Carrier GT-PX Split Series, GT-GS Indoor Split Series, GT-S Outdoor Split Series Installation, Operation & Maintenance Instructions Manual

Split Products
GT-PX Split (50YDS) Series
GT-GS Indoor Split (50YCS) Series
GT-S Outdoor Split (38WQS) Series
Indoor and Outdoor Split
Geothermal Heat Pumps
Installation, Operation &
Table of Contents
Model Nomenclature 3
Safety 4
Storage 5
Pre-Installation 5
Equipment Selection 6
Air Coil Match-ups 6-7
Air Handler Selection 8
Installation 9
Water Connections 10-11
Ground Loop Applications 11-13
Open Loop - Ground Water Systems 14-15
Water Quality Standards 16
Refrigeration Installation 17-22
Lineset Information 17
Hot Water Generator 23-24
Electrical - Line Voltage 27-26
Electrical - Line Voltage 27-28
Electrical - HWG Wiring 29
Electrical - Low Voltage Wiring 30-32
Thermostat Wiring 32
CXM Controls 33-36
Unit Start-Up and Operating Conditions 37-38
Unit Start-Up Procedure 39
Unit Operating Conditions 40-42
Preventive Maintenance 43
Troublesh o o t i n g 4 4
CXM Process Flow Chart 45
Functional Troubleshooting Charts 46-47
Troublesh o o t i n g Fo r m 48
Revision Log 50
Maintenance Instructions
Revision: 5 June, 2008
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Model Nomenclature: for Indoor Split Series
321
YDS05
YDS = INDOOR TWO-STAGE PURON
SPLIT SYSTEM CONDENSING UNIT
YCS = INDOOR SPLIT SYSTEM
YCS
018 024 030 036 042 048 060
NOTE: Some options/configurations not availaible on all series. Please consult Engineering Guides for model specific options.
UNIT TYPE:
CONDENSING UNIT
SIZE:
YDS 026
038
049
064
AIRFLOW CONFIGURATION:
2
N = NONE
CONTROL:
YDS - C = CXM
YCS - L = CXM
86754
C06N
3C
HEAT EXCHANGER OPTIONS:
C = COPPER WATER COIL
D = COPPER WATER COIL W/HOT WATER GENERATOR
N = CUPRO-NICKEL WATER COIL
P = CUPRO-NICKEL WATER COIL W/HOT WATER GENERATOR
NOTE: Above model nomenclature is a general reference. Consult individual specifi cation catalogs for detailed information.
1211109
0
1
PACKAGING:
1=SINGLE PACK,DOMESTIC
REVISION LEVEL:
0 = CURRENT REV IS ION
VOLTAGE:
3 = 208V, 230V/1PH/60Hz
Rev.: 08/15/05D
Model Nomenclature: for Outdoor Split Series
38 SS0 2 4 C 3 1 1
Prefix
WQS = Extended Range Ultra High Efficiency Residential Outdoor Split
Series
018, 024, 030, 036, 042, 048, 060
1 2 3
WQS
Unit Size
4 5 6 7 8 9 10 11 12
Voltage
3 = 208-230/60/1
Standard
SS = Standard
Heat Exchanger Options
Standard
Packaging
1 = Single Pack, Domestic
Revision Level
1 = Current Revision
Copper Cupro-Nickel
CN
Carrier: Turn to the Experts
3
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Safety
Safety
Warnings, cautions and notices appear throughout this manual. Read these items carefully before attempting any installation, service or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which if not avoided will result in death or serious injury. DANGER labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which if not avoided could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which if not avoided could result in minor or moderate injury or product or property damage.
NOTICE: Notifi cation of installation, operation or maintenance information, which is important, but which is not hazard-related.
WARNING!
WARNING! All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
CAUTION!
CAUTION!
these units as a source of heating or cooling during the construction process. The mechanical components and lters will quickly become clogged with construction dirt and debris, which may cause system damage.
To avoid equipment damage, DO NOT use
WARNING!
WARNING! Verify refrigerant type before proceeding. Units are shipped with R-22, R-407c and R-410A (Puron®) refrigerants. The unit label will indicate which refrigerant is provided. The Puron® Application and Service Manual should be read and understood before attempting to service refrigerant circuits with R-407c or R-410A.
WARNING!
WARNING! To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal profi ciency requirements.
4
Water-Source Heating and Cooling Systems
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
General Information
Inspection
Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the packaging of each unit, and inspect each unit for damage. Insure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not fi led within 15 days, the freight company can deny the claim without recourse. Note: It is the responsibility of the purchaser to fi le all necessary claims with the carrier. Notify your equipment supplier of all damage within fi fteen (15) days of shipment.
Storage
Equipment should be stored in its original packaging in a clean, dry area. Store units in an upright position at all times. Stack units a maximum of 3 units high.
Unit Protection
Cover units on the job site with either the original packaging or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up.
5. Loosen compressor bolts on units equipped with compressor spring vibration isolation until the compressor rides freely on the springs. Remove shipping restraints.
6. REMOVE COMPRESSOR SUPPORT PLATE 1/4” SHIPPING BOLTS (2 on each side) TO MAXIMIZE VIBRATION AND SOUND ATTENUATION (R22 indoor units only).
7. Locate and verify any hot water generator (HWG) or other accessory kit located in the compressor section.
CAUTION!
CAUTION! DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can signifi cantly reduce performance, reliability, and service life. Always move and store units in an upright position. Tilting units on their sides may cause equipment damage.
NOTICE! Failure to remove shipping brackets from spring­mounted compressors will cause excessive noise, and could cause component failure due to added vibration.
CAUTION!
Examine all pipes, fi ttings, and valves before installing any of the system components. Remove any dirt or debris found in or on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions are provided with each unit. Horizontal equipment is designed for installation above false ceiling or in a ceiling plenum. Other unit confi gurations are typically installed in a mechanical room. The installation site chosen should include adequate service clearance around the unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check the system before operation.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Keep the cabinet covered with the original packaging until installation is complete and all plastering, painting, etc. is fi nished.
3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be clean and tight at the terminals.
CAUTION! CUT HAZARD - Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing heat pumps.
Carrier: Turn to the Experts
5
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
The installation of geothermal heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
General
Proper indoor coil selection is critical to system effi ciency. Using an older-model coil can affect effi ciency and may not provide the customer with rated or advertised EER and COP. Coil design and technology have dramatically improved operating effi ciency and capacity in the past 20 years. Homeowners using an older coil are not reaping these cost savings and comfort benefi ts. NEVER MATCH AN R-22 INDOOR COIL WITH AN R-410A COMPRESSOR SECTION.
Newer indoor coils have a larger surface area, enhanced fi n design, and grooved tubing. These features provide a larger area for heat transfer, improving effi ciency and expanding capacity. Typical older coils may only have one-third to one­half the face area of these redesigned coils.
Table 1a: GT-PX Air Handler Matches for ARI Ratings
Indoor Coil Selection - GT-PX Split (50YDS)
Carrier Geothermal split system heat pumps are rated in the ARI directory with a specifi c indoor coil match. GT-PX Split (50YDS) models are rated with Carrier/Bryant FV4 or FE4 series variable speed air handlers as shown in Table 1a. Other brands of air handlers may attain the same ARI ratings providing that the specifi cations meet or exceed those listed in Table 1a AND Table 1b. An ECM motor and TXV is required. Cap tubes and fi xed orifi ces are not acceptable. PSC fans may be used if matched to Table 1b, but will not meet ARI ratings. If using PSC fan, compressor section must be operated as a single stage unit (i.e. wired for either 1st stage or 2nd stage). Without the ability to vary the airfl ow, supply air temperatures may not be acceptable if the compressor is allowed to change stages when used with a PSC fan motor.
Compressor Section 026 038 049 064
Air Handler Model FV4
003 005 006 006
Refrigerant R-410A
Metering Device TXV (required)
Air Coil Type Rows - Fins/in. Face Area (sq. ft.)
Cabinet Confi gura-
Slope
3 - 14.5
3.46
A
3 - 14.5
5.93
Upfl ow/Downfl ow/Horizontal (Multipoise)
A
3 - 14.5
7.42
A
3 - 14.5
7.42
tion
ECM Settings for ARI Ratings (FV4 Fan Coil)
AC/HP size: 036
System Type:
Comfort AC/HP
CFM Adjust: Nom
AC/HP size: 036
System Type:
HP-Effi c AC/HP
CFM Adjust: High
AC/HP size: 048
System Type:
Comfort AC/HP
CFM Adjust: High
AC/HP size: 060
System Type:
Comfort AC/HP
CFM Adjust: High
Fan Motor Type - HP ECM - 1/2 ECM - 1/2 ECM - 3/4 ECM - 3/4
6
Water-Source Heating and Cooling Systems
Residential Split - 60Hz R22 &R410A
Table 1b: GT-PX Air Handler Characteristics for Brands other than Above Models
Rev.: 5 June, 2008
Equipment Selection
Model*
Nominal
Tons*
Evaporator
Temp (ºF)
CFM
Capacity
(MBtuh)**
026 - Part Load 1.5 50 530 19.2 - 22.4
026 - Full Load 2.0 52 880 24.2 - 28.2
038 - Part Load 2.5 51 700 25.2 - 29.2
038 - Full Load 3.0 50 1200 34.5 - 40.1
049 - Part Load 3.5 47 1000 34.3 - 39.9
049 - Full Load 4.0 48 1650 46.3 - 53.8
064 - Full Load 5.0 48 1850 54.5 - 63.3
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. Two-stage units may be operated in single-stage mode if desired, where smaller
capacity is required. For example, a model 026 may be used as a 1-1/2 ton unit if “locked” into 1st stage operation only. If PSC fan is used, unit must be “locked” into either 1st or 2nd stage. An ECM fan is required for two-stage operation and for ARI ratings. Size air handler for “Full Load” if operating in two-stage mode.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Indoor Coil Selection - R-22 Units
Geothermal split system heat pumps with R-22 refrigerant are rated in the ARI directory with a “generic” indoor coil match and PSC fan. Selection of air handlers that attain the published ARI ratings must meet or exceed the specifi cations listed in Table 2. A TXV is required. Cap tubes and fi xed orifi ces are not acceptable.
Table 2: R-22 Air Handler Characteristics
Model*
Nominal
Tons*
018 1.5 50 600 18.5 - 21.3
024 2.0 47 800 25.5 - 29.3
030 2.5 49 1000 31.5 - 36.2
036 3.0 48 1200 37.0 - 42.5
042 3.5 45 1400 42.2 - 48.5
048 4.0 46 1600 50.0 - 57.5
060 5.0 45 2000 58.0 - 66.7
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. **When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Evaporator
Temp (ºF)
CFM
Capacity
(MBtuh)**
Carrier: Turn to the Experts
7
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
Air Handler Selection Example
Figure 1 shows a typical performance table for a heat pump air handler. Suppose the evaporator temperature required is 50ºF, the capacity required is 35,000 Btuh and the airfl ow required is 1,200 CFM. Each evaporator temperature listed in the table shows three wet bulb temperatures. As recommended in the table notes above, select the 67ºF WB column. At 1,200 CFM, the model 003 capacity is 36 MBtuh, which is higher than the minimum capacity required of 35,000 Btuh. In this example, model 003 would be the appropriate match.
Figure 1: Selecting Air Handler
Utilizing the Existing Air Handler or Coil (R22 units only)
It is recommended that a new coil or air handler be installed with any geothermal split system compressor section due to the low initial cost of the additional equipment versus the reliability and benefi t of new technology, increased reliability and warranty. However, if the existing air handler must be used (R22 systems only), the following conditions apply:
• If the existing coil currently uses an orifi ce, the orifi ce
must be removed and replaced with a TXV. If the coil utilizes capillary tubes, it will not operate properly with the geothermal split system and should be replaced.
• If life expectancy of indoor coil (and associated components
- fan, cabinet, etc.) is less than 7-10 years, indoor section should be replaced.
8
Water-Source Heating and Cooling Systems
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
NOTICE! Failure to remove shipping brackets from spring­mounted compressors will cause excessive noise, and could cause component failure due to added vibration.
The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
Removing Existing Condensing Unit (Where Applicable)
1. Pump down condensing unit. Close the liquid line service valve of existing condensing unit and start compressor to pump refrigerant back into compressor section. Then, close suction service valve while compressor is still running to trap refrigerant in outdoor section. Immediately kill power to the condensing unit.
2. Disconnect power and low voltage and remove old condensing unit. Cut or unbraze line set from unit. Remove condensing unit.
3. If condensing unit is not operational or will not pump down, refrigerant should be recovered using appropriate equipment.
4. Replace line set, especially if upgrading system from R­22 to R-410A refrigerant. If line set cannot be replaced, it must be thoroughly fl ushed before installing new compressor section. R-410A compressors use POE oil instead of mineral oil (R-22 systems). Mineral oil is not compatible with POE oil, and could cause system damage if not completely fl ushed from the line set.
“Indoor” Compressor Section Location
Both “indoor” and “outdoor” versions of the geothermal split system compressor section are available. “Indoor” version is not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit. Units are typically installed in a mechanical room or closet. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). Consideration should be given to access for easy removal of service access panels. Provide suffi cient room to make water, electrical, and line set connections.
2. Provide adequate clearance for maintenance and service. Do not block access panels with piping, conduit or other materials.
3. Provide access for servicing the compressor and coils without removing the unit.
4. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be suffi cient to allow removal of the unit, if necessary.
5.
In limited side access installations, pre-removal of the control box side mounting screws will allow control box removal for future servicing (R22 units only).
6. Provide access to water valves and fi ttings and screwdriver access to the unit side panels and all electrical connections.
“Outdoor” Compressor Section Loacation
Locate the unit in an outdoor area that allows easy loop and lineset access and also has enough space for service personnel to perform typical maintenance or repairs. The “outdoor” compressor section is usually installed on a condensor pad directly outside the lineset access into the building. The service valve side can be located toward the building, keeping the loop access end away from the building. Conform to the following guidelines when selecting unit location:
1. Provide adequate access for loop trench excavation.
2.
Locate unit directly outside lineset penetration if possible. Utilize existing condensor pad where possible.
3. Provide access for servicing and maintenance.
“Outdoor” compressor section may be mounted on a vibration isolation pad with loop access hole as shown in Figure 3. When mounting on an existing concrete condenser pad, 3” [76mm] holes should be bored through the pad to accomodate the pipe (1-1/4” - 32mm) and insulation (1/2” [13mm] wall thickness). Figure 3 illustrates location and dimensions of the holes required.
Air Handler Installation
This manual specifi cally addresses the compressor section of the system. Air handler location and installation should be according to the instructions provided with the air handling unit.
Any access panel screws that would be diffi cult to remove after the unit is installed should be removed prior to setting the unit. Refer to Figure 2 for an illustration of a typical installation. Refer to “Physical Dimensions” section for dimensional data. selecting unit location:
Install the unit on a piece of rubber, neoprene or other
1. mounting pad material for sound isolation. The pad should be at least 3/8” [10mm] to 1/2” [13mm] in thickness. Extend the pad beyond all four edges of the unit.
Conform to the following guidelines when
Carrier: Turn to the Experts
9
Residential Split - 60Hz R22 &R410A
Air Pad with access hole
Existing Pad larger than 22" x 33" [54 x 84cm]
Bottom view
of Unit
22" x 33"
[56 x 84cm]
Flow
Controller
8.00"
25"
[63.5cm]
Drill 3" [76mm] holes for
clearance of 1-1/4" [32mm] pipe
with 1/2" [13mm] wall insulation
5.5"
[14.0cm]
8.25"
[21.0cm]
Gasket
Swivel Nut
Stainless steel
snap ring
Brass Adaptor
Hand Tighten
Only!
Do Not
Overtighten!
Rev.: 5 June, 2008
Installation
Figure 2: 50YDS/GT-GS Installation
Figure 3: GT-S Installation
External Flow Controller Mounting
The Flow Controller can be mounted beside the unit as shown in Figure 7. Review the Flow Controller installation manual for more details.
Water Connections-Residential (Distributor) Models
Residential models utilize swivel piping fi ttings for water connections that are rated for 450 psi (3101 kPa) operating pressure. The connections have a rubber gasket seal similar to a garden hose gasket, which when mated to the
10
ush end of most 1” threaded male pipe fi ttings provides a leak-free seal without the need for thread sealing tape or joint compound. Insure that the rubber seal is in the swivel connector prior to attempting any connection (rubber seals are shipped attached to the swivel connector). DO NOT OVER TIGHTEN or leaks may occur.
Water-Source Heating and Cooling Systems
The female locking ring is threaded onto the pipe threads which holds the male pipe end against the rubber gasket, and seals the joint. HAND TIGHTEN ONLY! DO NOT OVERTIGHTEN!
Figure 4: Water Connections (Indoor Compressor Section)
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
Internal Flow Controller Mounting ­“Outdoor” Compressor Section Only
The Flow Controller can be mounted in the “outdoor” compressor section directly inside the cabinet as shown in Figure 5. Remove the water legs from the outdoor unit at the union fi ttings. Attached the AFC4T 1” MPT x o-ring fi ttings to the removed water legs. Carefully attached the Flow Controller to the loop piping and mount to the outdoor unit using the mounting lugs attached to the unit. Insert the water legs into the Flow Controller using the o-ring fi ttings. Re- connect the water leg unions.
NOTICE! Opening in the bottom of the unit for loop piping must be sealed to prevent rodents from getting into the cabinet and damaging control wiring. Spray type foam may be used to seal the opening(s).
Figure 6: AFC4T Connector
Figure 5: Water Connections (Outdoor Compressor Section)
1” IPT Water Connections
Mount Flow Controller
on studs provided
Wire pump power
using provided wires
for L1 and L2
GROUND-LOOP HEAT PUMP APPLICATIONS
CAUTION!
CAUTION! The following instructions represent industry accepted installation practices for closed loop earth coupled heat pump systems. Instructions are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State/provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
Pre-Installation
Prior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.
Piping Installation
The typical closed loop ground source system is shown in Figures 7 and 8. All earth loop piping materials should be limited to polyethylene fusion only for in-ground sections of the loop. Galvanized or steel fi ttings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fi ttings should be avoided due to their potential to leak in earth coupled applications. A fl anged fi tting should be substituted. P/T plugs should be used so that fl ow can be measured using the pressure drop of the unit heat exchanger.
Carrier: Turn to the Experts
11
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Loop Heat Pump Applications
Earth loop temperatures can range between 25 and 110°F [-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton [2.41 to 3.23 l/m per kW] of cooling capacity is recommended in these applications.
Test individual horizontal loop circuits before backfi lling. Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled.
Flushing the Earth Loop
Once piping is completed between the unit, Flow Controller and the ground loop (Figures 7 and 8), the loop is ready for nal purging and charging. A fl ush cart with at least a 1.5 hp [1.1 kW] pump is required to achieve enough fl uid velocity in the loop piping system to purge air and dirt particles. An antifreeze solution is used in most areas to prevent freezing. All air and debris must be removed from the earth loop piping before operation. Flush the loop with a high volume of water at a minimum velocity of 2 fps (0.6 m/s) in all piping. The steps below must be followed for proper fl ushing.
1. Fill loop with water from a garden hose through the fl ush cart before using the fl ush cart pump to insure an even ll.
2. Once full, the fl ushing process can begin. Do not allow the water level in the fl ush cart tank to drop below the pump inlet line to avoid air being pumped back out to the earth loop.
3. Try to maintain a fl uid level in the tank above the return tee so that air cannot be continuously mixed back into the fl uid. Surges of 50 psi (345 kPa) can be used to help purge air pockets by simply shutting off the return valve going into the fl ush cart reservoir. This “dead heads” the pump to 50 psi (345 kPa). To purge, dead head the pump until maximum pumping pressure is reached. Open the return valve and a pressure surge will be sent through the loop to help purge air pockets from the piping system.
4. Notice the drop in fl uid level in the fl ush cart tank when the return valve is shut off. If air is adequately purged from the system, the level will drop only 1-2 inches (2.5
- 5 cm) in a 10” (25 cm) diameter PVC fl ush tank (about a half gallon [2.3 liters]), since liquids are incompressible. If the level drops more than this, fl ushing should continue since air is still being compressed in the loop fl uid. Perform the “dead head” procedure a number of times.
Note: This fl uid level drop is your only indication of air in the loop.
Antifreeze may be added before, during or after the fl ushing procedure. However, depending upon which time is chosen, antifreeze could be wasted when emptying the fl ush cart tank. See antifreeze section for more details.
Loop static pressure will fl uctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fl uctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for a number of minutes to condition the loop to a homogenous temperature. This is a good time for tool cleanup, piping insulation, etc. Then, perform fi nal fl ush and pressurize the loop to a static pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer). After pressurization, be sure to loosen the plug at the end of the Grundfos loop pump motor(s) to allow trapped air to be discharged and to insure the motor housing has been fl ooded. This is not required for Taco circulators. Insure that the Flow Controller provides adequate fl ow through the unit by checking pressure drop across the heat exchanger and compare to the pressure drop tables at the back of the manual.
Antifreeze
In areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales manager should be consulted for the antifreeze best suited to your area. Freeze protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop temperature, the leaving loop temperature would be 25 to 22°F [-4 to -6°C] and freeze protection should be at 15°F [-10°C]. Calculation is as follows: 30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes. Calculate the total volume of fl uid in the piping system. Then use the percentage by volume shown in Table 2 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specifi c gravity.
Low Water Temperature Cutout Setting CXM or DXM Control
When antifreeze is selected, the FP1 jumper (JW3) should be clipped to select the low temperature (antifreeze 13°F [-10.6°C]) set point and avoid nuisance faults (see “Low Water Temperature Cutout Selection” in this manual). NOTE: Low water temperature operation requires extended range equipment.
12
Water-Source Heating and Cooling Systems
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Loop Heat Pump Applications
Table 1: Approximate Fluid Volume (U.S. gal. [L]) per 100' of Pipe
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)
Pipe Size Volume (gal) [liters]
1” 4.1 [15.3]
Copper
Rubber Hose 1” 3.9 [14.6]
Polyethylene
Unit Heat Exchanger Typical 1.0 [3.8]
Flush Cart Tank
1.25” 6.4 [23.8]
2.5” 9.2 [34.3]
3/4” IPS SDR11 2.8 [10.4]
1” iPS SDR11 4.5 [16.7]
1.25” IPS SDR11 8.0 [29.8]
1.5” IPS SDR11 10.9 [40.7]
2” IPS SDR11 18.0 [67.0]
1.25” IPS SCH40 8.3 [30.9]
1.5” IPS SCH40 10.9 [40.7]
2” IPS SCH40 17.0 [63.4]
10” Dia x 3ft tall
[254mm x 91.4cm tall]
10 [37.9]
Figure 7: Loop Connection (Indoor Compressor Section)
Unit Power Disconnect
AH & Thermostat Wiring
Air Pad or Extruded polystyrene insulation board
Flow
Controller
Insulated
Hose Kit
To Loop
P/T Plugs
Figure 8: Loop Connection (Outdoor Compressor Section)
P/T Ports
Flow Controller
Insulate all piping with 1/2"
[13mm] closed cell insulation
Backfill carefully to avoid stress on piping and flow
controller connection
Air Pad with access hole
Header Pit
Table 2: Antifreeze Percentages by Volume
Type
Methanol 100% USP food grade Propylene Glycol Ethanol*
10°F [-12.2°C] 15°F [-9.4°C] 20°F [-6.7°C] 25°F [-3.9°C]
25% 38% 29%
Minimum Temperature for Low Temperature Protection
NOTICE! Cabinet opening around loop piping (outdoor compressor section) must be sealed to prevent entry of rodents that could potentially damage unit wiring by chewing on the insulation.
NOTICE! Outdoor compressor section may not be tilted more than 5 degrees from level. Damage to the compressor or stress on the loop piping could result if unit is tilted. A concrete pad, anchor posts and/or soil compaction may be required to avoid tilting as ground settles.
21% 25% 25%
16% 22% 20%
10% 15% 14%
* Must not be denatured with any petroleum based product
Carrier: Turn to the Experts
13
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Water Heat Pump Applications ­“Indoor” Compressor Section Only
Open Loop - Ground Water Systems (“Indoor” Compressor Section Only)
The “outdoor” version of the compressor section may not be used with open loop systems due to potential freezing of water piping. Typical open loop piping is shown in Figure 9. Shut off valves should be included for ease of servicing. Boiler drains or other valves should be “tee’d” into the lines to allow acid fl ushing of the heat exchanger. Shut off valves should be positioned to allow fl ow through the coax via the boiler drains without allowing fl ow into the piping system. P/T plugs should be used so that pressure drop and temperature can be measured. Piping materials should be limited to copper or PVC SCH80. Note: Due to the pressure and temperature extremes, PVC SCH40 is not recommended.
Water quantity should be plentiful and of good quality. Consult Table 3 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Consult Table 3 for recommendations. Copper is recommended for closed loop systems and open loop ground water systems that are not high in mineral content or corrosiveness. In conditions anticipating heavy scale formation or in brackish water, a cupro-nickel heat exchanger is recommended. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must only be serviced by a qualifi ed technician, as acid and special pumping equipment is required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional acid fl ushing. In some cases, the desuperheater option should not be recommended due to hard water conditions and additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality requirements. Scaling potential should be assessed using the pH/Calcium hardness method. If the pH <7.5 and the Calcium hardness is less than 100 ppm, scaling potential is low. If this method yields numbers out of range of those listed, the Ryznar Stability and Langelier Saturation indecies should be calculated. Use the appropriate scaling surface temperature for the application, 150°F [66°C] for direct use (well water/ open loop) and DHW (desuperheater); 90°F [32°F] for indirect use. A monitoring plan should be implemented in these probable scaling situations. Other water quality issues such as iron fouling, corrosion prevention and erosion and clogging should be referenced in Table 3.
Expansion Tank and Pump
Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. The expansion tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity rating to
prevent pump short cycling. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain fi eld, adjacent stream or pond, etc.). Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area.
The pump should be sized to handle the home’s domestic water load (typically 5-9 gpm [23-41 l/m]) plus the fl ow rate required for the heat pump. Pump sizing and expansion tank must be chosen as complimentary items. For example, an expansion tank that is too small can causing premature pump failure due to short cycling. Variable speed pumping applications should be considered for the inherent energy savings and smaller expansion tank requirements.
Water Control Valve
Note the placement of the water control valve in fi gure 9. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the discharge line to prevent mineral precipitation during the off-cycle. Pilot operated slow closing valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Insure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, a slow closing valve can draw up to 35VA. This can overload smaller 40 or 50 VA transformers depending on the other controls in the circuit. A typical pilot operated solenoid valve draws approximately 15VA (see Figure 24). Note the special wiring diagrams for slow closing valves (Figures 25 & 26).
Flow Regulation
Flow regulation can be accomplished by two methods. One method of fl ow regulation involves simply adjusting the ball valve or water control valve on the discharge line. Measure the pressure drop through the unit heat exchanger, and determine fl ow rate from Tables 11a through 11b. Since the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired fl ow of
1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second method of fl ow control requires a fl ow control device mounted on the outlet of the water control valve. The device is typically a brass fi tting with an orifi ce of rubber or plastic material that is designed to allow a specifi ed fl ow rate. On occasion, fl ow control devices may produce velocity noise that can be reduced by applying some back pressure from the ball valve located on the discharge line. Slightly closing the valve will spread the pressure drop over both devices, lessening the velocity noise. NOTE: When EWT is below
50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m per kW) is required.
14
Water-Source Heating and Cooling Systems
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Water Heat Pump Applications
Water Coil Low Temperature Limit Setting
For all open loop systems the 30°F [-1.1°C] FP1 setting (factory setting-water) should be used to avoid freeze damage to the unit. See “Low Water Temperature Cutout Selection” in this manual for details on the low limit setting.
CAUTION!
CAUTION! Many units installed with a factory or fi eld supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation. A high pressure switch must be installed on the heat pump side of any fi eld provided shut-off valves and connected to the heat pump controls in series with the built-in refrigerant circuit high pressure switch to disable compressor operation if water pressure exceeds pressure switch setting. The fi eld installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from Carrier Geothermal with a 1/4” internal fl are connection as part number 39B0005N02.
CAUTION!
CAUTION! Refrigerant pressure activated water regulating
valves should never be used with Carrier Geothermal equipment.
Figure 9: Water Well Connections
Wate r
Control
Va l v e
P/T Plugs
Flow
Regulator
Boiler
Drains
Pressure
Ta n k
Water Out
Water In
Shut-Off
Valve
Optional
Filter
Carrier: Turn to the Experts
15