Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
NOTE: Installer: Make sure the Owner's Manual and Service
Instructions are left with the unit after installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS ......................... 2
RECEIVING AND INSTALLATION ................. 2-13
Check Equipment .................................. 2
Identify Unit .................................... 2
Inspect Shipment ................................. 2
Provide Unit Support ............................... 2
Roof Curb ...................................... 2
Slab Mount ..................................... 2
Ground Mount .................................. 2
Field Fabricate Ductwork ............................ 2
Provide Clearances ................................. 2
Rig and Place Unit ................................. 7
Inspection ...................................... 7
Installation ...................................... 7
Connect Condensate Drain ........................... 8
Install Duct Connections ............................. 9
Configuring Units for Downflow (Vertical) Discharge .... 9
Install Electrical Connections ........................ 10
High-Voltage Connections ........................ 10
Special Procedures for 208-v Operation .............. 11
Control Voltage Connections ....................... 11
Easy Select _ - 50XP ............................ 11
Standard Connection ............................. 13
Transformer Protection ........................... 13
PRE-START-UP ................................... 13
START-UP ..................................... 16-17
Check for Refrigerant Leaks ......................... 16
Start-Up Cooling Section and Make Adjustments ........ 16
50XP Start-Up ................................... 16
Checking and Adjusting Refrigerant Charge ........... 16
Indoor Airflow and Airflow Adjustments ............. 17
50XP Sequence Of Operation ...................... 17
MAINTENANCE ................................ 19-22
Air Filter ........................................ 20
Evaporator Blower and Motor ........................ 20
Condenser Coil, Evaporator Coil, and Condensate
Drain Pan ....................................... 20
Condenser Fan ................................... 21
Electrical Controls and Wiring ....................... 21
Refrigerant Circuit ................................. 21
Evaporator Airflow ................................ 21
Metering Devices-TXV & AccuRater cR)Piston ........... 21
Pressure Switches ................................. 21
Loss-of-Charge/Low-Pressure (Air Conditioner Only) .... 21
High-Pressure Switches ............................ 21
Copeland Scroll Compressor (Puron cR)Refrigerant) ........ 21
Refrigerant ...................................... 22
®
Turn to the Expertg
C99064
Fig. 1 - Model 50XP
Compressor Oil ................................... 22
Servicing Systems on Roofs with Synthetic Materials ...... 22
Liquid-Line Filter Drier ............................ 22
Puron (R-410A) Refrigerant Charging ................. 22
TROUBLESHOOTING .............................. 22
START-UP CHECKLIST ............................ 22
SAFETY CONSIDERATIONS
Improper installation adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes, the
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the Canadian electrical
Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol Z_.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
The power supply (volts, phase, and hertz) must correspond to that
specified on unit rating plate.
INTRODUCTION
The 50XP units are fully self-contained, and designed for outdoor
installation (see Fig. 1). See Fig. 2 and 3 for unit dimensions. All
unit sizes have discharge openings for both horizontal and down-
flow configurations, and are factory shipped with all duct openings
covered. (]nits may be installed either on a rooftop, ground-level
cement slab, or directly on the ground if local codes permit. See
Fig. 4 for roof curb dimensions.
ELECTRICALSHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Turn off accessory heater power switch if
applicable,
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal iniury or
equipment damage.
Puron (R-410A) systems operate at higher pressures than
standard R-22 systems. DO NOT use R-22 service equipment
or components on Puron (R-410A) equipment. Ensure service
equipment is rated for Puron (R-410A).
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a water tight seal. Install gasketing material supplied
with the roof curb. Improperly applied gasketing also can result in
air leaks and poor unit performance.
Curb should be level to within 1/4 in. (6 mm) (see Fig. 8). This is
necessary for unit drain to flmction properly. Refer to accessory
roof curb installation instructions for additional information as
required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4
in. (102 mm) thick, with 2 in. (51 mm) above grade. The slab
should extend approximately 2 in. (51 mm) beyond the casing on
all 4 sides of the unit. Do not secure the unit to the slab except
when required by local codes.
GROUND LEVEL
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground
prepared with gravel for condensate discharge.
Step 3 -- Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier. If a plenum return is used on a
vertical unit, the return should be ducted through the roof deck to
comply with applicable fire codes. A minimum clearance is not
required around ductwork. Cabinet return-air static shall not
exceed -.25 in. wc.
Step 4 -- Provide Clearances
The required minimum operating and service clearances are shown
in Fig. 2 and 3. Adequate ventilation and condenser air must be
)rovided.
RECEIVING AND INSTALLATION
Step 1 -- Check Equipment
IDENTIFY UNIT
The unit model number and serial number are printed on the unit
informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.
Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest equipment distribution office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.
Step 2 -- Provide Unit Support
For hurricane tie downs, contact distributor for details and PE
(Professional Engineering) Certificate, if required.
ROOF CURB
Install accessory roof curb in accordance with instructions shipped
with curb (see Fig. 4). Install insulation, cant strips, roofing, and
flashing. Ductwork must be attached to curb.
[]NIT HAZARD
Failure to follow this caution could result in equipment
damage.
Do not restrict condenser airflow. An air restriction at either
the outdoor-air inlet or the fan discharge can be detrimental
to compressor life.
The condenser fan draws air through the condenser coil and
discharges it through the top fan grill. Be sure that the fan
discharge does not recirculate to the condenser coil. Do not locate
the unit in either a corner or under an overhead obstruction. The
minimum clearance under a partial overhang (such as a normal
house overhang) is 36-in. (914 mm) above the unit top. The
maximum horizontal extension of a partial overhang must not
exceed 48 in. (1219 mm).
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting, tile, or other combustible materials.
UNIT
50XPO24
5OXPOBO
BDXPOBE
705
[R78]
INOO011
ml
I
OUTDOORCOIL
i m
D
1
Y
CORNER WEIGHT LBSIHO
"I' "2" "3 .... 4"
024 62/28 49/22 7a/34 123156
030 62128 50/23 75134 125157
OSH 66/30 53124 79/3H 132/60
ELECTRICAL
CHARACTERISTICS
208-230-I-60, 2081230-3-60
208-230-:-60, 2081230-3-H0
208-R30-i-HO, 2081230-3-60
UNIT WT UNIT HEIGHT CENTER OF GRAVITY MMIIN
LBS HG 'AT' Y Z
308 i40 i091714298: 44761176] 45721180]
312 I42 :142514498: 495B[19B] 44761176] 4572[:80]
330 i50 :193314698: 533412101 5OBO[2OO] 4420[:761
REQIJIPN_:)CLEARANCES TO _'BBLE MAR-
TOP OF UNIT ............................................. 3556 [1400]
DUCT SIDE OF UNIT ......................................... 508 [HO0]
SIDE OPPOSITE DUCTS ............................. 3556 [1400]
BOTTOM OF UNIT ........................ O 0 [0001
ELECTRIC HEAT PANEL .................................... 9144 [3600]
N_C. I_.I_QIJII_ Cl.EARANCE&
BETWEEN UNITS, POWER ENTRY SIDE ....................... 10668 [4ROO]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .......... 9140 [3600]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWERENTRY SIDE .......... 1066 8 [4200]
REO_JlREDCL,.E&RANOE FOR O_A"IIOI_ AND S_VlCll&3
EVAP COIL ACCESS SIDE ................... 9140 [H6 OH]
POWER ENTRY SIDE ..................................... 9140 13600]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ................................................ 12192 [48H0]
SIDE OPPOSITE DUCTS ........................... 9140 [36 00]
DUCT PANEL ............................. 3048 [1200]_
_MINIMUM DISTANCES:IF UNIT IS PLACED LESS THAN 3048 [iHO0] FROM WALL
SYSTEM,THEN SYSTEM PERFORMANCEMAYBE COMPROMISED
DIMENSIONS IN [] AHE IN INCHES
MILLIMETERS [IN]
MILLIMETERS [IN]
MILLIMETERS [IN]
TOP ViEW
m_
I
1985
[3 441
FIELD ENTRY--
SERVICE PORTS
[oG_I
t
11939
[4700]
.=.
t_
_o
, FULL LOUVER
............]i
LEFT SiDE VIEW
>
g
b3
T T
[32 7R]
_724
l
570 3
ERR 45]
L42 7
[ 6B]
[2 85]
Lk
" _ " 22R[O_T_E_ _
/x
L 81 :
COMPRESSOR, BLOWER, ELECTRIC HEAT
& ELECTRICAL ACCESS PANEL
12265
[48281
[3:43]
FRONT ViEW
FULL LOUVER
5505
[H1.67]
L POiER E_IT_Y [ : ]
222
[481]
L ...................... IL
SUPPLY
DUCT •
OPENING
i
[983]
RIGHT SiDE VIEW REAR ViEW
50XPHO0017
[983]
UNIT
15391 11349]
3558 #_--114D13558 1
[1Aoll /l
! UETURNJ _W"/sUPRLY/ I_
I 'IIII OPTIONAL I I OPTIONAL
704
[B771 4066 IIII RETURN I I SUPPLY
[1601] AIR I AIR
INDOOR COIL
ml
OPENING I OPENING
IIII
llll
IIII
50XPO42
50XPO48
5OXPOBO
CORNER WEIGHT LBS/HG
"1' "2" "3 .... 4"
042 78135 62128 93/42 155170
048 84138 68/31 101146 109177
060 93/42 75134 112/51 187/85
CHARACTERISTICS G
ELECTRICAL J UL35iBIT _
208-230-1-0%2081230-3-60 176
208-230-1-60, 2081230%%0 422 I 192
BEQ_JI_ CI,,,_AR/84CES TO _S'I'U.I_ MAR,..
TOD OF UNIT ............................................. 3550 [i400]
DUCT SIDE OF UNIT ......................................... 508 [200]
SIDE OPPOSITE DUCTS ......................... 3556 [1400]
BOTTOM OF UNIT ........................... O O [OOO]
ELECTRIC HEAT PANEL ................................... 9144 [3600]
NEC. REQIJIR_:)CLEARANCE&
BETWEEN UNITS, POWER ENTRY SIDE ........................ 10068 [4200]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .......... 9140 [3600]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, ROWERENTRY SIDE ............. 1066 8 142 001
RE(_JIRIB) CI..EARANCE FOR OPiE_A'BOI_ AND SB_VlClr_3
EVAP COIL ACCESS SIDE .................... 914 0 [3600]
POWER ENTRY SIDE ........................................ 9140 [3600]
(EXCPT FOR NEC REQUIREMENTS)
UNIT TOP................................................ 12192 [4800]
SIDE OPPOSITE DUCTS ................. 9140 [36 DO]
DUET PANEL ............................................. 5048 [1200D
_MINIMUM DISTANCES:IF UNIT IS PLACED LESS THAN 3048 [1200] FROM WALL
/ t 1i1
I
OUTDOOR COIL _/
UNIT HEIGHT CENTER OF GRAVITY MM/IN
1091714298] 49531195] 4476[176] 45721180]
1142514498] 49551195] 44761i761 45721180]
I208-230-1-60, 208/230-3-60 467 22
"AI' 533412i0] 50801200] Z
1!93314098] 44201176]
SYSTEM,THEN SYSTEM PERFORMANCE MAYBE COMPROMISED
DIMENSIONS IN [] ARE IN INCHES
MILLIMETERS [IN]
MILLIMETERS [IN]
MILLIMETERS [[N]
TOP VIEW
&
.=.
O
10906
[42941
SERVICE PORTS
•__ i¸
L,' I'I , 2_
4% J /]
I,/o,:!;_;s!_T=L_32_
x 220 [088] DP [12 95]
11231
[44 221
LEFT SIDE VIEW
>
g
co
FIELD ENTRY--
620 2
[24 42]
J
_722
F 11959
[4700]
]
JI.::Ta
[284]
COMPRESSOR, BLOWER, ELECTRIC HEAT _
& ELECTRICAL ACCESS PANEL
12263
[4828]
FRONT VIEW
\
75] DIA HO
445 [I POWER ENTRY_
_ 326_ _
809
[342]
1220
[481]
FULL LOUVER
[0881DIA HOLE
CONTROL ENTRY
RIGHTSIDE VIEW
402 0
[1583]
I
b_
1177
[465]
SUPPLY RETURN
DUCT DUCT
OPENING OPENING
o
_872 3475
351 2
[13 83] [ 383]
REAR VIEW
I 50XP500018
ase
/ Screw -___
/ (NOTE A) -_
/ *Gasketina_ _
[/ ou_a?_le_;g_g _ _]1 ..............................
1_ Wood nailer*\
[ Flashing field Ill_l II \
I supplied _ _Jll_il_ R°°fcurb* I
ll_iiiill_ Insulation(field
I Roofing mate_al tl_!i_ II supphed) /
/ base
/
/ ,,,scrtw_
/ ,.(NOTE A) -_H
/ *Gask_tin"g .._, _
Woodnai,er*
I Flashing field Ill'Ill
I supplied _ JIl_l _ Roofcurb*
l Roofing mate_al supplied)
tl_su_ation (f!e_d
/l_:iill II _auctwork [
\ II ,ie,dsupp,ed/
Roof Curb for Small Cabinet
Note A:When unit mounting screw is used
retainer bracket must also be used.
Supply opening
(Bx c)
\ o_1111 f'_d supplied /
]I_!_IP -- Ductw°rk t
Roof Curb for Large Cabinet
Note A:When unit mounting screw is used
retainer bracket must also be used.
\/
R/A
\,
'_'_- Gasket around
duct
\
S/A
/\
Long
Suppo_
Retu'n opening
(Bx c)
50XP UNIT SIZE
024-036
ROOF CURB
042-060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 1d-gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1-in. (25mm) thick fiberglass 1 lb. (.45 kg) density.
ODS CATALOG NUMBER
CPRFCURB006A00
CPRFCURB007A00
CPRFCURB008A00
CPRFCURB009A00
\
Support
Fig. 4 - Roof Curb Dimensions
Insulated Gasket around
deck pan outer edge.
A
IN, (MM)
8 (203)
14 (356)
8 (203)
14 (356)
B
IN. (MM)
11 (279)
11 (279)
16-3/16 (411)
16-3/16 (411)
\
\
C
IN. (MM)
16-1/2 (419)
16-1/2 (419)
17-3/8 (441)
17-3/8 (441)
C00076
D
IN, (MM)
28-3/4 (730)
28-3/4 (730)
40-1/4 (1022)
40-1/4 (1022)
Unit* 024 024 030 030
Ib kg Ib kg
Rigging 319 145 323 147
Weight
NOTE: See dimensional drawing for corner weights
SMALL CABINET
036 036 042 042 048 048
Ib kg Ib kg Ib kg
341 155 Rigging 399 181 433 196
Unit*
Weight
Fig. 5 - Rigging Weights
•/,1 w/IONAL, ---_----- SUPPLY !111
t RETURN
IIIII AIR
i1111!OPENING//)__ i \_ .._ AIR Illl'
((Ill /' l(i\ _ ( __ j(II
UII! II [1!1
J,.lllll l'If(l,_ @ _ l fillllll
OPENING !! II
II II
,,,,, ,,.., /,// II',',
LARGE CABINET
060
478
060
Ib
kg
217
2" (51 mm
___=__= ,//
I
EVAP. COIL COND. COIL
Fig. 6 - Slab Mounting Details
Step 5 -- Rig and Place Unit
Rigging and handling of this equipment can be hazardous for
many reasons due to the installation location (roofs, elevated
structures, etc.)
Follow all applicable safety codes. Wear safety shoes and work
gloves.
UNIT FALLING HAZARD
Failure to follow this warning could result in personal
iniury, death or property damage.
When installing the unit on a rooftop, be sure the roof will
support the additional weight.
Never stand beneath rigged units or lift over people.
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
A08465
INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets
and straps should be visually inspected for any damage, evidence
of wear, structural deformation, or cracks. Particular attention
should be paid to excessive wear at hoist hooking points and load
support areas. Brackets or straps showing any kind of wear in these
areas must not be used and should be discarded.
DUCTS
y 5527")
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
PLACE _" (48.28")
BASEPAN SLOT (BELOW HANDHOLDS)
BEFORE RIGGING
UNIT ON ROOF CURB
C99015
Fig. 7 - Suggested Rigging
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
iniury/death or property damage.
Rigging brackets for one unit use only. When removing a
unit at the end of its useful life, use a new set of brackets.
Never exceed 200 lb. (91 kg) per bracket lifting force.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
iniury or death.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Turn off accessory heater power switch if
applicable. Tag disconnect switch with a suitable warning
label.
MAXIMUM ALLOWABLE
DIFFERENCE in. (mm)
A-B
1/4 (6.35)
Fig. 8 - Unit Leveling Tolerances
B-C ArC
1/4 (6.35) 1/4 (6.35)
INSTALLATION
6. Remove unit from shipping carton. Leave top shipping
skid on the unit as a spreader bar to prevent the rigging
straps fromdamaging the unit. If the wood skid is not
available, use a spreader bar of sufficient length to protect
unit from damage.
7. Position the lifting bracket assembly around the base of the
unit. Be sure the strap does not twist.
8. Place each of the 4 metal lifting brackets into the rigging
holds in the composite unit base.
9. Thread lifting bracket strapping around bottom perimeter of
unit as follows:
a. Open lever of tension buckle (ratchet type).
b. Feed strapping through tension buckle (See Fig. 9).
A07925
DETAIL A
UNIT HEIGHT
SEE DETAIL A/
A08005
Fig. 10 - Lifting Point
14. Lift unit. When unit is directly over the roof curb, remove
the 2 safety straps. Lower the equipment onto the roof curb.
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
iniury/death or property damage.
Rigging bracket MUST be under the rain lip to provide
adequate lifting.
FEED _
C99067
Fig. 9 - Belt Threading
c. Pull strapping through tension buckle unit taut.
d. Snap lever down to lock strap in tension buckle. To
release strapping, squeeze safety latch, lift lever, and
pull webbing outward.
10. Tighten the tension buckle until it is taut. Lifting brackets
must be secure in the rigging holds.
11. Attach field-supplied clevis or hook of sufficient strength to
hole in the lifting bracket (See Fig. 10).
12. Attach the 2 safety straps directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safety straps to the
lifting brackets (See Fig. 10).
13. Position lifting point directly over the unit's center of
gravity.
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
iniury/death or property damage.
Do not strip screws when re-securing the unit. If a screw is
stripped, replace the stripped one with a larger diameter
screw (included).
UNIT FALLING HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36
in. (914 mm) above the unit top cover.
Table 1 - Physical Data - Unit 50XP
UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT (Ib)
SHIPPING WEIGHT (kg)
COMPRESSORS
Quantity
REFRIGERANT (R-410A)
Quantity (lb.)
Quantity (kg)
REFRIGERANT METERING DEVICE
OUTDOOR COIL
Rows...Fins/in,
Face Area (sq ft)
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
Diameter (mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in,
Face Area (sq ft)
INDOOR BLOWER
Nominal Cooling Airflow (Cfm) 800 1000 1100 1400 1400 1750
Size (in.) 10x10 10x10 1lx10 1lx10 1lx10 1lx10
Size (mm.) 254x254 254x254 279.4x254 279.4x254 279.4x254 279.4x254
Motor HP (RPM) 1/2 (1050) 1/2 (1050) 3/4 (1000) 3/4 (1075) 3/4 (1075) 1.0 (1040)
HIGH-PRESSURE SWITCH 650 +/- 15
(psig) Cut-out Reset (Auto) 420 +/- 25
LOSS-OF-CHARGE / LOW-PRESSURE 20 +/- 5
SWITCH (Liquid Line) (psig) cut-out Re- 45 +/- 10
set (auto)
RETURN-AIR FILTERSt$
Throwaway Size (in.) 20x20x1 20x24x1 24x30x1
Throwaway Size (mm) 508x508x25 508x610x25 610x762x25
1- Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity
of 300 ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 IN. W.C..
$ If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
024 030 036
2 2-1/2 3
356 360 378
161 163 171
042 048 060
3-1/2 4 5
436 470 515
198 213 234
Scroll
1
7.3 8.0 9.5 10.7 11.25 13.2
3.3 3.6 4.3 4.9 5.1 6.0
TXV
2...21 2...21 2...21 2...21 2...21 2...21
11.95 12.0 13.6 15.4 17.4 19.3
2350 2700 2350 2800 3300 3300
22 22 22 22 22 22
558.8 558.8 558.8 558.8 558.8 558.8
1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (1100)
3...15 3...15 4...15 3...15 4...15 4...17
3.7 3.7 3.7 4.7 4.7 5.7
Step 6 -- Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 50XP disposes of condensate water through a 3/4 in. NPT
fitting which exits through the base on the evaporator coil access
side (See Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in
groundlevel installations. Install a field-supplied condensate trap at
end of condensate connection to ensure proper drainage. Make sure
that the outlet of the trap is at least 1 in. (25 ram) lower than the
drainpan condensate connection to prevent the pan from
overflowing (See Fig. 11). When using a gravel apron, make sure it
slopes away from the unit.
1" (25 mm) MIN.
Lt
A08001
Fig. 11 - Condensate Trap
Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in.
copper pipe (all field-supplied) at the outlet end of the 2-in. (51
ram) trap. Do not undersize the tube. Pitch the drain tube
downward at a slope of at least 1-in. (25 ram) for every 10ft (3 m)
of horizontal run. Be sure to check the drain tube for leaks. Prime
trap at the beginning of the cooling season start-up.
Table 2 - Minimum Airflow for Safe Electric Heater Operation
(Cfm)
SIZE
024 030 036 042 048 060
800 1000 1200 1400 1600 2000
Step 7 -- Install Duct Connections
The unit has duct flanges on the supply- and return-air openings
on the side and bottom of the unit. For downshot applications, the
ductwork can be connected to the roof curb (See Fig. 2 and 3 for
connection sizes and locations).
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weathertight and airtight seal. When electric heat is
installed, use fire proof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24-in.
(610 ram) from the unit discharge connection flange into the
ductwork.