58NVP
[HEATING & COOUNG
\isit_ v_wcarrier.corn
VariabMe-Capacity Condensing Gas Furnace
tnstallation, Start-Up, and Operating
For Sizes 040 120, Series t80
NOTE: Read the entire instruction
manual bei\_re starting the installation
A93040
4-VVay MuMtipoise Dkect-Vent
This symbol --> indicates a change since the last issue,
Index Page
SAFETY CONSIDERATIONS ..................................................... 2
DIMENSIONAL DRAWING ........................................................ 3
(learances to ( ombustibles ...................................................... 4
<;ODES AND STANDARDS ........................................................ 4
ELE< TROSTATIC DIS<HARGE (ESD) PRE(AUTIONS ........ 5
INTRODU< TION .......................................................................... 5
APPLICATIONS ............................................................................ 6
General ...................................................................................... 6
Upflow Applications ................................................................. 6
Downflow Applications ............................................................ 8
Horizontal Left (Supply-Air Discharge) Applications ............ 9
Horizontal Right (Supply-Air Discharge) Applications ........ 12
LO< ATION .................................................................................. 13
General .................................................................................... ] 3
Low-Heat Only Installation .................................................... 14
Furnace Location Relative to ( oGling Equipment ................ 14
Hazardous Locations ............................................................... 15
INSTALLATION ......................................................................... 15
Leveling Legs (If Desired) ..................................................... 15
Installation In [pflow or Downflow Applications ................ 15
Installation In Horizontal Applications .................................. 15
Air Ducts ................................................................................. ] 7
General Requirements ....................................................... 17
Ductwork Acoustical Treatment ....................................... 18
Supply-Air Connections .................................................... 1S
Return=Air < onnections ..................................................... 18
Filter Arrangement .................................................................. 18
Bottom Closure Panel ............................................................. i9
Gas Piping ............................................................................... 19
Electrical ( onnections ............................................................ 20
] 15-v Wiring ...................................................................... 20
24-v Wiring ........................................................................ 22
Accessories ........................................................................ 22
Direct Venting ......................................................................... 23
Removal of Existing Furnaces fl'om
( ommon Vent Systems ......................... 23
Combustion-Air and Vent Piping .................... 23
Concentric Vent and Combustion-Air Temaination
Kit Installation ................................ 29
Multiventing and Vent Tem_inations ................. 32
Condensate Drain ................................. 35
NNNNN
As an ENERGY STAR're
Pmtne< Came* ('o_pora-
don has detem_ined that
this Ixoduct meets the E\ u REGISTERED QUALITY SYSTEM
ERGY STAR® guidelh_es
fbl energ 3 efficiency
START-UP, ADJUSTMENTS AND SAFETY CHECK. _ 36
AIRFLOW
4>
¢
HORIZONTAL HORIZONTAL
LEFT RIGHT
AIRFLOW AIRFLOW
©
AIRFLOW
Fig. 1--MuRipoise Orientations
General ............................................................................... 35
Application ........................................ 35
Condensate Drain Protection ...................... 36
General ......................................... 36
Select Setup Switch Positions ........................................... 36
Prime < ondensate Trap With Water ................................. 37
Purge Gas Lines ................................................................ 38
Sequence of Operation ...................................................... 38
Single-Stage Thermostat and Two-Stage Heating
(Adaptive Mode) .......................... 38
Two=Stage Them_ostat and Two=Stage Heating ...... 39
Cooling Mode .............................. 40
Them_idistat Mode .......................... 40
Supe*-Dehumidif) Mode ............................ 40
Continuous Blower Mode ...................... 41
Heat Pump ................................ 41
Component Test ............................ 41
Ac{iustments ................................... 4 l
Set Gas Input Rate .......................... 41
Set Temperam*e Rise .......................... 48
Set Them_ostat Heat Anticipator .................. 49
A93041
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No 535-80130 Printed in U.S.A. Form 58MVP-14SI Pg 1 5-04 Replaces: 58MVP-13SI
(heck Safety Controls 49
Check Primary Limit Control 49
Check Pressure Switch ................................................. 50
CHECKLIST ...................................................................... 50
SAFETY CONSIDERATIONS
M
(ITS AND ABRASION HAZARD
Failure to %11ow this caution may result in personal ir!iury.
Sheet metal parts may have sharp edges or burrs Use care and
wear appropriate protective clothing and gloves when han-
dling parts Failure to follow this caution could result in
personal injury
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of _hrnace can require
excessive servicing or cause premature component failure
Application of this l\maace should be indoors with special
attention gi\en to xent sizing and material, gas input rate, air
temperature rise, unit leveling, and unit sizing
FIRE, EXPLOSION, ELECTRICAL SHOCK AND
(ARBON MONOXIDE POISONING HAZARD
Failure to follow this wariaing could result in electrical shock,
firQ personal injury, or death.
Improper installation, adjustment, alteration, service, mainte-
nancQ or use can cause carbon monoxide poisoning, explo-
sion, tire, electrical shock, or other conditions which may
cause personal ir!iu V or property damage. Consult a qualified
installer, sela-ice agency, local gas supplier, or your distribu-
tor or branch ibr information or assistance. The qualified
installer or agency must use only [i_ctory-authorized and
listed kits or accessories when modi_)ing this prodact.
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
personnel should ilistaH, repair, or service heating equipment.
Untrained personnel can perform basic maintenance _hnctions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in literature, on tags, and
or* labels attached to or shipped with unit and other safety
precautions that may apply.
These instructions cover the n?inin?um requirements and conform
to existing national standards and sa_kty codes. In some instances,
these instl_actions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial constl_./ction practices. We require these instl_./ctions as a
minimum %r a safe installation.
Wear safety glasses and work gloves Have a fire extinguisher
axailable during start-up and adjustment procedures and serxice
calls.
Recognize safety information. This is the safbty-alert symbol .A_
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury
Understand these signal words: DANGER, WARNING, CAU-
TION, and NOTE. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards which will
result in severe personal injm2¢ or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION
is used to identii) unsaI:_ practices which may result in minor
personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
The 58MVP Multipoise Condensing Gas-Fired Furnaces are
C.S.A. (formerly AGA and CGA) design=certified %r natural and
propane gases (see I\N'nace rating plate) and for installation in
alcoves, attics, basements, closets, utility rooms, crawlspaces, and
garages. The furnace is factory-shipped [br use with natmal gas. A
C.S.A. (formerly AGA and CGA) listed gas conversion kit is
required to convert f_arnace %r use with propane gas.
See Fig. 3 for required clearances to combustibles.
Maintain a l-in. clearance fiom combustible materials to supply air
ductwork for a distance of 36 inches horizontally from the ftmaace.
See NFPA 90B or local code _br t:urther requirements.
These furnaces SHALL NOT be installed directly on carpeting,
tile, or any other combustible material other than wood flooring. In
downflow installations, factory accesso_' floor base MUST be
used when installed on combustible materials and wood flooring.
Special base is not required when this Nriaace is installed on
manufacturer's (:oil Assembly Part No. CD5 or CK5, or when (Toil
Box Part No. KCAKC is used. These fi/rnaces are suitable for
installation in a structure built on site or a manu£_ctured building
completed at final site. The design of this furnace line is NOT
C.S.A. (formerly AGA and CGA) design-certified for installation
in recreation vehicles, manufactured (mobile) homes or outdoors.
This Nmace is designed for continuous return-air minimum
temperature of 60 °F db or intermittent operation down to 55°F db
such as when used with a night setback thermostat. Return-air
temperature must not exceed 85°F db. Failure to follow fl_ese
remm air limits may affect reliability of heat exchangers, motors
and controls. (See Fig. 4.)
These Nmaces are shipped with the drain and pressure robes
connected for UPFLOW applications. Minor modifications are
required when used in DOWNFLOW, HORIZONTAL RIGHT, or
HORIZONTAL LEFT (supply-air discharge direction) applica-
tions as shown in Fig. 1. See details in Applications section.
This Nrnace must be installed with a direct-vent (combustion air
and flue) system and a fi_ctory accessory termination kit. In a
direct-vent system, all air for combustion is taken directly fiom the
outside atmosphere and all flue products are discharged to tl_e
outside atmosphere. See fi/rnace and factoQ" accessory termination
kit instructions for proper installation.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks
to check all connections as specified in the GAS PIPING section
of these instrtlctions.
Always install furnace to operate within the furnace's intended
temperature-rise range with a duct system which has an external
static press-are within the allowable range as specified in the SET
TEMPERATURE RISE section of these insm/ctions.
When a /:umace is installed so that the supply ducts cat_" air
circulated by the _imaace to areas omside the space containing tl_e
Nmace, the return air must also be handled by a duct(s) sealed to
the furnace casing and terminating outside the space containing the
i:t_rnace.
O
AIRFLOW
TYP
OUTLET
A m
, 1biN DiA GAS CONN
27
CONDENSATE DRAIN
TRAP LOCATION _
(DOWNFLOW &
HORIZONTAL RIGHT)
OR ALTERNATE
30 i_,,
7m-IN DIA
POWER CONN
I_z-IN DIA
THERMOSTAT ENTRY
)NN
1
18 _,_
i
I SiDE INLET
I
I
I
CONDENSATE
SiDE iNLET
DRAIN LOCATION
(UPFLO\A/}
NOTES:
1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
2. Minimum return-air opening at furnace:
a, For 800 CFM-16qn, round or 14V_x 12in, rectangle.
b. For 1200 CFM-20qn. round or 14V,x 19V2qn.rectangle.
c. For 1600 CFM-22-in. round or !4_/_x 23V,-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM.
UNIT SBZE A D E
040-14* 24-1/2" 22-7/8" 23*
060-14 17-1/2 15-7/8 16
080-14 21 19_3/8 19-1/2
080-20 21 19_3/8 19-1/2
100=20 21 19_3/8 19-1/2
120=20 24-1/2 22-7/8 23
* These dimensions reflect the wider casing for the Trophy (96,6 percent AFUE) furnace
Fig. 2--Dimensional Drawing
INLE_ DRA{N LOCATION
Dimensions (in.)
DIMPLE LOCATORS
FOR HORIZON 17_,L
HANGING
A99111
iNSTALLATION
This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 f_(0 - 3,050m), except 140 size f:dmaces are orlly approved for altitudes 0 - 7,000 ft
(0 - 2,135m).
e An accessory kit, supplied by the manufacturer, sbe}l be used to convert topropane gas use or may be required for some natural gas applications.
o This furnace is for indoor installation in a building constructed on site This furnace may be instaltadin a mant_astored (mobile) home when stated on rating p_ate and
using factory authorized kit.
o This Furnace may be installed on combustibta flooring in a_cove or closet at Minimum Inches Clearance To OombustiMe Construction as described below.
o This furnace requires a spedal venting system Refer to the installation instructions for parts list and method of installation This furnace is for use with scheduta4O PVC,
PVC_DWV, CPVC, or ABS_DV',N pipe, and must not be vented in comrr'_n with other gas_red appliances. Construction through which vent/air intake pipes may be
installed is maximum 24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roo_ng materials) m
o Cette foumaise & air pulse est 6quip6e pou_ utilisation avec gaz naturefl et aYdtudes comprises entre 0 _ 3,050m (0 - 10,000 pi),except6 quetas foumaises de 140 tai_ta
sont pour aNtudas comprises entre 0 _ 2,135m (0 - 7,000pi)
o Uti_iser une trousse de conversion, foumta par le fabdcant, pour passer au gaz propane ou pour certaines tastNiations au gaz natureL
o Cette foumNse & air puls6 est pour installatbn B I'tat@ieur dans un b_timent construit sur place Cette foornaise a air pu}se peut 6tre insta_lee dans une maison
p@_bbdquSe (maison mobile) si prescdt par la plaque signatatique et si I' on uti_ise une trousse spedfi_e par le fabbeant.
o Cette foumaise peut @tre instaJl6e sur un ptancher combustibta dans un enfoncemerlt ou un ptacard en obseNant tas D_gagement Minimum En Pouces Avec
Elenlents De Construction Oombustibtas.
I o Cette foumaise n@cesqte un systg_ne d'evacuation special La m_thode d'instaltation et la liste des pi_ces necessaires figurent dans tas instructions d'instailation Cet[e_
fournaise doit s'@liser avec la tuyautede des nom_nctatures 40 PVC, PVC-DVeV, CPVC, ou ABS-D'¢,N et elta ne peut pas _tre ventil@e conjointment avec d'autres
appareils & gaz. Epaisseur de _a constiuction au travers de laquelta il est possible de faire passer tas tuyaux d'a_ration (admisstan/_vacuation): 24 pc (600 mm) []
maximum, 3/4 pc (19ram) minimum (y compris la toitu_)
For up[low and downflow applicatbns, forr_qce must be installod level, a- pitched within 1/Z' of level, For a LEVEL (0 /TO ,_,,,]Z:::_::£3 \4IN 1_4 TO 1_2 MAX
horizontal app}icatbn, the furnace must be pitched minimum 1/4" to maximorn of 1/Z _faward for proper 1,2 MA£ _.._/ .Ca" . _¢_h_- l
@_inage See Ir_staltaflon Mar_al fa- IMPORTANT unit support deta_s Gnhorisontaf apdicattans --/ " I_ _
_ Pourdeeapp!k;_ionsde,uxascer,dantetde_scendant la roornaise doit @_einstafl_ de niveauouindi._e_ !_FRONTI _ / ----_('(1 _
as UPFLOW OR [_
p plusde I/Z'dunive_ Pooruneapplicatbr_hodzontale lafournaisedoit_treinclta&ee,Y.rerninimum ) FRON]| /
1/4"etmaximcrml/Z'duniveaupour_edrairk_geapprc_.. En c_sd'instaltation erngositic_q berisontaJe, DOWNFLOW _ /. _ -K,_ L/
_a e_sta_ion L _" HORIZONTA_ [_
NN_U_ INCHES CLEARANCE TO CONBUSTtBLE CONSTRUCTION
ALL POSITIONS:
* Minimum front clearance for service 24 inches (61gram).
DOWNFLOW POSITIONS:
For installation on combustible floors only when installed on spedal base No KGASBO201ALL
Coi_Assembly Pad No. CD5 or CKS. or Coil Casing, Part No. KCAKC.
HORIZONTAL POSITIONS:
Line contact is permissible only between lines formed by intersections of top and two sides
of furnace jacket, and building joists, studs, or framing.
Clearance shown is for air in_et and air outlet ends.
120 and 140 size furnaces require 1 inch bottom clearance to combustible materials.
DEGAGEMENTNNMUN ENPOUCESAVEC ELEMENTSDE
POUR TOUS LES POSITIONS:
* Dg%Jagement avant minimum de 61 gram (24 pc) pour rentretien
POUR LA POSITION COURANT DESCENDANT:
Pour Hnstallation sur le p_ancbar combustible seulement quand on utilise la base spedale,
piece n o KGASBC/201ALL Fensemble se@entin, piece noCD5 ou CKS. ou le carter de
se@entin, piece no KCAKC.
POUR LA POSITION HORIZONTALE:
Le contact n'est permis qOenb_ les lignes fortunes bar Jes intersections du dessus et des
deuxc6t@s de la chemise de la fournaise, et des so_ives, des montanta ou de la charpente du
b_timent.
La distance indiqu6e concerne I'extr_mit@ du tuyau d'ardv@e d'ak et I'extrcmit@ du tuyau de
sortie d'air.
Pour les fournaises de 120 et 140 taille. 1 pc (25ram) dg_gagement des mat&iaux combusitbles
est requis au-dessous
CONSTRUCTIONCONBUSTIBLES
This Drnace is approved for UPFLOW, DOWNFLOW and
HORIZONTAL installations.
Cet[e toumaise esl approuvee pour Hnstallation HORIZONTALE
st la drculatisn d'air VERS LE HAUT etVERS LE BAS
C[esrance arrows
do not change with
furnace orientation
Cbarance in inches
Degagemest (pc),
ne change tJas avec
I'otientatisn de is
gen@atecr d'air chaud
VelY{cle&.8rice to
combustibles 0"
0 (pc) D_gagement
1
[]
--> Fig. 3--Clearances to Combustibles
A gas-fired fttrnace %r installation in a residential garage must be
installed as specified in the Hazardous Locations section and Fig.
5.
The L'umace is not to be used for temporary heating of buildings or
stn_ctures under construction unless the furnace installation and
operation complies with first CAUTION in the LO(ATION
section of these instructions.
These [imaaces are shipped with the following materials to assist in
proper Nmace installation. These materials are shipped in the main
blower compartment.
A04116
Installer Packet includes:
Installation, Start-Up, and Operating Instn_ctions
Service and Maintenance Inst_qactions
User's Information Manual
Wan'anty Certificate
Loose Parts Bag includes: Quantity
Pressure mbe extension 1
Collector box or condensate trap extension tube 1
Inducer housing drain tube 1
li2oia. CPVC street elbow 2
Drain tube coupling 1
Drain robe coupling grommet 1
Vent and combustionoair pipe support 2
Combustion-air pipe perforated disk assembly 1
Condensate trap hole filler plug 3
Vent and con£bustionoair intake hole filler plug 2
For accessory installation details, re_r to applicable installation
titeratt_re
_ MAX 85°F
Fig, 4_Retum-Air Temperature
F
'F
2 MIN 55°F
A93042
Step 3--Combustion and Ventilation Air
* US: Section 83 of the NFGC, Air fbr Combustion and
Ventilation
CANADA: Part 7 of the NSCNGPIC, Venting Systems and Air
Supply for Appliances
Step 4--Duct Systems
* US and (ANADA: Air (onditioning (ontractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Con-
tlactors National Association (SMACNA), or American Soci-
ew of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 2001 Fundamentals Handbook Chapter 34
Step 5--Acoustical Lining and Fibrous Gmass Duct
* US and (ANADA: current edition of SMA(NA, NFPA 90B as
tested by UL Standard 18! for (lass I Rigid Air Ducts
Step 6--Gas Piping and Gas Pipe Pressure Testing
* US: NFG(; chapters 5, 6, 7, and 12 and national plumbing
codes
--> In
the state of Massachusetts:
This product must be installed by a licensed plumber or gas
fitter.
When flexible connectors are used, the n_axinmm length shall
not exceed 36 inches
When lever type gas shutoffls are used they shall not exceed 36
inches.
CANADA: NSCNGPIC Parts 3, 4, 5, A, B, E, G, and H
Step 7--Emectrical Connections
* US: National Electrical (:ode (NEC) ANSI NFPA 70°2002
CANADA: Canadian ElectIical (:ode CSA (722.1
ELECTROSTATIC DBSCNARGE {ESD) PRECAUTIONS
18-1N. MINIMUM
TO BURNERS
A93044
Fig. 8--_nstallatJon in a Garage
CODES AND STANDARDS
FMlow MI national and locM codes and standards in addition to
these instructions° The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and
other codes. In absence of local codes, the installation must
comply with the national codes listed below and all authorities
having jurisdiction in Canada.
In the United States and Canada, follow all codes and standards for
the fbllowing:
Step l--Safety
* US: National Fnet Gas (:ode (NFGC) NFPA 54-2002/ANSI
Z223.1o2002 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI NFPA 90B
* CANADA: National Standard of Canada, Natural Gas and
Propane Installation Code (NSCNGPIC) (SA BI49H-00
Step 2--General hstaHation
* US: NFG( and the NFPA 90B. For copies, contact the National
Fire Protection Association Inc., Batte_rnarch Park, Quincy,
MA 02269; or for only the NFG( contact the American Gas
Association, 400 N. Capitol, N.W., Washington DC 20001
* CANADA: NSCNGPI(. For a copy, contact Standard Sales,
CSA International, 178 Rexdale Boulevard, Etobicoke (Tof
onto), Ontario, M9W 1R3, (anada.
e
-->
[NIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will pre-
vent electrostatic discharges t]'om personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electlostatic discharge
by putting the t:umacQ the control, and the person at the same
electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may
be required. DO NOT TOU(H THE CONTROL OR ANY
WIRE CONNE(TED TO THE ( ONTROL PRIOR TO DIS-
CHARGING YOUR BODY'S ELECTROSTATI( CHARGE
TO GROUND,
2 Firefly touch a clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person's
hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as tong as you do nothing that
recharges your body with static electricity (fbr example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc)
4 If you touch ungrounded objects (recharge your body with
static electricity), firmly touch f_/rnace again befbre touching
control or wires
5 Use this procedure for installed and uninstalled (ungrounded)
f_/rnaces
__D FURNACE
TRAP (INSIDE_ X[
OOR
/_ CONDENSATE
/ TRA uRNAOE7
] S'DV
/o
£_2% ......
_1 FURNACE
OOR
-- FURNACE
SIDE
FIELD--
DRAIN
CONN
TUTo OOSO ETRAP
DRAIN TUBE LOCATION
UPFLOW APPLICATIONS
SIDE VIEW FRONT VIEW
DOWNFLOW AND ALTERNATE
EXTERNAL UPFLOW APPLICATIONS
s'-°7'-%:°:U7
(OPTIONAL) /
W, ET,E
GUIDES
(WHEN USED)
FRONT VIEW SIDE VIEW
Fig. 6--Condensate Trap
26_/4 1_/2
71/8
l
FIELD --
DRAIN
CONN
END VIEW FRONT VIEW
COD
COLLECTOR BOX TO
TRAP RELIEF PORT
_OD
INDUCER HOUSING
DRAIN CONNECTION
'_OD
COLLECTOR BOX
DRAIN CONNECTION
SCREW HOLE FOR
UPFLOW OR DOWN-
FLOW APPLICATIONS
(OPTIONAL)
YnlN. PVC OR CPVC
¾
HORIZONTAL
APPLICATIONS
A93026
6, Be%re removing a new contlol t'rom its container, discharge
your body's electrostatic charge to ground to protect the
control t'rom damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control
or yourself into contact with the fhrnace. Put all used AND
new controls into containers be_bre touching ungrounded
objects.
7. An ESD service kit (available fi'om commercial sources) may
also be used to prevent ESD damage.
INTRODUCTION
The model 58MVP 4-way muhipoisQ Gas-Fired, (ategory IV,
direct-vent condensing fknace is available in model sizes ranging
in input capacities of 4@000 to 120,000 Btuh
APPUCATIONS
Step l--General
Some assembly and modifications are required for furnaces
installed in any of the 4 applications shown in Fig. 1. All &ain and
pressure robes are connected as shown in Fig 7 See appropriate
application instrnctions _br these procedures
: O 'I
MINOR PROPERTY DAMAGE
Failure to fbllow this caution may result in minor property
damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing fhmace is used in an attic
application or over a finished ceiling.
NOTE: In (anada, installations shall be in accordance with
cun'ent NS(NGPIC andor local codes.
Step 2--Upflow Applications
An upflow furnace application is where furnace blower is located
below combustion and controls section of furnace, and conditioned
air is discharged upwards
CONDENSATE TRAP LOCATION (FACTORY-SHIPPED
ORIENTATK)N)
The condensate trap is factory installed in the blowm shelf and
factory connected for UPFLOW applications. A fi_ctow-supplied
robe is used to extend the condensate trap drain connection to the
desired furnace side for field drain attachment. See Condensate
Trap Tubing (Factow-Shipped Orientation) section for drain robe
extension details. (See Fig. 6.)
COLLECTOR
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR
TUBE (PINK)
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN)
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FACTORY-SUPPLIED
//2 -IN CPVC STREET
LEFT DRAIN OPTION
PLUG
CAP
FIELD-INSTALLED
ELBOWS (2) FOR
FIELD-INSTALLEE
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (RIGHT
DRAIN OPTION)
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (GREEN)
TRAP
HOUSING
DRAIN TUBE
(VIOLET)
©
O O
A94213
Fig. 7--Factory-SNpped Upflow Tube Configuration
(Shown With Blower Access Panel Removed}
(ONDENSATE TRAP TLTBING (FACTORY_SHIPPED
ORIENTATION)
NOTE: See Fig 7 or tube routing label on main furnace door to
confirm location of these tubes
1. Collector Box Drain, Inducer Honsing Drain_ Relief Port, and
Pressure Switch Tubes
These tubes should be factory attached to condensate trap and
pressure switch ready for use in UPFLOW applications. These
robes can be identified by their connection location and also
by a color label on each tube. These tubes are identified as
follows: collector box &ain tube (blue label), inducer housing
&ain robe (violet label or molded), relief port robe (green
label), and pressure switch robe (pink label).
2. Condensate Trap Drain Tube
The condensate trap drain connection must be extended for
field attachment by doing the fbllowing:
a. Detem_ine location of field drain connection. (See Fig. 2 or
7.)
NOTE: If internal filter or side filter media cabinet is used., &ain
robe should be located to opposite side of casing flora return duct
attachment to assist in filter removal
b. Remove and discard casing drain hole plug button from
desired side.
A94214
Fig. 8--Alternate Upflow Tube Configuration and
Trap Location
c Install drain tube coupling grommet (fScto_--supplied in
loose parts bag) in selected casing hole.
d. Slide &ain robe coupling (fi_ctoryosupplied in loose parts
bag) through grommet so long end of coupling fitces
blower.
e Cement 2 factolw-supplied 1/2-in. street (PVC elbows to
rigid drain tube connection on condensate trap. (See Fig. 7.)
These elbows must be cemented together and cemented to
condensate trap drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink,
preventing draining.
f\ (onnect larger diameter drain robe and clamp (factor-
supplied in loose parts bag) to condensate trap and clamp
securely.
g. Route robe to coupling and cut to appropriate length.
h. Attach robe to coupling and clamp securely.
COND]_NSATE TRAP LOCATION (ALTERNATE UPFLOW
ORIENTATION)
An alternate location for the condensate trap is the leR_hand side
of casing. (See Fig. 2 and 8.)
NOTE:Ifthealternateleft-handsideofcasinglocationisuse&
thefhctory-connecteddrainaridreliefportrobesmustbediscon-
nectedandmodifiedtbrattachmenLSeeCondensateTrapTubing
(AlternateUpflowOrientation)sectiont\_rrobingattachment
Torelocatecondensatetlaptotheleft-handside,performthe
fbllowing:
1.Remove3tubesconnectedtocondensatetrap
2.Removetlapfiomblowershelfbygentlypushingtabsinward
androtatingtrap
3.Installcasingholetillercap(factory-suppliedinlooseparts
bag)intoblowershelfholewheretrapwasremoved.
FIRE,IN!![RYORDEATH HAZARD
Failure to %llow this warning could result in electrical shocL
fire, personal injury or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated.
4. Install condensate trap into left-hand side casing hole by
inserting robe connection stubs through casing hole and
rotating until tabs snap into locking position
5. Fill unused condensate trap casing holes with plastic filler
caps (thctory-supplied in loose parts bag)
CONDENSATE TRAP TUBING (ALTERNATE [ PFL()W
ORIENTATION)
NOTE: See Fig 8 or tube routing label on main fi/rnace door to
confirm location of these tubes
1. (ollector Box Drain Tube
Connect collector box drain robe (blue label) to condensate
t_ap.
NOTE: On 1%1/2-in. wide furnaces ONLY, cut tube between
corrugated sections to prevent kinks.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) in&cer housing
&ain robe which was previously connected to condensate
t_ap.
b. Use inducer housing &ain extension robe (violet label and
t_ctory-supplied in loose parts bag) to connect LOWER
inducer housing &ain connection to condensate trap.
c. Determine appropriate length, then cut and connect robe.
& (lamp robe to prevent any condensate leakage.
3. Relief Port Tube
a. (onnect relief port robe (green label) to condensate trap.
b. Extend this tube (if required) by splicing to small diameter
robe (ti_ctory-supplied in loose parts bag).
c. Determine appropriate length, then cut and connect robe.
( ONDENSATE TRAP FIELD DRAIN ATTA(HMENT
Refer to Condensate Drain section for recommendations and
procedures
PRESSURE SWIT(H TUBING
The LOWER collector box pressure robe (pink label) is factory
connected to the pressure switch and should riot require any
modification.
NOTE: See Fig. 7 or 8 or robe routing label on main furnace door
to check fbr proper connections.
UPPER (OLLECTOR BOX AND INDU(ER HOUSING
(UNUSED) DRAIN CONNECTIONS
Upper Collector Box Drain Connection
Attached to the UPPER collector box drain connection is a
factory-installed corrugated, plugged tube (blue and white striped
label). This tube is plugged to prevent condensate leakage in this
application Ensure this robe is plugged.
NOTE: See Fig 7 or 8 or robe routing label on main furnace door
to check tbr proper connections.
Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing &ain connection
is a cap and clamp. This cap is used to prevent condensate leakage
in this application. Ensure this connection is capped.
NOTE: See Fig. 7 or 8 or tube routing label on main f:urnace door
to check tbr proper connections.
CONDENSATE TRAP FREEZE PROTECTION
Refer to (ondensate Drain Protection section for recommenda-
tions and procedures.
Step 3--Downflow Applications
A downflow Nrnace application is where Nrnace blower is located
above combustion and controls section of fi/rnace, and conditioned
air is discharged downwards.
CONDENSATE TRAP LOCATION
The condensate trap must be removed fi'om d-ie fScto_-installed
blower shelf location arid relocated in selected application location
as shown in Fig. 2, 9, or 10.
To relocate condensate trap fi'om the blower shelf to desired
location, pertbrm the tbllowing:
1. Remove 3 tubes connected to condensate t_ap.
2. Remove trap fi'om blower shelf by gently pushing tabs inward
and rotating trap.
3. Remove casing hole filler cap fi'om casing hole. (See Fig. 2
and 10.)
4. Install casing hole filler cap (fi_ctory-supplied in loose parts
bag) into blower shelf hole where trap was removed.
FIRE, INJURY OR DEATH HAZARD
Failure to fbllow this warning could result in electrical shocL
fire, personal injury or death
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated
5. Install condensate trap into te_hand side casing hole by
inserting robe connection stubs through casing hole and
rotating until tabs snap into locking position,
6. Fill unused condensate trap casing holes with plastic filler
caps (fi_ctory°supplied in toose parts bag)
CONDENSATE TRAP T[ BING
NOTE: See Fig. 9 or 10 or robe routing label on main furnace
door to check for proper connections
1. Collector Box Drain Tube
a Remove factmy°installed plug from LOWER collector box
drain robe (blue and white striped 1abet).
b. Install removed clamp and plug into UPPER collector box
&ain tube (blue 1abel) which was connected to condensate
tlap.
c (onnect LOWER collector box drain connection to con=
densate trap,
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAF
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
TUBE (PINK)
O O
TUBE (GREEN)
BOX
DRAIN TUBE (BLUE)
BOX
TUBE (PINK)
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
TRAP
©
iNDUCER HOUSING
DRAIN TUBE (VIOLET)
Fig. 9--Downflow Tube Configuration
(Left-Hand Trap Installation)
(1) Condensate Trap Located on Left Side of Casing
Ca) Connect LOWER collector box &ain robe (blue
and white striped label) to condensate trap. Tube
does not need to be cut.
(b) Clamp tube to prevent any condensate leakage.
(2) Condensate Trap Located on Right Side of Casing
Ca) Install drain tube coupling (fi_cto_--supplied in
loose parts bag) into collector box drain robe
(blue and white striped label) which was previ-
ously plugged.
(b) Connect larger diameter &ain robe (gtctory-
supplied in loose parts bag) to &ain tube cou-
pling, extending collector box drain robe for
connection to condensate trap
(c0 Route extended collector box &ain tube between
gas valve and inlet housing as shown in Fig. 10.
(&) Determine appropriate length and cut.
(e.) Connect to condensate trap.
(f.) Clamp robe to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove fi_ctoLy-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
&ain robe which was previously connected to condensate
t_ap,
c Install cap and clamp on UPPER induce* housing &ain
connection whe*e molded &ain robe was removed,
d, Lse inducer housing &ain robe (violet 1abel and factory°
supplied in loose parts bag) to connect LOWER inducer
housing &ain connection to the condensate t*ap
A94215
DRAIN TUBE (BLUE
BOX
& WHITE STRIPED)
EXTENSION TUBE
DRAIN TUBE
(VIOLET)
O TRAP
EXTENSION
DRAIN TUBE
DRAIN TUBE
COUPLING
A94216
Fig. 10--Downflow Tube Configuration
(Right-Hand Trap Installation)
e Connect inducer housing drain connection to condensate
trap.
(1.) Condensate Trap Located on Left Side of Casing
Ca.) Determine appropriate tengtia and cut.
(b.) Connect tube to condensate tlap.
(c.) Clamp robe to prevent any condensate leakage.
(20 Condensate Trap Located on Right Side of Casing
Ca.) Route in&cot housing drain robe (violet label)
directly from inducer housing to condensate tlap.
(b.) Determine appropriate lengd_ and cut.
(c.) Connect robe to condensate trap.
(&) Clamp robe to prevent any condensate leakage.
3. Relief Port Tube
Refkr to Pressure Switch Tubing section for connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refkr to Condensate Drain section fbr recommendations and
procedures.
PRESSURE SWITCH TUBING
One collector box pressure tube (pink label) is factory connected to
the pressure switch fbr use when furnace is installed in UPFLOW
or HORIZONTAL LEFT applications. This robe MUST be dis-
connected and used *;or the condensate trap relief port robe. The
other collector box pressure robe (green label) which was *:actory
connected to the condensate trap relief port connection MUST be
connected to the pressure switch in DOVv_FLOW or HORIZON-
TAL RIGHT applications.
NOTE: See Fig. 9 or 10 or robe routing label on main furnace
door to check fbr proper connections.
Relocate robes as described below,
1. Disconnect collector box pressure tube (pink label) attached to
pressure switch.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connection
by splicing to small diameter robe (factoD'-supplied in loose
parts bag).
3. Connect collector box pressure tube (green label) to pressure
switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was
previously connected to pressure switch by splicing to remain°
ing small diameter robe (factoD'-supplied in loose parts bag)
5. Route this extended robe (pink label) to condensate t_ap relief
port connection.
6. Determine appropriate length, cut, and connect robe.
7. (lamp robe to relief port connection.
( ONDENSATE TRAP FREEZE PROTE( TION
Refkr to Condensate Drain Protection section %r recommenda-
tions and procedures.
Step 4--Horizontal Left (Supp[yoAir Discharge)
Applications
A horizontal left furnace application is where t_urnace blower is
located to the right of combustion and controls section of furnace,
and conditioned air is discharged to the left.
2 0 _
--€
MINOR PROPERTY DAMAGE
Failure to fbllow this caution may result in minor property
damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing f_lrnace is used in an attic
application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with
cmxent NS(NGPIC and/or local codes.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the fhctow-installed
blowe* shelf'location and relocated in selected application location
as shown in Fig 2or 11.
To relocate condensate trap fi'om the blowe* shelf to desired
location, perfbrm the following:
1. Remove 3 tribes connected to condensate trap.
2. Remove trap from blowe* shelf by gently pushing tabs inward
and rotating trap.
3. Remove casing hole filler cap fiom casing hole (See Fig. 2 or
11)
4. Install casing hole filler cap (fi_ctou-supplied in toose parts
bag) into blower shelf hole where trap was removed
PLUG "-_
t F CAP
AUXILIARY "J" BOX _ \ / f-- COLLECTOR BOX
\ \ / / DRAIN TUBE
/ / (BLUE AND WHITE STRIPED)
CONOE S T 711 "\----\\ --CO ' CTO OOX
TRAP \\\ XX \ TUBE(GREEN)
LL_ \ \ \ \\ "--INDUCER HOUSING
COLLECTOR BOX _ N N \\ DRAIN TUBE (VIOLET)
EXTENSION TUBE X X X_COLLECTOR BOX
.... C_%_L_E.C_T.gR_ N \ DRAIN TUBE (BLUE)
BOX EXTENSION N \
DRAIN TUBE X X
DRAIN TUBE COUPLING _
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
060, AND 080 HEATING INPUT FURNACES
COLLECTOR BOX TUBE (PINK) --_
Fig. 11--Horizontal Left Tube Configuration
10
\
A02288
_: iiiiiii!
FIRE, INJURY OR DEATH HAZARD
Failure to fbltow this warning could result in electrical shock
fire, personal injury or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated.
5. Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler
caps (ilactory=supptied in loose parts bag)
(ONDENSATE TRAP TUBING
NOTE: See Fig. 11 or robe routing label on main fl/rnace door to
check for proper connections
1. (ollector Box Drain Tube
a. Install &ain tube coupling (fhctory=supplied in loose parts
bag) into collector box drain robe (blue label) which was
previously connected to condensate trap.
b. Connect large diameter drain robe and clamp (factory°
supplied in loose parts bag) to drain robe coupling, extend°
ing collector box &ain tube.
c. Route extended robe (blue label) to condensate trap and cut
to appropriate lengd_.
d. Clamp robe to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to condensate
trap.
b. Use inducer housing &ain extension tube (violet label and
fhctow-supplied in loose parts bag) to connect LOWER
inducer housing drain connection to condensate trap.
c. Determine appropriate length, cut, and connect robe.
d. Clamp robe to prevent any condensate leakage.
3. Relief Port Tube
a. Extend collector box robe (green label) which was previ=
ously connected to condensate trap by splicing to small
diameter robe (fhctory=supptied in loose parts bag).
b. Rome extended collector box pressure robe to relief port
connection on condensate trap
c. Determine appropriate tength, cuL and connect robe.
d. (lamp robe to prevent any condensate leakage.
(ONDENSATE TRAP FIELD DRAIN ATTA(HMENT
Refkr to Condensate Drain section ibr recommendations and
procedures
PRESS[ RE SWIT(H TUBING
The LOWER collector box pressure tube (pink label) is factow
connected to the High Pressure Switch fbr use when fhrnace is
installed in UPFLOW applications This robe MUST be discon=
nected, extended, rerouted, and then reconnected to the pressure
switch in HORIZONTAL LEFT applications ibr 060 and 080
heating input fl/rnaces.
NOTE: See Fig. 11 or robe routing label on main Nrnace door to
check for proper connections.
ModK}" robe as described below.
1. Disconnect collector box pressure tube (pink label) attached to
High Pressure Switch.
2 Use smaller diameter tube (factou-supplied in loose parts
bag) to extend tube disconnected in item 1.
3 Route extended robe:
a Behind indtlcer housing.
b Between blower shelf and inducer housing.
4 Determine appropriate length, cut, and reconnect tube to High
Pressure Switch connection labeled (OLLE(TOR BOX.
CONDENSATE TRAP FREEZE PROTECTION
Refer to (ondensate Drain Protection section %r recommenda-
tions and procedures
CONSTRU(T A WORKING PLATFORM
Construct working platfbnn where all required furnace clearances
are met (See Fig. 3 and 12)
INIT MAY NOT OPERATE
Failure to %llow this caution may result in intermittent unit
operation
The condensate trap MUST be installed below thrnace. See
Fig. 6 ibr dimensions. The drain connection to condensate
trap must also be properly sloped to an open drain.
NOTE: (onft_ustion=air and vent pipes are restricted to a mini-
mum length of 5 fi. (See Table 7.)
NOTE: A 12°in. minimum offset pipe section is recommended
with short (5 to 8 ft) vent systems. This recommendation is to
reduce excessive condensate droplets fi'om exiting the vent pipe.
(See Fig. 12 or 35.)
Step 5--Horizontal Right {Supply-Air Discharge)
Applications
A horizontal right furnace application is where thrnace blower is
tocated to the 1eft of combustion and controls section of fl/rnace,
and conditioned air is discharged to the right.
1
MINOR PROPERTY DAMAGE
Failure to %11ow this caution may result in minor property
damage
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing fhrnace is used in attic
application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with
cmTent NS(NGPIC Installation Codes and/or local codes
NOTE: The auxiliaL'y junction box (J-box) MUST be relocated to
opposite side of furnace casing. (See Fig. 130 See Electrical
Connection section for J°box relocation,
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the ii_ctow=installed
blower shetf location and relocated in selected application location
as shown in Fig 2 or 13.
To relocate condensate trap fi'om the blower shelf to desired
location, peribnn the following:
1 Remove 3 tnbes connected to condensate trap.
2 Remove trap from blowe* shelf by gentty pushing tabs inward
and rotating trap.
3 Install casing hole filler cap (ihctory=supplied in loose parts
bag) into blower shelf hole where trap was removed
11
COMBUSTION
INTAKE
VENT
12-1N. MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT) VENT SYSTEMS
TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
SHUTOFF
GAS VALVE
SEDIMENT
TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
CONDENSATE
TRAP
DRAIN
Fig. 12--Attic Location and Working Platform
CAP
UG
F COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (GREEN)
-- COLLECTOR BOX TUBE (PINK)
BOX RELOCATED HERE
O
O
ACCESS OPENING
FOR TRAP
A93031
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 13--Horizontal Right Tube Configuration
CONDENSATE
TRAP
A02289
12
_: iiiiiii!
FIRE, INJURY OR DEATH HAZARD
Failure to £4tow this warning could result in electrical shocL
fire, personal injury or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated.
4. Instal! condensate trap into right-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (fi_ctoryosupplied in loose parts bag).
CONDENSATE TRAP TUBING
NOTE: See Fig. 13 or tube routing label on main f_./rnace door to
check for proper connections.
1. (ollector Box Drain Tube
a. Remove fitctoryoinstalled plug fiom LOWER collector box
drain robe (blue and white striped label).
b. Install removed clamp and plug into UPPER collector box
&ain tube (blue label) which was previously connected to
condensate t_ap.
c. Connect LOWER collector box drain robe (blue and white
striped label) to condensate trap. Tube does not need to be
cut.
d. (lamp robe to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove fitctoryoinstalled cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
&ain tobe which was previously connected to condensate
trap.
c. Install cap and clamp on UPPER inducer housing &ain
connection where molded &ain robe was removed.
d. Use inducer housing &ain extension robe (violet label and
factow-supplied in loose parts bag) to connect LOWER
inducer housing &ain connection to condensate trap.
e. Determine appropriate length, cut, and connect robe to
condensate trap.
£ Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
Refer to Pressure Switch Tubing section fbr connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refhr to Condensate Drain section fbr recommendations and
procedures.
PRESSURE SWITCH TUBING
One collector box pressure robe (pink label) is fi_ctory connected to
the pressure switch fbr use when i_urnace is installed in UPFLOW
or HORIZONTAL LEFT applications. This tube MUST be dis°
connected and used for the condensate trap relief port robe. The
other collector box pressure robe (green label) which was fhcto V
connected to the condensate trap relief port connection MUST be
connected to the pressure switch in DOWNFLOW or HORIZON°
TAL RIGHT applications.
NOTE: See Fig. 13 or tube routing label on main Nmace door to
check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to
pressure switch.
2. Extend collector box pressure robe (green label) which was
previously connected to condensate trap relief port connection
by splicing to small diameter robe (flactou-supptied in loose
parts bag).
3. (onnect collector box pressure robe (green label) to pressure
switch connection labeled COLLECTOR BOX.
4. Use remaining small diameter tube (factory-supplied in loose
parts bag) to extend collector box pressure tube (pink label)
which was previously connected to pressure switch.
5. Route this extended tube (pink label) to condensate trap relief
port connection.
6. Determine appropriate length, cut, and connect robe.
7. Clamp robe to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
CONSTRUCT A WORKING PLATFORM
Construct working platfbrm where all required furnace clearances
are met. (See Fig. 3 and 12.)
. , IR
[NIT MAY NOT OPERATE
Failure to fbllow this caution may result in intermittent unit
operation.
The condensate trap MUST be installed below l::urnace See
Fig. 6 for dimensions. The drain connection to condensate
trap must also be properly sloped to an open drain.
NOTE: Combustionoair and vent pipes are restricted to a mini-
mun_ length of 5 ft (See Table 7.)
NOTE: A 12oin mininmnl of_;et pipe section is recommended
with short (5 to 8 ft) vent systems. This recommendation is to
reduce excessive condensate droplets fiom exiting the vent pipe.
(See Fig 12 or 35)
LOCATION
Step l--General
This furnace must
* be installed so the electrical components are protected from
water
not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
* be located so combustion-air and vent pipe maximum lengths
are not exceeded. Refer to Table 7.
* be located where available electric power and gas supplies meet
specifications on the l::urnace rating plate.
* be attached to an air distribution system and be located as close
to the center of the distribution system as possible. Refer to Air
Ducts section
* be provided with ample space fbr servicing and cleaning.
Always comply with n_inimnm fire protection clearances
shown on the ft_rnace clearanceoto-combustibles label. (See
Fig. 3.)
This Nmace may be located in a confined space without special
provisions £_r dilution or ventilation air.
NOTE: For upflowidownflow applications install furnace so that
it is level or pitched fbrward within 1i2oin. for proper fitrnace
operation. For horizontal applications pitch 1i4oin. minimum to
1i2oin. maximunx forward to ensure proper condensate &ainage
from secondary heat exchangers. (See Fig. 14.)
13
t
LEVEL (0")
TO
1/2"MAX
V2" MAX
UPFLOW OR DOWNFLOW HORIZONTAL
Fig. 14_Proper Condensate Drainage
When a fhmace is installed so that supply ducts can 7 air circulated
by the _hmace to areas outside the space containing the/hmace,
the return air shall also be handled by ducts sealed to furnace
casing. The ducts terminate outside the space containing the
ihrnace to ensure there will not be a negative pressure condition
within equipment room or space.
FIRE, INJURY OR DEATH HAZARD
Failure to ibllow this warning could result in fire, personal
injury, or death
Do not install fhrnace on its back. (See Fig. 15.) Safbty
control operation will be adversely affecte& Never connect
return-air ducts to hack of filrnace.
A02146
BACK
FRON]
A93043
Fig. 16--Prohibit Installation on Back
The thrnace and its return air system shall be designed and
installed so that negative pressure created by the air circulating fan
cannot affect another appliance's combustion air supply or act to
mix products of confbustion with circulating air, and that the air
circulating fhn of the fhmace, if installed in an enclosure commu-
nicating with another fllel-burning appliance not of the direct-vent
type, shall be operable only when any door or panel covering an
opening in the ihmace fan compartment or in a return air plenum
on dt/cts is in the closed position.
--€ [;NIT DAMAGE HAZARD
This gas fire, ace may be used %r construction heat provided
that:
-The [hrnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions A return air duct is provide&
sealed to the ft_raace casing, and terminated outside the space
containing the thrnace This prevents a negative pressure
condition as created by the circulating air blower, causing a
flame rollout an&or drawing combustion products into the
strncttlre.
-The furnace is controlled by a thermostat It may not be "hot
wired" to provide heat continuously to the stlt/cture without
thermostatic control.
-(Dan outside air is provided for combustion. This is to
minimize the con'osive efDcts of adhesives, sealers and other
constn_ction materials. It also prevents the entraimnent of
d_wall dust into combustion air_ which can cause fouling and
plugging of Nrnace components.
-The temperature of the return air to the /hrnace is no less
than 55°F_ with no evening setback or shutdown. The use of
the fimaace while the structure is under construction is
deemed to be intermittent operation per our installation
instructions.
-The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
nameplate value.
-The filters used to clean the circulating air during the
construction process nmst be either changed or thoroughly
cleaned prior to occupancy.
-The Nrnace, ductwork and filters are cleaned as necessary to
remove &ywall dust and construction debris fiom all HVA(
system components after construction is completed.
[;NIT DAMAGE HAZARD
Failure to fbllow this caution may result in minor property or
unit damage.
If these farnaces are installed in an unconditioned space
where ambient temperatt_res may be 32_F or lower, freeze
protection measures n-rest be taken (See Fig. 16)
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
/
/
A93058
Fig. 16--Freeze Protection
Step 2--LowoHeat Only hstaltation
This 58MVP furnace can be installed to operate in the low-heat
only heating mode when sized using the low-heat heating capacity.
This is accomplished by placing setup switch SWI-2 in the ON
position to provide only low-heat operation. See Fig 32 and Table
9 With this semp_ high-heat operation will not occur
14
--€
[SNTT DAMAGE HAZARD
Failure to %llow this caution may result in minor property or
unit damage.
The fhrnace can operate in the high=heat mode when certain
fault conditions occur. The following precautions should be
taken:
l.Size gas piping based on the high-heat input.
2.(hock the high=heat input and adjust it per the main
literature instl-t_ctions.
Step 3--Furnace Location Reiative to Cooling
Equipment
The cooling coil must be installed parallel with or on downstleam
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a _hmace, dampers or other means used to
control flow of air shall be adequate to prevent chilled air t'rom
entering t:tmaace. If dampers are manually operated, they must be
equipped with a means to prevent operation of either unit unless
damper is in Nil=heat or Nil=cool position.
Step 4--Hazardous Locations
m
1¾"
1¾"
1
A89014
Fig, 18--Leveling Legs
2. For each hole, install nut on bolt and then install bolt and nut
in hole. (Install flat washer if desired.)
3 Install another nut on other side of ftm_ace base (Install flat
washer if desired.)
4 Adjust outside nut to provide desired height, and tighten inside
nut to secure aiTangement
NOTE: Bottom closure must be used when leveling legs are used.
See Bottom (losure Panel section.
18-IN. MINIMUM
TO BURNERS
Fig. 17--installation in a Garage
--€
FIRE, EXPLOSION, INJURY OR DEATH HAZARD
Improper location or inadeq_mte protection could result in fire
or explosion.
When fhrnace is installed in a residential garage, it must be
installed so that burners and ignition sources are located a
minimum of 18 in. above floor The _hmace must be located
or protected to avoid physical damage by vehicles. When
furnace is installed in a public garage, airplane hangar, or
other building having a hazardous atmosphere, unit must be
installed in accordance with requirements of National Fire
Protection Association, Inc. (See Fig. 17.)
INSTALLATION
Step l--Leveling Legs {if Desired)
When I:hmace is used in upflow position with side inlet(s), leveling
legs may be desired. (See Fig. 18.) Install field=supplied,
co_Tosion-resistant 5/16=in. machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1=1/2 in.
1. Position Nmace on its back. Locate and drill a 5/16=in.
diameter hole in each bottom corner of Nrnace. (See Fig. 18.)
Holes in bottom closure panel may be used as guide locations.
A93044
Step 2--hstaHation in Upflow or Downflow
Applications
NOTE: _his fhmace is approved for use on combustible flooring
when manul:acmrer's accessory floor base, Part No.
KGASB020 IALL, is used. Manufacturers accessory floor base in
not required when this 5m_ace is installed on manufacturer's (Toil
Assembly Part No. CD5 or CK5, or (oil Box Part No. KCAK( is
used.
1 Determine application being installed from Table 1
2 Construct hole in floor per dimensions specified in Table 1
and Fig 19.
3 Consm/ct plenum to dimensions specified in Table 1 and Fig.
19.
4 If downflow subbase (KGASB) is used, install as shown in
Fig. 20
If coil assembly CD5 or CK5 or (?oil Box K(AK( is used,
install as shown in Fig 21.
NOTE: Remove fhmace perforated discharge duct flanges when
they interfere with mating flanges on coil on downflow subbase.
To remove f_amace perforated discharge duct flange, use hand
seamers, wide duct pliers or duct flange tool to bend flange back
and forth until it breaks off, Be carefid of sharp edges. (See Fig.
22.)
15
A96283
Fig. 19--Floor and Plenum Opening Dimensions
FURNACE
(OR COiL CASING
WHEN USED)
FLOORING
SUBBASE
SHEET METAL
PLENUM
-- FLOOR --
OPENING
A96285 A96284
FURNACE
CD5OR CK5
COILASSEMBLY
OR KCAKC
COILBOX
FLOORING
SHEET METAL._
PLENUM
__ FLOOR __
OPENING
Fig. 20--Furnace, Plenum, and Subbase Fig. 21--Furnace, Plenum, and Coil
Installed on a Combustib{e Floor Assembly or Coi! Box Installed
on a Combustible Floor
Tab{e 1--Opening Dimensions (In.)
FURNACE
CASING
APPUCATION
WIDTH
Upftow Applications 16-5/8
Downflow Applications on Non-Combustible Flooring 16-1/2
17olt2 Downflow Applications on Combustible Flooring Using KGASB Subbase 16-3/4
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Ftooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications 20-1/8
Downflow Applications on Non-Combustible Flooring 20
21 Downflow Applications on Combustible Flooring Using KGASB Subbase 20-1/4
Furnace with or without CD5 or CK5 Coil Assembiy or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coit Assembly or KCAKC Coil Box
Upftow Applications 23-5/8
Downflow Applications on Non-Combustible Flooring 23-1/2
24o112 Downflow Applications on Combustible Flooring Using KGASB Subbase 23-3/4
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Ftooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
PLENUM OP_=N_NG
A B
16 24-1/8
15-7/8 19
15-1/8 19
15-1/2 19
19-1/2 24-1/8
19-3/8 19
18-5/8 19
19 19
23 24-1/8
22-7/8 19
22-1/8 19
22-1/2 19
FLOOR OPENING
C
D
24-3/4
19-5/8
20-3/8
16-1/2
20
24-3/4
19-5/8
20-3/8
20
20
24-3/4
19-5/8
20-3/8
23-1/2
20
16