Carrier 68G5-105 Series, MCI J4500 COACH Operation & Service Manual

Page 1
Carrier Transicold
Transport Air Conditioning
68G5-105 SERIES MCI J4500 COACH
T-312 Rev-
Operation &Service
Page 2
OPERATION AND SERVICE MANUAL
TRANSPORT
AIR CONDITIONING
EQUIPMENT
Model 68G5--105 Series
MCI J4500 Model Coach
Carrier Transport Refrigeration and Air Conditioning, A member of the United Technologies Corporation family. Stock symbol UTX. Carrier Transicold, Carrier Corporation, P.O. Box 4805, Syracuse, N.Y . 13221 U. S. A.
2003 CarrierCorporation D Printed in U. S. A. 0903
for
Page 3
SAFETY SUMMARY
GENERAL SAFETY NOTICES
The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the following three sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautions appearing elsewhere in the manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS
Always wear safety glasses. Keep hands, clothing and tools clear of the evaporator and condenser fans.
No work should be performed on the unit until all circuit breakers and start-stop switches are turned off, and power supply is disconnected.
Always work in pairs. Never work on the equipment alone. In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator and condenser fans. Do not open the condenser fan grille or evaporator access panels before turning the power off, and securing the power source.
Be sure power is turned off before working on motors, controllers, solenoid valves and electrical control switches. Tag circuit breaker and power supply to prevent accidental energizing of circuit.
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems with the system should be diagnosed, and any necessary repairs performed, by qualified service personnel.
When performing any arc welding on the unit, disconnect all wire harness connectors from the modules in the control box. Do not remove wire harness from the modules unless you are grounded to the unit frame with a static-safe wrist strap.
In case of electrical fire, open circuit switch and extinguish with CO
(never use water).
2
Safety - 1 T312
Page 4
SPECIFIC WARNINGS AND CAUTIONS
WARNING BE SURE TO OBSERVE WARNINGS LISTED IN THE SAFETY SUMMARY IN THE FRONT OF THIS MANUAL BEFORE PERFORMING MAINTENANCE ON THE HVAC SYSTEM
WARNING DO NOT USE A NITROGEN CYLINDER WITHOUT A PRESSURE REGULATOR
WARNING DO NOT USE OXYGEN IN OR NEAR A REFRIGERATION SYSTEM AS AN EXPLOSION MAY
OCCUR.
WARNING EXTREME CARE MUST BE TAKEN TO ENSURE THAT ALL THE REFRIGERANT HAS BEEN REMOVED FROM THE COMPRESSOR CRANKCASE OR THE RESULTANT PRESSURE WILL FORCIBLY DISCHARGE COMPRESSOR OIL.
WARNING WHEN MOVING THE COIL CARE MUST BE TAKEN TO AVOID PERSONAL INJURY BE­CAUSE OF THE WEIGHT OF THE COIL.
CAUTION Do not under any circumstances attempt to service the microprocessor. Should a problem develop with the microprocessor, replace it.
CAUTION Care Must Be Taken To Ensure That The Manifold Common Connection Remains Immersed In Oil At All Times Or Air And Moisture Will Be Drawn Into The System.
CAUTION To prevent trapping liquid refrigerant in the manifold gauge set be sure set is brought to
suction pressure before disconnecting.
T-312
Safety - 2
Page 5
TABLE OF CONTENTS
Section Page
SAFETY SUMMARY i........................................................................
DESCRIPTION 1-1..........................................................................
1.1 INTRODUCTION 1-1................................................................
1.2 GENERAL DESCRIPTION 1-2........................................................
1.2.1 Condenser Assembly 1-2.........................................................
1.2.2 Compressor Assembly 1-4........................................................
1.2.3 Evaporator Assemblies 1-4.......................................................
1.2.4 Main Control Box 1-7.............................................................
1.2.5 System Operating Controls And Components 1-8....................................
1.2.6 Other Carrier Supplied Items 1-9...................................................
1.3 REFRIGERATION SYSTEM COMPONENT SPECIFICATIONS 1-9........................
1.4 ELECTRICAL SPECIFICATIONS - WOUNDFIELD MOTORS 1-9.........................
1.5 ELECTRICAL SPECIFICATIONS-MAIN CONTROLLER INPUT SENSORS AND
TRANSDUCERS 1-9................................................................
1.6 SAFETY DEVICES 1-10.............................................................
1.7 HEATING (ENGINE COOLANT) FLOW CYCLE 1-11....................................
1.8 AIR CONDITIONING REFRIGERANT CYCLE 1-12......................................
1.9 ELECTRONIC AUTOMATIC CONTROL DATA FLOW 1-14...............................
OPERATION 2-1............................................................................
2.1 STARTING, STOPPING AND OPERA TING INSTRUCTIONS 2-1.........................
2.1.1 Operating Controls 2-1...........................................................
2.1.2 HVAC Power to Controller 2-2.....................................................
2.1.3 Starting 2-2.....................................................................
2.1.4 Activating Defrost 2-3............................................................
2.1.5 Setting RAM (Fresh) Air 2-3.......................................................
2.1.6 Active Alarm 2-3.................................................................
2.1.7 Diagnostics (Parameters) 2-3.....................................................
2.1.8 Stopping 2-3....................................................................
2.2 PRE-TRIP INSPECTION 2-3.........................................................
2.3 SYSTEM DESCRIPTION 2-3.........................................................
2.3.1 Pull Up and Pull Down Modes 2-3..................................................
2.3.2 Bypass Heat valve Control 2-5....................................................
2.3.3 Auxiliary Heater Control 2-5......................................................
2.3.4 Humidity Control 2-5.............................................................
2.3.5 Compressor Unloader Control 2-5..................................................
2.3.6 Passenger Area Evaporator Fan Speed Selection 2-5................................
2.3.7 Driver’s Area Evaporator Fan Speed Selection 2-5...................................
2.3.8 Condenser Fan Speed Control 2-5.................................................
2.3.9 Staging 2-6.....................................................................
2.3.10 Compressor Clutch Control 2-6....................................................
2.3.11 RAM Air Control 2-6.............................................................
2.3.12 Startup 2-6.....................................................................
2.3.13 Input Processing 2-6.............................................................
2.3.14 Self Tests 2-6...................................................................
i
T-312
Page 6
TABLE OF CONTENTS -- Continued
Section Page
2.3.15 Alarm Description 2-6............................................................
2.3.16 Hour Meters 2-6.................................................................
2.3.17 Communications (Driver Display - Controller) 2-6....................................
TROUBLESHOOTING 3-1....................................................................
3.3.1 System Will Not Cool 3-5.........................................................
3.3.2 System Runs But Has Insfficient Cooling 3-5........................................
3.3.3 Abnormal Pressures 3-5..........................................................
3.3.4 Abnormal Noises Or Vibrations 3-5.................................................
3.3.5 Control System Malfunction 3-6....................................................
3.3.6 No Evaporator Air Flow Or Restricted Air Flow 3-6...................................
3.3.7 Expansion Valve Malfunction 3-6...................................................
3.3.8 No Or Insufficient Heating 3-6.....................................................
SERVICE 4-1...............................................................................
4.1 MAINTENANCE SCHEDULE 4-1......................................................
4.2 SUCTION AND DISCHARGE SERVICE VAL VES 4-1....................................
4.3 INSTALLING MANIFOLD GAUGES 4-2................................................
4.3.1 Installing R-134a Manifold Guage Set 4-2...........................................
4.4 PUMPING THE SYSTEM DOWN OR REMOVING THE REFRIGERANT CHARGE 4-2......
4.4.1 System Pumpdown 4-2...........................................................
4.4.2 Removing the Refrigerant Charge 4-3..............................................
4.4.3 Refrigerant Removal From An Inoperative Compressor. 4-3...........................
4.4.4 Pump Down An Operable Compressor For Repair 4-3................................
4.5 REFRIGERANT LEAK CHECK 4-4....................................................
4.6 EVACUATION AND DEHYDRATION 4-4...............................................
4.6.1 General 4-4.....................................................................
4.6.2 Preparation 4-4..................................................................
4.6.3 Procedure for Evacuation and Dehydrating System 4-4...............................
4.7 ADDING REFRIGERANT TO SYSTEM 4-6.............................................
4.7.1 Checking Refrigerant Charge 4-6..................................................
4.7.2 Checking Refrigerant Charge (Alternate Method) 4-6.................................
4.7.3 Adding Full Charge 4-6...........................................................
4.7.4 Adding Partial Charge 4-6........................................................
4.8 CHECKING FOR NONCONDENSIBLES 4-6...........................................
4.9 CHECKING AND REPLACING HIGH PRESSURE CUTOUT SWITCH 4-7..................
4.9.1 Replacing High Pressure Switch 4-7................................................
4.9.2 Checking High Pressure Switch 4-7................................................
4.10 FILTER-DRIER 4-7..................................................................
4.10.1. To Check Filter Drier 4-7..........................................................
4.10.2. To Replace Filter Drier 4-7........................................................
4.11 THERMOSTATIC EXPANSION VALVE 4-7.............................................
4.11.1 Replacing the Expansion Valve 4-7.................................................
4.11.2 To Check/Measure Superheat 4-8..................................................
iiT-312
Page 7
TABLE OF CONTENTS -- Continued
Section Page
4.12 MODEL 05G COMPRESSOR MAINTENANCE 4-8......................................
4.12.1 Removing the Compressor 4-8....................................................
4.12.2 Re--installing the Compressor 4-9..................................................
4.12.3 Compressor Unloaders 4-9.......................................................
4.12.4 Compressor Oil Level 4-10........................................................
4.12.5 Adding Oil with Compressor in System 4-10.........................................
4.12.6 Adding Oil to Service Replacement Compressor 4-10.................................
4.12.7 Removing Oil from the Compressor: 4-10...........................................
4.13 TEMPERATURE SENSOR CHECKOUT 4-11...........................................
4.14 HUMIDITY SENSOR CHECKOUT 4-11................................................
4.15 SUCTION AND DISCHARGE PRESSURE TRANSDUCER CHECKOUT 4-11...............
4.16 REPLACING SENSORS AND TRANSDUCERS 4-12....................................
4.17 SERVICING MAIN EVAPORATOR BLOWER ASSEMBLY 4-12...........................
4.18 ACCESSING MAIN EVAPORATOR MOTOR BRUSHES 4-12.............................
4.19 SERVICING MOTOR BRUSHES 4-12.................................................
4.20 SERVICING THE MAIN EVAPORATOR AND HEATER COIL 4-13.........................
4.21 REMOVING THE CONDENSER ASSEMBLY 4-13......................................
4.22 SERVICING THE CONDENSER COIL 4-13............................................
4.23 SERVICING THE CONDENSER MOTOR 4-13..........................................
4.24 SERVICING THE DRIVER CONTROL BOX 4-13........................................
4.25 SERVICING THE DRIVER EVAPORATOR 4-14.........................................
4.25.1 Access Cover Removal 4-14......................................................
4.25.2 Blower Removal 4-14............................................................
4.25.3 Air filter Removal 4-14............................................................
4.25.4 Removal of Evaporator/Heater Coil Assembly 4-14...................................
4.25.5 RAM Air Actuator Removal 4-14...................................................
4.26 SERVICING THE PARCEL RACK EVAPORATOR 4-14..................................
4.26.1 Motor Removal 4-14.............................................................
4.26.2 Removal of Parcel Rack Evaporator Coil 4-14.......................................
ELECTRICAL SCHEMATIC DIAGRAMS 5-1....................................................
5.1 INTRODUCTION 5-1................................................................
LIST OF ILLUSTRATIONS
Figure Page
1-1. Coach Cutaway View 1-1.................................................................
1-2. Condenser Assembly 1-2.................................................................
1-3. Compressor Assembly 1-3................................................................
1-4. Driver Evaporator Assembly 1-5...........................................................
1-5. Parcel Rack Evaporator 1-5...............................................................
1-6. Main Evaporator Assembly 1-6............................................................
1-7. Main Control Box 1-7.....................................................................
1-8. System Operating Controls (upper left hand switch panel) 1-8.................................
1-9. Parcel Rack On/Off 1-8...................................................................
1-10. Driver A/C 1-9..........................................................................
1-11. Heating System Flow Diagram 1-11.......................................................
iii
T-312
Page 8
LIST OF ILLUSTRATIONS -- Continued
Figure Page
1-12 Air Conditioning Refrigerant Flow Diagram 1-13.............................................
1-13. Electronic Automatic Control Data Flow Block Diagram 1-14..................................
2-1. System Operating Controls (upper left hand switch panel) 2-1.................................
2-2. Parcel Rack On/Off 2-2...................................................................
2-3. Driver A/C 2-2...........................................................................
2-4. Main Controller Automatic Control Sequence 2-4............................................
4-1. Suction or Discharge Service Valve 4-1....................................................
4-2. Manifold Gauge Set (R--134a) 4-2.........................................................
4-3. Compressor Service Connections 4-3......................................................
4-4. Refrigerant Service Connections 4-5.......................................................
4-5. Checking High Pressure Switch 4-7........................................................
4-6. Thermostatic Expansion Valve 4-7.........................................................
4-7. Thermostatic Expansion Valve Bulb and Thermocouple Installation 4-8.........................
4-8. Removing Bypass Piston Plug 4-9.........................................................
4-9. Model O5G Compressor 4-9..............................................................
4-10.Removing Driver Control Box 4-13........................................................
5-1. Electrical Schematic Diagram Legend and Symbols 5-2......................................
5-2. Electrical Schematic Diagram 5-3.........................................................
5-3. Electrical Schematic Diagram 5-4.........................................................
5-4. Electrical Schematic Diagram 5-5.........................................................
LIST OF TABLES
Tab le Page
1-1. Part (Model) Number Chart 1-1............................................................
1-2. Additional Support Manuals 1-1............................................................
1-3. Safety Devices (Within Carrier Supplied Equipment) 1-10.....................................
2-1. Main Evaporator Fan Speed Relay Operation 2-5............................................
2-2. Main Area Staging 2-6....................................................................
3-1. Microprocessor Error Message Definition 3-1................................................
3-2. Display Error Message Definition 3-1.......................................................
3-3. Driver Display Panel Alarm Message Definition 3-1...........................................
3-4. Parameter Codes 3-4....................................................................
3-5. General System Troubleshooting Procedures 3-5............................................
4-1. Checking Refrigerant Charge 4-6..........................................................
4-2. Checking Refrigerant Charge 4-6..........................................................
4-3. T emperature Sensor(AT, TSC, TSD and TSR) Resistance 4-11................................
4-4. Humidity Sensor (HS) Voltage 4-11.........................................................
4-5. Suction and Discharge Pressure Transducer (SPT and DPT) Voltage 4-12.......................
4-6. R-134a Temperature - Pressure Chart 4-15..................................................
ivT-312
Page 9
SECTION 1
DESCRIPTION
1.1 INTRODUCTION
heater, a driver evaporator with integral heater, optional
parcel rack evaporators, compressor assembly, main This manual contains Operating and Service Instructions and Electrical Data for the Model 68G5-105
Coach Air Conditioning and Heating equipment furnished by Carrier Transicold Division for the MCI J-Series Intercity coach. Table 1-1 provides a model number chart.
The Model 68G5-105 equipment (see Figure 1-1) consist of a condenser, a main evaporator with integral
control box, driver display panel, check valve assembly,
temperature sensors and a bypass heat valve.
The 68G5 air conditioning and heating equipment
interfaces with electrical cabling, a parcel rack
evaporator thermostat kit, refrigerant piping, engine
coolant piping, ductwork and other components
furnished by the coach manufacturer to complete the
system.
Table 1-1. Part (Model) Number Chart
Model No. Refrigerant Controller Fan Motors Parcel Rack Connection
68G5-105
R-134a
Microprocessor 24VDC Yes
Table 1 -2. Additional Support Manuals
MANUAL/FORM NUMBER EQUIPMENT COVERED TYPE OF MANUAL
62--02756 O5G Compressor Operation and Service
T--200PL O5G Compressor Parts List T--279PL MCI E/J Coach Parts List
Driver Evaporator
Driver Display Panel
*Driver Evaporator
Control Box
Parcel Rack Evaporator
Main Control Box
Condenser
Roadside Return Air Temperature Sensor
*INDICATES COMPONENTS FURNISHED
BY THE COACH MANUFACTURER
*Bypass
Heat Val ve
Main Evaporator
Curbside Return Air Temperature and Humidity Sensor
Check Val ve
Compressor Assembly
Figure 1 -1. Coach Cutaway View
1-1
T-312
Page 10
1.2 GENERAL DESCRIPTION
1.2.1 Condenser Assembly
The condenser assembly (See Figure 1-2) includes a condenser coil, fan and motor assemblies, filter-drier, sight glass, control box, liquid line solenoid valve(s), king valves and an ambient temperature sensor.
The condenser coil provides a heat transfer surface for condensing refrigerant gas at a high temperature and pressure into a liquid at high temperature and pressure. The condenser fans circulate ambient air across the outside of the condenser tubes at a temperature lower than refrigerant circulating inside the tubes; this results in condensing the refrigerant into a liquid. The filter-drier removes moisture and other noncondensibles from the liquid refrigerant before it enters the thermal expansion valves in the evaporator assemblies.
The condenser is also fitted with a fusible plug which protects the system from unsafe high temperatures. The control box includes condenser fan relays no. 1 and no. 2 (CFR1 and CFR2) to enable the main controller to control operation of condenser fan motors no. 1 and no. 2 (CM1 and CM2). The control box also includes condenser speed relay no. 1 (CSR1) which controls the speed of both condenser fan motors CM1 and CM2. The main evaporator liquid line solenoid valve and the parcel rack liquid line solenoid valve (when so equipped) closes when the system is shut down to prevent refrigerant migration and to isolate the filter-drier for servicing when the compressor is shut down. The king valves enable servicing of the condenser assembly. The ambient temperature sensor measures ambient temperature and sends an electrical signal to the main controller.
16827
435
91011
14
19
20
1. Condenser Coil Assembly
2. Fusible Plug
3. Liquid Line Outlet Fitting (Parcel Rack)
4. Liquid Line Outlet Fitting (Main)
5. Model/Serial No. Nameplate
6. Fan Guard
7. Filter-Drier
8. Venturi Ring
9. Condenser Fan Motor CM1
10. Fan Blade 1 1. Condenser Fan Motor CM2
15161718 13
13 Control Box--Contains: Condenser Fan
Relay No.1 (CFR1), Condenser Fan Relay No. 2 (CFR2) and Condenser Speed Relay No. 1 (CSR1)
14. Moisture & Liquid Indicator
15. Control Box Positive (+) Stud
16. Control Box Positive (+) Stud
17. Control Box Negative (--) Stud 18 Liquid Line (King) Valve
19. Discharge Shutoff King Valve
20. Refrigerant Inlet Fitting
12. Outside Temperature Sensor
12
T-312
Figure 1 -2. Condenser Assembly
1-2
Page 11
87654321
4
9
24
23
2
4
ROADSIDE VIEW
22
DRIVE END VIEW
CURBSIDE VIEW
19
18 17 16 15 14 13
21
20
PUMP END VIEW
1
TOP VIEW
1. Suction Pressure Transducer 2 Bracket, Belt Guard
3. Weatherpack Clutch Coil Connector
4. Electric Solenoid Unloader
5. Discharge Valve Connection, Size 16 ORS
6. Discharge Service Valve
7. Discharge Valve Charging Port
8. O–Ring
9. Oil Drain Plug
10. Solenoid Unloader Electric Connectors
11. High Pressure Switch
12. Discharge Pressure Transducer
13. Capscrew
14. Lockwasher
15. Special Washer
16. Lock Nut
17. Key
18. Suction Valve Charging Port
19. Suction Service Valve
20. Clutch Assembly
21. Oil Fill Plug
22. Oil Level Sightglass
23. Suction Valve Connection, Size 24 ORS
24. O–Ring
10
11
12
Figure 1-3. Compressor Assembly
1-3
T-312
Page 12
1.2.2 Compressor Assembly
The compressor assembly (See Figure 1-3.) includes the refrigerant compressor, clutch assembly, suction and discharge service valves, high pressure switch, suction and discharge pressure transducers, suction and discharge servicing (charging) ports and electric solenoid unloaders.
The compressor raises the pressure and temperature of the refrigerant gas and forces it into the condenser tubes. The clutch assembly provides a means of belt driving the compressor by the coach engine. The suction and discharge service valves enable servicing of the compressor. Suction and discharge access (charging) ports mounted on the service valves enable connection of charging hoses for servicing of the compressor, as well as other parts of the refrigerant circuit. Transducers convert refrigerant pressures into electrical signal inputs which are sent to the main controller. The high pressure switch (HPS) is a normally closed switch, its contacts open on a pressure rise to shut down the system when abnormally high refrigerant pressures occur. The electric unloaders provide a means of controlling compressor capacity , which enables control of temperature inside the coach. For more detailed information on the compressor, refer to manual number 62-02756.
1.2.3 Evaporator Assemblies
The evaporator assemblies include a driver evaporator assembly (See Figure 1-4), a main evaporator assembly (See Figure 1-6), and may include two parcel rack evaporator assemblies (See Figure 1-5).
The driver evaporator assembly includes an evaporator coil assembly, a thermal expansion valve, a heater coil assembly, an evaporator heat valve (EHV), two fan and
motor assemblies, an air filter, and two condensate drain connections. The evaporator heat valve (EHV) for the driver evaporator is installed in the piping outside the evaporator assembly. In addition, the driver evaporator has an actuator, which controls the outside (RAM) air damper upon receipt of signal from the main controller.
The main evaporator assembly includes an evaporator and heater coil assembly, a thermal expansion valve, an evaporator heat valve (EHV), a fan and motor assembly, an air filter, and two condensate drain connections. There is also an evaporator speed fan relay (EFRL), which changes main evaporator fan speed upon receipt of a signal from the main controller.
The optional parcel rack evaporator assemblies includes an evaporator coil assembly, a thermal expansion valve, a fan and motor assembly, condensate drain connection, and a return air thermostat (on the road side only).
The evaporator coils provide a heat transfer surface for transferring heat from air circulating over the outside surface of the coil to refrigerant circulating inside the tubes; thus providing cooling when required. The thermal expansion valves meter the flow of refrigerant entering the evaporator coils. The heating coils provide a heat transfer surface for transferring heat from engine coolant circulating inside the tubes to air circulating over the outside surface of the tubes, thus providing heating when required. The evaporator heat valve(s) (EHV) controls the flow of engine coolant supplied to the heating coils. The fans circulate the air over the coils. The air filters filter dirt particles from the air before the air passes over the coils. The condensate drain connections provide a means for disposing of condensate collected on the evaporator coils during cooling operation.
T-312
1-4
Page 13
2
31
5
4
6
16
15
14
13
1. Access Panel
2. Electrical Connector
3. Nameplate
4. Air Bleed Valve
5. Fan and Motor
6. Solenoid Valve and Coil
7. Thermal Expansion Valve
8. RAM Actuator
Figure 1-4. Driver Evaporator Assembly
12
13
11
9. RAM Air Door
10. Liquid Inlet Connection, Size 11/16 ORS 1 1. Suction Outlet Connection, 1-7/16 ORS
12. Service Port
13. Condensate Drain Connections
14. Air Filter
15. Evaporator Coil Assembly
16. Heater Coil Assembly
7
8
9
10
3
2 1
1. Suction Outlet Connection
2. Liquid Inlet Connection
3. Side Access Panel
4. Top Access Panel
5. Thermal Expansion Valve
6. Evaporator Coil Assembly
7654
8
11
7. Fan and Motor
8. Motor Mount Bracket 9 Condensate Drain Connection
10. Relay 1 1. Thermostat (Not supplied by Carrier)
Figure 1-5. Parcel Rack Evaporator Assembly
1-5
9
10
T-312
Page 14
20
19
18
17
16
15
31
4
52
14 13 12 67
10
11 9
1. Thermal Expansion Valve
2. Refrigerant Liquid Inlet Connection, 3/8“ ORS
3. Evaporator/Heater Coil Assembly
4. Heater Coil Inlet Connection, 7/8 OD
5. Evaporator Heat Valve (EHV)
6. Blower Housing, Right
7. Blower Wheel, Right
8. Nameplate
9. Evaporator Fan Relay, High Speed (EFRH)
10. Evaporator Fan Relay, Low Speed (EFRL) 1 1. Elastomeric Motor Mounts
12. 2-Speed Motor
13. Blower Wheel, Left
14. Blower Housing, Left
15. Service Port
16. Coolant Drain valve
17. Heater Coil Outlet Connection, 7/8 OD
18. Capillary Tube and Bulb (TXV)
19. Refrigerant Suction Outlet Connection, 1” ORS
20. Air Bleed Valve
21. Air Filter Channel
8
21
Figure 1-6. Main Evaporator Assembly
T-312
1-6
Page 15
1.2.4 Main Control Box
The main control box (See Figure 1-7) includes a main controller (microprocessor module), expansion output board, receptacle, quick connectors, connectors and fuses (F2 and F3). The main controller (microprocessor module) contains the electronic hardware to measure inputs and process the outputs to automatically control
the air conditioning and heating system to maintain
temperatures inside the coach. The microprocessor
section has a built in memory facility for checking proper
operation; this includes checks of the program memory,
data memory and analog. It has a self test feature which
is executed when the system is first powered up. The
expansion board drives six discrete outputs in addition
to the standard outputs from the controller.
20
18 17 16
1110987654321
1312
20
21
14
15
19
1. Connector (MA)
2. Connector (MB)
3. (Not Used)
4. Fuse (F2)
5. (Not Used)
6. Fuse (F3)
7. (Not Used)
8. Quick Connector (QC1)
9. Connector (KA)
10. Connector (KB) 1 1. Connector (MA)
12. Quick Connector (QC2)
13. Connector (MB)
14. Relay
15. Expansion Board
16. Main Controller
17. Packard Connector Pins L thru Y
18. Packard Connector Pins A thru K
19. Coach Interface Connector
20. Model/Serial Number Plate (Box)
21. Model/Serial Number Tag (Controller)
Figure 1 -7. Main Control Box
1-7
T-312
Page 16
Defrost (Driver’s Evap Blower)
Display
Up (Increase) Selection
Down (Decrease) Selection
Automatic Control
Vent Only
Cooling Only
DEF
H
I
G
H
L O W
HEAT
H
I G H
L O
W
Heat (Driver’s Evap Coolant Valve)
Figure 1-8. System Operating Controls
(upper left hand switch panel)
1.2.5 System Operating Controls And Components
There are five controls on the driver’s station which affect the operation of the Carrier supplied equipment covered by this manual. These controls include two rocker switches, two slide switches, and the Micromate Control Panel.
On/Off
Fresh Air Heat Only
Inside/Outside
Fan Speed
Tem p e ra t u re
temperature reaches the desired set point, the system will maintain compressor operation and open the heat valve to allow reheating of the return air. In the reheat mode interior temperature is maintained at the desired set point while additional dehumidification takes place.
The first slide switch is the Defrost Switch (Figure 1-8). This switch controls the driver evaporator blower motor speed. The second slide switch is the Heat Switch (Figure 1-8). This switch controls the driver evaporator coolant valve. These switches are located on the dashboard to the left of the steering wheel.
The third control is the Driver Display Panel (Figure 1-8) which operates the Carrier Transicold microprocessor controller, circuit breakers and relays. Modes of operation include Vent, Heat, Cool and Auto. This control panel is located on the dashboard with the slide switches to the left of the steering wheel.
In the vent mode the evaporator fans are operated to circulate air in the bus interior.
In the heat mode the heat valve and the OEM supplied floor blower and/or boost pump are energized. The evaporator fans operate to circulate air over the evaporator coil and heater coil in the same manner as the vent mode.
In the cooling mode the compressor is energized while the evaporator and condenser fans are operated to provide refrigeration as required. The compressor is fitted with cylinder unloaders to match compressor capacity to the bus requirements. Once the interior
Figure 1-9. Parcel Rack On/Off
The forth control is the rocker switch for the Parcel Rack (Figure 1-9). This switch will de--activate the parcel rack evaporators if the main evaporator is in operation. This switch is located on the dashboard to the right of the steering wheel.
The fifth control is the rocker switch for the Driver A/C (Figure 1-10). It is located on the left side console panel near the transmission gear selector. This switch will activate the system to provide cooling for the driver in the event that cooling is not called for by the Carrier Transicold microprocessor.
T-312
1-8
Page 17
Figure 1-10. Driver A/C
1.2.6 Other Carrier Supplied Items
Other Carrier supplied items include curbside and roadside return air temperature sensors, two coolant control valves and a check valve. The temperature sensors provide input to the controller on temperature conditions in the coach. The bypass heat (coolant control) valve provides a path for coolant flow when all evaporator heat valves are closed. The other coolant control valve is the heat valve that controls the flow of coolant to the driver heater coil. The check valve is installed in the compressor refrigerant discharge line and allows refrigerant flow in only one direction to prevent liquid return to the compressor when the compressor is shut down.
1.3 REFRIGERATION SYSTEM COMPONENT SPECIFICATIONS
a. Refrigerant Charge
R-134a: 17.5 lb (8 kg)
b. Compressor
Model: 05G No. of Cylinder: 6 Weight (Dry): 145 lb (66 kg) including clutch Oil Charge:
New Compressor: 5.8 pints (2.7 liters) Replacement Compressor: 5.5 pints (2.6 liters)
Oil Level:
Level in sight glass between bottom of glass and middle of glass on compressor crankcase (curbside)
Approved Compressor Oils - R-134a:
Castrol: Icematic SW68C Mobil: EAL Arctic 68 ICI: Emkarate RL68H
c. Thermostatic Expansion Valve - for R-134a
Units:
1. Main Evaporator:
Superheat Setting (Nonadjustable): 12 to 18_F
(6.7 to 10.1_C)
MOP Setting: None
2. Driver Evaporator and Parcel Rack Evaporator:
Superheat Setting (Nonadjustable): 5 to 12_F
(6.7 to 10.1_C)
MOP Setting: None
d. High Pressure Switch (HPS):
Opens at: 385 10 psig (26.2 . 68 BAR) Closes at: 285 10 psig (19.39 .68 BAR)
1.4 ELECTRICAL SPECIFICATIONS - WOUND FIELD MOTORS
a. Main Evaporator/Heater Blower (Fan) Motor
Bearing Lubrication: Factory Lubricated (additional
grease not required)
Horsepower:
High Speed: 1.6 (1.2 kw) Low Speed: 0.7 (0.5 kw)
Full Load Amps (FLA):
High Speed: 56 Low Speed: 28
Operating Speed:
High Speed: 1550 rpm Low Speed: 1200 rpm
Voltage: 24 vdc
b. Driver Evaporator/Heater Blower (Fan) Motor
Bearing Lubrication: Factory Lubricated (additional
grease not required) Full Load Amps (FLA): 9.5 Operating Speed:
High Speed: 3300 rpm
Medium Speed: 1600 rpm
Low Speed: 1100 rpm Voltage: 24 vdc
c. Condenser Fan Motor
Bearing Lubrication: Shell Dolium R Horsepower: 0.8 hp (1.072 kw) Full Load Amps (FLA):
High Speed: 32
Low Speed: 21 Operating Speed:
High Speed: 1800 rpm
Low Speed: 1600 rpm Voltage: 24 vdc
d. Parcel Rack Evaporator Fan Motor
Bearing Lubrication: Factory Lubricated (additional
grease not required) Full Load Amps (FLA): 9.5 Operating Speed: 3300 rpm Voltage: 24 vdc
1.5 ELECTRICAL SPECIF ICATIONS-MAIN CONTROLLER INPUT SENSORS AND TRANSDUCERS
a. Suction and Discharge Pressure Transducer
Supply Voltage: 4.5 to 5.5 vdc (5 vdc nominal) Input Range: --6.7 to 450 psig (--0.05 to 30.62 BAR) Output Voltage: vdc = 0.0098 x psig
+ 0.4659 (See Table 4-5 for calculations.)
b. Temperature Sensors
Input Range: --52.6 to 158_F (--47 to 70_C) Output: NTC 10K ohms at 77_F (25_C)
(See Table 4-3 for calculations.)
1-9
T-312
Page 18
1.6 SAFETY DEVICES
System components are protected from damage caused by unsafe operating conditions with safety devices. Safety devices that are connected to Carrier Transicold supplied equipment include a high pressure switch (HPS), fuses (See T able 1-3.) and a fusible plug.
In addition, evaporator and condenser fan motors and the main control box are protected independently against high current draw by circuit breakers suppliedby the coach manufacturer. The evaporator and condenser fan motors are also protected from high temperature with internal thermal protection switches. If a condenser fan motor safety device opens to stop the condenser fan motor(s), the system may develop a high pressure condition, which may open the high pressure switch (HPS) to shut the unit down.
a. Pressure Switches
High Pressure Switch (HPS)
The high pressure switch (HPS) is installed in the compressor center cylinder head and opens on a pressure rise to shut down the system when high pressure conditions occur. (Refer to: 1.3.d.)
Table 1-3. Safety Devices (For Carrier Supplied Equipment)
Unsafe Condition Safety Device Device Setting
High compressor discharge
High Pressure Switch (HPS) Refer to 1.3.d.
pressure
Excessive current draw by the
Fuse (F2) Opens at 5 amps
controller 12 vdc supply circuit
Excessive current draw by the
Fuse (F3) Opens at 10 amps
controller 24 vdc output circuit
During the A/C mode, HVAC system operation will automatically stop if the HPS switch contacts open due to an unsafe operating condition. Opening HPS contacts de-energizes, through the main controller, the A/C compressor clutch and condenser fan relays shutting down the system.
b. Fuses
Fuses (F2 and F3)
Fuse (F2), internal to the controller, protects the controller 12 vdc supply circuit from excessive current draw. Fuse (F3) protects the controller 24 vdc output circuit from excessive current draw.
c. Thermal Switches
Condenser Motor Overloads (CMOL1 and CMOL2)
Each condenser fan motor is equipped with an internal thermal protector switch, condenser motor overloads (CMOL1 and CMOL2). If excessive motor temperature exists, the CMOL switch will open to de-energize the corresponding condenser fan relay (CFR1 or CFR2); this will stop the affected condenser motor.
T-312
1-10
Page 19
1.7 HEATING (ENGINE COOLANT) FLOW CYCLE
Heating circuit components furnished by Carrier Transicold include heater cores and evaporator heat valves (EHV) for the driver and main evaporator assemblies and a coolant bypass heat valve. Components furnished by the coach manufacturer include auxiliary heater and engine water pump, auxiliary heater, hand valves and “Y” type strainers. The
main controller automatically controls the EHV valves during heating and reheat cycles to maintain required temperatures inside the coach. Engine coolant (glycol solution) is circulated through the heating circuit by the engine and auxiliary water pumps. When the evaporator heat valve solenoid is de-energized, the valve will open to allow engine coolant to flow through the heater coil. (See Figure 1-11.) The valve is normally open so that if a failure occurs, the system will still be able to supply heat.
*HAND VALVE
*’Y’ STRAINER
*AUXILIARY
HEATER
HEAT VALVE
DRIVER HEATER CORE
HEAT VALVE
MAIN HEATER CORE
BYPASS HEAT VALVE
AIR BLEED
VALVE
AIR BLEED
VALVE
DRAIN VALVE
*HAND VALVE
*ENGINE
WATER PUMP
*ENGINE
*INDICATES COMPONENTS FURNISHED
BY THE COACH MANUFACTURER
Figure 1-11. Heating System Flow Diagram
1-11
T-312
Page 20
1.8 AIR CONDITIONING REFRIGERANT CYCLE
When air conditioning (cooling) is selected by the main controller, the unit operates as a vapor compression system using R-134a as a refrigerant. The main components of the system are the reciprocating compressor, air-cooled condenser coil, subcooler, filter-drier, thermostatic expansion valves, liquid line solenoid valves and evaporator coils. (See Figure 1-12)
The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line, and the check valve into the condenser tubes. The condenser fan circulates surrounding air (which is at a temperature lower than the refrigerant) over the outside of the condenser tubes. Heat transfer is established from the refrigerant (inside the tubes) to the condenser air (flowing over the tubes). The condenser tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquefy.
The refrigerant leaves the condenser and then flows through the subcooler, which subcools the refrigerant before it enters the thermal expansion valves; this reduces flash gas in the evaporator. From the subcooler, the liquid refrigerant passes through the liquid line (King) service valve, and then through a filter-drier where an absorbent keeps the refrigerant clean and free of water.
From the filter-drier, the liquid refrigerant then flows through the main liquid line solenoid valve to the main evaporator and thermal expansion valve and to the
parcel rack evaporator solenoid valve (if this option is active) the parcel rack thermal expansion valve and through the driver solenoid valve (if this option is active) and to the driver thermal expansion valve. The solenoid valves open during cooling to allow refrigerant to flow to the thermal expansion valves. The main liquid solenoid valve and the parcel rack liquid line solenoid valve (when so equipped) closes during shutdown to prevent refrigerant migration. The thermal expansion valves reduce the pressure and temperature of the liquid and meters the flow of liquid refrigerant to the evaporator to obtain maximum use of the evaporator heat transfer surface.
The low pressure, low temperature liquid that flows into the evaporator tubes is colder than the air that is circulated over the evaporator tubes by the evaporator blower (fan). Heat transfer is established from the evaporator air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The evaporator tubes have aluminum fins to increase heat transfer from the air to the refrigerant; therefore the cooler air is circulated to the interior of the coach.
The transfer of heat from the air to the low temperature liquid refrigerant in the evaporator causes the liquid to vaporize. This low temperature, low pressure vapor passes through the suction line and returns to the compressor where the cycle repeats.
When ventilation only is selected by the main controller, only the evaporator fans function to circulate air throughout the coach. The refrigerant cycle will remain off.
T-312
1-12
Page 21
DRIVER SOLENOID VALVE
Discharge Liquid
Suction
CONDENSER ASSEMBLY
MAIN LIQUID LINE SOLENOID VALVE
CONDENSER
PARCEL RACK LIQUID LINE SOLENOID VALVE
FILTER
DRIER
SIGHT-­GLASS
TXV
DRIVER EVAPORATOR ASSEMBLY
TXV
MAIN EVAPORATOR ASSEMBLY
PARCEL EVAPORATOR ASSEMBLY
TXV
TXV
TXV BULB
SERVICE PORT
TXV BULB
SERVICE PORT
SERVICE PORT
SUBCOOLER
DISCHARGE LINE SERVICE VALVE
SERVICE PORT
FUSIBLE PLUG
DISCHARGE LINE
LIQUID LINE (KING) SERVICE VALVE
DISCHARGE CHECK VALVE
COMPRESSOR
PARCEL EVAPORATOR
ASSEMBLY
SUCTION LINE
Figure 1 -12 Air Conditioning Refrigerant Flow Diagram
SERVICE PORT
1-13
T-312
Page 22
1.9 ELECTRONIC AUTOMATIC CONTROL DATA FLOW
The system is supplied with 12 and 24 vdc power from the coach power supply. The main controller receives input from pressure transducers, temperature sensors, condenser and evaporator fan motor overloads, high pressure switch, fuses. It then processes these inputs to control output devices enabling automatic control of
12 /24 VDC POWER SUPPLY
temperature conditions inside the coach. The driver display provides a communication link between the main controller and the rest of the system. The following block diagram (Figure 1-13) indicates data flow through the system. Refer to section 2 for more detailed information on the theory of operation of the control system and see section 5 for system electrical schematics.
24 VDC POWER SUPPLY
INPUT DEVICES (Transducers, Sensors and HP switch)
12 VDC POWER SUPPLY
DRIVER DISPLAY
OUTPUT DEVICES
MAIN CONTROLLER
(Solenoids,
Relays, Clutch)
EXPANSION
BOARD
OUTPUT DEVICES (Heater Solenoid Valves and RAM Air Actuators)
MAIN CONTROL BOX
24 VDC POWER SUPPLY
Figure 1 -13. Electronic Automatic Control Data Flow Block Diagram
Fan Motors, Compressor, Driver Control Box
T-312
1-14
Page 23
SECTION 2
OPERATION
HEAT
(a.)
(b.)
Down (Decrease) Selection
On/Off
(1.)
Defrost (Driver’s Evap Blower)
Driver Display Panel (c.)
DEF
H
I G H
L O
W
H
I G H
L O
W
Heat (Driver’s Evap Coolant Valve)
Display
Figure 2-1. System Operating Controls
(upper left hand switch panel)
2.1 STARTING, STOPPING AND OPERATING INSTRUCTIONS
2.1.1 Operating Controls
There are five operating controls (Figure 2-1) used to control the functions of this system. They are as follows:
a. The Defrost Switch controls the driver evaporator
blower motor speeds. With this switch the driver con­trols the amount of air discharged to the windshield. This function is independent of any other HVAC func­tion in the coach.
b. The Heat Switch controls the coolant valve to the driv-
er’s evaporator. With this switch the driver controls the amount of engine coolant flowing thru the driver’s evaporator heater core, hence increasing or decreas­ing the temperature of air that is discharged to the windshield. This function is independent of any other HVAC function in the coach.
c. The Driver Display Panel controls the Carrier Trans-
icold microprocessor controller which in turn controls the operation of the heating and air conditioning sys­tem. With this control the driver controls the tempera­ture of air to the passenger area and cooling to the driver area. The panel has 10 keys whose functions are described as follows:
1. On/Off -- Pressing this key will change the display
state from inactive to active. If the controller is active the display will illuminate and the other keypad LEDs will be active.
Automatic Control
Up (Increase) Selection
Inside/Outside Temperature
(2.)
(3.)
Fresh Air
(8.)
Vent Only
(9.)
Fan Speed
(6.)
Heat Only
2. Up (Increase Selection) -- If the set point is displayed when the Up key is pressed, the display will increase set point 1_F (0.5_C).
3. Down (Decrease Selection) -- If the set point is dis­played when the Down key is pressed, the display will decrease set point 1_F (0.5_C).
4. Auto (Auto Control Selection) -- Pressing the Auto button illuminates the AUTO LED and signals the controller to automatically cycle to the control set point. If the AUTO LED is illuminated, the manual modes will be de--activated, the COOL, VENT, and HEAT LED’s will not be illuminated.
5. Cool (Cool Mode Selection) -- If the COOL button is pressed, the COOL LED is illuminated, the system will only cool to control set point. The AUTO, VENT, and HEAT LED’s will not be illuminated.
6. Vent (Ventilation Mode Selection) -- If the VENT but­ton is pressed, the VENT LED is illuminated, only the system fans will operate. The AUTO, COOL, and HEAT LED’s will not be illuminated.
7. Heat (Heat Mode Selection) -- If the HEAT button is pressed, the HEAT LED is illuminated, the system will operate in the heat mode only, cycling the coolant control valves as needed to maintain set point. The AUTO, COOL, and VENT LED’s will not be illumi­nated.
8. Inside/Outside Temperature -- After start--up, the display shows set point. The temperature display selection button will toggle the display to show bus
(4.)
Cooling Only
(7.)
(10.)
(5.)
2-1
T-312
Page 24
inside or outside temperature. The inside tempera­ture is obtained by averaging the curb and road side return air sensors (located in the return air ducts). If one sensor is not functioning the display will read only the functioning sensor, if both are not function­ing, the display will show ’--40’. The outside temper­ature sensor is located in the condenser assembly.
When the key is toggled to display the inside temper­ature, the inside LED will be illuminated. When the key is toggled to display the outside temperature, the outside LED will be illuminated. When the key toggles to show set point, both inside and outside LEDs are turned off.
9. Fresh Air -- The Fresh Air Button has two selection LEDs, Fresh Air and Circulation. If the fresh air damper door is open, the Fresh Air LED is illumi­nated, if the fresh air damper door is closed, the Cir­culation LED will be illuminated.
After start-- up, the fresh air selection is in AUTO, the controller will control the fresh air damper door. When the key is toggled the damper selection will move to the next step an Auto--Closed--Open--Auto sequence. The Auto selection allows controller to operate the damper, the Closed or Open being the closed or open damper door selections with the damper door held in those respective positions until the button is toggled again.
10.Fan Speed -- After start--up, the display obtains the the current fan speed status from the controller. If the controller is in AUTO no fan speed LEDs will be illu­minated. When a fan speed is selected the appropri­ate LED will be illuminated.
11. _F/_C -- Key combination is used to select _For_C. When the display is showing temperature, press and hold the Inside/Outside Temperature selection key(8.) and press the UP key(2.), the display will show in the _F scale. When the display is showing temperature, press and hold the Inside/Outside Temperature selection key(8.) and press the DOWN key(3.), the display will show in the _C scale.
Figure 2-2. Parcel Rack On/Off
d. The Parcel Rack Switch (Figure 1-9) controls the liq-
uid line solenoid valve and the blower motors of the parcel rack evaporators. The driver controls the par­cel rack evaporator function with this switch. The par­cel rack evaporators will function only after the main evaporator is operating.
Figure 2 -3. Driver A/C
e. The Driver A/C Switch (Figure 2-3) allows the driver
to control cooling with the driver’s evaporator. When the switch is in AUTO, the driver’s area cooling is controlled by the microprocessor controller. When the switch is in COOL, the driver’s area is demanding cooling, even if the microprocessor is calling for heat­ing in the passenger area.
2.1.2 HVAC Power to Controller
Before starting the system, electrical power must be available from the coach power supply.
2.1.3 Starting
The Driver Display Panel consists of a display and a keypad (Figure 2-1), which allows the user to modify and observe system operating parameters.
On start--up a self test will execute. While the test is being executed the display will show its programing revision number in the format of X.X, where X is a digit from 1 to 9 (ex. 1.4). At his time three possible error messages may also appear on the display. Refer to Table 3-2 for definitions.
a. If the engine is not running, start the engine. The
HV AC system will restart in the AUTO mode. All sys­tem controls will operate automatically in heating, cooling or ventilating mode, as required.
b. CONTROL PANEL (Figure 2-1)
It is suggested the system be started in the automatic mode.
1. The Driver Display Panel may be programmed to display the set point temperature or return air tem­perature. To determine which display temperature is programmed, press the TEMPERATURE button so that the OUT SIDE AIR indicator is illuminated. If the controller cycles back to the INSIDE AIR indicator, than the controller is programmed to display return air temperature. If the controller does not automati­cally cycle back to the return air indicator, than the controller is programmed to display set point temper­ature.
2. The Control Panel will signal the controller to perform start up when the ON/OFF button is pushed. Ensure the AUTO button indicator is illuminated. If not, press the AUTO button to place the system in the automat­ic mode.
3. If cooling only, heating only or ventilation only is de­sired, press the corresponding button (refer to Figure 2-1) to illuminate the indicator light and manu­ally place the system in that mode of operation.
4. If low or high speed evaporator fan speed is desired, press the FAN SPEED button to illuminate the indi­cator light and bring speed to the desired level.
T-312
2-2
Page 25
5. To open or close the fresh air damper, press the FRESH AIR button.
6. To read interior or exterior temperature, press the TEMPERATURE button to illuminate the indicator light and bring the display to the desired temperature reading. After a short delay, the display will return to the default set point or return air temperature read­ing.
7. Setpoint may be changed by pressing the UP or DOWN arrow button. The UP button will increase the setpoint temperature and the DOWN button will de­crease the setpoint temperature.
2.1.4 Activating Defrost
2.1.8 Stopping
With the system operating, pressing the ON/OFF key will stop the HVAC system operation and the display will be blank.
2.2 PRE-TRIP INSPECTION
After starting system operation, allow system to stabilize for ten to fifteen minutes and check for the following:
a. Listen for abnormal noises in compressor or fan mo-
tors.
b. Check compressor oil level. (Refer to paragraph
4.12.4)
Windshield defrost is initiated and controlled with the Defrost switch and the Heat switch (Figure 2-1). Moving the switches to the high setting on both will deliver the highest volume of warm air on the windshield. Correspondingly, moving either or both of the two switches to the low setting will decrease the volume of air and the temperature of air delivered across the windshield.
2.1.5 Active Alarm
During normal operation, the controller monitors system operating parameters for out of tolerance conditions. The display gets the controller alarm queue information every 30 seconds. Alarms will be shown as an alarm code. If an alarm is activated and the display is reading temperature, the display will show the temperature and the alarm code alternately in 1 second intervals.
2.1.6 Diagnostics (Check for Alarms)
If an alarm condition exists, diagnostics can be manually initiated to isolate system fault(s) by simultaneously pressing the Up and Down Selection keys continuously for five seconds. Diagnostics should be accessed only when the coach is not moving. When entering the diagnostic mode, all LEDs for the key pad will be turned off. All keys except the On/Off, Up (increase) Selection and Auto keys will stop functioning. T o scroll through the diagnostic information press the UP key. Pressing the O/I key at any time will exit this mode. To clear the alarm message, scroll thru the alarms until ’------’ appears, then press the Auto Key for 5 seconds or until ’------’ disappears. Refer to section 3 for description of diagnostics. Refer to Table 3-3 for definition of alarm messages.
2.1.7 Diagnostics (Parameters)
To access the system parameters press the Up and Down Selection keys continuously for five seconds. The display will now be in the Diagnostics mode and may be displaying alarms. Scroll thru the alarms(if present) until ’------’ appears. With ’-- -- --’ displayed on the read--out, press the Up Selection key. The first parameter code will be displayed. To scroll thru the parameters press the Up Selection key. When showing parameters, the display will first flash out the parameter identifier Pxx for one second and then show the parameter value. To return to normal operation press the On/Off key (see Figure 2-1). Refer to Section 3 for for definitions of the parameter codes.
c. Check refrigerant level. (Refer to paragraph 4.7.1)
d. Ensure that self-test has been successfully per-
formed and that there are no errors or alarms indi­cated. (Refer to paragraph 2.1.5 or 2.1.6)
2.3 SYSTEM DESCRIPTION
Refer to Section 5 for sample schematic diagrams of the power and control circuits.
2.3.1 Pull Up and Pull Down Modes
At power up, the system will enter a pull up or pull down mode to rapidly obtain desired temperatures within the coach. During this mode, the system will run at maximum heating or cooling capacity until the set point (in the passenger zone) is reached for the first time. For the driver zone, temperature control is controlled by the two slide switches next to the controller (See Figure 2-1).
1. Pullup/pulldown main evaporator fan speed is limit­ed to a maximum of thirty minutes and can be put in pullup/pulldown speed only once. When the control­ler switches out of pullup/pulldown speed, pullup/ pulldown speed is prevented again by the controller unless the controller is shut off and restarted. The display cannot override the fan speed to pullup/pull­down.
2. The minimum run time in pullup or pulldown for the main evaporator fans is three minutes for automatic control.
a. Capacity State Selection
The main controller automatically compares system temperature with the controller set point and changes system operating modes at certain temperature deviations. Figure 2-4 shows various changes in operating modes and controller actions at various temperature deviations from controller set point. Upon rising temperature, mode changes occur at values in Figure 2-4 above controller set points, On a falling temperature, mode changes occur when temperatures are equal to those given in Figure 2-4 The system will operate in these modes unless pressure overrides the controller settings. If the controller detects that the temperature setting is not being reached during a period of time, it will slowly adjust the temperature at which these modes are entered; this will allow the system to always attempt to reach the controller temperature setting.
2-3
T-312
Page 26
COOLING MODE HIGH SPEED MAIN EVAP FAN COMPR FULLY LOADED (6 CYL)
COOLING MODE COMPR FULLY LOADED (6 CYL)
EVAPORATOR
RETURN AIR TEMP
ABOVE SET POINT
____F (4.75____ C)
8.5
8 _
_F(4.5 ____C)
__
closing the heating valve. The compressor clutch and condenser fan motors are energized as appropriate.
Reheat allows for both net cooling and net heating by varying the time that the heat valve is open. The time is automatically calculated by the controller and is based on a 20 second period.
c. Heating
In the heat capacity state, the liquid solenoid valve is closed to stop cooling and the compressor will shut down. The heating capacity can then be varied by adjusting the time the heat valve is open. The time is automatically calculated by the controller and is based on a 20 second period.
COOLING MODE LOW SPEED MAIN EVAP FAN COMPR FULLY LOADED (6 CYL)
COOLING MODE LOW SPEED MAIN EVAP FAN COMPR SEMI-LOADED (4 CYL)
REHEAT MODE HUMIDITY LESS THAN 49% LOW SPEED MAIN EVAP FAN COMPR UNLOADED (2 CYL)
OR
HUMIDITY CONTROL MODE HUMIDITY GREATER TAN 50% HIGH SPEED MAIN EVAP FAN COMPR FULLY LOADED (6 CYL)
HEAT MODE LOW SPEED MAIN EVAP FAN COMPR FULLY UNLOADED (CLUTCH DISENGAGED)
HEAT MODE COMPR FULLY UNLOADED (CLUTCH DISENGAGED)
HEAT MODE HIGH SPEED MAIN EVAP FAN COMPR FULLY UNLOADED (CLUTCH DISENGAGED)
6.75 _
_F(3.75 ____C)
__
5.5 _
_F(3.0 ____C)
__
SET POINT
-- 3 . 5 _F(-- 2 . 0 _C)
-- 8 _
_F(-- 4 . 5 ____C)
__
-- 8 . 5 _
_F(--4.75 ____C)
__
d. Driver Area Control
The Driver’s A/C switch on the left side console is turned on when cooling is desired in the driver area.
The driver area conditions are controlled by manually adjusting the Defrost and Heat slide switches on the dash board. These controls operate in conjunction with the main coach controller. Temperature control is ac­complished by regulating the flow of engine coolant through the heating coil in the driver evaporator (with the Heat slide switch) by controlling a normally open electric solenoid valve. The volume of air flow directed about the driver area is controlled (with the Defrost slide switch) by the speed of the drivers evaporator fan motors.
The heating coil reheats the precooled air to maintain the desired temperature at the set point. During heat­ing, the driver area liquid solenoid valve is closed and the heating valve is opened and closed for a percentage of the heat valve period.
e. Passenger Area Control
The passenger area temperature is controlled by maintaining the return air temperature as measured by the return air sensors located at the rear of the coach in the return air ducts. The return air sensors are averaged together to provide input for the controller.
FALLING TEMP.
RISING TEMP.
For humidity control refer to 2.3.4
Figure 2-4. Main Controller Automatic Control
Sequence
b. Cooling/Reheat
Cooling and reheat require various combinations of evaporator fan speeds and compressor unloading. Cooling is accomplished by energizing the compressor and condenser, opening the liquid solenoid valve and
T-312
If cooling is required for the passenger area, the compressor and condenser will start and the main liquid line solenoid valve is opened and the heat valve is closed.
During reheat, the main liquid solenoid valve is opened and the heating valve is opened and closed for a percentage of the heat valve period (20 seconds).
To enter the heat mode for the passenger area, the controller must be calling the heat valve to be cycling at 51% or higher. If this condition is not met, the area requiring heat is put into reheat. During heating, the main evaporator liquid solenoid valve is closed and the heating valve is opened and closed for a percentage of the heat valve period (20 seconds). Once the heat mode has been entered, the controller will not re--enter heat until the heat valve has closed to less than 25%.
2-4
Page 27
2.3.2 Bypass Heat Valve Control
The normally open Bypass Heat Valve is closed on system start--up. During re--heat, the bypass heat valve remains closed when the heat valves are open, and opens 2 seconds before the heat valves close (to prevent water hammering).
2.3.3 Auxiliary Heater Control
The auxiliary heater output is energized when the heat valve has been opened 100% for 60 seconds. Once energized, the auxiliary heater output is de--energized when the heat valve percentage is less than 20 percent for fifteen minutes.
The OEM supplied Auxiliary Heater Switch located on the left side console can independently energize the auxiliary heater when the engine is off. When placing the switch in the ON position, the switch activates the auxiliary heater for a timed period of 90 minutes. Placing the switch in the OFF position or starting the coach engine will de--activate the auxiliary heater.
2.3.4 Humidity Control
Humidity control (reheat mode) is activated when the humidity is greater than fifty percent and the passenger zone temperature is less than 5_F(3_C) above set point. When these conditions are met the compressor will be fully loaded (6 cylinders)and at the same time the heat valve(s) will cycle open to maintain temperature. Once humidity control is activated, it will remain activated until the humidity is less than 45 percent or the return air temperature drops 2_F(1_C) below set point.
2.3.5 Compressor Unloader Control
The unloader outputs control the capacity of the compressor by energizing or de-energizing unloader solenoid valves. Energizing a valve solenoid de-activates a pair of compressor cylinders. The 05G compressor has six cylinders. Four cylinders are equipped with two sets of unloader valves (UV1 and UV2), each controlling two cylinders; this allows the compressor to be operated with two, four or six cylinders. When the compressor is off, the unloader solenoids are de-energized immediately .
Whenever the compressor is changed from off to on, the unloaders are forced energized for fifteen seconds. After fifteen seconds, one unloader solenoid may be de-energized, if required. Any subsequent changes between energizing and de-energizing the unloader solenoids must be staged with a thirty second delay. Only one unloader may change state at a time when staging is required.
a. Suction Pressure
In addition to temperature control, the electric unloaders will be used to prevent coil frosting. Staging is ignored for energizing the unloader solenoid due to suction pressure overrides :
1. Compressor Unloader Bank 1 Solenoid (UV1). When the suction pressure decreases below 25 psig (1.7 BAR), the first unloader solenoid is energized unloading the first compressor cylinder bank (two
cylinders); this output will remain energized until the pressure increases to above 32 psig (2.18 BAR).
2. Compressor Unloader Bank 2 Solenoid (UV2). When the suction pressure decreases below 21 psig (1.43 BAR), the second unloader solenoid is ener­gized unloading the second compressor cylinder bank (two cylinders); this output will remain ener­gized until the pressure increases to above 28 psig (1.91 BAR).
b. Discharge Pressure
Head Pressure is also controlled by the unloaders. Staging is ignored for energizing the unloader solenoid due to discharge pressure overrides :
1. Compressor Unloader Bank 1 Solenoid (UV1). When the discharge pressure increases above 340 psig (23.13 BAR), the first compressor unloader so- lenoid is energized; this output will remain energized until the pressure decreases below 300 psig (20.41 BAR).
2.3.6 Passenger Area Evaporator Fan Speed
Selection
The passenger area evaporator assembly is equipped with a two speed fan motor. Temperature control is the primary method of determining the fan speed selection. Table 2-1 indicates relay operational status for the various fan motor states.
Table 2 -1. Main Evaporator Fan Speed Relay
Operation
STATE
HIGH SPEED
RELA Y
LOW SPEED
RELA Y
Off Off Off
Low On On
High On Off
Pull
Up/Down
On Off
2.3.7 Driver’s Area Evaporator Fan Speed
Selection
The driver air conditioning unit is equipped with two evaporator fan motors. The Defrost slide switch determines the fan speed. See (Figure 2-1).
2.3.8 Condenser Fan Speed Control
The first condenser fan motor (CM1) is energized when the compressor clutch output is energized.
The second condenser fan motor (CM2) is energized when the clutch is energized and the discharge pressure increases above 175 psig (1.2 mkPa). It will be de-energized when the clutch is de-energized or the discharge pressure decreases below 125 psig (0.861 mPa).
The condenser fans are started in low speed and will remain in low speed until the discharge pressure increases above 225 psig (1.6 mPa). The fans will remain in high speed until the discharge pressure decreases below 165 psig (1.1 mPa).
2-5
T-312
Page 28
2.3.9 Staging
When the system is started, the fans are staged on to reduce the total starting current. There is no staging required for the driver evaporator fan motors, as they start immediately. Staging for the evaporator and condenser fan motors are given in the Table 2-2.
Table 2 -2. Main area Staging
Ref.
Time
(seconds)
Controller Action
Time 0 0 Main Evaporator Fan Low
Time 2 Time0+2 Main Evaporator Fan High
Time 3 Time0+4 Condenser Fan 1 Low
Time 4 Time3+1 Condenser Fan 2 Low
Time 5 Time3+3 Both Condenser Fans High
2.3.10 Compressor Clutch Control
A belt driven electric clutch is employed to transmit en­gine power to the air conditioning compressor. De-ener­gizing the clutch electric coil disengages the clutch and removes power from the compressor. The clutch will be engaged whenever any area is calling for cooling. The clutch will be disengaged when the system is off, when all areas are in heating or during high and low pressure conditions. The clutch coil is controlled by the main con­troller.
The clutch coil is prevented from engagement when the ambient temperature is below 32_F (0_C).
The clutch coil will be de-energized if the discharge pressure rises to 350 psig (2.4 mPa), the setting of the compressor mounted high pressure switch. The clutch coil will energize when the discharge pressure falls to 240 psig (1.7 mPa).
The clutch coil will be de-energized if the suction press­ure decreases below 6 psig (41 kPa).
2.3.11 RAM Air Control
The RAM air control regulates admission of outside air into the system.
a. Display Override
The RAM air can be automatically controlled or set to open or closed by the display .
b. RAM Air Auto Mode
1. If the passenger return air temperature is greater than controller set point plus 2_F (1.1_C) or less than set point minus 2_F (1.1_C), the RAM air will be closed.
2. Otherwise, RAM air is open.
An exception to the above is that there is a five minute delay to open RAM air once it is closed in the auto mode. There is no delay to close RAM air.
2.3.12 Startup
At startup, the controller will power on and perform all power up tests.
2.3.13 Input Processing
The system determines correct operation by reading temperature sensors (thermistors), pressure transducers and the humidity sensor. Refer to section
1.5 for electrical specifications for input devices and
sections 1.2.1, 1.2.2 and 1.2.6 for functional descriptions.
2.3.14 Self Tests
With the engine running, self tests are automatically executed.
“ER5” indicates a data memory failure. “ER6” indicates a program memory failure. If any of these or any other errors are displayed on the screen, proceed to Table 3-1.
2.3.15 Alarm Description
Alarm descriptions and troubleshooting procedures are provided in section 3.
2.3.16 Hour Meters
An hour meter records the compressor run time in hours. The maximum reading is 999,999.
An Hourmeter records the total elapsed time the controller has been on in hours. The maximum reading is 999,999.
2.3.17 Communications (Driver Display -
Controller)
The controller uses communications to transmit data to the display. The communications link is RS232.
T-312
2-6
Page 29
SECTION 3
TROUBLESHOOTING
CAUTION Do not under any circumstances attempt to service the microprocessor. Should a problem develop with the microprocessor, replace it.
NOTE
To access LED display on the microprocessor, remove cover from main control box located in rear of electrical compartment.
Table 3-1. Microprocessor Error Message Definition
ERROR
CODE
0 1secon-1secoff Not Applicable as system is operating normally.
1 1 flash - 5 sec pause Record error code number, tag and replace the mi croprocessor.
2 2 flashes - 5 sec pause Record error code number, tag and replace the mi croprocessor.
3 3 flashes - 5 sec pause Record error code number, tag and replace the mi croprocessor.
4 4 flashes - 5 sec pause Record error code number, tag and replace the mi croprocessor.
5 5 flashes - 5 sec pause Record error code number, tag and replace the mi croprocessor.
6 6 flashes - 5 sec pause Record error code number, tag and replace the mi croprocessor.
STATUS OF
LED DISPLAY
REMEDY
Table 3-2. Display Error Message Definition
ERROR
CODE
Er4 Communications Failure If the display does not receive data from the microprocessor.
Er5 Data Memory If memory on the display is not verified on power up.
Er6 Program Memory If program memory on the display is not verified on power up by a checksum.
ALARM
NO.
A11 Main Left
MESSAGE MESSAGE DEFINITION
Table 3-3. Driver Display Panel Alarm Message Definition
TITLE CAUSE REMEDY MICROPROCESSOR RESPONSE
Probe Failure
Sensor is unplugged, wiring defective or main left evaporator return air temperature sensor failure.
Ensure sensor is
plugged in. Check
sensor resistance or
wiring. Replace sen-
sororrepairwiring.
(Refer to section 4.13
Switches to the right probe. If both probes are bad, the microprocessor will run in the full reheat and evapo­rator fans will operate on low speed. The compressor will operate on six cylinders if pressures permit.
and Table 4-3.)
A12 Main Right
Probe Failure
Sensor is unplugged, wiring defective or main right evaporator return air temperature sensor failure.
Ensure sensor is
plugged in. Check
sensor resistance or
wiring. Replace sen-
sororrepairwiring.
(Refer to section 4.13
Switches to the left probe. If both probes are bad, the microprocessor will run in the full reheat and evapo­rator fans will operate on low speed. The compressor will operate on six cylinders if pressures permit.
and Table 4-3.)
3-1 T-312
Page 30
Table 3-3. Driver Display Panel Alarm Message Definition - Continued
ALARM
NO.
A14 Ambient
TITLE CAUSE REMEDY MICROPROCESSOR RESPONSE
Probe Failure
A15 Suction Press-
ure Transducer Failure
A16 Discharge
Pressure Transducer Failure
A17 Humidity
Transducer Failure
A18 Fuse Blown
Alarm
Sensor is unplugged, wiring defective or ambient temperature sensor failure.
Sensor is unplugged, wiring defective or suction pressure trans­ducer failure.
Sensor is unplugged, wiring defective or discharge pressure transducer failure.
Sensor is unplugged, wiring defective or humidity transducer failure.
Defective wiring or coach power source de­fective. microprocessor Internal fuse is blown.
Ensure sensor is plugged in. Check sensor resistance or wiring. Replace sen­sor or repair wiring. (Refer to section 4.13 and Table 4-3.)
Ensure sensor is plugged in. Check transducer voltage or wiring. Replace sen­sor or repair wiring. (Refer to section 4.15 and Table 4-5.)
Ensure sensor is plugged in. Check transducer voltage or wiring. Replace sen­sor or repair wiring. (Refer to section 4.15 and Table 4-5.)
Ensure sensor is plugged in. Check transducer voltage or wiring. Replace sen­sor or repair wiring. (Refer to section 4.14 and Table 4-4.)
Repair or replace wiring or power source. Replace Fuse.
Ignores ambient temperature and does not lock out the compressor and does not open driver RAM air in AUTO mode.
Energizes unloaders.
Energizes unloaders.
If conditions allow, not including the humidity set point/humidity sensor condition, activates humidity control (dehumidification). (See section
2.3.4.) Does not open passenger RAM air in AUTO. (Refer to section
2.3.11.)
All microprocessor outputs are de­energized.
A19 Main
Evaporator Fan Overload
A22 Condenser
Fan Overload
Main evaporator fan overload.
Condenser fan over­loads
Refertosection3.3.6. No microprocessor response other
than alarm.
Refertosection3.3.3 and/or 3.3.4
If the compressor is energized and the first condenser fan overload opens, the microprocessor will ener­gize the second condenser fan in or­der to detect the first overload con­dition.
If, after energizing the second con­denser fan, the second condenser fan overload opens, the compressor clutch will de-energize for the mini­mum off time, since neither con­denser fan is operating.
3-2T-312
Page 31
ALARM
NO.
TITLE CAUSE REMEDY MICROPROCESSOR RESPONSE
A22 Condenser
Fan Overload (continued)
Table 3-3. Driver Display Panel Alarm Message Definition - Continued
Condenser fan over­loads
Refertosection3.3.3
and/or 3.3.4
If after energizing the second con­denser fan, the second condenser fan overload does not open, the micro­processor will keep the first over­load alarm activated and leave the compressor and second condenser fan energized. (The second condens­er fan remains energized since at least one condenser fan must be en­ergized when the compressor is en­ergized.)
A23 High Pressure
Discharge
High discharge pressure.
A25 Out of Range If the system is con-
_F
A26 Low Voltage/
Load Shed
trolling within 9
(5_C) of setpoint for a period of 15 minutes and then fails to con­trol within 18_F (10_C) for any reason this alarm will be acti­vated.
Low coach voltage. Coach 12 vdc battery supply voltage dropped below 12.6 vdc for 30 seconds.
Check discharge
pressure transducer
voltage, wiring or
cause of high dis-
charge pressure. (Re-
fertosection4.15and
Table 4-5 and/or sec-
tion 3.3.3.)
Refertosection3.3.1,
3.3.2 and/or 3.3.8 de-
pending on heating/
cooling requirements.
Check/repair alterna-
tor or coach power
supply.
If this alarm has not been activated three times in 30-minutes, it de-en­ergizes the clutch for the minimum off time and until the alarm is de-ac­tivated. Energizes the second con­denser fan at high speed. De-ener­gizes the rest of the system unless heat is required.
If this alarm has been re-activated three times in 30-minutes, it de-en­ergizes the rest of the system. The system will operate only in the heat mode until the alarm is reset via communications.
No microprocessor response other than alarm.
De-energizes all outputs except driv­er evaporator fan motor. (See section
2.1.2.)
3-3 T-312
Page 32
ALARM
ControllerSoftwar
e
NO.
TITLE CAUSE REMEDY MICROPROCESSOR RESPONSE
A27 Low Pressure
Shutdown
Table 3-3. Driver Display Panel Alarm Message Definition - Continued
Low suction pressure. Check cause of low
suction pressure. (Re­fer to section 3.3.3.)
If alarm has been activated three times in 30-minutes, the clutch will be de-energized until the alarm is de-activated.
If alarm has been activated three times in 30-minutes, de-energizes the rest of the system unless heat is required. Runs the main evaporator fan at low speed until alarm is reset.
A28 High Voltage Power 12 vdc source
voltage is greater than
Check, repair or re­place alternator.
All microprocessor outputs are de­energized.
17 vdc.
A29 Low Voltage Power 12 vdc source
voltage is less than 10
Repair or replace wiring or alternator.
All microprocessor outputs are de­energized.
vdc.
A31 EEPROM Memory failure. Replace main micro-
processor at next ser-
Modifies out of range values to their default values.
vice stop.
Table 3-4. Parameter Codes
CODE CODE NAME DESCRIPTION
P5 Suction Pressure This value is the suction pressure measured by the suction pressure transduc-
P6 Discharge Pressure This value is the discharge pressure measured by the discharge pressure
P20 Compressor Hours
P21 Compressor Hours
P22 Evaporator Hours
P23 Evaporator Hours
P30
P31
High
Low
High
Low
Controller Software Version
er. If the sensor is shorted it will display CL If it is open circuited it will display OP. NOTE: This value is not updated, it is the value at the time that the code is accessed.
transducer. If the sensor is shorted it will display “CL” and if it is open circuited it will display “OP”. NOTE: This value is not updated, it is the value at the time that the code is accessed.
This is the number of hours of operation that the compressor has run with the clutch energized. The reading is in thousands.
This is the number of hours of operation that the compressor has run with the clutch energized. The reading is in hundreds, tens and ones.
This is the number (in thousands) of hours of operation with the evaporator fans energized.
This is the number (in hundreds, tens and ones) of hours of operation with the evaporator fans energized.
This is the software version of the logic board. The first two digits of the soft­ware revision are displayed. Ex. Revision XXYY XX is displayed after P30.
This is the software version of the logic board. The second two digits of the software revision are displayed. Ex. Revision XXYY YY is displayed after P31.
3-4T-312
Page 33
Table 3 -5. General System Troubleshooting Procedures
INDICATION/
TROUBLE
3.3.1 System Will Not Cool
POSSIBLE CAUSES
Compressor will not run V-Belt loose or defective
Clutch coil defective Clutch malfunction Compressor malfunction
Electrical malfunction Coach power source defective
Circuit Breaker/safety device open
3.3.2 System Runs But Has Insfficient Cooling
Compressor V-Belt loose or defective
Compressor valves defective
Refrigeration system Abnormal pressures
No or restricted evaporator air flow Expansion valve malfunction Restricted refrigerant flow Low refrigerant charge Service valves partially closed Safety device open Liquid solenoid valve stuck closed
3.3.3 Abnormal Pressures
High discharge pressure Refrigerant overcharge
Noncondensable in system Condenser fan rotation incorrect Condenser coil dirty
Low discharge pressure Compressor valve(s) worn or broken
Low refrigerant charge
REFERENCE
SECTION
Check Check/Replace Check/Replace
See Note.
Check/Repair
Check/Reset
Check
See Note.
3.3.3
3.3.6
3.3.7 and 4.11
3.3.7 and 4.11
4.5 and 4.7 Open
1.6
Check
4.4
4.8
Check
Clean
See Note.
4.5 and 4.7
High suction pressure Compressor valve(s) worn or broken See Note. Low suction pressure Suction service valve partially closed
Filter-drier inlet valve partially closed Filter-drier partially plugged Low refrigerant charge Expansion valve malfunction Restricted air flow
Suction and discharge pressures
Compressor valve defective See Note.
Open
Check/ Open
4.10
4.5 and 4.7
3.3.7
3.3.6
tend to equalize when system is operating
3.3.4 Abnormal Noises Or Vibrations
Compressor Loose mounting hardware
Worn bearings Worn or broken valves Liquid slugging Insufficient oil Clutch loose, rubbing or is defective V-belt cracked, worn or loose Dirt or debris on fan blades
Condenser or evaporator fans Loose mounting hardware
Defective bearings Blade interference Blade missing or broken
Check/Tighten
See Note. See Note.
3.3.7
4.12.4 Check
Check/Adjust
Clean
Check/Tighten
Replace
Check
Check/Replace
3-5 T-312
Page 34
Table 3 -5. General System Troubleshooting Procedures - Continued
INDICATION/
TROUBLE
3.3.5 Control System Malfunction
POSSIBLE CAUSES
Will not control Sensor or transducer defective
Relay(s) defective Microprocessor malfunction
3.3.6 No Evapotator Air Flow Or Restricted Air Flow
Air flow through coil blocked Coil frosted over
Dirty coil Dirty filter
No or partial evaporator air flow Motor running in reverse
Motor(s) defective Motor brushes defective(main evaporator) Evaporator fan loose or defective Fan damaged Return air filter dirty Icing of coil Fan relay(s) defective Safety device open
3.3.7 Expansion V alve Malfunction
Low suction pressure with high superheat
Low refrigerant charge Wax, oil or dirt plugging valve orifice Ice formation at valve seat Power assembly failure Loss of bulb charge Broken capillary
Low superheat and liquid slugging in the compressor
3.3.8 No Or Insufficient Heating
Superheat setting too low Ice or other foreign material holding valve open
Insufficient heating Dirty or plugged heater core
Coolant solenoid heat valve(s) malfunctioning or plugged Low coolant level Coolant bypass heat valve open or malfunctioning Strainer(s) plugged Hand valve(s) closed Water pumps defective Auxiliary Heater malfunctioning.
No Heating Coolant solenoid heat valve(s) malfunctioning or plugged
Microprocessor malfunction Pump(s) malfunctioning Safety device open
NOTE: Refer to Model 05G Compressor Manual, Form No. 62-02756.
REFERENCE
SECTION
4.13, 4.15 or
4.14 Check Check
Defrost coil
Clean
Clean/Replace
Check
Repair/Replace
4.18/4.19 Repair/Replace Repair/Replace
Clean/Replace
Clean/Defrost
Check/Replace
1.6
4.5 and 4.7
4.6
4.6
4.11.1
4.11.1
4.11.1
4.11
4.6
Clean
Check/Replace
Check
Check/Replace
Clean
Open Repair/Replace Repair/Replace
Check/Replace
Replace
Repair/Replace
1.6
3-6T-312
Page 35
SECTION 4
OPERATION
REFERENCE
SERVICE
WARNING
BE SURE TO OBSERVE WARNINGS LISTED IN THE SAFETY SUMMARY IN THE FRONT OF THIS MANUAL BEFORE PERFORMING MAINTENANCE ON THE HVAC SYSTEM
NOTE
Following completion of all maintenance or service activities, the alarm queue should be cleared of any original alarms and any alarms generated during service. Refer to paragraph 2.1.6
4.1 MAINTENANCE SCHEDULE
SYSTEM
ON OFF
a. Daily Maintenance
X
Pre-trip Inspection -- after starting Check tension and condition of V-belt
X
b. Weekly Inspection
X
Perform daily inspection
X
Check condenser, evaporator coils and air filters for cleanliness
X
Check refrigerant hoses and compressor shaft seal for leaks
X
Feel filter-drier for excessive temperature drop across drier
c. Monthly Inspection and Maintenance
X
Perform weekly inspection and maintenance
X
Clean evaporator drain pans and hoses
X
Check wire harnesses for chafing and loose terminals
X
Check fan motor bearings
X
Check compressor mounting bolts for tightness
X
Check fan motor brushes
4.2 SUCTION AND DISCHARGE SERVICE VALVES
The suction and discharge service valves (See Figure 4-1) used on the compressor are equipped with mating flanges for connection to flanges on the compressor. These valves are provided with a double seat and a gauge connection, which allows servicing of the compressor and refrigerant lines.
Turning the valve stem counterclockwise (all the way out) will backseat the valve to open the suction or discharge line to the compressor and close off the gauge connection. In normal operation, the valve is backseated to allow full flow through the valve. The valve should always be backseated when connecting the service manifold gauge lines to the gauge ports.
Turning the valve stem clockwise (all the way forward) will frontseat the valve to close off the suction or discharge line to isolate the compressor and open the gauge connection.
To measure suction or discharge pressure, midseat the valve by opening the valve clockwise 1/4 to 1/2 turn. With the valve stem midway between frontseated and backseated positions, the suction or discharge line is open to both the compressor and the gauge connection.
REFERENCE
paragraph
2.2 None
4.1.a None
4.5
4.10
4.1.b None Replace/Tighten None None
4.19, 4.23
TO DISCHARGE OR FROM SUCTION LINE
PORT TO COMPRESSOR
ACCESS VALVE CAP
Service Valve Frontseated (clockwise)
VALVE STEM CAP
VALVE STEM
ACCESS VALVE (R-134a)
Service Valve Backseated (counterclockwise)
Figure 4 -1. Suction or Discharge Service Valve
4-1 T-312
Page 36
4.3 INSTALLING MANIFOLD GAUGES
The manifold gauge set can be used to determine system operating pressures, add charge, equalize or evacuate t he system.
Low Pressure
Gauge
Opened (Backseated ) Hand Valve
To Low Side Access Valve
1
2
High Pressure
Gauge
Closed (Frontseated) Hand Valve
To High Side Access Valve
3
BLUE
3
RED
3
YELLOW
4
5
(Red Knob)
6
(Blue Knob)
2
4
1. Manifold Gauge Set
2. Hose Fitting (0.5-16 Acme)
3. Refrigeration and/or Evacuation Hose . (SAE J2196/R-134a)
4. Hose Fitting w/O-ring (M14 x 1.5)
5. High Side Field Service Coupler
6. Low Side Field Service Coupler
Figure 4-2. Manifold Gauge Set (R-134a)
4.3.1 Installing R-134a Manifold Gauge Set
An R-134a manifold gauge/hose set with self-sealing hoses is required for service of models covered within this manual. The manifold gauge/hose set is available from Carrier Transicold. (CTD P/N 07-00294-00, which includes items 1 through 6, see Figure 4-2.) To perform service using the manifold gauge/hose set, do the following:
a. Preparing Manifold Gauge/Hose Set For Use
1. If the manifold gauge/hose set is new or was exposed to the atmosphere it will need to be evacuated to remove contaminants and air as follows:
2. Back seat (turn counterclockwise ) both field service couplers (See Figure 4-2, items 5 and 6) and midseat both hand valves.
3. Connect the yellow hose to a vacuum pump and an R-134a cylinder.
4. Evacuate to 10 inches (0.69
BAR) of vacuum and then charge with R-134a to a slightly positive pressure of 1.0 psig (0.07 BAR).
5. Front seat both manifold gauge set hand valves and disconnect from cylinder. The gauge set is now ready for use.
b. Connecting Manifold Gauge/Hose Set
To connect the manifold gauge/hose set for reading pressures, do the following:
1. Remove service valve stem cap and check to make sure it is backseated. Remove access valve cap.
2. Connect the field service coupler (see Figure 4-2, items 5 and 6) to the access valve.
3. Turn the field service coupling knob clockwise, which will open the system to the gauge set.
4. Read system pressures.
5. Repeat the procedure to connect the other side of the gauge set.
c. Removing the Manifold Gauge Set
1. While the compressor is still ON, backseat the high side service valve.
2. Midseat both hand valves on the manifold gauge set and allow the pressure in the manifold gauge set to be drawn down to low side pressure. This returns any liquid that may be in the high side hose to the system.
CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set be sure set is brought to suction pressure before disconnecting.
3. Backseat the low side service valve. Backseat both field service couplers and frontseat both manifold set hand valves. Remove the couplers from the access valves.
4. Install both service valve stem caps and access valve caps (finger-tight only).
4.4 PUMPING THE SYSTEM DOWN OR
REMOVING THE REFRIGERANT CHARGE
NOTE
To avoid damage to the earth’s ozone layer , use a refrigerant recovery system whenever removing refrigerant.
4.4.1 System Pumpdown
To service or replace the filter-drier, expansion valve, evaporator coil, or suction line, pump the refrigerant into condenser coil as follows:
a. Install manifold gauge set. (Refer to paragraph 4.3)
b. Start the unit and allow it to run in the cool mode for 15
to 20 minutes.
c. Unplug the suction pressure transducer(SPT).
NOTE
The following procedure may have to be repeated several times to maintain the 0 to 2 psig (6.9 kPa) pressure depending upon amount of refrigerant absorbed in the oil.
4-2T-312
Page 37
d. Frontseat the liquid line (King) valve by turning
clockwise. Start system and run in cooling. Stop the unit when the suction pressure reaches 1 psig (0.07 BAR).
e. Frontseat (close) suction service valve to trap the
refrigerant in the high side of the system between the compressor suction service valve and the filter drier inlet valve. The low side of the system will now be at 1 psig (0.07 BAR) pressure and ready for servicing,
f. Service or replace the necessary component on the
low side of the system.
g. Leak check connections. (Refer to paragraph 4.5)
h. Evacuate and dehydrate the low side. (Refer to
paragraph 4.6)
i. Reconnect the suction pressure transducer (SPT).
j. Clear the low pressure alarm. (Refer to paragraph
2.1.6)
4.4.2 Removing the Refrigerant Charge
Connect a refrigerant recovery system to the unit at the condenser service (King) valve to remove refrigerant charge. (See Figure 4-4) Refer to instructions provided by the manufacturer of the refrigerant recovery system.
NOTE
1. Before opening up any part of the system, a slight positive pressure should
be indicated on the gauge.
2. When opening up the refrigerant system, certain parts may frost. Allow the part to warm to ambient temperature before dismantling; this avoids internal condensation, which puts moisture into the system.
3. When opening or closing the service valves, care should be given to note if the packing around the valve stem is worn or may need adjustment to prevent refrigerant leaks.
4.4.3 Refrigerant Removal From An Inoperative Compressor.
To remove the refrigerant from a compressor that is not operational, do the following:
a. Attach a manifold gauge set as shown in Figure 4-3
and isolate the compressor by front seating the suction and discharge valves.
b. Recover refrigerant with a refrigerant reclaimer. If the
discharge service valve port is not accessible, it will be necessary to recover refrigerant through the suction service valve port only.
c. Service or replace components as required and leak
check the compressor.
d. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of manifold gauge set. Evacuate compressor to 500 microns. Close off pump valve, isolate vacuum gauge and stop pump. Wait 5 minutes to verify that vacuum holds.
e. Once vacuum is maintained, recharge low side with
R-134a to 20 to 30 PSIG by admitting vapor from the refrigerant cylinder. Backseat compressor service valves and disconnect manifold gauge set.
3
DS
2
1
4
5
7
6
1. Discharge Service Valve and Port
2. Suction Service Valve and Port
3. Manifold Gauge
4. Vacuum Pump
5. Reclaimer
6. Refrigerant Cylinder
7. Thermistor Vacuum Gauge
Set
Figure 4-3. Compressor Service Connections
4.4.4 Pump Down An Operable Compressor For Repair
To service an operable compressor, pump the refrigerant into the condenser coil as follows:
a. Install manifold gauge set. (See Figure 4-3) b. Unplug the suction pressure transducer (SPT). c. Frontseat the compressor suction service valve by
turning clockwise.
d. Start the unit and run in cooling until 10 ”/hg (0.69
BAR) of vacuum is reached. Shut the system down and tag out system power source.
e. Frontseat the compressor discharge service valve
and wait 5 minutes to verify vacuum is maintained. If the pressure rises above vacuum, open the compressor discharge service valve and repeat steps c and d until a vacuum is maintained.
f. Service or replace components as required and leak
check the compressor.
g. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of manifold gauge set. Evacuate system to 500 microns. Close off pump valve, isolate vacuum gauge and stop pump. Wait 5 minutes to verify that vacuum holds.
h. Once vacuum is maintained, backseat compressor
service valves and disconnect manifold gauge set. i. Reconnect the suction pressure transducer (SPT). j. Clear the low pressure alarm. (Refer to paragraph
2.1.6)
4-3 T-312
Page 38
4.5 REFRIGERANT LEAK CHECK
A refrigerant leak check should always be performed after the system has been opened to replace or repair a component.
To check for leaks in the refrigeration system, perform the following procedure:
NOTE
It must be emphasized that only the correct refrigerant drum should be connected to pressurize the system. Any other gas or vapor will contaminate the system, which will require additional evacuation.
a. Ensure all the service valves and solenoid valves are
open. It will be necessary to energize the solenoid valves from an external power source.
b. If the system is without refrigerant, charge the system
with refrigerant vapor to build up pressure between 30 to 50 psig (2.74to3.40BAR).
c. Add sufficient nitrogen to raise system pressure to a
maximum of 150 psig (10.21 BAR).
d. Check for leaks. It is recommended that an electronic
leak detector be used to find refrigerant leaks in a system. Testing joints with soapsuds is satisfactory and may be necessary under conditions when an electronic leak detector will not function correctly.
e. Remove refrigerant from system and repair any
leaks.
f. Evacuate and dehydrate the system. (Refer to
paragraph 4.6) g. Charge the unit. (Refer to paragraph 4.7)
h. Ensure that self-test has been performed and that
there are no errors or alarms indicated. (Refer to
paragraphs 2.1.5 and 2.1.6)
4.6 EVACUATION AND DEHYDRATION
4.6.1 General
The presence of moisture in a refrigeration system can have many undesirable effects. The most common are copper plating, acid sludge formation, “freezing-up” of metering devices by free water, and formation of acids, resulting in metal corrosion.
4.6.2 Preparation
NOTE
1. Using a compound gauge for determination of vacuum level is not recommended because of its inherent inaccuracy.
2. Never evacuate an open drive compressor below 500 microns.
a. Evacuate and dehydrate only after pressure leak test.
(Refer to paragraph 4.5)
b. Essential tools to properly evacuate and dehydrate
any system include a good vacuum pump with a minimum of 6 cfm (10.2 m
3
/hr) volume displacement,
(CTD P/N 07-00176-11), and a good digital (micron) vacuum indicator (CTD P/N 07--00414--00).
c. Keep the ambient temperature above 60_F (15.6_C)
to speed evaporation of moisture. If ambient temperature is lower than 60_F (15.6_C), ice may form before moisture removal is complete. It may be necessary to use heater blankets, heat lamps or alternate sources of heat to raise system temperature.
4.6.3 Procedure for Evacuation and Dehydrating System
a. Remove refrigerant using a refrigerant recovery
system. (CTD P/N MVS--115--F--L--CT for 115 volt power source or CTD P/N MVS--240--F--L--CT for 240 volt power source)
b. The recommended method is connecting two lines
(3/8” OD copper tubing or refrigerant hoses designed for vacuum service) to the manifold guage set. Attach one line to the condenser service (King) valve and the other line to the evaporator service port. (See Figure 4-4)
c. Connect lines to unit and manifold and make sure
vacuum gauge valve is closed and vacuum pump valve is open.
d. To speed up evacuation time, open solenoid valves
electrically. An additional vacuum pump may be added and connected to the compressor suction service port. (See Figure 4-4)
e. Start vacuum pump. Slowly open valves halfway and
then open vacuum gauge valve.
f. Evacuate unit until vacuum gauge indicates 1500
microns vacuum. Close gauge valve, vacuum pump valve, and stop vacuum pump.
g. Break the vacuum with clean dry refrigerant or dry
nitrogen. Use the refrigerant that the unit calls for. Raise system pressure to approximately 2 psig (0.14 BAR).
h. Remove refrigerant using a refrigerant recovery
system, or if using nitrogen vent to atmosphere.
i. Start vacuum pump and open all valves. Evacuate
unit to 500 microns vacuum.
j. Close off pump valve, isolate vacuum gauge in
system and stop pump. Wait five minutes to see if vacuum holds.
k. With a vacuum still in the unit, the refrigerant charge
may be drawn into the system from a refrigerant container on weight scales. (Refer to paragraph 4.7)
4-4T-312
Page 39
1. Reclaimer
DS
2
4
2. Manifold Guage Set
3. Thermistor Vacuum Guage
4. V acuum Pump
5. Refrigerant Cylinder
6. Evaporator Service Port
3
1
7. Liquid Line (King) Valve and Service Port
8. Discharge Service Port
5
Discharge
DRIVER SOLENOID VALVE
Liquid Suction
MAIN LIQUID LINE SOLENOID VALVE
CONDENSER ASSEMBLY
CONDENSER
SUBCOOLER
DISCHARGE LINE SERVICE VALVE
PARCEL RACK LIQUID LINE SOLENOID VALVE
FILTER
DRIER
SIGHT-­GLASS
FUSIBLE PLUG
DISCHARGE LINE
TXV
DRIVER EVAPORATOR ASSEMBLY
TXV
PASSENGER EVAPORATOR ASSEMBLY
PARCEL EVAPORATOR ASSEMBLY
TXV
TXV
7
DISCHARGE CHECK VALVE
PARCEL EVAPORATOR
ASSEMBLY
TXV BULB
SERVICE PORT
TXV BULB
6
SERVICE PORT
SERVICE PORT
SUCTION LINE
SERVICE PORT
8
COMPRESSOR
Figure 4 -4. Refrigerant Service Connections
4-5 T-312
OPTIONAL VACUUM PUMP
Page 40
4.7 ADDING REFRIGERANT TO SYSTEM
4.7.1 Checking Refrigerant Charge
a. Connect an accurate high pressure gauge to the
discharge service port at the compressor. (See Figure 4-4)
b. The condenser coil should be clean and free of any
debris.
c. Coach engine operating at high idle (800--1000RPM).
d. The compressor should be fully loaded (six cylinder
operation).
e. Unit must be operating in the cool mode until the
discharge pressure has stabilized (3 to 5 minutes) and the interior temperature is between 70 and 80_F (21.1 and 26.7_C).
f. Discharge pressure at least 150 psig (10.21 BAR)
and stable for R-134a systems (It may be necessary to partially block condenser airflow to raise discharge pressure).
g. Observe the Liquid Line Sight Glass and use the
following chart to determine the condition of the refrigerant charge:
Table 4-1. Checking Refrigerant Charge
Sight Glass
Observation
Liquid present
Clear of all bubbles
charge -- Continue to step
Condition
Good/Possible over
i.
Liquid present
Occasional bubbles
Good
present
Liquid present
Many bubbles present
Possible under charge --
Continue to step i.
h. If the conditions in steps b. thru f. are met and there is
still doubt about the refrigerant charge level use Table 4-2:
Table 4-2. Checking Refrigerant Charge
Condenser Inlet Air
Temperature
Discharge Pressure
Range
____F ____C PSIG BAR
60 16 110--135 7.48--9.19 65 18 120--145 8.16--9.87 70 21 130--155 8.85--10.55 75 24 140--165 9.53--11.23 80 27 150--175 10.21--11.91 85 29 160--186 10.89--12.66 90 32 175--200 11.91--13.61 95 35 190--212 12.93--14.42
i. With an accurate temperature gauge, measure the
condenser inlet air temperature.
NOTE
Do not use a temperature gun as it measures surface temperature and not air temperature.
1. If the actual discharge pressure is higher than the discharge pressure range, the system may be over charged.
2. If the actual discharge pressure is lower than the discharge pressure range, the system may be under charged.
3. If the actual discharge pressure is in the discharge pressure range, the system charge is adequate.
NOTE
Many system related problems will effect system pressures. Use Table 3-5 General System Troubleshooting Procedures to determine other possible causes before adding or removing refrigerant.
4.7.2 Adding Full Charge
a. Evacuate and dehydrate system. (Refer to paragraph
4.6.)
b. Place appropriate refrigerant cylinder on scales and
connect charging hose from container to filter-drier
inlet valve. Remove air from hoses. c. Note weight of refrigerant and container. d. Open liquid valve on refrigerant container. Midseat
filter-drier inlet valve and allow refrigerant to flow into
the unit. Refer to paragraph 1.3 for correct charge. e. When drum weight (scale) indicates that the correct
charge has been added, close liquid line valve on
drum and backseat the filter-drier inlet valve.
4.7.3 Adding Partial Charge
NOTE
Refrigerant charge is critical, when adding charge to the unit do not add any more charge to the system after bubbles have been eliminated from the sight glass.
a. Start the vehicle engine and allow the system to
stabilize. (Refer to 4.7.1a. to f.) b. Connect charging hose from appropriate refrigerant
cylinder vapor valve to compressor suction service
valve. c. Open cylinder valve and add vapor charge. Under the
above conditions, the system is properly charged
when the condenser sight glass is clear with
occasional bubbles showing. Add or remove
refrigerant until the proper charge is obtained. d. Backseat suction service valve. Close vapor valve on
refrigerant drum. Replace all valve caps.
4.8 CHECKING FOR NONCONDENSIBLES
To check for noncondensibles, proceed as follows: a. Stabilize system to equalize pressure between the
suction and discharge side of the system. The engine
needs to be off for several hours. b. Measure temperature at any of the copper tubing in
the condenser. c. Check pressure at the compressor discharge service
valve. d. Determine saturation pressure as it corresponds to
the condenser temperature using the
Temperature-Pressure Chart, Table 4-6.
4-6T-312
Page 41
e. If gauge reading is 3 psig (.2 BAR) or higher than the
calculated P/T pressure in step d, noncondensibles are present.
f. Remove refrigerant using a refrigerant recovery
system. (Refer to paragraph 4.6.3)
g. Evacuate and dehydrate the system. (Refer to
paragraph 4.6)
h. Charge the unit. (Refer to paragraph 4.7)
4.9 CHECKING AND REPLACING HIGH PRESSURE CUTOUT SWITCH
4.9.1 Replacing High Pressure Switch
a. The high pressure switch is equipped with schrader
valve to allow removal and installation without pumping the unit down.
b. Unplug the wiring from the switch.
c. Check switch operation. (Refer to paragraph 4.9.2)
d. Replace switch if it does not function as outlined
below. (Refer to paragraph 4.9.2)
4.9.2 Checking High Pressure Switch
WARNING DO NOT USE A NITROGEN CYLINDER WITHOUT A PRESSURE REGULATOR
DO NOT USE OXYGEN IN OR NEAR A REFRIGERATION SYSTEM AS AN EXPLOSION MAY OCCUR.
f. Close cylinder valve and release pressure through
the bleed-off valve. As pressure drops to cut-in point, the switch contacts should close, indicating continuity on the ohmmeter.
4.10 FIL TER-DRIER
4.10.1.To Check Filter Drier
Check for a restricted or plugged filter-drier by feeling the liquid line inlet and outlet connections of the filter-drier. If the outlet side feels cooler than the inlet side, then the filter-drier should be changed.
4.10.2.To Replace Filter Drier
a. Pump down the unit. (Refer to paragraph 4.4) b. Replace filter-drier, ensuring that the arrow points in
the direction of the refrigerant flow .
c. Drier can be evacuated at liquid line service valve.
(See Figure 4-4)
d. Check refrigerant charge. (Refer to paragraph 4.7.1)
2
1
3
4
8
5
6
a. Remove switch from unit. All units are equipped with
schrader valves at the high pressure switch connection.
b. Connect an ohmmeter across switch terminals. If the
switch is good, the ohmmeter will indicate continuity, indicating that the contacts are closed.
1
4
1. Cylinder Valve
2
5
and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge,
3
6
0 to 400 psig
(0 to 2.8 mPa)
5. Bleed-Off Valve
6. 1/4 inch Connection
Figure 4-5. Checking High Pressure Switch
c. Connect switch to a cylinder of dry nitrogen. (See
Figure 4-5)
d. Set nitrogen pressure regulator higher than cutout
point on switch being tested. (Refer to paragraph 1.3)
e. Open cylinder valve. Slowly open the regulator valve
to increase the pressure until it reaches cutout point. The switch should open, which is indicated by an infinity reading on an ohmmeter (no continuity).
7
1. Power Head Assembly
2. Equalizer Connection
3. Bulb
4. Cage Assembly
5. Seat Gasket
6. Body Flange
7. Capscrew
8. Body Flange Gasket
Figure 4 -6. Thermostatic Expansion Valve
4.11 THERMOSTATIC EXPANSION VALVE
The thermostatic expansion valve (TXV) is an automatic device which maintains constant superheat of the refrigerant gas leaving the evaporator regardless of suction pressure. The valve functions are: (a) automatic response of refrigerant flow to match the evaporator load and (b) prevention of liquid refrigerant returning to the compressor. Unless the valve is defective, it seldom requires any maintenance. All TXV’s are non--adjustable.
4.11.1 Replacing the Expansion Valve (See Figure 4 -6)
a. Pump down low side of the unit. (Refer to paragraph
4.4)
b. Remove insulation (Presstite) from expansion valve
bulb.
4-7 T-312
Page 42
c. Loosen retaining straps holding bulb to suction line
and detach bulb from the suction line.
d. Loosen flare nut on equalizer line and disconnect
equalizer line from the expansion valve.
e. Remove capscrews and lift off power head and cage
assemblies and gaskets.
f. Check, clean and remove any foreign material from
the valve body, valve seat and mating surfaces.
NOTE
Do not adjust the new replacement expansion valve. Valves are preset at the factory.
g. Using new gaskets, install new cage and power head
assemblies provided with repair kit.
h. The thermal bulb is installed below the center of the
suction line (four or eight o’clock position). This area must be clean to ensure positive bulb contact. Strap thermal bulb to suction line and insulate both with “Presstite.” Ensure that retaining straps are tight. (See Figure 4-7)
i. Connect equalizer line to the expansion valve.
j. Evacuate and dehydrate. (Refer to paragraph 4.6)
k. Open filter-drier inlet valve (liquid line service valve)
and all service valves.
l. Run the coach for approximately 30 minutes on fast
idle.
m.Check refrigerant charge. (Refer to paragraph 4.7.1)
n. Check superheat. (Refer to paragraph 4.11.2)
d. Place temperature thermocouple in contact with the
suction tube and parallel to the TXV bulb, and then secure loosened clamp making sure both bulbs are firmly secured to suction line. (See Figure 4-7) Reinstall insulation around the bulb.
e. Connect an accurate low pressure gauge (or install a
manifold gauge set) to the service port on the leaving side of the evaporator. (Refer to paragraph 4.3)
f. Close evaporator access door being careful to route
thermocouple sensing wire and guage hose thru the access hole to outside the evaporator.
g. Start coach and run on fast idle until unit has
stabilized, about 20 to 30 minutes.
h. From the temperature/pressure chart, determine the
saturation temperature corresponding to the evaporator outlet pressure. (Refer to Table 4-6)
i. Note the temperature of the suction gas at the
expansion valve bulb. Subtract the saturation temperature determined in step 8 from the temperature measured in this step. The difference is the superheat of the suction gas.
j. Repeat steps 8. and 9. six times at three minute
intervals and average the six readings to determine average superheat. Average superheat should be 12 to 18_F (6.7 to 10.1_C).
4.12 MODEL 05G COMPRESSOR MAINTENANCE
3
2
4
5
1
1. Suction Line (end view)
2. TXV Bulb Clamp
3. Nut and Bolt (clamp)
4. Thermocouple
5. TXV Bulb (Shown in the four o’clock position)
Figure 4 -7. Thermostatic Expansion Valve
Bulb and Thermocouple Installation
4.11.2 To Check/Measure Superheat
NOTE
All readings must be taken from the leaving side of the evaporator.
a. Open filter access door.
b. Remove Presstite insulation from expansion valve
bulb and suction line.
c. Loosen one TXV bulb clamp and make sure area
under clamp (above TXV bulb) is clean.
4.12.1 Removing the Compressor
If compressor is inoperative and the unit still has refrigerant pressure, isolate the compressor and remove the refrigerant. (Refer to paragraph 4.4.3)
If compressor is operative, perform a pump down. (Refer to paragraph 4.4.4)
a. Turn main battery disconnect switch to OFF position
and lock.
b. Loosen the compressor drive belt, and remove.
c. Loosen bolts at suction and discharge service valve
flanges and break seal to be sure pressure is released.
d. Remove bolts from suction and discharge service
valve flanges.
e. Tag and disconnect wiring to the high pressure cutout
switch, discharge pressure transducer, suction pressure transducer, unloaders and the clutch.
f. Remove four bolts holding compressor to base.
g. Attach sling or other device to the compressor and
remove compressor from the coach through the right rear access door.
h. Set the compressor on a sturdy work surface.
4-8T-312
Page 43
4.12.2 Re--installing the Compressor
NOTES
1. The service replacement 05G compressors are sold without shutoff valves. Valve pads are installed in their place. The optional unloaders are not supplied, as the cylinder heads are shipped with plugs. The customer should retain the original unloader valves for use on the replacement compressor.
2. Thepistonplugthatisremovedfromthe replacement compressor head must be installed in the failed compressor if returning for warranty.
3. Do not interchange allen head capscrews that mount the piston plug and unloader; they are not interchangeable.
4. Check oil level in service replacement compressor. (Refer to paragraphs 1.3 and
4.12.4)
d. Re--install and tension the compressor drive belt. e. Unlock and turn main battery disconnect switch to ON
position..
f. Attach two lines (with hand valves near vacuum
pump) to the suction and discharge service valves.
g. Fully backseat (open counterclockwise) both suction
and discharge service valves.
h. Remove vacuum pump lines and install manifold
gauges.
i. Start unit and check refrigerant level. (Refer to
paragraph 4.7.1)
j. Check compressor oil level. (Refer to paragraph
4.12.4) Add or remove oil if necessary.
k. Check compressor unloader operation.
4.12.3 Compressor Unloaders
Although the electric unloaders are non--adjustable, they will require some periodic maintenance. Service kits are available for repair of the electric unloaders solenoid and stem assemblies.
To check the unloaders proceed as follows:.
a. Ensure that the compressor is fully loaded. Heat the
interior of the coach if necessary.
5. Service replacement compressors are supplied with a suction filter sock for initial startup. Ensure the filter sock is installed and removed in accordance with the instructions furnished.
a. Remove the three socket head capscrews from both
unloader valves on the side heads of the 05G compressor. Remove the unloader valve and bypass piston assembly , keeping the same capscrews with the assembly. (See Figure 4-8) The original unloader valve must be transferred to the replacement compressor. The plug arrangement removed from the replacement is installed in the original compressor as a seal. If piston is stuck, it may be extracted by threading a socket head capscrew into top of piston. A small T eflon seat ring at the bottom of the piston must be removed.
COMPRESSOR
HEAD
GASKET
BYPASS
PISTON
PLUG
SPRING
FLANGE
COVER
CAPSCREWS
(NOT INTERCHANGEABLE WITH
CONTROL VALVE SCREWS)
Figure 4 -8. Removing Bypass Piston Plug
b. Remove the high pressure switch and pressure
transducer assemblies and install on replacement compressor after checking switch operation.
c. Install compressor in unit by performing steps c.
through g. in reverse sequence. It is recommended that new locknuts be used when replacing compressor. Install new gaskets on service valves and tighten bolts uniformly.
12
1
2
11
10
9
3
4
5
8
6
7
1. Electric Unloader Val ve
2. Suction Service Valve Charging Port
3. Suction Service Val ve
4. Clutch
5. Oil Fill Plug
7. Oil Drain Plug
8. Oil Level Sight Glass
9. Oil Pump
10. O’Ring 1 1. Discharge Service
Val ve
12. Service Port
6. Bottom Plate
Figure 4-9. Model O5G Compressor
b. Connect manifold guages to the compressor. c. Slowly frontseat the suction valve until 26 psig shows
on the suction guage. The first unloader should energize (check for magnetism at the unloader coil) increasing suction pressure by 3 to 5 psig.
d. Slowly open the suction valve until the suction gauge
reads 32 psig. The first unloader should de--energize decreasing suction pressure by 3 to 5 psig to show it is operating properly.
e. To check the second unloader, continue to frontseat
the suction valve until 21 psig shows on the suction
4-9 T-312
Page 44
guage. The second unloader should energize (check for magnetism at the unloader coil) increasing suction pressure by 3 to 5 psig.
f. Slowly open the suction valve until the suction guage
reads 28 psig. The first unloader should de--energize decreasing suction pressure by 3 to 5 psig to show it is operating properly.
g. Back seat the suction service valve, remove the
guage(s) to resume normal operation.
4.12.4 Compressor Oil Level
NOTE
The compressor should be fully loaded (six cylinder operation); the unit should be fully charged and the compressor crankcase should be warm to the touch.
a. Start the unit and allow the system to stabilize.
b. Check the oil sight glass on the compressor to ensure
that no foaming of oil is present after 20 minutes of operation. If oil is foaming excessively after 20 minutes of operation, check the refrigerant system for flood-back of liquid refrigerant. Correct this situation before proceeding.
c. Check the level of oil in oil level sight glass
immediately after shutting down the compressor. The lowest level visible should be at the bottom of the sightglass and the highest level should be at the middle of the sight glass. (See Figure 4-9)
4.12.5 Adding Oil with Compressor in System
Two methods for adding oil are: the oil pump method and closed system method.
NOTE
Special care must be taken when working with POE oil that is used with HFC refrigerants such as R--134a, as POE oil is very hygroscopic. (POE oil will easily absorb water.) Do not leave POE oil containers open to the atmosphere.
4.12.5.1. Oil Pump Method
a. One compressor oil pump that may be purchased is a
Robinair part no. 14388. This oil pump adapts to one U.S. gallon (3.785 liters) metal refrigeration oil container and pumps 2-1/2 ounces (72.5 milliliters) per stroke when connected to the suction service valve port. Also, there is no need to remove pump from can after each use.
b. When the compressor is in operation, the pump
check valve prevents the loss of refrigerant while allowing servicemen to develop sufficient pressure to overcome the operating suction pressure to add oil, as necessary.
c. Backseat suction service valve and connect oil
charging hose to port. Crack open the service valve and remove air from the oil hose at the oil pump. Add oil as necessary.
NOTE
Allow time (at least 60 seconds) for the oil to flow thru to the crankcase and show on the sightglass.
4.12.5.2. Closed System Method
a. Install manifold gauge set. (See Figure 4-3) b. Unplug the suction pressure transducer (SPT). c. Frontseat the compressor suction service valve by
turning clockwise.
d. Start the unit and run in cooling until 10 ”/hg (25.4
cm/hg) of vacuum is reached. Shut the system down and tag out system power source.
e. Frontseat the compressor discharge service valve
and wait 5 minutes to verify vacuum is maintained.
f. Remove the crankcase oil fill plug on the side of the
crankcase.
g. Replace the crankcase oil fill plug with a Carrier
Service Parts no. OTBO889 fitting. This fitting has a 1/4 inch flare access port with a shrader valve.
h. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of manifold gauge set.
CAUTION Care Must Be Taken To Ensure That The Manifold Common Connection Remains Immersed In Oil At All Times Or Air And Moisture Will Be Drawn Into The System.
i. Connect a refrigerant hose with a shrader depressor
to the fitting described in step g. above, put the other end of the hose in a fresh oil container.
j. Evacuate the compressor and observe the oil level in
the compressor crankcase. When the desired oil
level is reached, disconnect the hose from the fitting. k. Reinstall the crankcase oil fill plug. l. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of
manifold gauge set. Evacuate system to 500
microns. Close off pump valve, isolate vacuum gauge
and stop pump. Wait 5 minutes to verify that vacuum
holds. m.Once vacuum is maintained, backseat compressor
service valves and disconnect manifold gauge set. n. Reconnect the suction pressure transducer(SPT).
4.12.6 Adding Oil to Service Replacement
Compressor
Service replacement compressors may or may not be shipped with oil.
If the replacement compressor is shipped without oil, add oil through the oil fill plug. (See Figure 4-9)
4.12.7 Removing Oil from the Compressor:
a. If the lowest oil level observed in paragraph 4.12.4,
step c., is above middle of the sight glass on
compressor crankcase, oil must be removed from the
compressor by performing the following procedure. If
lowest oil level visible is below bottom of the
sightglass, oil must be added to the compressor by
following the procedure in paragraph 4.12.5.
4-10T-312
Page 45
b. Close (frontseat) suction service valve and pump unit
Resi
O
h
downto3to5psig(21to34kPa).Reclaim remaining refrigerant.
NOTE
If oil drain plug is not accessible, it will be necessary to extract oil through the oil fill plug with a siphon tube.
WARNING
EXTREME CARE MUST BE TAKEN TO ENSURE THAT ALL THE REFRIGERANT HAS BEEN REMOVED FROM THE COMPRESSOR CRANKCASE OR THE RESULTANT PRESSURE WILL FORCIBLY DISCHARGE COMPRESSOR OIL.
c. Remove the oil drain plug on the bottom plate of the
compressor and drain the proper amount of oil from the compressor. Replace the plug securely back into the compressor.
d. Repeat step a. to ensure proper oil level.
Table 4 -3. Temperature Sensor
(AT, TSC, TSD and TSR) Resistance
Temperature
_F _C
stanceIn
ms
-- 2 0 --28.9 165,300
-- 1 0 --23.3 117,800
0
10 --12.2
--17.8 85,500
62,400 20 -- 6 . 7 46,300 30 -- 1 . 1 34,500 32
0
32,700
40 4.4 26,200 50 10.0 19,900 60 15.6 15,300 70 21.1 11,900 77 25 10,000 80 26.7 9,300 90 32.2 7,300
100 37.8 5,800 110 43.3 4,700 120 48.9 3,800
NOTE
This system is equipped with three temperature sensors, two located in the return air ducts inside the coach, the third sensor is located in the condenser section. The two inside sensors are wired in parallel and together send an averaged signal to the controller. If one of these sensors fails the control function will continue with the remaining sensor. The sensor located in the condenser section reads outdoor temperature.
4.14 HUMIDITY SENSOR CHECKOUT
a. Use a sling psychrometer or similar device to check
relative humidity inside the coach.
NOTE
System can be shut down but 5 vdc power must be applied to the humidity sensor to enable checking.
b. Measure voltage across the sensor and compare to
values in Table 4-4 for the measured relative humidity. A reading within two percent of the values in the table would be considered good.
c. At least one sensor lead must be disconnected from
the controller before any reading can be taken. Not doing so will result in a false reading. Two preferred methods of determining the actual test temperature at the sensor are an ice bath at 32_F (0_C) and/or a calibrated digital temperature meter.
d. If the driver display indicates that temperature at
sensor is --40_F (--40_C), sensor could be open. If driver display indicates that temperature at sensor is 127_F (52.8_C), sensor could be shorted.
Table 4 -4. Humidity Sensor (HS) Voltage
%RH Volt age %RH Vol tage %RH Vo ltag e
30 0.990 55 1.815 80 2.640 35 1.155 60 1.980 85 2.805 40 1.320 65 2.145 90 2.970 45 1.485 70 2.310 95 3.168 50 1.650 75 2.475
4.15 SUCTION AND DISCHARGE PRESSURE TRANSDUCER CHECKOUT
4.13 TEMPERA TURE SENSOR CHECKOUT
a. An accurate ohmmeter must be used to check
resistance values shown in Table 4-3.
b. Due to variations and inaccuracies in ohmmeters,
thermometers or other test equipment, a reading within two percent of the chart value would be considered good. If a sensor is bad, the resistance value would usually be much higher or lower than the value given in the Table 4-3.
NOTE
1. System must be operating to check transducers.
2. Both transducers are mounted on the compressor
a. With the system running, use the driver display or
manifold gauges to check suction and/or discharge pressure(s).
4-11 T-312
Page 46
b. Use a digital volt-ohmmeter to measure voltage
across the transducer and compare to values in Table 4-5. A reading within two percent of the values in the table would be considered good.
Table 4-5. Suction and Discharge Pressure
Transducer (SPT and DPT) Voltage
Psig Vo l tag e Psig Volt age Psig Voltage
20” 0.369 105 1.495 220 2.622 10” 0.417 110 1.544 225 2.671
0 0.466 115 1.593 230 2.720
5 0.515 120 1.642 235 2.769 10 0.564 125 1.691 240 2.818 15 0.614 130 1.740 245 2.867
20
0.663 135 1.789 250 2.916
25 0.712 140 1.838 255 2.965 30 0.761 145 1.887 260 3.014 35 0.810 150 1.936 265 3.063 40 0.858 155 1.985 270 3.112 45 0.907 160 2.034 275 3.161 50 0.956 165 2.083 280 3.210 55 1.007 170 2.132 285 3.259 60 1.054 175 2.181 290 3.308 65 1.103 180 2.230 295 3.357 70 1.152 185 2.279 300 3.406 75 1.204 190 2.328 305 3.455 80 1.250 195 2.377 310 3.504 85 1.299 200 2.426 315 3.553 90 1.348 205 2.475 320 3.602 95 1.397 210 2.524 325 3.651
100 1.446 215 2.573 330 3.700
d. Remove blower transitions ducts. e. Remove the four bolts securing the evaporator motor
mounting plate, motor and blower housing assembly to the bottom panel.
f. Remove motor and blower wheel assembly by sliding
out of evaporator housing.
g. Repair or replace any defective component(s), as
required.
h. Replace by reversing steps b. thru f.
4.18 ACCESSING MAIN EVAPORATOR MOTOR BRUSHES
a. Turn main battery disconnect switch to OFF position
and lock. b. Remove access door. (Refer to 4.17.b.)
c. Disconnect electrical connections to the motor. d. With a marker, trace the outline of the motor on the
motor plate. e. Remove the four brush access doors on the motor.
f. Service two brushes (top front and top rear). g. Remove the four bolts securing the evaporator motor
to the mounting plate. h. Rotate the motor to gain access to the lower front
brush. i. Rotate the motor the opposite way to gain access to
the lower rear brush. j. Rotate the motor back to its feet and position back to
its original position guided by the outline drawn in step
d. k. Re--secure the motor with the four bolts removed in
step g. Check fan rotation, insuring that the fan
wheels do not make contact with the fan housings.
l. Complete the procedure by performing steps a. thru
c. in reverse.
4.16 REPLACING SENSORS AND TRANSDUCERS
a. Turn main battery disconnect switch to OFF position
and lock.
b. Tag and disconnect wiring from defective sensor or
transducer.
c. Remove and replace defective sensor or transducer .
d. Connect wiring to replacement sensor or transducer.
e. Checkout replacement sensor or transducer. (Refer
to paragraph 4.13, 4.15 or 4.14, as applicable.)
4.17 SERVICING MAIN EVAPORATOR BLOWER ASSEMBLY
a. Turn main battery disconnect switch to OFF position
and lock.
b. Remove access door located in the #3 baggage
compartment. To remove the access door, unlatch, then open the door enough to slide the hinge pins out of the pin brackets.
c. Disconnect electrical connections to the motor.
4.19 SERVICING MOTOR BRUSHES
If the brushes are broken, cracked, severely chipped, or worn to 1/3 their original length, replace them.
a. Remove the four brush access doors on the motor.
b. With fingers or a suitable hook, lift the brush spring
end up so the brush may slide up and out of the holder. Loosen the brush screw to remove the brush shunt terminal. Remove the brush.
c. T o replace, lift the brush spring and place the brush in
the holder. Position the end of the spring on top of the brush.
d. Connect the brush shunt terminal to its proper
crossover with the brush screw assembled loosely.
NOTE
Assure positioning of the brush to permit the brush shunt to travel freely in the holder slot as the brush wears. If the brush hangs up, commutator damage and motor failure will result
e. Tighten screw.
4-12T-312
Page 47
4.20 SERVICING THE MAIN EVAPORA T OR AND HEATER COIL
j. Remove condenser module by sliding out on
mounting rails.
a. Drain engine coolant from the heater coil.
b. Pump down low side of the HVAC system. (Refer to
paragraph 4.4.1.)
c. Remove remaining refrigerant. (Refer to paragraph
4.4.)
d. Remove the evaporator motor by following paragraph
4.17 steps a. thru f.
e. Disconnect all remaining electrical connections,
move wires out of the way.
f. Remove the evaporator electrical panel assembly.
g. Remove the liquid line (3 connection points) and the
discharge line (2 connection points) that pass thru the evaporator and connect to the evaporator.
h. Disconnect and remove the suction line.
i. Disconnect and remove the heater hoses.
j. Remove the door frame surrounding the evaporator
enclosure.
k. Remove the four bolts that secure the coil bracket to
the drain pan. Leave the coil bracket bolted to the evaporator coil until the coil has been removed from the coach.
WARNING
WHEN MOVING THE COIL CARE MUST BE TAKEN TO AVOID PERSONAL INJUR Y BECAUSE OF THE WEIGHT OF THE COIL.
l. Brace the top of the coil hold it in position.
m.Remove the four bolts that secure the top of the coil to
the evaporator housing.
n. Rotate the top of the coil till the coil is horizontal and
slide out of the evaporator housing.
o. Re-install by performing the above procedure in
reverse.
4.21 REMOVING THE CONDENSER ASSEMBLY
4.22 SERVICING THE CONDENSER COIL
a. Remove the condenser assembly from the coach.
(Refer to paragraph 4.21) b. Remove side panel (with control box). c. Remove front shroud and panel assemblies. d. Unbraze coil/tubing connections and roll front module
assembly forward to provide clearance for coil
removal. e. Remove condenser coil. f. Repair or replace the condenser coil. g. Re-install by performing the above procedure in
reverse.
4.23 SERVICING THE CONDENSER MOTOR
a. Turn main battery disconnect switch to OFF position
and lock. b. Remove appropriate front condenser grill. c. Remove fan blade, secure the shaft key to the motor
shaft or fan hub slot. d. Disconnect the wires to the motor. e. Remove the four motor base mounting screws. f. Remove the motor and place on workbench. g. Repair or replace defective component(s), as
required. h. For brush inspection/replacement refer to paragraph
4.19.
i. Re-install by performing the above procedure in
reverse.
4.24 SERVICING THE DRIVER CONTROL BOX
The driver control box is located behind the return air panel below the passenger side dash and under the right headlight. (See Figure 4-10.) Remove the return air panel by removing the eight screws holding the panel in place. Remove and service the control box by performing the following procedure:
a. Remove two side access panels from rear of the last
baggage bay.
b. Remove and reclaim the entire refrigerant charge.
(Refer to paragraph 4.4.2.)
c. Turn main battery disconnect switch to OFF position
and lock.
d. Disconnect all electrical leads to the module.
e. Disconnect refrigerant lines to the module.
f. Remove the door latch stud to the right side of the
condenser compartment.
g. Remove the front panel and the eight screws
fastening the condenser to the coach.
h. Remove the stabilizing bracket on the top of the
condenser.
i. Remove the eight screws securing the condenser
door hinges to the frame.
HEADLIGHT DRIVER CONTROL BOX
Figure 4 -10. Removing Driver Control Box
a. Turn main battery disconnect switch to OFF position
and lock.
4-13 T-312
Page 48
b. Remove the power wire from the power stud and the
connector from the box.
c. Remove the 1/4-inch capscrew at the upper right
cover of the box. Pull the box laterally approximately 3/4-inch to the right to remove it from the pocket.
d. Rotate box counterclockwise 90 degrees as shown in
Figure 4-10 and carefully lift the box out.
e. Repair or replace defective components, as
necessary.
f. Re-install the driver control box by reversing the
above procedure.
4.25 SERVICING THE DRIVER EVAPORATOR
4.25.1 Access Cover Removal
a. Remove stepwell access cover and disconnect
2-inch flex hose adapter.
b. Using a flat screwdriver, unfasten three 1/4 turn
fasteners from access cover on driver evaporator assembly.
c. Open driver storage compartment and remove plug in
sheet metal.
d. With screwdriver, unfasten the last 1/4 turn fastener.
e. Draw access cover towards the rear and slide to the
right.
4.25.2Blower Removal
a. Disconnect plugs and speed control from the blower.
b. Undo latch and push the blower towards the rear.
c. Drop the blower down and remove.
4.25.3 Air filter Removal
a. With the access cover removed, slide right hand side
air filter towards center and turn right corner past edge.
b. Slide left hand side filter to the right and repeat as
above.
c. Clean/replace filter and re-install.
4.25.4 Removal of Evaporator/Heater Coil Assembly
a. Clamp off silicon hose close to the input and output
end of the heater core.
b. Disconnect hose clamps and separate hose from
fitting.
c. Pump down the refrigerant system. (Refer to
paragraph 4.4.1)
d. Disconnect liquid line solenoid valve plug. e. Disconnect expansion valve thermal bulb attached to
the 7/8-inch copper tube. f. Disconnect 7/8 and 3/8-inch copper lines.
g. Remove screws that attach the heater core to the
unit.
h. Lift evaporator coil up and pull towards the rear for
removal.
4.25.5 RAM Air Actuator Removal
a. Disconnect the plug.
b. Remove the no. 10 screw from the end of the spring
on the RAM air actuator.
4.26 SERVICING THE PARCEL RACK
EVAPORATOR
4.26.1 Motor Removal
a. Disconnect the motor wires from the connector.
b. Remove the two bolts from the motor mount and
remove the motor.
c. Remove the blower and motor assembly.
4.26.2 Removal of Parcel Rack Evaporator Coil
a. Pump down the refrigerant system. (Refer to
paragraph 4.4.1)
b. Remove the side access panel. c. Disconnect expansion valve thermal bulb attached to
the 7/8-inch copper tube. d. Disconnect 7/8 and 3/8-inch copper lines.
e. Lift evaporator coil up and push towards the rear for
removal.
4-14T-312
Page 49
Table 4-6. R-134a Temperature - Pressure Chart
Temperature
F C
-- 4 0 -- 4 0 14.6 37.08 0.49
.35 .37 12.3 31.25 0.42
-- 3 0 -- 3 4 9.7 24.64 0.33
-- 2 5 -- 3 2 6.7 17.00 0.23
-- 2 0 -- 2 9 3.5 8.89 0.12
-- 1 8 -- 2 8 2.1 5.33 0.07
-- 1 6 -- 2 7 0.6 1.52 0.02
Temperature Pressure
F C
-- 1 4 -- 2 6 0.4 0.03 0.03
-- 1 2 -- 2 4 1.2 0.08 0.08
-- 1 0 -- 2 3 2.0 0.14 0.14
-- 8 -- 2 2 2.9 0.20 0.20
-- 6 -- 2 1 3.7 0.26 0.26
-- 4 -- 2 0 4.6 0.32 0.32
-- 2 -- 1 9 5.6 0.39 0.39
0 -- 1 8 6.5 0.46 0.45
2 -- 1 7 7.6 0.53 0.52
4 -- 1 6 8.6 0.60 0.59
6 -- 1 4 9.7 0.68 0.67
8 -- 1 3 10.8 0.76 0.74
10 -- 1 2 12.0 0.84 0.83
12 -- 11 13.2 0.93 0.91
14 -- 1 0 14.5 1.02 1.00
16 -- 9 15.8 1.11 1.09
18 -- 8 17.1 1.20 1.18
20 -- 7 18.5 1.30 1.28
22 -- 6 19.9 1.40 1.37
24 -- 4 21.4 1.50 1.48
26 -- 3 22.9 1.61 1.58
“/hg Kg/cm@@@@ Bar
Psig Kg/cm@@@@ Bar
Vacuum
Temperature Pressure
F C
28 -- 2 24.5 1.72 1.69
30 -- 1 26.1 1.84 1.80
32 0 27.8 1.95 1.92
34 1 29.6 2.08 2.04
36 2 31.3 2.20 2.16
38 3 33.2 2.33 2.29
40 4 35.1 2.47 2.42
45 7 40.1 2.82 2.76
50 10 45.5 3.20 3.14
55 13 51.2 3.60 3.53
60 16 57.4 4.04 3.96
65 18 64.1 4.51 4.42
70 21 71.1 5.00 4.90
75 24 78.7 5.53 5.43
80 27 86.7 6.10 5.98
85 29 95.3 6.70 6.57
90 32 104.3 7.33 7.19
95 35 114.0 8.01 7.86
100 38 124.2 8.73 8.56
105 41 135.0 9.49 9.31
110 43 146.4 10.29 10.09
115 46 158.4 11.1 4 10.92
120 49 171.2 12.04 11.80
125 52 184.6 12.98 12.73
130 54 198.7 13.97 13.70
135 57 213.6 15.02 14.73
140 60 229.2 16.11 15.80
145 63 245.6 17.27 16.93
150 66 262.9 18.48 18.13
155 68 281.1 19.76 19.37
Psig Kg/cm@@@@ Bar
4-15 T-312
Page 50
SECTION 5
ELECTRICAL SCHEMATIC DIAGRAMS
5.1 INTRODUCTION
This section contains Electrical Schematic Diagrams covering the Models listed in Table 1-1. Contact your Carrier Transicold service representative or call the technical hot line at 800--450--2211 for a copy of the schematic for your specific model.
5-1
T-312
Page 51
ATHRUK
1 2 3
LTHRUY
P ACKARD CONNECTOR
Figure 5-1. Electrical Schematic Diagram Legend and Symbols
(Based On Drawing No. 62-10907 Rev ---)
T-312
COACH INTERFACE
CONNECTOR
5-2
Page 52
CONDENSER
**DRIVER CONTROL BOX
MAIN EVAPORATOR
DRIVER EVAPORATOR
PARCEL RACK (ROAD SIDE)
PARCEL RACK (CURB SIDE)
NOTE
In 2003, early production units were retrofitted with diodes. If servicing a unit that is not wired as shown above, the unit should be retrofitted. Contact Carrier Service Engineering.
See Figure 5-1 for legend and symbols.
Figure 5-2. Electrical Schematic Diagram, Sheet 1 of 2
(Based On Drawing No. 62-10907 Rev ---)
5-3
T-312
Page 53
Figure 5-3. Electrical Schematic Diagram, Sheet 2 of 2
(Drawing No. 62-10907 Rev---)
T-312
5-4
Page 54
Figure 5-4. Electrical Schematic Diagram
(Contact vehicle manufacturer for a specific diagram)
5-5
T-312
Page 55
INDEX
A
Air Conditioning Refrigerant Cycle, 1-12
AirFilter,3-6,4-14
C
Checking For Noncondensibles, 4-6
Checking High Pressure Switch, 4-7
Checking Refrigerant Charge, 4-6
Compressor, 1-3, 1-4
Compressor Oil Level, 4-10
Compressor Re--install, 4-9
Compressor Removal, 4-8
Compressor Unloaders, 4-9
Condenser Assembly, 1-2, 4-13
Condenser Coil, 4-13
Condenser Motor, 4-13
H
Heating Flow Cycle, 1-11
Humidity Control, 2-5
Humidity Sensor, 4-11, 4-12
I
Installing Manifold Guages, 4-2
Introduction, 1-1
M
Main Control Box, 1-7
Main Controller Auto Control Sequence, 2-4
Main Evaporator Assembly , 1-6
Main Evaporator Blower Assembly, 4-12
Main Evaporator Or Heater Coil, 4-13
Maintenance Schedule, 4-1
Microprocessor Error Message Definition, 3-1
D
Display Error Message Definition, 3-1
Driver A/C Switch, 1-9, 2-2
Driver Control Box, 4-13
Driver Display Alarm Message, 3-1
Driver Display Panel, 1-8, 2-1
Driver Evaporator, 4-14
Driver Evaporator, 1-5
Driver Evaporator--Blower, 4-14
E
Electrical Specifications -- Controls, 1-9
Electrical Specifications -- Motors, 1-9
Electronic Control Data Flow, 1-14
Evacuation And Dehydration, 4-4
Evaporator Assemblies, 1-4
Evaporator Coils, 1-12
F
Filter--Drier, 4-7
O
Oil Charge, 1-9
Oil: Adding Charge, 4-10
Operating Controls, 1-8
P
Parameter Codes, 3-4
Parcel Rack Evaporator, 4-14
Parcel Rack Evaporator, 1-5
Parcel Rack On/Off, 1-8, 2-2
Pressure Transducer, 4-11, 4-12
R
Refrigerant Charge, 1-9, 4-6
Refrigerant Charge Removal, 4-3
Refrigerant Leak Check, 4-4
Refrigerant Removal From Compressor, 4-3
Refrigerant Service Connections, 4-5
Refrigeration System Components, 1-9
Replacing High Pressure Switch, 4-7
Index-1 T-312
Page 56
INDEX
S
Safety Devices, 1-10
Safety Summary , General, i
Schematic Diagram, 5-3, 5-4, 5-5
Servicing Motor Brushes, 4-12
Suction and Discharge Service Valves, 4-1
Superheat -- Check/Measure, 4-8
System Pumpdown, 4-2
System Service, 4-1
T
Temperature Pressure Chart, 4-15
Temperature Sensor, 4-11
Thermostatic Expansion Valve, 4-7
TroubleShooting, 3-1
Troubleshooting Proceedures, 3-5
Index-2T-312
Loading...