Carrier MAQB303 User Manual

Page 1
40MAQ / 38MAQ High- Wall Ductless Split System Sizes 09 to 30
Product Data
INDUSTRY LEADING FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN BUDGET LIMITS, ENERGY SAVINGS AND COMFORT.
The 38/40MAQ series ductless split systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the wall, near the ceiling. This selection of fan coils permits creative solutions to design problems such as:
S Add- ons to current space (an office or family room
addition)
S Special space requirements
S When changes in the load cannot be handled by the
existing system.
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.
Page 2
LOW SOUND LEVELS
When noise is a concern, the ductless split systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.
When sound ordinances and proximity to neighbors demand quiet operation, the 38MAQ unit is the right choice: The advanced, horizontal airflow design distributes air more evenly over the coil.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since 38MAQ units can be installed close to an outside wall, coils are protected from vandals and severe weather.
FAST INSTALLATION
This compact ductless split system is simple to install. A mounting bracket is standard with the indoor units and only wire and piping need to be run between indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in the home or workplace. This makes the 38/40MAQ ductless split systems the equipment of choice, especially in retrofit situations.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel on outdoor units provides immediate access to the control compartment, providing a service technician access to check unit operation. In addition, the draw- thru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced due to easy- to- use cleanable filters. In addition, these high wall systems have extensive self- diagnostics to assist in troubleshooting.
BUILT- IN RELIABILITY
Ductless split system indoor and outdoor units are designed to provide years of trouble- free operation.
The high wall indoor units include protection against freeze- up and high evaporator temperatures on heat pumps.
The condensing units on heat pumps are protected by a three minute time delay before the compressor will start the over- current protection and the high temperature protection.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year- round comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The ductless split system design allows individual room heating or cooling when required. There is no need to run large supply- air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts.
EASY- TO- USE CONTROLS
The high- wall units have microprocessor-based controls to provide the ultimate in comfort and efficiency. The user friendly wireless remote control provides the interface between user and the unit.
ACCESSORIES
Customizing these ductless split systems to your application is easily accomplished.
Adding a condensate pump accessory to the high wall fan coil provides installation flexibility.
OPTIONAL WIRED CONTROLLER
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating & Refrigeration Institute), and ETL.
2
Page 3
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
40 MA 309
40= FAN COIL UNIT
MA =MODEL
SYSTEM TYPE Q =HEATPUMP
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B=1:1
NOMINAL CAPACITY 09 -3/4TON 12 -1TON 18 -1-1/2TONS 24 -2TONS 30 -2-1/2TONS
BQB
--
VOLTAGE 1 =115-1-60 3 = 208/230 - 1 - 60
NOT USED
INDOOR FAN COIL TYPE
B= HIGH- WALL
38 MA 309
38 = OUTDOOR UNIT
MA =MODEL
SYSTEM TYPE Q =HEATPUMP
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B=1:1
NOMINAL CAPACITY 09 -3/4TON 12 -1TON 18 -1-1/2TONS 24 -2TONS 30 -2-1/2TONS
OUTDOOR UNIT
BQ-
--
VOLTAGE 1 =115-1-60 3 = 208/230 - 1 - 60
NOT USED
UNIT TYPE
- = OUTD OOR UNIT
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
3
Page 4
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting Brackets S Low Voltage Controls S
Comfort Features
Microprocessor Controls S Wired Remote Control A Wireless Remote Control S Automatic Horizontal Air Sweep S Air Direction Control S Auto Restart Function S Cold Blow Protection On Heat Pumps S Freeze Protection Mode On Heat Pumps S Turb o Mod e S Silence Mode S Auto Changeover On Heat Pumps S
Follow Me S
Energy Saving Features
Sleep Mode S Stop/Start Timer S
46° F Heating Mode (Heating Setback)
Safety And Reliability
3MinuteTimeDelayForCompressor S Over Current Protection For Compressor S Indoor Coil Freeze Protection S Indoor Coil High Temp Protection in Heating Mode S Condenser High Temp Protection in Cooling Mode S
Ease Of Service And Maintenance
Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S
Application Flexibility
Condensate Pumps A Crankcase Heater S
Legend
SStandard A Accessory
S
INDOOR UNITS
On high wall fan coils, the condensate pump has a lift capability of 12 ft (3.6 m) on the discharge side with the pump mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump is remote mounted. The pump is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
NOTE: An external 115v power source will be required to run the pump on unit sizes 9k and 12k.
OUTDOOR UNITS
Crankcase Heater
Standard on all unit sizes. Heater clamps around compressor oil stump.
Fig. 1 – Condensate Pump Accessory
4
Page 5
DIMENSIONS - INDOOR
Unit Size W in (mm) D in (mm) H in (mm) Operating Weight lb (kg)
9K/12K 32.9 (835) 7.8 (198) 11.0 (280) 19.2 (8.7)
18K 39.0 (990) 8.6 (218) 12.4 (315) 26.5 (12.0)
24K/30K 46.7 (1186) 10.2 (258) 13.4 (343) 40.8 (18.5)
DIMENSIONS - OUTDOOR
Fig. 2 – Indoor unit
Fig. 3 – Outdoor unit
Model W in (mm) D in (mm) H in (mm) L1 in (mm) L2 in (mm)
9K/12K 32.0 (810) 12.2 (310) 22.0 (558) 20.9 (530) 11.4 (290) 82.5 (37.4)
18K 32.3 (845) 12.6 (320) 27.6 (700) 22.1 (560) 13.2 (335) 102.5 (46.5) 24K 37.2 (945) 15.6 (395) 31.9 (810) 25.1 (640) 15.9 (405) 137.6 (62.4) 30K 37.2 (945) 15.6 (395) 31.9 (810) 25.1 (640) 15.9 (405) 157.6 (71.5)
Operating
Weight lb (kg)
5
Page 6
CLEARANCES - INDOOR
5
"
(0.13m)
min.
CEILING
6" (0.15m) min.
(1.8m)
6'
FLOOR
Fig. 4 – Indoor Unit Clearance
5
"
(0.13m)
min.
CLEARANCES - OUTDOOR
A
D
UNIT
A 24 (609) B 24 (609) C 24 (609) D 4 (101) E 4 (101)
B
Air-outlet
Fig. 5 – Clearances Outdoor
Air-inlet
E
C
Minimum Value
in. (mm)
6
Page 7
SPECIFICATIONS - HEAT PUMP UNITS (MAQ SERIES)
Size 9 12 9 12 18 24 30
System
Perfor­mance
Controls
Operating
Range
Piping
Refrigerant
Outdoor
Coil
Indoor Coil
Compres-
sor
Electrical
Outdoor
Indoor
Condensing unit above or below indoor unit
Outdoor Model 38MAQB09---1 38MAQB12---1 38MAQB09---3 38MAQB12---3 38MAQB18---3 38MAQB24---3 38MAQB30---3
Indoor Model 40MAQB09B--1 40MAQB12B--1 40MAQB09B--3 40MAQB12B--3 40MAQB18B--3 40MAQB24B--3 40MAQB30B--3
Energy Star YES YES YES YES YES YES NO
Cooling Rated Capacity Btu/h 9,000 12,000 9,000 12,000 17,500 23,000 30,000
Cooling Cap. Range Min - Max Btu/h 3500~11000 4000~13000 3500~11000 4000~13000 4500~18000 5500~23500 8000~30500
Heating Cap. Range Min - Max Btu/h 4,500~11,500 5,000~13,500 4,500~11,500 5,000~13,500 5,500~19,000 6,000~26,000 9,000~34,000
Wireless Remote Controller (°F/°CConvertible) Standard
Wired Remote Controll er (°F/°C Convertible) Optional
Cooling Outdoor DB Min - Max °F 4~122 4~122 4~122 4~122 4~122 4~122 4~122 Heating Outdoor DB Min - Max °F 4~86 4~86 4~86 4~86 4~86 4~86 4~86
Heating Indoor DB Min -Max °F 32~86 32~86 32~86 32~86 32~86 32~86 32~86
Pipe Connection Size - Li quid In. 1/4 1/4 1/4 1/4 1/4 3/8 3/8
Pipe Connection Size - S uction In. 3/8 1/2 3/8 1/2 1/2 5/8 5/8
Sound Pressure (lowest to highest) dB(A) 27/34/42 27/34/42 27/34/42 27/34/42 33/40/46 39/45/50 39/45/50
SEER 23.5 21.5 23.5 21.5 19.5 20.0 16.5
EER 14.5 13 14.5 13 12.5 12.5 9.5
Heating Rated Capacity Btu/h 10,000 12,000 10,000 12,000 18,000 25,000 32,000
HSPF 10.0 10.0 10.0 10.0 9.6 10.0 9.6
COP W/W 3.36 3.22 3.66 3.36 3.36 3.22 2.92
Cooling Indoor DB Min -Max °F 63~90 63~90 63~90 63~90 63~90 63~90 63~90
Total Piping Length Ft. 82 82 82 82 98 98 164
DesignPressure PSIG 550 550 550 550 550 550 550 MeteringDevice CapillaryTube in Outdoor Unit
Fins per inch 21 21 21 21 18 18 17
Face Area (sq. ft.) Sq. Ft. 2.2 2.2 2.2 2.2 2.6 3.7 3.7
Fins per inch 20 20 20 20 20 18 18
Rated Current RLA 5.3 5.7 5.3 5.7 7.3 8.8 13.5
Voltage, Phase, Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Power Supply Indoor unit powered from outdoor unit
MOCP - Fuse Rating A. 20 20 15 15 20 25 30
Sound Pressure dB(A) 56 56 56 56 59 60 63
Number of Fan Speeds 4 4 4 4 4 4 4
Airflow (lowest to highest) CFM 210/290/360/380 210/300/360/380 210/290/360/380 210/300/360/380 310/450/650/680 520/620/780/870 520/620/780/870
Air throw Data Ft. 23 23 23 23 30 36 36
*
Piping Lift
Type R410A
Charge Lb. 2.76 2.76 2.76 2.76 4.19 5.18 6.62
Face Area Sq.Ft. 9.2 9.2 9.2 9.2 16.0 21.1 17.2
No. Rows 2 2 2 2 2 3 3
Circuits 4 4 4 4 6 8 6
No. Rows 2 2 2 2 2 3 3
Circuits 3 3 3 3 4 7 7
Type Hermetic Rotary DC Inverter Compressor
Model ASM98D1UFZA ASM108D1UFZA ASM98D1UFZA ASM108D1UFZA ASM135D23UFZ DA250S2C-30MT TNB306FPGMC-L
Oil Type VG74 VG74 VG74 VG74 VG74 VG74 FV50S
Oil Charge Fl. Oz. 12.5 12.5 12.5 12.5 15.2 27.7 36.2
MCA A. 15 15 15 15 15 15 20
Unit Width In. 31.9 31.9 .9 31.9 33.3 37.2 37.2
Unit Height In. 22.0 22.0 .0 22.0 .6 31.9 31.9
Unit Depth In. 12.2 12.2 .2 12.2 .6 15.6 15.6
Net Weight Lbs. 82.5 82.5 82.5 82.5 102.5 137.6 157.6
Airflow CFM 1200 1200 1200 1200 1390 2130 2130
Unit Width In. 32.9 32.9 32.9 32.9 39.0 46.7 46.7
Unit Height In. 11.0 11.0 11.0 11.0 12.4 13.4 13.4
Unit Depth In. 7.8 7.8 7.8 7.8 8.6 10.2 10.2
Net Weight Lbs. 19.2 19.2 19.2 19.2 26.5 40.1 40.1
Ft. 32 32 32 32 65 65 82
7
Page 8
COOLING PERFORMANCE DATA - 38/40MAQ (HEAT PUMP)
Model
38-40MAQ
09
(115V)
12
(115V)
09
(208-230V)
12
(208-230V)
18
(208-230V)
24
(208-230V)
30
(208-230V)
LEGEND
DB - Dry Bulb WB - Wet Bulb TC - Total Net Cooling Capacity (1000 Btu/hour) SC - Sensible Capacity (1000 Btu/hour) Input - Total Power (kW)
Indoor Conditions DB IndoorConditions WB (BTU/h) 77F(25C) 86F(30C) 95F(35C) 104F(40C) 113F(45C) 122F(50C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
69.8F(21C) 59F(15C)
75.2F(24C) 62.6F(17C)
80.6F(27C) 66.2F(19C)
89.6F(32C) 73.4F(23C)
Cooling Outdoor conditions (DB)
TC 7.43 7.83 9.74 8.38 6.11 5.11
SC 6.68 6.69 8.18 7.37 4.36 3.74
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 7.78 9.14 9.89 8.65 6.92 5.83
SC 3.58 8.11 6.27 5.52 4.85 4.29
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 8.21 9.22 10.41 9.27 7.32 6
SC 7.39 5.88 8.22 7.79 5.11 4.37
Input 0.35 0.75 0.82 0.81 0.75 0.75
TC 8.41 9.72 11.59 10.22 8.82 7.51
SC 3.68 5.76 6.9 6.2 5.55 5
Input 0.36 0.56 0.83 0.82 0.76 0.77
TC 8.21 11.75 11.42 9 7.85 6.68
SC 7.06 9.05 8.68 7.38 6.42 5.58
Input 0.38 0.8 1.04 0.87 0.82 0.81
TC 8.42 11.84 12.01 9.35 8.32 7.34
SC 7.28 8.69 8.66 7.62 6.53 5.81
Input 0.57 0.94 1.25 1.27 0.98 0.94
TC 8.81 11.95 12.23 9.69 8.87 7.95
SC 7.49 8.32 8.63 7.85 6.64 6.04
Input 0.39 0.75 1.06 0.89 0.85 0.82
TC 9.01 12.15 12.43 9.89 9.07 8.15
SC 7.7 8.53 8.84 8.06 6.85 6.25
Input 0.4 0.97 1.3 1.34 0.92 0.85
TC 7.41 7.82 9.73 8.34 6.12 5.1
SC 6.64 6.69 8.18 7.37 4.36 3.74
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 7.76 9.16 9.89 8.62 6.92 5.83
SC 3.58 8.11 6.27 5.52 4.85 4.29
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 8.21 9.22 10.41 9.27 7.32 6
SC 7.39 5.88 8.22 7.79 5.11 4.37
Input 0.35 0.75 0.82 0.81 0.75 0.75
TC 8.41 9.72 11.59 10.22 8.82 7.51
SC 3.68 5.76 6.9 6.2 5.55 5
Input 0.36 0.56 0.83 0.82 0.76 0.77
TC 8.21 11.75 11.42 9 7.85 6.68
SC 7.06 9.05 8.68 7.38 6.42 5.58
Input 0.38 0.8 1.04 0.87 0.82 0.81
TC 8.42 11.84 12.01 9.35 8.32 7.34
SC 7.28 8.69 8.66 7.62 6.53 5.81
Input 0.57 0.94 1.25 1.27 0.98 0.94
TC 8.81 11.95 12.23 9.69 8.87 7.95
SC 7.49 8.32 8.63 7.85 6.64 6.04
Input 0.39 0.75 1.06 0.89 0.85 0.82
TC 9.01 12.15 12.43 9.89 9.07 8.15
SC 7.7 8.53 8.84 8.06 6.85 6.25
Input 0.4 0.97 1.3 1.34 0.92 0.85
TC 12.58 15.24 16.25 11.04 8.32 6.78
SC 8.34 10.3 10.6 7.93 6.18 5.16
Input 0.58 0.93 1.53 1.2 1.42 1.32
TC 13.48 16.41 16.66 12.3 9.43 7.74
SC 8.85 10.94 11.35 8.62 6.87 5.91
Input 0.57 0.93 1.56 1.22 1.45 1.35
TC 14.43 18.04 18.37 13.35 9.97 7.96
SC 9.59 11.95 12.37 9.28 7.23 6.02
Input 0.57 0.94 1.59 1.24 1.48 1.38
TC 14.7 19.03 20.18 15.36 12.02 9.97
SC 9.08 11.72 12.5 9.69 7.85 6.89
Input 0.6 0.97 1.62 1.27 1.51 1.41
TC 19.5 20.69 21.43 18.05 14.27 13.32
SC 15.15 15.61 15.49 14.23 10.03 8.78
Input 1.2 1.88 2.29 2.14 1.9 1.86
TC 20.01 21.21 22.31 18.51 15.08 13.3
SC 15.25 15.71 15.59 14.33 10.13 8.88
Input 1.2 1.87 2.3 2.21 2.14 1.92
TC 20.54 21.75 23.21 18.98 15.91 13.3
SC 15.35 15.81 15.69 14.43 10.23 8.98
Input 1.21 1.86 2.31 2.26 2.16 1.93
TC 20.61 22.94 24.4 21.84 19.17 16.66
SC 15.58 16.04 15.92 14.66 10.46 9.21
Input 1.22 1.87 2.34 2.33 2.32 1.96
TC 27.33 27.43 27.51 22.77 18.29 17.32
SC 19.4 19.48 19.56 17.21 16.32 15.28
Input 2.28 3.29 3.63 3.11 2.35 2.25
TC 29.41 30.01 29.82 24.53 20.71 18.24
SC 19.95 20.47 20.07 17.73 17.24 16.29
Input 2.31 3.32 3.68 3.17 2.41 2.31
TC 31.57 32.68 32.21 26.37 23.2 19.21
SC 20.55 21.52 20.65 18.3 18.21 17.35
Input 2.35 3.35 3.74 3.23 2.47 2.38
TC 32.6 33.71 33.24 27.4 24.23 20.24
SC 20.9 21.87 21 18.65 18.56 17.7
Input 2.42 3.42 3.81 3.3 2.54 2.45
8
Page 9
HEATING PERFORMANCE DATA - - 38/40MAQ (HEAT PUMP)
Model
38-40MAQ
09(115V)
12(115V)
09
(208-230V)
12
(208-230V)
18
(208-230V)
24
(208-230V)
30
(208-230V)
LEGEND
DB - Dry Bulb WB - Wet Bulb TH - Total Net Heating Capacity (1000 Btu/hour) Input - Total Power (kW)
Heating Outdoor conditions (DB)
Indoor Conditions DB 53.6F(12C) 44.6F(7C) 39.2F(4C) 32F(0C) 24.8F(-4C) 19.4F(-7C) 17F(-8C) 5F(-15C)
59F(15C)
64.4F(18C)
69F(20.5C)
71.6F(22C)
59F(15C)
64.4F(18C)
69F(20.5C)
71.6F(22C)
59F(15C) TH 11.2 11.1 10.89 10.65 9.87 9.11 8.27 6.71
64.4F(18C)
69F(20.5C)
71.6F(22C)
59F(15C) TH 11.8 12.7 12.42 11.32 10.4 9.54 8.9 5.75
64.4F(18C) TH 12.1 12.7 12.32 11.34 10.32 9.32 8.81 6.14
69F(20.5C) TH 12.3 12.6 12.12 11.32 10.21 9.12 8.43 6.49
71.6F(22C) TH 11.1 12.4 12.01 11.21 10.01 9.02 8.21 6.01
59F(15C) TH 23.2 20.5 19.42 17.56 16.52 14.28 12.08 9.39
64.4F(18C) TH 22.4 20.1 18.66 16.89 16.05 13.94 12.06 9.16
69F(20.5C) TH 21.7 19.7 17.93 16.26 15.62 13.62 12.07 8.95
71.6F(22C) TH 21 19 17.23 15.56 14.92 12.92 11.37 8.25
59F(15C) TH 28.6 27.8 25.85 23.56 23.42 23.22 23.16 18.93
64.4F(18C)
69F(20.5C)
71.6F(22C)
59F(15C)
64.4F(18C)
69F(20.5C)
71.6F(22C)
TH 11.2 11.1 10.89 10.65 9.87 9.11 8.27 6.71
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
TH 11.1 10.8 10.65 10.54 9.63 8.84 8.01 5.46
Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
TH 10.8 10.6 10.48 10.32 9.43 8.55 7.95 4.29
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
TH 10.6 10.3 10.21 10.11 9.23 8.41 7.89 4.11
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
TH 11.8 12.7 12.42 11.32 10.4 9.54 8.9 5.75
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
TH 12.1 12.7 12.32 11.34 10.32 9.32 8.81 6.14
Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91
TH 12.3 12.6 12.12 11.32 10.21 9.12 8.43 6.49
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
TH 11.1 12.4 12.01 11.21 10.01 9.02 8.21 6.01
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
TH 11.1 10.8 10.65 10.54 9.63 8.84 8.01 5.46
Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
TH 10.8 10.6 10.48 10.32 9.43 8.55 7.95 4.29
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
TH 10.6 10.3 10.21 10.11 9.23 8.41 7.89 4.11
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
Input 1.58 1.49 1.48 1.58 1.46 1.4 1.35 1.21
Input 1.62 1.55 1.55 1.61 1.52 1.45 1.4 1.29
Input 1.67 1.62 1.63 1.65 1.58 1.5 1.45 1.38
Input 1.72 1.67 1.68 1.7 1.63 1.55 1.5 1.43
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
TH 27.6 27.6 24.52 23.54 23.4 22.52 20.45 17.45
Input 2.24 2.45 2.35 2.35 2.32 2.23 2.21 2.16
TH 29.1 29.3 26.75 24.63 22.98 21.85 19.61 16.38
Input 2.39 2.74 2.64 2.58 2.42 2.25 2.2 2.18
TH 26.9 27.5 24.21 23.41 22.54 21.67 19.54 16.24
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
TH 43 41.2 37.52 34.65 32.32 30.65 28.84 20.51
Input 3.79 3.99 3.69 3.43 3.2 2.96 2.82 2.61
TH 39.6 39.9 36.55 33.84 30.95 28.58 26.47 19.96
Input 3.35 4.23 3.85 3.65 3.24 3.11 3.04 2.76
TH 36.3 38.6 35.62 33.07 29.62 26.54 24.13 19.43
Input 3.45 4.46 4.01 3.9 3.31 3.2 3.16 2.89
TH 32.9 35.2 32.22 29.67 26.22 23.14 20.73 16.03
Input 3.68 4.69 4.24 4.13 3.54 3.43 3.39 3.12
9
Page 10
APPLICATION DATA
UNIT SELECTION
Select equipment to either match or be slightly less than anticipated peak load. This provides better humidity control, fewer unit cycles, and less part- load operation.
For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total anticipated load. Adjust for anticipated room wet bulb temperature to avoid undersizing equipment.
UNIT MOUNTING (INDOOR)
Refer to unit Installation Instructions for further details. Unit leveling - For reliable operation, units should be level in all
planes. Clearance - Provide adequate clearance for airflow as shown in
Fig. 2. Unit location - Select a location which will provide the best air
circulation for the room. These units should be positioned as high as possible on the wall for
best air circulation. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause unit short cycling or air recirculation. Place the unit in the middle of the selected wall (if possible). Use an outside wall, if available, to make piping easier, and place the unit so it faces the normal location of room occupants.
UNIT MOUNTING (OUTDOOR)
Refer to unit Installation Instructions for further details. Unit leveling - For reliable operation, units should be level in all
planes. Clearance - Minimum clearance, as shown in Fig. 3, must be
provided for airflow. The condensing units are designed for free-blow application. Air inlets and outlets should not be restricted.
Unit location - A location which is convenient to installation and not exposed to strong wind.
A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position.
Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your Carrier representative.
MOUNTING TEMPLATE
Refer to unit Installation Instructions for further details.
The fan coil units are furnished with mounting to mark the location of the wiring, and refrigeration line hole locations.
SUPPORT
Adequate support must be provided to support the weight of all fan coils. Refer to the Physical Data section for fan coil weights, and the base unit dimensional drawings for the location of mounting brackets.
SYSTEM OPERATING CONDITIONS
Operating Range
Min / Max °F (°C)
Cooling Heating
Outdoor DB 4 / 122 (-20 / 50) 4 / 86 (-20 / 30)
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29)
Non-Operating Temperature Range
Min / Max °F (°C)
Indoor/Outdoor DB 32 / 86 (0 / 30)
NOTE: Reference the Product Installation Instructions for mor e information.
METERING DEVICES
These units have capillary tube metering devices in the outdoor unit.
DRAIN CONNECTIONS
Install drains to meet local sanitation codes. If adequate gravity drainage cannot be provided, unit should be equipped with accessory condensate pump. High wall fan coil unit condensate pumps have a maximum lift of 10’ (3.05 m) for 9k and 12k units and 25’ (7.62 m) for 18k and 30k units.
See physical dimension tables for drain sizes.
NOTE: High wall fan coil units have internal condensate traps. A trap is not required.
Drain connections may be routed through alternate locations on mostfancoilsasshowninFig.4.
Pipe cover
Pipe holder
1
2
Right back piping
Pipe cover
4
Left piping
3
Left back piping
Right piping
Fig. 6 – Piping Locations
A14349
REFRIGERANT LINES
General refrigerant line sizing:
1. The 38MAQ units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft (7.6 m). For runs over 25 ft (7.6 m), consult long- line section on this page for proper charge adjustments.
2. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36- in (914 mm) should be buried. Provide a minimum 6- in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
3. Both lines must be insulated. Use a minimum of 1/2- in. (12.7 mm) thick insulation. Closed- cell insulation is recommended in all long- line applications.
4. Special consideration should be given to isolating interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise is not transmitted into the structure.
Long Line Applications, 38MAQ Units:
1. No change in line sizing is required.
2. Add refrigerant per table below.
ADDITIONAL CHARGE TABLE
Total Line
Length ft
Unit Size
Min Max
9
10
18 24 30 164
82 98
Additional Charge, oz/ft.
10 - 25
(3 - 8)
None
>25 - 82
ft (m)
(8 - 25)
0.1612
0.32 0.32
>82 - 164
(25 - 50)
10
Page 11
WIRING
Recommended Connection Method for Power and Communi­cation Wiring (To minimize communication wiring ence)
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt rating and 2/64-inch thick insulation must be used.
Communication Wiring:
A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64- inch thick insulation, must be used as the communication wire from the outdoor unit to the indoor unit.
To minimize voltage drop, the factory recommended wire size is 14/3 stranded with a ground. In special cases where there is high electrical interference, please use a separate shielded 16GA stranded control wire.
Alternate Connection Method for Power and Wiring (May not prevent communication wiring interfer
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four (4) wires and provides the power and communication signals for the indoor unit. Two conductors are for power wiring (L1/L2, or L/N), one is a ground wire, and one is a DC communication wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements. All power wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt rating and 2/64-inch thick insulation must be used.
interfer-
Communication
ence)
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
The main power is supplied to the outdoor unit. the field supplied connecting cable from the outdoor unit to indoor unit consists of four wires and provides the power for the indoor unit as well as the communication signal between the outdoor unit and indoor unit. Two wires are high voltage AC power (L1 and L2), one is a ground wire, and one is a DC communication wire.
CAUTION
CONTROL SYSTEM
The 40MAQ unit is equipped with a microprocessor control to perform two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort and efficiency
The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors located in the fan coil air inlet and on the indoor coil. Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation to maintain the unit within acceptable parameters and control the operating mode.
WIRELESS REMOTE CONTROL
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
CAUTION
Fig. 7 – Wireless remote control
1. A wireless remote control is supplied for system operation for system operation of all high- wall units.
2. Each battery operated wireless (infrared) remote control may be used to control more than one unit.
WIRED REMOTE CONTROL (OP TIONAL)
P/N KSACN0101CAC
1. Optional wired remote controller used for system operation of all high- wall units.
2. Kit includes a wired remote controller and a connecting cable.
3. Connect with wire terminal between remote controller and indoor unit.
4. Display in _For_C and temperature increments every 1_Forevery1_C.
11
Page 12
AIR FLOW DATA
15
SYSTEM SIZE
Turbo 380 380 380 380 680 870 870
Indoor (CFM)
Outdoor
(CFM)
High 360 360 360 360 650 780 780
Medium 290 300 290 300 450 620 620
Low 210 210 210 210 310 520 520
AIR THROW DATA
Unit Capacity MaxApproximate Air Throw ft. (m) Approximate Air Throw ft. (m) range
9K, 12K 23(7) 11 (3.5) - 23 (7)
18K 30 (9) 13 (4) - 30 (9) 24K 36 (11) 16 (5) - 36 (11) 30K 36 (11) 16 (5) - 36 (11)
SOUND PRESSURE
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
1200 1200 1200 1200 1390 2130 2130
System Size
Indoor Sound Pressure cooling mode (at different speeds)
Indoor Sound Pressure heating mode (at different speeds)
Outdoor sound pressure level dBa 55.5 56 55.5 56 59 60 63
dBa 42/34/27 42/34/27 42/34/27 42/34/27 46.5/40/33 50/45/39 50/45/39
dBa 40/33/26 41/34/27 40/33/26 41/34/27 45/39/32 47/44/38 47/44/38
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
ELECTRICAL DATA
UNIT
OPER. VOLTAGE
SIZE
9K
12K 5.7
9K
12K 5.70 0.42 0.053 40 0.07 0.027 20 15 18K 7.3 0.95 0.067 50 0.17 0.077 58 15 20 24K 8.8 0.47 0.16 120 0.23 0.080 60 15 25 30K 13.5 1.21 0.16 120 0.23 0.080 60 20 30
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps MCA - Minimum Circuit Amps RLA - Rated Load Amps
MAX / MIN*
127 / 104 115/1/60
253 / 187 208-230/1/60
COMPRESSOR OUTDOOR FAN INDOOR FAN
V/PH/HZ RLA V/PH/HZ FLA HP W V/PH/HZ FLA HP W
5.3
5.3
115/1/60 0.14 0.053 40 115/1/60 0.17 0.027 20 15 20
208-230/1/60
0.42 0.053 40
208-230/1/60
0.07 0.027 20 15
MCA
MAX FUSE
CB AMP
12
Page 13
FAN AND MOTOR SPECIFICATIONS
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
1300/1170/900/700 1300/1170/900/700 1300/1170/900/700 1300/1170/900/700 1300/1170/900/700 1250/1200/1100/900 250/1200/1100/900
1350 1350 1350 1350 1350 1350 1350
800/700/600 800/700/600 800/700/600 800/700/600 800/700/600 850/750/700 850/800/750
900 900 900 900 900 1050 1050
Indoor fan
Indoor fan
Outdoor
fan
Indoor fan
motor
Outdoor
fan motor
System size
material AS AS AS AS AS AS AS
Type GL-98*655-N GL-98*655-N GL-98*655-N GL-98*655-N GL-107.5*760-IN GL-118*895-IN GL-118*895-IN
Diameter inch 3.8 3.8 3.8 3.8 4.2 4.6 4.6
Height inch 25.8 25.8 25.8 25.8 30 35.2 35.2
material AS AS AS AS AS AS AS
Type ZL-421*117*8-3K ZL-421*117*8-3K ZL-421*117*8-3K ZL-421*117*8-3K ZL-460*180*10-3N ZL-560*139*12-3KN ZL-560*139*12-3KN
Diameter inch 16.5 16.5 16.5 16.5 18.1 22 22
Height inch 4.6 4.6 4.6 4.6 7 5.5 5.5 Model WZDK20-38M WZDK20-38M WZDK20-38G WZDK20-38G WZDK58-38G WZDK60-38G WZDK60-38G
Type DC DC DC DC DC DC DC
Phase 3 3 3 3 3 3 3
FLA 0.17 0.17 0.07 0.07 0.17 0.23 0.23
Insulation class E E E E E E E
Safe cl ass IPX0 IPX0 IPX0 IPX0 IPX0 IPX0 IPX0
Input W 25 25 22 22 52 72 72
Output W 20 20 20 20 58 60 60
Range of cur-
rent
Rated current Amps 0.17 0.17 0.07 0.07 0.17 0.23 0.23
Rated HP HP 0.027 0.027 0.027 0.027 0.077 0.08 0.08
Speed
Rated RPM
Max. input W 25 25 22 22 52 72 72
Model WZDK40-38G-1 WZDK40-38G-1 WZDK40-38G-W-1 WZDK40-38G-W-1 ZKFN-50-8-2 WZDK120-38G-1 WZDK120-38G-W Phase 3 3 3 3 3 3 3
FLA 0.14 0.14 0.42 0.42 0.95 0.47 1.21
Type DC DC DC DC DC DC DC
Insulation class E E E E E E E
Safe cl ass IPX0 IPX0 IPX0 IPX0 IPX0 IPX0 IPX0
Input W 42 42 46 46 116 145 150
Output W 40 40 40 40 50 120 120
Range of cur-
rent
Rated current Amps 0.14 0.14 0.42 0.42 0.95 0.47 1.21
Rated HP HP 0.053 0.053 0.053 0.053 0.067 0.16 0.16
Speed
Rated RPM
Max. input W 42 42 46 46 116 145 150
Amps 0.17±10% 0.17±10% 0.07±10% 0.07±10% 0.17± 10% 0.23±10% 0.23±10%
rev/ min
rev/ min
Amps 0.14±10% 0.14±10% 0.42±10% 0.42±10% 0.95± 10% 0.47±10% 1.21±10%
rev/ min
rev/ min
13
Page 14
Fig. 8 – Wiring Diagram 38/40MAQ09 / 38/40MAQ12 (115V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE L_IN Power Voltage AC 115V CN11 Power Voltage AC115V CN16 Relative to the N terminal voltageDC 24V CN15 Maximum voltageDC5V CN6 Maximum output voltage AC115V CN4 I ndoor fan interface,Maximum voltage:DC310V CN5 Stepper motor interface,Maximum voltage between the linesDC12V P_1 Ground CN8 Room temperature sensor interface,maximum voltageDC5V CN9 Pipe temperature sensor interface,maximum voltageDC5V CN10A Display interface,maximum voltage between the linesDC5V CN14 Stepper motor interface (optional),maximum voltage between the linesDC12V
OUTDOOR UNIT CONTROL BOARD
CODE PART NAME
CN1 Output:Pin5&6(12V) Pin1 - Pin4:Pulse waveform,(0 - 12V) CN15 Input:Pin1-Pin2(0- 1.8V) CN16 Input: Pin1,Pin3 ,Pin4,Pin5(0- 1.8V)
CN19 Output:Pin1- Pin5(0 - 115V High voltage)
CN31,CN33 Output:115VAC High voltage
CN32,CN34 Output:115 VAC High voltage
CN26,CN28 Output:115 VAC for 4 - way control
CN4 Input:115 VAC High voltage
CN5 Input:115 VAC High voltage
CN6 Connection to the earth
CN7 Output: Connection of the high voltage
CN8,CN9 Output: High voltage
CN36,CN37 Output: High voltage
N- B Output: High voltage
UV W Output: Pulse(0- 320VDC)
14
Page 15
Fig. 9 – Wiring Diagram 38/40MAQ09 / 38/40MAQ12 (208-230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage AC 230V
CN11 Power Voltage AC230V
CN16 Relative to the N terminal voltageDC 24V
CN15 Maximum voltageDC5V
CN6 Maximum output voltage AC230V
CN4 Indoor fan interface, Maximum voltageDC310V
CN5 Stepper motor interface, Maximum voltage between the linesDC12V
P_1 Ground
CN8 Room temperature sensor interface, maximum voltageDC5V
CN9 Pipe temperature sensor interface,maximum voltageDC5V
CN10A Display interface, maximum voltage between the linesDC5V
CN14 Stepper motor interface (optional), maximum voltage between the linesDC12V
OUTDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
CN31 Output:Pin5&6(12V) Pin1 - Pin4:Pulse waveform,(0- 12V)
CN21 Input:Pin3- 4 (3.3V) Pin2(0V),Pin1,Pin5(0 - 3.3V) CN22 Input:Pin1 (3.3V) Pin2(0- 3.3V) CN37 Output: 230VAC High voltage CN9 - 1,CN32 - 1 Output: Connection of the high voltage CN1 Input:230VAC High voltage CN2 Input:230 VAC High voltage CN3 Connection to the earth CN16 Output: Connection of the high voltage CN26,CN27 Output: High voltage for 4- way control CN7 Output: Pulse(0 - 320VDC) for DC FAN UVW Output: Pulse(0- 320VDC) for COMPRESSOR
15
Page 16
Fig. 10 – Wiring Diagram 38/40MAQ18 (208- 230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage AC 230V
CN11 Power Voltage AC230V
CN16 Relative to the N terminal voltageDC 24V
CN15 Maximum voltageDC5V
CN6 Maximum output voltage AC230V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the linesDC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltageDC5V
CN9 Pipe temperature sensor interface,maximum voltageDC5V
CN10A Display interface,maximum voltage between the linesDC5V
CN14 Stepper motor interface (optional),maximum voltage between the linesDC12V
OUTDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
CN7CN8 Input: 230V High voltage
CN2 Output: Connection of the high voltage
CN3CN4 Output: High voltage for 4 - way control
CN11CN16 Output: 230V High voltage for HEATER
CN5 Output: Pulse(0- 320V) for DC FAN
CN12CN13 Output: Connection of the high voltage
UVW Output: Pulse(0- 320V) for compressor
CN10 Input:Pin1 (5V) Pin2(0- 5V)
CN1 Input:Pin3 - 4 (5V) Pin2(0V),Pin1,Pin5(0 - 5V)
CN18 Output:Pin5&6(12V) Pin1- Pin4:Pulse waveform,(0- 12V)
16
Page 17
Fig. 11 – Wiring Diagram 38/40MAQ24 (208-230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage AC 230V CN11 Power VoltageAC230V CN16 Relative to the N terminal voltageDC 24V CN15 Maximum voltageDC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface,MaximumvoltageDC310V CN5 Stepper motor interface,Maximum voltage between the linesDC12V P_1 Ground CN8 Room temperature sensor interface,maximum voltageDC5V CN9 Pipe temperature sensor interface,maximumvoltageDC5V CN10A Display interface,maximum voltage betweenthe linesDC5V CN14 Stepper motorinterface (optional),maximum voltage between the linesDC12V
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage AC 230V
CN11 Power Voltage AC230V
CN16 Relative to the N terminal voltageDC 24V
CN15 Maximum voltageDC5V
CN6 Maximum output voltage AC230V
CN4 Indoor fan interface,Maximum voltageDC310V
CN5 Stepper motor interface,Maximum voltage between the linesDC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltageDC5V
CN9 Pipe temperature sensor interface,maximum voltageDC5V
CN10A Display interface,maximum voltage between the linesDC5V
CN14 Stepper motor interface (optional),maximum voltage between the linesDC12V
17
Page 18
Fig. 12 – Wiring Diagram 38/40MAQ30 (208- 230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage AC 230V
CN11 Power Voltage AC230V
CN16 Relative to the N terminal voltageDC 24V
CN15 Maximum voltageDC5V
CN6 Maximum output voltage AC230V
CN4 Indoor fan interface,Maximum voltageDC310V
CN5 Stepper motor interface,Maximum voltage between the linesDC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltageDC5V
CN9 Pipe temperature sensor interface,maximum voltageDC5V
CN10A Display interface,maximum voltage between the linesDC5V
CN14 Stepper motor interface (optional),maximum voltage between the linesDC12V
OUTDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
CN1CN2 Input: 230V High voltage
S Output: Connection of the high voltage
CN11CN12 Output: Pulse(0 - 320V) for DC FAN
CN33 Input:Pin1 (5V) Pin2(0- 5V)
CN3CN22 Output: High voltage for 4- way control
CN4CN40 Output: 230V High voltage for HEATER1
CN10CN44 Output: 230V High voltage for HEATER2
CN8 Input:Pin3- 4 (5V) Pin2(0V),Pin1,Pin5(0 - 5V) CN9 Input:Pin1~ 3 (0V) Pin2~ 4(0- 5V)
CN51 CN52 Output: Connection of the high voltage
UVW Output: Pulse(0 - 380V) for compressor
18
Page 19
GUIDE SPECIFICATIONS
INDOOR WALL- MOUNTED DUCTLESS UNITS
Size Range: 3/4 to 2 1/2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MAQ
PART 1 - GENERAL
1.01 System Description
Indoor, wall- mounted, direct- expansion fan coils are matched with cooling only or heat pump outdoor unit .
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General:
Indoor, direct- expansion, wall-mounted fan coil. Unit shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit shall be furnished with integral wall mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles shall be attractively styled, high- impact polystyrene. Cabinet shall be fully insulated for improved thermal and acoustic performance.
C. Fans:
1. Fan shall be tangential direct- drive blower type with air intake at the top of the unit and discharge at the bottom front. Automatic, motor- driven vertical air sweep shall be provided standard.
2. Air sweep operation shall be user selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction may be set manually.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A drip pan under the coil shall have a drain connection for hose attachment to remove condensate. Condensate pan shall have internal trap.
E. Motors:
Motors shall be open drip-proof, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 4- speed.
F. Co ntrols:
Controls shall consist of a microprocessor- based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range shall be from 62_Fto86_F(17_Cto30_C) in increments of 1_F or 1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort.
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating conditions as at failure.
2. A timer function to provide a minimum 24- hour timer cycle for system Auto Start/Stop.
3. Temperature- sensing controls shall sense return air temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and operating conditions.
6. Automatic air sweep control to provide on or off activation of air sweep louvers.
7. Dehumidification mode shall provide increased latent removal capability by modulating system operation and set point temperature.
8. Fan- only operation to provide room air circulation when no cooling is required.
9. Diagnostics shall provide continuous checks of unit operation and warn of possible malfunctions. Error messages shall be displayed at the unit.
10. Fan speed control shall be user-selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
11. Automatic heating- to- cooling changeover in heat pump mode. Control shall include deadband to prevent rapid mode cycling between heating and cooling.
12. Indoor coil high temperature protection shall be provided to detect excessive indoor discharge temperature when unit is in heat pump mode.
G. Filters:
Unit shall have filter track with factory- supplied cleanable filters.
H. Electrical Requirements:
Indoor fan motor to operate on 115V on model sizes 09- 12 and on 208- 230V on model sizes 09- 30, as specified. Power is supplied from the outdoor unit.
I. Operating Characteristics:
The 40MAQ system shall have a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump:
- The condensate pump shall remove condensate from the drain pan when gravity drainage cannot be used. Pump shall be designed for quiet operation. Pump shall consist of two parts: an internal reservoir/sensor assembly, and a remote sound- shielded pump assembly. A liquid level sensor in the reservoir shall stop cooling operation if the liquid level in the reservoir is unacceptable.
19
Page 20
PART 1 - GENERAL
1.01 System Description
A. Outdoor air- cooled split system compressor sections suitable
for on- the- ground, rooftop, wall hung or balcony mounting. Units shall consist of a rotary compressor, an air- cooled coil, propeller- type draw-through outdoor fan, reversing valve (HP), accumulator (HP units), metering device(s), and control box. Units shall discharge air horizontally as shown on the contract drawings. Units shall function as the outdoor component of an air- to- air cooling only, or heat pump system.
B. Units shall be used in a refrigeration circuit matched to ductless
cooling only or heat pump fan coil units.
1.02 Agency Listings
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with the NEC. B. Units shall be evaluated in accordance with UL standard 1995.
C. Units shall be listed in the CEC directory.
D. Unit cabinet shall be capable of withstanding 500- hour salt
spray test per Federal Test Standard No. 141 (method 6061).
E. Air- cooled condenser coils shall be leak tested at 550 psig.
1.03 Delivery, Storage, And Handling
Units shall be shipped in one piece and shall be stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air- cooled outdoor unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, and the compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a baked-enamel finish on inside and outside.
2. Unit access panels shall be removable with minimal screws and shall provide full access to the compressor, fan, and control components.
3. Outdoor compartment shall be isolated and have an acoustic lining to assure quiet operation.
C. Fans:
1. Outdoor fans shall be direct- drive propeller type, and shall discharge air horizontally. Fans shall draw air through the outdoor coil.
2. Outdoor fan motors shall be totally- enclosed, single phase motors with class B insulation and permanently- lubricated ball bearings. Motor shall be protected by internal thermal overload protection.
GUIDE SPECIFICATIONS
HORIZONTAL DISCHARGE OUTDOOR UNITS
Size Range: 3/4 to 2 1/2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 38MAQ
3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be non metallic and shall be statically and dynamically balanced.
5. Outdoor fan openings shall be equipped with PVC metal/mesh coated protection grille over fan.
D. Compressor:
1. Compressor shall be fully hermetic rotary type.
2. Compressor shall be equipped with oil system, operating oil charge, and motor. Internal overloads shall protect the compressor from over-temperature and over- current.
3. Motor shall be NEMA rated class F, suitable for operation in a refrigerant atmosphere.
4. Compressor assembly shall be installed on rubber vibration isolators.
5. Compressors shall be single phase.
E. Outdoor Coil:
Coil shall be constructed of aluminum fins mechanically bonded to seamless copper tubes, which are cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigerant circuit components shall include brass external liquid line service valve with service gage port connections, suction line service valve with service gage connection port, service gage port connections on compressor suction and discharge lines with Schrader type fittings with brass caps, accumulator, reversing valve.
G. Controls and Safeties:
Operating controls and safeties shall be factory selected, assembled, and tested. The minimum control functions shall include the following:
1. Controls:
a. A time delay control sequence is provided standard through
the fan coil board.
b. Automatic outdoor- fan motor protection.
2. Safeties:
a. System diagnostics.
b. Compressor motor current and temperature overload
protection.
c. Outdoor fan failure protection.
H. Electrical Requirements:
1. Unit shall operate on single-phase, 60 Hz power at 115 v for unit sizes 09- 12 and 208- 230v for unit sizes 09, 12, 18, 24, and 30, as specified.
2. Unit electrical power shall be a single point connection.
3. Unit Control voltage to the indoor fan coil shall be 0 - 15V DC.
4. All power and control wiring must be installed per NEC and all local electrical codes.
5. Unit shall have high- and low- voltage terminal block connections.
Copyright 2015 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 02/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
Catalog No: 38 - 40MA- 01PD
Replaces: NEW
Loading...