NOTE: Read the entire instruction manual before starting the
installation.
Page 2
PARTS LIST
Part
No.
1Indoor Unit1
2Mounting Plate1
3M o u n t ing S c r e w A S T 3 . 9 x 2 5 --- C --- H5
4Anchor5
5Air Filter1
6Remote Control1
7Remote Control Holder1
8M o u n t ing S c r e w B S T 2 . 0 x 1 0 --- C --- H2
9Outdoor Unit1
Name of PartQty
■ Indoor
6
I
o
n
8
■ Outdoor
3
4
1
2
5
A
U
T
O
C
O
O
D
L
R
Y
H
E
A
T
F
A
N
H
I
G
H
T
M
E
E
M
D
L
P
M
O
o
W
d
e
O
n/
S
O
w
f
f
i
n
g
F
a
n
S
e
l
f
C
S
l
e
l
e
a
e
n
p
F
ol
l
o
i
w
z
er
M
e
S
T
ma
L
i
m
E
r
D
e
t
E
r
y
e
T
u
r
F.P.
b
o
S
i
l
e
n
c
e
Air Outlet
7
9
Note:
--- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe bef ore i t
enters the wall to the indoor unit. This will ensure that rain will drip from the connection pipe before it enters the wall.
--- Piping and the interconnecting wiring are field supplied.
--- The illustration above is only a sketch. Different models may be slightly different.
A14342
2
Page 3
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air--conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by
trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult
local building codes and National Electrical Code (NEC) for
special requirements. Recognize safety information. This is the
!
!
safety--alert symbol
in instructions or manuals, be alert to the potential for personal
injury.Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
. When you see this symbol on the unit and
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 mm) vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start--up.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION
3
Page 4
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and servicing unit. See Fig. 3 and 4 for minimum required distances between unit and walls or ceilings.
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.
S Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
S Table 1 lists the maximum lengths:
ft (m)32 (10)32 (10)32(10)32(10)65(20)65(20)82(25)
ft (m)26 (8)26(8)26(8)26(8)26(8)26(8)26(8)
Oz/ft
(g/m)
in
(mm)
in1/4 in1/4 in1/4 in1/4 in1/4 in3/8 in3/8 in
(mm)6.356.356.356.356.359.529.52
Lbs
(kg)
S Above charge is for piping runs up to 25 ft. (7.6 m).
S For piping runs greater than 25 ft. (7.6 m), add refrigerant up to the allowable length as specified in Table 2.
Table 2—Additional Charge Table
TOTAL LINE LENGTH ftADDITIONAL CHARGE, oz/ft. ft (m)
UNIT SIZE
9
18
24
30164
MinMax
10
82
98
10 --- 25
( 3 --- 8 )
None
> 2 5 --- 8 2
( 8 --- 2 5 )
0.1612
0.320.32
> 8 2 --- 1 6 4
( 2 5 --- 5 0 )
The outdoor unit (Sizes 09 -- 18) has an electronic expansion valve to manage the refrigerant flow of the fan coil connected. Sizes 24 and 30
have capillary tube metering devices in the outdoor unit.
WIRING
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use Electrical
Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively. Per the caution note, only
stranded copper conductors with a 600 volt rating and double
insulated copper wire must be used.
The use of BX cable is not recommended.
Recommended Connection Method for Power
Communication Wiring -- Power and Communication W
and
iring:
The main power is supplied to the outdoor unit. The field supplied
PowerW
The main power is supplied to the outdoor unit. The field supplied
power wiring from the outdoor unit to indoor unit consists of three
(3) wires and provides the power for the indoor unit. Two wires are
high voltage AC power and one is a ground wire.
To minimize voltage drop, the factory recommended wire size is
14/2 stranded with a ground.
Communication W
A separate shielded Stranded copper conductor only, with a 600
volt rating and double insulated copper wire, must be used as the
communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.
iring:
iring:
14/3 power/communication wiring from the outdoor unit to indoor
unit consists of four (4) wires and provides the power for the
!
CAUTION
indoor unit. Two wires are high voltage AC power, one is
communication wiring and the other is a ground wire.
Recommended Connection Method for Power
and
Communication Wiring (To minimize communication
interfer
ence)
wiring
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
4
Page 5
DIMENSIONS -- INDOOR
Unit SizeW in (mm)D in (mm)H in (mm)Operating Weight lb (kg)
9K/12K32.9 (835)7.8 (198)11.0 (280)19.2 (8.7)
18K39.0 (990)8.6 (218)12.4 (315)26.5 (12.0)
24K/30K46.7 (1186)10.2 (258)13.4 (343)40.8 (18.5)
DIMENSIONS -- OUTDOOR
Fig. 1 --- Indoor unit
Fig. 2 --- Outdoor unit
ModelW in (mm)D in (mm)H in (mm)L1 in (mm)L2 in (mm)
S A location where there are no obstacles near inlet and outlet area.
S A location which can bear the weight of indoor unit.
S Do not install indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
S A location which provides appropriate clearances as outlined in
Fig. 3.
Outdoor
S A location which is convenient to installation and not exposed to
S A location which can bear the weight of outdoor unit and where
S A location which provides appropriate clearances as outlined in
S Do not install the indoor or outdoor units in a location with
Unit
strong wind.
the outdoor unit can be mounted in a level position.
Fig. 4.
special environmental conditions. For those applications, contact
your Ductless Split representative.
INDOOR UNIT INSTALLA TION
INSTALL MOUNTING PLATE
The mounting plate will look like one of the following depending
on model size:
1. Carefully remove the mounting plate, which is attached to
the back of the indoor unit.
2. The mounting plate should be located horizontally and level
on the wall. All minimum spacings shown in Fig. 3 and 5
should be maintained.
3. If the wall is block, brick, concrete or similar material, drill
.2” (5 mm) diameter holes and insert anchors for the
appropriate mounting screws.
4. Attach the mounting plate to the wall.
DRILL HOLE IN WALL FOR INTERCONNECTING
PIPING, DRAIN AND WIRING
Refrigerant Line Routing
The refrigerant lines may be routed in any of the four directions
showninFig.9.
For maximum serviceability, it is recommended to have refrigerant
line flare connections and the drain connections on the outside of
the wall that the fan coil can be mounted on.
If piping is going through the back:
1. Determine the pipe hole position using the mounting plate
as a template. Drill pipe hole diameter per values given in
Fig. 5 through 7. The outside pipe hole is 1/2--in. (13 mm)
min. lower than inside pipe hole, so it slants slightly
downward (see Fig. 8).
Fig. 5 --- Mounting Plate -- Model sizes 09, 12
Fig. 6 --- Mounting Plate -- Model size 18
1/2 in. (13 mm)
Min.
INDOOR
Fig. 8 --- Drill Holes
If piping is going through the right or left side:
1. Use a small saw blade to carefully remove the corresponding plastic covering on side panel and drill the appropriate
size hole where the pipe is going through the wall.
Pipe holder
Pipe cover
1
Right piping
Fig. 9 --- Piping Locations
OUTDOOR
2
Right back piping
Pipe cover
4
Left piping
3
Left back piping
A07371
A14349
Fig. 7 --- Mounting Plate -- Model sizes 24, 30
7
Page 8
OUTDOOR UNIT INSTALLATION
G
1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
In regions with snowfall and cold temperatures, avoid
installing the outdoor unit in areas where it can be covered by
snow. If the outdoor unit is installed in areas where heavy
snow is expected, a field supplied ice or snow stand and/or
field supplied-- installed wind baffle should be installed to
protect the unit from snow accumulation and/or blocked air
intake. Blocking the air intake may result in reduced airflow,
significantly reduced performance and damage to the
equipment.
CAUTION
Strong
wind
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Excessive torque can break flare nut depending on
installation conditions.
CAUTION
INSTALL ALL POWER AND INTERCONNECTING
WIRING TO OUTDOOR UNITS
1. Mount outdoor power disconnect.
2. Run power wiring from main box to disconnect per NEC
and local codes.
3. Remove field wiring cover from unit by loosening screws.
4. Remove caps on conduit panel.
5. Connect conduit to conduit panel (see Fig.12 ).
6. Properly connect both power supply and control lines to terminal block per the connection diagram for the appropriate
unit capacity and voltage.
7. Ground unit in accordance with NEC and local electrical
codes.
8. Use lock nuts to secure conduit.
9. Reinstall field wiring cover.
A07350
Fig. 10 --- High Wind Installation
MAKE REFRIGERANT PIPING CONNECTIONS
(OUTDOOR UNIT)
IMPORTANT: Use refrigeration grade tubing ONLY. No other
type of tubing may be used. Use of other types of tubing will
void manufacturer’s warranty.
Do not open service valves or remove protective caps from tubing
ends until all the connections are made.
Bend tubing with bending tools to avoid kinks and flat spots.
Keep the tubing free of dirt, sand, moisture, and other
contaminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation of oil traps.
Insulate each tube with minimum 3/8--in. (10 mm) wall thermal
pipe insulation. Inserting the tubing into the insulation before
making the connections will save time and improve installation
quality.
1. Remove service valve cover if provided with unit.
2. Cut tubing with tubing cutter. Remove service connection if
provided with unit.
3. Install correct size flare nut onto tubing and make flare
connection.
4. Apply a small amount of refrigerant oil to the flare
connection on the tubing.
5. Properly align tubing in with service valve.
6. Tighten flare nut and finish installation using two wrenches
as shown in Fig. 11.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction.
A fire hazard may also exist. Therefore, be sure all wiring
is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
S Connecting cable with conduit shall be routed through
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
F L A --- F u l l L o a d A m p s
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
COMPRESSOROUTDOOR FANINDOOR FAN
V/PH/HZRLAV/PH/HZFLA HPWV/PH/HZFLAHPW
5.3
5.3
115/1/600.14 0.053 40115/1/600.17 0.027201520
208-230/1/60
0.42 0.053 40
208-230/1/60
0.07 0.0272015
MCA
MAX FUSE
CB AMP
CONNECTION DIAGRAMS
2(N)
115-1-60
FIELD POWER SUPPLY
GND
S
Indoor
Signal
High
Voltage
L
N
Main
Power Supply
115-1-60
TINU ROODTUO v511 k21 dna K9TINU ROODNI v511 k21 dna K9
L1
L2
Indoor Unit
Power Supply
208-230-1-60
Indoor
Signal
High
Voltage
S
CONNECTING CABLE
OUTDOOR TO INDOOR
GND
S
L
N
Indoor
Indoor Unit
Signal
Power Supply
115-1-60
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
High
Voltage
Ground
1(L)
Power to
Indoor Unit
115-1-60
CONNECTING CABLE
OUTDOOR TO INDOOR
GND
Ground
L2
L1
Power to
Indoor Unit
208-230-1-60
12K to 30K 208-230V OUTDOOR UNIT12K to 30K 208-230V INDOOR UNIT
Fig. 13 --- Connection Diagrams
INSTALL ALL POWER, INTERCONNECTING
WIRING, AND PIPING TO INDOOR UNIT
1. Run interconnecting piping and wiring from outdoor unit to
indoor unit.
2. Run interconnecting cable through hole in wall (outside to
inside).
3. Lift indoor unit into position and route piping and drain
through hole in wall (inside to outside). Fit interconnecting
10. Connect refrigerant piping and drain line outside of indoor
unit. Refer to Fig. 11 for proper installation of the flare
connections. Complete pipe insulation at flare connection
then fasten piping and wiring to the wall as required.
Completely seal the hole in the wall.
11. Connect the drain line. The drain line must not have a trap
anywhere in its length, must pitch downwards, and must be
insulated up to the outside wall (see Fig. 15).
wiring into back side of indoor unit.
4. Put upper claw at back of indoor unit on upper hook of
Mounting Plate, move indoor unit from side to side to see
that it is securely hooked.
5. Open front cover of indoor unit and remove field wiring
terminal block cover.
ProperDo not put drain end into waterDo not form a rise
6. Pull interconnecting wire up from back of indoor unit and
position in close to the terminal block on indoor unit.
7. Push lower part of indoor unit up on wall, then move
indoor unit from side to side, up and down to check if it is
hooked securely (see Fig. 14).
Upper hook
NOTE: For proper orientation of the refrigerant piping, electrical
cable and drain lines, refer to Fig. 16.
Fig. 15 --- Proper Drain Hose Installation
208-230-1-60
FIELD POWER SUPPLY
GND
S
Indoor
Main
Signal
Power Supply
High
Voltage
208-230-1-60
L1
L2
A14506
A14351
Lower hoo
A07347a
Fig. 14 --- Indoor Unit Installation
8. Connect wiring from outdoor unit per connection diagram
(see Fig. 13 and Fig. 17).
9. Replace field wiring cover and close front cover of indoor unit.
Indoor unit
Interconnecting
Wiring
Drain Piping
Fig. 16 --- Proper Orientation
9
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Refrigerant Piping
.
Tape
A07346
.
.
..
.
.
.
.
.
.
.
.
Page 10
NOTE:For applications where gravity cannot be used for
t
drainage, a condensate pump accessory is available. Consult the
condensate pump Installation Instructions for more information.
REMOTE CONTROL INSTALLATION
Mounting Bracket (if installed o n the wall)
1. Use the two screws supplied with control to attach the
Mounting Bracket to the wall in a location selected by
customer and within operating range.
2. Install batteries in Remote Control.
3. Place Remote Control into remote control Mounting
Bracket.
4. For remote control operation, refer to the unit Owner’s
Manual.
Front Panel
Electrical box
cover
9K and 12K 115V12K to 30K 208-230V
LNSL1 L2 S
A14352
Fig. 17 --- Control and Power Wiring on Indoor Unit
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.
CAUTION
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold
gage charge hose to a charge port of the low side service
valve (see Fig. 18).
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage (see Fig. 19).
4. Start the vacuum pump.
5. Evacuate using either deep vacuum or triple evacuation
method.
6. After evacuation is complete, fully close the low side of
manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for
up to 25 ft. (8 m) of line length. For refrigerant lines longer
than 25 ft (8 m), add refrigerant, up to the allowable length,
as specified in the System Requirements section.
8. Disconnect the charge hose from charge connection of the
low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
Refrigerant
Low Side
A
High Side
B
Fig. 18 --- Service Valve
Manifold Gage
500 microns
Low side valve
Charge hose
Low side valve
Fig. 19 --- Manifold
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water (see Fig. 20).
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
Indoor Uni
C
D
High side valve
Charge hose
Vacuum pump
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
A07360
A07361
01234567
MINUTES
Fig. 20 --- Deep Vacuum Graph
A95424
10
Page 11
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water.
Refer to Fig. 21 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to
continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout
the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 21. System will
then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 21 --- Triple Evacuation Method
Final Tubing
Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.
START--UP
Tes t Operation
Perform test operation after completing gas leak and electrical
safety check (see Fig. 22).
NOTE: A protection feature prevents air conditioner from being
activated for approximately 3 to 4 minutes.
2. Push MODE button, select COOLING, HEATING, FAN
mode to check if all functions work correctly.
3. To run the test using the manual button in the indoor unit:
(1.) Open front panel of the indoor unit;
(2.) Push the manual switch once to energize the unit.
The set conditions of manual operation are as
follows:
· Preset set point: 76_F(24_C)
· Fan speed: AUTO
· Discharge air direction: Pre--set position based on
operation in “Cool” or “Heat” mode.
4. Be sure to set manual switch to “OFF” (by pushing it twice
again) after finishing test operation.
SYSTEM CHECKS
1. Conceal the tubing where possible.
2. Make sure that the drain tube slopes downward along its
entire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall, when possible.
5. Seal the hole through which the cables and tubing pass.
INDOOR UNIT
1. Do all Remote Control buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drain work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
Explain Following Items To Customer
(with the aid of the Owner’s Manual):
1. How to turn air conditioner on and off; selecting
COOLING, HEATING and other operating modes; setting
a desired temperature; setting the timer to automatically start
and stop air conditioner operation; and all other features of
the Remote Control and display panel.
2. How to remove and clean the air filter.
3. How to set air deflection louver.
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions to
customer.
Manual control
button
AUTO/COOL
A14353
Fig. 22 --- Test Operation
1. Push the “ON/OFF” button on Remote Control to begin
testing.
11
Page 12
TROUBLESHOOTING
For ease of service, the systems are equipped with diagnostic code
display LEDs on both the indoor and outdoor units. The outdoor
diagnostic display is two LEDs (Red and Green) on the outdoor
unit board and is limited to very few errors. The indoor diagnostic
the front of the unit. If possible, always check the diagnostic codes
displayed on the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are
listed in the tables below.
display is a combination of flashing LEDs on the display panel or
INDOOR UNIT DIAGNOSTIC GUIDES
Operation LampTimer LampDisplayFailure Mode
☆ 1timeXE0Indoor unit EEPROM parameter error
☆ 2timesXE1Indoor / outdoor units communication error
☆ 3timesXE2Zero-crossing signal detection error
☆ 4timesXE3Indoor fan speed has been out of control
☆ 5timesXE4Indoor room temperature sensor is open circuit or short circuited
☆ 6timesXE5Evaporator coil temperature sensor is open circuit or short circuited
☆ 7timesXECRefrigerant leakage detection
☆ 2timesOnF1Outdoor temperature sensor is open circuit or short circuited
☆ 3timesOnF2Condenser coil temperature sensor is open circuit or short circuited
☆ 4timesOnF3Compressor discharge temperature sensor is open circuit or short circuited
☆ 5timesOnF4Outdoor unit EEPROM parameter error
☆ 6timesOnF5Outdoor fan speed has been out of control
☆ 1times☆P0IPM malfunction or IGBT over-strong current protection
☆ 2times☆P1High or low voltage low voltage protection activated
☆ 3times☆P2High temperature protection of compressor top diagnosis and solution (only for 9k,12k
models
☆ 5times☆P4Inverter compressor drive error
☆ = Flashing, X = Off
For additional diagnostic information, refer to the Service Manual