40MAQ / 38MAQ
619PB / 538PR
High---Wall D uctless Split System
Sizes 09 to 30
Installation Instructions
TABLE OF CONTENTS
PAGE
PARTS L IS T 2.......................................
SAFETY CONSIDERATIONS 3.........................
SYSTEM REQUIREMENTS 4...........................
DIMENSIONS 5......................................
CLEARANCES 6.....................................
INSTALLATION TIPS 7................................
INDOOR UNIT INSTALLATION 7.......................
OUTDOOR UNIT INSTALLATION 8.....................
INSTALL ALL POWER AND INTERCONNECTING WIRING
TO OUTDOOR UNITS 8...............................
ELECTRICAL DATA 9................................
CONNECTION DIAGRAMS 9..........................
INSTALL ALL POWER, INTERCONNECTING WIRING,
AND PIPING TO INDOOR UNIT 9......................
REMOTE CONTROL INSTALLATION 10.................
SYSTEM VACUUM AND CHARGE 10...................
START--UP 11........................................
TROUBLESHOOTING 12..............................
NOTE: Read the entire instruction manual before starting the
installation.
PARTS LIST
Part
No.
1 Indoor Unit 1
2 Mounting Plate 1
3 M o u n t ing S c r e w A S T 3 . 9 x 2 5 --- C --- H 5
4 Anchor 5
5 Air Filter 1
6 Remote Control 1
7 Remote Control Holder 1
8 M o u n t ing S c r e w B S T 2 . 0 x 1 0 --- C --- H 2
9 Outdoor Unit 1
Name of Part Qty
■ Indoor
6
I
o
n
8
■ Outdoor
3
4
1
2
5
A
U
T
O
C
O
O
D
L
R
Y
H
E
A
T
F
A
N
H
I
G
H
T
M
E
E
M
D
L
P
M
O
o
W
d
e
O
n/
S
O
w
f
f
i
n
g
F
a
n
S
e
l
f
C
S
l
e
l
e
a
e
n
p
F
ol
l
o
i
w
z
er
M
e
S
T
ma
L
i
m
E
r
D
e
t
E
r
y
e
T
u
r
F.P.
b
o
S
i
l
e
n
c
e
Air Outlet
7
9
Note:
--- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe bef ore i t
enters the wall to the indoor unit. This will ensure that rain will drip from the connection pipe before it enters the wall.
--- Piping and the interconnecting wiring are field supplied.
--- The illustration above is only a sketch. Different models may be slightly different.
A14342
2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air--conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by
trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult
local building codes and National Electrical Code (NEC) for
special requirements. Recognize safety information. This is the
!
!
safety--alert symbol
in instructions or manuals, be alert to the potential for personal
injury.Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
. When you see this symbol on the unit and
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 mm) vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start--up.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION
3
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and servicing unit. See Fig. 3 and 4 for minimum required distances between unit and walls or ceilings.
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.
S Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
S Table 1 lists the maximum lengths:
Table 1—Piping Lengths
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208 ---230V) (208 --- 230 V) (208 --- 230 V) (208 --- 230 V) (208 --- 230 V)
164
(50)
0.16 (15) 0.16 (15) 0.16 (15) 0.16 (15) 0.16 (15) 0.32 (30) 0.32 (30)
3/8 (9.52) 1/2 (12.7) 3/8 (9.52) 1/2 (12.7)
2.76
(1.25)
2.76
(1.25)
2.76
(1.25)
2.76
(1.25)
1/2
(12.7)
4.19
(1.90)
5/8
(16)
5.18
(2.35)
5/8 (16)
6.62
(3.00)
Piping
Refrigerant
SYSTEM SIZE
Min. Piping Length ft (m) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3) 10 (3)
Standard Piping Length ft (m) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5)
Max. outdoor ---indoor
height difference
Max. Piping Length with
no additional refrigerant
charge
Max. Piping Length ft (m) 82 (25) 82(25) 82(25) 82(25) 98(30) 98(30)
Additional refrigerant
charge (between
Standard – Max piping
length)
G a s P i p e ( s i z e --connection type)
Liquid Pipe (size --connection type)
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A
Heat Pump Models
Charge Amount
ft (m) 32 (10) 32 (10) 32(10) 32(10) 65(20) 65(20) 82(25)
ft (m) 26 (8) 26(8) 26(8) 26(8) 26(8) 26(8) 26(8)
Oz/ft
(g/m)
in
(mm)
in 1/4 in 1/4 in 1/4 in 1/4 in 1/4 in 3/8 in 3/8 in
(mm) 6.35 6.35 6.35 6.35 6.35 9.52 9.52
Lbs
(kg)
S Above charge is for piping runs up to 25 ft. (7.6 m).
S For piping runs greater than 25 ft. (7.6 m), add refrigerant up to the allowable length as specified in Table 2.
Table 2—Additional Charge Table
TOTAL LINE LENGTH ft ADDITIONAL CHARGE, oz/ft. ft (m)
UNIT SIZE
9
18
24
30 164
Min Max
10
82
98
10 --- 25
( 3 --- 8 )
None
> 2 5 --- 8 2
( 8 --- 2 5 )
0.1612
0.32 0.32
> 8 2 --- 1 6 4
( 2 5 --- 5 0 )
The outdoor unit (Sizes 09 -- 18) has an electronic expansion valve to manage the refrigerant flow of the fan coil connected. Sizes 24 and 30
have capillary tube metering devices in the outdoor unit.
WIRING
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use Electrical
Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively. Per the caution note, only
stranded copper conductors with a 600 volt rating and double
insulated copper wire must be used.
The use of BX cable is not recommended.
Recommended Connection Method for Power
Communication Wiring -- Power and Communication W
and
iring:
The main power is supplied to the outdoor unit. The field supplied
PowerW
The main power is supplied to the outdoor unit. The field supplied
power wiring from the outdoor unit to indoor unit consists of three
(3) wires and provides the power for the indoor unit. Two wires are
high voltage AC power and one is a ground wire.
To minimize voltage drop, the factory recommended wire size is
14/2 stranded with a ground.
Communication W
A separate shielded Stranded copper conductor only, with a 600
volt rating and double insulated copper wire, must be used as the
communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.
iring:
iring:
14/3 power/communication wiring from the outdoor unit to indoor
unit consists of four (4) wires and provides the power for the
!
CAUTION
indoor unit. Two wires are high voltage AC power, one is
communication wiring and the other is a ground wire.
Recommended Connection Method for Power
and
Communication Wiring (To minimize communication
interfer
ence)
wiring
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
4