Carrier MPC Open XP Series, MPC Open XPIO48, MPC Open XPIO816 Installation And Startup Manual

MPPCC OOppeenn XXPP
M
MPPCC OOppeenn XXPPIIOO4488//881166
M
IInnssttaallllaattiioonn aanndd SSttaarrtt--uupp GGuuiiddee
CARRIER CORPORATION ©2019 A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-431-01 · 1/24/2019
www.hvacpartners.com
Document revision history
Verify that you have the most current version of this document from
office.
Important changes are listed in
CARRIER CORPORATION ©2019. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier Corporation. All other trademarks are the property of their respective owners.
at the end of this document.
or your local Carrier
Introduction .................................................................................................................................................................. 1
Installing the MPC Open XP ........................................................................................................................................ 7
Local access to the MPC Open XP............................................................................................................................ 27
Troubleshooting ......................................................................................................................................................... 28
Compliance ................................................................................................................................................................ 33
Appendix A: MPC Open XP wire lists ........................................................................................................................ 34
Document revision history ........................................................................................................................................ 42
Contents
What are the MPC Open XP and MPC Open XPIO expanders? ..................................................................... 1
MPC Open XP specifications ............................................................................................................................... 3
MPC Open XPIO48 and MPC Open XPIO816 specifications .......................................................................... 5
Safety considerations........................................................................................................................................... 6
Mounting the MPC Open XP ................................................................................................................................ 7
Wiring the MPC Open XP for power ................................................................................................................... 7
To wire for power ................................................................................................................................... 8
Addressing the MPC Open XP ............................................................................................................................. 8
Wiring for communications ................................................................................................................................. 9
Wiring specifications for BACnet MS/TP and ARC156 ........................................................................ 9
To wire the controller to the network ................................................................................................... 9
Installing an MPC Open XPIO expander ......................................................................................................... 10
To mount an expander ........................................................................................................................ 11
To wire the expander for power .......................................................................................................... 12
To attach MPC Open XPIO expanders ................................................................................................ 13
To set expander's address .................................................................................................................. 13
Wiring inputs and outputs ................................................................................................................................ 14
Inputs ................................................................................................................................................... 14
Input wiring specifications .................................................................................................................. 15
Outputs ................................................................................................................................................ 15
Output wiring specifications ............................................................................................................... 16
To wire inputs and outputs ................................................................................................................. 16
To use the Auto-Off-On switches ........................................................................................................ 19
Wiring devices to the MPC Open XP's Rnet port ........................................................................................... 19
Rnet wiring specifications ................................................................................................................... 20
To wire ZS sensors to the controller ................................................................................................... 20
To wire the Wireless Adapter for wireless sensors ............................................................................ 21
To wire an Equipment Touch to the MPC Open XP ............................................................................ 23
To wire the TruVu™ ET Display ........................................................................................................... 24
Installing the MPC Open XP into an i-Vu® Control System ......................................................................... 25
MPC Open XP LED's ........................................................................................................................................... 28
Expander LED's .................................................................................................................................................. 29
To restore factory defaults ............................................................................................................................... 30
To get the serial number .................................................................................................................................. 30
To replace the MPC Open XP's battery ........................................................................................................... 31
To replace the fuse ............................................................................................................................................ 31
FCC Compliance ................................................................................................................................................. 33
CE Compliance ................................................................................................................................................... 33
BACnet Compliance........................................................................................................................................... 33
MPC Open XP wire list ....................................................................................................................................... 35
MPC Open XPIO48 wire list .............................................................................................................................. 37
MPC Open XPIO816 wire list ........................................................................................................................... 39

What are the MPC Open XP and MPC Open XPIO expanders?

Introduction

The Multipurpose Controller Open XP (MPC Open XP - #OPN-MPCXP) provides monitoring and control for a variety of HVAC system applications. The MPC Open XP supports multiple I/O configurations for both common and custom HVAC control and connects to up to 20 field points directly (8 outputs and 12 inputs).
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 1
Introduction
The MPC Open XPIO48 (#OPN-MPCXPIO48) and MPC Open XPIO816 (#OPN-MPCXPIO816) are expanders that connect to the expandable MPC Open XP to increase the number of inputs and outputs. To add inputs or outputs to the MPC Open XP, you can attach up to 3 expanders, using any combination of MPC Open XPIO48 and/or MPC Open XPIO816 expanders connected to the Xnet.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 2
Introduction

MPC Open XP specifications

NOTE
Driver drv_mpcxpopen_vanilla
Maximum number of control programs*
Maximum number of BACnet objects*
Maximum number of third­party integration points using Snap*†
* Depends on available memory † BACnet third-party integration points are not counted.
Power 24 Vac ±10%, 50–60 Hz
BACnet port For communication with the controller network using BACnet ARC156 (156
Rnet port
999
12000
200
50 VA power consumption 26 Vdc (25 V min, 30 V max), 23 W Single Class 2 source only, 100 VA or less
kbps) or BACnet MS/TP (9600 bps – 76.8 kbps)
Supports up to 15 wireless and/or ZS sensors, and one Equipment Touch or TruVu™ ET Display
Supplies 12 Vdc/210 mA power to the Rnet at an ambient temperature of 77°F (25°C) with a 24 Vac nominal power source. NOTE Ambient temperature and power source fluctuations may reduce the power supplied by the Rnet port.
If the total power required by the sensors on the Rnet exceeds the power supplied by the Rnet port, use an external power source. The Wireless Adapter, Equipment Touch, or TruVu™ ET Display must be powered by an external power source. See the specifications in each device's Installation and Start-up Guide to determine the power required.
Local Access port For system start-up and troubleshooting using Field Assistant
Xnet Remote Expansion port For communication with expanders MPC Open XPIO48 and/or MPC Open
XPIO816. Up to 3 expanders with a maximum of 92 points between the MPC Open XP and the expanders.
Inputs 12 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry
contact
Input resolution 14 bit A/D
Input pulse frequency 40 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 12.5 msec.
Outputs 8 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA. Does not support dry
contact output channels.
Output resolution 12 bit D/A
Memory 16 MB non-volatile battery-backed RAM (with 12 MB available for use), 8 MB
Flash memory, 32-bit memory bus
Real-time clock Battery-backed real-time clock keeps track of time in event of power failure
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 3
Introduction
Battery Low
CAUTION
Battery 10-year Lithium CR123A battery ensures the following data is retained for a
maximum of 720 hours during power outages:
Time
Graphics
Control programs
Editable properties
Schedules
Trends
To conserve battery life, you can set the driver to turn off battery backup after a specified number of days and depend on the archive function to restore data when the power returns. A low battery is indicated by the Vu® application, a touchscreen device, and Field Assistant.
LED or a low battery alarm in the i-
Protection Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power is protected by a replaceable 3 Amp Pico® fuse. Network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal.
The power, network, input, and output connections are also protected against transient excess voltage/surge events lasting no more than 10 msec.
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
BT485 connector You can install a BT485 (#BT485 - sold separately) to an MPC Open XP at the
beginning and end of a network segment to add bias and to terminate a network segment.
Status indicators LEDs indicate status of communications and low battery status. Seven segment
display indicates running, error, and power status.
Environmental operating
0 to 140° F (-18 to 60°C), 0 to 90% relative humidity, non-condensing
range
Storage temperature range -24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical Rugged aluminum cover, removable screw-type terminal blocks
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 4
Introduction

MPC Open XPIO48 and MPC Open XPIO816 specifications

MPC Open XPIO48
MPC Open XPIO816
MPC Open XPIO48
MPC Open XPIO816
MPC Open XPIO48
MPC Open XPIO816
Overall dimensions A:
B:
Mounting dimensions C:
D: E: F:
11-5/16 in. (28.7 cm) 7-1/2 in. (19 cm)
10-7/8 in. (27.6 cm) 1-1/4 in. ( 3.2 cm) 2-1/2 in. ( 6.4 cm) 1/4 in. (.6 cm)
Depth 1-7/16 in. (3.7 cm)
Weight 1.7 lbs (0.8 kg)
BACnet support Conforms to the BACnet Building Controller (B-BC) Standard Device Profile as
defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 9
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A
Power
24 Vac ±10%, 50–60 Hz 40 VA power consumption 26 Vdc (25 V min, 30 V max), 21 W Single Class 2 source only, 100 VA or less
24 Vac ±10%, 50–60 Hz 45 VA power consumption 26 Vdc (25 V min, 30 V max), 21 W Single Class 2 source only, 100 VA or less
Inputs
Input resolution 14 bit A/D
Input pulse frequency 40 pulses per second. Minimum pulse width (on or off time) required for each
Outputs
Output resolution 12 bit D/A
Microprocessor 8-bit microprocessor with 60 kB Flash memory, 2 kB SRAM, and CAN controller
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 5
8 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry contact
16 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry contact
pulse is 12.5 msec.
4 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA
8 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA
Introduction
NOTE

Safety considerations

WARNING
Protection Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power is protected by 2 replaceable 3 Amp Pico
®
fuses. The power, network, input, and output connections are protected against transient excess voltage/surge events lasting no more than 10 msec.
Status indicators LEDs indicate status of communications, running, errors, and outputs.
Environmental operating range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
Install in a UL Listed enclosure only.
Storage temperature range -24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical Rugged aluminum cover, removable screw-type terminal blocks
Overall dimensions A:
B:
Mounting dimensions (in a panel)
C: D: E: F:
Depth 1-7/16 in. (3.7 cm)
9 in. (22.9 cm) 4-13/16 in. (12.2 cm)
8-5/8 in. (21.8 cm) 1 in. (2.5 cm) 2-13/16 in (7.1 cm) 1/4 in. (.6 cm)
Weight 13.3 oz. (.377 kg)
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
could cause electrical shock, personal injury, or damage to the controller.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 6
Disconnect electrical power to the MPC Open XP before wiring it. Failure to follow this warning
Installing the MPC Open XP

Mounting the MPC Open XP

WARNING

Wiring the MPC Open XP for power

WARNING
CAUTIONS

Installing the MPC Open XP

To install the MPC Open XP:
1 Mount the controller (page 7).
2 Wire the controller for power (page 7).
3 Set the controller's address (page 8).
4 Wire the controller to the BACnet MS/TP or BACnet ARC156 network (page 9).
5 Wire inputs and outputs (page 14).
6 Wire expanders to the controller (page 10).
7 Wire devices to the Rnet port (page 19).
When you handle the MPC Open XP:
• Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
• Do not touch components or leads.
• Handle the board by its edges.
• Isolate from high voltage or electrostatic discharge.
• Ensure that you are properly grounded.
Screw the MPC Open XP into an enclosed panel using the mounting slots on the cover plate. Leave about 2 in. (5 cm) on each side of the controller for wiring. See mounting dimensions in Specifications.
If using expanders, see Installing an expander (page 10) before mounting the controller.
The MPC Open XP is powered by a Class 2 power source. Take appropriate isolation measures when mounting it in a control panel where non-Class 2 circuits are present.
Carrier controllers can share a power supply as long as you:
Maintain the same polarity.
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 7
Installing the MPC Open XP

To wire for power

Return
24 Vac/26 Vdc

Addressing the MPC Open XP

Tens (10's
Ones (1's
EXAMPLE
Tens (10's
Ones (1's
10's
1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
NOTE
CAUTION
Use the power supply only for Carrier controllers.
1 Turn off the MPC Open XP's power switch to prevent it from powering up before you can verify the correct
voltage.
2 Remove primary power from the 24 Vac transformer.
3 Pull the screw terminal connector from the controller's power terminals labeled
4 Connect the transformer wires to the screw terminal connector.
5 Apply primary power to the transformer.
6 Measure the voltage at the controller's power screw terminal connector to verify that the voltage is within the
operating range of 21.6 - 26.4 Vac.
7 Insert the screw terminal connector into the controller's power terminals.
8 Turn on the MPC Open XP's power switch.
9 Verify that the Power LED is on and the Run LED is blinking.
and
.
The MPC Open XP's two rotary switches determine its MAC address when it is placed on a BACnet MS/TP network. The rotary switches define the MAC address portion of the device's BACnet address, which is composed of the network address and the MAC address.
1 Turn on the controller's power.
2 Using the rotary switches, set the controller's address. Set the
address, and set the
the
If the controller’s address is 25, point the arrow on the
) switch to 5.
3 Turn on the controller's power.
The controller reads the address each time you apply power to it.
The factory default setting is 00 and must be changed to successfully install your MPC Open XP.
) switch to the ones digit.
) switch to the tens digit of the
) switch to 2 and the arrow on
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 8
Installing the MPC Open XP

Wiring for communications

NOTE

Wiring specifications for BACnet MS/TP and ARC156

WARNING

To wire the controller to the network

24 Vac/26 Vdc
Return
Net +, Net -
Shield
NOTE
For...
Set BACnet Mode jumper to... Set DIP switches 7 and 8 to...
BACnet MS/TP
MS/TP
Baud
BACnet ARC156
NOTE
The MPC Open XP communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
For more networking details, see the Open Controller Network Wiring Installation Guide.
Cable: 22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length: 2000 feet (610 meters)
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
1 Pull the screw terminal connector from the controller's power terminals labeled
(Ground).
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the controller’s screw terminals labeled
Use the same polarity throughout the network segment.
4 Set the communication type and baud rate.
MS/TP
ARC156
Use the same baud rate for all controllers on the network segment.
5 Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration.
The appropriate baud rate. See the BACnet
N/A. Baud rate will be 156 kbps regardless of the DIP
, and
and
.
diagram on the controller.
switch settings.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 9
Installing the MPC Open XP

Installing an MPC Open XPIO expander

6 Install a BT485 on the first and last controller on a network segment to add bias and prevent signal
distortions due to echoing.
7 Insert the power screw terminal connector into the MPC Open XP's power terminals.
8 Turn on the MPC Open XP's power.
9 Verify communication with the network by viewing a Module Status report in the i-Vu® interface.
See the Open Controller Network Wiring Guide for more details.
To install the MPC Open XPIO48 and/or the MPC Open XPIO816:
1 Mount the expander (page 11).
2 Wire the expander for power (page 12).
3 Attach the expander (page 13).
4 Address the expander (page 13).
5 Wire inputs and outputs (page 14).
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 10
Installing the MPC Open XP

To mount an expander

WARNING
Gnd
Gnd, Xnet-
Xnet-
Xnet+
Xnet+
When you handle the expander:
• Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
• Do not touch components or leads.
• Handle the board by its edges.
• Isolate from high voltage or electrostatic discharge.
• Ensure that you are properly grounded.
Wiring restrictions for connecting the expander to the MPC Open XP
Maximum length: 100 feet (30 meters)
22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
You can mount the expander in one of the following locations:
On top of a MPC Open XP, using the two allen cap screws provided. Connect
to
to
to
,
.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 11
Installing the MPC Open XP
Gnd
Gnd, Xnet-
Xnet-, Xnet+
Xnet+

To wire the expander for power

CAUTIONS
Off
24 Vac/26 Vdc
Return
Power
Run
Beside the MPC Open XP, by screwing the expander into an enclosed panel using the mounting slots on the coverplate. Leave about 2 in. (5 cm) on each side of the expander for wiring. Mounting hole dimensions 1.5" from the left (width) by 10.2" (height). Connect
to
to
to
. You can mount the
expander up to 100 ft away from the controller.
The expanders are powered by a Class 2 power source. Take appropriate isolation measures when mounting it in a control panel where non-Class 2 circuits are present.
For the MPC Open XP to recognize an attached expander, you must turn on the expander before you turn on the controller.
1 Verify that the expander's power switch is in the
2 Connect the 24 Vac power source to the
polarity if power is being shared.
3 Turn on the expander's power switch.
4 Verify that the expander's
LED is on and the
position.
and
LED is blinking.
terminals, being sure to maintain proper
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 12
Installing the MPC Open XP

To attach MPC Open XPIO expanders

Xnet Remote Expansion
NOTE
Xnet Remote Expansion
Xnet
Term
Term

To set expander's address

EXAMPLE
NOTE
CAUTION
Error
Run
1 Wire the MPC Open XP's
Connect:
Gnd to Gnd
Xnet- to Xnet-
Xnet+ to Xnet+
To use more than one expander, wire their
configuration. The MPC Open XP must be the first device on the expander network.
2 Set the Xnet baud rate to 500 kbps in the i-Vu® interface on the driver's
3 If the expander network has more than one expander, place the
it from all expanders except the one at the end of the expander network. The position on the expander at the end of the network.
You must give the expanders an address that is unique on the expander network.
1 If wired for power, turn off the expander's power and the attached MPC Open XP's power.
2 Set the expander's address on the rotary switch.
If the controller’s address is 2, point the arrow on the switch to 2.
port to the same port on the expander.
ports together in a daisy-chain
page.
jumper in the down position or remove
jumper must be in the up
The MPC Open XP can have a maximum of 3 expanders. You MUST address the expanders as 1, 2,
and 3. Higher addresses will not work.
3 Turn on the expander's power, then turn on the attached MPC Open XP's power. The MPC Open XP reads the
powered expander's address each time you turn on the MPC Open XP.
The first time the controller communicates with an expander, it triggers a software download. This may occur if the expander(s) are blank (not a normal condition) and in cases where the controller’s driver has been updated. During that time, the red
LED and the green
LED on the expander(s) flash in sequence. This process may take several minutes to complete. Do not disconnect power or communications wiring during this download.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 13
Installing the MPC Open XP

Wiring inputs and outputs

WARNING

Inputs

Signal Type
Description
Aux Power Out
Aux Power
Out
Gnd
NOTE
NOTE
See Appendix A (page 34) to print a blank wire list.
The MPC Open XP and expanders have universal inputs that accept the signal types described below.
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
Thermistor 1
Precon type 2 (10 kOhm at 77°F). Input voltages should be from 0.489 Vdc to 3.825 Vdc for thermistors.
Dry contact A 5 Vdc wetting voltage detects contact position, resulting in a 1 mA maximum sense
current when the contacts are closed.
0–5 Vdc 0–10 Vdc
0–20 mA The input resistance on the positive (+) terminal is 250 Ohms. The
The output impedance of a 0–5 Vdc or a 0–10 Vdc source must not exceed 200 Ohms. The input impedance of the MPC Open XP is approximately 20 kOhm.
connector is capable of supplying 24 Vdc to multiple 4–20 mA transducers, but the total current demanded must not exceed 200 mA. If the voltage measured from the
RTD 1
connector to
Platinum - 1 kOhm at 32°F (0°C)
is less than 18 Vdc, you need to use an external power supply.
Nickel/Iron - 1 kOhm at 70°F (21°C) Balco TS8000 - 1 kOhm at 70°F (21°C) Input voltages should be from 0.6–1.2 V
For improved accuracy, Carrier recommends using an external current transducer-
type RTD, when RTD's are required with the MPC Open XP. Be aware that milliamp-type
Pulse counter 2
sensors require different jumper settings and different wiring arrangements.
Pulse counting up to 40 pulses per second. Minimum pulse width (on or off time) required for each pulse is 12.5 msec.
1
To use a thermistor or RTD not listed above, you can set up a custom translation table for your sensor.
2
The MPC Open XP can perform pulse counting for dry contact or voltage inputs if you assign the input to a Pulse
to Analog Input microblock.
If you have one or more RTD's connected to the inputs, the total current draw of all Thermistor, RTD, and Dry contact devices wired to the inputs should not exceed 10 mA. Exceeding this limit affects the accuracy of the RTD's. Use the following approximations as a reference:
10 kOhm Thermistor draws approximately 0.334 mA.
1 kOhm RTD draws approximately 0.834 mA.
Dry contact draws approximately 1 mA.
For example, if using an expander with 12 RTD's connected to the inputs, the remaining 4 inputs cannot be used. This assumes negligible wiring impedance (<10 Ohms) for each RTD input, with up to 100 feet of 22 AWG cable.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 14
Installing the MPC Open XP

Input wiring specifications

Input Maximum length
Minimum gauge
Shielding

Outputs

WARNING
If output controls a...
Resistance to ground must be...
NOTES
Aux Power Out
0–5 Vdc 0–10 Vdc
0–20 mA 1000 feet
Thermistor Dry contact Pulse counter TLO
RTD 100 feet
ZS sensors
Wireless Adapter for Wireless sensors
Equipment Touch
TruVu™ ET Display
500 feet (152 meters)
(305 meters)
500 feet (152 meters)
22 AWG
22 AWG
22 AWG 100 feet Unshielded
100 feet Unshielded
100 - 500 feet Shielded
100 feet Unshielded
100 - 1000 feet Shielded
100 - 500 feet Shielded
22 AWG Shielded
(30 meters)
See Wiring devices to the MPC Open XP's Rnet port (page 19).
The MPC Open XP and expanders have universal outputs that you can use as binary outputs or analog outputs. The outputs support:
driving external 24 Vdc relays
0-10 Vdc devices
0-20 mA devices
this product line. Do NOT apply 24 Vac to these universal outputs.
0–10 Vdc device 500 Ohms minimum
0–20 mA device 800 Ohms maximum
The device must share the same ground as the controller.
The total output current from all outputs and the
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 15
Binary outputs are powered, 24 Vdc channels. Dry contact binary outputs are not supported in
connection must not exceed:
500 mA at 115°F 300 mA at 140°F
For temperatures above 115°F, use the following equation to calculate the total current at 8 mA per degree:
Installing the MPC Open XP

Output wiring specifications

NOTE

To wire inputs and outputs

WARNING
off
500mA - ((max. expected temp. - 115°F) * 8mA/F)
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
The following applies to the inputs and outputs on the MPC Open XP and expanders.
1 Verify that the MPC Open XP's power and communications connections work properly.
2 Turn
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
the MPC Open XP's power.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 16
Installing the MPC Open XP
NOTES
GND
+
Aux Power Out
3 Connect the input wiring to the screw terminals on the controller or expander. See figure below.
Connect the shield wire to the
For a loop-powered 4-20 mA sensor, wire the sensor's positive terminal to the
Open XP's
terminal with the ground wire.
terminal on the MPC
connector. Wire the sensor's negative terminal to an input's + terminal.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 17
Installing the MPC Open XP
Universal Input Mode Select
Gnd
WARNING!
4 Set each input's
jumper to indicate the type of input.
5 Connect digital and analog output wiring to the UO screw terminals on the MPC Open XP and to the controlled
device. Connect the ground wire to the UO's
Binary outputs are powered, 24 Vdc channels. Dry contact binary outputs are not
terminal.
supported in the MPC Open XP product line. Do NOT apply 24 Vac to these universal outputs.
6 Set each output's jumper to the type of device wired to the output.
7 For each digital output, turn the output's potentiometer clockwise until it stops (maximum output).
8 Turn on the MPC Open XP's power.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 18
Installing the MPC Open XP

To use the Auto-Off-On switches

Auto-Off-On
Set the switch to...
To...
On
Off Auto
Auto-Off-On
Auto-Off-On
WARNING!
Auto-Off-On

Wiring devices to the MPC Open XP's Rnet port

NOTES
You can control an output using the
switch.
Turn on the output.
Turn off the output.
Let the control program control the output.
The potentiometer, located between the output level of an analog output. Place the
switch and the jumper, allows you to manually control the
switch in the On position, then turn the potentiometer
counterclockwise to reduce the output, or clockwise to increase the output.
The output potentiometer is NOT used for binary output channels. For a binary output, turn the potentiometer clockwise until it stops (maximum output) and leave it in this position. Failure to do so may result in relay-chattering or failure of the relay to energize when the
switch is in the On position.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 19
The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain or hybrid configuration.
Supports up to
15 wireless and/or ZS sensors (5 per control program)
One Equipment Touch
One TruVu™ ET Display
ZS sensors, a Wireless Adapter, and an Equipment Touch can share the Rnet, but not SPT sensors.
The Wireless Adapter, Equipment Touch, or TruVu™ ET Display must be powered by an external power source.
Installing the MPC Open XP

Rnet wiring specifications

NOTE

To wire ZS sensors to the controller

NOTES
Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor 22 AWG (7x0096) bare copper if Rnet has only sensors
Maximum length 500 feet (152 meters)
Insulation Low-smoke PVC (or equivalent)
Color Code Black, white, green, red
Shielding If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated
at controller
UL temperature rating 32–167°F (0–75°C)
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO2, or VOC. ZS Sensors are wired to the Rnet port on i-Vu® Open controllers. You can use the following ZS sensors:
ZS Standard
ZS Plus
ZS Pro
ZS Pro-F
The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc, unless it is the only device on
the Rnet port.
A control program can use no more than 5 ZS Sensors
SPT sensors cannot share the Rnet with other devices.
For detailed instructions, see the ZS Sensor Installation Guide.
1 Remove power from the MPC Open XP.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 20
Installing the MPC Open XP
Outer Jac
ket
Inner insulation
.25 in. (.6 cm)
NOTE
Connect this wire...
To this terminal...

To wire the Wireless Adapter for wireless sensors

WARNING
REQUIREMENTS
2 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
3 Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
Carrier recommends that you use the following Rnet wiring scheme:
Red
Black
White
Green
+12V
Rnet-
Rnet+
Gnd
4 Apply power to the MPC Open XP.
The Carrier wireless sensors are available in 868, 902, and 928 MHz radio frequency. The sensors are thermistor­based temperature sensors that may optionally sense humidity.
Wireless sensors communicate through a Wireless Adapter, which is wired to the Rnet port of the controller.
A v6.5 or later i-Vu® system
Do not apply line voltage (mains voltage) to the Wireless Adapter.
v6-xx-xxx or later controller drivers
To configure the control program for the desired user interaction with the sensor, see the Wireless Sensors Application Guide. For detailed instructions, see the Wireless Sensors Installation Guide.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 21
Installing the MPC Open XP
NOTES
Inner insulation
Outer jacket
Foil shield
.25 in. (.6 cm)
Shield wire
Rnet +, Rnet -
Gnd
Rnet
NOTES
Gnd
Enhanced Access
Off
To wire, power, and mount the Wireless Adapter
The Wireless Adapter requires a 24 Vac power supply. It is not powered by the Rnet.
If the Wireless Adapter will be:
Daisy-chained on the Rnet with ZS sensors, an Equipment Touch, or TruVu™ ET Displayuse the standard
4-conductor Rnet wiring.
The only device on the Rnet, you can use a 3-conductor cable instead of the standard 4-conductor Rnet
cable.
1 Turn off the power to the controller that the Wireless Adapter will be wired to.
2 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
3 Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
4 Wire the
, and
terminals on the controller's
port to the terminals of the same name on
the Wireless Adapter's Rnet connector.
If using shielded wire, connect the shield wire and the ground wire to the
Verify the
DIP Switch is set to
terminal.
.
5 Wire the 24 Vac external power supply to the Wireless Adapter's power connector.
6 Mount the Wireless Adapter by inserting 2 screws through the mounting tabs on each end of the Wireless
Adapter.
7 Apply power to the external power supply.
8 Verify that the LED on top of the Wireless Adapter is blinking. See "LED" below.
9 Turn on the controller's power.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 22
Installing the MPC Open XP
LED
If the LED is...
Then the device...
device.

To wire an Equipment Touch to the MPC Open XP

CAUTION
NOTES
CAUTION
The blue LED on the top of the Wireless Adapter indicates the following:
Off Is not powered or there is a problem.
Blinking Is working properly.
Steadily on Has a problem. Do one of the following:
Cycle power to the device.
Insert a small screwdriver or paper clip into the hole next to the LED to reboot the
by the equipment may be impaired.
The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
If the Equipment Touch will be:
Daisy-chained on the Rnet with ZS sensors or a Wireless Adapter, use the standard 4-conductor Rnet
The only device on the Rnet, you can use a 2-conductor cable instead of the standard 4-conductor Rnet
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
If the equipment is used in a manner not specified by the manufacturer, the protection provided
wiring and follow the wiring instructions To wire ZS sensors to the MPC Open XP (page 20).
cable and follow the instructions below.
The MPC Open XP can share a power supply with the Carrier controller as long as:
The power supply is AC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
1 Turn off the MPC Open XP's power.
2 Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 23
Installing the MPC Open XP
Rnet+
Rnet-
NOTES
Gnd
Enhanced Access
Off

To wire the TruVu™ ET Display

WARNING
24V DC
CAUTION
NOTE
3 Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
4 Wire the MPC Open XP's
and
terminals to the terminals of the same name on the Equipment
Touch's connector.
If using shielded wire, connect the shield wire and the ground wire to the
Verify that the
DIP switch is set to
.
terminal.
5 Turn on the MPC Open XP's power.
6 Turn on the Equipment Touch.
Wiring power
Do not apply line voltage (main) - 24 Vdc power only.
Wire the TruVu™ ET Display
connector to the 24 Vdc power supply using 2-conductor 18 AWG wire.
Maximum distance 100 feet (30 meters).
The TruVu™ ET Display can share a power supply with the Carrier controller as long as:
The power supply is DC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
Purchase a power supply from a third-party manufacturer.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 24
Installing the MPC Open XP
RS485
Rnet
Gnd
Gnd, +
Rnet +, -
Rnet -
NOTE
Enhanced Access
Off

Installing the MPC Open XP into an i-Vu® Control System

NOTE
Reports
Wiring communication
1 Turn off the MPC Open XP's power.
2 Wire the TruVu™ ET Display's
using 2-conductor 22 AWG wire with a maximum distance of 500 feet (152 meters).
Verify the <ALCProduct>'s
connector to the <ALCProduct>'s
DIP switch is set to
port,
.
to
to
to
3 Turn on the MPC Open XP's power.
You must complete the following procedures to successfully install your MPC Open XP into an i-Vu® Control System. Use the Help in the referenced software for detailed descriptions of these procedures.
EquipmentBuilder or Snap
1 Use EquipmentBuilder or Snap to create control program(s) for your MPC Open XP.
2 If applicable, print the Sequence of Operation, which includes the points list.
You can create a points list under
your control program.
This Installation Guide
1 Prepare a wire list using the points list. Refer to Appendix A (page 34).
2 Use the wire list and the following installation procedures to install and wire I/O points to your MPC Open XP
and expanders, if applicable.
in the i-Vu® application or Field Assistant after installing
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 25
Installing the MPC Open XP
Devices
Manage
Upload
Display Name
Controller
NOTES
Reference Name
If the control program is...
Control Program
Control Program
Add New
Open
Continue
Add New
Views
Continue
File added successfully
Close
Close
Check Status
File Mismatch
Download All Content
Properties
I/O Points
Properties
Control Program
The i-Vu® or Field Assistant application
1 Upload the controller to the database by selecting the router in the navigation tree.
2 Select
3 Select the controller in the list on the page and click
4 If you are adding a new control program, click . A dialog window appears.
5 Enter a name for your control program in
6 Do one of the following:
>
tab.
.
and select your controller in the
drop-down
list.
If you already have the maximum number of control programs for a controller, it will not appear in the
list.
Optional: You can change the control program's
if needed.
In the
Not in the
drop-down list Select the control program.
drop-down list a. Click
.
b. Browse to select the control program.
c. Click
d. Click
.
.
e. Click Close.
7 To upload a graphic, click
8 Click
9 Click
again.
. When message appears
10 Right-click on the programmable controller in the controller list and select
status of the controller should say
11 Click the
button.
under
and browse to your .view file.
.
, click
.
from the list. The
12 Assign channel numbers to the physical points by selecting the controller in the navigation tree and going to
13 Configure the controller on the
page >
tab.
page >
tab.
14 Check out and commission the equipment.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 26
Local access to the MPC Open XP
Connect...
To the controller's...
For...
Field Assistant
Equipment Touch
CAUTION

Local access to the MPC Open XP

You can use the following items as a local user interface to an Open controller. These items let you access the controller information, read sensor values, and test the controller.
1
application
device
1
Requires a USB Link (Part #USB-L)
2
See the Equipment Touch Installation and Setup Guide for detailed instructions.
2
touchscreen
If multiple controllers share power but polarity was not maintained when they were wired, the
Local Access port Temporary user interface for start-up
Rnet port Temporary or permanent user interface
for start-up
difference between the controller's ground and the computer's AC power ground could damage the USB Link and the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB Link. Purchase a USB isolator online from a third-party manufacturer.
These are accessory items that do not come with the controller.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 27
Troubleshooting
NOTE

MPC Open XP LED's

Module Status
Error Code...
Indicates...
Possible solutions
DIP switches are set correctly

Troubleshooting

If you have problems mounting, wiring, or addressing the MPC Open XP or the expander, contact Carrier Control Systems Support.
To help you troubleshoot, obtain a Module Status (Modstat) from the controller and review the System Error
and Warning details.
The controller and noting the lights and flashes.
LED can display the following error codes. Verify the LED patterns by cycling power to the
0 The control program or
module driver has not been downloaded.
1 A control program error Obtain a Module Status Report (Modstat) and look for error messages. See
2 The controller's
memory is full
3 A setup error Verify:
Download memory to the MPC Open XP.
the i-Vu® application or Field Assistant Help for instructions on obtaining a Modstat.
If you cannot determine the error from the Modstat, contact Carrier Control Systems Support.
In the i-Vu® application, reduce the amount of trend data being stored in the controller.
The address has been set on the rotary switches. See Addressing the MPC Open XP (page 8).
The address is unique on the network
4 A system error Obtain a Module Status Report (Modstat) and look for error messages. See
the i-Vu® application or Field Assistant Help for instructions on obtaining a Modstat.
If you cannot determine the error from the Modstat, contact Carrier Control Systems Support.
7 Abnormal startup Obtain a Module Status Report (Modstat) and look for error messages. See
the i-Vu® application or Field Assistant Help for instructions on obtaining a Modstat.
If you cannot determine the error from the Modstat, contact Carrier Control Systems Support.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 28
Troubleshooting
Error Code...
Indicates...
Possible solutions
Replace the MPC Open XP.
If this LED is on...
Status is...
Power BACnet Tx
BACnet Port
BACnet Rx
BACnet Port
Archive Valid
Brownout
Battery low

Expander LED's

If this LED is on...
Status is...
Power
Rx Tx
UO#
Run
Error
Run
Error
If Run LED shows...
And Error LED shows...
Status is..
8 The controller is
formatting
The number 8 should display only during the short formatting period. If this number displays continuously or flashes intermittently with another number, try each of the following:
Turn the MPC Open XP's power off, then on.
Restore factory defaults. See Restore factory defaults (page 30).
Other LED's show the status of certain functions.
The MPC Open XP has power.
The MPC Open XP is transmitting data from
The MPC Open XP is receiving data from
The controller's memory backup is valid
Incoming power is low
The battery is low
The LED's show the status of certain functions.
The
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 29
The MPC Open XP has power.
The MPC Open XP is receiving data from the network segment
The MPC Open XP is transmitting data over the network segment
The binary output is active
Lights based on expander health. See table below
Lights based on expander health. See table below
and
LED's indicate expander and network status.
2 flashes per second Off Normal
Troubleshooting
If Run LED shows...
And Error LED shows...
Status is..

To restore factory defaults

CAUTION
Format
Format

To get the serial number

Core
Main) board hardware
Module Status
5 flashes per second 2 flashes per second Boot is running or driver is updating
5 flashes per second On Fatal error. Replace expander or return for repair.
all custom settings. It is recommended to restore the factory defaults only under the guidance of Carrier Control Systems Support.
To erase volatile memory data and restore factory default configuration settings:
1 Turn off the MPC Open XP's power switch.
2 Hold down the controller’s
3 Continue to hold down the
release the button.
4 Turn on the MPC Open XP's power switch.
This erases all archived information and user-configuration settings. You will have to reconfigure
Make sure the address switches are not set to 0, 0.
button while you turn its power on.
button until the controller displays 8 and then the chase pattern, then
If you need the MPC Open XP's serial number when troubleshooting, the number is on:
a sticker on the back of the main controller board
a Module Status report (Modstat) under
To obtain a modstat in the i-Vu® interface:
1 Select the MPC Open XP in the navigation tree.
2 Right-click and select
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 30
(or
.
Troubleshooting

To replace the MPC Open XP's battery

Battery low

To replace the fuse

Controller
Off On
Power
Retur n
24ac/26dc
Fuse
Expander
Fuses
The MPC Open XP's 10-year Lithium CR123A battery retains the following data for a maximum of 720 hours during power outages: time, control programs, editable properties, schedules, and trends. To conserve battery life, you can set the driver to turn off battery backup after a specified number of days and depend on the archive function to restore data when the power returns. A low battery is indicated by the replacement batteries from any retailer that sells a CR-123A battery.
1 Verify that the MPC Open XP's power is on.
2 Using a small flathead screwdriver, pry up each side of the black battery clip until it is free and you can
remove it.
3 Remove the battery from the expander, making note of the battery's polarity.
4 Insert the new battery into the expander, matching the polarity of the battery you removed.
5 Push the black clip back onto the battery until you hear both sides click in place.
6 Download the MPC Open XP.
LED or a low battery alarm in the i-Vu® application. You can purchase
If you turn on the MPC Open XP's power switch and the Power LED is not lit, use a multimeter to see if one of the 3 Amp Pico fuses that protects the incoming power is blown.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 31
Troubleshooting
MPC Open XP
Aux Power Out
off
1 inch
inch
2
1
/
You can order replacement 3 Amp Pico fuses from a local or online retailer.
Before replacing the fuse, try to determine why the fuse blew.
Check the Power wiring polarity of the MPC Open XP, any attached expanders, and any other controllers that share the power supply. Use the same polarity for all of them.
Verify that outputs are wired to the appropriate types of devices. See Outputs (page 15). For example, you cannot wire a 24 Vac device to an output.
outputs (page
- If the
16).
port is used, verify that it is wired correctly. See To wire inputs and
To replace the fuse:
1 Turn
the MPC Open XP's power.
2 If the fuse is on an expander, remove the coverplate.
3 Using needle-nose pliers, pull the bad fuse from the MPC Open XP.
4 Cut the wires on the new fuse so that the total length is approximately 1 inch and the fuse is centered.
5 Bend the wire ends so that the length is approximately 1/2 inch.
6 Use the pliers to grip one wire end of the fuse and push into a fuse socket on the MPC Open XP.
7 Grip the other wire end of the fuse and push into the other fuse socket.
8 If working on an expander, replace the coverplate.
9 Turn on the power and verify that the Power LED is lit.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 32
Compliance

FCC Compliance

CAUTION

CE Compliance

WARNING

BACnet Compliance

Compliance

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
void the user’s authority to operate the equipment.
Changes or modifications not expressly approved by the responsible party for compliance could
This is a Class A product. In a domestic environment, this product may cause radio interference
in which case the user may be required to take adequate measures.
Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet International. BTL
®
is a registered trademark of BACnet International.
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 33
Appendix A: MPC Open XP wire lists
CAUTION

Appendix A: MPC Open XP wire lists

Important notes about AHU application I/O points
The MPC Open XP accepts any of the following:
UC applications in the UC equipment sal library
Any application from the CV AHU or VAV AHU library
User-created Snap programs
of the 39m AHU applications in the 39m sal library are used, the I/O channels are pre-assigned for the UC Open XP, UC Open, or AppController. These channel assignments are NOT correct in the MPC Open XP.
When using 39m AHU applications in the MPC Open XP or expanders, you must reassign the correct hardware channel numbers in the i-Vu® application or Field Assistant. See To install the <ALCProduct01 into an i-Vu® Control System (page 25). When installing the MPC Open XP with any of the 39m AHU applications, do not connect any I/O channel wiring until you have set the I/O channel numbers specifically for the application.
These cautions pertain ONLY to using 39m AHU applications in the MPC Open XP. UC library applications and Snap applications come with the channel numbers set to 0:0 and you set them to match the application. No special steps are required.
We do NOT recommend using the 39m library applications in the MPC Open XP controller. If any
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 34
Appendix A: MPC Open XP wire lists

MPC Open XP wire list

Open System Network
Project Name: Location:
Controller: Network Number: MAC Address:
Aux
1 24 Vdc
2 24 Vdc
Point/
Cable#
Universal
Inputs
(+)
(G) Input
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1
1 2 0-20 mA
Left
UI-1
1 2 Thermistor
Middle
1 2 0-10 V
Right 2 3 4 0-20 mA
Left
UI-2
3 4 Thermistor
Middle
3 4 0-10 V
Right
3
5 6 0-20 mA
Left
UI-3
5 6 Thermistor
Middle
5 6 0-10 V
Right 4 7 8 0-20 mA
Left
UI-4
7 8 Thermistor
Middle
7 8 0-10 V
Right
5
9
11
0-20 mA
Left
UI-5
9
11
0-10 V
Right
6
10
11
0-20 mA
Left
UI-6
10
11
Thermistor
Middle
10
11
0-10 V
Right 7 12
14
0-20 mA
Left
UI-7
12
14
Thermistor
Middle
12
14
0-10 V
Right
MPC Open XP Multi-purpose Controller
Power
Out
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
9 11 Thermistor
Dry contact
RTD
Middle
Dry contact
RTD
Dry contact
RTD
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 35
Appendix A: MPC Open XP wire lists
8
13
14
0-20 mA
Left
UI-8
13
14
Thermistor
Middle
9
15
17
0-20 mA
Left
UI-9
15
17
Thermistor
Middle
15
17
0-10 V
Right
10
16
17
0-20 mA
Left
UI-10
16
17
Thermistor
Middle
16
17
0-10 V
Right
11
18
20
0-20 mA
Left
UI-11
18
20
Thermistor
Middle
18
20
0-10 V
Right
12
19
20
0-20 mA
Left
UI-12
19
20
0-10 V
Right
Point/
Cable#
Universal
Outs
(+)
(G) Output
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1 1 2
0-20 mA
Left
UO-1
0-10 Vdc
Middle
Relay
Right
2 3 4
0-20 mA
Left
UO-2
0-10 Vdc
Middle
3
5 6
0-20 mA
Left
UO-3
0-10 Vdc
Middle
Relay
Right
4
7 8
0-20 mA
Left
UO-4
0-10 Vdc
Middle
Relay
Right
5
1 2
0-20 mA
Left
UO-5
0-10 Vdc
Middle
Relay
Right
6 3 4
0-20 mA
Left
UO-6
Relay
Right
Dry contact
RTD
13 14 0-10 V Right
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
19 20 Thermistor
Dry contact
RTD
Middle
Relay Right
0-10 Vdc Middle
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 36
Appendix A: MPC Open XP wire lists
7 5 6
0-20 mA
Left
UO-7
0-10 Vdc
Middle
Relay
Right
8 7 8
0-20 mA
Left
UO-8
Relay
Right

MPC Open XPIO48 wire list

System network
Project Name: Location:
Controller: Network Number: MAC Address:
Aux
1 24 Vdc
2 24 Vdc
Point/
Cable#
Universal
Inputs
(+)
(G) Input
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1
1 2 0-20 mA
Left
UI-1
1 2 Thermistor
Middle
1 2 0-10 V
Right 2 3 4 0-20 mA
Left
UI-2
3 4 Thermistor
Middle
3 4 0-10 V
Right
3
5 6 0-20 mA
Left
UI-3
5 6 Thermistor
Middle
5 6 0-10 V
Right
7 8 0-20 mA
Left
UI-4
7 8 Thermistor
Middle
0-10 Vdc Middle
MPC Open XPIO48 expander
Power
Out
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
+4
Dry contact
RTD
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 37
Appendix A: MPC Open XP wire lists
7 8 0-10 V
Right
5
1 2 0-20 mA
Left
UI-5
1 2 Thermistor
Middle
6
3 4 0-20 mA
Left
UI-6
3 4 Thermistor
Middle
3 4 0-10 V
Right 7 5 6 0-20 mA
Left
UI-7
5 6 Thermistor
Middle
5 6 0-10 V
Right 8 7 8 0-20 mA
Left
UI-8
7 8 Thermistor
Middle
7 8 0-10 V
Right
Point/
Cable#
Universal
Outs
(+)
(G) Output
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1
1 2
0-20 mA
Left
UO-1
0-10 Vdc
Middle
Relay
Right
2 3 4
0-20 mA
Left
UO-2
0-10 Vdc
Middle
Relay
Right
3
5 6
0-20 mA
Left
UO-3
0-10 Vdc
Middle
Relay
Right
4
7 8
0-20 mA
Left
UO-4
0-10 Vdc
Middle
Dry contact
RTD
1 2 0-10 V Right
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
Relay Right
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 38
Appendix A: MPC Open XP wire lists

MPC Open XPIO816 wire list

System network
Project Name: Location:
Controller: Network Number: MAC Address:
Aux
1 24 Vdc
2 24 Vdc
Point/
Cable#
Universal
Inputs
(+)
(G) Input
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1
1 2 0-20 mA
Left
UI-1
1 2 Thermistor
Middle
1 2 0-10 V
Right
3 4 Thermistor
Middle
3 4 0-10 V
Right
3
5 6 0-20 mA
Left
UI-3
5 6 Thermistor
Middle
5 6 0-10 V
Right 4 7 8 0-20 mA
Left
UI-4
7 8 Thermistor
Middle
5
1 2 0-20 mA
Left
UI-5
1 2 Thermistor
Middle
1 2 0-10 V
Right
6
3 4 0-20 mA
Left
UI-6
3 4 Thermistor
Middle
3 4 0-10 V
Right
7
5 6 0-20 mA
Left
UI-7
5 6 Thermistor
Middle
MPC Open XPIO816 expander
Power
Out
2 3 4 0-20 mA Left UI-2
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
7 8 0-10 V Right
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 39
Appendix A: MPC Open XP wire lists
5 6 0-10 V
Right
8
7 8 0-20 mA
Left
UI-8
7 8 Thermistor
Middle
9
1 2 0-20 mA
Left
UI-9
1 2 Thermistor
Middle
1 2 0-10 V
Right
10
3 4 0-20 mA
Left
UI-10
3 4 Thermistor
Middle
11
5 6 0-20 mA
Left
UI-11
5 6 Thermistor
Middle
5 6 0-10 V
Right
12
7 8 0-20 mA
Left
UI-12
7 8 Thermistor
Middle
7 8 0-10 V
Right
1 2 Thermistor
Middle
1 2 0-10 V
Right
14
3 4 0-20 mA
Left
UI-14
3 4 Thermistor
Middle
3 4 0-10 V
Right
15
5 6 0-20 mA
Left
UI-15
5 6 Thermistor
Middle
5 6 0-10 V
Right
16
7 8 0-20 mA
Left
UI-16
7 8 0-10 V
Right
Point/
Cable#
Universal
Outs
(+)
(G) Output
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1 1 2
0-20 mA
Left
UO-1
0-10 Vdc
Middle
Dry contact
RTD
7 8 0-10 V Right
Dry contact
RTD
Dry contact
RTD
3 4 0-10 V Right
Dry contact
RTD
Dry contact
RTD
13 1 2 0-20 mA Left UI-13
Dry contact
RTD
Dry contact
RTD
Dry contact
RTD
7 8 Thermistor
Dry contact
RTD
Middle
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 40
Appendix A: MPC Open XP wire lists
Relay
Right
2 3 4
0-20 mA
Left
UO-2
0-10 Vdc
Middle
Relay
Right
3
5 6
0-20 mA
Left
UO-3
Relay
Right
4
7 8
0-20 mA
Left
UO-4
0-10 Vdc
Middle
Relay
Right
5
1 2
0-20 mA
Left
UO-5
0-10 Vdc
Middle
Relay
Right
6 3 4
0-20 mA
Left
UO-6
0-10 Vdc
Middle
Relay
Right
7 5 6
0-20 mA
Left
UO-7
0-10 Vdc
Middle
Relay
Right
8 7 8
0-20 mA
Left
UO-8
0-10 Vdc
Middle
Relay
Right
0-10 Vdc Middle
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 41
Document revision history
Date
Topic
Change description
Code*
1/24/19
Wiring devices to the MPC Open XP's
Removed star configuration from the first paragraph.
X-TS-TS-O Specifications
Added surge CAUTION to Protection specification.
X-TS-AK-E-CC
10/29/18
Outputs
Added /F to end of formula.
X-CC-E
Specifications - MPC Open XPIO48 and
Reworded Protection specification and added first paragraph.
X-H-JS-O
Specifications - MPC Open XP
Reworded Rnet port specification and added power supplied by
X-H-JS-O
Wiring inputs and outputs > Input
Removed SPT sensor from Input wiring table, added TruVu™ ET
C-D Wiring devices to the MPC Open XP's Rnet port
Combined overview and wiring on the zone sensors and touchscreen devices. Added TruVu™ ET Display.
C-D
6/20/17
Appendix A: MPC Open XP wire lists
Caution added to not use 39m library applications with the MPC
C-TS-CP-E-WB 2/23/17
Changed sensor and adapter name from WS to wireless.
C-D
1/18/17
Wireless sensor overview
New topics
C-D Wiring devices to the MPC Open XP's
Updated format and added Wireless Adapter for Wireless sensors
C-D
Input wiring specifications
Added Wireless Adapter for Wireless sensors
C-D To wire the controller to the network
Added BACnet ARC156 connection information.
C-D
Wiring for communications
Changed from Wiring the MPC Open XP to the MS/TP network
C-D
Specifications
Added BACnet ARC156 and updated Rnet port information to
C-D
Cover
Changed MPC Open XP to new silkscreen
C-D 2/19/16
Local access to the MPC Open XP
Added USB Link wiring caution.
C-TS-RD-E-JH
2/9/16
To attach the MPC Open XPIO expander
Added step explaining jumper settings for connecting more than
X-TS-RD-E-BR 12/3/15
Replacing the battery
Corrected instructions from the wrong battery to the correct one.
X-D
11/18/14
MPC Open XPIO48 and MPC Open
Power rating corrected from 45VA to 40VA, as listed on the
C-D-LJ-O-BR

Document revision history

Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not listed.
Rnet port
MPC Open XPIO816
Rnet port. Reworded Protection specification and added first paragraph.
wiring specifications
To install the Wireless Adapter for Wireless sensors
Rnet port
What are the MPC Open XP and MPC Open XP expanders?
XPIO816
Display, and referred user to the device's Installation and Start-up Guide.
Open XP.
include Wireless Adapter.
one expander.
silkscreen
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 42
Document revision history
Date
Topic
Change description
Code*
8/14/14
MPC Open XP specifications
Maximum number of BACnet third-party integration points using
C-D-LJ-O
Wiring devices to the Rnet port
Changed from "Wiring a communicating zone sensor to the MPC
Connecting an SPT sensor
Removed BACview and added Equipment Touch
To wire an Equipment Touch to the
New topic
BACview devices
Removed references and topics Local Access to the MPC Open XP
Removed BACview and added Equipment Touch
To wire the Equipment Touch to the
Added Caution to maintain polarity and use the power supply only
C-TS-RD-E Restore factory defaults
Corrected from using a jumper to holding the Format button
C-D-LJ
Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not listed.
MPC Open XP
MPC Open XP
* For internal use only
Snap - changed to unlimited, depending on memory Power - removed references to BACview Rnet port - added Equipment Touch and removed BACview
Rnet port - added note that number of possible ZS sensors you can have with an Equipment Touch is 15
Local Access port - removed BACview, added Equipment Touch Battery - added Equipment Touch and removed BACview
Open XP" Removed references to BACview
for Carrier controllers
MPC Open XP MPC Open XPIO48/816 CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 43
CARRIER CORPORATION ©2019
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-431-01 · 1/24/2019
Loading...