Carrier MAQB09B1 Installation manual

Page 1
40MAQ / 38MAQ 619PB / 538PR High---Wall D uctless Split System Sizes 09 to 30
Installation Instructions
TABLE OF CONTENTS
PARTS L IS T 2.......................................
SAFETY CONSIDERATIONS 3.........................
SYSTEM REQUIREMENTS 4...........................
DIMENSIONS 5......................................
CLEARANCES 6.....................................
INSTALLATION TIPS 7................................
INDOOR UNIT INSTALLATION 7.......................
OUTDOOR UNIT INSTALLATION 8.....................
INSTALL ALL POWER AND INTERCONNECTING WIRING
TO OUTDOOR UNITS 8...............................
ELECTRICAL DATA 9................................
CONNECTION DIAGRAMS 9..........................
INSTALL ALL POWER, INTERCONNECTING WIRING,
AND PIPING TO INDOOR UNIT 9......................
REMOTE CONTROL INSTALLATION 10.................
SYSTEM VACUUM AND CHARGE 10...................
START--UP 11........................................
TROUBLESHOOTING 12..............................
NOTE: Read the entire instruction manual before starting the installation.
Page 2
PARTS LIST
Part
No.
1 Indoor Unit 1 2 Mounting Plate 1 3 M o u n t ing S c r e w A S T 3 . 9 x 2 5 --- C --- H 5 4 Anchor 5 5 Air Filter 1 6 Remote Control 1 7 Remote Control Holder 1 8 M o u n t ing S c r e w B S T 2 . 0 x 1 0 --- C --- H 2 9 Outdoor Unit 1
Name of Part Qty
■ Indoor
6
I o n
8
■ Outdoor
3
4
1
2
5
A U T
O
C
O O
D
L R Y
H E
A T
F A
N H I G
H
T
M
E
E
M
D
L
P
M
O
o
W
d e
O n/
S
O
w
f
f
i n
g
F a
n S e
l f C
S
l e
l e
a
e
n
p
F
ol l o
i
w z er
M
e
S
T
ma
L
i
m
E
r
D
e
t E
r
y
e
T u
r
F.P.
b o
S
i l e n
c e
Air Outlet
7
9
Note:
--- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe bef ore i t enters the wall to the indoor unit. This will ensure that rain will drip from the connection pipe before it enters the wall.
--- Piping and the interconnecting wiring are field supplied.
--- The illustration above is only a sketch. Different models may be slightly different.
A14342
2
Page 3
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the
!
!
safety--alert symbol in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the unit and
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start--up.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION
3
Page 4
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and servicing unit. See Fig. 3 and 4 for minimum required distances between unit and walls or ceilings.
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.
S Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m). S Table 1 lists the maximum lengths:
Table 1—Piping Lengths
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208 ---230V) (208 --- 230 V) (208 --- 230 V) (208 --- 230 V) (208 --- 230 V)
164 (50)
0.16 (15) 0.16 (15) 0.16 (15) 0.16 (15) 0.16 (15) 0.32 (30) 0.32 (30)
3/8 (9.52) 1/2 (12.7) 3/8 (9.52) 1/2 (12.7)
2.76
(1.25)
2.76
(1.25)
2.76
(1.25)
2.76
(1.25)
1/2
(12.7)
4.19
(1.90)
5/8
(16)
5.18
(2.35)
5/8 (16)
6.62
(3.00)
Piping
Refrigerant
SYSTEM SIZE
Min. Piping Length ft (m) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3) Standard Piping Length ft (m) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) Max. outdoor ---indoor
height difference Max. Piping Length with
no additional refrigerant charge
Max. Piping Length ft (m) 82 (25) 82(25) 82(25) 82(25) 98(30) 98(30)
Additional refrigerant charge (between Standard – Max piping length)
G a s P i p e ( s i z e --­connection type)
Liquid Pipe (size --­connection type)
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A Heat Pump Models
Charge Amount
ft (m) 32 (10) 32 (10) 32(10) 32(10) 65(20) 65(20) 82(25)
ft (m) 26 (8) 26(8) 26(8) 26(8) 26(8) 26(8) 26(8)
Oz/ft
(g/m)
in
(mm)
in 1/4 in 1/4 in 1/4 in 1/4 in 1/4 in 3/8 in 3/8 in
(mm) 6.35 6.35 6.35 6.35 6.35 9.52 9.52
Lbs (kg)
S Above charge is for piping runs up to 25 ft. (7.6 m). S For piping runs greater than 25 ft. (7.6 m), add refrigerant up to the allowable length as specified in Table 2.
Table 2—Additional Charge Table
TOTAL LINE LENGTH ft ADDITIONAL CHARGE, oz/ft. ft (m)
UNIT SIZE
9
18 24 30 164
Min Max
10
82
98
10 --- 25
( 3 --- 8 )
None
> 2 5 --- 8 2
( 8 --- 2 5 )
0.1612
0.32 0.32
> 8 2 --- 1 6 4
( 2 5 --- 5 0 )
The outdoor unit (Sizes 09 -- 18) has an electronic expansion valve to manage the refrigerant flow of the fan coil connected. Sizes 24 and 30 have capillary tube metering devices in the outdoor unit.
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per the caution note, only stranded copper conductors with a 600 volt rating and double insulated copper wire must be used.
The use of BX cable is not recommended.
Recommended Connection Method for Power Communication Wiring -- Power and Communication W
and
iring:
The main power is supplied to the outdoor unit. The field supplied
PowerW
The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire. To minimize voltage drop, the factory recommended wire size is 14/2 stranded with a ground.
Communication W
A separate shielded Stranded copper conductor only, with a 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire.
iring:
iring:
14/3 power/communication wiring from the outdoor unit to indoor unit consists of four (4) wires and provides the power for the
!
CAUTION
indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire.
Recommended Connection Method for Power
and Communication Wiring (To minimize communication interfer
ence)
wiring
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
4
Page 5
DIMENSIONS -- INDOOR
Unit Size W in (mm) D in (mm) H in (mm) Operating Weight lb (kg)
9K/12K 32.9 (835) 7.8 (198) 11.0 (280) 19.2 (8.7)
18K 39.0 (990) 8.6 (218) 12.4 (315) 26.5 (12.0)
24K/30K 46.7 (1186) 10.2 (258) 13.4 (343) 40.8 (18.5)
DIMENSIONS -- OUTDOOR
Fig. 1 --- Indoor unit
Fig. 2 --- Outdoor unit
Model W in (mm) D in (mm) H in (mm) L1 in (mm) L2 in (mm)
9K/12K 32.0 (810) 12.2 (310) 22.0 (558) 20.9 (530) 11.4 (290) 82.5 (37.4)
18K 32.3 (845) 12.6 (320) 27.6 (700) 22.1 (560) 13.2 (335) 102.5 (46.5) 24K 37.2 (945) 15.6 (395) 31.9 (810) 25.1 (640) 15.9 (405) 137.6 (62.4) 30K 37.2 (945) 15.6 (395) 31.9 (810) 25.1 (640) 15.9 (405) 157.6 (71.5)
Operating
Weight lb (kg)
5
Page 6
CLEARANCES -- INDOOR
"
5
(0.13m)
min.
CEILING
6" (0.15m) min.
(1.8m)
6'
FLOOR
Fig. 3 --- Indoor Unit Clearance
5
"
(0.13m)
min.
A07891
CLEARANCES -- OUTDOOR
A
D
B
Air-outlet
Fig. 4 --- Outdoor Unit Clearance
Table 3—Outdoor Unit Clearance Dimensions
UNIT
A 24 (610) B 24 (610)
C 24 (610) D 4 (101)
E 4 (101)
Minimum Value
in. (mm)
Air-inlet
E
C
A07894
6
Page 7
INSTALLATION TIPS
Ideal installation locations include:
Indoor
Unit
S A location where there are no obstacles near inlet and outlet area. S A location which can bear the weight of indoor unit. S Do not install indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
S A location which provides appropriate clearances as outlined in
Fig. 3.
Outdoor
S A location which is convenient to installation and not exposed to
S A location which can bear the weight of outdoor unit and where
S A location which provides appropriate clearances as outlined in
S Do not install the indoor or outdoor units in a location with
Unit
strong wind.
the outdoor unit can be mounted in a level position.
Fig. 4.
special environmental conditions. For those applications, contact your Ductless Split representative.
INDOOR UNIT INSTALLA TION
INSTALL MOUNTING PLATE
The mounting plate will look like one of the following depending on model size:
1. Carefully remove the mounting plate, which is attached to the back of the indoor unit.
2. The mounting plate should be located horizontally and level on the wall. All minimum spacings shown in Fig. 3 and 5 should be maintained.
3. If the wall is block, brick, concrete or similar material, drill .2” (5 mm) diameter holes and insert anchors for the appropriate mounting screws.
4. Attach the mounting plate to the wall.
DRILL HOLE IN WALL FOR INTERCONNECTING PIPING, DRAIN AND WIRING
Refrigerant Line Routing
The refrigerant lines may be routed in any of the four directions showninFig.9.
For maximum serviceability, it is recommended to have refrigerant line flare connections and the drain connections on the outside of the wall that the fan coil can be mounted on.
If piping is going through the back:
1. Determine the pipe hole position using the mounting plate as a template. Drill pipe hole diameter per values given in Fig. 5 through 7. The outside pipe hole is 1/2--in. (13 mm) min. lower than inside pipe hole, so it slants slightly downward (see Fig. 8).
Fig. 5 --- Mounting Plate -- Model sizes 09, 12
Fig. 6 --- Mounting Plate -- Model size 18
1/2 in. (13 mm)
Min.
INDOOR
Fig. 8 --- Drill Holes
If piping is going through the right or left side:
1. Use a small saw blade to carefully remove the correspond­ing plastic covering on side panel and drill the appropriate size hole where the pipe is going through the wall.
Pipe holder
Pipe cover
1
Right piping
Fig. 9 --- Piping Locations
OUTDOOR
2
Right back piping
Pipe cover
4
Left piping
3
Left back piping
A07371
A14349
Fig. 7 --- Mounting Plate -- Model sizes 24, 30
7
Page 8
OUTDOOR UNIT INSTALLATION
G
1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
In regions with snowfall and cold temperatures, avoid installing the outdoor unit in areas where it can be covered by snow. If the outdoor unit is installed in areas where heavy snow is expected, a field supplied ice or snow stand and/or field supplied-- installed wind baffle should be installed to protect the unit from snow accumulation and/or blocked air intake. Blocking the air intake may result in reduced airflow, significantly reduced performance and damage to the equipment.
CAUTION
Strong
wind
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Excessive torque can break flare nut depending on installation conditions.
CAUTION
INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNITS
1. Mount outdoor power disconnect.
2. Run power wiring from main box to disconnect per NEC and local codes.
3. Remove field wiring cover from unit by loosening screws.
4. Remove caps on conduit panel.
5. Connect conduit to conduit panel (see Fig.12 ).
6. Properly connect both power supply and control lines to ter­minal block per the connection diagram for the appropriate unit capacity and voltage.
7. Ground unit in accordance with NEC and local electrical codes.
8. Use lock nuts to secure conduit.
9. Reinstall field wiring cover.
A07350
Fig. 10 --- High Wind Installation
MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT)
IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be used. Use of other types of tubing will void manufacturer’s warranty.
Do not open service valves or remove protective caps from tubing ends until all the connections are made.
Bend tubing with bending tools to avoid kinks and flat spots.
Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation of oil traps. Insulate each tube with minimum 3/8--in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections will save time and improve installation quality.
1. Remove service valve cover if provided with unit.
2. Cut tubing with tubing cutter. Remove service connection if provided with unit.
3. Install correct size flare nut onto tubing and make flare connection.
4. Apply a small amount of refrigerant oil to the flare connection on the tubing.
5. Properly align tubing in with service valve.
6. Tighten flare nut and finish installation using two wrenches as shown in Fig. 11.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
Outdoor unit
Terminal Block
Over 1.57" (40mm)
CAUTION
Conduit panel
Conduit
Fig. 12 --- Field Wiring
A07455
Fig. 11 --- Tighten Flare Nut
A07354
8
Page 9
ELECTRICAL DATA
15
k
UNIT
OPER. VOLTAGE
SIZE
9K
12K 5.7
MAX / MIN*
127 / 104 115/1/60
9K
12K 5.70 0.42 0.053 40 0.07 0.027 20 15 18K 7.3 0.95 0.067 50 0.17 0.077 58 15 20
253 / 187 208-230/1/60
24K 8.8 0.47 0.16 120 0.23 0.080 60 15 25 30K 13.5 1.21 0.16 120 0.23 0.080 60 20 30
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
F L A --- F u l l L o a d A m p s
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
COMPRESSOR OUTDOOR FAN INDOOR FAN
V/PH/HZ RLA V/PH/HZ FLA HP W V/PH/HZ FLA HP W
5.3
5.3
115/1/60 0.14 0.053 40 115/1/60 0.17 0.027 20 15 20
208-230/1/60
0.42 0.053 40
208-230/1/60
0.07 0.027 20 15
MCA
MAX FUSE
CB AMP
CONNECTION DIAGRAMS
2(N)
115-1-60 FIELD POWER SUPPLY
GND
S
Indoor Signal High Voltage
L
N Main Power Supply
115-1-60
TINU ROODTUO v511 k21 dna K9TINU ROODNI v511 k21 dna K9
L1
L2
Indoor Unit
Power Supply
208-230-1-60
Indoor Signal High Voltage
S
CONNECTING CABLE
OUTDOOR TO INDOOR
GND
S
L
N
Indoor
Indoor Unit
Signal
Power Supply
115-1-60
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
High Voltage
Ground
1(L)
Power to
Indoor Unit
115-1-60
CONNECTING CABLE
OUTDOOR TO INDOOR
GND
Ground
L2
L1
Power to
Indoor Unit
208-230-1-60
12K to 30K 208-230V OUTDOOR UNIT12K to 30K 208-230V INDOOR UNIT
Fig. 13 --- Connection Diagrams
INSTALL ALL POWER, INTERCONNECTING WIRING, AND PIPING TO INDOOR UNIT
1. Run interconnecting piping and wiring from outdoor unit to indoor unit.
2. Run interconnecting cable through hole in wall (outside to inside).
3. Lift indoor unit into position and route piping and drain through hole in wall (inside to outside). Fit interconnecting
10. Connect refrigerant piping and drain line outside of indoor unit. Refer to Fig. 11 for proper installation of the flare connections. Complete pipe insulation at flare connection then fasten piping and wiring to the wall as required. Completely seal the hole in the wall.
11. Connect the drain line. The drain line must not have a trap anywhere in its length, must pitch downwards, and must be insulated up to the outside wall (see Fig. 15).
wiring into back side of indoor unit.
4. Put upper claw at back of indoor unit on upper hook of Mounting Plate, move indoor unit from side to side to see that it is securely hooked.
5. Open front cover of indoor unit and remove field wiring terminal block cover.
Proper Do not put drain end into waterDo not form a rise
6. Pull interconnecting wire up from back of indoor unit and position in close to the terminal block on indoor unit.
7. Push lower part of indoor unit up on wall, then move indoor unit from side to side, up and down to check if it is hooked securely (see Fig. 14).
Upper hook
NOTE: For proper orientation of the refrigerant piping, electrical cable and drain lines, refer to Fig. 16.
Fig. 15 --- Proper Drain Hose Installation
208-230-1-60
FIELD POWER SUPPLY
GND
S
Indoor
Main
Signal
Power Supply
High Voltage
208-230-1-60
L1
L2
A14506
A14351
Lower hoo
A07347a
Fig. 14 --- Indoor Unit Installation
8. Connect wiring from outdoor unit per connection diagram (see Fig. 13 and Fig. 17).
9. Replace field wiring cover and close front cover of indoor unit.
Indoor unit
Interconnecting Wiring
Drain Piping
Fig. 16 --- Proper Orientation
9
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Refrigerant Piping
.
Tape
A07346
.
.
..
.
.
.
. .
.
.
.
Page 10
NOTE: For applications where gravity cannot be used for
t
drainage, a condensate pump accessory is available. Consult the condensate pump Installation Instructions for more information.
REMOTE CONTROL INSTALLATION
Mounting Bracket (if installed o n the wall)
1. Use the two screws supplied with control to attach the Mounting Bracket to the wall in a location selected by customer and within operating range.
2. Install batteries in Remote Control.
3. Place Remote Control into remote control Mounting Bracket.
4. For remote control operation, refer to the unit Owner’s Manual.
Front Panel
Electrical box cover
9K and 12K 115V 12K to 30K 208-230V
LNS L1 L2 S
A14352
Fig. 17 --- Control and Power Wiring on Indoor Unit
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
CAUTION
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve (see Fig. 18).
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage (see Fig. 19).
4. Start the vacuum pump.
5. Evacuate using either deep vacuum or triple evacuation method.
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add refrigerant, up to the allowable length, as specified in the System Requirements section.
8. Disconnect the charge hose from charge connection of the low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
Refrigerant
Low Side
A
High Side
B
Fig. 18 --- Service Valve
Manifold Gage
500 microns
Low side valve
Charge hose
Low side valve
Fig. 19 --- Manifold
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water (see Fig. 20).
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
Indoor Uni
C
D
High side valve
Charge hose
Vacuum pump
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A07360
A07361
01234567
MINUTES
Fig. 20 --- Deep Vacuum Graph
A95424
10
Page 11
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 21 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. Dur­ing this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 21. System will then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 21 --- Triple Evacuation Method
Final Tubing
Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
START--UP
Tes t Operation
Perform test operation after completing gas leak and electrical safety check (see Fig. 22).
NOTE: A protection feature prevents air conditioner from being activated for approximately 3 to 4 minutes.
2. Push MODE button, select COOLING, HEATING, FAN mode to check if all functions work correctly.
3. To run the test using the manual button in the indoor unit:
(1.) Open front panel of the indoor unit;
(2.) Push the manual switch once to energize the unit.
The set conditions of manual operation are as follows:
· Preset set point: 76_F(24_C)
· Fan speed: AUTO
· Discharge air direction: Pre--set position based on operation in “Cool” or “Heat” mode.
4. Be sure to set manual switch to “OFF” (by pushing it twice again) after finishing test operation.
SYSTEM CHECKS
1. Conceal the tubing where possible.
2. Make sure that the drain tube slopes downward along its entire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall, when possible.
5. Seal the hole through which the cables and tubing pass.
INDOOR UNIT
1. Do all Remote Control buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drain work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
Explain Following Items To Customer (with the aid of the Owner’s Manual):
1. How to turn air conditioner on and off; selecting COOLING, HEATING and other operating modes; setting a desired temperature; setting the timer to automatically start and stop air conditioner operation; and all other features of the Remote Control and display panel.
2. How to remove and clean the air filter.
3. How to set air deflection louver.
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions to customer.
Manual control
button
AUTO/COOL
A14353
Fig. 22 --- Test Operation
1. Push the “ON/OFF” button on Remote Control to begin testing.
11
Page 12
TROUBLESHOOTING
For ease of service, the systems are equipped with diagnostic code display LEDs on both the indoor and outdoor units. The outdoor diagnostic display is two LEDs (Red and Green) on the outdoor unit board and is limited to very few errors. The indoor diagnostic
the front of the unit. If possible, always check the diagnostic codes displayed on the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are listed in the tables below.
display is a combination of flashing LEDs on the display panel or
INDOOR UNIT DIAGNOSTIC GUIDES
Operation Lamp Timer Lamp Display Failure Mode
1time X E0 Indoor unit EEPROM parameter error2times X E1 Indoor / outdoor units communication error3times X E2 Zero-crossing signal detection error4times X E3 Indoor fan speed has been out of control5times X E4 Indoor room temperature sensor is open circuit or short circuited6times X E5 Evaporator coil temperature sensor is open circuit or short circuited7times X EC Refrigerant leakage detection2times On F1 Outdoor temperature sensor is open circuit or short circuited3times On F2 Condenser coil temperature sensor is open circuit or short circuited4times On F3 Compressor discharge temperature sensor is open circuit or short circuited5times On F4 Outdoor unit EEPROM parameter error6times On F5 Outdoor fan speed has been out of control1times P0 IPM malfunction or IGBT over-strong current protection2times P1 High or low voltage low voltage protection activated
3times P2 High temperature protection of compressor top diagnosis and solution (only for 9k,12k
models
5times P4 Inverter compressor drive error
= Flashing, X = Off
For additional diagnostic information, refer to the Service Manual
OUTDOOR UNIT DIAGNOSTIC GUIDES
Green LED Red LED Failure Mode
On X Standby, normal
X On Operation, normal
On On High/Lowvoltageprotectiononcompressorterminal On EEPROM error
X Compressor’s speed is out of control
On Zero --- crossing signal detection error; lack of phase; synchronization error X IGBT or Module protection
= Flashing, X = Off For additional diagnostic information, refer to the Service Manual
Communication error
Copyright 2015 CAC ---BDP S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to c hange, at any time, specifications and designs without notice and without obligations.
Edition Date: 06/15
12
Catalog No: 38 --- 40MA---02SI
R e p l a ce s : 3 8 --- 4 0 M A --- 0 1 S I
Loading...