Carrier 59SP5A User Manual

Page 1
Installation, Start-up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS ......................... 3
INTRODUCTION ................................... 4
CODES AND STANDARDS ........................... 4
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ... 4
ACCESSORIES ..................................... 5
LOCATION ........................................ 7
General ......................................... 7
AIR FOR COMBUSTION AND VENTILATION ......... 10
Introduction .................................... 10
CONDENSATE TRAP ............................... 13
Upflow ........................................ 13
Downflow ..................................... 13
Horizontal Right ................................. 14
Horizontal Left .................................. 14
CONDENSATE DRAIN ............................. 18
Upflow ........................................ 20
Downflow ..................................... 20
Horizontal ...................................... 21
Filter Arrangement ............................... 22
General Requirements ............................. 28
Ductwork Acoustical Treatment ..................... 28
115-V Wiring ................................... 30
J-Box Installation ................................ 31
24-V Wiring .................................... 31
Accessories ..................................... 31
Alternate Power Supplies .......................... 31
Special Venting Requirements for Installations in Canada . 37
General ........................................ 37
Materials ....................................... 38
Venting Systems ................................. 38
Locating the Vent Termination ...................... 38
Combustion Air and Vent Piping Insulation Guidelines ... 39
General ......................................... 57
Prime Condensate Trap ............................. 57
Purge Gas Lines ................................... 57
Adjustments ...................................... 57
Cleaning Heat Exchangers ........................... 70
PARTS REPLACEMENT GUIDE ...................... 80
TABLES
Loose Parts Bag ..................................... 5
Minimum Clearances to Combustible Materials ............. 8
Minimum Free Area Required ......................... 12
Minimum Space Volumes ............................. 12
Filter Size Information ............................... 22
Air Delivery CFM ................................... 28
Maximum Capacity of Pipe ........................... 30
Electrical Data ...................................... 32
Vent Ternfination Kit for Direct Vent (2-Pipe) System ....... 38
Maxinmm Allowable Exposed Vent Lengths Insulation ...... 43
Maximum Equivalent Vent Length ...................... 44
Deductions from Maximum Equivalent Vent Length ........ 44
Blower Speed Taps .................................. 59
Blower Off Delay Setup Switch ........................ 59
Altitude DerateMultiplierfor U.S.A..................... 60
_ Always Ask For
Use of the AHRI Certified TM Mark indicales a manufacturer's
participalion in the program For verification
of certification [or individual products, go to www ahddirectory org
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2009©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the complete
and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.
ISO9001
Page 2
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA-54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It
shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in acrawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of
NFPA 54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of
the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be
satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and
Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617-727-9952.
Page 3
SAFETY CONSIDERATIONS
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal iniury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal iniury or property damage. Consult a qualified service agency, local gas supplier, or your
distributor or branch for information or assistance. The qualified service agency nmst use only factory-authorized
and listed kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD Failure to follow this caution may result in unit component
damage. Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified installer or agency nmst use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels
attached to or shipped with furnace and other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residential construction practices. We require these instructions as a
minimum for a safe installation. Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit.
CUT HAZARD
Failure to follow this caution may result in personal iniury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
This is the safety-alert symbol A'x When you see this symbol on the furnace and in instructions or manuals, be alert to the potential
for personal iniury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal iniury or death. WARNING signifies a hazard
which could result in personal iniury or death. CAUTION is used to identify hazards which may result in nfinor personal iniury or
product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as spe- cified in the "Location" section of these instructions.
3. Provide adequate combustion and ventilation air to the fur- nace space as specified in "Air for Combustion and Ventila-
tion" section.
4. Combustion products must be discharged outdoors. Con- nect this furnace to an approved vent system only, as spe-
cified in the "Venting" section of these instructions.
5. Never test for gas leaks with an open flame. Use a commer- cially available soap solution made specifically for the de-
tection of leaks to check all connections, as specified in the "Gas Piping" section.
6. Always install furnace to operate within the furnace's inten- ded temperature-rise range with a duct system which has an
external static pressure within the allowable range, as spe- cified in the "Start-Up, Adjustments, and Safety Check"
section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain-
ing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and ternfinating outside
the space containing the furnace. See "Air Ducts" section.
8. A gas-fired furnace for installation in a residential garage nmst be installed as specified in the warning box in the
"Location" section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first
CAUTION in the LOCATION section of these instruc- tions.
10. These Multipoise Gas-Fired Furnaces are CSA design-cer- tified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, base-
ments, closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A CSA
(A.G.A. and C.G.A.) listed accessory gas conversion kit is required to convert furnace for use with propane gas.
11. See Table 2 for required clearances to combustible con- struction.
12. Maintain a 1-in. (25 ram) clearance from combustible ma- terials to supply air ductwork for a distance of 36 in. (914
ram) horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpet- ing, tile, or any other combustible material other than wood
flooring. In downflow installations, factory accessory floor
base MUST be used when installed on combustible materi-
als and wood flooring. Special base is not required when this furnace is installed on manufacturer's Coil Assembly Part No. CNRV, CNPV, CAP, or CAR or when Coil Box Part No. KCAKC is used. See Table 2 for clearance to com-
bustible construction information.
il
Page 4
INTRODUCTION
This 4-way multipoise Category IV condensing furnace is CSA design-certified as a direct (2-pipe) or non-direct vent (1-pipe)
furnace. (See Fig. 2.)The furnace is factory-shipped for use with natural gas. The furnace can be converted in the field for use with propane gas when a factory-supplied conversion kit is used. Refer
to the furnace rating plate for conversion kit information. This furnace is approved for installation in a mobile home when a
factory-supplied accessory mobile home conversion kit is used. The conversion kit is required for use with both natural and propane gas. The furnace must also be installed on a
factory-supplied accessory combustible floor base or evaporator coil casing.
This furnace is designed for minimum continuous return-air temperature of 60°F (15°C) db or intermittent operation down to
55°F (13°C) db such as when used with a night setback thermostat. Return-air temperature must not exceed 80°F (27°C)
db. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 3).
g
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning
Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air-Conditioning Engineers; or other approved engineering methods. Excessive oversizing of the furnace could
cause the furnace and/or vent to fail prematurely. For accessory installation details, refer to the applicable instruction
literature. NOTE: Remove all shipping materials, loose parts bag, and
literature before operating the furnace. (See Table 1).
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
Safet2_
US: National Fuel Gas Code (NFGC) NFPA 54-2009/ANSI Z223.1-2009 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
A manufactured (Mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when this standard is not @plicable, the Standard for Manufactured Home Installation (Manufactured Home Sites, Communities, and Set-Ups),ANSI/NCS A225.1,
and/or CAN/CSA-Z240, MH Series Mobile Homes
CANADA: National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC CAN/CSA
B149.1-2010
General Installation
US: NFGC and the NFPA 90B. For copaes, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas
Association, 400 N. Capitol, N.W., Washington DC 20001
CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke
(Toronto), Ontario, Mgw IR3, Canada
Combustion and Ventilation Air
US: Section 9.3 of the NFPA54/ANSI Z223.1-2009 Air for
Combustion and Ventilation
CANADA: Part 8 of the CAN/CSA B149.1-2010, Venting Systems and Air Supply for Appliances
Duct Systems
US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005
Fundamentals Handbook Chapter 35
Acoustical Lining and Fibrous Glass Duct
US and CANADA: current edition of SMACNA, NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
US: NFPA 54/ANSI Z223.1-2009 NFGC; Chapters 5, 6, 7, and 8 and national plumbing codes. CANADA: CAN/CSA-BI49A-2010, Parts 4, 5, 6, and 9.
In the state of Massachusetts:
This product must be installed by a licensed plumber or gas fitter.
When flexible connectors are used, the maximum length shall not exceed 36 in. (914 mm).
When lever type gas shutoffs are used they shall be T-handle type.
The use of copper tubing for gas piping is not approved by the state of Massachusetts.
Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA 70-2011
CANADA: Canadian Electrical Code CSA C22.1
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL
OR ANY WIRE CONNECTED TO THE CONTROL
PRIOR TO DISCHARGING YOUR BODY'S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the fur- nace chassis which is close to the control. Tools held in a
person's hand during grounding will be satisfactorily dis- charged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO
Page 5
NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal
surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungroun- ded) furnaces.
6. Before removing a new control from its container, discharge your body's electrostatic charge to ground to protect the
Table 1 - Loose Parts Bag Contents (Provided in blower compartment)
Qty
1 1
2
10
1
2
1 1
1 1
2
1 1
1 1 1
1
3
1
Air Intake Pipe Flange Vent Pipe Flange Coupling Flange Gaskets
Sharp Tip Screws (Vent and Inlet Flanges) Vent Pipe Coupling Vent Pipe Coupling Clamps
Pressure Switch Tube
Outlet Choke Plate (used with 40k BTUH furnaces, only)
Drain Tube Elbow Drain Extension Tube
Drain Tube Clamps Drain Line Grommet
Gas Line Grommet Gas Line Knockout Plug
Junction Box Cover Junction Box Base
Green Ground Screw
Blunt Tip Screws (Junction Box)
Thermostat Wire Grommet
control from damage. If the control is to be installed in a furnace, follow items I through 4 before bringing the con-
trol or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded
objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
ACCESSORIES
See Product Data Sheet for a list of accessories for this product.
Description
Page 6
26 11116
[678.1]
263/8
[670.0]
25 1/8
[62O.7]
23 5/16
1592.9]
A_RFLOW 12_.31
CONDENSATE DRAIN TRAP
LOCATION \\\\
SIDE INLET
22
[55&3]
[634.0]
265/16
166S.6!
7/8 .......... _-_
_7/8 ....
122.21 _q_
THERMOSTAT ENTRY
126.4]
¢,7/8 _
615/II
[176.1]
11/16
[170.11
2 3/10
[58.41
176,21 VENT
-_3
[76.2|
/ AIR INTAKE
,;hI 3/4
/ 'CONN
[76.2] VENT
[22.2] POWER CONN
1413/16
[376.3]
169/16 [42O.9]
175/16
[439.2]
FURNACE SIZE
(MODELS)
(59SP5)
040,10 060-14
580,16 100-16
120-22
2O
_4 25
[61
9] [6: 22" /15
[58 .9|
(CABINET WIDTH)
inches mm
14 3/16 361
17112 445
21 533
24 1/2 622
28
[71
,91 1_
28 /8
[_ ,4]
/16
,.1]
A
B
(OUTLET WIDTH)
_nches mm 12 1/2 319
15 7/8 403
19 3/8 492
22 718 581
_A_
_B_
OUTLET WIDTH
AIR FLOW
C
(BO]q-OM INLET WIDTH)
inches mm
12 9/16 322
16 406
19 1/2 495
23 584
® ® 'l
' ® ® ,_i °]_
11/16_4_c__11/16
[17,5] BOTTOM RETURN [17.5]
WIDTH
D SHIPPING
inches mm LBS KG
7 1/8 181 120.9 54.0
83!4 222
10 1/2 267 165.5 74.5
12 1/4 311 169.5 653
[76,2]
AIR INTAKE
116
21
L7]
IZ
2_
_8
;.9]
WEIGHT
141,6 63.4 151,0 67,9
_3
[76.2] I
1 5/16
[_._l
NOTE: ALL DIMENSIONS IN INCH [MM]
291/2 [749,3]
283/4
Fa0,51
26 11116
[678.1 ]
_3/8
[37o.01
;_ 7/16
[670.0]
21 1/16
AIR FLOW
f
\ F_I 3/4 ,' F [44.5]
_" GAS CONN
.,,_ _ _ [22.2]
................._ 7/8
[22.21
THERMOSTAT ENTRY
_' _ 7/8
_i_--i [22.2] POWER CONN
SIDE INLET _q_
233/8
[S_2.0]
265/16
[658,6]
$D_,024 4
I
[2&4]
8
rD
Page 7
LOCATION
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may result in premature furnace component failure. This gas furnace may be used for heating buildings under construction provided
that:
-The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be "hot wired" to provide heat continuously to the structure
without thermostatic control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with
no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
-Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting
according to these installation instructions.
General These furnaces are shipped with the following materials to assist in
proper furnace installation. These materials are shipped in the main blower compartment.
See Table 1 for loose parts bag contents. This furnace must:
be installed so the electrical components are protected from water.
not be installed directly on any combustible material other than wood flooring (refer to SAFETY CONSIDERATIONS).
be located close to the chimney or vent and attached to an air distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown in Table
2 or on the furnace clearance to combustible construction label.
CARBON MONOXIDE POISONING / COMPONENT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install ftlrnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met,
in addition to all local codes and ordinances.
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Laundry rooms
Hobby or craft rooms
Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for
combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return-air duct to
prevent pulling air from the burner area.
FIRE, INJURY OR DEATH HAZARD Failure to follow this warning could result in personal
iniury, death and/or property damage. When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18 in. (457 mm) above the floor. The furnace must be located or
protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must
be installed in accordance with the NFPA 54/ANSI Z223.1-2009 or CAN/CSA B149.2-2010. (See Fig. 5.)
ii
Page 8
ii
Location Relative to Cooling Equipment
FIRE HAZARD Failure to follow this warning could result in personal
iniury, death and/or property damage. Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. (See Fig. 4.)
Table 2 - Minimum Clearances to Combustible Materials for All Units
POSITION CLEARANCE
REAR 0
FRONT (Combustion air openings in furnace and in structure) 1 in. (25 mm)
Required for service *24 in. (610 mm)
All Sides of Supply Plenum 1 in. (25 mm)
Sides 0
Vent 0
Top of Furnace 1 in. (25 mm)
Recommended
The cooling coil nmst be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they nmst be
equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
Page 9
AIRFLOW
THE BLOWER IS LOCATED
TOTHE RIGHT OFTHE
BURNER SECTION, AND
AIR CONDiTiONED AiR iS
DISCHARGED TO THE LEFT.
THE BLOWER iS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDiTiONED AIR IS
DISCHARGED DOWNWARD AIRFLOW
Fig. 2 - Multipoise Orientations
THE BLOWER iS
LOCATED BELOW THE
BURNER SECTION, AND
CONDiTiONED AiR iS
DISCHARGED UPWARD.
AIRFLOW
THE BLOWER iS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDiTiONED AiR IS
DISCHARGED TO THE RIGHT.
A02097
SUPPLYAIR
32° F/0 ° C MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
Fig. 3 - Freeze Protection and Return Air Temperature
FRONT
RETURN
AIR
MAX80 °F / 27°C
MIN60°F / 16°O
A10490
BACK FRONT
Fig. 4 - Prohibited Installations
A10494
18-iN. (457.2 mm) MiNiMUM TO BURNERS
A93044
Fig. 5 - Installation in a Garage
Page 10
il
AIR FOR COMBUSTION AND
VENTILATION
Introduction
Direct Vent (2-pipe) Applications When the furnace is installed as a direct vent (2-pipe) furnace, no
special provisions for air for combustion are required. However, other gas appliances installed in the space with the furnace may
require outside airfor combustion. Follow the guidelines below to insure thatother gas appliances have sufficient air for combustion.
Non-Direct Vent (1-pipe) Applications
When the furnace is installed as a non-direct vent (l-pipe) furnace, it will be necessary to insure there is adequate air for combustion. Other gas appliances installed with the furnace may also require air
for combustion and ventilation in addition to the amount of combustion air and ventilation air required for the furnace. Follow
the guidelines below to insure that the furnace and other gas appliances have sufficient air for combustion.
Ventilated Combustion Air Applications When the furnace is installed using the ventilated combustion air
option, the attic or crawlspace nmst freely communicate with the outdoor to provide sufficient air for combustion. The combustion
air pipe cannot be terminated in attics or crawlspaces that use ventilation fans designed to operate during the heating season. If ventilation fans are present in these areas, the combustion air pipe
nmst terminate outdoors as a Direct Vent/2-Pipe system. All air for combustion is piped directly to the furnace from a space
that is well ventilated with outdoor air (such as an attic or crawl space) and the space is well isolated from the living space or
garage. In addition, other gas appliances installed in the space with the furnace may require outside air for combustion. Follow the
guidelines below to insure that the roof or crawlspace walls have sufficient free area to provide sufficient air for combustion and ventilation for the furnaces. The guidelines below can be used to
insure that other gas appliances have sufficient air for combustion. Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
U.S.A. Installations: Section 9.3 of the NFPA 54/ANSI Z223.1-2009, Air for Combustion and Ventilation and
applicable provisions of the local building codes.
Canada: Part 8 of the CAN/CSA-B149.1-2010, Venting Systems and Air Supply for Appliances.
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage. Air for combustion nmst not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal iniury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of make-up air is availaMe.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of
at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
Spaces having less than 50 cubic feet per 1,000 Btuh (4.8 cubic meters per kW) require the Outdoor Combustion Air Method.
Spaces having at least 50 cubic feet per 1,000 Btuh (4.8 cubic meters per kW) may use the Indoor Combustion Air,
Standard or Known Air Infiltration Method.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent hori-
zontal or vertical duct(s) or opening(s) directly communicat- ing with the outdoors or spaces that freely communicate
with the outdoors.
2. Fig. 6 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and vent-
ilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 ram)
of the ceiling and the second opening MUST commence within 12 in. (300 ram) of the floor.
b. Size openings and ducts per Fig. 6 and TaMe 3.
c. TWO HORIZONTAL DUCTS require I sq. in. (645 sq.
ram) of free area per 2,000 Btuh (1,100 mm2/kW) of com- bined input for all gas appliances in the space per Fig. 6and
Table 3.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq. in. (645 sq. ram) of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 6 and Table 3.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. ram) of free area per 3,000 Btuh (734
mm2/kW) for combined input of all gas appliances in the space per Fig. 6 and Table 3.
b. Not less than the sum of the areas of all vent connectors in
the space.
The opening shall commence within 12 in. (300 ram) of the ceiling. Appliances in the space shall have clearances of at least 1
in. (25 ram) from the sides and back and 6 in. (150 ram) from the front. The opening shall directly communicate with the outdoors or
shall conmmnicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the
outdoors.
10
Page 11
Indoor Combustion Air© NFPA & AGA Standard and Known-Air-Infiltration Rate Methods
Indoor air is pernfitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Method is used.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal iniury or death.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
Standard Method
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances
installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of
ACH and shall be deternfined per Table 4 or Equations 1 and 2. Deternfine the minimum required volume for each appliance in the
space and add the volumes together to get the total minimum required volume I\_r the space.
Table 4 - Minimum Space Volumes were deternfined by using the following equations from the current edition of the National Fuel
Gas Code ANSI Z223.1/NFPA 54, 9.3.2.2:
1. For other than fan-assisted appliances, such as a draft hood-equipped water heater:
Volume _ 21ft3 ("- !other __
Other ACH _000 Btu/hrJ
A04002
2. For fan-assisted appliances such as this furnace:
of the floor. The minimum dimension of air openings shall be at least 3 in. (80 ram). (See Fig. 7.)
c. Combining space on different floor levels. The volumes of
spaces on different floor levels shall be considered as com- municating spaces if connected by one or more permanent
openings in doors or floors having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of
all gas appliances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are ad-
equate permanent ventilation openings directly to outdoors having free area of at least 1-in.2/4,000 Btuh of total input
rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, in- filtration should be adequate to provide air for combustion,
permanent ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air
MUST be provided using the methods described in the Outdoor Combustion Air Method section.
4. Unusually tight construction is defined as Construction
with:
a. Walls and ceilings exposed to the outdoors have a continu-
ous, sealed vapor barrier. Openings are gasketed or sealed
and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels,
at penetrations for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combus-
tion Air Method below and,
2. Outdoor openings shall be located as required in the Out- door Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided by
required volume for Indoor Combustion Air Method be- low.
b. Outdoor opening size reduction Factor is I nfinus the Ra-
tio in a. above.
c. Minimum size of Outdoor openings shall be the size re-
quired in Outdoor Combustion Air Method above multi- plied by reduction Factor in b. above. The minimum di- mension of air openings shall be not less than 3 in. (80 ram).
ii
Volume _ 15ft 3 ("_ I _ _'_
Fan ACH _000" Btu/hr/
If: Iother = combined input of all other than fan-assisted appliances in Btuh/hr
Ifan = combined input of all fan-assisted appliances in Btuh/hr ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening shall
have free area of at least I in.2/1,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances in the space,
but not less than 100 in. 2 (0.06 m2). One opening shall commence within 12 in. (300 ram) of the ceiling and the
second opening shall commence within 12 in. (300 ram)
J
A04003
11
Page 12
Table3 - Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR
FURNACE (1,100 SQ, MM/KW) (734 SQ, MM/KW) (1 SQ, IN,/4,000 BTUH)
INPUT (550 SQ, MM/KW) (BTUH) Free Area of Free Area of Free Area of
40,000* 20 (12904) 5 (127) 14 (8696) 5 (127) 10 (6452) 4 (102)
80,000 30 (19355) 6 (152) 20 (13043) 5 (127) 15 (9678) 5 (127) 80,000 40 (25807) 7 (178) 27 (17391) 6 (152) 20 (12904) 5 (127)
100,000 50 (32258) 8 (203) 34 (21739) 7 (178) 25 (16130) 6 (152) 120,000 60 (38709) 9 (229) 40 (26087) 7 (178) 30 (19355) 6 (152)
140,000" 70 (45161) 10 (254) 47 (30435) 8 (203) 35 (22581) 7 (178)
*Not all families have these models.
100,000 + 30,000 =
60,000 + 40,000 =
I FURNACE WATER HEATER
80,000 + 30,000 =
Table 4 - Minimum Space Volumes for 100 % Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE) (1,000'S BTUH GAS INPUT RATE)
30 40 50 40 80 80 100 120 140
ACH Space Volume Ft3 (M 3)
0.80 (29.7) (39.6) (49.5) (39.6) (42.5) (56.6) (70.8) (84.9) (99.1)
0.50 (35.6) (47.5) (59.4) (47.5) (51.0) (67.9) (84.9) (101.9) (118.9)
0.40 (44.5) (59.4) (74.3) (59.4) (63.7) (84.9) (106.1 ) (127.3) (148.6)
0.30 (59.4) (79.2) (99.1) (79.2) (84.9) (113.2) (141.5) (169.8) (198.1)
0.20 (89.1) (118.9) (148.6) (118.9) (127.3) (169.8) (212.2) (254.6) (297.1)
O.10 (178. O) (237.8) (297.3) (237.8) (254.6) (339.5) (424.4) (509.2) (594.1)
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
1,050 1,400 1,750 1,400 1,500 2,000 2,500 3,000 3,500
1,260 1,680 2,1 O0 1,680 1,800 2,400 3,000 3,600 4,200
1,575 2,1 O0 2,625 2,1 O0 2,250 3,000 3,750 4,500 5,250
2,1 O0 2,800 3,500 2,800 3,000 4,000 5,000 6,000 7,000
3,150 4,200 5,250 4,200 4,500 6,000 7,500 9,000 10,500
6,300 8,400 10,500 8,400 9,000 12,000 15,000 18,000 21,000
(1 SQ, IN,/2,000 BTUH) (1 SQ, IN,/3,000 BTUH) VERTICAL DUCTS
Opening and Round Duct Opening and Round Duct Opening and Round Duct
Duct In, (mm) Dia Duct In, (mm) Dia Duct In, (mm) Dia,
Sq, In (Sq, mm) Sq, In (Sq, mm) Sq, In (mm)
EXAMPLES: Determining Free Area
TOTAL INPUT
(130,000 divided by 4,000) = 32.5 Sq. In. for each two Vertical Ducts or Openings (100,000 divided by 3,000) = 33.3 Sq. In. for each Single Duct or Opening
(110,000 divided by 2,000) = 55.0 Sq. In. for each two Horizontal Ducts
12
Page 13
DUCTS PER 4000
-- 1 SQIN.
OUTDOORSI "%,>G_
I I [i i
1 1
(305mm) 12"MAX] J I I D II 1-_
1sa,a &/ I _ IMEaT lJ_
PER2000 "/ :IB I _ _ I THROUGH FI:_ B1VH* ! I <;_ I ROOF F:_. _.._,.,.
" //I I& IIPE
_a i bu
// rQ II
DUCTS II o
u;°oRs// II
1SQN /J I _ _ = _M ,
PER20004,/IAI _ _ 7- i:::_--
BTUH* _/ :O 7-
......, @ O
// II so
PE "
// II 40 0.
! -J Ii I I BTL
[ 12
A i i i i 12"MAX/
" I ( 05mm)"
?
(305mm)
(305mm)
CIRCULATING AIR
!
I
I
I
DUCTS
I ['1
I I I I
I I II
I
INTERIOR
HEATED
SPACE
I I I
VENT THROUGH ROOF
_: 12" AX(305mm)
0
-_- 1 SQ IN. PER 1000
BTUH* IN DOOR
OR WALL
UNCONFINED SPACE
6" MIN (152mm) (FRONT)0
1 SQ IN. PER 1000
BTUH* IN DOOR
-- OR WALL
12" MAX (305mm)
il
J TO PER 4000
OUTDOORS BTUFF
*Minimum dimensions of 3-in. (76 mm).
NOTE: Use any of the following combinations of openings:
A&BC&DD&EF&G
Fig. 6 - Air for Combustion, Ventilation, and Dilution for
Outdoors
A03174
CONDENSATE TRAP
Condensate Trap - Upflow Orientation When the furnace is installed in the upflow position, it is not
necessary to relocate the condensate trap or associated tubing. Refer to Fig. 8 for upflow condensate trap information. Refer to
Condensate Drain section for information how to install the condensate drain.
Condensate Trap - Downflow Orientation.
When the furnace is installed in the downflow position, the factory-installed trap will be located at the upper left corner of the
collector box. When the furnace is installed in the downflow orientation, the factory-installed trap must be relocated for proper
condensate drainage. To Relocate the Condensate Trap:
Orient the furnace in the downflow position.
Fig. 9 shows the condensate trap and tubing before and after relocation.
Remove the relief tube from the condensate trap.
Remove the screw that secures the condensate trap to the collector box.
Remove the trap.
Remove the relief tube from the port on the collector box. It is not necessary to remove the tube from the inducer assembly.
Remove the pressure switch tube from the front pressure switch and discard the tube. A new pressure switch tube is shipped in the loose parts bag.
Loosen the clamp around the inlet of the vent elbow on the inducer.
Remove the nfiddle and bottom plugs from the lower right side of the collector box and set aside. Do Not Discard Plugs.
CIRCULATING AIR DUCTS
l'
* Minimum opening size is 100 sq, in. (64516 sq, mm) with minimum dimensions
of 3 in. (76 mm)
1-Minimum of 3 in. (76 mm) when type-B1 vent is used.
Fig. 7 - Air for Combustion, Ventilation, and Dilution from
Indoors
Refer to the appropriate figure to begin the trap conversion.
Install the 2 plugs previously removed from the collector box in the ports where the condensate trap was removed.
Install the trap over the ports on the lower right side of the collector box.
Secure the trap to the collector box with the screw.
Connect the relief tube to the condensate trap to the relief port of the condensate trap.
If necessary, slide the relief tube in the inducer stand-offs to adjust the position of the tube.
Connect the relief tube to the relief port of the condensate trap.
Connect the new pressure switch tube to the port on the front pressure switch. Route the tube through the stand-offs on the inducer assembly and connect to the port on the collector box. Trim off any excess tube to avoid sags or kinks in the tube.
Rotate the vent elbow to the desired position and tighten the clamp 15 in.-lbs.
Refer to Condensate Drain section for information how to install the condensate drain.
A03175
Condensate Trap - Horizontal Orientation.
When the furnace is installed in the horizontal right position, the factory-installed trap will be located at the bottom of the collector
box. When the furnace is installed in the horizontal left position, the factory-installed trap will be located at the top of the collector
box. The trap must be repositioned on the collector box for proper condensate drainage.
When the furnace is installed as a direct-vent furnace, a field supplied, accessory Horizontal Installation Kit is required for all
horizontal installations. The kit contains a rubber Casing Grommet designed to seal between the furnace casing and the condensate
trap. (See Fig. 17).
13
Page 14
NOTE: The condensate trap extends below the side of the casing in the horizontal position. A minimum of 2 in. (51 mm) of
clearance is required between the casing side and the furnace platform for the trap to extend out of the casing in the horizontal position.
To Relocate the Condensate Trap:
Remove the knockout in the casing for the Casing Grommet.
Install the grommet in the casing.
Orient the furnace in the desired position.
Allow for 2 in. (51 mm) of clearance underneath the furnace for the condensate trap and drain line.
Fig. 10 shows the condensate trap and tubing before and after relocation in the horizontal right position.
Fig. 11 shows the condensate trap and tubing before and after relocation in the horizontal left position.
Refer to the appropriate figure to begin the trap conversion.
Remove the relief tube from the condensate trap.
ii
Remove the screw that secures the condensate trap to the collector box.
Remove the trap.
Remove the relief tube from the port on the collector box. It is not necessary to remove the tube from the inducer assembly.
For Horizontal Left only:
Remove the pressure switch robe from the front pressure switch and discard the tube. A new pressure switch tube is shipped in the loose parts bag.
For Horizontal Right only:
The pressure switch tube location is not modified.
Loosen the clamp around the inlet of the vent elbow on the
inducer.
Remove the plugs from the collector box and set aside. Do Not Discard Plugs.
For Horizontal Left only:
Remove the middle and right plug from the ports at the bottom of the collector box.
For Horizontal Right only:
Remove the plug to the right of the condensate trap.
Refer to the appropriate figure to begin the trap conversion,
Install the plugs previously removed from the collector box in the ports where the condensate trap was removed.
Install the trap over the ports on the lower side of the collector
box.
Secure the trap to the collector box with the screw.
Connect the relief tube to the condensate trap to the relief port of the condensate trap.
If necessary, slide the relief tube in the inducer stand-offs to adjust the position of the tube.
Connect the relief tube to the relief port of the condensate trap,
For Horizontal Left only:
Connect the new pressure switch tube to the port on the front pressure switch. Route the tube through the stand-offs on the inducer assembly and connect to the port on the collector box. Trim off any excess tube to avoid sags or kinks in the tube.
Rotate the vent elbow to the desired position and tighten the clamp 15 in.-lbs.
Refer to Condensate Drain section for information how to install the condensate drain,
Collector Box
Plugs
Condensate Trap
Relief Port
Vent Pipe Clamp
Pressure Switch
Port
UPFLOW TRAP CONFIGURATION
1 & 2 Stage Units
Fig. 8 - Upflow Trap Configuration
Elbow Clamp
Elbow
Collector Box
Plug
Condensate Trap
Relief Port
Outlet
Al1307
14
Page 15
Remove pressure switch tube from
front pressure switch and discard.
Remove relief tube from relief port on collector trap.
Remove trap from collector box.
Loosen clamp on inlet to vent elbow.
Unconverted Factory Configuration
As Viewed in the Downflow Orientation
(1 and 2 Stage Units)
,'_ Remove tube from relief port.
ii
Remove middle and bottom plugs. DO NOT DISCARD.
(_) Install plugs in
(_ Connect relief tube
open ports on
collector box.
to port on collector
box.
desired position and
Rotate elbow to
tighten clamp to
15 lb.-in.
(_ Slide tube in stand-offs
to adjust length.
Connect tube from Loose Parts bag to port on front pressure switch.
(1 and 2 Stage Units)
Route tube through inducer stand-offs.
Trim excess tube. Connect pressure switch tube to port on collector
box.
Attach condensate trap with screw to collector box.
Connect relief tube to relief port on condensate
trap.
Align condensate trap over middle and bottom
ports of collector box.
Downflow Trap Configuration
Fig. 9 - Downflow Trap Configuration
15
Al1280
Page 16
Remove plug from
collector box.
DO NOT DISCARD.
If alternate vent position is required, loosen clamp
on inlet of vent elbow.
ii
©
(1 AND 2 STAGE UNITS)
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Right Orientation
Slide relief tube in stand-offs to adjust length.
Remove trap from
collector box.
trap with screw to
Attach condensate
collector box.
open port on
(_ nstall plug in
collector box. (1 AND 2 STAGE UNITS)
Vent elbow shown in alternate orientation. Tighten clamp on
inlet to vent elbow 15 lb.-in.
Align trap over middle and
right-hand post on collector box.
Horizontal Right Trap Configuration
Al1402
Fig. 10 - Horizontal Right Trap Configuration
ld
Page 17
If alternate vent position is required, loosen clamp
on vent elbow inlet.
from port on collector
(_) emove relief tube
box.
Remove trap from collector box.
Remove relief tube from relief port on condensate
trap.
Remove front pressure
switch tube and discard.
ii
Remove middle and right plug from collector box.
(1 AND 2 STAGE UNITS)
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Left Orientation
(_ otate elbow to
desired position and torque clamp
on inlet 15 lb.-in.
(_ Slide relief tube instand-offs to adjust
length.
(_ ttach condensatetrap with screw to
collector box.
(_ Align trap over middleand right-hand port on
collector box.
(1 AND 2 STAGE UNITS)
Install plug in open
ports on collector box.
Connect relief tube to port on collector box.
Connect tube from Loose Parts bag to port on front
pressure switch.
Route pressure switch tube underneath relief tube and
connect to port on collector box.
Connect relief tube to relief port on condensate trap.
Horizontal Left Trap Configuration
Fig. ll - Horizontal Left Configuration
17
Al1282
Page 18
ii
CONDENSATE DRAIN CONNECTION
Upflow/Downflow Orientation In the Upflow or Downflow orientation, the condensate trap is
inside the furnace casing. The condensate drain must be routed from the trap through the furnace casing. The condensate drain can
be routed through the left or right side of the casing. (The left or right side is as you are viewing the furnace.) The furnace
condensate drain can be connected to the Air Conditioning condensate drain as shown in Fig. 13.
NOTE: On narrower casings, it may be easier to remove the condensate trap, connect the drain line components and re-install the condensate trap. Read the steps thoroughly to familiarize yourself with the required steps.
For Right Side Condensate Drain:
1. Remove the 7/8-in. knock-out from the right side of the casing. (See Fig. 12 .)
2. Remove the pre-formed drain tube and two spring clamps from the loose parts bag.
3. Slide a spring clamp 1 in. (25 mm) down the plain end of the drain tube.
4. From inside the casing, insert the formed grommet end of the tube through the 7/8-in. knockout in the casing.
5. Pull the tube through the casing from the outside until it is seated in the knockout
6. Attach the plain end of the drain tube to the outlet stub on the drain trap. Secure the drain tube to the trap with the
spring clamp.
7. Slide a spring clamp over the open end of the drain tube outside the casing.
8. Open the spring clamp and connect a field-supplied 1/2-in. CPVC street elbow to the open end of the drain tube. (See
Fig. 14.)
9. Connect additional 1/2-in. CPVC piping to a condensate pump approved for use with acidic furnace condensate or to
a code-approved drain.
For Left Side Condensate Drain Connection:
1. For left side condensate drainage, the drain line is routed from the condensate trap, behind the inducer and out
through the left side of the casing. A pre-formed "Z" pipe is provided in the loose parts bag shipped with the furnace.
The "Z" pipe is long enough to extend out of the casing on the 14 3/16-in. (360 mm) wide furnace. Larger casings will
require a field supplied CPVC pipe and to extend the drain line out of the furnace.
2. The "Z" pipe is connected to the condensate trap by modifying the formed rubber drain tube. Connect the drain line as shown below:
3. Remove the knock-out from the left side of the casing. (See Fig. 12.)
4. Install the grommet for the l/2-in. CPVC drain line in the 7/8-in. knockout in the casing.
5. Remove the pre-formed drain tube, the offset l/2-in. CPVC pipe and two spring clamps from the loose parts bag.
6. Remove the formed grommet on the tube by cutting the tube along the vertical line located about 1 in. (25 mm)
away from the formed grommet.(See Fig. 15.)
7. Slide a spring clamp 1 in. (25 mm) down the plain end of the drain tube.
8. With the bend in the tube oriented horizontally and plain end of the tube pointing away from you, insert the l/2-in.
CPVC pipe into the other end of the drain tube. Rotate the tube so the offset in the tube points away from you. Slide a
spring clamp over the open end of the l/2-in. CPVC tube
and secure the cut end of drain tube to the pipe. (See Fig.
16)
9. Prime the bare end of the pipe with CPVC primer.
10. Route the offset pipe behind the inducer assembly and
through the grommet in the casing, if the "Z" pipe is long enough. If the "Z" pipe is not long enough, continue with
installation.
11. Attach the plain end of the drain tube to the outlet stub on the drain trap. Secure the drain tube to the trap with the
spring clamp.
12. If the "Z" pipe does not extend through the casing, slide a
piece of field supplied CPVC through the grommet in the casing, otherwise, go to Step 17.
13. Cement a 1/2-in. CPVC coupling to the end of the CPVC pipe.
14. Apply cement to the end of the "Z" pipe connected to the condensate trap.
15. Connect the field-supplied CPVC pipe to the CPVC pipe connected to the condensate trap.
16. Cut off excess CPVC pipe outside the casing.
17. Connect additional 1/2-in. CPVC piping to a condensate pump approved for use with acidic furnace condensate or to
a code-approved drain.
18. When a condensate pump is not used, slope the pipe away from the furnace to allow for proper drainage.
Horizontal Orientation
1. In the Horizontal orientation, a field supplied accessory drain trap grommet is required to seal the gap between the
casing and the condensate trap. The condensate trap outlet extends 2 in. (51 mm) below the furnace casing. To allow
for servicing the trap, the condensate drain tube in the loose parts bag can be modified to make a coupler to allow for
future service of the condensate trap and drain line.
2. Remove the knock-out for the condensate trap in the side of the casing.
3. Install the drain trap grommet in the casing. If necessary, remove the trap, install the grommet and re-install the trap.
4. Remove the pre-formed drain tube, the offset l/2-in. CPVC pipe and two spring clamps from the loose parts bag.
5. Remove the formed grommet on the tube to create an elbow or straight connector. (See Fig. 15.)
6. Connect the cut tube to the outlet of the condensate trap with 1 spring clamp.
7. Slide the other spring clamp down the plain end of the drain tube.
8. Connect additional l/2-in. CPVC piping to the open end of the tube.
9. Slide the spring clamp down over the l/2-in. CPVC pipe
10. Connect additional l/2-in. CPVC piping to a condensate pump approved for use with acidic furnace condensate or to a code-approved drain.
11. When a condensate pump is not used, slope the pipe away from the furnace to allow for proper drainage.
18
Page 19
INSTALL CLAMPS ON DRAIN TUBE ATTACH DRAIN TUBE TO CONDENSATF---- 7
DRAIN TRAP
PULL DRAIN STUB
THROUGH CASING
/
/
/
/
,/
/
0
¢
CUT HAZARD Failure to follow this caution may result in personal iniury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Fig. 12 - Knockout Removal
OPENSTAND PIPEFOR
A/COR
HUMIDIFIER DRAIN
Al1305
OPEN SPRING CLAMP
INSERT FIELD - SUPPLIED
1/2'" CPVC DRAIN PIPE * CLAMP MAY BE LOCATED ON OUTSIDE OF DRAIN TUBE
RIGHT SIDE DRAIN INSTALLATION
Fig. 14 - Formed 1hhe Grommet
Cut and remove formed end of drain tube for left side and horizontal
drain connection
\
\
\
il
Al1342
U
_'='_TE E
TO OPEN
DRAIN
"-I
Fig. 13 - Example of Field Drain Attachment
RIGHT SIDE DRAIN ELBOW
Al1388
Fig. 15 - Modify Drain 1hbe
Al1276
19
Page 20
ii
Attach tube to condensate trap
Cut formed end off \
condensate drain tube \
Field supplied 1/2"CPVC Connect short end _ _]_
_7UlPl_l,_g2t,drnainexten,sion of"Z"pipetomodified\_ \" i_
TRAP, DRA_N ELBOW WiTH D_SCHARGE P_PE
Modified drain tube connect to condensate trap and"Z" pipe
Field supplied 1/2"
CPVC to drain
ommet from
loose parts bag
LEFT SIDE DRAIN ROUTED BEHIND INDUCER
Field-supplied 1/2"CPVC coupling & drain pipe 17 1/2'; 21"and 24 1/2"casings
\
\
A11344
Fig. 16 - Drain Trap Connection and Routing
trap
Horizontal Drain Trap Grommet
Al1348
Fig. 17 - Horizontal Drain Trap Grommet
INSTALLATION
Upflow Installation NOTE: The furnace nmst be pitched forward as shown in Fig. 23
for proper condensate drainage. Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Connect supply-air duct to flanges on furnace supply-air outlet. Bend flange upward to 90 ° with wide duct pliers. (See Fig. 20.)
The supply-air duct must be connected to ONLY the furnace supply-outlet-air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach supply air duct, hunfidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
Return Air Connections
FIRE HAZARD A failure to follow this warning could cause personal iniury,
death and/or property damage. Never connect return-air ducts to the back of the furnace.
Follow instructions below.
The return-air duct nmst be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing. Bypass hunfidifier may be attached into unused return air
side of the furnace casing. (See Fig. 24, 25, 26.) Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom plate. (See Fig. 22.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. This panel MUST be in place when
only side return air is used. NOTE: Side return-air openings can be used in UPFLOW and some HORIZONTAL configurations. Do not use side return-air
openings in DOWNFLOW configuration. (See Fig. 24, 25, 26.) Leveling Legs (If Desired) In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 21.) Install field-supplied, 5/16 x 1-1/2 in. (8 x 38 ram) (max) corrosion-resistant machine bolts, washers and nuts.
NOTE: Bottom closure nmst be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each
bottom corner of furnace.
2. For each leg, install nut on bolt and then install bolt with nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten in- side nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
Downflow Installation
NOTE: The furnace nmst be pitched forward as shown in Fig. 23 for proper condensate drainage.
Supply Air Connections
NOTE: For downflow @plications, this furnace is @proved for use on combustible flooring when any one of the following 3
accessories are used:
Special Base, KGASB
Cased Coil Assembly Part No. CNPV, CNRV, CAP, or CAR
Coil Box Part No. KCAKC
1. Deternfine application being installed from Table 6.
2. Construct hole in floor per Table 6 and Fig. 19.
2O
Page 21
3.ConstructplenumtodimensionsspecifiedinTable6 and Fig.19.
4.Installspecialbasecoilassemblyorcoilboxasshowninin Fig.19.
NOTE:It isrecommendedthattheperforatedsupply-airduct fangesbecompletelyremovedfromfurnacewheninstallingthe furnaceonafactory-suppliedcasedcoilorcoilbox.Toremovethe supply-airductflange,usewideductpliersorhandseamersto
bendflangebackandforthuntilitbreaksoff.Becarefulofsharp edges.(SeeFig.20.)
FIRE,EXPLOSION,ANDCARBONMONOXIDE POISONINGHAZARD
Failuretofollowthiswarningcouldresultinpersonal injury,death,orpropertydamage.
Donotinstallthefurnaceonitsbackorhangfurnacewith controlcompartmentfacingdownward.Safetycontrol operationwill be adverselyaffected.Neverconnect
return-airductstothebackofthefurnace.
CUTHAZARD Failureto follow this caution may result in personal iniury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
Connect supply-air duct to supply-air outlet on furnace. Bend flange inward past 90 ° with wide duct pliers (See Fig. 20.) The
supply-air duct nmst be connected to ONLY the furnace supply outlet or air conditioning coil casing (when used). When installed
on combustible material, supply-air duct must be connected to ONLY the factory-approved accessory subbase, or a
factory-approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, hunfidifier, or other
accessories. All accessories MUST be connected to duct external to furnace casing. Return Air Connections
FIRE HAZARD A failure to follow this warning could cause personal injury,
death and/or property damage. Never connect return-air ducts to the back of the furnace.
Follow instructions below.
The return-air duct nmst be connected to return-air opening (bottom inlet). DO NOT cut into casing sides (left or right).
Bypass hunfidifier connections should be made at ductwork or coil casing sides exterior to furnace. (See Fig. 25.)
Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform
the following:
1. Tilt or raise furnace and remove 4 screws holding bottom plate. (See Fig. 22.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Horizontal Installation
for proper condensate drainage.
The furnace can be installed horizontally in an attic or crawlspace on either the left-hand (LH) or right-hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a non-combustible platform, blocks, bricks or pad.
Platform Furnace Support
Construct working platform at location where all required furnace
clearances are met. (See Table 2 and Fig. 27.) For furnaces with
non-combustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists,
the ground underneath furnace must be level and the furnace set on blocks or bricks.
Suspended Furnace Support
The furnace must be supported under the entire length of the furnace with threaded rod and angle iron. (See Fig. 28.) Secure
angle iron to bottom of furnace as shown.
Roll-Out Protection Provide a minimum 12-in. x 22-in. (305 x 559 ram) piece of sheet
metal for flame roll-out protection in front of burner area for furnaces closer than 12-in. (305 ram) above the combustible deck or suspended furnaces closer than 12-in. (305 ram) to joists. The
sheet metal MUST extend underneath the furnace casing by 1-in. (25 ram) with the door removed.
The bottom closure panel on furnaces of widths 17-1/2-in. (445 ram) and larger may be used for flame roll-out protection when bottom of furnace is used for return air connection. See Fig. 27 for
proper orientation of roll-out shield.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Connect supply-air duct to flanges on furnace supply-air outlet.
Bend flange upward to 90 ° with wide duct pliers. (See Fig. 20.) The supply-air duct must be connected to ONLY the furnace supply-outlet-air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing. Return Air Connections
The return-air duct must be connected to bottom of the furnace. The side of casing that faces downward may also be used for return
air connection. A combination of the bottom and downward
facing side may also be used. The side of the casing cannot be used as a return air connection. Bypass humidifier may be attached
into unused return air side of the furnace casing. (See Fig. 26.) Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel, perform the following:
21
ii
Page 22
il
1. Tilt or raise furnace and remove 4 screws holding bottom plate. (See Fig. 22.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when side return air inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections (See Fig. 26.)
Filter Arrangement
FIRE, CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in fire, personal injury or death.
Never operate a furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration
device access doors removed.
FOR FURNACES SHIPPED WITH A
MEDIA CABINET
There are no provisions for an internal filter rack in these furnaces. An external filter is required.
The furnace is shipped with a factory-supplied Media Filter
Cabinet. The Media Filter Cabinet uses either a standard I-in. (25
ram) filter or 4-in. (102 ram) wide Media Filter which can be purchased separately. A field supplied accessory air cleaner may
also be used in place of the media cabinet.
The Media Cabinet is sized for bottom return applications for use in upflow, downflow and horizontal applications. A 16-in. (406
ram) Media Cabinet is shipped with the 14-3/16-in. (360 ram) furnace and includes block-off plates
For upflow side return applications, the Media Cabinet (or field supplied accessory air cleaner) can be installed on the side of the
furnace or side and bottom when a bottom plenum is used. (See Fig. 18 and 24.)
For downflow applications, the Media Cabinet (or field supplied
accessory air cleaner) nmst only be connected to the bottom
opening on the furnace. See Fig. 18 and 25. For horizontal applications, the Media Cabinet (or field supplied
accessory air cleaner) for all models can be connected to the bottom opening on the furnace. For side return use in the horizontal position, refer to Fig. 26. If both side and bottom
openings are used in Fig. 26, each opening used will require a filter.
The media cabinet (or field supplied accessory air cleaner) can also be installed in the common return duct prior to entering the return
air opening in any orientation. Refer to the instructions supplied with Media Cabinet or accessory
air filter for assembly and other details.
See Table 5 for filter size details.
Table 5 - Filter Size Information - In. (mm)
FURNACE CASING WIDTH FILTER TYPE
14-3/161- (360) (406 x 635 x 19) (356 x 635 x 19)
17-1/2 (445) (406 x 665 x 19) (406 x 665 x 19)
21 (566) (406 x 635 x 19) (508 x 635 x 19)
24-1/2 (622) (406 x 665 x 19) (610 x 665 x 19)
Recommended to maintain air filter face velocity. See Product Data for part number. Not all families have these models.
FILTER CABINET HEIGHT - IN (MM) FILTER SIZE - IN (MM) FILTER TYPE
16 (406) (1) 16 x 25 x 4-5/16
20 (508) (1) 20 x 25 x 4-5/16
24 (610) (1) 24 x 25 x 4-5/16
Filters with a side return-air may have a different filter size. Measure the filter to obtain the correct size. Recommended to maintain air filter face velocity. See Product Data for part number.
SIDE RETURN BOTTOM RETURN
16 x 25 x 6/4 14 x 25 x 6/4 Washable*
16 x 25 x 6/4 16 x 25 x 6/4 Washable*
16 x 25 x 6/4 20 x 25 x 6/4 Washable*
16 x 25 x 6/4 24 x 25 x 6/4 Washable*
Air Filter Located in Filter Cabinet
FILTER SIZE
(1) 16 x 25 x 6/4"
(406 x 665 x 19) or Washable or Media*
(406 x 665 x 110)
(1) 20 x 25 x 6/4"
(508 x 665 x 19) or Washable or Media*
(508 x 665 x 110)
(1) 24 x 25 x 3/4"or
(610 x 665 x 19) or Washable or Media*
(610 x 635 x 110)
22
Page 23
k I V xl
14-3/16 and 17-1/2-in.
Furnace
m
16-in. Media Cabinet /
Media Cabinet Installation
Side Return
V "4
21- or 24-1/2-in.
t?urnace
Up to 5-Ton AC
capacity airflow
21-in. Furnace
4-Ton or less, AC
capacity airflow
_t
t
20-in. Media Cabinet
4-in. Block Off
Plate
Media Cabinet Installation Option for
4-Ton or Less A/C Capacity
21-in. Furnace up to 5-Ton AC
Capacity
20- or 24-in. Media
Cabinet
Bottom Return l lenum
_X
20- or -24-in. Media Cabinet Installation
for Combination Side and Bottom Return
14-3/16-in. Furnace
R
s.... i 4 g
24-1/2-in. Furnace up to 4-Ton AC
Capacity
Transition j
20- or 24-in. Media Cabinet ._..J
20- or -24-in. Media Cabinet Installation
with Angled Transition
14-3/16-in. Furnace
Screwsi _7
is....
!_ _ Filler plates
14-3/16-in. Furnace with Filler Plates, Centered
14-3/16-in. Furnace with Filler Plates, Off-Set to Right
A11437
Fig. 18 - Media Filter
23
Page 24
(OR COIL CASING
WHEN USED)
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
_ COMBUSTIBLE
FLOORING
SUBBASE
SHEET METAL
PLENUM
-- FLOOR -- OPENING
SHEET METAL_
PLENUM
__ FLOOR __
OPENING
Fig. 19 - Installation on Combustible Flooring
FURNACE
Table 6 - Opening Dimensions
CASING
WIDTH
APPLICATION
IN.(mm)
Upflow Applications on Combustible or Noncombustible Floor- 12-11/16 21-5/8 13-5/16 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 12-9/16 19 13-3/16 19-5/8
14-3/161-
(360) Downflow applications on combustible flooring (KGASB sub- 11 - 16/16 19 13- 7/16 20- 5/8
Downflow Applications on Combustible Flooring with CNPV, 12-5/16 19 13-5/16 20
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB (619) (483) (338) (508)
Upflow Applications on Combustible or Noncombustible Floor- 16 21 - 5/8 16- 5/8 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 15- 7/8 19 16-1/2 19- 5/8
17-1/2
(445) Downflow applications on combustible flooring (KGASB sub- 15-1/8 19 16-6/4 20-5/8
Downflow Applications on Combustible Flooring with ON PV, 15-1/2 19 16-1/2 20
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB (394) (483) (419) (508)
Upflow Applications on Combustible or Noncombustible Floor- 19-1/2 21-5/8 20-1/8 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 19-3/8 19 20 19-5/8
21
(533) Downflow applications on combustible flooring (KGASB sub- 18-5/8 19 20-1/4 20-5/8
Downflow Applications on Combustible Flooring with CNPV, 19 19 20 20
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB (483) (483) (508) (508)
Upflow Applications on Combustible or Noncombustible Floor- 26 21 - 1/8 26- 5/8 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 22- 7/8 19 26-1/2 19- 5/8
24-1/2
(622) Downflow applications on Combustible flooring (KGASB su b- 22-1/8 19 26- 6/4 20- 5/8
Downflow Applications on Combustible Flooring with ON PV, 22-1/2 19 26-1/2 20
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB (572) (483) (597) (508)
Not all families h_ve these models.
ing (KGASB subbase not required) (322) (549) (338) (565)
subbase not required) (319) (483) (335) (498)
base required) (284) (483) (341) (600)
subbase not required)
ing (KGASB subbase not required) (406) (549) (422) (565)
subbase not required) (403) (483) (419) (498)
base required) (384) (483) (425) (600)
subbase not required)
ing (KGASB subbase not required) (495) (549) (511) (565)
subbase not required) (492) (483) (508) (498)
base required) (473) (483) (514) (600)
subbase not required)
ing (KGASB subbase not required) (584) (537) (600) (565)
subbase not required) (581) (483) (597) (498)
base required) (562) (483) (603) (600)
subbase not required)
In. (mm)
PLENUM OPENING FLOOR OPENING
A B C D
F
A10491
24
Page 25
DISCHARGE DUCT FLANGE
UPFLOW DOWNFLOW HORIZONTAL
[......
(8mm)
5/
1
(44mm)
120 °_
MIN
YES
\
YES 120°_
'\
YES
YES
YES
YES
MIN
NQ
NQ
Fig. 20 - Duct Flanges
(8mm)
(44mm) 1 3/4"
(44mm) 1
Fig. 21 - Leveling Legs
LEVEL 0-IN. (0 MM) TO 1/2-1N. (13 MM) MAX
__ J
FRONT
BOTTOM CLOSURE PANEL
BOTFOMPLATE
A89014
Al1092
Fig. 22 - Removing Bottom Closure Panel
MIN 1/4-1N. (6 MM) TO 1/2-1N. (13 MM) MAX
/
UPFLOW OR DOWNFLOW
Fig. 23 - Furnace Pitch Requirements
HORIZONTAL
Al1237
25
Page 26
NOT PERMITTED
l 0
d
n_URN
AI_
0
R_-- ANY COMBINATION OF 1,2, OR 3 PERMITTED
_T JRN
AIR
A11036
Fig. 24 - Upflow Return Air Configurations and Restrictions
Al1037
Fig. 25 - Downflow Return Air Configurations
and Restrictions
0
N
HORIZONAL
2d
RETURN AIR RESTRICTIONS
NOTE: RESTRICTION SAME FOR A
HOR[ZONAL LEFT (_ T AIR
Fig. 26 - Horizontal Return Air Configurations and Restrictions
Al1038
Page 27
COMBUSTION - AIR PIPE (SEEVENTING SECTION) \\
A 12-IN. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH A
5 TO 8 FT / 1.5 TO 2.4 M) VENT
\
\
_VENT
MANUAL S SHUTOFF GAS VALVE
TRAP
30 IN. (762 mm)
COIL
CONDENSATE-- TRAP
NOTE: FURNACE SHOWN AS DIRECT VENT APPLICATION. REFER TO THE
VENTING SECTION FOR ALLOWABLE VENT CONFIGURATIONS
Fig. 27 - Working Platform for Attic Installation
ROLLOUT PROTECTION REQUIRED
Install 12"x 22"(305 x 559 mm) sheet metal in front of burner compartment
COMBUSTION-AIR PIPE (SEEVENTING SECTION)
--_ .... VENT
ii
Al1154
ROD
NOTE: EXTEND
,/
IRON OUT FOR COIL
o%o%,o2/
LOCATORS
HEX NUT
& WASHER (4)
REQD. PER ROD
NOTES: 1. A 1 In. (25mm) clearance minimum between
top of furnace and combustible material
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
3. Furnace shown isa direct vent application, Refer to the Venting section for allowable vent
configurations,
Al1155
Fig. 28 - Suspended Furnace Installation
27
Page 28
ii
AIR DUCTS
General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design
Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system
design CFM at the design external static pressure. The furnace airflow rates are provided in Table 7-Air Delivery-CFM (With
Filter). When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the
furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer. NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
Table 7 - Air Delivery - CFM (With Filter)
INPUT RETURN-AIR EXTERNAL STATIC PRESSURE (IN. W,C,)
BTUH SUPPLY SPEED
5(Gry) 1120 1080 1030 980 925 875 820 760 690 630
4(Yel) 880 845 810 780 740 710 680 640 615 570
40000 SIDE/BOTTOM 3(Blu) 695 665 620 575 535 495 455 420 370 280
2(Org) 640 595 540 495 460 420 370 310 260 230 1(Red) 570 525 475 425 385 330 255 220 5(Gry) 1720 1670 1620 1565 1505 1440 1375 1295 1220 1135
4(Yel) 1325 1285 1255 1220 1185 1145 1115 1075 1040 1000
60000 SIDE/BOTTOM 3(Blu) 1010 970 925 875 835 785 745 690 660 620
2(0 rg) 1160 1115 1080 1045 1000 960 920 875 840 785 1(Red) 785 715 655 595 530 490 435 385 340 285
5(Gry) 1810 1770 1720 1665 1610 1540 1475 1400 1315 1235
4(Yel) 1535 1500 1475 1435 1405 1370 1340 1310 1245 1160
80000 SIDE/BOTTOM 3(Blu) 1380 1340 1305 1270 1240 1200 1165 1130 1090 1050
2(Org) 1180 1130 1095 1060 1015 975 935 895 850 800 1(Red) 1100 1045 1010 970 920 885 845 790 745 690 5(Gry) 2040 1970 1885 1795 1720 1635 1540 1450 1360 1230
4(Yel) 1550 1505 1460 1415 1365 1325 1280 1230 1180 1135
100000 SIDE/BOTTOM 3(Blu) 1780 1730 1690 1645 1610 1555 1481 1400 1310 1210
2(0 rg) 1345 1295 1250 1195 1155 1105 1055 1000 955 915 1(Red) 1390 1350 1295 1260 1200 1160 1105 1050 1010 965 5(Gry) 2275 2230 2185 2130 2055 1950 1825 1710 1610 1500
4(Yel) 1875 1820 1770 1720 1660 1600 1550 1505 1450 1390
120000 SIDE/BOTTOM 3(Blu) 2170 2125 2075 2025 1975 1900 1790 1695 1590 1470
2(Org) 1475 1420 1350 1280 1215 1165 1105 1050 995 930 1(Red) 1625 1565 1505 1445 1385 1325 1275 1225 1170 1130
*A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. W.C. available external static pressure.
- Indicates unstable operating conditions.
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is
used, a vapor barrier is recommended. Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36-in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further
requirements.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft. (3 M) of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance
with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork
shall comply with NFPA 90B as tested by UL Standard 181 for
Class 1 Rigid air ducts. NOTE: For horizontal applications, the top most flange may be
bent past 90 ° to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil
are performed.
28
Page 29
GAS PIPING
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal
iniury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal iniury or loss of
life.
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal
injury, death, and/or property damage. Use proper length of pipe to avoid stress on gas control
manifold and gas valve.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve
from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S.A. Refer to
current edition of CAN/CSA B149.1 in Canada. Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace. NOTE: Use a back-up wrench on the inlet of the gas valve when
connecting the gas line to the gas valve. NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
Refer to Table 8 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. (1.8 M). Joint compound (pipe dope) should be applied
sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.
FIRE OR EXPLOSION HAZARD A failure to follow this warning could result in personal
iniury, death, and/or property damage. If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2-in. (51 mm)
outside the furnace.
FURNACE DAMAGE HAZARD Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft. (1.8 M) of furnace.
Install a sediment trap in riser leading to furnace as shown in Fig.
30. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground
joint union between furnace gas control valve and exterior manual equipment gas shutoff valve.
A l/8-in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas
supply connection to furnace and downstream of manual equipment shutoff valve.
Piping should be pressure and leak tested in accordance with the current addition of the NFGC in the United States, local, and
national plumbing and gas codes before the furnace has been connected. Refer to current edition of NSCNGPIC in Canada.
After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
NOTE: The furnace gas control valve inlet pressure tap connection is suitable to use as test gauge connection providing
test pressure DOES NOT exceed maximum 0.5 psig (14-in. w.c.) stated on gas control valve. (See Fig. 51.)
If pressure exceeds 0.5 psig (14-in. w.c.), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than 0.5 psig
(14-in. w.c.), turn off electric shutoff switch located on furnace gas control valve and accessible manual equipment shutoff valve
before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with
the furnace burners ON and OFF.
Some installations require gas entry on right side of furnace (as
viewed in upflow). (See Fig. 29.)
Gas Pipe Grommet
For direct vent (2-pipe) applications, the knockout for the gas pipe must be sealed to prevent air leakage. Remove the knockout, install the grommet in the knockout, then insert the gas pipe. The
grommet is included in the loose parts bag. See Fig. 29.
29
Page 30
g
Table 8 - Maximum Capacity of Pipe
NOMINAL LENGTH OF PIPE - FT (M)
IRON PIPE
SIZE 10 20 30 40 50
IN. (MM) (3.0) (6.0) (9.1) (12.1) (15.2)
1/2 (13) 175 120 97 82 73 3/4 (19) 360 250 200 170 151
1 (25) 680 465 375 320 285
1-1/4 (32) 1400 950 770 660 580 1-1/2 (39) 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. w.c.) or less and a pressure drop of 0.5-in. w.c. (based on a 0.60 specific gravity gas).
Ref: Table 8 above and 6.2 of NFPA54/ANSI Z223.1-2009.
Left Side Gas Entry. Gas Pipe Grommet Required For Direct
Vent Applications.
Gas Pipe Grommet Required For Direct Vent Applications
Field-supplied wiring shall conform with the limitations of 63°F
33 ° C) rise.
ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal
injury, death, or property damage. The cabinet MUST have an uninterrupted or unbroken
ground according to NEC ANSI/NFPA 70-2011 or local codes to minimize personal injury if an electrical fault
should occur. In Canada, refer to Canadian Electrical Code CSA C22.1. This may consist of electrical wire, conduit
approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer's ratings for proper wire gauge. Do not use gas piping as an electrical ground.
MANUAL ,._
SHUTOFF [
VALVE
(REQUIRED)
J
SEDIMENT TRAP
Fig. 30 - Typical Gas Pipe Arrangement
ELECTRICAL CONNECTIONS
Fig. 29 - Gas Entry
/
/
UNION _
NOTE: Union may be inside the vestibule where permitted by
local codes.
FRONT
I
Al1338
Al1035
FURNACE MAY NOT OPERATE HAZARD Failure to follow this caution may result in intermittent
furnace operation. Furnace control must be grounded for proper operation or
else control will lock out. Control nmst remain grounded through green/yellow wire routed to gas valve and manifold
\
bracket screw.
l15-V Wiring
Furnace must have a 115-v power supply properly connected and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control LED status indicator light will flash
rapidly and furnace will NOT operate. Verify that the voltage, frequency, and phase correspond to that
specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 9 for equipment electrical specifications.
U.S.A. Installations: Make all electrical connections in accordance with the current edition of the National Electrical Code (NEC)
ANSI/NFPA 70 and any local codes or ordinances that might
apply. Canada Installations: Make all electrical connections in accordance with the current edition of the Canadian Electrical Code CSA C22.1 and any local codes or ordinances that might apply.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal iniury or death.
Blower door switch opens 115-v power to control. No component operation can occur. Do not bypass or close
switch with blower door removed.
See Fig. 34 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for
tightness.
FIRE HAZARD Failure to follow this warning could result in personal
iniury, death, or property damage. Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. See Fig. 32.
Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 9 for wire size
and fuse specifications. A readily accessible means of electrical
disconnect must be located within sight of the furnace.
3O
Page 31
J-Box Installation
FIRE OR ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal
iniury, death, or property damage. If field-supplied manual disconnect switch is to be mounted
on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components.
The J-Box is used when field line voltage electrical connections are made to the furnace wiring harness inside the furnace casing. The
J-Box is not required if a field-supplied electrical box is attached to the outside of the furnace casing and the box is grounded to the green ground wire of the main wiring harness and the earth ground
of the field electrical supply. The J-Box cover, mounting bracket and screws are shipped in the
loose parts bag included with the furnace. The J-Box can be mounted on the left or right side of the casing, as viewed from the
upflow position. Remove the J-Box cover and mounting bracket from the loose
parts bag. Select a 7/8-in. (22 mm) knock-out on the desired side of the casing. Remove the knock-out from the casing. Drill two (2)
l/8-in. (3 mm) pilot holes in the casing dimples by the desired 7/8-in. (22 mm) knock-out.
Align the J-Box mounting bracket against the inside of the casing and secure the mounting bracket with the screws. (See Fig. 31.)
Electrical Box on Furnace Casing Side NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
1. Fasten a field-supplied external electrical box to the outside of the casing by driving two field-supplied screws from in-
side electrical box into casing. (See Fig. 32.)
2. Route field power wiring into external electrical box.
3. Pull furnace power wires through l/2-in. (12 mm) diameter hole in J-Box. If necessary, loosen power wires from strain-
relief wire-tie on furnace wiring harness.
4. Connect any code required external disconnect(s) to field power wiring.
5. Route external field power wires through holes in electrical box and casing.
6. Connect field ground wire and factory ground wire to green ground screw on J-Box mounting bracket as shown in Fig.
31.
7. Connect field power and neutral leads to furnace power leads as shown in Fig. 34.
8. Attach furnace J-Box cover to mounting bracket with screws supplied in loose parts bag. Do not pinch wires
between cover and bracket.
9. Complete external disconnect wiring and installation. Con- nect line voltage leads as shown in Fig. 32. Use best prac-
tices (NEC in U.S.A. for wire bushings, strain relief, etc., CANADA: Canadian Electrical Code CSA C22.1)
Power Cord Installation in Furnace J-Box NOTE: Power cords must be able to handle the electrical
requirements listed in Table 9. Refer to power cord manufacturer's listings.
1. Install J-Box mounting bracket to inside of furnace casing. (See Fig. 31 .)
2. Route listed power cord through 7/8-in. (22 mm) diameter hole in casing and J-Box bracket.
3. Secure power cord to J-Box bracket with a strain relief bushing or a connector approved for the type of cord used.
4. Pull furnace power wires through l/2-in. (12 mm) diameter
hole in J-Box. If necessary, loosen power wires from strain--relief wire-tie on furnace wiring harness.
5. Connect field ground wire and factory ground wire to green
ground screw on J-Box mounting bracket as shown in Fig.
31.
6. Connect power cord power and neutral leads to furnace power leads as shown in Fig. 34.
7. Attach furnace J-Box cover to mounting bracket with screws supplied in loose parts bag. Do not pinch wires
between cover and bracket. (See Fig. 31).
BX Cable Installation in Furnace J-Box
1. Install J-Box mounting bracket to inside of furnace casing. See Fig. 31.
2. Route BX connector through 7/8-in. (22 mm) diameter hole in casing and J-Box bracket.
3. Secure BX cable to J-Box bracket with connectors ap- proved for the type of cable used.
4. Connect field ground wire and factory ground wire to green ground screw on J-Box mounting bracket as shown in Fig.
31.
5. Connect field power and neutral leads to furnace power leads, as shown in Fig. 34.
6. Attach furnace J-Box cover to mounting bracket with screws supplied in loose parts bag. Do not pinch wires
between cover and bracket.
24-V Wiring
Make field 24-v connections at the 24-v terminal strip. (See Fig.
35.) Connect terminal Y/Y2 as shown in Fig. 34 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat
wire. NOTE: Use AWG No. 18 color-coded copper thermostat wire for
lengths up to 100 ft. (30.5 M). For wire lengths over 100 ft., use AWG No. 16 wire.
The 24-v circuit contains an atttomotive-type, 3-amp. fuse located on the control. Any direct shorts during installation, service, or
maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp. fuse of identical size. See Fig. 35.
Accessories (See Fi_. 33 and 35,)
1. Electronic Air Cleaner (EAC) Connect an accessory Electronic Air Cleaner (if used) using
1/4-in. female quick connect terminals to the two male 1/4-in. quick-connect terminals on the control board
marked EAC-1 and EAC-2. The terminals are rated for II5VAC, 1.0 amps maximum and are energized during
blower motor operation.
2. Humidifier (HUM)
The HUM terminal is a 24 VAC output, energized when the gas valve relay is operating during a call for heat.
Connect an accessory 24 VAC, 0.5 amp. maximum humidifier (if
used) to the ¼-in. male quick-connect HUM terminal and
COM-24V screw terminal on the control board thermostat strip.
NOTE: If the humidifier has its own 24 VAC power supply, an isolation relay may be required. Connect the 24 VAC coil of the isolation relay to the HUM and COM/24V screw terminal on the
control board thermostat strip. (See Fig. 33.)
Alternate Power Supplies
This furnace is designed to operate on utility generated power which has a smooth sinusoidal waveform. If the furnace is to be
operated on a generator or other alternate power supply, the
alternate power supply must produce a smooth sinusoidal
waveform for compatibility with the furnace electronics. The
31
Page 32
alternatepowersupplymustgeneratethe same voltage, phase, and
frequency (Hz) as shown in Table 9 or the furnace rating plate.
Contact the alternate power supply manufacturer for specifications and details,
Power from an alternate power supply that is non-sinusoidal may damage the furnace electronics or cause erratic operation.
Table 9 - Electrical Data
UNIT SIZE
40,000 11.0 60,000 13.0
80,000 13.0 100,000 16.1 120,000 16.1
* Permissible limits of the voltage range at which the unit operates satisfactorily. # Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps. 1"Time-delay type is recommended. _Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
VOLTS- HERTZ-
PHASE
115-60-1 115-60-1
115-60-1 115-60-1 115-60-1
OPERATING VOLTAGE
RANGE*
Maximum* Minimum*
127 104 127 104
127 104 127 104 127 104
MAXIMUM
UNIT
AMPS
6.8
8.4
8.4
10.9
10.9
UNIT
AMPACITY#
MINIMUM MAXIMUM
WIRE WIRE
SIZE LENGTH
AWG FT (M):_
14 33 (10.0) 14 26 (8.5)
14 28 (8.5) 12 35 (10.6) 12 35 (10.6)
GROUND--
MAXIMUM
FUSE OR CKT
BKR
AMPSt
15 15
15 2O 2O
J-BOX LOCATIONS
Fig. 31 - Installing J-Box (When Used)
Al1299
NEUTRAL
ELECTRIC
DISCONNECT
SWITCH
®
Fig. 32 - Field-Supplied Electrical Box on Furnace Casing
Al1146
32
Page 33
I To Hum_dilier Leads
I To Hum_d_fie r Leads
Fig. 33 - Field-supplied Isolation Relay for Humidifiers with Internal Power Supply
NOTE 2
FIVEWIRE_ @_ @_ TERMINALSTHERMOSTAT
THREE-WIRE I I I I II
HEATING_ON Ly _"_ ___ {i I I L
BLOWERDOORSWITCH--&______" '' "--{,'
W HT_ ..... JWHI L_ [ O _ ------1----J II
f_ GND T I __
115-VFIELD- AUXILIARY n _ __1 [ II
SUPPLIED J-BOX _ _ / ] I
DISCONNECT (_ ..... _N_O_T_E_I.... J
24-V
TERMINAL WIRE
BLOCK
FURNACE
Fig. 34 - Typical Single-Stage Wiring Diagram
NOTES: 1.
/
Connect Y-terminal in furnace as shown for proper blower operation.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
To HUMTerminal On I
Furnace Conirol Board
.... FIELD 24-V WIRING
.... FIELD 115-, 208/230-, 460-VWIRING
-- FACTORY 24-VWIRING FACTORY 115-V WIRING
iiiiiiii_iiiiiiiii!iiiii
iiiii,;iit!!iiiY_Y#i?_ii_
I
I
FIELD-SUPPLIED DISCONNECT
208/230- OR 460-V THREE
PHASE
208/230-V
SINGLE PHASE
SiN
"---
Al1157
g
A11387
33
Page 34
1 J
TEST / TWIN
o o BLOWER OFF-DELAY
24-V THERMOSTAT TERMINALS
TWINNING AND/OR
COMPONENT TEST
TERMINAL
ii
HUM
0.5-AMP
@24VAC
[FUSE 3-AM_
SEC-2 SEC-1
OPERATION &
C'eO'_P" LIGHTDIAGNOSTIC
_ r-
OOM
_ .-I!
m
0 []
[] [] []
[] [] [] [] D
[] []
-- (115 VAC 1.0 AMP MAX.)
HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX)
3-AMP FUSE
TRANSFORMER 24VAC CONNECTIONS
PL1 - LOW VOLTAGE MAIN HARNESS CONNECTOR
BLOWER SPEED SELECTION TERMINALS
EAC TERMINAL
= 1
c_l ' '
r _ _ 1_'_ CONNECTIONS
F---'I | [ r-"m,,_-INPUT
115-VAC (L2) EAC-1
_ NEUTRAL
/ 115 VAC (L1)
L1 BL-1
PL-2 HOT SURFACE IGNITOR (HSI) &
INDUCER MOTOR (IND) CONNECTOR
I I
_ g
PR-1 IND HSl
Fig. 35 - Single Stage Furnace Control
34
Al1391
Page 35
THERMOSTAT SINGLE-STAGE SINGLE-SPEED THERMOSTAT SINGLE-STAGE TWO-SPEED
FURNACE AIR CONDITIONER FURNACE AIR CONDITIONER
N_
N_
HEAT STAGE 1 [_
COOL STAGE 1 [_
FAN [_
24 MAC HOT [_
* DEHUMIDIFY [_
24 VAC COMM [_
HUM ""-
HUMIDIFY
N/A [_
Os_gOoO2_
(24 VAC)
SENSOR
CONNECTONL[_
See notes 2, 5, 7, 10, and 14
Single-Stage Furnace with Single-Speed Air Conditioner
N/A
COOL STAGE 1
HEAT STAGE 1
COOL STAGE 2
FAN [_
24 VAC HOT
* DEHUMIDIFY
24 VAC COMM [_
HUMIDIFY
N/A [_
F_
C_
_HUMDFER_i
°S_N_S°°R_
CONNECT,ONL_
See notes 2, 5, 8, 10, and 14
Single-Stage Furnace with Two-Speed Air Conditioner
HUM
(24 MAC)
OUTDOOR ]_
SENSOR
ii
THERMOSTAT SINGLE-STAGE SINGLE-SPEED
RVS COOLING_
N/A[_
HEAT STAGE 2 [_
(FURNACE)
HEAT/COOL STAGE 1
(COMPRESSOR)
FAN [_
24 VAC HOT [_
* DEHUMIDIFY [_
24 VAC COMM [_
HUMIDIFY [_
N/A
%T_s°°R_[_
FURNACE HEAT PUMP
CK_
HUM
HOM,O,F,ER_ i
(24 VAC)
_ OUTDOOR _z_,
SENSOR
CONNECT,ON_
See notes 1, 2, 4, 6, 7, 9, 10, 12 and 14
THERMOSTAT SINGLE-STAGE TWO-SPEED
RVS COOLING_
HEAT/COOL STAGE 1 _ .................. _ ......
(COMPRESSOR LO)
HEAT STAGE 3 _ ............... _ .....
(FURNACE)
HEAT/COOL STAGE 2 _o NOTE 12
(COMPRESSOR HI) _ ........... _ .....
FAN_ ...........
FURNACE HEAT PUMP
_4"ACHOT_.............._ ........
*OEHUM,D,FY_ I_
_4MACCOMM_............._
HUM "'-. ......
HUMIDIFY
N/A
°s_gs°°2_ .....
/_J HUMIDIFIER [/_ i
..... (24 VAC) - -
!_t OUTDOOR ]_
SENSOR
CONNECT,ON_
See notes 1, 2, 3, 4, 6, 8, 9, 10 12 and 14
Single-Stage Furnace with Single-Speed Heat Pump Single-Stage Furnace with Two-Speed Heat Pump
Fig. 36 - Thermostat Wiring Diagrams
35
A11275
Page 36
NOTES FOR THERMOSTAT WIRING DIAGRAMS
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. If the heat pump date code is 1501E or earlier, select the "ZONE" position on the two speed heat pump control. Heat pumps with date code 1601E and later do not have or require a "ZONE" selection.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Configure the thermostat for air conditioner installations. Refer to thermostat instructions.
6. Configure thermostat for heat pump installations. Refer to thermostat instructions.
7. Configure thermostat for single-stage compressor operation. Refer to thermostat instructions.
8. Configure thermostat for two-stage compressor operation. Refer to thermostat instructions.
9. Configure thermostat for Dual Fuel Operation. Refer to thermostat instructions.
10. NO connection should be made to the furnace HUM terminal when using a thermostat with a 24 volt humidifier output.
11. The RVS Sensing terminal "L" should not be connected. This is used internally to sense defrost operation.
12. If thermostat has internal control of heat pump balance point, DO NOT SELECT the "FURNACE INTERFACE" or "BALANCE
POINT" option on the two-speed heat pump control board. Refer to thermostat instructions.
13. The RVS Sensing terminal "L" should not be connected. This is internally used to sense defrost operation.
14. Configure Dehumidify function to remove 24 VAC from Dehum terminal on a demand to dehumidify.
36
Page 37
VENTING
Furnace is set in place in the required orientation.
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CAN/CSA B149 code. Vent systems must be composed of pipe,
fittings, cements, and primers listed to ULC $636. The special vent fittings and accessot T concentric vent termination kits and
accessot T external drain trap have been certified to ULC $636 for use with those Royal Pipe and IPEX PVC vent components which
have been certified to this standard. In Canada, the primer and cement must be of the same manufacturer as the vent system
GVS-65 Primer (Pm_le) for Royal Pipe or IPEX System 636, PVC/CPVC Primer, Pm_le Violet for Flue Gas Venting and GVS-65 PVC Solvent Cement for Royal Pipe or IPEX System
636(1)t, PVC Cement for Flue Gas Venting, rated Class IIA, 65 deg C. must be used with this venting system - do not mix primers and
cements from one manufacturer with a vent system from a different manufacturer. Follow the manufacturer's instructions in the use of
primer and cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC $636, of the vent system is based on following these installation instructions, the vent system manufacturer's installation instructions, and proper use of primer
and cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard
CAN/CSA B149 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended
that the vent system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority, municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a permit.
*IPEX System 636T'_isa trademark of IPEX Inc.
Consignes sp6ciales pour l'installation de ventilation au Canada
composer de tuyaux, raccords, ciments et appr_ts conformes au ULC $636. La tuyauterie de ventillation des gaz, ses accessoires,
le terminal concentrique mural ainsi que l'ensemble du drain de condensat extdrieur ont _td certifids ULCS 636 pour l'application
des composantes Royal Pipe, IPEX PVC qui sont certifides 5. ce standard. Au Canada, l'appr_t et le ciment doivent _tre du m_me
fabricant que le syst_me d'@acuation. L'appr_t GVS-65 (Purple) et le ciment-solvant GVS-65 doivent _tre utilis6 avec les Royal Pipe.
Syst_me IPEX 636, appr_t PVC/CPVC, Purple pour @acuation des gaz de combustion et syst_me IPEX 636(1)t, ciment PVC pour
@acuation des gaz de combustion, cord classe IIA, 65 deg C. doivent _tre utilis6s avec le syst_me d'@acuation IPEX 636 - Ne
Bien suivre les indications du manufacturier lors de l'utilisation de
l'apprat et du ciment et ne pas utiliser ceux-ci si la date d'expiration est atteinte.
L'opdration sdcuritaire, tel que ddfinit par ULC $636, du systame de ventilation est basd sur les instructions d'installation suivantes,
ainsi que l'usage approprid de l'apprat et ciment. Tout arret feu et solin de toit utilisds avec ce systame doivent atre des matdriaux listds UL. L'acceptation du standard Canadien CAN/CSA B149
est directement relid fi l'installation conforme aux instructions ci- haut mentionndes. Le standard Canadien recommande 1' inspection
par un personel qualifid et ce, une fois par annde.
Les autoritdes ayant juridiction (inspecteurs de gas, inspecteurs en bfitiments, d@artement des incendies, etc) devraient _tre consultdes
avant l'installation afin de d_terminer si un permis est requis.
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas
Code, NFPA 54/ANSI Z223.1-2009 and these instructions. In Canada, refer to CAN/CSA- B149.1-2010. Determine that there is no blockage or
restriction, leakage, corrosion and other defciencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, NFPA
54/ANSI Z223.1-2009. In Canada, refer to CAN/
CSA-BI49.1-2010.
9. After it has been determined that each appliance
connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other
gas-fired burning appliance to their previous conditions of use.
General
If this furnace replaces a furnace that was connected to a vent system or chimney, the vent or vent connectors of other remaining
appliances may need to be re-sized. Vent systems or vent
connectors of other appliances must be sized to the minimum size
as determined using appropriate table found in the current edition of National Fuel Gas Code NFPA 54/ANSI Z-223.1. In Canada, refer to CAN/CSA-BI49.1.
An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion-air (when
applicable) and vent pipes. Each furnace must have its own set of combustion-air and vent pipes and be terminated individually, as
shown in Fig. 47 for Direct Vent (2-Pipe) system or Fig. 48 for ventilated combustion air option.
ii
37
Page 38
ii
A furnace shall not be connected to a chinmey flue serving a separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use the abandoned chinmey as a raceway providing it is permitted by
local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer's installation instructions. Care must
be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.
Do not take combustion air from inside the chinmey when using ventilated combustion air or single pipe vent option.
These furnaces can be vented as either direct vent furnace, ventilated combustion air system or non-direct (single pipe) vent
system. Each type of venting system is described below. Common venting between furnaces or other appliances prohibited.
Materials
U.S.A. Combustion air and vent pipe, fittings, primers, and solvents nmst
conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM)
standards. See Table 11 for approved materials for use in the U.S.A.
Canada
Special Venting Requirements for Installations in Canada Installation in Canada nmst conform to the requirements of
CAN/CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC $636.
Venting Systems
A factory accessory KGAVT vent termination kit nmst be used for all direct vent terminations. Termination kits are available for 2-in.
or 3-in. pipe. See Table 10 for available options.
Table 10 - Vent Termination Kit for Direct Vent (2-pipe)
Systems
DIRECT VENT TERMINATION COMBUSTION AIR
(2- PIPE) SYSTEM AND VENT PIPES
TERMINATION KIT
2-in. (51 mm) Single Penetration 2-1/2
Concentric Vent Kit of Wall or Roof (24, 36, 51,64
3-in. (76 mm) Single Penetration 2-1/2, 6 or 4
Concentric Vent Kit of wall or Roof (64, 76, 102 mm)
2-in. (51 mm) 2-Pipe
Termination Termination 1, 1-1/2 or 2
Bracket Kit System (25, 36, 51 mm)
3-in. (76 mm) 2-Pipe 2-1/2, 6 or 4
Termination Termination
Bracket Kit System (64, 76, 102 mm)
Direct Vent / 2-Pipe System
In a direct-vent (2-pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. Combustion-air and vent pipes nmst terminate together in the same atmospheric pressure zone,
either through the roof or a sidewall (roof termination preferred). A factory accessory vent termination kit MUST be used in a direct
vent (2-pipe) system. See Fig. 45 for required clearances.
Ventilated Combustion Air Systems
In a ventilated combustion air option, the vent terminates and discharges the flue products directly to the outdoors similar to a
direct vent system. See Fig. 46 for required clearances. All air for combustion is piped directly to the furnace from a space
that is well ventilated with outdoor air (such as an attic or crawl space) and the space is well isolated from the living space or garage. Combustion air requirements for this option are the same as the requirements for providing outside air for combustion for a
DIAM. OF
- IN. (mm)
1, 1-1/2, 2, or
mm)
single pipe vent system. Refer to the "Air For Combustion and Ventilation Section.
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S.A. Installations: Section 9.3 NFPA 54/ANSI Z223.1-2009, Air for Combustion and Ventilation and applicable provisions of
the local building codes.
Canadian Installations: Part 8 of CAN/CSA-B149.1-10. Venting
Systems and Air Supply for Appliances and all authorities having jurisdiction.
Non-Direct Vent (1-pipe) System
In a non direct-vent (1-pipe) system, all air for combustion is taken from the area adjacent to furnace, and all flue products are discharged to outdoor atmosphere. Air for combustion nmst be
supplied as described in the Air For Combustion and Ventilation
Section. Do not use an abandoned chinmey to supply outside air to the furnace. See Fig. 46 for required clearances.
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S.A. Installations: Section 9.3 NFPA 54/ANSI Z223.1-2009, Air for Combustion and Ventilation and applicable provisions of the
local building codes.
Canadian Installations: Part 8 of CAN/CSA-B149.1-10. Venting
Systems and Air Supply for Appliances and all authorities having jurisdiction.
A combustion air pipe to the outdoors is not required for a single pipe vent system. A 12-in. (304 ram) long pipe with a 2-in. (51
ram) tight radius 90 degree elbow is required to be attached to the combustion air pipe adapter on the furnace. (See Fig. 44)
Locating the Vent Termination
General NOTE: Termination Requirements for the Provinces of
Alberta and Saskatchewan are located at the end of this section.
Combustion-air (direct vent/2-pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof.
For vent termination clearance, refer to Fig 45 for Direct Vent/2-Pipe system and Fig. 46 for Non-direct Vent/I-Pipe
system. For exterior termination arrangements, refer to Fig. 47 for Direct Vent/2-Pipe system and Fig. 48 for Non- Direct/l-Pipe
system. Roof termination is preferred since it is less susceptible to damage
or contamination, and it has less visible vent vapors. Sidewall terminations require sealing or shielding of building surfaces with a
corrosive resistance material due to corrosive combustion products of vent system.
NOTE: (Direct Vent/2-Pipe system ONLY) A factory accessory termination kit MUST be used.
When determining appropriate location for termination, consider the following guidelines:
1. Comply with all clearance requirements stated in Fig 45 or Fig 46 per application.
2. Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air condi-
tioning equipment.
3. Termination or termination kit should be positioned so that
it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves,
or light snow.
4. Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such
as stones, balls, etc.
38
Page 39
5. Termination or termination kit should be positioned where vent vapors are not objectionable.
Direct Vent / 2-Pipe System Direct vent (2-pipe) vent and combustion air pipes must terminate
outside the structure. Follow all clearances as shown Fig 45.
Allowable vent and combustion airterminations are shown in Fig.
47. Ventilated Combustion Air
The vent pipe for a Ventilated Combustion Air System must terminate outdoors. Follow all vent termination clearances shown
in Fig 46. Allowable vent terminations are shown in Fig 48. The combustion air pipe terminates in a well-ventilated attic or crawl space. Follow the clearances as shown in Fig. 50.
The combustion air pipe cannot terminate in attics or crawl spaces that use ventilation fans designed to operate in the heating season.
If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent System.
Non-Direct Vent / 1-Pipe System
The vent pipe for a Non Direct Vent (I-pipe) system must terminate outdoors. Follow all vent termination clearances shown
in Fig 46. Allowable vent terminations are shown in Fig. 48 A combustion air pipe to the outdoors is not required for a
Non-Direct Vent System. A 12-in. long section of pipe with a tight radius 2-in. (50.8 mm) 90 degree elbow is required to be
attached to the furnace. Termination Requirements for the Provinces of Alberta and
Saskatchewan
The Provinces of Alberta and Saskatchewan require a minimum unobstructed distance of 4 ft. (1.2 M) from the foundation to the
property line of the adjacent lot for vent termination of any appliance with an input over 35,000 btuh. If there is less than 4 ft.
(1.2 M) of unobstructed distance to the property line of the adjacent lot, no type of vent termination is permitted for appliances with inputs greater than 35,000 btuh.
There are no additional restrictions on unobstructed distances greater than 8 ft. (2.4 M). All single, two-pipe and concentric vents
nmy be used, providing all other Code and manufacturer's requirements in these instructions are adhered to. Refer to the
appropriate Vent Termination section above for locating the vent termination
If the unobstructed distance from the foundation to the property line of the adjacent lot is no less than 4 ft. (1.2 M) and no greater
than 8 ft. (2.4 M), it will be necessary to re-direct the flue gas plume. In this situation, a concentric vent kit cannot be used. A
2-pipe termination (or single pipe termination when permitted) that re-directs the flue gas away by use of an elbow or tee, certified to ULC $636 from the adjacent property line must be used. See Fig.
49. The concentric vent kit currently cannot be modified to attach an
elbow to the vent portion of the rain cap. A tee attached to the rain cap could potentially direct the flue gas plume toward the intake air
stream and contaminate the incoming combustion air for the furnace.
Refer to Fig. 49 for terminations approved for use in Alberta and Saskatchewan.
Size the Vent and Combustion Air Pipes General
Furnace combustion air and vent pipe connections are sized for 2-in. (51 mm) pipe. Any pipe diameter change should be made
outside furnace casing in vertical pipe. Any change is diameter to the pipe must be made as close to the furnace as reasonably
possible. The Maximum Vent Length for the vent and combustion air pipe
(when used) is determined from the Maximum Equivalent Vent
Length in Table 13 or 15, minus the number of fittings multiplied by the deduction for each type of fitting used from Table 14.
The measured length of pipe used in a single or 2-pipe termination is included in the total vent length. Include a deduction for a Tee
when used for Alberta and Saskatchewan terminations. Concentric vent terminations, pipe lengths or elbows do not require a
deduction from the Maximum Equivalent Vent Length.
1. Measure the individual distance from the furnace to the ter- mination for each pipe.
2. Select a Maximum Equivalent Vent Length (MEVL) longer than the measured distance of the individual vent and com-
bustion air connections to the vent termination.
3. Count the number of elbows for each pipe.
4. For each pipe, multiply the number of elbows by the equi-
valent length for the type of elbow used. Record the equi- valent length of all the elbows for each pipe.
5. If a Tee is used on the termination, record the equivalent length of the Tee used.
6. Record the equivalent length of the termination to be used.
7. Subtract the equivalent lengths of the fittings and termina- tions from the Maximum Equivalent Vent Length.
8. If the Maximum Vent Length calculated is longer than the individual measured length of the vent pipe and combustion
air pipe, then the diameter of pipe selected may be used.
9. If the Maximum Vent Length calculated is shorter than the individual measured length of either the vent pipe or the
combustion air pipe, recalculate the Maximum Vent Length using the next larger diameter pipe.
NOTE: The vent pipe and combustion air pipe must be the same diameter.
NOTE: If the Maximum Vent Length for diameter of the pipe selected is longer than the measured length and the equivalent length of all the fitting and terminations, recalculate using the next smaller diameter. If the recalculated Maximum Vent Length is longer than the measured length of the vent pipe and combustion
air pipe, then that diameter of pipe selected may be used.
When installing vent systems of short pipe lengths, use the smallest
allowable pipe diameter. Do not use pipe size greater than required
or incomplete combustion, flame disturbance, or flame sense lockout may occur.
Combustion Air and Vent Piping Insulation
Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. The vent pipe may pass through unconditioned areas. The amount
of exposed pipe allowed is shown in Table 12.
1. Using winter design temperature (used in load calculations), find appropriate temperature for your application and fur-
nace model.
2. Determine the amount of total and exposed vent pipe.
3. Determine required insulation thickness for exposed pipe length(s).
4. When combustion air inlet piping is installed above a sus- pended ceiling, the pipe MUST be insulated with moisture
resistant insulation such as Armaflex or other equivalent type of insulation.
5. Insulate combustion air inlet piping when run in warm, hu- mid spaces.
6. Install the insulation per the insulation manufacturer's in- stallation instructions.
NOTE: Pipe length (ft. / M) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe
length as calculated from Table 13 or 15.
ii
39
Page 40
Configure the Furnace
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal
iniury or death. To route the vent pipe and combustion air pipe through the
furnace, the manufacturer supplied kit must be used. Failure to properly seal the blower compartment from the furnace vestibule could result in the circulation of carbon monoxide
throughout the structure. The vent pipe and combustion air pipe must be a continuous pipe while passing through the
blower compartment. Seals supplied in this kit must be installed per the instructions provided. Follow all procedures outlined in these instructions.
Install the Vent and Combustion Air Pipe With the furnace installed in the required position, remove the
desired knockouts from the casing. It will be necessary to remove one knockout for the vent pipe and the other knockout for the
combustion air connection. (See Fig. 12.) Use a fiat blade screwdriver and tap on the knockout on opposite
sides, where the knockout meets the casing. Fold the knockout down with duct pliers and work the knockout back and forth until
it is removed. Trim any excess metal from the knockout with tin snips.
The vent elbow can be rotated to the required location on the casing if necessary. See Fig 38. To rotate the vent elbow:
1. Loosen the clamp on the inlet of the vent elbow attached to the inducer.
2. Rotate the vent elbow to the required position. There are rounded notches on the vent elbow to align it with the
inducer housing for each orientation.
3. Tighten the clamp around the vent elbow. Torque the clamp to 15 lb-in. See Fig. 39-42.
Installing the Vent Pipe Adapter and Combustion Air
Pipe Adapter
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal iniury or death.
To route the vent pipe and combustion air pipe through the furnace, the manufacturer supplied kit must be used. Failure to properly seal the blower compartment from the furnace
vestibule could result in the circulation of carbon monoxide throughout the structure. The vent pipe and combustion air
pipe must be a continuous pipe while passing through the blower compartment. Seals supplied in this kit must be installed per the instructions provided. Follow all procedures outlined in these instructions.
NOTE: The rubber coupling that attaches to the vent pipe adapter must be used. The adapter seals the vent pipe to the casing and
reduces the strain on the vent elbow attached to the inducer.
1. Apply the gaskets to the vent pipe and combustion air pipe adapters. See Fig. 3%
NOTE: The vent pipe adapter has a larger ID than the combustion air pipe adapter.
2. Align the screw holes in the plastic vent pipe adapter with the dimples in the casing.
3. Pilot drill the screw holes for the adapter in the casing and attach the vent pipe adapter to the furnace with sheet metal
screws
4. Slide the end of the rubber vent coupling with notches in it over the standoffs on the vent pipe adapter.
5. Insert a length of vent pipe through the coupling into the outlet of the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow.
Torque the clamp to 15 lb-in.
Install the remaining vent and combustion air pipes as shown below. It is recommended that all pipes be cut, prepared, and
preassembled before pem_anently cementing any joint.
1. Working from furnace to outside, cut pipe to required length(s).
2. Deburr inside and outside of pipe.
3. Chamfer outside edge of pipe for better distribution of primer and cement.
4. Clean and dry all surfaces to be joined.
5. Check dry fit of pipe and mark insertion depth on pipe.
6. Insert the vent pipe into the vent elbow.
7. Torque clamp on vent elbow 15 lb-in.
8. Torque clamp on vent coupling 15 lb-in.
9. Insert the combustion air pipe into the adapter.
10. Pilot drill a screw hole through the adapter into the combus- tion air pipe and secure the pipe to the adapter with sheet
metal screws.
11. Seal around the combustion air pipe with silicone or foil tape.
12. After pipes have been cut and preassembled, apply generous layer of cement primer to pipe fitting socket and end of pipe
to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a
light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
13. While cement is still wet, twist pipe into socket with 1/4-in. turn. Be sure pipe is fully inserted into fitting socket.
14. Wipe excess cement from joint. A continuous bead of ce- ment will be visible around perimeter of a properly made
joint.
15. Handle pipe joints carefully until cement sets.
16. Horizontal portions of the venting system shall be suppor- ted to prevent sagging. Support combustion air piping and
vent piping a minimum of every 5 ft. (1.5M) [3 ft. (.91M)
for SDR-21 or -26 PVC] using perforated metal hanging strap or commercially available hangars designed to support plastic pipe.
17. Prevent condensate from accumulating in the pipes by slop- ing the combustion air piping and vent piping downward
towards furnace a minimum of 1/4-in. per linear ft. with no sags between hangers.
18. Complete the vent and combustion air pipe installation by connecting the concentric vent or by installing the required
termination elbows as shown in Figs. 47, 48 and 49. For Ventilated Combustion Air Termination, See Fig. 50
19. Use appropriate methods to seal openings where combus- tion air pipe and vent pipe pass through roof or sidewall.
Optional Installation of the vent pipe
This option provides a disconnect point for the vent pipe. The vent pipe must be cemented to the plastic vent pipe adapter to maintain
a sealed vestibule. See Fig. 43.
1. Insert a length of vent pipe through the casing into the outlet of the vent elbow.
4O
Page 41
2. Slide the plastic vent pipe adapter over the length of the vent pipe down to the furnace casing. Mark the pipe where
it is flush with the outlet of the adapter.
3. Remove the pipe from the furnace and the adapter and cut off any excess pipe.
4. Clean and prime the end of the pipe that is flush with the vent adapter with a primer that is appropriate for the type of
pipe being used.
5. Re-insert the pipe through the casing into the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow. Torque the clamp to 15 lb-in.
7. Apply cement to the end of the pipe and to the inside of the plastic vent adapter.
8. Slide the adapter over the vent pipe and align the screw holes in the adapter with the dimples in the furnace casing.
9. Pilot drill 1/8-in. screw holes for the adapter in the casing and secure the adapter to the furnace with sheet metal
screws.
10. Loosen the clamps on the rubber vent coupling.
11. Slide the end of the coupling with notches in it over the standoffs in the vent pipe adapter.
12. Tighten the clamp of the coupling over the vent pipe adapter. Torque the lower clamp around the vent pipe
adapter to 15 lb-in.
13. Pilot drill a 1/8-in. hole in the combustion air pipe adapter.
14. Complete the vent and combustion air pipe as shown in "Install the Vent and Combustion Air Pipe"
Installing the Vent Termination
Roof Terminations
A roof termination of any type will require a 4-in. (102 ram) flashing for a 2 in. (51 ram) concentric vent or a 5-in. diameter
(127 ram) flashing for a 3-in. (76 ram) concentric vent kit. For two-pipe or single pipe vent systems, a flashing for each pipe of the
required diameter will be necessary. It is recommended that the flashing be installed by a roofer or
competent professional prior to installing the concentric vent. The terminations can be installed on a flat or pitched roof.
Concentric Vent Single or multiple concentric vent nmst be installed as shown in
Fig. 47. Maintain the required separation distance between vents or pairs of vents as shown in Fig. 47 and all clearance shown in
Fig. 45. Cut one 4-in. (102 ram) diameter hole for 2-in. (51 ram) kit, or
one 5-in. (127 ram) diameter hole for 3-in. (76 ram) kit in the desired location.
Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
Slide assembled kit with rain shield REMOVED through hole in wall or roof flashing. NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole. Disassemble loose pipe fittings. Clean and cement using same
procedures as used for system piping. Two-Pipe and Single-Pipe Terminations
Single and two pipe vent must be installed as shown in Fig. 47 and
48. Maintain the required separation distance between vents or pairs of vents as shown in Fig. 47 and 48. and all clearance shown
in Fig. 45 and 46 . Cut the required number of holes in the roof or sidewall for vent
and (when used) combustion air pipes. Sidewall holes for two-pipe vent terminations should be side-by-side, allowing space between
the pipes for the elbows to fit on the pipes.
Holes in the roof for two pipe terminations should be spaced no more than 18 in. (457 ram) apart.
Termination elbows will be installed after the vent and (if used) combustion air pipe is installed.
Sidewall Terminations
Concentric Vent
Determine an appropriate location for termination kit using the guidelines provided in section "Locating The Vent Termination" in
this instruction.
1. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in. dia- meter hole for 3-in. kit.
2. Loosely assemble concentric vent/combustion air termina- tion components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through hole.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
4. Locate assembly through sidewall with rain shield posi- tioned no more than 1-in. (25 ram) from wall as shown in
Fig. 47.
5. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
2-Pipe and 1-Pipe Vent Termination
Determine an appropriate location for termination kit using the guidelines provided in section "Locating The Vent Termination" in
this instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.
2. Loosely install elbow in bracket and place assembly on combustion-air pipe.
3. Install bracket as shown in Fig. 47 and 49.
NOTE: For applications using vent pipe option indicated by dashed lines in Fig. 47 and 48, rotate vent elbow 90 ° from position.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
(Direct Vent / 2-Pipe System ONLY)
When 2 or more furnaces are vented near each other, 2 vent
terminations may be installed as shown in Fig. 47, but next vent termination must be at least 36 in. (914 ram) away from first 2
terminations. It is important that vent terminations be made as
shown in Fig. 47 to avoid recirculation of flue gases.
Inducer Outlet Restrictor
To improve efficiency and operation of 40,000 BTUH input models on very short vent systems, an inducer outlet restrictor is required to be installed on the outlet of the inducer assembly. The
outlet restrictor is shipped in the loose parts bag. To determine if the outlet restrictor is required, see Table 13 and
Table 15. Failure to use an outlet choke when required may
result in flame disturbance or flame sense lockout.
To install the outlet restrictor:
1. Remove the vent elbow from the inducer outlet.
2. Align the lock tabs on the outlet restrictor with the slots on inside outlet of the inducer assembly.
3. Snap the outlet restrictor in place.
4. Re-install the vent elbow.
5. Torque vent elbow clamp 15-1b. in.
ii
41
Page 42
Table11 - Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations)
ASTM SPECIFICATION SOLVENT CEMENT
(MARKED ON MATERIAL) MATERIAL PIPE FITTINGS AND PRIMERS DESCRIPTION
D1527 D1785
D2235 D2241 D2466 D2468
D2564 D2661 D2665
F438 F441
F442 F493
F628
F656 F891
ABS Pipe -- PVC Pipe --
For ABS -- --
PVC Pipe -- PVC -- Fittings
ABS -- Fittings
For PVC -- --
ABS Pipe Fittings PVC Pipe Fittings
CPVC -- Fittings CPVC Pipe -- CPVC Pipe --
For CPVC -- --
ABS Pipe --
For PVC -- --
PVC Pipe --
Solvent Cement
Solvent Cement
DWV at Schedule-40 IPS sizes
Solvent Cement
Cellular Core DWV at Schedule-40
Primer
Cellular Core Schedule-40 & DWV
Schedule-40 Schedule-40
For ABS
SDR-21 & SDR-26
Schedule-40 Schedule-40
For PVC
DWV Schedule-40 Schedule-40
SDR
For CPVC
IPS sizes
For PVC
42
Page 43
Single
Stage
Furnace
Input
40000*
80000
80000
Table 12 - Maximum Allowable Exposed Vent Lengths Insulation Table - Ft. / M
Maximum Length of Uninsulated and Insulated Vent Pipe-Ft (M)
Winter Design
Temp °F
(°C)
20 (-1 O)
0 (-20)
-20 (-30)
-4o (-4o)
20 (-10) M 9.1 18.6 18.6 16.5 N/A 9.1 41.1 49.7 43.3 N/A 9.1 41.1 58.2 50.6 N/A
0 (-20) M 9.1 9.4 9.1 7.0 N/A 9.1 34.4 30.5 25.9 N/A 9.1 41.1 36.6 30.8 N/A
-20 (-30) M 7.3 5.2 4.6 2.1 N/A 9.1 24.7 21.3 17.4 N/A 9.1 29.9 25.9 21.3 N/A
-40 (-40) M 4.6 2.4 1.5 0.0 N/A 9.1 18.6 15.8 12.2 N/A 9.1 22.9 19.5 15.5 N/A
20 (-10) M 6.1 21.3 23.8 21.3 18.3 6.1 21.3 53.3 55.8 46.9 6.1 21.3 53.3 65.5 55.2
0 (-20) M 6.1 12.8 12.5 10.1 6.4 6.1 21.3 40.2 33.8 27.1 6.1 21.3 47.9 40.5 32.6
-20 (-30) M 6.1 7.6 7.0 4.3 0.3 6.1 21.3 28.7 23.5 17.4 6.1 21.3 34.4 28.7 21.6
-40 (-40) M 6.1 4.3 3.7 0.9 0.0 6.1 21.3 21.6 17.1 11.6 6.1 21.3 26.2 21.3 15.2
Pipe
Length in
Ft. &M
Ft.
M
Ft.
M
Ft.
M
Ft.
M
Ft. 30 61 61 54 N/A 30 135 163 142 N/A 30 135 191 166 N/A
Ft. 30 31 30 23 N/A 30 113 100 85 N/A 30 135 120 101 N/A
Ft. 24 17 15 7 N/A 30 81 70 57 N/A 30 98 85 70 N/A
Ft. 15 8 5 0 N/A 30 61 52 40 N/A 30 75 64 51 N/A
Ft. 20 70 78 70 60 20 70 175 183 154 20 70 175 215 181
Ft. 20 42 41 33 21 20 70 132 111 89 20 70 157 133 107
Ft. 20 25 23 14 1 20 70 94 77 57 20 70 113 94 71
Ft. 20 14 12 3 0 20 70 71 56 38 20 70 86 70 50
No Insulation 3/8-in. (9.5 mm) Insulation
Pipe Diameter-in. (mm)
1 1/2 2 2 1/2 3 4
(38) (51) (64) (76) (102)
48 42 42 N/A N/A
14.6 12.8 12.8 N/A N/A 25 19 17 N/A N/A
7.6 5.8 5.2 N/A N/A 14 7 5 N/A N/A
4.3 2.1 1.5 N/A N/A
7 0 0 N/A N/A
2.1 0.0 0.0 N/A N/A
Pipe Diameter-in. (mm)
1 1/2 2 2 1/2 3 4
(38) (51) (64) (76) (102)
50 122 111 N/A N/A
15.2 37.2 33.8 N/A N/A 50 75 66 N/A N/A
15.2 22.9 20.1 N/A N/A 50 52 45 N/A N/A
15.2 15.8 13.7 N/A N/A 50 38 31 N/A N/A
15.2 11.6 9.4 N/A N/A
1/2-in, (12.7 mm) Insulation
Pipe Diameter-in. (mm)
1 1/2 2 2 1/2 3 4
(38) (51) (64) (76) (102)
50 144 130 N/A N/A
15.2 43.9 39.6 N/A N/A 50 90 79 N/A N/A
15.2 27.4 24.1 N/A N/A 50 64 55 N/A N/A
15.2 19.5 16.8 N/A N/A 50 48 40 N/A N/A
15.2 14.6 12.2 N/A N/A
20 (-10) M N/A 7.6 30.2 27.1 23.8 N/A 7.6 33.5 71.0 80.8 N/A 7.6 33.5 71.6 69.8
100000
120000
0 (-20) M N/A 7.6 16.8 14.0 10.1 N/A 7.6 33.5 44.2 35.7 N/A 7.6 33.5 52.7 42.7
-20 (-30) M N/A 7.6 10.4 7.3 3.4 N/A 7.6 33.5 31.4 24.1 N/A 7.6 33.5 37.8 29.6
-40 (-40) M N/A 7.0 6.1 3.4 0.0 N/A 7.6 29.0 23.5 16.8 N/A 7.6 33.5 28.7 21.3
20 (-10) M N/A N/A 4.6 30.2 26.2 N/A N/A 4.6 30.5 66.8 N/A N/A 4.6 30.5 76.2
0 (-20) M N/A N/A 4.6 15.5 11.6 N/A N/A 4.6 30.5 39.6 N/A N/A 4.6 30.5 47.5
-20 (-30) M N/A N/A 4.6 8.5 4.3 N/A N/A 4.6 30.5 26.8 N/A N/A 4.6 30.5 32.9
-4o(-4o)
*Not all families have these models.
Ft. N/A 25 99 89 78 N/A 25 110 233 265 N/A 25 110 235 229
Ft. N/A 25 55 46 33 N/A 25 110 145 117 N/A 25 110 173 140
Ft. N/A 25 34 24 11 N/A 25 110 103 79 N/A 25 110 124 97
Ft. N/A 23 20 11 0 N/A 25 95 77 55 N/A 25 110 94 70
Ft. N/A N/A 15 99 86 N/A N/A 15 100 219 N/A N/A 15 100 250
Ft. N/A N/A 15 51 38 N/A N/A 15 100 130 N/A N/A 15 100 156
Ft. N/A N/A 15 28 14 N/A N/A 15 100 88 N/A N/A 15 100 108
Ft. N/A N/A 15 14 0 N/A N/A 15 85 62 N/A N/A 15 100 79
M N/A N/A 4.6 4.3 0.0 N/A N/A 4.6 25.9 18.9 N/A N/A 4.6 30.5 24.1
43
Page 44
Table 13 - Maximum Equivalent Vent Length - Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
NOTE: Maximum Equivalent Vent Length (MEVL) does" NOT include elbows or terminations. Use Table 14 - Deductions from
Maximum Equivalent Vent Length to determine allowable vent length for each application.
DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE)
Altitude
FT (M)
0 to 2000 (0 to 610)
2001 to 3000
(610 to 914)
3001 to 4000
(914 to 1219)
4001 to 4500 60,000
(1219 to 80,000
1370) 100,000
NOTE: See notes at end of venting tables.
See Table 15 for altitudes over 4500 ft. (1370 M)
*Not all families have these models.
Unit Size Vent Pipe
BTU/Hr
40,000 *2
60,000 80,000
100,000 120,000
40,000"
60,000 80,000
100,000 120,000 40,000"
60,000 80,000
100,000 120,000
40,000"
120,000
1-1/2
50 (15.2)
30 (9.1)
20 (6.1)
45 (13.7) 27 (8.2)
17 (5.2)
39 (11.9) 23 (7.0)
15 (4.6)
36 (11.0) 21 (6.4)
14 (4.3)
2 2-1/2
210 (64.0) 250 (76.2) 135 (41.1) 235 (71.6) 265
70 (21.3) 175 (53.3) 235 25 (7.6) 110 (33.5) 235
15 (4.6) 1O0 198 (60.4) 232 (70.7) 127 (38.7) 222 (67.7) 250
64 (19.5) 165 (50.3) 222 22 (6.7) 104 (31.7) 223
11 (3.4) 93 184 (56.1) 214 (65.2) 119 (36.3) 210 (64.0) 235
59 (18.0) 155 (47.2) 210 19 (5.8) 98 (29.9) 211
8 (2.4) 86
177 (53.9) 205 (62.5) 115 (35.1) 204 (62.2) 226
56 (17.1) 150 (45.7) 202 17 (5.2) 94 (28.7) 205
Diameter (in.)
(60.8)
(71.6) 265 (80.8) (71.6) 265 (80.8)
(30.5) 250 (76.2)
(76.2) (67.7) 249 (75.9)
(68.0) 250 (76.2) (28.3) 237 (72.2)
(71.6) (64.0) 232 (70.7)
(64.3) 236 (71.9) (26.2) 224 (68.3)
(69.5)
(61.6) 224 (68.3) (62.5) 229 (69.8)
83
(25.3) 217 (66.1)
Table 14 - Deductions from Maximum Equivalent Vent Length - Ft. (M)
Pipe Diameter (in): 1-1/2 2 2-1/2 3* 4*
Mitered 90 ° Elbow 8 (2.4) 8 (2.4) 8 (2.4)
Medium Radius 90 ° Elbow 5 (1.5) 5 (1.5) 5 (1.5)
Long Radius 90 ° Elbow 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9)
Mitered 45 ° Elbow 4 (1.2) 4 (1.2) 4 (1.2)
Medium Radius 45 ° Elbow 2.5 (0.8) 2.5 (0.8) 2.5 (0.8)
Long Radius 45 ° Elbow 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5)
Tee 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9)
Note: 3- and 4-in. Vent
Venting System Length Calculations
The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 13 or Table 15 minus the number of elbows nmltiplied by the deduction for each elbow in Table 14.
Standard vent terminations and concentric vent terminations count for zero deductions.
Example
A direct-vent 60,000 Btuh furnace installed at 2100 ft. (640 M ) with 2-in. (51 ram) vent piping. Venting system includes, FOR EACH PIPE, (3) 90° long radius elbows, (2) 45 ° long radius elbows and a concentric vent kit.
Maximum Equivalent Vent Length
Deduct (3) 90 long radius Deduct (2) 45 long radius
Maximum Vent Length
3 x 3ft. = 9ft. 2 x 1.5 ft. = 3ft.
= 127 ft.
= 115 ft.
(From Table 13) (From Table 14) (From Table 14)
For EACH vent or inlet pipe
44
Page 45
Table 15 - Maximum Equivalent Vent Length - Ft. (M)
4501 to 10,000 Ft. (0 to 1370 M) Altitude
NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 14 - Deductions from
Maximum Equivalent Vent Length to determine allowable vent length for each application.
DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE)
Altitude
FT (M)
4501 to 5000 60,000 (33.8) 221 (67.4)
(1370 to 80,000 (16.5) 195 (59.4) 216 (65.8)
1524) 100,000 (4.9) 200 (61.0) 222 (67.7)
5001 to 8000 60,000 (31.4) 186 (56.7) 207 (63.1)
(1524 to 80,000 (14.9) 137 (41.8) 183 (55.8) 200 (61.0)
1829) 100,000 (3.7) 85 (25.9) 188 (57.3) 208 (63.4)
8001 to 7000 60,000 (29.3) 174 (53.0) 194 (59.1)
(1829 to 80,000 (13.4) 120 (36.6) 171 (52.1) 185 (56.4)
2134) 100,000 (6.0) 79 (24.1) 178 (54.6) 195 (59.4)
7001 to 8000 60,000 (27.1) 163 (49.7) 181 (55.2)
(2134 to 80,000 (12.2) 120 (36.6) 159 (48.5) 170 (51.8)
2438) 100,000 73 (22.3) 167 (50.9) 182 (55.5)
8001 to 9000 60,000 (25.0) 152 (46.3) 168 (51.2)
(2438 to 80,000 (10.7) 111 (36.8) 148 (45.1) 156 (47.5)
2743) 100,000 67 (20.4) 157 (47.9) 170 (51.8)
9001 to 60,000 (26.2) 142 (43.3) 156 (47.5)
10,000 80,000 (9.4) 103 (31.4) 137 (41.8) 142 (43.3)
(2743 to
3048) 100,000 62 (18.9) 147 (44.8) 157 (47.9)
Unit Size
1-1/2 J 2
40,000* (52.1)
33 I (10'1) I 171
I 20 I (61)I 111
54 16
120,000 80 (24.4) 211 (64.6) 40,000* (48.2) 179 (54.6)
120,000 74 (22.6) 199 (60.7) 40,000* (44.2) 162 (49.4)
120,000 68 (20.7) 187 (57.0) 40,000* (40.5) 146 (44.5)
I 27 I (62>I 156
I 16 I (4.9) J 103
49 12
I 21 I (6.4) I 145 I 13 I (4.0) I 96
44 10
I 15 I (4.6) I 133
Vent Pipe Diameter
2-1/2
196 (59.7) 198 (60.4) 146 (44.5)
91 (27.7)
I 10 I (6.0) I 89
40
120,000 62 (18.9) 175 (56.3) 40,000* (36.9) 130 (39.6)
120,000 56 (17.1) 164 (50.0) 40,000" (33.5) 115 (35.1)
120,000 51 (15.5) 156 (46.6)
I 10 I /60) I 121
I 7 I (2'1) I 82
35
I 5 I /15)I 110
76 31
Notes:
1. 3- and 4-in. Vent pipe systems require long radius elbows.
2. Total equivalent vent lengths under 10' for 40,000 BTUH require the use of an outlet choke plate at altitudes 0 to 2000 ft (0 to 610 M). Failure to use an outlet choke when required may result in flame disturbance or flame sense lockout.
3. Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
4. NA - Not allowed; pressure switch will not close, or flame disturbance may result.
5. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
6. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.
7. Assume the two 45 ° elbows equal one 90 ° elbow. Wide radius elbows are desirable and may be required in some cases.
8. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
9. The minimum pipe length is 5 ft. (1.5 M) for all applications.
10. Use 3-in. (76 mm) diameter vent termination kit for installations requiring 4-in. (102 mm) diameter pipe.
45
Page 46
ii
Attach gaskets to vent pipe and combustion air adapters.
Fig. 37 - Vent Coupling and Adapter with Gaskets
Vent Coupling and Adapter
Al1314
INDUCER OUTLET
VENT ELBOW CLAMP TORQUE 15 LB-IN.
VENT PIPE CLAMP TORQUE 15 LB-IN.
ELBOW
Fig. 38 - Inducer Vent Elbow
46
INDUCER OUTLET CHOKE 40,000 BTUH MODELS ONLY
Al1285
Page 47
Any other unused
knockout be used
may
for combustion air
connection.
Rotate vent elbow to
required position.
x_ r
UPFLOW LEFT CONFIGURATION
Any otherunused
knockout may be used
_rcombustion air
connedion.
C) Attach vent pipe adapter with gasket to furnace casing.
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
(_ Slide vent pipe through adapter and coupling into vent elbow. 1_ Insert vent pipe into vent elbow.
(_ Torque all clamps 15 lb.-in. @ Attach combustion air pipe adapter with gasket to furnace.
(_ Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
A11309 A11308
A11310
UPFLOW VERTICAL VENT
A11399
Fig. 39 - Uptlow Configurations (Appearance may vary)
47
Page 48
Rotateventelbowto
requiredposition.
\s
Al1311
OWNFLOW LEFT CONFIGURATION
Rotate vent elbow to
required position.
Any other unused <_
knockout may be used
for combustion air
connection.
Al1312
DOWNFLOW RIGHT CONFIGURATION
Al1313
Downflow Vertical
Requires Accessory Internal Vent Kit.
See Product Data for current kit number.
(_) Attach vent pipe adapter with gasket to furnace casing. (_) Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
G) Slide vent pipe through adapter and coupling into vent elbow. (_) Insert vent pipe into vent elbow.
(_ Torque all clamps 15 lb.-in. @ Attach combustion air pipe adapter with gasket to furnace.
(_ Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 40 - Downflow Configurations (Appearance may vary)
48
Al1400
Page 49
HORIZONTAL LEFT -
VERTICAL VENT CONFIGURATION
Al1327
HORIZONTAL LEFT - LEFT VENT CONFIGURATION
I
A11328
ii
HORIZONTALLEFT- RIGHT VENT CONFIGURATION*
*RequiresAccessoryInternalVentKit SeeProductDataforCurrentKitNumber
(_ Attach vent pipe adapter with gasket to furnace casing. (_ Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
G) Slide vent pipe through adapter and coupling into vent elbow. (_ Insert vent pipe into vent elbow.
(_ Torque all clamps 15 lb.-in. @ Attach combustion air pipe adapter with gasket to furnace.
(Z) Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 41 - Horizontal Left (Appearance may vary)
Al1329
A11340
49
Page 50
g
_--_ ALTERNATE
CONNECTIONS
HORIZONTAL RIGHT -
VERTICAL VENT CONFiGURATiON
Al1337
ALTERNATE COMBUSTION AiR
\
HORIZONTAL RIGHT - LEFT VENT CONFIGURATION*
*Requires internal Vent Kit See Product Data for Current Kit Number
Al1336
HORIZONTAL RIGHT -
Al1335
RIGHT VENT CONFIGURATION
(_ Attach vent pipe adapter with gasket to furnace casing. (_) Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
(_ Slide vent pipe through adapter and coupling into vent elbow. (_ Insert vent pipe into vent elbow.
(_ Torque all clamps 15 lb.-in. @ Attach combustion air pipe adapter with gasket to furnace.
(Z) Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 42 - Horizontal Right (Appearance may vary)
50
A11341
Page 51
ALIGN NOTCHES IN VENT PiPE COUPLING OVER STAND-OFF
ON ADAPTER. TORQUE LOWER
VENT PiPE ADAPTER WiTH GASKET
INSTALLED ON FURNACE VENT PiPE IS CUT FLUSH WiTH TOP OF
CLAMP 15 LB-IN. WHEN REMAINING VENT PiPE iS INSTALLED, TORQUE
UPPER CLAMP TO 15 LBqN.
/
VENT PIPE FLUSH WITH ADAPTER VENT PIPE FLUSH SHOWING COUPLING
Fig. 43 - Vent Pipe Flush with Adaptor
Point elbow down towards
Al1339
uace
2 Omm
CASING SIDE ATTACHMENT COMBUSTION AIR PIPE
(NON-DIRECT VENT)
Fig. 44 - Combustion Air Pipe Attachment
TOP PLATE ATTACHMENT COMBUSTION AIR PIPE
(NON-DIRECT VENT)
Al1345
51
Page 52
ii
0 _
M
Item
Clearance Description Canadian Installation (I) U.S. Installation (2)
A
Clearance above grade veranda porch deck, bal 12 in. (305 mm). 18 in. (457 mm) above roof surface. 12 in. (305 mm) cony or anticipated snow level
B
Clearance to a window or door that may be opened and </- 100,000 Btuh (30 kW), 36 in. (914 mm) for and </- 50,000 Btuh (I5 kW), I2 in. (305 mm) for
C
Clearance to a permanently closed window Vertical clearance to a ventilated soffit located above
D
the terminal within a horizontal distance of 2feet (61 cm) from the centerline of the terminal
E
Clearance to an unventilated soffit
F
Clearance to an outside corner
G
Clearance to an inside corner Clearance to each side of the centerline extended
H
above electrical meter or gas service regulator as sembly
I Clearance to service regulator vent outlet
Clearance to non- mechanical air supply inlet to
J
building or the combustion air inlet to any other appli ance
K
Clearance to a mechanical air supply inlet
L Clearance under a veranda porch deck, or balcony deck, or balcony is fully open on a minimum of two
Clearance to each side of the centerline extended
M above or below vent terminal of the furnace to a dryer
or water heater vent or other appliance's direct vent 12 in. (305 mm) 12 in. (305 mm) intake or exhaust
Clearance to the vent terminal of a dryer vent water
N heater vent or other appliances direct vent intake or 3 ft. (.9 M) 3 ft. (.9 M)
exhaust
© Clearance from a plumbing vent stack 3 ft. (.9 M) 3 ft. (.9 M)
p Clearance above paved sidewalk or paved driveway walk or paved driveway that is located between two with local installation codes and the requirements of
located on public property single family dwellings and serves both dwellings, the gas supplier and the manufacturer's installation
(1) In accordance with the current (: A N / CSA B 149.1, Natural Gas and Propane Installation (:ode. (2) In accordance with the current ANSI Z223.1 .NFPA 54. National Fuel Gas (:ode
Notes:
1. The vent tier this appliance shall not terminate: a. Over public walkways; or b. Near sottit vents ot crawl space vents or other areas where condensale or Valtor could create a nuisance or hazard or property danlage; or c. Where condensate vapor could cause damage or court be detrimental to the operation ill ¸regulators, reliel ¸vah'es, or other equipment.
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recircukdkln ill¸ the combustkln products ill ¸ adjacenl venls. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion (1t¸the heat exchangers.
3. Avoid venling under a deck or large overhang. Recircukdkln could occur and cause pertormance or system problems.
12 in. (305 mm) for appliances > 10,000 Btuh (3kW) 9 in. (229 mm) for appliances > I0,000 Btuh (3kW)
appliances > 100,000 Btuh (30 kW) appliances > 500,000 Btuh (15 kW)
For clearances not specified in ANSI Z223.I/NFPA 54 or C A N / CSA BI49.1 clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's installation
instructions.
3 ft. (.9 M) within 15 ft. (4.6 M) above the meter/ 3 ft. (.9 M) within I5 ft. (4.6 M) above the meter/ regulator assembly regulator assembly
3 ft. (.9 M)
12 in. (305 mm) for appliances > 10,000 Btuh(3kW) and </- 100,000 Btuh (30 kW), 36 in. (914 mm) for appliances > 100,000 Btuh (30 kW)
6 ft. (I .8 M)
12 in. (305 mm). Permitted only if veranda porch,
sides beneath the floor.
7 ft. (2.I M). A vent shall not terminate above a side- CAN/CSA Bt49.I, clearances shall be in accordance
For clearances not specified in ANSI Z223.I/NFPA 54 or C A N / CSA BI49.1 clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's installation
instructions.
*3 ft. (.9 M) *For clearances not specified in ANSI Z223.1 /NFPA 54or C A N / CSA BI49.I, clearances shall be in
accordance with local installation codes and the
requirements of the gas supplier and the manufacturer's
installation instructions. 9 in. (229 mm) for appliances > I0,000 Btuh (3kW)
and </- 50,000 Btuh (I5 kW), I2 in. (305 mm) for appliances > 500,000 Btuh (15 kW)
3 ft. (.9 M)
For clearances not specified in ANSI Z223.I/NFPA 54 or C A N / CSA BI49.1 clearances shall be in accordance
with local installation codes and the requirements of the gas supplier and the manufacturer's installation
instructions.
For clearances not specified in ANSI Z223.t/NFPA 54 or
instructions.
Fig. 45 - Direct Vent Termination Clearance
A11046
52
Page 53
................. /
/
/
/
/
/
/
/
..........._ \
\\\ j -......
....... >
D VENT TERMINAL
Item Clearance Description Canadian Installation (I) U.S. Installation (2)
A Clearance above grade veranda porch deck, bal 12 in. (305 mm). 18 in. (457 mm) above roof surface. 12 in. (305 mm)
cony or anticipated snow level
B
Clearance to a window or door that may be opened and </- 100.000 Btuh (30kW) 36 in. (914 mm) for (.3 M) above the opening.
C
Clearance to a permanently closed window Vertical clearance to a ventilated soffit located above
D
the terminal within a horizontal distance of 2 feet (61 cm) from the centerline of the terminal
E
Clearance to an unventilated soffit
F
Clearance to an outNde corner
G
Clearance to an inside corner Clearance to each side of the centerline extended
H
above electrical meter or gas service regulator as sembly
I Clearance to service regulator vent outlet 3 ft. (.9 M) be in accordance with local installation codes and the
Clearance to non mechanical air supply inlet to 6 in. (152 mm) for appliances </ I0.000 Btuh (3kW)
J building or the combustion air inlet to any other appli 12 in. (305 mm) for appliances > 10.000 Btuh (3kW) 4 ft. (1.2 M) below or to the side of the opening. 1 ft.
ance appliances > 100,000 Btuh (30 kW)
K Clearance to a mechanical air supply inlet 6 ft. (I .8 M) 3 ft. (.9 M)
L Clearance under a veranda porch deck, or balcony deck. or balcony is fully open on a minimum of two with local installation codes and the requirements of
Clearance to each side of the centerline extended
M above or below vent terminal of the furnace to a dryer
or water heater vent or other appliance's direct vent 12 in. (305 mm) 12 in. (305 mm) intake or exhaust
Clearance to the vent terminal of a dryer vent water
N heater vent or other appliances direct vent intake or 3 ft. (.9 M) 3 ft. (.9 M)
exhaust
Q Clearance from a plumbing vent stack 3 ft. (.9 M) 3 ft. (.9 M)
p Clearance above paved sidewalk or paved driveway walk or paved driveway that is located between two 7 ft. (2.1 M).
located on public property single family dwellings and serves both dwellings.
(1) In accordance wilh Ihe current ( A N / (SA B 149.], Natural Gas and Propane Inslallalion (ode. (2) In accordance wilh Ihe currenl ANSI Z223.1 .NFPA 54. Nalional Fuel Gas (ode
Noles:
]. The venl fl)r this appliance shall nol lerminale:
a. Over publicwalkways; or
b. Near soflil vents ol crawl space vents or other areas where condensate or vapor cotlld creale a nuisance or hazard or property dan]age; or
c. Where condensate vapor could cause dan]age or could be detril_qental to the operation oI' regulators, relic[ valves, or olher equipment.
2. When localing vent terl_inalions, consideration must be given to prevailing winds, localion, and other condilions which may cause recirculalion oI' Ihe combuslion products oI' adjacenl vents. Recirculation can cause poor COlllbuslion. inlet condensale problems, and accelerated corrosion of the heat exchangers.
3. Avoid venling under a deck or large overhang. Recircuhdion could occur and cause pert'ormance or syslem problems.
(_'_ AIR SUPPLY INLET
6 in. (152 mm) for appliances </ I0.000 Btuh (3kW) 12 in. (305 mm) for appliances > 10.000 Btuh (3kW) 4 ft. (1.2 M) below or to the side of the opening. 1 ft.
appliances > 100,000 Btuh (30 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B149.I, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's installation
instructions.
3 ft. (.9 M) within I5 ft. (4.6 M) above the meter/ 3 ft. (.9 M) within 15 ft. (4.6 M) above the meter/regu regulator assembly lator assembly.
and </- 100.000 Btuh (30kW) 36 in. (914 mm) for (.3 M) above the opening.
12 in. (305 mm). Permitted only if veranda, porch. C A N / CSA BI49.1. clearances shall be in accordance
sides beneath the floor, the gas supplier and the manufacturer's installation
7 ft. (2.I M). A vent shall not terminate above a side
E_ AREA WHERE TERMINAL IS NOT PERMITED
For clearances not specified in ANSI Z223.t/NFPA 54 or CAN/CSA B149.I, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's installation
instructions.
* 3 ft. (.9 M) * For clearances not specified in ANSI Z223.1/NFPA 54 or C A N / CSA Bt49.1. clearances shall
requirements of the gas supplier and the manufacturer's installation instructions.
For clearances not specified in ANSI Z223.1/NFPA 54 or
instructions.
Fig. 46 - Ventilated Combustion Air and Non-Direct Vent Termination Clearance
ii
A11047
53
Page 54
ii
Con_ntric Vent and Corn bustion Air
Roof Termination {ptefurted) ......
clearance above
\\\\\
Fig. 47 - Combustion Air and Vent Pipe Termination for Direct Vent (2-Pipe) System
A05090
Roof Termination (Preferred)
cr_ 305ram)mnmum earance
above highest a_licipated
snow bevel maximum of
24 in (610ram) above roof
Side walHermination with 2 ehbows (preferred)
if:b°i
Abandoned masonry used as raceway (percode)
12 in (305 ram) rain from
overhang or roof
Maintain 12 in (305ram) minimum clearance
above highest a_licipated snow level or grade whichever is greater
6 in (152ram) minimum clearance
between wal[ aid end of vent pipe
10 in (254mm) maximum pipe [enql]
12 in rain (305 mm)fron
overhang or roof
Sidewall Termination
with Straight Pipe (preferred)
Fig. 48 - Vent Pipe Termination for Non-Direct Vent and Ventilated Combustion Air System
ghest anticipated
snow level or grade
whichever is greater
_O5mm)
A05091
54
Page 55
\
NOTE: This illustration is for reference only, Your unit may
differ in appearance or may not include all components shown.
OVERHANG OR ROOF
12-in
30A8 cm
Above anticipated snow UeveU
/ COMBUSTION AIR
(ELBOW PARALLEL
TO WALL)
L10F024=1
UVL_IN£_
EXHAUST -I r
_ __ L ea ance to overhang per code
12 IN, SEPARATION BETWEEN BOTTOM OF I"
COMBUSTION AIR AND
BOTTOM OF VENT
MAINTAIN 12 IN. CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
J
Fig. 49 - Alberta and Saskatchewan Vent Termination
55
Al1346
Page 56
Ventilated Combustion
// Air intake pipe _U
ii
/
-"19-_ Pipe hangar _ _ _
_ R" [7_ mm _,
Ventilated Combustion Air 12" (305 mm) intake termination in crawl
space
CRAWL SPACE
Ventilated Combustion Air intake pipe
Vent through
roof flashing
ATTI C
Fig. 50 - Vent Terminations for Ventilated Combustion Air
56
ff
12" (305 ram) rain. above highest level of insulation
A10497
Page 57
START-UP, ADJUSTMENT, AND SAFETY
CHECK
General
1. Furnace must have a 115-v power supply properly connec- ted and grounded.
NOTE: Proper polarity must be maintained for l15-v wiring. Control status indicator light flashes rapidly and furnace does not operate if polarity is incorrect.
2. Thermostat wire connections at terminals R, W, G, and Y/Y2 must be made at 24-v terminal block on furnace con-
trol.
3. Natural gas service pressure must not exceed 0.5 psig (14- in. w.c.), but must be no less than 0.16 psig (4.5-in. w.c.).
4. Blower door must be in place to complete l15-v electrical circuit to furnace.
Purge Gas Lines If not previously done, purge the lines after all connections have
been made and check for leaks,
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal
iniury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal iniury or loss of
life.
Adjustments
UNIT OPERATION HAZARD Failure to follow this caution may result in intermittent unit
operation or performance satisfaction. These furnaces are equipped with a manual reset limit
switch in burner assembly. This switch opens and shuts off power to the gas valve is an overheat condition (flame
rollout) occurs in burner assembly. Correct inadequate combustion-air supply or improper venting condition
before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
EAC-I terminal is energized whenever blower operates. HUM terminal is only energized when blower is energized in heating.
Prime Condensate Trap with Water
[]NIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has two internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
1. Remove upper and middle collector box drain plugs oppos- ite of the condensate trap. (See Fig. 57.)
2. Connect field-supplied 1/2-in. (13 mm) OD tube to upper collector box drain connection.
3. Insert field-supplied funnel into tube.
4. Pour one quart of water into funnel/tube. Water should run through collector box, overfill condensate trap, and flow in-
to open field drain.
5. Remove funnel; replace collector box drain plug.
6. Connect field-supplied l/2-in. (13 mm) OD tube to middle collector box drain port.
7. Pour one quart of water into funnel/tube. Water should run through collector box, overfill condensate trap, and flow in-
to open field drain.
8. Remove funnel and tube from collector box and replace col- lector box drain plug.
g
FIRE HAZARD Failure to follow this warning could result in personal
iniury, death and/or property damage. DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
FURNACE DAMAGE HAZARD Failure to follow this caution may result in reduced furnace
life.
DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig.
52.)
For proper operation and long term reliability, the Furnace input rate must be within +2 percent of input rate on furnace rating plate.
The gas input rate on rating plate is for installations at altitudes up to 2000 ft. (609.6M).
In the USA., the input rating for altitudes above 2000 ft. (609.6M) must be reduced by 2 percent for each 1000 ft. (304.8M) above sea
level. Refer to Table 18. In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft. (609.6M) to 4500 ft. (1371.6M) above sea
level. To adjust manifold pressure to obtain the proper input rate, first,
determine if the furnace has the correct orifice installed. At higher
altitudes or different gas heat contents, it may be necessary to
change the factory orifice to a different orifice. Tables have been provided in the furnace installation instructions to match the
required orifice to the manifold pressure to the heat content and specific gravity of the gas. To do this:
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation altitude in Table 20.
d. Find closest natural gas heat value and specific gravity in
Table 20.
57
Page 58
g
e. Follow heat value and specific gravity lines to point of in-
tersection to find orifice size and manifold pressure setting
for proper operation.
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (609.6 to
1371.6M), use USA altitudes of 2001 to 3000 ft. (609.6 to
914.4M). NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.
g. Replace orifice with correct size, if required by Table 20.
Use only factory-supplied orifices. See EXAMPLE 1.
EXAMPLE 1:0 - 2000 ft. (0 - 609.6M) altitude Heating value = 1050 Btu/cu ft.
Specific gravity = 0.62 Therefore: Orifice No. 44
Manifold pressure: 3.4-in. w.c. * Furnace is shipped with No. 44 orifices. In this example, all main
burner orifices are the correct size and do not need to be changed to obtain proper input rate.
1. Adjust manifold pressure to obtain input rate. (See Fig. 51.)
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Manually close blower door switch.
f. Jumper R and W thermostat connections on control to start
furnace. (See Fig. 35.)
g. Remove regulator adjustment cap from gas valve pressure
regulator (See Fig. 51.) and turn adjusting screw (3/16 or smaller flat-tipped screwdriver) counterclockwise (out) to
decrease input rate or clockwise (in) to increase input rate.
NOTE: DO NOT set manifold pressure less than 3.2-in. w.c. or more than 3.8 in. w.c. for natural gas. If manifold pressure is outside this range, change main burner orifices to obtain manifold pressure in this range.
h. When correct input is obtained, replace cap that conceals
gas valve regulator adjustment screws. Main burner flame should be clear blue, almost transparent (See Fig. 59.)
i. Remove jumper R to W.
2. Verify natural gas input rate by clocking meter.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Jumper R to W.
c. Run furnace for 3 minutes.
d. Measure time (in sec) for gas meter to complete 1 revolu-
tion and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.
e. Refer to Table 19 for cubic ft. of gas per hr.
f. Multiply gas rate cu fl./hr by heating value (Btuh/cu ft.)
to obtain input. If clocked rate does not match required in- put from Step 1, increase manifold pressure to increase in-
put or decrease manifold pressure to decrease input. Repeat steps b through e until correct input is achieved. Re-install
regulator seal cap on gas valve.
Adjust Temperature Rise
NOTE: Blower door must be installed when taking temperature rise reading. Leaving blower door off will result in incorrect temperature measurements.
FURNACE OVERHEATING HAZARD Failure to follow this caution may result in shortened
furnace life. Set air temperature rise within limits specified on the rating
plate to prevent reduced life of furnace components.
FURNACE DAMAGE HAZARD Failure to follow this caution may result in overheating the
heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate.
Temperature rise must be within limits specified on unit rating plate.
[]NIT DAMAGE HAZARD
Failure to follow this caution may result in component damage,
Temperature rise must be within limits specified on furnace rating plate. Recommended operation is at midpoint of rise range or slightly above,
This furnace must operate within the temperature rise ranges specified on the furnace rating plate. Determine the air temperature
as follows:
a. Place duct thermometers in return and supply ducts as close
to furnace as possible. Be sure thermometers do not "see" heat exchangers so that radiant heat does not affect thermometer readings. This is particularly important with
straight run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine temperature rise.
If the temperature rise is outside this range, check the following:
a. Gas input for gas heat operation.
b. Derate for altitude if applicable.
c. Return and supply ducts for excessive restrictions causing
static pressures greater than 0.50-in. w.c.
d. Adjust temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
58
Page 59
ELECTRICALOPERATIONHAZARD Failuretofollowthiswarningcouldresultinpersonalinjury
ordeath. Disconnect115velectricalpowerbeforechangingspeedtap.
Table 16 - Blower Speed Taps
FACTORY ATTACHED
COLOR SPEED TO:
Gray 5 Cool
Yellow 4 Spare
Blue 3 Heat
Orange 2 Spare
Fled 1 LO HT/Cont. Fan
Read following caution before changing taps).
[]NIT DAMAGE HAZARD
To avoid operating outside the rise range and avoid component damage:
1. NEVER connect Speed Tap 1 (Red) wire to "HEAT."
2. NEVER connect Speed Tap 2 (Orange) wire to "HEAT" on all models.
To change blower motor speed selections for heating mode, remove blower motor lead from control HEAT ternfinal. (See Fig.
35) Select desired blower motor speed lead from one of the other motor leads and relocate it to HEAT ternfinal. (See Table 16 for lead color identification.) Reconnect original lead on SPARE
ternfinal.
Adjust Blower Off Delay (Heat Mode)
The blower off delay has four adjustable settings from 90 sec to 180 sec. (See Table 17.) The blower off delay jumpers are located
on the furnace control (See Fig. 35 and Fig. 63.) To change the blower off delay setting, move the jumper from one set of pins on
the control to the pins used for the desired blower off delay. Factory blower off delay setting is 120 sec.
Table 17 - Blower Off Delay Jumper Positions
PINS 1 AND 2 2 AND 3 3 AND 4 4 AND 5
Time (in sec.) 90 120 150 180
Adjust Cooling Airflow
The cooling airflow can be set from the remaining blower speed
taps. Refer to the Air Delivery Tables in these instructions.
Adjust Continuous Fan Airflow
The Continuous Fan airflow can be set from the remaining blower speed taps. Refer to the Air Delivery Tables in these instructions. The Continuous Fan speed can be changed to any other speed tap
by toggling the Fan switch at the thermostat. See the Sequence of Operation for details.
FIREHAZARD Failureto follow this warning could result in personal
iniury, death, and/or property damage. Reinstall manifold pressure tap plug in gas valve to prevent
gas leak.
FURNACE OVERHEATING HAZARD Failure to follow this caution may result in reduced furnace
life. Recheck temperature rise. It nmst be within linfits specified
on the rating plate. Recommended operation is at the nfid-point of rise range or slightly above.
Adjust Thermostat Heat Anticipator
When using a non-electronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of the electrical
components in R-W circuit. Accurate amp draw readings can be
obtained at the thermostat subbase terminals R and W. Fig. 53 illustrates the easy method of obtaining actual amp draw. The amp
reading should be taken after blower motor has started and furnace is heating. Connect ammeter wires as shown in Fig. 53. The
thermostat anticipator should not be in the circuit while measuring current. If thermostat has no subbase, the thermostat must be
disconnected from R and W wires during current measurement.
See thermostat manufacturer's instructions for ac[iusting heat
anticipator and for varying heating cycle length. For an electronic
thermostat, set cycle rate for 3 cycles per hr.
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the Start-up procedure section as part of normal operation.
1. Check Main Linfit Switch This control shuts off combustion system and energizes air-
circulating blower motor, if furnace overheats. By using this method to check linfit control, it can be established that lim-
it is functioning properly and will operate if there is a re- stricted return-air supply or motor failure. If linfit control
does not function during this test, cause nmst be determined and corrected.
a. Run furnace for at least 5 nfinutes.
b. Gradually block off return air with a piece of cardboard or
sheet metal until the limit trips.
c. Unblock return air to pernfit normal circulation.
d. Burners will re-light when furnace cools down.
2. Check Pressure Switch(es) This control proves operation of the draft inducer blower.
a. Turn off 115-v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115-v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
low pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light
flashes a status code 31. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immedi-
ately.
e. Deternfine reason low pressure switch did not function
properly and correct condition.
f. Turn off 115-v power to furnace.
59
g
Page 60
g. Reconnect inducer motor wires, replace door, and turn on
l15-v power.
h. Blower will run for 90 sec before beginning the call for
heat again.
i. Furnace should ignite normally.
ChecMist
1. Put away tools and instruments. Clean up debris.
2. Verify that jumper for the blower OFF DELAY is set as de- sired per Table 17.
3. Verify that blower and control doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer's instruc- tions.
6. Review Owner's Manual with owner.
7. Attach literature packet to furnace.
SiNGLE-STAGE
TERMINALS WITH
SUBBASE
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
10 TURNS
ii
PressureTap
ON/O_tch
Fig. 51 - Gas Valve
RegulatorSealCap
Regu[atorAdjustment RegulatorSealCap underCap
Al1153
FROM UNIT 24-V CONTROL TERMINALS
EXAMPLE:
9001-10,000
*Derate multiplier factors are based on midpoint altitude for altitude range.
5.0AMPSON AMMETER 0.5AMPSFORTHERMOSTAT
10 TURNS AROUND JAWS ANTICIPATOR SETTING
Fig. 53 - Amp. Draw Check with Ammeter
Table 18 - Altitude Derate Multiplier for U.S.A.
ALTITUDE PERCENT DERATE
FZ
0-2000 2001-3000 3001-4000 4001-5000
5001-6000 6001-7000 7001-8000 8001-9000
M
0-610
610-914
914-1219
1219-1524 1524-1829
1829- 2134 2134- 2438 2438- 2743 2743- 3048
=
DERATE
8-10
10-12 12-14 14-16 16-18 18-20
4-6 6-8
OF
A96316
MULTIPLIER
FACTOR*
0
1.00
0.95
0.93
0.91
0.89
0.87
0.85
0.83
0.81
-- BURNER --_
Fig. 52 - Orifice Hole
)
ORIFICE
A93059
60
Page 61
SERVICE
................. Ifstatuscoderecallisneeded,brieflyremovethenreconnectonemainlimitwireto
..... displaylaststoredstatuscode.Afteronestatuscoderecamliscompletedcomponent
...... testwilloccur.
LED CODE STATUS
CONTINUOUS OFF- Check for 115VACat L1 & L2,& 24VAC at SEC-1& SEC-2. CONTINUOUS ON- Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarityreversed. If twinned,
EACHOFTHEFOLLOWINGSTATUSCODESiSATWODiGiTNUMBERWITHTHEFIRSTDiGiTDETERMINED BYTHENUMBEROFSHORTFLASHESANDTHESECONDDiGiTBYTHENUMBEROFLONGFLASHES,
1t NOPREVIOUSCODE.Storedstatuscodesareerasedautomaticallyafter72hours. 12BLOWERONAFTERPOWERUP(115VACor24VAC)Blowerrunsfor90seconds,ifunitis poweredup
duringacallforheat(R-Wclosed)orR-Wopensduringbloweron-delay.
13LIMITCIRCUITLOCKOUT.Lockoutoccursifalimitorflamerolloutswitchisopenlongerthan3minutes.
-Controlwillautoresetafterthreehours. Referto#33 14IGNITIONLOCKOUT.Controlwillauto-resetafterthreehours.Referto#34. 21GASHEATINGLOCKOUT.ControlwillNOTautoreset.Checkfor:
-Mis-wiredgasvalve -Defectivecontrol(valverelay)
22ABNORMALFLAME.PROVINGSIGNAL.Flameisprovedwhilegasvalveisde-energized.
Nucerwillrununtilfaultiscleared.Checkfor: -Leakygasvalve-Stuck-opengasvalve
23PRESSURESWITCHDIDNOTOPEN.Checkfor: -Obstructedpressuretubing
-Pressureswitchstuckclosed
24SECONDARYVOLTAGEFUSEISOPEN.Checkfor: -Shortcircuitinsecondaryvoltage(24VAC)wiring. 31PRESSURESWITCHDIDNOTCLOSEORREOPENED-IfLPSopenlongerthanfiveminutes,inducershutsoff
forI5 minutesbeforeretry.IfHPSremainsopenforoneminuteaftergasvalvecloses(afterthreesuccesivetrials),
thenfurnacecontrolwilllockoutfor3hoursbeforeretry.Checkfor:
- Excessivewind -Restrictedvent - Defectiveinducermotor
- Lowinletgaspressure(ifLGPSused) - Defectivepressureswitch -Lowinducervoltage(115VAC)
- Inadequatecombustionairsupply- Properventsizing - Disconnectedorobstructedpressuretubing
-Condensatedrainagerestrictedorblocked
Ifitopensduringbloweron-delayperiod,blowerwillcomeonfortheselectedbloweroff-delay.
33LIMffCIRCUITFAULT.Indicatesalimitorflamerollout,switchisopen.Blowerwillrunfor4minutesoruntil
openswitchremakeswhicheverislonger.Ifopenlongerthan3minutes,codechangestolockout#I3. If openlessthan3minutesstatuscode#33continuestoflashuntilblowershutsoff.Flamerolloutswitch requiresmanualreset.Checkfor:-Dirtyfilterorrestrictedductsystem-Properventsizing
-Restrictedvent - Looseblowerwheel -Excessivewind - Defectiveblowermotor
-Defectiveswitchorconnections -Inadequatecombustionairsupply(FlameRoll-outSwitchopen).
34 IGNiTiONPROVINGFAILURE-Controlwilltrythreemoretimesbeforelockout#I4occurs.
Ifflamesignallostduringbloweron-delayperiod,blowerwillcomeonfortheselectedbloweroff-delay.
Checkfor: -Oxidebuilduponflamesensor(cleanwithfinesteelwool)
-Properflamesensemicroamps(.5microampsD.C.rain.,4.0-6.0nominal)
-Manualvalveshut-off-Controlgroundcontinuity-Gasvalvedefectiveorgasvalveturnedoff
-Lowinletgaspressure-Inadequateflamecarryoverorroughignition-DefectiveHotSurfaceIgnitor
-Flamesensormustnotbegrounded - Green/yellowwireMUSTbeconnectedtofurnacesheetmetal
45CONTROLCIRCUITRYLOCKOUT.Auto-resetafteronehourlockoutdueto;- Gasvalverelaystuckopen
-Flamesensecircuitfailure - Softwarecheckerror Resetpowertoclearlockout.Replacecontrolifstatuscoderepeats.
referto twinning kit instructions.
ii
COMPONENT TEST
ToinitiatethecomponenttestsequenceshutOFFtheroomthermostatordisconnectthe"R"thermostat lead.BrieflyshorttheTEST/TWiNterminaltothe"Corn24V"terminalStatusLEDwillflashlaststatus
codeandthenturnONtheinducermotor.Theinducermotorwillrunfortheentirecomponenttest.The hotsurfaceignitor,blowermotorFANspeed(ifequiped)blowermotorHEATspeed,andblowermotor
COOLspeedwillbeturnedONfor10-15secondseach.GasValveandHumidifierwillnotbeturnedon.
/
Jr-
...... 3383 11-2 Rev,C
Fig. 54 - Service Label Information
61
Al1410
Page 62
SECONDS
FOR 1 REVOLUTION
10 11
12 13 14 15
16 17 18 19
20 21
22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49
SIZE OF TEST DIAL
Cu Ft.
36O 327
3OO 277 257 24O
225 212 2OO 189 18O
171 164 157 150 144
138 133 129 124 120
116 113 109 106 103
100
97 95 92 90
88 86 84 82 80
78 76 75 73
Table 19 - Gas Rate (CU ft./hr)
2 Cu Ft. 5
72O 655
6OO 555 514 48O
45O 424 4OO 379 36O
343 327 313 300 288
277 267 257 248 240
232 225 218 212 206
200
195 189 185 180
176 172 167 164 160
157 153 150 147
Cu Ft. 1800
1636 1500 1385 1286 1200
1125 1059 1000
947 900
857 818 783 750 720
692 667 643 621 600
581 563 545 529 514
500 486 474 462 450
439 429 419 409 400
391 383 375 367
SECONDS
FOR 1 REVOLUTION
50 51
52 53 54 55
56 57 58 59 60
62 64 66 68 70
72 74 76 78 80
82 84 86 88 90
92 94 96 98
100 102
104 106 108 110
112 116 120
SIZE OF TEST DIAL
1 Cu Ft.
72 71
69 68 67 65
64 63 62 61 6O
58 56 54 53 51
5O 48 47 46 45
44 43 42 41 40
39 38 38 37 36
35 35 34 33 33
32 31 30
2 Cu Ft.
144 141
138 136 133 131
129 126 124 122 12O
116 112 109 106 103
100
97 95 92 90
88 86 84 82 80
78 76 75 74 72
71 69 68 67 65
64 62 60
5 Cu Ft.
360 355
346 340 333 327
321 316 310 3O5 3OO
290 281 273 265 257
250 243 237 231 225
220 214 209 205 200
196 192 188 184 180
178 173 170 167 164
161 155 150
62
Page 63
Table 20 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate
SINGLE-STAGE FURNACE
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2°/o/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE AVG. GAS SPECIFIC GRAVITY OF NATURAL GAS
RANGE HEAT VALUE 0.58 0.60 0.62 0.64
AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold
ft (m) _ No. Pressure No. Pressure No. Pressure No. Pressure
900 43 3.8 42 3.2 42 3.3 42 3.4
"o
t-
O 975 44 3.7 44 3.8 43 3.4 43 3.6
r..
,_ Canada 925 44 3.5 44 3.6 44 3.8 43 3.4 _ 2001 (611) 950 44 3.3 44 3.4 44 3.6 44 3.7
.-_ (915) 825 43 3.6 43 3.7 43 3.8 42 3.2 O 850 44 3.8 43 3.5 43 3.6 43 3.7
.-_ (1220) 800 43 3.5 43 3.6 43 3.7 43 3.8
r..
O 825 44 3.8 43 3.4 43 3.5 43 3.6
<.' to
O 800 44 3.7 44 3.8 43 3.4 43 3.5
O 750 43 3.4 43 3.5 43 3.6 43 3.7
775 44 3.6 44 3.7 43 3.4 43 3.5
0 925 43 3.6 43 3.7 43 3.8 42 3.2
(0) 950 43 3.4 43 3.5 43 3.6 43 3.7
to 1000 44 3.5 44 3.6 44 3.8 43 3.4
1025 44 3.3 44 3.5 44 3.6 44 3.7
2000 1050 44 3.2 44 3.3 44 3.4 44 3.5 (610) 1075 45 3.7 45 3.8 44 3.3 44 3.4
1100 46 3.7 46 3.8 45 3.8 44 3.2
U.S.A. 800 42 3.4 42 3.5 42 3.6 42 3.7
2001 (611) 825 43 3.8 42 3.3 42 3.4 42 3.5
to 850 43 3.6 43 3.7 42 3.2 42 3.3
3000 (914) 875 43 3.4 43 3.5 43 3.7 43 3.8
900 44 3.7 44 3.8 43 3.5 43 3.6
to 975 44 3.2 44 3.3 44 3.4 44 3.5
1000 44 3.0 44 3.1 44 3.2 44 3.3
775 42 3.3 42 3.4 42 3.5 42 3.6
3001 800 43 3.8 42 3.2 42 3.3 42 3.4
to 875 44 3.6 44 3.7 43 3.4 43 3.5
4000 900 44 3.4 44 3.5 44 3.7 44 3.8
(1219) 925 44 3.2 44 3.4 44 3.5 44 3.6
950 44 3.1 44 3.2 44 3.3 44 3.4
750 42 3.3 42 3.4 42 3.5 42 3.6
4001 775 43 3.7 43 3.8 42 3.3 42 3.4
850 44 3.5 44 3.7 44 3.8 43 3.4
5000 875 44 3.3 44 3.5 44 3.6 44 3.7
(1524) 900 44 3.2 44 3.3 44 3.4 44 3.5
925 44 3.0 44 3.1 44 3.2 44 3.3
725 42 3.2 42 3.3 42 3.4 42 3.5
5001 750 43 3.7 43 3.8 42 3.2 42 3.3
(1525) 775 43 3.4 43 3.5 43 3.7 43 3.8
to
6000 850 44 3.3 44 3.4 44 3.5 44 3.6
(1829) 875 44 3.1 44 3.2 44 3.3 44 3.4
6001 700 42 3.2 42 3.3 42 3.4 42 3.5
(1830) 725 43 3.6 43 3.7 43 3.8 42 3.3
to
7000 800 44 3.4 44 3.5 44 3.6 44 3.7
(2133) 825 44 3.2 44 3.3 44 3.4 44 3.5
825 44 3.5 44 3.6 44 3.7 44 3.8
900 44 2.9 44 3.0 44 3.1 44 3.2 675 42 3.4 42 3.5 42 3.6 42 3.8
850 44 3.0 44 3.1 44 3.2 44 3.3
ii
A11253A
63
Page 64
Table 20 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Cont.)
SINGLE-STAGE FURNACE
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2°/all000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE AVG, GAS SPECIFIC GRAVITY OF NATURAL GAS
RANGE HEAT VALUE 0.58 0.60 0.62 0.64
AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold
ft (m) _ No. Pressure No. Pressure No. Pressure No. Pressure
650 42 3.4 42 3.5 42 3.6 42 3.7
7001 675 43 3.8 42 3.2 42 3.3 42 3.4
--_ (2134) 700 43 3.5 43 3.7 43 3.8 42 3.2 O 725 44 3.8 43 3.4 43 3.5 43 3.6
___
= (2439) 675 43 3.5 43 3.6 43 3.7 42 3.2
0
__ 775 44 3,0 44 3,2 44 3,3 44 3,4
--_ (2744) 625 43 3.7 42 3.2 42 3.3 42 3.4 O 650 43 3.5 43 3.6 43 3.7 43 3.8
* Orifice numbers shown in BOLD are factory-installed.
to
8000 775 44 3.3 44 3.4 44 3.5 44 3.7
(2438) 800 44 3,1 44 3,2 44 3,3 44 3,4
8001 650 43 3.8 42 3.2 42 3.3 42 3.4
to
9000 750 44 3,3 44 3,4 44 3,5 44 3,6
9001 600 42 3.3 42 3.4 42 3.6 42 3.7
to 675 44 3,7 44 3,8 43 3.4 43 3.5
10000 700 44 3,4 44 3,5 44 3,7 44 3,8
_ 72_ 44 3._ 44
750 44 3.5 44 3.7 44 3.8 43 3.4
825 44 2,9 44 3,0 44 3,1 44 3,2 625 42 3.4 42 3.5 42 3.6 42 3.7
700 44 3,7 43 3.4 43 3.5 43 3.6 725 44 3,5 44 3,6 44 3,7 44 3,8
3,3 44 3.4 44 3,5
A11253 B
64
Page 65
SERVICE AND MAINTENANCE
PROCEDURES
FIRE, INJURY OR DEATH HAZARD Failure to follow this warning could result in personal
iniury, death and/or property damage. The ability to properly perform maintenance on this
equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not
attempt to perform any service and maintenance on this
equipment other than those procedures recommended in the
Owner's Manual.
ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental
pollution. Remove and recycle all components or materials (i.e. oil,
refrigerant, control board, etc.) before unit final disposal.
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death, or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and
install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in improper
furnace operation or failure of furnace. Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
General
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 2, you must revise your orientation to component location
accordingly.
Electrical Controls and Wiring
ELECTRICALSHOCK HAZARD Failure to follow this warning could result in personal iniury
or death. There may be more than one electrical supply to the furnace.
Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing. Lock out and tag switch with a suitable warning label.
The electrical ground and polarity for 115-v wiring must be properly maintained. Refer to Fig. 34 for field wiring information
and to Fig. 63 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from heating. The control system also requires an earth ground for proper operation of the control and flame-sensing electrode.
The 24-v circuit contains an automotive-type, 3-amp. fuse located on the control. (See Fig. 35.) Any shorts of the 24-v wiring during
installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp. fuse. The control
LED will display status code 24 when fuse needs to be replaced.
Troubleshooting Refer to the service label. (See Fig. 54--Service Label.)
The Troubleshooting Guide (See Fig. 62) can be a useful tool in isolating furnace operation problems. Beginning with the word "Start," answer each question and follow the appropriate arrow to
the next item. The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence. Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED (Light-Emitting Diode) to aid in installation, servicing, and
troubleshooting. Status codes can be viewed at the indicator in blower door. The amber furnace control LED is either ON
continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the
number of long flashes. For an explanation of status codes, refer to service label located on
control door or Fig. 54, and the troubleshooting guide which can be obtained from your distributor.
Retrieving Stored Fault Codes NOTE: Fault codes cannot be retrieved if a thermostat signal
(24-v on W, Y, G, etc.) is present, or if any delays such as blower off-delays are active.
The stored status codes will NOT be erased from the control memory when 115- or 24-v power is interrupted. See the Service
Label (Fig. 54) for more information. The most recent fault code may be retrieved as follows:
1. Leave 115-v power connected to furnace.
2. Observe the status LED through the blower door (the lower door on upflow applications) indicator. Refer to the Service
Label (Fig. 54) to interpret the LED.
3. Remove the Main/Control door (the upper door on upflow installations).
4. BRIEFLY disconnect and reconnect ONE of the main limit
wires.
5. The LED will flash the last stored fault code. Refer to the Service Label (Fig. 54) to interpret the LED.
6. A component test sequence will follow.
7. Reinstall the Main/Control door.
ii
65
Page 66
g
Component Self-Test NOTE: The furnace control component test allows all
components to run for a short time; except the gas valve and humidifier terminal HUM are not energized. The EAC-1 terminal
is energized when the blower is energized. This feature helps diagnose a system problem in case of a component failure. The component test feature will not operate if any thermostat signal is present at the control and not until all time delays are completed.
To Begin Component Self-Test:
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
Caution must be taken when manually closing this switch for service purposes.
ELECTRICALSHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower door switch opens 115-v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
4. For approximately 2 sec, short (jumper) the COM-24v terminal on control to the TEST/TWIN 3/16--in. (5 mm) quick-connect terminal on control until the LED goes off.
Remove jumper from terminals. (See Fig. 35.)
NOTE: If TEST/TWIN and COM-24v terminals are jumpered longer than 2 sec, LED will flash rapidly and ignore component test request.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step g of
component test sequence.
c. After 7 sec the hot surface igniter is energized for 15 sec.,
then off.
d. Blower motor operates on Continuous-FAN speed for 10
sec.
e. Blower motor operates on HEAT speed for 10 sec.
f. Blower motor operates on COOL speed for 10 sec.
g. Inducer motor stops.
5. Reconnect R lead to furnace control, remove tape from blower door switch, and re-install blower door.
6. Verify furnace shut down by lowering thermostat setting below room temperature.
7. Verify that furnace restarts by raising thermostat setting above room temperature.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/TWIN terminal. Verify that there is nothing plugged into the PLT
connector. (Note: If there is a jumper connector plugged into PLT, remove it and discard.) (See Fig. 35.)
3. Verify that the Blower/Heat Off Delay jumpers are set as desired. (See Fig. 35.)
4. Verify that the blower and control ("Main") doors are properly installed.
5. Verify that the Status LED glows. If not, check that the power supply is energized and that the blower door is
secure. (See Fig. 54.)
6. Cycle test furnace with room thermostat to be sure that it
operates properly with the room thermostat. Check all modes including Heat, Cool and Fan.
7. Check operation of accessories per manufacturer's instructions.
8. Review Owner's Manual with owner.
9. Attach entire literature packet to furnace.
Care and Maintenance
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal iniury, death and/or property damage.
Never store flammable or combustible materials on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline,
kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products. Exposure to these
materials could lead to corrosion of the heat exchangers.
For continuing high performance and to minimize possible furnace failure, periodic maintenance must be performed on this furnace.
Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal iniury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label
attached to the furnace.
CARBON MONOXIDE POISONING AND FIRE HAZARD
Failure to follow this warning could result in personal iniury, death and/or property damage.
Never operate furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration
device access doors removed.
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if required. Replace if torn.
66
Page 67
2.Checkblowermotorandwheelforcleanlinesseachheating andcoolingseason.Cleanasnecessary.
3.Checkelectricalconnectionsfortightnessandcontrolsfor properoperationeachheatingseason.Serviceasnecessary.
4.Inspectburnercompartmentbeforeeachheatingseasonfor rust,corrosion,sootorexcessivedust.If necessary,have
furnaceandburnerservicedbyaqualifiedserviceagency.
5.Inspecttheventpipe/ventsystembeforeeachheatingsea- sonforwaterleakage,saggingpipesorbrokenfittings.
Haveventpipes/ventsystemservicedbyaqualifiedservice agency.
6.Inspectanyaccessoriesattachedtothefurnacesuchasahu- midifierorelectronicaircleaner.Performanyserviceor
maintenancetotheaccessoriesasrecommendedintheac- cessoryinstructions.
Cleaning and/or Replacing Air Filter
The air filter type may vary depending on the application or orientation. The filter is external to the furnace casing. There are no
provisions for an internal filter with this furnace. See "Filter Arrangement" under the "Installation" section of this manual,
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never operate furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration
device access doors removed.
NOTE: If the filter has an airflow direction arrow, the arrow must point toward the blower. To clean or replace filters, proceed as follows:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal iniury or death, or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by spraying cold tap water through filter in opposite direction
of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended.
5. If equipped with factory specified disposable media filter, replace only with a factory specified media filter of the same
size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
The following items should be performed by a qualified service technician. Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove blower door.
3. All factory wires can be left connected, but field thermostat and accessory wiring may need to be disconnected depend-
ing on their length and routing.
4. If the vent and combustion air pipe passes through the
blower compartment, it will be necessary to remove the
pipes from the blower compartment.
Disconnect the vent and combustion air pipe by:
a. Loosen the clamps on the vent couplings and combustion
air pipe external to the furnace.
b. Separate the pipes from the couplings and move them
aside.
c. Loosen the clamps on the vent couplings and combustion
air pipe located on the blower shelf.
d. Separate the pipes from the blower compartment and set
aside.
e. Remove the couplings from the pipe adapters and set aside.
f. After servicing the blower, reverse steps a through e.
g. Tighten all clamps 15 lb -in.
See Fig. 60 for steps 5 through 14.
5. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace. Detach ground
wire and disconnect blower motor harness plugs from blower motor.
NOTE: Blower wheel is fragile. Use care.
6. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected.
7. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner. Do not
get degreaser in motor.
8. Reassemble motor and blower wheel by reversing items 7b through 7f. Ensure wheel is positioned for proper rotation.
9. Torque motor mounting bolts to 40 +/- 10 lb-in, when re- assembling.
10. Torque blower wheel set screw to 160 +/- 20 lb-in, when reassembling.
11. Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if necessary.
12. Spin the blower wheel by hand to verify that the wheel does not rub on the housing.
ii
67
Page 68
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower
deck.
15. Reconnect blower leads to furnace control. Refer to furnace wiring diagram, and connect thermostat leads if previously
disconnected.
NOTE: Be sure to attach ground wire and reconnect blower harness plugs to blower motor.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal iniury or death.
Blower door switch opens 115-v power to control. No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes.
16. Downflow or horizontal furnaces with vent pipe through furnace only:
a. Install and connect short piece of vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
17. Turn on electrical supply. Manually close blower door switch. Use a piece of tape to hold switch closed. Check for
proper rotation and speed changes between heating and cooling by jumpering R to G and R to Y/Y2 on furnace
control thermostat terminals. If outdoor temperature is be- low 70°F, turn off circuit breaker to outdoor unit before
running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle. (See Fig. 35.)
NOTE: If R-W/W1 thermostat terminals are jumpered at the time blower door switch is closed, blower will run for 90 sec before
beginning a heating cycle.
a. Perform component self-test as shown atthe bottom of the
SERVICE label, located on the control door.
b. Verify blower is rotating in the correct direction
18. If furnace is operating properly, RELEASE BLOWER DOOR SWITCH. Remove any jumpers or reconnect any
disconnected thermostat leads. Replace blower door.
19. Turn on gas supply and cycle furnace through one complete heating cycle. Verify the furnace temperature rise as shown
in Adjustments Section. Adjust temperature rise as shown in Adjustments Section.
Cleaning Burners and Flame Sensor The following items must be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:
NOTE: Use a back-up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to
the burner assembly.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal iniury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or
service. Follow the operating instructions on the label
attached to the furnace.
Refer to Fig. 61.
1. Disconnect power at external disconnect, fuse or circuit breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect the gas pipe from gas valve and remove pipe from the furnace casing.
6. Remove individual wires from terminals on gas valve.
7. Disconnect Hot Surface Igniter (HSI) wires from HSI.
8. Disconnect Flame Sensor wire from Flame Sensor.
9. Support the manifold and remove the 4 screws that secure the manifold assembly to the burner assembly and set aside.
Note the location of the green/yellow wire and ground ter- minal.
10. Inspect the orifices in the manifold assembly for blockages or obstructions. Remove orifice and clean or replace orifice.
11. Remove the four screws that attach the top plate of the cas- ing to the furnace.
12. Raise top plate up slightly and prop it up with a small piece of wood or folded cardboard.
13. Support the burner assembly and remove the screws that at- tach the burner assembly to the heat exchanger cell panel.
14. Remove wires from both rollout switches.
15. Slide one--piece burner out of slots on sides of burner- assembly.
16. Remove the flame sensor from the burner assembly.
17. (Optional) Remove the Hot Surface Igniter (HSI) and
bracket from the burner assembly.
18. Check igniter resistance. Nominal resistance is 40 to 70 ohms at room temperature and is stable over the life of the
igniter.
19. Clean burner with a brush and a vacuum.
20. Clean the flame sensor with fine steel wool (0000 grade). Do not use sand paper or emery cloth.
To reinstall burner assembly:
1. Install the Hot Surface Igniter (HSI) and bracket in burner assembly.
2. Install flame sensor on burner.
3. Align the edges of the one-piece burner with the slots in the burner assembly and slide the burners forward until they are
fully seated in the burner assembly.
4. Align the orifices in the manifold assembly with the support
rings on the end of the burner.
5. Insert the orifices in the support rings of the burners.
NOTE: If manifold does not fit fush against the burner, do not force the manifold on the burner assembly. The burners are not fully seated forward in the burner assembly. Remove the manifold
and check burner positioning in the burner assembly assembly
before re-installing the manifold.
6. Attach the green/yellow wire and ground terminal to one of the manifold mounting screws.
7. Install the remaining manifold mounting screws.
8. Check the igniter alignment. See Fig. 55, 56 and 61.
9. Attach the wires to the roll-out switches.
10. Align the burner assembly with the openings in the primary cell inlet panel and attach the burner assembly to the cell
panel.
11. Connect the wire for the flame sensor.
12. Connect the wire for the Hot Surface Igniter.
NOTE: Use propane-resistant pipe dope to prevent leaks. Do not use Teflon tape.
13. Install the gas pipe to the gas valve.
68
Page 69
FIREOREXPLOSIONHAZARD Failureto follow this warning could result in personal
iniury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal iniury or loss of
life.
14. Check for gas leaks with a commercially available soap solution made specifically for the detection of leaks.
15. Turn gas on at electric switch on gas valve and at external shut-off or meter
16. Turn power on at external disconnect, fuse or circuit break- er.
17. Run the furnace through two complete heating cycles to check for proper operation
18. Install control door when complete.
Servicing Hot Surface Igniter
The igniter does NOT require annual inspection. Check igniter resistance before removal. Refer to Fig. 55, 56 and 61.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. Igniter resistance is affected by temperature. Only check resistance when the igniter is at
room temperature.
a. Using an ohm meter, check resistance across both igniter
leads in connector.
b. Cold reading should be between 40 ohms and 70 ohms.
5. Remove igniter assembly.
a. Using a 1/4-in. driver, remove the two screws securing the
igniter mounting bracket to the burner assembly (See Fig. 61 .)
b. Carefully withdraw the igniter and bracket assembly
through the front of the burner assembly without striking the igniter on surrounding parts.
c. Inspect igniter for signs of damage or failure.
d. If replacement is required, remove the screw that secures
the igniter on igniter bracket and remove the igniter.
6. To replace igniter and bracket assembly, reverse items 5a through 5d.
7. Reconnect igniter harness to the igniter, dressing the igniter wires to ensure there is no tension on the igniter itself. (See
Fig. 61.)
8. Turn on gas and electrical supplies to furnace.
9. Verify igniter operation by initiating control board self-test feature or by cycling thermostat.
10. Replace control door.
Flushing Collector Box and Drainage System
ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal iniury,
death, and/or property damage. Turn off the gas and electrical supplies to the furnace and
install lockout tag before performing any maintenance or service. Follow the operating instructions on the label
attached to the furnace.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect pressure switch tube from pressure switch port.
NOTE: Ensure the pressure switch tube disconnected from the pressure switch is higher than the collector box opening or water
will flow out of tube.
4. Remove the collector box plug from the top port on the up- per corner of the collector box. (See Fig. 57)
5. Attach a funnel with a flexible tube to port on the collector
box.
6. Flush inside of collector box with water until discharge water from condensate trap is clean and runs freely.
7. Repeat steps 4 thru 6 with middle plug on upper corner of collector box.
8. Remove the pressure switch tube from the collector box.
NOTE: Do NOT blow into tube with tube connected to the pressure switch.
9. Clean pressure switch port on collect box with a small wire. Shake any water out of pressure switch tube.
10. Reconnect tube to pressure switch and pressure switch port.
11. Remove the relief tube from the port on the collector box and the trap.
12. Clean the relief port on collect box and the trap with a small wire. Shake any water out of the tube.
13. Reconnect relief tube to trap and collector box ports.
Cleaning Condensate Drain and Trap
NOTE: If the condensate trap is removed, a new gasket between the trap and collector box is required. Verify a condensate trap
gasket is included in the service kit or obtain one from your local distributor.
1. Disconnect power at external disconnect, fuse or circuit breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect external drain from condensate drain elbow or drain extension pipe inside the furnace and set aside.
6. Disconnect the condensate trap relief hose from collector box port and condensate trap.
NOTE: If condensate has a heat pad attached to the trap, trace the wires for the pad back to the connection point and disconnect the wires for the heat pad.
7. Remove the screw that secures the condensate trap to the collector box, remove the trap and set aside.
8. Remove the trap gasket from the collector box if it did not come off when the trap was removed.
9. Discard the old trap gasket.
10. Rinse condensate trap in warm water until trap is clean.
11. Flush condensate drain lines with warm water. Remember to check and clean the relief port on the collector box.
12. Shake trap dry.
13. Clean port on collector box with a small wire.
To re-install Condensate Drain and Trap:
1. Remove adhesive backing from condensate trap gasket
2. Install gasket on collector box
3. Align the condensate trap with the drain opening on the col- lector box and secure the trap with the screw
4. Attach the relief hose to the relief port on the condensate trap and collector box.
5. Secure tubing to prevent any sags or traps in the tubing.
6. Connect condensate drain elbow or drain extension elbow to the condensate trap
7. Connect the leads of the condensate heat pad (if used)
8. Connect external drain piping to the condensate drain elbow or drain extension pipe.
ii
69
Page 70
g
9. Turn gas on at electric switch on gas valve and at external shut-off or meter
10. Turn power on at external disconnect, fuse or circuit break- er.
11. Run the furnace through two complete heating cycles to check for proper operation
12. Install control door when complete.
Checking Heat Pad Operation (If Applicable) In applications where the ambient temperature around the furnace
is 32°F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it
will operate when low temperatures are present. NOTE: The Heat Pad, when used, should be wrapped around the
condensate drain trap. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Cleaning Heat Exchangers
The following items must be performed by a qualified service technician.
Primary Heat Exchangers If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure: NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem.
1. Turn off gas and electrical supplies to furnace.
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal iniury or death, or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal iniury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label
attached to the furnace.
3. Disconnect wires or connectors to flame rollout switch, gas valve, igniter, and flame sensor.
4. Using backup wrench, disconnect gas supply pipe from fur-
nace gas control valve.
5. Remove two screws attaching top filler plate and rotate up- wards to gain access to screws attaching burner assembly to
cell panel.
6. Remove screws attaching burner assembly to cell panel. (See Fig. 61.)
NOTE: Burner cover, manifold, gas valve, and burner assembly should be removed as one assembly.
7. Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 58.)
NOTE: After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
8. Reverse items 6 through 1 for reassembly.
9. Refer to furnace wiring diagram and reconnect wires to flame rollout switch, gas valve, igniter, and flame sensor.
10. Turn on gas and electrical supplies to furnace.
11. Check furnace operation through 2 complete heat operating cycles. Look at burners. Burner flames should be clear blue,
almost transparent. (See Fig. 59.)
12. Check for gas leaks.
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal
iniury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal iniury or loss of
life.
13. Replace main furnace door.
Secondary Heat Exchangers
The condensing side (inside) of the secondary heat exchanger
CANNOT be serviced or inspected without complete removal of the heat exchanger assembly. Detailed information on heat exchanger removal can be obtained from your Distributor.
WINTERIZATION
[]NIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in unit component or property damage.
If the furnace is installed in an unconditioned space where the ambient temperatures may be 32 ° F (0 ° C) or lower, freeze
protection measures must be taken to prevent minor property or product damage.
2. Remove control door.
7O
Page 71
Sincethefurnaceusesacondensingheatexchanger,somewater willaccunmlateintheunitasaresultoftheheattransferprocess.
Therefore,onceithasbeenoperated,itcannotbeturnedoffand leftoffforanextendedperiodoftimewhentemperatureswill reach32°F(0°C)or lowerunlesswinterized.Followthese
)rocedurestowinterizeyourfurnace:
2-in.
(50.0)
UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the
furnace and other property damage. Do not use ethylene glycol (automotive antifreeze coolant or
equivalent). Failure of plastic components may occur.
1. Obtain propylene glycol (RV/swinmfing pool antifreeze or equivalent).
2. Turn off gas and electrical supplies to your fllmace.
3. Remove fllmace control door.
4. Remove the top unused robber plug from the port on the collector box opposite the condensate trap. See Fig 57.
5. Connect a field supplied 3/8-in. (9.5-ram) ID tube to the open port on the collector box.
6. Insert a field supplied flmnel into the tube.
7. Pour 1 quart of anti-freeze solution into the flmnel/tube. Antifreeze should mn through the inducer housing, overfill
condensate trap and flow to an open drain.
8. Replace the robber plug in the port on the collector box.
9. Remove the nfiddle unused robber plug from the port on the collector box opposite the condensate trap. See Fig. 57.
10. Repeat Steps 5 through 8.
11. If a condensate pump is used, check with pump manufacturer to verify pump is safe for use with antifreeze used. Allow
pump to start and pump anti-freeze to open drain.
12. Replace main door.
13. When fllmace is re-started, flush condensate pump with clear water to check for proper operation before re-starting fllmace.
14. Propylene glycol need not be removed before re-starting furnace.
216-in,
_ (4.6)
/
Fig. 56 - Igniter Position - Side View
Fig. 57 - Priming Condensate Trap
2.5 mm +/-.75 ram)
Al1272
g
Al1392
0 o o L _0
)0 _0
(644)
Fig. 55 - Igniter Position - Top View
Al1405
71
Page 72
ii
Al1273
Fig. 58 - Cleaning Heat Exchanger Cell
Burner Flame
Burner
Manifold
Al1461
Fig. 59 - Burner Flame
72
Page 73
)MMET
MOTOR SHAFT FLAT _ / "_/-- BLOWER
SET SCREW /_ _ // /
TORQUE J _
BLO HSG ASSY
BRA(
BRACKET ENGAGEMENT
MOTOR ARM
W gEL
I _I,SCREW
SPECIAL
(REF)
SCREW
CHOKE, POWER (WHEN REQ'D
CUTOFF,
#
SCREW (GND)
Fig. 60 - Blower Assembly
BLOWER
HSG ASSY
MOTOR BLOWER
A11347
73
Page 74
BURNER ASSY
ii
BURNER SUPZ ASSY
IGNITER
BRACKET, IGNITER
FLAME ROLLOUT
SWITCH
'__.,,,, FLAME SENSOR
(BELOW BURNER)
Fig. 61 - Burner Assembly
A11403
74
Page 75
SEQUENCE OF OPERATION
NOTE: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow
wire routed to gas valve and manifold bracket screw. Using the schematic diagram in Fig. 63, follow the sequence of operation
through the different modes. Read and follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat (W), the control will start a 90-sec blower-only ON period two sec after
power is restored, if the thermostat is still calling for gas heating. The Amber LED light will flash code 12 during the 90-sec period, after which the LED will be ON continuous, as long as no faults are detected. After the 90-sec period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot-surface igniter HSI, and gas valve GV.
1. Heating (See Fig. 35 and 36 for thermostat connections.)
The wall thermostat "calls for heat," closing the R-to-W circuit. The furnace control performs a self-check, verifies
the pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM.
a. Inducer Prepurge Period- As the inducer motor IDM
comes up to speed, the low pressure switch contacts LPS close to begin a 15-sec prepurge period. The high pressure
switch contacts HPS are ignored until one minute after the gas valve closes.
b. Igniter Warm-Up- At the end of the prepurge period, the
Hot-Surface igniter HSI is energized for a 17-sec igniter warm-up period.
c. Trial-for-Ignition Sequence- When the igniter warm-
up period is completed, the main gas valve relay contacts GVR close to energize the gas valve GV, the gas valve opens, and 24 vac power is supplied for a field-installed
humidifier at the HUM terminal. The gas valve GV permits gas flow to the burners where it is ignited by the HSI. Five
sec after the GVR closes, a 2-sec flame proving period be- gins. The HSI igniter will remain energized until the flame
is sensed or until the 2-sec flame proving period begins.
d. Flame-Proving- When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control CPU begins the blower-ON delay period and continues to
hold the gas valve GV open. If the burner flame is not proved within two sec, the control CPU will close the gas
valve GV, and the control CPU will repeat the ignition se- quence for up to three more Trials-For-Ignition before go-
ing to Ignition-Lockout. Lockout will be reset automatic- ally after three hours or by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power
at SEC1 or SEC2 to the furnace control CPU (not at W, G, R, etc.). If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode
and operate the inducer motor IDM until flame is no longer proved.
e. Blower-On Delay- If the burner flame is proven, the
blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized.
Simultaneously, the electronic air cleaner terminal EAC-1 is energized and remains energized as long as the blower
motor BLWM is energized.
f. Blower-Off Delay- When the thermostat is satisfied, the
R-to-W circuit is opened, de-energizing the gas valve GV,
stopping gas flow to the burners, and de-energizing the hu- midifier terminal HUM. The inducer motor IDM will re-
main energized for a 15-sec post-purge period. The blower motor BLWM and air cleaner terminal EAC- 1 will
remain energized for 90, 120, 150, or 180 sec (depending on the blower-OFF delay selection). The furnace control
CPU is factory-set for a 120-sec blower-OFF delay.
2. Cooling Mode The thermostat "calls for cooling."
a. Single-Speed Cooling
(See Fig. 35 and 36 for thermostat connections) The thermostat closes the R-to-G-and-Y circuits. The
R-to- Y circuit starts the outdoor unit, and the R-to-
G-and-Y/Y2 circuits start the furnace blower motor BLWM on COOL speed. The electronic air cleaner terminal EAC-1 is energized
with 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y cir-
cuits are opened. The outdoor unit will stop, and the fur- nace blower motor BLWM will continue operating on the
COOL speed for an additional 90 sec. Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5 sec. (See Fig.
35.)
b. Two-Speed Cooling
(See Fig. 35 and 36 for thermostat connections.) The thermostat closes the R-to-G-and-Yl circuits for
low-cooling or closes the R-to-G-and-Yl-and-Y2 cir- cuits for high-cooling. The R-to-Yl circuit starts the out-
door unit on low-cooling speed, and the R-to-G-and-Yl circuit starts the furnace blower motor BLWM on low-cool
speed (same speed as FAN). The R-to-Yl-and-Y2 cir- cuits start the outdoor unit on high-cooling speed, and the R-to-G and- Y/Y2 circuits start the furnace blower motor
BLWM on COOL speed. The electronic air cleaner terminal EAC-I is energized
with 115 vac whenever the blower motor BLWM is operat- ing.
When the thermostat is satisfied, the R-to-G-and-Yl or R-to-G-and-Yl and Y2 circuits are opened. The outdoor
unit stops, and the furnace blower BLWM and electronic
air cleaner terminal EAC-I will remain energized for an
additional 90 sec. Jumper YI to DHUM to reduce the cool- ing off-delay to 5 sec. (See Fig. 35.)
3. Dehumidification Mode (See Fig. 35 and 36 for Thermidistat connections.)
The dehumidification output, D or DHUM from a thermo- stat should be connected to the furnace control thermostat
terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is re-
moved from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned
ON when no dehumidify demand exists. Once 24 vac is de- tected by the furnace control on the DHUM input, dehumid-
ification capability is activated. If the DHUM is removed for more than 48 hr, the furnace control reverts back to non-dehumidification mode.
The cooling operation described in item 2. above also ap- plies to operation with a Thermidistat. The exceptions are
listed below:
a. When the R-to-G-and-Yl circuit is closed and there is a
demand for dehumidification, the furnace blower motor BLWM will continue running at low-cool speed (same
speed as FAN).
b. When the R-to-G-and-Y/Y2 circuit is closed and there
is a demand for dehumidification, the furnace blower mo- tor BLWM will drop the blower speed from COOL to
HEAT for a maximum of 10 minutes before reverting back to COOL speed. If there is still a demand for dehumidifica-
ii
75
Page 76
tion after 20 minutes, the furnace control CPU will drop the blower speed back to HEAT speed. This alternating 10-
minute cycle will continue as long as there is a call for cool- ing.
c. When the "call for cooling" is satisfied and there is a de-
mand for dehumidification, the cooling blower-off delay is decreased from 90 sec to 5 sec.
4. Continuous Blower Mode When the R-to-G circuit is closed by the thermostat, the
blower motor BLWM will operate on continuous-blower speed (can be adjusted to FAN, HEAT, or COOL speed) at
the thermostat. Factory default is FAN speed. Terminal EAC-1 is energized as long as the blower motor BLWM is
energized. During a call for heat, the blower BLWM will stop during igniter warm-up (17 see), ignition (7 see), and
blower-ON delay (25 see), allowing the furnace heat ex- changers to heat up more quickly, then restarts at the end of
the blower-ON delay period at HEAT speed. In heating, the furnace control CPU will hold the blower
ii
motor BLWM at HEAT speed during the selected blower- OFF delay period before reverting to continuous-blower speed. When the thermostat "calls for low-cooling," the
blower motor BLWM will switch to operate at low-cool speed (same speed as FAN). When the thermostat is satis-
fied, the blower motor BLWM will operate an additional 90 sec on low-cool speed (same speed as FAN) before revert-
ing back to continuous-blower speed. When the thermostat "calls for high-cooling', the blower
motor BLWM will operate at COOL speed. When the ther- mostat is satisfied, the blower motor BLWM will operate an
additional 90 sec on COOL speed before reverting back to continuous-blower speed.
When the R-to-G circuit is opened, the blower motor BLWM will continue operating for an additional 5 sec, if no other function requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat
-To select different continuous-blower speeds from the room thermostat, momentarily turn off the FAN switch or
push button on the room thermostat for 1-3 sec after the blower motor BLWM is operating. The furnace control
CPU will shift the continuous-blower speed from the fact- ory setting of FAN to HEAT speed. Momentarily turning
off the FAN switch again at the thermostat will shift the continuous-blower speed from HEAT to COOL. Repeating
the procedure will shift the continuous-blower speed from COOL to FAN speed. The selection can be changed as
many times as desired and is stored in the memory to be automatically used following a power interruption.
5. Heat pump (See Fig. 35 and 36 for thermostat connections.) When in-
stalled with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times
during demand defrost cycles. When the R-to- W-and-Y1 or R-to-W-and-Yl-and-G circuits are energized the fur-
nace control CPU will switch to or turn on the blower motor BLWM at HEAT speed, and begin a heating cycle. The
blower motor BLWM will remain on until the end of the
prepurge period, then shut off for 24 sec then come back on at HEAT speed. When the W input signal disappears, the
furnace control begins a normal inducer post-purge period and the blower remains running at HEAT speed for the se- lected blower-OFF delay period then switches to low-cool
speed (same speed as FAN). If the R-to-W-and-Yl-and- G signals disappear at the same time, the blower motor
BLWM will remain on for the selected blower-OFF delay period. If the R-to- W-and-Y1 signals disappear, leaving
the G signal, the blower motor BLWM will remain on for the selected blower-OFF delay period then switch to con-
tinuous-blower speed. When the R-to-W-and-Y/Y2, R-to-W-and-Y/Y2-and-G, R-to-W-and-Yl-and-
Y/Y2, or R-to-W- and-Yl-and-Y/Y2-and-G circuits are
energized the furnace control CPU will switch to or turn on the blower motor BLWM at HEAT speed, and begin a heat-
ing cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 sec then
come back on at HEAT speed. When the W input signal dis- appears, the furnace control begins a normal inducer post-
purge period and the blower switches to COOL speed after a 3 sec delay. If the R-to-W-and-Y/Y2-and-G or R-to-
W-and-Yl-and -Y/Y2-and-G signals disappear at the same time, the blower motor BLWM will remain on for the
selected blower-OFF delay period. If the R-to-W-and-
Y/Y2 or R-to-W-and-Yl-and-Y/Y2 signals disappear,
leaving the G signal, the blower motor BLWM will remain on for the selected blower-OFF delay period then switch to
continuous blower speed.
Component Self-Test
Refer to page 66 for instructions.
76
Page 77
START
Is LED status light on? }.L_
YES
Kith
Troubleshooting Guide
Is there 115V at L1 and L2?
_l YES
i s there 24V at SECq and SECt2?
I YES
[ Replace furnace control. 1
Is door switch closed?
_! YES
i Is there 115V going to switch?
!! YES
Replace door switch.
._ Is door switch closed?
Is circuit breaker closed?
l Check for continuity in wire from circuitbreaker to furnace.
1
NO
H-
YES
Is LED status light blinking rapidly without
I a pause? I "1
r j YES [
Check for correct line voltage polarity. If units are twinned, check for proper low- voltage (24V) transformer phasing.
-._ Replace transformer.
Close circuit breaker and go back toSTART.
F
NO [
slowly with a combination of short and
Is LED status light blinking ON/OFF INO
long flashes?
i
Determine status code. The status code is a 2 digit number with the first digit
determined by the number of short
"-4 "-4
flashes and the second digit by the
number of long flashes?
d_ d_
I YES
b-.
To recall status code briefly remove and reconnect one RED wire from the draft safeguard switch to display stored status code. You can also recall
the previous status code by momentarily shorting the TEST/TWiN terminal to Com24V terminal until the LED goes out. LED will flash the status code of the previous fault or status code #11 (1 short and 1 long flash) if there was no previous fault. After the control repeats the code 4 times the control will go through a brief component test sequence. The
inducer will start and run for the entire component test. The HSl, blower motor FAN speed (AMBER LED boards only) HEAT speed, and COOL speed will run for 10 15 seconds each. Gas valve and humidifier will not
be turned on.
interconnecting cable.
I heck room thermostat or
l.o
¢b
r,"
that was flashed.
Go to section below for the status code
._ Was there a previous status code otherthan #11 ?
!_ oes the control respond to W, Y1 (if
present), Y/Y2, and G (24V) thermostat signals?
i YES
cycle to check operation. Status codes Run system through a heating or cooling
are erased after 72 hours.
1_ Is 24V present at W, Y1 (if present), Y/Y2
or G thermostat terminals on the furnace control?
I YES
the furnace control.
i isconnect all the thermostat wires from
l
Replace furnace control.
_ Does the problem repeat when using a
jumper wire?
_! NO
The thermostat is not compatible with the furnace control. Either install a ballast
resistor, connect the Com24V thermostat
co EB
terminal to the thermostat, or replace the thermostat.
Page 78
NO PREVIOUS CODE - Stored codes are erased after 72 hours. Run system
through a heating or cooling cycle to check system.
12 BLOWER ON AFTER POWER UP -
(115V OR 24V) - Normal operation. Blower runs for 90 seconds, if unit is
powered up during a call for heat (R-W closed) or when (R-W opens) during the blower on-delay period.
13 LIMIT CIRCUIT LOCKOUT - Lockout
occurs if the limit or flame rollout is open longer than 3 minutes. Control will auto-
reset after 3 hours. See code 33.
14 IGNITION LOCKOUT - System failed to
ignite gas and prove flame in 4 attempts. Control will auto-reset after 3 hours. See
status code 34.
_o
..q oo
o
21 GAS HEATING LOCKOUT - Turn off
power and wait 5 minutes to retry. Check for:
- Stuck closed gas valve relay on control.
- Miswire or short to gas valve wire.
22 ABNORMAL FLAME-PROVING SIGNAL
Flame is proved while gas valve is de- energized. Inducer will run until fault is cleared. Check for:
- Stuck open or leaky gas valve.
23 PRESSURE SWITCH DID NOT OPEN -
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for:
- Short circuit in secondary voltage (24V) wiring including thermostat leads.
Disconnect thermostat leads to isolate short circuit.
31 LPS or HPS PRESSURE SWITCH DID
NOT CLOSE OR REOPENED - If opens during blower on-delay period, blower will come on for the selected blower off-delay.
If LPS opens longer than 5 minutes,
inducer shuts off for 15 minutes before retry. If HPS remains open for one minute
after gas valve closes the furnace will shut down and retry. If HPS fails to close on three successive cycles the furnace will lockout for 3 hrs before retry.
Check for:
- Proper vent sizing.
- Air leak between vestibule and blower compartment.
- Low inlet gas pressure (if LGPS used).
- Disconnected or obstructed pressure tubing.
- Defective or miswired pressure switches
- Excessive wind.
- Plugged condensate drain
- Water in vent piping, possible sagging
pipe
- Restricted vent.
- Defective Inducer motor.
- Low inducer voltage (115 VAC)
33 LIMIT CIRCUIT FAULT - Indicates the
limit, flame rollout is open. Blower will run
for 4 min. or until open switch remakes whichever is longer. If open longer than 3
min, code changes to lockout #7. If open less than 3 min. status code #4 continues
to flash until blower shuts off. Flame
rollout switch requires manual reset.
Check for:
- Loose blower wheel.
- Defective switch or connections.
- Dirty filter or restricted duct system.
- Improper gas input adjustment
- Improper limit switch or no limit gasket.
34 IGNITION PROVING FAILURE - If flame
is not sensed during the trial for ignition
period, the control will repeat the ignition sequence 3 more times before lockout #14 occurs. If flame signal is lost during the
blower on-delay period, blower will come on for the selected blower off-delay.
Check the following items first before
proceeding to the next step.
- Gas valve turned off.
- Manual shut-off valve.
- Green/Yellow wire MUST be connected
to furnace sheet metal.
- Flame sensor must not be grounded. To determine whether the problem is in the gas valve, igniter, or flame sensor the
system can be operated in the component test mode to check the igniter. First
remove the R thermostat connection from the control and initiate the component test
sequence. Does the igniter glow orange/white by the end of the 15 second
warm-up period?
Y --s
Unplug igniter harness from control and initiate another component test
sequence. Check for 115V between pin 1 and NEUTRAL-L2 on the control. Was
115V present for the 15 second period?
Reconnect the R thermostat lead and set thermostat to call for heat. Connect voltmeter across gas valve connections. Does gas valve receive 24V?
flow?
I Does gas valve open and allow gas to
YES
I DO the main burners ignite?
I YES
I Uothe main burners on?
stay
No
sensor current during trial for ignition
I Repeat call for heat and check flame INOI
period. Is the DC microamps below 0.5?
_ YES
and recheck current. Nominal current is
4.0 to 6.0 microamps.
I Clean flame sensor with fine steel wool I
I s current near typical value?
YES
I ill main burners ignite and stay on?
YES
. I
m
I
,NO,
YES
[Fixed. l
45 CONTROL CIRCUITRY
LOCKOUT Auto-reset after 1 hour lockout due
to:
- Flame circuit failure.
- Gas valve relay stuck open.
- Software check error. Reset power to clear
lockout. Replace
control if code repeats.
Replace furnace control.
Check for continuity in the
YES
harness and igniter. Replace defective component.
NO
Check connections. If OK,
..-q
replace control.
Check that all gas valves are turned on. Replace valve.
Check for:
- Inadequate flame carryover or rough ignition.
- Low inlet gas pressure.
- Proper firing rate.
Allow blower to come on and
repeat test to check for intermittent operation.
Check connections and retry. If current is near typical value
(4.0-6.0 nominal) and burners
will not stay on, replace
control.
Replace electrode. ]
Replace furnace control. ]
Page 79
/
SEC.-2SEC-1
EAC-2 L2
CONNECTION DIAGRAM
PL1
NOTE #10
BLK 7 BRN BRN
BLK
WHT
LGPS
(WHENUSED)
.... 7
NOTE #101
F-YEL ..... I
CAP -2
SCHEMATIC DIAGRAM
TO115MACFIELD DISCONNECT NOTE#2 /_ EQUIPMENT GROUND
2
L1
DR
SLWR
BFANR
PL2
EAC-1
/
PL5
BLWM
PL7
EAC-2B
PL1-6 FUSE TRAN
L2
L2
L2
!=:=
H
_Z:_ I_ WHT (COM)--
p i
RED(FAN) 1 _ _ I
ORG(SPARE)2 _ / _ li
BLU(HEAT)3 _ / X _
-- BLK L
- GRNHELG
___GRY COOL 5
_PL7
PL7
BLK
/
BLK
I
ILK
GND" = -- I
WHT--
FUSEOR CIRCUIT
BREAKER & DISCONNECT
SWITCH(WHENREQD)
NOTE #2
r........ i NEUTRAL
i
H
21
L_______J
WIll
NOTES:
1. If anyof theoriginal equipment wire is repbced use wire rated for 105°C.
2. Use only copper wire between the disconnect switch andthe furnace junction box (JB).
3. This wire must be connected to furnace sheet metal for control to prove flame.
4. Symbolsare electrical representation only.
5. Solid lines inside PCB are printed circuit board conductors and are not included in legend.
6. Replaceonly with a 3 amp fuse.
7. Inducer(IDM) motor contains internal auto-reset thermal overload switches(OL).
8. L2 connections are interchangeable within the L2 connector block.
9. Blower motorspeed selections are for average conditions, see installation instructions for details on optimum speed selection.
10. Factory connected when LGPS is not used.
11.Ignition lockout will occurafterfour consecutive usuccessful trials for ignition. Controlwill auto-reset after three hours.
12. Blower-on delay: gas heating 25 seconds, cooling or heat pump 2seconds.
13. Blower-off delay: gas heating selections are 90, 120, 150 or 180 seconds, coolingor
heat pump 90 seconds or 5 secondswhen DHUM is active.
14. BLWM is locked - rotor overload protected by redundant electronic control circuits.
15. Inductor (When Used).
Fig. 63 - Wiring Diagram
t
FURNACETYPE ,_t:_) " I_FS E
BACKWARDCOMPATIBLE_:::>> PL1-11 |
L -o- JUNCTIONTERMINAL _ FACTORYPOWERWlRING(115VAC) E 0 CONTROLTERMINAL FACTORYCONTROLWIRING(24VAC)
G Imam PCBCONTROLTERMINAL .... FIELDCONTROLWIRING(24VAC)
E _ FIELDEARTHGROUND CONDUCTORONCONTROL
N -_ _ FIELDWIRINGSCREWTERMINALEQUIPMENTGROUND -4 e= PLUGRECEPTACLE
BFANR CONTINUOUS-FANSELECTRELAY,SPDT J1 BLOWER-OFFDELAYJUMPER BHT/CLR BLOWERMOTORSPEEDCHANGERELAY,SPDT SELECTOR
BLWR BLOWERMOTORRELAY,SPST-{N.O.) JB JUNCTIONBOX BLWM BLOWERMOTOR,PERMANENT-SPLIT-CAPACITOR LED LIGHT-EMITTINGDIODEFOR CAP CAPACITOR STATUSCODES-AMBER
CPU MICROPROCESSORANDCIRCUITRY LGPS LOWGASPRESSURESWITCH, EAC-1 ELECTRONICAIRCLEANERCONNECTION SPST-(N.O.)
115VAC1.0AMPMAX.) LPS COLLECTORBOXPRESSURE
EAC-2 ELECTRONCARCLEANERCONNECTON SWITCH,SPST(N.O.)
(COMMON) LS LIMITSWITCH,AUTO-RESET,
FRS1,2 FLAMEROLLOUTSW.-MANUALRESET, SPSTN.C.)
SPST-(N.C.) PCB PRNTEDC RCUTBOARD
FSE FLAME-PROVINGELECTRODE CONTROL FU1 FUSE,3AMP,AUTOMOTIVEBLADETYPE, PL1 11-CIRCUITPCBCONNECTOR
FACTORYINSTALLED PL2 2..CIRCUITCONNECTOR
FU2 FUSEORCIRCUITBREAKERCURRENT PL3 2..CIRCUITHSI,CONNECTOR
INTERRUPTDEVICE(FIELDINSTALLED&SUPPLIED) PL4 3-CIRCUITIDM,CONNECTOR
GND EQUIPMENTGROUND PL5 5,.CIRCUITBLWMSPEEDTAP GV GASVALVE-REDUNDANT CONNECTOR
GVR1,2 GASVALVERELAY,DPST..{N.O. PL6 #.CIRCUITBLWMPOWER HPS INDUCERHOUSINGPRESSURESWITCH,SPST(N.O.) CONNECTOR
HSI HOTSURFACEIGNITER(I15VAC) PL7 1-CIRCUITINDUCERSPLICE HSIR HOTSURFACEIGNITERRELAY,SPST-(N.O.) CONNECTOR
HUM 24VACHUMDIFIERCONNECTION(0.5AMP.MAX.) TEST_IN COMPONENTTEST&TWlN IDM INDUCEDDRAFTMOTOR,PSC TERMINAL
IDR INDUCEDDRAFTMOTORRELAY,SPST-(N.O,) TRAN TRANSFORMER-115VAC/24VAC ILK BLOWERACCESSPANELINTERLOCK
SWITCH,SPST-(N.O.)
IND INDUCTOR(SEENOTE#16) 33831 1-2 Rev. C
PL1 1 NOTE #3
,_:::>>-- PLI-9_
, >-- PL1-7_
Al1409
79
Page 80
PARTS REPLACEMENT INFORMATION GUIDE
ii
Casing Group
Blower door
Bottom plate Control door
Door knob assembly Top filler plate
Electrical Group
3-Amp fuse Circuit board
Control box Door switch
Junction box Linfit switch(es)
Transformer
Blower Group Blower housing
Blower motor Blower wheel
Capacitor (when used) Capacitor strap (when used)
Cut-off plate Power choke (where used)
Filter Group Filter(s)
Media Cabinet (when used)
Gas Control Group
Burner
Flame sensor
Gas valve
Hot surface igniter Manifold
Orifice
Heat Exchanger Group
Containment plate
Coupling box Heat exchanger assembly Primary HX cell panel
Secondary HX assembly Tubing gaskets
Inducer Group
Collector box
Condensate trap
Condensate trap elbow
Gaskets Inducer
Inducer assembly Inducer motor capacitor (when used)
Inducer motor module (when used) Pressure switch(es)
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under "Heating Equipment" or "Air Conditioning Contractors and Systems" headings for dealer listing by brand name or contact:
CARRIER CORPORATION
Consumer Relations Department
P.O. Box 4808
Syracuse, New York 13221
1 - 800 - CARRIER
Have available the model number, series number, and serial number located on the unit rating plate to ensure correct replacement part.
Model Nomenclature
MODEL MOTOR WIDTH VOLTAGE MINOR SERIES AIRFLOW
59SP5A 120 E 24 .... 22
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation, personal injury, death or property damage.
Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, or death. Consult a qualified installer, service agency, or your local gas supplier for information or assistance. The qualified installer or service agency
must use only factory-authorized replacement parts, kits, or accessories when modifying this product.
HEATING COOLING
SIZE (CFM)
Copyright 2011 Carrier Corp. * 7310 W. Morris St. * Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 08/11
Manufacturer reserves the right to change, at any time, specification8 and design8 without notice and without obligations,
80
Catalog No: 59SP5A-03SI
Replaces: 59SP5A- 02Sl
Loading...