Carrier : Turn to the Experts.
Carrier Geothermal Heat Pump Systems
50YEW Water-To-Water Design Features
The 50YEW series is unlike any other water-to-water heat pump on
the market today. The large operating map of the scroll compressor
allows high temperature operation, up to 145°F [63°C] leaving
load water temperature even at 32°F [0°C] entering source water
temperature. The combination of a coaxial (tube-in-tube) heat
exchanger for the source (ground loop) side and a brazed plate
heat exchanger for the load (heating/hot water) side provides very
high efciencies. Integral controls for hydronic heating and domestic
water heating avoid the need for external microprocessor-based
controls for outdoor temperature reset, warm weather shutdown,
staging and other controls.
The 50YEW has an extended range refrigeration circuit, capable of
ground loop (geothermal) applications as well as open loop (well
water) applications. Standard features and factory-installed options
are many. Unique application-specic controls make the 50YEW
series ideal for hydronic heating and domestic hot water generation.
The heating-only refrigeration circuit is optimized for high water
temperatures, heating efciencies, and capacities.
The dual level compressor isolation mounting system, insulated
compressor enclosure, and compressor discharge mufer make
the 50YEW series one of the quietest water-to-water heat pumps
available. The attractive “Euro-style” cabinet allows the unit to t into
any decor.
Application Flexibility
• Capacities 10kW [32,600 Btuh].
• High temperature scroll compressor, up to 145°F [63°C] leaving
water temperature.
• Ultra high efciencies (4.2 COP at ground loop conditions; up to
5.5 COP at ground water conditions).
• Built-in programmable controller with Outdoor Temperature Reset
and Warm Weather Shutdown.
• Large, back-lit digital user interface.
• Rugged coaxial (tube-in-tube) “Source” heat exchanger (copper or
cupro-nickel).
• Close approach temperature brazed plate stainless steel “Load”
heat exchanger.
• Dual level compressor isolation, compressor enclosure, and
discharge mufer for Ultra quiet operation.
• “Euro-style” cabinet for attractive look.
• Insulated cabinet with foil backed insulation for ease of cleaning.
• Flush-mount FPT ttings, secured to the cabinet (no backup
wrench required).
• TXV metering device.
• 12-point low voltage terminal strip for ease of installation.
• ETL safety listing.
• Wide variety of options including internally factor y installed
Domestic Hot Water Mode, Load and Source side pumps with
expansion tanks, VSFP (variable speed oor pump connection)
Controls and Cupro-Nickel Source Heat Exchanger.
Service & Installation Advantages
• Hinged front access door and 3 removable panels for ease
of installation and service.
• Galvanized steel construction with protective powder coat paint
and hinged front access door.
• Bi-directional thermal expansion valve.
®
• Puron
• Circuit breaker protected 75VA control transformer.
• High and low pressure service por ts on refrigerant circuit.
• Accurate refrigerant sensing freeze protection.
Factory Quality & Certications
• All units are built on our Integrated Process Control Assembly
a. Veries that the correct components are being assembled.
b. Automatically performs special leak tests on all joints.
c. Conducts pressure tests.
d. Performs highly detailed run test unparalleled in the
HVAC industry.
e. Automatically disables packaging for a “failed” unit.
f. Creates computer database for future service analysis and
• All units are water run-tested in all modes to insure efciency
• Heavy gauge galvanized steel cabinets are epoxy powder coated
• All refrigerant brazing is done in a nitrogen atmosphere.
• All units are deep evacuated to less than 100 microns prior to
• All joints are both helium and halogen leak tested to insure annual
• Coaxial heat exchanger, refrigerant suction lines and all water
• Noise Reduction features include: dual level compressor isolation,
• Safety features include: high pressure and loss of charge to
• 10-year limited warranty on major refrigerant circuit components,
• AHRI/ASHRAE/ANSI/ISO 13256-2 certied.
• NRTL & CSA listed.
• US EPA “Energy Star” compliant.
• ISO 9001:2000 Certied.
Options & Accessories
• Full Condensing Hot Water Generation With Internal Secondar y
• Factory Installed “Load” and “Source” Pumps.
• Factory Installed Expansion Tanks.
• Cupro-Nickel Source Water Coil.
• Extended Labor Allowance and Service Warranty.
HFC-410A zero ozone depletion refrigerant.
System (IPCS). The IPCS is a unique state of the art manufacturing
system that is designed to assure quality of the highest standards of
any manufacturer in the water-source industry. Our IPCS system:
diagnostics from run test results.
and reliability.
for durable and long-lasting nish.
refrigerant charging.
leak rate of less than 1/4 ounce.
lines are fully insulated to eliminate condensation problems in low
temperature applications.
insulated compressor compartment, interior cabinet insulation
using 1/2” coated glass ber, and variable speed fan.
protect the compressor, condensate overow protection, freeze
protection sensors to safeguard the coaxial heat exchanger
and air coil, hot water high-limit and low compressor discharge
temperature switch provided to shut down the hot water
generator when conditions dictate. Fault lockout enables
emergency heat and prevents compressor operation until
thermostat or circuit breaker has been reset.
Optional extended warranties available.
Heat Exchanger and Potable Water Circulating Pump.
Residential Products Technical Guide
50YEW
197
GT-PW Water-to-Water (50YEW) Series
50YEW Water-To-Water Series Features
1
Euro-Style Cabinet For Attractive Look
2
High Temperature Scroll Compressor
3
Rugged Coaxial “Source” Heat Exchanger
Close Approach Temperature Brazed Plate
4
Stainless Steel “Load” Heat Exchanger
Optional Full Condensing Hot Water
5
Generation With Internal Secondary
Heat Exchanger and Potable Water
Circulating Pump
Optional Factory Installed “Load” and
6
“Source” Pumps with expansion tanks
Fully Insulated Water and
7
Refrigerant Lines
6
7
5
11
14
4
1
8
Fully Insulated Compressor Section
Powder Coated Galvanized Steel Cabinet
9
and Front Access Panel For Long Life,
Taupe Metallic
Large Backlight User Interface
10
Built-In Programmable Controller With
11
Outdoor Temperature Reset and Warm
Weather Shutdown
Dual level compressor isolation and discharge
12
mufer for ultra quiet operation
Hinged Front Access Door and Three
13
Removable Panels For Ease of Installation
and Service
12-Point Terminal Strip For Ease of Low
14
Voltage Wiring
3
2
12
9
13
10
50YEW
198
8
Carrier : Turn to the Experts.
Carrier Geothermal Heat Pump Systems
Model Key
5 0A0 1 0CW311
Y E W
Prefix
Residential Series
YEW = Puron High Temperature
Heating Only Water-to-Water
1 2 3
4 5 67
Unit Size
010 (10kW)
Hydronic Options
A = No Pump
B = Load Pump w/Expansion Tank
C = Load Pump & Source Pump(s)
w/Expansion Tanks
8
9101112
Controls
W = CXM
Y = CXM w/VSFP
Packaging
1 = Single Pack, Domestic
Revision Level
1 = Current
Voltage
3 = 208-230/60/1
Water Coil & DHW Options
C = Copper Source & Braze Plate Load, No DHW
D = Copper Source & Braze Plate Load, DHW w/Sec. hx & pump
N = Cupro-Nickel Source & Braze Plate Load, No DHW
P = Cupro-Nickel Source & Braze Plate Load, DHW w/Sec. hx & pump
*When digit 9 = “D” or “P,” digit 7 cannot be A.”
*
*
Residential Products Technical Guide
50YEW
199
GT-PW Water-to-Water (50YEW) Series
Rated Equipment Performance & Efciencies
60 Hz (I-P) Units
Ground Loop Heat PumpGround Water Heat Pump
HeatingHeating
Model
50YEW010
THW01032.64.230.83.342.65.239.94.1
Indoor temperature is also called “Load;” outdoor temperature is also called “Source.” Numbers shown with “/” indicate entering/leaving water temperatures.
Bold outline indicates typical radiant oor application temperatures. Ratings at 40°C [104°F] are based upon AHRI/ISO Standard 13256-2; all other ratings are
based upon Standard EN 14511-2.
Indoor 86/95°F
Outdoor 32/27°F
Capacity
Mbtuh
COP
60 Hz (S-I) Units
Ground Loop Heat PumpGround Water Heat Pump
HeatingHeating
Model
50YEW010
THW0109.574.29.033.312.505.211.694.1
Indoor temperature is also called “Load;” outdoor temperature is also called “Source.” Numbers shown with “/” indicate entering/leaving water temperatures.
Bold outline indicates typical radiant oor application temperatures. Ratings at 40°C [104°F] are based upon AHRI/ISO Standard 13256-2; all other ratings are
based upon Standard EN 14511-2.
Indoor 30/35°C
Outdoor 0/-3°C
Capacity
kW
COP
Indoor 104/113°F
Outdoor 32/27°F
Capacity
Mbtuh
Indoor 40/45°C
Outdoor 0/-3°C
Capacity
kW
COP
COP
Indoor 86/95°F
Outdoor 50/45°F
Capacity
Mbtuh
Indoor 30/35°C
Outdoor 10/7°C
Capacity
kW
COP
COP
Indoor 104/113°F
Outdoor 50/45°F
Capacity
Mbtuh
Indoor 40/45°C
Outdoor 10/7°C
Capacity
kW
COP
COP
50YEW
200
Carrier : Turn to the Experts.
Carrier Geothermal Heat Pump Systems
Performance Data - 50YEW010
SourceLoad
EWT
GPM
°F
208.31.33.1
4.20.30.8
30
8.30.92.0
4.20.30.7
50
8.30.71.7
4.20.30.7
70
8.30.71.7
50YEW operating parameters are as follows: Min Source EWT = 20°F; Max Load LWT = 145°F (see application section for design guidelines).
Interpolation is permissible; extrapolation is not.
Operation below 40°F EWT (source) is based upon 15% methanol antifreeze solution.
All performance data is based upon the lower voltage of dual voltage units.
Antifreeze for source water is required for operation in the shaded area and all source EWTs below 40°F.
50YEW operating parameters are as follows: Min Source EWT = 20°F; Max Load LWT = 145°F (see application section for design guidelines).
Interpolation is permissible; extrapolation is not.
Operation below 40°F EWT (source) is based upon 15% methanol antifreeze solution.
All performance data is based upon the lower voltage of dual voltage units.
Antifreeze for source water is required for operation in the shaded area and all source EWTs below 40°F.
The water-source heating units shall be high temperature water-towater heat pumps. Units shall be performance rated in accordance
with EN 14511-2 or ARI/ISO/ASHRAE 13256-2, and listed by a
recognized safety-testing laboratory or agency, such as ETL. Each unit
shall be water run-tested at the factory. The quality control system
shall automatically perform via computer: triple leak check, pressure
tests, evacuate and accurately charge system, perform detailed
heating mode tests, and quality cross check all operational and test
conditions to pass/fail data base. Each unit shall be pallet mounted
and shipped with appropriate protective packaging to help avoid
damage in transportation.
The units shall be warranted by the manufacturer against defects
in materials and workmanship for a period of 10 years on all parts,
and 10 years on the compressor and refrigerant circuit par ts with a
service labor allowance for 5 years on refrigeration components and
2 years on other parts. An optional extended warranty is available
for the 50YEW Series units, which increases the labor allowance to
10 years on all parts. The water source units shall be designed to
operate with entering Source temperature between 20 and 110°F
[-7 and 43°C], and entering Load temperature between 50 and
130°F [10 and 54°C] with a maximum leaving load temperature of
145°F [63°C].
Casing & Cabinet
The cabinet shall be fabricated from heavy-gauge galvanized steel and
painted with a polyester powder coating. Access door shall be hinged
for easy access. The interior shall be insulated with 1/2” [13mm]
thick, multi-density, foil-backed coated glass ber. Three access panels
shall be provided and shall be removable with piping in place. The
internal component layout shall provide for major service with the
unit in place for restricted access installations. The units shall have
an insulated compressor section to minimize the transmission of
compressor noise.
Refrigerant Circuit
All units shall contain Puron® (HFC-410A) sealed refrigerant circuit
employing a hermetic motor-compressor, thermal expansion valve,
coaxial tube water-to-refrigerant Source heat exchanger, brazed plate
Load heat exchanger, compressor discharge mufer, 100% molecular
sieve lter drier with XH-11 desiccant, and service ports. An optional
Domestic Hot Water mode shall be available. Compressors shall be
scroll type designed for heat pump duty and shall be double isolated
from the cabinet with two sets of compressor mounting hardware.
Compressor motors shall be single-phase PSC with internal over
load protection.
The coaxial water-to-refrigerant heat exchangers shall be designed
for close approach temperatures and be constructed of a convoluted
copper (optional cupro-nickel) inner tube and steel outer tube. The
brazed plate heat exchanger shall be designed for close approach
temperatures and shall be constructed with stainless steel plates. The
thermal expansion valve shall provide proper superheat over the
entire uid temperature range with minimal “hunting”. The coaxial
heat exchangers and refrigerant suction lines shall be insulated to
prevent condensation at low liquid temperatures.
Electrical
CXM Control – A microprocessor-based compressor controller
shall be provided to monitor and control unit operation. The control
shall provide compressor enable, high and low pressure monitoring,
eld selectable water coil low temperature sensing, and over/under
voltage monitoring. The control shall also provide for water valve
connection, a test mode, short cycle protection, random startup, as well as fault LED, fault memory, and intelligent fault retry.
The control shall employ quick attach harness assemblies for low
voltage connections to the control board to aid in troubleshooting
or replacement. An integral terminal block with screw terminals
shall be provided on the control for connection to other low
voltage controls. The control system microprocessor board shall be
specically designed to protect against building electrical system noise
contamination, EMI, and RFI interference.
MPC Control – A programmable controller shall be provided to
monitor buffer tank temperature, Domestic Hot Water (DHW)
tank temperature, outdoor air temperature, and other inputs to
determine when to operate the compressor, pump(s) and hot water
valve. The MPC shall be factory-wired to the CXM compressor
control module and user interface. MPC programming shall include
outdoor temperature reset, warm weather shutdown, cooling enable,
heat pump staging, emergency DHW output, pump control, vacation
mode, DHW time schedule, advanced diagnostics, user interface
communication, and sensor monitoring.
Digital User Interface – A panel-mounted backlit digital user interface
shall be factory installed and wired for customization of the MPC
programming. Four arrow keys and a select key will be used to
control a large dot-matrix style 2” x 2” (5 x 5 cm) backlit display. The
main screen shall display current outdoor and water temperatures,
and allow the user to change settings by selecting from one of
the menus at the bottom of the screen. A special installer set up
mode will allow the technician to change some of the default MPC
parameters. The user interface shall include a time schedule for
DHW operation, Fahrenheit/Celsius selection, vacation mode for
DHW, and other user preference options.
12-point terminal block – A low voltage terminal block with a blue/
gray pattern for ease of identication shall be provided to connect
thermistors and external wiring. The MPC, user interface, CXM
board and other relays/components shall be factory-wired to the
terminal block.
Line voltage lugs shall be provided for unit wiring. A circuit breaker
protected 75VA transformer shall be employed. Units shall have
knockouts for entrance of low and line voltage wiring.
Piping
Source/Load supply and return water connections, as well as
Domestic Hot Water supply and return connections shall be FPT
(Female Pipe Thread) copper ttings and shall be securely mounted
ush to the cabinet allowing for connection to an MPT (Male Pipe
Thread) tting without the use of a back-up wrench. All Source
water piping shall be insulated to prevent condensation at low liquid
temperatures.
50YEW
214
Carrier : Turn to the Experts.
Carrier Geothermal Heat Pump Systems
Accessories & Warranty
Accessories & Options
Hot Water Mode Option
An optional mode to provide domestic hot water shall be
provided. This mode shall include a factory-installed, internal
secondary heat exchanger and a factory-installed potable
water, bronze circulating pump. This option shall provide an
additional set of water connections for the potable domestic
hot water and shall be completely factory installed and wired.
An external sensor shall be provided to sense the domestic
water storage tank temperature.
Internal Source and Load Pumps / Internal
Expansion Tanks
Optional Source pump(s), Load pump, and expansion tank(s)
shall be factory installed and wired to help lower installation
costs and labor. When installed at the factory, pumps are
controlled by the MPC.
Variable Speed Floor Pump Connection
An optional relay and line voltage lugs shall be provided for a
variable speed radiant oor system pump. Some radiant oor
systems utilize a variable speed pump on the oor system,
which changes ow based upon the number of zones open
or closed. Since the pump has built-in controls, only a power
supply is needed.
Warranty Information
The 2010 standard warranty applies to units ordered on or after July
1, 2010. See Carrier’s 2010 Limited Express Residential Warranty
Certicate CA234 for specic coverage and limitation.
Carrier residential class heat pumps are backed by a ten-year limited
warranty on all unit par ts, including the following accessories when
installed with Carrier units: Flow Controllers & Electric Heaters.
Carrier goes even further to back up its commitment to quality
by including a service labor allowance for the rst ve years on
refrigeration circuit components and two years on all other par ts,
auxiliary heaters and geothermal pumping modules.
The Optional Extended Factory Ser vice Labor Allowance Warranty
offers additional length of term protection to the consumer by
offsetting service labor costs for 10 years.
To order this warranty, contact your Carrier distributor. This coverage
must be purchased within 90 days of unit installation. See Limited
Express Extended Labor Warranty Certicate CA235 for details.
Cupro-Nickel Heat Exchanger
An optional corrosion resistant CuNi coaxial heat exchanger
shall be factory installed in lieu of standard copper
construction (Source heat exchanger only).
Flow Controller (eld installed)
A self-contained module shall provide all uid pumping, ll
and connection requirements for ground-source closedloop systems up to 20 GPM [76 l/m]. The Flow Controller
shall provide 1” pump isolation valves/3-way service valves.
Pump heads shall be removable from the volute for easy
replacement. The Flow Controller shall be enclosed in a
polystyrene case and fully insulated with urethane foam to
prevent condensation. The Flow Controller shall have a 5- year
warranty on all par ts.
Hose Connection Kit (eld installed)
An accessory hose kit shall provide 150psi [1034 kPa] 1”
rubber hose with brass ttings equipped with service pressure/
temperature ports for connection between the unit and Flow
Controller.