Carrier Comfort Pro 33CSCNACHP-01 Installation Instructions Manual

°
F
actual temp
set at
mode
fan
Fig. 1 — Comfort Pro Non-Programmable
Commercial Thermostat
a33-9224
Non-Programmable
Commercial Thermostat
Installation Instructions
Part Number 33CSCNACHP-01
Comfort™ Pro
IMPORTANT: Read entire instruction before installing the thermostat.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION CONSIDERATIONS. . . . . . . . . . . . . .1,2
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Thermostat Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,3
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Entering and Exiting Configuration Mode . . . . . . . . 3
Exiting Configuration Mode . . . . . . . . . . . . . . . . . . . . . . 6
SYSTEM START-UP AND CHECKOUT . . . . . . . . . . . . 6
Installer Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Terminating Installer Test . . . . . . . . . . . . . . . . . . . . . . . . 6
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mode Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fan Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Set Temperature Selection . . . . . . . . . . . . . . . . . . . . . . . 6
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Display Lighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Remote Sensor Temperature Display. . . . . . . . . . . . . 7
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Five-Minute Compressor Timeguard . . . . . . . . . . . . . 7
Minimum On Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cycle Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Staging Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Space Temperature Sensor Failure. . . . . . . . . . . . . . . 7
Fan Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Memory Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Equipment Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17
THERMOSTAT CONFIGURATION RECORD . . . . CL-1
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Fol­low all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage thermostat.
Recognize safety information. This is the safety alert sym­bol . When the safety alert symbol is present on equipment or in the instruction manual, be alert to the potential for person­al injury.
Catalog No. 04-53330027-01 Printed in U.S.A. Form 33CS-75SI Pg 1 7-13 Replaces: 33CS-70SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a haz­ard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage.
GENERAL
Carrier’s Comfort Pro non-programmable thermostats are wall-mounted, low-voltage thermostats that maintain room temperature by controlling the operation of a heating and/or air conditioning system (Fig. 1). This thermostat can be used with a heat pump, air conditioner or water source heat pump opera­tion. A variety of features are provided including battery opera­tion, separate heating and cooling set points, auto changeover, keypad lockout, backlighting, and built-in installer test.
This Installation Instruction covers installation, configura­tion, and start-up of the Comfort Pro non-programmable ther­mostat. For operational details, consult the Owner's Manual for this specific thermostat.
PACKAGE CONTENTS
1 — Thermostat
1 — Backplate (mounting base)
2 — Screws and anchors
INSTALLATION CONSIDERATIONS
Power —
one of two ways: full 24 volt AC (50/60 Hz) power via the Rc/ Rh and C terminals or two AA alkaline batteries. The 24 vac operation is preferred, if available. Battery operation is used when there are not enough wires to support 24 vac operation.
The thermostat will obtain full operating power
When the battery is low, a Low Battery indication will be dis-
Fig. 2 — Backplate Mounting
a33-9233
played to the user.
For an air conditioning system, up to six wires are needed for 24 vac operation and one less wire for battery operation. For a heat pump system, up to seven wires are needed for 24 vac operation and one less wire would be sufficient for bat­tery operation. For heat only operation with batteries, only two wires are required. When battery operation is used, the C termi­nal does not need to be connected.
Provision is also made for separate heating and cooling transformers via separable Rc and Rh terminals which are con­nected via factory-installed jumper wire.
Wiring — The wire length should be no more than 250 ft
(76 m). Use 22 AWG (American Wire Gage) for normal wiring applications. Continuous wire lengths over 100 ft (30.5 m) should use 20 AWG or larger.
Thermostat Location — The thermostat should be
mounted:
• approximately 5 ft (1.5 m) from the floor
• close to or in a frequently used space, preferably on an
inside wall
• on a section of wall without pipes or ductwork
The thermostat should NOT be mounted:
• close to a window, on an outside wall, or next to a door
leading to the outside
• where exposed to direct light and heat or any other tem-
perature-radiating object which may cause a false
reading
• close to or in direct airflow from supply registers or
return air grille in areas with poor air circulation
INSTALLATION
To install the thermostat, perform the following procedure:
1. Turn off all power to equipment.
WARNING
3. Press the thumb release at the top of the thermostat and snap apart carefully to separate backplate from the ther­mostat and expose mounting holes.
4. Route thermostat wires through large hole in backplate. Level backplate against wall (for appearance only, the thermostat does not need be leveled for proper operation) and mark wall through two mounting holes. See Fig. 2.
MOUNTING
HOLES
5. Drill two
3
/16-in. mounting holes in the wall where
marked.
6. Secure backplate to wall with two screws and anchors provided. Make sure all wires extend through hole in backplate.
7. Adjust length and routing of each wire to reach proper connector block and terminal on backplate with
1
/4-in. (6 mm) of extra wire. Strip only 1/4-in. of insulation from each wire to prevent adjacent wires from shorting togeth­er when connected.
Electrical shock can cause personal injury and death. Before installing thermostat, shut off all power to this equipment during installation. There may be more than one power disconnect. Tag all disconnect locations to alert oth­ers not to restore power until work is completed.
2. If an existing thermostat is being replaced: a. Remove existing thermostat from wall. b. Disconnect wires from existing thermostat, one at
a time. Be careful not to allow wires to fall back into the wall.
c. As each wire is disconnected, record the wire color
and terminal marking.
d. Discard or recycle old control.
CAUTION
ENVIRONMENTAL HAZARD: Failure to follow this caution may result in environmental
damage. Mercury is a hazardous waste. Federal regulations require
that mercury be disposed of properly.
CAUTION
Failure to follow this caution may result in equipment dam­age or improper operation.
Improper wiring or installation may damage the thermo­stat. Check to make sure wiring is correct before proceed­ing with installation or turning on unit.
8. Match and connect equipment wires to proper terminals of the connector blocks (see Fig. 3). If there are separate 24 vac transformers, one in the indoor unit and one in the outdoor unit, connect the common of each to the C termi­nal. Remove factory-installed jumper wire from Rc and Rh terminals. Connect the R from the indoor unit to the Rh terminal. Connect the R from the outdoor unit to the Rc terminal. Then the W signal is taken from the Rh pow­er and the Y1, Y/Y2, G and O/B signals are taken from the Rc power.
2
-01
S2
S1
Y1
O/B
Rc
Rh
W
C
G
Y2
Fig. 3 — Terminal Strip
a33-9230
9. Push any excess wire into wall and against backplate. Seal hole in wall to prevent air leaks. Leaks can affect operation.
10. Attach thermostat to backplate by inserting tab on bottom edge and hinging up until top snap secures.
11. Turn ON power to unit.
When power is applied, all display icons are lit for 2 sec­onds to test the display. Following this, the equipment type for which the thermostat is configured is displayed for an addition­al 2 seconds. Equipment type will be either HP, AC, H, C or 35 (for WSHP) (for explanation see Option 01 below).
NOTE: If a common wire has not been connected, two AA batteries must be used to power the thermostat.
CONFIGURATION
Configuration options enable the installer to configure the thermostat for a particular installation. These configuration op­tions are stored to the internal memory so they are retained through a power outage. The availability of some configuration options will be dependent upon other conditions in the thermo­stat. For example, the backlight configuration is not available unless full 24 vac power is connected. See Table 1.
Table 1 — Configuration Options Summary
OPTION
NUMBER
01 Equipment Type 02 Remote Sensor Selection
03* English/Metric
04 Fan (G) on with W Output 05 Space Temperature Sensing 07 Equipment DDC Controller 10 Reversing Valve 11 Deadband between Heating and Cooling Set Points 13 Space Temperature Display Adjustment (Offset) 15 Auto Mode Availability 16 Maximum Cycles Per Hour 17 Time Between Equipment Stages
18* Backlight Configuration
20 Outdoor Air Temperature Adjustment (Offset) 21 Keypad Lockout 26 Minimum Cooling Set Point 27 Maximum Heating Set Point 35 Emergency Heat Mode Availability 39 Temperature Display 99 Reset to Factory Defaults
* These settings are adjustable by the user. See Owner’s Manual for additional information.
CONFIGURATION
Entering and Exiting Configuration Mode —
Press and hold the fan button for about 10 seconds. After the 10-second period the Option number "01" will appear flashing in the space temperature location. The value of the configura­tion setting will be displayed in the set point location.
The parameter that is changeable will be determined by the flashing area. The up or down button can be used to select a new value. The mode button can be used to toggle/move the selection between the configuration option number and the configuration value. To exit the installer configuration screen, press the fan button. If no button is pressed for three minutes, the installer configuration screen will time out and the thermo­stat will return to normal operation.
All changes to the installer configuration are saved as they are made. There is no provision to exit the installer configura­tion and cancel the change. The installer will have to manually change a configuration back to its original value to "undo" a change.
Configuration Options
OPTION 01 — EQUIPMENT TYPE — This option deter­mines the control method of the thermostat. It should match the type of equipment used.
Selection: HP, AC, H, C, 35
HP — operates a two-stage heat pump
AC — operates a two-stage AC with single unit
H — operates a heat only system
C — operates a cool only system
35 — operates a water source heat pump
Default: AC OPTION 02 — REMOTE SENSOR SELECTION — A re-
mote thermistor can be connected to the S1 and S2 screw ter­minals to sense either remote space, outdoor air, supply or re­turn air temperature.
NOTE: Carrier sensors 33ZCT55SPT, 33ZCSENDAT, 33ZCSENSAT, and 33ZCSENOAT may be used for standard space temperature sensor averaging. Sensors must be used as a single sensor, 4 sensors or 9 sensors, with total sensor wiring not to exceed 1,000 ft.
Selection: rS, SA, Od, rA
rS — Sense remote space temperature
SA*— Sense supply air temperature
Od*— Sense outdoor air temperature
rA* — Sense return air temperature
* Display only, not used for temperature control.
Default: Od OPTION 03 — ENGLISH/METRIC — This configuration
selects between Fahrenheit (F) and Celsius (C) operation.
Selection: F, C
Default: F OPTION 04 — FAN (G) ON WITH W OUTPUT — This
configuration is not available if the thermostat is configured as Cool Only in Option 01. This selection determines whether fan (G) output is to be on or off when the W is energized in AC, HP, H or 35 (WSHP) configurations, and when the O/B output is energized in the AC or H (heat only) configurations.
Selection: OF(F), ON
OF — Fan does not turn on with W output
ON — Fan turns on with W output
Default: ON OPTION 05 — SPACE TEMPERATURE SENSING —
This selection determines which sensor the control will use for measuring space temperature. Space temperature can be
3
sensed in one of three ways: the local sensor (L) located on the thermostat, the remote sensor (r), or the average of local and remote sensors (Lr).
Selection: L, r, Lr L — Local sensor: The onboard thermistor is the control
point for the temperature control algorithm. r — Remote space sensor: The remote space temperature
is the control point for the temperature control algorithm. NOTE: This selection is only available if Option 02 indi-
cates that the S1, S2 terminals are sensing a remote space temperature.
Lr — Average (remote space sensor and space tempera­ture): The average of the onboard thermistor and the remote space sensor is the control point for the tempera­ture control algorithm.
NOTE: This selection is only available if Option 02 indi­cates that the S1, S2 terminals are sensing a remote space temperature.
Default: L
OPTION 07 — EQUIPMENT DDC CONTROLLER — This selection should be set to ON when control is to be used with DDC (direct digital controller) equipment. These control systems will take care of the time guard and cycle timers. Examples are zone controlling units or two-position valve assemblies that can open or close as required, without regard to exceeding a maximum number of operations per hour. Rooftop units used with PremierLink™ or ComfortLink controls do not require thermostat control to handle timers and safeties, so this selection would also be set to ON in this case.
Set this selection to OF (off) if the thermostat is directly connected to equipment such as a furnace or fan coil unit with DX condensing units, or electro-mechanical rooftop units that have a maximum number of cycles per hour rating, but do not implement that requirement themselves and rely instead on the thermostat.
Selection: OF(F), ON
OF — Timeguard and cycle timers are enabled
ON — Timeguard and cycle timers are disabled
Default: OF (off) OPTION 10 — REVERSING VALVE — This feature is
only available on heat pump (HP) systems. Although the water source heat pump is also a heat pump system, a WSHP system will always energize the reversing valve in cooling and there­fore, this option is not available to the installer on either 35 or WSHP systems.
The "O/B" terminal can be configured to be energized in ei­ther heating mode or in cooling mode, depending on heat pump operation. The "C" configuration is used to describe a heat pump system that energizes its reversing valve in cooling. The "H" configuration is used to describe a heat pump system that energizes its reversing valve in heating.
Selection: H, C
H — The reversing value output (O/B) is energized when
HEAT mode is selected.
C — The reversing value output (O/B) is energized when
COOL mode is selected.
Default: H OPTION 11 — DEADBAND BETWEEN HEATING AND
COOLING SET POINTS — The selection allows the install­er to choose how much differential will exist between the heat­ing and cooling set points.
Selection: 1 to 10 (F or C)
Default: 5
OPTION 13 — SPACE TEMPERATURE DISPLAY ADJUSTMENT (OFFSET) — This configuration is the number of degrees to be added to the displayed temperature to calibrate or deliberately miscalibrate the measured space tem- perature. This selection is not available to the installer if Option 39 is set to SP (setpoint display).
Selection: –5 to 5 F (always in F) Default: 0
OPTION 15 — AUTO MODE AVAILABILITY — The ON selection will allow automatic changeover between heating and cooling as demand requires a mode selection. OF maintains either heating or cooling mode selection only. Auto changeover is not available when H or C is selected under Op­tion 01.
Selection: ON, OF(F) ON — Auto mode is an available option that can be
selected OF — Auto mode is not an available option Default: ON
OPTION 16 — MAX CYCLES PER HOUR — The maxi­mum cycle rate is limited by internal timers to the selected number of cycles per hour. Selection of a higher number causes faster cycling resulting in more constant room temperature.
Selection: 4, 6, 8 4 — The Y1 and W outputs will be energized at most
twice per hour. When an output is energized, it will not be energized again for 15 minutes.
6 — The Y1 and W outputs will be energized at most four times per hour. When an output is energized, it will not be energized again for 10 minutes.
8 — The Y1 and W outputs will be energized at most six times per hour. When an output is energized, it will not be energized again for 8 minutes.
Default: 4
OPTION 17 — TIME BETWEEN EQUIPMENT STAGES — This configuration determines the minimum number of minutes of equipment operation before allowing the transition to the next logical stage.
Selection: 10, 15, 20, 25 Default: 15
NOTE: If the difference between the space air temperature and set point results in a demand greater than three degrees, then the staging timers are ignored and the equipment will stage up in 60-second increments.
OPTION 18 — BACKLIGHT CONFIGURATION — This function is only available when the thermostat is operating from 24 volt AC power connected to the R and C terminals. It is not available when the thermostat operates from batteries.
When set to OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off.
When ON is enabled, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed. After 10 seconds of no button press­es, the backlight will return to the dimmer level until another button press occurs.
Selection: OF(F), ON
Default: ON with 24 vac power; for batteries only,
default is OFF. OPTION 20 — OUTDOOR AIR TEMPERATURE DIS-
PLAY ADJUSTMENT (OFFSET) — This selection is not available unless Option 02 is set to Od (outdoor air tempera­ture) and a valid sensor is connected to S1 and S2 terminals. It allows the calibration, or deliberate miscalibration of the out­door air temperature sensor reading.
4
Selection: –5 to 5 (number of degrees F added to the out-
Fig. 4 — Selection of Code Value
a33-9225
door air temperature reading to "calibrate" the tempera­ture sensor)
Default: 0
OPTION 21 — KEYPAD LOCKOUT WITH PASS­CODE — The thermostats are shipped with the keypad fully accessible. This option allows the installer to limit access to the keypad.
Selection: OF(F), 1, cd OF — When set to OF, the user has full access to the key-
pad 1 — The user will only have access to modify the set points
(within the set point limits of Option 26 and Option 27). The padlock icon will be displayed until the user presses and holds the up and down buttons simultaneously for five seconds to unlock the keypad. Once the keypad is unlocked, the user has full access to the thermostat functionality. The keypad returns to the locked condition after no buttons have been pressed for two minutes.
cd — The entire keypad is locked and the padlock icon is displayed. When the user presses a button the backlight turns on to maximum brightness for 10 seconds and a "--" is displayed in the temperature setting. The user must enter the unlock code and press the mode button to unlock the ther­mostat. The padlock icon will then turn off and the user will have full access to the thermostat functionality. The thermo­stat will lock after no buttons have been pressed for two minutes.
If the option value is set to "cd," the mode, up and down buttons will work as follows:
1. Pressing the mode button once will display the flashing Option number (21).
2. Pressing the mode button again and the option value will flash OF, 1 or cd.
3. Pressing the mode button a third time will display the keypad lock icon and the code entry values (see Fig. 4). The up and down buttons will allow the selection of a code value between 00 to 199.
4. Pressing the mode key again will return the focus to the Option number (21).
In the event that the installer or user cannot remember the unlock code for the thermostat, the code can be displayed if the user presses and holds the fan and the down buttons simultane­ously for 30 seconds. After the 30-second period, the unlock code will be displayed for five seconds. This information does not appear in any other user documentation.
Default: OF (off)
OPTION 26 — MINIMUM COOLING SET POINT — This parameter establishes the minimum cooling set point that the user is allowed to set. If the equipment type is Cool Only, the lower limit is 55 F and the upper limit is 90 F. Otherwise, the equipment type allows both heating and cooling operation, so the minimum is 55 F plus Option 11 (deadband) and the maximum is 90 F.
Selection: minimum = 55 F + deadband, maximum = 90 F Default: 60 F (based on the adjustable deadband default = 5)
OPTION 27 — MAXIMUM HEATING SET POINT — This parameter establishes the maximum heating set point that the user is allowed to set. If the equipment type is Heat Only, the lower limit is 50 F and the upper limit is 90 F. Otherwise, the equipment type allows both heating and cooling opera­tions, so the minimum is 50 F plus Option 11 (deadband) and the maximum is 90 F.
Selection: minimum = 50 F, maximum = 90 F – deadband Default: 85 F (based on adjustable deadband default = 5)
OPTION 35 — EMERGENCY HEAT MODE AVAIL­ABILITY — This configuration allows the installer to turn on or off the Emheat (emergency heat) mode. When set to ON, the Emergency Heat mode is an available m
ode selection. When set to OF, the Emergency Heat mode is not an available mode selection. Not available if Option 01 is set to C (cool only).
Selection: OF(F), ON Default: OF (off)
OPTION 39 — TEMPERATURE DISPLAY — This con­figuration allows the installer to select either the set point tem­perature or the space temperature to be displayed on the large temperature display digits.
When the option St is chosen, the space temperature, as de­fined by Option 05, is displayed using the traditional space temperature digits on the LCD display. The current set temper­ature is displayed using the normal set point display digits.
When SP is chosen, the current set point temperature is dis­played using the traditional space temperature digits on the LCD display. The normal set point display digits remain blank. Space temperature is not displayed, but if a problem occurs with the actual space temperature sensor, the characters "- -" will be displayed instead of the Set temperature to indicate that the temperature sensor has an error.
NOTE: The "Actual Temp" icon is not be displayed when the sensor type is set to set point display (SP).
Selection: St, SP
Default: St (Space Temperature) OPTION 99 — RESET TO FACTORY DEFAULTS —
This configuration allows the installer to return the thermostat to its "out of the box" settings.
mode
fan
IMPORTANT: All configuration options, mode, fan and set point settings which have been manually entered will be lost and reset.
When this setting is first selected, 99 will be displayed in the space temperature location and an initial value of 10 will be displayed in the set point location.
To initiate factory defaults, the installer then presses the mode button until the 10 is flashing. The installer then presses and holds the down button. While the down button is held, the 10 will count down from 10 to zero at a rate of 2 counts per second (5 seconds total). When the value reaches zero, all dis­play segments are turned on for five seconds and the factory defaults are restored. If at any time during the countdown the installer releases the down button, the countdown terminates and the display returns to the starting value of 10.
5
Exiting Configuration Mode — To exit the configu-
mode
fan
heat
auto fan
aux heat on
Fig. 5 — Installer Test Mode
a33-9226
ration mode, press the fan button.
SYSTEM START-UP AND CHECKOUT
Installer Test Mode —
staller test capability. It allows easy operation of equipment without delays or set point adjustments to force heating or cooling. To enter installer test mode, press and hold the fan button for 15 seconds (after 10 seconds installer configuration is entered; a continuous 15 seconds and installer test is entered). At the start of installer test, the mode is Off, the fan is "fan auto" and the set point displays “InS.”
The mode button is used to change the system operating mode to test the heating and cooling equipment. Auto mode is not available during installer test.
When the mode is set to heat, heating is energized for 180 seconds. During the installer test operation, the "on" icon is displayed.
At the end of the equipment test cycle the mode returns to OFF.
The LCD display counts down the time remaining (in sec­onds, from 180 to 0) for each stage when the equipment is en­ergized. See Fig. 5.
This thermostat has a built-in in-
in its normal operating mode, consult the Owner's Manual.
2. If the equipment is to be left in operation, the set points and operating mode must be properly selected.
3. Put away tools and instruments and clean up debris.
4. Review and leave Owner's Manual with customer.
OPERATION
Mode Selection —
display the off, heat, cool, auto and emergency heat icons. Pressing the mode button cycles through the available modes based on the equipment selection from Option 01, the auto availability setting from Option 15, and the electric heat avail­ability from Option 35. Available choices are listed in Table 2.
Table 2 — Mode Selection
OPTION 01
(Equipment
Selection)
AC, HP or
35 (WSHP)
H Not Available
C Not Available Not Available Off, Cool
OPTION 15
The mode button allows the user to
OPTION 35
(Auto
Available)
On
Off
(Emergency
Heat Mode
Available)
On
Off
On
Off Off, Heat, Cool
On
Off Off, Heat
AVAILABLE
MODES
Off, Heat,
Cool, Auto,
Em Heat
Off, Heat,
Cool, Auto
Off, Heat,
Cool, Em Heat
Off, Heat,
Em Heat
The same procedure is repeated for the cool mode. "C" is
displayed when cooling is active.
The test of a heating or cooling cycle can be terminated be­fore the timer counts down to zero by pressing the mode button.
Pressing the fan button alternates the fan selection between fan auto and fan on and the fan output follows accordingly. There is no timer associated with the installer testing of the fan operation.
Setting the mode to Em heat, if available, turns on the auxil­iary heat for 180 seconds. The space temperature location dis­plays an "E," the clock display counts down from 180 to 0 in one-second increments and the "aux heat on" icon is displayed. At the end of the 180 seconds, the mode returns to OFF.
Terminating Installer Test — After 15 minutes of no
button presses by the installer, installer test is terminated.
Pressing the up button, down button, or cycling thermostat power at any time during installer test terminates the installer test and returns the thermostat to normal operation.
Checklist — The following installer checklist should be
performed after completing installation:
1. Run equipment through several heating and cooling cy­cles to ensure proper operation. To operate the thermostat
Fan Selection — Pressing the fan button toggles between
the Fan On and Fan Auto selections. When the “fan on” icon is displayed, the fan operates continuously. When “fan auto” is displayed, the fan will run only with the equipment.
Set Temperature Selection — If auto mode is not ac-
tive and off mode is not active, pressing the up or down button causes the set point corresponding to the current system mode to be updated. If the up or down button is held, the set point value will be scrolled. The set point change also takes into ac­count that Option 11 (deadband) is preserved along with ensur­ing that Option 26 (minimum cooling set point) and Option 27 (maximum heating set point) are taken into account to enforce set point limits.
If auto mode is active, pressing the up or down button causes the set point corresponding to the current operating mode to be updated. To move between the heat and cool set points, press the mode button to toggle between set points. Once the desired set point has been adjusted, press the mode button to return to auto mode.
If off mode is active, the up and down buttons are ignored for changing set point(s).
When changing the set points, the following restrictions are in place. The cool set point cannot be increased above 90 de­grees F (32 C) or decreased below Option 26, the minimum cooling set point. The heat set point cannot be decreased below 50 F (10 C) or increased above Option 27, the maximum heat­ing set point.
When Option 39 is set to SP (set point), the set point adjust­ment is displayed in the large space temperature digits.
Batteries — Battery operation is available for installations
where there is no common (C) wire available at the thermostat. For battery operation, install two alkaline AA batteries. The
6
Loading...
+ 14 hidden pages