Installation, Start-up, and Operating Instructions
Sizes 050-125, Series 101
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA No.
54-1992/ANSI Z223.1-1992. In Canada, refer to the current
edition of the National Standard of Canada CAN/CGA-B149.1and .2-M91 Natural Gas and Propane Gas Installation Codes
(NSCNGPIC). Wear safety glasses and work gloves. Have fire
extinguisher available during start-up and adjustment procedures
and service calls.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury. Understand
the signal word DANGER, WARNING, or CAUTION. These
words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards that could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions that
will result in enhanced installation, reliability, or operation.
INTRODUCTION
The design of the 58EJB Deluxe Horizontal Gas-Fired Condensing
Furnace is A.G.A./C.G.A. certified as a Category IV furnace for
natural and propane gases and for installation in alcoves, basements, crawlspaces, utility rooms, and attics. The design of the
horizontal gas-fired furnace is A.G.A./C.G.A. certified for installation on noncombustible floors. This furnace may be installed on
combustible wood flooring; however, it may not be installed
directly on carpeting, tile, or any combustible material other than
wood. The design of this furnace line is not A.G.A. certified for
installation in recreational vehicles, manufactured housing (mobile
homes), or outdoors.
Before installing this furnace, refer to the current edition of the
NFGC NFPA 54-1992/ANSI Z223.1-1992 which is available from
the National Fire Protection Association Inc., Batterymarch Park,
Quincy, MA 02269, American Gas Association, 1515 Wilson
Boulevard, Arlington, VA 22209, or from Literature Distribution.
®
In Canada, contact Standards Department of Canadian Gas Association, 55 Scarsdale Road, Don Mills, Ontario, Canada M3B2R3.
Installation must conform to the regulations of the serving gas
supplier and the local building, heating, and plumbing codes in
effect in the area in which the installation is made, or in the
absence of local codes with the requirements of the NFGC or
NSCNGPIC.
These instructions cover minimum requirements for a safe installation and conform to existing national standards and safety codes.
In some instances, these instructions exceed certain local codes
and ordinances, especially those that may not have kept pace with
changing residential construction practices. We require these
.
instructions as a minimum for a safe installation.
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air
temperature rise, and unit sizing. Improper installation or
misapplication of the furnace can require excessive servicing
or cause premature component failure.
This furnace is designed for a minimum continuous return-air
temperature of 60°F db or intermittent operation down to 55°F db
such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F db.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified
installer, service agency, local gas supplier, your distributor
or branch for information or assistance. The qualified installer
or agency must use only factory-authorized and listed kits or
accessories when modifying this product. Failure to follow
this warning could result in electrical shock, fire, personal
injury, or death.
ama
58EJB
CANADIAN GAS ASSOCIATION
APP R O VE D
R
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101Catalog No. 535-869Printed in U.S.A.Form 58EJB-1SIPg 12-94Replaces: 58EJA-3SI
* Vent size is 3 in. with factory-supplied 2-X-3 in. bell reducer.
DUCT SUPPLY
AND RETURN
OPENINGS
Fig. 1—Dimensional Drawing
14
1
26
1
27
⁄2″
⁄2″
1
⁄4″
3
31
⁄4″
COMBUSTION-AIR
VENT DIAMETER
55″
7″
1
3
⁄8″
21
3
⁄8″
23
1
4
⁄4″
17″
1
⁄2″ GAS CONNECTION
1
⁄2″ CONDENSATE DRAIN
7
⁄8″
HEAT EXCHANGERS
1
⁄8″
NUMBER OF
A91190
If this furnace is used during construction when adhesives,
sealers, and/or new carpets are being installed, make sure all
combustion and circulating air requirements are followed. If
operation of the furnace is required during construction, use
clean outside air for combustion and ventilation. Compounds
of chlorine and fluorine when burned with combustion air
form acids which will cause corrosion of the heat exchangers.
Some of these compounds are found in paneling and dry wall
adhesives, paints, thinners, masonry cleaning materials, and
many other solvents commonly used in the construction
process.
NOTE: Excessive exposure to contaminated combustion-air will
result in safety and performance related problems.
For accessory installation details, refer to the applicable installation literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
This furnace is equipped with a metal blower wheel shipping
bracket which MUST be removed before starting the unit.
Table 1—Attic or Alcove Clearances From
Combustible Materials (In.)
UNIT SIZE
Sides0
Back0*
Top of Plenum0
Vent Connector
(PVC Pipe)
Front Casing1†
Front Service30
* Zero in. with controls on front of furnace, 1 in. from back of elbow with
combustion-air inlet on back of furnace, and 1 in. from end of inducer motor
with controls located on back of furnace.
† Measured from end of inducer motor.
This furnace may be located in an attic, basement, crawlspace,
alcove, or suspended from the ceiling of a utility room or
basement.
2
Page 3
Fig. 2—Typical Attic Installation
Do not install the furnace on its back or side. Safety control
operation will be adversely affected. Never connect return-air
ducts to the back of the furnace. Failure to follow this warning
could result in a fire, personal injury, or death.
This furnace may be installed in an unconditioned space with
possible ambient temperatures of 32°F or lower if special
installation requirements are met. See Step 7—Direct Venting
and Step 9—Condensate Drainage.
GENERAL — When a furnace is installed so that the supply ducts
carry air to areas outside the space containing the furnace, the
return air must also be handled by duct(s) sealed to the furnace
casing and terminating outside the space containing the furnace to
ensure there will not be a negative pressure condition within the
equipment room or space.
This furnace must be located so the electrical components are
protected from water.
This furnace may be located in a confined space without special
provisions for dilution or ventilation air.
Locate the furnace as close to the center of the air distribution
system as possible.
For proper furnace operation, locate and install the furnace so it is
within 1/2 in. of level. Refer to Step 9—Condensate Drainage.
Locate the furnace so that maximum allowable vent and
combustion-air pipe lengths are not exceeded. Refer to Step
7—Direct Venting.
Provide ample space for servicing and cleaning. Always comply
with the minimum fire protection clearances shown on the unit
rating plate and in Table 1.
Locate the furnace where available electrical and gas supplies meet
the specifications on the furnace rating plate.
A91192
FURNACE LOCATION RELATIVE TO COOLING EQUIPMENT — The cooling coil must be installed parallel with or on
the downstream side of the furnace to avoid condensation in the
heat exchanger. When installed parallel with a furnace, dampers or
other means used to control the flow of air must prevent chilled air
from entering the furnace. If the dampers are manually operated,
they must be equipped with a means to prevent operation of either
unit unless the damper is in the full-heat or full-cool position.
HAZARDOUS LOCATIONS — When the furnace is installed in
a residential garage, it must be installed so that the burners and
ignition source are located a minimum of 18 in. above the floor.
The furnace alos must be located or protected to avoid physical
damage by vehicles.
When the furnace is installed in a public garage, airplane hangar,
or another building having a hazardous atmosphere, the unit must
be installed in accordance with the requirements of the National
Fire Protection Association, Inc.
This furnace is not watertight and is not designed for outdoor
installation. This furnace shall be installed in such a manner
as to protect the electrical components from water. Outdoor
installation would lead to a hazardous electrical condition and
premature component failure. Failure to follow this warning
could result in fire, personal injury, or death.
Step 2—Horizontal Attic Installation
Do not install the furnace on its back. Safety control operation
will be adversely affected. Never connect return-air ducts to
the sides or back of the furnace. Failure to follow this warning
could result in fire, personal injury, or death.
The furnace can be installed horizontally for either left- or
right-side supply. See Fig. 2 for a typical attic installation and Step
10 for field reversing procedure.
3
Page 4
1. Construct a working platform on location where all required
furnace clearances are met. (See Table 1 and Fig. 2.)
2. Position furnace in desired location.
3. Connect gas supply pipe. See Fig. 2 for typical gas piping.
4. Connect supply- and return-air ducts.
5. Install 24- X 24-in. sheet metal shield on platform in front of
controls as shown in Fig. 2.
Step 3—Horizontal Crawlspace Installation
The furnace can be installed horizontally for either left- or
right-side supply. In a crawlspace, the furnace can either be hung
from the floor joists or installed on suitable blocks or a pad. The
furnace can be suspended using steel pipe straps around each end
of the furnace. These straps should be attached to the furnace with
sheet metal screws and to the floor joists with lag bolts. A framed
assembly of angle iron suspended with all-thread rod of suitable
diameter may be used to support the length of the furnace.
The horizontal crawlspace installation is very similar to the attic.
Refer to Step 2, items 2, 3, 4, and 5. A 24- X 24-in. sheet metal
shield must be installed above the controls for crawlspace installations. Extend the sheet metal shield over the furnace top far
enough to cover the gas pipe entry hole.
Step 4—Filter Arrangement
Connect a capped nipple to the lower end of the tee. The capped
nipple should extend below the level of the gas controls. Place a
ground joint union between the gas control manifold and the
manual gas shut-off valve. (See Fig. 3.)
An accessible manual shut-off valve MUST be installed upstream
of the furnace gas controls and within 6 ft of the furnace. A 1/8-in.
NPT plugged tapping, accessible for test gage connection, MUST
be installed immediately upstream of the gas supply connection to
the furnace and downstream of the manual shut-off valve.
GAS
SUPPLY
MANUAL
SHUTOFF
UNION
SEDIMENT
TRAP
VALVE
A91212
Fig. 3—Typical Gas Piping
Never operate the unit without a filter or with the filter
removed. Failure to follow this caution can result in a fire,
personal injury, or death.
The factory-supplied filter and wire filter retainer are shipped with
the furnace. After the return-air duct has been connected to the
furnace, install the filter in the blower compartment, just ahead of
the return-air plenum, and secure it with the wire filter retainer.
The cross-mesh binding side of the filter should face the blower.
Step 5—Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC.
The gas supply line should be a separate line running directly from
the meter to the furnace, if possible. Refer to Table 3 for the
recommended gas pipe sizing. Risers must be used to connect to
the furnace and to the meter.
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54-1992.
INTERNAL
DIAMETER (IN.)
Support all piping with appropriate straps, hangers, etc. Use a
minimum of 1 hanger every 6 ft.
Joint compounds (pipe dope) should be applied sparingly and only
to the male threads of the joints. This pipe dope must be resistant
to the action of propane gas.
Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading to the
furnace, so that the straight-through section of the tee is vertical.
LENGTH OF PIPE (FT)
1020304050
Use the proper length of pipes to avoid stress on the gas
control manifold. A failure to follow this warning could result
in a gas leak causing fire, explosion, personal injury, or death.
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), close the manual shut-off valve located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing.
Use a backup wrench when connecting the gas pipe to the
furnace to avoid damaging gas controls.
After all connections have been made, purge the lines and check
for leakage.
Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition to check
for leaks. Use a soap-and-water solution to check for leakage.
Failure to follow this warning could result in a fire, explosion,
personal injury, or death.
Step 6—Electrical Connections
See Fig. 17 for a wiring diagram showing the proper field 115- and
24-v wiring. Check all factory and field electrical connections for
tightness.
115-V WIRING — Before proceeding with the electrical connections, make certain that voltage, frequency, and phase correspond
to that specified on the unit rating plate. Also, check to be sure that
the service provided by the utility is sufficient to handle the load
imposed by this equipment. Refer to rating plate or to Table 4 for
the equipment electrical specifications.
4
Page 5
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-, 208/230-, 460-VOLT WIRING
FOUR
WIRE
GWYR
TWO-WIRE
HEATING-
ONLY
G
115-VOLT
SINGLE
W
PHASE
GND
115-VOLT
FIELD-SUPPLIED
FUSED DISCONNECT
GND
Y
C
R
24-VOLT
TERMINAL
BLOCK
NOTE :
1. Connect Y-terminal as shown for proper cooling operation.
2. If any of the original wire, as supplied, must be replaced,
use same type or equivalent wire.
3. Proper polarity must be maintained for 115-volt wiring.
Fig. 4—Heating and Cooling Application Wiring Diagram
Do not connect aluminum wire between the disconnect switch
and the furnace. Use only copper wire.
Make all electrical connections in accordance with the National
Electric Code (NEC) ANSI/NFPA 70-1993 and any local codes or
ordinances that might apply.
For Canadian installations, all electrical connections must be made
in accordance with CSA C22.1 Canadian Electrical Code, or
authorities having jurisdiction.
Use a separate, fused branch electrical circuit containing a properly
sized fuse or HACR-type circuit breaker for this furnace. See
Table 4 for wire size and fuse specifications. A disconnecting
means must be located within sight of and readily accessible to the
furnace.
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR
460-VOLT
THREE
PHASE
GNDGND
208/230-
VOLT
SINGLE
GND
GND
PHASE
CONDENSING
UNIT
TWO
WIRE
A91338
24-V WIRING — Make field 24-v connections at the 24-v terminal block. Connect Y terminal as shown in Fig. 4 for proper
cooling operation. The 24-v terminal board is marked for easy
connection of field wiring. (See Fig. 5.)
ELECTRONIC
AIR CLEANER
TERMINALS
(115 VAC, 1 AMP MAX)
3-AMP FUSE
W Y R C G
HUMIDIFIER TERMINAL
(24 VAC, 0.5 AMP MAX)
EAC-2 EAC-1
3
HUM-1
BLOWER OF DELAY SELF TEST
90 100 180 225
JW9
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC, ANSI/ NFPA 70-1992, Canadian Electrical Code, CSA C22.1, or local codes to minimize personal
injury if an electrical fault should occur. This ground may
consist of electrical wire or conduit approved for electrical
ground when installed in accordance with existing electrical
codes. Do not use gas piping as an electrical ground. Failure
to follow this warning could result in an electrical shock, fire,
or death.
If manual disconnect switch is to be mounted on the furnace,
select a location where a drill or fastener will not contact
electrical or gas components.
NOTE: Proper polarity MUST be maintained for 115-v wiring. If
polarity is incorrect, the pilot flame will not be sensed and the
ignition control will shut down the unit until the control is reset.
24-VOLT THERMOSTAT
SELF-TEST PINS
TERMINALS
BLOWER OFF-DELAY
ADJUSTMENT CONTROL
Fig. 5—Control Board
NOTE: Use AWG No. 18 color-coded copper thermostat wire for
lengths up to 100 ft. For wire lengths over 100 ft, use AWG No.
16 wire.
ACCESSORIES — Install accessories per manufacturer’s instructions. Cycle test furnace and accessories twice to ensure proper
operation.
Step 7—Direct Venting
The 58EJB Furnace requires a dedicated (one 58EJB Furnace
only) direct vent system. In a direct vent system all air for
combustion is taken directly from the outside atmosphere and all
flue gases are discharged to the outside atmosphere.
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Time-delay fuse is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
Maximum*Minimum*
MAXIMUM
UNIT
AMPS
MINIMUM
WIRE
SIZE
MAXIMUM WIRE
LENGTH
(FT)‡
MAXIMUM FUSE OR
HACR-TYPE
CKT BKR AMPS†
REMOVAL OF EXISTING FURNACES FROM COMMON
VENT SYSTEMS — If the furnace being replaced was connected
to a common vent system with another appliance(s), these steps
shall be followed with each appliance remaining connected to the
common vent system placed in operation. Ensure that the other
appliances remaining connected to the common vent system are
not in operation.
1. Seal any unused openings in the common vent system.
2. Visually inspect the vent system for proper size and horizontal
pitch, and determine there is no blockage or restriction,
leakage, corrosion, and other deficiencies which could cause
an unsafe condition.
3. Insofar as is practical, close all building doors, windows, and
doors between the space in which the appliances remaining
connected to the common vent system are located and other
spaces of the building. Turn on clothes dryers and any
appliance not connected to the common vent system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts,
so they operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions and place the appliance in
operation. Adjust the thermostat so appliance will operate
continuously.
5. Test for flue gas spillage at the drafthood relief opening after
5 minutes of main burner operation. Use the flame of a match
or candle, or smoke from a cigarette, etc.
6. After it has been determined that each appliance remaining
connected to the common vent system properly vents when
tested as above, return doors, windows, exhaust fans, fireplace
dampers, any other gas burning appliances to their previous
condition of use.
7. If improper venting is observed during any of the above tests,
the common vent system must be corrected. The vent system
or vent connectors may need to be resized. When resizing vent
systems or vent connectors, the minimum size of the system or
connector must be as determined using the appropriate table
found in Appendix G of the NFGC, or Section 5 of NSCNGPIC for Canadian Standards.
COMBUSTION-AIR AND VENT PIPING — The combustionair and vent pipe fittings must conform to American National
Standards Institute (ANSI) standards and American Society for
Testing and Materials (ASTM) standards D1785 (schedule-40
PVC), D2665 (PVC-DWV), D2241 (SDR-21 and SDR-26 PVC),
D2661 (ABS-DWV), or F628 (schedule-40 ABS). Pipe cement
and primer must conform to ASTM standards D2564 (PVC) or
D2235 (ABS). See Table 5 for maximum pipe lengths (including
maximum lengths adjusted for high-altitude installations) and Fig.
6 or 7 for exterior piping arrangements.
HORIZONTAL VENT TERMINATION
NOTE: 7″ MIN CLEARANCE TO NEAREST
BUILDING OR WALL
1
1
⁄2″ MIN
18
″ MAX
WALL THICKNESS
12″ MIN
24
AIR INLET
COUPLING
NOTE: HORIZONTAL VENT
TOP VIEWSIDE VIEW
RUNS MUST HAVE A
1
⁄4″ SLOPE TOWARD
THE FURNACE FOR
EVERY 12
COMBUSTION-AIR INLET
″ OF PIPE
″ MAX
FLUE OUTLET
TERMINATION
BRACKET
12″ MIN
24
″ MAX
VENT
DRAIN
COMBUSTION-AIR
(ELBOW WITH
AIR SPLITTER)
12″ MIN
24
″ MAX
VENT
(PVC TEE)
A91213
Fig. 6—Sidewall Termination
Table 5—Maximum Allowable Pipe Length (Ft)
ALTITUDE ABOVE
SEA LEVEL
(FT)
0 to 20005050505050
2001 to 30004443434242
3001 to 40004039383736
4001 to 50003736353433
5001 to 60003432312928
6001 to 70003129282625
7001 to 80002725232119
8001 to 90002422201816
9001 to 10,0002118161311
NOTE:
1. Up to five 90° elbows may be used, not including the vent termination.
Assume that two 45° elbows equal one 90° elbow.
2. Pipe length based on 2-in. diameter pipe for size 050-12 and 075-12, and
3-in. diameter pipe for size 100-16 and 125-20.
3. Minimum pipe length is 5 ft for all applications.
NUMBER OF 90° ELBOWS
12345
6
Page 7
In Canada construct all combustion-air and vent pipes for this unit
of CSA or ULC certified schedule-40 PVC, PVC-DWV or ABSDWV pipe and pipe cement. SDR pipe is not approved in Canada.
A secondary vent pipe drain (provided) MUST be installed in the
furnace vent pipe as shown in Fig. 6 and 7. This ensures proper
drainage of condensation that collects in the vent pipe. A vertical
pipe may be installed in the inducer housing outlet, but it must turn
horizontally at a 90° angle into the vent drain before continuing out
of the structure. (See Fig. 6 or 7.) No straight vertical vent piping
may be used.
Z-SHAPED
TERMINATION
BRACKET
12″ MIN ABOVE
ANTICIPATED MAX
SNOW LEVEL
12″ MIN
24
″ MAX
NOTE: HORIZONTAL VENT
RUNS MUST HAVE A
1
⁄4″ SLOPE TOWARD
THE FURNACE FOR
EVERY 12
NOTE: Z-SHAPED BRACKET
MUST BE INSTALLED
AS SHOWN TO
SECURE PIPES
PROPERLY
PVC TEE
VENT
COMBUSTION-AIR
(ELBOW WITH
AIR SPLITTER)
″ OF PIPE
A91214
Fig. 7—Rooftop Termination (Preferred)
If installing 2 or more 58EJB Furnaces refer to the Multiventing
and Vent Terminations section of this instruction.
Combustion air must NOT be taken from inside the structure
because that air frequently is contaminated by halogens,
which include fluorides, chlorides, bromides, and iodides.
These elements are found in aerosols, detergents, bleaches,
cleaning solvents, salts, air fresheners, adhesives, paint, and
other household products.
Maintain a minimum of 36 in. between combustion-air inlet
and clothes dryer vent.
Locate the combustion-air inlet as far as possible from the
swimming pool and swimming pool pump house.
When the vent pipe is exposed to temperatures below
freezing, such as when it passes through an unheated space or
when a chimney is used as a raceway, the pipe must be
insulated with 1/2-in. thick Armaflex-type insulation.
When the combustion-air pipe is installed above a suspended
ceiling, the pipe must be insulated with 1/2-in. Armaflex-type
insulation. The combustion-air pipe should also be insulated
when it passes through a warm, humid space.
Solvent cements are combustible. Keep away from heat,
sparks, and open flame. Use only in well ventilated areas.
Avoid breathing of the vapor and contact with the skin or
eyes. Failure to follow this warning could result in a fire,
property damage, personal injury, or death.
The vent terminal bracket described in the next section MUST be
used in constructing the vent terminal for this unit. Pipes must
terminate through either the roof or the sidewall although roof
termination is preferable. Locate sidewall terminations to prevent
damage to shrubs, condensing unit, and siding materials. Table 6
gives clearance requirements.
Table 6—Combustion-Air and Vent Terminal
Clearances
LOCATION
Above anticipated snow depth11
Dryer vent34
From plumbing vent stack33
Gas appliance vent terminal and
chimney
From any opening where vent gases
could enter building
Above grade level11
From combustion-air opening of any
appliance
From a fresh air intake3*6
From electric or gas meters, regula-
tors, and relief equipment
Above grade when adjacent to public
walkway
* Three ft above an intake located within 10 ft.
† Horizontal distance.
CLEARANCE (FT)
U.S.A.Canada
44
13
16
4†6
77
All combustion-air and vent pipes must be airtight and
watertight except top joint of the elbow on the combustion-air
inlet plate which must be left unglued to facilitate removal of
burners. The pipes must also terminate exactly as shown in
Fig. 6 or 7. Failure to follow this warning could result in
property damage, personal injury, or death.
NOTE: The unit is shipped with a 3- to 2-in. bell reducer for units
where 3-in. combustion-air pipe is required.
NOTE: Do not count the elbows to which the terminal bracket
attaches or any elbow between the bracket and the open end of the
pipe. (See Fig. 6 or 7.) Also, do not count pipe sections inside
furnace casing.
NOTE: It is recommended that all pipes be cut, prepared, and
preassembled before permanently cementing any joint.
1. Attach PVC pipe to inducer housing outlet, run vent pipe
vertically for a short distance. Turn piping horizontally 90° to
allow installation of secondary vent drain before continuing
out of structure. (See Fig. 6 or 7.)
NOTE: If 3-in. vent pipe is required, the 3- to 2-in. reducing
adapter provided must be used. Install the adapter as close to the
inducer housing outlet as possible.
2. Connect 90° elbow to combustion-air inlet plate with elbow
pointing upward. (See Fig. 8.) Do NOT cement the elbow to
the conbustion-air inlet plate since this joint must be unglued
to facilitate removal of burners during maintenance.
7
Page 8
AIR INLET
PIPE
In all installations the
NOTE:
combustion-air inlet
piping must be connected
with an elbow pointing up
to allow access to the
burner assembly.
DO NOT SEAL
THIS JOINT
COMBUSTION-AIR INLET PLATE
A91215
Fig. 8—Combustion-Air Piping
3. Working from furnace to outside, cut pipe to required
length(s).
4. Deburr inside and outside of pipe.
5. Chamfer outside edge of pipe for better distribution of primer
and cement.
6. Clean and dry all surfaces to be joined.
7. Check dry fit of pipe and mark insertion depth on pipe.
8. After pipes have been cut and preassembled, apply generous
layer of cement primer to pipe fitting socket and end of pipe
to insertion mark. Quickly apply approved cement to end of
pipe and fitting socket (over primer). Apply cement in light,
uniform coat on inside of socket to prevent buildup of excess
cement. Apply second coat.
9. While the cement is still wet, twist pipe into socket with a
1/4-turn. Be sure pipe is fully inserted into fitting socket.
10. Wipe excess cement from joint. A continuous bead of cement
will be visible around the perimeter of a properly made joint.
11. Handle pipe joints carefully until cement sets.
12. Support piping at minimum of every 5 ft (3 ft for SDR-21 or
-26 PVC) using perforated metal hanging strap. Slope
combustion-air and vent pipes toward furnace a minimum of
1/4 in. per linear ft with no sags between hangers.
13. Use appropriate methods to seal openings where vent and
combustion-air pipes pass through roof or side wall.
c. Top of chimney is sealed and weatherproofed.
3. Sidewall termination. (See Fig. 6.)
a. Terminations must be made 12 in. above anticipated annual
snow accumulation level or grade, whichever is greater.
b. Minimum of 4 ft clearance must be provided from electric
or gas meters, regulators, and relief equipment.
4. Install 90° elbows as shown in Fig. 6 or 7, or use a 180°
U-fitting.
5. Install tee as shown in Fig. 6 or 7.
6. Check required dimensions as shown in Fig. 6 or 7.
7. Disassemble loose pipe fittings. Clean and cement fittings
using same procedures as outlined for system piping.
8. Secure combustion-air and vent pipe terminations with
Z-shaped termination bracket (provided).
MULTIVENTING AND VENT TERMINATIONS OF 58EJB
FURNACES — When 2 or more 58EJB Furnaces are vented near
each other, each furnace must be individually vented. Never
common vent or breach-vent these furnaces. There must be a
12-in. separation between the combustion-air and vent pipes of the
first and second furnaces. The next vent termination must be at
least 4 ft away from the first 2 terminations. It is important that the
vent terminations be constructed in this manner to avoid recirculation of flue gases.
Step 9—Condensate Drainage
This furnace must use the condensate trap supplied with the unit.
See Fig. 9 for proper drain installation. The drain must terminate
at a floor drain, sewer system, or drain vent for proper condensate
removal. Drain installation must conform with local building
codes. For proper condensate drainage from the furnace, the
furnace MUST be within 1/2 in. of level. That is, the highest corner
of the furnace must not be more than 1/2 in. higher than the lowest
corner.
TO VENT
TERMINATION
VENT DRAIN
TUBE
INDUCER
HOUSING
TUBE
1″
Step 8—Vent Terminal Kit Installation
The combustion-air and vent pipes must terminate outside the
structure. A factory-supplied terminal kit must be installed as in 1
of the installations shown in Fig. 6 or 7. A roof termination is
preferred. The combustion-air inlet fitting is the factory-provided
elbow with air splitter. (See Fig. 7.)
1. Roof termination is preferred. (See Fig. 7.)
a. Inlet of combustion-air pipe must terminate no less than 12
in. above roof or snow accumulation level.
b. Inlet of combustion-air pipe must terminate 12 in. away
from vertical wall or other protrusion.
2. Termination through existing chimney may be used provided:
a. No other gas-fired or wood-burning appliance is vented
into chimney.
b. Both combustion-air and vent pipes run entire length of
chimney.
Connect to approved
NOTE:
sewer system per these
instructions and local
codes.
Fig. 9—Condensate Drain System
NOTE: The condensate trap MUST be connected to the PVC tee
on the drain line exiting the unit as shown in Fig. 9. Failure to
place the trap at this location may cause erratic unit operation and
nuisance furnace shutdown.
The 1/2-in. diameter schedule-40 PVC or CPVC condensate drain
piping and pipe fittings must conform to ANSI standards and
ASTM D1785 or D2846. The schedule-40 PVC or CPVC cement
and primer must conform to ASTM D2564 or F493.
8
A91176
Page 9
BLOWER
DOOR
BLOWER
DOOR
CONTROL LAYOUT (AS SHIPPED)
Fig. 10—Control Layout for Reversal
In Canada, use CSA or ULC certified schedule-40 PVC or CPVC
drain pipe and cement.
When a condensate pump is required, select a pump that is
approved for condensing furnace applications. To avoid condensate spillage, select a pump with an overflow switch.
1. Determine which side of furnace drain will exit, then cut and
preassemble drain piping (not provided) directly to an open
drain. Refer to Step 7—Direct Venting for instructions on
preparing and cementing plastic pipe.
2. Cement condensate drain tee on pipe assembly from furnace,
then connect to condensate trap. (See Fig. 9.)
3. Attach tubing (provided with furnace) to drain connections on
inducer housing, vent drain, and condensate drain tee as
shown in Fig. 9.
4. Connect other ends of tubing to barbed tee (provided) as
shown in Fig. 9.
5. Cement remaining pipe joints.
NOTE: If this furnace is installed in an unconditioned space (such
as an attic or crawlspace) where the temperature is at or near the
outdoor ambient temperature, a UL listed, thermostaticallycontrolled or self-regulating heat tape must be installed along the
entire length of the condensate drain line in the unconditioned
space.
Failure to install heat tape on condensate lines in an unconditioned space could lead to condensation freezing in drain
line, resulting in nuisance furnace shutdown and hazardous
conditions.
Step 10—Reversing Procedure
NOTE: This procedure must be performed only by trained and
qualified personnel. Due to the complexity of the procedure as well
as the time required, it is strongly recommended that the unit be
field-reversed prior to transporting it to the installation site. Refer
to Fig. 10 throughout the procedure.
Before proceeding with field reversal of controls, ensure all
electrical and gas supplies to the furnace are off. All gas
piping should be disconnected from the furnace. Failure to do
so could result in a hazardous condition causing property
damage, personal injury, or death.
CONTROL LAYOUT (FIELD REVERSED)
A91216
Before starting the field reversal, be sure to have a correct
wiring diagram available and be prepared to mark all wires as
they are disconnected.
The inducer assembly, burner controls, gas valve, and electrical
controls are designed to be field reversed as necessary for certain
field installations and applications per the following procedure.
1. Remove manifold cover plate and air inlet plate/burner removal cover.
2. Disconnect electrical wiring from gas valve and ignition wire.
3. Remove both manifold retention plates from front and rear of
unit.
4. Remove burner/manifold assembly from unit and place assembly on a flat work surface.
5. Remove ignition wire and pilot tubing from grommet.
6. Remove gas valve from manifold using a backup wrench.
7. Remove manifold extension pipe and manifold cap from
manifold.
8. Clean any old joint compound (pipe dope) from manifold,
manifold extension pipe, and manifold cap.
NOTE: Pipe dope must be resistant to the action of propane gas.
9. Reapply pipe dope to male threads of piping and reassemble
manifold assembly as follows.
a. Install manifold extension pipe at previous location of
manifold cap. Tighten extension into position so it points
toward blower when installed.
b. Install manifold cap at previous location of manifold
extension pipe.
c. Install gas valve onto manifold extension pipe so manual
ON/OFF knob is in 12 o’clock position.
d. Tighten manifold cap on manifold pipe.
10. Remove screws securing pilot bracket to burner support
between first 2 burners.
11. Install pilot bracket between crossovers of first 2 burners on
gas valve side of manifold.
12. Rebend pilot tubing to new location of pilot and gas valve.
Ensure pilot tubing is free of kinks.
13. Route pilot tubing through grommet and reattach to pilot and
gas valve. Check pilot to ensure pilot orifice is in place before
connecting tubing.
14. Route ignition wire through grommet and connect to plug on
pilot.
15. Check pilot position per dimensions shown in Fig. 12.
16. Reinstall manifold retention plate on front (control side) of
unit with screws loose.
9
Page 10
SWITCH BRACKET
1
/8″
Fig. 13—Pressure Tubing Diagram
A91218
P2
P1
PRESSURE SWITCH TUBE ROUTING
1
2
3
TOP OF THE CONDENSING COIL
BOTTOM OF THE CONDENSING COIL
INDUCED
DRAFT
MOTOR
10
REMOVE
BASE BRACKET
A92306
Fig. 11—Rollout Switch Assembly
A91064
Fig. 12—Position of Pilot Assembly to Burner
17. Reinstall rear center panel of unit.
18. Remove burner patch plate from rear center panel of unit, cut
insulation, and reinstall burner/manifold assembly through
rear of unit. Ensure manifold assembly slides under front
manifold retention plate.
19. Reinstall rear manifold retention plate and tighten screws on
both retention plates.
20. Disconnect wiring from limit switch and remove limit switch.
21. Disconnect wiring from pressure switches using needle nose
pliers.
22. Remove control box cover and disconnect blower leads from
control board.
23. Disconnect tubing to pressure switches (mark tubing P1 and
P2) and remove switches. (See Fig. 13.)
24. Remove control box from unit with draft inducer motor
attached.
25. Remove 4 screws securing inducer assembly plate to front
center panel.
26. Remove 4 screws securing front center panel to vent return
pipe.
27. To avoid cuts during this procedure, place a piece of cardboard between condensing heat exchanger fins and vent return
pipe. From rear of unit, remove 4 screws securing vent return
pipe to bottom plate of condensing heat exchanger.
NOTE: Any gaskets or seals broken in items 25, 26, or 27 MUST
be resealed properly to ensure safe furnace operation.
If the integrity of any gasket or seal is questionable due to
separation of the gasket material, malformed appearance, or
any noticeable deformity, the gasket material must be replaced. Failure to replace gaskets may result in nuisance
tripping of safety controls, unit operation failure, or other
conditions which may lead to personal injury.
28. Inspect gasket material on vent return pipe and on condensing
heat exchanger bottom plate. Replace gasket material if
necessary.
29. Reinstall vent return pipe so pipe outlet is facing rear of unit.
Reinstall 4 washers and nuts securing pipe to heat exchanger
bottom plate. Remove and discard cardboard previously
placed between fins and pipe. Remove patch plate and cut
insulation on rear center panel and position vent return pipe
through panel. Secure pipe to panel with 4 screws.
30. Remove blower motor wiring harness strain relief from front
center panel. Cut insulation and reinstall strain relief in same
opening on back center panel. Route harness behind vent
return pipe and through strain relief.
31. Remove pressure tubing strain relief from front center panel.
Pull tubing through grommets and remove grommets. Cut
insulation and reinstall grommets in similar openings in rear
center panel. Route pressure tubing through grommets. Label
1 tube "top of coil" and the other "bottom of coil."
32. Reinstall rear heat exchanger panel.
33. Position control box (with wiring still attached to draft inducer
motor and burner cover plate) on rear heat exchanger panel,
route blower wiring into control box, and reinstall box.
34. Inspect gasket material on draft inducer assembly plate, and
replace gasket material if necessary.
35. Reinstall draft inducer assembly on rear center panel over vent
return pipe.
36. Reinstall air inlet plate/burner removal cover and manifold
cover plate.
37. Reinstall limit switch with sensing disc toward blower.
38. Remove condensate drain line and reinstall through rear center
panel.
39. Reinstall pressure switches on rear center panel. Route pressure tubing to switches and reconnect tubing as shown in Fig.
13.
Page 11
40. Remove blower access panel from front of unit and reinstall
on rear of unit. Reinstall rear blower panel on front of unit.
Reinstall top of unit. Install patch plates on front center panel
and seal all remaining holes as necessary.
41. Reconnect wiring to blower motor, gas valve, pressure
switches, and limit switches using unit wiring diagram. (See
Fig. 17.) Ensure all wiring is properly connected and tight.
NOTE: Upon completing the installation, pressure test the furnace (using the following procedure) as critical gaskets/seals have
been broken.
PRESSURE TEST
Do not place the unit into operation without checking the
system pressures of the unit as outlined in this procedure.
Failure to follow the pressure test procedure may result in a
non- operational unit, nuisance tripping and/or a condition
which may lead to personal injury.
1. Check wiring to insure it is properly connected and tight.
2. Place a jumper wire across pressure switches to bypass both
controls.
3. Turn gas valve off.
4. Set room thermostat above room temperature.
5. Turn on electrical supply to furnace.
6. Check pressures at:
a. Induced-draft motor tap (located at top left of motor
casing).
b. Tube previously labelled "top of coil."
c. Tube previously labelled "bottom of coil."
Excessive variation of the pressures listed in Table 7 indicates
a system leak and/or blockage. This is especially true of the
induced-draft motor pressure. An induced-draft motor pressure in the 1.5-in. to 1.6-in. wc range of vacuum pressure
indicates a leak in the system and/or excessive vent length.
Corrective action must be taken before the unit is placed into
operation. Failure to take corrective action may result in a
non-operational unit, condensate leakage, nuisance tripping,
premature unit failure, and/or a condition which may lead to
personal injury.
7. Use Table 7 to verify a properly-sealed unit.
NOTE: The pressures listed are for an ambient temperature of
approximately 76°F. These pressures may vary slightly due to
temperature, vent configuration, and vent length. The table is a
general guideline of system pressures and may vary slightly from
unit to unit.
Table 7—Unit Pressures (In. wc)
UNIT SIZE/
VENTING
50/Min Vent
Max Vent
75/Min Vent
Max Vent
100/Min Vent
Max Vent
125/Min Vent
Max Vent
INDUCED-DRAFT
MOTOR
PRESSURE
2.5
2.5
2.5
2.0
2.4
2.2
2.5
2.3
TOP OF COIL
PRESSURE
0.32
0.32
0.37
0.58
0.23
0.29
0.28
0.38
BOTTOM OF
COIL
PRESSURE
0.94
0.94
1.45
1.50
1.50
1.50
1.60
1.70
8. Reconnect pressure switch tubing as shown in Fig. 13.
9. Turn off electrical supply to unit.
10. Remove jumper wire on pressure switches.
11. Turn on gas valve.
12. Turn on electrical supply to unit. Unit should begin ignition
cycle.
Step 11—Start-up, Adjustment, and Safety Check
GENERAL — The furnace must have a 115-v power supply
properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W,
Y, G, and C must be made at the 24-v terminal block on the control
board. The gas service pressure must not exceed 0.5 psig (14-in.
wc), but must be no less than 0.16 psig (4.5-in. wc) for natural gas.
The unit must not be installed, operated, and then turned off
and left turned off in an unoccupied structure during cold
weather when the temperature drops to 32°F and below.
Freezing condensate left in the furnace will damage the
equipment. See Service and Maintenance Instructions for
winterizing procedure.
SEQUENCE OF OPERATION — Using the schematic diagram in
Fig. 17, follow the sequence of operation through the different
modes. This furnace has a unique control system—read and follow
the wiring diagram very carefully.
1. When thermostat "calls for heat", the R-W circuit closes.
a. Ignition sequence—Power from the transformer energizes
the fan control board. The fan control energizes the
induced-draft blower motor. Pressure switches P1 and P2
normally open contacts close to initiate the ignition sequence.
b. Ignition trial—The ignition control energizes the pilot gas
valve. The ignition electrode begins sparking to light the
pilot. When the pilot flame is sensed, the main gas valve
opens and the pilot flame lights the burners. If the pilot
flame is not sensed, the ignition control locks out after 90
sec. Reset the ignition control by turning the thermostat
below room temperature for 1 minute and then above room
temperature.
c. Blower on delay— The fan control starts the blower after
30 sec. The blower on delay is not adjustable.
d. Blower off delay—When the thermostat is satisfied, the
circuit between R and W is broken, de-energizing the gas
valve and stopping gas flow to the burners. The blower
motor remains energized 60, 90, 120, or 150 sec depending
on the blower off delay selection (factory shipped set for
60-sec delay).
2. Cooling mode.
The thermostat "calls for cooling" closing R and R-Y circuits.
The R-Y circuit starts the outdoor condensing unit, and the
combined R-Y and R-G circuit starts the furnace blower motor
on cooling speed. The (EAC) terminals are energized with
115v whenever the blower is operating.
When the thermostat is satisfied, the R and R-Y circuits are
broken. The furnace blower will continue operating on cooling
speed for an additional 90 sec.
START-UP PROCEDURES
1. Fill condensate trap with water.
a. Disconnect condensate drain tube from bottom of inducer
housing.
11
Page 12
GAS HEAT
VALUE
(BTU/CU FT)
860
875
890
905
920
935
950
965
980
995
1010
1025
1040
1055
1070
1085
1100
Table 8—Model 58EJB Orifice Size and Manifold Pressure for Correct Input Rate
(Tabulated data based on altitudes up to 2000 ft and 25,000 Btuh per burner)
SPECIFIC GRAVITY OF NATURAL GAS
0.560.580.600.620.640.660.680.700.72
Orf.
Mnfld
Orf.
Mnfld
Orf.
Mnfld
Orf.
Mnfld
Orf.
Mnfld
Orf.
Mnfld
Orf.
Mnfld
Orf.
No.
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
41
39
40
41
40
41
—
40
41
—
41
42
—
41
42
—
41
42
—
42
—
—
42
—
—
42
—
—
42
—
—
43
—
—
Press
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.4
3.7
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6
—
3.2
3.5
—
3.4
3.8
—
3.3
3.7
—
3.2
3.6
—
3.4
—
—
3.4
—
—
3.3
—
—
3.2
—
—
3.8
—
—
No.
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
40
41
—
40
41
—
41
42
—
41
42
—
41
42
—
42
—
—
42
—
—
42
—
—
42
—
—
Press
3.4
3.8
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.4
3.7
3.3
3.6
—
3.2
3.4
3.7
3.3
3.6
—
3.2
3.5
—
3.4
3.8
—
3.3
3.7
—
3.2
3.6
—
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
No.
36
37
—
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
40
41
—
40
41
—
40
41
42
41
42
—
41
42
—
42
—
—
42
—
—
42
—
—
Press
3.2
3.5
—
3.4
3.8
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.3
3.6
—
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
—
3.2
3.4
3.8
3.3
3.7
—
3.2
3.6
—
3.5
—
—
3.4
—
—
3.3
—
—
No.
36
37
—
36
37
—
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
39
40
41
40
41
—
40
41
42
41
42
—
41
42
—
41
42
—
42
—
—
Press
3.3
3.7
—
3.2
3.5
—
3.4
3.8
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
3.8
3.2
3.4
3.6
3.3
3.5
—
3.2
3.4
3.8
3.3
3.7
—
3.2
3.6
—
3.2
3.5
—
3.4
—
—
No.
36
37
—
36
37
—
36
37
—
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
39
40
41
40
41
—
40
41
42
41
42
—
41
42
—
41
42
—
Press
3.4
3.8
—
3.3
3.6
—
3.2
3.5
—
3.4
3.8
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6
—
3.2
3.4
3.8
3.4
3.7
—
3.3
3.6
—
3.2
3.5
—
No.
36
—
—
36
37
—
36
37
—
36
37
—
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
39
40
41
40
41
—
40
41
42
41
42
—
41
42
—
Press
3.5
—
—
3.4
3.8
—
3.3
3.6
—
3.2
3.5
—
3.4
3.7
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
—
No.
35
36
—
36
—
—
36
37
—
36
37
—
36
37
—
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
39
40
41
40
41
—
40
41
42
41
42
—
Press
3.2
3.6
—
3.5
—
—
3.4
3.7
—
3.3
3.6
—
3.2
3.5
—
3.4
3.7
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
No.
34
35
36
35
36
—
36
—
—
36
37
—
36
37
—
36
37
38
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
39
40
41
40
41
—
40
41
—
Mnfld
Press
3.2
3.3
3.7
3.2
3.6
—
3.5
—
—
3.4
3.7
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6
—
3.2
3.5
—
Orf.
No.
34
35
—
34
35
36
35
36
—
36
37
—
36
37
—
36
37
—
36
37
38
37
38
—
37
38
—
37
38
39
38
39
—
38
39
40
38
39
40
39
40
—
39
40
41
39
40
41
40
41
—
Mnfld
Press
3.3
3.4
—
3.2
3.3
3.7
3.2
3.6
—
3.5
3.8
—
3.4
3.7
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
—
3.2
3.5
3.8
3.4
3.7
—
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6
—
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6
—
b. Insert funnel into tube and pour 1 quart of water into tube.
This should overfill the trap and flow into an open drain.
c. Reconnect drain tube to bottom of inducer housing.
2. Purge gas lines.
If not previously done, purge the lines after all connections have
been made and check for leaks.
Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition for the
purpose of checking leakage. Use a soap-and-water solution
to check for leakage. Failure to follow this warning could
result in a fire, explosion, personal injury, or death.
3. Furnace Operation
Follow procedures on operating instruction label attached to
furnace. With furnace operating, set thermostat below room
temperature and observe that furnace goes off. Set thermostat
above room temperature and observe that furnace restarts.
ADJUSTMENTS
NOTE: Do not use the Carrier orifice calculator for this unit—the
orifice K-factor for this unit is different.
1. Set gas input rate.
There are 2 methods of adjusting gas input rate. The preferred
method is by using Table 8 and following instructions in item a.
The second method is by clocking the gas meter and following
instructions in item b. Item b must be used for altitudes above 2000
ft.
a. Determine natural gas orifice size and manifold pressure
for correct input by using Table 8. Adjust manifold
pressure per item c.
12
Page 13
(1.) Obtain average yearly heat value for local gas supply.
(2.) Obtain average yearly specific gravity for local gas
supply.
(3.) Verify the furnace model. Table 8 can only be used for
model 58EJB Furnaces.
(4.) Find natural gas heat value and specific gravity in
Table 8.
(5.) Follow heat value line and specific gravity line to
point of intersection to find orifice size and manifold
pressure settings for proper operation at given natural
gas condition.
(6.) Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.
EXAMPLE: Heat value 1025 Btu/cu ft
Specific gravity of 0.62
Therefore, Orifice No. 41,
Manifold pressure 3.5-in. wc
The furnace is shipped with No. 42 orifices. In this example
all main burner orifices must be changed and manifold
pressure must be adjusted.
(1.) Remove burner enclosure front and cap that conceals
adjustment screw for gas valve regulator. (See Fig.
14.)
(2.) Turn adjusting screw either counterclockwise (out) to
decrease input rate or clockwise (in) to increase rate.
When adjusting input rate, DO NOT set manifold
pressure less than 3.2 or more than 3.8-in. wc for
natural gas. Make any major adjustments by changing
main burner orifices.
MANUAL
ON/OFF
MANIFOLD
PRESSURE
TAP
INLET
PRESSURE
TAP
REGULATOR
ADJUSTMENT
(7.) Proceed to item c to adjust manifold pressure.
b. Determine natural gas input rate by clocking gas meter and
adjusting manifold pressure per item c.
NOTE: Be sure all pressure tubing, combustion-air and vent
pipes, and burner enclosure plates are in place when checking
input.
(1.) Obtain average yearly heat value for local gas supply.
NOTE: Be sure heating value of gas used for calculations is
correct for your altitude. Consult local gas utility for altitude
adjustments of gas heating value.
(2.) Turn off all other gas appliances and pilots.
(3.) Start furnace and let it run for 3 minutes.
(4.) Measure time (in sec) for gas meter test dial to
complete 1 revolution.
(5.) Refer to Table 9 for cubic ft of gas per hr.
(6.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu
ft). Obtain heating value from local gas utility.
EXAMPLE: Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1070 Btu/cu ft
Time for 1 revolution of 2 cu ft dial = 72 sec
Gas rate = 100 cu ft/hr (from Table 9)
Btu heating input = 100 X 1070 = 107,000 Btuh
(7.) Measured gas input must not exceed gas input on unit
rating plate.
NOTE: High altitude—Gas input on rating plate is for altitudes
up to 2000 ft. Ratings for altitudes over 2000 ft must be 4 percent
less for each 1000 ft above sea level. To obtain the adjusted
altitude rating, adjust the manifold pressure, item c, and replace the
main burner orifices as needed. Refer to NFGC Appendix F, Table
F-4 for proper orifice sizing at high altitudes.
(8.) Proceed to item c to adjust manifold pressure.
c. Adjust gas input.
NOTE: The gas meter must always be clocked with the burner
enclosure front installed. The gas valve has been nominally set at
3.5-in. wc for natural gas.
A91219
Fig. 14—Redundant Automatic Gas Valve
DO NOT redrill orifices. Improper drilling (burrs, out-ofround holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of the burners and heat exchangers, causing
failures.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check the orifice hole with the correct size
numbered drill bit. Never redrill an orifice. A burr-free and
squarely aligned orifice hole is essential for proper flame characteristics.
(3.) Replace burner enclosure plates and measure adjusted
gas input rate using method outlined in item b.
(4.) Replace cap that conceals gas valve regulator adjust-
ment screw.
Be sure burner enclosure front is in place after adjustments
have been made.
d. Look through sight glass in burner enclosure and check
burner flame. The main burner flame should be clear blue,
almost transparent. (See Fig. 15.)
2. Set temperature rise.
The furnace must not be operated outside the range of temperature
rise specified on the unit rating plate. Determine the air temperature rise as follows.
a. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not "see" heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
13
Page 14
BURNER FLAMEPILOT FLAME
BURNER
MANIFOLD
Fig. 15—Burner Flame
Table 9—Gas Rate Cu Ft/Hr
SECONDS
FOR 1
REVOLUTION
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
SIZE OF TEST DIAL
1
cu ft2cu ft5cu ft
360
720
655
600
555
514
480
450
424
400
379
360
343
327
313
300
288
277
267
257
248
240
232
225
218
212
206
200
195
189
185
180
176
172
167
164
160
157
153
150
147
1800
1636
1500
1385
1286
1200
1125
1059
100
947
900
857
818
783
750
720
692
667
643
621
600
581
563
545
529
514
500
486
474
462
450
439
429
419
409
400
391
383
375
367
327
300
277
257
240
225
212
200
189
180
171
164
157
150
144
138
133
129
124
120
116
113
109
106
103
100
97
95
92
90
88
86
84
82
80
78
76
75
73
SECONDS
FOR 1
REVOLUTION
50
51
52
53
54
55
56
57
58
59
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
116
120
c. Adjust temperature rise by adjusting blower speed. Increase
blower speed to reduce temperature rise. Decrease blower
speed to increase temperature rise.
SIZE OF TEST DIAL
1
cu ft2cu ft5cu ft
72
144
71
141
69
138
68
136
67
133
65
131
64
129
63
126
62
124
61
122
60
120
58
116
56
112
54
109
53
106
51
103
50
100
48
47
46
45
44
43
42
41
40
39
38
38
37
36
35
35
34
33
33
32
31
30
A84076
97
95
92
90
88
86
84
82
80
78
76
75
74
72
71
69
68
67
65
64
62
60
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
164
161
155
150
Disconnect the electrical power before changing the speed
tap. Failure to follow this warning could result in personal
injury.
d. To change motor speed taps, remove the motor tap lead and
relocate it on the desired terminal on the plug in terminal
block/speed selector located at the blower motor. (See
Table 10.)
Table 10—Blower Speed Selection
SPEEDTAP NO.
Common1
High2
Medium3
Low4
Recheck the temperature rise. It must be within limits
specified on the unit rating plate. Recommended operation is
at midpoint of rise or above.
3. Set thermostat heat anticipator.
The thermostat heat anticipator must be set to match the amp draw
of the components in the R to W circuit. Accurate amp draw
measurements can be obtained at the thermostat subbase terminals
R and W.
Fig. 16 illustrates an easy method of obtaining these measurements. The amp reading should be taken after the blower motor has
started. See the thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying the heating cycle length.
The control shuts off the combination control system and energizes
EXAMPLE:
the circulating-air blower motor if the furnace overheats.
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
FROM UNIT 24-VOLT
TERMINAL BLOCK
= 0.5 AMPS FOR THERMOSTAT SETTING
The recommended method of checking this limit control is to
gradually block off the return air after the furnace has been
operating for a period of at least 5 minutes. As soon as the limit
control has shut off the burners, the return-air opening should be
unblocked to permit normal air circulation. By using this method
to check the limit control, it can be established that the limit is
functioning properly and will operate if there is a restricted
circulating-air supply or motor failure. If the limit control does not
function during this test, the cause must be determined and
corrected.
This control ensures the condensate drain is open to allow
condensate flow and that combustion air is flowing through the
unit prior to starting the ignition cycle. The blocked drain safety
switch has only 1 tube connected to it. Check switch operation as
follows.
a. Place unit into operation with burners on.
b. Pinch off tube leading to pressure switch P2. The burners
should shut off.
c. Release the restriction on tube and furnace should begin an
ignition trial.
d. If burners do not shut off, determine reason pressure switch
did not function properly and correct condition.
CHECKLIST
1. Put away tools and instruments. Clean up debris. Verify that
blower and control access panels are properly installed.
2. Cycle test furnace with room thermostat.
3. Check operation of accessories per manufacturer’s instructions.
4. Review User’s Manual with owner.
5. Leave literature packet near furnace.
15
Page 16
N1
N2
CIRCULATION
FAN
HI
MED
LOW
50, 75
100,125
HEAT
M2
FOR 75, 100, 125
115 VAC 1 0 60 HZ POWER SUPPLY
(FUSED DISCONNECT ON HOT LEG)
GND
BI
L1(H)L2(N)
COOL
K1K2
K2
S1
N3D1
K3
N4
C
INDUCER MOTOR
TRANSFORMER
24VAC
(115 VAC)
X
S2
CONDENSING
UNIT
ST912081005
ELECTRONIC
CN23-1
RYC
FAN TIMER
CN23-6
LIMIT
CONTROL
TSTAT
PILOT
CN23-2
GAS VALVE
HONEYWELL VR8204
G
W
GNO
MVPV
MV\PV
PS1 PS2 V1
N.O.N.C.
CN23-3CN23-5
COM.
ROS
24V (GNO)
GNO (BURNER)
MVMV\PV PV
24V
PRESSURE SW.
IGNITION MODULE
HONEYWELL S8600
SPARK
OR 8660
A91349
with orange wire nuts.
and local codes.
replaced, it must be replaced with wiring material having a temperature
rating of at least 185 C and be a minimum of 16 GA. AWG copper
strand wire.
a temperature rise within the range specified on the rating plate.
Connect unused motor leads to the "M1 & M2" terminals.
(1) Make field power supply connections to black and white wires capped
(2) WARNING --- Unit must be grounded. Wiring must conform to N.E.C.
(3) If any of the original wire, as supplied with the furnace, must be
(4) Connect required motor lead to heat terminal on circuit board to deliver
NOTES:
LIMIT
LPROS
BLACK
BLUE
BROWN
BK
BL
BR
LEGEND
PRINTED CIRCUIT
BOARD WIRING
FACTORY WIRING
LINE Y
24 V
PRESSURE SWITCH
ROLL OUT SWITCH
BLOWER INTERLOCK
CONDENSING UNIT
BI
CU
GREEN
ORANGE
RED
RED/BLACK STRIPE
VIOLET
WHITE
YELLOW
GR
OR
RD
RD/BK
VI
WH
YL
FIELD WIRING
VI
POWER SUPPLY
115 VAC 10 60 HZ
(FUSED DISCONNECT
ON HOT LEG)
L1 (H)
L2 (N)
GND
RD
BI
ORANGE WIRE NUTGROUND
ROSP
L
I.D.
OR
150 SEC
DELAY OFF SCREW SETTINGS
60 SEC 90 SEC 120 SEC
BLOWER
VI
BK
S8600
BK
BR
VI
SPARK
IS
TH-W (OPT)
24V
24V (GNO)
GNO (BURNER)
PV
MV/PV
MV
T
CAP.
BR
INDOOR
BLOWER
MOTOR
1 2 3 4 5 6 789
WHBL
L
RD/
3 4
M
H
2
C
1
G.V.
MV/PV
PV
MV
GR
BK
YL
GND
BL
OR
Fig. 17—Wiring Diagram
PILOT
HONEYWELL
1 2 3 4D1
L
O
S
O
C
1 2 3 4 5 6
T
A
E
H
M1 M2
SELECT
DELAY OFF
A B
M3
LEADS
MOTOR
UNUSED
100, 125K INPUT
50, 75K INPUT
BK
RD
BK
CU
R Y WG
GHCOYR
BL
YL
X X Y
YL
C C
BC
WH
WH
BK
Copyright 1994 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 4623145001c
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101Catalog No. 535-869Printed in U.S.A.Form 58EJB-1SIPg 162-94Replaces: 58EJA-3SI
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.