Carrier 50XT User Manual

50XT Infinity 15t SEER Single---Packaged Heat Pump System with Puronr (R---410A) Refr ige rant Single Phase 2---5 Nominal Tons (Sizes 024 --- 060)
Product Data
Comfort Heat Pump System with IdealHumidityt featuring Infinityt control variable--speed blower motor and two--stage
cooling and heating that provides greater comfort, humidity control, and energy efficiency.
Variable-- speed blower motors provide better comfort and energy efficiency. You can expect up to 30 times better dehumidification; economical constant airflow which provides improved indoor air quality and more even temperatures from room to room; and reduced indoor noise due to lower air velocity. In addition, you’ll realize improved installation flexibility with 3 different airflow choices for best overall comfort.
Easy installation
Factory-- assembled package is a compact, fully self-- contained heat pump unit that is pre-- wired, pre--piped, and pre--charged for minimum installation expense. 50XT units are available in a variety of standard capacity ranges. Units install easily on a rooftop or at ground level.
Durable, dependable components
Compressors have two stages of cooling and heating and are
designed for high efficiency. Each compressor is hermetically sealed against contamination to help promote longer life and dependable operation. Vibration isolation provides quiet operation.
A05307
Single--Packaged Products with energy--saving features and
®
refrigerant.
Puron
S Up to 15.5 SEER S Up to 8.0 HSPF S Up to 12 EER at 95°F(35°C) OD S Low Sound Levels S Variable--Speed Blower (Standard) S Factory--Installed TXV S Two--stage cooling and heat pump operation

FEATURES/BENEFITS

One--piece Heat Pump unit with optional electric heater, low installation cost, dependable performance and easy maintenance.
Efficient operation
High--efficiency design with SEERs (Seasonal Energy Efficiency
Ratio) of up to 15.5.
®
Puron
refrigerant designed to help protect the environment. Puron is an HFC refrigerant which does not contain chlorine that can harm the ozone layer. Puron refrigerant is in service in millions of systems proving highly reliable, environmentally sound performance.
environmentally-- sound refrigerant is Carrier’s unique
Compressors have internal high-- pressure and overcurrent protection.
Convertible du ct configuration
Unit is designed for easy use in either downflow or horizontal applications. Each unit is easily converted from horizontal to downflow with two duct covers (available as an accessory). Downflow operation is easily provided in the field to allow vertical ductwork connections. The basepan utilizes knockout style seals on the bottom openings to ensure a positive seal in the horizontal airflow mode.
Direct-- drive, variable--speed blower motor is standard on all 50XT models.
Direct--drive, PSC condenser fan motors are designed to help reduce energy consumption and provide for cooling operation downto55°F (12.7°C) outdoor temperature. Low--ambient cooling is available below 55°F (12.7°C) when low-- ambient cooling is enabled in the User Interace (UI). Motormaster low--ambient kit is not required.
Infinityt User Interface is designed to work as a system with Carrier’s single--packaged product.
Refrigerant system is designed to provide dependability. Liquid refrigerant filter driers are used to promote clean, unrestricted operation. Each unit leaves the factory with a full Puron refrigerant charge. Refrigerant service connections make checking operating pressures easier.
Indoor and outdoor coils are computer designed for optimum heat transfer and cooling efficiency. The indoor coil is fabricated from copper tube and aluminum fins and is located inside the unit
®
II
1
for protection against damage. The outdoor coil is internally mounted on the top tier of the unit. Copper fin coils and pre-- coated fin coils are available from the factory by special order. These coils are recommended in applications where aluminum fins are likely to be damaged due to corrosion. They are ideal for seacoast applications.
Thermostatic expansion valve (TXV) —A hard-- shutoff, balance port TXV maintains a constant superheat at the evaporator exit (cooling cycle) resulting in higher overall system efficiency.
High-- and low--pressure switches give added safety and reliability to the compressor.
Low sound ratings ensure a quiet indoor and outdoor environment with sound ratings as low as 75 dBA.
Easy to service cabinets provide easy single--panel accessibility to serviceable components during maintenance and installation. The basepan, with integrated drain pan, provides easy ground level installation with or without a mounting pad. Convenient handholds are provided to manipulate the unit on the job site. A nesting feature ensures a positive basepan to roof curb seal when the unit is
roof mounted. A convenient 3/4--in. wide perimeter flange makes frame mounting on a rooftop easy.
Louvered grille provides hail and vandalism protection for the coil.
Cabinets are constructed of heavy--duty, phosphated, zinc--coated, pre--painted steel capable of withstanding 500 hrs of salt spray. Interior surfaces of the evaporator and electric heater compartments are insulated with cleanable, semi-- rigid insulation board, which keeps the conditioned air from being affected by the outdoor ambient temperature and provides improved indoor air quality. (Conforms to American Society of Heating, Refrigeration and Air Conditioning Engineers No. 62P.) The sloped drain pan minimizes standing water in the unit, which is provided with an external drain.
Short--cycling protection for the compressor is incorporated into our Infinity heat pump/air conditioner dual capacity control board ensuring a five--minute delay before restarting compressor after shutdown for any reason.
Limited Warranty—Standard 5--year limited warranty on all parts and10--yearlimitedwarrantyoncompressor.
50XT

TABLE OF CONTENTS

FEATURES/BENEFITS 1--2.......................................................................................
MODEL NUMBER NOMENCLATURE 3...........................................................................
ARI CAPACITIES 3.............................................................................................
PHYSICAL DATA 4.............................................................................................
OPTIONS AND ACCESSORIES 5--6...............................................................................
BASE UNIT DIMENSIONS 7--8...................................................................................
ACCESSORY DIMENSIONS 9....................................................................................
SELECTION PROCEDURE 10....................................................................................
PERFORMANCE DATA 11--30....................................................................................
TYPICAL PIPING AND WIRING 31...............................................................................
APPLICA TION DATA 32.........................................................................................
ELECTRICAL DATA 33.........................................................................................
TYPICAL WIRING SCHEMATICS 34..............................................................................
CONTROLS 35.................................................................................................
GUIDE SPECIFICATIONS 36-- 37..................................................................................
2

MODEL NUMBER NOMENCLATURE

50XT 0 1024 3
– – –
– –
Options
Type of Unit
50XT - Packaged Electric Heat Pump
BT - AL evap, vinyl condens CC - AL evap, CU condens CU - CU evap & condens TP - Base unit with tin plated
indoor coil hairpins
Nominal Cooling Capacity 024 - 2 Ton 030 - 2.5 Ton 036 - 3 Ton 042 - 3.5 Ton
TV - TP with vinyl coating on outdoor coil TC - TP with AL indoor coil and
CU/CU outdoor coil
Only used if ordering an option
048 - 4 Ton 060 - 5 Ton
Packaging
N/A
LEGEND AL - Aluminum
Series
Electrical Supply
3- 208/230-1-60
CU - Copper

ARI* CAPACITI ES

Cooling Capacities and Efficiencies
UNIT
50XT
024 2 800 / 600 22,600 / 17,600 11. 4 15.5 030 2--1/2 1000 / 700 28,600 / 21,400 11. 6 15.0 036 3 1200 / 850 34,600 / 24,400 12 15.0 042 3--1/2 1500 / 975 40,500 / 29,000 11. 6 15.0 048 4 1600 / 1100 46,000 / 33,400 11 15.0 060 5 1750 / 1200 57,000 / 40,500 11 14.5
NOMINAL
TONS
STANDARD CFM (High/Low Stage)
(Cooling & Heating)
NET COOLING CAPACITIES (Btuh)
(High/Low Stage)
EER @A{
50XT
SEER‡
Heating Capacities and Efficiencies
UNIT
50XT
024 20,800 / 16,800 3.3 / 3.2 11,600 / 8,400 2.2 / 1.8 8.0 030 27,600 / 20,400 3.5 / 3.5 14,000 / 9,600 2.1 / 1.9 8.0 036 33,600 / 23,000 3.4 / 3.4 17,200 / 11,200 2.4 / 1.7 8.0 042 39,500 / 27,600 3.6 / 3.5 20,600 / 14,200 2.3 / 2.0 8.0 048 45,500 / 32,200 3.3 / 3.5 25,000 / 15,200 2.4 / 1.9 8.0 060 56,000 / 39,500 3.2 / 3.3 30,800 / 20,400 2.2 / 1.9 8.0
{ ”A” conditions---80°F ( 26.6°C) indoor db/67°F (19.4°C) indoor wb & 95°F(35°C) outdoor db.
} Rated in accordance with U.S. Government DOE (Department of Energy) test procedures a nd/or ARI Standards 210/240.
** Tested in accordance with ARI Standard 270 ---95 (not listed in ARI).
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80°F (26.6°C) db, 67°F (19.4°C) wb indoor entering ---air temperature and 95°F(35°C) db outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
LEGEND dBA—Sound Levels (decibels) db—Dry Bulb SEER—Seasonal Energy Efficiency Ratio wb—Wet Bulb COP—Coefficient of Performance HSPF—Heating Season Performance Factor
HIGH HEAT CAPACITY
(BTUH) @ 47°F(8.3°C)
(High/Low Stage)
HIGH HEAT COP
@47°F(8.3°C)
(High/Low Stage)
LOW HEAT CAPACITY
(BTUH) @ 17°F(--8.3°C)
(High/Low Stage)
3
LOW HEAT COP
@17°F(--8.3°C)
(High/Low Stage)
HSPF‡

PHYSICAL DATA

UNIT SIZE 024 030 036 042 048 060
NOMINAL CAPACITY (ton) 2 2 --- 1 / 2 3 3 --- 1 / 2 4 5 OPERATING WEIGHT (lb)
COMPRESSOR Tw o --- S t a g e S c r o l l REFRIGERANT: PURON (R---410A) Quantity (lb)
EXPANSION DEVICE --- HEATING AccuRater
ORIFICE OD (in .) --- Left ORIFICE OD (in .) --- Right 0.038 0.035 0.042 0.046 0.046
EXPANSION DEVICE --- COOLING TXV
Size 2Ton 3Ton 3Ton 4Ton 4Ton 5Ton Part Nu mber EA36YD129 EA36YD139 EA36YD139 EA36YD149 EA36YD149 EA36YD159
OUTDOOR COIL
RowsFins/in. 221 221 221 221 221 221 Face Ar ea ( sq. ft.) 13.6 15.3 17.5 19.4 19.4 23.3
OUTDOOR FAN
Nominal Cfm 2700 2700 2800 2800 3300 3300 Diameter (in.)
Motor HP (RPM) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/4 (1100) 1/3 (1110)
INDOOR COIL
RowsFins/in. 317 317 317 317 317 417
50XT
Face Ar ea ( sq. ft.) 3.7 3.7 4.7 4.7 5.7 5.7 INDOOR FAN Nominal Airflow (Cfm) Comfort Variable based on Comfort Settings (see User Interface instruction s for more information). Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000
Size (in.)
Motor HP (RPM) 1/2 1/2 3/4 3/4 3/4 1
HIGH--- PRESSURE SWITCH (psig)
Cutout 670 ± 10
Reset (Auto) 470 ± 25
HIGH--- PRESSURE SWITCH 2 (psig) (Compressor Solenoid)
Reset (Auto) 455 ± 15
L O S S --- OF --- C H A R G E / L O W --- P R E S S U R E S W I T C H
(Liquid Line) (psig)
Cutout 23 ± 5
Reset (Auto) 55 ± 5
RETURN ---AIR FILTERS Throwaway (in.)*
*Recommended filter sizes for field---installed air filter grilles mounted on th e wall or ceiling of the conditioned structure. Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. WC.
ISO 9001:2000
(mm)
(mm)
Cutout 565 ± 15
(kg)
(kg)
(mm)
405 184
10.3
4.7
0.042
22
559
10x10
254x254
20x24x1
508x610x25
435 197
11.5
5.2
0.038 0.035 0.040 0.038 0.046
22
559
10x10
254x254
464 210
9.7
4.4
22
559
11x10
279x254
24x30x1
610x762x25
476 216
14.0
6.4
22
559
11x10
279x254
492 223
15.5
7.0
22
559
11x10
279x254
24x36x1
610x914x25
535 243
16.0
7.3
22
559
11x10
279x254
REGISTERED
A--WEIGHTED SOUND POWER LEVEL (dBA)
MODEL 50XT
RATING
(dBA)
125 250 500 1000 2000 4000 8000
024 75 58.8 63.5 67.2 66.9 63.7 58.3 50.0 030 75 58.8 63.5 67.2 66.9 63.7 58.3 50.0 036 75 60.7 63.3 66.8 66.5 64.2 60.3 53.0 042 75 56.7 62.8 67.8 67.4 63.7 57.7 50.8 048 78 62.4 69.9 71.3 73.4 70.0 66.3 60.1 060 78 63.5 67.6 71.8 75.5 71.0 68.1 59.9
NOTE: Tested in accordance with ARI Standard 270 --- 95 (not listed in ARI).
STANDARD
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
4

OPTIONS AND ACCESSORIES

Factory--installed options
Coil options include tin--plated* indoor hairpins, copper/copper
and vinyl--coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomenclature for coil options.
*Tin--plated indoor coils are built with special hairpins that are designed to resist both general pitting corrosion and excessive indoor corrosion (Formicary Corrosion).
Field--installed accessories
Manual Air Damper (25% open) Electric Heaters Filter Rack Flat Roof Curbs (8--in. and 14--in.) (203 mm and 256 mm) Square--to--Round Duct Transition Kit Infinityt User Interface Crankcase Heater Lifting Kit Compressor Hard Start Kit
Manual outside air damper includes hood and filter rack with adjustable damper blade for up to 25% outdoor air.
Electric heaters provide additional heat in the unit when required. Each package has a heater module that slides into the controls
Electric Heaters
CATALOG
ORDERING NO.
CPHEATER080A00 3.8 / 5.0 NO 1 X X X
CPHEATER081A00 3.8 / 5.0 YES 1 X X X
CPHEATER083A00 5.4 / 7.2 YES 1 X X X X X X
CPHEATER085A00 7.5 / 10.0 YES 1 X X X X X X
CPHEATER087A00 11.3 / 15.0 YES 2 X X X X X
CPHEATER089A00 15.0 / 20.0 YES 2 X X X
NOTE
Electric heaters are rated at 240v. Refer to Multiplication Factors table for oth er voltages. X=Approved combination
NOMINAL
CAPACITY
(kW) FUSED STAGES 24 30 36 42 48 60
208/240 — SING LE PHASE (60 Hz)
compartment. Heater sizes range from 5.0 to 20.0 kW. The electric heater design allows the use of a single--point power supply for the entire unit, resulting in lower installed costs.
Flat roof curbs in both 8 in. (203 mm) and 14 in. (256 mm) sizes are available for roof mounted applications.
Square--to-- round duct transition kit enables 024-- 048 size units to be fitted to 14 in. round ductwork.
Infinity User Interface coupled with the system’s variable--speed indoor blower delivers Carrier’s patented IdealHumidity technology that allows for even greater humidity control. Along with more precisely controlling temperature and humidity, the Infinity User Interface offers full seven--day programmability allowing you to further customize your comfort and energy savings.
Lifting kit includes 4 metal brackets that are available to assist in lifting this product onto a roof application.
Crankcase heater provides anti--floodback protection for low--load cooling applications.
Filter rack features easy installation, serviceability, and high--filtering performance for vertical or horizontal applications.
Compressor hard start kit assists compressor start--up by providing additional starting torque on single phase units and prolongs compressor motor life.
USED WITH SIZES
50XT
5
FILTER RACK
EVAPORATOR COIL
50XT
BEND FLANGE AT 90°-SCREW TO DIVIDER WITH 1-IN. SCREW
TOP FILTER RACK
BOTTOM FILTER RACK
MANUAL OUTSIDE AIR DAMPER
REPLACEMENT PANEL
MANUAL OUTSIDE AIR HOOD
DAMPER BLADE
6
A06594
50XT
Fig. 2 -- 50XT024-- 030 Unit Dimensions
7
A06595
50XT
Fig. 3 -- 50XT036-- 060 Unit Dimensions
8

ACCESSORY DIMENSIONS

HVAC unit
base
Scre w
(NO TE A)
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
*Provided with roof curb
Gask eting
inner flange*
Wood nailer*
Roof curb*
Insulation (field
supplied)
Ductwork
field supplied
Roof
Roof Curb for Small Cabinet
Note A: When unit mounting scre w is used,
retainer bra cke t must also be used.
HVAC unit
Scre w
(NOTE A)
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
*Provided with roof curb
base
Gask eting
inner flange*
Ductwork
field supplied
Wood nailer*
Roof curb*
Insulation (field
supplied)
Roof
Roof Curb for Large Cabinet
Note A: When unit mounting scre w is used,
retainer bra cket must also be used.
Return opening
(B X C)
UNIT SIZE
024--030
036--060
E
Supply opening
G
F
B Typ.
C Typ.
(B x C)
D
R/A
A
Short
Insulated deck pan
CATALOG
NUMBER
Support
A
IN. (MM)BIN. (MM)
Support
Long
CPRFCURB006A00 8 (203) 11 (279) 16--1/2 (419) 28--3/4 (730) 30--3/8 (771) 44--5/16 (1126) 45 --15/16 (1167) CPRFCURB007A00 14 (356) 11 (279) 16--1/2 (419) 28--3/4 (730) 30--3/8 (771) 44--5/16 (1126) 45 --15/16 (1167) CPRFCURB008A00 8 (203) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41 --15/16 (1065) 44--7/16 (1129) 46--1/16 (1169) CPRFCURB009A00 14 (356) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41 --15/16 (1065) 44--7/16 (1129) 46--1/16 (1169)
E
C
IN. (MM)
D
Insulated deck pan
D
IN. (MM)
Gask et around
outer edge
IN. (MM)
G
F
Gask et around
duct
E
F
IN. (MM)
S/A
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25 mm) thick fiberglass 1 lb. density.
6. When unit mounting screw is used ( see Note A), a retainer br acket must be used as well. This bracket must also be used when required by code for hurricaneorseismic conditions. This bracket is available through Micrometl.
A05308
G
IN. (MM)
9
50XT SUGGESTED RIGGING
DETAIL
A
-in. (914 mm)
A06296
A06298

SELECTION PROCEDURE

Determine cooling and heating requirements at design conditions
Given:
REQUIRED COOLING CAPACITY (TC) 34,500 BTUH......
SENSIBLE HEAT CAPACITY (SHC) 24,000 BTUH.........
REQUIRED HEATING CAPACITY (SHC) 36,000 BTUH.....
CONDENSER ENTERING AIR TEMPERATURE 95°F(35°C) INDOOR--AIR TEMPERATURE 80°F (26.6°C) EDB, 67°F...
(19.4°C) EWB
EVAPORATOR AIR QUANTITY 1200 CFM...............
ELECTRICAL CHARACTERISTICS 230--1--60.............
Select unit based on required cooling capacity
Enter Net Cooling Capacities table at condenser entering temperature of 95°F(35°C). The 036 unit at 1200 cfm and 67°F (19.4°C) ewb (entering wet bulb) will provide a total capacity of 34,600 Btuh and a SHC of 24,220 Btuh. Calculate SHC correction, if required, using Note 4 under Cooling Capacities tables.
CABINET MODEL
Small
Large
NOTE: See dimensional drawing for corner weight distribution. Corner
weights shown on drawing are based on unit--- only weights and do not include packaging.
50XT--024 418 190 50XT--030 448 203
50XT--036 469 213 50XT--042 491 223 50XT--048 497 225 50XT--060 548 249
RIGGING WT lb kg
Enter the Electric Heater table on page 5 for 208/230v, single--phase, unit. The 7.2--kW heater at 240v most closely satisfies the heating required. To calculate kW at 230v, multiply the heater kW by multiplication factor 0.92 found in the Multiplication Factors table on page 29.
7.2 kW x 0.92 = 6.6 kW
6.6 kW x 3414 Btuh/kW = 22,532 Btuh Total unit heating capacity is 39,342 Btuh
(16,810 + 22,532).
Select unit that corresponds to power source available
The Electrical Data table shows that the unit is designed to operate at 208/230--1--60.
Select electric heat
Enter the 036 unit Heating Extended Performance table at 1200 cfm. At 70°F (21.1°C) return indoor air and 20°F(--6.6°C) air entering outdoor coil, the integrated heating capacity is 16,810 Btuh. (Select integrated heating capacity value since deductions for outdoor--coil frost and defrosting have already been made. No correction is required.)
The required heating capacity is 36,000 Btuh. Therefore, at least 19,190 Btuh additional electric heat is required.
Determine additional electric heat capacity in kW.
19,190 Btuh
3414 Btuh/kW
=5.6kWofheatrequired
10
KW
Tot al
System
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
MBtuh
Capacity
MBtuh
Capacity
KW
Tot al
System
MBtuh
Capacity
50XT
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
MBtuh
CONDENSER ENTERING AIR TEMPERATURES _F(_C)
Capacity
CONDENSER ENTERING AIR TEMPERATURES _F(_C)
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
MBtuh
Capacity
PERFORMANCE DATA--STANDARD ECM INDOOR MOTOR
Cooling Extended Performance Table
EVAPORATOR
50XT024 High Cool
75 (23.8) 85 (29.4) 95 (35) 105 (40.5) 115 (46.1) 125 (51.6)
AIR
Tot al
Capacity
Tot al
Capacity
System
MBtuh
System
MBtuh
EWB
CFM
KW
KW
Tot al Sens To ta l Sens Tot al Sens To ta l Sens Tot al Sens To ta l Sens
21.77 21.77 1.61 20.88 20.88 1.79 19.95 19.95 2.00 18.94 18.94 2.23 17.86 17.86 2.48 16.66 16.66 2.77
22.40 18.69 1.61 21.29 18.21 1.80 20.13 17.70 2.00 18.95 18.95 2.23 17.86 17.86 2.48 16.66 16.66 2.77
22.85 15.18 1.62 21.71 14.70 1.80 20.52 14.21 2.01 19.25 13.70 2.23 17.90 13.16 2.48 16.42 12.58 2.77
24.66 15.72 1.64 23.44 15.24 1.83 22.15 14.75 2.03 20.79 14.24 2.26 19.34 13.70 2.51 17.74 13.12 2.79
27.16 12.75 1.67 25.83 12.28 1.86 24.42 11. 80 2.06 22.94 11. 29 2.29 21.33 10.76 2.54 19.57 10.18 2.83
22.76 22.76 1.64 21.81 21.81 1.82 20.81 20.81 2.03 19.74 19.74 2.26 18.58 18.58 2.51 17.29 17.29 2.80
22.97 20.16 1.64 21.84 21.76 1.82 20.81 20.81 2.03 19.74 19.74 2.26 18.58 18.58 2.51 17.29 17.29 2.80
23.39 16.20 1.64 22.19 15.71 1.83 20.94 15.21 2.03 19.62 14.69 2.26 18.22 14.14 2.51 16.69 13.54 2.79
25.22 16.81 1.67 23.94 16.32 1.85 22.60 15.82 2.05 21.18 15.30 2.28 19.67 14.74 2.53 18.01 14.14 2.82
27.77 13.43 1.70 26.37 12.96 1.88 24.90 12.48 2.09 23.35 11.9 5 2.31 21.66 11. 41 2.57 20.60 11. 05 2.57
57
62
(13.9)
_F(_C)
(16.7)
63*
(17.2)
67
72
57
(19.4)
(22.2)
(13.9)
62
(16.7)
63*
(17.2)
67
72
(19.4)
(22.2)
75 (23.8) 85 (29.4) 95 (35) 105 (40.5) 115 (46.1) 125 (51.6)
Tot al
Capacity
Tot al
Capacity
System
MBtuh
System
MBtuh
EWB
KW
KW
Tot al Sens To ta l Sens Tot al Sens To ta l Sens Tot al Sens To ta l Sens
16.65 16.65 1.05 15.95 15.95 1.20 15.21 15.21 1.37 14.40 14.40 1.57 13.52 13.52 1.80 12.55 12.55 2.07
17.20 14.47 1.06 16.29 14.07 1.21 15.34 13.65 1.37 14.40 14.40 1.57 13.52 13.52 1.80 12.55 12.55 2.07
17.61 11.7 5 1.06 16.69 11 .36 1.21 15.70 10.96 1.38 14.64 10.53 1.57 13.50 10.07 1.80 12.27 9.58 2.06
19.23 12.26 1.08 18.23 11 .8 7 1.22 17.18 11. 47 1.39 16.05 11. 03 1.58 14.83 10.58 1.81 13.50 10.09 2.07
21.48 10.05 1.09 20.41 9.66 1.24 19.26 9.26 1.41 18.02 8.84 1.60 16.69 8.39 1.83 15.24 7.90 2.09
17.52 17.52 1.08 16.77 16.77 1.23 15.96 15.96 1.39 15.10 15.10 1.59 14.15 14.15 1.82 13.11 13.11 2.09
17.71 15.66 1.08 16.78 16.75 1.23 15.96 15.96 1.39 15.10 15.10 1.59 14.15 14.15 1.82 13.12 13.12 2.09
18.10 12.58 1.08 17.12 12.18 1.23 16.09 11 .7 6 1.39 14.98 11. 32 1.59 13.80 10.85 1.81 12.51 10.35 2.08
19.75 13.14 1.09 18.71 12.74 1.24 17.60 12.32 1.41 16.41 11. 88 1.60 15.14 11. 41 1.83 13.76 10.91 2.09
22.06 10.61 1.11 20.93 10.21 1.26 19.72 9.80 1.43 18.41 9.36 1.62 17.03 8.91 1.85 15.51 8.41 2.11
57
62
(13.9)
_F(_C)
(16.7)
63*
(17.2)
67
72
57
(19.4)
(22.2)
(13.9)
62
(16.7)
63*
(17.2)
67
72
(19.4)
(22.2)
AIR
700
800
50XT024 Low Cool
EVAPORATOR
CFM
525
600
See page 29 f or cooling notes.
11
KW
Tot al
System
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
50XT
Heating Capacity
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(_C)
MBtuh
Capacity
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(_C)
MBtuh
Capacity
KW
Tot al
System
MBtuh
Capacity
KW
Tot al
System
PERFORMANCE DATA--STANDARD ECM INDOOR MOTOR
50XT024 High
MBtuh
Capacity
KW
Tot al
System
-- 10 ( --23.3) 0 (-- 17.7) 10 ( --12.2) 17 (--8.3) 20 (--6.6)
MBtuh
Capacity
Tot al Integ Tot al Integ Tot al Integ Tot al Integ Tota l Integ
700 4.21 3.88 1.12 6.40 5.89 1.21 9.38 8.61 1.32 11. 90 10.85 1.42 14.22 12.90 1.45
800 4.24 3.90 1.11 6.47 5.95 1.20 9.46 8.69 1.31 11. 94 10.89 1.43 14.27 12.94 1.44
700 3.97 3.65 1.25 6.12 5.63 1.35 9.01 8.27 1.46 11. 51 10.49 1.55 12.36 11.2 1 1.49
800 4.02 3.70 1.24 6.20 5.71 1.34 9.12 8.37 1.45 11. 60 10.58 1.55 12.46 11.3 0 1.66
700 3.77 3.47 1.38 5.83 5.36 1.49 8.62 7.91 1.61 11. 03 10.06 1.70 11 .85 10.75 1.75
70
(21.1)
800 3.82 3.51 1.38 5.91 5.43 1.48 8.74 8.02 1.59 11. 17 10.19 1.69 12.00 10.88 1.72
80
(26.7)
50XT024 High Con’t.
CFM
(_C)
60
(15.6)
_F
INDOOR AIR
EDB
MBtuh
Capacity
KW
Tot al
System
30 (--1.1) 40 (4.4) 47 (8.3) 50 (10) 60 (15.5)
MBtuh
Capacity
Tot al Integ Tot al Integ Tot al Integ Tot al Integ Tota l Integ
700 16.65 14.60 1.58 19.30 19.30 1.69 21.15 21.15 1.75 22.00 22.00 1.78 25.14 25.14 1.92
800 16.84 14.76 1.53 19.36 19.36 1.61 21.27 21.27 1.66 22.16 22.16 1.70 25.40 25.40 1.82
700 16.03 14.05 1.62 18.69 18.69 1.86 20.68 20.68 1.95 21.51 21.51 1.98 24.54 24.54 2.11
800 16.25 14.24 1.68 18.95 18.95 1.79 20.80 20.80 1.85 21.65 21.65 1.87 24.82 24.82 2.00
700 14.91 13.06 1.89 17.97 17.97 2.03 20.04 20.04 2.14 20.96 20.96 2.20 23.91 23.91 2.32
CFM
(_C)
60
(15.6)
_F
INDOOR AIR
EDB
800 15.10 13.23 1.84 18.27 18.27 1.96 20.30 20.30 2.05 21.13 21.13 2.08 24.20 24.20 2.21
70
80
(21.1)
(26.7)
LEGEND
Cap.— Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db —DryBulb
kW — Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh — Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
12