote Control with the external contacts open. The control
mode will be 3 (Off Time) when the Enable/Off/Remote Control switch is in Enable or Remote Control with external contacts closed and the time of day is during an unoccupied period.
Similarly, the control mode will be 7 (On Time) when the time
of day is during an occupied period.
Local Schedule
— Local Schedules are defined by schedule
the Enable/Off/Remote Control switch must be in the Enable
or Remote Control position with external contacts closed.
For this option to function properly, the correct time, day
and date must be set. See the section Time, Day, and Date on
page 20. The time clock is programmed in a 24-hour format,
00.00 to 23.59. If configured, the 30MP controls can
automatically adjust the time for daylight savings time. See the
section Daylight Savings Time on page 20.
If holidays are to be used, they must be configured. Thirty
holidays are provided as part of the local schedules, HD.01
through HD.30. Each holiday requires a Holiday Month, Time
Clock
HOL.LHD.xxMON (Holiday Start Month)
where “xx” is a number from 01 to 30; the Holiday Start Day
of Month, Time Clock
where “xx” is a number from 01 to 30; and the Holiday Duration, Time Clock
where “xx” is a number from 1 to 99. Holidays that do not occur on fixed dates will require annual programming.
In the example shown in Table 19, the following holidays
are to be programmed: January 1 for one day, July 4 for one
day, December 24 for two days.
Eight separate time periods, Period 1 through 8, are available as part of the local schedule. Each period has Monday
through Sunday and a Holiday day flag, and occupied and unoccupied times. For example, an occupied time from 6:00 AM
to 8:00 PM is desired from Monday through Friday. For Saturday an occupied period from 6:00 AM to 12:00 Noon is desired. On Sunday and holidays the unit is to remain unoccupied. This schedule is shown graphically in Fig. 15.
To program this schedule, Time Clock
Number) must change from 0 to a number between 1 and 64.
In this example, the Schedule Number will be 1. Two of the
eight time periods are required to create this schedule. See
Table 20.
Default: 4 (April)
Range: 1 to 12
(1=January, 2=February, etc.)
Daylight Savings Start Week
Default: 1
Range: 1 to 5
Daylight Savings Start Day
Default: 7 (Sunday)
Range: 1 to 7
(1=Monday, 2=Tuesday, etc.)
CCN Global Schedule
SCH.N from 65 to 99 indicate operation under a CCN Global
Schedule. For unit operation based on a CCN Global Schedule,
the Enable/Off/Remote Control switch must be in the Enable
or Remote Control position with external contacts closed.
In the example in Table 21, the CCN Global Schedule the
unit is to follow is 65. To set up the unit to follow this schedule,
Time Clock
SCH.N must be modified.
Any unit can be the Global Schedule Broadcaster. When
using a Global Broadcast Schedule, the schedule broadcaster
must have the Global Schedule Broadcast, ConfigurationBCSTG.S.BC=ON and all other devices on the network
— Schedule Numbers, Time Clock
interface device, the number of hours requested must be set in
Time Clock
Table 22.
Once a non-zero value has been entered, the unit will resume an occupied period for the duration of the time programmed. The number of hours in the override time period will
be displayed in OVR.T and will count down as the time period
progresses. This value cannot be changed until the override period has expired or is cancelled. The override time period can
be cancelled by changing the OVR.T value to 0. This can be
done at the unit’s interface device or through CCN communications by writing to the point OVR_EXT.
should have their Global Schedule Broadcast flag set to
Configuration
BCSTG.S.BC=OFF. There can be only
one broadcaster of a specific schedule. The unit set to be the
schedule broadcaster must have a schedule number from 65 to
99, and the Local Schedule configured as described above. It
will broadcast the internal time schedule once every 2 minutes.
Table 21 — CCN Global Schedule Required
SUBMODE ITEM DISPLAY
SCH.NXX
Timed Override
Configuration
TIME CLOCK MODE
ITEM
DESCRIPTION
Schedule
Number XX
COMMENT
Default: 0
Range: 0 to 99
Example = 65
— There are several ways to override the
occupancy schedule to keep the unit in an occupied period.
Schedule overrides can be initiated at the unit’s interface with
either the scrolling marquee or Navigator™ device, from a
space temperature sensor equipped with a timed override button (see unit Installation Instructions for selection and wiring
information), or through CCN communications. Initiation of
an override period can only be accomplished if the unit is in an
unoccupied period. If Timed Override is in effect, Operating
Modes
MODEMD06, Timed Override in Effect will be
active. Override expires after each initiation.
Timed Override from Scrolling Marquee/Navigator Device —
A timed override period can be initiated with the unit’s interface device. To initiate an override period from the unit’s
SUBMODE ITEM DISPLAY
OVROVR.TX
Timed Override from Space Temperature Sensor with Override
Button — A timed override period can be initiated using a
space temperature sensor with an override button from the
space.
NOTE: This feature requires a single space temperature sensor
connected to the unit. It does not function when used with
averaging space temperature sensor arrays.
To configure this feature, Time Clock
(Override Time Limit) must be set to a non-zero value. This
determines the maximum number of hours the override period
can extend an occupied period when the override button is
pushed. This item has a range of 0 to 4 hours and should be set
to the limit desired for the override period. See Table 23.
Pressing the override button on the Space Temperature Sensor will initiate an override period. The override button must
be pressed for 2 to 4 seconds for the control to acknowledge the
call. The control will ignore a momentary press of the override
button. However, if the override button is held for longer than 4
seconds, a Space Temperature Thermistor Failure alarm will be
generated. The number of hours in the override time period
24
OVROVR.T (Timed Override Hours). See
Table 22 — Timed Override Required
Configuration
TIME CLOCK MODE
DESCRIPTION
Timed Override
ITEM
Hours
COMMENT
Default: 0
Range: 0 to 4
OVROVR.L
will be displayed in Time Clock
OVROVR.T (Timed
Override Hours) and will count down as the time period progresses. See Table 22.
Once a non-zero value has been entered, the unit will resume an occupied period for the duration of the time programmed. The number of hours in the override time period will
be displayed in OVR.T and will count down as the time period
progresses. This value cannot be changed until the override period has expired or is cancelled. The override time period can
be cancelled by changing the OVR.T value to 0. This can be
done at the unit’s interface device or through CCN communications by writing to the point OVR_EXT.
Table 23 — Space Temperature Override Required
Configuration
TIME CLOCK MODE
SUBMODEITEM DISPLAY
OVROVR.LX
ITEM
DESCRIPTION
Override Time
LImit
COMMENT
Default: 0
Range: 0 to 4
Timed Override from CCN — A timed override period can be
initiated through CCN communications by writing to the point
OVR_EXT. This point has a range of 0 to 4 hours and should
be set for the desired amount of time.
The number of hours in the override time period will be displayed in Time Clock
OVROVR.T (Timed Override
Hours) and will count down as the time period progresses. See
Table 22.
Once a non-zero value has been entered, the unit will resume an occupied period for the duration of the time programmed. The number of hours in the override time period will
be displayed in OVR.T and will count down as the time period
progresses. This value cannot be changed until the override period has expired or is cancelled. The override time period can
be cancelled by changing the OVR.T value to 0. This can be
done at the unit’s interface device or through CCN communications by writing to the point OVR_EXT.
CCN CONTROL — With the control method set to CCN
Control, CTRL=3 (CCN), an external CCN device controls the
On/Off state of the machine. This CCN device forces the point
CHIL_S_S between Start/Stop to control the unit.
Under normal operation, Run Status
VIEWSTAT
(Control Mode) will be 1 (Off Local) when the Enable/Off/Remote Control switch is in the Off position or in the Remote
Control position with the remote external contacts open. With
the Enable/Off/Remote Control switch in the Enable position
or in Remote Control position with the remote external contacts closed, the Control Mode will be 2 (Off CCN) when the
CHIL_S_S variable is “Stop.” Similarly, the control mode will
be 6 (On CCN) when the CHIL_S_S variable is “Start.”
Units controlled via communications by a separate thirdparty building automation system through a translator or UPC
Open Controller must be set to CCN Control, CTRL=3. If the
unit is to be monitored only via communications, CTRL=3
(CCN Control) is not required.
Emergency Stop
— A controls feature exists to shut down the
machine in the event of an emergency. Writing to the CCN
Point EMSTOP, the command “EMSTOP” will force the machine to stop all mechanical cooling immediately and shut
down. While this feature is enabled, the Control Mode Run
Status
VIEWSTAT=4 (Emergency) will be displayed. For
the machine to operate normally, the EMSTOP point value
should be “ENABLE.”
Cooling Set Point Select
SINGLE — Unit operation is based on Cooling Set Point 1
(Set Points
DUAL SWITCH — Unit operation is based on Cooling Set
Point 1 (Set Points
COOLCSP.1).
COOLCSP.1) when the Dual Set
Point switch contacts are open and Cooling Set Point 2 (Set
Points
COOLCSP.2) when they are closed.
DUAL CCN OCCUPIED — Unit operation is based on
Cooling Set Point 1 (Set Points
COOLCSP.1) during the
Occupied mode and Cooling Set Point 2 (Set
Points
COOLCSP.2) during the Unoccupied mode as
configured under the local occupancy schedule accessible only
from CCN. Schedule Number in Table SCHEDOVR (see Appendix B) must be configured to 1. If the Schedule Number is
set to 0, the unit will operate in a continuous 24-hr Occupied
mode. Control method must be configured to 0 (switch). See
Table 24.
4 TO 20 mA INPUT — Unit operation is based on an external
4 to 20 mA signal input to the Energy Management Module
(EMM).
Ice Mode — When Ice Mode is enabled, Cooling Setpoint
Select must be set to Dual Switch, Dual 7 day or Dual CCN
Occupied and the energy management module (EMM) must be
installed. Unit operation is based on Cooling Setpoint 1
(CSP.1) during the Occupied mode, Ice Setpoint (CSP.3)
during the Unoccupied mode with the Ice Done contacts open
and Cooling Setpoint 2 (CSP.2) during the Unoccupied mode
with the Ice Done contacts closed. These 3 set points can be
utilized to develop your specific control strategy. Ice Mode is
not compatible with the Multi-Chiller Controller Accessory
Panel.
Table 24 illustrates how the control method and cooling set
point select variables direct the operation of the chiller and the
set point to which it controls. The illustration also shows the
ON/OFF state of the machine for the given combinations.
Cooler Pump Control — The AquaSnap
®
30MP ma-
chines are configured with the Cooler Pump Control (Configu-
ration
OPT1CPC) = ON.
The maximum load allowed for the Chilled Water Pump
Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil
is powered from the chiller control system. The starter should
be wired between LVT 24 and TB3-1. If equipped, the field-installed chilled water pump starter auxiliary contacts should be
connected in series with the chilled water flow switch between
LVT 16 and LVT 17.
Alarm Routing — A CCN feature within the 30MP units
allows for alarm broadcasting.
ALARM ROUTING CONTROL — Alarms recorded on
the 30MP unit can be routed through the CCN. To configure
this option, the ComfortLink control must be configured to
determine which CCN elements will receive and process
alarms. Input for the decision consists of eight digits, each of
which can be set to either 0 or 1. Setting a digit to 1 specifies
that alarms will be sent to the system element that corresponds
to that digit. Setting all digits to 0 disables alarm processing.
The factory default is 00000000. See Figure 16. The default
setting is based on the assumption that the unit will not be connected to a network. If the network does not contain a ComfortVIEW™, ComfortWORKS™, TeLink, DataLINK™, or
BAClink module, enabling this feature will only add unnecessary activity to the CCN communication bus.
The CCN Point ALRM_CNT is the variable and can be
modified with ComfortVIEW software or Network Service
Tool only. It cannot be modified with the scrolling marquee or
Navigator™ display.
Typical configuration of the Alarm Routing variable is
11010000. This Alarm Routing status will transmit alarms to
ComfortVIEW software, TeLink, BAClink, and DataLINK.
Alarm routing is not supported with the LON Translator.
25
Table 24 — Control Methods and Cooling Set Points
DESCRIPTION STATUS POINT
Alarm Routing 0 0 0 0 0 0 0 0 ALRM_CNT
Building Supervisor,
ComfortVIEW™,
ComfortWORKS
™
,
BACnet Communications (UPC),
BACnet Translator
TeLink,
Autodial Gateway
Unused
Alarm Printer interface Module,
BACLink or DataLINK™
Unused
Fig. 16 — Alarm Routing Control
Control Type
(CTRL)
0 (Switch)—
1 or 2
(Occupancy)
3 (CCN)
* Energy management module (EMM) required for operation.
† Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.
ALARM EQUIPMENT PRIORITY — The ComfortVIEW
software uses the equipment priority value to determine the
order in which to sort alarms that have the same level. A priority of 0 is the highest and would appear first when sorted. A
priority of 7 would appear last when sorted. For example, if
two units send out identical alarms, the unit with the higher priority would be listed first. The default is 4. The CCN point
EQP_TYPE is the variable and can be changed when using
ComfortVIEW software or Network Service Tool only. This
variable cannot be changed with the scrolling marquee or Navigator display.
COMMUNICATION FAILURE RETRY TIME —
This variable specifies the amount of time that will be allowed
to elapse between alarm retries. Retries occur when an alarm is
not acknowledged by a network alarm acknowledger, which
may be either ComfortVIEW software or TeLink. If acknowledgement is not received, the alarm will be re-transmitted after
the number of minutes specified in this decision. The factory
default for this item is 10 minutes with a range of 1 to 254 minutes. The CCN Point RETRY_TM is the variable and can be
changed with ComfortVIEW software or Network Service
Tool only. This variable cannot be changed with the scrolling
marquee or Navigator display.
RE-ALARM TIME — This variable specifies the amount of
time that will be allowed to elapse between re-alarms. A realarm occurs when the conditions that caused the initial alarm
continue to persist for the number of minutes specified in this
decision. Re-alarming will continue to occur at the specified
interval until the condition causing the alarm is corrected. To
disable this feature, set the variable to 255. The factory default
is 30 minutes with a range of 1 to 254. The CCN Point REALARM is the variable and can be changed with ComfortVIEW software or Network Service Tool only. This variable
cannot be changed with the scrolling marquee or Navigator
display.
ALARM SYSTEM NAME — This variable specifies the
system element name that will appear in the alarms generated
by the unit control. The name can be up to 8 alphanumeric
characters long and should be unique to the unit. The factory
default is SPLIT. The CCN point ALRM_NAM is the variable
and can be changed with ComfortVIEW software or Network
Service Tool only. This variable cannot be changed with the
scrolling marquee or Navigator display.
Cooler Pump Sequence of Operation — At any-
time the unit is in an ON status, as defined by the one of the
following conditions, the cooler pump relay will be enabled.
1. The Enable-Off-Remote Switch in ENABLE,
(CTRL=0).
2. Enable-Off-Remote Switch in REMOTE with a
Start-Stop remote control closure (CTRL=0).
3. An Occupied Time Period from an Occupancy Schedule
in combination with items 1 or 2 (CTRL=2).
4. A CCN Start-Stop Command to Start in combination
with items 1 or 2 (CTRL=3).
Certain alarm conditions and Operating Modes will turn the
cooler pump relay ON. This sequence will describe the normal
operation of the pump control algorithm.
When the unit cycles from an ON state to an OFF state, the
cooler pump output will remain energized for the Cooler Pump
Shutdown Delay (Configuration
lay is configurable from 0 to 10 minutes. The factory default is
1 minute. If the pump output was deenergized during the transition period, the pump output will not be energized.
The Cooler Pump Relay will be energized when the machine is ON. The chilled water pump interlock circuit consists
of a chilled water flow switch and a field-installed chilled water
pump interlock. If the chilled water pump interlock circuit does
not close within five (5) minutes of starting, an A200 - Cooler
OPT1PM.DY). The de-
Flow/Interlock failed to close at Start-Up alarm1 will be generated and chiller will not be allowed to start.
If the chilled water pump interlock or chilled water flow
switch opens for at least three (3) seconds after initially being
closed, an A201 - Cooler Flow 1 Interlock Contacts Opened
During Normal Operation alarm will be generated and the machine will stop.
Condenser Pump/Condenser Fan Output Control —
control either a condenser fan output or a condenser pump output depending on the unit configuration.
UNITTYPE = 2 (air cooled), then the output will be off as
long as capacity is equal to 0 and will be energized 5 seconds
before a compressor is started and remain energized until
capacity is 0 again.
UNITTYPE = 3 (water cooled), then the output will be used
for condenser pump control and additional configuration is required. To enable the condenser pump control, use Configura-
tion
pump control (0), on when occupied (1), and on when
capacity is greater than 0 (2).
The main base board (MBB) has the capability to
If the unit is configured for Configuration
If the unit is configured for Configuration
OPT1D.PM.E. The pump can be configured for no
Configuring and Operating Dual Chiller Control —
two units supplying chilled fluid on a common loop. This
control algorithm is designed for parallel fluid flow arrangement
only. One chiller must be configured as the master chiller, the
other as the slave. An additional leaving fluid temperature
thermistor (Dual Chiller LWT) must be installed as shown in
Fig. 17 and 18 and connected to the master chiller. Refer to Sensors section, page 15, for wiring. The CCN communication bus
must be connected between the two chillers. Connections can be
made to the CCN screw terminals on LVT. Refer to Carrier
Comfort Network
mation. Configuration examples are shown in Tables 25 and 26.
example the master chiller will be configured at address 1 and
the slave chiller at address 2. The master and slave chillers
must reside on the same CCN bus (Configuration
ration
have Lead/Lag Chiller Enable (Configuration
uration
the master chiller and SLVE for the slave. Also in this example,
the master chiller will be configured to use Lead/Lag Balance
Select (Configuration
ance Delta (Configuration
chiller run-times weekly. The Lag Start Delay (Configura-
tion
will prevent the lag chiller from starting until the lead chiller
has been at 100% capacity for the length of the delay time. Parallel configuration (Configuration
only be configured to YES. The variables LLBL, LLBD and
LLDY are not used by the slave chiller.
tion of Control Method (Configuration
the Master chiller. The Slave chiller should always be configured for CTRL=0 (Switch). If the chillers are to be controlled
by Remote Controls, both Master and Slave chillers should be
enabled together. Two separate relays or one relay with
two sets of contacts may control the chillers. The Enable/Off/
Remote Control switch should be in the Remote Control
position on both the Master and Slave chillers. The Enable/Off/
Remote Control switch should be in the Enable position for
CTRL=2 (Occupancy) or CTRL=3 (CCN Control).
The dual chiller routine is available for the control of
®
Interface section, page 13, for wiring infor-
Refer to Table 25 for dual chiller configuration. In this
CCN
RSET
CCNB) but cannot have the same CCN address (Configu-
CCNCCNA). Both master and slave chillers must
LLEN) configured to ENBL. Master/Slave Select (Config-
RSETMSSL) must be configured to MAST for
RSETLLBL) and Lead/Lag Bal-
RSETLLBD) to even out the
RSETLLDY) feature will be set to 10 minutes. This
RSETPARA) can
Dual chiller start/stop control is determined by configura-
1. Slave Control Method (CTRL) must be configured for 0.
2. Slave CCN Address (CCNA) must be different than Master.
3. Slave CCN Bus Number (CCNB) must be the same as Master
4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.
30
Both chillers will stop if the Master chiller Enable/Off/
MASTER
CHILLER
SLAVE
CHILLER
LEAVING
FLUID
RETURN
FLUID
THERMISTOR
WIRING
INSTALL DUAL CHILLER LWT
LEAVING FLUID TEMPERATURE
THERMISTOR (T10) HERE*
*See Fig. 18 for thermistor and well part numbers.
Fig. 17 — Dual Chiller Thermistor Location
Fig. 18 — Dual Leaving Water Thermistor Well
PART
NUMBER
DIMENSIONS in. (mm)
A B
10HB501068013.10 (78.7)1.55 (39.4)
10HB50106802 4.10 (104.1)1.28 (32.5)
00PPG000008000A 2.32 (58.86) 1.31 (33.28)
A
B
1/4 N.P.T.
0.505/0.495
0.61
DIA
6” MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
10HB50106801 and 10HB50106802
Brass Well Thermistor — 00PPG000008000A
Remote Control switch is in the Off position. If the Emergency
Stop switch is turned off or an alarm is generated on the Master
chiller the Slave chiller will operate in a Stand-Alone mode.
If the Emergency Stop switch is turned off or an alarm is
generated on the Slave chiller the Master chiller will operate in
a Stand-Alone mode.
The master chiller controls the slave chiller by changing its
Control Mode (Run Status
VIEWSTAT) and its operat-
ing setpoint or Control Point (Run Status
B
0.38
(9.53)
A
Temperature Reset — The control system is capable of
handling leaving-fluid temperature reset based on return cooler
fluid temperature. Because the change in temperature through
the cooler is a measure of the building load, the return temperature reset is in effect an average building load reset method.
The control system is also capable of temperature reset based
on outdoor-air temperature (OAT), space temperature (SPT), or
from an externally powered 4 to 20 mA signal. Accessory sensors must be used for SPT reset (33ZCT55SPT) and for OAT
reset (HH79NZ014). The energy management module (EMM)
must be used for temperature reset using a 4 to 20 mA signal.
See Tables 27 and 28.
VIEWCT.PT).
0.25
(6.35)
IMPORTANT: Care should be taken when interfacing with
other control systems due to possible power supply differences: full wave bridge versus half wave rectification. Connection of control devices with different power supplies
may result in permanent damage. ComfortLink controls
incorporate power supplies with half wave rectification. A
signal isolation device should be utilized if the signal generator incorporates a full wave bridge rectifier.
To use outdoor air or space temperature reset, four variables
must be configured. In the Configuration mode under the submode RSET, items (Configuration
RSETCRST),
(ConfigurationRSETRM.NO), (Configuration
RSETRM.F), and (ConfigurationRSETRT.DG)
must be properly set. See Table 29 — Configuring Outdoor Air
and Space Temperature Reset. The outdoor air reset example
provides 0° F (0° C) chilled water set point reset at 85.0 F
(29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at
55.0 F (12.8 C) outdoor-air temperature. The space temperature reset example provides 0° F (0° C) chilled water set point
reset at 72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) reset at 68.0 F (20.0 C) space temperature. The variable CRST
should be configured for the type of reset desired. The variable
RM.NO should be set to the temperature that no reset should
occur. The variable RM.F should be set to the temperature that
maximum reset is to occur. The variable RM.DG should be set
to the maximum amount of reset desired. Figures 19 and 20 are
examples of outdoor air and space temperature resets.
To use return reset, four variables must be configured. In the
Configuration mode under the sub-mode RSET, items CRST,RT.NO, RT.F and RT.DG must be properly set. See Table 30
— Configuring Return Temperature Reset. This example provides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C)
cooler T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The
variable RT.NO should be set to the cooler temperature difference (T) where no chilled water temperature reset should occur. The variable RT.F should be set to the cooler temperature
difference where the maximum chilled water temperature reset
should occur. The variable RM.DG should be set to the maximum amount of reset desired.
To verify that reset is functioning correctly proceed to Run
Status mode, sub-mode VIEW, and subtract the Active
Setpoint (Run Status
Point (Run Status
VIEWSETP) from the Control
VIEWCTPT) to determine the degrees
reset.
Under normal operation, the chiller will maintain a constant
leaving fluid temperature approximately equal to the chilled
fluid set point. As the cooler load varies, the entering cooler
fluid will change in proportion to the load as shown in Fig. 21.
Usually the chiller size and leaving-fluid temperature set point
are selected based on a full-load condition. At part load, the fluid temperature set point may be colder than required. If the
leaving fluid temperature were allowed to increase at part load,
the efficiency of the machine would increase.
Return fluid reset allows for the leaving temperature set
point to be reset upward as a function of the return fluid temperature or, in effect, the building load (See Fig. 22).
31
Table 27 — Menu Configuration of 4 to 20 mA Cooling Set Point Control
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
MODE
(RED LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
DISP
UNIT
OPT1
OPT2
CCN
CONFIGURATION
EXV.A
RSET
SLCTCLSP0COOLING SETPOINT SELECT
Table 28 — 4 to 20 mA Reset
SUB-MODE
RSET
NOTE: The example above shows how to configure the chiller for
4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F
reset will occur at 20.0 mA. An EMM (energy management module)
is required.
KEYPAD
ENTRY
ITEM DISPLAY
CRST1
MA.DG
5.0 F
(2.8 C)
Table 29 — Configuring Outdoor Air and Space Temperature Reset
ITEM
EXPANSION
COMMENT
0Scrolling Stops
0Flashing ‘0’
3Select ‘3’
3Change Accepted
ITEM
EXPANSION
COOLING RESET
TYPE
DEGREES COOL
RESET
0 = no reset
1 = 4 to 20 mA input
2 = Outdoor air temp
3 = Return Fluid
4 = Space Temperature
Default: 0° F (0° C) Reset at 20 mA
Range: –30 to 30 F (–16.7 to 16.7 C)
COMMENT
MODE
(RED LED)
CONFIGURATION
KEYPAD
ENTRY
SUB-
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
Outdoor
Air
Space
DISP
UNIT
OPT1
OPT2
CCN
EXV.A
RSETCRST 24
RM.NO85 F72 F
RM.F55 F68 F
RM.DG15 F6 F
ITEM
EXPANSION
COOLING RESET
TYPE
REMOTE - NO
RESET TEMP
REMOTE - FULL
RESET TEMP
REMOTE - DEGREES
RESET
COMMENT
2 = Outdoor-Air Temperature
(Connect to LVT-4,5)
4 = Space Temperature
(Connect to LVT-3,4)
Default: 125.0 F (51.7 C)
Range: 0° to125 F
(–17.8 to 51.7 C)
Default: 0.0° F (-17.7 C)
Range: 0° to 125 F
(–17.8 to 51.7 C)
Default: 0° F (0° C)
Range: –30 to 30 F
(–16.7 to -16.7 C)
32
Table 30 — Configuring Return Temperature Reset
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 19 — Outdoor-Air Temperature Reset
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 20 — Space Temperature Reset
LEGEND
Fig. 21 — Standard Chilled Fluid
Temperature Control — No Reset
EWT —
Entering Water (Fluid) Temperature
LWT —
Leaving Water (Fluid) Temperature
DESIGN RISE
EWT
LWT
LWT TEMPERATURE (F)
LWT TEMPERATURE (C)
54
54
50
48
46
44
42
12.2
11.1
10.0
8.9
7.8
6.7
5.6
010203040506070 8090100
% UNIT LOADING
SET POINT — 44 FDESIGN RISE — 10 F
Fig. 22 — Return Fluid Reset
MODE
(RED LED)
CONFIGURATION
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
DISPTESTON/OFFTEST DISPLAY LEDs
UNITTYPEXUNIT TYPE
OPT1FLUD XCOOLER FLUID
OPT2CTRL XCONTROL METHOD
CCN
EXV.A
RSETCRST 3 COOLING RESET TYPE
RT.NO10.0 F
RT.F2.0 F
RT.DG5.0 F
RETURN FLUID - NO
RESET TEMP
RETURN FLUID - FULL
RESET TEMP
RETURN - DEGREES
RESET
COMMENT
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM TB6-2,3)
2 = Outdoor-Air Temperature
3 = Return Fluid
4 = Space Temperature
(Connect to TB5-5,6)
Default: 10.0 F (5.6 C)
Range: 0° to 30 F COOLER DT
(0.0 to 16.7 C)
Default: 0 F (–17.8 C)
Range: 0° to 30 F COOLER DT
(0.0 to 16.7 C)
Default: 0 F (0 C)
Range: –30 to 30°F (–16.7 to 16.7 C)
33
10
9
8
7
6
5
4
3
CHANGE IN
Reset Amount (°F or °C)
LIMIT SETPOINT
2
1
0
012345678910
ΔT (°F or °C), Entering Fluid Temperature - Leaving Fluid Temperature
RT.F =2
DESIGN RISE
CHANGE IN CHILLED
FLUID, ΔT
RESET AMOUNTRT.NO = 10
RT.DG = 5
Demand Limit — Demand limit is a feature that allows
50% CAPACITY AT 20 mA
75% CAPACITY AT 12 mA
100% CAPACITY AT 4 mA
0
2
4
6
8
10
12
14
16 18
20
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT
100
80
60
40
20
0
MAX. ALLOWABLE LOAD (%)
Fig. 23 — 4 to 20-mA Demand Limiting
the unit capacity to be limited during periods of peak energy usage. Three types of demand limiting can be configured. The
first type is through 2-stage switch control, which will reduce
the maximum capacity to 2 user-configurable percentages. The
second type is by 4 to 20 mA signal input which will reduce the
maximum capacity linearly between 100% at a 4 mA input signal (no reduction) down to the user-configurable level at a
20 mA input signal. The third type uses the CCN Loadshed
module and has the ability to limit the current operating capacity to maximum and further reduce the capacity if required.
NOTE: The 2-stage switch control and 4 to 20-mA input signal types of demand limiting require the energy management
module (EMM).
For units with the digital compressor option, digital operation is ignored when determining capacity limit of the machine.
Since Demand Limit controls the number of compressors operating, the requested demand limit must allow for the corresponding capacity of the full digital compressor capacity plus
any remaining compressors. For example, a 30MP045 unit
with a digital compressor will require a demand limit of at least
33% for the first compressor to be energized. No compressor
operation will be allowed prior to this demand limit level. Digital operation below 33% will require a demand limit of at least
33% to allow a compressor to start. Digital operation between
33 and 67% will require a demand limit of at least 67% to allow 2 compressors to be operating. Finally, for digital operation
above 67%, demand limit must be at 100% to allow for all
compressors to be operating.
To use demand limit, select the type of demand limiting to
use. Then configure the demand limit set points based on the
type selected.
DEMAND LIMIT (2-Stage Switch Controlled) — To configure demand limit for 2-stage switch control, set the Demand
Limit Select (Configuration
configure the 2 Demand Limit Switch points (Configura-
tion
RSETDLS1) and (ConfigurationRSETDLS2)
to the desired capacity limit. See Table 31. Capacity steps are
controlled by 2 relay switch inputs field wired to LVT as shown
in Fig. 4.
For demand limit by 2-stage switch control, closing the first
stage demand limit contact will put the unit on the first demand
limit level. The unit will not exceed the percentage of capacity
entered as Demand Limit Switch 1 set point (DLS1). Closing
contacts on the second demand limit switch prevents the unit
from exceeding the capacity entered as Demand Limit Switch
2 set point. The demand limit stage that is set to the lowest demand takes priority if both demand limit inputs are closed. If
the demand limit percentage does not match unit staging, the
unit will limit capacity to the closest capacity stage.
To disable demand limit, configure DMDC to 0. See
Table 31.
RSETDMDC) to 1. Then
EXTERNALLY POWERED DEMAND LIMIT (4 to
20 mA Controlled) — To configure demand limit for 4 to 20
mA control, set the Demand Limit Select (Configura-
tion
RSETDMDC) to 2. Then configure the Demand
Limit at 20 mA (Configuration
RSETDM20) to the
maximum loadshed value desired. Connect the output from an
externally powered 4 to 20 mA signal to terminal block LVT,
terminals 7 and 8 (+,–). Refer to the unit wiring diagram for
these connections to the optional/accessory energy management module and terminal block. The control will reduce allowable capacity to this level for the 20 mA signal. See
Table 31 and Fig. 23.
CAUTION
Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink controls use half wave rectification. A signal
isolation device should be utilized if a full wave bridge
signal generating device is used.
DEMAND LIMIT (CCN Loadshed Controlled) — To configure Demand Limit for CCN Loadshed control set the Demand Limit Select (Configuration
RSETDMDC) to 3.
Then configure the Loadshed Group Number (Configura-
tion
RSETSHNM), Loadshed Demand Delta (Configu-
ration
RSETSHDL), and Maximum Loadshed Time
(ConfigurationRSETSHTM). See Table 31.
The Loadshed Group number is established by the CCN
system designer. The ComfortLink controls will respond to a
Redline command from the Loadshed control. When the
Redline command is received, the current stage of capacity is
set to the maximum stages available. Should the loadshed control send a Loadshed command, the ComfortLink controls will
reduce the current stages by the value entered for Loadshed
Demand delta. The Maximum Loadshed Time is the maximum
length of time that a loadshed condition is allowed to exist. The
control will disable the Redline/Loadshed command if no
Cancel command has been received within the configured
maximum loadshed time limit.
Cooling Set Point (4 to 20 mA) — A field supplied
and generated, externally powered 4 to 20 mA signal can be
used to provide the leaving fluid temperature set point. Connect
the signal to LVT-10,8 (+,–). See Table 31 for instructions to
enable the function. Figure 24 shows how the 4 to 20 mA signal is linearly calculated on an overall 10 F to 80 F range for
fluid types (Configuration
point will be limited by the fluid (FLUD) type. Be sure that the
chilled water loop is protected at the lowest temperature.
OPT1FLUD) 1 or 2. The set
34
Table 31 — Configuring Demand Limit
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Fig. 24 — Cooling Set Point (4 to 20 mA)
EMM — Energy Management Module
MODE
KEYPAD
ENTRY
SUB-MODE
CONFIGURATION
*Seven items skipped in this example.
KEYPAD
ENTRY
ITEM DISPLAYITEM EXPANSIONCOMMENT
DISPTESTON/OFFTest Display LEDs
UNITTYPE XUnit Type
OPT1FLUDXCooler Fluid
OPT2CTRLXControl Method
CCN
CCNAXCCN Address
EXV.A
RSETCRSTXCooling Reset Type
DMDC*XDemand Limit Select
DM20XXX %Demand Limit at 20 mA
SHNMXXX
SHDLXXX%
SHTMXXX MIN
DLS1XXX %
DLS2XXX %
Loadshed Group
Number
Loadshed Demand
Delta
Maximum Loadshed
Time
Demand Limit
Switch 1
Demand Limit
Switch 2
Default: 0
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
Range: 0 to 100
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
Default: 60 min.
Range: 0 to 120 min.
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
90
(32)
80
(27)
70
(21)
60
(15)
50
(10)
40
(4.4)
Set Point, F (C)
30
(–1)
20
(–7)
10
(–12)
0
(–17)
0
FLUD=2 (Medium Temp Brine)
Minimum Set Point
14 F (–10.0 C)
5
10
FLUD=1 (Water)
Minimum Set Point
38 F (3.3 C)
mA Signal
Maximum Set Point
70 F (21.1 C)
1520
25
35
Digital Scroll Option — The 30MP020-045 units have
a factory-installed option for a digital scroll compressor which
provides additional stages of unloading for the unit. The digital
compressor is always installed in the A1 compressor location.
When a digital compressor is installed, a digital unloader solenoid (DUS) is used on the digital compressor. Digital Scroll
Option not available for units controlled by the MultiChiller Controller Accessory panel.
DIGITAL SCROLL OPERATION — A digital scroll operates in two stages — the “loaded state” when the solenoid
valve is de-energized and the “unloaded state” when the solenoid valve is energized. During the loaded state, the compressor operates like a standard scroll and delivers full capacity and
mass flow.
However, during the unloaded state, there is no capacity
and no mass flow through the compressor. The capacity of the
system is varied by varying the time the compressor operates
in an unloaded and loaded state during a 15-second period. If
the DUS is energized for 7 seconds, the compressor will be
operating at 47% capacity. If the DUS is energized for 10 seconds, the compressor will be operating at approximately 33%
of its capacity. Capacity is the time averaged summation of
loaded and unloaded states, and its range is continuous from
the minimum configured capacity to 100%. Regardless of
capacity, the compressor always rotates with constant speed.
As the compressor transitions from a loaded to unloaded state,
the discharge and suction pressures will fluctuate and the compressor sound will change.
The ComfortLink controller controls and integrates the operation of the DUS into the compressor staging routine to
maintain temperature control. When a digital compressor is installed, an additional discharge gas temperature thermistor
(DTT) is installed along with the AUX board for control of the
DUS.
DIGITAL COMPRESSOR CONFIGURATION — When a
digital compressor is installed, the configuration parameter
(Configuration
There is also a maximum unload time configuration, (Config-
uration
020,030) or 7 seconds (sizes 040,045), which indicates the
maximum unloading for the digital compressor is 47%. This is
done to optimize efficiency of the system.
MINIMUM LOAD CONTROL — Minimum load control is
generally not recommended for split systems. If installed, the
feature must be enabled in the controls. Minimum load control
or hot gas bypass cannot be used in conjunction with the digital
scroll option.
Minimum load control can only be added to standard compressor units in the field. This feature will not operate with an
optional digital compressor and when the digital function is enabled (Configuration
minimum load valve, confirm that the digital compressor option is disabled and set Minimum Load Valve Select to YES,
(Configuration
NOTE: Minimum Load Control and Digital Compressor operation cannot be used together.
Table 32 — Configuring Minimum Load Control
ITEMEXPANSIONCOMMENTS
A1.TY
MLV.S
UNITA1.TY) is configured to YES.
UNITMAX.T) that is set to 10 seconds (sizes
UnitA1.TY=YES). To enable the
OPT1MLV.S=YES). See Table 32.
CONFIGURATIONUNIT
Range: NO/YES
Compressor A1
Digital?
CONFIGURATIONOPT1
Minimum Load Vlv
Select
Default: Depends on product configuration
NO = Not Equipped
Value must be set to NO
Range: NO/YES
Default: NO
Set to YES to activate
If equipped and enabled, the Minimum Load Control valve
is active as the last stage of capacity when the unit is unloading.
MAINTENANCE REMINDER — The 30MP ComfortLink
controls have the ability to provide a reminder for service personnel that regularly scheduled strainer maintenance is required. Maintenance interval is a field-configurable item. The
service interval should be adjusted for the job site conditions.
See Table 33.
Table 33 — Configuring Maintenance Reminder
RUN STATUSPMSTRN
ITEMEXPANSIONCOMMENTS
Range: 0 to 65,500 hrs
SI.STStrainer Srvc Interval
Default: 8760 hrs
Setting SI.ST to 0 disables
the feature
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,
complete Start-Up Checklist for 30MP Liquid Chiller at
end of this publication (pages CL-1 to CL-8). The checklist
assures proper start-up of a unit, and provides a record of
unit condition, application requirements, system information, and operation at initial start-up.
Do not attempt to start the chiller until following checks
have been completed.
System Check
1. Check all auxiliary components, such as chilled fluid
pumps, air-handling equipment, condenser pump or other
equipment to which the chiller supplies liquid. Consult
manufacturer’s instructions. Verify that any pump interlock contacts have been properly installed. If the unit has
field-installed accessories, be sure all are properly installed and wired correctly. Refer to unit wiring diagrams.
2. Use the scrolling marquee display to adjust the Cooling
Set Point.
3. Fill chilled fluid circuit with clean water (with recommended inhibitor added) or other non-corrosive fluid to
be cooled. Bleed all air out of the high points of the system. If chilled water is to be maintained at a temperature
below 40 F (4.4 C), a brine of sufficient concentration
must be used to prevent freeze-up at anticipated suction
temperatures. To ensure sufficient loop volume, see
Tables 34 and 35.
4. Check tightness of all electrical connections.
5. Oil should be visible in the compressor sight glass(es).
See Fig. 25. An acceptable oil level in the compressors is
1
from
/8 to 3/8 of sight glass when the compressors are off.
Adjust the oil level as required. See Oil Charge section on
page 45 for Carrier approved oils.
6. Crankcase heaters must be firmly attached to compressors, and must be on for 24 hours prior to start-up
(30MPA015-045, 30MPA,MPW050-071 only).
7. Electrical power source must agree with unit nameplate.
8. Check rotation of scroll compressors. Monitor control
alarms during first compressor start-up for reverse rotation protection alarm.
36
Table 34 — Minimum Flow Rates and Minimum Loop Volume — English
Crankcase heaters are wired into the control circuit, so they
are always operable as long as the main power supply disconnect is on (closed), even if any safety device is open.
Compressor heaters must be on for 24 hours prior to the
start-up of any compressor. Equipment damage could result
if heaters are not energized for at least 24 hours prior to
compressor start-up.
Compressor crankcase heaters must be on for 24 hours before start-up. To energize the crankcase heaters, close the field
disconnect. Leave the compressor circuit breakers off/open.
The crankcase heaters are now energized.
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-8.
PRELIMINARY CHARGE (30MPA) — Refer to GTAC II
(General Training Air Conditioning), Module 5, Charging, Recovery, Recycling and Reclamation for charging procedures.
The 30MPA units (condenserless) are shipped with a nitrogen holding charge only. Leak check the 30MPA unit, discharge and liquid lines, and the condenser. Be sure the liquid
START-UP AND OPERATION
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,
review Start-Up Checklist at the back of this publication.
The checklist assures proper start-up of a unit and provides
a record of unit condition, application requirements, system
information, and operation at initial start-up.
line service valve is open. After leak check is completed, system must be evacuated and dehydrated. Following the evacuation, the system must be fully charged.
The liquid charging method is recommended for complete
charging or when additional charge is required.
Using the liquid charging method and charging by weight
procedure, charge the circuit with the amount of Puron refrigerant (R-410A) with the sum of the operating charge listed in Table 36 for the base unit, the liquid line charge and the operating
charge of the condenser as the preliminary charge.
NOTE: For liquid line piping, use the following information:
½ in. (12.7 mm) liquid line - 0.6 lb per 10 linear feet
(0.27 kg per 3 m)
5
/8 in. (15.9 mm) liquid line - 1.0 lb per 10 linear feet
(0.45 kg per 3 m)
7
/8 in. (22.2 mm) liquid line - 2.0 lb per 10 linear feet
(0.91 kg per 3 m)
1
1
/8 in. (28.6 mm) liquid line - 3.5 lb per 10 linear feet
(1.59 kg per 3 m)
3
1
/8 in. (34.9 mm) liquid line - 5.1 lb per 10 linear feet
(2.32 kg per 3 m)
CAUTION
Never charge liquid into the low pressure side of the system. Do not overcharge. Overcharging results in higher
discharge pressure, possible compressor damage, and
higher power consumption. During charging or removal of
refrigerant, be sure cooler water is continuously circulating
through the cooler to prevent freezing.
While the unit is running at full capacity, add refrigerant un-
til the sight glass is clear. The required refrigerant is R-410A.
With the unit operating at full load, check liquid line sight
glass to be sure the unit is fully charged (bubbles in the sight
glass indicate the unit is not fully charged).
IMPORTANT: For proper charging, units equipped with a
digital compressor must have the digital compressor operation disabled to maintain stable operation. To disable digi-
UNIT
tal compressor operation, set Configuration
A1.TY (Compressor A1 Digital?) to NO. Be sure to re-
enable the digital operation after charging operation is
complete.
Follow approved evacuation procedures when removing refrigeration. Release remaining pressure to an approved evacuated cylinder.
Actual Start-Up — Actual start-up should be done only
under supervision of a qualified refrigeration mechanic.
1. Be sure all service valves are open (30MPA units only).
2. Using the scrolling marquee display, set leaving-fluid set
point (Set Points
adjustment is necessary.
3. Start chilled fluid pump (if not configured for cooler
pump control).
4. Start condenser fluid pump (if not configured for condenser pump control (30MPW only).
5. Turn ENABLE/OFF/REMOTE CONTROL switch to
ENABLE position.
6. Allow unit to operate and confirm that everything is functioning properly. Check to see that leaving fluid tempera-
COOLCSP.1). No cooling range
ture agrees with leaving set point (Set Points
CSP.1) or (Set PointsCOOLCSP.2), or if reset is
COOL
used, with the control point (Run StatusVIEW
CTPT).
7. Check the cooler leaving chilled water temperature to see
that it remains well above 32 F (0° C), or the brine freezing point if the unit is a medium temperature brine unit.
8. Recheck compressor oil level (see Oil Charge section).
Check Refrigerant Charge — All 30MPW units are
shipped with a complete operating charge of R-410A and
should be under sufficient pressure to conduct a leak test after
installation. If there is no system pressure, admit nitrogen until
a pressure is observed and then proceed to test for leaks. After
leaks are repaired, the system must be dehydrated.
All refrigerant charging should be done through the ¼-in.
Schrader connection on the liquid line. Do NOT add refrigerant
charge through the low-pressure side of the system. If complete
charging is required, weigh in the appropriate charge for the
circuit as shown on the unit nameplate. If partial charging is required, operate circuit at full load and add charge to reach 9 to
12 F (–12.8 to –11.1 C) subcooling entering the expansion
valve. See Step 6b on page 39.
The liquid charging method is recommended for complete
charging or when additional charge is required.
NOTE: On units with digital scroll option do not check refrigerant; charge if compressor is operating at less than 100%
capacity; digital operation can be disabled by configuring
A1.TY = NO(Configuration
UnitA1.TY).
CAUTION
Never charge liquid into low-pressure side of system. Do
not overcharge. Overcharging results in higher discharge
pressure, possible compressor damage, and higher power
consumption. During charging or removal of refrigerant, be
sure water is continuously circulating through the cooler
and condenser (30MPW) to prevent freezing.
CAUTION
Be careful not to overcharge the system. Overcharging
results in higher discharge pressure, possible compressor
damage, and higher power consumption.
EVACUATION AND DEHYDRATION — The 30MP015045 systems use polyol ester (POE) oil, and 30MP050-071 systems use polyvinyl ester (PVE) oil. Because either type of oil
can absorb moisture, it is important to minimize the amount of
time that the system interior is left exposed to the atmosphere.
Minimizing the exposure time of the oil to the atmosphere will
minimize the amount of moisture that needs to be removed
during evacuation.
Once all of the piping connections are complete, leak test
the unit and then pull a deep dehydration vacuum. Connect the
vacuum pump to the high flow Schrader valve in the suction
line and liquid line. For best results, it is recommended that a
vacuum of at least 500 microns (0.5 mm Hg) be obtained. Afterwards, to ensure that no moisture is present in the system,
perform a standing vacuum-rise test.
With the unit in deep vacuum (500 microns or less), isolate
the vacuum pump from the system. Observe the rate-of-rise of
the vacuum in the system. If the vacuum rises by more than
50 microns in a 30-minute time period, then continue the dehydration process. Maintain a vacuum on the system until the
standing vacuum requirement is met. This will ensure a dry
system.
38
By following these evacuation and dehydration procedures,
the amount of moisture present in the system will be
minimized. It is required that liquid line filter driers be installed
between the condenser(s) and the expansion devices to capture
any foreign debris and provide additional moisture removal
capacity.
LIQUID CHARGING METHOD
For 30MP015-045: Add charge to the unit through the liquid
line service valve. Never charge liquid into the low-pressure
side of the system.
For 30MP050-071: Add the charge to the unit through the high
flow Schrader valve on the filter drier.
1. Close liquid line ball valve (30MPA only).
2. Connect a refrigerant cylinder loosely to the high flow
Schrader valve connection on the liquid line. Purge the
charging hose and tighten the connections.
3. Open the refrigerant cylinder valve.
4. If the system has been dehydrated and is under vacuum,
break the vacuum with refrigerant gas. For R-410A, build
up system pressure to 101 psig and 32 F (697 kPa and
0° C). Invert the refrigerant cylinder so that the liquid refrigerant will be charged.
5. a. For complete charge of 30MPW units, follow
charging by weight procedure. When charge is
nearly full, complete the process by observing the
sight glass for clear liquid flow while the unit is
operating. The use of sight glass charging is validonly when unit is operating at full capacity.
b. For complete charge of 30MPA units or where
refrigerant cylinder cannot be weighed, follow the
condenser manufacturer’s charging procedure or
follow charging by sight glass procedure. The use
of sight glass charging is valid only when unit is
operating at full capacity.
6. a. The 30MPA condenserless units are shipped
with a nitrogen holding charge. After installation
with the field-supplied system high side, the complete system should be evacuated and charged per
the condenser manufacturer’s charging procedure
or charged until the sight glass is clear (with the
unit running at full capacity). To achieve maxi-
mum system capacity, add additional charge equal
to the difference between the condenser optimal
charge and the condenser minimum charge, which
can be obtained from the charge data provided in
the condenser installation instructions.
b. To ensure maximum performance of 30MPW
units, raise the compressor saturated discharge
temperature (SDT) to approximately 100 F
(37.8 C) by throttling the condenser water intake.
Add charge until there is approximately 9 to 12° F
(5.0 to 6.6° C) of system subcooling (SDT minus
actual temperature entering the expansion valve).
Check Compressor Oil Level — After adjusting the
refrigerant charge, allow each circuit to run fully loaded for
20 minutes. Stop the compressors and check the oil level. Oil
level should be
1
/8 to 3/8 up on the sight glass.
IMPORTANT: Oil level should only be checked when the
compressors are off.
Add oil only if necessary to bring the oil into view in the
sight glass. If oil is added, run the circuit for an additional
10 minutes, then stop and check oil level. If the level remains
low, check the piping system for proper design for oil return;
also, check the system for leaks. If checking the oil level with
unit running in part load, let unit run one hour, then run at full
load for 10 minutes. If oil does not return to acceptable sight
glass levels, check for correct suction piping and line sizing.
Adjust Oil Charge — Although the compressors are
factory charged with oil, additional oil is likely required to
maintain the oil level in the compressor. Tables 37 and 38 indicate the likely amount required based on the liquid line size
and system piping length. Additional lubricant estimate is
based on using recommended pipe sizes. Values listed are estimates only. See Add Oil section for Carrier-approved oils.
After operating the compressor for a period of time, the oil
level should be between
compressor oil level should be checked with the compressor
off to avoid the sump turbulence when the compressor is running. Oil must be added if the oil level does not meet the
requirements.
TEMPERATURES — See Table 39 for 30MP standard
temperature limits. The 30MPW050-071 and 30MPA050071 units use different compressors that require different
operating envelopes. The 30MPW050-071 units (standard
condensing) use water-cooled optimized compressors,
which operate at lower condensing temperatures. The
30MPA050-071 units and 30MPW050-071 heat reclaim
units use air-cooled optimized compressors, which allow
for higher condensing temperatures.
CAUTION
Do not operate with cooler leaving chiller water (fluid)
temperature (LCWT) below 32 F (0° C) for standard units
with proper brine solution, 40 F (4.4 C) for the standard
units with fresh water, or below 15 F (–9.4 C) for units factory built for medium temperature brine, or unit damage
may occur.
High Cooler Leaving Chilled Water (Fluid) Temperatures
(LCWT) — During start-up with cooler the LCWT should not
be above approximately 60 F (16 C).
Low Cooler LCWT
the LCWT must be no lower than 40 F (4.4 C). For standard
units with a proper brine solution, the LCWT must be no lower
than 32 F (0° C). If the unit is the factory-installed optional
medium temperature brine unit, the cooler LCWT can go
down to 15 F (–9.4 C).
Table 39 — Temperature Limits for
TEMPERATURE LIMIT
Maximum Condenser LWT
Minimum Condenser EWT
Maximum Cooler EWT*
Maximum Cooler LWT
Minimum Cooler LWT†
EWT —
LWT —
*For sustained operation, EWT should not exceed 85 F (29.4 C).
†Unit requires modification below this temperature.
Entering Fluid (Water) Temperature
Leaving Fluid (Water) Temperature
IMPORTANT: Medium temperature brine duty application
(below 32 F [0° C] LCWT) for chiller normally requires
factory modification. Contact your Carrier representative
for applicable LCWT range for standard water-cooled
chiller in a specific application.
VOLTAGE — ALL UNITS
Main Power Supply
supply voltages are listed in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage — Never operate a motor
where a phase imbalance between phases is greater than 2%.
To determine percent voltage imbalance:
% Voltage Imbalance = 100 x
The maximum voltage deviation is the largest difference
between a voltage measurement across 2 legs and the average
across all 3 legs.
— For standard units with fresh water,
Standard 30MP Units
30MPA,
LEGEND
30MPW015-045,
30MPW050-071
HIGH
CONDENSING
FCFC
1406012049
6518 6518
75237523
60156015
40 4 40 4
STANDARD
30MPW050-071
— Minimum and maximum acceptable
max voltage deviation
from avg voltage
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
1. Determine average voltage:
Average voltage =
243 + 236 + 238
3
717
=
3
= 239
2. Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
4
239
= 1.7%
This voltage imbalance is satisfactory as it is below the
maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately. Do not operate unit until imbalance condition
is corrected.
Control Circuit Power
— Power for the control circuit is
supplied from the main incoming power through a factoryinstalled control power transformer (TRAN1) for all models.
Field wiring connections are made to the LVT.
OPERATION SEQUENCE
The unit is started by putting the ENABLE/OFF/REMOTE
CONTROL switch in the ENABLE or REMOTE CONTROL
position. When the unit receives a call for cooling (either from
the internal control or CCN network command or remote control closure), the unit stages up in capacity to maintain the leaving fluid set point. The first compressor starts 1
1
/2 to 3 minutes
after the call for cooling.
For all units, if temperature reset is being used, the unit controls to a higher leaving-fluid temperature as the building load
reduces. If demand limit is used, the unit may temporarily be
unable to maintain the desired leaving-fluid temperature because of imposed power limitations.
SERVICE
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during service. There may
be more than one disconnect switch. Tag all disconnect
locations to alert others not to restore power until work is
completed.
Service Test —
power must be on.
The Service Test function should be used to verify proper
operation of condenser output, compressors, minimum load
Both main power and control circuit
40
valve solenoid (if installed), cooler pump, EXV, and remote
ENTER
ENTER
ESCAPE
Fig. 26 — Cutaway View of the Electronic
Expansion Valve (Sizes 050-071)
alarm relay. To use the Service Test mode, the Enable/Off/Remote Control switch must be in the OFF position. Use the display keys to enter the mode and display TEST. Press
twice so that OFF flashes. Enter the password if required. Use
either arrow key to change the TEST value to the ON position
and press . Move the Enable/Off/Remote Control
switch to enable. Press and the button to enter
the OUTS or COMP sub-mode. ENABLE/OFF/REMOTE
must be set to ENABLE to operate test.
switch
NOTE: Cooler and condenser (30MPW) water flow must be
established in order to operate compressor in service test.
Test the condenser output, cooler pump, liquid line solenoid
valve (30MPA only), crankcase heater, water valve (accessory), and alarm relay by changing the item values from OFF to
ON. These discrete outputs are then turned off if there is no
keypad activity for 10 minutes. When testing compressors, the
lead compressor must be started first. All compressor outputs
can be turned on, but the control will limit the rate by staging
one compressor per minute. Minimum load valve can be tested
with the compressors on or off. The relays under the COMP
mode will stay on for 10 minutes if there is no keypad activity.
Compressors will stay on until they are turned off by the operator. The Service Test mode will remain enabled for as long as
there is one or more compressors running. All safeties are monitored during this test and will turn a compressor, circuit or the
machine off if required. Any other mode or sub-mode can be
accessed, viewed, or changed during the TEST mode. The
STAT item (Run Status
VIEW) will display “0” as long as
the Service mode is enabled. The TEST sub-mode value must
be changed back to OFF before the chiller can be switched to
Enable or Remote control for normal operation.
Charging — For 30MPW units, when service is required,
recover the refrigerant from the system.
For 30MPA units when service is required, the compressor
and evaporator can be serviced by closing the factory-installed
liquid line service valve and field-installed discharge line service valve. After the valves are closed, recover the refrigerant
from the system.
Electronic Components
CONTROL COMPONENTS — Unit uses an advanced electronic control system that normally does not require service.
For details on controls refer to Controls section.
Access to the controls is through a hinged panel. Inner panels are secured in place and should not be removed unless all
power to the chiller is off.
High-pressure liquid refrigerant enters valve through the top.
As refrigerant passes through the orifice, pressure drops and refrigerant changes to a 2-phase condition (liquid and vapor).
The electronic expansion valve operates through an electronically controlled activation of a stepper motor. The stepper motor stays in position, unless power pulses initiate the two discrete sets of motor stator windings for rotation in either direction. The direction depends on the phase relationship of the
power pulses.
As the stepper motor rotates, its motion is transferred to linear movement by a lead screw. Refrigerant flow is modulated
by either opening or closing the port. The valve includes a positive shut-off when closed.
See Fig. 26 for a cutaway view of the EXV.
1. Cable
2. Glass Seal
3. Motor Housing
4. Stepper Motor
5. Bearing
6. Lead Screw
7. Insert
8. Valve Piston
9. Valve Seat
10. Valve Port
Table 40 shows the number of steps for the EXV. The EXV
motor moves at 150 steps per second. Commanding the valve
to either 0% or 100% will add extra steps to the move, to ensure the value is open or closed completely.
Table 40 — EXV Steps
UNIT SIZE 30MPEXV STEPS
050-0713690
The EXV board controls the valve. Each circuit has a
thermistor located in a well in the suction manifold before the
compressor. Suction pressure as measured by the suction pressure transducer is converted to a saturated suction temperature.
The thermistor measures the temperature of the superheated
gas entering the compressor and the pressure transducer determines the saturated temperature of suction gas. The difference
between the temperature of the superheated gas and the saturated suction temperature is the superheat. The EXV board
controls the position of the electronic expansion valve stepper
motor to maintain superheat set point.
The MBB controls the superheat leaving cooler to approximately 9° F (5° C). Because EXV status is communicated to
the main base board (MBB) and is controlled by the EXV
boards, it is possible to track the valve position. The unit is then
protected against loss of charge and a faulty valve. Just prior to
compressor start, the EXV will open. At low ambient temperatures the EXV is closed at start up. After initialization period,
valve position is tracked by the EXV board by constantly
monitoring the amount of valve movement.
The EXV is also used to limit cooler saturated suction temperature to 50 F (10 C). This makes it possible for the chiller to
start at higher cooler fluid temperatures without overloading
the compressor. This is commonly referred to as MOP (maximum operating pressure).
If it appears that the EXV module is not properly controlling circuit operation to maintain correct superheat, there
are a number of checks that can be made using test functions
and initialization features built into the microprocessor control.
See the EXV Troubleshooting Procedure section to test EXVs.
41
EXV Troubleshooting Procedure — Follow steps
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Fig. 27 — 30MP050-071 EXV Cable Connections
to EXV Module
ENTER
below to diagnose and correct EXV problems.
Check EXV motor operation first. Switch the Enable/Off/
Remote Control (EOR) switch to the Off position. Press
on the scrolling marquee until the display is blank or on Navigator™ display until ‘Select a menu item’ appears on the display. Use the arrow keys to select the Service Test mode. Press
. The display will be:
> TESTOFF
OUTS
COMP
Press (password entry may be required) and use
to change OFF to ON. Switch the EOR switch to Enable.
The Service Test mode is now enabled. Move the pointer down
to the OUTS sub-mode and press . Move the pointer to
item EXV.A. Press and the valve position will flash. Use
to select 100% valve position (hold for quick movement) and press .
The technician should be able to feel the actuator moving by
placing a hand on the EXV. A sight glass is located on the valve
body to verify that the actuator is moving. A hard knocking
should be felt from the actuator when it reaches the top of its
stroke (can be heard if surroundings are relatively quiet). Press
again twice if necessary to confirm this. To close the
valve, press , select 0% with and press . The actuator should knock when it reaches the bottom of its stroke. If
it is believed that the valve is not working properly, continue
with the checkout procedure below.
Check the EXV output signals at appropriate terminals on
the EXV Board (see Fig. 27). Do not disconnect EXV connector with power applied to the board. Damage to the board may
result if disconnected while under power. Connect positive test
lead to EXV-J6 terminal 3. Set meter to approximately
20 vdc. Using the Service Test procedure above, move the
valve output under test to 100%. DO NOT short meter leads
together or connect pin 3 to any other pin as board damage will
occur.
6 vdc. If it remains constant at a voltage other than 6 vdc or
shows 0 volts, remove the connector to the valve and recheck.
Press and select 0% to close the valve. Check the 4position DIP switch on the board (all switches should be set to
On). If a problem still exists, replace the EXV board. If the
reading is correct, the expansion valve and EXV wiring should
be checked.
1. Check color coding and wire connections. Make sure
they are connected to the correct terminals at the EXV
board and EXV plug and that the cables are not crossed.
2. Check for continuity and tight connection at all pin
terminals.
3. If the motor fails to operate properly, check the resistance
of each motor phase. Remove the EXV Board J6 connector. Check the resistance of the two windings. Resistance
between pins 1 and 2 for one winding or between pins 4
and 5 for the other winding should be approximately 52 ±
5.2 ohms. Differences of more than 10% between windings indicate a defective motor. Resistance between any
lead and ground should be infinite or “open.” Any resistance reading will indicate a shorted winding and the
valve will need to be replaced.
FIELD SERVICING INSTRUCTIONS — See Fig. 26 for a
cutaway view of the EXV. Motor kits for the EXV valve are
available as replacement parts.
EXV VALVE REPLACEMENT — To replace the valve,
perform the following procedure:
1. Be sure the refrigerant has been recovered from the
circuit.
2. Disconnect the EXV cable from the EXV.
3. The valve may be replaced by cutting the piping. A tubing cutter must be used to prevent creating contaminants
in the piping.
4. The EXVs have copper connections and any brazing alloy can be used to install the valve. During installation
the torch flame should be directed away from the valve
body and cable. The valve body should be wrapped with
a wet cloth during the brazing operation. Be sure to use a
nitrogen purge while brazing the valve in place.
5. Check for refrigerant leaks.
6. Once the valve body has cooled, reconnect the EXV cable. Care should be taken to ensure engagement of the
alignment key.
7. Check the operation of the valve using the EXV Troubleshooting Procedure on this page.
VALVE MOTOR REPLACEMENT
CAUTION
Do not disconnect EXV connector with power applied to
the board. Damage to the board may result if disconnected
while under power. DO NOT short meter leads together or
connect pin 3 to any other pin as board damage will occur.
During the next several seconds, carefully connect the negative test lead to pins 1,2,4 and 5 in succession (plug J6). Digital
voltmeters will average this signal and display approximately
IMPORTANT: Obtain replacement gasket before opening
EXV. Do not re-use gaskets.
Perform the following procedure to replace the EXV
motor:
1. Be sure the refrigerant has been recovered from the
circuit.
2. Use Service Test to open the EXV to 100%. This will retract the piston fully.
3. Remove power from the EXV board and then disconnect
the EXV Cable from the EXV.
4. Using a wrench and back-up wrench, remove the motor
assembly from the EXV body. Be sure to place the backup wrench on the adapter to remove the motor as shown
in Fig. 28.
5. To install the motor, be sure to use a new gasket.
42
6. Manually depress the valve piston before installing the
CLOSED
OPEN
CLOSED
OPEN
27mm / 11/16''
ADAPTER
GASKET
EF05BD331 NV 36mm
50Nm (36 ft-lb)+ 30°
27mm / 1
1
/16''
a30-5977
DISASSEMBLY
ASSEMBLY
NOTES:
1. Push down on valve piston to close valve before assembling.
2. After valve is assembled close valve in Quick Test sub-mode or
cycle power before opening service valve.
Fig. 28 — Disassembly and Assembly of EXV Motor
(30MP050-071)
NOTE: Open valve in Quick Test sub-mode before disassembling.
motor assembly. This will allow for the lead screw to engage the piston as the motor is installed.
7. Lightly oil the threads and gasket on the new motor.
Carefully seat the motor on the valve body. Using a
wrench and back-up wrench as described above, tighten
the motor assembly as follows: Tighten the motor to
36 ft-lb (50 N-m) and then tighten an additional 30 degrees as indicated in Fig. 28.
8. After the motor is tightened, the cable should be replaced
on the valve. Care should be taken to ensure engagement
of the alignment key. Pressurize the system and check for
leaks.
9. Reapply control power and test the operation using Service Test operation listed above.
43
Compressor Replacement — All models contain
LEGEND
CWFS — Chilled Water Flow Switch
DPT— Discharge Pressure Transducer
EWT— Entering Water Thermistor
HPS— High Pressure Switch
LWT— Leaving Water Thermistor
RGT— Return Gas Thermistor (Optional)
SPT— Suction Pressure Transducer
a30-5049
Fig. 29 — Compressor Location — 30MP015-045 Units (30MPW045 Unit Shown)
scroll compressors and have two or three compressors. A compressor is most easily removed from the side of the unit or
above, depending on where clearance space was allowed
during unit installation. See Fig. 29.
Remove the junction box cover bolts and disconnect the
compressor power and crankcase heater connections. Remove
the cable from the compressor junction box. Remove the connections from the high-pressure switch. Remove the crankcase
heater. Knock the same holes out of the new compressor junction box and install the cable connectors from the old
compressor.
The compressors are bolted to rails, which are in turn bolted
to the unit basepan for all sizes. Remove the 4 bolts holding the
compressor to the rail on the basepan. Save the mounting hardware for use with the new compressor. Carefully cut the compressor suction and discharge lines with a tubing cutter as close
to the compressor as feasible. Remove high-pressure switch
and pressure transducer(s) if required for compressor removal.
Lift one corner of the compressor at a time and remove all the
steel spacers. Remove the old compressor from the unit.
Slide the new compressor in place on the rails. Lifting one
side of the compressor at a time, replace all of the compressor
mounting hardware. Using new tubing as required, reconnect
compressor suction and discharge lines. Using hardware saved,
reinstall the mounting bolts and washers through the compressor feet. Using proper techniques, braze suction and discharge
lines and check for leaks. Reconnect oil equalization line.
Re-install the crankcase heater. Reconnect the compressor
power connections and high-pressure switch wiring as on the
old compressor. Refer to Fig. 29. Following the installation of
the new compressor, tighten all hardware to the following
specifications. (See Tables 41 and 42.)
Table 41 — Unit Torque Specification,
30MP015-045
FASTENERRECOMMENDED TORQUE
Compressor Mounting
Bolts
Compressor Power
Connections
Compressor Ground
Terminal Connections
7 to 10 ft-lb (9.5 to 13.5 N-m)
2 to 2.33 ft-lb (2.7 to 3.16 N-m)
1.2 to 1.5 ft-lb (1.6 to 2.0 N-m)
Table 42 — Unit Torque Specification,
30MP050-071
FASTENERRECOMMENDED TORQUE
Compressor Mounting
Bolts
Compressor Power
Connections
Compressor Ground
Terminal Connections
7 to 10 ft-lb (9.5 to 13.5 N-m)
3.33 to 3.75 ft-lb (4.5 to 5.1 N-m)
3.33 to 3.75 ft-lb (4.5 to 5.1 N-m)
30MP Cooler and 30MPW Condenser
BRAZED-PLATE COOLER AND CONDENSER HEAT
EXCHANGER REPLACEMENT — Brazed-plate heat exchangers cannot be repaired if they develop a leak. If a leak
(refrigerant or water) develops, the heat exchanger must be
replaced. To replace a brazed plate heat exchanger:
1. Disconnect the liquid-in and liquid-out connections at the
heat exchanger.
2. Check that the replacement heat exchanger is the same as
the original heat exchanger. For the condensers, compare
part numbers on the heat exchangers. For the coolers, insulation covers the manufacturer’s part number. Make
sure the depths of the replacement and original cooler
heat exchangers are the same.
3. Recover the refrigerant from the system, and unsolder the
refrigerant-in and refrigerant-out connections.
HPS
DPT
RGT
SPT
EWT
(HIDDEN)
CWFS
LWT
44
4. Remove the four nuts holding the heat exchanger to the
brackets. Save the nuts.
5. Install the replacement heat exchanger in the unit and attach to the bracket using the four nuts removed in Step 4.
For sizes 015 and 020, torque is 7 to 10 ft-lb. For sizes
030-045, torque is 35 to 50 ft-lb. For sizes 050-071,
torque is 10 to 11 ft-lb.
6. Carefully braze the refrigerant lines to the connections on
the heat exchanger. Lines should be soldered using silver
as the soldering material with a minimum of 45% silver.
Keep the temperature below 1472 F (800 C) under normal soldering conditions (no vacuum) to prevent the copper solder of the brazed plate heat exchanger from changing its structure. Failure to do so can result in internal
or external leakage at the connections which cannot be
repaired.
7. For coolers, ensure that the original size tubing is used
1
(
/2 in. for sizes 015 and 020, 5/8 in. for sizes 030-045, and
3
1
/8 in. for sizes 050-071) between the TXV/EXV or expansion device and the cooler. The TXV/EXV or expansion device must be located within 1 ft of the heat exchanger, with no bends between the TXV/EXV or expansion device outlet and the cooler inlet.
8. Reconnect the water/brine lines.
9. Dehydrate and recharge the unit. Check for leaks.
BRAZED-PLATE COOLER AND CONDENSER HEAT
EXCHANGER CLEANING — Brazed-plate heat exchangers must be cleaned chemically. A professional cleaning service skilled in chemical cleaning should be used. Use a weak
acid (5% phosphoric acid, or if the heat exchanger is cleaned
frequently, 5% oxalic acid). Pump the cleaning solution
through the exchanger, preferably in a backflush mode. After
cleaning, rinse with large amounts of fresh water to dispose of
all the acid. Cleaning materials must be disposed of properly.
The strainers in front of the water/brine inlets of the heat exchangers should be cleaned periodically, depending on
condition of the chiller water/brine.
Water Treatment — Untreated or improperly treated
water may result in corrosion, scaling, erosion, or algae. The
services of a qualified water treatment specialist should be obtained to develop and monitor a treatment program. See water
system cleaning section for water quality characteristics and
limitations in the unit installation instructions.
CAUTION
Water must be within design flow limits, clean and treated
to ensure proper machine performance and reduce the
potential of tubing damage due to corrosion, scaling,
erosion, and algae. Carrier assumes no responsibility for
chiller or condenser damage resulting from untreated or
improperly treated water.
Oil Charge
CAUTION
The compressor in a Puron® refrigerant (R-410A) system
uses a polyol ester (POE) oil or poly vinyl ester (PVE) oil.
This is extremely hygroscopic, meaning it absorbs water
readily. Take all necessary precautions to avoid exposure of
the oil to the atmosphere. Failure to do so could result in
possible equipment damage.
Puron refrigerant systems use a polyol ester (POE) oil for
30MP015-045 units. The 30MP050-071 units use polyvinyl
ester (PVE) oil. See Table 43.
Table 43 — Compressor Oils
30MP UNIT SIZEOIL
015-045POE 3MAF
050-071PVE FVC32D
Use only Carrier approved compressor oil. Oil should be
visible in compressor oil sight glass. An acceptable oil level is
1
/8 to 3/8 of sight glass. All compressors must be off when
from
checking oil level. Recommended oil level adjustment method
is as follows:
ADD OIL — Additional oil may be required in 30MPA units.
Tables 37 and 38 provide an estimate of the amount of oil required, based on the line length and the recommended pipe sizes. The actual circuit oil charge will depend on the application
piping. The guidelines listed are estimates and will likely need
adjusting depending on the number of traps in the application
and the pipe sizes utilized.
No attempt should be made to increase the oil level in the
sight-glass above the
3
/4 full level. A high oil level is not sustainable in the compressor and the extra oil will be pumped out
into the system causing a reduction in system efficiency and a
higher-than-normal oil circulation rate.
Add oil to suction line Schrader valve on tandem compressors sets and the compressor Schrader on the trios. When oil
can be seen at the bottom of the sight glass, add oil in 5 oz increments which is approximately
1
/8 in oil level. Run all compressors for 20 minutes then shut off to check oil level. Repeat
procedure until acceptable oil level is present.
NOTE: Use only Carrier approved compressor oil. Approved
sources for 30MP015-045 units are:
Do not reuse oil that has been drained out, or oil that has
been exposed to atmosphere.
Check Refrigerant Feed Components
FILTER DRIER — The function of the filter drier is to maintain a clean, dry system. The moisture indicator (described
below) indicates any need to change the filter drier. The filter
drier is a sealed-type drier for 30MP015-045 and removeable
core for 30MP050-071. When the drier needs to be changed,
the entire filter drier must be replaced for 30MP015-045 units.
MOISTURE-LIQUID INDICATOR — The indicator is
located immediately ahead of the TXV to provide an indication
of the refrigerant moisture content. It also provides a sight glass
for refrigerant liquid. Clear flow of liquid refrigerant (at full unitloading) indicates sufficient charge in the system. Bubbles in the
sight glass (at full unit loading) indicate an undercharged system
or the presence of noncondensables. Moisture in the system,
measured in parts per million (ppm), changes the color of the
indicator as follows:
Green (safe) —Moisture is below 75 ppm
Yellow-Green (caution) — 75 to 150 ppm
Yellow (wet) — above 150 ppm
The unit must be in operation at least 12 hours before the
moisture indicator gives an accurate reading, and must be in
contact with liquid refrigerant. At the first sign of moisture in
the system, change the corresponding filter drier.
THERMOSTATIC EXPANSION VALVE (TXV)
(30MP015-045 ONLY) — The TXV controls the flow of
liquid refrigerant to the cooler by maintaining constant superheat of vapor leaving the cooler. The valve is activated by a
temperature-sensing bulb strapped to the suction line.
45
The valve(s) is factory-set to maintain between 8° and 10° F
(4.4° and 5.6° C) of superheat leaving the cooler. Check the
superheat during operation after conditions have stabilized. If
necessary, adjust the superheat to prevent refrigerant floodback
to the compressor.
MINIMUM LOAD VALVE — On units equipped with the
factory-installed hot gas bypass option, a solenoid valve and
discharge bypass valve (minimum load valve) are located
between the discharge line and the cooler entering-refrigerant
line. The MBB cycles the solenoid to perform minimum load
valve function and the discharge bypass valve modulates to the
suction pressure set point of the valve. The bypass valve has an
adjustable opening setting between 95 to 115 psig (655 to
793 kPa). The factory setting is 105 psig (724 kPa).
The amount of capacity reduction achieved by the minimum load valve is not adjustable. The total unit capacity with
the minimum load valve is shown in Table 14.
PRESSURE RELIEF DEVICES — All units have one pressure relief device per circuit located in the liquid line which relieves at 210 F (100 C).
The 30MPW unit does not have a condenser pressure relief
valve because the brazed-plate condenser is not considered a
pressure vessel, as defined in ANSI/ASHRAE 15 (American
National Standards Institute/American Society of Heating,
Refrigerating, and Air-Conditioning Engineers) safety code
requirements.
For 30MPA condenserless units, pressure relief devices designed to relieve at the pressure determined in local codes,
must be field-supplied and installed in the discharge line piping
in accordance with ANSI/ASHRAE 15 safety code requirements. Additional pressure relief valves, properly selected,
must be field-supplied and installed to protect high side equipment and may be required by applicable codes.
Most codes require that a relief valve be vented directly to
the outdoors. The vent line must not be smaller than the reliefvalve outlet. Consult ANSI/ASHRAE 15 for detailed information concerning layout and sizing of relief vent lines.
Check Unit Safeties
HIGH-PRESSURE SWITCH — A high-pressure switch is
provided to protect the circuit and refrigeration system from
unsafe high pressure conditions. For 30MP050-071, two
different high pressure switches are used, depending on unit
configuration. See Table 44 for high-pressure switch settings.
The high-pressure switch is mounted in the discharge line of
the circuit. If an unsafe, high-pressure condition should exist,
the switch opens and shuts off the unit. The MBB senses the
HPS feedback signal and generates an appropriate alarm. The
MBB prevents the circuit from restarting until the alert condition is reset. The switch should open at the pressure corresponding to the appropriate switch setting as shown in
Table 44.
Table 44 — Factory Settings, High-Pressure
Switch (Fixed)
UNIT
All 30MP015-045;
30MPA050-071,
30MPW050-071
High Condensing
30MPW050-07155838484353000HK02ZZ003
CUTOUTCUT-IN
PsigkPaPsigkPa
65044825003447HK02ZZ001
Clear the alarm using the scrolling marquee display. The
unit should restart after the compressor anti-short-cycle delay,
built into the unit control module, expires.
PRESSURE TRANSDUCERS — Each unit is equipped with
a suction and discharge pressure transducer. These inputs to the
MBB are not only used to monitor the status of the unit, but
also to maintain operation of the chiller within the compressor
PART
NUMBER
manufacturer’s specified limits. The input to the MBB from the
suction pressure transducer is also used to protect the compressor from operating at low pressure conditions. If suction return
gas thermistors are installed, then additional low superheat
conditions are detected. In some cases, the unit may not be able
to run at full capacity. The control module will automatically
reduce the capacity of a circuit as needed to maintain specified
maximum/minimum operating pressures.
COOLER FREEZE-UP PROTECTION
WARNING
On medium temperature brine units, the anti-freeze solution must be properly mixed to prevent freezing at a temperature of at least 15 F (8.3 C) below the leaving-fluid
temperature set point. Failure to provide the proper antifreeze solution mixture is considered abuse and may impair
or otherwise negatively impact the Carrier warranty.
The main base board (MBB) monitors cooler leaving fluid
temperature at all times. The MBB will rapidly remove stages
of capacity as necessary to prevent freezing conditions due to
the rapid loss of load or low cooler fluid flow.
When the cooler is exposed to lower temperatures (40 F
[4.4 C] or below), freeze-up protection is required using inhibited ethylene or propylene glycol.
Thermistors — Electronic control uses up to five 5,000-
ohmthermistors to sense temperatures used to control operation of the chiller. Thermistors EWT, LWT, RGT.A, CNDE,
CNDL, and OAT are identical in their temperature and voltage
drop performance. The SPT space temperature thermistor has a
10,000-ohm input channel and it has a different set of temperature vs. resistance and voltage drop performance. Resistance
values at various temperatures are listed in Tables 45-49. For
dual chiller operation, a dual chiller sensor is required which is
a 5,000-ohm thermistor.
REPLACING THERMISTORS (EWT, LWT, RGT, CNDE,
CNDL) — Add a small amount of thermal conductive grease
to the thermistor well and end of probe. For all probes, tighten
the retaining nut ¼ turn past finger tight. See Fig. 30.
THERMISTOR/TEMPERATURE SENSOR CHECK —
A high quality digital volt-ohmmeter is required to perform
this check.
1. Connect the digital voltmeter across the appropriate themistor terminals at the J8 terminal strip on the main base
board (see Fig. 31).
2. Using the voltage reading obtained, read the sensor temperature from Tables 45-49.
3. To check thermistor accuracy, measure temperature at
probe location with an accurate thermocouple-type temperature measuring instrument. Insulate thermocouple to
avoid ambient temperatures from influencing reading.
Temperature measured by thermocouple and temperature
determined from thermistor voltage reading should be
close, ± 5° F (3° C) if care was taken in applying thermocouple and taking readings.
If a more accurate check is required, unit must be shut down
and thermistor removed and checked at a known temperature
(freezing point or boiling point of water) using either voltage
drop measured across thermistor at the J8 terminal, by determining the resistance with chiller shut down and thermistor
disconnected from J8. Compare the values determined with the
value read by the control in the Temperatures mode using the
scrolling marquee display.
Pressure Transducers — The suction and discharge
transducers are different part numbers and can be distinguished
by the color of the transducer body, suction (yellow) and discharge (red). No pressure transducer calibration is required.
46
The transducers operate on a 5 vdc supply, which is generated
Fig. 30 — Thermistor Well
Fig. 31 — Thermistor Connections to
Main Base Board, J8 Connector
LEGEND
ACCSY — Accessory
DPT— Discharge Pressure Transducer
EFT— Entering Fluid Temperature
LFT— Leaving Fluid Temperature
LWT— Leaving Water Temperature Sensor
LVT— Low Voltage Terminal
OAT— Outdoor Air Temperature Sensor
RGT— Return Gas Temperature Sensor
SEN— Sensor Terminal Block
SPT— Space Temperature Sensor
Fig. 32 — Chilled Water Flow Switch
a30-499
NOTE: Dimensions are in millimeters.
by the main base board (MBB). See Fig. 31 for transducer connections to the J8 connector on the MBB.
TROUBLESHOOTING — If a transducer is suspected of being faulty, first check supply voltage to the transducer. Supply
voltage should be 5 vdc ± 0.2 v. If supply voltage is correct,
compare pressure reading displayed on the scrolling marquee
display module against pressure shown on a calibrated pressure
gage. Pressure readings should be within ± 15 psig. If the two
readings are not reasonably close, replace the pressure transducer.
Chilled Water Flow Switch — A factory-installed
flow switch is installed in the leaving fluid piping for all units.
This is a thermal-dispersion flow switch with no field adjustments. The switch is set for approximately 0.5 ft/sec of flow.
The sensor tip houses two thermistors and a heater element.
One thermistor is located in the sensor tip, closest to the flowing fluid. See Fig. 32. This thermistor is used to detect changes
in the flow velocity of the liquid. The second thermistor is
bonded to the cylindrical wall and is affected only by changes
in the temperature of the liquid. The thermistors are positioned
to be in close contact with the wall of the sensor probe and, at
the same time, to be kept separated from each other within the
confines of the probe.
In order to sense flow, it is necessary to heat one of the
thermistors in the probe. When power is applied, the tip of the
probe is heated. As the fluid starts to flow, heat will be carried
away from the sensor tip. Cooling of the first thermistor is a
function of how fast heat is conducted away by the flowing
liquid.
The difference in temperature between the two thermistors
provides a measurement of fluid velocity past the sensor probe.
When fluid velocity is high, more heat will be carried away
from the heated thermistor and the temperature differential will
be small. As fluid velocity decreases, less heat will be taken
from the heated thermistor and there will be an increase in temperature differential.
When unit flow rate is above the minimum flow rate, then
the output is switched on, sending 24 vac to the MBB to prove
flow has been established.
For recommended maintenance, check the flow switch operation. If operation is erratic check the sensor tip for build-up
every 6 months. Clean the tip with a soft cloth. If necessary,
build-up (e.g., lime) can be removed with a common vinegar
cleansing agent.
The flow sensor cable is provided with (3) LEDs that indicate if 24 vac power is present and also status of the switch
contacts. The LEDs are as follows:
• Green LED ON – 24 vac present
• One Yellow LED ON – Flow sensor switch OPEN
• Two Yellow LED ON – Flow sensor switch CLOSED
If nuisance trips of the sensor are occurring, follow the steps
below to correct the situation:
1. Check to confirm that the field-installed strainer is clean.
Use the blow-down valve provided or remove the screen
and clean it. For the case of VFD controlled pumps, ensure that the minimum speed setting has not been
changed.
2. Measure the pressure drop across the cooler and compare
this to the system requirements.
3. Verify that cable connections at the switch and at the terminal block are secure.
4. Check for wrong pump motor rotation. Pump must rotate
clockwise when viewed from motor end of pump.
5/8 in. HEX
1/4-18 NPT
6" MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
MAIN
BASE
BOARD
A30-6018
47
Table 45 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop
Strainer — Periodic cleaning of the required field-installed
strainer is required. Pressure drop across strainer in excess of
3 psi (21 kPa) indicates the need for cleaning. Normal (clean)
pressure drop is approximately 1 psi (6.9 kPa). Open the
blowdown valve to clean the strainer. If required, shut the
chiller down and remove the strainer screen to clean. When
strainer has been cleaned, enter ‘YES’ for Strainer Maintenance Done (Run Status
PM
S.T.MN).
Replacing Defective Modules — The Comfort-
Link replacement modules are shown in Table 50. If the main
base board (MBB) has been replaced, verify that all configuration data is correct. Follow the Configuration mode table and
verify that all items under sub-modes UNIT, OPT1 and OPT2
are correct. Any additional field-installed accessories or options (RSET, SLCT sub-modes) should also be verified as well
as any specific time and maintenance schedules.
Refer to the Start-Up Checklist for 30MP Liquid Chillers
(completed at time of original start-up) found in the job folder.
This information is needed later in this procedure. If the checklist does not exist, fill out the current information in the Configuration mode on a new checklist. Tailor the various options and
configurations as needed for this particular installation.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
1. Check that all power to unit is off. Carefully disconnect
all wires from the defective module by unplugging its
connectors.
2. Remove the defective module by removing its mounting
screws with a Phillips screwdriver, and removing the
module from the control box. Save the screws later use.
3. Verify that the instance jumper (MBB) or address switches (all other modules) exactly match the settings of the
defective module.
NOTE: Handle boards by mounting standoffs only to
avoid electrostatic discharge.
4. Package the defective module in the carton of the new
module for return to Carrier.
5. Mount the new module in the unit’s control box using a
Phillips screwdriver and the screws saved in Step 2.
6. Reinstall all module connectors. For accessory Navigator™ device replacement, make sure the plug is installed
at TB3 in the LEN connector.
7. Carefully check all wiring connections before restoring
power.
8. Verify the ENABLE/OFF/REMOTE CONTROL switch
is in the OFF position.
9. Restore control power. Verify that all module red LEDs
blink in unison. Verify that all green LEDs are blinking
and that the scrolling marquee or Navigator™ display is
communicating correctly.
10. Verify all configuration information, settings, set points
and schedules. Return the ENABLE/OFF/REMOTE
CONTROL switch to its previous position.
Table 50 — Replacement Modules
MODULE
Main Base Board (MBB)30MP500346
Scrolling Marquee DisplayHK50AA031
Energy Management Module (EMM)30GT515218
Navigator DisplayHK50AA033
Electronic Expansion Valve (EXV)30GT515217
REPLACEMENT
PART NO.
(with Software)
MAINTENANCE
Recommended Maintenance Schedule —
following are only recommended guidelines. Jobsite conditions may dictate that maintenance tasks are performed
more often than recommended.
Routine
Every month:
• Check water quality. Inspection interval to be determined
•Check moisture indicating sight glass for possible refrig-
Every 3 months (for all machines):
•Check refrigerant charge.
•Check all refrigerant joints and valves for refrigerant
•Check chilled water flow switch operation.
•Check compressor oil level.
Every 6 months (for all machines):
• Clean chilled water/condenser water flow switch sensor
Every 12 months (for all machines):
•Check all electrical connections, tighten as necessary.
•Inspect all contactors and relays, replace as necessary.
•Check accuracy of thermistors, replace if greater than
•Check to be sure that the proper concentration of anti-
•Verify that the chilled water loop is properly treated.
•Check refrigerant filter driers for excessive pressure
•Check chilled water and condenser strainers, clean as
•Perform Service Test to confirm operation of all
•Check for excessive cooler approach (Leaving Chilled
• Check for excessive condenser approach (Saturated Dis-
:
by site conditions and water quality specialist.
erant loss and presence of moisture.
leaks, repair as necessary.
tip.
± 2° F (1.2° C) variance from calibrated thermometer.
freeze is present in the chilled water loop, if applicable.
drop, replace as necessary. The 30MP015-045 units contain a hermetic filter drier. The 30MP050-071 units contain a replaceable core type filter drier.
necessary.
components.
Water Temperature – Saturated Suction Temperature)
which may indicate fouling. Clean evaporator if necessary.
charge Pressure – Leaving Condenser Water Temperature)
which may indicate fouling. Clean condenser if necessary
(30MPW only).
The
TROUBLESHOOTING
Complete Unit Stoppage and Restart —
ble causes for unit stoppage and reset methods are shown below and in Table 51. Refer to Fig. 2-6 for component arrangement and control wiring diagrams.
GENERAL POWER FAILURE — After power is restored,
restart is automatic through normal MBB start-up.
UNIT ENABLE-OFF-REMOTE CONTROL SWITCH IS
OFF — When the switch is OFF, the unit will stop immediately. Place the switch in the ENABLE position for local switch
control or in the REMOTE CONTROL position for control
through remote control closure.
Possi-
52
Table 51 — Troubleshooting
SYMPTOMSCAUSEREMEDY
Compressor Cycles
Off on Loss of Charge
Compressor Cycles Off on Out
of Range Condition
Compressor Shuts Down on
High-Pressure Control
Unit Operates Too Long
or Continuously
Unusual or Loud System
Noises
Compressor Loses OilLeak in systemRepair leak.
Hot Liquid LineShortage of refrigerant due to leakRepair leak and recharge.
Frosted Liquid LineRestricted filter drierReplace filter drier.
Frosted Suction LineExpansion valve admitting excess refrigerant (note: this is a
Freeze-UpImproper chargingMake sure a full quantity of fluid is flowing through the cooler
CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN —
After the problem causing the loss of flow has been corrected,
reset is manual by resetting the alarm with the scrolling
marquee.
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — Determine the cause of the failure and correct. Reset circuit breaker(s). Restart is automatic after MBB start-up cycle is
complete.
COOLING LOAD SATISFIED — Unit shuts down when
cooling load has been satisfied. Unit restarts when required to
satisfy leaving fluid temperature set point.
THERMISTOR FAILURE — If a thermistor fails in either an
open or shorted condition, the unit will be shut down. Replace
EWT, or LWT as required. Unit restarts automatically, but must
be reset manually by resetting the alarm with the scrolling
marquee.
CAUTION
If unit stoppage occurs more than once as a result of any of
the safety devices listed, determine and correct cause
before attempting another restart.
Loss of charge control. Acting erratically.Repair leak and recharge.
Low refrigerant chargeAdd refrigerant.
Low suction temperatureRaise cooler leaving fluid temperature set point.
Thermistor failureReplace thermistor.
System load was reduced faster than controller could
remove stages
Temperature controller deadband setting is too lowRaise deadband setting.
High-pressure control acting erraticallyReplace control.
Noncondensables in systemPurge system.
Condenser scaled/dirty (30MPW)Clean condenser.
Fans in remote condensing unit (30MPA only) not operating Repair or replace if defective.
System overcharged with refrigerantReduce charge.
Low refrigerant chargeAdd refrigerant.
Control contacts fusedReplace control.
Air in systemPurge system.
Partially plugged or plugged expansion valve or filter drierClean or replace as needed.
Defective insulationReplace or repair as needed.
Service loadKeep doors and windows closed.
Damaged compressorCheck compressor and replace if necessary.
Piping vibrationSupport piping as required.
Compressor not pumpingAdvanced scroll temperature protection is active. Determine
Mechanical damage (Failed seals or broken scrolls)Replace compressor.
Oil trapped in lineCheck piping for oil traps.
normal condition for brine applications)
Stuck TXV (thermostatic expansion valve)Replace valve if defective.
System not drained for winter shutdownRecommended that system be filled with an appropriate gly-
Loose thermistorVerify thermistors are fully inserted in wells.
Replace control.
Unit will restart after fluid temperature rises back into the
control band. Avoid rapidly removing system load or
increase loop volume.
Check for loose pipe connections or damaged compressor
Check for plugged liquid line filter drier.
Check for loose compressor holddown bolts.
Operation outside of compressor operating envelope. Con-
sider head pressure control, clean condenser. Check water
flow (cooler and condenser).
high discharge temperature reason.
Replace valve if defective.
while charging, and suction pressure in cooler is equal to or
greater than pressure corresponding to 32 F (0° C).
col mixture to prevent freezing of pumps and fluid tubing.
ENABLING AND DISABLING COMPRESSORS —
Compressors in the 30MP units can be enabled or disabled in
the controls. To enable or disable a compressor, toggle the
value in the Configuration
SERV menu for each individual
compressor.
COMPRESSOR DISCHARGE CHECK VALVE — A
disk-type check valve in the discharge of the compressor prevents high pressure discharge gas from flowing rapidly back
through the compressor at shutdown. This same check valve
prevents a high to low side bypass in multiple compressor
circuits.
LOW SATURATED SUCTION — Several conditions can
lead to low saturated suction alarms and the chiller controls
have several override modes built in which will attempt to keep
the chiller from shutting down. Low fluid flow, low refrigerant
charge and plugged filter driers are the main causes for this
condition. To avoid permanent damage and potential freezing
of the system, do NOT repeatedly reset these alert and/or alarm
conditions without identifying and correcting the cause(s).
COMPRESSOR SAFETIES — The 30MP units with Com-fortLink controls include a compressor protection board that
protects the operation of each of the compressors. Each board
senses the presence or absence of current to each compressor.
53
If there is a command for a compressor to run and there is
Fig. 33 — Advanced Scroll Temperature
Protection Label
Fig. 34 — Recommended Minimum Cool Down
Time After Compressor is Stopped*
0
10
20
30
40
50
60
70
80
90
100
110
120
0 102030405060708090
Recommended Cooling Time
(Minutes)
Compressor Unloaded Run Time (Minutes)
*Times are approximate.
NOTE: Various factors, including high humidity, high ambient temperature,
and the presence of a sound blanket will increase cool-down times.
no current, then one of the following safeties or conditions
have turned the compressor off:
Compressor Overcurrent
— All compressors have internal
line breaks or a motor protection device located in the compressor electrical box.
Compressor Short Circuit
— There will not be current if the
compressor circuit breaker that provides short circuit protection
has tripped.
Compressor Motor Over Temperature
— The internal line-
break or over temperature switch has opened.
High-Pressure Switch Trip
— The high-pressure switch has
opened. See Table 44 for the factory settings for the fixed highpressure switch.
ASTP Protection Trip
(30MP015-045 Only) — All non-digital Copeland compressors are equipped with an advanced
scroll temperature protection (ASTP). A label located above
the terminal box identifies models that contain this technology.
See Fig. 33.
Advanced scroll temperature protection is a form of internal
discharge temperature protection that unloads the scroll compressor when the internal temperature reaches approximately
300 F (149 C). At this temperature, an internal bi-metal disk
valve opens and causes the scroll elements to separate, which
stops compression. Suction and discharge pressures balance
while the motor continues to run. The longer the compressor
runs unloaded, the longer it must cool before the bi-metal disk
resets. See Fig. 34 for approximate reset times.
automatically before the motor protector resets, which may
take up to 2 hours.
High Discharge Gas Temperature Protection
— Units
equipped with optional digital compressors have an additional
thermistor located on the discharge line. If discharge temperature exceeds 265 F (129.4 C), the digital compressor will be
shut off.
Alarms will also occur if the current sensor board malfunctions or is not properly connected to its assigned digital input. If
the compressor is commanded OFF and the current sensor
reads ON, an alert is generated. This will indicate that a compressor contactor has failed closed. In this case, a special mode,
Compressor Stuck on Control, will be enabled and all other
compressors will be turned off. An alarm will then be enabled
to indicate that service is required. Outdoor fans will continue
to operate. The condenser output is turned on immediately.
Motor Overload Protection
COPELAND* COMPRESSORS MODELS WITH
ELECTRICAL CODE TF — Models with a “TF” in the
electrical code (i.e., ZP182KCE-TFE) have an internal line
break motor overload located in the center of the Y of the motor windings. This overload disconnects all three legs of the
motor from power in case of an over-current or over-temperature condition. The overload reacts to a combination of motor
current and motor winding temperature. The internal overload
protects against single phasing. Time must be allowed for the
motor to cool down before the overload will reset. If current
monitoring to the compressor is available, the system controller
can take advantage of the compressor internal overload operation. The controller can lock out the compressor if current draw
is not coincident with contactor energizing, implying that the
compressor has shut off on its internal overload. This will prevent unnecessary compressor cycling on a fault condition until
corrective action can be taken.
COPELAND COMPRESSORS MODELS WITH ELECTRICAL CODE TW OR TE
To manually reset ASTP, the compressor should be stopped
and allowed to cool. If the compressor is not stopped, the motor
will run until the motor protector trips, which occurs up to 90
minutes later. Advanced scroll temperature protection will reset
* Copeland is a registered trademark of Emerson Climate
Technologies.
CAUTION
The electronic motor protection module is a safety device
that must not be bypassed or compressor damage may
result.
Models with a “TW” or “TE” in the electrical code (i.e.,
ZP182KCE-TWD or ZP182KCE-TED) have a motor overload system that consists of an external electronic control module connected to a chain of four thermistors embedded in the
motor windings. The module will trip and remain off for a minimum of 30 minutes if the motor temperature exceeds a preset
point to allow the scrolls to cool down after the motor temperature limit has been reached. It may take as long as two hours for
the motor to cool down before the overload will reset.
NOTE: Turning off power to the module will reset it
immediately.
CAUTION
Restoring the compressor sooner may cause a destructive
temperature build up in the scrolls.
For this reason, module power must never be switched with
the control circuit voltage.
Current sensing boards monitor to the compressor current.
The ComfortLink control system takes advantage of the compressor overload operation by locking out the compressor if
current draw is not detected. This will prevent unnecessary
compressor cycling on a fault condition until corrective action
can be taken.
54
Kriwan Motor Protection Module Troubleshooting — Co-
LEGEND
1—Kriwan Motor Protection Module Power
2—Kriwan Control Circuit Connections
3—Motor Thermal Sensor
Fig. 35 — Kriwan Motor Protection Wiring
peland models with a “TW” in the electrical code (i.e.,
ZP182KCE-TWD), have a motor overload system that consists of an external Kriwan
have been replaced by the CoreSense
*
electronic control module. These
†
communication module
for motor protection. This section is included for reference, and
contains instructions for replacing the Kriwan module with the
CoreSense module in the field.
Follow the steps listed below to troubleshoot the Kriwan
module in the field. See wiring diagram on terminal box cover,
or Fig. 35.
WARNING
Do not supply power to unit with compressor cover
removed. Failure to follow this warning can cause a fire,
resulting in personal injury or death.
WARNING
Exercise extreme caution when reading compressor currents when high-voltage power is on. Correct any of the
problems described below before installing and running a
replacement compressor. Wear safety glasses and gloves
when handling refrigerants. Failure to follow this warning
can cause fire, resulting in personal injury or death.
CAUTION
Do not manually operate contactors. Serious damage to the
machine may result.
123
reconnected, then the control circuit relay in the module
is open. Remove the temporary jumper installed in Step
1.
3. The thermistor protection chain now needs to be tested to
determine if the module’s control circuit relay is open due
to excessive internal temperatures or a faulty component.
Check the thermistor protection chain located in the
compressor as follows:
a. De-energize control circuit and module power.
b. Remove the sensor leads from the module (S1 and
S2).
c. Measure the resistance of the thermistor protection
chain through these sensor leads with an ohm
meter.
CAUTION
Use an ohmmeter with a maximum of 9 volts to check the
sensor chain. The sensor chain is sensitive and easily damaged; no attempt should be made to check continuity
through it with anything other than an ohmmeter. The
application of any external voltage to the sensor chain may
cause damage requiring the replacement of the compressor.
d. The diagnosis of this resistance reading is as
follows:
• 200 to 2250 ohms: Normal operating range
• 2750 ohms or greater: Compressor overheated.
Allow time to cool.
• Zero resistance: Shorted sensor circuit. Replace the
compressor.
• Infinite resistance: Open sensor circuit. Replace
the compressor.
4. If the resistance reading is abnormal, remove the sensor
connector plug from the compressor and measure the resistance at the sensor fusite pins. This will determine if
the abnormal reading was due to a faulty connector.
5. On initial start-up, and after any module trip, the resistance of the sensor chain must be below the module reset
point before the module circuit will close. Reset values
are 2250 to 3000 ohms.
6. If the sensor chain has a resistance that is below 2250
ohms, and the compressor will run with the control circuit
bypassed, but will not run when connected properly, the
solid-state module is defective and should be replaced.
The replacement module must have the same supply
voltage rating as the original module.
CoreSense Replacement of Kriwan Motor Protection
Module — The Kriwan module has been replaced by the Core-
Sense communication module for motor protection. Minor
wiring changes are required as described below.
1. De-energize control circuit and module power. Remove
the control circuit wires from the module (terminals M1
and M2). Connect a jumper across these control circuit
wires. This will bypass the control contact of the module.
CAUTION
The motor protection system within the compressor is now
bypassed. Use this configuration to temporarily test module only.
2. Re-energize the control circuit and module power. If the
compressor will not operate with the jumper installed,
then the problem is external to the solid-state protection
system. If the compressor operates with the module bypassed but will not operate when the module is
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag
all disconnect locations to alert others not to restore power
until work is completed.
WARNING
Do not supply power to unit with compressor cover
removed. Failure to follow this warning can cause a fire,
resulting in personal injury or death.
* Kriwan is a registered trademark of Kriwan Industrie-Elektronik.
GmbH
† CoreSense is a registered trademark of Emerson Climate
Technologies.
55
Removing the Kriwan motor protection module:
HOLDING
TA B
HOLDING
TA B
a38-7310
Fig. 36 — Kriwan Motor Protection Module
Removal
INSTALL IN THIS
ORIENTATION
A38-7311
Fig. 37 — Compressor Motor Sensor Harness
Installation (under motor protection module)
ROCKER DOWN
O
F
F
ON
OFF OFF OFF OFF OFF OFF OFF
OFF
123456789
OFF
10
A38-7812
Fig. 38 — CoreSense Communication DIP
Switch Settings for Kriwan Retrofit
1 2 3 4 5 6 7 8 9 10
T2 T1
L3
L2L1
RED
BLACK
WHITE
VIOLET
HOLDING
TA B
HOLDING
TA B
THERMISTOR WIRE
HARNESS PLUGGED
INTO 2X2 SOCKET
BLACK
WHITE
A38-7313
BLUE
M1/M2
Fig. 39 — CoreSense Communication Module
Mounting
MOTOR
PTC
CIRCUIT
SCROLL
NTC CIRCUIT
(NOT USED)
FOR FUTURE
USE
COMMON
CONNECTION
a38-7308
Fig. 40 — CoreSense Communications
Motor Thermistor Plug
1. Disconnect and lock out the high voltage and control
voltage supply to the unit.
2. Using a straight blade screwdriver, carefully depress the
tabs holding the terminal cover to the terminal box to remove the terminal cover. Before proceeding, use a volt
meter to verify that the power has been disconnected
from the unit.
3. Using wire markers, label the M1, M2, T1, and T2 wires
that are connected to the Kriwan module. Using needle
nose pliers, remove the M1, M2, T1, T2, S1 and S2 wires
from the Kriwan motor protector module.
4. Gently bend the holding tabs holding the Kriwan module
in the terminal box and remove the Kriwan module from
the terminal box. See Fig. 36.
5. Take note of the S1-S2 plug orientation on the compressor thermistor fusite. Remove the S1-S2 wire harness and
plug from the compressor.
2. Review the DIP switch settings on the CoreSense module. DIP switch no. 1 should be ON (up position) and all
other DIP switches should be OFF (down position). See
Fig. 38.
3. Install the CoreSense module in the compressor terminal
box as shown in Fig. 39, with the tabs holding the module in place. Route the thermistor wire harness as shown
and plug the harness into the 2x2 socket on the CoreSense
module.
4. Connect the previously labeled M1, M2, T1, and T2
wires to the appropriate terminals on the CoreSense module.
5. Connect the L1, L2, and L3 phase sensing wires to the
L1, L2, and L3 compressor terminal block connections.
See the compressor terminal cover diagram for identication of the L1, L2, and L3 terminal block connections.
6. Double-check the installation and make sure all connections are secure. Install the compressor terminal cover.
The CoreSense retrofit is complete and the system can be
put back into service.
Installing the CoreSense communications module:
1. A new S1-S2 thermistor wiring harness is shipped with
the CoreSense kit and must be used. The wiring harness
connector block should be fully inserted on the three pins
in the orientation shown in Fig. 37 for proper operation.
CoreSense Communications Module Troubleshooting —
Copeland models with a "TE" in the electrical code (i.e.,
ZP182KCE-TED) have a motor overload system that consists
of an external CoreSense communication electronic control
module.
Motor thermistors are connected to the CoreSense commu-
nication module via a 2x2 plug (Fig. 40).
56
The CoreSense communications module has field configu-
Fig. 41 — CoreSense Communication Motor
Protection Wiring
rable DIP switches for addressing and configuring the module.
The DIP switches should be addressed as shown in Table 52.
The CoreSense communication module has a green and a
red light-emitting diode (LED). A solid green LED indicates
the module is powered and operation is normal. A solid red
LED indicates an internal problem with the module. If a solid
red LED is encountered, power down the module (interrupt the
T1-T2 power) for 30 seconds to reboot the module. If a solid
red LED is persistent, change the CoreSense module.
The CoreSense module communicates warning codes via a
green flashing LED. Warning codes do not result in a trip or
lockout condition. Alert codes are communicated via a red
flashing LED. Alert codes will result in a trip condition and
possibly a lockout condition. See wiring diagram on terminal
box cover, or Fig. 41. The flash code corresponds to the number of LED flashes, followed by a pause, and then the flash
code is repeated. A lockout condition produces a red flash, followed by a pause, a solid red, a second pause, and then repeated. Table 53 lists the flash code information for Warning and
Alert codes along with code reset and troubleshooting
information.
LEDS
DIP SWITCHES
MODULE
POWER
1 2 3 4 5 6 7 8 9 10
T2 T1L3L2L1
R
G
M2
MOTOR THERMAL
SENSORS
JUMPER
COMMUNICATION
PORT
M1
CONTROL CIRCUIT
CONNECTIONS
COMPRESSOR PHASE
SENSING
A38-7314
Warning Codes (Green LED Flash Code):
• Code 1 – Loss of Communication: The module will flash
the green Warning LED one time indicating the module
has not communicated with the master controller for lon-
ger than 5 minutes. Once communication is reinitiated,
the Warning will be cleared. The 30MP units do not sup-
port the communication capability of this module.
• Code 2 – Reserved For Future Use
• Code 3 – Short Cycling: The module will flash the green
Warning LED three times indicating the compressor has
short cycled more than 48 times in 24 hours. A short
cycle is defined as compressor runtime of less than 1
minute. The Warning will be activated when the “Short
Cycling” DIP Switch (no. 10) is OFF (in the down posi-
tion). When fewer than 48 short cycles are accumulated
in 24 hours the Warning code will be cleared.
• Code 4 – Open/Shorted Scroll Thermistor: The module
will flash the green Warning LED four times, indicating
that the scroll NTC thermistor has a resistance value that
indicates an open/shorted thermistor. The Warning will
be cleared when the resistance value is in the normal
range. The 30MP units do not utilize a scroll thermistor.
• Code 5 – Not used.
Alert/Lockout Codes (Red LED Flash Code):
• Code 1 – Motor High Temperature: The module will
flash the red Alert LED one time indicating the motor
PTC circuit has exceeded 4500 .. A Code 1 Alert will
open the M2-M1 contacts. The Alert will reset after 30
minutes and the M2-M1 contacts will close if the resistance of the motor PTC circuit is below 2750 .. Five
consecutive Code 1 Alerts will lock out the compressor.
Once the module has locked out the compressor, a power
cycle will be required for the lockout to be cleared.
• Code 2 – Open/Shorted Motor Thermistor: The module
will flash the red Alert LED 2 times indicating the motor
PTC thermistor circuit has a resistance value greater than
220 or less than 100 . that indicates an open/shorted
thermistor chain. A Code 2 Alert will open the M2-M1
contacts. The Alert will reset after 30 minutes and the
M2-M1 contacts will close if the resistance of the motor
PTC circuit is back in the normal range. The module will
lock out the compressor if the trip condition exists for
longer than 6 hours. Once the module has locked out the
compressor, a power cycle will be required to clear the
lockout.
• Code 3 – Short Cycling: The module will flash the red
Alert LED 3 times indicating the compressor is locked
out due to short cycling. A Code 3 Alert will open the
M2-M1 contacts. Code 3 will be enabled when the Short
Cycling DIP switch (no. 10) is ON (in the up position)
and the compressor has exceeded the number of short
cycles configured by the user in a 24-hour period. Once
the module has locked
out the compressor, a power cycle
will be required to clear the lockout.
• Code 4 – Scroll High Temperature: The module will
flash the red Alert LED 4 times indicating the scroll NTC
circuit is less than 2400 .. A Code 4 Alert will open the
M2-M1 contacts. The Alert will reset after 30 minutes
and the M2-M1 contacts will close if the resistance of the
scroll NTC circuit is higher than 5100 .. The module
will lock out the compressor if the number of Code 4
Alerts exceeds the user configurable number of Code 4
events within a 24-hour period. Once the module has
locked out the compressor, a power cycle will be
required to clear the lockout.
• Code 5 – Not used.
• Code 6 – Missing Phase: The module will flash the red
Alert LED 6 times indicating a missing phase in one of
the three leads to the compressor. A Code 6 Alert will
open the M2-M1 contacts. The Alert will reset after 5
minutes and the M2-M1 contacts will close if the missing
phase condition is not present. The module will lock out
the compressor after 10 consecutive Code 6 Alerts. Once
the module has locked out the compressor, a power cycle
will be required to clear the lockout.
• Code 7 – Reverse Phase: The module will flash the red
Alert LED 7 times indicating a reverse phase in two of
the three leads to the compressor. A Code 7 Alert will
open the M2-M1 contacts. The module will lock out the
compressor after one Code 7 Alert. A power cycle will
be required to clear the lockout.
• Code 8 – Not used.
• Code 9 – Module Low Voltage: The module will flash
the red Alert LED 9 times indicating low module voltage, less than 18 vac on the T2-T1 terminals for more
than 5 seconds. A Code 9 Alert will open the M2-M1
contacts. The Alert will reset after 5 minutes and the M2M1 contacts will close if the T2-T1 voltage is above the
reset value in 18 to 30 vac.
Resetting Alert codes can be accomplished manually by cy-
cling power to the module (disconnect T2 or T1 for 5 seconds).
If the fault that initiated the Alert code is absent after the reset
is performed, the Alert code will be cleared and CoreSense
module will allow normal operation. If the fault is still present
after the reset is performed, the fault code will continue to be
displayed via the green or red flashing LED.
57
Table 52 —CoreSense Communication Module DIP Switch Settings
COPELAND
ELECTRICAL
CODE
“TE”ONOFFOFFOFFOFFOFFOFFOFFONOFF
“TW”*ONOFFOFFOFFOFFOFFOFFOFFOFFOFF
*Settings for Kriwan retrofit. See “CoreSense Replacement of
Kriwan Motor Protection Module” on page 55.
12345678910
DIP SWITCH
Table 53 — CoreSense Communication Module LED Flash Codes
LED STATUSFAULT CONDITION
SOLID GREEN
SOLID RED
GREEN FLASH CODE 1
GREEN FLASH CODE 2 Not usedNot applicableNot applicableNot applicable
GREEN FLASH CODE 3
GREEN FLASH CODE 4
GREEN FLASH CODE 5 Not usedNot applicableNot applicableNot applicable
RED FLASH CODE 1
RED FLASH CODE 2
RED FLASH CODE 3
RED FLASH CODE 4Scroll high temperatureNot applicableNot applicableNot applicable
RED FLASH CODE 5Not usedNot applicableNot applicableNot applicable
RED FLASH CODE 6
RED FLASH CODE 7
RED FLASH CODE 8Not usedNot applicableNot applicableNot applicable
RED FLASH CODE 9
None, normal operationModule is powered and
Module malfunctionModule has an internal fault Not applicable1. Reset module by removing
Loss of communicationModule and Master Control-
Short cyclingRun time of less than 1 min-
Open/Shorted Scroll
Thermistor
High motor temperatureThermistor resistance
Open/shorted motor
thermistor
Short cyclingRun time of less than 1 min-
Missing phaseMissing phase detected.
Reverse phaseReverse phase detected.
Module low voltageLess than 18 vac supplied
FAULT CODE
DESCRIPTION
under normal operation
WARNING LED FLASH
ler have lost communications with each other for
more than 5 minutes
ute. Number of short cycles
exceeds 48 in a 24-hour
period.
Not applicableNot applicableNot applicable
ALERT/LOCKOUT LED FLASH
greater than 4500 . Lockout occurs after 5 alerts.
Thermistor resistance
greater than 4500 , or less
than 100 . Lockout occurs
after 6 hours.
ute. Lockout if the number
of alerts exceeds the number configured by the user
in 24 hours.
Lockout after 10 consecutive alerts.
Lockout after 1 alert.
to module
FAULT CODE RESET
Not applicableNone
Automatic when communications are re-established
Fewer than 48 short cycles
in 24 hours
Thermistor resistance less
than 2750 and 30 minutes have elapsed
Thermistor resistance is
between 100 and 2750
and 30 minutes have
elapsed
Interrupt power to T2-T130MP controls do not allow
After 5 minutes and missing
phase con
ent
Interrupt power to T2-T11. Check incoming power
After 5 minutes and voltage
is between 18 and 30 vac
dition is not pres-
TROUBLESHOOTING
INFORMATION
power from T1-T2.
2. Replace module.
Not Supported. Check DIP
Switch settings.
30MP controls do not allow
this operation normally. Confirm proper wiring and DIP
switch settings.
1. Check power supply.
2. Check system charge and
superheat.
3. Check compressor
contactor.
1. Check for poor connec-
tions at module and thermistor fusite.
2. Check continuity of therm-
istor wiring harness.
3. Check for an open thermistor circuit.
this operation normally. Confirm proper wiring.
1. Check incoming power.
2. Check fuses or circuit
breakers.
3. Check compressor contactor.
phase sequence.
2. Check compressor contactor.
3. Check module phase wiring A-B-C.
This alert does not result in a
lockout fault.
1. Verify correct 24 vac module is installed.
2. Check for a wiring error.
58
Troubleshooting procedures described for the Kriwan mod-
Fig. 42 — External Motor Protection Module,
30MP050-071 Units
ENTER
ENTER
ENTER
ENTER
ENTER
ule section (page 55) are applicable to the CoreSense communication module.
BITZER
*
PROTECTION MODULE — The 30MP unit sizes 050-071 use Bitzer compressors, which are equipped with
24V Lodam motor protection modules. See Fig. 42. The module opens the relay contact in the control circuit and locks out
immediately if the motor temperature exceeds the preset limit.
If a lockout occurs the compressor must cool to ambient temperature and the unit alarm must be cleared manually before
the compressor will restart.
CAUTION
Do not apply external voltage to orange instrument leads,
even for test purposes. Damage to the Lodam protection
device may result.
FIELD TROUBLESHOOTING SOLID-STATE MOTOR
PROTECTION MODULE — Follow the steps listed below
to troubleshoot the module in the field. See wiring diagram in
Fig. 3 and Fig. 4 or in terminal box cover.
1. De-energize control circuit and module power. Remove
the control circuit wires from the module (Terminals M1
and M2 or L and N). Connect a jumper across these “control circuit” wires. This will bypass the “control contact”
of the module.
Re-energize the control circuit and module power. If the
compressor will not operate with the jumper installed,
then the problem is external to the solid-state protection
system.
If the compressor operates with the module bypassed but
will not operate when the module is reconnected, then the
control circuit relay in the module is open. The thermistor
protection chain now needs to be tested to determine if
the module’s control circuit relay is open due to excessive
internal temperatures or a faulty component.
CAUTION
2. Check the thermistor protection chain located in the compressor as follows:
a. De-energize control circuit and module power.
b. Remove the sensor leads from the module (S1 and
S2 or 11 and 14). Measure the resistance of the
thermistor protection chain through these sensor
leads with an ohmmeter.
IMPORTANT: Use an ohmmeter with a maximum of 9
volts to check the sensor chain. The sensor chain is sensitive and easily damaged; no attempt should be made to
check continuity through it with anything other than an
ohmmeter. The application of any external voltage to the
sensor chain may cause damage requiring the replacement
of the compressor.
The diagnosis of this resistance reading is as follows:
• 200 to 2250 ohms - Normal operating range
• 2750 ohms or greater - Compressor overheated - Allow
time to cool
• Zero resistance - Shorted sensor circuit - Replace the
compressor
• Infinite resistance - Open sensor circuit - Replace the
compressor
Motor Protector PTC Key Values
Normal PTC resistance:250 to 2250 Ohms
Trip resistance:>4500 Ohm ± 20%
Reset resistance:<2750 Ohm ± 20%
If the resistance reading is abnormal, remove the sensor
connector plug from the compressor and measure the resistance at the sensor fusite pins. This will determine if
the abnormal reading was due to a faulty connector. On
initial start-up, and after any module trip, the resistance of
the sensor chain must be below the module reset point before the module circuit will close. Reset values are 2250
to 3000 ohms.
3. If the sensor chain has a resistance that is below 2250
ohms, and the compressor will run with the control circuit
bypassed, but will not run when connected properly, the
solid-state module is defective and should be replaced.
The replacement module must have the same supply voltage rating as the original module.
Alarms and Alerts — These are warnings of abnormal
or fault conditions, and may cause either one circuit or the
whole unit to shut down. They are assigned code numbers as
described in Table 54.
Automatic alarms will reset without operator intervention if
the condition corrects itself. The following method must be
used to reset manual alarms:
Before resetting any alarm, first determine the cause of the
alarm and correct it. Enter the Alarms mode indicated by the
LED on the side of the scrolling marquee display. Press
and until the sub-menu item RCRN “RESET
ALL CURRENT ALARMS” is displayed. Press .
The control will prompt the user for a password, by displaying
PASS and WORD. Press to display the default password, 1111. Press for each character. If the password
has been changed, use the arrow keys to change each individual character. Toggle the display to “YES” and press .
The alarms will be reset.
The motor protection system within the compressor is now
bypassed. Use this configuration to temporarily test module only. Failure to do this may result in unit damage.
* Bitzer is a registered trademark of Bitzer Kuhlmaschinenbrau
GmbH.
59
Table 54 — Alarm and Alert Codes
ALARM/
ALERT
CODE
See legend on page 63.
ALARM
OR
ALERT
A048Alarm
T051Alert
A051Alarm
T052Alert
A052Alarm
T053Alert
A053Alarm
A060Alarm
A061Alarm
T062AlertCondenser Leaving Fluid
T063AlertCondenser Entering Fluid
T068None
T073Alert
T074Alert
A077Alarm
T079Alert
A090Alarm
A092Alarm
T094Alert
A110AlarmCircuit A Loss of Charge
A112Alarm
A114Alarm
DESCRIPTION
Circuit A Compressor
Availability Alarm
Circuit A, Compressor 1
Failure
Circuit A, Compressor 1
Stuck on Failure
Circuit A, Compressor 2
Failure
Circuit A, Compressor 2
Stuck on Failure
Circuit A, Compressor 3
Failure
Circuit A, Compressor 3
Stuck on Failure
Cooler Leaving Fluid
Thermistor Failure
Cooler Entering Fluid
Thermistor Failure
Thermistor Failure
Thermistor Failure
Circuit A Return Gas
Thermistor Failure
Outside Air Thermistor
Failure
Space Temperature/Dual Chiller
Thermistor Failure
Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Lead/Lag LWT
Thermistor Failure
Circuit A Discharge
Pressure Transducer Failure
Circuit A Suction
Pressure Transducer Failure
Discharge Gas
Thermistor Failure
Circuit A High Saturated
Suction Temperature
Circuit A Low Suction
Superheat
WHY WAS THIS
ALARM
GENERATED?
Two compressors on circuit
failed
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
uld be off
sho
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F (–40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
(if enabled)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
(if enabled)
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor.
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Outside of range (0 to 667
psig)
Outside of range (0 to 420
psig)
Discharge thermistor (DTT) is
either open or shorted outside
of range –39.9 to 356 F (–39.9
to 180 C)
If the compressors are off
and discharge pressure
reading is < 26 psig for
30 sec.
Circuit saturated suction
temperature pressure
transducer > 70 F (21.1 C)
for 5 minutes
Suction superheat is
less than 5° F (2.8 C) for 5
minutes. (if RGT installed)
ACTION TAKEN
BY CONTROL
Circuit shut downManual
Compressor A1 shut
down.
All compressor outputs
de-energized. 30MPA
head pressure routine
remains active.
Compressor A2 shut
down.
All compressor outputs
de-energized. 30MPA
head pressure routine
remains active.
Compressor A3 shut
down.
All compressor outputs
de-energized. 30MPA
head pressure routine
remains active.
Chiller shut down
immediately
Chiller shut down
immediately
Alert only.
No action taken.
Alert only.
No action taken.
Circuit A shut downAutomatic
Temperature reset
disabled. Chiller runs
under normal control/set
points.
Temperature reset
disabled. Chiller runs
under normal control/set
points.
Circuit A shut down.Manual
iller runs as a stand
Ch
alone machine
Circuit A shut downAutomatic
Circuit A shut downAutomatic
Digital compressor shut
down.
Circuit not allowed to
start.
Circuit shut downManual
Circuit A shut down.
RESET
METHOD
Manual
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic
AutomaticThermistor failure, damaged
AutomaticThermistor failure, damaged
Automatic
Automatic
Automatic
Automatic
Manual
Automatic restart
after first daily
occurrence.
Manual restart
thereafter.
PROBABLE
CAUSE
See applicable compressor
alarm.
High-pressure switch open,
faulty CSB, loss of condenser
flow, filter drier plugged, noncondensables, operation
beyond capability, motor protection module open.
Welded contactor, welded
control relay on MBB, wiring
error, faulty CSB.
High-pressure switch open,
faulty CSB, loss of condenser
flow, filter drier plugged, noncondensables, operation
beyond capability, motor protection module open.
Welded contactor, welded
control relay on MBB, wiring
error, faulty CSB.
High-pressure switch open,
faulty CSB, loss of condenser
flow, filter drier plugged, noncondensables, operation
beyond capability, motor protection module open.
Welded contactor, welded
control relay on MBB, wiring
error, faulty CSB.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
cable/wire or wiring error.
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Faulty expansion valve
suction pressure transducer
or leaving fluid thermistor.
Dual LWT thermistor failure,
damaged cable/wire or
wiring error.
Transducer failure, poor
connection to MBB, or wiring
damage/error.
Transducer failure, poor
connection to MBB, or wiring
damage/error.
Thermistor failure, damaged
cable/wire or wiring error.
Refrigerant leak or
transducer failure
Faulty expansion valve,
faulty suction pressure
transducer or high entering
fluid temperature.
Circuit overcharged, faulty
discharge temperature
thermistor
Circuit overcharged, faulty
discharge temperature
thermistor
Faulty transducer/high
pressure switch.
Plugged filter drier unit operating outside of range. Faulty
transducer/high pressure
switch overcharged, low/
restricted condenser
airflow (30MPA) low or loss of
condenser flow (30MPW),
fouled condenser (30MPW),
faulty EXV.
Faulty or plugged TXV or
EXV, low refrigerant charge,
TXV out of adjustment, liquid
line valve partially closed.
Plugged filter drier. Low
cooler flow.
Reverse any two incoming
power leads to correct. Check
for correct fan rotation first.
CCN Network
command.
Configuration error.
Check unit settings.
Alarm notifies user
that chiller is 100%
down.
Time/Date/Month/
Day/Year not
properly set.
Main Base Board
failure.
Potential failure of
MBB. Download
current operating
software. Replace
MBB if error occurs again.
Main Base Board
failure.
Main Base Board
failure.
Wiring error, faulty wiring or
failed EXV board.
Wiring error, faulty
wiring or failed
Energy Management Module
(EMM).
Faulty signal
generator, wiring
error, or faulty EMM.
Faulty signal
generator, wiring
error, or faulty EMM.
61
Table 54 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
T177Alert
P200Pre-Alert
T200Alert
P201Pre-Alert
A201Alarm
A202Alarm
T203Alert
T204Alert
T205Alert
T206Alert
A207Alarm
A208Alarm
A220
P221Pre-AlertCondenser Pump
See legend on page 63.
ALARM
OR
ALERT
AlarmCondenser Pump
DESCRIPTION
4 to 20 mA Demand
Limit Input Failure
Coder Flow/Interlock
Contacts Failed to Close
at Start-Up
Cooler Flow/Interlock
Contacts failed to Close
at start-up
Cooler Flow/Interlock
Contacts Opened
During Normal
Operation
Cooler Flow/Interlock
Contacts Opened
During Normal
Operation
Cooler Pump Interlock
Closed When Pump is
Off
Loss of Communication
with slave chiller
Loss of Communication
with master chiller
Master and slave chiller
with same address
High Leaving Chilled
Water Temperature
Cooler Freeze
Protection
EWT or LWT
Thermistor failure
terlock Failure to
In
Close
at Start-Up
Interlock Opened During
Normal Operation
WHY WAS THIS
ALARM
GENERATED?
If configured with EMM and
input less than 2 mA or
greater than 22 mA
Cooler flow switch contacts
failed to close within
1 minute (if cooler pump
control is enabled) or
within 5 minutes (if cooler
pump control is not
enabled) after start-up
Cooler flow switch contacts
failed to close within
1 minute (if cooler pump
control is enabled) or
within 5 minutes (if cooler
pump control is not
enabled) after start-up
Flow switch opens for at
least 3 seconds after
being initially closed
Flow switch opens for at
least 3 seconds after
being initially closed
If configured for cooler
pump control and flow
switch input is closed for
5 minutes while pump
output(s) are off
Master chiller MBB
loses communication
with slave chiller MBB
Slave chiller MBB loses
communication with
master chiller MBB
Master and slave chiller
have the same CCN
address (CCN.A)
LWT read is greater than
LCW Alert Limit, Total
capacity is 100% and LWT
is greater than LWT
reading one minute ago
Cooler EWT or LWT is less
than Brine Freeze (BR.FZ)
Cooler EWT is less than
LWT by 3° F (1.7° C) for
1 minute after a circuit is
started
If configured for condenser pump interlock
and the flow switch
input fails to close within 5 minutes after startup. Also valid when
configured for condenser pump control.
If configured for condenser pump interlock
and the flow switch
opens for 15 seconds
during normal
operation (or when
the condenser pump
relay is on when condenser pump control
is configured.)
ACTION TAKEN
BY CONTROL
Demand limit function
disabled. Chiller
returns to 100%
demand limit
control.
Chiller not allowed to
start.
Chiller not allowed to
start.
All compressors shut
down.
All compressors shut
down.
Chiller not allowed to
art
st
Dual chiller control
disabled. Chiller runs
as a stand-alone
machine.
Dual chiller control
disabled. Chiller runs
as a stand-alone
machine
Dual chiller routine
disabled. Master/slave
run as stand-alone
chillers.
Alert only. No action
taken.
Chiller shut down
without going through
pumpdown. Cooler
pump continues to
run a minimum of
5 minutes (if control
enabled).
Chiller shut down.
Cooler pump shut off
(if control enabled).
Condenser and cooler
pumps shut off.
Chiller shut down
Condenser and cooler
pumps shut off. Chiller
shut down
RESET
METHOD
Automatic
Manual
Manual
Manual
Manual
Automatic when
aux contacts open
Automatic
Automatic
Automatic
Automatic
Both EWT and LWT
must be at least 6 F
(3.3 C) above Brine
Freeze point
(BR.FZ). Automatic
for first, Manual reset
there after.
Manual
ManualFailure of condenser
ManualFailure of condenser
Faulty signal
generator, wiring
error, or faulty EMM.
No chilled water flow.
Faulty flow switch or
interlock. Wiring
error.
No chilled water flow.
Faulty flow switch or
interlock. Wiring
error.
Cooler pump failure,
faulty flow switch or
interlock. Wiring
error.
Cooler pump failure,
faulty flow switch or
interlock. Wiring
error.
CCN— Carrier Comfort Network
CSB— Current Sensor Board
CSM— Chiller System Manager
EEPROM — Electronic Eraseable Programmable Read Only Memory
EMM— Energy Management Module
EWT— Entering Fluid Temperature
EXV— Electronic Expansion Valve
LCW— Leaving Chilled Water
LWT— Leaving Fluid Temperature
MBB— Main Base Board
RGT— Return Gas Temperature
SCT— Saturated Condenser Temperature
TXV— Thermostatic Expansion Valve
WSM— Water System Manager
ALARM
OR
ALERT
AlarmLoss of Communication
LEGEND
DESCRIPTION
Interlock Opened During
Normal Operation
Interlock Closed When
Pump is Off
Strainer Blowdown
Scheduled
Maintenance Due
Current Sensor Board
A1 Failure
Current Sensor Board
A2 Failure
Current Sensor Board
A3 Failure
with Water System
Manager
illervisor System
with Ch
Manager
WHY WAS THIS
ALARM
GENERATED?
If configured for condenser pump interlock
and the flow switch
opens for 15 seconds
during normal
operation (or when
the condenser pump
relay is on when condenser pump control
is configured.)
If configured for condenser pump interlock
condenser pump control, and the flow
switch is closed
when pump relay is off.
Strainer Service
Countdown (S.T.DN)
expired. Complete strainer
blowdown and enter 'YES'
for Strainer Maintenance
Done (S.T.MN) item.
Alert occurs when CSB output is a constant high value
Alert occurs when CSB output is a constant high value
Alert occurs when CSB output is a constant high value
No communications have
been received by the MBB
within 5 minutes of last
transmission
No communications have
been received by the MBB
within 5 minutes of last
transmission
ACTION TAKEN
BY CONTROL
Condenser and cooler
pumps shut off. Chiller
shut down
Chiller is not allowed to
start.
NoneAutomatic
Compressor A1 shut
down
Compressor A2 shut
down
Compressor A3 shut
down
WSM forces removed.
Chiller runs under own
control
CSM forces removed.
Chiller runs under own
control
COMPRESSOR FAILURE ALERTS
A048 (Circuit A Compressor Availability Alarm)
— This
alarm occurs when two compressors are unavailable to run on
a 3-compressor circuit. The control ensures proper oil return by
ensuring a circuit does not operate with one compressor for
longer than one hour of cumulative run time.
T051, T052, T053 (Circuit A Compressor Failures)
— Alert
codes 051, 052, and 053 are for compressors A1, A2, and A3
respectively. These alerts occur when the current sensor (CS)
does not detect compressor current during compressor operation. When this occurs, the control turns off the compressor.
If the current sensor board reads OFF while the compressor
relay has been commanded ON, an alert is generated.
POSSIBLE CAUSES
Compressor Overload
— Either the compressor internal overload protector is open or the external overload protector (Kriwan, Copeland CoreSense, or Lodam module) has activated.
The external overload protector modules are mounted in the
compressor wiring junction box. Temperature sensors embedded in the compressor motor windings are the inputs to the
module. The module is powered with 24 vac from the units
main control box. The module output is a normally closed contact that is wired in series with the compressor contactor coil.
In a compressor motor overload condition, contact opens,
de-energizing the compressor contactor.
Low Refrigerant Charge
— If the compressor operates for an
extended period of time with low refrigerant charge, the compressor ASTP device will open, which will cause the compressor to trip on its overload protection device.
Circuit Breaker Trip
— The compressors are protected from
short circuit by a breaker in the control box.
Wiring Error
— A wiring error might not allow the compres-
sor to start.
To check out alerts T051-T053:
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely
the problem is one of the following: HPS open, open internal protection, circuit breaker trip, incorrect safety wiring, incorrect compressor wiring or incorrect Copeland
CoreSense internal phase monitor wiring.
2. If the compressor does start, verify it is rotating in the correct direction.
63
.
IMPORTANT: Prolonged operation in the wrong direction
can damage the compressor. Correct rotation can be verified by a gage set and looking for a differential pressure
rise on start-up.
IMPORTANT: If the CS is always detecting current, verify
that the compressor is on. If the compressor is on, check
the contactor and the relay on the MBB. If the compressor
is off and there is no current, verify the CSB wiring and
replace if necessary.
IMPORTANT: Return to Normal mode and observe compressor operation to verify that compressor current sensor
is working.
COMPRESSOR STUCK ON FAILURE ALARMS
Circuit A A051, A052, A053
— Alarm codes 051, 052, and
053 are for compressors A1, A2, and A3. These alarms occur
when the CSB detects current when the compressor should be
off. When this occurs, the control turns off the compressor.
If the current sensor board reads ON while the compressor
relay has been commanded OFF for a period of 4 continuous
seconds, an alarm is generated. These alarms are only monitored for a period of 10 seconds after the compressor relay has
been commanded OFF. This is done to facilitate a service technician forcing a relay to test a compressor.
In addition, if a compressor stuck failure occurs and the current sensor board reports the compressor and the request off,
certain diagnostics will take place as follows:
1. If any of the compressors are diagnosed as stuck on and
the current sensor board is on and the request is off, the
control will command the condenser fans to maintain
normal head pressure.
2. The control will shut-off all other compressors.
The possible causes include welded contactor or frozen
compressor relay on the MBB.
To check out alarms A051 to A053:
1. Place the unit in Service Test mode. All compressors
should be off.
2. Verify that there is not 24-v at the contactor coil. If there
is 24 v at the contactor, check relay on MBB and wiring.
3. Check for welded contactor.
4. Verify CSB wiring.
5. Return to Normal mode and observe compressor operation to verify that compressor current sensor is working
and condenser fans are energized.
A060 (Cooler Leaving Fluid Thermistor Failure)
— If the
sensor reading is outside the range of –40 to 240 F (–40 to
116 C) then the alarm will occur. The cause of the alarm is usually a faulty thermistor, a shorted or open thermistor caused by
a wiring error, or a loose connection. Failure of this thermistor
will shut down the entire unit.
A061 (Cooler Entering Thermistor Failure)
— If the sensor
reading is outside the range of –40 to 240 F (–40 to 116 C) then
the alarm will occur. The cause of the alarm is usually a faulty
thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. Failure of this thermistor will shut
down the entire unit.
T062 (Condenser Leaving Fluid Thermistor Failure)
— If
the sensor reading is outside the range of –40 to 240 F (–40 to
116 C) then the alert will occur. The cause of the alert is usually
a faulty thermistor, a shorted or open thermistor caused by a
wiring error, or a loose connection. Failure of this thermistor
will send out an alert only.
T063 (Condenser Entering Thermistor Failure)
— If the sensor reading is outside the range of –40 to 240 F (–40 to 116 C)
then the alert will occur. The cause of the alert is usually a
faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. Failure of this thermistor will
send out an alert only.
T068 (Circuit A Compressor Return Gas Temperature
Thermistor Failure) — This alert occurs if the RGT is configured and the compressor return gas temperature sensor is outside the range of –40 to 240 F (–40 to 116 C). Failure of this
thermistor will shut down the appropriate circuit.
T073 (Outside Air Temperature Thermistor Failure)
— This
alert occurs when the outside air temperature sensor is outside
the range of –40 to 240 F (–40 to 116 C). Failure of this thermistor will disable any elements of the control which requires its
use. The OAT must be configured.
T074 (Space Temperature Thermistor Failure)
— This alert
occurs when the space temperature sensor is outside the range
of –40 to 240 F (–40 to 116 C). Failure of this thermistor will
disable any elements of the control which requires its use. The
cause of the alert is usually a faulty thermistor in the T55 or
T58 device, a shorted or open thermistor caused by a wiring error, or a loose connection. The SPT must be configured.
A077 (Circuit Saturated Suction Temperature Exceeds
Cooler Leaving Water Temperature) — This alarm occurs
when the saturated suction temperature (SST) is greater than
leaving water for 5 minutes. This alarm will occur if either the
suction pressure transducer reading, which is used to calculate
SST, or cooler leaving water is incorrect. Potential causes for
this alarm are loose wiring connection, sensor not located in
well, or bad Schrader fitting. Reset is manual.
T079 (Dual Chiller Thermistor Failure)
— This alert occurs
when the dual chiller temperature sensor is outside the range of
–40 to 240 F (–40 to 116 C). Failure of this thermistor will disable dual chiller operation and return to stand-alone operation.
The unit must be configured for dual chiller operation for this
alert to occur. The cause of the alert is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a
loose connection. Reset is automatic.
A090 (Circuit A Discharge Pressure Transducer Failure)
—
This alarm occurs when the pressure is outside the range of 0.0
to 667.0 psig (0.0 to 4599 kPag). A circuit cannot run when this
alarm is active. Use the scrolling marquee to reset the alarm.
The cause of the alarm is usually a faulty transducer, faulty 5-v
power supply, or a loose connection.
A092 (Circuit A Suction Pressure Transducer Failure)
—
This alarm occurs when the pressure is outside the range of 0.0
to 420.0 psig (0.0 to 2896 kPag). A circuit cannot run when this
alarm is active. Use the scrolling marquee to reset the alarm.
The cause of the alarm is usually a faulty transducer, faulty 5-v
power supply, or a loose connection.
T094 (Discharge Gas Thermistor Failure)
— This alert occurs for units which have the digital compressor installed on
circuit A. If discharge gas temperature is open or shorted, the
circuit will be shut off. The valid range for this thermistor is
–39.9 to 356 F (–39.9 to 180 C). The alert will reset itself when
discharge temperature is less than 250 F (121.1 C). The cause
of the alert is usually low refrigerant charge or a faulty
thermistor.
A110 (Circuit A Loss of Charge)
— This alarm occurs when
the compressor is OFF and the discharge pressure is less than
26 psig (179.2 kPa).
A112 (Circuit A High Saturated Suction Temperature)
—
Alarm code 112 occurs when compressors in a circuit have
been running for at least 5 minutes and the circuit saturated
suction temperature is greater than 70 F (21.1 C). The high saturated suction alarm is generated and the circuit is shut down.
64
A114 (Circuit A Low Superheat)
when the superheat of a circuit is less than 5 F (2.8 C) for 5
continuous minutes. The low superheat alarm is generated and
the circuit is shut down. The RGT sensor must be installed.
A116 (Circuit A Low Cooler Suction Temperature)
Alarm code 116 occurs when mode 7 causes the compressor to
unload 3 consecutive times in less than 30-minute intervals between each circuit shutdown. The low cooler suction temperature alarm is generated and the circuit is shut down. If this condition is encountered, check the following items:
• Check for a faulty expansion valve.
• Check for a plugged filter drier.
• Check for a low refrigerant charge condition.
• Check the suction pressure transducer for accuracy.
• Check the cooler flow rate.
• Check the chilled water strainer for a restriction.
• Consider a fouled cooler.
• Check the glycol concentration in the loop; high glycol
concentrations can cause the same effect as a fouled
cooler.
• Check that the water flow is in the proper direction.
P118 — High Discharge Gas Temperature
T118 — High Discharge Gas Temperature
Criteria for Trip: This alert is part of the compressor protection
algorithm for digital compressor units. The following conditions must be true:
1. This alert will be triggered if the unit has a digital compressor and it is enabled (ConfigurationA1.TY=YES).
2. The discharge gas temperature (TemperaturesCIR.AD.GAS) is greater than 268 F (131.1 C).
Action To Be Taken: Compressor A1 is shut down. If this is the
first or second occurrence within a 32-minute window, the prealert P118 will be generated. This is a non-broadcast alert. If
this is the third occurrence within the 32-minute window, the
alert T118 is generated.
Reset Method: The first two times compressor A1 is shut down
due to the pre-alert P118, the pre-alert will automatically reset
after the discharge temperature is less than 250 F (121.1 C) and
the compressor will restart. The third occurrence will result in
the alert T118 and will require a manual reset.
Multiple P118 pre-alerts may be stored in the alarm history.
If there are 1 or 2 strikes on the circuit and the circuit recovers
for a period of time, it is possible to clear out the strikes, thereby resetting the strike counter automatically.
Possible Causes: If this condition is encountered, check the
following items:
• Check to be sure that the circuit is properly charged. If a
leak is found, repair the leak and recharge the circuit.
• Check the discharge temperature thermistor (DTT) for
accuracy.
• Check the discharge temperature thermistor (DTT) con-
nections.
• Check unit configuration. A1.TY = NO if no digital com-
pressor is installed.
A122 (Circuit A, High Pressure Switch Failure)
high-pressure switch is wired in series with the compressor
contactor coils of each compressor on the circuit to disable
compressor operation immediately upon a high discharge pressure condition.
For all 30MP015-045, 30MPA050-071, and 30MP050-071
high condensing units: The normally closed contacts in the
switches are calibrated to open at 650 ± 10 psig (448.2 ± 68.9
kPag) which corresponds to a saturated condensing temperature of 155.6 ± 1.3 F (68.7 ± 0.7 C). The pressure switches will
automatically reset when the discharge pressure is reduced to
500 ± 15 psig (3448 ± 103.4 kPag) which corresponds to a saturated condensing temperature of 134.1 ± 2.4 F (56.7 ± 1.3 C).
— Alarm code 114 occurs
—
UNIT
— The
For all 30MPW050-071 standard units: The normally
closed contacts in the switches are calibrated to open at 558 ±
10 psig (3847 ± 68.9 kPag) which corresponds to a saturated
condensing temperature of 140.3 ± 2.3 F (60.16± 16.5 C). The
pressure switches will automatically reset when the discharge
pressure is reduced to 435 ± 29 psig (2999 ± 199.9 kPag)
which corresponds to a saturated condensing temperature of
120.35 ± 5.3 F (49.08 ± 14.83 C).
The output of the high-pressure switch is wired to inputs on
the MBB to provide the control with an indication of a high
pressure switch trip. This alert could occur when compressors
are off if the wiring to the switch is broken or the switch has
failed open.
When the trip occurs, all mechanical cooling on the circuit
is shut down for 15 minutes. After 15 minutes, the circuit is allowed to restart.
A126 (Circuit A High Head Pressure)
when the appropriate saturated condensing temperature is
greater than the operating envelope shown in Fig 43-45. Prior
to the alarm, the control will shut down one compressor on a
circuit if that circuit’s saturated condensing temperature is
greater than the maximum SCT minus 5° F (2.7° C). If SCT
continues to rise to greater than the maximum SCT, the alarm
will occur and the circuit’s remaining compressor will shut
down. The cause of the alarm is usually an overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil (30MPA only), plugged filter drier, a faulty high-pressure switch, faulty expansion valve, or loss of condenser water
flow. Figures 43-45 shows the operating envelope for the
compressor.
This alarm is also generated when the saturated suction temperature is below the low limit for compressors (outside of
compressor envelope).
If this condition is encountered, check the following items:
• Check to be sure that the circuit is properly charged. If a
leak is found, repair the leak and recharge the circuit.
• Check for proper water flow for the cooler.
• For 30MPA units, if the alarms are occurring during cold
ambient conditions, consider installing head pressure
control on remote condenser.
• If wind baffles are required, check to see if they are
installed.
• Check the suction pressure transducer accuracy.
• Check for a low load condition. Check the control sys-
tem to see if the unit should be operating.
• Check for restrictions in the liquid line. Be sure all ser-
vice valves are open.
• Check the filter drier. Change the core(s) if necessary.
• Check glycol concentration and make sure brine freeze
(Set Points
centration.
• Check the operation of the liquid line solenoid valves, if
equipped. Be sure that the correct valve operates for the
circuit.
• Be sure that the liquid line solenoid valve is installed cor-
rectly (flow), if equipped.
• For the circuit TXV(s):
- Check the superheat setting of the TXV. A very high setting will cause low saturated suction condition.
- Check to be sure the proper TXV is installed.
- Check the operation of the TXV.
- Check the location of the TXV bulb and that it is properly
installed on the suction line.
- Check the TXV equalizer line to be sure that it is properly
connected to the suction line and open to suction pressure.
FRZBR.FZ) is properly set for the con-
— This alarm occurs
65
1
60
170
140
150
160
110
120
130
80
90
100
50
60
70
30
40
-30-20-1001020304050607080
SCT (F)
SST (F)
LEGEND
Fig. 43 — Operating Envelope for R-410A Compressor, 30MP015-045 Units
SCT —
Saturated Condensing Temperature
SST —
Saturated Suction Temperature
a30-4969
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
-30-20-1001020304050607080
SCT (F)
SST (F)
a30-5978
LEGEND
SCT —
Saturated Condensing Temperature
SST —
Saturated Suction Temperature
Fig. 44 — Operating Envelope for R410-A Compressor, 30MPA,MPW050-071 High Condensing Units
66
The example below lists sample suction pressures of a starting
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
-30-20-1001020304050607080
SCT (F)
SST (F)
a30-5979
LEGEND
SCT —
Saturated Condensing Temperature
SST —
Saturated Suction Temperature
Fig. 45 — Operating Envelope for R410-A Compressor, 30MPW050-071 Units
A133 (Circuit A Low Suction Pressure)
— This alarm indi-
cates that after the compressor has been running for 1 minute
circuit. Figures 46 and 47 show reverse rotation detection for
this example.
one of the following has occurred: suction pressure is below
34 psig (234 kPa), saturated suction temperature is less than
12 F (–24.4 C) for 8 seconds, the suction pressure falls below
TIME
23 psig (158 kPa), or saturated temperature is less than –18 F
(–27.8 C). The Circuit A low suction pressure alert occurs and
the circuit is shut down. The reset function will occur automatically for the first daily occurrence and manually (MBB) for
each reoccurrence.
If this condition is encountered, check the following items:
• Check the unit refrigeration charge, a low charge condition can cause low suction pressures.
• Check the TXV operation.
• Check the liquid line service valve to be sure that it is
fully open.
• Check the liquid line filter drier for a restriction.
• Check the head pressure control device. For 30MPA
units, check the remote condenser to be sure that it is
operating correctly. If the remote condenser does not
have head pressure control, consider adding it. For
30MPW units, check the condenser water regulating
valve for proper operation. If the unit does not have head
pressure control, consider adding one, or adjusting the
loop temperature.
A140 — Reverse Rotation Detected
Criteria for Trip: The alarm criterion is checked when the first
compressor in a circuit is started. The control writes the value
of the suction pressure 5 seconds before starting the first compressor in the circuit. At the time the compressor is started,
another reading is obtained. A rate of change is calculated
based on the two values and extrapolated to the expected value
5 seconds later. The suction pressure is obtained 5 seconds
after the compressor has been started. If the suction pressure is
not at least 1.25 psig (8.62 kPa) lower than the expected value
or the upper limit for proof of proper rotation, a reverse
rotation alarm is declared.
t=–5 (5 seconds before
compressor start)
t=0 (compressor start)197.1 (1359)69 (20.6)
t=5 (5 seconds after
compressor start)
Using the rate of change of the suction from the example,
five (5) seconds after t=0, the suction pressure should be 193.8
psig (1336 kPa), if the compressor did not start. Subtracting
the 1.25 psig (8.62 kPa) from extrapolated suction pressure,
192.55 psig (1328 kPa) determines the upper limit that if the
suction pressure is above this level the unit will fault on reverse
rotation. This point is denoted by a black dot in Fig. 46 and 47.
In the example, the suction pressure is lower than the upper
limit, and therefore is allowed to continue operation.
Action To Be Taken: The unit shuts down immediately.
Reset Method: Manual.
Possible Causes: If this condition is encountered, check the
following items:
• Check the wiring of the incoming power for proper phas-
ing. This alarm may be disabled once the reverse rota-
tion check has been verified by setting Reverse Rotation
Enable Configuration
• Check for an inoperative compressor
67
SUCTION
PRESSURE
psig (kPa)
200.4 (1382)70 (21.1)
169.6 (1169)60 (15.6)
SERVREV.R=DSBL.
SATURATED
SUCTION
TEMPERATURE
°F (°C)
-5 -4 -3 -2 -1 0 1 2 3 4 5
Time (sec)
205
200
195
190
185
180
175
170
165
Suction Pressure (psig)
Suction Pressure (psig)
Extrapolated Suction Pressure (psig)
Upper Limit for Proof of Proper Rotation (psig)
LEGEND
Fig. 46 — Reverse Rotation Detection (psig)
Time (sec)
Suction Pressure (psig)
Suction Pressure (psig)
Extrapolated Suction Pressure (psig)
Upper Limit for Proof of Proper Rotation (psig)
LEGEND
-5 -4 -3 -2 -1 0 1 2 3 4 5
1400
1350
1300
1250
1200
1150
Fig. 47 — Reverse Rotation Detection (kPa)
A150 (Unit is in Emergency Stop)
stop command is received, the alarm is generated and the unit
will be immediately stopped.
— If the CCN emergency
If the CCN point name EMSTOP in the system table is set
to emergency stop, the unit will shut down immediately and
broadcast an alarm back to the CCN, indicating that the unit is
down. This alarm will clear when the variable is set back to
“enable.”
A151 — Illegal Configuration Alarm
Criteria for Trip: This alarm is indicated when an illegal con-
figuration has been entered. There are several different
configuration alarms. When expanding the alarm, the control
will indicate which configuration is incorrect. For example, if
the wrong size is configured, the A151 expansion will indicate
“ILLEGAL CONFIG - INVALID UNIT SIZE.”
Action To Be Taken: The unit is not allowed to start.
Reset Method: Automatic, once the illegal configuration is cor-
rected.
• Possible Causes: If this condition is encountered, check the
items shown in Table 55 based on the illegal configuration.
A152 (Unit Down Due to Failure)
— Reset is automatic
when all alarms are cleared. This alarm indicates the unit is at
0% capacity.
T153 (Real Time Clock Hardware Failure)
— A problem
has been detected with MBB real time clock hardware. Try resetting the power and check the indicator lights. If the alert continues, the board should be replaced.
A154 (Serial EEPROM Hardware Failure)
— A problem
has been detected with the EEPROM on the MBB. Try
resetting the power and check the indicator lights. If the alarm
continues, the board should be replaced.
T155 (Serial EEPROM Storage Failure Error)
— A problem
has been detected with the EEPROM storage on the MBB. Try
resetting the power and check the indicator lights. If the alert
continues, the board should be replaced.
A156 (Critical Serial EEPROM Storage Failure Error)
problem has been detected with the EEPROM storage on the
MBB. Try resetting the power and check the indicator lights. If
the alarm continues, the board should be replaced.
A157 (A/D Hardware Failure)
— A problem has been detected with A/D conversion on the boards. Try resetting the power
and check the indicator lights. If the alarm continues, the board
should be replaced.
A172 (Loss of Communication with the EXV Board)
This alarm indicates that there are communication problems
with the EXV board. The alarm will automatically reset.
T173 (Energy Management Module Communication Failure) — This alert indicates that there are communication problems with the energy management module. All functions performed by the EMM will stop, which can include demand limit, reset and capacity input. The alert will automatically reset.
T174 (4 to 20 mA Cooling Set point Input Failure)
alert indicates a problem has been detected with cooling set
point 4 to 20 mA input. The input value is either less than 2 mA
or greater than 22 mA.
A175 (Loss of Communication with the AUX Board)
This alarm will be generated when the Main Base Board
(MBB) loses communication with the AUX Board. The digital
control option will be disabled while this alert is active. The
chiller continues to run without Digital Compressor Control.
The alert will reset automatically if communication is re-established or the unit configuration for digital control, A1.TY Compressor A1 Digital?
(Configuration Mode→UNIT) = NO.
If this condition is encountered, check the following items:
• Check for a wiring error.
• Check for a faulty communication bus, or no connection
to the AUX Board.
• Check the AUX Board.
• If the unit is configured for digital control, A1.TY Com-
pressor A1 Digital?
(Configuration Mode→UNIT) is
YES, but the unit is not a Digital Capacity machine, (no
digital compressor or AUX Board), this alarm will be
generated.
T176 (4 to 20 mA Reset Input Failure)
— This alert indi-
cates a problem has been detected with reset 4 to 20 mA input.
68
— A
—
— This
—
The input value is either less than 2 mA or greater than 22 mA.
The reset function will be disabled when this occurs.
T177 (4 to 20 mA Demand Limit Input Failure)
— This
alert indicates a problem has been detected with demand limit
4 to 20 mA input. The input value is either less than 2 mA or
greater than 22 mA. The reset function will be disabled when
this occurs.
P200 (Coder Flow/Interlock Contacts Failed to Close at
Start-Up Pre-Alarm)
T200 (Cooler Flow Interlock Contacts Failed to Close at
Start-Up Alert) — If Cooler Pump Control is enabled, (Con-figuration→OPT1→CPC=ON) and the Cooler Flow Switch/
Cooler Pump Interlock Contacts failed to close within 1 minute
of a start command, a P200 alarm will be declared. This is a
non-broadcasting alarm. The control will wait for flow to be
established before starting any compressors. If after 5 minutes,
the Cooler Flow Switch/Cooler Pump Interlock Contacts have
not closed, the T200 alarm is declared.
Cooler Pump Interlock Contacts failed to close within 1
minute of a start command, a P200 alarm will be declared.
This is a non-broadcasting alarm. The control will wait for
flow to be established before starting any compressors. If after
5 minutes, the Cooler Flow Switch/Cooler Pump Interlock
Contacts have not closed, the T200 alarm is declared.
If Cooler Pump Control is not enabled, (Configura-
tion
→OPT1→CPC=OFF) and the Cooler Flow Switch/Cooler
Pump Interlock Contacts failed to close within 5 minutes of a
start command, a T200 alarm will be declared.
If this condition is encountered, check the following items:
• Check the chilled water flow switch for proper operation.
• Check the flow switch cable for power and control.
• Check the chilled water loop to be sure that it is com-
pletely filled with water, and all air has been purged.
• Check the chilled water pump interlock circuit for proper
operation.
• Check the pump electrical circuit for power.
• Check the pump circuit breaker.
• Check the pump contactor for proper operation.
• Check the chilled water pump for proper operation.
Look for overload trips.
• Check the chilled water strainer for a restriction.
• Check to be sure that all isolation valves are open
completely.
P201 (Cooler Flow/Interlock Contacts Opened During Normal Operation Pre-alarm)
A201 (Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm) — This alarm will be generated if the
chilled water flow switch opens for at least three (3) seconds
after initially being closed, and a P201 - Cooler Flow/Interlock
Contacts Opened During Normal Operation Alarm will be generated and the machine will stop. If flow is proven, the machine
will be allowed to restart. If after 5 minutes, the cooler flow
switch/interlock contacts do not close, the alarm will change to
a A201 - Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm. When this alarm is generated the chiller
is shut down.
If this condition is encountered, check the following items:
• Check the chilled water flow switch for proper operation.
• Check the flow switch cable for power and control.
• Check the chilled water loop to be sure that it is
completely filled with water, and all air has been purged.
• Check the chilled water pump interlock circuit for proper
operation.
• Check the pump electrical circuit for power.
• Check the pump circuit breaker.
• Check the pump contactor for proper operation.
• Check the chilled water pump for proper operation.
Look for overload trips.
• Check the chilled water strainer for a restriction.
• Check to be sure that all isolation valves are open
completely.
A202 (Cooler Pump Interlock Closed When Pump Is Off
Alarm) — This alarm will be generated if the unit is configured for CPC=ON Cooler Pump Control, (Configura-
tion
→OPT1) without a call for the Chilled Water Pump,
C.LWP=OFF (Outputs→GEN.O) and the chilled water switch
is closed, FLOW=ON Cooler Flow Switch (Inputs
→GEN.I)
for 5 minutes. When this alarm is generated the chiller is not allowed to start.
If this condition is encountered, check the following items:
• Check for a wiring error for the chilled water flow
switch, the chilled water flow switch’s connection to the
MBB, or a wiring error to the chilled water pump.
• Check to see if the chilled water pump control has been
manually bypassed.
• Check for a faulty or grounded chilled water flow switch.
• Check chilled water pump contactor for welded contacts.
Table 55 — Illegal Configurations (Alarm A151)
ILLEGAL CONFIGURATIONPOSSIBLE CAUSES
Check to see if the AUX Board is an older revision not compatible with the current software.
Check the red LED on the AUX Board to be sure that it is blinking in unison with the other
boards in the unit. If it is not, it is not communicating:
AUX BOARD INCORRECT REVISION
AUX BOARD SOFTWARE REV
MUST BE 3 OR HIGHER
AUX BOARD SHOULD BE AUX1, NOT AUX2
INVALID UNIT SIZE HAS BEEN ENTEREDCheck to be sure that a valid unit size Configuration
UNIT CONFIGURATION SET TO
FLUID IS WATER, ICE MAKING ENABLED
INVALID TYPE
- Check the LEN Communication wiring for continuity to the Main Base Board.
- Check the AUX Board DIP Switch settings for the address.
For 208 volt systems, check the control transformer to be sure that it is tapped correctly.
Consider cycling power to the AUX Board.
Check to see if the AUX Board is an older revision not compatible with the current software.
The AUX Board software revision can be found in the vendor part number, CEPL130567-03.
The -03 indicates Revision 03.
Check the part number of the AUX Board. It should have the Carrier Part Number
32GB500442EE (UTEC Part Number CEPL130567-03). This board is required for the digital
compressor output as well as the Motormaster drive signal. An AUX2 Board, Carrier Part
Number 332GB500432EE (UTEC Part Number CEPL130568-02) does not have the capability
to supply these outputs.
Digital compressor, ConfigurationOPT1MLV=YES are both enabled. Only one can be enabled.
Ice mode is enabled, Configuration
OPT1FLUD= 1 (water).
tion
UNITA1.TY=YES, and hot gas Configuration
OPT2ICE.M=ENBL, but fluid type Configura-
69
UNITSIZE has been entered.
T203 (Loss of Communication with the Slave Chiller Alert)
— This alert will be generated if Dual Chiller Control is enabled, LLEN=ENBL Lead/Lag Chiller Enable (Configura-
tion
→RSET), the chiller has been configured to be the Master
Chiller MSSL=MAST Master/Slave Select (Configura-
tion
→RSET) and it has not established or lost communication
with the Slave Chiller. When this alert is generated the dual
chiller control will be disabled and the unit will operate in
stand-alone mode.
If this condition is encountered, check the following items:
• Check that the communication wiring between the two
chillers is proper and is not grounded.
• Check to be sure that both the Master and Slave Chillers
are on the same bus, CCNB CCN Bus Number (Config-
uration
→CCN).
• Check to be sure that the slave chiller address CCNA
CCN Address (Configuration
→CCN) matches what is
programmed in the master chiller’s configuration for
slave address, SLVA Slave Address (Configura-
tion
→RSET).
• Check for power at the slave chiller. If power is not present, this alarm will be generated.
• Check for a faulty master or slave MBB. If CCN communications is not working, this alarm will be generated.
T204 (Loss of Communication with the Master Chiller
Alert) — This alert will be generated if Dual Chiller Control is
enabled, LLEN=ENBL Lead/Lag Chiller Enable (Configura-
tion
→RSET), the chiller has been configured to be the Slave
Chiller MSSL=SLVE Master/Slave Select (Configura-
tion
→RSET) and it has not established or lost communication
with the Master Chiller. When this alert is generated the dual
chiller control will be disabled and the unit will operate in
stand-alone mode.
If this condition is encountered, check the following items:
• Check that the communication wiring between the two
chillers is proper and is not grounded.
• Check to be sure that both the master and slave chillers
are on the same bus, CCNB CCN Bus Number (Config-
uration
→CCN).
• Check to be sure that the slave chiller address CCNA
CCN Address (Configuration
→CCN) matches what is
programmed in the master chiller's configuration for
slave address, SLVA Slave Address (Configura-
tion
→RSET).
• Check for power at the master chiller. If power is not
present, this alarm will be generated.
• Check for a faulty master or slave MBB. If CCN communications is not working, this alarm will be generated.
T205 (Master and Slave Chiller with Same Address Alert)
— This alert will be generated if Dual Chiller Control is enabled, LLEN=ENBL Lead/Lag Chiller Enable (Configura-
tion
→RSET), the chiller has been configured to be the Master
Chiller MSSL=MAST Master/Slave Select (Configura-
tion
→RSET) and both the master chiller and slave chiller have
the same address, CCNA CCN Address (Configura-
tion
→CCN). When this alert is generated the dual chiller con-
trol will be disabled and both units, master and slave, will operate in stand-alone mode.
If this condition is encountered, check to be sure that the
Chiller's configuration for slave address. SLVA Slave Address
(Configuration
T206 (High Leaving Chilled Water Temperature Alert)
→RSET).
—
The criterion for this alert is checked when the unit is ON and
the total available capacity is 100%. The alert is generated
when the leaving chilled water temperature is greater than the
LCWT, High LCW Alert Limit (Configuration
→OPT2) plus
the control point and the leaving chilled water temperature is
higher than it was 1 minute before the current reading. The
LCWT is a delta temperature, not an absolute value. The alert
will automatically reset when the leaving water temperature is
less than the control point, or is less than the control point plus
LCWT minus 5° F (2.8° C).
If this condition is encountered:
• Check building load.
• Check the LCWT, High LCW Alert Limit (Configura-
tion
→OPT2) value.
• Check compressor operation.
• Check water flow.
A207 (Cooler Freeze Protection Alarm)
— This alarm will
be generated when the leaving water temperature is below
BR.FZ, Brine Freeze Point (Set Point Mode
→FRZ). When
this condition is encountered, the machine will enter Mode 16,
and the Chilled Water Pump relay will be energized, even if the
CPC Cooler Pump Control (Configuration Mode
→OPT1) is
OFF. If the machine is equipped with a pump, the pump will
run for a minimum of 5 minutes. The unit will be shut down or
prevented from starting.
The control will allow the machine to reset automatically if
the leaving chilled water temperature rises above the BR.FZ
Brine Freeze Point (Set Point Mode
→FRZ) plus 6°F (3.3°C).
If the alarm is generated again during the same day, it shall be a
manual reset.
If this condition is encountered, check the following items:
• Check the entering or leaving water thermistor for accu-
racy.
• Check water flow rate.
• Check for freezing conditions.
• Check the heat tape and other freeze protection means
for proper operation.
• Check glycol concentration and adjust BR.FZ accord-
ingly.
A208 (EWT or LWT Thermistor Failure Alarm)
— This
alarm will be generated if the entering water temperature, EWT
Entering Fluid Temp (Run Status
→VIEW) is less than the
leaving water temperature, LWT Leaving Fluid Temp (Run
Status
→VIEW) by 3° F (1.7° C) or more for 1 minute after the
circuit has started. When this alarm is generated the chiller is
shut down and prevented from starting. Chilled water pump is
also shut down.
If this condition is encountered, check the following items:
• Check for a correct chilled water flow.
• Check the entering and leaving water thermistors for
accuracy.
• Check to be sure the entering and leaving water thermis-
tors are correctly wired and installed in the proper
location.
A220 (Condenser Pump Interlock Failure to Close At StartUp Alarm) — This alarm will be generated if the unit is configured for D.FL.S=ENBL Enable Cond Flow Switch (Con-
figuration
→OPT1) and condenser flow interlock (if used) cir-
cuit fails to close within 5 minutes of the condenser pump start.
When this alarm is generated the chiller is prevented from
starting or will be shut down; condenser and chilled water
pumps are shut down.
If this condition is encountered, check the following items:
• Check for a condenser pump failure.
• Check for power at the condenser pump.
• Check condenser pump control wiring
• Check condenser strainer for a restriction. Flush or
replace as necessary.
• Check the condenser water flow switch operation.
• Check condenser water flow switch wiring.
• If the unit utilizes a flow regulating valve for head pres-
P221 (Condenser Pump Interlock Opened During Normal
Operation Pre-alarm)
A221 (Condenser Pump Interlock Opened During Normal
Operation Alarm) — If the unit is configured for D.FL.S=ENBL Enable Cond Flow Switch (Configuration
→OPT1) and
condenser flow interlock (if used) circuit was established and
opens for 15 seconds. When this alarm is generated the chiller
is prevented from starting or will be shut down; condenser and
chilled water pumps are shut down.
If this condition is encountered, check the following items:
• Check for a condenser pump failure.
• Check for power at the condenser pump.
• Check condenser pump control wiring.
• Check condenser strainer for a restriction. Flush or
replace as necessary.
• Check the condenser water flow switch operation.
• Check condenser water flow switch wiring.
• If the unit utilizes a flow regulating valve for head pressure control, consider disabling this feature.
A222 (Condenser Pump Interlock Closed When Pump is
Off Alarm) — If the unit is configured for Condenser Pump
Control, D.PM.E Enable Condenser Pump (Configura-
tion
→OPT1) is 1 (On when Occupied) or 2 (On with Compres-
sor), the Condenser Flow Switch is enabled, D.FL.S=ENBL
Enable Cond Flow Switch (Configuration
→OPT1) and con-
denser flow interlock (if used) circuit is closed while the pump
is commanded off, this alarm will be generated. When this
alarm is generated the chiller is prevented from starting.
If this condition is encountered, check the following items:
Ax — Alert codes 500, 501, and 502 are for compressors A1,
A2, and A3 respectively. These alerts occur when the output of
the CSB is a constant high value. These alerts reset automatically. If the problem cannot be resolved, the CSB must be
replaced.
T950 (Loss of Communication with Water System Manager) — This alert will be generated if no communications
have been received by the Main Base Board for five (5) minutes. When this occurs the Water System Manager (WSM)
forces are removed. The chiller runs in stand-alone mode.
If this condition is encountered, check the following items:
• Check CCN wiring.
• Check for power at the water system manager.
• Check Main Base Board for a communication failure.
A951 (Loss of Communication with Chillervisor System
Manager) — This alarm will be generated if no communications have been received by the Main Base Board for five (5)
minutes. When this alert is generated the Chillervisor System
Manager (CSM) forces are removed, and chiller runs in standalone mode.
If this condition is encountered, check the following items:
• Check CCN wiring.
• Check for power at the Chillervisor System Manager.
• Check Main Base Board for a communication failure.
71
APPENDIX A — LOCAL DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
ITEMEXPANSIONRANGEUNITSCCN POINTCOMMENT
VIEWAUTO VIEW OF RUN STATUS
EWTEntering Fluid Tempxxx.x °F EWT
LWTLeaving Fluid Tempxxx.x °FLWT
SETPActive Setpointxxx.x °FSP
CTPTControl Pointxxx.x °FCTRL_PNT
LOD.FLoad/Unload FactorxxxSMZ
STATControl Mode0=Service Test
OCCOccupiedNO/YESOCC
MODEOverride Modes in EffectNO/YESMODE
CAPPercent Total CapacityxxxCAP_T
DEM.LActive Demand LimitDEM_LIM
STGERequested StagexSTAGE
ALRMCurrent Alarms and AlertsxxxALRMALRT
TIMETime of Day00:00 to 23:59xx.xxTIMECOPY
MNTHMonth of Year1 to 12
DATEDay of Month01 to 31xxDOM
YEARYear of CenturyxxYOCDISP
RUNUNIT RUN HOUR AND START
HRS.UMachine Operating Hours0 to 999999xxxx HRSHR_MACH
STR.UMachine Starts0 to 1000000xxxxCY_MACH
HR.P1Cooler Pump Run Hours0 to 999999.9xxxx HRSHR_CPUMP
HR.P2Condenser Pump Run Hours0 to 999999.9xxxx HRSHR_DPUMP
HOURCIRC AND COMP RUN HOURS
HR.A1Compressor A1 Run Hours0 to 999999xxxx HRSHOURS_A1
HR.A2Compressor A2 Run Hours0 to 999999xxxx HRSHOURS_A2
HR.A3Compressor A3 Run Hours0 to 999999xxxx HRSHOURS_A3
STRTCOMPRESSOR STARTS
ST.A1Compressor A1 Starts0 to 999999xxxxCY_A1
ST.A2Compressor A2 Starts0 to 999999xxxxCY_A2
ST.A3Compressor A3 Starts0 to 999999xxxxCY_A3
PMPREVENTIVE MAINTENANCE
STRNSTRAINER MAINTENANCE
STRNSI.STStrainer Srvc Intervalxxxx HRSSI_STRNR
STRNS.T.DNStrainer Srvc Countdown0 to 65535xxxx HRSST_CDOWNDefault: 8760
STRNS.T.MNStrainer Maint. Done0 to 65535NO/YESST_MAINT
ST.DTSTRAINER MAINT. DATES
ST.DTS.T.M0MM/DD/YY HH:MM
ST.DTS.T.M1MM/DD/YY HH:MM
ST.DTS.T.M2MM/DD/YY HH:MM
ST.DTS.T.M3MM/DD/YY HH:MM
ST.DTS.T.M4MM/DD/YY HH:MM
VERSSOFTWARE VERSION NUMBERS
MBBCESR131482-xx-xx
EXV*CESR131172-xx-xx
AUX1*CESR131333-xx-xx
EMM*CESR131174-xx-xx
MARQCESR131171-xx-xx
NAVI*CESR130227-xx-xx
* If these devices are not installed, they will not show in the table.
1=Off Local
2=Off CCN
3=Off Time
4=Off Emergency
5=On Local
6=On CCN
7=On Time
9=Pump Delay
(1 = January,
2 = February, etc.)
xSTAT
xxMOY
72
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Service Test Mode and Sub-Mode Directory
ITEMEXPANSIONRANGEUNITSCCN POINTCOMMENT
TESTSERVICE TEST MODEOFF/ONMAN_CTRLTo enable Service Test
SERVICE CONFIGURATION
Enable Compressor A1DSBL/ENBL
1 = Dual Switch
2 = Dual CCN
Occupied
3 = 4 to 20 mA Input
Time Clock Mode and Sub-Mode Directory
ITEMEXPANSIONRANGEUNITSCCN POINTDEFAULT
TIMETIME OF DAY
HH.MMHour and Minute0 to 65535XXXXXTIME
DATEMONTH, DATE, DAY, AND YEAR
MNTHMonth of Year1 to 12 (1 = January,
DOMDay of Month1 to 31XXDOM
DAYDay of Week1 to 7 (1 = Monday,
YEARYear of Century1999 to 2098XXXXYOCDISP
DSTDAYLIGHT SAVINGS TIME
STR.MMonth1 to 12XXSTARTM4
STR.WWeek1 to 5XSTARTW1
STR.DDay1 to 7XSTARTD7
MIN.AMinutes to Add0 to 90XXMINADD60
STP.MMonth1 to 12XXSTOPM10
STP.WWeek1 to 5XXSTOPW5
STP.DDay1 to 7XXSTOPD7
MIN.SMinutes to Subtract0 to 90XXMINSUB60
HOL.LLOCAL HOLIDAY SCHEDULES
HD.01HOLIDAY SCHEDULE 01
HD.01MON Holiday Start Month0 to 12XXHOLMON01
HD.01DAYStart Day0 to 31XXHOLDAY01
HD.01LENDuration (days)0 to 99XXHOLLEN01
HD.02HOLIDAY SCHEDULE 02
HD.02MON Holiday Start Month0 to 12XXHOLMON02
HD.02DAYStart Day0 to 31XXHOLDAY02
HD.02LENDuration (days)0 to 99XXHOLLEN02
HD.03HOLIDAY SCHEDULE 03
HD.03MON Holiday Start Month0 to 12XXHOLMON03
HD.03DAYStart Day0 to 31XXHOLDAY03
HD.03LENDuration (days)0 to 99XXHOLLEN03
HD.04HOLIDAY SCHEDULE 04
HD.04MON Holiday Start Month0 to 12XXHOLMON04
HD.04DAYStart Day0 to 31XXHOLDAY04
HD.04LENDuration (days)0 to 99XXHOLLEN04
HD.05HOLIDAY SCHEDULE 05
HD.05MON Holiday Start Month0 to 12XXHOLMON05
HD.05DAYStart Day0 to 31XXHOLDAY05
HD.05LENDuration (days)0 to 99XXHOLLEN05
HD.06HOLIDAY SCHEDULE 06
HD.06MON Holiday Start Month0 to 12XXHOLMON06
HD.06DAYStart Day0 to 31XXHOLDAY06
HD.06LENDuration (days)0 to 99XXHOLLEN06
HD.07HOLIDAY SCHEDULE 07
HD.07MON Holiday Start Month0 to 12XXHOLMON07
HD.07DAYStart Day0 to 31XXHOLDAY07
HD.07LENDuration (days)0 to 99XXHOLLEN07
HD.08HOLIDAY SCHEDULE 08
HD.08MON Holiday Start Month0 to 12XXHOLMON08
HD.08DAYStart Day0 to 31XXHOLDAY08
HD.08LENDuration (days)0 to 99XXHOLLEN08
HD.09HOLIDAY SCHEDULE 09
HD.09MON Holiday Start Month0 to 12XXHOLMON09
HD.09DAYStart Day0 to 31XXHOLDAY09
HD.09LENDuration (days)0 to 99XXHOLLEN09
HD.10HOLIDAY SCHEDULE 10
HD.10MON Holiday Start Month0 to 12XXHOLMON10
HD.10DAYStart Day0 to 31XXHOLDAY10
HD.10LENDuration (days)0 to 99XXHOLLEN10
2 = February, etc.)
2 = Tuesday, etc.)
XCLSP_TYP0 = Single
DSBL/ENBL
XX MOY
XDOWDISP
ENABLEA1
ENABLEA2
77
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
ITEMEXPANSIONRANGEUNITSCCN POINTDEFAULT
HOL.LLOCAL HOLIDAY SCHEDULES
HD.11HOLIDAY SCHEDULE 11
HD.11MON Holiday Start Month0 to 12XXHOLMON11
HD.11DAYStart Day0 to 31XXHOLDAY11
HD.11LENDuration (days)0 to 99XXHOLLEN11
HD.12HOLIDAY SCHEDULE 12
HD.12MON Holiday Start Month0 to 12XXHOLMON12
HD.12DAYStart Day0 to 31XXHOLDAY12
HD.12LENDuration (days)0 to 99XXHOLLEN12
HD.13HOLIDAY SCHEDULE 13
HD.13MON Holiday Start Month0 to 12XXHOLMON13
HD.13DAYStart Day0 to 31XXHOLDAY13
HD.13LENDuration (days)0 to 99XXHOLLEN13
HD.14HOLIDAY SCHEDULE 14
HD.14MON Holiday Start Month0 to 12XXHOLMON14
HD.14DAYStart Day0 to 31XXHOLDAY14
HD.14LENDuration (days)0 to 99XXHOLLEN14
HD.15HOLIDAY SCHEDULE 15
HD.15MON Holiday Start Month0 to 12XXHOLMON15
HD.15DAYStart Day0 to 31XXHOLDAY15
HD.15LENDuration (days)0 to 99XXHOLLEN15
HD.16HOLIDAY SCHEDULE 16
HD.16MON Holiday Start Month0 to 12XXHOLMON16
HD.16DAYStart Day0 to 31XXHOLDAY16
HD.16LENDuration (days)0 to 99XXHOLLEN16
HD.17HOLIDAY SCHEDULE 17
HD.17MON Holiday Start Month0 to 12XXHOLMON17
HD.17DAYStart Day0 to 31XXHOLDAY17
HD.17LENDuration (days)0 to 99XXHOLLEN17
HD.18HOLIDAY SCHEDULE 18
HD.18MON Holiday Start Month0 to 12XXHOLMON18
HD.18DAYStart Day0 to 31XXHOLDAY18
HD.18LENDuration (days)0 to 99XXHOLLEN18
HD.19HOLIDAY SCHEDULE 19
HD.19MON Holiday Start Month0 to 12XXHOLMON19
HD.19DAYStart Day0 to 31XXHOLDAY19
HD.19LENDuration (days)0 to 99XXHOLLEN19
HD.20HOLIDAY SCHEDULE 20
HD.20MON Holiday Start Month0 to 12XXHOLMON20
HD.20DAYStart Day0 to 31XXHOLDAY20
HD.20LENDuration (days)0 to 99XXHOLLEN20
HD.21HOLIDAY SCHEDULE 21
HD.21MON Holiday Start Month0 to 12XXHOLMON21
HD.21DAYStart Day0 to 31XXHOLDAY21
HD.21LENDuration (days)0 to 99XXHOLLEN21
HD.22HOLIDAY SCHEDULE 22
HD.22MON Holiday Start Month0 to 12XXHOLMON22
HD.22DAYStart Day0 to 31XXHOLDAY22
HD.22LENDuration (days)0 to 99XXHOLLEN22
HD.23HOLIDAY SCHEDULE 23
HD.23MON Holiday Start Month0 to 12XXHOLMON23
HD.23DAYStart Day0 to 31XXHOLDAY23
HD.23LENDuration (days)0 to 99XXHOLLEN23
HD.24HOLIDAY SCHEDULE 24
HD.24MON Holiday Start Month0 to 12XXHOLMON24
HD.24DAYStart Day0 to 31XXHOLDAY24
HD.24LENDuration (days)0 to 99XXHOLLEN24
HD.25HOLIDAY SCHEDULE 25
HD.25MON Holiday Start Month0 to 12XXHOLMON25
HD.25DAYStart Day0 to 31XXHOLDAY25
HD.25LENDuration (days)0 to 99XXHOLLEN25
HD.26HOLIDAY SCHEDULE 26
HD.26MON Holiday Start Month0 to 12XXHOLMON26
HD.26DAYStart Day0 to 31XXHOLDAY26
HD.26LENDuration (days)0 to 99XXHOLLEN26
HD.27HOLIDAY SCHEDULE 27
HD.27MON Holiday Start Month0 to 12XXHOLMON27
HD.27DAYStart Day0 to 31XXHOLDAY27
HD.27LENDuration (days)0 to 99XXHOLLEN27
HD.28HOLIDAY SCHEDULE 28
HD.28MON Holiday Start Month0 to 12XXHOLMON28
HD.28DAYStart Day0 to 31XXHOLDAY28
HD.28LENDuration (days)0 to 99XXHOLLEN28
HD.29HOLIDAY SCHEDULE 29
HD.29MON Holiday Start Month0 to 12XXHOLMON29
HD.29DAYStart Day0 to 31XXHOLDAY29
HD.29LENDuration (days)0 to 99XXHOLLEN29
HD.30HOLIDAY SCHEDULE 30
HD.30MON Holiday Start Month0 to 12XXHOLMON30
HD.30DAYStart Day0 to 31XXHOLDAY30
HD.30LENDuration (days)0 to 99XXHOLLEN30
SCH.NSCHEDULE NUMBER0 to 99XXSCHEDNUM0
78
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
ITEMEXPANSIONRANGEUNITSCCN POINTDEFAULT
SCH.LLOCAL OCCUPANCY SCHEDULE
PER.1OCCUPANCY PERIOD 1
PER.1OCC.1 Period Occupied Time0 to 6144XX:XXPER1OCC
PER.1UNC.1 Period Unoccupied Time0 to 6144XX:XXPER1UNC
PER.1MON.1 Monday In PeriodNO/YESPER1MON
PER.1TUE.1 Tuesday In PeriodNO/YESPER1TUE
PER.1WED.1 Wednesday In PeriodNO/YESPER1WED
PER.1THU.1 Thursday In PeriodNO/YESPER1THU
PER.1FRI.1Friday In PeriodNO/YESPER1FRI
PER.1SAT.1 Saturday In PeriodNO/YESPER1SAT
PER.1SUN.1 Sunday In PeriodNO/YESPER1SUN
PER.1HOL.1 Holiday In PeriodNO/YESPER1HOL
PER.2OCCUPANCY PERIOD 2
PER.2OCC.2 Period Occupied Time0 to 6144XX:XXPER2OCC
PER.2UNC.2 Period Unoccupied Time0 to 6144XX:XXPER2UNC
PER.2MON.2 Monday In PeriodNO/YESPER2MON
PER.2TUE.2 Tuesday In PeriodNO/YESPER2TUE
PER.2WED.2 Wednesday In PeriodNO/YESPER2WED
PER.2THU.2 Thursday In PeriodNO/YESPER2THU
PER.2FRI.2Friday In PeriodNO/YESPER2FRI
PER.2SAT.2 Saturday In PeriodNO/YESPER2SAT
PER.2SUN.2 Sunday In PeriodNO/YESPER2SUN
PER.2HOL.2 Holiday In PeriodNO/YESPER2HOL
PER.3OCCUPANCY PERIOD 3
PER.3OCC.3 Period Occupied Time0 to 6144XX:XXPER3OCC
PER.3UNC.3 Period Unoccupied Time0 to 6144XX:XXPER3UNC
PER.3MON.3 Monday In PeriodNO/YESPER3MON
PER.3TUE.3 Tuesday In PeriodNO/YESPER3TUE
PER.3WED.3 Wednesday In PeriodNO/YESPER3WED
PER.3THU.3 Thursday In PeriodNO/YESPER3THU
PER.3FRI.3Friday In PeriodNO/YESPER3FRI
PER.3SAT.3 Saturday In PeriodNO/YESPER3SAT
PER.3SUN.3 Sunday In PeriodNO/YESPER3SUN
PER.3HOL.3 Holiday In PeriodNO/YESPER3HOL
PER.4OCCUPANCY PERIOD 4
PER.4OCC.4 Period Occupied Time0 to 6144XX:XXPER4OCC
PER.4UNC.4 Period Unoccupied Time0 to 6144XX:XXPER4UNC
PER.4MON.4 Monday In PeriodNO/YESPER4MON
PER.4TUE.4 Tuesday In PeriodNO/YESPER4TUE
PER.4WED.4 Wednesday In PeriodNO/YESPER4WED
PER.4THU.4 Thursday In PeriodNO/YESPER4THU
PER.4FRI.4Friday In PeriodNO/YESPER4FRI
PER.4SAT.4 Saturday In PeriodNO/YESPER4SAT
PER.4SUN.4 Sunday In PeriodNO/YESPER4SUN
PER.4HOL.4 Holiday In PeriodNO/YESPER4HOL
PER.5OCCUPANCY PERIOD 5
PER.5OCC.5 Period Occupied Time0 to 6144XX:XXPER5OCC
PER.5UNC.5 Period Unoccupied Time0 to 6144XX:XXPER5UNC
PER.5MON.5 Monday In PeriodNO/YESPER5MON
PER.5TUE.5 Tuesday In PeriodNO/YESPER5TUE
PER.5WED.5 Wednesday In PeriodNO/YESPER5WED
PER.5THU.5 Thursday In PeriodNO/YESPER5THU
PER.5FRI.5Friday In PeriodNO/YESPER5FRI
PER.5SAT.5 Saturday In PeriodNO/YESPER5SAT
PER.5SUN.5 Sunday In PeriodNO/YESPER5SUN
PER.5HOL.5 Holiday In PeriodNO/YESPER5HOL
PER.6OCCUPANCY PERIOD 6
PER.6OCC.6 Period Occupied Time0 to 6144XX:XXPER6OCC
PER.6UNC.6 Period Unoccupied Time0 to 6144XX:XXPER6UNC
PER.6MON.6 Monday In PeriodNO/YESPER6MON
PER.6TUE.6 Tuesday In PeriodNO/YESPER6TUE
PER.6WED.6 Wednesday In PeriodNO/YESPER6WED
PER.6THU.6 Thursday In PeriodNO/YESPER6THU
PER.6FRI.6Friday In PeriodNO/YESPER6FRI
PER.6SAT.6 Saturday In PeriodNO/YESPER6SAT
PER.6SUN.6 Sunday In PeriodNO/YESPER6SUN
PER.6HOL.6 Holiday In PeriodNO/YESPER6HOL
PER.7OCCUPANCY PERIOD 7
PER.7OCC.7 Period Occupied Time0 to 6144XX:XXPER7OCC
PER.7UNC.7 Period Unoccupied Time0 to 6144XX:XXPER7UNC
PER.7MON.7 Monday In PeriodNO/YESPER7MON
PER.7TUE.7 Tuesday In PeriodNO/YESPER7TUE
PER.7WED.7 Wednesday In PeriodNO/YESPER7WED
PER.7THU.7 Thursday In PeriodNO/YESPER7THU
PER.7FRI.7Friday In PeriodNO/YESPER7FRI
PER.7SAT.7 Saturday In PeriodNO/YESPER7SAT
PER.7SUN.7 Sunday In PeriodNO/YESPER7SUN
PER.7HOL.7 Holiday In PeriodNO/YESPER7HOL
79
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
ITEMEXPANSIONRANGEUNITSCCN POINTDEFAULT
SCH.L (cont)LOCAL OCCUPANCY SCHEDULE
PER.8OCCUPANCY PERIOD 8
PER.8OCC.8 Period Occupied Time0 to 6144XX:XXPER8OCC
PER.8UNC.8 Period Unoccupied Time0 to 6144XX:XXPER8UNC
PER.8MON.8 Monday In PeriodNO/YESPER8MON
PER.8TUE.8 Tuesday In PeriodNO/YESPER8TUE
PER.8WED.8 Wednesday In PeriodNO/YESPER8WED
PER.8THU.8 Thursday In PeriodNO/YESPER8THU
PER.8FRI.8Friday In PeriodNO/YESPER8FRI
PER.8SAT.8 Saturday In PeriodNO/YESPER8SAT
PER.8SUN.8 Sunday In PeriodNO/YESPER8SUN
PER.8HOL.8 Holiday In PeriodNO/YESPER8HOL
OVRSCHEDULE OVERRIDE
OVR.TTimed Override Hours0 to 4 hoursX OVR_EXT0
OVR.LOverride Time Limit0 to 4 hoursX OTL0
T.OVRTimed OverrideNO/YESTIMEOVERNO
Operating Mode and Sub-Mode Directory
ITEMEXPANSIONRANGEUNITSCCN POINTDEFAULT
MODEMODES CONTROLLING UNIT
MD01CSM controlling ChillerOFF/ONMODE_1
MD02WSM controlling ChillerOFF/ONMODE_2
MD03Master/Slave controlOFF/ONMODE_3
MD05Ramp Load LimitedOFF/ONMODE_5
MD06Timed Override in effectOFF/ONMODE_6
MD07Low Cooler Suction TempAOFF/ONMODE_7
MD09Slow Change OverrideOFF/ONMODE_9
MD10Minimum OFF time activeOFF/ONMODE_10
MD13Dual SetpointOFF/ONMODE_13
MD14Temperature ResetOFF/ONMODE_14
MD15Demand/Sound LimitedOFF/ONMODE_15
MD16Cooler Freeze ProtectionOFF/ONMODE_16
MD17Low Temperature CoolingOFF/ONMODE_17
MD18High Temperature CoolingOFF/ONMODE_18
MD19Making ICEOFF/ONMODE_19
MD20Storing ICEOFF/ONMODE_20
MD21High SCT Circuit A OFF/ONMODE_21
MD23Minimum Comp. On TimeOFF/ONMODE_23
MD24Pump Off Delay TimeOFF/ONMODE_24
MDAOCircuit A Trio Oil MgmtOFF/ONMD_A_OIL
80
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Alarms Mode and Sub-Mode Directory
ITEMEXPANSIONRANGEUNITSCCN POINTCOMMENT
CRNTCURRENTLY ACTIVE ALARMS
AA01
AA02
AA03
AA04
AA05
AA06
AA07
AA08
AA09
AA10
AA11
AA12
AA13
AA14
AA15
AA16
AA17
AA18
AA19
AA20
AA21
AA22
AA23
AA24
AA25
RCRNReset All Current AlarmsNO/YESALRESET
HISTALARM HISTORY
AL01
AL02
AL03
AL04
AL05
AL06
AL07
AL08
AL09
AL10
AL11
AL12
AL13
AL14
AL15
AL16
AL17
AL18
AL19
AL20
Current Alarms 1-25
Alarm History 1-20
AXXX
TXXX
PXXX
AXXX
TXXX
PXXX
Alarms are shown as
AXXX
Alerts are shown as
TXXX
PreAlerts are shown as
PXXX
Alarms are shown as
AXXX
Alerts are shown as
TXXX
PreAlerts are shown as
PXXX
81
APPENDIX B — CCN TABLES
CCN DISPLAY TABLES
TABLEDISPLAY NAMERANGEUNITSPOINT NAMEWRITE STATUS
A-UNITGENERAL UNIT PARAMETERS
Control Mode10-char ASCIISTAT
OccupiedNo/YesOCC
CCN ChillerStop/StartCHIL_S_Sforcible
Alarm State6-char ASCIIALM
Active Demand LimitNNN%DEM_LIMforcible
Override Modes in EffectNo/YesMODE
Percent Total CapacityNNN%CAP_T
Requested StageNNSTAGE
Active SetpointNNN.ndegFSP
Control PointNNN.n degFCTRL_PNTforcible
Degrees of ResetNN.ndeltaFDEG_RST
Entering Fluid TempNNN.n degFEWT
Leaving Fluid TempNNN.n degFLWT
Emergency StopEnable/EMStopEMSTOPforcible
Minutes Left for Start5-char ASCIIMIN_LEFT
EXVA Position in StepsNNNNNNstepsEXVAPOSS
EXVA Position in PercentNNNN.nn%EXVAPOSP
EXVA Commanded StepsNNNNNNstepsEXVACMDS
EXVA Run StatusNNNEXVASTAT
EXVA Write CommandOff/OnEXVARITE
EXVA Command ByteNNNEXVACMDB
EXVA Absolute PercentageNNNN.nn%EXVAABSP
EXVA Delta PercentageNNNNN.n%EXVADELP
Saturated Suction TempNNN.ndegFTMP_SSTA
Compr Return Gas TempNNN.ndegFTMP_RGTA
Discharge Gas TempNNN.ndegFDISGAS
EXV % OpenNNN%EXV_A
Amount of SH ResetNNN.ndeltaFSH_RESET
EXVA OverrideNNNNNEXVAOVRR
EXVA Steps in RangeNNNNNstepsEXVARANG
EXVA Steps Per SecondNNNNNEXVARATE
EXVA Fail Position in %NNNN.nn%EXVAPOSF
EXVA Minimum StepsNNNNNstepsEXVAMINS
EXVA Maximum StepsNNNNNstepsEXVAMAXS
EXVA Overrun StepsNNNNNstepsEXVAOVRS
EXVA Stepper TypeNNNEXVATYPE
STRTHOUR
CURRMODS
Machine Operating HoursNNNNNNhoursHR_MACH
Machine StartsNNNNNNhoursCY_MACH
Compressor A1 Run HoursNNNNNN.nhoursHR_A1
Compressor A2 Run Hours NNNNNN.nhoursHR_A2
Compressor A3 Run Hours NNNNNN.nHR_A3
Compressor A1 StartsNNNNNNCY_A1
Compressor A2 StartsNNNNNNCY_A2
Compressor A3 StartsNNNNNNCY_A3
PUMP HOURS
Cooler Pump Run HoursNNNNNN.nhoursHR_CPUMP
Condenser Pump Run HoursNNNNNN.nhoursHR_DPUMP
CSM controlling ChillerOff/OnMODE_1
WSM controlling ChillerOff/OnMODE_2
Master/Slave controlOff/OnMODE_3
Ramp Load LimitedOff/OnMODE_5
Timed Override in effectOff/OnMODE_6
Low Cooler Suction TempAOff/OnMODE_7
Slow Change OverrideOff/OnMODE_9
Minimum OFF time activeOff/OnMODE_10
Dual SetpointOff/OnMODE_13
Temperature ResetOff/OnMODE_14
Demand/Sound LimitedOff/OnMODE_15
Cooler Freeze ProtectionOff/OnMODE_16
Low Temperature CoolingOff/OnMODE_17
High Temperature CoolingOff/OnMODE_18
Making ICEOff/OnMODE_19
Storing ICEOff/OnMODE_20
High SCT Circuit AOff/OnMODE_21
Minimum Comp. On TimeOff/OnMODE_23
Pump Off Delay TimeOff/OnMODE_24
Circuit A Trio Oil MgmtOff/OnMD_A_OIL
83
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES (cont)
TABLEDISPLAY NAMERANGEUNITSPOINT NAMEWRITE STATUS
ALARMS
VERSIONS
LOADFACTCAPACITY CONTROL
LEARNFNS
PM-STRN
TESTMODE
Active Alarm #14-char ASCIIALARM01C
Active Alarm #24-char ASCIIALARM02C
Active Alarm #34-char ASCIIALARM03C
Active Alarm #44-char ASCIIALARM04C
Active Alarm #54-char ASCIIALARM05C
Active Alarm #64-char ASCIIALARM06C
Active Alarm #74-char ASCIIALARM07C
Active Alarm #84-char ASCIIALARM08C
Active Alarm #94-char ASCIIALARM09C
Active Alarm #104-char ASCIIALARM10C
Active Alarm #114-char ASCIIALARM11C
Active Alarm #124-char ASCIIALARM12C
Active Alarm #134-char ASCIIALARM13C
Active Alarm #144-char ASCIIALARM14C
Active Alarm #154-char ASCIIALARM15C
Active Alarm #164-char ASCIIALARM16C
Active Alarm #174-char ASCIIALARM17C
Active Alarm #184-char ASCIIALARM18C
Active Alarm #194-char ASCIIALARM19C
Active Alarm #204-char ASCIIALARM20C
Active Alarm #214-char ASCIIALARM21C
Active Alarm #224-char ASCIIALARM22C
Active Alarm #234-char ASCIIALARM23C
Active Alarm #244-char ASCIIALARM24C
Active Alarm #254-char ASCIIALARM25C
Service PasswordNNNNPASSWORD1111
Password EnableDisable/EnablePASS_EBLEnable
Metric DisplayOff/OnDISPUNITOff
Language SelectionNLANGUAGE0
CONFIGURATION
EXV Opening at Low LWTNNN.N%EXV_Y125
LWT for EXV Min Opening NNN.NLWT_X110
EXV Opening at High LWTNNN.N%EXV_Y250
LWT for EXV Max OpeningNNN.N°FLWT_X235
EXV Circ. A Min PositionNNN.N%EXVAMINP2
EXVA Steps in RangeNNNNNstepsEXVARANG2500
EXVA Steps Per Second NNNNNEXVARATE150
EXVA Fail Position In %NNNN.NN%EXVAPOSF0
EXVA Minimum StepsNNNNNstepsEXVAMINS0
EXVA Maximum StepsNNNNNstepsEXVAMAXS2500
EXVA Overrun StepsNNNNNstepsEXVAOVRS167
EXVA Stepper TypeNNNEXVATYPE1
High SCT ThresholdNNN.N°FHIGH_SCT115
Open EXV X% on 2nd compNNN.N%EXV_HSCT10
Move EXV X% on DISCRSOLNNN.N%EXVDISCR5
Lag Start DelayNNNsecDELAYLAG10
SH Reset MaximumNNN.N^FMAXSHRST11
Cap at SH Offset MaximumNNN.N%SHRSTBGN25
SH Rate ThresholdNNN.N^FSHR_THR0.2
Low SH DeltaT EXV MoveNNNsecLSH_DL_T60
Low SH Override EXV MoveNNN.N%LSH_EXVM1
* BACnet is a registered trademark of ASHRAE (American Society
of Heating, Refrigerating, and Air-Conditioning Engineers).
† BACview is a registered trademark of Automated Logic
Corporation.
The following section is used to configure the UPC Open controller which is used when the BACnet* communication
option is selected. The UPC Open controller is mounted in the
main control box per unit components arrangement diagrams.
TO ADDRESS THE UPC OPEN CONTROLLER — The
user must give the UPC Open controller an address that is
unique on the BACnet network. Perform the following procedure to assign an address:
1. If the UPC Open controller is powered, pull the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the address
each time power is applied to it.
2. Using the rotary switches (see Fig. A and B), set the controller's address. Set the Tens (10's) switch to the tens digit of the address, and set the Ones (1's) switch to the ones
digit.
As an example in Fig. B, if the controller’s address is 25,
point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
0
1
9
2
8
3
7
8
7
10's
4
6
5
0
1
9
2
3
1's
4
6
5
BACNET DEVICE INSTANCE ADDRESS — The UPC
Open controller also has a BACnet Device Instance address.
This Device Instance MUST be unique for the complete BACnet system in which the UPC Open controller is installed. The
Device Instance is auto generated by default and is derived by
adding the MAC address to the end of the Network Number.
The Network Number of a new UPC Open controller is 16101,
but it can be changed using i-Vu
®
Tools or BACView† device.
By default, a MAC address of 20 will result in a Device Instance of 16101 + 20 which would be a Device Instance of
1610120.
88
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Fig. C — DIP Switches
Fig. D — Network Wiring
CONFIGURING THE BAS PORT FOR BACNET MS/
TP — Use the same baud rate and communication settings for
all controllers on the network segment. The UPC Open controller is fixed at 8 data bits, No Parity, and 1 Stop bit for this
protocol's communications.
If the UPC Open controller has been wired for power, pull
the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the DIP
Switches and jumpers each time power is applied to it.
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS
Port DIP switch DS4 to “E1-485.” Set the BMS Protocol DIP
switches DS8 through DS5 to “MSTP.” See Table A.
Table A — SW3 Protocol Switch Settings
for MS/TP
DS8DS7DS6DS5DS4DS3
OffOffOffOffOnOff
Verify that the EIA-485 jumpers below the CCN Port are set
to EIA-485 and 2W.
The example in Fig. C shows the BAS Port DIP Switches
set for 76.8k (Carrier default) and MS/TP.
Set the BAS Port DIP Switches DS2 and DS1 for the appropriate communications speed of the MS/TP network (9600,
19.2k, 38.4k, or 76.8k bps). See Fig. C and Table B.
Table B — Baud Selection Table
BAUD RATEDS2DS1
9,600OffOff
19,200OnOff
38,400OffOn
76,800OnOn
WIRING THE UPC OPEN CONTROLLER TO THE MS/
TP NETWORK — The UPC Open controller communicates
using BACnet on an MS/TP network segment communications
at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration. Wire specifications for the cable are
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,
twisted, stranded, shielded copper wire. The maximum length
is 2000 ft.
Install a BT485 terminator on the first and last Multi-Chiller
Controller on a network segment to add bias and prevent signal
distortions due to echoing. See Fig. A, D, and E. For MultiChiller Controller only need BT485 on the end.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's
BAS Port.
2. Check the communications wiring for shorts and
grounds.
3. Connect the communications wiring to the BAS port’s
screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not currently connected.
5. Verify communication with the network by viewing a
module status report. To perform a module status report
using the BACview keypad/display unit, press and hold
the “FN” key then press the “.” Key.
89
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Fig. E — BT485 Terminator Installation
To install a BT485 terminator, push the BT485 terminator
on to the BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
®
i-Vu
Open Control System Master Prices.
MS/TP WIRING RECOMMENDATIONS — Recommendations are shown in Tables C and D. The wire jacket and UL
Conductor 22 or 24 AWG stranded copper (tin plated)
Insulation Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Color Code Black/White
Twist Lay 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Shielding Aluminum/Mylar shield with 24 AWG TC drain wire
Jacket
DC Resistance 15.2 Ohms/1000 feet (50 Ohms/km) nominal
Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor
Characteristic Impedance 100 Ohms nominal
Weight 12 lb/1000 feet (17.9 kg/km)
UL Temperature Rating
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG— American Wire Gage
CL2P— Class 2 Plenum Cable
DC— Direct Current
FEP— Fluorinated Ethylene Polymer
NEC— National Electrical Code
O.D.— Outside Diameter
TC— Tinned Copper
UL— Underwriters Laboratories
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)
temperature rating specifications list two acceptable alternatives. The Halar* specification has a higher temperature rating
and a tougher outer jacket than the SmokeGard† specification,
and it is appropriate for use in applications where the user is
concerned about abrasion. The Halar jacket is also less likely to
crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum
signal integrity.
Halar is a registered trademark of Solvay Plastics.
*
† SmokeGard is a registered trademark of AlphaGary-Mexichem
Corp.
90
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Fig. F — BACview6 Device Connection
Table D — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS
Wire Type Description
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
AWG— American Wire Gage
CL2P— Class 2 Plenum Cable
CMP— Communications Plenum Rated
FEP— Fluorinated Ethylene Polymer
TC— Tinned Copper
specifications.
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
Connect Air
International
W221P-22227—25160PVCLP0520LC
W241P-2000F8284125120-OR—
Belden RMCORP
Contractors
Wire and Cable
LOCAL ACCESS TO THE UPC OPEN CONTROLLER — The user can use a BACview
6
handheld keypad display unit or the Virtual BACview software as a local user interface to an Open controller. These items let the user access the
controller network information. These are accessory items and
do not come with the UPC Open controller.
The BACview
6
unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will require an additional USB link cable for connection.
See the BACview Installation and User Guide for instruc-
tions on connecting and using the BACview
To order a BACview
6
Handheld (BV6H), consult Commer-
6
device.
cial Products i-Vu Open Control System Master Prices.
CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES — The UPC Open device and ComfortLink
controller must be set to the same CCN Address (Element)
number and CCN Bus number. The factory default settings for
CCN Element and CCN Bus number are 1 and 0 respectively.
If modifications to the default Element and Bus number are
required, both the ComfortLink and UPC Open configurations
must be changed.
The following configurations are used to set the CCN Address and Bus number in the ComfortLink controller. These
configurations can be changed using the scrolling marquee display or accessory Navigator handheld device.
Configuration→CCN→CCN.A (CCN Address)
Configuration→CCN→CCN.B (CCN Bus Number)
The following configurations are used to set the CCN Address and Bus Number in the UPC Open controller. These configurations can be changed using the accessory BACview
6
dis-
play.
Navigation: BACview→CCN
Home: Element Comm Stat
Element: 1
Bus: 0
91
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
If the UPC Open controller is used with the chiller application of Lead/Lag/Standby (Lead/Lag/Standby applications are
not used with the Multi-Chiller Controller), all chillers and
UPC Open controller's CCN element numbers must be
changed to a unique number in order to follow CCN specifications. In this application, there can only be a maximum of 3
UPC Open controllers on a CCN bus.
For the CCN Alarm Acknowledger configuration, the UPC
Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/
Standby application is being used, then the Carrier technician
must change the configuration to only one CCN Acknowledger
on the CCN bus.
For the CCN Time Broadcaster configuration, the UPC
Open defaults to CCN Time Broadcaster. If the Chiller Lead/
Lag/Standby application is used, then the Carrier technician
must change the configuration to only one CCN Time Broadcaster on the CCN bus.
TROUBLESHOOTING — If there are problems wiring or
addressing the UPC Open controller, contact Carrier Technical
Support.
COMMUNICATION LEDS
— The LEDs indicate if the
controller is communicating with the devices on the network.
Table E — LED Status Indicators
LEDSTATUS
Power
Rx Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Tx Lights when the controller transmits data to the network segment; there is a Tx LED for Ports 1 and 2.
Run Lights based on controller status. See Table F.
Error Lights based on controller status. See Table F.
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on
the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition
that caused the fault returns to normal.
See Tables E and F. The LEDs should reflect communication
traffic based on the baud rate set. The higher the baud rate the
more solid the LEDs become. See Fig. A for location of LEDs
on UPC Open module.
REPLACING THE UPC OPEN BATTERY — The UPC
Open controller’s 10-year lithium CR2032 battery provides a
minimum of 10,000 hours of data retention during power outages.
IMPORTANT: Power must be ON to the UPC Open controller when replacing the battery, or the date, time, and
trend data will be lost.
Remove the battery from the controller, making note of the
battery's polarity. Insert the new battery, matching the battery's
polarity with the polarity indicated on the UPC Open
controller.
NETWORK POINTS LIST — The points list for the controller is shown in Table G.
Refer to Appendix B for additional information on CCN
point name.
Table F — Run and Error LEDs Controller and Network Status Indication
RUN LEDERROR LEDSTATUS
2 flashes per second Off Normal
2 flashes per second 2 flashes, alternating with Run LED Five minute auto-restart delay after system error
2 flashes per second 3 flashes, then off Controller has just been formatted
2 flashes per second 1 flash per second Controller is alone on the network
2 flashes per second On Exec halted after frequent system errors or control programs halted
5 flashes per second On Exec start-up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second 7 flashes per second, alternating with Run LED Ten second recovery period after brownout
14 flashes per second 14 flashes per second, alternating with Run LED Brownout
92
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List
POINT DESCRIPTION
4-20 ma Demand SignalLMT_MARmA0-20AV:36lmt_ma_1
4-20 ma Reset SignalRST_MARmA0-20AV:33rst_ma_1
Active Demand LimitDEM_LIMR/W%1000-100AV:2dem_lim_1
Active SetpointSPR°F-20-70AV:4sp_1
Control ModeSTATR0-9AV:8stat_1
Control PointCTRL_PNTR/W°F44.0-20-70AV:5ctrl_pnt_1
Cooler Entering FluidCOOL_EWTR°F-40-245AV:30cool_ewt_1
Cooler Flow SwitchCOOLFLOWROpen/CloseBV:11coolflow_1
Dual SetpointMODE_13ROn/OffBV:39mode_13_1
Dual Setpoint SwitchDUAL_INROn/OffBV:29dual_in_1
Element Comm StatusRBV:2999element_stat_1
Emergency StopEMSTOPR/WEnabledEnabled/EmstopBV:6emstop_1
Entering Fluid TempEWTR°F-40-245AV:6ewt_1
EXV% OpenEXV_AR%AV:18exv_a_1
High SCT Circuit AMODE_21ROn/OffBV:47mode_21_1
High Temperature CoolingMODE_18ROn/OffBV:44mode_18_1
Ice DoneICE_DONEROn/OffBV:27ice_done_1
ICE SetpointCSP3R/W°F32.0-20-32AV:55csp3_1
Lead/Lag Circuit SelectLEAD_TYPR/W11-3AV:43lead_typ_1
Lead/Lag Leaving FluidDUAL_LWTR°F-40-245AV:32dual_lwt_1
Leaving Fluid TempLWTR°F-40-245AV:7lwt_1
Loading Sequence SelectSEQ_TYPER/W1-2AV:77seq_type_1
Low Cooler Suction TempAMODE_7ROn/OffBV:35mode_7_1
Low Sound ModeMODE_25ROn/OffBV:51mode_25_1
Low Temperature CoolingMODE_17ROn/OffBV:43mode_17_1
Machine Operating HoursHR_MACHRhr0-9999AV:57mr_mach_1
Machine StartsCY_MACHR0-9999AV:58cy_mach_1
Making ICEMODE_19ROn/OffBV:45mode_19_1
Master/Slave ControlMODE_3ROn/OffBV:32mode_3_1
Minimum Comp. On TimeMODE_23ROn/OffBV:49mode_23_1
Minimum Load Valve RelayMLV_RLYROn/OffBV:79mlv_rly_1
Minimum OFF Time ActiveMODE_10ROn/OffBV:38mode_10_1
Minutes Left for StartMIN_LEFTRmin00:00-15:00AV:39min_left_1
Minutes Off TimeDELAYR/Wmin00-15AV:42delay_1
Occupancy StatusOCCRYes/NoBV:2008occ_status_1
Outdoor Air TemperatureOATR/W°F-40-245AV:1003oa_temp_1
Override Modes in EffectMODERYes/NoBV:5mode_1
Percent Available Cap.CAPA_AR%0-100AV:12capa_a_1
Percent Total CapacityCAP_TR%0-100AV:3cap_t_1
Percent Total CapacityCAPA_TR%0-100AV:11capa_t_1
Pump Off Delay TimeMODE_24ROn/OffBV:50mode_24_1
Ramp Load LimitedMODE_5ROn/OffBV:33mode_5_1
Requested StageSTAGER0-99AV:9stage_1
Saturated Condensing TmpTMP_SCTAR°F-40-245AV:16tmp_scta_1
Saturated Suction TempTMP_SSTAR°F-40-245AV:17tmp_ssta_1
Slow Change OverrideMODE_9ROn/OffBV:37mode_9_1
Space TemperatureSPTR/W°F-40-245AV:2007space_temp_1
Storing ICEMODE_20ROn/OffBV:46mode_20_1
Strainer Maint. DoneST_MAINTR/WYes/NoBV:55st_maint_1
Strainer Srvc CountdownST_CDOWNRhr0-9999AV:52st_cdown_1
Strainer Srvc IntervalSI_STRNRR/Whr0-9999AV:51si_strnr_1
Suction PressureSP_ARpsig0-999AV:14sp_a_1
Suction Superheat TempSH_A
System Cooling Demand LevelR1-3AV:9006cool_demand_level_1
System Demand LimitingRACTIVE_INACTIVEBV:83dem_lmt_act_1
Temperature ResetMODE_14ROn/OffBV:40mode_14_1
Timed Override in EffectMODE_6ROn/OffBV:34mode_6_1
User Defined Analog 1R/WAV:2901user_analog_1_1
User Defined Analog 2R/WAV:2902user_analog_2_1
User Defined Analog 3R/WAV:2903user_analog_3_1
User Defined Analog 4R/WAV:2904user_analog_4_1
User Defined Analog 5R/WAV:2905user_analog_5_1
User Defined Binary 1R/WBV:2911user_binary_1_1
User Defined Binary 2R/WBV:2912user_binary_2_1
User Defined Binary 3R/WBV:2913user_binary_3_1
User Defined Binary 4R/WBV:2914user_binary_4_1
User Defined Binary 5R/WBV:2915user_binary_5_1
WSM Controlling ChillerMODE_2ROn/OffBV:31mode_2_1
CCN POINT
NAME
READ/
WRITE
UNITS
R°F-40-245AV:44sh_a_1
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
94
APPENDIX D — MAINTENANCE SUMMARY AND LOG SHEETS
30MP Weekly Maintenance Log
Plant ___________________________ Unit ID ______________________
Machine Model No. ________________
DATEOIL LEVEL
CHECK ALARMS
/ FAULTS
OPERATOR
INITIALS
REMARKS
95
APPENDIX D — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
30MP Monthly Maintenance Log
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
CCN loadshed, 34
Discharge temperature thermistor
(DTT), 15
Dual leaving water temperature sensor
(DLWT), 15
Electronic expansion valves, 41
Emergency On/Off switch, 7
Enable/Off/Remote Control switch, 7
Energy management module (EMM),
16,18
Described, 7
Evacuation and dehydration, 38
INDEX
Expansion Valve Board (EXV)
Described, 7
Filter drier service, 45
High pressure switch (HPS)
Described,
Usage,46
Language, changing display, 6
LEDs, 7
Main base board (MBB)
Described, 7
Schematic, 12
Maintenance, 52
Schedule, 52
Measure of units, changing display, 6
Minimum load control, 36
Minutes left for start, 17
Minutes off time, 18
Motor overload protection,
compressor, 54
Copeland with TF code, 54
Copeland with TW or TE, 54
CoreSense module mounting, 56
Kriwan, 55
Navigator display
Backlight brightness, 6
Contrast adjustment, 6
Display tables, 72-81
Occupancy schedule
CCN global, 24
Holidays, 21
Local schedule, 21
Setting, 21
Timed override, 24
Oil
Adjusting charge (start-up), 39
Checking level (start-up), 39
Charging (service), 45
Quantity per compressor, 39
Operating limitations, 40
Operating modes