TheFreshAirVentandControllerareinstalledaspartofthehome'sheatingandcoolingsystemtomanage
thequantityoffreshair introducedinto thestructure.
Withtoday'shomesbeingbuilt"tighter"for improvedenergyefficiency,manystatesandprovincesnow
requiremechanicalventilationas partof the buildingcode.Inthesetighthomes,contaminantsincluding
radon,formaldehyde,householdchemicals,smokeandotherodorscanbuildupto levelsthatexceedsafe
thresholds.
TheFreshAirVentsystemcontrollerprovidestheuserwith adjustableflexibilityto preciselysetupand
managefreshairto reduceor dilutethevolumeof "stale" air in thehome- at anaffordablepricepoint.
Thesystemallowsfreshairto beintroducedthroughouttheyear,exceptin extremetemperatureand
humidityconditions.Thecontrollerdoesnotallowthe damperto openwhenoutdoortemperaturesare
aboveIO0°F(38°C),belowO°F(-17°C),orif indoorhumiditylevelsareabove55%,inorderto prevent
conditionsthat wouldhavea negativeimpactoncomfort.
Workingwithyour FreshAirVentDampersystemtheVentilationControllertellswhen,andhowlong,it
shouldoperate.It doesthis throughcontinuousmonitoringofyourindoorhumidity,alongwith theoutdoor
temperature.Itthenoperatesaccordingtothetimersettingsasadjustedto yourpreference,or localcodes
ortheHVACindustryrecognizedASHRAE62.2-2007guidelines.
PleaseNete: TheVentilationControllerwill notworkif the outdoorfreshairintakeventis cloggedwith
debris.Cleanthisregularly.Alsopleasemakesureto notobstructorcloseoffthereturnairgrillesof your
heatingsystemin ordertoprotectyourfurnace.
YourVentilationControlleris installedinthe returnductofyourfurnaceorheatpump.Therearetwo adjustable
settings,thecycle time andtheactualventilationtime withineachcycle.Here'showthisworks.Ifthe
cycletime issetto 2 hoursandthecontrollerknobissetto40minutes,youwill get40minutesofventilation
everytwo hours.
Yourventilationsetting,whichis40minutesevery2hoursinthis example,canbemetbytheoperationof
yourheatingorcoolingsystem.Orif weatherconditionsarecomfortableorthethermostatisonsetback,the
Controlleritselfwill turnonthe furnaceblowerto providethe40minutes.
• YourInstallershouldhavealreadysetthisfor you.Thiswill likelybeatthe recommendedfactorysetting
oftwo hours.
Ifthereisaneedto changethis,consultyourdealer.
Theknobonthefrontof the Controlleris usedtosetthe
ventilationtime withinthecycleintervalsetinStepA.
TheTESTsettingis usedto checkthe deviceforproper
installation.Itisnotfor normaloperation,it will only
activatetheControllerfor 1minute.Donotleavetheknob
atTEST,it doesnotallow actualoperatingtime.
TheOFFsettingcutsoff all circuitactivation,while 0
leavesthe circuitelectricallyactivebut itwill notoperate.
Thedialislabeledin 15minuteincrements,butcanbesetto
anyestimatedvaluewithin 5minuteaccuracy.TheInstaller
will havealreadysetthisfor youaccordingto the sizeand
numberofoccupantsforyourhome.Ifyoufeellikeyouneed
moreorlesstime,turntheknobto a maximumof5minutes
eitherway.Seehowthis worksbeforeadjustingagain.
60
3O
0
MINUTES PER CYCLE
AsinstalledyourVentilationControllerwill useinputmeasurementsofOutdoorTemperatureandIndoor
Humidity,plustheadjustedtimesettings,tocomputeactivation.Thetemperatureoutdoorsismeasured
with a sensoratthefreshair ductinlet.IndoorHumidityismeasuredinthe returnductwith asensorbuilt
intotheController.Incoordinationwith thetimersettings,theControllerthenoperatesaccordingto the
temperatureandhumiditylimitsshownin Diagram1below.
..=.
o,.
oo
15% 25% 35% 45% 55% 65%
iNDOOR RELATIVE HUMiDiTY
SectionA:Ventilationpreventedduetotemperatureextremesand/orhighindoorhumidity.
SectionB:Ventilationperthetimersettings.
SectionC:Ventilationoptionalif required.Consultyourdealerforrecommendations.
Ifthe "TIMEONLY"resistorisusedinsteadof theOutdoorTemperatureSensor,the Controller'soperationis
determinedbythetimersettingsasadjustedonly.TheControllerwill notlimit operationbasedon the
temperatureandhumiditylimitsasshownin Diagram 1.Thisfeatureis importantfor areaswithmoderate
climates.
Ifa jumperwireis usedinplaceof the OutdoorTemperatureSensor,theControllerwill disregardthe
temperaturesettingandbaseventilationoperationontheindoorrelativehumidityandthe timersettings
only.Inthis modetheControllerwon'tallowventilationif the indoorRHrisesabove55%.