Carrier 58MVB120F10120, 58MVB060F10114, 58MVB100F10120, 58MVB080F10120, 58MVB080F10116 Installation Guide

...
Page 1
Installation Instruction
Visit www.Carrier.com
NOTE: Read the entire instruction manual before starting the installation. Please retain these instructions with the furnace
after installation for future reference.
NOTE: This furnace can be installed as a (2-pipe) direct vent or (1-pipe) non-direct vent condensing gas furnace,
®
to the Expertg
iso 9001:2000
Special Venting Requirements for Installations in Canada
Installation in Canada nmst conform to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings,
cements, and primers listed to ULC $636. The special vent fittings and accessory concentric vent termination kits and accessory external drain trap have been certified to ULC $636 for use with
those IPEX PVC vent components which have been certified to this standard. In Canada, the primer and cement must be of the
same manufacturer as the vent system - IPEX System 636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and IPEX System 636(1) '_, PVC Cement for Flue Gas Venting, rated Class
IIA, 65 deg C. must be used with this venting system - do not mix primers and cements from one manufacturer with a vent system from a different manufacturer. Follow the manufacturer's
instructions in the use of primer and cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC $636, of the vent system is based on following these installation instructions, the vent system
manufacturer's installation instructions, and proper use of primer and cement. All fire stop and roof flashing used with this system
must be UL listed material. Acceptability under Canadian standard CSA B149 is dependent upon full compliance with all installation
instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority, municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a permit.
Consignes sp_ciales pour l'installation de ventillation au Canada
L'installation faite au Canada doit se conformer aux exigences du code CSA B149. Ce syst_me de ventillation dolt se composer de
tuyaux, raccords, ciments et appr_ts conformes au ULC $636. La tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que l'ensemble du drain de condensat ext_rieur ont _t_ certifies ULCS 636 pour l'application des
composantes IPEX PVC qui sont certifi_es g_ce standard. Au
Canada l'appr_t et le ciment doivent _tre du m_me manufacturier
que le syst_me de ventillation - IPEX Syst_me 636, Appr_t PVC/CPVC. Mauve Violette pour conduit en _vacuation des gaz et
IPEX Syst_me 636(1) '_, ciment pour PVC pour conduit en _vacuation des gaz, _valu_ CLASSE IIA, 65 deg. C. doit _tre
utilis_ avec ce syst_eme d'_vacuation - ne pas m_langer l'appr_t et le ciment d'un manufacturier avec le syst_me de ventillation d'un
autre manufacturier. Bien suivre les indications du manufacturier
lors de l'utilisation de l'appr_t et du ciment et ne pas utiliser ceux-ci si la date d'expiration est atteinte.
L'op_ration s_curitaire, tel que d_finit par ULC $636, du syst_me de ventilation est bass sur les instructions d'installation suivantes,
ainsi que l'usage appropri_ de l'appr_t et ciment. Tout arr_t feu et solin de toit utilis_s avec ce syst_me doivent _tre des mat_riaux list,s UL L'acceptation du standard Canadien CSA B419 est
directement reli_ _ l'installation conforme aux instructions ci- haut mentionn_es. Le standard Canadien recommande 1' inspection par
un personel qualifi_ et ce, une fois par annie. Les autorit_es ayant juridiction (inspecteurs de gas, inspecteurs en
bfitiments, d@artement des incendies, etc) devraient _tre consult_es
avant l'installation afin de d_terminer si un permis est requis.
(1) System 636 is a trademark of IPEX Inc.
Page 2
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA-54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It
shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA
54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by
the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and
Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617-727-9952.
Page 3
TABLEOFCONTENTS......................... PAGE
IMPORTANT ..................................... 2
SAFETY CONSIDERATIONS ........................ 3
CODES AND STANDARDS ......................... 6
INTRODUCTION .................................. 7
APPLICATIONS ................................... 7
LOCATION ...................................... 15
INSTALLATION .................................. 20
START-UR ADJUSTMENTS AND SAFETY CHECK ... 43
4_ _ HOR/Z?NTA I HORIIZGOHNTAL_ 0
AIRFLOW AIRFLOW
©
AIRFLOW
Fig. 1 - Multipoise Orientations
A93041
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component
failure. Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building
codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC)
NFPA 70. In Canada, refer to the current editions of the National Standards of
Canada CAN/CSA-BI49.1 and .2 Natural Gas and Propane
Installation Codes, and Canadian Electrical Code CSA C22A
Recognize safety information. This is the safety-alert symbol Z_ When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
g
SAFETY CONSIDERATIONS
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious iniury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use could cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal iniury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or
assistance. The qualified service agency must use only factory-authorized and listed kits or accessories when modifying this product.
ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental
polution. Remove and recycle all components or materials (i.e., oil,
refrigerant, control boards, etc.) before unit final disposal.
CUT HAZARD Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
Page 4
2 IN (51 mm) COMBUSTION
!_lN(13mm)
GAS CONN
2IN VENTOONN
]_INDIA(13mm)
1
(576 mm)
(684 ram)
664 ram)
©
AIRFLOW
A_ (14 ram)
TYP
(829 mm)
(21 ram)
TRAP LOCATION (DOWNFLOW &
HORIZONTAL LEFT)
;a IN DIA (22ram)
_- POWER CONN
ACCESSORY POWER ENTRY
LOCATION (ALTERNATE
UPFLOW)
DRAIN TRAP ]
8_6' 17 _16"
TYP (439
(240 ram)
DRAIN LOCATION 11'!6"_ _ 1'16" (UPFLOW) (17 ram) (17 ram)
OUTLET
[]_] HORIZONTAL RIGHT) "_
INLET
_E_
28 i_, (724 mm)
_26 s,i6" (684 mm)
2614" (667 ram)
22 _' (567 mm)_
'l:',r,, T
CONDENSATE DRAIN
(DOWNFLOW &
OR ALTERNATE
!_z IN D]A GAS CONN
1
30 %" _+_ 2 N _f/T,r,l_5 39 7S"
(......... ) f_ _'_"- _ENT_ONN (......... )
1
l'T' ,' ,,,,,.......1
DRAIN LOCATION / _ 22 1i' TYP _1 _g_6" (11 mm)
(UPFLOW) (o65 ram)
............... J _.__TTu#_1_47___lI...... ,,( ........ )
FOR NORIZONTAL
HANGING (614 ram)
_19"(483 ram) _ _!_1d' (21 ram)
I / COMBUSTION AIR CONN b6"|
GAS CONN
......../
,Z......
T_4 ER MOSTAT_TRY |
SIDE INLET ,
b <!
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturerb recommendations for equivalent diameters.
2. Minimum return-air opening at furnace: a. For 800 OFM 16-in. (408mm) round or !41A (388 mm)x 12-in. (305 mm) rectangle
b. For !200 CFM 20-in. (508mm) round or 141# (368mm)x 197Mn. (495mm).rectangle c. For !600 CFM 22-in. (558mm) round or 141# (368mm)x 231#-in.(591mm) [ectangle d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM.
Dimensions - In. (mm)
UNIT SIZE A D E 040-14 / 042040 24-1/2 (622)* 22- 7/6 (581)* 23 (584)* 060-14 / 042060 17-1/2 (445) 15- 7/8 (403) 16 (406)
080-14 / 042080 21 (533) 19- 3/6 (492) 19-1/2 (495) 080-20 / 060080 21 (533) 19-3/6 (492) 19-1/2 (495)
100-20 / 060100 21 (533) 19- 3/6 (492) 19-1/2 (495) 120-20 / 060120 24-1/2 (622) 22- 7/6 (581) 23 (584)
*These dimensions reflect the wider casing for the Trophy (96.6% AFUE) furnace.
Fig. 2 - Dimensional Drawing
The 58MVB Multipoise Condensing Gas-Fired Furnaces are CSA (formerly AGA and CGA) design-certified for natural and propane gases (see furnace rating plate) and for installation in alcoves,
attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A CSA listed gas conversion kit is required to convert furnace for use with
propane gas. See Fig. 3 for required clearances to combustibles.
Maintain a 1-in. (25 ram) clearance from combustible materials to supply air ductwork for a distance of 36 inches (914.4 ram) horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In
downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring.
Special base is not required when this furnace is installed on Manufacturer's Coil Assembly or when Manufacturer's Coil Box
is used. These furnaces are suitable for installation in a structure built on site or a manufactured building completed at final site. The
design of this furnace line is NOT CSA design-certified for installation in recreation vehicles, manufactured (mobile) homes or
outdoors. This furnace is designed for continuous return-air minimum
temperature of 60°F (16°C) db or intermittent operation down to
A05124
55°F (13°C) db such as when used with a night setback thermostat. Return-air temperature must not exceed 80°F (27 °C) db. Failure to follow these return air limits may affect reliability of
heat exchangers, motors and controls. (See Fig. 4.) These furnaces are shipped with the drain and pressure tubes
connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT, or HORIZONTAL LEFT (supply-air discharge direction)
applications as shown in Fig. 1. See details in Applications section.
Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions.
Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in the
Combustion Air and Vent piping sections of these instructions.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for detection of leaks to
check all connections as specified in the GAS PIPING section of these instructions.
Always install the furnace to operate within the furnace's intended rise range with a duct system which has an external static pressure
within the allowable range as specified in the SET TEMPERATURE RISE section of these instructions.
Page 5
NSTALLATION
e This forced air fumace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 fL
(0 -2,135m).
An accessory kit, supplied by the manufacturer, shah be used to convert to propane gas use or may be required for some natural gas appiicetions.
This famace is for indoor installation in a building constructed on site. This furnace may be instated in a manufactured (mobile) home when stated on rating plate and using factory authorized kit..
This furnace may be instated on combustible floodng in alsove or closet at Minimum Inches Clearance To Combustible Construction as described below.
e This _mace requires a special venting system. Refer to the installation instructions for parts list and method of installation. In the US this furnace is for use with
schedule=40 PVC, PVC-DWV, CPVC, or AB,S-DWV pipe, and must not be vented in common with other gas-fired appliances. In Canada, refer to installation instructions for vent materiaN. Construction through which vent/air intake pipes may be installed is maximum 24 inches (610 ram), minimum 3/4 inches (19 mm) thickness (including
roofing materials).
e Cette foumaise _ air puls6 est 6quip6e pour utilisation avec gaz naturem et altitudes comprises entre 0 - 3,050m (0 - 10,000 pi),except6 queles foumaises de 140 taifle
sont pour altitudes comprises entre 0 - 2,135m (0 - 7,000pi).
® Utiiiser une trousse de conversion, foumie par le fabdcant, pour passer au gaz propane ou pour certaines installations au gaz natureL e Cette foumaise & air pulse est pour installation a I'intedeur dans un b_timent construit sur place. Cette foumaise a air puNe peut 6tre install6e dans une maison
prCfabdqu6e (maison mobile) si prescrit par la plaque signal6tique et si'l on utilise une trousse specifi6e par le fabrleant.
C.ette foumaise pout 6tre install6e sur un piancher combustible dans un enfoncement ou un pmacerd en observant les D6gagernent Minimum En Pouces Avec EI6ments De Construction Combustibles.
Cette foumaise n6cessite un syst_me d'6vacuation sp6cial. La m6thode d'instaliation et la iiste des pi_ces n6cessaires figurent dana les instructions d"installation. Aux Etats-Unis, cette foumaise dolt s'utiliser avec la tuyautede des nomenclatures 40 PVC, PVC-DWV, CPVC, ou ,ABS-DWV et elle ne peut pas _tre ventil6e conjointment
avec d'autres appareils & gaz. Au Canada, referer aux instructions d'installation pour lax matedaux a ventiler. Epaisseur de la construction au travers de laquene il est possible de faire passer les tuyaux d'aeration (admission/evacuation): 24 po (610 mm) maximum, 3/4 pc (19mm) minimum (y compds la toiture).
For up&3w and downflow applications, furnace must be installed level, or pitched within 1/2" (12.7ram) of level. For a LEVEL 0" ( 0 ) TO _,. MINI 14" (6.35mm) TO horizonfal application, the furnace must be pitched minimum 1/4" (6.35mm) to maximum of 1/Z' (12.7mm) forward for 1/2" (12.7mm) MAXj ¢_L-_-_ 1/2" (12.7mm)MAX
proper drainage. See Installation Manual for IMPORTANT unit support details on horizontal applications.
Pour des applications de flux ascendant et descendant, la foumaise doit ¢¢e install6e de niveau ou indin6e _ T ............. !
pas plus de 1/2" (12.7mm) du niveau. Pour une application hodzontale, lafOumaise dOlt &'Ire inclle_-_eenli'e minimum UPFLOW OR F_0RONT_) 1/4" (6.35mm) et maximum 1/2" (12.7ram) du niveau pour le drainage appropn6. En cas d'installation en position DOWN FLOW
hodzootale, consulter les renseignements mMPORTANTS sur le support dans le manuel d'instaHation. HORIZONTAL
MINIMUMINCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
ALL POSiTiONS:
* Minimum front clearance for service 24 inches (610mm).
t 1 140 size furnaces require I inch back clearance to combustible materials.
DOWNFLOW POSITIONS:
t For installation on combustible 11oors only when instated on special base No. KGASB0201ALL or
NAHA01101SB, CoilAssembly, Part No. CAR, CAP, CNPV, CNRV or Coil Casing, Part No. KCAKC,
or WENC or WTNC.
HORIZONTAL POSITIONSi
Line contact is permissible only between lines formed by intersections of top and two sides of
furnace jacket, and building joists, studs, or framing.
§ Clearance shown is for air inlet and air ou_et ends.
O 120 and 140 size furnaces require 1 inch bottom clearance to combustible materials.
DEGAGEMENT IVIINII_UIVIEN POUCESAVECI_LCMENTSDECONSTRUCTION COMBUSTIBLES
POUR TOUS LES POSITIONS:
D@jagement avant minimum de 24 po (610mm ) pour l'entretien.
1- t Pour les foumaises de 140 taifle, 1 pc (25mm) d6gagement des mat6riaux combustibles est
requis au-arriere.
POUR LA POSITION COURANT DESCENDANT:
1 Pour Ilnstaflation sur le plancher combustible seulement quand on utilise la base sp_ciale, piece
n° KGASB0201ALL ou NAHA01101SB, I'ensemble serpentin, pi_:e n ° CAR, CAP, CNPV, CNRV, ou le carter de serpentin, piece n ° KCAKC ou WENC ou WTNC.
POUR LA POSmON HORIZONTALE:
Le contact n'est permis qOentre les lignes form6es par les intersec_ons du dessus et des deuxottes de la chemise de la foumaise, et des solives, des montants ou de la charpente du
batiment.
§ La distance indiqu_e conceme I'extr_mit6 du tuyau d'ardv_e d'air et I'extr_mit_ du tuyau de sortie d'aic Pour les foumaises de 120 et 140 taifie, 1 pc (25mm) d6gagement des materiaux combustibles
est requis au-dessous.
This furnace is approved for UPFLOW, DOWNFLOW and HORIZONTAL installations.
Cette foumaise est approuv_e pour I'installation HORIZONTALE et la circulation d'air VERS LE HAUT et VERS LE BAS.
Clearance arrows Les _hes de degagement do not change with ne change pas avec
furnace orientation, gen#rateur d'air chaud.
Clearanceininches 0 (pc)D_Jagement D6gagement(pc). d'_ventaveccombustibles.
I'orientation de la
Vent dearance to
combustibles 0".
g
Fig. 3 - Clearances to Combustibles
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the
return air shall also be handled by ducts sealed to the furnace casing and terminating outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed as specified in the Hazardous Locations section of these
instructions and Fig. 5. The furnace may be used for construction heat provided that the
furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
This gas furnace may be used for construction heat provided that:
The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the
A08435
structure.
The furnace is controlled by a thermostat. It may not be "hot
wired" to provide heat continuously to the structure without
thermostatic control.
Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is maintained
between 55°F (13°C) and 80°F (27°C), with no evening
setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per
our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the
nameplate value.
The filters used to clean the circulating air during the
Page 6
constructionprocessmustbeeitherchangedorthoroughly
cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions. If this
furnace is installed with a direct-vent (combustion air and flue) system, a factory accessory termination kit nmst be installed. In a
direct-vent system, all air for combustion is taken directly from the outside atmosphere. See furnace and factory accessory termination kit instructions for proper installation.
These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
Installer Packet Includes:
Installation, Start-up, and Operating Instructions Service and Maintenance Instructions
User's Information Manual
Warranty Certificate
Loose Parts Bag includes: Quantity
Pressure tube extension 1 Collector Box or condensate trap extension tube 1
Inducer Housing drain tube 1
1/2-in. (13 mm) CPVC street elbow 2
Drain tube coupling 1
Drain tube coupling grommet 1 Gas line grommet 1
Vent pipe grommet 1
Combustion-air pipe grommet 2
Gas line entry hole filler plug 1 Power entry hole filler plug 2
Condensate trap hole filler plug 3
Vent and combustion-air intake hole filler plug 2
Combustion-air pipe perforated disk assembly 1
The furnace shall be installed so that the electrical components are protected from water.
For accessory installation details, refer to applicable installation literature.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of
the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply
with the national codes listed below and all authorities having
jurisdiction in Canada.
In the United States and Canada, follow all codes and standards for the following:
Step 1 -- Safety
US: National Fuel Gas Code (NFGC) NFPA 54-2006/ANSI Z223.1-2006 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
CANADA: National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC) CAN/CSA B149.1-05
Step 2 -- General Installation
US: NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas
Association, 400 N. Capitol, N.W., Washington DC 20001
CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard,
Step 3 -- Combustion and Ventilation Air
NFPA 54-2006/ANSI Z223.1-2006, Air for Combustion and Ventilation
CANADA: Part 8 of the NSCNGPIC CAN/CSA B149.1-05, Venting Systems and Air Supply for Appliances
Step 4 -- Duct Systems
US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter
35.
Step 5 -- Acoustical Lining and Fibrous Glass
Duct
US and CANADA: current edition of SMACNA, NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 -- Gas Piping and Gas Pipe Pressure
Testing
US: NFGC; chapters 5, 6, 7, and 8 and national plumbing codes
CANADA: NSCNGPIC Parts 4, 5, 6 and 9. In the state of Massachusetts:
This product must be installed by a licensed plumber or gas fitter.
When flexible connectors are used, the maximum length shall not exceed 36 inches.
! MAX80°F/270
FRONT
:_ MIN60°F / 16 C
A06745
Fig. 4 - Return-Air Temperature
Page 7
18-1N. (457.2 mm)
MINIMUM TO BURNERS
Fig. 5 - Installation in a Garage
When lever type gas shutoffs are used they shall be T-handle type.
The use of copper tubing for gas piping is not approved by the state of Massachusetts.
Step 7 -- Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA 70-2008
CANADA: Canadian Electrical Code CSA C22.1
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
A93044
6. Before removing a new control from its container, discharge your body's electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the
control or yourself into contact with the furnace. Put all used AND new controls into containers before touching
ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
INTRODUCTION
The model 58MVB 4-way multipoise, Gas-Fired, Category IV, direct vent and non-direct vent condensing furnace is available in
model sizes ranging in input capacities of 40,000 to 120,000 Btuh.
APPLICATIONS
Step 1 -- General Some assembly and modifications are required for furnaces /
installed in any of the 4 applications shown in Fig. 1. All drain and pressure tubes are connected as shown in Fig. 7. See appropriate
application instructions for these procedures.
MINOR PROPERTY DAMAGE Failure to follow this caution may result in minor property
damage. Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
1
ii
[]NIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY'S ELECTROSTATIC
CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a
person's hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch
ungrounded objects, etc.)
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before
touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
Step 2 -- Upflow Applications
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned
air is discharged upwards.
Condensate Trap Tubing (Factory-Shipped Orienta-
tion)_
The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications, A factory-supplied
tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate
Trap Tubing (Factory-Shipped Orientation) section for drain tube extension details. (See Fig. 70
NOTE: See Fig. 7 or tube routing label on main furnace door to confirm location of these tubes,
1. Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes These tubes should be factory
attached to condensate trap and pressure switch ready for use in UPFLOW applications. These tubes can be identified
by their connection location and also by a color label on
each tube. These tubes are identified as follows: collector
box drain tube (blue label), inducer housing drain tube
(violet label or molded), relief port tube (green label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube The condensate trap drain connection must be extended for
field attachment by doing the following:
a. Determine location of field drain connection. (See Fig. 2
or 7.)
NOTE: If internal filter or side filter/media cabinet is used, drain tube should be located to opposite side of casing from return duct
attachment to assist in filter removal.
Page 8
b. Remove and discard casing drain hole plug button from
desired side.
c. Install drain tube coupling grommet (factory-supplied
in loose parts bag) in selected casing hole.
d. Slide drain tube coupling (factory-supplied in loose
parts bag) through grommet so long end of coupling faces blower.
e. Cement 2 factory-supplied l/2-in. (13 mm)street CPVC
elbows to rigid drain tube connection on condensate trap. (See Fig. 7.) These elbows must be cemented
together and cemented to condensate trap drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink, preventing draining.
f. Connect larger diameter drain tube and clamp
(factorysupplied in loose parts bag) to condensate trap and clamp securely.
g. Route tube to coupling and cut to appropriate length. h. Attach tube to coupling and clamp securely.
Condensate Trap Tubing (Alternate Upflow
Orientation)
An alternate location for the condensate trap is the left-hand side of
casing. (See Fig. 2 and 8.) NOTE: If the alternate left-hand side of casing location is used,
the factory-connected drain and relief port tubes must be disconnected and modified for attachment. See Condensate Trap
Tubing (Alternate Upflow Orientation) section for tubing
attachment.
To relocate condensate trap to the left-hand side, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts
bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion
products being drawn in from appliances in the equipment room.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
BLOWERSHELF '_ FURNACE
CONDENSATE '_
TRAP (INSIDE)
TUBE LOCATION
--ALTERNATE DRAIN CONDENSATE TRAP
DRAIN TUBE LOCATION
UPFLOW APPLICATIONS
DOOR r'-" CONDENSATE
X
FURNACE
\
FIELD 26 /4 11/2
DRAIN (667mm) (38ram)
CONN
SIDE VIEW FRONT VIEW
DOWNFLOW AND ALTERNATE
EXTERNAL UPFLOW APPLICATIONS
SLOTFORSCREW --7
HORIZONTAL/
APPLICATION
(OPTIONAL) /
11/2 (88ram) /
__/4 (44ram)! ,_,1 _
E 3mm)7/8--I ,--"
GUIDES " -_1 21/4 (WHEN USED) (57ram)
FRONT VIEW SIDE VIEW
/
f
RNACE
DOOR
4
(102mm)
261/4
DRAIN
CONN
1/4" (6mm) COLLECTOR BOX TO TRAP RELIEF PORT
1/2 (13ram) INDUCER HOUSING
DRAIN CONNECTION 5/8 (16ram)
COLLECTOR BOX DRAIN CONNECTION
SCREW HOLE FOR UPFLOW OR DOWN-
FLOW APPLICATIONS (OPTIONAL)
1/2 IN. (13ram) PVC OR CPV
(667mm)
END VIEW
HORIZONTAL
APPLICATIONS
i FURNACE
IDE
_4 (146mm)
3/4
(19ram)
FRONT VIEW
Fig. 6 - Condensate Trap
A07459
Page 9
PLUG--
oAP >.. o HH
D AO L O O 'tOX--,Lr'h ',/All
TUBE (PINK) _ 2 I I- F
PLUG _',
CAP --'-
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX j
TUBE (GREEN) _ C j_'_" ........ _*,,.-\-''-'--,L2 lib
J £O0 E ISATEII
/ ?tlr
FA F_E;;::iiiiiii )/ _/_ "
FIELD-INSTALLED J FIELD-INSTALLED -_
FACTORY-SUPPLIED FACTORY-SUPPLIED
102 -IN. CPVC STREET DRAIN TUBE
ELBOWS (2) FOR COUPLING (RIGHT
LEFT DRAIN OPTION DRAIN OPTION)
A94213
Fig. 7 - Factory-Shipped Upflow Tube Configuration
(Shown with Blower Access Panel Removed)
Condensate Trap Tubing (alternate Upflow Orienta- tion)_
NOTE: See Fig. 8 or tube routing label on main furnace door to confirm location of these tubes.
1. Collector Box Drain Tube Connect collector box drain tube (blue label) to condensate
trap.
NOTE: On 17-1/2-in. (445 ram) wide furnaces ONLY, cut tube between corrugated sections to prevent kinks.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to
condensate trap.
c. Determine appropriate length, then cut and connect
tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Connect relief port tube (green label) to condensate trap.
b. Extend this tube (if required) by splicing to small
diameter tube (factory-supplied in loose parts bag).
Condensate Trap Field Drain Attachment Refer to Condensate Drain section for recommendations and procedures.
COLLECTOR BOX --
DRAIN TUBE (GREEN)
CONDENSATE "'''_l _
TRAP EL
INDUCER --J
HOUSING
DRAIN TUBE
(VIOLET)
A94214
Fig. 8 - Alternate Upllow Tube Configuration and Trap
Location
Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any
modification. NOTE: See Fig. 7 or 8 or tube routing label on main furnace door
to check for proper connections.
Upper Collector Box and Inducer Housing (Unused)
Drain Connections
Upper Collector Box Drain Connection
Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped
label). This tube is plugged to prevent condensate leakage in this
application. Ensure this tube is plugged.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations
and procedures.
Step 3 -- Downflow Applications
A downflow furnace application is where furnace blower is located
above combustion and controls section of furnace, and conditioned air is discharged downwards.
B
Page 10
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAPII I
PLUG
c II
TUBE (PINK)
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX --_
EXTENSION TUBE
CONDEN_
TRAP
INDUCER HOUSING
DRAIN TUBE(VIOLET)
Fig. 9 - Downflow Tube Configuration
(Left-Hand Trap Installation)
©
A94215
DRAINTUBE
COUPLING
TUBE (GREEN)
PLUG
O O
DRAIN TUBE (BLUE)
TUBE (PINK)
DRAIN TUBE (BLUE & WHITE STRIPED)
EXTENSION TUBE
DRAIN TUBE _IOLET)
©
EXTENSION DRAIN TUBE
Fig. 10 - Downflow Tube Configuration
(Right-Hand Trap Installation)
;TOR BOX
BOX
BOX
BOX
CTOR BOX
JCERHOUSING
TRAP
A94216
Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location
as shown in Fig. 2, 9, or 10. To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs in- ward and rotating trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2 and 10.)
4. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal iniury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment
room
5. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
Condensate Trap Tubing
NOTE: See Fig. 9 or 10 or tube routing label on main furnace
door to check for proper connections.
1. Collector Box Drain Tube a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap.
Condensate Trap Located on Left Side of Casing
a. Connect LOWER collector box drain tube (blue and white
striped label) to condensate trap. Tube does not need to be cut.
b. Clamp tube to prevent any condensate leakage.
Condensate Trap Located on Right Side of Casing
a. Install drain tube coupling (factory-supplied in loose parts
bag) into collector box drain tube (blue and white striped
label) which was previously plugged.
b. Connect larger diameter drain tube (factorysupplied in loose
parts bag) to drain tube coupling, extending collector box drain tube for connection to condensate tr@.
c. Route extended collector box drain tube between gas valve
and inlet housing as shown in Fig. 10.
d. Determine @propriate length and cut.
e. Connect to condensate trap.
f. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed c@ and clamp from LOWER
inducer housing drain connection.
10
Page 11
PLUG
AUXILIARY "J" BOX
COLLECTOR BOX
DRAIN TUBE (BLUE AND WHITE STRIPED)
O O
CONDENSATE
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
TRAP
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR
BOX EXTENSION
DRAIN TUBE
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
060, AND 080 HEATING INPUT FURNACES
Fig. 11 - Horizontal Left Tube Configuration
COLLECTOR BOX
TUBE (GREEN)
JCER HOUSING
DRAIN TUBE (VIOLET)
DRAIN TUBE (BLUE)
A02288
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and
factorysupplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap,
e. Connect inducer housing drain connection to
condensate trap.
(1.) Condensate Trap Located on Left Side of Casing
a. Determine appropriate length and cut.
b. Connect tube to condensate trap.
c. Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
a. Route inducer housing drain tube (violet label) directly
from inducer housing to condensate trap,
b. Determine appropriate length and cut.
c. Connect tube to condensate trap. d. Clamp tube to prevent any condensate leakage,
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection pro-
cedure,
Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch Tubing One collector box pressure tube (pink label) is factory connected to
the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be
disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory
connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or
HORIZONTAL RIGHT applications. NOTE: See Fig. 9 or 10 or tube routing label on main furnace
door to check for proper connections. Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube
(factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to
remaining small diameter tube (factory-supplied in loose parts bag).
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
11
Page 12
il
MAN1
SHUTOFF
GAS VALVE
SEDIMENT TRAP
COMBUSTION -
INTAKE
(146mm)
CONDENSATE
TRAP
30" (762 mm)MIN
)RK AREA
DRAIN
A 12-1N. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH
(5 TO 8 FT/1.5 TO 2.4 M) VENT
SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
ACCESS OPENING
FOR TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
Fig. 12 - Attic Location and Working Platform for Direct Vent (2-Pipe) Application - All Sizes
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
Step 4 -- Horizontal Left (Supply-Air Discharge) Applications
A horizontal left furnace application is where furnace blower is
located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.
MINOR PROPERTY HAZARD Failure to follow this caution may result in minor property
damage. Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
Condensate Trap Location The condensate trap nmst be removed from the factory-installed
blower shelf location and relocated in selected application location as shown in Fig. 2 or 11.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
A93031
3. Remove casing hole filler cap from casing hole. (See Fig. 2 or 11.)
4. Install casing hole filler cap (factory-supplied in loose parts
bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment
room.
5. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
Condensate Trap Tubing
NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.
1. Collector Box Drain Tube
a. Install drain tube coupling (factory-supplied in loose
parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp
(factorysupplied in loose parts bag) to drain tube coupling, extending collector box drain tube.
12
Page 13
A 3-1N.(76mm) MINIMUM CLEARANCE TO COMBUSTION-AIR INTAKE
IS REQUIRED.
S VENT
COMBUSTION
INTAKE
A 12-1N. (305mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT / 1.5 TO 2.4M) VENT SYSTEMS TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
30-IN. (762mm) MIN
IN. (146mm)
MANt
SHUTOFF
GAS VALVE
SEDIMENT TRAP
CONDENSATE
TRAP
DRAIN
ACCESS OPENING
FOR TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
Fig. 13 - Attic Location and Working Platform for Non-Direct Vent (1-Pipe) Applications - Sizes 040 through 120 Only
A96184
c. Route extended tube (blue label) to condensate trap and
cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
c. Deternfine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was
previously connected to condensate trap by splicing to small diameter tube (factory-supplied in loose parts
bag).
b. Route extended collector box pressure tube to relief port
connection on condensate trap.
c. Deternfine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
Condensate Trap Field Drain Attachment Refer to Condensate Drain section for recommendations and
procedures.
Pressure Switch Tubing The LOWER collector box pressure tube (pink label) is factory
connected to the High Pressure Switch for use when furnace is
installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the
pressure switch in HORIZONTAL LEFT applications for 060 and 080 heating input furnaces.
NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.
Modify tube as described below.
1. Disconnect collector box pressure tube (pink label) attached to High Pressure Switch.
2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.
3. Route extended tube:
a. Behind inducer housing.
b. Between blower shelf and inducer housing.
4. Deternfine appropriate length, cut, and reconnect tube to
High Pressure Switch connection labeled COLLECTOR BOX.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations
and procedures.
Construct a Working Platform
Construct working platforn_ where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
13
Page 14
PLUG
CAP
BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX TUBE (PINK)
BOX RELOCATED HERE
o 0
g
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 14 - Horizontal Right Tube Configuration
[]NIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A 12-in. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft./ 1.5 - 2.4 M) vent systems.
This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13 or 42.)
Step 5 -- Horizontal Right (Supply-Air Discharge) Applications
A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace,
and conditioned air is discharged to the right.
MINOR PROPERTY DAMAGE
Failure to follow this caution may result in minor property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in attic
application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes.
CONDENSATE TRAP
A02289
NOTE: The auxiliary junction box (J-box) MUST be relocated to opposite side of furnace casing. (See Fig. 13.) See Electrical
Connection section for J-box relocation.
Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location
as shown in Fig. 2 or 14.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal iniury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion
products being drawn in from appliances in the equipment room.
4. Install condensate trap into right-hand side casing hole by
inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
Condensate Trap Tubing
NOTE: See Fig. 14 or tube routing label on main furnace door to check for proper connections.
14
Page 15
1.CollectorBox Drain Tube
a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was previously connected to condensate trap.
c. Connect LOWER collector box drain tube (blue and
white striped label) to condensate trap. Tube does not need to be cut.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to
condensate trap.
e. Determine appropriate length, cut, and connect tube to
condensate trap.
f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
Refer to Pressure Switch Tubing section for connection procedure.
Condensate Trap Field Drain Attachment
Refer to Condensate Drain procedures.
LEVEL 0" l
TO MIN 1/4"
V2" MAX TO
(0 to 13mm) 1/2" MAX
UPFLOW OR DOWNFLOW HORIZONTAL
Fig. 15 - Proper Condensate Drainage
Pressure Switch Tubing One collector box pressure tube (pink label) is factory connected to
the pressure switch for use when furnace is installed in UPFLOW
or HORIZONTAL LEFT applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory
connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 14 or tube routing label on main furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached
to pressure switch.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connection by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to
pressure switch connection labeled COLLECTOR BOX.
section for recommendations and
(6 to 13 mm)
A02146
4. Use remaining small diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (pink
label) which was previously connected to pressure switch.
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations
and procedures.
Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
[]NIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A 12-in. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft./ 1.5 - 2.4 M) vent systems.
This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13 or 42.)
LOCATION
Step 1 -- General
This furnace must
be installed so the electrical components are protected from
water.
not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
be located so combustion-air and vent pipe maximum lengths are not exceeded. Refer to Table 11.
be located where available electric power and gas supplies meet specifications on the furnace rating plate.
be attached to an air distribution system and be located as close to the center of the distribution system as possible. Refer to Air
Ducts section.
be provided with ample space for servicing and cleaning.
Always comply with minimum fire protection clearances shown
on the furnace clearance-to-combustibles label. (See Fig. 3.)
This furnace may be located in a confined space without special provisions for dilution or ventilation air.
NOTE: For upflow/downflow applications install furnace so that it is level or pitched forward within 1/2-in. (13 mm) for proper furnace operation. For horizontal applications pitch 1/4-in. (6 mm) minimum to 1/2-in. (13 mm) maximum forward to ensure proper condensate drainage from secondary heat exchangers. (See Fig. 15.)
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to furnace casing.
The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within
equipment room or space.
g
15
Page 16
g
FIRE, INJURY OR DEATH HAZARD Failure to follow this warning could result in fire, property
damage, personal iniury, or death. Do NOT install furnace on its back. (See Fig. 16.) Safety
control operation will be adversely affected. Never connect return-air ducts to back of furnace.
[]NIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided that:
-The furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is
provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative
pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products
into the structure.
-The furnace is controlled by a thermostat. It may not be "hot
wired" to provide heat continuously to the structure without thermostatic control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening
setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent
operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
-After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions.
[]NIT DAMAGE HAZARD Failure to follow this caution may result in minor property or
unit damage. If these furnaces are installed in an unconditioned space where
ambient temperatures may be 32°F (0°C) or lower, freeze protection measures must be taken. (See Fig. 17.)
BACK
A93043
Fig. 16 - Prohibit Installation on Back
32° F/0 ° C MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
/
The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot
affect another appliance's combustion air supply or act to mix products of combustion with circulating air, and that the air
circulating fan of the furnace, if installed in an enclosure communicating with another fuel-burning appliance not of the
direct-vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return
air plenum on ducts is in the closed position.
A07911
Fig. 17 - Freeze Protection
Step 2 -- Low-Heat Only Installation
This 58MVB furnace can be installed to operate in the low-heat only heating mode when sized using the low-heat heating capacity. This is accomplished by placing setup switch SWI-2 in the ON
position to provide only low-heat operation. See Fig. 37 and Table
13. With this setup, high-heat operation will not occur.
16
Page 17
[]NITDAMAGEHAZARD
Failure to follow this caution may result in minor property or unit damage.
The furnace can operate in the high-heat mode when certain fault conditions occur. The following precautions should be
taken:
1. Size gas piping based on the high-heat input
2. Check the high-heat input and adjust it per the main
literature instruction.
Step 3 -- Furnace Location Relative to Cooling Equipment The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to
control flow of air shall be adequate to prevent chilled air from entering furnace. If dampers are manually operated, they must be
equipped with a means to prevent operation of either unit unless damper is in full-heat or full-cool position.
Step 4 -- Hazardous Locations
NON-DIRECT VENT (1-PIPE) APPLICATION
UNIT DAMAGE HAZARD Failure to follow this caution may result in intermittent unit
operation. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air
requirements are met.
Refer to the AIR FOR COMBUSTION AND VENTILATION section for details.
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. Installations: Section 9.3 of the NFGC, Air for Combustion
and Ventilation and applicable provisions of the local building codes.
Canadian Installations: Part 8 of the NFPA54/ANSI Z223.1-2006 CAN/CSA-B149.1-05, Venting Systems and Air
Supply for Appliances and all authorities having jurisdiction.
g
FIRE, EXPLOSION, INJURY OR DEATH HAZARD Improper location or inadequate protection could result in fire
or explosion. When furnace is installed in a residential garage, it must be
installed so that burners and ignition sources are located a minimum of 18 in. (457 mm) above floor. The furnace must
be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire
Protection Association, Inc. (See Fig. 18.)
Step 5 -- Furnace Location and Application DIRECT VENT (2-PIPE) APPLICATION
Furnace may be located in a confined space without special provisionsfor dilution or ventilation air.
18-1N. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 18 - Installation in a Garage
FURNACE CORROSION HAZARD
Failure to follow this warning could result in reduced furnace component life.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements could corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Laundry rooms
Hobby or craft rooms, and
Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for
combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative
17
Page 18
pressure in the equipment room or space. A positive seal nmst be made between the furnace cabinet and the return-air duct to
prevent pulling air from the burner area.
Indoor combustion air is permitted for combustion, ventilation,
and dilution, if the Standard or Known-Air-Infiltration Rate
Method is used,
il
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in
addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of make-up air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of
at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
Spaces having less than 50 cubic feet per 1,000 Btuh require the OUTDOOR COMBUSTION AIR METHOD.
Spaces having at least 50 cubic feet per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or
KNOWN-AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion,
ventilation, and dilution of flue gases using permanent horizontal or vertical duct(s) or opening(s) directly
communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 18 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and
ventilation air openings to the outdoors.
a. One opening MUST commence within 12" (300 ram)
of the ceiling and the second opening MUST commence within 12" (300 ram) of the floor.
b. Size openings and ducts per Fig. 19 and Table 1.
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm /kW) _f combined input for all gas appliances in the space per Fig. 19 and
Table 1.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 19 and Table 1.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch of free area per 3,000 Btuh (734
mm2/kW) for combined input of all gas appliances in the space per Table 1 and Fig. 19.
b. Not less than the sum of the areas of all vent connectors
in the space. The opening shall commence within 12" (300 ram) of the ceiling. Appliances in the space shall
have clearances of at least 1" (25 ram) from the sides and back and 6" (150 ram) from the front. The opening
shall directly conmmnicate with the outdoors or shall communicate through avertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
Indoor Combustion Air© NFPA & AGA Standard and Known-Air-Infiltration Rate Methods
2
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in
accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances
installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of
ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the
space and add the volumes together to get the total n_ininmm required volume for the space.
Table 2-Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1-2006/NFPA 54-2006, 9.3.2.2:
1. For other than fan-assisted appliances, such as a draft hood-equipped water heater:
Volume - 21ft3 _ I °ther
2. For fan-assisted appliances such as this furnace:
Other ACH 000 Btu/hr
A04002
Volume
Fan
If Iother = combined input of all other than fan-assisted appliances in Btu/hr
Ifan -- combined input of all fan-assisted appliances in Btu/hr ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
ACH 000 Btu/hr
A04003
18
Page 19
Table1- MinimumFree Area Required for Each Combustion Air Opening or Duct to Outdoors
FURNACE
iNPUT
(BTUH) (1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
40,000 20 6 13.4 5 10 4 80,000 30 7 20 6 15 5
80,000 40 8 26.7 6 20 6 100,000 50 8 33.4 7 25 8 120,000 80 9 40 8 30 7
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
Free Area of Opening Round Duct (in. Free Area of Opening Round Duct (in. Free Area of Opening Round Duct (in.
and Duct (Sq. In.) Dia) and Duct (sq In.) Dia) and Duct (Sq In.) Dia)
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
100,000 + 40,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
80,000 + 40,000 = (100,000 divided by 3,000) = 33.4 Sq. In. for a Single Duct or Opening 80,000 + 30,000 = (110,000 divided by 2,000) = 55.0 Sq. In. for each of two Horizontal Ducts
Table 2 - Minimum Space Volumes for 100 % Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL
ACH
0.80 1,050 1,400 1,750 1,000 1,500 2,000 2,500 3,000
0.50 1,260 1,680 2,1 O0 1,200 1,800 2,400 3,000 3,600
0.40 1,575 2,1 O0 2,625 1,500 2,250 3,000 3,750 4,500
0.30 2,1 O0 2,800 3,500 2,000 3,000 4,000 5,000 6,000
0.20 3,150 4,200 5,250 3,000 4,500 6,000 7,500 9,000
0.10 6,300 8,400 10,500 6,000 9,000 12,000 15,000 18,000
0.00 NP NP NP NP NP NP NP NP
(1,000'S BTUH GAS INPUT RATE) (1000'S BTUH GAS INPUT RATE)
30 40 50 40 80 80 100 120
Space Volume (ft3)
/
U
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.2/l,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances
in the space, but not less than 100 in. 2 (0.06 m2). One opening shall commence within 12" (300 ram) of the
ceiling and the second opening shall commence within 12" (300 ram) of the floor. The n_ininmm dimension of
air openings shall be at least 3 in. (80 ram). (See Fig.
20.)
c. Combining space on different floor levels. The volumes
of spaces on different floor levels shall be considered as communicating spaces if connected by one or more
permanent openings in doors or floors having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total
input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that freely conmmnicates with the outdoors provided there are
adequate permanent ventilation openings directly to outdoors having free area of at least 1-in.2/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for
combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight
construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air
Method section.
Unusually tight construction is defined as
Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between
wall panels, at penetrations for plumbing, electrical and gas lines, etc.
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens nmst be considered. If the free area of a louver or grille design is unknown, it may be
assumed that wood louvers have a 20 percent free area, and metal
louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. (6 ram) mesh. Louvers and grilles
nmst be constructed so they cannot be closed.
19
Page 20
VENT THROUGH ROOF
(305mm)
(305mm)
OUTDOORS BTUH*
*Minimum dimensions of 3 in. (76 mm). Use any of the following combinations of openings:
A&BC&DD&EF&G
Fig. 19 - Air for Combustion, Ventilation, and Dilution for
Outdoors
PER 4000
A03174
When combustion air ducts are used, they nmst be of the same cross sectional area as the free area of the openings to which they
connect. The n_ininmm dimension of ducts must not be less than 3 in. (76 ram).
Combination of Indoor and Outdoor Air
1. Indoor openings shall compy with the Indoor Combustion Air Method below and,
2. Outdoor openings shall be located as required in the Outdoor Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The
minimum dimension of air openings shall be not less than 3 in. (76 mm).
INSTALLATION
Step 1 -- Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 21.) Install field-supplied, corrosion-resistant 5/16-in. (8 ram) machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1-1/2 in. (38 ram).
1. Position furnace on its back. Locate and drill a 5/16-in. (8 ram) diameter hole in each bottom corner of furnace. (See
Fig. 21.) Holes in bottom closure panel may be used as guide locations,
(305mm)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
INTERIOR
HEATED
SPACE
UNCONFINED SPACE
6" MIN (152mm)
(FRONT)0
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
L 12" MAX(805ram)
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in. (76 mm)
t Minimum of 3 in. (76 mm) when type-B1 vent is used.
A03175
Fig. 20 - Air for Combustion, Ventilation, and Dilution from
Indoors
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
5/16',
(8rnm)
1
(44mm)
1 3/4"
(44mm)
(8rnm)
5/16"
(44ram) 1 3/4"
(44ram) 1
A89014
Fig. 21 - Leveling Legs
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
NOTE: Bottom closure nmst be used when leveling legs are used.
See Bottom Closure Panel section.
Step 2 -- Installation in Upflow or Downflow
Applications NOTE: This furnace is approved for use on combustible flooring.
Special base is not required when this furnace is installed on
2O
Page 21
Manufacturer's Coil Assembly or when Manufacturer's Coil Box is
used.
1. Determine application being installed from Table 3.
2. Construct hole in floor per dimensions specified in Table 3
and Fig. 22.
3. Construct plenum to dimensions specified in Table 3 and
Fig. 22.
4. If downflow subbase is used, install as shown in Fig. 23.
5. If coil assembly is used, install as shown in Fig. 24.
NOTE: Remove furnace perforated discharge duct flanges when they interfere with mating flanges on coil on downflow subbase.
To remove furnace perforated discharge duct flange, use hand seamers, wide duct pliers or duct flange tool to bend flange back
and forth until it breaks off. Be careful of sharp edges. (See Fig.
25.)
[]NIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit
operation or performance satisfaction. Do not bend duct flanges inward as shown in Fig. 25. This
will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210 ° as shown in Fig. 25.
Step 3 -- Installation in Horizontal Applications
These furnaces can be installed in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung
from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron
supports. (See Fig. 26.) Cut hanger bolts (4 each 3/8-in. (10 mm) all-thread rod) to desired length. Use 1 X 3/8-in. (10 mm) fiat
washers, 3/8-in. (10 mm) lock washers, and 3/8-in. (10 mm) nuts on hanger rods as shown in Fig. 26. Dimples are provided for hole
locations. (See Fig. 2.)
[]NIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit
operation or performance satisfaction. The entire length of furnace MUST be supported when
furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf
area.
Step 4 -- Air Ducts
GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system
design CFM at the design static pressure. When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the
furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier
is recommended. Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further
requirements. For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft. (3.0 M) of main duct to the first branch take-off may require
internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest
edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with
NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
SUPPLY AIR CONNECTIONS
Upflow Furnaces
Connect supply-air duct to 3/4-in. (19.1 mm) flange on furnace
supply-air outlet. The supply-air duct attachment must ONLY be connected to furnace supply-/outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace
casing to attach supply side air duct, humidifier, or other
accessories. All accessories MUST be connected external to
furnace main casing.
Downflow Furnaces
Connect supply-air duct to supply-air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when
installed on non-combustible material. When installed on combustible material, supply-air duct attachment must ONLY be
connected to an accessory subbase or factory approved air conditioning coil casing. DO NOT cut main furnace casing to
attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
Supply air opening duct flanges must be modified per Fig. 25.
Horizontal Furnaces
Connect supply-air duct to supply air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT
cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external
to furnace main casing.
g
21
Page 22
FURNACE
FACTORY SUPPLIED
CASED COIL OR COIL BOX
COMBUSTIBLE
FLOORING
/
SHEET METAL
PLENUM
FLOOR _
OPENING
Fig. 22 - Floor and Plenum Opening Dimensions
FURNACE
(OR OTHER MANUFACTURER'S
COIL CASING WHEN USED)
/_ COMBUSTIBLE
FLOORING
_/
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 23 - Furnace, Plenum, and Subbase Installed
on a Combustible Floor
A96283
A07585
A07586
Fig. 24 - Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
DISCHARGE DUCT FLANGE
210 DEG.
Fig. 25 - Duct Flanges
MIN
A93029
NO
YES
YES
22
Page 23
Table 3- Opening Dimensions - In. (mm)
FURNACE
CASING
WIDTH
Downflow Applications on Non-Combustible Flooring (419) (498)
17-1/2 Downflow Applications on Combustible Flooring Using KGASB Sub- 16-3/4 20-3/8
(446) base Furnace with or without CAP, CAR, CNPV, CNRV Coil Assem-
Downflow Applications on Combustible Flooring NOT Using KGASB 16-1/2 20
Subbase Furnace with CAP, CAR, CNPV, CNRV Coil Assembly or
Downflow Applications on Non-Combustible Flooring (508) (498)
21 Downflow Applications on Combustible Flooring Using KGASB Sub- 20-1/4 20-3/8
(533) base Furnace with or without CAP, CAR, CNPV, CNRV Coil Assem-
Downflow Applications on Combustible Flooring NOT Using KGASB
Subbase Furnace with CAP, CAR, CNPV, CNRV Coil Assembly or 20 20
Downflow Applications on Non-Combustible Flooring (597) (498)
24-1/2 Downflow Applications on Combustible Flooring Using KGASB Sub- 28-8/4 20-3/8
(622) base Furnace with or without CAP, CAR, CNPV, CNRV Coil Assem-
Downflow Applications on Combustible Flooring NOT Using KGASB 23-1/2 20
Subbase Furnace with CAP, CAR, CNPV, CNRV Coil Assembly or
APPLICATION
A B
16 24-1/8
Upflow Applications (422) (629)
(406) (613)
15-7/8 19
(403) (483)
15-1/8 19
bly or KCAKC Coil Box (425) (518)
(384) (483)
15-1/2 19
KCAKC Coil Box (419) (508)
(394) (483)
19-1/2 24-1/8
Upflow Applications (511) (629)
(495) (613)
19-3/8 19
(492) (483)
18-5/8 19
bly or KCAKC Coil Box (514) (518)
(473) (483)
19 19
KCAKC Coil Box (508) (508)
(483) (483)
23 24-1/8
Upflow Applications (600) (629)
(584) (613)
22-7/8 19
(581) (483)
22-1/8 19
bly or KCAKC Coil Box (603) (518)
(562) (483)
22-1/2 19
KCAKC Coil Box (597) (508)
(572) (483)
FLOOR OPENINGPLENUM OPENING
C D
16-5/8 24-3/4
16-1/2 19-5/8
20-1/8 24-8/4
20 19-5/8
23-5/8 24-3/4
23-1/2 19-5/8
......... _ APPLICATION)
........ 2.
_ COMBUSTION-AIR INTAKE IS REQUIRED-_
_ (NON-DIRECT VENT/I-PIPE
APPLICATION,)
ANGLE
IRON OR
(A) ROD LOCATION
USING DIMPLE LOCATORS
(SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION
(B) ALTERNATE ROD LOCATION
& WASHER (4)
REQD PER ROD
(B) ALTERNATE SUPPORT
NOTES: 1. A 1 In. (25mm) clearance minimum between
top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
3. For non-direct vent/I-pipe application, bottom side combustion-air entry cannot be
used when furnace is installed with hangers as shown.
3/16-1N. (21mm) MAX
LOCATION FROM BACK
3/8-1N. (10mm) ROD
ALTE RNATE SUPPORT LOCATION 4-IN. (102mm) MIN
-IN. (203mm) MAX
A93304
Fig. 26 - Crawlspace Horizontal Application for Direct Vent / 2-Pipe Installation (Sizes 040 through 140) and for Non-Direct Vent
/ 1-Pipe Installation (Sizes 040 through 120 Only)
23
Page 24
RETURN AIR CONNECTIONS
FIRE HAZARD Failure to follow this warning could result in fire, personal
iniury or death. Never connect return-air ducts to the back of the furnace. Return-air duct connections on furnace side(s) pernfitted in
upflow applications only.
CUT HAZARD Failure to follow this caution may result in personal injury.
Use care when cutting support rods in filters to protect against fying pieces and sharp rod ends. Wear safety glasses, gloves,
and appropriate protective clothing.
g
Upflow Furnaces The return-air duct nmst be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace casing. Bypass hunfidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any portion of return-air duct to back of furnace casing.
Downflow and Horizontal Furnaces The return-air duct must be connected to return-air opening
provided. DO NOT cut into casing sides or back to attach any portion of return-air duct. Bypass hunfidifier connections should be made at ductwork or coil casing sides exterior to furnace.
Step 5 -- Filter Arrangement
FIRE, CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Never operate unit without a filter or with filter access door removed.
The air filter arrangement will vary due to application, furnace orientation, and filter type. The filter may be installed in an external Filter/Media cabinet (if provided) or the furnace blower
compartment. Factory supplied washable filters are shipped in the blower compartment.
If a factory-supplied external Filter/Media cabinet is provided, instructions for its application, assembly, and installation are packaged with the cabinet. The Filter/Media cabinet can be used
with the factory-supplied washable filter or a factory-specified high-efficiency disposable filter (see cabinet instructions). If
installing the filter in the furnace blower compartment, deternfine location for filter and relocate filter retaining wire, if necessary. See
Table 4 to deternfine correct filter size for desired filter location. Table 4 indicates filter size, location, and quantity shipped with this
furnace. See Fig. 2 for location and size of bottom and side return-air openings.
[]NIT MAY NOT OPERATE
Failure to follow this caution may result in internfittent unit operation or performance satisfaction.
For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of I side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
NOTE: Side return-air openings can ONLY be used in UPFLOW configurations. Install filter(s) as shown in Fig. 27.
For bottom return-air applications, filter may need to be cut to fit some furnace widths. Install filter as shown in Fig. 28.
Table 4 - Filter Information
AIR FILTER LOCATED iN BLOWER COMPARTMENT
Furnace
Casing
Width
In. (ram)
17-1/2
(445)
2!
(533)
24-1/2 (1or2) 18X25 (1) 24 X 25 X 3/4
(622) (406 X 635 X 19) (609 X 635 X 19)
* Factory-provided with the furnace. Filters may be field modified by cut-
ting filter material and support rods (3) in filters. Alternate sizes can be
ordered from your distributor or dealer, 1-Upflow only. Alternate sizes and additional filters may be ordered from
your dealer.
Filter Size - in. (ram)
Side Return*1- Bottom Return*
(1)16 X 25 X 3/4 (1)16 X 25 X 3/4 (406 X 635 X 19) (406 X 635 X 19)
(1)16 X 25 X 3/4 (1) 20 X 25 X 3/4 (406 X 635 X 19) (508 X 635 X 19)
X 3/4
Filter Type
Framed
Washable
Washable
Washable
24
Page 25
WASHABLE
FILTER
FILTER RETAINER
A93045
Fig. 27 - Filter Installed for Side Inlet
171/2-1N.(444mm) WIDE CASINGS ONLY: CASINGS ONLY: SUPPORT RODS (3)
INSTALL FIELD-SUPPLIED EXTEND 1/4" (6ram) ON FILTER FILLER STRIP EACH SIDE OF FILTER AND
UNDER FILTER. REST ON CASING FLANGE
\
SUPPORT
Fig. 28 - Bottom Filter Arrangement
NOTE: Remove and discard bottom closure panel when bottom
inlet is used.
21-IN. (533mm) WIDE
_HABLE
FILTER
FILTER RETAINER
A00290
Step 6 -- Bottom Closure Panel
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. This panel MUST be in place when
side return air is used. To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front filler panel. (See Fig. 29.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
Step 7 -- Gas Piping
Gas piping nmst be installed in accordance with national and local
codes. Refer to NFGC NFPA54/ANSI Z2223.1-2006 in the U.S.
Canadian installations must be made in accordance with CAN/CSA-BI49A-05 and all authorities having jurisdiction. Gas
supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 5 for recommended gas pipe
sizing. Risers must be used to connect to furnace and to meter.
Support all gas piping with appropriate straps, hangers, etc. Use a
n_ininmm of 1 hanger every 6 ft. (1.8 M). Joint compound (pipe dope) should be applied sparingly and only to male threads of
joints. Pipe dope must be resistant to propane gas.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in fire, explosion, personal iniury or death.
- Connect gas pipe to furnace using a backup wrench to avoid
damaging gas controls.
- Gas valve shutoff switch MUST be facing forward or tilted
upward.
- Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of
leaks to check all connections.
- Use proper length of pipe to avoid stress on gas control
manifold.
- If a flexible connector is required or allowed by authority
having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a naininmm of 2 in. (51 ram) outside
furnace casing.
-Protect gas valve from water and debris. Gas valve inlet and/or inlet piping must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.
Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so
straight-through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below
level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 30.)
An accessible manual shutoff valve MUST be installed external to furnace casing and within 6 ft. (1.8 M) of furnace. A l/8-in. (3
ram) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection
to furnace and downstream of manual shutoff valve.
Gas line grommet (factory-supplied loose parts bag) should be
used when installing gas piping. Gas line entry hole filler plug should be installed in unused gas line entry hole. (See Fig. 31.)
NOTE: The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT
exceed n_axinmm 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 59.)
25
Page 26
g
Table 5 - Maximum Capacity of Pipe*
NOMINAL
IRON
PIPE SIZE
IN. (MM)
1/2(13)
3/4 (19)
1(25)
1-1/4 (32)
1-1/2(38)
* Cubic ft. of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less and a pressure drop of 0.5-in wc (based on a 0.60 specific gravity gas). Ref: Table 9.2 NFGC.
Piping should be pressure and leak tested in accordance with NFGC in the United States or NSCNGPIC in Canada, local, and
national plumbing and gas codes before the furnace has been connected. If pressure exceeds 0.5 psig (14-in. wc), gas supply
pipe must be disconnected from furnace and capped before pressure test.
If test )ressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on gas valve before test. It is recommended that ground joint union be loosened before pressure
testing. After all connections have been made, purge lines and check for leakage at furnace prior to placing it into service.
The gas supply pressure shall be within the maximum (13.6-in. wc) and and nfininmm (4.5-in. wc) inlet supply pressures marked
on the rating plate with the furnace burners ON at HI-HEAT and OFF.
INTERNAL LENGTH OF PIPE - FT. (M)
DIA. 10 20 30 40 50
IN. (MM) (3.0) (6.0) (9.1) (12.1) (15.2)
0.622
(158)
0.824 (21) 360 250 200 170 151
1.049 (27) 680 465 375 320 285
1.380 (35) 1400 950 770 660 580
1.610 (41) 2100 1460 1180 990 900
175 120 97 82 73
SUPPLY
MANUAL _/ II SHUTOFF ._. _
VALVE
SEDIMENT / TRAP !
Fig. 30 - Typical Gas Pipe Arrangement
UNION -J
A93324
Step 8 -- Electrical Connections
See Fig. 32 for field wiring diagram showing typical field l15-v and 24-v wiring. Check all factory and field electrical connections
for tightness.
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal iniury
or death. Blower access door switch opens 115-v power to furnace
control. No component operation can occur. Do not bypass or close switch with panel removed.
BOTTOM CLOSURE PANEL
Fig. 29 - Removing Bottom Closure Panel
[]NIT MAY NOT OPERATE
Failure to follow this caution may result in internfittent unit operation.
Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire connected to gas valve and burner box
screw.
A93047
115-V WIRING Before proceeding with electrical connections,
make certain that voltage, frequency, and phase correspond to that specified on furnace rating plate. Also, check to be sure that service provided
26
Page 27
_ OMBUSTION
-AIRPIPE
IGAS
COMBUSTION-AIR PIPE GROMMET
UNUSED 1-3/4 -IN. (44 mm) DIAMETER GAS
CONN. HOLE
_VENT PIPE
GAS LINE GROMMET
VENT PIPE GROMMET
NOTE: PIPE GROMMETS AND ENTRY HOLE FILLER
PLUGS ARE INCLUDED IN FACTORY-SUPPLIED LOOSE PARTS BAG
Fig. 31 - Casing Pipe Grommets
[THERMOSTAT
L_J ITERMINALS FIELD-SUPPLIED
I I DISCONNECT
[ I
[[[[__ GAS LINE ENTRY
.... FIELD 24-V WIRING
.... FIELD 115-, 208/280-, 460-V WIRING
-- FACTORY 24-V WIRING FACTORY 115-, 208/230-, 460-V WIRING
HOLE FILLER PLUG
A05057
SINGLE
115-V f
PHASE
115-V AUXILIARY
FIELD-SUPPLIED J-BOX
DISCONNECT
SWITCH
FURNACE
CONTROL
CENTER
Connect Y or Y/Y2 terminal as shown for proper cooling operation. Proper polarity must be maintained for 115-v wiring. Use W2 with 2-stage thermostat when zoning. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
8.
Some thermostats require a "C" terminal connection as shown.
Fig. 32 - Heating and Cooling Application Wiring Diagram
27
208/230- OR
460-V
PHASE
208/230-V
SINGLE
PHASE
A98325
Page 28
Table 6 - Electrical Data
UNIT SIZE
040-14 / 042040 14 61 (9) 15 060-14 / 042060 14 61 (9) 15
080-14 / 042080 14 30 (9) 15 080-20 / 060080 12 61 (9) 20
100-20 / 060100 12 61 (9) 20 120-20 / 060120 12 61 (9) 20
* Permissible limits of voltage range at which unit will operate satisfactorily. 1- Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps. $ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended.
VOLTS-
HERTZ-
PHASE
115-60-1 115-60-1
115-60-1 115-60-1
115-60-1 115-60-1
OPERATING VOLTAGE
RANGE
Maximum*
127 127
127 127
127 127
Minimum*
104 104
104 104
104 104
MAXIMUM
UNIT
AMPS
8.90
8.90
8.90
14.00
14.00
14.00
MINIMUM
WIRE SIZE
MAXIMUM
WIRE LENGTH
FT. (M)_
MAXIMUM FUSE
OR CKT BKR
AMPS**
by power supply is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 6 for equipment electrical
specifications. Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70-2008 and any local codes
ELECTRIC
DISCONNECT
SWITCH
or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or authorities having jurisdiction. Field-supplied wiring shall conform with the limitations of 63°F
(33 ° C) rise. The furnace must be electrically grounded in accordance with local
codes; or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA
Fig. 33 - Disconnect Switch and Furnace
A93033
C22.1, Part I, if an external electrical source is utilized. Use a separate branch electrical circuit containing a properly sized
fuse or circuit breaker for this furnace. See Table 6 for wire size and fuse specifications. A disconnecting means must be located
within sight from and readily accessible to furnace. NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, furnace control status code indicator light will flash rapidly and furnace will NOT operate.
Factory Installed J-Box Location Install power entry hole filler plugs (factory-supplied in loose parts
bag) in unused power entry holes. (See Fig. 34.)
J-Box Relocation
1. Remove 2 screws holding auxiliary J-box. (See Fig. 35.)
2. Rotate J-box 180 ° and attach box to left side, using holes provided.
3. Install power entry hole filler plugs (factory-supplied loose parts bag) in unused power entry holes. (See Fig. 35.)
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 33.)
FIRE OR ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in intermittent unit
operation or performance satisfaction. If manual disconnect switch is to be mounted on furnace,
select a location where a drill or fastener will not contact electrical or gas components.
ELECTRICAL AND FIRE HAZARD Failure to follow this warning could result in electrical shock,
fire or death. The cabinet MUST have an uninterrupted or unbroken ground
according to NEC ANSI/NFPA 70-2008 and Canadian
Electrical Code CSA C22.1 or local codes to minimize personal iniury if an electrical fault should occur. This may
consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
CONTINUOUS FAN (CF) SETUP SWITCHES
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select low-cooling
airflow for two-speed cooling units. This setup feature allows
continuous fan airflow or low-cooling airflow to be adjusted. To set desired continuous fan airflow or low-cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig. 37.)
3. Determine desired continuous fan airflow or low-cooling airflow.
4. Use Fig. 47 or wiring schematic to determine proper setup position of CF switches. (See Fig. 36.)
5. Replace main furnace door and blower access panel.
28
Page 29
POWER ENTRY HOLE FILLER PLUG (FACTORY- SUPPLIED LOOSE PARTS BAG)
UNUSED 7/SqN. (22 DIAMETER POWER
ENTRY HOLES
INSTALLED LOCATION
f ACTORY
2. Humidifier (HUM) Connect an accessory 24 VAC, 0.5 amp maximum
humidifier (if used) to the 1/4-in. (6 mm) male quick-connect HUM terminal and COM-24V screw terminal on the control board thermostat strip. The HUM
terminal is energized when blower is energized in heating. (See Fig. 37.)
A05113
Fig. 34 - Factory Installed J-Box Location
SETUP SWITCHES (SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the
appropriate requirement.
1. Remove main furnace door and blower access panel.
2. Locate setup switches on furnace control. (See Fig. 37.)
3. See Table 13 for setup switch description.
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SWI-3 (Low HEAT Rise Adjust) should be in ON position. This compensates
for the increased temperature in return air resulting from bypass. NOTE: If modulating dampers are used, blower motor
automatically compensates for modulating dampers. If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
24-V Wirin_
Make field 24-v thermostat connections at 24-v terminal block on furnace control. Y wire from thermostat MUST be connected to
Y/Y2 terminal on control, as shown in Fig. 32, for proper cooling operation. The 24-v terminal block is marked for easy connection
of field wiring. (See Fig. 37.) The 24-v circuit contains a 3-amp, automotive-type fuse located on furnace control. (See Fig. 370
Any electrical shorts of 24-v wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is
required, use only a fuse of identical size (3 amp) and type. The furnace control will flash status code 24 when fuse needs
replacement. NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. (30 M). For wire lengths over 100 ft. (30 M),
use AWG No. 16 wire. NOTE: For additional thermostat connection diagrams, reference
Fig. 51-58.
ACCESSORIES
1.
Electronic Air Cleaner (EAC) The furnace control EAC terminals are energized with 115v
(1.0-amp maximum) during blower operation. Connect an accessory Electronic Air Cleaner (if used) using
l/4-in. (6 mm) female quick connect terminals to the two male 1/4-in. (6 mm) quick-connect terminals on the control
board marked EAC-I and EAC-2. The terminals are rated for II5VAC, 1.0 amps maximum and are energized during
blower motor operation. (See Fig. 37.)
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat '_ , Zone Controller or
similar device. See Thermidistat'_, Zone Controller, thermostat, or controller manufacturer's instructions for proper
connection.
Step 9 -- Removal of Existing Furnaces from Common Vent Systems
When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent
the remaining attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the
furnace and vent, leakage of condensate and combustion products, spillage of combustion products into the living space, etc.
Step 10 -- Combustion Air and Vent Pipe Systems GENERAL
For additional venting information, contact www.Carrier.com. Vent system or vent connectors may need to be resized. For any
other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as
determined using appropriate table found in the NFGC NFPA54/ANSI Z223.1-2006 or CAN/CSA-BI49.1-05.
The 58MVB can be vented as either a direct vent or as a non-direct vent application. A direct vent system shall be installed in
accordance with the direct vent (2-pipe) procedures in the
following Combustion Air and Vent Pipe Systems section. For non-direct vent (I-pipe) applications, refer to the non-direct vent (l-pipe) procedures in the same section.
Common venting prohibited.
DIRECT VENT/2-PIPE SYSTEM (ALL SIZES)
In a direct-vent (2-pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. A factory accessory vent
termination kit MUST be used in a direct vent (2-pipe) system.
NON-DIRECT VENT/I-PIPE SYSTEM (SIZES I)40 THROUGH 121) ONLY)
In a non-direct vent (1-pipe) system, all air for combustion is taken from the area adjacent to furnace, and all flue products are discharged to outdoor atmosphere. A factory-supplied perforated
disk assembly (in loose parts bag) MUST be used in combustion
air pipe elbow.
29
Page 30
ALTERNATE
FIELD
LOCATION
I l : I
J
J
POWER ENTRY HOLE -----¢p_@¢_"_IU.- FILLER PLUG (FACTORY-
SUPPLIED LOOSE PARTS BAG)
/
UNUSED 7/8-1N. (22 mm) DIAMETER POWER ENTRY HOLES
Fig. 35 - Relocating J-Box
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1-2006/NFPA 54-2006 or the CSA B149.1-05, Natural
Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe
condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with
the National Fuel Gas Code, ANSI Z223.1- 2006/NFPA 54-2006 and/or CSA B149.1-05, Natural Gas and Propane
Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous
conditions of use.
iNSTALLED LOCATION
FACTORY
POWER ENTRY HOLE
iiiiii_0 _ --FILLER PLUG (FACTORY-
SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. (22 mm) DIAMETER POWER ENTRY HOLES
A05058
MATERIALS
Combustion-air and vent pipe, fittings, primers, and solvents must
conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards. See Table 7 for approved materials for use in the U.S.A.
FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in fire, property
damage, personal iniury or death. Solvent cements are combustible. Keep away from heat,
sparks, and open flame. Use only in well-ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
In Canada, construct all combustion-air and vent pipes for this unit of CSA or ULC listed schedule-40 PVC, PVC-DWV or ABSDWV pipe and pipe cement. SDR pipe is NOT approved in
Canada.
In direct vent (2-pipe) systems, combustion air and vent pipes must terminate together in same atmospheric pressure zone, either
through roof or sidewall (roof termination preferred), using
accessory termination kit. See Table 8 for required clearances.
In non-direct vent (I-pipe) system, vent pipe termination must be installed with adequate clearances to building openings and equipment to comply with national and local codes. See Table 9 for
required clearances.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in property damage, personal iniury, or death.
All combustion-air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig.
43 for direct vent (2-pipe) system and Fig. 44 for non-direct vent (l-pipe) system.
30
Page 31
Table 7 - Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials
ASTM SPECiFICATiON
(MARKED ON
MATERIAL)
D1527 D1785 D2235 D2241 D2466
D2468 D2564 D2661 D2665
F438 F441
F442 F493
F628
F656 F891
MATERIAL PiPE FITTINGS
ABS Pipe --
PVC Pipe --
For ABS -- --
PVC Pipe -- PVC -- Fittings
ABS -- Fittings
For PVC -- --
ABS Pipe Fittings
PVC Pipe Fittings CPVC -- Fittings CPVC Pipe -- CPVC Pipe --
For CPVC -- --
ABS Pipe
For PVC
PVC Pipe
An abandoned masonry chinmey may be used as a raceway for properly insulated and supported combustion-air (when
applicable) and vent pipes. Each furnace must have its own set of combustion-air and vent pipes and be terminated individually, as
shown in Fig. 43 for Direct Vent (2-Pipe) system and Fig. 44 for Non-Direct Vent (l-Pipe) system.
A furnace shall not be connected to a chinmey flue serving a separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use the abandoned chinmey as a raceway providing it is permitted by
local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer's installation instructions. Care must
be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.
SOLVENT CEMENT AND
PRIMERS
DESCRIPTION
Schedule--40 Schedule--40
Solvent Cement
For ABS
SDR--21 & SDR--26
Schedule--40 Schedule--40
Solvent Cement
For PVC
DWV at Schedule--40 IPS sizes
DWV
Schedule--40 Schedule--40
SDR
Solvent Cement
For CPVC
Cellular Core DWV at Schedule-40
IPS sizes
Primer
For PVC
Cellular Core Schedule-40 & DWV
UNIT CORROSION HAZARD
Excessive exposure to contaminated combustion air may result in safety and performance related problems.
Combustion air nmst not be taken from inside structure because inside air is frequently contaminated by halogens,
which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches,
cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion-air inlet as far
as possible from swimming pool and swimming pool pump house, pipe.
UNIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit
operation. When vent pipe is exposed to temperatures below freezing,
such as when it passes through an unheated space or when a chinmey is used as a raceway, pipe nmst be insulated as shown in Table 10 with Armaflex-type insulation.
Furnace combustion air and vent pipe connections are sized for 2-in. (51 ram) pipe. Any pipe size change should be made outside
furnace casing in vertical pipe. The transition has to be made as close to the furnace as reasonably possible. See Fig. 40.
COMBUSTION AIR PIPE
General
Furnace combustion-air connection must be attached as shown in Fig. 38. Combustion-air intake housing plug may need to be
relocated in some applications. For Non-Direct Vent (I-Pipe) system, combustion-air must
terminate outside of furnace casing with 1 elbow. Orient elbow so that its opening faces down for upflow or downflow applications.
Orient elbow so that its opening faces sideways (left or right) for horizontal left or horizontal right applications (See Fig. 38.) Maintain a 3-in minimum clearance between the opening of the
combustion-air inlet pipe and any object.
NOTE: All pipe joints nmst have cemented attachment of combustion-air inlet pipe to inlet housing connection, since it may
be necessary to remove pipe for servicing. Assembly of Combustion Air Pipe (Non-Direct
Vent/l-Pipe System ONLY)
1. Permanently install perforated disk assembly (factory sup- plied in loose parts bag) in combustion-air elbow using RTV or by cementing, as shown in Fig. 39. For 120,000
Btuh size units only: separate the 2 halves of perforated disk assembly and use only the shouldered disk half.
2. Determine the length of straight portion of combustion-air inlet pipe from Fig. 39.
3. Cut field-supplied 2-in. (51 ram) diameter PVC pipe to length as determined per Fig. 39.
4. Permanently attach elbow/perforated disk assembly to straight portion of pipe using RTV or by cementing as
shown in Fig. 39.
Assembly of Combustion Air Pipe (Direct Vent-2-Pipe
System ONLY)
1. Using Table 11, individually determine the smallest
combustion air and vent pipe diameters permitted for each pipe. Pick the larger of these two pipe diameters and use this
for both combustion-air and vent pipes.
NOTE: Do not count elbows or pipe sections in terminations or within furnace (All elbows shown in Fig. 43 are not to be counted).
31
Page 32
C _ce _oa perm_ closed _r_
/
/
/,
/
/
2_24_=2
_ = _,00_ B_uh(30 kW), 36 _ 50,000 _uh (_5_v_, 12 _r_ (_)for a_r_ > (91 c_) _ _es > 100,_ _t_ (30 kW) 5o_oe__tuh (_5_w)
J _r_n_e _o n_-me_ar_lcal air s_pi'y _nlet to l_J_idit_ or 12 inches (30 cm) for applieances >10,000 Btuh(3 kW)
the _,_t _nl_ I0 _t ap_ and <_ 100,000 Btuh(30kW), 36 inches (91cm) for
appliances > 100,000 Btuh(30kW)
9 inch_ (23 _) _, app_ > 10._ 8tuh (3kW) and
50i000 Btuh (i5k_V), 12 tr_ (_s(30_)_or _
> 50,000 _h (_SkW)
A08600
Table 8 - Direct Vent Termination Clearance
32
Page 33
/
/
//
/
25-24-65-2
[]VENTTERMINAL \\ _ AIR SUPPLY INLET
Item Clearance Descriptions Canadian Installation (1) U.S. Installation (2)
A Clearance above grade, veranda, porch, deck, balcony, or 12 inches (30cm) # 12 inches (30 cm)
anticipated snow level
B Clearance to a window or door that may be opened 6 inches (15 cm) for appliances <_ 10,000 Btuh (3 kW) 4 feet(l.2 m) below or to the side of the opening. 1 foot(30 cm
C Clearance to a permanently closed window
D Vertical clearance to a ventilated soffit located above the
terminal within a horizontal distance of 2"(61cm) from the centerline of the terminal
E Clearance to an unventilated soffit
F Clearance to an outside corner
G Clearance to an inside corner
H Clearance to each side of the centerline extended above 3 feet (91 cm) within 15 feet(4.5 m) above the meter/regulator 3 feet (91 cm) _iithin 15 feet (4.5 m) above the meter/regulator
electrical meter or gas service regulator assembly assembly assembly
I Clearance to service regulator vent outlet 3 feet (91 cm)
J Clearance to non-mechanical air supply inlet to building or 6 inches (15 cm) for appliances -< 10,000 Btuh (3 kW) 4 feet(t .2 m) below or to the side of opening: 1 foot (30 cm)
the combustion air inlet to any other appliance 12 inches ( 30 cm) for appliances > 10,000 Btuh (3 kW0) above opening.
K Clearance to a mechanical air supply inlet 6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3 m horizontally)
L Clearance under a veranda, porch, deck, or balcony 12 inches(30 cm) +
M
Clearance to each side of the centerline extended above or below vent terminal of the furnace to a dryer or water heater
vent, or other appliance's direct vent intake or exhaust.
N Clearance to the vent terminal of a dryer vent, water heater
vent, or other appliances direct vent intake or exhaust.
O Clearance from a plumbing vent stack
p Clearance above paved sidewalk or paved 7 feet (2.13m)**
driveway located on public property
(1.) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code (2.) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
# 18" (46 cm) above roof surface + Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.t, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the Manufacturer's installation instructions.
** A vent shall not terminate above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Notes:
1. The vent for this appliance shall not terminate a. Over public walkways; or
b. Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard or property damage; or c. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other c onditions which may cause recirculation of the combustiob products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
3 Avoid venting under a deck or large overhang. Recirculation could occur and cause performance or system problems.
12 inches ( 30 cm) for appliances > 10,000 Btuh (3 kW0) above the opening. and -< 100,000 Btuh (30 kW), 36 inches (9t cm) for
appliances > 100,000 Btuh (30 kW)
and -< 100,000 Btuh (30 kW) 36 inches (91 cm) for appliances > t00,000 Btuh (30 kW)
AREA WHERE TERMINAL IS NOT PERMITED
7 feet (2.13m)
A08601
Table 9 - Other than Direct Vent Termination Clearance
33
Page 34
II
I
u
I i
Fig. 36 - Wiring Diagram
34
A07902
Page 35
MODEL PLUG CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
24-V THERMOSTAT
TERMINALS
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
USER INTERFACE CONTINUOUS FAN SW4 SETUP
OR ADVANCED (CF) AIRFLOW OAT SWITCHES
BETUPBW,TCHEBCONNECTOR
\p= /OA,
•_ _4.11/ d
/
HU==M__------'---
ACRDJ
m_ COMM
FUSE 3-AMP
!i0- o
SEC-2 SEC-1
HUMIDIFIER
TERMINAL(24-VAC
O.BAMPMAX.
ACRDJ -AIR
CONDITIONING
RELAY DISABLE
JUMPER
CONNECTOR
(FACTORY
ONLY)
g
TRANSFORMER 24-VAC
CONNECTIONS
11S-VAC (L2) NEUTRAL
CONNECTIONS
PL1 - LOW VOLTAGE MAIN
HARNESS CONNECTOR
SOFTWARE PART DATE
VERSION NUMBER CODE
NUMBER
Fig. 37 - Control Center
@OWNS ;i@
3(.)_,IBIIIYIIO 8
A_
aORI O_TA£ IF t GH/_,£OE
_I Isertlqll@dl Io_ [)i141 Ve_ 8Or,16#F @I'_)I_ t# Otd_l/_S k3
ORe_ I'_ faces s _ewa_
1¸¸_ _n_ake _
H©_ ZOt'_l_A_ ,R;$ "r D SC: ARO
_R
V_
Fig. 38 - Combustion-Air and Vent Pipe Connections
EAC-1 TERMINAL
(115 WAC 1.0 AMP MAX.)
EXAMPLE:
A07898
EAC-1
PL2
VS HSI HI LO_,_
i
\ \
11SWAC (L1) LINE
VOLTAGE CONNECTIONS
[]NIT MAY NOT OPERATE Failure to follow this caution may result in incomplete
combustion, flame disturbance, or flame sense lockout. When installing combustion air and vent system of short pipe
length, the smallest allowable pipe diameter must be used.
NOTE: A 2-in. (51 ram) diameter pipe must be used within furnace casing. Make all pipe diameter transitions outside furnace
casing per Fig. 40.
2. Unless noted in Table 11, insert perforated disk assembly (factory-supplied in loose parts bag) in intake housing
where combustion air pipe will be connected. If half disk set
is required, install only shouldered disk half.
Attachment of Combustion Air Pipe
1. Determine location of combustion air intake pipe connection to combustion air intake housing as shown in
Fig. 38 for application.
2. Reposition combustion air intake housing plug fitting in appropriate unused intake housing connection.
3. Install combustion-air pipe grommet (factory-supplied in loose parts bag) into selected furnace casing combustion-air
pipe hole.
PL2 - HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A07422
35
Page 36
Table 10 - Maximum Allowable Exposed Vent Pipe Length (Ft / M) with Insulation in
Winter Design Temperature Ambient*
WINTER DESIGN
UNIT SIZE
TEMPERATURE
F(C)
20°F (-6.7 °)
040
060
080
100
120
Pipe length (ft./m) specified for maximum pipe lengths located in unconditioned
pipe length as specified in Table 11.
1qnsulation thickness based on R value of 3.5 per in. (25 mm)
0OF (-17.8 °)
-2OOF (-28.9 o) 2O°F (-6.7 °)
0OF (-17.8 °)
-2OOF (-28.9 o) 2O°F (-6.7 °) 0OF (-17.8 °)
-2OOF (-28.9 o) 2O°F (-6.7 °) 0OF (-17.8 °)
-2OOF (-28.9 o) 2O°F (-6.7 °)
0OF (-17.8 °)
-2OOF (-28.9 o)
MAXIMUM PiPE
DIAMETER
IN. (ram)
2 (51) 2 (51)
2 (51) 2 (51)
2 (51) 2 (51) 2 (51) 2 (51)
2 (51) 2-1/2 (64) 2-1/2 (64)
2-1/2 (64)
3 (76)
3 (76)
3 (76)
INSULATION THICKNESS - IN. (ram)l
o (o) a/8" (1o)
21 (6) 37(11) 10 (3) 22 (7)
5 (2) 14 (4)
30 (9) 55 (17)
16 (5) 33 (10)
9 (3) 23 (7)
37 (11 ) 65 (20)
20 (6) 39 (12) 11 (3) 27 (8)
41 (13) 70 (21)
21 (6) 42 (13)
1/2" (13) 3/4" (19)
42 (13) 50 (15)
25 (8) 30 (9) 17 (5) 21 (6)
61 (19) 70 (21) 38 (12) 46 (14)
26 (8) 33 (10) 70 (21) 70 (21) 45 (14) 55 (17)
31 (9) 39 (12) 70 (21) 70 (21)
48 (15) 59 (18)
11 (3) 28 (8) 33 (10) 41
49 (15) 70 (21) 70 (21) 70
26 (8) 51 (16) 58 (18) 70 15 (5) 35 (11 ) 40 (12) 50
spaces. Pipes located in unconditioned space cannot
1" (25)
57 (17)
35 (11)
25 (8)
70 (21)
53 (16)
38 (12) 70 (21)
63 (19) 45 (14)
70 (21) 68 (21)
(13)
(21) (21)
(15)
exceed total allowable
49 (15)
70 (21) 70 (21)
59 (18)
FIELD-SUPPLIED 2-IN. (51 mm) DIA._ FIELD-SUPPLIED PVC90ELBOW J 2-IN. (51 mm) DIA.
J PVC PIPE
--E 1
i -_ A _
COMBUSTION-AIR DISC LOCATION-NON DIRECT VENT/I-PIPE SYSTEM (FACTORY-SUPPLIED IN LOOSE PARTS BAG)
A05122
CASING WIDTH A
8-1/2 +/- 1/2
17-1/2 (445) (216 +/- 13)
10-1/2 +/- 1/2
21 (533) (267 +/- 13)
12+/- 1/2
24-1/2 (622) (605 +/- 16)
Fig. 39 - Combustion-Air Inlet Pipe Assembly - In, (ram)
4. Insert assembled combustion air inlet pipe into intake housing as shown in Fig. 38.
5. Drill a 1/8-in. hole in 2-in, combustion air pipe using the hole in intake housing as a guide.
6. Install a field-supplied No. 6 or No. 8 sheet metal screw into combustion air pipe.
7. Install casing hole filler cap (factory-supplied in loose parts bag) in unused combustion air pipe casing hole.
NOTE: Do not attach combustion air intake pipe permanently to combustion air intake housing since it may be necessary to remove pipe for service of igniter or flame sensor.
Attachment of Combustion Air Intake Housing Plug
Fittin_ The combustion-air intake plug fitting must be installed in unused
combustion air intake housing. This fitting must be attached by
using RTV sealant, or by drilling a 1/8-in. (3 ram) hole in fitting, using hole in intake housing as a guide. Install a field-supplied No.
6 or No. 8 sheet metal screw.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for use when moisture is tbund in combustion air intake pipe and combustion box. If use of this drain connection is desired, drill out
fitting's tap plug with 3/16-in. drill and connect a field-supplied 3/8-in. tube. This tube should be routed to open condensate drain
for furnace and A/C (if used), and should be trapped, as shown in Fig. 41.
NOTE: (Direct Vent/2-Pipe System ONLY). Moisture in combustion air intake may be a result of improper termination.
Ensure combustion air pipe termination is similar to those as shown in Fig. 43 so that it will not be susceptible to area where
light snow or others sources of moisture could be pulled in.
VENT PIPE
General
Furnace vent connection must be attached as shown in Fig. 38.
CARBON MONOXIDE POISONING AND PROPERTY
DAMAGE HAZARD
Failure to follow this warning could result in property damage, personal iniury, or death.
Vent pipes must be airtight. NOTE: A 2-in. (51 ram) diameter pipe must be used within the furnace casing. Make all pipe
diameter transitions outside furnace casing per Fig. 40.
NOTE: A 2-in. (51 ram) diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace
casing per Fig. 40.
36
Page 37
ALTITUDE UNIT SIZE
F_ (M) (BTUH)
0 to 2000 80,000
(0to610)
ALTITUDE
2001 to 3000 80,000
(610 to 914)
ALTITUDE
3001 to 4000 80,000
(914 to 1219)
ALTITUDE
4001to 50005
(1219 to 1524) 80,000
ALTITUDE
5001to 60005
(1524 to 1829) 80,000
*See notes on next page.
40,000
60,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
60,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
60,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
60,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
60,000
100,000
120,000
Table11- MaximumAllowablePipe Length (Ft. / M)
VARIABLE SPEED VENT SIZING TABLE
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (76) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (76) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (76) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (76) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (76) Concentric
Direct & Non-
Direct Pipe
Dia.
In. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64) 2 - 1/2 (64)
3 (76)
3 (76)l-
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)
3 (76)l-
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)
3 (76)l-
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)1-
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)1-
1 2
5O(15) 45(14)
70 (21) 70 (21) 5O (15) 45 (14)
70 (21) 70 (21)
30 (9) 25 (8)
70 (21) 70 (21) 45 (14) 40 (13)
70 (21) 70 (21)
10 (3) NA 35 (11) 30 (9) 70 (21) 70 (21)
1 2
45 (14) 40 (13) 70 (21) 70 (21)
45 (14) 40 (13) 70 (21) 70 (21)
26 (8) 21 (6) 70 (21) 70 (21) 40 (12) 35 (11)
70 (21) 70 (21)
31 (9) 26 (8) 63 (19) 62 (19)
1 2
42 (13) 37 (11) 70 (21) 70 (21)
42 (13) 37 (11) 70 (21) 70 (21)
25 (8) 20 (6) 70 (21) 70 (21) 38 (12) 33 (10)
70 (21) 70 (21)
29 (9) 24 (7) 59 (18) 59 (18)
1 2
40 (12) 35 (11) 70 (21) 70 (21)
40 (12) 35 (11) 70 (21) 70 (21)
23 (7) 18 (6) 70 (21) 70 (21)
36(11) 31 (9) 70 (21) 70 (21)
56 (17) 55 (17)
1 2
37 (11) 32 (10) 70 (21) 70 (21)
37 (11) 32 (10) 70 (21) 70 (21)
22 (7) 17 (5) 70 (21) 70 (21)
33 (10) 28 (9) 70 (21) 70 (21)
53 (16) 52 (16)
NUMBER OF 90 ° ELBOWS
3 4
40(13) 35 (11) 70 (21) 70 (21)
40(13) 35 (11) 70 (21) 70 (21)
20 (6) 15 (5)
70 (21) 70 (21) 35 (11) 30 (9)
70 (21) 70 (21)
NA NA
15 (5) NA
70 (21) 70 (21)
NUMBER OF 90 ° ELBOWS
3 4
35 (11) 30 (9) 70 (21) 70 (21)
35 (11) 30 (9) 70 (21) 70 (21)
16 (5) 11 (3)
70 (21) 70 (21)
30 (9) 25 (8)
70 (21) 70 (21)
12 (4) NA
62 (19) 61 (19)
NUMBER OF 90 ° ELBOWS
3 4
32 (10) 27 (8) 70 (21) 70 (21)
32 (10) 27 (8) 70 (21) 70 (21)
15 (5) 10 (3)
70 (21) 70 (21)
28 (9) 23 (7)
70 (21) 70 (21)
10 (3) NA
58 (18) 57 (17)
NUMBER OF 90 ° ELBOWS
3 4
30 (9) 25 (8)
70 (21) 70 (21)
30 (9) 25 (8)
70 (21) 70 (21)
13 (4) 8 (2)
70 (21) 70 (21)
26 (8) 21 (6)
70 (21) 70 (21)
54 (17) 53 (16)
NUMBER OF 90 ° ELBOWS
3 4
27 (8) 22 (7)
70 (21) 70 (21)
27 (8) 22 (7)
70 (21) 70 (21)
12 (4) 7 (2)
70 (21) 70 (21)
23 (7) 18 (6)
70 (21) 70 (21) 50 (15) 49 (15)
30 (9)
70 (21)
30 (9)
70 (21)
10 (3)
70 (21)
25 (8)
70 (21)
NA NA
70 (21)
5
25 (8)
70 (21)
25 (8)
70 (21)
6 (2)
70 (21)
20 (6)
70 (21)
NA
61 (19)
5
22 (7)
70 (21)
22 (7)
70 (21)
5 (2)
70 (21)
18 (6)
70 (21)
NA
57 (17)
5
20 (6)
70 (21)
20 (6)
70 (21)
NA
70 (21)
16 (5)
70 (21) 52 (16)
5
17 (5)
70 (21)
17 (5)
70 (21)
NA
68 (21)
13 (4)
70 (21) 48 (15)
25 (8)
70 (21)
25 (8)
70 (21)
5 (2)
70 (21)
20 (6)
70 (21)
NA NA
70 (21)
6
20 (6)
70 (21)
20 (6)
70 (21)
NA
70 (21)
15 (5)
70 (21)
NA
61 (19)
6
17 (5)
70 (21)
17 (5)
70 (21)
NA
70 (21)
13 (4)
70 (21)
NA
56 (17)
6
15 (10)
70 (21)
15 (10)
70 (21)
NA
68 (21)
11 (3)
70 (21) 52 (16)
6
12 (4)
70 (21)
12 (4)
70 (21)
NA
63 (19)
8(2)
70 (21)
47 (14)
37
Page 38
B
NA-Not Allowed; pressure switch will not make. NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion -air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter for both pipes.
3. Assume two 45 ° elbows equal one 90 ° elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft. (1.5 M) for all applications.
Table 11 -- Maximum Allowable Pipe Length (Ft. / M) (Continued)
Variable Speed Vent Sizing Table
ALTITUDE
FT. (M)
6001 to 70001:
(1829 to 2134)
ALTITUDE
7001 to 80005
(2134 to 2438)
ALTITUDE
8001 to 9000
Ft.$
(2438 to 2743)
ALTITUDE
9001 to 10000 1:
(2743 to 3048)
Disk usage-Unles. _ Wide radius elbow.
UNIT SIZE
(BTUH)
40,000
80,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
80,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
80,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
40,000
80,000
80,000
100,000
120,000
otherwise statec
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (78) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (78) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (78) Concentric
Termination
Type
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 2-In. (51) Concentric
2 Pipe or 3-In. (78) Concentric
I, use perforated disk
Direct & Non- NUMBER OF 90 °
Direct Pipe
Dia. in. (ram)* 1 2 3
1-1/2 (38) 35 (11) 30 (9) 25 (8)
2 (51) 70 (21) 70 (21) 88 (21)
1-1/2 (38) 35 (11) 30 (9) 25 (8)
2 (51) 70 (21) 70 (21) 88 (21)
1-1/2 (38) 20 (8) 15 (5) 10 (3)
2 (51) 70 (21) 70 (21) 88 (21) 2 (51) 31 (9) 26 (8) 21 (8)
2-1/2 (64) 70 (21) 70 (21) 88 (21)
3 (78)1- 49 (15) 48 (15) 47 (14)
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)1-
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)1-
Direct & Non-
Direct Pipe
Dia. in. (ram)*
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51)
1-1/2 (38)
2 (51) 2 (51)
2 - 1/2 (64)
3 (76)1-
ssembly (factory-
1
32 (10) 86 (20)
32 (10) 86 (20)
18 (8) 86 (20)
29 (9) 86 (20)
48 (14)
1
30 (9) 82 (19)
30 (9) 82 (19)
17 (5) 82 (19)
27 (8) 82 (19)
43 (13)
1
27 (8) 57 (17)
27 (8) 57 (17)
15 (5) 57 (17)
24 (7) 57 (17)
39 (12)
supplied in k
85 (20)
85 (20)
85 (20)
85 (20)
44 (13)
80 (18)
80 (18)
80 (18)
80 (18)
41 (13)
55 (17)
55 (17)
55 (17)
55 (17)
37 (11)
ose parts ba!
NUMBER OF 90 ° ELBOWS
2
27 (8)
22 (7) 17 (5)
83 (19) 82 (19)
27 (8)
22 (7) 17 (5)
83 (19) 82 (19)
13 (4)
8 (2) NA
83 (19) 82 (19)
24 (7)
19 (8) 14 (4)
83 (19) 82 (19) 43 (13) 41 (13)
NUMBER OF 90 ° ELBOWS
2
25 (8)
20 (8) 15 (5)
58 (18) 56 (17)
25 (8)
20 (8) 15 (5)
58 (18) 56 (17)
12 (3)
7 (2) NA
58 (18) 56 (17)
22 (7)
17 (5) 12 (4)
58 (18) 56 (17) 39(12) 37(11)
NUMBER OF 90 ° ELBOWS
2
22 (7)
17 (5) 12 (4)
53 (18) 51 (18)
22 (7)
17 (5) 12 (4)
53 (18) 51 (18)
10 (3)
5 (2) NA
53 (18) 51 (18)
19 (8)
14 (4) 9 (3)
53 (16) 51 (16) 35 (11) 33 (10)
I).
3 4
3 4
3 4
Vent sizing for Canadian installations over 4500 ft. (1372 M) above sea level are subject to acceptance by the local authorities having jurisdiction.
ELBOWS
4
20 (8)
87 (20)
20 (8)
87 (20)
5 (2)
87 (20)
18 (5)
87 (20)
45 (14)
5
15 (5)
86 (20)
15 (5)
86 (20)
NA
82 (19)
11 (3)
86 (20) 44 (13)
5
12 (4)
80 (18)
12 (4)
80 (18)
NA
57 (17)
9 (3)
eo (18)
40 (12)
5
10 (3)
55 (17)
10 (3)
55 (17)
NA
51 (16)
7 (2)
55 (17) 35 (11)
5
7 (2)
49 (15)
7 (2)
49 (15)
NA
48 (14)
NA
49 (15) 31 (10)
8
10 (3)
84 (20)
10 (3)
84 (20)
NA
57 (17)
8 (2)
84 (20) 43 (13)
8
7 (2)
59 (18)
7 (2)
59 (18)
NA
52 (16)
NA
59 (18) 38 (12)
8
5 (2)
53 (18)
5 (2)
53 (18)
NA
48 (14)
NA
53 (16) 34 (10)
6
NA
47 (14)
NA
47 (14)
NA
41 (13)
NA
47 (14)
29 (9)
38
Page 39
NOTIN HORIZONTAL SECTION
FURNACE
[]NIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage.
TRANSITION IN
VERTICAL SECTION
A93034
Fig. 40 - Combustion-Air and Vent Pipe Diameter Transition
Location and Elbow Configuration
COMBUSTION AIR
3/8" (10 mm) ID TUBE --
KE HOUSING BURNER
TRA ?
AOO ST'ON
TO OPEN --
DRAIN
A93035
Fig. 41 - Intake Housing Plug Fitting Drain
The n_ininmm vent pipe length for these furnaces is 5 ft. (1.5 M) Short pipe lengths (5-8 ft. / 1.5 - 8 M) may discharge condensate droplets. These condensate droplets may be undesirable. A 12-in.
(304.8 ram) n_ininmm offset pipe section is recommended to reduce excessive condensate droplets from exiting vent pipe outlet.
(See Fig. 42.) Attachment of Vent Pipe Determine combustion-air and vent pipe diameter.
1. Using Table 11, individually determine the smallest combustion-air and vent pipe diameters permitted for eahc pipe. Pick the larger of these two pipe diameters and use
this diameter for both combustion-air and vent pipes.
NOTE: (Direct Vent/2-Pipe ONLY) vent pipe system has the same diameter and same length as combustion air pipe as mentioned in section "Assembly of Combustion Air Pipe (Direct Vent/2-Pipe system ONLY)."
NOTE: Do not count elbows or pipe sections in terminations or within furnace (all elbows shown in Fig. 43 and Fig. 44 are not be counted).
2. Determine location of vent pipe connection to inducer housing as shown in Fig. 38 for application.
3. Reposition elastomeric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing
connection. Tighten clamp.
4. Install combustion-air pipe grommet (factory-supplied in loose parts bag) into selected furnace casing vent pipe hole.
(See Fig. 31.)
5. Be certain that mating surfaces of inducer housing connection elastomeric (rubber) coupling, and 2-in. (51 mm) diameter vent pipe are clean and dry. Assemble the
elastomeric (rubber) vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2-in. (51 ram)
diameter vent pipe through the elastomeric (rubber) coupling and fully into inducer housing connection until it
touches a stop inside the inducer housing outlet. Tighten the screws on both clamps to 15-in-lb. of torque, pipe to
inducer housing. Tighten the clamp screws to 15 in.-lb, of torque.
NOTE: Starting at furnace, slope vent pipe a minimum of 1/4-in. (6 ram) per linear ft. with no sags between hangers.
[]NIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Vent pipe must be installed and fully seated against inducer housing internal stop. Clamp must be tightened to prevent any
condensate leakage.
6. Install casing hole filler cap (factory-supplied in loose parts bag) in unused vent pipe casing hole.
Installation Guidelines for Combustion Air Pipe and
Vent Pipe
It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint.
1. Attach combustion air pipe and vent pipe per instructions in
sections "Combustion Air Pipe" and "Vent Pipe."
2. Working from furnace to outside, cut pipe to required length(s).
3. Deburr inside and outside of pipe.
4. Chamfer outside edge of pipe for better distribution of primer and cement.
5. Clean and dry all surfaces to be joined.
6. Check dry fit of pipe and mark insertion depth on pipe.
7. After pipes have been cut and preassembled, apply generous layer of cement primer to pipe fitting socket and end of pipe
to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a
light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made
joint.
10. Handle pipe joints carefully until cement sets.
39
g
Page 40
il
11. Horizontal portions of the venting system shall be supportive to prevent sagging support. Support combustion air piping (if applicable) and vent piping a minimum of
every 5 ft. (1.5 M)(3 ft. (.91 M) for SDR-21 or -26 PVC) using perforated metal hanging strap.
12. Slope combustion air piping (if applicable) and vent piping downward towards furnace a nfininmm of 1/4 in. (6 ram)
per linear ft. with no sags between hangers.
13. Horizontal portions of the venting system shall be installed so as to prevent the accunmlation of condensate.
14. Use appropriate methods to seal openings where combustion air pipe (if applicable) and vent pipe pass
through roof or sidewall.
EXAMPLE An 100-14 size furnace located in Indianapolis, elevation 650
ft. (198 M) above sea level, could be installed as either a direct vent/2-pipe system that requires 3 elbows and 28 ft. (8.5 M) of vent pipe, along with 5 elbows and 34 ft. (10.3 M) of combustion-air pipe OR a non-direct vent/I-pipe system that requires 3 elbows and 28 ft. (8.5 M) vent pipe. For a direct vent/2-pipe system, Table 11 indicates this
application would allow a 2-in. (51 ram) diameter vent pipe, but require a 2-1/2 in. (64 ram) diameter combustion air pipe. According to Table 11, 2-in. (51 ram) diameter pipe is good for 30 ft. (9.1 M) with 3 elbows, but only 20 ft. (6.1 M) with 5 elbows. Therefore, 2-1/2 in. (64 ram) diameter pipe nmst be
used for both vent and combustion air pipes since larger required diameter must always be used for both pipes.
For a non-direct vent/l-pipe system, Table 11 indicates that this application would allow a 2-in. (51 ram) diameter vent pipe. If same installations were in Albuquerque, elevation 5250 ft. (1600 M) above sea level:
For a direct vent/2-pipe system, Table 11 indicates that 2-1/2 in. (64 ram) diameter vent pipe and combustion-air pipe are
required. For a non-direct vent/l-pipe system, Table 11 indicates that
2-1/2-in. (64 ram) diameter vent pipe is required. If same
applications are to be installed at 5001- to 6000 ft. (1524 -
1829 M) elevation: For a direct vent/2-pipe system, 2-in. (51 ram) pipe is only good for 23 ft. (7.0 M) (with 3 elbows) and 13 ft. (3.9 M) (with 5 elbows). Therefore, 2-1/2 in. (64 ram) diameter
combustion air and vent pipe must be used. For a non-direct vent/l-pipe system, a 2-in. (51 ram)
diameter pipe is only good for 23 ft. (7.0 M) with 3 elbows. A 2-1/2-in. (64 ram) diameter vent pipe must be used.
VENT TERMINATION
General Combustion-air (direct vent/2-pipe system only) and vent pipe
must ternfinate outside structure, either through sidewall or roof. For vent ternfination clearance, refer to Table 8 for Direct Vent/2-Pipe system and Table 9 for Non-direct Vent/I-Pipe
system. For exterior piping arrangements, refer to Fig. 43 for Direct Vent/2-Pipe system and Fig. 44 for Non-Direct/I-Pipe
system. Roof ternfination is preferred since it is less susceptible to damage
or contanfination, and it has less visible vent vapors. Sidewall ternfination require sealing or shielding of building surfaces with a
corrosive resistance material due to corrosive combustion products of vent system.
NOTE: (Direct Vent/2-Pipe system ONLY) A factory accessory ternfination kit MUST be used. See section "Vent Ternfination Kit
(Direct Vent/2-Pipe System Only)" in this instruction. When deternfining appropriate location for ternfination, consider
the following guidelines:
1. Comply with all clearance requirements stated in Table 8 or Table 9 per application.
2. Ternfination or ternfination kit should be positioned where vent vapors will not damage plants/shrubs or air
conditioning equipment.
3. Ternfination or ternfination kit should be positioned so that
it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.
4. Ternfination or ternfination kit should be positioned where it will not be damaged by or subjected to foreign objects such
as stones, balls, etc.
5. Ternfination or ternfination kit should be positioned where vent vapors are not objectionable.
Extended Exposed Sidewall Pipes
Sidewall combustion air pipe termination (direct vent/2-pipe
system only) and vent pipe termination may be extended beyond
area shown in Fig. 43 or in Fig. 44 per @plication in outside ambient by insulating pipe as indicated in Table 10.
1. Determine combustion air pipe diameter (direct vent/2-pipe system only) and vent pipe diameter, as stated above, using
total pipe length and number of elbows.
2. Using winter design temperature (used in load calculations), find @propriate temperature for your @plication and
furnace model.
3. Deternfine required insulation thickness for exposed pipe length(s).
NOTE: Pipe length (ft. / M) specified for naaxinmm pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 11.
Vent Termination Kit (Direct Vent/2-Pipe System
NOTE: Always refer to the instructions in termination kit for the latest version.
Combustion air and vent pipes MUST terminate outside structure.
A factory accessory termination kit must be installed as shown in Table 12. There are four options of vent/combustion air
ternfination kits available as shown in Table 12. NOTE: Combustion air pipe must have the same diameter as vent
pipe.
Concentric Vent/Combustion Air Termination Kit (Direct Vent/2-Pipe System Only)
Determine an @propriate location for termination kit using the guidelines provided in section "Vent Termination: General" in this
instruction.
1. Cut one 4-in. (102 ram) diameter hole for 2-in. (51 ram) kit, or one 5-in. (125 ram) diameter hole for 3-in. (76 ram)
kit.
2. Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through hole.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
Roof terminations-Locate assembly through roof to @propriate height as shown in Fig. 43.
Sidewall terminations-Locate assembly through sidewall with
rain shield positioned no more than 1-in. (25 ram) from wall as shown in Fig. 43.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
5. Check required dimensions as shown in Fig. 43.
40
Page 41
I
VENTP'PE---".II VENTP'PE--'-.,I]
!! !!i"--C° UST'°N-A'RP'PE!! !!,--'-C°MBUST'°N-A'RP'PE
HORIZONTALTO ROOF HORIZONTAL TO SIDEWALL
COMBUSTION-AIR PIPE "_
COMBUSTION-AIRPIPE --,_ f VENT PIPE
I]J
:_-----_ 12" MIN
(304.8mm)
VERTICALTO ROOF VERTICAL TO SIDEWALL
NOTE: A 12-in. (304.8mm) minimum offset pipe section is recommended
with short (5 to 8 ft / 1.5 to 2,5M) vent systems. This recommendation is to reduce excessive condensate droplets.
Fig. 42 - Short Vent (5 to 8 Ft. or 1.5M - 2.4M) System
[i 12,_MIN _ /
(304.1mm)
VENT PIPE
A96230
Two-Pipe Termination Kit (Direct Vent/2-Pipe System
Determine an appropriate location for termination kit using the guidelines provided in section "Vent Termination: General" in this
instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.
2. Loosely install elbow in bracket and place assembly on combustion-air pipe.
Roof terminations-Loosely install pipe coupling on prop- erly cut vent pipe. Coupling must be positioned so bracket
will mount as shown in Fig. 43. For applications using combustion-air pipe option, indic-
ated by dashed lines in Fig. 43, install 90 ° street elbow into 90 ° elbow, making a U-fitting. A 180 ° U-fitting may be
used. Sidewall terminations-Install bracket as shown in Fig. 43.
For applications using vent pipe option indicated by dashed lines in Fig. 43, rotate vent elbow 90 ° from position shown
in Fig. 43.
3. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
4. Check required dimensions as shown in Fig. 43.
Multiventing and Vent Terminations
When 2 or more 58MVB Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or
breach vent 58MVB furnaces.
(Direct Vent/2-Pipe System ONLY)-When 2 or more 58MVB furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 43, but next vent termination must be at
least 36 in. (914 ram) away from first 2 terminations. It is important that vent terminations be made as shown in Fig. 43 to
avoid recirculation of flue gases.
Step 11 -- Condensate Drain General
Condensate trap is shipped installed in the blower shelf and factory
connected for UPFLOW applications. Condensate trap nmst be RELOCATED for use in DOWNFLOW and HORIZONTAL
applications. Condensate trap MUST be used for all applications.
An external trap is not required when connecting the field drain to this condensate trap.
The field drain connection (condensate trap or drain tube coupling) is sized for 1/2-in. (13 ram) CPVC, l/2-in. PVC (13 ram), or
5/8-in. (16 ram) ID tube connection. Drain pipe and fittings must conform to ANSI standards and
ASTM D1785, D2466, or D2846. CPVC or PVC cement nmst conform to ASTM D2564 or F493. Primer nmst conform to
ASTM F656. In Canada, use CSA or ULC certified schedule 40
CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is
approved for condensing furnace applications. To avoid
condensate spillage, select a pump with an overflow switch.
41
Page 42
g
Rool Te rmlnat[on (Preferred)
Con c_mt ric Vont and Combustion Air
_4_rtica[ separation belween combustion
air and vent
Maintain 12 in (305ram)rain clear an_ above
\\\\\\
Note: "A" denotes 0 to < 2 in. (51ram)
Between the first 2 vents
Third vent must be > 36 in. away (914mm)
i
Abandoned masonry used asraceway
(percode)
snowlevelorgrade wh4cheveris greater(typ}
Roo f Tot ruination (preferred} ...........................
Fig. 43 - Combustion Air and Vent Pipe Termination for Direct Vent (2-pipe) System
12 in(3O5mm)mm4mumfrom overhangorroof
A05090
Roof Termination (Preferred)
Maintainminimum12ciearancein(3OSmm) ........... ":]above highest anticipated
snow level maximum of ' ,
24 _n (610ram) above roof ........ J"-....
"',L ............
Abandoned masonry used as raceway (per code)
12 in rain (305 mm)fi
6 in 152mm) minimum clearance
betweenwa andendo vent pipe
10 _n (254mm) maximum p_pe le_h
w_th Straight P_pe (preferred)
Maintain 12 in (3O5mm) m[n[mu m clearance
above Mghest anticipated s_qow level or grade
Side wall termination
\\\\\\\\ w_th 2 elbows (preferred)
iMchever _s greater
Fig. 44 - Vent Pipe Termination for Ventilated Combustion Air System
S_dewa[I Termination
Maintain 12 in 3O5mm m[n[mu m c earance above Mghest anticipated
snow [evel or grade wMchever _s gleater
A05091
42
Page 43
Table 12 - Vent Termination Kit for Direct Vent / 2-Pipe System
DIRECT VENT (2 PIPE) TERMINATION KIT TERMINATION SYSTEM
2-in. (51 mm) Concentric Vent Kit Single Penetration of Wall or Roof 1, 1-1/2, 2, or 2-1/2
3-in. (76 mm) Concentric Vent Kit Single Penetration of Wall or Roof 2-1/2, 3 or 4 (64, 76, or 102)
2-in. (51 mm)Termination Bracket Kit 2Pipe Termination System 1, 1-1/2 or 2 (25, 38, or 51)
3-in. (76 mm) Termination Bracket Kit 2Pipe Termination System 2-1/2, 3 or 4 (64, 76, or 102)
DIAMETER OF COMBUSTION AIR AND
VENT PIPES - IN. (MM)
(25, 38, 51, or 64)
Furnace condensate is mildly acidic, typically in the pH range of
3.2 to 4.5. Due to corrosive nature of this condensate, a condensate pH neutralizing filter may be desired. Check with local authorities
to determine if a pH neutralizer is required.
APPLICATION
The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external,
fieldsupplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) nmst be terminated into
an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment's drain.
See Fig. 45 for example of possible field drain attachment using l/2-in. (13 ram) CPVC or PVC tee for vent and A/C or humidifier
drain connection. Outdoor draining of the furnace is permissible if allowed by local
codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.
PERSONAL INJURY HAZARD Failure to follow this warning could result in property damage
and personal iniury or death.
Caution should be taken to prevent draining causing slippery conditions Excessive condensate draining may cause saturated soil conditions which may result in damage to plants,
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status indicator light flashes rapidly
and furnace does not operate.
2. Thermostat wire connections at terminals R, W/WI, G, and Y/Y2 must be made at 24-v terminal block on furnace
control.
3. Natural gas service pressure nmst not exceed 0.5 psig
(14-in. wc), but nmst be no less than 0.16 psig (4.5-in. wc).
4. Blower access panel nmst be in place to complete l15-v
electrical circuit to furnace.
f \
PIPE FOR
A/C OR
HUMIDIFIER
OPEN STANDy
DRAIN
TEE Uh_
CONDENSATE DRAIN PROTECTION
Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze
protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft. at 120v and 40°F (4°C)
self-regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer's
recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back. (See Fig. 46.)
3. Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig.
46.)
4. Wrap field drain pipe with remaining heat tape, approximately 1 wrap per ft.
5. When using field-supplied heat tape, follow heat tape manufacturer's instructions for all other installation
guidelines.
START-UP, ADJUSTMENTS AND SAFETY
CHECK
Step 1 -- General
1. Furnace must have a 115-v power supply properly connected and grounded.
A94054
Fig. 45 - Example of Field Drain Attachment
CONDENSATE TRAP-_
WiRE TiE
HEAT TAPE_.
(8WRAPS MINIMUM)_
A93036
Fig. 46 - Condensate Trap Heat Tape
43
Page 44
AIR CONDITIONING
TONS (12,000 BTU/HR)
1-1/2
2
2-1/2
3
3-1/2
4 5 6
X Indicates an allowable selection. * Airflow shown in parentheses is airflow unit that the
AIRFLOW* (CFM) 040,060 & 080-14
525 (600) X 700 (800) X X X
875 (1000) X X X
1050 (1200) X X X 1225 (1400) X X X 1400 (1600) X X 1750 (2000) X X
2100 (2100) X
MODEL 080-20 & 100 MODEL 120 MODEL
unit will deliver when setup switch SW1-5 is ON (selects 400 CFM/ton)
AIRCONDITIONING (A/C) ORCONTINUOUS-FAN (CF)
BASED ON 350 CFMMON (SETUP SWITCH SWl-5 OFF)
I
MODEL m'_ r-_
SIZE
g I SETUP SWITCH SW2 & SW3 POSITIONS
o, 060, 3.5q
040,060,3.5T080 5T080, 100 DEF. 7002 875 1050 1225 1400 1750_ 1750
I
120 DEF. 700 8752 1050 1225 1400 17501 2100
BASEDON 400 CFM/TON (SETUPSWITCHSW1-5 ON)
MODEL
AIRFLOW SELECTIONCHART
0 _ _ _ _ _ _
m_c, m_co mr--m c_
DEF. 5252 700 875 1050, I 1225 1225 1225
SETUP SWITCH SW2 & SW3 POSITIONS
S,ZE o Z,
m_c, m_co m_c, m_c_ ml:_mco ml:_mo: _l:_mco ml:_mo.
040,060,3.5T080 DEF. 6002 800 1000 1200,I 1400 1400 1400
5T080, 100 DEF. 8002 1000 1200 1400 1600 2000_ 2000
120 DEF. 800 10002 1200 1400 1600 2000_ 2100
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHESARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS AREALSO SHOWN ON FURNACE WIRING DIAGRAM
Fig. 47 - A/C or CF Airflow Selection Chart Based on 350
and 400 CFM/Ton
[]NIT MAY NOT OPERATE Failure to follow this caution may result in internfittent unit
operation or performance satisfaction. These furnaces are equipped with a manual reset linfit switch
in burner box. This switch opens and shuts off power to the gas valve if an overheat condition (flame rollout) occurs in
burner enclosure. Correct inadequate combustion-air supply or improper venting condition before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
Step 2 -- Sdeet Setup Switch Positions AIR CONDITIONING (A/C) SETUP SWITCHES
The air conditioning setup switches are used to match furnace airflow to cooling unit used.
To set the desired cooling airflow:
1. Remove main furnace door and blower access panel.
A07899
A07907
Fig. 48 - Example of Setup Switch in Off Position
2. Locate A/C setup switches on furnace control. (See Fig. 37.)
3. Deternfine air conditioning tonnage used,
4. Use Fig. 47 or wiring schematic to deternfine proper setup position of A/C switches. (See Fig. 36 and 48.)
NOTE: Excessive airflow caused by improper A/C switch setup may cause condensate blowoff in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE: EAC-1 ternfinal is energized whenever blower operates. HUM ternfinal is only energized when blower is energized in heating.
CONTINUOUS FAN (CF) SETUP SWITCHES
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select low-cooling
airflow for two-speed cooling units. This setup feature allows
continuous fan airflow or low-cooling airflow to be adjusted, To set desired continuous fan airflow or low-cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig. 37.)
3. Deternfine desired continuous fan airflow or low-cooling airflow,
4. Use Fig. 47 or wiring schematic to deternfine proper setup position of CF switches. (See Fig. 36 and 48.)
5. Replace main furnace door and blower access panel.
44
Page 45
Table13- Furnace Setup Switch Description
SETUP SWITCH NORMAL
NO. POSiTiON
SW1- 1 StatusCode Recovery OFF
SW1-2 Adaptive Heat Mode OFF
SW1-3 Low Heat RiseAdjust OFF pensatesfor increased return airtemperature caused with bypass
SW1-4 Comfort/EfficiencyAdjustment ON airflow 8 percent for maximumcomfort. On 040 unitwill decrease
SW1-5 CFM perton adjust OFF TurnON for 400 CFM per ton. Turn OFFfor 350 CFMper ton.
SW1-6 Component Self-Test OFF sistancewhen Rthermostat lead is disconnected. Turn OFFwhen
SW1-7 BlowerOFF delay ONor OFF SeeTable 14. SW1-8 BlowerOFF delay ONor OFF
SWITCH NAME DESCRIPTION OF USE
TurnON to retrieveup to 7 stored status codesfor troubleshooting assistancewhen R thermostat lead is disconnected.
Allows 2-stage operation with a single stage thermostat. Turn ON when using 2 stagethermostat to allow Low Heat operation when
Rto W/W1 closes and High Heatoperation when R to W/W1 and
W2 close. TurnON to increase LowHeat airflow by 18 percent.This com-
humidifier.
TurnON to decrease Low Heatairflow by 7 percent and High Heat
Low- HeatAirflow 11 percent and High- HeatAirflow 10percent.
TurnON to initiate Component Self-Test fortroubleshooting as- 1
Self-Test is completed. Control blower Off Delaytime. Usedin conjunction with SW1-8.
Control blower Off Delaytime. Usedin conjunction with SW1-7. SeeTable 14.
SETUP SWITCHES (SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the
appropriate requirement.
1. Remove main furnace door and blower access panel.
2. Locate setup switches on furnace control. (See Fig. 37.)
3. See Table 13 for setup switch description. (See Fig. 36 and
48.)
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SWl-3 (Low HEAT Rise Adjust) should be in ON position. This compensates
for the increased temperature in return air resulting from bypass. NOTE: If modulating dampers are used, blower motor
automatically compensates for modulating dampers.
FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in personal iniury,
death or property damage. Never purge a gas line into a combustion chamber. Never test
for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to
check all connections.
Step 5 -- Sequence of Operation
Step 3 -- Prime Condensate Trap With Water
[]NIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
[]NIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit
operation or performance satisfaction. Condensate trap must be PRIMED or proper draining may not
occur. The condensate trap has 2 internal chambers which can ONLY be primed by pouring water into the inducer drain side
of condensate trap.
1. Remove upper inducer housing drain connection cap. (See Fig. 49.)
2. Connect field-supplied 1/2-in. (13 mm) ID tube to upper inducer housing drain connection.
3. Insert field-supplied flmnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 50.)
5. Remove flmnel and tube from inducer housing and replace drain connection cap and clamp.
Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
[]sing schematic diagram, follow sequence of operation through different modes. (See Fig. 36.) Read and follow wiring diagram
carefully. NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/Wl-and-W2), the control will start a 90-second blower-only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90-second period, after which the LED will be ON continuous, as long as no faults are detected. After the
90-second period, the furnace will respond to the thermostat
normally. The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot-surface igniter HSI, and gas valve GV.
Step 4 -- Purge Gas Lines
If not previously done, purge the lines after all connections have been made and check for leaks.
U
45
Page 46
©
Agg118
Fig. 49 - Inducer Housing Drain Tube
SINGLE-STAGE THERMOSTAT AND TWO- STAGE HEATING (ADAPTIVE MODE)
See Fig. 32 or 58 for thermostat connections
NOTE: Low-heat-only switch, SWI-2, selects either the low-heat- only operation mode when ON, (see item 2. below) or
adaptive heating mode when OFF, in response to a call for heat.
(See Fig. 37.) When the W2 thermostat terminal is energized, it will always cause high-heat operation when the R to W circuit is
closed, regardless of the setting of the low-heat only switch.
DESIRED HEATING
MODE
BLOWER OFF
DELAY (SEe)
9O
120 15O 18O
This furnace can operate as a two-stage furnace with a single-stage thermostat because furnace control CPU includes a programmed
adaptive sequence of controlled operation, which selects low-heat or high-heat operation. This selection is based upon the stored history of the length of previous gas heating periods of the
single-stage thermostat. The furnace will start up in either low- or high-heat. If the furnace
starts up in low-heat, the furnace control CPU determines the low-heat on time (from 0 to 16 minutes) which is permitted before
switching to high-heat.
SETUP SWITCH (SW1-7 AND SW1-8)
POSITION
SW1-7 SW1-8
OFF OFF
ON OFF
OFF ON
ON ON
Aggllg
Fig. 50 - Filling Condensate Trap
If power is interrupted, the stored history is erased. When this happens, the control CPU will initially select low-heat for up to 16 minutes and then switch to high-heat, as long as the thermostat
continues to call for heat. Subsequent selection is based on stored history of thermostat cycle times.
The wall thermostat "calls for heat", closing the R to W circuit. The furnace control CPU performs a self-check, verifies the low-heat
and high-heat pressure switch contacts LPS and HPS are open.
1. Inducer Prepurge Period - The furnace control CPU turns
on inducer motor IDM and slowly increases the inducer motor speed. When the low-heat pressure switch LPS
closes, inducer motor RPM is noted by the furnace control CPU, and a 25-sec. prepurge period begins. The RPM is
used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor during the low-heat prepurge
period and low-heat mode. NOTE: The heat cycle can start in either high-or low-heat. If a high-heat cycle is initiated, the furnace control CPU will
deenergize the high-heat pressure switch relay HPSR to close the NC contact and continues to increase the inducer motor speed after the low-heat pressure switch LPS closes. When the high-heat pressure switch closes, inducer motor RPM is noted by the furnace control CPU before the 25-sec prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in high-heat mode.
2. Igniter Warm-Up - At end of the prepurge period, the Hot Surface Igniter HSI is energized for a 17-sec igniter
warm-up period.
3. Trial-For-Ignition Sequence - When the igniter warm-up period is completed, the main gas valve relay contacts GVR
close to energize the gas valve GV, the gas valve opens. The gas valve GV permits gas flow to the burners where it is
46
Page 47
ignited by the Hot Surface Igniter HSI. Five seconds after the GVR closes, a 2-second flame period begins. The HSI
igniter will remain energized until the flame is sensed or until the 2-second flame proving period begins.
If the furnace control CPU selects high-heat operation, the high-heat gas valve solenoid GV-HI is also energized.
4. Flame-Proving - When burner flame is proved at the
flameproving sensor electrode FSE, the furnace control CPU begins the blower-ON delay period and continues to
hold the gas valve GV-M open. If the burner flame is not proved within two seconds, the control CPU will close the
gas valve GV-M, and the furnace control CPU will repeat the ignition sequence for up to three more Trials-For-Igni-
tion before going to Ignition-Lockout. Lockout will be re- set automatically after three hours, by momentarily inter-
rupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU
(not at W/W1, G, R, etc.). If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode and operate the inducer motor IDM
on high speed until flame is no longer proved.
5. Inducer Speed Change - If the cycle starts in low-heat,
the furnace control CPU reduces the inducer speed slightly after flame sense. If cycle starts in high-heat, the furnace
control CPU increases the inducer speed 15 seconds after flame sense. The reduction in speed in low-heat is to optim-
ize combustion for maximum efficiency.
6. Blower-On delay - If the burner flame is proven, the blower-ON delay for low-heat and high-heat are as fol-
lows: Low-heat-60 seconds after the gas valve GV-M is opened,
the BLWM is turned ON at low-heat airflow. High-heat-35 seconds after gas valve GV-M is opened,
the BLWM is turned ON at high-heat airflow. Simultan- eously, the humidifier terminal HUM and electronic air
cleaner terminal EAC-1 are energized and remain energized throughout the heating cycle.
7. Switching From Low- To High- Heat - If the furnace control CPU switches from low-heat to high-heat, the fur-
nace control CPU will de-energize the the high-heat pres- sure switch relay HPSR to close the NC contact and slowly
increase the inducer motor speed until the high-heat pres- sure switch HPS closes. When the high-heat pressure
switch HPS closes, the high-heat gas valve solenoid GV- HI is energized and the inducer motor RPM is noted by the
furnace control CPU. The RPM is used to evaluate vent sys- tem resistance. This evaluation is then used to determine the
required RPM necessary to operate the inducer motor in high-heat mode. The blower motor BLWM will transition
to high-heat airflow five seconds after the furnace control CPU switches from low-heat to high-heat.
8. Switching From High- To Low- Heat - The furnace con- trol CPU will not switch from high-heat to low-heat while
the thermostat R-to-W circuit is closed when using a single-stage thermostat.
9. Blower-Off delay - When the thermostat is satisfied, the R to W circuit is opened, de-energizing the gas valve GV-M,
stopping gas flow to the burners, and de-energizing the hu- midifier terminal HUM. The inducer motor IDM will re-
main energized for a 15-second post-purge period. The blower motor BLWM and air cleaner terminal EAC-1 will
remain energized at low-heat airflow or transition to low- heat airflow for 90, 120, 150, or 180 seconds (depending on
selection at blower-OFF delay switches). The furnace con- trol CPU is factory-set for a 120-second blower-OFF delay.
TWO-STAGE THERMOSTAT AND TWO-
STAGE HEATING
See Fig. 57 for thermostat connections.
NOTE: In this mode, the low-heat only switch SWl-2 must be
ON to select the low-heat only operation mode in response to closing the thermostat R-to-W1 circuit. Closing the thermostat R-to-Wl-and-W2 circuits always causes high-heat operation, regardless of the setting of the low-heat-only switch.
The wall thermostat "calls for heat", closing the R to Wl circuit for low-heat or closing the R to Wl-and-W2 circuits for high-heat.
The furnace control performs a self-check and verifies the low-heat and high-heat pressure switch contacts LPS and HPS are
open. The start-up and shutdown flmctions and delays described in Item
1. above apply to 2-stage heating mode as well, except for
switching from low- to high-heat and vice versa.
1. Switching From Low- To High- Heat-If the thermostat R to Wl circuit is closed and the R toW2 circuit closes, the
furnace control CPU will de-energize the high-heat pressure switch relay HPSR to close the NC contact and
slowly increase the inducer motor speed until the high-heat pressure switch HPS closes. When the high-heat pressure
switch closes, the highheat gas valve solenoid GV-HI is energized and the inducer motor RPM is noted by the
furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine
the required RPM necessary to operate the inducer motor in high-heat mode. The blower motor BLWM will transition
to high-heat airflow five seconds after the R to W2 circuit closes.
2. Switching From High- To Low- Heat- If the thermostat
R to W2 circuit opens, and the R to WI circuit remains closed, the furnace control CPU will energize the high-heat
pressure switch relay HPSR to open the NC contact and slowly decrease the inducer motor speed to the required
low-heat RPM. When the high-heat pressure switch HPS opens, the high-heat gas valve solenoid GV-HI is
de-energized. When the inducer motor IDM reduces pressure sufficiently, the high-heat pressure switch HPS
will open. The gas valve solenoid GV-M will remain
energized as long as the low-heat pressure switch LPS remains closed. The blower motor BLWM will transition to
low-heat airflow five seconds after the R to W2 circuit
opens.
COOLING MODE
The thermostat "calls for cooling".
1. Single-Speed Cooling (See Fig. 32 and Fig. 51 for thermostat connections.)
The thermostat closes R-to-G-and-Y circuits. The R-to-Y circuit starts the outdoor unit, and R-to-G-and-Y/Y2
circuits start the furnace blower motor BLWM on cooling airflow. Cooling airflow is based on the A/C selection shown in Fig. 47.
The electronic air cleaner terminal EAC-1 is energized with 115-v when blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y
circuits are opened. The outdoor unit will stop, and furnace
blower motor BLWM will continue operating at cooling
airflow for an additional 90 sec. Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 37.)
2. Single-Stage Thermostat and Two-Speed Cooling
(Adaptive Mode) (See Fig. 58 for thermostat connections.)
This furnace can operate a two-speed cooling unit with a single-stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
47
Page 48
operation,whichselectslow-coolingor high-cooling operation.Thisselectionisbaseduponthestoredhistoryof
thelengthofpreviouscoolingperiodofthesingle-stage
thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a
call for cooling. (See Fig. 37.) When in place the furnace control CPU can turn on the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling. The furnace control CPU can start up the cooling unit in either
low- or high-cooling. If starting up in low-cooling, the furnace control CPU determines the low-cooling on-time (from 0 to 20
minutes) which is permitted before switching to high-cooling. If the power is interrupted, the stored history is erased and the
furnace control CPU will select low-cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat "calls for cooling", closing the R to G-and-Y circuits. The R to YI circuit starts the outdoor unit on low-cooling
speed, and the R to G-and-Yl circuits starts the furnace blower motor BLWM at low-cooling airflow which is the true on-board
CF selection as shown in Fig. 47. If the furnace control CPU switches from low-cooling to
high-cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R to Yl-and-Y2 circuits switch the outdoor unit to
high-cooling speed, and the R to G-and-Yl-and-Y/Y2 circuits transition the furnace blower motor BLWM to highcooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
47. NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the furnace blower motor BLWM transitions to run at high-cooling
airflow. The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R to G-and-Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized
for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 37.)
3. Two-Stage Thermostat and Two-Speed Cooling
(See Fig. 57 for thermostat connections)
NOTE: The air conditioning relay disable jumper ACRDJ must be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 37.) The thermostat closes the R to G and-Yl circuits for low cooling
or closes the R to G and-Yl-and-Y2 circuits for high-cooling. The R to YI circuit starts the outdoor unit on low-cooling speed,
and the R to G-and-Yl circuit starts the furnace blower motor BLWM on low-cooling airflow which is the true on-board CF
selection as shown in Fig. 47. The R to Yl-and-Y2 circuits start the outdoor unit on high-cooling speed, and the R to G-and-Y/Y2
circuits start the furnace blower motor BLWM at high-cooling airflow. High-cooling airflow is based on the A/C selection shown
in Fig. 47. The electronic air cleaner terminal EAC-I is energized with 115
vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R to G-and-Yl or R to
G-and-Yl-and-Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal
EAC-I will remain energized for an additional 90 seconds. Jumper YI to DHUM to reduce the cooling off-delay to 5 seconds. (See
Fig. 370
THERMIDISTAT MODE
See Fig. 51-54 for Thermidistat connections.
The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal DHUM.
When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input
terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists.
Once 24 vac is detected by the furnace control on the DHUM
input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control
reverts back to non-Thermidistat mode. The cooling operation described in item 3. above applies to
operation with a Thermidistat. The exceptions are listed below:
a. Low cooling-When the R to G-and-Yl circuit is closed
and there is a demand for dehumidification, the furnace
blower motor BLWM will drop the blower airflow to 86%
of low-cooling airflow which is the true on-board CF selection as shown in Fig. 47.
b. High cooling-When the R to G-and Y/Y2 circuit is closed
and there is a demand for dehumidification, the furnace
blower motor BLWM will drop the blower airflow to 86%
of high-cooling airflow. High-cooling airflow is based on the A/C selection shown in Fig. 47.
c. Cooling off-delay-When the "call for cooling" is satisfied
and there is a demand for dehumidification, the cooling
blower-off delay is decreased from 90 seconds to 5
seconds.
SUPER-DEHUMIDIFY MODE
Super-Dehumidify mode can only be entered if the furnace control
is in Thermidistat mode and there is a demand for dehumidification. The cooling operation described in Item 3.
above also applies to operation with a Thermidistat. The exceptions are listed below:
a. Low cooling-When the R to YI circuit is closed, R to
G circuit is open, and there is a demand for
dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65% of low-cooling airflow for a maximum of 10 minutes each cooling cycle or
until the R to G circuit closes or the demand for dehumidification is satisfied. Low-cooling airflow is the true on-board CF selection as shown in Fig. 47.
b. High cooling-When the R to Y/Y2 cicuit is closed, R
to G circuit is open, and there is a demand for dehumidifiation, the furnace blower motor BLWM will
drop the blower to 65% of high-cooling airflow for a maximum of 10 minutes each cooling cycle or until the
R to G circuit closes or the demand for dehumidification is satisfied. High-cooling airflow is based on the A/C
selection shown in Fig. 47.
c. Cooling off-delay-When the "call for cooling" is
satisfied and there is a demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds
to 5 seconds.
CONTINUOUS BLOWER MODE
When the R to G circuit is closed by the thermostat, the blower motor BLWM will operate at continuous-blower airflow.
Continuous blower airflow selection is initially based on the CF
selection shown in Fig. 4% Factory default is shown in Fig. 4% Terminal EAC-I is energized as long as the blower motor BLWM
is energized. During a call for heat, the blower BLWM will transition the blower
motor BLWM to continuous blower airflow, low-heat airflow, or the mid-range airflow, whichever is lowest. The blower motor
OFF and remain OFF for the blower-ON delay (60 seconds in
low-heat and 35 seconds in high-heat) allowing the furnace heat
48
Page 49
exchangersto heat more quickly, then restarts at the end of the
blower-ON delay period at low-heat or high-heat airflow respectively.
The blower motor BLWM will revert to continuous-blower airflow after the heating cycle is completed. In high-heat, the furnace control CPU will drop the blower motor BLWM to
low-heat airflow during the selected blower-OFF delay period before transitioning to continuous-blower airflow.
When the thermostat "calls for high-cooling", the blower motor BLWM will operate at high-cooling airflow. When the thermostat
is satisfied, the blower motor BLWM will operate an additional 90 seconds at high-cooling airflow before transitioning back to
continuous-blower airflow. When the R to G circuit is opened, the blower motor BLWM will
continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
CONTINUOUS BLOWER SPEED SELECTION FROM THERMOSTAT
To select different continuous-blower speeds from the room thermostat, momentarily turn off the FAN switch or pushbutton on
the room thermostat for 1-3 seconds after the blower motor BLWM is operating. The furnace control CPU will shift the
continuous-blower airflow from the factory setting to the next highest CF selection airflow as shown in Fig. 47. Momentarily
turning off the FAN switch again at the thermostat will shift the continuous-blower airflow up one more increment. If you repeat
this procedure enough, you will eventually shift the continuous-blower airflow to the lowest CF selection as shown in
Fig. 47. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power
interruption. This feature is disabled when blower off delay is set for 180 sec.
HEAT PUMP
See Fig. 53-56 for thermostat connections. When installed with a heat pump, the furnace control automatically
changes the timing sequence to avoid long blower off times during demand defrost cycles. Whenever W/W1 is energized along with
Y1 or Y/Y2, the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow, low-heat airflow, or
the mid-range airflow, whichever is the lowest. The blower motor BLWM will remain on until the main burners ignite, then shut OFF
and remain OFF for 25 seconds before coming back on at heating airflow. When the W/W1 input signal disappears, the furnace
control begins a normal inducer post-purge period while changing the blower airflow. If Y/Y2 input is still energized, the furnace
control CPU will transition the blower motor BLWM airflow to cooling airflow. If Y/Y2 input signal disappears and the Y1 input is
still energized, the furnace control CPU will transition the blower motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM will remain on at low-heat airflow for the selected blower-OFF delay
period. At the end of the blower-OFF delay, the blower motor BLWM will shut OFF unless G is still energized, in which case the
blower motor BLWM will operate at continuous blower airflow.
COMPONENT TEST
The furnace features a component test system to help diagnose a system problem in the case of a component failure. To initiate the
component test procedure, ensure that there are no thermostat inputs to the control and all time delays have expired. Turn on setup switch SWl-6 (See Fig. 37.)
NOTE: The component test feature will not operate if the control is receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows:
a. The furnace control CPU turns the inducer motor IDM
ON at medium speed and keeps it ON through step c.
b. After waiting 15 seconds, the furnace control CPU turns
the hot surface igniter ON for 15 seconds, then OFF.
c. The furnace control CPU then turns the blower motor
BLWM ON at mid-range airflow for 15 seconds, then
OFF.
d. After shutting the blower motor BLWM OFF, the
furnace control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is operating.
After the component test is completed, 1 or more status codes (11, 25, 41, or 42) will flash. See Service Label on blower access panel or Service/Status Code Instructions for explanation of status codes.
NOTE: To repeat component test, turn setup switch SWI-6 to
OFF and then back ON.
Step 6 -- Adjustments
SET GAS INPUT RATE
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. (610 M).
In the U.S.A., the input rating for altitudes above 2000 ft. (610 M) must be reduced by 2 percent for each 1000 ft. (305 M) above sea
level. In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft. to 4500 ft. (610 to 1372 M) above sea level.
Adjust manifold pressure to obtain input rate. Furnace input rate must be within +/-2 percent of input rate on
furnace rating plate.
1. Determine natural gas orifice size and manifold pressure for correct input.
a. Obtain average heat value (at installed altitude) from
local gas supplier.
b. Obtain average specific gravity from local gas supplier.
c. Verify furnace model. Table 14 can only be used for
model 58MVB Furnaces.
d. Find installation altitude in Table 14.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (610 to 1372 M), use U.S.A. altitudes of 2001 to 3000 ft. (610 to 914 M) in
Table 14.
e. Find closest natural gas heat value and specific gravity in
Table 14.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low- and high-heat manifold pressure settings for proper operation.
EXAMPLE: 0-2000 ft. altitude (0-610 M) Heating value = 1050 Btu/cu ft. Specific gravity = 0.62
Therefore: Orifice No. 45 Manifold pressure:
3.8-in. wc for high heat
1.6-in. wc for low heat * Furnace is shipped with No. 45 orifices. In this example,
all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
g. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
49
Page 50
THERMIDISTAT TWO-STAGE SINGLE-SPEED FURNACE HEAT PUMP
FURNACE AIR CONDITIONER
THERMIDISTAT TWO-STAGE SINGLE-SPEED
HEAT STAGE 2 IO_._
N/A
HEAT STAGE 1 I___
COOL STAGE 1 __
FAN I_--
24 VAC HOT __
DEHUMIDIFY I_Mt_ _
24 VAC COMM __
HUMIDIFY [_0__ _
N/A [_
%T%OR_-I_q-
CONNECT,ONLl_q-
NOTE 11 __
C_
-i_q
-i_q--
........_--IB
-i_q
-i_q
-i_
I HUM
........ _ HUMIDIFIER(24VAC) t-Z_L---
........ _ OUTDOORsENSOR t--Z_;
See notes 2, 5, 7, 10, and 11
........ I
Fig. 51 - Two-Stage Furnace with Single-Speed
Air Conditioner
THERMIDISTAT TWO-STAGE TWO-SPEED
FURNACE AIR CONDITIONER
RVSCOOLING_
HEATSTAGE3_
(FURNACEHI)
HEATSTAGE2_
(FURNACELO)
HEAT/COOLSTAGEI_
(COMPRESSOR)
FAN
24 VAC HOT
DEHUMIDIFY
24 VAC COMM [_
HUMIDIFY
N/A
I I
NOTE 11
C_
I HUM "'-.
_)x_ HUMIDIFIER _ i
(24 VAC)
z_[ OUTDOOR _
SENSOR
CONNECTIONL_
See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15
A00275
Fig. 53 - Two-Stage Furnace with Single-Speed
Heat Pump (Dual Fuel)
THERMIDISTAT TWO-STAGE TWO-SPEED
FURNACE HEAT PUMP
A00277
HEAT STAGE 2 _-.
COOL STAGE 1 [_.
HEAT STAGE 1 _-.
COOL STAGE 2 __.
FAN [__.
24 VAC HOT __.
DEHUMIDIFY [_.
24 VAC COMM [_-.
HUMIDIFY [_.
N/A _]
Os_oo__-I_
CONNECTION k[_- .
NOTE 11
-I_q
NOTE 12
-I_q
I HUM
........ HUMIDIFIER ___lI
........ _ OUTDOORsENSOR
See notes 2, 5, 8, 10, 11, and 12
Fig. 52 - Two-Stage Furnace with Two-Speed
Air Conditioner
(24 VAC)
RVS COOLING
HEAT/COOL STAGE 1
(COMPRESSOR LO)
HEAT STAGE 3 _.
(FURNACE)
HEAT/COOL STAGE 2 _.
(COMPRESSOR HI)
FAN
24 VAC HOT
DEHUMIDIFY
24 VAC COMM
HUMIDIFY
N/A
i i
OUTDOOR [_" _ OsUTND_)OR ]_/_
................. [_ .......
I HUM ""_ .... ,
{"=°'F'=,24we,
J _Ol
coS SO,¢q...............................
Seenotes l, 2, 3, 4, 6, 8, 9,10,12,13, and15
A00276
Fig. 54 - Two-Stage Furnace with Two-Speed
Heat Pump (Dual Fuel)
A00278
50
Page 51
DUAL FUEL TWO-STAGE SINGLE-SPEED TWO-STAGE TWO-STAGE TWO-SPEED
THERMOSTAT FURNACE HEAT PUMP
THERMOSTAT FURNACE AIR CONDITIONER
RVS COOLING
HEAT STAGE 3
(FURNACE HI)
HEAT STAGE 2
(FURNACE LO)
HEAT/COOL STAGE 1
(COMPRESSOR)
FAN [_
24 VAC HOT [_
24 VAC COMM
N/A
RVS SENSING [_
OONNEOTIONL_
NOTE 11
C_
] HUM
OUTDOOR _
SENSOR
See notes 1, 2, 4, 11, 14,15, and 16
A00279
Fig. 55 - Dual Fuel Thermostat with Two-Stage Furnace and
Single-Speed Heat Pump
DUAL FUEL TWO-STAGE TWO-SPEED
THERMOSTAT FURNACE HEAT PUMP
NOTE 11
I q- I q-
I q-
NOTE 12
I q- I q-
[_-
HUM
See notes 2, 11, and 12
A00281
Fig. 57 - Two-Stage Thermostat with Two-Stage Furnace
and Two-Speed Air Conditioner
SINGLE-STAGE TWO-STAGE TWO-SPEED
THERMOSTAT FURNACE AIR CONDITIONER
RVS COOLING
HEAT/COOL STAGE 1
(COMPRESSOR LO)
HEAT STAGE 3
(FURNACE)
HEAT/COOL STAGE 2
(COMPRESSOR HI)
FAN [_
24 VAC HOT [_
24 VAC COMM [_
N/A [_
RVS SENSING [_
Os_2#oo_/ _
NOTE 12
E2_ E2_
] HUM
OUTDOOR ] z_
SENSOR
IW31
CONNEOT'ON[12_
See notes 1, 2, 3, 4, 12, 13, 14,15, and 17
A00280
Fig. 56 - Dual Fuel Thermostat with Two-Stage Furnace and
Two-Speed Heat Pump
HUM
See note 2
A02348
Fig. 58 - Single-Stage Thermostat with Two-Stage Furnace
and Two-Speed Air Conditioner
51
Page 52
Notes for Fig. 51-58:
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Select the "ZONE" position on the two-speed heat pump control.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Dip switch No.l on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for single-speed compressor operation. This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON position for two-speed compressor operation.
9. Configuration Option No. 10 "Dual Fuel Selection" must be turned ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11. Optional connection. If wire is connected, dip switch SWI-2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control furnace staging.
12. Optional connection. If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.
13. Furnace must control its own high-stage heating operation via furnace control algorithm. This is factory default.
14. The RVS Sensing terminal "L" should not be connected. This is internally used to sense defrost operation.
15. DO NOT SELECT the "FURNACE INTERFACE" or "BALANCE POINT" option on the two-speed heat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.
16. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single-speed compressor operation. This is factory default.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position for two-speed compressor operation.
52
Page 53
ALTITUDE
RANGE
ft (m)
¢;
"0
t-
r-
2001 (611)
"o
C
(3
3000 (914)
t-
t_
Canada
2001 (611)
450011372/
r'-
o
t=
0
C
0
C
o
Table 14 - Orifice Size* and Manifold Pressures for Gas Input Rate
(Tabulated Data Based on 20,000 Btuh High-Heat/13,000 Btuh Low-Heat Per Burner,
Derated 2%/1,000 Ft. (305 M) Above Sea Level)
0
(o)
to
2000 (610)
U.S.A.
to
to
3001 (915)
to
4000
(1219)
4001
(1220)
to
5000
(1524)
5001
(1525)
to
6000
(1829)
6001
(1830)
to
7000
(2133)
AVG. GAS
HEAT VALUE
AT ALTITUDE
IBtu/cu _1
900 925 950
975 1000 1025 1050 1075 1100
800
825
850
875
900
925
950
975 1000
775
800
825
850
875
900
925
950
750
775
800
825
850
875
900
925
725
750
775
800
825
850
875
900
675
700
725
750
775
800
825
850
0.58 0.60 0.62
Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
No. Hi_hlLow No. Hi_hlLow No. Hi_h/Low
43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 44 3.8 / 1.6 43 3.5 / 1.5 43 3.6 / 1.5 44 3.6 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4 44 3.4 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 45 3.8 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 45 3.4 / 1.4 45 3.5 / 1.5 45 3.7 / 1.5 45 3.3 / 1.4 45 3.4 / 1.4 45 3.5 / 1.5 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4 43 3.6 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5 44 3.7 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 45 3.7 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 43 3.7 / 1.6 42 3.2 / 1.3 42 3.3 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5 44 3.2 / 1.3 44 3.3 / 1.4 44 3.4 / 1.4
45 3.7 / 1.5 45 3.8 / 1.6 44 3.2 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6
43 3.7 / 1.6 43 3.8 / 1.6 42 3.2 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6 44 3.7 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 45 3.8 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 42 3.2 / 1.4 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5 44 3.7 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4 44 3.4 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 44 3.4 / 1.5
45 3.7 / 1.6 45 3.8 / 1.6 44 3.2 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 45 3.3 / 1.4 45 3.4 / 1.4 45 3.5 / 1.5
42 3.2 / 1.3 42 3.3 / 1.4 42 3.4 / 1.4 43 3.6 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6 44 3.8 / 1.6 43 3.5 / 1.5 43 3.6 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5 45 3.8 / 1.6 44 3.3 / 1.4 44 3.4 / 1.4 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
42 43 43 44 44 44 44
45
45 42 42 43 43 44 44 44 44
45 42 42 43 43 44 44 44
45 42 43 43 43 44 44 44
45 42 43 43 44 44 44
45
45 42 42 43 43 44 44 44
45
0.64
MnfldPress
Hi_h/Low
3.2/1.3
3.7/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.5/1.5
3.2/1.4
3.7/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.6
3.4/1.4
3.2/1.3
3.7/1.5
3.4/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.5
3.2/1.4
3.7/1.6
3.3/1.4
3.8/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.8/1.6
3.6/1.5
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.6
A08376A
53
Page 54
B
Table 14 -- Orifice Size* and Manifold Pressures for Gas Input Rate
(Tabulated Data Based on 20,000 Btuh High-Heat/13,000 Btuh Low-Heat Per Burner,
Derated 2%/1,000 Ft. (305 M) Above Sea Level) (Cont)
ALTITUDE
RANGE
ft (m)
7001
--_ (2134)
C
O
to
8000
(2438)
8001
" (2439)
O
to
9000
!27431
9001
--_ (2744)
C
O
<." to
10000
!30481
* Orifice numbers shown inBOLD are factory-installed.
AVG. GAS SPECIFIC GRAVITY OF NATURAL GAS
HEAT VALUE 0.58 0.60 0.62
AT ALTITUDE Orifice MnfldPress Orifice MnfldPress Orifice MnfldPress
!Stu/cu ft ! No. Hi_h/Low No. Hi_h/Low No. Hi_h/Low
650 43 3.8 / 1.6 42 3.2 / 1.4 42 3.4 / 1.4 675 43 3.5 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6 700 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 725 44 3.5 / 1.5 44 3.6 / 1.5 44 3.8 / 1.6 750 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 775 45 3.7 / 1.6 44 3.2 / 1.3 44 3.3 / 1.4
800 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 825 45 3.3 / 1.4 45 3.4 / 1.4 45 3.5 / 1.5 625 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4 650 43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 675 44 3.7 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 700 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 725 44 3.2 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 750 45 3.7 / 1.5 45 3.8 / 1.6 44 3.2 / 1.4 775 45 3.4 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 600 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4 625 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6 650 44 3.7 / 1.6 44 3.8 / 1.6 43 3.4 / 1.5 675 44 3.4 / 1.4 44 3.5 / 1.5 44 3.7 / 1.5 700 44 3.2 / 1.3 44 3.3 / 1.4 44 3.4 / 1.4 725 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6
Orifice
No.
42 42 43 43 44 44 44
45 42 42 43 44 44 44
45 42 43 43 44 44 44
0.64
Mnfld Press
Hi,h/Low
3.5/1.5
3.2/1.4
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.4
3.2/1.4
3.6/1.5
3.4/1.5
3.2/1.3
3.6/1.5
3.8/1.6
3.6/1.5
3.3/1.4
3.8/1.6
3.4/1.4
3.8/1.6
3.6/1.5
3.8/1.6
3.5/1.5
3.3/1.4
A08376B
54
Page 55
2. Adjust manifold pressure to obtain input rate. a. Remove burner enclosure front.
NOTE: Manifold pressure MUST always be measured with the burner box cover REMOVED.
b. Remove regulator seal caps that conceal adjustment
screws for low- and high-heat gas valve regulators. (See Fig. 59.)
c. Move setup switch SWI-2 on control center to ON
position. (See Fig. 37.) This keeps furnace locked in low-heat operation.
d. Jumper R and W/WI thermostat connections on control
to start furnace.
e. Turn low-heat adjusting screw (3/32) hex Allen
wrench) counterclockwise (out) to decrease input rate or clockwise (in) to increase input rate.
NOTE: DO NOT set low-heat manifold pressure less than 1.3-in. wc or more than 1.7-in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices to obtain manifold
)ressure in this range.
[]NIT DAMAGE HAZARD Failure to follow this caution may result in reduced furnace
life or property damage. DO NOT bottom out gas valve regulator adjusting screw. This
can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
ON/OFF SWITCH
1/2 NPT INLET
INLET
PRESSURE TAP
/2 NPT OUTLET J
_ -REGULATOR COVER SCREW
....... PLASTIC ADJUST SCREW
i ADJUSTMENT ;
Fig. 59 - Redundant Automatic Gas Valve
A04167
g
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
f. Move setup switch SWI-2 to OFF position after
completing low-heat adjustment.
g. Jumper R and W/W1 and W2 thermostat connections
on furnace control. (See Fig. 37) This keeps furnace locked in high-heat operation.
h. Turn high-heat adjusting screw (3/32 hex Allen
wrench) counterclockwise (out) to decrease input rate or clockwise (in) to increase rate.
NOTE: DO NOT set high-heat manifold pressure less than
3.2-in. wc or more than 3.8-in. wc for natural gas. If manifold
pressure is outside this range, change main burner orifices to obtain manifold pressures in this range.
i. When correct input is obtained, replace caps that
conceal gas valve regulator adjustment screws. Main burner flame should be clear blue, almost transparent. (See Fig. 61.)
j. Remove jumpers R to W/W1 and R to W2.
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter.
A93059
Fig. 60 - Burner Orifice
a. Calculate high-altitude adjustment (if required).
UNITED STATES At altitudes above 2000 ft. (610 M), this furnace has
been approved for a 2 percent derate for each 1000 ft. (305 M) above sea level. See Table 15 for derate
multiplier factor and example.
55
Page 56
BURNER FLAME
/X F BURNER
..!:_.:-.
MANIFOLD J
Fig. 61 - Burner Flame
Table 15 - Altitude Derate Multiplier for USA.
ALTITUDE PERCENT OF DERATE MULTIPLIER
FT (M) DERATE FACTOR*
0-2000
(0-810) 0 1.00
2001-3000
(610-914) 4-6 0.95
3001-4000 (914-1219) 6-8 0.93
4001-5000
(1219-1524) 8-10 0.91
5001-8000
1524-1829) 10-12 0.89
8001-7000
(1829 -2134) 12-14 0.87
7001-8000
(2134-2438) 14-16 0.85
8001-9000
(2438-2743) 16-18 0.83 9001-10,000 18- 20 0.81
(2743-3048)
Derate multiplier factors are based on midpoint altitude for altitude range.
EXAMPLE: 100,000 BTUH HIGH-HEAT INPUT FURNACE INSTALLED AT 4,300 FT. (1311 M)
A89020
e. Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
f. Turn off all other gas appliances and pilots.
g. Move setup switch SW1-2 to ON position. (See Fig.
37.) This keeps furnace locked in low-heat operation.
h. Jumper R to W/W1.
i. Let furnace run for 3 minutes in low-heat operation. j. Measure time (in sec) for gas meter to complete 1
revolution. Note reading.
k. Refer to Table 16 for cubicfl, of gas per hr.
1. Multiply gas rate cu fl./hr by heating value (Btu/cu ft.).
m. Move setup switch SW1-2 to OFF position and jumper
R and W/W1 and W2 thermostat connections. (See Fig.
37.) This keeps furnace locked in high-heat operation. Repeat items i through 1 for high-heat operation.
EXAMPLE: (High-heat operation at 0-2000ft. (0-610 M) altitude)
Furnace input from rating plate is 100,000 Btuh Btu heating input = Btu/cuft. X cu ft./hr
Heating value of gas = 975 Btu/cu ft. Time for 1 revolution of 2-cu ft. dial -- 70 sec
Gas rate = 103 cu ft./hr (from Table 16) Btu heating input = 103 X 975 = 100,425 Btuh In this example, the orifice size and manifold pressure adjustment
is within +/-2 percent of the furnace input rate.
NOTE: Measured gas inputs (high heat and low heat) nmst be within +/-2 percent of that stated on furnace rating plate when
installed at sea level or derated per that stated above when installed
at higher altitudes.
n. Remove jumper across R, W/WI, and W2 thermostat
connections to ternfinate call for heat.
Furnace Input Rate at Sea Level X Derate Multiplier Factor = Furnace Input Rate at Installation Altitude
100,000 X 0.91 = 91,000
CANADA
At installation altitudes from 2000 to 4500 fl, (610 to 1372 M) this furnace nmst be derated 5 percent by an authorized Gas
Conversion Station or Dealer. To deternfine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor.
b. Reinstall burner box cover.
NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.
c. Check that gas valve adjustment caps are in place for
proper input to be clocked.
d. Obtain average heat value (at altitude) from local gas
supplier.
NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude
adjustment of gas heating value.
56
Page 57
Table16- Gas Rate Cu Ft./Hr
SECONDS SIZE OF TEST DIAL SECONDS
FOR 1 1 2 5 FOR 1
REVOLUTION REVOLUTION
10 360 720 1800 50 11 327 655 1636 51 12 300 600 1500 52 13 277 555 1385 53 14 257 514 1286 54 15 240 480 1200 55
16 225 450 1125 56 17 212 424 1059 57 18 200 400 1000 58 19 189 379 947 59 20 180 360 900 60 21 171 343 857 62
22 164 327 818 64 23 157 313 783 66 24 150 300 750 68 25 144 288 720 70 26 138 277 692 72 27 133 267 667 74
28 129 257 643 76 29 124 248 621 78 30 120 240 600 80 31 116 232 581 82 32 113 225 563 84 33 109 218 545 86 34 106 212 529 88
35 103 206 514 90 36 100 200 500 92 37 97 195 486 94 38 95 189 474 96 39 92 185 462 98 40 90 180 450 100
41 88 176 439 102 42 86 172 429 104 43 84 167 419 106 44 82 164 409 108 45 80 160 400 110 46 78 157 391 112
47 76 153 383 116 48 75 150 375 120
49 73 147 367
cuff. cuff. cuff.
SIZE OF TEST DIAL
1 2 5
cuff. cuff. cuff.
72 144 360 71 141 355 69 138 346 68 136 340 67 133 333 65 131 327
64 129 321 63 126 316 62 124 310 61 122 305 60 120 300 58 116 290
56 112 281 54 109 273 1
53 106 265 51 103 257 50 100 250 48 97 243
47 95 237 46 92 231 45 90 225 44 88 220 43 86 214 42 84 209 41 82 205
40 80 200 39 78 196 38 76 192 38 75 188 37 74 184 36 72 180
35 71 178 35 69 173 34 68 170 33 67 167 33 65 164 32 64 161
31 62 155 30 60 150
U
SET TEMPERATURE RISE
UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate.
Temperature rise must be within limits specified on unit rating plate. Operation is within a few degrees of midpoint of rise range when setup switch SWl-4 is OFF.
Furnace must operate within ranges of temperature rise specified on the furnace rating plate. Determine air temperature rise as
follows:
1. Place thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air
temperature rise.
NOTE: Temperature rise can be determined for low-heat operation by placing setup switch SWI-2 on furnace control in
ON position. For high-heat operation, place setup switch SWI-2 in OFF position and jumper R-W2 on furnace control. DO NOT forget to return setup switch to OFF position and remove R-W2 jumper upon completion of testing. (See Fig. 37 for switch and terminal location.)
3. This furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on furnace rating plate. If temperature rise is
outside this range, proceed as follows:
a. Check gas input for low- and high-heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive
restrictions causing static pressure greater than 0.5-in. wc.
d. Ensure Low Heat Rise Adjust switch SWl-3 on furnace
control is in ON position when a bypass humidifier is used. (See Fig. 37 for switch location.)
e. Check Troubleshooting Guide for Variable-Speed
2-Stage Electronic Condensing Furnaces Series 170 and later.
57
Page 58
il
SET THERMOSTAT HEAT ANTICIPATOR
When using a non-electronic thermostat, the thermostat heat anticipator nmst be set to match the amp draw of components in the R-W/WI circuit. Accurate amp draw measurements can be
obtained only at the thermostat subbase terminals R and W. The thermostat and anticipator should NOT be in the circuit while
measuring current. If thermostat has no subbase, the thermostat must be disconnected from R and W/W1 wires during current
measurement. Fig. 62 illustrates an easy method of obtaining thermostat amp
draw measurements. The amp reading should be taken after blower motor has started and furnace is operating in low-heat.
1. To operate furnace in low-heat, turn setup switch SWI-2 to ON position (See Fig. 37) and connect ammeter leads across
thermostat subbase R-W.
2. See thermostat manufacturer's instructions for adjusting the heat anticipator and for varying heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3 cycles per hr.
TERMINALS WITH THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE: 5.0 AMPS ON AMMETER = 0.5 AMPS FOR THERMOSTAT
10 TURNS AROUND JAWS ANTICIPATOR SETTING
Fig. 62 - Amp Draw with Ammeter
3. Return setup switch SW1-2 to OFF position and replace thermostat on subbase.
SUBBASE
AMMETER
A96316
Step 7 -- Check Safety Controls
This section covers the safety controls that must be checked before the installation is complete. The flame sensor, gas valve, and
pressure switches were all checked in the Start-up procedure section as part of normal operation.
CHECK PRIMARY LIMIT CONTROL
This control shuts off the gas control system and energizes the
air-circulating blower motor if furnace overheats.
1. The recommended method of checking this linfit control is to gradually block off return air after furnace has been operating for a period of at least 5 nfinutes.
2. As soon as limit control has shut off burners, a status code 33 will appear on furnace control.
3. The return-air opening should be unblocked to pernfit normal air circulation.
By using this method to check the linfit control, it can be established that the linfit is functioning properly and the furnace
will operate safely if there is a restricted return-air duct or motor failure. If the linfit control does not function during this test, the cause nmst be determined and corrected.
CHECK PRESSURE SWITCHES
This control proves operation of the draft inducer. Check switch operation as follows:
1. Turn off 115-v power to furnace.
2. Remove control access door and disconnect inducer motor 12-pin wire harness at inducer motor.
3. Turn on 115-v power to furnace.
4. Set thermostat to "call for heat." When pressure switches are functioning properly, status code 42 will flash on furnace
control approximately 20 sec after thermostat switch is closed. If either a status code 31 or 32 is flashed when
inducer motor is disconnected, the furnace will shut itself down immediately. Deternfine the reason pressure switches
did not function properly and correct the condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor wire harness. Reinstall furnace access door.
7. Turn on l15-v power to furnace.
8. Reset thermostat to desired temperature.
CHECKLIST
1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Verify that blower and main access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer's
instructions.
6. Review User's Manual with owner.
7. Leave literature packet near furnace.
58
Page 59
CHECKLIST-- DIRECT VENT (2-PIPE) INSTALLATION
LOAD CALCULATION
Heating Load (Btuh)
Cooling Load (Btuh)
Furnace Model Selection
COMBUSTION AND VENT PIPING
Termination Location
Roof or Sidewall
Termination Kit - 2 Pipe or Con- centric
Combustion-Air Pipe Length
Combustion-Air Pipe Elbow Quantity
Vent Pipe Length Vent Pipe Elbow Quantity
Pipe Diameter Determined from
Sizing Table
Pipe Sloped To Furnace
Pipe Insulation
Over Ceilings
Low-Ambient Exposed Pipes
Condensate Drain
Unit Level or Pitched Forward Internal Tubing Connections
Free of Kinks and Traps External Drain Connection Leak
Tight and Sloped Condensate Trap Primed before
Start- Up
Heat Tape Installed if Required
CHECKLIST - START-UP
Gas Input Rate (Set Within 2 percent of Rating Plate)
Temperature Rise Adjusted
Thermostat Anticipator
Anticipator Setting Adjusted or Cycle Rate (3 Cycles per Hr)
Selected
Safety Controls Check Operation
CHECKLIST - START-UP
Gas Input Rate (Set Within 2 percent of Rating Plate)
Temperature Rise Adjusted
Thermostat Anticipator
Anticipator Setting Adjusted or Cycle Rate (3 Cycles per Hr)
Selected
Safety Controls Check Operation
Primary Limit Pressure Switches
59
Page 60
CHECKLIST -- DIRECT VENT (1 -PIPE) INSTALLATION
LOAD CALCULATION
Heating Load (Btuh)
Cooling Load (Btuh)
Furnace Model Selection
VENT PIPING
Termination Location
Roof or Sidewall
Vent Pipe Length
Vent Pipe Elbow Quantity
Pipe Diameter Determined from
Sizing Table
Pipe Sloped to Furnace
Pipe Insulation
Over Ceilings
Low-Ambient Exposed Pipes
Condensate Drain
Unit Level or Pitched Forward Internal Tubing Connections
Free of Kinks and Traps External Drain Connection Leak
Tight and Sloped Condensate Trap Primed before
Start- Up
Heat Tape Installed if Required
CHECKLIST - START-UP
Gas Input Rate (Set Within 2 percent of Rating Plate)
Temperature Rise Adjusted
Thermostat Anticipator
Anticipator Setting Adjusted or Cycle Rate (3 Cycles per Hr)
Selected
Safety Controls Check Operation
Primary Limit Pressure Switches
Copyright 2008 Carrier Corp. 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 12/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
60
Catalog No: 58MVB-4SI
Replaces: 58MVB-3SI
Loading...