Carrier MDB121NO170F, MDB121TO170F, BDB121NO170F, BDB121TO170F, MDB123TO170F Use And Maintenance

...
USE AND MAINTENANCE
BEDIENUNGSANLEITUNG
INSTRUCTIONS D’USAGE ET ENTRETIEN
USO E MANUTENZIONE
DB-O
DB-O
2
a = Condensing Unit • Verflüssigungssatz • Unité de Condensation • Unità Condensante
b = Cooler • Verdampfer • Evaporateur • Unità Evaporante
Pipe connections
Rohranschlüsse
Raccordements
Raccordi
Code Cooling capacity Nominal horsepower Voltage
Running Nominal absor. Max. Absor. Refrigerant Air Flow Air throw Net Weight Suction line Liquid line
Code Kälteleistung Nennleistung Spannung
Nennaufnahme bei Betrieb
Nennaufnahme max.
Kältemittel Luftmenge Luftwurf Poids Net Saugleitung Flüssigkeit
Code Puissance frig Puissance nominale Tension
Absorp. nomin. en marche Absorp. max
Réfrigérant Débit d’air Projection d’air Nettogewicht Aspiration Liquide
Codice Potenza Frigorifera Potenza nominale Tensione
Assorb. nom. in marcia Assorb. mass. Refrigerante Portata d’aria Freccia d’aria Peso Netto Aspirazione Liquido
Ta/Tc (°C) Watt HP Kw Volt/Ph/Hz Kw A A m
3
/h m Kg
ø mm ø mm
ab
MDB121NO170F
+30 / 0 1096 1/2 0,4 230/1~/50 0,6 3,8 5,4 R404A 600 4 39 13 12 6
MDB121TO170F
+30 / 0 1162 5/8 0,5 230/1~/50 0,7 4,3 7,9 R404A 600 4 43 13 12 6
BDB121NO170F
+30 / -20 761 1 0,7 230/1~/50 0,8 4,8 7,6 R404A 600 4 43 13 12 6
BDB121TO170F
+30 / -20 965 1,2 0,9 230/1~/50 0,8 5,0 7,5 R404A 600 4 46 13 12 6
MDB123TO170F
+30 / 0 1332 3/4 0,6 230/1~/50 0,8 5,0 8,4 R404A 600 4 43 13 12 6
BDB123TO170F
+30 / -20 1096 1,7 1,3 230/1~/50 0,9 5,5 11,3 R404A 600 4 50 13 12 6
MDB221TO170F
+30 / 0 2243 1,2 0,9 400/3N~/50 1,5 4,3 5,9 R404A 1200 4 61 19 16 10
BDB221NO170F
+30 / -20 1507 1,7 1,3 230/1~/50 1 6,9 11,9 R404A 1200 4 61 19 16 10
BDB221TO170F
+30 / -20 1773 2 1,5 400/3N~/50 2,2 5,7 11,9 R404A 1200 4 69 19 16 10
MDB135NO170F
+30 / 0 3516 1,5 1,1 400/3N~/50 1,8 5,3 7,0 R404A 1800 9 62 28 16 10
MDB135TO170F
+30 / 0 4019 2 1,5 400/3N~/50 2,3 6,2 7,8 R404A 1800 9 70 28 16 10
BDB135NO170F
+30 / -20 2295 2 1,5 400/3N~/50 2,4 6,3 12,5 R404A 1800 9 72 28 16 10
BDB135TO170F
+30 / -20 2613 3 2,2 400/3N~/50 1,9 5,5 7,5 R404A 1800 9 78 28 16 10
- Maximum Outside temperature - Maximale Umgebungstemperatur - Temperature éxtérieure maximaIe- Limiti temperatura esterna : 45°C
DADATTAASHEET • DA
SHEET • DA
TENBLA
TENBLA
TT • FICHE TECHNIQUE • SCHEDA
TT • FICHE TECHNIQUE • SCHEDA
TECNICA
TECNICA
3
SERVICE SHEET - SERVICEBLATT - FICHE DE SERVICE - FOGLIO SERVIZIO
DATE - DATUM OPERATION -MASSNAHME SERVICE FIRM - SERVICEFIRMA
SIGNATURE- UNTERSCHRIFT
DATE - DATA OPERATION - OPERAZIONE ETS DE SERVICE - DITTA ASSISTENZA SIGNATURE - FIRMA
T
hank you for choosing our refrigerating unit. This model is equipped with a highly evolved electronic control panel that dispenses with a series
of conventional components such as timers, thermostats and thermometers while offering the facility for straightforward personalisation of the control program to suit your needs. The panel also provides a self-diagnostic function showing the nature of any functional anomalies so that they can be solved fast. This operation and programming manual has been published to assist you, please read it carefully.
1) OPERATION
The distinguishing feature of this unit is that it is formed of two separate parts: the condensing unit with remote electronic control panel, for instal-
lation outside the coldroom , and the evaporator for installation inside the room. This design solution eliminates problems related to space restrictions outside the cell. The two units can be installed at a distance from each other. The air is drawn through the evaporator by means of the motor driven fan and exhausted through the grids on the sides. In the evaporator, the air drawn in by the motor driven fan units is cooled by the heat exchanger and expelled from the front of the unit. The temperature is monitored by room sensor. Once the set-point is reached the refrigeration plant is stopped. Defrosting is automatic by means of electrical heaters in the evaporator; this cycle terminates in correspondence with the "defrost end" temperature set on the control unit and detected by a sensor. The defrost water is collected in a tray located beneath the evaporator from where it is drained to outside the rooml.
2) INSTALLATION
For correct installation, proceed thus:
1) Position the condenser unit on floor level outside the coldroom.
2) Secure the evaporator unit to the coldroom ceiling (pict. 1) as follows:
2A) Open the fan holder bottom ‘A’ by
loosing screws ‘B’ (pict. 2-3).
2B) Drill the fixing holes on the
coldroom ceiling observing the recommended distance from the wall (pict. 4).
2C) Secure the evaporator using the
supplied components (pict. 5):
1 - Threaded bar 2 - Washer 3 - Nut
2D) Hook up the evaporator to the electrical supply utilising the terminal board located inside
the junction box. Close the junction box and clamp the cable so that it is clear of the fan blades.
2E) Re-close the air-cooler cover and then make the refrigeration connections (pict. 6).
REMOTE CONTROL PANEL INSTALLATION
Unscrew the lateral fixings to remove the remote control panel cover plate (pict. 7).
Fix the base plate in the desired position using the pre-drilled
holes and making sure it is level (pict. 8).
Replace the cover plate by performing the operation indicated at
pict. 7 in reverse.
Adjust the cable connection between the control panel and the
unit, making sure it does not interfere with existing cable connections.
To assure optimal operation of the refrigerating unit:
A) Restrict the number of times the coldroom is opened. B) Make sure that the unit has an efficient air intake and expels a generous amount of turbulent air. C) Position the unit on horizontal planes.. D) Avoid to place the condensing unit in closed ambient or not ventilated.
4
pict. 3pict. 2
pict. 4 pict. 5
pict. 6
Condensing unit
Evaporator
pict. 1
pict. 7
pict. 8
E N G L
I S H
100-150
B
A
3
1
2
2
1
3) ELECTRICAL HOOK-UP
To make the correct electrical connections:
1) Make sure the line voltage corresponds to the voltage indicated on the dataplate of the unit (± 10%).
2) To reach the electronic panel it is necessary to remove the front cover (C) of the condensing unit (pict.1). For this operation remove the fixing screws and position the selector (A) on 0.
3) Unscrew the screws (B) indicated in pict. 2 and remove the cover from the electronic panel.
LINE CABLE FOR SINGLE PHASE UNITS (230 V)
- Remove the plug (D) (pict.2) and insert a cable gland PG16. Insert the power cable (of the section indicated in the table of fuses) in the cable gland and connect:
1) the phase wire to the terminal1 (L1) of the isolator Q1
2) the neutral wire to the terminal 5 (N)
3) the protection wire (earth) to the terminal PE
- Tighten the cable gland.
LINE CABLE FOR THREE-PHASE UNITS (400 V)
- Remove the plug (D) (pict.2) and insert a cable gland PG 16. Insert the power cable (of the section indicated in the table of fuses) in the cable gland and connect:
1) the phase wires to the terminals 1 (L1) - 3 (L2) - 5 (L3)
2) the neutral wire to the terminal 7 (N)
3) the protection wire (earth) to the terminal PE
- Tighten the cable gland.
CONNECTION CABLE DOOR HEATER
- Remove the plug (E) (pict. 2) and insert a cable gland PG 11. Insert the cable of the door heater and connect:
1) the phase wire to the terminal 40 of the electrionic control panel (G)
2) the neutral wire to the terminal N of the electronic control panel (G)
3) the protection wire (earth) to the earth terminal (60) GND
- Tighten the cable gland.
Remeber that the voltage in output to the card is 230 V 1Amp. MAX. It is necessary to protect the door heater with a fuse (by costumer).
MICRO-DOOR CONNECTION
- Remove the plug (F) (pict.2) and insert a cable gland PG 11.
- Insert the cable deriving from the micro-door and connect the bands to the terminals 19 and 20 of the electronic control panel (G) after remo­ving connection bridge .
The installation has to follow the sequence: closed door - micro-door contact closed opened door - micro-door contact opened
- Tighten the cable gland.
WARNING: do not give voltage to the micro-door as it is fed with voltage deriving from the electronic control panel (low voltage).
When the operations for the electronic panel connection have finished close with the screws B (pict.2). Close the front cover (C) of the conden-
sing unit (pict. 1).
4) PROCEDURES BEFORE STARTING
Before switching on the unit check that:
The fixing screws are properly tightened The electrical and refrigeration connections have been made correctly
If the unit has been opened check that:
No tools have been inadvertently left inside the enclosure The enclosure has been assembled correctly There are no gas leaks The panels have been fitted correctly.
5) PLACING INTO SERVICE
Perform all the above mentioned connections and then the unit can be started. A period of pre-heating is required; this is achieved by powering up the unit without switching on the control unit for at least 2 hours (3 hours in
cold climates). This procedure must be repeated whenever the plant is idle for periods in excess of 12 hours.
5
pict. 1
pict. 2
E N G L
I S H
G
C
B
A
F E D
Q1
PE
6) DESCRIPTION OF ELECTRONIC PANEL
1) Compressor LED (GREEN): LIT: the compressor is running.The unit is cooling. FLASHING: the compressor is a delayed start mode. OFF: the compressor is OFF. The required room temperature has been reached .
2) Evaporator fan LED (GREEN): LIT: Evaporator fan is running. FLASHING: the evaporator fan is in a delayed start mode. OFF: Evaporator fan is off.Unit in Defrost mode.
3) Defrost LED (YELLOW): LIT: automatic or manual defrost in progress.
4)Alarm LED (RED): LIT: Alarm mode: malfunctioning of a sensor, or intervention of pressure-stat or room temperature outside preset limits. OFF: Unit working normally.
5) DISPLAY: When the machine is not in operation, the label “OFF” and the cell temperature are inter mittently displayed one after the other on the digital display.When the machine is in operation, during the normal working cycle, the display indicates the cell temperature. Parameters being set will be displayed during programming. A "Fault Code" will be displayed during alarm mode.
6) “SET” KEY. Permits entry of room temperature requirements.
7) “DOWN” KEY. Key to decrease data values.
8) “MAN.DEFR./UP” KEY. Key to increase data values. Press for 8 seconds at least to initiate manual defrost as well.
9) Key “T.A.A.” Key to mute audible alarm. This alarm is not fitted as standard to the unit but can be added by the client. To connect use the free terminals 1 & 2 (volt free) on the internal electronic panel. Terminal 2 should have a live feed brought to it.
10) “ON/OFF” KEY.Main switch.
11) “LAMP” KEY.Push to turn room lamp ON/OFF.A red LED lights when lamp is ON.
7) PROGRAMMING
With the unit in normal operating mode,the only active keys are "ON/OFF" (10) and "LAMP"(11). The latter is always operative except when in
programming mode.
Cell temperature programming:
- Press key (10) to turn ON unit.The actual room temperature will be shown on the display (5).In this condition the unit is ready for program­ming.It is necessary therefore to set the required room temperature bearing in mind the limits of the range which the unit is able to operate.
- Press the SET (6) key (the yellow LED will light).The last set temperature will be displayed on the display screen (5) which showes the set value.
Press the set key (6): the yellow led will light for one second and the display (5) will start flashing a few seconds later, indicating the set tempera-
ture. If you wish to change the setting, use the following keys: (8) to raise set temperature (7) to lower set temperature
Once the required setting is displayed, press the set key (6) to confirm. The unit is now fully operational and no other programming is requi-
red. The refrigerating cycle is fully automatic according to factory-set parameters, that can eventually be modified by authorised personnel only.
8) ALARMS
When a fault is detected,the red Led in key (4) will be lit and a fault code displayed on the screen (5).This code enables a speedy identification
of the problem and should be reported when making the service call.(The audible alarm will also sound if fitted).
HIGH TEMPERATURE ALARM
The label (HI) and the cell temperature are intermittently displayed one after the other.
Alarm relay activated
Causes: - The door has been opened too frequently - The product load in the cell exceeds cell capacity - The temperature of the products stored in the cell is too high - Refrigeration system malfunction
LOW TEMPERATURE ALARM
The label (LO) and the cell temperature are intermittently displayed one after the other.
Alarm relay activated
Causes: -Electronic control unit malfunction. Solution: -Call technical assistance service
AMBIENT TEMPERATURE SENSOR ALARM
The label (EO) appears on the digital display.
Alarm relay is active
Causes: -The sensor is not connected. Solution: -Replace sensor
EVAPORATOR SENSOR ALARM
The label (E1) and the cell temperature are intermittently displayed one after the other.
6
Minimum Temp. Maximum Temp
M RANGE (Medium temperature) - 5 °C +10 °C
B RANGE (Low temperature) - 25 °C - 15 °C
E N G
L
I S H
4
5910
3
2
1
67811
Loading...
+ 14 hidden pages