Carrier 58PAV User Manual

Page 1
58PAV
HEATING A COOLING
Upflow Induced-Combustion Furnaces
Installation, Start-Up, and Operating Instructions
Sizes 035-125,
NOTE: Before beginning the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY.
SAFETY CONSIDERATIONS
Untrained personnel can perform basic maintenance func tions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, tags, and labels attached to or shipped
with the unit and other safety precautions that may apply. Follow all safety codes. In the United States, follow all
safety codes including the National Fuel Gas Code NFPA No. 54-1988/ANSI Z223.1-1988. In Canada, refer to the cur rent edition of the National Standard of Canada CAN/CGA­B149.1- and .2-M86 Natural Gas and Propane Gas Installa tion Codes. Wear safety glasses and work gloves. Have fire extinguisher available duriag startup and adjustment pro cedures and service calls.
Recognize safety information: This is the safety-alert symognize
A. VI
bol A. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for per sonal injury.
Understand the signal word—DANGER, WARNING, or CAUTION. These words are used with the safety-alert sym bol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING
signifies a hazard that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and prop erty damage.
Table 1—Minimum Clearances From
Combustible Materials (In Ins.)
Size Sides—Single-Wall Vent 1 0
Type B-1 Double-Wall Vent Back Top of Plenum Vent Connector—Single-Wall Vent
Type B-1 Double-Wall Vent
Front—Single-Wall Vent
Type B-1 Double-Wall Vent Service
NOTES:
1. Provide 30-in. front clearance for servicing. An open door in front of the furnace can meet this requirement.
2. A minimum clearance of 3 ins. must be provided in front of the furnace for combustion air and proper operation.
035 and 055 075 thru 125
0 0 0 0 1 1 6 6
1 1 6 6
3 ■ 3
30 30
These instructions cover minimum requirements and con form to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residentieil construction practices.
We require these instructions as a minimum for a safe
installation.
INTRODUCTION
The design of the upflow gas-fired furnace is A.G.A./CGA certified for natural and propane gas and for instaUation on combustible flooring, in alcoves, attics, basements, closets, or utility rooms. The design of this furnace line is not A.G.A./CGA certified for installation in mobile homes, rec reation vehicles, or outdoors.
Before instalhng the furnace, refer to the current edition of the National Fuel Gas Code NFPA No. 54-1988/ANSI Z223.1-1988. Canadian installations must be installed in accordance with CAN/CGA.B149 Installation Codes and aU authorities having jurisdiction. For further information, the National Fuel Gas Code is available from National Fire Protection Association Inc. Batterymarch Park, Quincy, MA 02269, American Gas Association, 1515 Wilson Boule vard, Arlington, VA 22209, or from Literature Distribution.
Installation must conform to the regulations of the serving gas supplier and the local building, heating, and plumbing codes in effect in the area in which the installation is made, or in the absence of local codes, with the requirements of the National Fuel Gas Code.

A CAUTION

Application of this furnace should be indoors with spe cial attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause premature component failure.
This furnace is designed for a minimum continuous return air temperature of 60 degrees F DB or an intermittent oper ation down to 55 degrees F DB such as when used with a thermostat night setback. Return air temperature must not exceed a maximum of 85 degrees F DB.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book] 1 I 4 PC 101 Catalog No. 565-913 Printed in U.S.A. Form58PA-1SI Pg 1 5-90 Replaces: New Tab 16a i 8a
Page 2
RETURN AIR.
Fig. 1 —Dimensional Drawing

A WARNING

Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poison ing, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier or your distributor or branch for information or assistance. The qualified installer or agency must use only factory authorized and fisted kits or accessories when modifying this product. A failure to foUow this warning can cause electrical shock, fire, personal injury, or death.
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove aU shipping brackets and materials before operating the furnace.
I. LOCATION A. General

A CAUTION

Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are adhered to, in addition to eiU local codes and ordinances.
Do not use this furnace during construction when adhe sives, sealers, and/or new carpets are being installed. If the fm-nace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which will cause corrosion of the heat
exchangers and metal vent system. Some of these com pounds are: paneling and dry waU adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.
Locate the furnace close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearemces shown on the unit rating plate. This furnace shall not be installed directly on carpeting, tüe, or any combustible material other than wood flooring.
Table 2—Dimensions (In Ins.)
Vent Conn
Size 035-EC 035-GC 14-3/16 12-9/16
055-EC 14-3/16 12-9/16 055-GC 14-3/16 12-9/16 075-GC 17-1/2 15-7/8 075-JC 21 090-GC 090-JC 21 090-LC 24-1/2 22-7/8 23 110-JC 110-LC 24-1/2 22-7/8 23 125-LC
A D
14-3/16 12-9/16
17-1/2
21
24-1/2
19-3/8 15-7/8 19-3/8
19-3/8 22-7/8
E 12-11/16 12-11/16 12-11/16 12-11/16
16
19-1/2
16
19-1/2 19-1/2
23
4 4 4 126 4 128 4 143 4 147 4 153 4 159 4 176 5 5 5 196
B. Location With Respect to Cooling Equipment
The coofing coil must be installed parallel with, or on the downstream side of, the furnace to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or fuU-cool position.
C. Hazardous Locations
When the furnace is installed in a residential garage, it must be installed so that the burners and ignition source are located no less them 18-ins. above the floor. Also, the fur nace should be protected from physical damage by vehicles.
When a furnace is installed in public garages, airplane han gars, or other buildings having hazardous atmospheres, the unit must be installed in accordance with the recommended good practice requirements of the National Fire Protection Association, Inc.
II. AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-1988, or applicable provisions of the local building codes.
Canadian installations must be installed in accordance with CAN/CGA.B149 Installation Codes, and aU authorities hav ing jurisdiction.
Ship. Wt
116 118
171 186

A CAUTION

Air for combustion must not be contaminated by halo gen compounds, which include fluoride, chloride, bro mide and iodide.
These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
AU fuel burning equipment must be supplied with air for combustion of the fuel. Sufficient air MUST be provided to insure there wfll not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct puUing air from the burner area and draft safeguard opening.

A CAUTION

The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a negative pressure condition at the furnace. Make up air must be provided for the ventilation devices, in addition to that required by the furnace.
WA
Page 3
Combustion air requirements are determined by whether the fiunace is in an UNCONFINED or CONFINED space. A confined space is a space whose volume is less than 50 cubic ft per 1000 Btu per hour of the total output rating for aU appliances installed in that space.
I
A. Unconfined Space
An unconfined space must have at least 50 cubic ft for each 1000 Btuh of input for all the appliances (i.e. furnaces, clothes dryer, water heaters, etc.) in the space.
For Example:
Minimum Sq Ft
58PAV Furnace
Input Btuh
with
7-1/2 Ft Ceiling
1. All air from inside the structure Each opening MUST have at least 1 square in. of free area per 1000 Btuh of the total input for all equipment within the confined space, but not less than 100 square ins. per opening. See Fig. 2.
For Example:
58PAV Furnace
Input Btuh
Free Area per Opening
(square ins.) 44,000 100 66,000 100 88,000 100
110,000 110 132,000
132
154,000 154 44,000 293 66,000
88,000 587
110,000 132,000 154,000
If the unconfined space is of unusually tight construction, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the out doors. Combustion and ventilation openings must be sized the same as for a confined space. A minimum opening hav ing a total of not less than 1 square in. per 5000 Btuh of total input rating for all equipment must be provided. Return air must not be taken from the room, unless an equal or greater eimount of air is supplied to the room.
B. Confined Space
A confined space MUST have two permanent openings, one within 12-ins. of the ceiLing, and the other within 12-ins. of the floor. See Fig. 2.
NOTE: In deterniining the free area of an opening, the blocking effect of the louvers, grilles and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 per cent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
The size of the openings depend upon whether the air comes from inside or outside of the structure.
SUPPLY
AIR
r~Hn
VENT TO ROOF
12 MAX
440
733 880
1026
If the building is of unusually tight construction, a perma nent opening directly communicating with the outdoors shall be provided. This opening shall have a minimum free area of 1 square in. per 5000 Btuh of total input rating for all equipment in the enclosure.
If the furnace is installed on a raised platform to provide a return air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, aU air for combus tion must come from outdoors.
2. All air from outdoors a. If combustion air is taken from outdoors through
vertical ducts, the openings and ducts MUST have at least one square inch of free area per 4000 Btuh of the total input for aU equipment within the con fined space. See Fig. 3.
For Example:
58PAV Furnace
input Btuh
44,000 66,000
88,000 110,000 132,000 154,000
Free Area per Opening
(square ins.)
11.0 4
16.5 5
22.0 6
27.5 6
33.0 7
38.5 7
Round Pipe
(ins. dia)
b. If combustion air is taken from the outdoors through
horizontal ducts, the openings and ducts MUST have at least one square in. of free area per 2000 Btuh of the
1 so INCH PER 4000 BTUH
I'. ".I
T TO ROOF
MAX 12
1 SQ INCH PERT 2000 BTUH
DUCTS TO ROOF-
SUPPLY D
AIR
A A VENT
^ 1 SQ INCH
PER 1000
I BTUH*
INTERIOR HEATED SPACE
-6 MIN
(FRONT)
♦Minimum opening size is 100 square ins. tMinimum of 3 ins. when type-B vent is used.
Fig. 2
A89012
DUCTS TO OUTS DE
1 SQ INCH PER
2000 BTUH ^
MAX 12
A
RETURN AIR
USE ANY OF THE FOLLOWING COMBINATIONS OF OPENINGS: A&B C&D D&E
j

Fig-3

,^PER 4000
DUCT TO OUTSIDE
i
2 MAX
1 SQ INCH
BTUH
A89013
Page 4
total input for all equipment within the confined space.
For Example:
58PAV Furnace
Input Btuh
44,000 66,000
88,000 44.0 110,000 132,000 66.0 154,000
Free Area per Opening
(square ins.)
22.0
33.0
55.0
77.0
Round Pipe
(ins. dia)
6 7 8
9 10 10
When ducts are used, they must be of the same cross sec tional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3-ins. See Fig. 3.
The front bracket(s) are installed on the bottom front plate as shown in Fig. 5, once the bottom enclosure has been removed. Rotate filter supports 180 degrees so filter will rest on support emd reinstall. (Do not reinstall in 17-1/2-in. casing.) Install the filter retaining rod (small U-shaped end) in the rear bracket, and the front of the filter retainer rod as
shown in Fig. 5. Two sets of hardware are needed for fur naces in 24-1/2-in. casings using one filter for bottom return. All hardware is provided for filter installation.

A WARNING

Never operate unit without a filter or with filter access door removed. A failure to follow this warning can cause a fire, personal injury, or death.

A WARNING

Do not install the furnace on its back; safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. A failure to follow this warning can cause a fire, personal injury, or death.
III. FILTER ARRANGEMENT
A bottom closure panel is factory-installed in the bottom of the furnace. When bottom return inlet is desired, remove and discard the enclosure panel.
Filter retaining brackets, supports, and retainers are fac tory assembled and shipped installed for side return appUca­tion, with one set of all required hardware provided. See Fig.
4. For bottom return appHcations, remove the brackets (front and back) and supports from each side. The back bracket(s) are installed in the rear of the furnace casing (dimples are provided to mark mounting screw locations).
Table 3—Filter Information
Furnace
Casing Width
14-3/16
17-1/2
21
24-1/2
*Filter can be field-modified by cutting to the desired size. Aiternate sizes
can be ordered from your Distributor or Deaier.
fFactory provided with the furnace.
Side Return Bottom Return
(1)16x25x1 (1)16x25x1 (1)16x25x1 (2)16x25x1
Fiiter Size* Fiiter
(1)14x25x1t (1)16x25x1t (1)20 x 25x1t (1)24 x 25x1t
Type
Cleanable Cleanable Cleanable Cleanable
Fig. 4—Side Filter Arrangement
Fig. 5—Bottom Filter Arrangement
IV. LEVELING LEGS (If Required)
When the furnace is used with side inlet(s), and leveling legs are required, refer to Fig. 6, and install field-supplied corrosion-resistant 5/16-in. machine bolts and nuts.
NOTE; The maximum length of the bolt should not exceed 1-1/2 ins.
1. Lay furnace on its back, locate and drill 5/16-in. diame ter hole in each bottom corner of furnace as shown in Fig. 6.
2. Install nut on bolt and install bolt and nut in hole. (Install flat washer if desired.)
Page 5
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
V. GAS PIPING
Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the National Fuel Gas Code. Canada installations must be installed in accordance with CAN/CGA.B149 Installation Codes, and all authorities having jurisdiction.
The gas supply line should be a separate line running directly from the gas meter to the furnace, if possible. Refer to Table 4 for the recommended gas pipe size. Risers must be used to connect to the furnace and the meter.
Table 4—Maximum Capacity of Pipe*
Nominal
Iron Pipe
Size Ins.
1/2 3/4
1 1-1/4 1-1/2
*Cubic ft of gas per hour, for gas pressures of 0.5 psig (14 ins. wc) or less,
and a pressure drop of 0.5 in. wc (based on a 0.60 specific gravity gas). Ref; Table C-4 NFPA 54-1988.
Internal
Diameter
Ins.
0.622 175
0.824
1.049 680
1.380 1400
1.610 2100 1460 1180 990 900
10 20 30 40 50 360 250 200 170
Length of Pipe, Ft
120 465
950 770 660 580
97
82 73
375 320
151 285
Fig. 7—Typical Gas Pipe Arrangement
made, purge the lines and check for leakage with regulated gas supply pressure.
Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. See Fig. 7.
Apply joint compound (pipe dope) sparingly and only to the male threads of each joint. The compound must be resistant to the action of propane gas.

A WARNING

Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and­water solution to check for leakage. A failure to follow this warning can cause a fire, explosion, personal injury, or death.
An accessible manual shut-off valve shall be installed upstream of the furnace gas controls and within 6 ft of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the furnace and downstream
of the manual shut-off valve. Place ground joint union between the gas control manifold and the manual shut-off valve.

A WARNING

Use the proper length of pipes to avoid stress on the
gas control manifold. A failure to follow this warning can cause a gas leak resulting in a fire, explosion, per sonal injury, or death.

A CAUTION

If a flexible connector is required or allowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2­ins. outside the furnace casing.
Piping should be pressure-tested in accordance with local
and national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig (14 in. wc), the gas supply pipe must be disconnected from the furnace and capped before the pressure test. If the test pressure is equal to or less than 0.5 psig (14 in. wc), close the manual shut-off valve located on the gas valve before the test. It is recommended that the ground joint union be loosened before pressure testing. After all connections have been

A CAUTION

Use a backup wrench when connecting the gas pipe to the furnace to avoid damaging gas controls.
VI. ELECTRICAL CONNECTIONS A. 115-Volt Wiring
Refer to the unit rating plate or Table 5 for equipment elec trical requirements. The control system requires an earth ground for proper operation.
A CAUTION
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Page 6
Fig. 8—Heating and Cooling Application Wiring Diagram
Table 5—Electrical Data
Furnace Volts-
Size Hertz-
035-EC 035-GC 115—60—1 055-EC 115—60—1 055-GC 115—60—1 075-GC 115—60—1
075-JC 090-GC
090-JC
090-LC
110-JC 115—60—1
110-LC 115—60—1 127
125-LC 115—60—1
Phase
115—60—1 127
115—60—1 127 104 115—60—1 127 115—60—1 127 115—60—1 127
♦Permissible limits of the voltage range at which the unit will operate
satisfactorily. tTime-delay fuse is recommended. ifLength shown is as measured one way along wire path between unit
and service panel for maximum 2% voltage drop.
Operating Voltage Range Unit Wire Length Max* Min.*
104 6.7 127 104 127 104 7.1 14 127 104 127 104
104 7.9
104 9.6
104 14.4 12 40 127 104
104 13.3 12 43 127 104 14.0 12 41
Max.
Amps
8.3
8.7
9.0
10.4
10.0
Min.
Max. Wire Max. Fusef or
Gage
14 14
14 14 14 14 14
14
Ftt Ckt Bkr Amps 53 15 43 50 41 40
35 45 37
36 15
HACR-Type
-------------------
FIELD 24-VOLT WIRING
—~ FIELD 115-, 208/230-, 460-VOLT WIRING
15 15 15 15 15 15 15 20
20 20
Make all electrical connections in accordance with the National ElectriceJ Code ANSI/NFPA 70 and local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with CSA C22.1 Canadian Electrical Code, or authorities having jurisdiction.

A WARNING

The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/ NFPA 70 and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
The auxihary junction box can be moved to the right-hand side of the furnace when a right side power supply is desired. Remove the two screws holding the auxihary junc
tion box. Mount the junction box on the right-hand side of the furnace (holes have been predrüled in casing). The blower door interlock switch must also be moved to the right side of the furnace due to the length of the wiring har
ness. When moved, tuck the wiring harness behind the clip provided to keep extra wire lengths out of the way.
NOTE; Proper polarity must be maintained for 115-VAC wiring. If polarity is incorrect, the microprocessor wiU shut off gas flow shortly after the completion of ignition trial
period.
Fig. 9—Blower Control Center
B. 24-Volt Wiring
Make field 24-volt connections at the 24-volt terminal strip.
See Fig. 8. Connect terminal Y as shown in Fig. 8 for proper cooHng operation. Use only AWG No. 18, color coded cop per thermostat wire.
C. Accessory
1. Electronic air cleaner Two screw terminals (EAC-1 and EAC-2) are provided for electronic air cleaner connection. The terminals are energized with 115-VAC, 1 amp maximum during blower motor operation.
2. Humidifier Screw terminals (HUM-1 and C) are provided for 24­VAC humidifier connection. The terminals are ener-
, gized with 24-VAC, 0.5 amp maximum during heating
blower motor operation.
VII. VENTING
These instructions are to be used only for 58PAV Furnace vent systems. These furnaces are equipped with induced­combustion blowers, and are classified as Category I type furnaces in accordance with ANSI/A.G.A. Z21.47 Central
Furnace Standards. Category I furnaces use nonpositive, noncondensing vent systems, and may be connected to Hned masonry chinmeys sized and installed per the National Fuel
Gas Code.
Page 7
RED
RED
|L1 L2 IgND
(Q
O
C
3
3
(Q
0)
(Q
s
3
GROUND SCREW
LEGEND
ALS 1# AUXILIARY LIMIT SWITCH-MANUAL RESET ALS 2# AUXILIARY LIMIT SWITCH-AUTOMATIC RESET BLWR BLOWER MOTOR RELAY BLWM BLOWER MOTOR CPU MICROPROCESSOR AND CIRCUITRY DSS DRAFT SAFEGUARD SWITCH EAC-1 ELECTRONIC AIR CLEANER CONNECT I ON(115V AC)(1 AMP MAX.) EAC-2 ELECTRONIC AIR CLEANER CONNECT I ON(COMMON) FSE FLAME SENSING ELECTRODE HSI HOT SURFACE IGNITOR (115V AC) HSIR HOT SURFACE IGNITOR RELAY
HUM-1 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.)
HUMR HUMIDIFIER RELAY
ILK BLOWER DOOR INTERLOCK SWITCH
I DM INDUCED DRAFT MOTOR
I DR INDUCED DRAFT RELAY LO/HI BLOWER MOTOR SPEED CHANGE RELAY L0T#1 LIMIT OVERTEMPERATURE-MANUAL RESET L0T#2 LIMIT OVERTEMPERATURE-MANUAL RESET
LS LIMIT SWITCH, OVERTEMPERATURE-AUTO RESET
MGV GAS VALVE-REDUNDANT OPERATORS MGVR MAIN GAS VALVE RELAY PL1 11-CIRCUIT EDGE CONNECTOR PL2 2-CIRCUIT HSI CONNECTOR PL3 2-CIRCUIT IDM CONNECTOR
(NOTE #1)
PL4 1-CIRCUIT FS CONNECTOR PL5 5-CIRCUIT BLWM CONNECTOR PLB 2-ClRCUlT 115V AC CONNECTOR PRS PRESSURE SWITCH TRAN TRANSFORMER-115V AC/24V AC TP1-TP7 TEST POINT (1) THRU (7)
—•
---------
JUNCTION
O UNMARKED TERMINAL
— TERMINAL FACTORY CONNECTOR
MARKED TERMINAL
— FACTORY WIRING C120V AC) FACTORY WIRING C24V AC)
- — — FIELD WIRING C120V AC) ' = CONDUCTOR ON PCB1
0 FIELD WIRING SCREW TERM.
^ FIELD GROUND
EQUIP. GROUND
FIELD SPLICE
-) )— PLUG RECEPTACLE
1. COMMON SIDE CSEC-2 AND C3 OF 24V AC TRANSFORMER CONNECTED TO
2. IF ANY OF THE ORIGINAL EQUIPMENT HIRE IS REPLACED USE WIRE
3. INDUCER AND BLOWER MOTORS CONTAIN INTERNAL AUTO-RESET THERMAL
4. BLOWER MOTOR SPEED SELECTIONS ARE FOR AVERAGE CONDITIONS.
5. USE COPPER HIRE ONLY BETWEEN THE DISCONNECT SWITCH AND THE
NOTES;
GROUND THROUGH THIS MOUNTING SCREW.
RATED FOR 105 C, OR EQUIVALENT.
OVERLOAD SWITCHES. SEE INSTALLATION INSTRUCTIONS FOR DETAILS ON OPTIMUM SPEED
SELECTION.
FURNACE JUNCTION BOX.
310278-401 REV. G
Page 8
However, the venting of this furnace into a hned masonry chimney could result in the formation of flue gas condensate
due to cold surfaces and oversizing. If condensate is present in the masonry chimney, a drain must be provided to pre vent condensate flow into the vent connector and furnace.
Refer to National Fuel Gas Code, Section 7.9 for additional information on condensate drains. Field experience on induced-combustion furnaces has shown that venting through a properly sized Type B-1 vent significantly reduces the occurrence of vent condensation. Any conden sate formed is acidic and could cause corrosion of the vent materials. Therefore, manufacturer suggests (but does not require) that these furnaces be connected to vent systems constructed of Tjq)e B-1 vent material.
A. General Instructions
1. This furnace must be installed in accordance with these instructions, the National Fuel Gas Code NFPA No. 54-1988/ANSI Z223.1-1988, Canadian CAN/CGA.B149 requirements and aU apphcable local codes, and all authorities having jurisdiction.
2. This furnace must not be connected to a chimney flue servicing a separate appliance designed to burn solid fuel.
3. Never cormect this furnace to a chimney serving a fire place, unless the fireplace opening is permanently sealed off.
4. The recommended vent system for this furnace is con structed of Type B-1 double-waU vent pipe (UL or ULC listed). A minimum 1-in. clearance is required between Type B-1 vent and combustible materials.
5. It may be necessary to add insulation to Type B-1 double-wall vent and to single-wall vent connector, if allowed by local codes, in some applications. When
insulation is required it must be at least 1-in. thick fiberglass with foil backing. Using permanent foil tape,
attach insulation to vent pipe. Both the foil tape and
fiberglass insulation must be suitable for temperatures up to 350 F.
6. Insulation must be added to any vent connector which will be exposed to ambient temperatures of 30 degrees Fahrenheit or less, especially any application using
single-wall vent pipe as a connector.
Add insulation to Type B-1 vent in some applications as indicated with an asterisk (*) in appropriate tables.
Do not insulate vent pipe exposed to outdoor weather conditions, (i.e. above roof lines).
7. Do not use a vent size smaller or larger than the size shown in Tables 6 thru 14.
8. If this furnace is connected to a Hned, masonry chim
ney, the chimney must be sized and installed according to the provisions of the National Fuel Gas Code, or
Canadian CAN/CGA.B149 requirements. Vent connec
tors from the furnace to the chimney should be made with insulated single-wall vent pipe or Type B-1 vent pipe. Insulate per Section A.5 when required.
9. Installation of the vent pipe should be as directly as possible, with a minimum number of turns or elbows.
10. Maintain a minimum of 1/4-in. upward slope per Hnear ft on all horizontal vent pipe runs.
11. Rigidly support the vent pipe every 5 ft or less with
hangers or straps to ensure that there will be no move ment after installation.
12. No portion of the vent system shall extend into, or pass
through, any circulation air duct or plenum.
13. The Type B-1 vent system shall terminate above the roof surface per the National Fuel Gas Code or CAN/
CGA.B149 requirements, emd shall include a UL or ULC Hsted vent cap or roof assembly, unless prohib ited by local codes.
14. This furnace may be common vented with another fur nace or other Hsted gas-fired appHances. Total input
rates of aU appHances wiU determine the vent size. See
Sections C and D for additional information.
15. If a common vent system becomes blocked, the furnace win be shut off by the draft safeguard switch located on the inducer assembly.

A WARNING

Do not bsqjass the draft safeguard switch, as an unsafe condition exists which must be corrected. A failure to foUow this warning could result in a buildup of carbon monoxide and lead to personal injury or death.
16. All vent pipe passing through floors, ceiHngs, and waUs must be instaUed with the proper clearances from com bustible material, and be fire-stopped according to the National Fuel Gas Code requirements and Canadian Standards CAN/CGA.B149.
17. In replacement instaUation, where an existing vent sys tem may be used, the vent system must be inspected for condition, size, type of vent material, and height to
meet the requirements in these instructions. If the
existing vent system is larger than shown in vent Tables 6 thru 14, the vent system wfll be oversized, and condensation cem occur causing corrosion of the vent system. InstaUation of a replacement vent system may
be required.
18. When removing an existing furnace from a common vent system, the vent system is likely to be oversized for the remaining appHances. Refer to Section E for
additional information.
19. Vent connectors or vents servicing Category I appH ances shall not be connected into any portion of mechanical draft systems operating under positive pressure.
20. For instaUation of vent systems not covered in Sec tions B, C, and D, or for vent systems with length/ height beyond that shown, refer to the National Fuel Gas Code for information. FoUowing the National Fuel Gas code requirements wiU provide for an acceptable vent system and proper operation of the furnace.
B. Venting Tables For Dedicated Vent System (one
58PAV Furnace)
The foUowing tables eire used to size the vent system for a 58PAV Furnace when using a dedicated vent system. The information shown in these tables indicate the maximum horizontal length of vent pipe aUowed for a vent system of a set height and number of elbows. Some tables include infor mation for vent lengths aUowed when insulation is added to the vent connector and the vent. See Tables 6 thru 11 and Fig. 11.
1. When single-waU vent pipe is used for vent connector, it must be insulated as indicated in venting table data marked with an asterisk {*). Insulation must be added as specified in Sections A.5 and A.6.
Insulation should be added to any single-waU vent pipe used as a vent connector, especiaUy those appHcations with long (over 5 ft) vent connector runs.
2. Each table is for a specific size of furnace depending upon the rated furnace input.
Page 9
Fig. 11 —Dedicated Vent (Typical)
Table 6—Dedicated Type B-1 Vent For
58PAV035-EC and GC Maximum
Horizontal Length Allowed (Ft)
Height Number of 90° Elbows
5 0 10 0 10 15 0
20 0 6
20* 0
25 0 NA NA 2
25* 0
30 NA NA NA NA
30* 0
5 0 5
10 0 4 15 0 NA NA NA
15* 0
20 NA NA NA NA
20* 0
25 NA
25* 0
30 NA NA
30* 0
0 1 2 3
5 5
10
10 10 10
6
20* 20* 20* 20*
25* 25* 25* 25*
30* 30* 30* 30*
5 4
15* 15*
20* 20*
NA NA
25* 25* 25*
NA
30* 30* 30* 30*
Table 7—Dedicated Type B-1 Vent For
58PAV055-EC and GC Maximum
Horizontal Length Allowed (Ft)
Height Number of 90° Elbows
5 0 5 10 0 10 10 15 0 20 0 20 25 0 25* 30 0
30*
5 0 10 15 0 20 0 20* 0 25 25* 0 30 30* 0
NA—Not allowed. Condensation could occur. ♦Insulated with 1-in.
0 1
0 25*.
0
0 10 10 10 10
0 8 8 8
0 4 4 4
of foil-backed insulation per Section A.5.
2
NA
15 15
20
18 16
25* 14 14 30* 30* 30*
5 5
15 15 12 12 20* 20*
25* 25* 25*
30* 30* 30* 30*
or positive pressure in vent system
4
NA
10
10
10 10
6
NA NA
5 4
NA NA
15*
15*
NA NA
20*
20*
NA
NA 25* 25*
NA
NA
3
4
NA
NA NA
10
NA
15
15
20
20 20
16
16 25* 25* 14
14
30* 30*
5
NA
15
15 12
12 20*
20*
25* 25*
4
6
2 2
5 4
NA 15
16
14
NA 10 15 12 20*
8 8
4
30*
5
NA
10
6
20*
25*
30*
5 4
15*
20*
NA
NA
30*
5
25*
4
A89017
Vent
Pipe
4-lN.
DIAMETER
5-IN.
DIAMETER
Vent
Pipe
4-IN.
DIAMETER
5-IN.
DIAMETER
3. For all applications, the horizontal length of vent and vent connector must not exceed the vertical height of the vent system.
4. Addition of insulation to vent connector and vent allows for longer horizontal runs in certain applications as indicated with an asterisk (*) in appropriate tables.
5. When Type B-1 vent pipe is used for vent connector, it must be insulated as indicated with an asterisk (*) in the vent tables.
Table 8—Dedicated Type B-1 Vent For
58PAV075-GC and JC Maximum
Horizontal Length Allowed (Ft)
Height
5 10 0 10 NA NA NA NA 15 0 15 20 0 20 25 30 0 30
5 0 5 10 15 0 20 0 20 25 30
NA—Not allowed. Condensation or positive pressure In vent system could occur. ♦Insulated with 1-in. of foil-backed Insulation per Section A.5.
Number of 90° Elbows
0 1 2 3 4 5
NA NA
0
25 25
0
10 10 10 10 15 15 15 15
0
22 22
0
20
NA
NA
15 NA NA
15
20 16 10
20
25 30 30 30
30
5
20 20 20
20
22 20 20 20
20
NA NA
25
5 NA
22
20
NA
10 15
22
Vent
Pipe
4-IN.
DIAMETER
5-IN.
DIAMETER
Table 9—Dedicated Type B-1 Vent For
58PAV090-GC, JC, and LC Maximum
Horizontal Length Allowed (Ft)
Height Number of 90° Elbows
0
1 2 3 4 5
5 10 15 0
NA
NA NA
NA
10 NA NA NA NA
15 8
20 0 20 25 0 30
5 10 0 15 20 25 30 0
NA—Not allowed. Condensation or positive pressure In vent system
could occur.
25 25
0
30
0
5 2 NA NA NA
10 10
0
15 15 15 15 15
0
20 20
0
25 30 30
NA
16 12 4
20
24 30 28 22
30
10
20 25 25 25
25
30
6
NA
NA
NA NA
12
18
NA
NA
20 20
30
30
Vent
Pipe
4-IN.
DIAMETER
5-IN.
DIAMETER
Table 10—Dedicated Type B-1 Vent For
58PAV110-JC and LC Maximum Horizontal
Length Allowed (Ft)
Height
5 10 0 15 0 20 25 0 30
5 0 10 0 10 15 0 20 0 25 0 30 0
NA—Not allowed. Condensation
could occur.
Number of 90° Elbows
0 1
NA
NA
10
15
0
20 25
0
30
5
15 20 25 25 25 25 30
2 3 4
NA NA NA
NA
6
15
15 20 20 20 20
25
25
30
30
4 NA
5
10 10 10
15
15
20 20
20
30
30
or positive pressure in vent system
NA
15 6
25 25 30 30
15 15
30
5
NA NA
NA 10
20 25 30
Vent
Pipe
5-IN.
DIAMETER
6-IN.
DIAMETER
Page 10
Table 11—Dedicated Type B-1 Vent For
58PAV125-LC Maximum
Horizontal Length Allowed (Ft)
Height Number of 90° Elbows Vent
5 NA
NA
10 0 10 10 15 0
15
20 0 20 20 20 20 20 25 30
5
0 25 25 0 30 0 5
10 0 10 10 10 10 10 15 0 15 15 15 15 15 20 0 20 20 20 20 20 25
0 25 25 25 25 25
30 0 30 30 30 30 30
NA—Not allowed. Condensation
could occur.
C. Venting Tables For Common Vented Furnaces (two, three, or four 58PAV Furnaces)
The following information refers to installations where two, three, or four 58PAV Furnaces are common vented into a single vent system. Do not connect more than four 58PAV Furnaces into a common vent system. See Fig. 12. Table 12 data is for a vent system where all the furnaces are the same size. For common vent apphcations using various sizes of 58PAV Furnaces, contact your Distributor or Dealer for more information.
To determine the proper common vent size, total the heat input of all the apphemces to be connected to the vent sys tem, next select the smallest vent size which wUl meet that rated input.
NOTE: A listed single-wall to T3?pe B-1 vent adaptor is required to connect single-wall vent connectors to the com mon vent.
1. Vent connectors should be as short and direct as possi ble, and should be made of Type B-1 double-wall vent pipe or insulated single-wall vent pipe.
2. Vent connectors shall be sized using dedicated venting table in Section B of this publication. The length of hor izontal run used in the vent connector and vent must never exceed the height of the common vent.
3 4
NA NA NA
NA NA
15 15 15
25 25
30 30 30
5 5 NA NA
or positive pressure in vent system
5
NA NA
15
25 30
FURNACE
Pipe0 1 2
5-IN.
DIAMETER
6-IN.
DIAMETER
A89018
Fig. 12—Common Venting Of Furnaces
(Typicai installation)
Table 12—Common Venting Of Furnaces
(Typicai instaliation)
58PAV
Size
035-EC
or
035-GC
055-EC
or
055-GC
075-GC
or
075-JC
090-GC,
090-JC,
or
090-LC
110-JC
or
110-LC
of
Furnaces
2
3
4
2
3
4 14
2
3 14 40 7
4 14
2 14
3 10 40 8
4 10 40 9
2 14 40 7
3
4
Common Vent Height (Ft)
Minimum Maximum*
8 40 6 40 6
14
8 40 6
14 40
8 40 7
14 40 5
8 40 6
14 40 6
8 40
10 40 8 10 40 6
8 40
8 40 8
10 40 9
10 40 7
8 40 9
10 40 10
8 40 8
10 40 9
8 40 10 16 40 9 10
40 5
40
40 8
40 6
40 10
125-LC 2 10 40 7
Number
6 40. 8
3
4 18
*For applications requiring
tion other than specified, information.
6
14
8 40 9
8 40 10
14 10 40 10
vent heights greater than 40 ft, or contact your Distributor or Dealer
40 9 40 8
40 8 40 9
3. Vent connectors should be spaced at least 1 ft when entering the common vent system.
4. Insulated vent connectors may be required for certain applications. See Sections A.5. and A.6. for additional information.
5. For multi-story installation, refer to Appendix G of National Fuel Gas Code or Canadian standards CAN/ CGA.B149 for additional information in sizing the com mon vent. Individual vent connectors should be sized per the dedicated appliemce tables shown in Section B.
D. Venting Tables For Common Vents (One 58PAV Furnace and Gas Hot Water Heater)
The information in this section refers to the installation of a common vent serving a 58PAV Furnace and a gas hot water heater. Tables 13 and 14 use typical hot water heater input
rates of 40,000 Btuh or 50,000 Btuh. Refer to the water
heater rating plate for input ratings of the installed equipment.
1. Size common vent and vent connector lengths using Tables 13 and 14.
2. Vent connectors should be as short and direct as
possible.
3. Size gas water heater vent connector per National Fuel
Vent
Dia
(Ins.)
5
6
7 7
7
combina-
for more
apart
10
Page 11
Fig. 13—Common Vent With Water Heater
(Typical Installation)
Table 13—Common Vent (With No Lateral Run)
Furnace and Water Heater (No Horizontal)
58PAV
Size
035-ECt
Connector Length (Ft)
5
or
Vent
035-GCt
055-ECt
10 12
15 12
5 18
or
055-GCt
075-GCt
10 20
15 20
5 10
or
075-JCt
090-GCt,
10 10
15 10
5
090-JCt,
or
10 14
090-LCt
15
110-JCÍ
5 10
or
110-иСф
10 10
15 10
125-LCt 5 8
10
15
Common Vent Height (Ft)
Minimum
12
6
6
6
8
8
8
5
5
5
14
6
6
14
6
5
5
5
6 6 8 6
■ 6 10
6 6
Maximum*
30 30 5 30 24 26 4 16 30 4 30 5 30 30 5 30 4 30 5 30 30 30 30 6 30 5 30 6 30 30 30 5
30 6 30 30 30 30 30 30 7 30 30 30 6 30 30 8 30 30 7 30 30 6 30 7 30 8
*For applications requiring vent heights greater than 30 ft, contact your
Distributor/Dealer for more information, flnstalied with a 40,000 Btuh gas-fired water heater—typical size. ^Installed with a 50,000 Btuh gas-fired water heater—typical size.
Common
Vent
Dia
(ins.)
A89019
4
4 5
5
4
5 6 5
5 6
5 6 6 7 6
6 7
7
6
8
Gas Code. The 58PAV Furnace vent connector is sized per the tables in Section B of this publication to deter mine allowable lengths, number of elbows, and insula tion requirements. The allowable vent connector length for the furnace cannot exceed 15 ft for any common vent installation or application, as shown in Tables 13 and 14.
4. Insulated vents and vent connectors may be required for certain applications. See Table 14. When insulation is required, it must be installed as indicated in Sections A.5. and A.6.
5. If the vent connector is exposed to ambient tempera tures of 30 degrees Fahrenheit or less, it must be insu lated, as indicated per Sections A.5. and A.6.
6. The vent connectors must be spaced within 3 ft of each other (3-ft rise).
7. Where possible, locate the vent closer to or directly over the smaller appliance connector.
8. For multi-story installation, refer to Appendix G of National Fuel Gas Code or Canadian standards CAN/ CGA.B149 for additional information to size the com mon vent. Individual vent connector for the furnace
should be sized per single apphemce tables found in Sec-
Table 14—Common Vent (With 10 Ft Max. Lateral
Run) Furnace and Water Heater
Vent and
58PAV
Size
035-ECt
035-GCt
055-ECt
055-GCt
075-GCt
075-JCt
090-GCt,
090-JCt,
090-LCt
110-JCt
110-LCt
125-LCt 5
Connector Length (Ft)
or
or
or
or
or
Vent
10
15
10
15
10
15
10
15
10
15
10
15
Vent Conn
Insulation
Required
5
5
5
5
5
Common Vent Height (Ft)
yes 6
yes 6
yes 6
yes 8
yes
yes 8
Minimum
NA
10
— —
— —
— — 14
_
_
— —
— —
— —
— —
10 10 30 6
10
Maximum*
8
8 14 5
NA 5
8
10 30 5
8 30
10 22 5 10
5
5
10
5
14 30 5
6
14
6 6 30
10
5
5
5 30
10
8 30 6
8 6
10 30 6
8 6 30 8
30
30 30 8
30
*For applications requiring vent heights greater than 30 ft, contact your
Distributor/Dealer for more information, tinstalled with a 40,000 Btuh gas-fired water heater—typical size, llnstalled with a 50,000 Btuh gas-fired water heater—typical size.
Common
Vent
Dia
(Ins.)
22
30
30
30 30 30
30 30 30 30 30 6 30 30 6
30 30 5 30 30 5
30 30 30
30
30 30
5
5
5
6
5
5
6 6
6 6 7 6 7
7 6 7 8 6 7
7
11
Page 12
tion B. The water heater vent connector must be sized per the National Fuel Gas Code.
E. Removal of Existing Furnaces From Common Vent Systems
1. These steps shall be followed with each appliance remaining connected to the common vent system placed in operation, while the other appliances remain ing connected to the common vent system are not in operation.
2. Seal any unused openings in the common vent system.
3. Visually inspect the vent system for proper size and horizontal pitch, and determine there is no blockage or
restriction, leakage, corrosion, and other deficiencies which could cause an unsafe condition.
4. Insofar as practical, close all building doors and win
dows and all doors between the space in which the appliances remaining connected to the common vent system are located and other spaces of the building. Turn on clothes dryers and emy appliance not con nected to the common vent system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
5. Follow the lighting instructions and place the apph-
ance in operation. Adjust the thermostat so appliance will operate continuously.
6. Test for flue gas spUlage at the drafthood rehef open
ing (or draft safeguard tube opening) after 5 minutes of main burner operation. Use the fleime of a match or candle, or smoke from a cigarette, etc.
7. After it has been determined that each appliance
remaining connected to the common vent system properly vents when tested as above, return doors, win dows, exhaust fans, fireplace dampers, any other gas­buming appliances to their previous condition of use.
8. If improper venting is observed during any of the above tests, the common vent system must be cor
rected. The vent system or vent connectors may need
to be resized. Resize any 58PAV Furnaces vent system according to these instructions. For any other appli ances when resizing vent systems or vent connectors,
the system or connector must be sized to approach the rninimum size as determined using the appropriate
table found in Appendix G of the National Fuel Gas Code, ANSI Z223.1 or Section 5 of CAN/CGA.B149 for Canadian installations.
VIII. STARTUP, ADJUSTMENT, AND SAFETY CHECK A. General
The furnace must have a 115-VAC power supply properly
connected and grounded. Proper polarity must be main
tained for proper operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-volt terminal block on the control board. The gas service pressure must not exceed 0.5 psig (14 in. wc), but must be no less than 0.16
psig (4.5 in. wc).
Before operating the furnace, check each manual reset switch for continuity. If necessary, press the button to reset
the switch. The blower compartment door must be in place to complete
the 115-VAC circuit to the furnace.

A CAUTION

This furnace is equipped with a manual reset limit
switch in the gas control area. The switch will open and shutoff power to the gas valve if a flame rollout or over
heating condition occurs in the gas control area. Do not bypass the switch. Correct inadequate combustion air
supply problem and reset the switch.
B. Sequence of Operation
Using the schematic diagram. Fig. 10, follow the sequence of operation through the different modes. This furnace has a new and unique control system, therefore, read and follow the wiring diagram very carefully.
1. Heating mode The waU thermostat “calls for heat,” closing the R and W circuit. The furnace control performs a selfcheck, verifies the pressure switch contacts are open, and starts the inducer motor.
a. Prepurge period—As the inducer motor comes up to
speed, the pressure switch contacts close to begin a 15 second prepurge period.
b. Ignitor warm up—At the end of the prepurge
period, the ignitor is energized for a 17 second igni
tor warm-up period. If ignition is not established during the first cycle, the next warm-up period is
increased to 45 seconds. AH subsequent ignition
cycles wiU be 45 seconds, or until the 115-VAC
power supply is interrupted. By interrupting the
115-VAC power supply, the warm-up period is auto matically reset to 17 seconds.
c. Ignition sequence—When the ignitor warm-up
period is completed the gas valve opens, permitting gas flow to the burners where it is ignited. After 5
seconds, the ignitor is deenergized and a 2 second
flame sensing period begins.
d. Flame sensing—When burner flame is sensed, the
control begins the blower “on” delay period and
continues holding the gas valve open. If burner flame is not sensed, the control will close the gas valve, and control wUl repeat ignition cycle.
e. Blower on delay—60 seconds after burner flame is
proven, the blower motor is energized on heating
speed. Simultaneously, the humidifier and electronic
air cleaner terminals (HUM-1 and C for humidifier, EAC-1 and EAC-2 for electronic air cleaner) are energized.
f. Blower off delay—When the thermostat is satisfied,
the circuit between R and W is broken, deenergizing the gas valve stopping gas flow to the burners. The blower motor, humidifier, and air cleaner wUl remain energized 90, 135, 180, or 225 seconds (depending
on the blower off-time selection). The furnace is factory-set for a 135-second blower off delay.
g. Post purge—The inducer motor will remain ener
gized 5 seconds after the burners are extinguished.
2. Cooling mode The thermostat “calls for cooling” closing R-G and R-Y
circuits. The R-Y circuit starts the outdoor condensing unit, and the combined R-Y and R-G circuit starts the furnace blower motor on cooling speed. The electronic air cleaner EAC terminals are energized with 115-VAC when the blower is operating on cooling speed.
When the thermostat is satisfied, R-G and R-Y circuits are broken. The furnace blower wUl continue operating on cooling speed for an additional 90 seconds.
12
Page 13
3. Continuous blower mode When the R-G circuit is made, the blower motor will
operate on heating speed. During a call for heat, the blower will stop, allowing the furnace heat exchangers to heat up more quickly.
The blower will revert to continuous operation after the heating cycle is completed.
When the thermostat “calls for cooling,” the blower wiU operate on cooling speed. When the thermostat is satisfied, the blower wiU operate an additional 90 sec onds before reverting back to continuous operation on heating speed.
4. Heat pump mode When instaUed with a heat pump, the furnace control automaticaUy changes the timing sequence to avoid
long blower off time during demand defrost cycles. When the W-Y or W-Y-G thermostat inputs are received together, the control wiU change the blower to
heating speed or start the blower if it was off, and begin a heating cycle. The blower wiU remain on until the end of the purge period, then shut off until the end of the ignition warm up and trial for ignition periods (a
total of 24 seconds). The blower wUl then come back on
at heating speed.
When the W input signal disappears, the control wiU begin the normal inducer post-purge period and the blower wUl change to cooling speed after a one second
delay. If the W-Y-G signals should disappear together,
the blower wiU remain on for the selected heating blower off delay period, and the inducer wUl go through its normal post-pm-ge period. If the W-Y inputs should disappear, leaving the G signal input, the control wUl go into continuous blower and the inducer wiU remain on for the normal post-purge period.
While in heat pump mode, the control will use only the
17 second ignition warm-up period, and will not use the
45 second period at all. The control wUl initiate a 90 second blower only on delay before starting another heat pump cycle, if there is a power interruption. Any time the control senses false flame, the control wUl lock out of the heating mode. This occurs because the con trol cannot sense the W input due to the false flame signal, and as a result sees only the Y input and goes into cooling mode blower off delay. AU other control functions remain in standard format.
C. Startup Procedures
1. Self test—The furnace features a self-test system to help diagnose a system problem in the case of a compo nent faUure. Two test pins (ST-1 and ST-2) are located in the lower left-hand corner of the control board as
shown in Fig. 9. To initiate the self-test procedure,
momentarUy short across the two pins.
NOTE: The self-test feature wUl not operate if the con
trol board is receiving any thermostat signals. The self-test sequence is as foUows:
a. The furnace control wUl check itself and then oper
ate the inducer motor for 10 seconds, then off.
b. The hot surface ignitor is then energized for 15 sec
onds, then off.
c. The humidifier relay is then energized for 10 sec
onds, then off.
d. The blower motor wUl operate on cooling speed for
10 seconds, then off.
e. The blower motor wUl operate on heating speed for
10 seconds, then off.
2. Purge gas lines—After aU connections have been made, purge the lines and check for leaks.

A WARNING

Never purge a line into a combustion chamber. Never
use matches, candles, flame or other sources of ignition
for the purpose of checking leakage. Use a soap-and­water solution to check for leakage. A faUure to foUow this warning can cause a fire, explosion, personal injury, or death.
3. To operate furnace, foUow procedures on operating instructions label attached to furnace.
4. With furnace operating, set thermostat below room temperature and observe that furnace goes off. Set thermostat above room temperature and observe that furnace restarts.
D. Adjustments
1. Set gas input rate. There are two methods of adjusting the gas input rate. The preferred method is by using Table 15 and step a. The second method is by clocking the gas meter and step b.
The gas valve regulator has been nominaUy-set at 3.5
ins. wc for natural gas. When adjusting input rate, do
not set manifold pressure above 3.8 or below 3.2 ins. wc.
a. Check gas input rate using Table 15.
(1.) Obtain average yearly heat value for local gas
supply.
(2.) Obtain average yearly specific gravity for local
gas supply.
(3.) Verify furnace model. Table 15 can only be used
for Model 58PAV Furnaces.
(4.) Check and verify orifice size in furnace.
NEVER ASSUME THE ORIFICE SIZE, ALWAYS CHECK AND VERIFY.
(5.) Find natural gas heat value and specific gravity
in Table 15.
(6.) FoUow heat value and specific gravity fines to
point of intersection. Find orifice size and mani fold pressure settings for proper operation at
given natural gas conditions. EXAMPLE: ' Heat value 1070 Btu/cu ft Specific gravity 0.58 Therefore; Orifice No. 44*
Manifold pressure 3.3 ins. wc
*The furnace is shipped with No. 43 orifices. Therefore, in this example aU main burner orifices must be changed and niamfold pressure must be adjusted.
(7.) Proceed to step c to adjust manifold pressure.
b. Check gas input rate by clocking gas meter.
(1.) Obtain average yearly heat value for local gas
supply.
(2.) Check and verify orifice size in furnace.
NEVER ASSUME THE ORIFICE SIZE,
ALWAYS CHECK AND VERIFY.

A CAUTION

DO NOT redrill burner orifices. Improper drilling (burrs, out of round, etc.) can cause excessive burner operating noise and misdirection of burner flames. This could result in flame impingment on burners and heat exchanger surfaces, leading to potential failures.
13
Page 14
(3.) Turn off all gas appliances £ind pUots. (4.) Start furnace and let run for 3 minutes. (5.) Measure time (in seconds) for gas meter to com
plete one revolution. (6.) Refer to Table 16 for cubic ft of gas per hour. (7.) Multiply gas rate cu ft/hr x heating value (Btu/
cu ft).
"Example:
Btu heating input = Btu/cu ft times cu ft/hr Heating value of gas = 1070 Btu/cu ft
Time for one revolution of 2-cu/ft dial = 72 seconds
Gas rate = 100x1070 = 107,000 Btuh
(8.) Measured gas input should not exceed gas
input on unit rating plate.
(9.) Proceed to step c to adjust manifold pressure,
c. Adjust gas input.
(1.) Remove regulator adjustment seal cap. See
Fig. 14.
(2.) Turn adjusting screw counterclockwise to
decrease input. Turn screw clockwise to increase input. DO NOT set manifold pressure less than 3.2 or more than 3.8 maximum ins. wc for natural gas. Make any major adjustments by changing meiin burner orifices.
(3.) When correct input is obtained, replace regula
tor seal cap. Main burner ñame should be clear blue, almost transparent. See Fig. 15.
BURNER FLAME
MANIFOLD PRESSURE TAP
Fig. 14—Redundant Automatic Gas Control Valve
Table 15—Model 58PAV Orifice Size and Manifold Pressure For Correct Input Rate
(Tabulated data based on altitude up to 2000 ft and 22,000 Btuh per burner.)
Gas
Heat
Value
(Btu/cu ft)
860
875
890
905
920
935
950
965
980
995
1010
1025
1040
1055
1070
1085
1100
Orf No.
41 42
42
42
42
43
43
43 44
43 44
44
4^ '45~'
0.56
MnfId
Press
3.2
3.6
3.4
3.3
3.2
3.8
3.7
3.6
3.4
3.8
3.3
3.7
3.2
3.6
3.5
3.4
3.3
3.2
3.8
3.7
Orf No.
41 42
41 42
42
42
42
4^
4^“
"4^
44 43
44 43
44 43
44 44 44
0.58
MnfId Press
3.3
3.7
3.2
3.6
3.4
3.3
3.2
"as"
3.7
3.6
3.5
“ as"
3.4
3.7
3.3
3.6
3.2
3.5
■aT“
3.3 3,2
3.8
Orf No.
41 42 40
41 42
41 42
42
42 42 43 43 43 43 44
43 44
43 44
43
44 44 44
44
0.60
MnfId Press
SPECIFIC GRAVITY OF NATURAL GAS
0.62
Orf No.
41
3.4 40
3.8
3.2 41
3.3 42
3.7 40
41
3.2 42
3.6 41
3.4 42
42
3.3 42
3.2 42
3.8 43 43
3.6 43
3.5 43
3.8
3.4
~4^
3.7
3.3 44
3.6 43
3.2 44
3.5 43
44
3.4 44
3.3 44
3.2
MnfId Press
3.5
3.3
3.4
3.8
3.2
3.3
3.7
3.2
3.6
3.4
3.3
3.2
3.8
3.7
3.6
3.5
“aA"
3.7
3.3
3.6
3.2
3.5
3.4
3.4
Orf No.
41
39
40 41
40 41
42 41
42 41
42 42
42 42 43 43 43 43 43 44
43 44
43 44
44
0.64
MnfId Press
3.7
3.2
3.4
3.5
3.3
3.4
3.8
3.3
3.7
3.2
3.5
3.4
3.3
3.2
3.8
3.7
3.6
3.5
3.4
3.8
3.3
3.7
3.2
3.6
3.5
Orf No.
41
39
40 41
39 40
41 40
41 42
41 42
41 42
42 42 42
43 43 43 43 44
43 44
43 44
0.66
MnfId Press
3.8
3.3
3.5
3.6
3.2
3.4
3.5
3.2
3.4
3.8
3.3
3.7
3.2
3.5
3.4
3.3
3.2
3.8
3.7
3.6
3.5
3.4
3.8
3.3
3.7
3.2
3.6
Orf No.
39 40
41 39 40
41 40
41 40
41 42
41 42
41 42
42 42 42 43 43 43 43 43 44
43 44
43
0.68
MnfId Press
3.4
3.6
3.8
3.3
3.5
3.6
3.3
3.5
3.2
3.4
3.8
3.3
3.7
3.2
3.5
3.4
3.3
3.2
3.8
3.7
3.6
3.5
3.4
3.8
3.3
3.7
3.2
Orf No.
38 39 40
39 40
41 39 40
41 40
41 40
41 42
41 42
41 42
42 42 42 43 43 43
43 43 44
43
0.70
MnfId Press
3.2
3.5
3.7
3.3
3.6
3.7
3.2
3.4
3.6
3.3
3.5
3.2
3.4
3.8
3.3
3.6
3.2
3.5
3.4
3.3
3.2
3.8
3.7
3.6
3.5
3.4
3.8
3.3
Orf No.
38 39 40
38 39 40
41 39 40
41 39 40
41 40
41 40
41 42
41 42
41 42
42 42 43 43
43 43 43 43
0.72
MnfId Press
3.3
3.6
3.8
3.2
3.4
3.7
3.8
3.3
3.5
3.7
3.2
3.4
3.6
3.3
3.5
3.2
3.4
3.7
3.3
3.6
3.2
3.5
3.4
3.3
“a2~
3.8
3.7
3.6
3.5
3.4
Page 15
Table 16—Gas Rate Cu Ft/Hr
Seconds
for one
Revolution cu ft CU ft CU ft Revolution
10 11 12 300 600 1500 52 13 277 555 1385 53 14 257 514 1286 54
15 240 480 1200 55 16 225 450 1125 56 17 18 200 400 1000 58 62 124 19
20 180 21 171 22 164 23 157 313 783 66 54 109 24 150
25 26 138 277 27 133 267 28 129 257 643 76 47 95 29 124
30 120 240 600 80 31 32 33 109 34
35 103 36 37 38 95 39
40 90 180 450 100 41 42 86 172 43 84 167 419 106 34 68 44 82 164 409 108
45 80 160 400 110 46 78 157 391 47 76 48 75 49 73 147 367
SIZE OF TEST DIAL
1 2 5
360 720 327
212 424 1059 57
189 379
144
116 232 581 113
106 100
97 92
88 176
1800
655 1636 51 71 141
360 343 327 818
300 288
248
225 218 212
206 200 500 92 195 486 94 189 185
153 150
Seconds SIZE OF TEST DIAL
for one 1
50 72 144
947 900
857 62
750 68 720 70
692 72 667 74
621 78
563 84 545 86 529
514
474 96 462
439 429
383 116 375 120
59 60 60 120
64
82
88 41 82 90
98 37 74
102 35 71 104
112 32
cu ft
69 138 68 136 67 133
65 131 327 64 129 63 126
61 58 116
56 53 106
51 103 257 50 48
46 45
44 88 43 86 214 42
40 80 200 39 38 76 192 38 75
36 35 33
33 31
30 60
d. Approved input ratings.
The U.S.A. ratings are approved for altitudes up to 2000 ft for natural and propane gases. Refer to National Fuel Gas Code Appendix F, Table F-4 for proper orifice sizing at high altitudes,
e. Canadian installations only.
The Canadian ratings are approved for altitudes up to 2000 ft for natural and propane gases. High alti tude ratings are from 2000 ft to 4500 ft above sea level. See Table 17 for nominal burner orifice size. High altitude rating includes a 10% derate as required by Canadian standards.
Table 17—Canadian Orifice Size
Gas
Natural 43 Propane
Sea Level
0—2000 ft 20Ô0—4500 ft
54
High Altitude
44 55
2
cu ft
122
112
100
97 92
90
84
78
72 69 67
65 64 62
5
cu ft
360 355 346 340 333
321 316 310 305
300 290 281 273 265
250 243 237 231
225 220
209 205
196 188
184 180
178 173 170 167
164 161 155 150
c. Adjust air temperature rise by adjusting blower
speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.

A WARNING

Disconnect the electrical power before changing the speed tap. A failure to follow this warning can cause personal injury.
d. To change motor speed taps, remove the motor tap
lead (see Table 18) and relocate it on the desired ter minal on the plug-in terminal block/speed selector located on the blower housing.

A CAUTION

Recheck the temperature rise. It must be within the Hmits specified on the unit rating plate. Recommended operation at mid-point of rise or above.
Table 18—Speed Selector
Speed Tap No.*
Common C
Hi
Med-Hi 2
Med-Low 3
Low 4
*White wire from control box to common; black wire from control box to
cooling speed selection; red wire from control box to heating and con stant fan speed selection.
3. Set thermostat heat anticipator. The thermostat heat anticipation must be set to match
the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R & W. Fig. 16 illus trates an easy method of obtaining the actual amp draw. The amp reading should be taken after the blower motor has started. See the thermostat manufac turer’s instructions for adjusting the heat anticipator and for varying the heating cycle length.
NOTE: When using an electronic thermostat, set the cycle
rate for three cycles per hour.
E. Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the Startup Section as part of normal operation.
1
2. Set temperature rise. Do not exceed the temperature rise range specified on
the unit rating plate. Determine the air temperature rise as follows:
a. Place duct thermometers in return and supply ducts
as near furnace as possible. Be sure thermometers do not “see” heat exchangers so that radiant heat will not affect thermometer readings. This is partic ularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract
return-air temperature from supply-air temperature
to determine temperature rise.
Fig. 16—Amp Draw Check With Ammeter
15
Page 16
1. Check Primary limit control. This control shuts off the combustion control system
and energizes the circulating-air blower motor if the
furnace overheats. The preferred method of checking the limit control is to
gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has shutoff the burners the retum-air opening should be unblocked. By using this method to check the limit control, it can be established that the limit is functioning properly and will “operate” if there is a motor failure.
2. Check draft safeguard switch. The purpose of this control is to permit the safe shut
down of the furnace during certain blocked vent conditions.
a. Disconnect power to furnace and remove vent con
nector from furnace outlet collar. Be sure to allow time for vent pipe to cool down before removing.
b. Set room thermostat above room temperature and
restore power to furnace.
c. After normal startup, allow furnace to operate for 2
minutes, then block (100%) flue outlet. Furnace should cycle off within 2 minutes.
d. Remove blockage and reconnect vent pipe to fur
nace outlet coUar.
e. Wait 5 minutes and then reset draft safeguard
switch.
3. Check flow-sensing switch. This control proves operation of draft inducer blower.
a. Turn off 115-volt power to furnace. ".. .
b. Remove control door and disconnect inducer motor
lead wires from wire harness.
c. Turn on 115-volt power to furnace. ^ ,
d. Close thermostat switch as if making normal
furnace start. If the hot surface ignitor does not glow, then the flow-sensing switch is functioning
properly.
e. Turn off 115-volt power to furnace.
f. Reconnect inducer motor wires, replace control
door, emd turn on 115-volt power.
F. Check List
1. Put away tools, instruments, and cleanup debris.
2. Verify manual reset switches have continuity.
3. Blower and control access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Guide with owner.
7. Leave literature packet near furnace.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
^°°^| 1 I ^ PC 101 Catalog No. 565-913 Printed in U.S.A. Form58PA-1SI Pg 16 5-90
Tab I6al8a
Replaces: New
Loading...