Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA
54-1999/ANSI Z223.1-1999 and the Installation Standards, Warm
A92496
Fig. 1—Multipoise Furnace in Upflow Orientation
EFFICIENCY
RATING
CERTIFIED
r
o
p
C
o
r
r
e
i
r
r
a
C
R
E
G
I
S
I
T
S
O
9
0
REGISTERED QUALITY SYSTEM
Air Heating and Air Conditioning Systems (NFPA 90B)
ANSI/NFPA 90B. In Canada, refer to the CAN/CGA-B/49.1- and
.2-M95 National Standard of Canada, Natural Gas and Propane
a
t
i
o
n
CERTIFIED
®
E
R
0
1
M
R
I
F
D
E
3
8
8
2
A
#
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101Catalog No. 535-795Printed in U.S.A.Form 58MVP–9SMPg 110-00Replaces: 58MVP-7SM
Installation Codes (NSCNGPIC). Wear safety glasses and work
gloves. Have a fire extinguisher available during start-up and
adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User’s Manual. FAILURE
TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.
Never store anything on, near, or in contact with the furnace,
such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum
cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene,
cigarette lighter fluid, dry cleaning fluids, or other volatile
fluids.
3. Paint thinners and other painting compounds, paper bags,
or other paper products.
Failure to follow this warning can cause corrosion of the
heat exchanger, fire, personal injury, or death.
INTRODUCTION
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 2,
you may need to revise your orientation to component location
accordingly.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
AIRFLOW
.
UPFLOW
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
HORIZONTAL
RIGHT
AIRFLOW
A93041
Fig. 2—Multipoise Orientation
2. Firmly touch a clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touching
control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control
or yourself into contact with the furnace. Put all used AND
new controls into containers before touching ungrounded
objects.
7. An ESD service kit (available from commercial sources) may
also be used to prevent ESD damage.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment failure, it is essential that maintenance be performed annually
on this equipment. Consult your local dealer for maintenance and
maintenance contract availability.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
Turn off the gas and electrical supplies to the unit before
performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace. Failure to
follow this warning could result in personal injury or death.
The minimum maintenance that should be performed on this
equipment is as follows:
1. Check and clean or replace air filter each month as required.
2. Check blower motor and wheel for cleanliness annually.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.
2
5. Check for blockages in combustion-air and vent pipes annually.
6. Check burners for cleanliness annually.
Personal injury could result from sharp metal edges, etc. Use
care when removing parts.
Step 1—Cleaning and/or Replacing Air Filter
The air filter arrangement may vary depending on the application
or orientation.
WASHABLE
FILTER
IN FURNACE
FILTER
RETAINER
Never operate unit without a filter or with the blower access
panel removed. Failure to follow this warning could result in
a fire or personal injury.
NOTE: If the filter has an airflow direction arrow, the arrow must
point toward the blower.
To clean or replace filters, proceed as follows:
→
If filter is installed in filter cabinet adjacent to furnace:
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by
spraying cold tap water through filter in opposite direction of
airflow. Rinse filter and let dry. Oiling or coating of the filter
is not recommended.
5. If equipped with factory specified disposable media filter,
replace only with media filter having the same part number
and size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
If filter is installed in furnace blower compartment:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Figs. 3 and 4.)
WASHABLE
FILTER
FILTER
SUPPORT
FILTER
RETAINER
WASHABLE FILTER OR
DISPOSABLE MEDIA FILTER
IN FILTER CABINET
Fig. 3—Bottom Filter Arrangement
A00232
WASHABLE FILTER OR
DISPOSABLE MEDIA
FILTER IN FILTER CABINET
A00233
Fig. 4—Filter Installed for Side Inlet
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s).
Clean filter by spraying cold tap water through filter in
opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating filter is not
recommended.
7. Slide filter into furnace.
8. Recapture filter retaining wire.
9. Replace blower access panel and main furnace door.
10. Turn on electrical supply to furnace.
Step 2—Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
The following items should be performed by a qualified service
technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires
a. Disconnect motor wiring harness plug on blower housing.
b. Disconnect auxiliary limit switch leads at switch.
c. Disconnect field thermostat connections depending on their
length and routing.
4. Position control box, transformer, and door switch assembly to
right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of
furnace casing, proceed to item 6. Otherwise remove trap and
tubing as described below:
a. Disconnect field drain connection from condensate trap.
b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and
slide blower assembly out of furnace.
3
7. Clean blower wheel and motor by using a vacuum with soft
brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades as
balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly to
ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing and
slide motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner.
9. Reassemble motor and blower wheel by reversing items 8b
through 8f. Ensure wheel is positioned for proper rotation. Be
sure to attach ground wire.
10. Reinstall blower assembly in furnace.
11. Reinstall condensate trap and tubing if previously removed.
a. Reinstall condensate trap in hole in blower shelf.
b. Connect condensate trap drain tubes. See Fig. 8 or tubing
diagram on main furnace door for proper tube location.
(1.) Connect 1 tube (blue or blue and white striped) from
collector box.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect
operation.
12. Reinstall control box, transformer, and door switch assembly
on blower shelf.
13. Reconnect wires.
a. Refer to furnace wiring diagram and connect motor and
auxiliary limit switch leads. (See Fig. 16.)
b. Connect thermostat leads if previously disconnected.
14. Turn on electrical supply. Manually close blower access panel
door switch. Use a piece of tape to hold switch closed. Check
for proper rotation and speed changes between heating and
cooling by jumpering R to G and R to Y on control center
thermostat terminals. (See Fig. 11.)
Blower access panel door switch opens 115-v power to
control center. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
personal injury or death.
15. If furnace is operating properly, release blower access panel
door switch, replace blower access panel, and replace main
furnace door.
Step 3—Cleaning Burners
The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from gas
valve.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation.
5. Remove wires from gas valve. Note location for reassembly.
6. Remove burner box pressure tube from gas valve regulator
fitting.
7. Remove screws that secure manifold to burner box. (See Fig.
5.)
CELL
PANEL
MANIFOLD
MOUNTING
SCREW
MANIFOLD
GAS VALVE
REGULATOR
FITTING
GAS VALVE
A96304
Fig. 5—Burner Box Assembly
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be
removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner
box. Ensure manifold seal grommet is installed properly and
burners fit over orifices.
13. Reconnect wires to gas valve. Refer to furnace wiring diagram
for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator
fitting.
15. Reinstall gas supply pipe to gas valve using backup wrench on
gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.
DO NOT use Teflon tape.
4
Gas valve switch or knob MUST be facing forward or tilted
upward. Failure to follow this warning could result in
property damage, personal injury, or death.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
Never use matches, candles, flame, or other sources of
ignition to check for gas leakage. Use a soap-and-water
solution. Failure to follow this warning could result in a fire,
personal injury, or death.
19. Replace main furnace door.
Step 4—Cleaning Heat Exchangers
The following items should be performed by a qualified service
technician.
PRIMARY HEAT EXCHANGERS
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and hazardous operation.
PRIMARY HX
INLET OPENINGS
A96305
Fig. 6—Cleaning Inlet Openings of Primary Heat
Exchangers
12. Reverse items 4 through 10 for reassembly.
The ground wire from the gas valve MUST be attached to the
burner box attachment screw. Failure to attach this ground
wire to an adequate casing ground will cause the furnace
control to lock out.
NOTE: Be sure burner box gasket is installed between burner box
and cell panel. If gasket is damaged, replace it.
NOTE: Inspect combustion-air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any
way, it must be repaired. To repair, remove damaged gasket
section, apply sealant releasing agent such as PAM cooking spray
or equivalent (must not contain corn or canola oil, aromatic or
halogenated hydrocarbons or inadequate seal may occur) to burner
box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or
Dow-Corning RTV 738 sealant to edge of combustion-air intake
housing. (See Fig. 7.)
3. Disconnect wires or connectors to rollout switch, gas valve,
ignitor, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and
rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas
valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate upwards
to gain access to screws attaching burner box to cell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
5.)
NOTE: Burner box cover, manifold, gas valve, and burner
assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft
brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
RTV
PAM
A93087
Fig. 7—Combustion-Air Intake Housing Gasket
Repair
13. Refer to furnace wiring diagram and reconnect wires to rollout
switch, gas valve, ignitor, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake
housing. Refer to tube routing label on main furnace door for
proper tube location. (See Fig. 8.) Be sure tubes are not
kinked.
15. Turn on gas and electrical supplies to furnace.
5
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Condensate Trap; Factory Installed
in Blower Shelf
Tube location when used in UPFLOW application
(Blower access panel removed)
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BO X TU BE (GREE N)
INDUCER HOUSING (MOLDED) DRAIN TUBE
(BEHIND COLLECTOR BOX DRAIN TUBE)
COLLECTOR BOX DRAIN TUBE
(BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED DR AIN TUB E
COUPLING (LEFT DRAIN OPTION)
FIELD-INSTALLED FACTORY-
SUPPLIED DRAIN TUBE
Condensate Trap on
LEFT Side
CAP
COLLECTOR B O X TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
BURNER E NCLOSURE PR ES SURE
REFERENCE TUBE ASSEMBLY
INDUCER HOUSING DRAIN TUBE (VIOLET)
Tube locatio n when used in DOWNFLOW ap plicatio n
Tube location when used on
HORIZONTAL - LEFT a pplication
PLUG
CAP
BURNER
ENCLOSURE
PRESSURE
REFERENCE TUBE
ASSEMBLY
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
COLLECTOR BOX EXTENSION DRAIN TUBE
COLLECTOR B OX TU BE (PINK) RELOCA TE TUB E BETW EE N BLOWER SHELF AND
INDUCER HOUSING FOR 040,060, AND 080 HEA TING INP UT FURNACES
NOTE:
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONT AL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and
the blower shelf to prevent a trap.Refer to the Installation Instructions for further details.
DRAIN TUBE
COUPLING
TUBE ROUTING
BURNER E NCLOSURE PR ES SURE
REFERENCE TUBE ASSEM BLY
CAP
PLUG
COLLECTOR BOX
DRAIN TUBE
(BLUE & WHITE STRIPED)
CONDENSATE TRAP
FIELD-INSTALLED
FACTORY-SUPPLIED DRAIN
TUBE COUPLING (RIGHT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
1/2-IN. CPVC STREET
ELBOWS (2) FOR LEFT
DRAIN OPTION
COLLECTOR BOX DRAIN TUBE
(BLUE)
COLLECTOR BOX
EXTENSION TUBE
PLUG
COLLECTOR BOX TU BE
(PINK)
COLLECTOR BO X DR AIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR
BOX TUBE
(GREEN)
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BO X TU BE
(PINK)
COLLECTOR BOX TU BE
(GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE)
CONDENSA T E T R AP
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX TUBE
(GREEN)
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
DRAIN TUBE
COUPLING
DRAIN TUBES ROUTED IN
FRONT OF GAS VALVE
Tube location when used on
HORIZONTAL - RIGHT application
COLLECTOR BOX DRAIN TUBE (BLUE)
PLUG
CAP
COLLECTOR BO X TU BE (GREE N)
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
Condensate Trap on LEFT
COLLECTOR BOX DRAIN TUBE
PLUG
COLLECTOR BOX EXTENSION TUBE
CONDENSATE TRAP
GAS VALVE
CO LLECTOR BOX TUBE (PINK)
INDUCER HOUSING DRAIN TUBE (VIOLET)
Side Optional
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX
DRAIN TUBE
(BLUE & WHITE STRIPED)
Condensate Trap on
RIGHT Side
CAP
(BLUE)
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX EXTENSION
DRAIN TUBE
AUXILIARY "J" BOX
RELOCATED HERE
BURNER
ENCLOSURE
PRESSURE
REFERENCE
TUBE ASSEMBLY
COLLECTOR BO X
EXTENSION TUBE
CONDENSATE TRAP
325400-201 REV. C
(LIT - BOTTOM)
Fig. 8—Furnace Pressure and Drain Tubing Diagram
16. Check furnace operation through 2 complete heat operating
cycles. Look through sight glass in burner enclosure to check
burners. Burner flames should be clear blue, almost transparent. (See Fig. 9.)
17. Check for gas leaks.
A00351
Never use matches, candles, flame, or other sources of
ignition to check for gas leakage. Use a soap-and-water
solution. Failure to follow this warning could result in a fire,
personal injury, or death.
18. Replace main furnace door.
SECONDARY HEAT EXCHANGERS
NOTE: The condensing side (inside) of the secondary heat
exchangers CANNOT be serviced or inspected. A small number of
bottom outlet openings can be inspected by removing the inducer
6
BURNER FLAME
MANIFOLD
Fig. 9—Burner Flame
RTV
PAM
BURNER
A89020
NOTE: Ensure the drain tube disconnected from the inducer
housing is higher than the collector box opening or water will flow
out tube.
9. Inspect inside area of collector box for any pieces of foreign
materials and remove if present.
DO NOT use wire brush or other sharp object to inspect or
dislodge materials in secondary heat exchangers as failure of
the secondary heat exchanger will occur. Flush with water
only.
10. Reassemble inducer assembly by reversing items 5-7. Tighten
the vent coupling clamp screw(s) to 15 in.-lb of torque.
NOTE: If seal between the inducer housing and the collector box
is damaged in any way, it must be repaired. To repair, apply
sealant releasing agent such as PAM cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) to inducer housing.
(See Fig. 10.) Apply a small bead of G.E. RTV 162, G.E. RTV
6702, or Dow-Corning RTV 738 sealant to groove in collector
box.
11. Refer to furnace wiring diagram and reconnect wires to
inducer motor and pressure switches or connectors.
12. Reconnect pressure tubes to pressure switches. See diagram
on main furnace door for proper location of tubes. Be sure
tubes are not kinked. (See Fig. 8.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating
cycles. Check area below inducer housing, vent pipe, and
condensate trap to ensure no condensate leaks occur. If leaks
are found, correct the problem.
15. Check for gas leaks.
A93081
Fig. 10—Gasket on Collector Box
assembly. See Flushing Collector Box and Drainage System
section for details on removing inducer assembly.
Step 5—Flushing Collector Box and Drainage
System
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or
connectors.
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by loosening coupling clamp on inducer outlet.
6. Disconnect drain tube from inducer housing. (See Fig. 8.)
7. Remove inducer housing assembly by removing 4 bolts
attaching assembly to cell panel.
8. Flush inside of collector box with water until discharge from
condensate trap is clean and runs freely.
Never use matches, candles, flame, or other sources of
ignition to check for gas leakage. Use a soap-and-water
solution. Failure to follow this warning could result in a fire,
personal injury, or death.
16. Replace main furnace door.
Step 6—Servicing Hot Surface Ignitor
The ignitor does NOT require annual inspection. Check ignitor
resistance before removal.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect ignitor wire connection.
4. Check ignitor resistance.
a. Using an ohm meter, check resistance across both ignitor
leads in connector.
b. Cold reading should be between 45 ohms and 90 ohms.
c. If ohm reading is higher than 110 ohms, ignitor is cracked
and must be replaced.
5. Remove ignitor assembly.
Allow ignitor to cool before removal. Normal operation
temperatures exceed 2000°F.
a. Do not remove ignitor from bracket while assembly is in
furnace. Using a 1/4 in. nutdriver, remove screw securing
7
bracket and ignitor assembly to bottom of burner box. The
screw in the bracket is always located toward outside of
burner box. The screw may be hidden by inlet box or inlet
pipe, but can be removed without removing either. After
removing screw, slide ignitor and bracket toward outside of
burner box and pull straight out.
The ignitor is fragile. DO NOT allow it to hit the side of the
burner box opening while removing or replacing it.
b. Inspect ignitor for a white area indicating a crack may be
present. If found, replace ignitor.
NOTE: A small crack cannot be seen on a new ignitor. After a
period of operation, a white area will be visible around the crack.
c. If replacement is required, replace ignitor on ignitor bracket
external to furnace to avoid damage as the silicon portion is
very brittle and will easily crack or shatter.
d. To remove ignitor from ignitor bracket, remove screw
holding ignitor ceramic block to bracket and pull ceramic
block out of bracket.
6. To replace ignitor/ignitor assembly, reverse items 5a through
5d.
7. Reconnect ignitor wire connection.
8. Turn on gas and electrical supplies to furnace.
9. Verify ignitor operation by initiating control board self-test
feature or by cycling thermostat.
10. Replace main furnace door.
Step 7—Electrical Controls and Wiring
There may be more than 1 electrical supply to the unit. Check
accessories and cooling unit for additional electrical supplies.
The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 11 for field wiring information
and to Fig. 15 for unit wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control center will flash rapidly and prevent the furnace from
operating. The control system also requires an earth ground for
proper operation of the control center and flame sensing.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control center. (See Fig. 12.) Any direct shorts of the 24-v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size.
With power to the unit disconnected, check all electrical connections for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.
Reconnect electrical supply to unit and observe unit through 1
complete operating cycle. Electrical controls are difficult to check
without proper instrumentation; if there are any discrepancies in
the operating cycle, contact your dealer and request service.
In applications where the ambient temperature around the furnace
is 32°F or lower, freeze protection measures are required. If this
application is where heat tape has been applied, check to ensure it
will operate when low temperatures are present.
WCRGY
NOTE
3
NOTE 1
TWO WIRE
NOTES:
1.
Connect Y or Y/Y2 terminal as shown for proper cooling operation.
2.
Proper polarity must be maintained for 115-v wiring.
3.
Use W2 with 2-stage thermostat when zoning.
4.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
5.
Some thermostats require a "C" terminal connection as shown.
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-, 208/230-, 460-V WIRING
THERMOSTAT
TERMINALS
GND
GND
CONDENSING
UNIT
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE PHASE
GND
208/230-V
SINGLE
PHASE
GND
Fig. 11—Field Wiring
8
A98325
EAC-ELECTRONIC AIR
CLEANER TERMINALS
(115-VAC 1 AMP MAX)
MAIN BLOWER
CONTROL WIRE
CONNECTOR
CONTINUOUS
FAN (CF) SETUP
SWITCHES
HOT SURFACE
IGNITOR CONNECTOR
115-V
CONNECTORS
HUM
RG
24-V THERMOST AT
TERMINALS
W/W1 Y/Y2
24V
COM
TRANSFORMER
24-V CONNECTORS
COMMUNICATION
CONNECTOR
W2
Fig. 12— Variable-Capacity Control Center
PRESSURE SWITCH
CONNECTOR
HUM-HUMIDIFIER
TERMINAL
(24-VAC 0.5 AMP MAX)
DEHUMIDIFY ENABLE (DE)
DEHUMIDIFIER (DEHUM)
CONNECTOR
3-AMP FUSE
STATUS AND DIAGNOSTIC
LED LIGHTS
AIR CONDITIONING
(A/C) SETUP SWITCH
SETUP SWITCHES
(SW) AND BLOWER
OFF DELAY SETUP
SWITCHES
MODEL PLUG
A99097
NOTE: Heat tape, when used, should be wrapped around the
condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks,
cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or
discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Step 9—Winterizing
Freezing condensate left in the furnace will damage the
equipment.
If the furnace will be off for an extended period of time in a
structure where the temperature will drop to 32°F or below,
winterize as follows:
If this furnace is installed in an unconditioned space where
the ambient temperatures may be 32°F or lower, freeze
protection measures must be taken.
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect drain tube from inducer housing. (See Fig. 13.)
4. Insert funnel in drain tube and pour antifreeze, propylene
glycol (RV, swimming pool antifreeze, or equivalent) into
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
A93058
furnace until it is visible at point where condensate enters open
drain. (See Fig. 14.)
5. Reconnect drain tube to inducer housing.
6. Replace main furnace door.
9
Fig. 13—Inducer Housing Drain Tube
A99118
Do not use ethylene glycol (Prestone II antifreeze/coolant or
equivalent automotive type). Failure of plastic components
will occur.
WIRING DIAGRAMS
See figures 11, 12 and 16 for the Deluxe 4-Way Multipoise
Furnace wiring diagrams.
TROUBLESHOOTING
For an explanation of fault codes, refer to service label located on
back of main furnace door (See Fig. 15.).
The control center stores all fault codes for a period of 5 “good or
proper” operating cycles, regardless of 115- or 24-v power
interruption.
NOTE: Removing blower access panel opens blower access
panel door switch and terminates 115-v power to control center.
Look into blower access panel sight glass for current LED status.
1. To retrieve fault code, proceed with the following:
NOTE: NO thermostat signal may be present at control center
and all blower time delay of periods must be completed.
a. Leave 115-v power to furnace turned on.
b. Remove main furnace door.
c. Look into blower access panel sight glass for current LED
status.
d. Remove blower access panel.
e. Turn setup switch SW-1 to ON position. (See Fig. 12 or 16
for location.)
f. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
Fig. 14—Funnel in Drain and Antifreeze Running
Through Trap
Blower access panel door switch opens 115-v power to
control center. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
personal injury or death.
g. LEDs display last fault code to occur first, followed by any
other fault that has occurred in the last 5 “good or proper”
cycles. The remaining faults displayed will be in numerical
order starting from the lowest number first. Only 1 of each
fault code will be displayed, regardless of how many times
the fault has occurred.
h. Fault code display will continue and repeat as described
above or until setup switch SW-1 is turned off.
i. Release blower access panel door switch and replace
blower access panel.
j. Operate furnace through 1 heat cycle to test for proper
operation and check LED status.
k. If furnace is operating properly and LEDs indicate proper
operation, replace main furnace door.
2. Fault code display can be removed from control’s display
mode by performing the following. This is also called the
“Clean Up Procedure.”
a. Leave 115-v power to furnace turned on.
b. Remove main furnace door.
c. Look into blower access panel sight glass for current LED
status.
d. Remove blower access panel.
10
A99119
SERVICE
LED CO D E
RED LED1 ON
RED LED2 ON
YELLOW LED3 ON
GREEN LED4 ON
RED LED2 FLASHING
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT
DETERMINED BY NUMBER OF FLASHES OF THE YELLOW LED AND THE SECOND DIGIT
DETERMINED BY NUMB ER O F FLASHES O F THE GREE N LED.
11 NO FAULT IN RECENT HISTORY DISPLAY - Indicates no faults have occurred within last fiv e cycles.
To read recent fault histor y put setu p switch "S W-1" in the " ON" position. To clear recent fault
history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals
"R", "W/W1", and "Y/Y2" simultaneously until an "11" is flashed.
12 BLOWER CALIBRATION LOCKOUT - Indicates RPM calculated for low heat was less than 250 RPM
or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset
power and refer to fault #44 section.
13 LIMIT SWITCH LOCKOUT - Indicates the occurrence of 10 successive limit trips during high heat
or three successive limit trips during low h eat. Auto reset aft er three hours.
Check for: - Improper or misaligned limit and/or limit shield.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 INVALID MODEL SELECTION - Indicates model plug is missing or incorrect. See wiring diagram
for correct connector jumper location.
22 SETUP ERROR - Indicates setup switch "SW-1" or SW-6" is positioned improperly. The following
combinations will cause the fault.
23 INVALID BLOWER AIRFLOW SELECTION - Indicates im proper "A/C" or "C F" switch setting. The 042
and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The
060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is
flashing unit will default to closest allowable airflow.
24 SECONDARY VOLTAGE FUSE IS OP EN
Check f o r: - Short circuit in secondary voltage (24V ) wiring.
31 HIGH PRESSURE SWITCH FAULT - Indicates high pressure switch is closed at call, or in low heat,
or fails to close after call, or opens in high heat.
Check f or: - Plugged c o ndensate drain.
32 LOW PRESSURE SWITCH FAULT - Indicates low pressure switch is closed at call, or fails to close
after call, or opens during operation.
Check f or: - Plugged c o ndensate drain.
33 LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - Indicates the limit, rollout switch or auxiliary limit
switch is open or the unit is operating in high heat only mode due to two successive low heat
limit trips. Check for: - Improper or misaligned limit and/or limit shield.
34 IGNITION PROVING FAULT - Control will try three more times before a lockout #14 occurs.
Check for: - Gas valve defective or gas valve turned " OFF".
- Defective Hot Surface Ignitor- Manual valve shut-off.
- Low inlet gas pressure
- Green wire MUST be connec ted to furnace sheet metal.
- Proper flame sense microamps (.5 microamps D.C. min imu m, 4.0 - 6.0 nominal HIGH HEAT)
- Inadequate flame carryover or rough ignition.
- Oxide buildup on flame sensor (clean with fine sandpaper.)
41 BLOWER OUTSIDE VALID SPEED RANGE - Indicates the blower is not operating at the ca lculated
RPM. If this fault occur s in conjunction with faul t #44 check wiring to motor otherwise refer to
the trouble-shooting guide.
42 INDUCER OUTSIDE VALID SPEED RANGE - Indicates the inducer is not operating at the
calculated RPM, or has not starte d within 10 seconds a f ter a call for heat. Check wiring to
motor ot herwise refer to the trouble-sh ooting guide.
43 PRESSURE SWITCH CALI B R ATION F AULT - Indicates the low and high pressure switch "make"
points during high heat purge are not within the calibration range.
Check f or: - Plugged c o ndensate drain.
44 BLOWER CALIBRATION FAULT - Indicates the calculated blower speed is below 250 or above
1300 RPM. Un it will default to low or high heat mode if possible. If this fault occurs in conjunction
with fault #41 check wiring to motor otherwise refer to the trouble-shooting guide. If this fault
occurs by itself check for undersized ductwork, or excessive static caused by a dirty filter, or
closed registers.
STATUS CODE EXAMPLE
To initiate the component test sequence, shut "OFF" the room thermostat or disconnect the "R"
thermostat lead. Put setup switch "SW-6" in the "ON" position to start the component test sequence.
Once initiated the main board will turn "ON" the inducer motor-low speed, inducer motor-high speed,
hot surface ignitor, blower motor-low speed, and blower motor-high speed for 15-20 seconds each.
When component test is completed one or more of the following cod e s will flash. Ga s Valve and
Humidifier will not be turned on.
CODE DESCRIPTION
11
Indicates inducer and blower motor tested OK. Visual check of hot surface ignitor required.
22 SETUP ER ROR
41 BLOWER OUTSIDE VALID SPEED RANGE -
42 INDUCER OUTSIDE VALID SPEED RANGE -
wiring and control center.
To repe at compone nt te s t turn s e tup switch "SW -6" "OFF" and the n ba c k "O N ". A fter componen t test is
completed put setup switch "SW-6" in the "OFF" position and reconnect the "R" thermostat lead.
Furnace is o perating in emergency heat.
The microprocessor has m alf unctioned. To reset: Put setup switch "
position and jum per thermostat terminal s "
the door sw itch pushed in and po wer to the unit "
setup switch in the "
Furnace is o perating in high hea t.
Furnace is o perating in low heat.
Line voltage polarity is reversed.
- Failed or "Out of Calibration" pressure switches.
RED LED2
MICROPROCESSOR
MALFUNCTION
1
21
FUSE
3
2
1
3
32
4
COUNT THE NO.
SETUP SW,(SW1-8)
OFF
YELLOW LED3
HIGH HEAT
GREEN LED4
LOW HEAT
RED LED1
EMER HEAT
OFF
1
2
3
45678
OFF
COMPONENT T E ST
- Same as code 22above.
and control center.
STATUS
R
", "
W/W1
", and "
ON
OFF
DEHUM
OF FLASHES
(4)
" posi tion. If
DE
LED2
W2
COUNT THE NO.
OF FLASHES
". Disconnect jumper and place
reappears replace main control board.
OM
C
24 V
42 FAULT
=
(2)
INDUCER OUTSIDE VALID
SPEED R ANGE
Indicates blower motor failed test. Check blower, wiring,
Indicates inducer m otor failed test. Check inducer,
SW-1
Y/Y2
" simultaneously with
320624-101 REV. H
" in the "ON"
HUMGRY/Y2W/W1
Fig. 15—Service Label
11
A99108
12
MODEL
JUMPERS
SIZE
1-4 2-5 3-6
042040
X
042060
042080
060100
060080
060120
PL10
PL11
PL11
LEGEND
A/CAIR CONDITIONING (ADJUSTA BLE TONN AGE )
ALSAUXILIARY LIMIT SWTIC H OVERTEMP - MANUAL RESET SPST-(N.C)
CFCONTINUOUS FAN (ADJUSTABLE CFM)
CPU1MAIN MICROPROCESSOR & CIRCUITRY
CPU2IGNITION MICROPROCESSOR & CIRCUITRY
DEDEHUMIDIFY ENABLE - IF DE CONNECTION PROVIDED REM OV E
DEHUMDEHUMIDIFICATION CONNECTION (24VA C .02 AMPS)
EAC-1ELECTRONIC AIR CLEANER C ONNECTION (115 VAC 1.5 AMP MAX.)
EAC-2ELECTRONIC AIR C LEANER CONNECTION (COMMON)
FRSFLAME ROLLOUT SWITCH - MANUAL RESET, SPST-(N.C.)
FSEFLAME PROVING SENSOR ELECTRODE
FU1FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FA CTORY INSTALLED
FU2FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
JUNCTION
UNMARKED TERMINAL
PCB TERMINAL (FACTORY CONNECTED)
FACTORY WIRING (115 VAC)
FACTORY WIRING (24 VAC)
FIELD WIRING (115 VAC)
CONDUCTOR ON P CB
FIELD WIRING SCREW TERMINAL
TERMIN A L BLO C K - MA R KE D TE R MIN A L
FIELD EARTH GROUND
EQUIPMENT GROUND
FIELD SPLICE
PCB TERMINAL (FIELD CONNECTION)
PLUG RECEPTACLE
HPS
C
YEL
LPS
C
NOTE #11
ORN
BRN
BLU
RED
NOTE
#6
SELECTION CHART
NOTE #2
FU2
BLU
NO
NOTE #11
NO
LGPS
BLOWER
OFF-DELAY
78
OFF
78
OFF
8
7
OFF
78
OFF
RED
ORN
(WHEN
USED)
TO 115 VAC FIELD DISCONNECT
ILK
90
SEC.
135
SEC.
180
SEC.
225
SEC.
HUM
R
G
Y/Y2
W2
W/W1
C
OM
L1
L1
NOTE #2
PL3
L2
654
PL1
CPU1
12345
FRS
DEHUM
(WHEN USED)
HUMR
HSIR
GVR
L2
T 2
T 1
CPU2
B17
B2
HSIR
EAC
LS
DE
PL10
CPU1
CPU2
5
4
3
2
1
6
HUMR
EMER. HEAT
PL11
EQUIPMENT GROUND
D.C.
POWER
SUPPL Y
SW - 4
IND
NOTE #7
EAC-1 EAC-2
ALS
D.C. POWER
GVR
EAC
PL11
PL12
PL1-9
SUPPLY
SCHEMATIC DIAGRAM
(NA TURAL GAS & PROPANE)
12
6
4
MTR1
2
1
10
PL7
PCB
NOTE #5
PL13
6
14
8
16
3
5
4
3
2
1
2
PL4PL9
1
FU1
NOTE #6
PL1-11
PL1-2
PL1-10
PL2-4
PL2-2
PL2-1
PL1-1
PCB
NOTE #5
NOTE #11
MTR2
2
1
SEC-1
P
M
HI
LGPS
(WHEN USED)
NOTES:
1. If any of the original equipment wire is replaced use wire rated for 105°C.
2. Use only copper wire between the disconnect switch and the furnace junction box (JB).
3. This wire must be connected to furnace sheet metal for control to prove flame.
4. Symbols are elec trical repre se n tation onl y.
5. Solid lines, inside circuit boa rd PCB are p rinte d cir c uit boa rd trac es and are n ot d epicted as s ho w n in th e legend .
6. Replace only with a 3 AM P fus e.
7. Inductor used on all 060 or -20 airflow units.
8. Blower-on delay, gas heating 60 seconds low heat, 35 seconds high heat, cooling or heat pump 2 seconds..
9. Blower-off delay, gas h eating 90, 135, 180 or 225 s econds, cooling or heat pump 90seconds.
10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset after three hours.
11. Factory connected when LGPS not used.
HSI
P1
115VAC
TRAN
24VAC
GV
PL1-7
C
NOTE #3
NO
NOTE #11
NO
FSE
322296-101 REV. E
SEC-2
HPS
LPS
P2
C
C
Fig. 16—Wiring DiagramA00350
e. Turn setup switch SW-1 to ON position. (See Fig. 12 or 16
for location.)
f. Jumper thermostat terminals R, W, and Y on control center.
g. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
Blower access panel door switch opens 115-v power to
control center. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
electrical shock, personal injury, or death.
h. h. After fault code 11 flashes for at least 2 times, remove R,
W, and Y jumpers.
i. Turn setup switch SW-1 to OFF position.
j. Release blower access panel door switch and replace
blower access panel.
k. Operate furnace through 1 heat cycle to check for proper
operation and check LED status.
l. If furnace is operating properly and LEDs indicate proper
operation, replace main furnace door.
3. The control can also assist in troubleshooting by performing a
Component Test. The Component Test will functionally
operate all furnace components, except the gas valve.
a. To initiate Component Test proceed with the following:
(1.) Leave 115-v power to furnace turned on.
(2.) Remove main furnace door.
(3.) Remove blower access panel.
(4.) Turn setup switch SW-6 to ON position.
(5.) Manually close blower access panel door switch. Use
a piece of tape to hold switch closed.
(1.) The control center goes through a brief self test. This
self test takes approximately 2 sec to complete. After
door switch is closed, red (microprocessor) LED
briefly comes on. Then green LED comes on for 1 sec,
followed by 1 sec where both the green and yellow
LEDs are on. During this time, the control is checking
itself.
(2.) Inducer motor operates for 20 sec at low speed,
operates for 20 sec at high speed, then turns off.
(3.) Hot surface ignitor is energized for 15 sec, then
de-energized.
(4.) Main blower motor operates for 20 sec at low speed,
operates at high speed for 20 sec, then turns off.
(5.) After component operation test is completed, 1 or
more fault codes (11, 22, 41, or 42) will flash. See
service label on back of main furnace door or Fig. 15
for explanation of codes.
NOTE: To repeat component test, turn setup switch SW-6 to OFF
and then back to ON.
c. After component test, perform the following:
(1.) Release blower access panel door switch and turn
setup switch SW-6 to OFF position.
(2.) Replace blower access panel.
(3.) Operate furnace through 1 heat cycle to check for
proper operation and check LED status.
(4.) If furnace is operating properly and LEDs indicate
proper operation, replace main furnace door.
Blower access panel door switch opens 115-v power to
control center. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
electrical shock, personal injury, or death.
b. When items (1) through (5) above have been completed,
the following will occur:
13
14
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
• Unit Familiarization• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training[ ] Classroom Service Training
Fig. 16—Wiring Diagram
A94328
15
Copyright 2000 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 4623158mvp9sm
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8aPC 101Catalog No. 535-795Printed in U.S.A.Form 58MVP–9SMPg 1610-00Replaces: 58MVP-7SM
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.