Carrier 40MFC, 38MFC, 40MFQ, 38MFQ, DACMA Installation Instructions Manual

...
Page 1
40MFC / 38MFC 40MFQ / 38MFQ High---Wall Ductless Split System Sizes 009 to 022
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PARTS L IST 2.......................................
MODEL NUMBER NOMENCLATURE 2.................
SAFETY CONSIDERATIONS 3.........................
SYSTEM REQUIREMENTS 3..........................
DIMENSIONS 5......................................
CLEARANCES 6.....................................
INSTALLATION TIPS 7...............................
INDOOR UNIT INSTALLATION 7.......................
OUTDOOR UNIT INSTALLATION 8.....................
INSTALL ALL POWER AND INTERCONNECTING WIRING
TO OUTDOOR UNIT 8................................
ELECTRICAL DATA 9................................
CONNECTION DIAGRAMS 9..........................
INSTALL ALL POWER, INTERCONNECTING WIRING,
AND PIPING TO INDOOR UNIT 10.....................
REMOTE CONTROL INSTALLATION 10.................
SYSTEM VACUUM AND CHARGE 11...................
START--UP 12........................................
TROUBLESHOOTING 13..............................
Page 2
PARTS LIS T
Part
No.
1 Indoor Unit 1 2 Mounting Plate 1 3 M o u n t ing S c r e w A S T 3 . 9 x 2 5 --- C --- H 5 4 Anchor 5 5 Air Filter 1 6 Remote Control 1 7 Remote Control Holder 1 8 M o u n t ing S c r e w B S T 2 . 0 x 1 0 --- C --- H 2 9 Outdoor Unit 1
Name of P art Qty
■ Indoor
6
I o n
8
■ Outdoor
3
4
1
2
5
A U T
O
C
O O
D
L R Y
H E
A T
F A
N H I G
H
T
M
E
E
M
D
L
P
M
O
o
W
d e
O n/
S
O
w
f
f
i n
g
F a
n S e
l f C
S
l e
l e
a
e
n
p
F
ol l o
i
w z er
M
e
S
T
ma
L
i
m
E
r
D
e
t E
r
y
e
T u
r
F.P.
b o
S
i l e n
c e
Air Outlet
7
9
Note:
--- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe bef ore i t enters the wall to the indoor unit. This will ensure that rain will drip from the connection pipe before it enters the wall.
--- Piping and the interconnecting wiring are field supplied.
--- The illustration above is only a sketch. Different models may be slightly different.
A14342
MODEL NUMBER NOMENCLATURE
38 MFC 009 - - - 1
Voltage 1 = 115-1-60Hz; 3 = 208-230-1-60Hz
System’s nominal capacity in 1000 BTU/Hr Example: 009 = 9000 BTU/Hr
System’s type: MFC = Air Conditioner;
MFQ = Heat pump Equipment type: 40 = Indoor unit; 38 = Outdoor unit
Blank
2
Page 3
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the
!
!
safety--alert symbol in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious h azards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
. When you see this symbol on the unit and
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start--up.
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and servicing unit. See Fig. 1 and 4 for minimum required distances between unit and walls or ceilings.
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.
S Minimum refrigerant line length between the indoor and outdoor
units is 10 ft. (3 m).
S The following maximum lengths are allowed:
REFRIGERANT LINE LENGTHS ft. (m)
Unit Size Max Line Length
9K 65 (20) 25 (8) 25 (8)
12K 65 (20) 25 (8) 25 (8) 17K HP 65 (20) 30 (10) 30 (10) 18K AC 65 (20) 30 (10) 30 (10)
22K 98 (30) 30 (10) 30 (10)
S The following are the piping sizes.
PIPE SIZES (in)
Unit Size Mix Phase Vapo r
9K 1/4 3/8
12K 1/4 1/2 17K HP 1/4 1/2 18K AC 1/4 1/2
22K 3/8 5/8
Refrigerant Charge
REFRIGERANT CHARGE lb. (kg)
Unit Size Air Conditioner (AC)
9K 1.34 (0.61) 2.70 (1.18)
12K 1.43 (0.65) 2.70 (1.18) 17K HP NA 2.87 (1.30) 18K AC 1.87 (0.85) NA
22K 2.60 (1.18) 3.52 (1.60)
S Above charge is for piping runs up to 25 ft. (7.6 m). S For piping runs greater than 25 ft. (7.6 m), add refrigerant
up to the allowable length as specified below:
ADDITIONAL REFRIGERANT CHARGE
Unit Size oz./ft. (g/m)
9K --- 18K 0.16 (15)
22K 0.32 (30)
S Capillary tubes in outdoor unit are used as metering devices.
Max Elevation
(ID over OD)
Max Elevation
(OD over ID)
Heat Pump (HP)
3
Page 4
Recommended Connection Method for Power and cation Wiring (To minimize communication wiring ence)
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt rating and 2/64 --inch thick insulation must be used.
Communication Wiring:
A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64--inch thick insulation, must be used as the communication wire from the outdoor unit to the indoor unit.
To minimize voltage drop of the control wire, use the following wire size and maximum lengths shown in the chart below:
Wire Size
18 AWG 50 (15) 16 AWG 50 (15) to 100 (30)
Communi-
interfer-
Length
ft (m)
Alternate Connection Method for Power and Communication Wiring (May not prevent communication wiring interfer
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four (4) wires and provides the power and communication signals for the indoor unit. Two conductors are for power wiring (L1/L2, or L/N), one is a ground wire, and one is a DC communication wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements. All power wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt rating and 2/64 --inch thick insulation must be used.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
CAUTION
ence)
4
Page 5
DIMENSIONS -- INDOOR
Unit Size W in (mm) D in (mm) H in (mm) Operating Weight lb (kg)
9K 26.8 (680) 7.0 (178) 10.0 (255) 15.4 (7)
12K 30.3 (770) 7.4 (188) 10.0 (255) 16.5 (7.5)
17K HP / 18K AC 35.6 (905) 7.8 (198) 10.8 (275) 19.8 (9)
22K 40.6 (1030) 8.6 (218) 12.4 (315) 26.4 (12)
DIMENSIONS -- OUTDOOR
A14343
L1
L2
Model W in (mm) D in (mm) H in (mm) L1 in (mm) L2 in (mm)
9K/12K 30.7 (780) 9.84 (250) 21.2 (540) 21.61 (549) 10.87 (276) 70.5 (32.0)
17K HP / 18K AC 29.9 (760) 11.2 (285) 23.2 (590) 20.87 (530) 11.42 (290) 82.7 (37.5)
22K 33.3 (845) 12.6 (320) 27.6 (700) 22.05 (560) 13.19 (335) 103.6 (47.0)
D
Operating
Weight lb (kg)
A14344
5
Page 6
CLEARANCES -- INDOOR
"
5
(0.13m)
min.
CEILING
6" (0.15m) min.
(1.8m)
6'
FLOOR
Fig. 1 --- Indoor Unit Clearance
5
"
(0.13m)
min.
A07891
CLEARANCES -- OUTDOOR
A
D
B
Air-outlet
UNIT
A 24 (610)
B 24 (610) C 80 (2032)
D 12 (305) E 24 (610)
Fig. 2 --- Outdoor Unit Clearance
Minimum Value
in. (mm)
Air-inlet
E
C
A07894
6
Page 7
INSTALLATION TIPS
Ideal installation locations include:
Indoor
Unit
S A location where there are no obstacles near inlet and outlet area. S A location which can bear the weight of indoor unit. S Do not install indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
S A location which provides appropriate clearances as outlined in
Fig. 1.
Outdoor
Unit
S A location which is convenient to installation and not exposed to
strong wind.
S A location which can bear the weight of outdoor unit and where
the outdoor unit can be mounted in a level position.
S A location which provides appropriate clearances as outlined in
Fig. 2.
S Do not install the indoor or outdoor units in a location with
special environmental conditions. For those applications, contact your Ductless Split representative.
INDOOR UNIT INSTALLATION
INSTALL MOUNTING PLATE
The mounting plate will look like one of the following depending on model size:
6 (150) or more to ceiling
5 (130) or more to wall
Left rear side refrigerant pipe hole ¶2.6 (65)
6.7 (170)
26.8 (680)
Fig. 3 --- Mounting Plate-- Model size 009
6 (150) or more to ceiling
6.7 (170)
5 (130) or more to wall
Left rear side refrigerant pipe hole 2.6 (65)
1.8 (45)
30.3 (770)
Fig. 4 --- Mounting Plate-- Model size 012
6 (150) or more to ceiling
3.2 (80)
5 (130) or more to wall
Left rear side refrigerant pipe hole 2.6 (65)
35.6 (905)
Fig. 5 --- Mounting Plate-- Model sizes 017 (AC) / 018 (HP)
Indoor unit outline
3.6 (92)


in. (mm)
Indoor unit outline
3.7 (95)
1.6 (41)
1.8 (45)
in. (mm)
3.9 (100)
1.4 (36.5)
in. (mm)
5 (130) or more to wall
10(255)
Right rear side refrigerant pipe hole ¶2.6 (65)
5 (130) or more to wall
10 (255)
Left rear side refrigerant pipe hole 2.6 (65)
Indoor unit outline
5 (130) or more to wall
1.8 (45)
10.8 (275)
Left rear side refrigerant pipe hole 2.6 (65)
A14345
A14346
A14347
1. Carefully remove the mounting plate, which is attached to the back of the indoor unit.
2. The mounting plate should be located horizontally and level on the wall. All minimum spacings shown in Fig. 1 and 3 through 6 should be maintained.
3. If the wall is block, brick, concrete or similar material, drill .2” (5 mm) diameter holes and insert anchors for the ap­propriate mounting screws.
4. Attach the mounting plate to the wall.
DRILL HOLE IN WALL FOR INTERCONNECTING PIPING, DRAIN AND WIRING
Refrigerant Line Routing
The refrigerant lines may be routed in any of the four directions showninFig.8.
For maximum serviceability, it is recommended to have refrigerant line flare connections and the drain connections on the outside of the wall that the fan coil can be mounted on.
If piping is going through the back:
1. Determine pipe hole position using the mounting plate as a template. Drill pipe hole diameter per values given in Fig. 3 through 6. The outside pipe hole is 1/2 --in. (13 mm) min. lower than inside pipe hole, so it slants slightly downward (see Fig. 7).
1/2 in. (13 mm)
Min.
INDOOR
Fig. 7 --- Drill Holes
If piping is going through the right or left side:
1. Use a small saw blade to carefully remove the correspond­ing plastic covering on side panel and drill the appropriate size hole where the pipe is going through the wall.
Pipe holder
Pipe cover
1
Right piping
Fig. 8 --- Piping Locations
OUTDOOR
2
Right back piping
Pipe cover
4
Left piping
3
Left back piping
A07371
A14349
Indoor unit outline
5 (130) or more to wall
Left rear side refrigerant pipe hole 2.6 (65)
6 (150) or more to ceiling
11.5 (292) 6.4 (163)
Installation plate
40.6 (1030)
0.8 (21.5)
Fig. 6 --- Mounting Plate-- Model size 022
1.8 (45)
12.4 (315)
Left rear side refrigerant pipe hole 2.6 (65)
in. (mm)
5 (130) or more to wall
A14348
7
Page 8
OUTDOOR UNIT INSTALLATION
G
1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
In regions with snowfall and cold temperatures, avoid installing the outdoor unit in areas where it can be covered by snow. If the outdoor unit is installed in areas where heavy snow is expected, a field supplied ice or snow stand and/or field supplied--installed wind baffle should be installed to protect the unit from snow accumulation and/or blocked air intake. Blocking the air intake may result in reduced airflow, significantly reduced performance and damage to the equipment.
CAUTION
Strong
wind
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Excessive torque can break flare nut depending on installation conditions.
CAUTION
INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNITS
1. Mount outdoor power disconnect.
2. Run power wiring from main box to disconnect per NEC and local codes.
3. Remove field wiring cover from unit by loosening screws.
4. Remove caps on conduit panel.
5. Connect conduit to conduit panel. (See Fig.11 )
6. Properly connect both power supply and control lines to ter­minal block per the connection diagram for the appropriate unit capacity and voltage. (See Fig. 12)
7. Ground unit in accordance with NEC and local electrical codes.
8. Use lock nuts to secure conduit.
9. Reinstall field wiring cover.
A07350
Fig. 9 --- High Wind Installation
MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT)
IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be used. Use of other types of tubing will void manufacturer’s warranty.
Do not open service valves or remove protective caps from tubing ends until all the connections are made.
Bend tubing with bending tools to avoid kinks and flat spots.
Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation of oil traps. Insulate each tube with minimum 3/8--in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections will save time and improve installation quality.
1. Remove service valve cover if provided with unit.
2. Cut tubing with tubing cutter. Remove service connection if provided with unit.
3. Install correct size flare nut onto tubing and make flare con­nection.
4. Apply a small amount of refrigerant oil to the flare connec­tion on the tubing.
5. Properly align tubing in with service valve.
6. Tighten flare nut and finish installation using two wrenches as shown in Fig. 10.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
Outdoor unit
Terminal Block
Over 1.57" (40mm)
CAUTION
Conduit panel
Conduit
Fig. 11 --- Field Wiring
A07455
Fig. 10 --- Tighten Flare Nut
A07354
8
Page 9
ELECTRICAL DATA
OPER.
UNIT SIZE
9K
12K
12K
017K (HP) /
018K (AC)
22K 9.70 17 0.6 0.72 53 0.4 0.061 45 16 25
VOLTAGE
MAX / MIN
127 / 104 115--- 1 --- 6 0 5.30 10 1 15 --- 1 --- 60 0.7 0.31 23 1 1 5 --- 1 --- 60 0.3 0.020 15 19 30
253 / 187 20 8 --- 2 30 --- 1 --- 6 0
COMPRESSOR OUTDOOR FAN INDOOR FAN
V --- P H --- H Z RLA LRA V --- P H --- H Z FLA HP W V --- P H --- H Z FLA HP W
5.30 10
3.95 14 0.6 0.68 50 0.3 0.038 28 14 20
2 08 --- 2 30 --- 1 --- 6 0
0.3 0.33 24
0.2 0.027 20 10 15
2 08 --- 2 30 --- 1 --- 6 0
MCA
CONNECTION DIAGRAMS
MAX FUSE
CB AMP
CONNECTING CABLE
115-1-60 FIELD POWER SUPPLY
OUTDOOR TO INDOOR
GND
2(N)
1(L)
GND
L
N
Indoor Unit Power Supply
115-1-60
9K and 12K 115V INDOOR UNIT 9K and 12K 115V OUTDOOR UNIT
S
Indoor Signal High Voltage
Ground
Power to Indoor Unit
115-1-60
S
Indoor Signal High Voltage
CONNECTING CABLE
L
N Main Power Supply
115-1-60
208-230-1-60 FIELD POWER SUPPLY
OUTDOOR TO INDOOR
GND
L1
GND
L1
L2
Indoor Unit Power Supply
208-230-1-60
12K to 22K 208-230V INDOOR UNIT
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
S
Indoor Signal High Voltage
Ground
Power to Indoor Unit
208-230-1-60
12K to 22K 208-230V OUTDOOR UNIT
L2
S
Indoor Signal High Voltage
L1
Main Power Supply
208-230-1-60
L2
Fig. 12 --- Connection Diagrams
9
Page 10
INSTALL ALL POWER, INTERCONNECTING
k
WIRING, AND PIPING TO INDOOR UNIT
1. Run interconnecting piping and wiring from outdoor unit to indoor unit.
2. Run interconnecting cable through hole in wall (outside to inside).
3. Lift indoor unit into position and route piping and drain through hole in wall (inside to outside). Fit interconnecting wiring into back side of indoor unit.
4. Put upper claw at back of indoor unit on upper hook of Mounting Plate, move indoor unit from side to side to see that it is securely hooked.
5. Open front cover of indoor unit and remove field wiring ter­minal block cover.
6. Pull interconnecting wire up from back of indoor unit and position in close to the terminal block on indoor unit.
7. Push lower part of indoor unit up on wall, then move in­door unit from side to side, up and down to check if it is hooked securely. (See Fig. 13.)
Upper hook
Lower hoo
Fig. 13 --- Indoor Unit Installation
8. Connect wiring from outdoor unit per connection diagram (see Fig. 12 and Fig. 16).
9. Replace field wiring cover and close front cover of indoor unit.
10. Connect refrigerant piping and drain line outside of indoor unit. Refer to Fig. 10 for proper installation of flare connections. Complete pipe insulation at flare connection then fasten piping and wiring to the wall as required. Com­pletely seal the hole in the wall.
11. Connect the drain line. The drain line must not have a trap anywhere in its length, must pitch downwards, and must be insulated up to the outside wall. See Fig. 14.
A07347a
Indoor unit
Interconnecting Wiring
Drain Piping
Fig. 15 --- Proper Orientation
NOTE: For applications where gravity cannot be used for
drainage, a condensate pump accessory is available. Consult the condensate pump Installation Instructions for more information.
REMOTE CONTROL INST ALLATION
Mounting Bracket (if installed o n the wall)
1. Use the two screws supplied with control to attach Mount­ing Bracket to wall in location selected by customer and within operating range.
2. Install batteries in Remote Control.
3. Place Remote Control into remote control Mounting Brack­et.
4. For remote control operation, refer to the unit Owner’s Manual.
Front Panel
9K and 12K 115V 12K to 22K 208-230V
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. .
.
Refrigerant Piping
.
Tape
A07346
.
.
..
.
.
.
. .
.
.
.
Electrical box cover
Proper Do not put drain end into waterDo not form a rise
Fig. 14 --- Proper Drain Hose Installation
NOTE: For proper orientation of the refrigerant piping, electrical
cable and drain lines, refer to Fig. 15.
LNS L1 L2 S
A14352
Fig. 16 --- Control and Power Wiring on Indoor Unit
A14351
10
Page 11
!
t
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve. (See Fig. 17)
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage. (See Fig. 18)
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation method.
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add refrigerant, up to the allowable length, as specified in the System Requirements section.
8. Disconnect charge hose from charge connection of the low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
Refrigerant
Low Side
A
High Side
B
Fig. 17 --- Service Valve
Manifold Gage
Indoor Uni
C
D
A07360
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 19)
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A95424
Fig. 19 --- Deep Vacuum Graph
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 20 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. Dur­ing this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 20. System will then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
500 microns
Low side valve
Charge hose
Low side valve
High side valve
Charge hose
Fig. 18 --- Manifold
Vacuum pump
A07361
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 20 --- Triple Evacuation Method
Final Tubing
Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
11
Page 12
START--UP
Tes t Operation
Perform test operation after completing gas leak and electrical safety check. (See Fig.. 21)
Manual control
button
Fig. 21 --- Test Operation
1. Push the “ON/OFF” button on Remote Control to begin testing.
NOTE: A protection feature prevents air conditioner from being activated for approximately 3 to 4 minutes.
2. Push MODE bu tton, select COOLING, HEATING, FAN mode to check if all functions work correctly.
3. To run the test using the manual button in the indoor unit:
(1.) Open front panel of the indoor unit; (2.) Push the manual switch once to energize the unit.
The set conditions of manual operation are as fol­lows:
· Preset set point: 76_F(24_C)
· Fan speed: AUTO
· Discharge air direction: Pre-- set position based on operation in “Cool” or “Heat” mode.
AUTO/COOL
A14353
SYSTEM CHECKS
1. Conceal the tubing where possible.
2. Make sure that the drain tube slopes downward along its en­tire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall, when possible.
5. Seal the hole through which the cables and tubing pass.
INDOOR UNIT
1. Do all Remote Control buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drain work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
Explain Following Items To Customer (with the aid of the Owner’s Manual):
1. How to turn air conditioner on and off; selecting COOLING, HEATING and other operating modes; setting a desired temperature; setting the timer to automatically start and stop air conditioner operation; and all other features of the Remote Control and display panel.
2. How to remove and clean the air filter.
3. How to set air deflection louver.
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions to customer.
4. Be sure to set manual switch to “OFF” (by pushing it twice again) after finishing test operation.
NOTE: For Heat Pumps, follow the same procedure.
12
Page 13
TROUBLESHOOTING
For ease of service, the systems are equipped with diagnostic code display LEDs on both the indoor and outdoor units. The outdoor diagnostic display is two LEDs (Red and Green) on the outdoor unit board and is limited to very few errors. The indoor diagnostic
the front of the unit. If possible, always check the diagnostic codes displayed on the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are listed in the tables below.
display is a combination of flashing LEDs on the display panel or
INDOOR UNIT DIAGNOSTIC GUIDES
Operation Lamp Timer Lamp Display Failure Mode
1time X E0 Indoor unit EEPROM parameter error2times X E1 Indoor / outdoor units communication error3times X E2 Zero-crossing signal detection error4times X E3 Indoor fan speed has been out of control5times X E4 Indoor room temperature sensor is open circuit or short circuited6times X E5 Evaporator coil temperature sensor is open circuit or short circuited2times On F1 Outdoor temperature sensor is open circuit or short circuited3times On F2 Condenser coil temperature sensor is open circuit or short circuited4times On F3 Compressor discharge temperature sensor is open circuit or short circuited5times On F4 Outdoor unit EEPROM parameter error1times P0 IPM malfunction or IGBT over-strong current protection2times P1 High or low voltage low voltage protection activated5times P4 Inverter compressor drive error
= Flashing, X = Off
For additional diagnostic information, refer to the Service Manual
OUTDOOR UNIT DIAGNOSTIC GUIDES
Green LED Red LED Failure Mode
On X Standby, normal
X On Operation, normal
On On High/Lowvoltageprotectiononcompressorterminal On EEPROM error
X Compressor’s speed is out of control
On Zero --- crossing signal d etection error; lack of phase; synchronization error X IGBT or Module protection
= Flashing, X = Off For additional diagnostic information, refer to the Service Manual
Communication error
13
Page 14
Copyright 2014 Carrier Corporation S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Edition Date: 05/14
Catalog No: 38 --- 40MF--- 1SI
Replaces: New
14
Loading...