Table 4--1 General System Troubleshooting Procedures4--1............................................
Table 5--1 R-134a Temperature - Pressure Chart5--10..................................................
T--30404/08
iv
SAFETY SUMMARY
GENERAL SAFETY NOTICES
The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this
manual. Theyarerecommended precautionsthatmust beunderstoodand appliedduring operationandmaintenance
of the equipment covered herein. A listing of the specific warnings and cautions appearing elsewhereinthe manual
follows the general safety notices.
FIRST AID
An injury, nomatter how slight, should never gounattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS
Always wear safety glasses.
Keep hands, clothing and tools clear of the evaporator and condenser fans.
Noworkshould beperformedon theunituntilall start-stop switches areplacedin the OFF position, andpowersupply
is disconnected.
Always work in pairs. Never work on the equipment alone.
In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator and condenser fans. Do not open the unit cover before turning
power off.
Be sure power is turned off before workingonmotors, controllers, solenoidvalvesandelectrical controls. Tagcircuit
breaker and power supply to prevent accidental energizing of circuit.
Donot bypassany electricalsafetydevices,e.g. bridginganoverload,or usinganysortof jumperwires. Problemswith
the system should be diagnosed, and any necessary repairs performed by qualified service personnel.
When performing any arcweldingon the unit, disconnect all wire harness connectors from the modulesinthecontrol
box. Donotremovewireharness fromthemodules unless you are grounded to the unit frame with a static-safewrist
strap.
In case of electrical fire, open circuit switch and extinguish with CO
(never use water).
2
04/08
Safety--1
T--304
SPECIFIC WARNINGS AND CAUTIONS
WARNING
Be sure to observe warnings listed in the safety summary in the front of this manual before per-
forming maintenance on the hvac system
WARNING
Read the entire procedure before beginning work. Park the vehicle on a level surface, with park-
ing brake applied. Turn main electrical disconnect switch to the off position.
WARNING
Do Not Use A Nitrogen Cylinder Without A Pressure Regulator
WARNING
Do Not Use Oxygen In Or Near A Refrigeration System As An Explosion May Occur.
WARNING
The Filter-drier May Contain Liquid Refrigerant. Slowly Loosen The Connecting Nuts And Avoid
Contact With Exposed Skin Or Eyes.
CAUTION
The AC310 & AC350 Rooftop Systems have R134a service port couplings installedon the compressor and 1/4 inch flare (Acme) fittings installed on the unit piping.
CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set be sure set is brought to suction
pressure before disconnecting.
T--30404/08
Safety--2
SECTION 1
DESCRIPTION
1.1 INTRODUCTION
This manual contains Operating Instructions, Service
Instructions and Electrical Data for the Model AC310
and AC350 Air Conditioning and Heating equipment
furnished by Carrier Transport Air Conditioning as
shown in Table 1--1 and Table 1--2.
Model AC310/350 systems consists of a Rooftop unit
containing the condensing section, the evaporator
sectionandenginecompartmentmounted
compressor(s). To complete the system, the air
conditioning and heating equipment interfaces with an
optionaldriversevaporator(dash--air),electrical
cabling, refrigerant piping, engine coolant piping (for
heating), duct work and other components furnished by
Carrier Transport Air Conditioning and/or the bus
manufacturer.
Additional support manuals are shown in Table 1--3.
Operation of the unit is controlled automatically by an
electronic thermostat. The controlls maintain the
vehicle’s interior temperature at the desired set point.
YesXX
*NOTE: 77--62032--06 (Tropic) -- Has an AC310 Evaporator Section & an AC350 Condenser Section.
T--200PL05G CompressorService Parts List
62--0275605G CompressorOperation & Service
62--1105205G Compressor -- Twin PortWorkshop Manual
62--1105305G Compressor -- Twin PortService Parts List
62--0246005K CompressorService Parts List
62--0249105K CompressorOperation & Service
The rooftop unit includes the condenser section and the evaporator section (See Figure 1--1).
Evaporator Section
Condenser Section
AC310
AC350
Figure 1--1 AC310/350 Rooftop Units
1.2.2 Condensing Section
The dual (See Figure 1--2) and single loop (See
Figure 1--3)condensing sections includethecondenser
coils, four (4) or six (6) fan and motor assemblies,
filter-driers, receivers, and filter drier service valves.
The condenser coils provide heat transfer surface for
condensing refrigerant gas at a high temperature and
pressure into aliquidat high temperatureand pressure.
The condenser fans circulate ambient air across the
outside of the condenser tubes at a temperature lower
Evaporator Section
Condenser Section
than refrigerant circulating inside thetubes; this results
in condensation of the refrigerant into a liquid. The
filter-drier removes moisture and debris from the liquid
refrigerant before it enters the thermostatic expansion
valve in the evaporator assembly. The service valves
enable isolation of the filter-drier for service.
The receiver collects and stores liquid refrigerant. The
receiver is also fitted with a pressure relief valve which
protects the system from unsafe high pressure
conditions.
Figure 1--3 Condensing Section Components (AC350 Single Loop -- GEN II)
1.2.3 Evaporator Section
The dual loop AC310 & AC350 (GEN I) evaporator
section (SeeFigure 1--4) includes the evaporator coils,
eight (8) or twelve (12) single--shafted blower/motor
assemblies,twoheatercoilassemblies,two
thermostatic expansion valves, two liquid line solenoid
valves, and condensate drain connections.
NOTE
The GEN I seriesof AC310 & AC350 evaporators are suppliedwithsingle shaft blower/motor
assemblies. The GEN II series have dual shaft
blower/motor assemblies.
The single loop AC310 & AC350 evaporator section
(See Figure 1--5)includes the evaporator coils, four (4)
or six (6) double--shafted blower/motor assemblies,
heater coil assemblies, one thermostatic expansion
4
2
3
2
5
3Filter Drier
4Fan & Motor
5Frame (Aluminum)
valve, one liquid line solenoid valve (to add in--dash
service port), and condensate drain connections.
The liquidlinesolenoid valve closes whenthe system is
shut down to prevent flooding of coils and the
compressor with liquid refrigerant. The evaporatorcoils
provide heat transfer surface for transferring heat from
air circulating over the outside of the coil to refrigerant
circulating inside the tubes;thus providing cooling. The
heating coils provide a heat transfer surface for
transferring heat from engine coolant water circulating
inside the tubes to air circulating over the outside
surface of the tubes, thus providing heating. The fans
circulate the air overthecoils.Theairfilters remove dirt
particles from theair before itpassesover thecoils.The
thermostatic expansion valve meters the flow of
refrigerant entering theevaporatorcoils.Theheat valve
controls the flow of engine coolant to the heating coils
upon receipt of a signal from the controller. The
condensate drain connections provide a means for
connecting tubingfordisposing ofcondensatecollected
on the evaporator coils during cooling operation.
Figure 1--5 Evaporator Section Components (AC350 Single Loop -- GEN II)
8
3
6
7
1
2
5.Control Panel
6.Heater Line
7.Front Evaporator Port
8.Liquid Line Solenoid
1.2.4 Drivers Evaporator (Optional)
Thedriversevaporatorassemblyis normally installedin
thevehicledashareaandinterfaceswiththerooftopunit
electrical cabeling and refrigerant piping.
Thedriversevaporatorassemblyincludesan
evaporator coil, thermalexpansion valve, blower motor
assembly and a condensate drain connection. Refer to
the OEM technical literature for driver’s evaporator
information.
1.2.5 Compressor Assembly
a. Dual Loop Compressors A--6 & TM--21
The standard AC310 dual loop compressor assembly
includes the refrigerant compressor, clutch assembly,
in--line high &low pressureswitches, suction
accumulatorand in--line suction anddischarge
servicing (charging) ports.
b. Single Loop Compressor TM--31
The TM--31 compressor assembly used only with the
AC310 Single Loop Unit includes the refrigerant
compressor, clutch assembly, suction & discharge
service valves, high pressure switch, low pressure
switch, suction accumulator and suction anddischarge
servicing (charging) ports.
T--304
c. Single Loop Compressors 05G & 05K
The 05G (AC350) & 05K (AC310) compressor
assemblies used withthesingleloopunits,includesthe
clutch assembly, suction & discharge service valves,
high pressure switch, low pressure switch, suction and
discharge servicing (charging) ports and electric
solenoid unloaders.
Thecompressorraisesthepressureand temperatureof
the refrigerant and forces it into the condenser coil
tubes. Theclutchassemblyprovidesa means ofdriving
the compressors by the vehicle engine. Suction and
discharge servicing (charging) ports mounted on the
compressor fittings enable connection of charging
hoses for servicing of the compressor, as well as other
parts of the refrigerant circuit.Thehighpressureswitch
contacts open on a pressure rise to shut down the
system when abnormally high refrigerant pressures
occur.
The electric unloaders (05G & 05K) provide a means of
controlling compressor capacity, which enables control
of temperature inside the vehicle. The suction and
discharge service valves enable servicing of these
compressors.
1--6
04/08
1.2.6 System Operating Controls And Components
Thesystem isoperated byanelectronicthermostattype
controller and/or manually operated switches. The
manually operated switches are located on the drivers
control and may consist of a single ON/OFF switch or
additional switches. The controller regulates the
operational cycles of the system by energizing or
de--energizing relays on the relay board in response to
deviations in interior temperature. Modes of operation
includeCoolingandHeating.Onsystemsfittedwithonly
an ON/OFF switch, the controller will cycle the system
between the operating modes as required to maintain
desired set point temperature (See Section 6 for wiring
diagrams).
In the heat mode the heat valves are opened to allow a
flow of engine coolant through the heat coils located in
the evaporator section. The evaporatorfans operate to
circulate air over the heat coils in the same manner as
the cooling mode.
In the cooling mode the compressor is energized while
the evaporator and condenser fans are operated to
provide refrigeration as required. The compressor (s)
capacity is matched to the bus requirements. Once
interior temperature reaches the desired set point, the
compressor(s) is deenergized.
This typecontrollerhas three (3)modes,Cool, Ventand
Heat.
The range on the potentiometer is 62.6° -- 8 6° F
(17--30° C).
1.2.8 CSDD BT--324
(Carrier--Sutrak Digital Display)
Microprocessor
This Carrier Sutrak Digital Display (BT--324) controller
has three (3)modes,Auto, V ent(Cycleclutchtype)and
Heat.
1.2.9 Motor Fault Board (Optional)
The motor fault board(SeeFigure 1--11)consists ofred
and green LED’s, which when illuminated, will reflect
each motors state of condition. When the evaporator
and condenser motors are energized, the green LED’ s
will beilluminated.Ifared LED is energized, it willshow
an “open circuit” condition, indicative of a motor failure.
The green LED will not be illuminated at this time. The
motor fault board is a seperate circuit board that is
located at the return air section. The return air grill is
oppened to view the LED indicators.
1.3 REFRIGERATION SYSTEM COMPONENT
SPECIFICATIONS
a. Refrigerant Charge R--134a (Approximate)
NOTE
Refrigerant charge will dependon hose lengths
and diameters; or if there is an In--Dash unit
(front evaporator). The followingshouldonly be
used as a guideline.
AC310 Dual Loop A--6 or TM--21 Compressor
6 Pounds (2.7 kg) -- Curbside
8 Pounds (3.6 kg) -- Roadside
AC310 -- Single Loop TM--31 Compressor
12 Pounds (5.4 kg) without In--Dash unit
AC310 -- Single Loop 05G or 05K Compressor
13.2 to 15.4 Pounds (6.0 to 7.0 kg) without
In--Dash unit
AC350 -- Single Loop 05G or 05K Compressor
16.5 to 18.7 Pounds (7.5 to 8.5 kg) without
In--Dash unit
For systems with In--Dash unit (Optional)
Add 2 pounds (0.9 kg) to above listed charge.
b. Compressors
Compressor
Weight, (Dry)34.5 Lbs.
Oil Charge10 Oz. PAG (07--00333--00)
[Bus Manufacturer Supplied -- Suggested close on
temperature rise at 105°F(41°C)]
1.4ELECTRICAL SPECIFICA TIONS -- MOTORS
a. Evaporator Blower/Motor
Evaporator Motor
Horsepower (kW)1/8 (.09)
Full Load Amps (FLA)9.519
Operating Speed High/
Low (RPM)
Bearing Lubrication
A6 (No longer Available)
6.1 Oz. (180 cc) PAG
(46--50006--00)
16.9 Oz. (500cc) PAG
(46--50006--00)
5.5 Pints POE
(07--00317--00pk6)
7.75 Pints POE
(07--00317--00pk6)
Permanent Magnet
24 VDC12 VDC
4200
1850
Factory Lubricated
(additional grease not required)
Change 07/09
1--7
T--304
b. Condenser Fan Motor
Condenser Motor
Permanent Magnet
24 VDC12 VDC
Horsepower (kW)1/8 (.09)
Full Load Amps (FLA)918
Operating Speed
(RPM)
Bearing Lubrication
(additional grease not required)
2950
Factory Lubricated
c. Temperature Sensors (Return Air Sensor)
Input Range: --52.6 to 158° F (--47 to 70°C)
Output: NTC 10K ohms at 77° F(25°C)
d. Ambient Sensor (Optional)
Opens at: 25° F(10°C)
Closes at: 35° F(1.7°C)
1.5 SAFETY DEVICES
System components are protected from damage
caused by unsafe operating conditions with safety
devices. Safety devices with Carrier Transport Air
Conditioning supplied equipment include high pressure
switch (HPS), low pressure switch (LPS), circuit
breakers and fuses.
a. Pressure Switches
High Pressure Switch (HPS)
During the air conditioning cycle, compressor clutch
operation will automatically stop if the HPS switch
contacts open due to an unsafe operating condition.
Opening HPS contacts de-energizes the compressor
clutchshuttingdownthecompressor.Thehighpressure
switch (HPS) is installed at the compressor assembly
(05G, 05K & TM--31).
Low Pressure Switch (LPS)
The low pressure switch is installed close to the
compressor andopenson apressuredrop to shutdown
the system when a low pressure condition occurs. The
lowpressureswitchisinstalledat thecompressor(05G,
05K & TM--31).
NOTE
Ondualloop systemsthatuse theA--6, TM--21
& some TM31’s,the pressure switches are not
located onthe compressors. They are installed
in--line.
b. Fuses and Circuit Breakers
TheRelayBoard is protected against highcurrentbyan
OEM supplied circuit breaker or fuse located in thebus
battery compartment (150 Amp for 12 VDC & 125 Amp
for 24 VDC systems). Independent 15 Amp, 24 VDC or
20 Amp, 12 VDC fuses protect each motor while the
output circuits are protected by an additional 5 Amp
circuit breaker. Duringahigh current condition, the fuse
may open.
1.6 AIR CONDITIONING REFRIGERATION
CYCLE
When air conditioning (cooling) is selected by the
controller, the unit operates as a vapor compression
system using R-134a as a refrigerant (See Figure 1--6
Dual Loop & Figure 1--8 Single Loop flow diagrams).
The main components of the system are the A/C
compressor, air-cooled condenser coils, receiver,
filter-drier, thermostatic expansion valve, liquid line
solenoid valve and evaporator coils.
Thecompressorraisesthepressureand the
temperature of the refrigerant and forces it into the
condenser tubes. The condenser fan circulates
surroundingair(whichisatatemperature lowerthanthe
refrigerant) over the outside of the condenser tubes.
Heat transfer is established from the refrigerant(inside
the tubes) to thecondenserair(flowingoverthetubes).
The condensertubeshavefins designed toimprovethe
transfer of heat from the refrigerant gas to the air; this
removal of heat causes the refrigerant to liquefy, thus
liquid refrigerant leaves the condenser and flows to the
receiver.
The refrigerant leavesthereceiver and passes through
the receiver outlet/service valve, through a filter-drier
where a descecant keeps the refrigerant clean and dry.
From the filter-drier, the liquid refrigerant then flows
through the liquid line solenoid valve to the sight--glass
and then to the thermostatic expansion valve. The
thermalexpansionvalve reducepressureand
temperature of the liquid and meters the flow of liquid
refrigerant to the evaporator to obtain maximum use of
the evaporator heat transfer surface.
The low pressure, low temperatureliquidthat flows into
the evaporator tubes is colder than the air that is
circulated over the evaporator tubes by the evaporator
fans (fans). Heat transfer is established from the
evaporator air (flowing over the tubes) to the refrigerant
(flowing inside the tubes). The evaporator tubes have
aluminum fins to increase heat transfer from the air to
the refrigerant; therefore the cooler air is circulated to
the interior of the bus. Liquid line solenoid valve closes
during shutdown to prevent refrigerant flow.
The transfer of heat from the air to the lowtemperature
liquid refrigerant in the evaporator causes the liquid to
vaporize. This low temperature, low pressure vapor
passes through the suction line and returns to the
compressor where the cycle repeats.
1.7 HEATING CYCLE
Heating circuit (See Figure 1--7) components furnished
byCarrier Transport AirConditioninginclude theheater
cores and solenoidoperated heat valves. Components
furnished by the bus manufacturer may include awater
temperature switch (WTS) and boost water pump.
The controller automatically controls the heat valves
during the heating mode to maintain required
temperatures inside the bus. Engine coolant (glycol
solution) is circulated through the heating circuit by the
engine and an auxiliary boost water pump. When the
heat valvesolenoidsareenergized, the valves willopen
to allow engine coolant to flow throughthe heater coils.
The valves are normally closed so that if a failure
occurs, the system will be able to cool.
T--304
1--8
04/08
5
3
6
2
4
1
4
1
3
1Thermal Expansion Valve
2Liquid Line Sight Glass
3Service Port
4Liquid Line Solenoid
5Evaporator Coil
6Heat Coil
Note: Items 1 through 12 are typical, both systems.
12...X3 -- X4 (Not Shown On Drawing) = Dash To Unit Interface Plug
+
K1M
K1A
K2A
K3A
+
GND
Relay Board
K2M
K3M
F1M 10A
F2M 10A
F3M 10A
K4M
K5M
F4M 10A
F5M 10A
F6M 10A
F7M 10A
F8M 10A
F9M 10A
F10M 10A
K6M
F11M 10A
F12M 10A
K7M
F13M 15A
X2
K8M
K9M
F14M 15A
F15M 15A
F16M 15A
F17M 15A
F18M 15A
K7M -- K9M
26.38.08.001
Ureg
Part Number
X1
--
Contact arrangement
Connect X1 -- X2
Figure 1--10 AC350 With BT324 Control
T--304
U3
U3A
+
Top View
SUTRAK SCHMATIC #65, 01, 28, 056--01--3
1--14
RELAYS FOR EVAP.MOTORSRELAYS FOR COND. MOTORS
UNIT
K1m -- K4MK7M -- K8M
AC310
K1M -- K6M
AC350
04/08
R26R25
D14
D26
Q2
Q1
U1
Q3
Q4
D15
R27
R30
D18
D30
Q6
Q5
U2
Q7
Q8
D31
D19
R31
D22
D34
Q10
Q9
U3
Q11
Q12
D35
D23
R35
D13
D25
D28D27
D16
R28
R29
D17
D29
D32
D20
R32
R33R34
D21
D33
D36
D24
R36
R37
R38
C1
R40
R41
R42
C2
R43
R44
R45
R46
C3
R47
R48R72
R61
R62
C13
C12
C14
C15
R63R39
R64
R65
R66
C9
C8
C10
C11
R67
R68
R69
R70
C13
C12
C14
C15
R71
R73
R74
U4
R75
R76
R77
R78
U5
R79
R80
R81
R82
U6
R83
R84
OPENCIRCUIT
DS13
DS14
C16
C17
C18
DS15
DS16
DS17
DS18
DS19
DS20
DS21
DS22
DS23
DS24
R12
D12
R24
MOTORPOWER
DS1
EVAP1
DS2
EVAP2
DS3
EVAP3
DS4
EVAP4
DS5
EVAP5
DS6
EVAP6
DS7
EVAP7
DS8
EVAP8
DS9
COND1
DS10
COND2
DS11
COND3
DS12
COND4
R11
D11
R23
D10
R22
POWER10--30V
POWER
OK
DS25
T25
T26
GROUND
R90
D51
D52
C23
C22
++
U8
R9
R8
R10
D9
D8
R21
R20
R19
D7
R7D6R6
R18
R85
R91
F1
D49
D50
R87
R86
C19
C20
R88
C21
R89
U7
R5
R4
R3
R2
D5
D4
R17
D3
R16
R14
R15
R1
D2
D1
R13
CARRIER CRO MOTOR FAULT BOARD
D37
T13
R49
D38
R50
D39
R51
D40
R52
D41
R53
D42
R54
D43
R55
D44
R56
D45
R57
D46
12- -00524--00
R58
D47
R59
D48
R60
MOTOR
T14
MOTOR
T15
MOTOR
T16
MOTOR
T17
MOTOR
T18
MOTOR
T19
MOTOR
T20
MOTOR
T21
MOTOR
T22
MOTOR
T23
MOTOR
T24
MOTOR
RS1
EVAP1
WHT/RED
BREAKER
RS2
EVAP2
BLK/RED
BREAKER
RS3
EVAP3
WHT/YEL
BREAKER
RS4
EVAP4
BLK/YEL
BREAKER
RS5
EVAP5
WHT/ORN
BREAKER
RS6
EVAP6
BLK/ORN
BREAKER
RS7
EVAP7
WHT/GRN
BREAKER
RS8
EVAP8
BLK/GRN
BREAKER
RS9
COND1
GRN/ORN
BREAKER
RS10
COND2
GRN/WHT
BREAKER
RS11
COND3
GRN/BLU
BREAKER
RS12
COND4
BREAKERGRN/YEL
X1--1
T1
X1--2
T2
X1--3
T3
X1--4
T4
X1--5
T5
X1--6
T6
X1--7
T7
X1--8
T8
X3--1
T9
X3--2
T10
X3--3
T11
X3--4
T12
04/08
Figure 1--11 Motor Fault Board (Optional)
1--15
T--304
SECTION 2
OPERATION (MANUAL CONTROLLER)
2.1 STARTING, STOPPING AND OPERATING
INSTRUCTIONS
The control switches supplied by Carrier Transport Air
Conditioning will be marked with international symbols
(See Figure 2.1).
Before starting, electrical power must be availablefrom
the bus power supply.
150Amp @12VDC or125Amp @24VDCfroma fusein
the battery compartment supplies power for the clutch,
evaporator and condenser assemblies.
LOW------HIGH
2.1.1 Starting
a. If the engine is not running, start the engine.
b. Actual start sequence depends on the operating co-
trol supplied. If only an ON/OFF switch is supplied,
place the switch in the ON (fan symbol) position to
start the system in the automatic mode.
c. After the pre--trip inspection is completed, the
switches may be set in accordance with the desired
control modes.
d. If low or high speed evaporator fan speed is desired,
press the FAN SPEED (fan symbol) button to bring
speed to the desired level.
2.1.2 Stopping
Placing the ON/OFF (Snowflake) switch in the OFF
position will stop the system operation by removing
power to the Logic Board.
OFF
Figure 2.1 Control Switches (Typical)
2.2 PRE--TRIP INSPECTION
After startingsystem,allow systemtostabilizefor tento
fifteen minutes and check for the following:
ON
HEATCOOL
Temperature Control
a. Listen for abnormal noises in compressoror fan mo-
tors.
b. Check compressor oil level (05G Compressor only).
c. Check refrigerant charge. (Refer to section 5.8.1 )
2--1
T--30404/08
2.3 MODES OF OPERATION
2.3.1 Temperature Control
Temperature is controlled by maintaining the return air
temperature measured at the return air grille. To
maintain cooling, turn the temperature control knob
towards the minus (--) symbol. To start heating cycle,
turn the temperature control knob towards the plus (+)
symbol (See Figure 2.1).
2.3.2 Cooling Mode
Cooling isaccomplished byenergizingthecompressor
and condenser fans, opening the liquid line solenoid
valve and closing the heating valve. Once interior
temperature reaches the desired set point, the system
will de--energize the compressor clutch and allow the
system to operate in the vent mode until further cooling
isrequired.Thetemperaturewillbemaintained within2°
C. or 3.6° F.
A controller programed for reheat will mantain
compressor operation and cycle the heat valve to allow
reheating of the return air. In the reheat mode interior
temperature is maintained at the desiredset pointwhile
additional dehumidification takes place.
2.3.3 Heating Mode
In the heat mode the liquid line solenoid is closed and
thecompressorand condenserfansare shutdown.The
heat valve is opened to allow a flow of engine coolant
through the heat section of the evaporator coil. The
evaporator fans speed is variedasrequiredto circulate
air over the evaporator coil based on the temperature
difference from setpoint.
Operating intheheating modeiscontrolled by thewater
temperature switch (WTS). The WTS is located on the
engine blockofthevehicleand is provided bytheOEM.
It senses the engine collant temperature and reverses
its contacts on temperature rise at 105° F. The switch
prevents the circulation of cooler air throughout the
vehicle as the engine comes up to temperature.
2.3.4 Boost Pump (Optional)
Whentheunit is inthe heatmode,andifa boostpumpis
supplied by the coach manufacturer, the boost pump
relay is energized, providing 24 VDC to activate the
boost pump.
2.3.5 Vent Mode
Once the temperature is satisfied, there is a window
whenthe unitwill gointoaventmode.This iswhen there
is neither heating or cooling. Only the evaporator fans
are operating. The range of the V ent mode is 2°C. or
3.6°F. from the set point. The compressor clutch is
disengaged at this time.
2.3.6 Compressor Unloader Control (Only with
05G or 05K Compressors)
When operating in cooling, the unloaders are used to
reduce system capacity as return air temperature
approaches set point. Operation of the unloaders
balances system capacity with the load and thereby
prevents overshoot from set point.
Relay Board mounted unloader outputs control the
capacityofthecompressorbyenergizingor
de--energizing unloader solenoid valves. The model
05Gcompressorhasthree banks oftwocylinders each.
Enercizingavalvede--activates abankofcylinders. The
outboard cylinder banks of the 05G are equipped with
unloader valves (UV1 and UV2), each controlling two
cylinders; this allows the 05G to be operated with two,
four or six cylinders.
The unloaders are used to control system capacity by
controlling compressor capacity.
Control of the unloaders is with the pressure switches.
a. Suction Pressure
The unloaders areusedtocontrolsuction pressure and
thereby prevent coil frosting:
1. Compressor Unloader UV1 Relay
-- When the suction pressure decreases below 26 psig (R--134a),
unloader UV1 is energized, unloading a cylinder
bank (2 cylinders); this output will remain energized
until the pressure increases to above 34 psig
(R--134a).
2. Compressor Unloader UV2 Relay
-- When suction
pressure decreases below 23 psig (R--134a), unloaderUV2is energized, unloadingthe secondcompressor cylinder bank; this output will remain energized until the pressure increases to above 31 psig
(R--134a).
b. Discharge Pressure
Discharge pressure is also controlledbytheunloaders:
1. Compressor Unloader UV1 Relay
-- When the discharge pressure increases above setpoint A (see
Table 2.1), unloader UV1 isenergized;thisunloader
will remain energized until the pressure decreases
below set point B (see Table 2.1).
Table 2.1 Unloader UV1 Relay
HP Switch
(PSIG)
Set Point A
(PSIG)
Set Point B
(PSIG)
300 (R--134a)275220
350 (R--134a)
(High Ambient)
325270
2. Compressor UnloaderUV2Relay -- On R--134asystems when the discharge pressureincreasesabove
setpoint A (see Table 2.2), unloader UV2 is energized; this unloader will remain energized until the
pressure decreases below set point B (see
Table 2.2).
Table 2.2 Unloader UV2 Relay
HP Switch
(PSIG)
Set Point A
(PSIG)
Set Point B
(PSIG)
300 (R--134a)285225
350 (R--134a)
(High Ambient)
330275
2.3.7 Override Mode -- AC310 (Dehumidification)
Wheninthe heatmodethe compressor willnotoperate.
The thermostat will allow only COOL, VENT or HEAT
modes independently. An override switch has been
installedin the return air area toallow the compressors
torunwhen intheHEATmode.Moving the switch tothe
ON position will energize both clutch relays energizing
the clutches. There are two temperature sensors that
are in series with the clutch relay circuit, Ambient
Sensor (mounted in the condenser) and Humidity
Control Sensor (mounted inthereturnair area). As long
as the return air temperature is above 60° F and the
ambient is above 25° F,the override circuit will function
when energized, providing dehumidification. (See
section 1.4 for sensor specs)
T--30404/08
2--2
2.3.8 Evaporator Fan Speed Selection
Evaporator fan speed(s) selection is one method of
controlling the cooling and heating throughout the bus
passenger compartment. The thermostat control is the
other.
2.3.9 Compressor Clutch Control
(A--6, TM--16, TM--21)
A belt driven electric clutch is employed to transmit
engine power to the air conditioning compressor.
De-energizing the clutch’s electric coil disengages the
clutch and removes power from the compressor. The
clutch will be engaged when in cooling and disengaged
whenthesystem is off,inheatingor duringhighand low
pressure conditions.
The clutch coil will be de-energized if the discharge
pressure rises to the 365 ±10 psig (19.42 bar) cutout
setting of the compressor mounted high pressure
switch. The clutch coilwillenergize (AutomaticRe--Set)
when the discharge pressure falls to 280 ± 10 psig
(11.41 bar).
The clutch coilwillbe de-energized (open) if the suction
pressure (LP) decreasesbelow6± 3psig (0.45 bar).
The clutch coil will energize (Automatic Re--Set) when
suction pressure rises (close)to 25 ± 3 psig (1.7 bar).
2.4 SEQUENCE OF OPERATION (280P / 282P)
2.4.1 Electronic Thermostat
With a signalfromtheHydraulicBrakeModule (or other
12 VDC source) the A/C Power Relay is grounded,
sending 12 VDC to the K1A relay. K1A relay energizes
sending battery power (Line B+) to the Dash Control
switches (S1A & S2A).
Begining with the Fan Speed Switch (S1A) in the low
speed position (vent 1)thefollowingactions takeplace:
a. Power flows from the Fan Speed Switch (S1A)
through relay K4A normally closedcontacts. Line U2
energizes evaporator fan motor low speed relays
(K1M, K4M, K7M & K10M). Closing these relays allows power to flow from the battery(line B+) through
the fan motors with two motors in series, operating
the motors at low speed.
b. The ON/OFF switch (S2A) is then placed in the ON
position. Power flows fromtheswitchtoenergizethe
Thermostat. With the Thermostat calling for cooling,
power also flows from the cooling switch:
1. Thorugh theHumidity ControlSensorandtheAmbient Sensor Switches located in the return air and
condenser respectively.If both oftheseswitchesare
in the closed position the following sequence will
take place.
2. Power will flow to the Clutch Lockout Relays (CLR1
& CLR2) allowing power to energize the Clutch Relays (CR1 & CR2). Relays CR1 & CR2 are poweredon terminal 30 from an OEM breaker, (A/C Low
Voltage Breaker). Energizing these relays will send
power through the high and low pressure switches
and to both compressor clutches energizing the
clutch coils and starting the compressor.
3. To the liquid line solenoids (Y1A & Y2A) to start the
flow of refrigerant.
4. Through line U3, to energize the condenser fan relays (K14M & K15M). Energizing these relays will
send B+ power to start the condenser fan motors.
The unit is now in low speed cooling.
5. To bring the evaporator fans to high speed the fan
speed switch (S1A) is placed in the HIGH (Vent 2)
position.Powerflows fromtheswitchthroughlineU5
to energize the high speed relay (K13M). The normally closed low speed relay (K4A) is de--energized
opening the low speed circuit. Power flows fromthe
high speed relay (K13M) to energize thehighspeed
fan relays (K2M, K3M, K5M, K6M, K8M, K9M,
K11M,& K12M). Energizingtheserelays individually
grounds eachevaporator fanmotorseparately placing them in high speed operation.
c. With the thermostat calling for heating, power flows
from the heat switch:
1. Through line UH to energize the heat relay (K3A).
With the heat realy energized, power flows from the
battery (line B+) to start the water pump and open
theheatvalve.The unitisnow intheheat mode. Fan
speeds can be adjusted the same as in the cooling
mode.
d. With the Thermostat calling for Heating and the need
for Dehumidification is required:
1. The override switch, located in the return air inlet is
switched to the ON position.
2. Power will flow through the ambient and humidity
controlswitch,if closed, andenergize thecoolingcircuits at the same time as heating.
This will put the system in a Reheat Mode of operation.
The thermostat willonlycycle the heat valveandpump.
The cooling circuit will stay energized as long as the
override switch is in the ON position and both sensor
switches are closed.
CONTROL ACTION -- CYCLING CLUTCH
RISING
TEMPERATURE
FULLCOOL
+1.8° F ABOVE
SETPOINT
SETPOINT
VENT
SETPOINT
-- 1. 8° F ABOVE
SETPOINT
HEAT
FALLING
TEMPERATURE
Figure 2.2 280P / 282P Thermostat
2--3
T--30404/08
SECTION 3
OPERATION BT324 CONTROLLER
3.1 STARTING, STOPPING AND OPERATING
INSTRUCTIONS
The BT324 Carrier Sutrak Digital Display (CSDD) is
marked with international symbols (See Figure 3--2).
Before starting, electrical power must be availablefrom
the bus power supply (See Figure 3--1).
A 150 Amp @12 VDC or a125 Amp @ 24 VDC fuse in
the battery compartment passes power for the clutch,
evaporator and condenser assemblies.
Figure 3--1 Bus Dash With A/C Switch & BT324 CSDD Controller
3.1.1 Starting
a. If the engine is not running, start the engine.
b. When the 12/24VDC power is applied, thedriverdis-
play will illuminate and show return air set point.
Press the A/C key (Item 5 Figure 3--2) on the display
to trigger the start up sequence.
c. After the pre--trip inspection is completed, the
switches may be set in accordance with the desired
control modes.
3.1.2 Stopping
A/C
Toggling the A/C key (Item 5 Figure 3--2)onthedisplay
again will stop the system operation.
3.2 PRE--TRIP INSPECTION
After startingsystem,allow systemtostabilizefor tento
fifteen minutes and check for the following:
a. Listen for abnormal noises in compressoror fan mo-
tors.
b. Check compressor oil level (05G Compressor only).
c. Check refrigerant charge. (Refer to section 5.8.1 )
3--1
T--30404/08
1
6
5432
10987
KEYS
Figure 3--2 BT324 CSDD Controller
1.Plus Key
2.Minus Key
3.Recirculate/Fresh Air Key
4.Blower Control Key
5.Automatic Climate Control (A/C)
3.3 SEQUENCE OF OPERATION BT324 CSDD
3.3.1 Function of Keys when “Engine On” and
controller active:
a. Plus Key-- Increasesinteriortemperaturesetpointby
1° per stroke or increases manual blower speed, depending on displayed mode.
b. Minus Key -- Decreasesinteriortemperaturesetpoint
by 1° per stroke or decreases manual blower speed,
depending on displayed mode.
c. Recirculating Air/Fresh Air -- Switches from Recircu-
lating Air to Fresh Air and vice--versa.
d. Blower Control-- Switcheson themanual blowercon-
trol.
e. Automatic Climate Control -- Switches on the Auto-
matic Temperature Control.
f. Temperature Indicator (Key2+Key3)-- Shows the
inside temperature for 10 seconds. If pressed a second time shows the outside temperature for 10 seconds (optional).
g. Reheat (optional) (Key3+Key5)-- Starts Reheat
mode for 3 minutes (duration adjustable).
h. Controller Off (A/C Switch ToOff) -- Switches off all
control functions and the display.
LEDS
6.Display
7.Fresh Air Operation (Green)
8.Manual Blower Control ’ON’ (Green)
9.Heating Mode (Green)
10.Malfunction Light (Red)
NOTE
The following blower steps are disabled when
the automatic climate control is on:
2--, 3--step blower: Off
Continuously adjustable blower: Off
3.3.2 Illuminating Indications (Display)
With “Engine--On” and Controller active
3.4 Operating Instructions BT324
Whentheengine is running, toggletheA/CSwitch to on
to activate the Air Conditioning Unit.
3.4.1 Display
When the unit is ON, the display shows the interior
setpointtemperature.Whenselectingindividual
functions, the display shows the corresponding
information forashort periodoftime. Thedisplayisdark
when the engine and control unit are OFF.
3.4.2 Interior Temperature Control
Press the Plus (1) or Minus (2) keys to set the desired
interior temperature.
Thetemperaturecanbeadjustedbetween 64° F(18° C)
and 82° F(28° C).
When the outside temperatures are below 35° F(2° C)
(adjustable parameter), the cooling function remains
disabled.
3.4.3 Ventilation
When the unitisoperatinginAutomaticClimateControl
mode, theblower speed iscontrolled basedon theroom
temperature.
T--304
3--2
04/08
However,theblowers maybeswitched tomanualmode
of operation by pressing the blower key.
Press the Plus orMinuskeys to define oneof 5 different
blower steps. The blowers can not be switched OFF
when Automatic Climate Control is ON.
When Automatic Climate Control is OFF, the blowers
stop when the manual control is turned to zero.
3.4.4 Reheat (optional)
The Reheat modeisused to remove air humidity and to
help defog the windshield. Press Key 3 (Recirculating
Air/FreshAir) and Key 5(Automatic Climate Control) at
the same time to activate Reheat. Heating and cooling
will be energized on for 3 minutes (adjustable
parameter). In addition, the blowers are switched to
maximum speed and the fresh air flap is closed. At the
end of the pre--set duration of time,the functions return
to the previously selected settings.
Reheatmodeisdisabledwiththeoutside temperatureis
below 35° F(2° C) (adjustable parameter), when the
sensor is notinstalled, orwhenthereis a sensorfailure.
3.4.5 Temperature Indication
Presskey2 (minus) and key3(RecirculatingAir/Fresh
Air) at the same time to display the inside temperature
for 10 seconds.
Optionally, the outside temperature may be displayed
when pressing the keys a second time.
A sensor malfunction is displayed by “ i -- -- ” or “ o -- -- ” .
3.5 CHANGING BETWEEN °F (FAHRENHEIT)
AND °C(CELCIUS)
Procedures for changing theBT324Controllerbetween
Fahrenheit and Celcius is as follows:
a. Engine “OFF” & Ignition “ON”.
b. Press Key 1 (plus) and Key 2 (minus) at the same
time until the display shows the word “Code”.
NOTE
After the display shows the word “Code” you
have 5 seconds to enter the correct access
code.
c. Press Key 1 (Plus Key) one time and release.
d. Press Key 3 (Recirculating Air/Fresh Air) one time
and release.
e. Press Key 4 (blower control) one time and release.
The display will show the mode “Fah” for temperatures
in °F or the mode “Cel” for temperatures in °C.
f. Press Key 1 (plus) or Key 2 (minus) to change the
temperature mode.
g. Press Key 5 (automatic climate control) one time to
end the program.
3--3
T--30404/08
SECTION 4
TROUBLESHOOTING
Table 4-- 1 General System Troubleshooting Procedures
INDICATION --
TROUBLE
4.1System Will Not Cool
Compressor will not runDrive--Belt loose or defective
Electrical malfunctionCoach power source defective
4.2System Runs But Has Insufficient Cooling
CompressorDrive-Belt loose or defective
Refrigeration systemAbnormal pressures
Restricted air flowNo evaporator air flow or restriction4.5
Heating systemHeat valve stuck open4.7
4.3Abnormal Pressures
High discharge pressureRefrigerant overcharge
Low discharge pressureCompressor valve(s) worn or broken
High suction pressureCompressor valve(s) worn or brokenSeeTable1--3
Low suction pressureSuction service valve partially closed
Suction and discharge pressures
tend to equalize when system is
operating
Worn bearings
Worn or broken valves
Liquid slugging
Insufficient oil
Clutch loose, rubbing or is defective
Drive-Belt cracked, worn or loose
Dirt or debris on fan blades
POSSIBLE CAUSES
REFERENCE
SECTION
Check
Check/Replace
Check/Replace
SeeTable1--3
Check/Repair
Check/Reset
Check
SeeTable1--3
4.3
4.5
4.6
5.11
5.8
Open
1.5
5.13
5.8.1
Check
Check
Clean
SeeTable1--3
5.8
Open
Check/Open
5.11
5.8
4.6
4.5
Check/Tighten
SeeTable1--3
SeeTable 1--3
4.6
1.3
Repair/Replace
Adjust/Replace
Clean
04/08
4--1
T-304
Table 4-- 1 General System Troubleshooting Procedures -- Continued
INDICATION --
TROUBLE
POSSIBLE CAUSES
REFERENCE
SECTION
4.4Abnormal Noise Or Vibrations -- Continued
Condenser or evaporator fansLoose mounting hardware
Defective bearings
Blade interference
Blade missing or broken
Check/Tighten
Replace
Check
Check/Replace
4.5No Evaporator Air Flow Or Restricted Air Flow
Air flow through coil blockedCoil frosted over
Dirty coil
Dirty filter
No or partial evaporator air flowMotor(s) defective
Motor brushes defective
Evaporator fan loose or defective
Fan damaged
Return air filter dirty
Icing of coil
Fan relay(s) defective
Safety device open
Fan rotation incorrect
Defrost coil
Clean
Clean/Replace
Repair/Replace
Replace
Repair/Replace
Repair/Replace
Clean/Replace
Clean/Defrost
Check/Replace
1.5
Check
4.6Expansion Valve Malfunction
Low suction pressure with high
superheat
Low superheat and liquid slugging
in the compressor
Low refrigerant charge
Wax, oil or dirt plugging valve orifice
Ice formation at valve seat
Power assembly failure
Loss of bulb charge
Broken capillary tube
Bulb is loose or not installed.
Superheat setting too low
5.8
Check
4.6
Replace
Replace
5.16
5.16
5.16
Ice or other foreign material holding valve open
Side to side temperature difference (Warm Coil)
Wax, oil or dirt plugging valve orifice
Ice formation at valve seat
Power assembly failure
Loss of bulb charge
Broken capillary
Check
5.7
Replace
Replace
5.16
4.7Heating Malfunction
Insufficient heatingDirty or plugged heater core
Coolant solenoid valve(s) malfunctioning or plugged
Low coolant level
Strainer(s) plugged
Hand valve(s) closed
Water pumps defective
Auxiliary Heater malfunctioning.
No HeatingCoolant solenoid valve(s) malfunctioning or plugged
Controller malfunction
Pump(s) malfunctioning
Safety device open
Besure toobservewarnings listed inthesafetysummaryin thefront ofthis manual beforeperforming maintenance on the hvac system
WARNING
Read the entire procedure before beginning work. Park the coach on a level surface, with parking
brake applied. T urn main electrical disconnect switch to the off position.
NOTE
To avoid damage to the earth’s ozone layer, use a refrigerant recovery system whenever removing refrigerant. The refrigerant recovery system isavailablefromCarrier Transicold (CarrierTransicoldP/NMVSII--115
orMVSII--240).Whenworkingwithrefrigerants youmustcomplywithall localgoverment environmental laws.
5.1 MAINTENANCE SCHEDULE
SYSTEM
ONOFF
a. Daily Maintenance
X
b. Weekly Inspection
X
c. Monthly Inspection and Maintenance
5.2 REMOVING EVAPORATOR COVER
To remove the evaporator cover do the following:
1. Turn all the 1/4 turn cam locks counterclockwise.
2. Using two people carefully grasp the cover under the
bottom edge and lift up.
3. Place the evaporator cover on top of the condenser
section.
5.3 REMOVING CONDENSER COVER
To remove the condenser cover do the following:
1. Turn all the 1/4 turn cam locks counterclockwise.
2. Using two people carefully grasp the cover under the
bottom edge and lift up.
Pre-tripInspection -- after starting
X
Check tension and condition of drive belts.
X
Perform daily inspection
X
Check condenser, evaporator coils and air filters for cleanliness
X
Check refrigerant hoses, fittings and component connections for leaks
Feel filter-drier for excessive temperature drop across drier
X
Perform weekly inspection and maintenance
X
Clean evaporator drain pans and hoses
X
Check wire harnesses for chafing and loose terminals
X
Check fan motor bearings
X
Check compressor mounting bolts for tightness
SYSTEM
REFERENCE
SECTION
2.2
None
See above
None
5.6
5.11
See above
None
Replace/Tighten
None
None
3. Place the condenser cover on top of the evaporator
section.
5.4 INSTALLING MANIFOLD GAUGE SET
A manifold gauge set can be used to determine system
operating pressures, add charge, equalize or evacuate
system.
When the suction pressure hand valve is frontseated
(turned alltheway in),thesuction(low) pressure can be
read. When the discharge pressure hand valve is
frontseated, discharge (high) pressure can be read.
When both valves are open (turnedcounterclockwise),
high pressure vapor will flow into the low side. When
only the low pressure valve is open, the system can be
charged or evacuated.
04/08
5--1
T-304
CAUTION
The AC310 & AC350 Rooftop Systemshave
R134a service port couplings installed on
the compressor and 1/4 inch flare (Acme)
fittings installed on the unit piping.
SUCTION
PRESSURE
GAUGE
1.
DISCHARGE
PRESSURE
GAUGE
5.4.1 Installing R--134a Manifold Gauge/Hose SET
An R--134a manifold gauge/hose set with self--sealing
hoses is pictured in Figure 5--1. The manifold
gauge/hose set is available from Carrier Transicold.
(Carrier Transicold P/N 07--00294--00, which includes
items1through6,Figure 5--1).Toperform serviceusing
the manifold gauge/hose set, do the following:
a. Preparing Manifold Gauge/Hose Set for use.
1. If the manifold gauge/hose set is new or was exposedtothe atmosphere itwillneed tobe evacuated
to remove contaminants and air as follows:
2. Back--seat (turncounterclockwise) bothfieldservice
couplers (see Figure 5--1) and mid--seat both hand
valves.
3. Connect the yellow hose to a vacuum pump and an
R--134a cylinder.
4. Evacuate to 10 inches of vacuum and then charge
with R134a to slightly positive pressure of 1.0 psig.
5. Front--seatbothmanifold gaugeset handvalvesand
disconnect from cylinder. The gauge set is now
ready for use.
b. Connecting the Manifold Gauge Gauge/Hose Set.
To connect the manifold gauge/hose set for reading
pressures, do the following:
1. Connect the field service couplers (see Figure 5--1)
to the high and low in--line service ports.
2. Turn the field service coupling knobs clockwise,
which will open the system to the gauge set.
3. Read the system pressures.
c. Removing the Manifold Gauge Set.
1. While the compressor is still ON, mid--seat both
hand valvesonthe manifold gaugesetand allow the
pressureinthemanifoldgauge settobedrawndown
tolowside pressure. Thisreturnsanyliquidthatmay
be in the high side hose to the system.
CAUTION
To prevent trapping liquid refrigerant inthe
manifoldgaugesetbesuresetis broughtto
suction pressure before disconnecting.
2. Back--seatbothfield servicecouplersand front--seat
bothmanifoldsethand valves.Removethe couplers
from the in--line access valves.
3. Install both in--line access valve caps.
T-304
5--2
04/08
5.5 PUMPING THE SYSTEM DOWN OR REMOVING THE REFRIGERANT CHARGE
To service or replace the filter--drier, pump the
refrigerant to the condenser and receiver as follows:
a. Remove evaporator and condenser covers.
b. Install manifold gauge/hose set. (Refer to Section
5.4.1).
c. Frontseatthefilter--drierinlet servicevalve by turning
clockwise. It will be necessary to install a jumper
across the low pressure switch(LPS) contacts at the
compressor in order to reach 0 PSIG.
d. Start the system and run in cooling. Stop the unit
when suction reaches 10 ”/hg (25.4 cm/hg) vacuum.
e. Frontseat filter/drieroutletservicevalve to traprefrig-
erantin thehighsideofthesystem betweenthe compressor andthefilter--drierinlet valve. Wait 5minutes
to verify that system remains in a vacuum.
f. Service or replace filter--drier.
1.
D
S
2.
To Compressor
7.
6.
Figure 5--2 In--Line Service Connections
1. Discharge Service
Port
2. Suction Service
Port
3. Manifold Gauge
4. Vacuum Pump
5. Reclaimer
6. Refrigerant Cylinder
7. Thermistor Vacuum
Gauge
Set
3.
4.
5.
g. Leak check connections after replacing filter--drier.
Refer to paragraph 5.6.
h. Usingrefrigeranthoses designedfor vacuumservice,
evacuateanddehydrate thefilter--drierby connecting
a vacuum pump to center connection of manifold
gauge set. Evacuate system to 500 microns. Close
off pump valve, isolate vacuum gauge and stop
pump. Wait 5 minutes to verify that vacuum holds.
i. Read MicronGaugeagainto verify that the pressure
did notrisemorethan500 microns within that 5--minute timeframe.
If the Micron Gauge rises more than 500 microns (to
excedeagaugereading of500 +500 =1000 microns) at
the end of 5 minutes, either a leak is present or an
unacceptable level of moisture remains in the circuit. If
the gauge reads a gain of less than 500 microns during
the5--minutewait, the circuit isacceptablytightanddry.
j. Oncevacuum is maintained, recharge systembyad-
mitting vapor from the refrigerant cylinder.
k. Remove manifold gauges. Backseat both filter drier
service valves.
5.5.2 Removing Entire System Charge
To remove the entire refrigerant charge, do the
following:
a. Connect a manifold gauge set to the system as
showninFigure5--2.
b. Connect a reclaimer tothecentermanifoldgauge set
connection.
c. Recover refrigerant in accordance with reclaimer
manufacturers instructions.
5.6 REFRIGERANT LEAK CHECK
A refrigerant leak check should always be performed
after the systemhasbeenopened to replaceorrepaira
component.
To check for leaks in the refrigeration system, perform
the following procedure:
NOTE
It must be emphasizedthat only the correct refrigerant should be used to pressurize the system. Use of any other refrigerant will contaminate the system, and require additional
evacuation.
a. Ensure filter drier service and solenoid valves are
open.
1. Filter drier service valves should be back seated.
b. If system is without refrigerant, charge system with
refrigerant vapor to build up pressure between 20 to
30 psig (1.36 to 2.04 bar).
c. Add sufficient nitrogen to raise system pressure to
150 to 200 psig (10.21 to 13.61 bar).
d. Check for leaks. The recommended procedure for
findingleaksina systemis withanelectronicleakdetector. Testing joints with soapsuds is satisfactory
only for locating large leaks.
e. Remove test gas and replace filter--drier.
f. Evacuate and dehydrate the system. (Refer to para-
graph 5.7.)
g. Charge the unit. (Refer to paragraph 5.8.)
5.7 EVACUATION AND DEHYDRATION
5.7.1 General
04/08
5--3
T-304
The presence of moistureinarefrigeration system can
have many undesirable effects. The most common are
copper plating, acid sludge formation, “freezing-up” of
metering devices by freewater, and formation of acids,
resulting in metalcorrosion. An evacuation shouldtake
place after a system repair (replacement of filter drier.
expansion valve, solenoid valve, etc).
5.7.2 Preparation
NOTE
Using a compound gauge (manifold gauge) for
determination of vacuum level is not recommended because of its inherent inaccuracy.
a. Evacuate anddehydrate onlyafter pressureleaktest.
(Refer to paragraph 5.6)
b. Essential tools to properly evacuate and dehydrate
anysysteminclude agood vacuumpumpwith aminimumof5cfm(8.5 m
3
/hr)volumedisplacement,(CTD
P/N 07-00176-11), and a good vacuum indicator
(CTD P/N 07--00414--00).
c. Keep the ambient temperature above 60°F (15.6°C)
to speed evaporation of moisture. If ambient temperature is lower than 60°F (15.6°C), ice may form before moisture removal is complete.
5.7.3 Procedure for Evacuation and Dehydrating
System
a. Removerefrigerant usingarefrigerant recovery sys-
tem. Refer to paragraph 5.5.2
b. Therecommendedmethod isconnecting3/8”OD re-
frigerant hoses designed for vacuum service as
shown in Figure 5--3.
c. Make sure vacuum pump valve is open.
d. Start vacuum pump. Slowly open valves halfway and
then open vacuum gauge valve.
e. Evacuate unit until vacuum gauge indicates 500 mi-
crons Hgvacuum. Closegaugevalve, vacuum pump
valve, and stop vacuum pump.
f. Close off pump valve, and stop pump. Wait five min-
utes to see if vacuum holds.
g. Charge system. Refer to paragraph 5.8.2
5.8 ADDING REFRIGERANT TO SYSTEM
5.8.1 Checking Refrigerant Charge
The following conditions must be met to accurately
check the refrigerant charge.
a. Bus engine operating at high idle.
b. Unit operating in cool mode for 15 minutes.
c. Compressor discharge pressure at least 150 psig
(10.21 bar). (It may benecessary toblockcondenser
air flow to raise discharge pressure.)
NOTE
Ideal charging conditions are with ambient
above 86°F(30°C) and interior vehicle temper-
ature above 77°F(25°C). Charging to a full
sight glass at lower temperatures may lead to
system overcharge.
d. Under the above conditions, the system is properly
the high side of the system
f. When correct charge has been added (refer to para-
graph 1.3, refrigerant specifications), close cylinder
valve and frontseat manifold discharge valve.
g. Preparethecylinder asrequired toallowvaporcharg-
ing. Backseat the manifold suction valve and charge
vapor until thecorrect chargehasbeen added. Close
cylinder valve and frontseat suction manifold set.
h. Check charge level in accordance with the proce-
dures of paragraph 5.8.1.
5.9 CHECKING FOR NONCONDENSIBLES
To check for noncondensibles, proceed as follows:
a. Stabilize system to equalize pressure between the
suction and discharge side of the system.
b. Check temperature at the condenser and receiver.
c. Check pressure at the discharge (in--line) service
port.
d. Check saturation pressure as it corresponds to the
condenser/receiver temperature. See temperature--
Pressure chart Table Table 5--1. for R134a.
e. If gauge readingis3 psig or more than the calculated
P/T pressure in step d., noncondensables are pres-
ent.
f. Removerefrigerant usingarefrigerant recovery sys-
tem.
g. Evacuate and dehydrate the system. (Refer to para-
graph 5.7.)
h. Charge the unit. (Refer to paragraph 5.8.2.)
5.10 CHECKING AND REPLACING HIGH OR LOW-
PRESSURE CUTOUT SWITCH
5.10.1 Replacing High Or Low Pressure Switches
a. The high and low pressure switches are equipped
withschradervalvestoallow removal andinstallation
without recovering the refrigerant charge.
b. Disconnect wiring from defective switch.
c. Install new cutout switch after verifying switch set-
tings.
T-304
5--4
Change 07/09
5.10.2 Checking High Or Low Pressure Switches
WARNING
5.11 FILTER-DRIER
Do not use a nitrogen cylinder without a pressure regulator
WARNING
Donot useoxygeninornear arefrigerationsystem as an explosion may occur.
a. Disconnect wiring and remove switch from system.
b. Connect an ohmmeter across switch terminals. If the
switch is good, the ohmmeter will indicate no resistance, indicating that the contacts are closed.
c. Connect switch to a cylinder of dry nitrogen.
(SeeFigure 5--4).
1.
4.
2.
3.
5.
6.
2.3.4.
1.
Figure 5--5 Filter--Drier Removal
1.Filter-Drier Inlet
Service Valve
2.Valve Service Port
3.Flare Nut
4.Filter-Drier
5.11.1 To Check Filter--Drier
Thefilter--drier(SeeFigure 5--5)mustbechanged ifthe
system has been opened, (for any reason), or the filter
drier is partially restricted. Restriction can be identified
by either the outlet frosting or a temperature difference
between the inlet and outlet.
5.11.2 To Replace Filter--Drier Assembly
Filter Drier replacement can be accomplished by
performingeitheroneofthetwoprocedures
recommended.
1. System operating,lowsidepumpdown (refertosection 3.4.1).
2. System not operating (see below).
a. Turn the driver’s A/C switch to “OFF” position.
b. Frontseat the filter--drier servicevalveson bothsides
of the filter drier.
c. Place a new filter-drier near the unit for immediate
installation.
3.
5.Liquid Line
6.Filter-Drier Outlet
2.
Solenoid Valve
Service Valve
6.
5.
Figure 5--4 Checking High Pressure Switch
1.Cylinder Valve and Gauge
2.Pressure Regulator
3.Nitrogen Cylinder
4.Pressure Gauge (0 to 400 psig = 0 to 27.22 bar)
5.Bleed-Off Valve
6.1/4 inch Connection
d. Set nitrogen pressure regulator higher than switch
cutout setting. (refer to paragraph 1.3.)
e. Open cylinder valve. Slowlyopentheregulator valve
to increase the pressureuntil it reaches cutout point.
The switch shouldopen,whichis indicated by an infinite reading on an ohmmeter (no continuity).
f. Close cylinder valve and release pressure through
the bleed--off valve. As pressure drops to cut--in
point, the switchcontacts should close, indicatingno
resistance (continuity) on the ohmmeter.
g. Replace switch if it does not function as outlined
above.
WARNING
The filter-drier may contain liquid refrigerant.Slowlyloosentheconnectingnuts and
avoid contact with exposed skin or eyes.
d. Using two openendwrenches, slowly crack openthe
connecting nuts on each side of the filter-drier assembly. Remove the filter-drier assembly.
e. Remove seal caps from the new filter-drier. Apply a
light coat of mineral oil to the filter--drier connections.
f. Assemblethenewfilter-driertolinesensuringthatthe
arrowonthe bodyofthefilter-drierpointsin the direction of the refrigerant flow (refrigerant flows from the
receiver to the evaporator). Finger tighten the connecting nuts.
g. Tighten filter-drier connecting nuts using two open
end wrenches.
h. Evacuate system (refer to section 5.7).
i. Backseat(fullyclose) bothservicevalveports andre-
place valve caps.
j. Check refrigerant charge (refer to section 5.8.1).
k. Remove Gauges.
04/08
5--5
T-304
5.12 SERVICING THE HEAT VALVE
f
f
The heat valve (Figure 5--6) requires no maintenance
unless a malfunction to theinternalparts or coiloccurs.
This may be caused by foreign material such as: dirt,
scale, or sludge in the coolant system, or improper
voltage to the coil.
1. Coil Retaining Screw
2. Nameplate
3. Coil Housing
Assembly
4. Enclosing Tube &
Bonnet Assembly
5. Kick-O
6. Plunger
7. Closing Spring
8. Diaphragm
9. O-Ring
10. Valve Body
Spring
NOTE
TheOEMsuppliedheating(hot water)Solenoid
Valve is normally located outside of the
AC310/350 rooftop air conditioning system.
There are only three possible valve malfunctions: coil
burnout, failure to open, or failure to close.
Coil burnout may be caused by the following:
1. Improper voltage
2. Continuous over-voltage, more than 10% or Undervoltage of more than 15%.
3. Incomplete magneticcircuitduetotheomissionofthe
coil housing or plunger.
4. Mechanical interference with movement of plunger
which may be caused by a deformed enclosing tube.
Failure to open may be caused by the following:
1.Coil burned out or an open circuit to coil connections.
2. Improper voltage.
3. Torn diaphragm.
4. Defective plunger or deformedvalvebodyassembly.
Failure to close may be caused by the following:
1. Defective plungerordeformedvalve bodyassembly.
2. Foreign material in the valve.
3. Torn diaphragm.
1.
2.
5.12.1 Coil Replacement
a. It is not necessary to drain the coolant from the sys-
tem.
b. Place mainbatterydisconnectswitchin OFF position
and lock.
c. Disconnect wire leads to coil.
d. Remove coil retaining screw and nameplate.
e. Lift burned-out coil from enclosing tube and replace.
f. Connect wire leads and test operation.
5.12.2 Internal Part Replacement
a. Disconnect system from bus battery.
b. Open the vent fitting atthetopoftheoutlet headerof
the heater coil.
c. Draincoil by opening thedrain-cock ontheinlet tube.
d. Disassemble valve and replace defective parts.
e. Assemble valve, refill and bleed coolant lines.
5.12.3 Replace Entire Valve
a. Disconnect system from bus battery.
b. Drain coolant fromlines as previously described and
disconnect hoses to valve .
c. Disconnect wire leads to coil.
d. Remove valve assembly from bracket.
e. Install new valve and re-connect hoses. It is not ne-
cessarytodisassemblethe valvewheninstalling.
f. Refill and bleed coolant lines.
g. Connect wire leads and test operation.
T-304
3.
4.
5.
6.
7.
8.
9.
10.
Figure 5--6 Heat Valve
5.13 SERVICING THE LIQUID LINE SOLENOID
VALVE
The Liquid line solenoid valve (Figure 5--7) is very
similar to the heat valve. It requires no maintenance
unless a malfunction to theinternalparts or coiloccurs.
This may be caused by foreign material such as: dirt,
scale, orsludgein the refrigeration system, or improper
voltage to the coil.
There are only three possible valve malfunctions: coil
burnout, failure to open, or failure to close.
Coil burnout may be caused by the following:
1. Improper voltage.
2. Continuous over-voltage, more than 10% or under-
voltage of more than 15%.
3. Incomplete magnet circuit due to the omission of the
coil hosing or plunger.
4. Mechanical interface with movement of plunger
which may be caused by a deformed enclosing tube.
5--6
04/08
Failure to open may be caused by the following:
g
y
1. Coil burnedoutoran open circuit to coil connections.
2. Improper voltage.
2.
1.
3. Defective plunger or deformedvalvebodyassembly.
Failure to close may be caused by the following:
1. Defective plunger or deformedvalvebodyassembly.
2. Foreign material in the valve.
5.13.1 Coil Replacement
a. It is not necessary to remove the refrigerant charge
from the system.
b. Disconnect system from bus battery.
c. Disconnect wire leads to coil.
d. Remove coil retaining clip and nameplate.
e. Lift failed coil from enclosing tube and replace.
f. Connect wire leads and test operation
5.13.2 Internal Part Replacement
a. Disconnect system from bus battery.
3.
4.
5.
6.
7.
8.
Figure 5--7 Liquid Line Solenoid Valve
1. Snap Cap
2. Coil Assembly
3. Enclosing Tube
Assembly
4. Plun
5.14 SERVICE V AL VES
The filter/drier (High Side) service valves (Figure 5--8)
areprovidedwith a doubleseatand agaugeport,which
allows servicing of the filter drier assembly.
er Assembl
5. Gasket
6. Piston Assembly
7. Body
8. Bracket Adapter
b. Recover and recycle system refrigerant.
c. Slowly loosen enclosing tube assembly to bleed any
remaining pressure from the valve. Disassemble
valve and replace defective parts.
d. Assemble valve and leak check.
e. Evacuate and recharge system.
5.13.3 Replace Entire Valve
a. Recover and recycle system refrigerant.
b. Remove valve assembly from bracket.
c. Disconnect wire leads to coil.
d. Disassemble newvalve,toprotectinternalparts,and
solder to lines.
e. Assemble and leak check valve.
f. Evacuate and recharge.system.
Turning the valve stem counterclockwise (all the way
out) will backseat the valve to open the line to the
system and close off the gauge port. In normal
operation, the valve is backseated to allow full flow
through the valve. The valve should always be
backseated before removing the gauge port cap.
Turning the valve stem clockwise (all the way forward)
will frontseat the valve to isolate the system and open
the gauge port.
TO DISCHARG LINE
Port To
Compressor
Service Valve
Frontseated
(clockwise)
Service Valve
Backseated
(counterclockwise)
VALVE CAP
SERVICE
PORT
VALVE
STEM
g. Connect wire leads and test operation.
04/08
5--7
Figure 5--8 Service Valve R134a (High Side)
T-304
5.15 REPLACING RETURN AIR FILTERS
The return air filters are located behind the return air
grill, inside the vehicle.
Thefiltersshould becheckedforcleanliness
periodically depending on operating conditions. A dirty
filter will restrict air flow over the evaporator coil which
may cause insufficient cooling or heating and possible
frost buildup on the coil. To remove the filters, do the
following.
a. Insure air conditioning system is in the off position.
b. Remove the return airgrillewiththefilter--diffuseras-
sembly,byturning the six 1/4 turn fastenerscounterclockwise.
Composit Frame
f. Pullfilterelement approximately 1/4inchover endsof
the diffuser.
Diffuser
Air Filter
Composit Frame
Figure 5--11
Filter, Diffuser and Composit Frame
g. Place filteranddiffuser intocompositframe, withfilter
element down (See Figure 5--11).
Return Air Filter
Figure 5--9 Return Air Grill Assembly
With Air Filter Showing
c. Remove diffuser from the bus composit frame.
Diffuser
Return Air Filter
Figure 5--10 Diffuser and Filter Element
d. Remove and replace the filter element.
e. Center diffuser on filter element.
Captive 1/4 Fastners
Figure 5--12 Return Air Grill Assembly
With Diffuser And Composit Frame Showing
h. Insert filter--diffuserassemblyintocomposit frameon
bus with the six captive 1/4 fasteners. (See
Figure 5--12)
i. Lock the six captive 1/4 turns in place by rotating
clockwise.
5.16 THERMOSTATIC EXPANSION VALVE
The thermostat expansion valve (Figure 5--13) is an
automatic device which maintains constant superheat
of the refrigerant gas leavingtheevaporator regardless
of suction pressure. The valve functions are: (a)
automatic control of refrigerant flow to match the
evaporator load and (b) prevention of liquid refrigerant
entering the compressor.Unless the valve is defective,
it seldom requires any maintenance.
T-304
5--8
04/08
1.
2.
3.
4.
5.
4.
6.
7.
Figure 5--13 Thermostatic Expansion Valve
1..Power Head
Assembly
2..Equalizer Connection
3..Bulb
5.16.1 Valve Replacement
a. If compressor is operative perform low side pump
down to replace expansion valve. (refer to 5.5.1) If
compressor isinoperativerecover and recycle refrigerant from the system.(refer to 5.5.2)
b. Remove insulation from expansion valve bulb. (See
Figure 5--13 and Figure 5--14.)
c. Loosen retaining straps holding bulb to suction line
and detach bulb from the suction line.
d. Loosen flare nuts on equalizer line and disconnect
equalizer line from the expansion valve.
e. Check, clean and remove any foreign material from
the valve body,valveseatandmatingsurfaces. If required, replace valve body.
4..Gasket
5..Cage Assembly
6..Body Flange
7..Cap screw
3.
2.
4.
5.
1.
Figure 5--14 Thermostatic Expansion Valve Bulb
1..Suction Line
(section view)
2..TXV Bulb Clamp
3..Nut & Bolt (clamp)
a. Open top cover.
b. Remove Presstite insulation from expansion valve
bulb and suction line.
c. Loosenone TXV bulb clamp and make sure area un-
der clamp is clean.
d. Place temperature thermocouple in contact with the
suction tube and parallel to the TXV bulb, and then
secure loosened clamp making sure both bulb and
thermocouple are firmly secured to suction line. (See
Figure 5--14). Reinstall insulation around the bulb.
e. Connect an accurate low pressure gauge to the low
pressure port.
and Thermocouple
4..Thermocouple
5..TXV Bulb (Shown
in the 4’clock
position)
NOTE
R--134a valves are adjustable. Valves are presetatthefactory.
f. Leak check the new valve and evacuate and dehy-
drate the system. (Refer to paragraph 5.7.)
g. The thermal bulb is installed below the center of the
suction line (four or eight o’clock position). This area
must be clean to ensure positive bulb contact. Strap
thermal bulb to suction line. Ensure that retaining
straps are tight and renew insulation.
h. Fasten equalizer line to the expansion valve.
i. Evacuate and recharge the system.
j. Run the coach for approximately 30 minutes on fast
idle.
k.Check refrigerant charge. (Refer to 5.8.1)
5.16.2 Superheat Measurement
NOTE
All readings must be taken from the TXV bulb
location and out of the direct air stream.
04/08
f. Close top cover being careful to route thermocouple
sensing wire and gauge hose outside the unit.
g. Start bus and run on fast idle until unit has stabilized,
about 20 to 30 minutes.
NOTE
Whenconductingthis test,thesuctionpressure
must be at least 6 psig (0.41bar)below theexpansion valve maximum operating pressure
(MOP). Refer to paragraph 1.3 for MOP.
h. From the temperature/pressurechart, determine the
saturation temperature corresponding to the evaporator outlet pressure.
i. Notethe temperature ofthesuctiongas attheexpan-
sion valve bulb. Subtract the saturation temperature
from this temperature. The difference is the superheat of the suction gas.
5--9
T-304
j. Thesuperheatmaycyclefromalowto high reading.
Monitorthesuperheat takingreadingsevery 3--5minutes for a total of 5--6 readings. Calculate the superheats, add the readings and divide by the number of
readings taken todetermine average superheat. The
superheat should be 18 ± 3°F.
k. Ifsuperheatis notwithintolerance,replacethevalve.
This section includes electrical wiring schematics. The
schematics shown in this section provides information
for theAC310 andAC350 modelrooftopair conditioning
units which are fitted with eight (8) and twelve (12)
single--shafted or four (4) and six (6) double--shafted
evaporator blower/motor assemblies and four (4) or six
UNIT
AC 310Thermostat With Manual ReheatFigure 6--1 Thru Figure 6--6
AC 350BT324Figure 6--7 Thru Figure 6--13
AC 310/AC350Thermostat One/Two CompressorsFigure 6--14 To Figure 6--18
CONTROLLERFIGURE NUMBERS
(6)condenserfan motors.Figure 6--1through
Figure 6--6shows the Thermostat with manualre--heat.
Figure 6--7 thru Figure 6--13 shows the CSDD BT324
controller usedwiththeAC310 single and dualsystems
and the AC350 single loop with transit compressors.
Figure 6--14 thru Figure 6--18 shows Thermostat
control with one or two compressors.
6--1
T--30404/08
EVAPORATOR
Compressor Clutch
Convection HeatingConnection
CONTROL PANEL
HP Switch
LP Swi tch
HEATING VALVE
Y31A
M31M
WATER PUMP HEATING
Figure 6--1 System Controls (Typical)
G
CONDENSER
R1N
R2N
VERSION B
Operation Board
S3A
S1A
VERSION A
Operation Board
S2A
S1A
AC 310 100A @ 24VDC
AC 350125A @24VDC
FOM
AC310 OPTION 150A @12VDC
ALTERNATOR
Battery 24 VDC
6--2T--304
04/08
B+
OR
11
810
1
UR
24V12V
-- --
LL
Sensors
UK
UH
BKGY
Clutch
OGRD
REF: 98- -62- -62668- -00
Y2A
V5
V4
REL 1REL 2
CoolingHeating
WH
Inside sensor
Sensor
1 9162435
Thermostat
7
Poti.
WH
BN
WH
B1N
X20
91011
2
1
Liquid Line Valve
Y1A
or
swor
B+
RD
BKYE
U5
15A
F1A
BKBU
U2
R1N
Temperature setting
Operation Board
OEM SUPPLIED
*
Dash Control
858787a
K4A
8630
Other Signal Indicating
Vehicle Electrical System
Is Ready To Operate AC
System
OR
WHBU
WH
V1
OGRD
87
30
WHRD
8687a
85
U3
K1A
V3
WHOG
345
WHYE
V2
RDWH
X3
12
WH
BKRD
Climate
S2A
High
Vent 2
1
S1A
3
7
Low
Vent 1
5A
F01A
Operation Board
T----Splice Into Freightliner
Wire 393 At Hydraulic
Wire 393
87A
86
87
Figure 6--2 Manual Controls With Manual Reheat Control (Sheet 1)
Brake Module
*
30
A/C Power
30 A Relay
85
Battery
Evap. Low
Evap. High
Cond. Mtrs.
6--3
Breaker 10
*
5A
T--30404/08
M31M
OEM SUPPLIED
*
RD
12VDC
Ov e r -- -- R i d e S w i t c h
10A
F2A
25F
60F
=
B21F
M
Waterpump heating
Y31A
Heating valve
L P -- -- s wi t c h
P
Y8M
Compressor clutch
NOTE A
Breaker
15A
*
A/C Low Voltage
BK
60 Switch --- - Closes On Temperature Rise
25 Switch --- - Opens On Temperature Decrease
87
BK
30
87a85
86
K3A
CLR1
86
85
8787a
30
BU
Note A
BK
8
*
CR1
85
8687
30
87a
B20F
H P -- -- s wi t c h
P
B+
RD
OR
CLR2
86
85
BKGY
UK
10A10A
F3AF4A
OGRD
87
30
87a
86
85
K2A
LL
87
30
87a
UH
*
CR2
868787a
85
30
H P -- -- s wi t c h
L P -- -- s wi t c h
P
B10F
B11F
P
Y7M
Figure 6--3 Manual Controls With Manual Reheat Control (Sheet 2)
Compressor clutch
T----Stat
LL Solenoids
REF: 98- -62668- -00
6--4T--304
04/08
B+
U2
U4
(OPTIONAL)
REF: 98- -62668- -00
15A
15A
15A
30
8786
GN
F4M
8585
K5M
F3M
BKGN
GN
BKBU
3086
BN
85
8587
BKOG
K6M
3086
BKWH
K4M
6
5
BN
WHGN
M3MM4M
MM
4
WHOG
Figure 6--4 Evaporator Motors 1 -- 4
M2MM1M
M
30
BK
F2M
BKYE
3086
BN
3
WHYE
8687
K2M
15A
F1M
GN
BKBU
8587
87
8587
BKRD
K3M
3086
BKBU
2
BN
M
K1M
+
F01M
1
BLACK
X2
150 AMP
SAO
WHRD
+
-- --
BATTERY 12 VDC
6--5
T--30404/08
B+
U2
U5
(Optional)
K13M
8630
8587
15A
15A
15A
F6M
87a
30
F8M
85
8687
K11M
GN
BKBU
WHOG
WHGNBU
3086
BN
85
87
8587
K12M
3086
WHBK
K10M
15
14
1310
M
BKGN
BN
M7MM8M
M
BKOG
F7M
M6M
MM
30
GY
WHYE
87
3086
BN
12
BKYE
Figure 6--5 Evaporator Motors 5 -- 8
85
8687
K8M
15A
F5M
B+
U2
GN
BKBU
WHRD
8587
85
K9M
3086
WHBU
K7M
11
BN
BKRD
M5M
X2
U4
REF: 98--62668--00
6--6T--304
04/08
B+
U2
BKBU
U5
BKYE
U3
OGRD
REF: 98--62668--00
(Optional)
15A
85
86
GNYE
Figure 6--6 Condenser Motors
87
30
K14MK15M
85
86
87
30
U2
B+
U5
15A
15A15A
F13MF14MF15MF16M
GNBU
GNWH
MMM
10131415
X1
GNOG
M
WHITE
M21MM22MM23MM24M
6--7
T--30404/08
UL SWITCHES
Y7M Compressor Clutch
EVAPORATOR
Convection HeatingConnection
CONTROL PANEL
UNLOADER
HP Switch
LP Swi tch
HEATING VALVE
Y31A
M31M
WATER PUMP HEATING
CONDENSER
Figure 6--7 BT324 Controls With (1) Compressor (AC350)