50XT
Infinity 15t SEER Single---Packaged Heat Pump System
with Puronr (R---410A) Refr ige rant
Single Phase
2---5 Nominal Tons (Sizes 024 --- 060)
Product Data
Comfort Heat Pump System with IdealHumidityt featuring
Infinityt control variable--speed blower motor and two--stage
cooling and heating that provides greater comfort, humidity
control, and energy efficiency.
Variable-- speed blower motors provide better comfort and energy
efficiency. You can expect up to 30 times better dehumidification;
economical constant airflow which provides improved indoor air
quality and more even temperatures from room to room; and
reduced indoor noise due to lower air velocity. In addition, you’ll
realize improved installation flexibility with 3 different airflow
choices for best overall comfort.
Easy installation
Factory-- assembled package is a compact, fully self-- contained heat
pump unit that is pre-- wired, pre--piped, and pre--charged for
minimum installation expense. 50XT units are available in a
variety of standard capacity ranges. Units install easily on a rooftop
or at ground level.
Durable, dependable components
Compressors have two stages of cooling and heating and are
designed for high efficiency. Each compressor is hermetically
sealed against contamination to help promote longer life and
dependable operation. Vibration isolation provides quiet operation.
A05307
Fig. 1 -- Unit 50XT
Single--Packaged Products with energy--saving features and
®
refrigerant.
Puron
S Up to 15.5 SEER
S Up to 8.0 HSPF
S Up to 12 EER at 95°F(35°C) OD
S Low Sound Levels
S Variable--Speed Blower (Standard)
S Factory--Installed TXV
S Two--stage cooling and heat pump operation
FEATURES/BENEFITS
One--piece Heat Pump unit with optional electric heater, low
installation cost, dependable performance and easy maintenance.
Efficient operation
High--efficiency design with SEERs (Seasonal Energy Efficiency
Ratio) of up to 15.5.
®
Puron
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems
proving highly reliable, environmentally sound performance.
environmentally-- sound refrigerant is Carrier’s unique
Compressors have internal high-- pressure and overcurrent
protection.
Convertible du ct configuration
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
downflow with two duct covers (available as an accessory).
Downflow operation is easily provided in the field to allow vertical
ductwork connections. The basepan utilizes knockout style seals
on the bottom openings to ensure a positive seal in the horizontal
airflow mode.
Direct-- drive, variable--speed blower motor is standard on all
50XT models.
Direct--drive, PSC condenser fan motors are designed to help
reduce energy consumption and provide for cooling operation
downto55°F (12.7°C) outdoor temperature. Low--ambient
cooling is available below 55°F (12.7°C) when low-- ambient
cooling is enabled in the User Interace (UI). Motormaster
low--ambient kit is not required.
Infinityt User Interface is designed to work as a system with
Carrier’s single--packaged product.
Refrigerant system is designed to provide dependability. Liquid
refrigerant filter driers are used to promote clean, unrestricted
operation. Each unit leaves the factory with a full Puron refrigerant
charge. Refrigerant service connections make checking operating
pressures easier.
Indoor and outdoor coils are computer designed for optimum
heat transfer and cooling efficiency. The indoor coil is fabricated
from copper tube and aluminum fins and is located inside the unit
®
II
1
for protection against damage. The outdoor coil is internally
mounted on the top tier of the unit. Copper fin coils and pre-- coated
fin coils are available from the factory by special order. These coils
are recommended in applications where aluminum fins are likely to
be damaged due to corrosion. They are ideal for seacoast
applications.
Thermostatic expansion valve (TXV) —A hard-- shutoff, balance
port TXV maintains a constant superheat at the evaporator exit
(cooling cycle) resulting in higher overall system efficiency.
High-- and low--pressure switches give added safety and
reliability to the compressor.
Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 75 dBA.
Easy to service cabinets provide easy single--panel accessibility to
serviceable components during maintenance and installation. The
basepan, with integrated drain pan, provides easy ground level
installation with or without a mounting pad. Convenient handholds
are provided to manipulate the unit on the job site. A nesting
feature ensures a positive basepan to roof curb seal when the unit is
roof mounted. A convenient 3/4--in. wide perimeter flange makes
frame mounting on a rooftop easy.
Louvered grille provides hail and vandalism protection for the
coil.
Cabinets are constructed of heavy--duty, phosphated, zinc--coated,
pre--painted steel capable of withstanding 500 hrs of salt spray.
Interior surfaces of the evaporator and electric heater compartments
are insulated with cleanable, semi-- rigid insulation board, which
keeps the conditioned air from being affected by the outdoor
ambient temperature and provides improved indoor air quality.
(Conforms to American Society of Heating, Refrigeration and Air
Conditioning Engineers No. 62P.) The sloped drain pan minimizes
standing water in the unit, which is provided with an external
drain.
Short--cycling protection for the compressor is incorporated into
our Infinity heat pump/air conditioner dual capacity control board
ensuring a five--minute delay before restarting compressor after
shutdown for any reason.
Limited Warranty—Standard 5--year limited warranty on all parts
and10--yearlimitedwarrantyoncompressor.
} Rated in accordance with U.S. Government DOE (Department of Energy) test procedures a nd/or ARI Standards 210/240.
** Tested in accordance with ARI Standard 270 ---95 (not listed in ARI).
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:
Cooling Standard: 80°F (26.6°C) db, 67°F (19.4°C) wb indoor entering ---air temperature and 95°F(35°C) db outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
LEGEND
dBA—Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP—Coefficient of Performance
HSPF—Heating Season Performance Factor
Motor HP (RPM)1/8 (825)1/8 (825)1/8 (825)1/8 (825)1/4 (1100)1/3 (1110)
INDOOR COIL
Rows…Fins/in.3…173…173…173…173…174…17
50XT
Face Ar ea ( sq. ft.)3.73.74.74.75.75.7
INDOOR FAN
Nominal Airflow (Cfm)
ComfortVariable based on Comfort Settings (see User Interface instruction s for more information).
Efficiency7008751050122514001750
Max80010001200140016002000
L O S S --- OF --- C H A R G E / L O W --- P R E S S U R E S W I T C H
(Liquid Line) (psig)
Cutout23 ± 5
Reset (Auto)55 ± 5
RETURN ---AIR FILTERS Throwaway (in.)*
*Recommended filter sizes for field---installed air filter grilles mounted on th e wall or ceiling of the conditioned structure. Required filter sizes shown are based
on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or
450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. WC.
NOTE: Tested in accordance with ARI Standard 270 --- 95 (not listed in ARI).
STANDARD
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
4
OPTIONS AND ACCESSORIES
Factory--installed options
Coil options include tin--plated* indoor hairpins, copper/copper
and vinyl--coated construction for refrigerant coils. Units are
shipped standard with copper tube/aluminum fin construction. See
model number nomenclature for coil options.
*Tin--plated indoor coils are built with special hairpins that are
designed to resist both general pitting corrosion and excessive
indoor corrosion (Formicary Corrosion).
Field--installed accessories
Manual Air Damper (25% open)
Electric Heaters
Filter Rack
Flat Roof Curbs (8--in. and 14--in.) (203 mm and 256 mm)
Square--to--Round Duct Transition Kit
Infinityt User Interface
Crankcase Heater
Lifting Kit
Compressor Hard Start Kit
Manual outside air damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Electric heaters provide additional heat in the unit when required.
Each package has a heater module that slides into the controls
Electric Heaters
CATALOG
ORDERING NO.
CPHEATER080A003.8 / 5.0NO1XXX
CPHEATER081A003.8 / 5.0YES1XXX
CPHEATER083A005.4 / 7.2YES1XXXXXX
CPHEATER085A007.5 / 10.0YES1XXXXXX
CPHEATER087A0011.3 / 15.0YES2XXXXX
CPHEATER089A0015.0 / 20.0YES2XXX
NOTE
Electric heaters are rated at 240v. Refer to Multiplication Factors table for oth er voltages.
X=Approved combination
NOMINAL
CAPACITY
(kW)FUSEDSTAGES243036424860
208/240 — SING LE PHASE (60 Hz)
compartment. Heater sizes range from 5.0 to 20.0 kW. The electric
heater design allows the use of a single--point power supply for the
entire unit, resulting in lower installed costs.
Flat roof curbs in both 8 in. (203 mm) and 14 in. (256 mm) sizes
are available for roof mounted applications.
Square--to-- round duct transition kit enables 024-- 048 size units
to be fitted to 14 in. round ductwork.
Infinity User Interface coupled with the system’s variable--speed
indoor blower delivers Carrier’spatentedIdealHumidity
technology that allows for even greater humidity control. Along
with more precisely controlling temperature and humidity, the
Infinity User Interface offers full seven--day programmability
allowing you to further customize your comfort and energy
savings.
Lifting kit includes 4 metal brackets that are available to assist in
lifting this product onto a roof application.
Crankcase heaterprovides anti--floodback protection for
low--load cooling applications.
Filter rackfeatures easy installation, serviceability, and
high--filtering performance for vertical or horizontal applications.
Compressor hard start kitassists compressor start--up by
providing additional starting torque on single phase units and
prolongs compressor motor life.
USED WITH SIZES
50XT
5
FILTER RACK
EVAPORATOR
COIL
50XT
BEND FLANGE AT 90°-SCREW TO
DIVIDER WITH 1-IN. SCREW
6. When unit mounting screw is used ( see Note A), a retainer br acket must be used as well. This bracket must also be used when required by code for hurricaneorseismic
conditions. This bracket is available through Micrometl.
A05308
G
IN. (MM)
9
50XT SUGGESTED RIGGING
DETAIL
A
-in. (914 mm)
A06296
A06298
SELECTION PROCEDURE
Determine cooling and heating requirements at design
conditions
Given:
REQUIRED COOLING CAPACITY (TC)34,500 BTUH......
SENSIBLE HEAT CAPACITY (SHC)24,000 BTUH.........
REQUIRED HEATING CAPACITY (SHC)36,000 BTUH.....
CONDENSER ENTERING AIR TEMPERATURE 95°F(35°C)
INDOOR--AIR TEMPERATURE80°F (26.6°C) EDB, 67°F...
(19.4°C) EWB
EVAPORATOR AIR QUANTITY1200 CFM...............
ELECTRICAL CHARACTERISTICS230--1--60.............
Select unit based on required cooling capacity
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F(35°C). The 036 unit at 1200 cfm and 67°F
(19.4°C) ewb (entering wet bulb) will provide a total capacity of
34,600 Btuh and a SHC of 24,220 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
CABINETMODEL
Small
Large
NOTE: See dimensional drawing for corner weight distribution. Corner
weights shown on drawing are based on unit--- only weights and do
not include packaging.
Enter the Electric Heater table on page 5 for 208/230v,
single--phase, unit. The 7.2--kW heater at 240v most closely
satisfies the heating required. To calculate kW at 230v, multiply the
heater kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 29.
7.2 kW x 0.92 = 6.6 kW
6.6 kW x 3414 Btuh/kW = 22,532 Btuh
Total unit heating capacity is 39,342 Btuh
(16,810 + 22,532).
Select unit that corresponds to power source available
The Electrical Data table shows that the unit is designed to operate
at 208/230--1--60.
Select electric heat
Enter the 036 unit Heating Extended Performance table at 1200
cfm. At 70°F (21.1°C) return indoor air and 20°F(--6.6°C) air
entering outdoor coil, the integrated heating capacity is 16,810
Btuh. (Select integrated heating capacity value since deductions for
outdoor--coil frost and defrosting have already been made. No
correction is required.)
The required heating capacity is 36,000 Btuh. Therefore, at least
19,190 Btuh additional electric heat is required.
Determine additional electric heat capacity in kW.