Carrier 50VL-A User Manual

Page 1
50VL---A Performancet 14 SEER Single---Packaged Air Conditioner System with Puron® (R ---410A) Refrigerant Single and Three Phase 2 --- 5 N o m i n a l To n s ( S i z e s 2 4 --- 6 0 )
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
NOTE: Installer: Make sure the Owner’s Manual and Service Instructions are left with the unit after installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1--2.......................
INTRODUCTION 2...................................
RECEIVING AND INSTALLATION 2--10.................
Check Equipment 2..................................
Identify Unit 2....................................
Inspect Shipment 2.................................
Provide Unit Support 2...............................
Roof Curb 2......................................
Slab Mount 2.....................................
Provide Clearances 7.................................
Field Fabricate Ductwork 7............................
Rig and Place Unit 7.................................
Inspection 7......................................
Rigging/Lifting of Unit 7............................
Connect Condensate Drain 8...........................
Install Duct Connections 8.............................
Configuring Units for Downflow (Vertical) Discharge 8....
Install Electrical Connections 9.........................
High--Voltage Connections 9.........................
Special Procedures for 208v Operation 10...............
Control Voltage Connections 10.......................
Standard Connection 10.............................
Transformer Protection 10...........................
PRE--START--UP 12...................................
START--UP 12--14.....................................
Check for Refrigerant Leaks 12.........................
Start--Up Adjustments 12..............................
Checking Cooling Control Operation 12................
Checking and Adjusting Refrigerant Charge 12...........
Indoor Airflow and Airflow Adjustments 13.............
Continuous Fan Operation 14........................
Cooling Sequence of Operation 14.....................
MAINTENANCE 24--2 6................................
Air Filter 24......................................
Indoor Blower and Motor 24.........................
Outdoor Coil, Indoor Coil, and Condensate Drain Pan 25...
Outdoor Fan 25...................................
Electrical Controls and Wiring 25.....................
Refrigerant Circuit 26...............................
Evaporator Airflow 26..............................
Puron Items 26....................................
TROUBLESHOOTING 27..............................
START--UP CHECKLIST 27............................
Improper installation adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-- authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Electrical Code (NEC) NFPA 70. In Canada refer to the current editions of the Canadian electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
SAFETY CONSIDERATIONS
A09033
Fig. 1 -- Unit 50VL --A
.
1
Page 2
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn of f accessory heater power switch if applicable.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
1. Relieve pressure and recover all refrigerant before
50VL -- A
servicing existing equipment, and before final unit disposal. Use all service ports and open all flow--control devices, including solenoid valves.
2. Federal regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposal.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 17) or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.
CAUTION
INTRODUCTION
The 50VL --A packaged air conditioner is fully self--contained and designed for outdoor installation (See Fig.1 ). See Fig. 2 and 3 for unit dimensions. All unit sizes have discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. The unit may be installed either on a rooftop or on a ground--level cement slab. (See Fig. 4 for roof curb dimensions.)
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT
The unit model number and serial number are printed on the unit informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage before removing packaging materials. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
If the unit is to be mounted on a curb in a downflow application, review Step 7 to determine which method is to be used to remove the downflow panels before rigging and lifting into place. The panel removal process may require the unit to be on the ground.
Step 2 — Provide Unit Support
IMPORTANT: The unit must be secured to the curb by installing
screws through the bottom of the curb flange and into the unit base rails. When installing large base units onto the common curb, the screws must be installed before allowing the full weight of the unit to rest on the curb. A minimum of six screws are required for large base units. Failure to secure unit properly could result in an unstable unit. See Warning near Rigging/Lifting information and accessory curb instructions for more details.
For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate if required.
ROOF CURB
Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 4). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb. IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance. Curb should be level to within 1/4 in. (6.35 mm) (See Fig 6). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
Installation on older “G” series roof curbs.
Two accessory kits are available to aid in installing a new “G” series unit on an old “G” roof curb.
1. Accessory kit number CPADCURB001A00, (small chassis) and accessory kit number CPADCURB002A00, (large chassis) includes roof curb adapter and gaskets for the perimeter seal and duct openings. No additional modifications to the curb are required when using this kit.
2. An alternative to the adapter curb is to modify the existing curb by removing the outer horizontal flange and use accessory kit number CPGSKTKIT001A00 which includes spacer blocks (for easy alignment to existing curb) and gaskets for the perimeter seal and duct openings. This kit is used when existing curb is modified by removing outer horizontal flange.
!
UNIT/STRUCTURAL DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Ensure there is sufficient clearance for saw blade when cutting the outer horizontal flange of the roof curb so there is no damage to the roof or flashing.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102 mm) thick with 2 in. (51 mm) above grade. The slab should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit (See Fig. 7). Do not secure the unit to the slab except when required by local codes.
CAUTION
2
Page 3
50VL -- A
Fig. 2 -- 50VL--A24--36 Unit Dimensions
3
A09462
Page 4
50VL -- A
Fig. 3 -- 50VL--A42--60 Unit Dimensions
4
A09463
Page 5
HVAC unit base rails
Anchor screw
Flashing field supplied
Roofing material field supplied
Cant strip field supplied
HVAC unit basepan
Sealing Gasket
Roofcurb
Wood nailer*
Roofcurb*
Insulation (field supplied)
B
G
C
F
A
H
D
Dashed lines show cross support location for large basepan units.
E
A09413
50VL -- A
*Provided with roofcurb
ROOF CURB DETAIL
SMALL/COMMON CURB
A09090
B
C
G
A
F
H
E
SUPPLY
AIR
RETURN
AIR
SMALL BASE UNIT
LARGE BASE UNIT
D
UNIT PLACEMENT ON
LARGE CURB
A09415
COMMON CURB
SMALL OR LARGE BASE UNIT
A09094
UNIT SIZE
Small
or
Large
CATALOG
NUMBER
CPRFCURB010A00
CPRFCURB011A00
CPRFCURB012A00
Large
CPRFCURB013A00
* Part Numbers CPRCURB010A00 and CPRCURB011A00 can be used on both small an d large basepan units. T he cross supports must be located based on whether the unit is a small basepan or a large basepan. NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16 --gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
A
IN.
(mm)
11
(279)
14
(356)
11
(279)
14
(356)
B
(small/common
base)
IN. (mm)*
10 (254)
14 (356)
B
(large base)
IN. (mm)*
14 (356)
C
IN.
(mm)
16
(406)
D
IN.
(mm)
47.8
(1214)
E
IN.
(mm)
32.4
(822)
43.9
(1116)
F
IN.
(mm)
2.7
(69)
G
IN. (mm)HIN. (mm)
30.6 (778)
46.1 (1170)
42.2 (1072)
Fig. 4 -- Roof Curb Dimensions
5
A09414
Page 6
CAUTION - NOTICE TO RIGGERS PRUDENCE - AVIS AUX MANIPULATEUR
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
DUCTS
MINIMUM HEIGHT: 36" (914.4 mm) HAUTEUR MINIMUM
50VL -- A
SEE DETAIL A VOIR DÉTAIL A
SMALL CABINET LARGE CABINET
Unit*
Rigging
Weight
* For 460 volt units, add 14 lb (6.35 kg) to the rigging weight. NOTE: See dimensional drawing for corner weighs.
24 30 36
lb kg lb kg lb kg lb kg lb kg lb kg
295 134 307 139 365 166
UNIT HEIGHT HAUTEUR D'UNITÉ
DETAIL A
VOIR DÉTAIL A
Unit*
Rigging
Weight
421 191 439 199 467 212
Fig. 5 -- 50VL--A Unit Suggested Rigging
SEAL STRIP MUST BE IN PLACE BEFORE PLACING UNIT ON ROOF CURB
42 48 60
BANDE SCELLANT DOIT ÊTRE EN PLACE AVANT DE PLACER L'UNITÉ SUR LA BASE DE TOIT
50CY502286 2.0
A09051
6
Page 7
Step 3 — Provide Clearances
A
The required minimum service clearances are shown in Fig. 2 and
3. Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm) IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life. Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab--mounted units should be at least 4 in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.
Step 4 — Field--Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. See unit rating plate for any required clearances around ductwork. Cabinet return--air static shall not exceed --.25 IN. W .C.
Step 5 — Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.). Only trained, qualified crane operators and ground support staff should handle and install this equipment. When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply. Training for operators of the lifting equipment should include, but not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded.
!
WARNING
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Never stand beneath rigged units or lift over people.
1. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover.
Rigging/Lifting of Unit (See Fig. 5)
!
WARNING
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Large base units must be secured to common curb before allowing full weight of unit to rest on curb. Install screws through curb into unit base rails while rigging crane is still supporting unit.
Lifting holes are provided in base rails as shown.
1. Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit (See Fig. 5).
2. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.
After the unit is placed on the roof curb or mounting pad, remove the top skid.
50VL -- A
OPTIONAL
RETURN
AIR
C
MAXIMUM ALLOWABLE
B
A-B
(6.35)
1/4
Fig. 6 -- Unit Leveling Tolerances
DIFFERENCE in. (mm)
1/4
B-C
(6.35)
A-C
1/4
(6.35)
A07925
(50.8mm)
7
OPENING
EVAP. COIL COND. COIL
Fig. 7 -- Slab Mounting Detail
OPTIONAL
SUPPLY
AIR
OPENING
A07926
Page 8
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 50VL-- A disposes of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side. See Fig. 2 and 3 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-- supplied 2--in. (51 mm) condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the drain pan condensate connection to prevent the pan from overflowing (See Fig. 8). When using a gravel apron, make sure it slopes away from the unit.
Connect a drain tube using a minimum of 3/4 -- in. PVC or 3/4 --in. copper pipe (all field--supplied) at the outlet end of the 2-- in. (51 mm) trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 -- in. (25 mm) for every 10 ft (3.1 m) of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of the cooling season start--up.
50VL -- A
TRAP OUTLET
1-in. (25 mm) min.
2-in. (51 mm) min.
Fig. 8 -- Condensate Trap
Step 7 — Install Duct Connections
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non--residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply--air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations. The unit has duct flanges on the supply-- and return--air openings on the side of the unit.
When designing and installing ductwork, consider the following:
1. All units should have field--supplied filters or accessory filter rack installed in the return--air side of the unit. Recommended sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather--tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24--in. (610 mm) from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and
A09052
Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof, and vibration--isolate duct openings in wall or roof according to good construction practices.
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance operations on the system, turn off main power to unit and install lockout tag.
1. Open all electrical disconnects and install lockout tag before starting any service work.
2. Remove horizontal (metal) ductcovers to access vertical (downflow) discharge duct knockouts in unit basepan. (See Fig. 9.)
To remove downflow return and supply knockout covers, break front and right side connecting tabs with a screwdriver and hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an electrical knockout. Reinstall horizontal duct covers (Fig. 9) shipped on unit from factory. Insure openings are air and watertight.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence--type air conditioning and ventilating systems, NFPA 90A or residence--type, NFPA 90B; and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Units are shipped for side shot installation.
2. Select and size ductwork, supply--air registers, and return--air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather--tight and airtight seal.
4. All units must have field --supplied filters or accessory filter rack installed in the return--air side of the unit. Recommended sizes for filters are shown in Table 1.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration--isolate all openings in building structure in accordance with local codes and good building practices.
DISCHARGE
!
WARNING
8
Page 9
Horizontal Duct Covers
Basepan Downflow (Vertical) Supply Knockout
Fig. 9 -- Supply and Return Duct Opening
Step 8 — Install Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NFPA 70 (NEC) (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
A09076
Basepan Downflow (Vertical) Return Knockout
A09093
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
1. Make all electrical connections in accordance with NFPA 70 (NEC) (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field--supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high--voltage power to unit is within operating voltage range indicated on unit rating plate. On 3--phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
CAUTION
HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field--supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over the high--voltage inlet hole when the standard power and low--voltage entry points are used. See Fig. 2 and 3 for acceptable location.
See unit wiring label (Fig. 12, 13 and 14) and Fig. 10 for reference when making high voltage connections. Proceed as follows to complete the high--voltage connections to the unit.
Single phase units:
1. Run the high-- voltage (L1, L2) and ground lead into the control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the contactor.
4. Connect field L1 to black wire on connection 11 of the compressor contactor.
50VL -- A
9
Page 10
CONTROL BOX
LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
50VL -- A
5.ConnectfieldwireL2toyellowwireonconnection23of
Three--phase units:
1. Run the high--voltage (L1, L2, L3) and ground lead into the
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
4. Connect field L1 to black wire on connection 11 of the
5.ConnectfieldwireL3toyellowwireonconnection13of
6. Connect field wire L2 to blue wire from compressor.
HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL
)
3-PHASE SHOWN 1-PHASE USES TWO POWER LEADS
EQUIP GR
SPLICE BOX
FIELD-SUPPLIED FUSED DISCONNECT
WHT(W1)
VIO (W2)
YEL(Y)
GRN(G)
RED(R)
BRN(C)
BLU (DH)
GRA (Y2)
W1
W2
Y
G
R
C
DH
3-Phase Only
Fig. 10 -- High-- and Control--Voltage Connections
the compressor contactor.
control box.
of the contactor.
compressor contactor.
the compressor contactor.
POWER SUPPLY
THERMOSTAT (TYPICAL
A09066
SPECIAL PROCEDURES FOR 208--V OPERATION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. With disconnect switch open, move black wire from transformer (3/16 in.)(4.8 mm) terminal marked 230 to terminal marked 208. This retaps transformer to primary voltage of 208 vac.
CONTROL VOLTAGE CONNECTIONS
NOTE: Do not use any type of power--stealing thermostat. Unit
)
control problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated (35°C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the control voltage wires), use no. 16 AWG color--coded, insulated (35° C minimum) wires.
STANDARD CONNECTION
Locate the seven (eight for 3-- phase) low voltage thermostat leads in 24 volt splice box. A gray wire is standard on 3--phase units for connection to an economizer. See Fig. 10 for connection diagram. Run the low-- voltage leads from the thermostat, through the control wiring inlet hole grommet (Fig. 2 and 3), and into the low-- voltage splice box. Provide a drip loop before running wires through panel. Secure and strain relief all wires so that they do not interfere with operation of unit.
If an accessory electric heater is installed, low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 connector.
NOTE: If the unit 24V wires do not have a matching receptacle, cut the 24V wires from the electric heater plug, strip the ends, and wire nut together to match the schematic connections. If the electric heater 24V wires do not have a matching plug, cut the 24V wires from the unit receptacle, strip the ends, and wire nut together to match the schematic connections.
Factory wires are provided for electric heat staging W1 and W2 (W2 and W3 on IFB). If room thermostat has only one stage of supplemental heat, connect white and violet wires shown in Fig. 10 to second stage heat field wire.
Some electric heaters have four control wires (plus common wire). Consult unit wiring diagram and electric heater wiring diagram for additional details.
TRANSFORMER PROTECTION
The transformer is of the energy--limiting type, however a direct short will likely blow a secondary fuse. If an overload or short is present, correct overload condition and check for blower fuse on Indoor Fan Board. Replace fuse as required with correct size and rating.
10
Page 11
Table 1 – Physical Data--Unit 50VL--A
UNIT SIZE 24 30 36 42 48 60 NOMINAL CAPACITY (ton) 2 2 --- 1 / 2 3 3 --- 1 / 2 4 5 SHIPPING WEIGHT* lb.
SHIPPING WEIGHT* (kg)
COMPRESSORS
Quantity
REFRIGERANT (R--- 410A)
Quantity lb Quantity (kg)
REFRIGERANT METERING DEVICE TXV OUTDOOR COIL
Rows...Fins/in. Face Ar ea (sq ft)
OUTDOOR FAN
Nominal Cfm Diameter in. Diameter (mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in. Face Ar ea (sq ft)
INDOOR BLOWER
Nominal Cooling Airflow (Cfm)
Size in. Size (mm.) Motor HP (RPM)
HIGH --- PRESSURE SWITCH (psig) Cut --- out Reset (Auto)
L O S S --- O F --- C H A R G E / L O W --- P R E S ­SURE SWITCH (Liquid Line) (psig) cut--- out Reset (auto)
RETURN--- AIR FILTERS}
Throwaway Si ze in. Throwaway Si ze (mm)
*For 460 volt units add 14 lb (6.35 kg) to the shipping weight. { Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-
flow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 in. W.C. } If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
295 134
6.0
2.7
1...21
11.9
2500
24
609.6
1/10 (810)
3...17
3.7
800
10x10
254x254
1/2 (1050)
20x20x1
508x508x25
307 139
5.6
2.5
1...21
13.6
2700
24
609.6
1/10 (810)
3...17
3.7
1000
10x10
254x254
1/2 (1050)
20x24x1
508x610x25
365 166
9.5
4.3
2...21
15.4
2800
24
609.6
1/5 (810)
3...17
3.7
1200
11x10
279.4x254 3/4 (1000)
610x762x25
Scroll
1
1/5 (810)
279.4x254 3/4 (1075)
650 +/ --- 15 420 +/ --- 25
2 0 + / --- 5
45 +/ --- 10
24x30x1
421 191
8.8
4.0
2...21
13.6
3000
26
660.4
3...17
4.7
1400
11x10
439 199
9.4
4.3
2...21
17.5
3200
26
660.4
1/5 (810)
3...17
4.7
1600 1750
11x10
279.4x254
1.0 ( 1075) 1.0 (1040)
24x36x1
610x914x25
467 212
12.5
5.7
2...21
21.4
3600
26
660.4
1/5 (810)
3...17
5.7
11x10
279.4x254
50VL -- A
Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)
SIZE 24 30 36 42 48 60
Cfm 800 1000 1200 1400 1600 1750
11
Page 12
PRE--START--UP
!
WARNING
ENVIRONMENTAL, FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Relieve and recover all refrigerant from system before touching or disturbing compressor plug if refrigerant leak is suspected around compressor terminals.
3. Never attempt to repair soldered connection while refrigerant system is under pressure.
4. Do not use torch to remove any component. System contains oil and refrigerant under pressure.
5. To remove a component, wear protective goggles and
50VL -- A
proceed as follows:
a. Shut off electrical power to unit and install
lockout tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for initial start--up:
1. Remove all access panels (see Fig. 17).
2. Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a refrigerant leak. Leak test all refrigerant tubing connections using electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section.
c. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
b. Make sure that all tools and miscellaneous loose parts
have been removed.
START--UP
Step 1 — Check for Refrigerant Leaks
Proceed as follows to locate and repair a refrigerant leak and to charge the unit:
1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high-- and low--pressure ports.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair.
3. Add a small charge of Puron (R--410A) refrigerant vapor to system and leak--test unit.
4. Recover refrigerant from system and evacuate to 500 microns if no additional leaks are found.
5. Charge unit with Puron (R--410A) refrigerant, using an accurate scale. Refer to unit rating plate for required charge.
Step 2 — Start--Up Cooling Section And Make Adjustments
Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit when the outdoor temperature is below 40°F(4°C) (unless accessory low--ambient kit is installed). Do not rapid cycle the compressor. Allow 5 minutes between “on” cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires.
IMPORTANT: Three--phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3--phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3--phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures may be minimal.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with Puron (R--410A) refrigerant and is tested and factory sealed.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper Puron (R--410A) charge.
A subcooling charging chart is attached to the inside of the compressor access panel (see Fig. 17). The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures.
An accurate thermocouple-- or thermistor-- type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial-- type thermometers because they are not adequate for this type of measurement.
NOTE: Allow system to operate for a minimum of 15 minutes before checking or adjusting refrigerant charge.
IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
12
Page 13
Proceed as follows:
1. Remove caps from low-- and high--pressure service fittings.
2. Using hoses with valve core depressors, attach low-- and high--pressure gauge hoses to low-- and high--pressure service fittings, respectively.
3. Start unit and let run until system pressures stabilize.
4. Measure and record the following:
a. Outdoor ambient--air temperature (°F[°C] db).
b. Liquid line temperature (°F[°C]) at TXV.
c. Discharge (high--side) pressure (psig).
d. Suction (low--side) pressure (psig) (for reference only).
5. Using Cooling Charging Charts compare outdoor--air temperature (°F[°C] db) with the discharge line pressure (psig) to determine desired system operating liquid line temperature (See Fig. 15).
6. Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of ±2°F(±1.1°C), add refrigerant if actual temperature is more than 2°F(1.1°C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2°F(1.1°C) lower than required liquid line temperature.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.
INDOOR AIRFLOW AND AIRFLOW ADJUST­MENTS
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.
NOTE: Be sure that all supply--and return--air grilles are open, free from obstructions, and adjusted properly.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before changing blower speed.
This unit is factory-set up for use with a single cooling fan speed. In addition, this unit has the field-selectable capability to run two different cooling fan speeds: The rated cooling fan speed (350~400 CFM/Ton) and an enhanced dehumidification fan speed (As low as 320 CFM/Ton) for use with either a dehumidistat or a thermostat that supports dehumidification.
The cooling speed is marked “LOW” on the interface fan board (IFB) (See Fig. 11) . The factory-shipped settings are noted in Table 4. There are 4 additional speed tap wires available for use in either electric heating or cooling (For color coding on the indoor fan motor leads, see Table 3). The additional 4 speed tap wires are
shipped loose with vinyl caps and are located in the control box, near the interface fan board (IFB) (See Fig. 11).
SINGLE COOLING FAN SPEED SET--UP (Dehumidi­fication feature not
To change cooling speed:
1. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding). Add the wet coil pressure drop in Table 6 to the system static to determine the correct cooling airflow speed in Table 4 that will deliver the nominal cooling airflow as listed in Table 1 for each size.
2. Remove the current speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 11) and place vinyl cap over the connector on the wire.
3. Connect the desired speed tap wire to the “LOW” terminal on the interface fan board (IFB).
NOTE: If accessory electric heat is installed, and the electric heat fan speed is chosen to be the same as the normal cooling fan speed, the dry airflow must meet or exceed the minimum airflow speed specified in Table 2 for the specific size unit.
used)
TWO COOLING FAN SPEEDS SET--UP (Dehumidi­fication feature
IMPORTANT: Dehumidification control must open control
circuit on humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of either a 24 V AC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point.
1. Using Fig. 11, move the two pin DEHUM jumper from the “STD” position to the “DEHUM” position.
2. Remove fan speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 11).
3. Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 6 to the system static to determine the correct cooling airflow speed in Table 4 that will deliver the nominal cooling airflow as listed in Table 1 for each size.
NOTE: If accessory electric heat is installed, the dry airflow must meet or exceed the minimum airflow speed specified in Table 2 for the specific size unit. The electric heat fan speed will be the same as the normal cooling fan speed.
4. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding) for the normal cooling fan speed and place desired speed tap wire on “HIGH” on the interface board.
5. Refer to airflow tables (Table 4) to determine allowable speeds for the dehumidification cooling fan speed. In T able 4, speeds that are not allowed for dehumidification cooling are shaded.
6. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the “LOW” connection on the interface board (IFB). V erify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling.
7. Use any spare vinyl plugs to cap any unused speed tap wires.
used)
50VL -- A
13
Page 14
HIGH LOW COM
QC5
07 09 080L0
C9
QIL Z2 06 04
D5 D3
P3
SDL
R2
50VL -- A
SSTZ-8
ALO
C4
C7
JW5
QCB
Y
STD
KZ
R13 C8 R11 Q1
A7 R9 AB A15
R3 R5 R6
P1
QC4
DEHUM
U1
P2 JW3
R W2 Y C W3W3W2 W2C
Y2 Y1
W2W3
QC3
KL
D2
Q3
RL
G1
G2
Z1
C3
JWZ
JW4
GCR
YDH
DCR QCR
C
QC1
AL2
01
C0
R4 RL4
Fig. 11 -- Interface Fan Board (IFB)
SINGLE SPEED COOLING WITH HIGHER ELECTRIC HEAT
This unit can also be configured to operate with single speed cooling and a higher speed for an accessory electric heater.
1. Using Fig. 11, move the two pin DEHUM jumper from the “STD” position to the “DEHUM” position.
2. See Table 2 for minimum airflow for electric heat operation. Add electric heater and filter pressure drop to duct system static pressure to determine total external static pressure.
3. Select speed tap from Table 4 that will achieve required airflow from Table 2.
4. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding).
5. Connect the desired speed tap wire to the “HIGH” terminal on the interface fan board (IFB).
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit component damage or improper operation.
To use this mode, a speed connection must be made on the “HIGH” terminal that meets or exceeds the minimum airflow found in Table 2.
SPEED
CAUTION
F1
P4
24VAC/R3AMP CDM/C
A09059
Table 3 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med--High Speed
Red = Med Speed
Pink = Med--Low Speed
Blue = Low Speed
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before changing blower speed.
CONTINUOUS FAN OPERATION
When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 11).
COOLING SEQUENCE OF OPERATION
With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequence of operation is as follows:
When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and time delay relay (TDR) (through unit wire G) across the 24-- V secondary of transformer (TRAN).
The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly.
A set of normally open contacts on the interface fan board (IFB) are closed which energizes a circuit to the indoor fan motor (IFB).
NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to a point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat breaks the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C and IFB. The condenser and compressor motors stop. After a 90--second delay, the blower motor stops. The unit is in a standby condition, waiting for the next call for cooling from the room thermostat.
14
Page 15
Table 4 – Dry Coil Air Delivery* -- Horizontal Discharge -- Unit 50VL--A24 --60
50VL -- A
EXTERNAL STATIC PRESSURE (IN. W.C.)
EXTERNAL STATIC PRESSURE (IN W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Table 5 – Dry Coil Air Delivery -- Downflow Discharge
Red CFM 941 851 774 684 576 479 --- --- ---
Orange CFM 1140 1064 996 915 840 758 687 564 480
Red CFM 1354 1290 1226 1158 1102 1046 981 918 843
Orange CFM 1545 1492 1449 1411 1362 1313 1278 1231 1188
Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381
Red CFM 1962 1915 1880 1843 1794 1753 1711 1675 1628
High Black CFM 1241 1167 1111 1036 969 881 818 731 640
1
Low Blue CFM 741 638 547 415 --- --- --- --- ---
Medium Red CFM 1088 1023 954 881 800 723 658 563 461
Med-Low Pink CFM 973 887 823 733 665 538 451 --- ---
1
Low Blue CFM 1234 1168 1093 1021 961 894 825 759 687
High Black CFM 1202 1140 1082 1015 961 881 810 732 631
Medium
Med-Low Pink CFM 1290 1223 1154 1090 1027 977 894 828 762
Med-High
Med-High Orange CFM 1606 1546 1489 1430 1371 1316 1258 1208 1140
1
Low Blue CFM 754 650 538 429 --- --- --- --- ---
Medium
Med-Low Pink CFM 851 777 675 591 475 --- --- --- ---
Med-High Orange CFM 1009 917 840 759 667 577 447 --- ---
High Black CFM 1630 1580 1517 1463 1407 1339 1277 1210 1131
Low Blue CFM 1295 1234 1182 1126 1075 1016 955 898 857
Med-Low Pink CFM 1345 1282 1235 1194 1140 1095 1027 974 921
1
Medium Red CFM 1505 1452 1413 1358 1323 1282 1234 1169 1130
1
Low Blue CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041
High Black CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360
Med-Low Pink CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104
Med-High
1
High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803
Med-Low Pink CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
High Black CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Medium
Med-High Orange CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Medium
Med-High Orange CFM 2149 2111 2062 2026 1980 1945 1905 1864 1793
MOTOR SPEED WIRE COLOR
UNIT MOTOR SPEED WIRE COLOR
50VL-A24
50VL-A30
50VL-A36
50VL-A42
50VL-A48
50VL-A60
Factory--- shipped cooling speed
Note: Deduct field- -- supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
* Air delivery valu es are without air filter and are for dry coil (See Table 6 --- 50VL --- A Wet Coil Pressure Drop table).
Note: Deduct 10% for 208 volt operation.
1
UNIT
50VL---A24 High Black 1050 1000 950 900 850 - - - - -
50VL---A30 High Black 1050 1000 950 900 850 - - - - -
50VL---A36 High Black 1615 1555 1495 1435 1375 1320 1260 1200 1140 -
50VL---A42 High Black 1775 1710 1670 1630 1580 1540 1505 1460 1415 -
50VL---A48 High Black 2505 2440 2345 2295 2215 2120 2040 1990 1750 -
50VL---A60 High Black 2530 2445 2380 2325 2250 2155 2080 1965 1880 -
15
Page 16
50VL -- A
STANDARD CFM (SCFM)
STANDARD CFM (SCFM)
STANDARD CFM (SCFM)
STANDARD CFM (SCFM)
Small Cabinet: 24 --36
STANDARD CFM (SCFM)
Large Cabinet: 42--60
Table 9 – Electric Heat Pressure Drop T ables (IN. W.C.)
Table 8 – Horizontal and Downflow Filter Pressure Drop Table (IN. W.C.)
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
Table 6 – 50VL--A Horizontal and Downflow Discharge Wet Coil Pressure Drop (IN. W.C.)
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
24 0.030 0.037 0.044 0.053 0.063 - - - - - - - - - - - -
30 - - - 0.053 0.063 0.072 0.081 0.105 - - - - - - - - -
36 - - - 0.055 0.060 0.090 0.100 0.110 0.140 - - - - - - - -
42 - - - - 0.045 0.050 0.060 0.065 0.075 0.080 0.090 0.094 0.110 - - - -
SIZE
UNIT
48 - - - - - - 0.041 0.063 0.085 0.100 0.104 0.110 0.120 0.130 0.140 - -
Table 7 – Horizontal and Downflow Economizer with 1--in. Filter Pressure Drop (IN. W.C.)
60 - - - - - - - - - 0.060 0.065 0.007 0.077 0.085 0.100 0.115 0.125
0.07 0.08 0.10 0.14 0.17 0.21 0.25 0.31 0.35 - - - - - - - -
3.0
TONS
COOLING
DOWNFLOW
ECONOMIZER +
INCLUDED FILTERS
5.0 - - - - - - - - - 0.10 0.12 0.13 0.15 0.17 0.18 0.20 0.23
3.5, 4.0 - - - - - - 0.10 0.12 0.13 0.15 0.17 0.19 0.22 - - - -
2.0, 2.5,
600-1400 cfm
1200-1800 cfm
1500-2200 cfm
(12x20x1+12x20x1)
(16x24x1+14x24x1)
(16x24x1+18x24x1)
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
TONS
COOLING
(mm)
FILTER SIZE in.
2.0,
600-1400 cfm
0.05 0.07 0.08 0.09 0.10 0.11 0.13 0.14 0.15 - - - - - - - -
2.5,
- - - - - - 0.07 0.08 0.09 0.10 0.11 0.11 0.12 - - - -
3.0
3.5,
1200-1800 cfm
(12x20x1+12x20x1)
5.0 - - - - - - - - - 0.08 0.10 0.10 0.11 0.12 0.13 0.14 0.15
4.0
1500-2200 cfm
(16x24x1+14x24x1)
(16x24x1+18x24x1)
STATIC
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
5kW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
10 kW 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07 0.09 0.10 0.11
15 kW 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18
20 kW 0.00 0.00 0.02 0.04 0.06 0.08 0.09 0.11 0.13 0.15 0.17 0.19
5kW 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.1 1 0.12
10 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13
15 kW 0.00 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15
STATIC
20 kW 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16
16
Page 17
50VL -- A
Fig. 12 -- Connection Wiring Diagram 208/230--1-- 60
17
A11004
Page 18
50VL -- A
Fig. 12 Cont. -- Ladder Wiring Diagram 208/230--1--6 0
18
A11003
Page 19
50VL -- A
Fig. 13 -- Connection Wiring Diagram 208/230--3-- 60
19
A11010
Page 20
50VL -- A
Fig. 13 Cont. -- Ladder Wiring Diagram 208/230--3--6 0
20
A11009
Page 21
CONNECTION WIRING DIAGRAM
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
BLK
C
11 21
13 23
YEL
460
24
IF USED
RED
BLU
BLK
RED
C
1423
AUTOTRANSFORMER
TRAN
BLK
FU1 5 AMP
FU2 5 AMP
YEL
C
460
24
BRN
460V
FOR WIRING WITH ELECTRIC HEATERS SEE SCHEMATIC ON HEATER ACCESSORY.
2435
1
COMPRESSOR PLUG
L2
GND
L1
COM
BRN
OFM
COMP
BLK
YEL
BLK
230V
SEE NOTE 8
RED
BLK
YEL
BLK
CAP
GND
GRN/YEL
YEL
BRN
T1
T3
YEL
T2
BLU
GRN-YEL
SEE NOTE 5 & 6
BRN
RED
BLU
YEL
FIELD
SUPPLY
POWER
UNIT ONLY MAXIMUM WIRE SIZE 2 AWG.
ECON PLUG
7 7
6 6
11 11
10 10
8 8
2 2
3 3
4 4
1 1
5 5
9 9
12 12
L1
EQUIP_GND
CCH
GRN
BLK
1
BLK
1
L3
YEL
1
L2
BLK
ECON
PNK
BLU
SAT
BLU
PNK
GRY
RED
BRN
YEL
BLK
SCHEMATIC
460-3-60
IFM
BLU
PNK
SEE NOTE 4
50VL -- A
RED
ORN
BLK
TSTAT
GRY
Y2
SEE NOTE 7
RED
R
BRN
C
YEL
Y1
GRN
G
DH
BLU
W2
WHT
VIO
W3
UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN SECTION
COMPRESSOR SECTION
INDOOR FAN SECTION
LPS
HPS
CAP
CF
H
COMP
C
S
CCH
R
SEE NOTE 9
R
C
COM
24VAC
3A
FUSE
P1
C
R
OFM
IFM
LOW
COM
COM
54321
6
7
G
W3
W2
Y1/Y
Y2/DH
CONTROL BOX AREA
SINGLE PT. CONNECTION FOR ELECT.HEAT
SEE HEATER SCHEMATIC FOR WIRING
STD
P2
21
TRAN
24V SPLICE
IFB
123
C
IFB
BOX
Y
C
HIGH
DEHUM
4
R
W2
11
1323
Y
EQUIP. GND
24V POWER ENTRY
12435
P4
C
W2
DISCONNECT PER NEC
ACCESSSORY ELECTRIC HEAT
1
WHT
1
VIO
1
PNK
1
GRY
1
BLK
COLOR CODE
BLK BLACK BLU BLUE BRN BROWN GRY GRAY GRN GREEN ORN ORANGE PNK PINK RED RED VIO VIOLET WHT WHITE
YEL YELLOW
BRN
HPS
BLK
NOTES:
1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED, IT MUST BE REPLACED WITH TYPE 90 DEGREE C WIRE OR IT'S EQUIVALENT.
2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.
3. USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION.
4. REFER TO INSTALLATION INSTRUCTIONS FOR CORRECT SPEED SELECTION OF IFM.
5. RELOCATION OF SPEED TAPS MAY BE REQUIRED WHEN USING FIELD INSTALLED ELECTRIC HEATERS, CONSULT INSTALLATION INSTRUCTIONS TO DETERMINE CORRECT SPEED TAP SETTING.
6. "DO NOT DISCONNECT PLUG UNDER LOAD."
7. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257003
8. THESE FUSES ARE MANUFACTURED BY COOPER BUSSMAN, P/N FNQ-R-5
9. DEHUM FEATURE CANNOT BE USED WHEN ECONOMIZER IS INSTALLED. UNIT FACTORY-SHIPPED IN STD MODE.
W3
W2
W3
HR1 (5 KW)
WHT
VIO
HR1,2,3
PNK
HR1 & 2 (10 KW)
GRY
HR1,2 & 3 (15 KW)
BRN
BLU
LEGEND
FIELD SPLICE
TERMINAL (MARKED)
TERMINAL (UNMARKED)
SPLICE (IF USED) SPLICE (MARKED)
FACTORY WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING ACCESSORY OR OPTIONAL WIRING
TO INDICATE COMMON POTENTIAL ONLY: NOT TO REPRESENT WIRING
& 4 (20 KW)
LPS
HR1
1
1
HR4
HR2
HR3
BLU
C CONTACTOR CAP CAPACITOR CCH CRANK CASE HEATER
ENERGIZED
COMP COMPRESSOR MOTOR DH DEHUMIDIFICATION MODE DEHUM DEHUMIDIFICATION MODE ECON ECONOMIZER GND GROUND HPS HIGH PRESSURE SWITCH HR HEATER RELAY IFB INTERFACE FAN BOARD IFM INDOOR FAN MOTOR LPS LOW PRESSURE SWITCH OFM OUTDOOR FAN MOTOR STD STANDARD MODE TRAN TRANSFORMER
BRN
3
BRN
BRN
3
BRN
BRN
C
C2
C1
A10204C
Fig. 14 -- Connection Wiring Diagram 460--3 --60
21
Page 22
LADDER WIRING DIAGRAM
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
YEL
L3
YEL
13
13
L1
L2
BLK
11
11
11
50VL -- A
BLK
BLK
IF USED
21
RED
BLK
BLK
BLU
BLK
C
G/Y
CCH
OFM
C
BRN
CAP
T1
COMP
G
L
N
X
GRN
R
S
YEL
YEL
YEL
T2
T3
G/Y
C
23
IFM
460V
TRAN
460V
SEE NOTE 7
R C
Y1 G
DH
W2
W3
Y2
RED
BRN YEL
GRN
BLU
WHT
VIO
VIO
G/Y
C
24V
BRN
BRN
BRN
YEL
C1
BRN
C2
C
BRN
BLK
RED
24VAC
RED
IFB
FUSE 3A
P1-1
"R"
P1-2
"C"
P1-3
"Y1/Y"
P1-4
"G"
P1-5
"Y2/DH"
P1-6
"W2"
P1-7
"W3"
P2-1 P2-2 P2-3 P2-4
Y
ACCESSORY
ELECTRIC HEAT
P4-1
P4-2
P4-3
YEL
P4-4
P4-5
LOW
STD
DEHUM
HIGH
WHT
VIO
PNK
GRY
BRN
SEE NOTE 9
SEE NOTE 4
BLK
WHT
VIO
PNK
GRY
HPS
BRN
PNK RED
BLK
BLK
BLU
ORN
HR1
HR4
HR2
HR3
BLU
24V
LPS
BLU
1 2
IFM
3 4
5
13
C,TRAN
BRN
ECON
HARNESS
2
3 4
5
6
7
8
BRN
PNK
PNK
COM C
BLU
BLU
BLK
SAT
G/Y
C
RED
BRN
50VL500271
D
A10204
Fig. 14 Cont. -- Ladder Wiring Diagram 460--3 -- 60
22
Page 23
50VL -- A
Fig. 15 -- Cooling Charging Chart
23
A09089
Page 24
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 8, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
!
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and possible unit component damage.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not
50VL -- A
attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner’s Manual.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow these warnings could result in personal injury or death:
1. Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on this unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact with the unit.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling season. Clean when necessary.
4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when necessary.
5. Ensure electric wires are not in contact with refrigerant tubing or sharp metal edges.
Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the same dimensional size and type as originally installed. See T able 1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway--type) or clean (cleanable--type) at least twice during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint.
Indoor Blower and Motor
NOTE: All motors are pre-- lubricated. Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect and tag electrical power to the unit before cleaning the blower motor and wheel.
To clean the blower motor and wheel:
1. Remove and disassemble blower assembly as follows:
a. Remove blower access panel (see Fig. 17).
b. Disconnect 5 pin plug and 4 pin plug from indoor
blower motor. Remove capacitor if required.
c. On all units remove blower assembly from unit.
Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation.
b. Lift wheel from housing. When handling and/or
cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
c. Remove caked--on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit.
f. Connect 5 pin plug and 4 pin plug to indoor blower
motor. Reinstall capacitor if required.
g. Reinstall blower access panel (see Fig. 17).
3. Restore electrical power to unit. Start unit and check for
proper blower rotation and motor speeds during cooling cycles.
24
Page 25
MOTOR
FAN GRILLE
A
MOTOR SHAFT
A08505
MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE
SIZE
24 6.3 160 30 6.3 160 36 7.3 185 42 7.6 193 48 7.6 193 60 7.6 193
IN. MM
Fig. 16 -- Fan Blade Position
air filter(s). If the drain trough is restricted, clear it with a “plumbers snake” or similar probe device.
OUTDOOR FAN
“A”
50VL -- A
Control Access Panel
A09214
Compressor Access Panel
Blower Access Panel
Fig. 17 -- Unit Access Panels
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components.
Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.
1. Remove 6 screws holding condenser grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the
fan off the motor shaft.
5. When replacing fan blade, position blade as shown in Fig.
16.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening
7. Replace grille.
Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.
Remove access panels (see Fig. 17) to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the access panels (see Fig. 17). Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in either or both operating cycles, or if a suspected malfunction has occurred, check
25
Page 26
each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation in this publication as an aid in determining proper control operation
Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrigerant leak.
!
WARNING
EXPLOSION, SAFETY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or equipment damage.
This system uses Puron (R--410A) refrigerant which has
50VL -- A
higher operating pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron. If you are unsure, consult the equipment manufacturer.
charge so that pressure gauges read 0 psi (0 Pa). Never open system without breaking vacuum with dry nitrogen.
High--Pressure Switch
The high--pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig (31.1 kPa). High pressure may be caused by a dirty condenser coil, failed fan motor, or condenser air recirculation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmmeter leads across switch. You should have
continuity on a good switch.
Copeland Scroll Compressor (Puron Refrigerant)
The compressor used in this product is specifically designed to operate with Puron (R--410A) refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrigerants present additional safety hazards.
!
WARNING
If oil is detected or if low cooling performance is suspected, leak--test all refrigerant tubing using an electronic leak--detector, halide torch, or liquid--soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.
Evaporator Airflow
The heating and/or cooling air--flow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply-- and return--air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to Indoor Airflow and Airflow Adjustments section to check the system airflow.
Puron Items
The indoor metering device is a TXV type device.
Pressure Switches
Pressure switches are protective devices wired into the control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R--410A) systems. R--22 pressure switches must not be used as replacements for the Puron (R--410A) air conditioner.
Loss of Charge/Low--Pressure Switch (Air Conditioner Only)
This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig (957 Pa). If system pressure is above this, switch should be closed.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmmeter leads across switch. You should have continuity on a good switch.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system
FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with a noise reducing shutdown device and an internal pressure relief port. The pressure relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 (26.3 kPa) and 625 (29.9 kPa) psig differential pressure.
Refrigerant
!
WARNING
EXPLOSION, ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or equipment damage.
This system uses Puron (R--410A) refrigerant which has higher operating pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron. If you are unsure, consult the equipment manufacturer.
This system uses Puron (R--410A) refrigerant which has higher operating pressures than R --22 and other refrigerants. No other refrigerant may be used in this system. Gage set, hoses, and recovery system must be designed to handle Puron. If you are unsure, consult the equipment manufacturer. Failure to use Puron compatible servicing equipment or replacement components may result in property damage or injury.
Compressor Oil
The Copeland scroll compressor uses 3MAF POE oil. If additional oil is needed, use Uniqema RL32--3MAF . If this oil is not available, use Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely hygroscopic, meaning it absorbs water
26
Page 27
readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
Servicing Systems on Roofs with Synthetic Materials
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionary Procedure
1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate10x10ft (3x3m)area.
2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills, prevent run--of fs, and protect drop cloth from tears caused by tools or components.
3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run -- offs through the louvered openings in the unit base.
4. Perform required service.
5. Remove and dispose of any oil contaminated material per local codes.
Liquid Line Filter Drier
The filter drier is specifically designed to operate with Puron. Use only factory--authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.
Puron (R--410A) Refrigerant Charging
Refer to unit information plate and charging chart. Some R--410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For cylinders equipped with a dip tube, charge Puron units with cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant into suction--line.
TROUBLESHOOTING
Refer to the Troubleshooting Chart (Table 10) for troubleshooting information.
START--UP CHECKLIST
Use the Start--Up Checklist at the back of this manual.
50VL -- A
27
Page 28
Table 10 – Troubleshooting Chart
SYMPTOM CAUSE REMEDY
Compressor and outdoor fan will not start
Compressor will not start but condenser fan runs
Three--phase scroll compressor (size 30-­60 unit) has a low pressure differential 3--phase power leads to the unit
50VL -- A
Compressor cycles (other than normally satisfying) cooling/heating calls
Compressor operates continuously
Excessive head pressure
Head pressure too low
Excessive suction pressure Refrigerant overcharged Recover excess refrigerant
Suction pressure too low
Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective contactor, transformer, control relay, or high--
pressure, loss --of --charge or low--pressure switch Insufficient line voltage Determine cause and correct Incorrect or faulty wiring Check wiring diagram and rewire correctl y Thermostat setting too low/too high Reset thermostat setting Faulty wiring or circuit Loose connections in compressor Compressor motor burned out, seized, or Determine cause internal overload open Replace compressor Defective run capacitor, overload, or PTC (positive temperature coefficient) thermistor
One leg of 3- -phase power dead
Low input voltage Determine cause and correct
Scroll compressor is rotating in the wrong direction
Refrigerant overcharge or undercharge
Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run/start capaci tor, overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat temperature set too low Reset thermostat setting Low refrigerant charge Locate leak, repair, and recharge
Air in system
Outdoor coil dirty or restricted Clean coil or remove restriction Dirty air filter Replace filter Dirty indoor or outdoor coil Clean coil Refrigerant overcharged Recover excess refrigerant
Air in system
Indoor or outdoor air restricted or air short--cycling Determine cause and correct Low refrigerant charge Check for leaks, repair and recharge Restriction in liquid tube Remove restriction
Dirty air filter Replace filter Low refrigerant charge Check for leaks, repair and recharge Metering device or low si de restricted Remove source of restriction Insufficient coil airflow Check filter–replace if necessary Temperature too low in conditioned area Reset thermostat setting Outdoor ambient below 55°F(13°C) Install low--ambient kit Filter drier restricted Replace
Replace component
Check wiring and repair or replace
Determine cause and replace
Replace fuse or reset circuit breaker Determine cause
Correct the direction of rotation by reversing the
Recover refrigerant, evacuate system, and re­charge to capacities shown on rating plate
Recover refrigerant, evacuate system, and re­charge
Recover refrigerant, evacuate system, and re­charge
28
Page 29
AIR CONDITIONER WITH PURON (R--410A) QUICK REFERENCE GUIDE
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron. Puron refrigerant cylinders are rose colored.
S Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright
position.
Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
S Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400. S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose. S Manifold sets should be minimum 700 psig high--side and 180 psig low--side with 550 psig low--side retard. S Use hoses with minimum 700 psig service pressure rating. S Leak detectors should be designed to detect HFC refrigerant. S Puron, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil. S Only use factory specified liquid--line filter driers with rated working pressures no less than 600 psig. S Do not install a suction--line filter drier in liquid line. S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A Puron liquid-- line filter drier is required on every unit. S Do not use an R--22 TXV. S Never open system to atmosphere while it is under a vacuum. S When system must be opened for service, break vacuum with dry nitrogen and replace filter driers. S Always replace filter drier after opening system for service. S Do not vent Puron into the atmosphere. S Observe all warnings, cautions, and bold text. S Do not leave Puron suction line driers in place for more than 72 hrs.
50VL -- A
29
Page 30
START--UP CHECKLIST
(Remove and Store in Job Files)
I. PRELIMINARY INFORMATION
MODEL NO.:
SERIAL NO.: DATE:
TECHNICIAN:
II. PREST ART--UP (Insert check mark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS ( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL ( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
III. START-- UP
50VL -- A
ELECTRICAL
SUPPLY VOLTAGE COMPRESSOR AMPS
INDOOR (EVAPORATOR) FAN AMPS
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE DB RETURN--AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB
PRESSURES
REFRIGERANT SUCTION PSIG, SUCTION LINE TEMP* REFRIGERANT DISCHARGE PSIG, LIQUID TEMP{ ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
* Measur ed at suction inlet to compressor { Measured at liquid line leaving condenser.
Copyright 2011 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 01/11
Manufacturer reserves the ri ght to change, at any time, specifications and designs without notice and without obligations.
30
Catalog No:50VL--- 08SI
Replaces: 50VL---07SI
Loading...