Carrier 58MVP120F15120, 58MVP080F15120 Installation Guide

4-Way Multipoise Direct-Vent
HEATING & COOLING
Visit www.carder.com
Variable-Capacity Condensing Gas Furnace
Installation, Start-Up, and Operating Instructions
For Sizes 040--120, Series 140 and 150
i ama !1
bRfeardestt_ing_r: inist_;lr_t_°nn
58MVP
JI
This symbol --->indicates a change since the last issue. Index Page
DIMENSIONAL DRAWING ........................................................ 3
SAFETY CONSIDERATIONS ..................................................... 2
Clearances to Combustibles ...................................................... 4
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ........ 2
INTRODUCTION ....................................................................... 2_-
APPLICATIONS ...................................................................... 5-11
General ...................................................................................... 5
Upflow Applications .............................................................. 5-7
Dowoflow Appiications ......................................................... 7-8
Horizontal Left (Supply-Air Discharge) Applications .......8-10
Horizontal Right (Supply-Air Discharge) Applications...10÷l 1
LOCATION ............................................................................ 1 l- 13
General ............................................................................... 11- 12
Low-Fire Only Installation ..................................................... 13
Furnace Location Relative to Cooling Equipment ................ 13
Hazardous Locations ............................................................... 13
INSTALLATION .................................................................... 13-14
Leveling Legs (If Desired) ..................................................... 13
Installation In Upflow or Downflow Applications .......... 14-15
Installation In Horizontal Applications .................................. 14
AIR DUCTS ............................................................................ 14-18
General Requirements ............................................................. 14
Ductwork Acoustical T_atment ............................................. 14
Supply-Air Connections .......................................................... 14
Return Air Connections .......................................................... 14
Filter Arrangement ............................................................ 16-17
Boltora Clo_ure Panel ............................................................. 17
Gas Piping .......................................................................... 17-18
ELECTRICAL CONNECTIONS ........................................... 18-22
115 v Wiring ...................................................................... 18-19
24-v Wiring ............................................................................. 19
Accessories ........................................................................ 21-22
DIRECT VENTING ............................................................... 22-31
Removal, of Existing Furnaces from
Common Vent Systems ..................................................... 23
Combustion-Air and Vent Piping ........................................... 23
Concentric Vent and Combustion-Air Termination
Kit Installation .............................................................. 28-31
Multiventing and Vent Terminations ..................................... 31
CONDENSATE DRAIN ........................................................ 31-33
General ............................................................................... 31-32
As an ENERGY STAR@ Pa_ner, Carder Coclmca-
don has determined that
thisixed_t m_ tl_ EN.
ERGY STAR® guidelines
for en_g_ efficiency.
AtRFLOW _ AIRFLOW
REGISTERED QUALITY SYSTEM
AIRFLOW
AIRFLOW
A9_4t
Fig. 1---Multipoise Orientations
Application .............................................................................. 31
Condensate Drain Protection .................................................. 31
SEQUENCE OF OPERATION .............................................. 33-36
Self-Test Mode ........................................................................ 33
Heating Mode .......................................................................... 33
Heating Mode Two Stage .................................................... 34
Emergency Heat Mode ........................................................... 34
Cooling Mode .........................................................................
Heat Pump Mode ............................................................... 34-35
Continuous Fan Mode ....................................................... 35-36
Component Test ...................................................................... 36
Bypass Humidifier Mode ........................................................ 36
Dehumidification Mode .......................................................... 36
Zone Mode .............................................................................. 36
START-UP PROCEDURES .................................................. 36-45
General .................................................................................... 36
Select Setup Switch Positions ................................................ 37
Prime Condensate Trap With Water ...................................... 37
Purge Gas Lines ...................................................................... 38
Adjustments ....................................................................... 38-45
Set Gas Input Rate ............................................................ 3824
Set Temperature Rise .............................................................. 44
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 535-80021 Pdnted in U.S.A. Fom_ 58MVP-11SI 1 2-01 Re#aces: 58MVP-10SI
Pg
Set Thermostat Heat Anticipator ............................................ 45
CHECK SAFETY CONTROLS .................................................. 45
Check Primary Limit Control ................................................. 45
Check Pressure Switch ........................................................... 45
CHECKLIST ................................................................................ 45
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person-
nel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as clean-
ing and replacing air filters. All other operations must be per- formed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that
may apply. Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1999/ANSI Z223.1-1999 and the Installation Standards, Warm
Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the current edition of the
CAN/CGA-BI49.1- and .2-M95 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have a fire extinguisher available
during start-up and adjustraent procedures and service calls. Recognize safety information. This is the safety-alert symbolz_ x.
When you see this symbol on unit or in instructions and manuals, be alert to potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with safety-alert symbol. DANGER
identifies the most serious hazards which win result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability,
or operation.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
¥!_['ff:.llii[*l_'l
Electrostatic discharge can affect electronic components, Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre- vent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the coturol, and the person at the same electrostatic potential.
1, Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CON- TROL PRIOR TO DISCHARGING YOUR BODY'S ELEC- TROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person's hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), FgraJy touch furnace again before touching control or wires.
5. Use this procedme for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body's electrostatic charge to ground to protect the control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded
objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
INTRODUCTION
The 58MVP Multipoise Condensing Ga_-Fired Furnaces are CSA
(A.G.A. and C.G.A.) certified for natural and propane gases and for installation in alcoves, attics, basements, closets, utility rooms.
crawlspaces, and garages. The furnace is factory-shipped for use
with natural gas. A manufacturer's accessory gas conversion kit is required to convert furnace for use with propane gas.
These furnaces SHALL NOT be installed directly on carpeting,
tile, or any other combustible material other than wood flooring. In
downflow installations, a manufacturers accessory floor base
MUST be used when installed on combustible materials and wood
flooring. Special base is not required when this furnace is installed on manufacturer's Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. The design of this furnace line
is not CSA (A.G.A. and C.G.A.) certified for installation in mobile homes, recreation vehicles, or outdoors. These furnaces are suit-
able for installation in a residence built on site or a manufactured residence completed at final site.
These furnaces are shipped with the drain and pressure tubes connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT. or HORIZONTAL LEFT (supply-air discharge direction) applica- tions as shown in Fig. 1, See details in Applications section.
These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
Installer Packet includes:
Installation, Start-Up, and Operating lnstnlctions
Service and Maintenance Instructions User's Information Manual
Warranty Cert'fficate
Loose Parts Bag includes: Quantity
Pressure tube extension 1 Collector box or condensate (rapextension tube l
Inducer housing drain tube 1
l/2-in. CPVC street elbow 2
Drain tube coupling 1 Drain tube coupling grommet I
Vent and combustion-air pipe support 2 Combustion-air pipe perforated disk assembly 1 Condensate trap hole filler plug 3
Vent and combustion-air intake hole filler plug 2
This furnace must be installed with a direct-vent (combustion air
and flue) system and a factory accessory termination kit. In a direct-vent system, all air for combustion is taken directly from the outside atmosphere and all flue products are discharged to the outside atmosphere. See furnace and factory accessory termination kit instructions for proper installation.
Before installing the furnace in the United States, refer to the current edition of _ NFGC and the NFPA 90B. For copies of the
NFGC and NFPA 90B, contact the National Fire Protetion
26 _/_ '
26 _
24 I_,,m
2-IN. COMBUSTION- AIR CONN
GAEC NN-- tt
2-IN. VENT CONN _
_-IN. DIA THERMOSTAT -- _.Jv
r7 ................. "q_
14 I/_ SIDE INLET
TYP i
ENTRY
TRAP LOCATION
f ONDENSATE DRAIN
(DOWNFLOW &
HORIZONTAL LEFT)
7_-IN. OIA
/f POWER CONN
7/_-IN. OIA ACCESSORY
POWER ENTRY
I
i i
DRAIN TRAP 279/. LOCATION TYP
i""-- CONDENSATE lI
(ALTERNATE UPFLOW) 24
--_ -- 17 _'le" 97A6 "
TYP
AIRFLOW
CONDENSATE DRAIN
TRAP LOCATION --'_
(OOWNFLOW &
HORIZONTAL RIGHT)
OR ALTERNATE
1/2-1N, DIA GAS CONN
30t_"
1
26¼"
19"_ 1_/16"
2-1NCOMBUST,ON-
.,._ _ ½-IN DIA
_ INDIA
GAS CONN
POWER DONN
-IN DIA
THERMOSTAT ENTRY
,I VENT CONN
;._
SIDE INLET
39 %
T
L_
I ".4=- 23 i/_., TYP
SIDE INLET
26 %16 TYP
3ONDENSATE
DRAIN LOCATION (UPFLOW)
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. ifflex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
2. Minimum return-air opening at furnace: a. For 800 CFM-16-in. round or 14% x 12-in. rectangle.
1¼e"..im
INLET
.e- _1/16" DRAIN LOCATION
(UPFLOW)
DIMPLE LODATORS
FOR HORIZONTAL
HANGING
b. For 1200 CFM-26-in. round or 14% x 19V_-in.rectangle. c. For 1600 CFM-22-in. round or 14% x 23%-in. rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets.The use of both side inlets, a combination of 1 side and the bottom, orthe bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM.
A99111
Dimensions (In.)
UNIT SIZE
040-14"
060-14 080-14
080-20 100-20 120-20
These dimensions reflect the wider casin(
A
24-1/2"
17-1/2
21 21 21
24-1/2
for the Trophy (96.6 percent AFUE) furnace.
D E
22-7/8" 23*
15-7/8 16 19-3/8 19-1/2
19-3/8 19-1/2
19-3/8 19-1/2 22-7/8 23
Fig. 2--Dimensional Drawing
A,_sociation Inc.. Batterymarch Park. Quincy. MA 02269: or American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209.
Before installing the furnace in Canada, refer to the current edition of the NSCNGPIC. Contact Standard Sales CSA International, 178
Rexdale Boulevard, Etobicoke. (Toronto) Ontario, Canada M9W
IR3.
Installation must comply with regulations of serving gas supplier and local building, heating, plumbing or other codes in effect in the
_ea in which installation is made. In absence of local codes, installation must comply with the NFGC in the United States and
the NSCNGPIC in Canada.
These instructions cover minimum requirements for a safe instal-
lation and conform to existing national standar&s and safety codes. In some instances, these instructions exceed certain local codes
and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these
instructions as a minimum for a safe installation.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air
temperature rise, unit leveling, and unit sizing. Improper
installation or misapplication of furnace can require excessive servicing or cause premature component failure.
Improper installation, adjustment, alteration, service, mainte- nance, or use can cause carbon monoxide poisoning, explo-
sion, fire. electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distribu- tor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning could result in electrical shock, ftre,
personal injury, or death.
For accessory installation details, refer to applicable installation literature.
INSTALLATION
Ttis forced ar furnaceisequippedforu=e,_ithnaturalgasat aJtittJdes0 - 10,_ ff (0 *3,_). Anaccessorykit,supplied_ _e manufacturer,shaJlbe usedtoc_t to propanegasuse or may _ r_u_ f_ _ _
flJrnaceis fat indoorinstaJlationina I_ilotng constructed_ site.]_is furnace may be _nstailedin a mandacturecl(mobile)
hc_e v,he_ statedon ratingpl_e andusingfactc_y authcciz_l_t.
furnacemay be ins_lled an c_l:i e ftoo_n9 in _ orcloset_ rrir_murndear_ncefrom o:_bus_iblematerial.
Ttis applmrce reqdres a speaal ve_ng system Refertothe itz_taJ_on _q._rt_ic_ fo¢par_ _stand _ of instaHa_or_Th_ furnaceis fc_ usewithschedule-40PVC, PVC-DWV, or ABS-DWVppe, andmust notbevent_ in _ _ o_ _ _pli_ce_ C_nslruc0on_rough _ch ve,_/air intake pipesmaybe installedis ma_rnum24 inches (600 ram),rrinimurn3'4inches (19 rr_) thid_ss (inclua_ roolingmaterials).
FurreceraJstbeinaalledlevel,or pitchedfo_wadw_hin1/2inchoflevel forproperdrainage.Failure_ill resuttin eq_pmea orpropertydamage.See
Installa_onManualfo_IMPQRTANTunit
suppoddetailsonho_
applications.
1/2" MAX
LEVEL (0") _
UPFLOWOR I I/
DOWNFLOW
MINIMUMINCHESCLEARANCE TO
COMBUSTIBLECONSTRUCTION
ALLP(TolTIONS:
* ICmlimumfrontdearanceforsen,ice30 bches
¢/_mm).
DOWlI,FLOWPOntoONS:
1" ForinstaJlalJ_oncembu_l_leIIoorsonlywhen
inst_ledm specktbaseNo.K_IALL Cdl /_sembly,P_tNO.CO5orCKS,orC_ilC_sing,Part
No.KCAKC
HORIZONTAL POSITIONS:
§ aearanceshownisfor_r inletandairouzelend. Unecottactispem=ssibleortyI:_tweenlines
"l_s lurnaee is _ro_d f_ UFFLCW, DOWNFLOWarrl
HO_ZONTAL inst_ons,
LEVEL (0")
112" M__HORIZONTAL
120 s_zeFurnacerequre1inchbott0md_ to
325400-201RE_.A
(UT.toP)
Fig. 3--Clearances to Combustibles
A99_03
4
BLOWERSHELF FURNACE
CONDENSATE _'- DC'OR -- FURNACE
SIDE FURNACE SIDE
F,E<D 20', ,'/2 F,E
L_ALTERNATE DRAIN CONN CONN
TUBELOCATION
CONDENSATE TRAP"_ SIDE VIEW FRONT VIEW END VIEW FRONT VIEW
DRAINTUBE LOCATION
UPFLOW APPLICATIONS EXTERNAL UPFLOW APPLICATIONS APPLICATIONS
DRAIN DRAIN
DOWNFLOW AND ALTERNATE HORIZONTAL
SIDE
I
LOT: 'i OqaE F 7
GUIDES
(WHEN USED)
FRONT VIEW SIDE VIEW
Fig. 4---Condensate Trap
APPUCATIONS
Step 1.--General
Some assembly and modifications are required for furnaces installed in any of the 4 applications shown in Fig. 1. All drain and pressure tubes are connected as shown in Fig. 5. See appropriate application instructions for these procedures.
Step 2--Opflow Applications
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned
air is discharged upwards. CONDENSATE TRAP LOCATION (FACTORY-SHIPPED
ORIENTATION) The condensate trap is factory installed in the blower shelf and
factory connected for UPFLOW applications. A factury-supplied tube is used to extend the condensate trap drain connection to the
desired furnace side for field drain attachment. See Condensate Trap Tubing (Factory-Shipped Orientation) section for drain tube
extension details. CONDENSATE TRAP TUBING (FACTORY-SHIPPED
ORIENTATION) NOTE: See Fig. 5 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes
COLLECTOR BOX TO TRAP RELIEF PORT
IizOD
INDUCER HOUSING
DRAINCONNECTION
1/40D
% OO
COLLECTOR BOX
DRAINCONNECTION SCREW HOLE FOR
UPFLOW OR DOWN-
7/8 (OPTIONAL)
__..__, FLOW APPLICATIONS
2114_ _-_ lz2-lN.PVC ORCPVC
These tubes should be factory attached to condensate trap and pressure switch ready for use in UPFLOW applications. These
tubes can be identified by their connection location and also by a color label on each tube. These tubes are identified as
follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green
label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube The condensate trap drain connection must be extended for
field attachment by doing the following: a. Determine location of field drain connection. (See Fig. 2 or
5.)
NOTE: If internal filter or side filter/media cabinet is used, drain tube should be located to opposite side of casing of return duct
attachment to assist in filter removal
b. Remove and discard c_qing drain hole plug button from
desired side.
c. Install drain tube coupling grommet (factory-supplied in
loose parts bag) in selected casing hole.
d. Slide drain robe coupling (factory-supplied in loose parts
bag) through grommet so long end of coupling faces blower.
A93026
-i i
©
DRAIN TUBE (BLUE
& WHITE STRIPED)
TUBE (PINK)
INDUCEI
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
DRAIN TUBE (BLUE)
TUBE (GREEN)
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED /
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
1/2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
Fig. 5---Factory-Shipped Upflow Tube Configuration
(Shown With Blower Access Panel Removed)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (RIGHT
DRAIN OPTION)
A94213
©
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK) --_
COLLECTOI
TUBE (GREEN)
DRAIN TUBE (GREEN)
TRAP
HOUSING
DRAIN TUBE
(VIOLET)
Fig. 6_Alternate Upflow Tube Configuration and
Trap Location
© ©
A94214
e. Cement 2 factory-supplied l/2-in, street CPVC elbows to
rigid drain tube connection on condensate trap.(See Fig. 5.) These elbows must be cemented together and cemented to
condensate trap drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink, preventing draining.
f. Connect larger diameter drain tube and clamp (factory-
supplied in loose parts bag) to condensate trap and clamp
securely.
g. Route tube to coupling and cut to appropriate length. h. Attach tube to coupling and clamp securely.
CONDENSATE TRAP LOCATION (ALTERNATE UPFLOW ORIENTATION)
An alternate location for the condensate trap is the left-hand side
of casing. (See Fig. 2 and 6.)
NOTE: If the alternate left-hand side of casing location is used, the factory-connected drain mad relief port tubes must be discon- nected and modified for attachment. See Condensate Trap Tubing
(Alternate Upflow Orientation) section for tubing attachment.
To relocate condensate trap to the left-hand side, perform the
following:
I. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole f'dler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
4. Install casing hole filler cap into blower shelf hole where trap
was removed.
5. Fill unused condenstate trap c_sing holes with placstic filler
caps ffactory-supplied in loose parts bag).
CONDENSATE TRAP TUBING (ALTERNATE UPFLOW ORI- ENTATION)
NOTE: See Fig. 6 or tube routing label on main furnace door to confirm location of these tubes.
1. Collector Box Drain Tube Connect collector box drain tube (blue label) to condensate
trap.
NOTE: On I7-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks.
2. Inducer Housing Drain Tube a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to condensate trap.
6
DRAINTUBE (BLUE)
COLLECTOR BOX !
CAPII t
PLUG
COLLECTORBOX --
TUBE (GREEN)
COLLECTORBOX
TUBE(PINK)
DRAIN TUBE (BLUE & WHITE STRIPED)
EXTENSION TUBE
TRAP
©
INDUCER HOUSINC
DRAIN TUBE (VIOLET)
A94.215
Fig. 7--Downflow Tube Configuration
(Left-Hand Trap Installation)
b. Use inducer housing drain extension tube (violet label and
factory-supplied in loose parts bag) to connect LOWER
inducer housing drain connection to condensate trap. c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Connect relief port tube (green label) to condensate trap.
b. Extend this tube (if required) by splicing to small diameter
tube (factory-supplied in loose par_s bag).
c. Determine appropriate length, cut, and connect tube.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT Refer to Condensate Drain section for recommendations and procedures.
PRESSURE SWITCH TUBING The LOWER collector box pressure tube (pink label) is factory
connected to the pressure switch and should not require any modification.
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.
UPPER CO1,LECTOR BOX AND INDUCER HOUSING (UN- USED) DRAIN CONNECTIONS
Upper Collector Box Drain Connection Attached to the UPPER collector box drain connection a
factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.
TUBE(GREEN)
© ©
DRAINTUBE(BLUE)
TUBE(PINK)
DRAIN TUBE (BLUE & WRITE STRIPED)
EXTENSION TUBE
DRAIN TUBE (VIOLET)
TRAP
©
EXTENSION DRAIN TUBE
COUPLING
Fig, 8---Downflow Tube Configuration
(Right-Hand Trap Installation)
Upper Inducer Housing Drain Connection Attached to the UPPER (unused) inducer housing drain connection
is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
Step 3---Downflow Applications
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned
air is discharged downwards.
CONDENSATE TRAP LOCATION The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location as shown in Pig. 2, 7, or 8. To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
4. Install casing hole filler cap into blower shelf hole where trap was removed.
5. Fill unused condenstate trap casing holes with placstic filler caps (factory-supplied in loose parts bag).
7
R BOX
R BOX
A94216
CONDENSATETRAPTUBING
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
I. Collector Box Drain Tube
a. Remove factory-installed plug from LOWER collector box
drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector box
drain tube (blue label) which was connected to condensate trap.
c. Connect LOWER collector box drain connection to con-
densate trap. (l.I Condensate Trap Located on Left Side of Cmsing
(a.) Connect LOWER collector box drain tube (blue
and white striped label) to condensate trap. Tube does not need to be cut.
(b.) Clamp tube to prevent any condensate leakage.
(2.1 Condensate Trap Located on Right Side of Casing
/a.) Install drain tube coupling (factory-supplied in
loose parts bag) into collector box drain tube (blue and white striped label) which was previ-
ously plugged.
(b.) Connect larger diameter drain tube (factory-
supplied in loose parts bag) to drain tube cou- pling, extending collector box drain tube for
connection to condensate trap.
(c.) Route extended collector box drain tube between
gas valve and inlet housing as shown in Fig. 8. (d.) Determine appropriate length and cut. (e.) Connect to condensate trap.
(f.) Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and factory-
supplied in loose parts bag) to connect LOWER inducer
housing drain connection to the condensate trap.
e. Connect inducer housing drain connection to condensate
trap. (1.) Condensate Trap Located on Left Side of Casing
(a.) Determine appropriate length and cut. (b.) Connect tube to condensate trap. (c.) Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
(a.) Route inducer housing drain tube (violet label)
directly from collector box drain to condensate
trap. (b.) Determine appropriate length and cut. (c.) Connect tube to condensate trap. (d.) Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
Refer to Pressure Switch Tubing section for connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refer to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH TUBING One collector box pressure tube (pink label) is factory connected to
the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be dis-
connected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory
connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZON-
TAL RIGHT applications.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door
to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to
pressure switch.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connection by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was
previously connected to pressure switch by splicing to remain- ing small diameter tube (factory-supplied in loose parts bag).
5. Route this extended tube (pink label) to condensate trap relief
port connection.
6. Determine appropriate length, cuL and connect tube.
7. Clamp tube to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda- tions and procedures.
Step 4--Horizontal Left (Supply-Air Discharge) Applications
A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace,
and conditioned air is discharged to the left.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
CONDENSATE TRAP LOCATION The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location ms shown in Fig. 2 or 9.
To relocate condensate trap from the blower shelf to desired location, perform the following:
i. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward
and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts
bag) into blower shelf hole where trap was removed.
4. Install casing hole filler cap into blower shelf hole where trap
was removed.
8
AL DRAIN TUBE
(BLUE AND WHITE STRIPED)
BOX
CONDENSATE
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
TRAP
COLLECTC
BOX EXTENSION
DRAINTUBE
EXTENSIONTUBE
040, 060, AND 080 HEATING INPUT FURNACES
Fig. 9--Horizontal Left Tube Configuration
5. Fill unused condenstate trap casing holes with placstic filler caps (factury-supplied in loose parts bag).
CONDENSATE TRAP TUBING
NOTE: See Fig. 9 or tube routing label on main furnace door to check for proper connections.
1. Collector Box Drain Tube a. Install drain tube coupling (factory-supplied in loose parts
bag) into collector box drain tube (blue label) which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp (factory-
supplied in loose parts bag) to drain tube coupling, extend- ing collector box drain tube.
c. Route extended tube (blue label) to condensate trap and cut
to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to condensate
trap.
b. Use i,nducer housing drain extension tube (violet label and
factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was previ-
ously connected to condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).
COLLECTOR
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
b. Route extended collector box pressure tube to relief port
connection on condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
CONDENSATE TRAP FIELD DRAIN ATFACHMENT Refer to Condensate Drain section for recommendations and
procedures. PRESSURE SWITCH TUBING
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any
modification. NOTE: See Fig. 9 or tube routing label on main furnace door to
check for proper connections. CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda- tions and procedures.
CONSTRUCT A WORKING PLATFORM Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 10.)
NOTE: Combustion-air and vent pipes are restricted to a mini- mum length of 5 ft. (See Table 6.)
9
TUBE(GREEN)
PRBOX
;ER HOUSING
DRAIN TUBE (VIOLET)
[BLUE)
A00215
INTAKE
MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS
TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
SHUTOFF
GAS VALVE
SEDIMENT TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
_ONDENSATE
TRAP
Fig. 10_Attic Location and Working Platform
NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 fi) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe.
(See Fig. l0 or 32.)
Step 5_Horizontal Right (Supply-Air Discharge) Applications
A horizontal fight furnace application is where furnace blower is located to the left of combustion and controls section of furnace,
and conditioned air is discharged to the right.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes.
NOTE: The auxiliary junction box (J-box) MUST be relocated to opposite side of furnace casing. (See Fig. li.) See Electrical
Connection section for J-box relocation. CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or I I, To relocate condensate trap from the blower shelf to desired
location, perform the following:
I. Remove 3 tubes connected to condensate trap,
2. Remove trap from blower shelf by gently pushing tabs inward
and rotating trap.
ACCESS OPENING FOR TRAP
DRAIN
A93031
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
4. Install casing hole filler cap into blower shelf hole where trap
was removed,
5. Fill unused condenstate trap casing holes with placsfic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube
a. Remove factory-installed plug from LOWER collector box
drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector box
drain tube (blue label) which was previously connected to condensate trap.
c. Connect LOWER collector box drain tube (blue and white
striped label) to condensate trap. Tube does not need to be cut.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
l0
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 11--Horizontal Right Tube Configuration
(BLUE)
(GREEN)
COLLECTOR BOX TUBE (PINK)
RELOCATED HERE
TRAP
A0_14
d. Use inducer housing drain extension tube (violet label and
factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
e. Determine appropriate length, cut. and connect tube to
condensate trap.
f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refer to Condensate Drain section for recommendations and
procedures. PRESSURE SWITCH TUBING
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be dis- connected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZON-
TAL RIGHT applications.
NOTE: See Fig. I l or tube routing label on main furnace door to check for proper connections.
Relocate tubes as described below.
I. Disconnect collector box pressure tube (pink label) attached to
pressure switch.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connection
by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
4. Use remaining small diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (pink labell
which was previously connected to pressure switch.
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION Refer to Condensate Drain Protection section for recommenda-
tions and procedures. CONSTRUCT A WORKING PLATFORM
Construct working platform where all required furnace clearances am met. (See Fig. 3 and 10.)
The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: Combustion-air and vent pipes are restricted to a mira- mum length of 5 ft. (See Table 6.)
NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 10 or 29.)
LOCATION
Step 1---General
When a furnace is installed so that supply ducts carry air to areas outside the space containing the furnace, return air must also be
handled by ducts sealed to furnace casing. The ducts terminate outaide the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space.
II
Furnace may be located in a confined space without special provisions for dilution or ventilation air. This furnace must be
installed so electrical components are protected from water.
UPFLOW OR DOWNFLOW
NOTE: For proper furnace operation, install furnace so that it is level or pitched forward within 1/2 in. to ensure proper condensate drainage from secondary heat exchangers.
HORIZONTAL
A93025
MAX 857=
If these furnaces are used during construction when adhe- sives, sealers, and/or new carpets are being installed, make
sure all combustion and circulating air requirements are followed. If operation of furnace is required during construc-
tion, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine, when burned with
combustion air, form acids which will cause corrosion of heat exchangers. Some of these compounds ,are found in paneling,
dry wall adhesives, paints, thinners, masonry cleaning mate- rials, and many other solvents commonly used in the con-
struction process.
Excessive exposure to contaminated combustion air will result in safety and performance related problems.
Provide ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown on unit's clear-
ance to combustibles label. (See Fig. 3.) Locate furnace where available electric power and gas supplies meet specifications on
furnace rating plate.
MIN 557=
A93042
NOTE: These furnaces are designed for a minimum continuous return-air temperature of 60°F or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temporature must not exceed a maximum of 85°F. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls.
Locate furnace as close to center of air distribution system as possible.
Locate furnace so combustion-air pipe lengths are not exceeded.
Refer to Table 6.
BACK'
A93043
12
_32°F MINIMUM INSTALLED
%%%%o
/!\
A93058
Step 2--Low-Fire Only Installation
This 58MVP furnace can be installed to operate in the low-fire only heating mode when sized using the low-fire heating capacity.
This is accomplished by placing setup switch SW-2 in the ON position to provide only low-fire-heat operation. See Fig. 25 and
Table 10. With this setup, high-fire operation will not occur.
When the model no. on the furnace rating plate is followed by an asterisk (*), the furnace has an alternate low-fire only efficiency
rating as listed in the GAMA and CEC directories. This alternate
rating will be listed as the furnace model number followed by an
(-L) suffix.
18-IN. MINIMUM
TO BURNERS
A93044
When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a
minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When
furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire
Protection Association, Inc.
¥__
The furnace can operate in the high-fire mode when certain fault conditions occur. The following precautions should be taken:
1. Size gas piping based on the high-fire input.
2. Check the high-fire input and adjust it per the main literature instructions.
NEVER assume the high-fire input rate is not important for low-fire-only installation.
Step 3--Furnace Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to
control flow of air must prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a
means to prevent operation of either unit unless damper is in full-heat or full-cool position.
Step 4--Hazardous Locations
INSTALLATION
Step 1--Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(sL leveling legs may be desired. (See Fig. 12.) Install field-supplied,
corrosion-resistant 5/16-in. machine bolts and nuts.
5/16_
1¾"
A89014
Fig. 12--Leveling Legs
NOTE: The maximum length of bolt should not exceed 1-1/2 in.
1. Position furnace on its back. Locate and drill a 5/16 in. diameter hole in each bottom corner of furnace. (See Fig. 12.)
Holes in bottom closure panel may be used as guide locations.
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside
nut to secure arrangement.
13
NOTE: Bottom closure mttst be used when leveling legs are used.
See Bottom Closure Panel section.
Step 2--Installation in Upflow or Downflow Applications
NOTE: This furnace is approved for use on combustible flooring
when manufacturer's accessory floor base, Part No.
KGASB020 IALL, is used. Manufacturers accessory floor base in not required when this furnace is installed on manafacturer's Coil
Assembly Part No. CD5 or CK5, or Coil Box part No. KCAKC is used.
I. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table l and Fig. 13.
3. Construct plenum to dimensions specified in Table l and Fig.
13.
4. If downflow subbase (KGASB) is used, install as shown in Fig. 14.
If coil assembly CD5 or CK5 or Coil Box KCAKC is used, install as shown in Fig. 15.
NOTE: Remove furnace perforated, discharge duct flanges when they interfere with mating flanges on coil on downflow subbase.
To remove furnace perforated, discharge duct flange, use wide duct pliers or duct flange tool to bend flange back and forth until
it breaks off. Be careful of sharp edges. (See Fig. 16.)
Do not bend duct flanges inward as shown in Fig. 16. This will affect airflow across heat exchangers and may cause limit
cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210 ° as shown in Fig. 16.
Step 3--Installation in Horizontal Applications
These furnaces can be installed horizontally in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung from floor joist or installed on suitable blocks or pad.
Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See Fig. 17.) Cut hanger bolts (4 each 3/8-in.
all-thread rod) to desired length. Use l X 3/8-in. flat washers, 3/8-in. lockwashers, and 3/8-in. nuts on hanger rods as shown in
Fig. 17. Dimples are provided for hole locations. (See Fig. 2.)
The entire length of furnace MUST be supported when
furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and
center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf
8J'ea.
AIR DUCTS
Step 1--General Requirements
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCAJ, Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). Or consult factory The Air Systems Design
Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system
design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace• the return air must
also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer. Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance system performance. When air conditioning is used. a vapor
barrier is recommended. Maintain a I-in. clearance from combustible materials to supply air
ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
Step 2--Ductwork Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 fi of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both acoustical hning and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Step 3--Supply Air Connections
UPFLOW FURNACES Connect supply air duct to 3/4-ni. flange on furnace supply-air
outlet. The supply-air duct attachment must ONLY be connected to furnace supply-/outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accesso-
ries MUST be connected external to furnace main casing.
DOWNFLOW FURNACES Connect supply-air duct to supply-air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace supply/outiet or air conditioning coil casing (when used), when
installed on non-combustible material. When installed on combus- tible material, supply-air duct attachment must ONLY be con-
nected to an accessory subbase or factory approved air condition- ing coil casing. DO NOT cut main furnace casing to attach supply
side air duct, humidifier, or other accessories. All accessories
MUST be connected external to furnace main casing. HORIZONTAL FURNACES
Connect supply-air duct to supply air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier•
or other accessories. All accessories MUST be connected external to furnace main casing.
Step 4,--Return Air Connections
UPFLOW FURNACES The return-air duct must be connected to bottom sides (left or
right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 1. Bypass humidifier may be attached into
unused side return air portion of the furnace casing. DO NOT connect any portion of return-air duct to back of furnace casing.
DOWNFLOW AND HORIZONTAL FURNACES The return-air duct must be connected to return-air opening provided as shown in Fig. 1. DO NOT cut into casing sides or back
to attach any portion of return-air duct. Bypass humidifier connec- tions should be made at ductwork or coil casing sides exterior to
furnace.
14
A96283
Fig. 13--Floor and Plenum Opening Dimensions
FURNACE
(OR COIL CASING
WHEN USED)
-- COMBUSTIBLE
FLOORING
SUBBASE
SHEET METAL
PLENUM
__FLOOR --
OPENING
A96285
Fig. 14--Furnace, Plenum, and Subbase
Installed on a Combustible Floor
Table l_pening Dimensions (In.)
FURNACE
CASING
WIDTH
17-1/2
21
24-1/2
Downflow Applications on Non-Combustible Flooring
Downflow Applications on Combustible Flooring Using KGASB Subbase Fumase with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CE)5 or CK5 Coil Assembly or KCAKC Coit Box
Downflow Applications on Non-Combustible Floodng
Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Non-Combustible Floodng
Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
APPLICATION
Upflow Applications
Upflow Applications
Upflow Applications
15
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
--COMSUSTIBLE_-_
FLOORING
._.SHEETMETAL
PLENUM
__ FLOOR --
OPENING
A96284
Fig. 15_Furnace, Plenum, and Coil
Assembly or Coil Box Installed
on a Combustible Floor
PLENUM OPENING
A B
16 24-1/8
15-7/8 19 15-1/8 19
15-1/2 19 19-1/2 24-1/8
19-3/8 19
18-5/8 19
19 19
23 24-1/8
22-7/8 19 22-1/8 19
22-1/2 19
FLOOR OPENING
C
16-5/8 16-1_
16-3/4
16-1/2
20-1/8
20
20-1/4
20
23-5/8 23-1/2
23-3/4
23-1F2
D
24-3/4
19-5/8
20-3/8
2O
24-3/4
19-5/8
20-3/8
20
24-3/4
19-5/8 20-3/8
2O
Loading...
+ 33 hidden pages