FA4A
Product
Data
®
Direct Expansion
FB4A
FC4B
Fan Coil
Sizes 018 thru 070
Air Handling Technology At
Its Finest
Carrier’s FA4A, FB4A, and FC4B
direct expansion multipoise fan coils
are designed to cover a wide range
of air handling requirements. They
are compact and ready to fit where
needed — in the basement, crawlspace, attic, utility room, or closet.
All units come with solid-state
power board controls, 1-in. insulation
with an R value of 4.2, super-quiet
multispeed motors, and fully wettable
coils. Units can accommodate
factory- or field-installed heaters
from 3 to 30 kw.
The FA4A is the residential new
construction (RNC) model in the
line-up. It has an embossed
galvanized steel casing, 2-speed
motor in 018 through 036 sizes and
3-speed motor in 042 through 060
sizes. The FA4A is equipped with an
AccuRater
The FB4A is the standard of
Carrier fan coils. It comes in a
prepainted galvanized steel casing
with foil-faced insulation and has a
3-speed motor in the full range of sizes
018 through 070. All FB4A units are
equipped with an AccuRater metering
device and are also shipped with a
cleanable, permanent framed filter.
The FC4B is the deluxe design in
the fan coil group. It incorporates all
the features found in the FB4A. In
addition, it has a hard shut-off
thermostatic expansion valve (TXV)
metering device with internal check
valve for reverse-flow bypass
capability. The FC4B is available in
sizes 024 through 070.
metering device.
Copyright 1996 Carrier Corporation Form FA4A-5PD
Standard features
• Grooved copper tubing
• Lanced sine-wave aluminum fin
• Fully wettable coils
• High-impact thermoplastic condensate pan
• Primary and secondary drain connections with brass inserts
• Multipoise design for maximum versatility
• Field-installed heater packages from 3–30 kw (fused, circuit breaker, non-fused)
• Control board with built-in, replaceable 5-amp blade-type auto fuse
• Cooling controls
• Time-delay relay (TDR)
• High-density, super thick R 4.2 insulation
• Sweat connections
• Inspection plate for cleaning A-coil design
• HUD approved for manufactured housing
• 40-va, 208/230-v transformer
• All models listed with UL, cUL, ARI, and RADCO
Additional features
FA4A
• 018-060 sizes
• Embossed galvanized steel cabinet
• 2-speed motor in 018 through 036 sizes
• 3-speed motor in 042 through 060 sizes
• AccuRater metering device
• Factory-installed heaters available
FB4A
• 018-070 sizes
• Prepainted galvanized steel cabinet
• 3-speed motor on all sizes 018 through 070
• Modular version available in 042 through 070 sizes
• AccuRater
• Foil-faced, high density insulation
• Factory-supplied, cleanable, permanent framed filter
• Factory-installed heaters available
• Factory-supplied power plug
• Multiple electric entry
metering device
FC4B
• 024-070 sizes
• TXV
• Prepainted galvanized steel cabinet
• 3-speed motor on 024 through 070 sizes
• Modular version available in 054 and 070 sizes
• Foil-faced, high-density insulation
• Factory-supplied, cleanable, permanent framed filter
• Factory-supplied power plug
• Multiple electric entry
2
A Common Unit
E Minor Engineering Change
A Standard Unit
A Standard Unit
Electric Heater (kw)
003 015
005 020
008 024
009 030
010
W
G
I
T
N
H
I
Y
L
P
M
O
C
S
A
A
I
E
H
R
A
O
T
D
E
I
F
I
T
Y
R
E
C
R
E
R
L
P
M
O
C
S
A
N
O
I
C
R
R
I
A
A
O
T
D
E
I
F
I
T
Y
R
E
C
R
E
R
0
4
P
M
U
2
P
T
R
A
T
I
U
T
I
Y
T
I
D
R
A
T
I
U
T
D
T
R
N
A
E
M
D
P
®
I
N
U
Q
A
E
T
S
I
N
U
R
A
M
A
C
N
A
F
U
W
G
I
T
N
H
0
1
N
I
G
N
O
I
2
D
T
R
N
A
E
M
D
P
I
N
U
Q
A
E
T
S
I
N
U
R
A
M
A
C
N
A
F
U
COMPLETE SYSTEM IS LISTED WITH ARI.
CERTIFICATION APPLIES ONLY WHEN THE
Nominal Capacity (Btu)
018 — 18,000 042 — 42,000
024 — 24,000 048 — 48,000
030 — 30,000 060 — 60,000
036 — 36,000 070 — 60,000
B — Modular with 1 in. Super Thick Insulation
C — Factory Installed Disconnects
F— Single Piece Cabinet with 1 in. Super Thick Insulation
N — 208/230-1-60
A — Original Series
B — Second Series
4 — Multipoise
®
• TESTING • INSPECTION
• CERTIFICATION • LISTING
F C 4 B N F 024 005 AEAA
Model number nomenclature
A — RNC
B — Standard
C — Deluxe
F — Fan Coil
3
A95535
TOP VIEW
″
16
⁄
1
22
″ FPT
4
⁄
3
″ ID SWEAT
8
⁄
7
″ ID SWEAT,
4
⁄
3
003, 005, & 006
UNIT CONNECTION SIZES
SUCTION: 001 & 002 -
DIA KNOCKOUTS
″
8
⁄
FOR LOW VOLTAGE
7
Series designation is the 14th position
of unit model number.
NOTE:
″ ID SWEAT
8
⁄
3
LIQUID:
CONDENSATE PAN CONNECTIONS:
1″
CONTROL WIRING
″
8
⁄
7
1
″
8
⁄
7
11″
″
16
⁄
3
1″
10
″
8
⁄
3
″ , 2″ DIA KNOCKOUTS
1
32
⁄
3
″ , 1
8
⁄
FOR HIGH VOLTAGE POWER WIRING
7
″
4
⁄
3
OUTLET AIR
″
8
⁄
1
2
ALTERNATE
DIA KNOCKOUT
″
8
⁄
7
FOR LOW VOLTAGE
for service.
Allow 21 In. from front
NOTE:
DISCONNECT OR CIRCUIT
BREAKER LOCATION
B
C
″
16
⁄
″
15
16
⁄
1
15
H
FOR
MODULAR
OPTIONAL FILED
COPNVERTED RIGHT
SIDE RETURN
OPENING
(SLOPE COIL
UNITS ONLY)
″ ,
8
⁄
7
19″
″ , 2″ DIA
32
⁄
3
ALTERNATE
KNOCKOUTS FOR
HIGH VOLTAGE
POWER WIRING
OPPOSITE SIDE
1
″
4
⁄
1
1
A
INLET AIR
CONTROL WIRING
E
LIQUID LINE
CONNECTION
LIQUID LINE
CONNECTION
BLOWER, CONTROL, & ELECTRIC
HEATER ACCESS PANEL
COIL ACCESS PANEL
″
″
16
16
⁄
⁄
1
11
3
4
LIQUID LINE
CONNECTION
FITTING
PANEL
5
″
8
⁄
2
UNITS
J
MAX.
″
2
⁄
1
1
will have a
two-piece
cabinet.
NOTE: Modular units
″
16
⁄
11
″
2
⁄
1
9
″
4
⁄
3
10
SUCTION LINE
CONNECTION
5″
″
16
⁄
7
10
″
2
⁄
1
2
OPENING
″
16
⁄
13
19
RIGHT SIDE VIEW
″
4
⁄
1
1
ACCESS PANEL CONFIG FOR
SUCTION LINE
CONNECTION
SLOPE COIL DETAILS
″
16
⁄
3
FILTER ACCESS
PANEL
6
D
OPENING
1″
INLET AIR
SLOPE COILS
AND "A" COILS
RIGHT APPLICATIONS
DOWNFLOW OR HORIZ
DOWNFLOW APPLICATIONS
CONNECTION LOCATIONS
SHOWN FOR UPFLOW
OR HORIZ LEFT APPLICATIONS
INLET AIR
DETAILS CONNECTION LOCATIONS
FRONT VIEW SHOWN WITH "A" COIL
FOR UPFLOW OR HORIZ APPLICATIONS
ABCDEH †J
In. mm In. mm In. mm In. mm In. mm In. mm In. mm
Dimensions
4
4
COIL
TYPE
UNIT
SIZE*
Slope 42-11/16 1084.3 14-5/16 363.5 12-7/16 316.0 12-5/16 312.7 10-7/16 265.1 — — 12.0 304.8
018, 024
Slope 47-11/16 1211.5 17-5/8 447.5 15-3/4 400.1 15-5/8 396.9 15-3/8 390.5 — — 17.0 431.8
030
Slope 49-5/8 1260.5 17-5/8 447.5 15-3/4 400.1 15-5/8 396.9 15-3/8 390.5 — — 17.0 431.8
036
Slope 53-7/16 1357.3 21-1/8 536.5 19-1/4 489.0 19-1/8 485.8 19-3/16 487.0 28-5/16 719.1 19.0 482.6
033, 042
A 49-5/8 1260.5 21-1/8 536.5 19-1/4 489.0 19-1/8 485.8 15-11/16 398.3 24-1/2 622.3 — —
048
A 53-7/16 1357.3 21-1/8 536.5 19-1/4 489.0 19-1/8 485.8 19-1/2 495.3 28-5/16 719.1 — —
038, 060
A 59-3/16 1503.4 24-11/16 627.0 22-3/4 577.9 22-11/16 576.2 25-1/4 641.5 34-1/16 865.2 — —
054, 070
* Descriptions and dimensions apply to all versions (FA4A, FB4A, and FC4B), unless otherwise specified.
† Applicable for modular units only.
⁄16″
3
2
TYP
(2 PLACES)*
AIRFLOW
SLOPE COIL
″
16
⁄
7
AIRFLOW
TYP
(4 PLACES)*
PRIMARY DRAIN
SECONDARY DRAIN
″
16
⁄
5
G
″
″
4
⁄
16
⁄
1
5
3
1
F
1″
TYP
(2 PLACES)*
″
PRIMARY DRAIN
16
⁄
13
1
SECONDARY DRAIN
PRIMARY DRAIN
TYP*
PRIMARY DRAIN
SECONDARY DRAIN
″
16
⁄
3
2
″
16
⁄
3
1
TYP*
SECONDARY DRAIN
TYP*
(2 PLCS)
A95531
″
8
⁄
TYP*
″
2
⁄
1
″
16
⁄
5
1
″
16
/
7
TYP
1″
″
8
⁄
7
2
5
″
16
⁄
5
″
⁄
7
2
1
″
8
⁄
7
″
TYP*
16
⁄
11
1
2″
″
16
⁄
13
TYP*
1
(4 PLACES)*
TYP
(2 PLACES)*
″
8
⁄
2
″
4
⁄
″
1
2
⁄
2
1
1
″
16
⁄
TYP*
11
1
8
5″
″
″
2
8
⁄
⁄
TYP*
7
TYP*
HORIZ RIGHT
(FIELD CONVERTED)
F
″
16
⁄
3
2
TYP
(2 PLACES)*
AIRFLOW
DOWNFLOW
(FIELD CONVERTED)
″
16
⁄
TYP
7
UPFLOW
(AS SHIPPED)
AIRFLOW
HORIZ LEFT
(AS SHIPPED)
TYP*
SECONDARY DRAIN
G
″
4
⁄
3
4
(4 PLACES)*
1″
PRIMARY DRAIN
SECONDARY DRAIN
SECONDARY DRAIN
PRIMARY DRAIN
″
16
⁄
TYP*
5
″
8
⁄
1
3
F
TYP
(2 PLACES)*
″
16
⁄
13
TYP*
1
PRIMARY DRAIN
SECONDARY DRAIN
1″
TYP
(2 PLACES)*
PRIMARY DRAIN
″
2
⁄
1
TYP*
″
4
⁄
1
1
″
8
⁄
7
5
″
16
⁄
13
1
″
16
⁄
7
3″
″
16
⁄
11
2
″
16
⁄
3
TYP
2
″
16
⁄
5
″
8
⁄
7
5
″
4
⁄
1
1
″
2
⁄
1
1
″
2
⁄
1
7
″
2
⁄
1
1
″
8
⁄
7
7
TYP*
TYP
(4 PLACES)*
″
4
⁄
″
3
8
⁄
4
1
3
(2 PLACES)*
TYP*
″
8
⁄
7
7
TYP*
HORIZ RIGHT
(FIELD CONVERTED)
DOWNFLOW
(FIELD CONVERTED)
A–COIL
UPFLOW
(AS SHIPPED)
HORIZ LEFT
(AS SHIPPED)
FG
In. mm In. mm
A 23-7/16 593.3 23-1/8 587.4
A 27-1/4 692.2 26-1516 684.2
COIL
TYPE
Slope 18-1/8 460.4 18-5/8 473.1
Slope 23-1/8 587.4 23-5/8 600.0
Slope 23-1/8 587.4 23-5/8 600.0
Slope 26-15/16 684.2 27-1/2 698.5
A 32-15/16 836.6 32-5/8 828.7
PANEL, AND BACK OF CABINET. IN CABINET BOTTOM, HOLES PROVIDED
.136 IN. DIA. HORIZONTAL HANGING HARDWARE TO BE FIELD
SUPPLIED.
* HORIZONTAL MOUNT LOCATIONS - DIMPLES PROVIDED IN TOP
Dimensions continued
″
8
⁄
7
TYP*
030
036
UNIT
SIZE*
018, 024
033, 042
048
038, 060
054, 070
* Descriptions and dimensions apply to all versions (FA4A, FB4A, and FC4B), unless otherwise specified.
5