Carrier 50TJM User Manual

Page 1
Installation, Operation and Maintenance Instructions
50TJM
Nominal Cooling Capacity 15 - 28 Tons
HFC R - 410A Refrigerant
Note: T his manual discusses the Mechanical Installation of this unit, Start-up Procedures, Operating Sequences
Quality Assurance
04 100 950420
Package Rooftop Units
Page 1
Certificate Reg. No:
Subject to change without notice Manufacturing point: Jeddah, Saudi Arabia Nearest port of embarkation: Jeddah Islamic port Product classification: Commercial
and Service Instructions. Read thoroughly the entire insta llation ins truction m anual bef ore starti ng the unit installation, to get familiarized with
all steps and to identify if any additional reference materials as required.
The 50TJM units are single side discharge rooftop cool ing unit utilizing electric heat as an option. Units are pre­wired, pre-charged with R-410A refrigerant, and tested at the factory. These units can b e placed on the side of a building or can be plac ed o n a roof without roof c urbs. Eac h unit is desi gned to occup y a minim al space. Piping an d drain connections are readily accessible.
For a complete list of options and accessories, refer to the Product Data Catalog. Contact your local Carrier representative for additional reference materials.
Page 2
Table of Contents
Page 2
1.0 – SAFETY CONSIDERATIONS ....................................................................................................... 3
1.1 – General ............................................................................................................................. 3
1.2 – Installation Safet y Cons iderat io ns ..................................................................................... 3
1.3 – Warranty ............................................................................................................................ 3
Physical Data ......................................................................................................................................... 5
Unit Dimensional Drawing.............................................................................................................. 6 – 7
2.0 – INSTALLATION ............................................................................................................................. 8
2.1 – Jobsite Survey ................................................................................................................... 8
2.2 – Plan for Unit Location ........................................................................................................ 8
2.3 – Rig and Place Unit ............................................................................................................ 8
2.4 – Positioning and Clearance ................................................................................................ 9
2.5 – Field Fabricate Ductwork .................................................................................................. 9
2.6 – Make Unit Duct Connections ............................................................................................ 9
2.7 – Trap Condensate Drain ................................................................................................... 10
2.8 – Outdoor Air-Vent ............................................................................................................. 10
2.9 – Make Electrical Connections ........................................................................................... 10
Electrical Data ..................................................................................................................................... 11
Electrical Resistance Heater Data ..................................................................................................... 12
Typical Wiring Schematic........................................................................................................... 13 – 14
3.0 – START–UP INSTRUCTIONS ...................................................................................................... 15
3.1 – Unit Preparation .............................................................................................................. 15
3.2 – Internal Wiring ................................................................................................................. 15
3.3 – Compressor Mounting ..................................................................................................... 15
3.4 – Refrigerant Service P or ts ................................................................................................ 15
3.5 – Compressor Rotation ...................................................................................................... 15
3.6 – Evaporator Fan ............................................................................................................... 15
3.7 – Condenser Fans and Motors ..........................................................................................
3.8 – Return – Air Filters .......................................................................................................... 16
3.9 – Base Unit Operation ........................................................................................................ 16
4.0 – SERVICE ..................................................................................................................................... 16
4.1 – Cleaning .......................................................................................................................... 16
4.2 – Lubrication ....................................................................................................................... 16
4.3 – Evaporator Fan Performance Adjustment ...................................................................... 17
4.4 – Evaporator Fan Service and Replacement ..................................................................... 17
4.5 – Belt Tension Adjustment ................................................................................................. 18
4.6 – Condenser – Fan Adjustment ......................................................................................... 18
4.7 – Refrigerant Charge.......................................................................................................... 18
4.8 – Protective Devices .......................................................................................................... 18
4.9 – Control Circuit, 24 – V ..................................................................................................... 19
5.0 – REPLACEMENT PARTS ............................................................................................................ 19
Fan Performance Table .............................................................................................................. 20 – 23
Cooling Chart .............................................................................................................................. 24 – 25
Troubleshooting .................................................................................................................................. 26
Start–up Check List ............................................................................................................................ 27
16
Page 3
1 – SAFETY CONSIDERATIONS
Page 3
1.1 General
Improper installation, adjustment, alteration, service, maintenance or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer; service agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all the safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes for special requirements. In absence of local codes, it is recommended that the USA standard ANSI/NFPA 70, National Electrical Code (NEC), be followed.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury of death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1.2 Installation Safety Considerations
After the unit has been received and when it is ready to be installed or reinstalled, it must be inspected for damage. If damage is detected upon receipt, immediately file a claim with the shipping company or repair.
This machine must be installed in a location that is not accessible to the public and protected against access by non-authorized people.
This machine must not be installed in an explosive atmosphere.
Do not remove the skid or the packaging until the unit is in its final position. These units can be moved with a fork lift truck, as long as the forks are positioned in the right place and direction on the unit.
The units can also be lifted with slings, using only the designated lifting points marked on the unit (labels on the chassis and a label with all unit handling instructions are attached to the unit). Use slings with the correct capacity, and always follow the lifting instructions on the certified drawings supplied for the unit.
Safety is only guaranteed, if these instructions are carefully followed. If this is not the case, there is a risk of material deterioration and injuries to personnel. These units are not designed to be lifted from above.
1.3 – Warranty
Warranty is based on the general terms and conditions of the manufacturer. Any modifications to the design and/or installation made without discussion with Carrier and without advance written agreement will result in the loss of the right to any warranty claims and any claim for injury to personnel as a result of these modifications.
Page 4
Units have high ambient operation limits. If limits are exceeded, the unit will automatically lock the
compressor out of operation. Manual reset will be required to restart the compressor.
Failure to follow this warning could cause personal injury, death and /or equipment damage.
Failure to follow this warning could cause personal injury or death damage.
Puron® (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron® refrigerant equipment.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
NOTE
IMPORTANT
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment
WARNING
WARNING
UNIT OPERATION AND SAFETY
HAZARD
PERSONAL SAFETY AND ENVIRONMENTAL
HAZARD
WARNING
CAUTION
ELECTRIC SHOCK HAZARD
CUT HAZARD
Failure to follow this warning could cause personal injury or death.
Failure to follow this warning could cause personal injury.
Page 4
Page 5
Physical Data Table - 1
Circuts No.
Low Pressure Switch (Trip / Reset) - PSIG
Fins
Qty x Face Area (ft2)
Quantity
Qty x Face Area (ft2)
Coil Test Pressure
Movable Pulley Maximum Full Turns From Closed Position
Approx.Speed Change Per Full Turn Of Movable Pulley Flange (rpm)
Page 5
50TJM Unit Physical Data (50Hz) (English)
Unit 50TJM Size
Unit Dimensions Unit Operating Weight
Refrigeration System
Compressor No. / Type Stage Of Capacity Control (%) Refrigerant Type
Charge Per Circuit (Down / Up) -LBS 15.96 / 15.96 22.19 / 25.62 31.19 / 29.19 31.62 / 31.37 Metering Device Filter Drier Qty / Size High Pressure Switch (Trip / Reset) - PSIG
Freeze Protection Thermostat (Open / Close) ±1.8 0F
Condenser Coil
Coil Type
18 24 28 34
Page - 9 Page - 9
2 / Scroll
50 / 50
Puron ® R410A
2
TXV - Adjustable
2 / DML085S
630 / 480
54 / 70
-18 / -14
Copper Tube, Aluminum Double Wavy Fins
Page - 10 Page - 10
2 / DMS165S
Copper Tube,
Aluminum LSW
Standard Coil Material Qty x Rows x FPI 1 x 3 x 16 1 x 4 x 16
1 x 26.7 2 x 28.8
Coil Test Pressure (PSIG)
Condenser Fan & Motor
Approx. Air Flow Rate (CFM) 12000 13000 18200 16700
Diameter (in) / No. of Blades Motor Type Motor HP / RPM
Evaporator Coil
Coil Type Standard Coil Material Qty x Rows Qty x FPI
Drain Pan connection Size (in) Return Air Filter Qty x Size (in)
Evaporator Fan and Motor Section
Fan Quantity / Fan Size (in) Fan Type Drive Type Motor Type Motor BHP 4.0 7.5 Motor Frame Size / Motor Shaft Diameter (mm) 100 / 28 132 / 38 Motor Pulley Pitch Diameter (Min / Max) (in) 4.3 / 5.6 Fan RPM Range (RPM) 1030 - 745 1029 - 740 Fan Pulley Pitch Diameter (in) 8.4 Belt, Quantity...Type 1 ... BX71 Pulley Center To Center Distance(in)
30 / 4 30 / 6
Copper Tube, Aluminum LSW Fins.
2 x 3 x 17 2 x 4 x 17
2 x 9.75 2 x 10.3
4 x 33.8 x 21.7 4 x 35.4 x 21.7
1 / 15.75 x 15.75 1 / 17.7 x 17.7
Copper / Aluminium
2 x 3 x 17
450
2
Induction Motor - Totally Enclosed
1 / 950
Copper / Aluminium
350
3/4
Centrifugal - Forward Blade
Belt
Induction Motor - TEFC
5.5
112 / 28
3.7 / 4.7 1041 - 753
6.6
1 ... BX66
24.4 - 27.51
6
Factory Speed Turns Setting 1.5 Factory Belt Standard Deflection (in) @ Force (Lb) 0.39 @ 4.65 Lb 0.40 @ 6.63 Lb
48
4
0.39 @ 5.99 Lb
Page 6
LENGTH WIDTH DEPTH A B C D TOTAL K L M 50TJM - 18 192 178 236 254 860 50TJM - 24 197 182 241 260 880
6. Dimensions are from outside of corner post. Allow 8mm on each side for top cover drip edge.
UNIT DIMENSIONAL DRAWING: 50TJM - 18 and 50TJM - 24 (Fig - 1)
1375
1050
1050
450
UNIT
SHIPPING DIMENSIONS (mm)
CORNER WEIGHT (Kg)
CENTER OF GRAVITY (mm)
2440
2235
7. Weights are Given for aluminim evaporator and condenser coil plate fins
5. With the exception of clearance for the condenser coil and the damper / power exhaust as stated in Note no. 6, a removal fence or barricade requires no clearance.
TOP: 1829mm to assure proper condenser fan operation.
SIDE: 1219mm for Compressor, Filter and Control boxes access.
- Local codes or jurisdiction may prevail.
4. Minimum clearance:
NOTES:
REAR: 2134mm for coil removal. This dimension can be reduced to 1219mm if conditions permit coil removal from the top.
2. Center of Gravity.
3. Direction of Airflow
1. Dimensions are in millimeters.
Page 6
Page 7
LENGTH WIDTH DEPTH A B C D TOTAL K L M 50TJM - 28 248 226 310 340 1125 50TJM - 34 254 231 317 348 1150
NOTES:
6. Dimensions are from outside of corner post. Allow 8mm on each side for top cover drip edge.
7. Weights are Given for aluminim evaporator and condenser coil plate fins
REAR: 2134mm for coil removal. This dimension can be reduced to 1219mm if conditions permit coil removal from the top.
TOP: 1829mm to assure proper condenser fan operation.
SIDE: 1219mm for Compressor, Filter and Control boxes access.
- Local codes or jurisdiction may prevail.
5. With the exception of clearance for the condenser coil and the damper / power exhaust as stated in Note no. 6, a removal fence or barricade requires no clearance.
1400
1350
1160
UNIT DIMENSIONAL DRAWING: 50TJM - 28 and 50TJM - 34 (Fig - 2)
UNIT
SHIPPING DIMENSIONS (mm)
CORNER WEIGHT (Kg)
CENTER OF GRAVITY (mm)
450
1. Dimensions are in millimeters.
2. Center of Gravity.
3. Direction of Airflow
4. Minimum clearance:
3200
2485
Page 7
Page 8

2 – INSTALLATION

Page 8

2.1 – Jobsite Survey

Complete the following checks before installation.
1. Consult local building codes or the U.S.A. National Electrical Code (Ref: ANSI/NFPA 70, [American National Standards Institute/National Fire Protection Association], latest revision) for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.

2.2 – Plan for Unit Location

Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in Fig - 3. For the centre of gravity coordinates, the position of the unit mounting holes, and the weight distribution points, refer to the unit dimensional drawing Fig - 1 and Fig - 2.
Fig. 3 Unit Clearance Diagram
NOTES:
1. Minimum clearance: REAR: 2134mm for coil removal. This dimension can be reduced to 1219mm if conditions permit coil removal from the top. TOP: 1829mm to assure proper condenser fan operation. SIDE: 1219mm for Compressor, Filter and Control boxes access.
- Local codes or jurisdiction may prevail.
2. With the exception of clearance for the condenser coil and the damper / power exhaust as stated in Note no. 3, a
removal fence or barricade requires no clearance.
3. Dimensions are from outside of corner post. Allow 8mm on each side for top cover drip edge.

2.3 – Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof Level by using unit frame as a reference; leveling tolerance is± 1/16 in. per linear ft in any direction. Four lifting holes are provided in ends of unit base rails as shown in Fig – 4 Refer to rigging instructions on unit.
Fig. 4 Rigging Diagram
Roof mount - Check building codes for weight distribution requirements. Unit weight and dimensions is shown in unit
dimensional drawing Fig 1 and Fig 2 on page 6 & 7 and table 2. NOTE: Consider also the effect of adjacent units.
Page 9
SHIPPING DIMENSIONS
(mm)
WEIGHT
LENGTH
WIDTH
DEPTH
GROSS (Kg)
LENGTH
WIDTH
DEPTH
NET(Kg)
50TJM - 18
2440
2235
1375
925
2440
2182
1348
860
50TJM - 24
2440
2235
1375
945
2440
2182
1348
880
50TJM - 28
3200
2485
1400
1190
3200
2432
1374
1125
50TJM - 34
3200
2485
1400
1215
3200
2432
1374
1150
NOTE
IMPORTANT
NOTE
IMPORTANT
corner weights.
UNIT DAMAGE HAZARD
CAUTION
Page 9
UNIT
Table – 2 Unit Weights and Dimensions
NOTES:
1. Remove boards at ends of unit and runners prior to rigging.
2. Rig by inserting hooks into unit base rails as shown. Use bumper boards for spreader bars.
SHIPPING
UNIT DIMENSIONS (mm) UNIT WEIGHT
All units are internally isolated against vibration. If extra isolation required, please see “Unit Dimensional Drawing” Fig - 1 and Fig - 2 for
Failure to follow this caution may result in equipment damage. All panels must be in place when rigging.

2.4 – Positioning and Clearance.

Before positioning the unit, check the following:
The permitted loading at the site is adequate or that appropriate strengthening measures have been taken.
The unit is installed level on an even surface (maximum tolerance is 5 mm in both axes).
Ensure access to the components (see “Unit Dimensional Drawings” Fig 1 & 2 & “Clearance Diagram” Fig 3).
The number of support points is adequate and that they are in the right places.
Although the unit is weatherproof guard against water from higher level runoff and overhangs.
Unit may be installed directly on wood flooring or on approved roof - covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or sources of contaminated air.

2.5 – Field Fabricate Ductwork

Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required (a space for 2.5 to 3ft is required in case of repairing or replacing the blower wheel). Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
The 50TJM units with electric heat require a 2-in.clearance for the first 24-in. of ductwork. Outlet grilles must not lie directly below unit discharge.
A 90-degree elbow must be provided in drain hole and must be removed in ductwork to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.

2.6 – Make Unit Duct Connections

Unit is shipped for side duct connections. Ductwork openings are shown in Fig. 1 and Fig. 2.
Page 10
WARNING

2.7 – Trap Condensate Drain

to rotate in the wrong direction. This may lead to premature compressors failure.
ELECTRIC SHOCK HAZARD
NOTE
IMPORTANT
Page 10
See Fig. 5, Fig.1 and Fig. 2 for drain pipe location. Trap should be deep enough to offset the maximum unit static difference. Fig. 5 shows the recommended trap sizing.
Fig. 5 Condensate Drain Details

2.8 – Outdoor Air-Vent

All units have a manual outdoor side vent to provide ventilation air. Side vents can admit up to 10% outdoor air into indoor air section return-air compartment.

2.9 – Make Electrical Con nect i on s

FIELD POWER SUPPLY – Unit is factory wired for voltage shown on nameplate. When installing units, provide disconnect as per NEC (National Electrical Code) requirements, of adequate size. All field wiring must comply with NEC and local requirements. Route power lines through the corner post openings as shown in Fig. 1 and Fig. 2. Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units,
voltages between phases must be balanced within 2% and the current must be balanced within 10%.
The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor
Failure to follow this caution may result in equipment damage.
UNIT DAMAGE HAZARD
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with local electrical codes or in absence of local codes, it is recommended that U.S.A standard ANSI/NFPA 70, National Electrical Code be followed.
FIELD CONTROL WIRING – Install a Carrier approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature. Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from sub-base terminals through conduit in unit to low-voltage connection. Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
For wire runs up to 50 ft, use no. 18 AWG insulated wire. For 50 to 75 ft, use no. 16 AWG insulated wire. For over 75 ft, use no. 14 AWG insulated wire. All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Failure to follow this warning could result in personal injury or death.
Page 11
KW
40.6 50
HACR - Heating, Air-Conditioning and Refrigeration
Supply
IFM -
Unbalanced 3-Phase Supply Voltage
Electrical Data Table - 3
OFM -
MOCP -
Page 11
Unit Size
50TJM
18
24
28
34
50TJM Size 18 - 34 Compressor
Min Voltage
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
360 440 400 / 3 / 50
Max
Voltage
Power
V / Ph / Hz
No.1 No.2
RLA LRA RLA LRA Qty HP FLA HP FLA
12.2 101 12.2 101 2 1 3.4 Std. Eff. 4 6.3
12.2 101 12.2 101 2 1 3.4 High Eff. 4 6.15 - - 40.4 50
12.2 101 12.2 101 2 1 3.4 Std. Eff. 4 6.3 21 30.3 44.2 50
12.2 101 12.2 101 2 1 3.4 High Eff. 4 6.15 21 30.3 44.0 50
16.7 111 16.7 111 2 1 3.4 Std. Eff. 5.5 8.3 - - 52.7 60
16.7 111 16.7 111 2 1 3.4 High Eff. 5.5 8 - - 52.4 60
16.7 111 16.7 111 2 1 3.4 Std. Eff. 5.5 8.3 28 40.4 58.8 90
16.7 111 16.7 111 2 1 3.4 High Eff. 5.5 8 28 40.4 58.5 90
17.9 118 17.9 118 2 1 3 Std. Eff. 5.5 8.3
17.9 118 17.9 118 2 1 3 High Eff. 5.5 8 - - 57.3 70
17.9 118 17.9 118 2 1 3 Std. Eff. 5.5 8.3 28 40.4 61.8 100
17.9 118 17.9 118 2 1 3 High Eff. 5.5 8 28 40.4 61.5 100
21.8 140 21.8 140 2 1 3 Std. Eff. 7.5 11.3 - - 66.4 80
21.8 140 21.8 140 2 1 3 High Eff. 7.5 11
21.8 140 21.8 140 2 1 3 Std. Eff. 7.5 11.3
21.8 140 21.8 140 2 1 3 High Eff. 7.5 11
OFM
IFM Type
IFM
Electric
Heater
Appl.
- -
- -
- -
28 40.4
28 40.4
Legend and Notes for Electrical Data Table
FLA - Full Load Amps
Indoor (Evaporator) Fan Motor
LRA - Locked Rotor Amps
NEC - National Electrical Code
Outdoor (Condenser) Fan Motor
RLA - Rated Load Amps
MCA - Minimum Circuit Amps
Maximum Overcurrent Protection
◊ Fuse or HACR Circuit Breaker
* Application heater kW @ 400 volt (Using multiplication factor table in Electric Resistance Heater Data table on page 13)
MCA MOCP◊
FLA
57.6 70
66.1 80
66.4 100
66.1 100
Never operate a motor where phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance
= 100 X
Maximum Deviation From Average Voltage
Average Voltage
Example: Supply Voltage is 400V - 3ph - 50Hz
3
392 + 404 + 395
3
= 397V
AB = 392v BC = 404v AC = 395v
Average Voltage =
1191
=
Determine maximum deviation from average voltage.
(AB) 397 - 392 =5v (BC) 404 - 397 =7v (AC) 457 - 397 =2v
Maximum Deviation is 7v.
Determine Percentage Voltage Imbalance.
% Voltage Imbalance
= 100 X
7
397
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
Page 12
Cfm L/s
24
240
Electric Resistance Heater Data - Table 4
40
50TJ600730
Duct heater assembly, 50TJM 28 - 34 480 V
EXAMPLE: 30 kW (at 480 v) heater o
Page 12
UNIT
50TJM
18 2 50/50 4800 2265 24 2 50/50 6000 2832 28 2 50/50 7000 3304 34 2 50/50 7000 3304
HEATER kW HEATER FLA (PER STAGE)
Unit Voltages Unit Voltages
460
28kW
37kW
ACCESSORY HEATER PART NUMBER
460
17.3
HEATER STAGES
23
HEAT
PER
STAGES
MINIMUM HEATING
CFM
UNIT
50TJM
18
28 34
Electric Heater Kits
Kit Ordering No
NOTE: Heaters are rated at 480 V. Use the Multiplication Factors table below to determine heater capacity for your particular voltage.
Multiplication Factors
Heater Rating
Voltage
480 0.62 0.7 1
NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.413 = Btuh.
= 30.0 (0.7 multiplication factor) = 21kW
Complete Kit P.N.
50TJ600287 50TJ601162
50TJ600287 50TJ601162
50TJ600730
Duct heater assembly, 50TJM 18 480 V Duct heater assembly, 50TJM 24 480 V
Actual Heater Voltage
380 400 480
400V
Casing P.N. Heater Element P. N.
( 1 Per Kit ) ( 2 Per Kit )
50TJ600289
50TJ600727
Description
CPHEATER036A00
CPHEATER037A00
Stages
2 2 2
Size (KW)
30 40
Heater capacity(kW) is based on heater voltage of 380v or 480v. If power distribution voltage to unit varies from heater voltage, heater kW will vary accordindly. To Detemine heater capacity at actual unit voltage, muptiply 480v capacity by multipliers found in table " Multiplication Factors" above.
MCA calculation for 50TJM 18 - 34 size units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).
Page 13
Page 13
Fig. - 6
Page 14
Page 14
Fig. - 7
Page 15
3 – START-UP INSTRUCTIONS
50TJM-24
NOTE
IMPORTANT
the unit’s lockout and requires a manual reset. Reset accomplished by turning the thermostat on and off.
Page 15
Use the following instructions and start-up checklist provided on the last page to check out the unit PRIOR to unit start-up.

3.1– Unit Preparation

Check that unit has been installed in accordance with these installation instructions and all applicable codes.

3.2 – Internal Wiring

Check all electrical connections in unit control boxes; tighten as required.

3.3 – Compressor Mounting

Compressors are internally spring mounted. Do not loosen or remove compressor hold down bolts.

3.4 – Refrigerant Service Ports

Each refrigerant system has a total of 3 Schrader type Service gage ports. One port is located on the suction line, one on the compressor discharge line, and one on the liquid line. In addition Schrader-type valves are located underneath the pressure switches. Be sure that caps on the ports are tight.

3.5 – Compressor Rotation

It is important to be certain the compressors are rotating in the proper direction. To determine whether or not compressors are rotating in the proper direct ion:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the compressor lead wires.
4. Turn on power to the compressor.
5. Check also phase monitor all ok green led before proceeding. The suction and discharge pressure levels should now move to their normal start-up levels.
When compressors are rotating in the wrong direction, the unit will have increased noise levels and will not provide heating and cooling. After a few minutes of reverse operation, the scroll compressor internal overload protection will open, which will activate

3.6 - Evaporator Fan

Fan belt and variable pulleys are factory installed. Remove tape from the fan pulley. See Table 5 for Air Quantity Limits. See Table 7 for Fan Performance data. Be sure that fans rotate in the proper direction. See Table 6 for Fan RPM at various fan motor pulley settings. To alter fan performance, see Evaporator Fan Performance Adjustment section.
Unit
50TJM-18
50TJM-28 50TJM-34
Minimum Maximum Minimum Maximum
4,000 7,000 4,800 7,000 5,000 7,500 6,000 7,500 5,000 8,500 7,000 8,500 7,000 10,000 7,000 10,000
Cooling Electric Heaters
Table 5 – Air Quantity Limits.
Page 16
Freq.
MOTOR PULLEY TURNS OPEN
0
1/2 1 1 1/2
2
2 1/2
3
3 1/2
4
4 1/2
5
5 1/2
6
18
830
804
775
745
24
839
813
784
753
28
839
813
784
753
34
1029
996
960
928
902
875
847
830
813
791
774
757
740
Page 16
50Hz
Unit
50TJM
- - 1030 1001 978 946 918 884
- - 1041 1011 989 956 928 894
- - 1041 1011 989 956 928 894
Bold Fan RPM is Factory Setting
860 870 870

Table 6 – Fan RPM at Motor Pulley Settings.

3.7– Condenser Fans and Motors

Fans and motors are factory set. Refer to Condenser-Fan Adjustment Section as required.

3.8– Return – Air Filters

Check that correct filters are installed in filter tracks. See Table 1 “Physical data”. Do not operate unit without return–air filters.

3.9 – Base Unit Operation

COOLING, UNITS — when thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator-fan motor, compressor no. 1 and condenser fans start. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts.
HEATING, UNITS — (If Accessory or Optional Heater is installed) — upon a call for heating through terminal W1, IFC and heater contactor no. 1 (HC1) are energized.
4.0 – SERVICE
4.1 – Cleaning
Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.
EVAPORATOR COIL — Clean as required with a commercial coil cleaner. CONDENSER COIL — Clean condenser coil ann ua lly and as required by location and outdoor-air conditions.
Inspect coil monthly — clean as required. CONDENSATE DRAIN — Check and clean each year at start of cooling season. FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions
require. Refer to Table 1 “Physical Data” type and size.
4.2 – Lubrication
Compressors are charged with the correct amount of oil at the factory. Replacing Compressor - In the case of a motor burnout, the majority of contaminated will be removed with the
compressor. The rest of the oil is cleaned through the use of suction and liquid line filter driers. A 100% activated alumna suction line filter drier is recommended but must be removed after 72 hours.
The compressor contains POE oil. POE oil has a high affinity for moisture. Do not remove the compressor’s tube plugs until ready to insert the unit suction and discharge tube ends. The discharge connection plug should be removed first before pulling the suction connection plug to allow the dry air pressure inside the compressor to escape.
Note: This is only valid for the R410A systems.
Page 17
CAUTION
UNIT DAMAGE HAZARD
starting the compressor.
Page 17
1. The compressor is in a Puron® refrigerant system and uses a (POE) lubricant Emkarate RL 32 3MAF. In
CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS – The condenser and evapora tor -fan motors have permanently-sealed bearings, so no field lubrication is necessary.
4.3 – Evaporator Fan Performance Adjustment NOTE: To remove belts only, follow Steps 1, 2 & 6. Fan motor pulleys are factory set speed shown in Table 6.
To change fan speeds:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting plate nuts. Slide the Motor and remove belt.
3. Loosen movable-pulley flange setscrew (see Fig. 8).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 6. See Table 7 for air flow.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 & 6 for speed change for each full turn of pulley flange.)
6. Replace and tighten belts. See Belt Tension Adjustment section on table 1.
the field the oil level could be topped up with Mobil EAL Arctic 22 CC if 3MAF is not available. POE oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much as other oils designed for HCFC and CFC refrigerants. Avoid exposure of the oil to the atmosphere.
2. Ensure that system is not subjected to liquid abuse. Turn the crankcase heater on 12 hours before
Failure to follow this caution may result in damage to components.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.
4.4 – Evaporator Fan Service and Replacement
1. Remove supply-air section panel (The bolts holding the flexible connection to the panel should be removed).
2. Remove the Control Side panel.
3. Remove the Belt (refer to the previous section for Belt removal).
4. Remove the locking device of the hub & shaft from the both sides; it can be accessed throw the fan side panel.
5. Pull the shaft gently from the control side, the blower will fall inside the blower housing.
6. Loosen the (lower) first two bolts from each side of the scroll fan housing mid-plate. This can be done from the supply panel side, now the fan can be removed easily from the supply panel side.
7. To assemble the fan, reverse the above procedure.
Fig. 8 Evaporator – Fan Pulley Alignment and Adjustment
Page 18
4.5 – Belt Tension Adjustment
Page 18
To adjust belt tension:
1. Loosen fan motor bolts.
2. Adjust belt tension by sliding the motor on the mounting base.
3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure motor in fixed position.
4.6 – Condenser-Fan Adjustment
1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub screws.
3. Adjust fan height on unit, using a straightedge placed across the fan orifice.
4. Tighten setscrews
Fig. 9 Condenser - Fan Adjustment
4.7 – Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure.
NOTE: Do not use recycled refrigerant as it may contain contaminants. NO CHARGE — Use standard evacuating techniques. After evacuating system, weight in the specified amount of
refrigerant (refer to Table 1). LOW CHARGE COOLING — Using cooling charging chart (see Fig. 10 to 13 according to the size of the unit) Add
or remove refrigerant until conditions of the chart are met. Note that charging chart is different from those normally used. An accurate pressure gage and temperature-sensing device is required. Charging is accomplished by ensuring the proper amount of liquid sub-cooling. Measure liquid line pressure at the liquid line service valve using pressure gage.
Connect temperature sensing device to the liquid line near the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading.
TO USE THE COOLING CHARGING CHART — Use the above temperature and pressure readings, and find the intersection point on the cooling charging chart. If intersection point on chart is above line, add refrigerant. If intersection point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.
NOTE: Indoor-air CFM must be within normal operating range of unit. All outdoor fans must be operating.
4.8 – Protective Devices
COMPRESSOR PRO TECTION – Each compressor is internally protected against over temperature. Compressor Lockout — If any of the safeties (high-pressure, low-pressure, compressor internal thermostat, external
compressor thermal overload) trip, the CLO (compressor lockout) will lock the compressors off. To reset, manually move the thermostat setting.
Page 19
EVAPORATER AND CONDENSER-FAN MOTOR PROTECTION — Each Evaporator and Condenser-fan motor is
NOTE
IMPORTANT
Page 19
internally protected against over temperature. HIGH- AND LOW-PRESSUR E SWITCHES — If either switch trips, or if the compressor over temperature switch
activates, that refrigerant circuit will be automatically locked out by the CLO. To reset, manually move the thermostat setting.
FREEZE PROTECTION THERMOSTAT (FPT) — An FPT is located on the top and bottom of the evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized.
After prolonged shutdown or servicing in cold weather, energize the crankcase heaters for 12 hours before starting the compressors.
4.9 – Control Circuit, 24-V
This control circuit is protected against over-current by a 3.2-amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting.
5.0 – REPLACEMENT PARTS
A complete list of replacement parts may be obtained from any Carrier distributor.
Page 20
Fan Performance Table - 7
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
4000 555 0.87 1.02 622 1.06 1.25 686 1.27 1.50 747 1.49 1.75 804 1.72 2.03
8. Conversion - Bhp to KWI
Unit - 50TJM - 018 - 15 Tons - 50Hz (Standard Motor)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.4
1.6
1.8
2.0
Available External Static Pressure (in. wg)
Bold, Italics -
1.2
1.2
1.4
1.6
1.8
2.0
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
Unit - 50TJM - 18 - 15 Tons - 50Hz (High Efficiency Motor) (cont)
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
RPM - Revolutions Per Minute
Legend:
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
Bhp X 0.746
Motor efficiency
Page 20
Air Flow Rate
(CFM)
4000 555 0.93 1.04 622 1.13 1.27 686 1.36 1.52 747 1.59 1.78 804 1.84 2.06
4500 589 1.20 1.34 652 1.42 1.59 711 1.65 1.86 767 1.90 2.14 823 2.17 2.43
5000 624 1.51 1.69 682 1.75 1.96 737 2.01 2.25 790 2.27 2.54 841 2.54 2.85
5500 658 1.87 2.10 711 2.13 2.39 762 2.40 2.69 813 2.68 3.00 861 2.96 3.32
6000 689 2.28 2.56 739 2.55 2.86 788 2.83 3.18 835 3.13 3.51 881 3.43 3.85
6500 721 2.74 3.07 765 3.01 3.38 811 3.31 3.71 855 3.62 4.06 899 3.93 4.41
7000 745 3.20 3.59 788 3.49 3.92 830 3.80 4.26 873 4.12 4.62 914 4.45 4.99
Unit - 50TJM - 018 - 15 Tons - 50Hz (Standard Motor) (cont)
Air Flow Rate
(CFM)
4000 859 2.09 2.35 910 2.43 2.72 959 2.62 2.94 1007 2.90 3.25 1052 3.18 3.57
4500 875 2.44 2.73 924 2.72 3.05 971 3.00 3.37 1018 3.29 3.70 1062 3.60 4.04
5000 891 2.83 3.17 939 3.13 3.51 986 3.43 3.85 1030 3.74 4.20 1073 4.06 4.55
5500 909 3.27 3.66 955 3.58 4.01 998 3.89 4.36 1042 4.23 4.74 1083 4.56 5.11
6000 925 3.74 4.20 969 4.07 4.56 1012 4.40 4.94 1054 4.75 5.32 1094 5.10 5.72
6500 942 4.26 4.78 983 4.60 5.15 1024 4.94 5.54 1065 5.30 5.94 1104 5.66 6.35
7000 954 4.79 5.37 994 5.13 5.76 1034 5.49 6.16 1072 5.86 6.57 1110 6.24 7.00
Unit - 50TJM - 18 - 15 Tons - 50Hz (High Efficiency Motor)
Air Flow Rate
(CFM)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
RPM KWI BHP RPM KWI BHP
Standard Motor and Drive Package
0.2
Available External Static Pressure (in. wg)
0.4 0.6 0.8 1.0
RPM KWI BHP RPM KWI BHP RPM KWI BHP
Available External Static Pressure (in. wg)
4500 589 1.12 1.32 652 1.33 1.57 711 1.55 1.83 767 1.79 2.10 823 2.03 2.39
5000 624 1.42 1.67 682 1.64 1.93 737 1.88 2.21 790 2.13 2.50 841 2.39 2.81
5500 658 1.76 2.07 711 2.00 2.35 762 2.25 2.65 813 2.51 2.95 861 2.78 3.27
6000 689 2.14 2.52 739 2.39 2.81 788 2.66 3.12 835 2.94 3.45 881 3.22 3.79
6500 721 2.57 3.02 765 2.83 3.32 811 3.11 3.65 855 3.40 3.99 899 3.69 4.34
7000 745 3.01 3.53 788 3.28 3.86 830 3.57 4.19 873 3.87 4.55 914 4.18 4.91
Air Flow Rate
(CFM)
4000 859 1.96 2.31 910 2.28 2.68 959 2.46 2.89 1007 2.72 3.20 1052 2.99 3.51
4500 875 2.29 2.69 924 2.55 3.00
5000 891 2.66 3.12 939 2.94 3.45 986 3.22 3.79 1030 3.51 4.13 1073 3.81 4.48
5500 909 3.07 3.60 955 3.36 3.95 998 3.65 4.29 1042 3.97 4.66 1083 4.28 5.03
6000 925 3.51 4.13 969 3.82 4.49 1012 4.13 4.86 1054 4.46 5.24 1094 4.79 5.63
6500 942 4.00 4.71 983 4.31 5.07 1024 4.64 5.45 1065 4.98 5.85 1104 5.32 6.25
7000 954 4.49 5.28 994 4.82 5.66 1034 5.15 6.06 1072 5.50 6.47 1110 5.86 6.88
Bold , Italics - High Efficiency Motor and Drive Package
KWI - Kilo Watts Input to Motor
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
971 2.82 3.31 1018 3.09 3.64 1062 3.38 3.97
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
KWI=
Page 21
Fan Performance Table - 7 (cont)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
5000 583 1.25 1.48 642 1.46 1.73 698 1.69 2.00 754 1.92 2.28 805 2.17 2.58
Unit - 50TJM - 24 - 19 Tons - 50Hz (High Efficiency Motor)
Unit - 50TJM - 24 - 19 Tons - 50Hz (High Efficiency Motor) (cont)
1.6
1.8
2.0
Unit - 50TJM - 24 - 19 Tons - 50Hz (Standard Motor)
Available External Static Pressure (in. wg)
1.2
1.4
Page 21
Air Flow Rate
(CFM)
5000 583 1.30 1.48 642 1.51 1.73 698 1.75 2.00 754 1.99 2.28 805 2.25 2.58
5500 617 1.62 1.86 672 1.86 2.13 724 2.10 2.41 775 2.36 2.70 825 2.63 3.01
6000 654 2.01 2.30 704 2.26 2.58 752 2.51 2.88 800 2.79 3.19 847 3.07 3.51
6500 689 2.44 2.80 735 2.71 3.10 781 2.98 3.41 826 3.27 3.74 871 3.57 4.08
7000 725 2.95 3.37 768 3.22 3.69 811 3.51 4.02 854 3.81 4.36 895 4.12 4.72
7500 761 3.51 4.02 802 3.80 4.35 842 4.11 4.70 882 4.42 5.06 921 4.74 5.43
Unit - 50TJM - 24 - 19 Tons - 50Hz (Standard Motor) (cont)
Air Flow Rate
(CFM)
5000 856 2.52 2.88 906 2.80 3.20
5500 874 2.91 3.34 920 3.20 3.67 966 3.50 4.01 1009 3.81 4.36 1052 4.13 4.72
6000 893 3.37 3.85 938 3.67 4.20 980 3.98 4.56 1023 4.30 4.93 1064 4.63 5.30
6500 913 3.87 4.43 956 4.19 4.79 998 4.51 5.17 1038 4.85 5.55 1077 5.20 5.95
7000 936 4.44 5.08 976 4.77 5.46 1016 5.11 5.85 1055 5.46 6.25 1094 5.82 6.66
7500 959 5.07 5.80 998 5.41 6.20 1035 5.77 6.60 1073 6.13 7.02 1110 6.50 7.44
Bold, Italics - Standard Motor and Drive Package
Air Flow Rate
(CFM)
5500 617 1.57 1.86 672 1.79 2.13 724 2.03 2.41 775 2.28 2.70 825 2.54 3.01
6000 654 1.94 2.30 704 2.18 2.58 752 2.42 2.88 800 2.69 3.19 847 2.96 3.52
6500 689 2.36 2.80 735 2.61 3.10 781 2.88 3.41 826 3.15 3.74 871 3.44 4.08
7000 725 2.84 3.37 768 3.11 3.69 811 3.39 4.02 854 3.68 4.36 895 3.98 4.72
7500 761 3.39 4.02 802 3.67 4.35 842 3.96 4.70 882 4.26 5.06 921 4.57 5.43
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
0.2 0.4 0.6 0.8 1.0
0.2 0.4
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
954 3.08 3.53 998 3.37 3.86 1040 3.67 4.20
0.6 0.8 1.0
Air Flow Rate
(CFM)
5000 856 2.43 2.88 906 2.70 3.20 954 2.97 3.53 998 3.25 3.86 1040 3.54 4.20
5500 874 2.81 3.34 920 3.09 3.67 966 3.38 4.01 1009 3.67 4.36 1052 3.98 4.72
6000 893 3.25 3.86 938 3.54 4.20
6500 913 3.73 4.43 956 4.04 4.80 998 4.36 5.17 1038 4.68 5.56 1077 5.01 5.95
7000 936 4.28 5.08 976 4.60 5.46 1016 4.93 5.85 1055 5.26 6.25 1094 5.61 6.66
7500 959 4.89 5.81 998 5.22 6.20 1035 5.56 6.60 1073 5.91 7.02 1110 6.27 7.44
Bold , Italics - High Efficiency Motor and Drive Package
Legend:
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
8. Conversion - Bhp to KWI
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
KWI=
Motor efficiency
1.2 1.4 1.6
Bhp X 0.746
Available External Static Pressure (in. wg)
1.8 2.0
980 3.84 4.56 1023 4.15 4.93 1064 4.47 5.31
Page 22
Fan Performance Table - 7 (cont)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
5000
753 1.95 2.31
Unit - 50TJM - 28 - 23 Tons - 50Hz (Standard Motor) (cont)
Available External Static Pressure (in. wg)
1.8
Bold, Italics - Standard Motor and Drive Package
Unit - 50TJM - 28 - 23 Tons - 50Hz (Standard Motor)
Unit - 50TJM - 28 - 23 Tons - 50Hz (High Efficiency Motor)
1.2
1.4
1.6
2.0
1.2
1.4
1.6
1.8
2.0
Available External Static Pressure (in. wg)
Page 22
Air Flow Rate
(CFM)
5000 535 1.06 1.21 592 1.27 1.45 647 1.50 1.71 700 1.75 2.00 753 2.02 2.31
5500 564 1.30 1.49 618 1.53 1.75 669 1.77 2.03 718 2.03 2.32 766 2.29 2.62
6000 596 1.59 1.82 643 1.82 2.09 692 2.07 2.37 738 2.34 2.68 783 2.63 3.01
6500 625 1.92 2.19 671 2.16 2.47 715 2.43 2.78 759 2.70 3.09 801 2.99 3.43
7000 656 2.28 2.61 698 2.54 2.91 740 2.82 3.22 781 3.10 3.55 821 3.40 3.89
7500 686 2.70 3.09 726 2.97 3.40 766 3.26 3.73 804 3.55 4.06 843 3.86 4.42
8000 714 3.15 3.61 753 3.43 3.93 790 3.74 4.28 827 4.04 4.63 864 4.37 5.00
8500 743 3.64 4.17 779 3.94
Air Flow Rate
(CFM)
5000 801 2.30 2.64 849 2.61 2.98 898 2.93 3.36 944 3.28 3.75 989 3.64 4.17
5500 813 2.60 2.97 859 2.90 3.32 904 3.23 3.70 948 3.58 4.10 990 3.94 4.51
6000 827 2.93 3.36 870 3.23 3.70 913 3.57 4.09 955 3.92 4.48 996 4.28 4.90
6500 843 3.30 3.77 884 3.62 4.15 924 3.96 4.53 964 4.30 4.93 1002 4.67 5.34
7000 861 3.72 4.25 900 4.05 4.64 939 4.39 5.02 976 4.74 5.43 1013 5.11 5.85
7500 880 4.19 4.79 917 4.52 5.18 954 4.87 5.57 989 5.22 5.98 1025 5.60 6.41
8000 899 4.69 5.37 935 5.04 5.76 969 5.39 6.17 1004 5.76 6.59
8500 919 5.23 5.99 952 5.59 6.40 985 5.96 6.82 1017 6.32 7.24 1051 6.71 7.68
Air Flow Rate
(CFM)
5500 564 1.25 1.49 618 1.47 1.75 669 1.71 2.02 718 1.96 2.32 766 2.21 2.62
6000 596 1.53 1.82 643 1.76 2.08 692 2.00 2.37 738 2.26 2.68 783 2.53 3.01
6500 625 1.85 2.19 671 2.08 2.47 715 2.34 2.78 759 2.60 3.09 801 2.89 3.43
7000 656 2.20 2.61 698 2.45 2.91 740 2.71 3.22 781 2.99 3.55 821 3.28 3.89
7500 686 2.60 3.09 726 2.87 3.40 766 3.14 3.73 804 3.42 4.06 843 3.72 4.42
8000 714 3.04 3.61 753 3.31 3.93 790 3.60 4.28 827 3.90 4.62 864 4.21 5.00
8500 743 3.51 4.17 779 3.79 4.50 815 4.10 4.86 849 4.40 5.22 884 4.71 5.60
Unit - 50TJM - 28 - 23 Tons - 50Hz (High Efficiency Motor) (cont)
Air Flow Rate
(CFM)
5000 801 2.22 2.64 849 2.51 2.98
5500 813 2.50 2.97 859 2.80 3.32 904 3.12 3.70 948 3.45 4.10 990 3.79 4.50
6000 827 2.83 3.35 870 3.12 3.70 913 3.44 4.09 955 3.77 4.48 996 4.13 4.90
6500 843 3.18 3.77 884 3.49 4.15 924 3.81 4.53 964 4.15 4.92 1002 4.50 5.34
7000 861 3.58 4.25 900 3.91 4.64 939 4.23 5.02 976 4.57 5.43 1013 4.92 5.85
7500 880 4.04 4.79 917 4.36 5.18 954 4.69 5.57 989 5.04 5.98 1025 5.40 6.41
8000 899 4.52 5.37 935 4.85 5.76 969 5.20 6.17 1004 5.55 6.59 1038 5.92 7.03
8500 919 5.05 5.99 952 5.39 6.40 985 5.74 6.82 1017 6.10 7.24 1051 6.47 7.68
Bold , Italics - High Efficiency Motor and Drive Package
Legend:
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
8. Conversion - Bhp to KWI
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
535 1.02 1.21 592 1.22 1.45 647 1.44 1.71 700 1.69 2.00
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
KWI=
Motor efficiency
0.2 0.4
0.2
Bhp X 0.746
Available External Static Pressure (in. wg)
0.6 0.8 1.0
4.51 815 4.25 4.87 849 4.56 5.22 884 4.89 5.60
1038 6.14 7.03
Available External Static Pressure (in. wg)
0.4
898 2.83 3.35 944 3.16 3.75 989 3.51 4.17
0.6 0.8 1.0
Page 23
Fan Performance Table - 7 (cont)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
7000 661 2.32 2.79 704 2.59 3.11 746 2.87 3.44 787 3.16 3.80 827 3.46 4.15
1.8
2.0
Available External Static Pressure (in. wg)
Unit - 50TJM - 34 - 28 Tons - 50Hz (Standard Motor)
0.6
0.8
1.0
Available External Static Pressure (in. wg)
0.2
0.4
1.2
1.4
1.6
1.2
1.4
1.6
1.8
2.0
Bold, Italics -
Unit - 50TJM - 34 - 28 Tons - 50Hz (High Efficiency Motor) (cont)
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
Page 23
Air Flow Rate
(CFM)
7000 661 2.42 2.79 704 2.69 3.11 746 2.98 3.44 787 3.29 3.79 827 3.60 4.15
7500 691 2.86 3.30 732 3.15 3.63 773 3.46 3.99 811 3.77 4.34 849 4.10 4.72
8000 723 3.36 3.87 761 3.65 4.22 798 3.96 4.57 836 4.30 4.95 872 4.64 5.35
8500 754 3.90 4.50 791 4.22 4.86 826 4.55 5.25 860 4.88 5.63 896 5.23 6.04
9000 785 4.49 5.18 819 4.83 5.57 853 5.17 5.96 887 5.52 6.37 920 5.89 6.79
9500 814 5.13 5.92 846 5.48 6.32 879 5.83 6.72 910 6.19 7.14 943 6.57 7.58
10000 843 5.83 6.72 875 6.19 7.14 905 6.56 7.56 936 6.93 8.00 966 7.32 8.44
Unit - 50TJM - 34 - 28 Tons - 50Hz (Standard Motor) (cont)
Air Flow Rate
(CFM)
7000 867 3.94 4.55 906 4.28 4.94 945 4.65 5.36 983 5.02 5.79 1020 5.41 6.24
7500 887 4.44 5.12 924 4.79 5.53 961 5.16 5.95 996 5.53 6.38 1032 5.93 6.84
8000 908 4.99 5.76 944 5.36 6.18 978 5.73 6.61 1012 6.12 7.05 1046 6.51 7.51
8500 930 5.60 6.46 964 5.97 6.89 997 6.36 7.34 1029 6.75 7.78 1062 7.16 8.25
9000 952 6.25 7.21 985 6.64 7.65 1017 7.03 8.11 1049 7.44 8.58 1080 7.86 9.07
9500 973 6.96 8.02 1004 7.34 8.47 1035 7.75 8.94 1065 8.16 9.41 1095 8.59 9.91
10000 996 7.72 8.90 1026 8.12 9.36 1055 8.54 9.84 1085 8.97 10.34 1114 9.40 10.84
Unit - 50TJM - 34 - 28 Tons - 50Hz (High Efficiency Motor)
Air Flow Rate
(CFM)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
RPM KWI BHP RPM KWI BHP
Standard Motor and Drive Package
0.2 0.4 0.6 0.8 1.0
Available External Static Pressure (in. wg)
RPM KWI BHP RPM KWI BHP RPM KWI BHP
Available External Static Pressure (in. wg)
7500 691 2.75 3.30 732 3.02 3.63 773 3.32 3.99 811 3.62 4.34 849 3.94 4.73
8000 723 3.23 3.87 761 3.51 4.22 798 3.81 4.57 836 4.13 4.96 872 4.46 5.35
8500 754 3.75 4.50 791 4.05 4.87 826 4.37 5.25 860 4.69 5.63 896 5.03 6.04
9000 785 4.32 5.19 819 4.64 5.57 853 4.97 5.96 887 5.31 6.37 920 5.66 6.79
9500 814 4.93 5.92 846 5.26 6.32 879 5.60 6.73 910 5.95 7.15 943 6.31 7.58
10000 843 5.60 6.73 875 5.95 7.15 905 6.30 7.57 936 6.66 8.00 966 7.04 8.45
Air Flow Rate
(CFM)
7000 867 3.79 4.55 906 4.12 4.94 945 4.47 5.36 983 4.83 5.80 1020 5.20 6.24
7500 887 4.27 5.12 924 4.61 5.53
8000 908 4.80 5.76 944 5.15 6.18 978 5.51 6.61 1012 5.88 7.06 1046 6.26 7.52
8500 930 5.38 6.46 964 5.74 6.89 997 6.11 7.34 1029 6.48 7.78 1062 6.88 8.26
9000 952 6.01 7.21 985 6.38 7.66 1017 6.76 8.12 1049 7.15 8.59 1080 7.56 9.07
9500 973 6.69 8.03 1004 7.06 8.47 1035 7.45 8.94 1065 7.84 9.42 1095 8.26 9.91
10000 996 7.42 8.91 1026 7.80 9.36 1055 8.20 9.85 1085 8.62 10.35 1114 9.03 10.84
Bold , Italics - High Efficiency Motor and Drive Package
Legend:
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
961 4.96 5.95 996 5.32 6.38 1032 5.70 6.84
8. Conversion - Bhp to KWI
KWI=
Bhp X 0.746
Motor efficiency
Page 24
Cooling Chart
Page 24
140
130
120
110
100
90
80
70
Liquid Temperature at Valve (F)
60
50
40
150 200 250 300 350 400 450 500 550 600
160
140
120
100
80
Liquid Temperature at Valve (F)
60
40
150 200 250 300 350 400 450 500 550 600
CHARGING CHART 50TJM-18
Both Circuits
All outdoor fans must be operating
Add charge if above upper curve
Reduce charge if below lower curve
Liquid Pressure (PSIG)
Fig - 10 Cooling Charging Charts for 50TJM Size 18
CHARGING CHART 50TJM-24
Both Circuits
All outdoor fans must be operating
Add charge if above upper curve
Reduce charge if below lower curve
Liquid Pressure (PSIG)
Fig - 11 Cooling Charging Charts for 50TJM Size 24
Page 25
Cooling Chart (cont)
Page 25
140
130
120
110
100
90
80
70
Liquid Temperature at Valve (F)
60
50
40
140
130
120
Add charge if above upper curve
150 200 250 300 350 400 450 500 550 600
All outdoor fans must be operating
Fig - 12 Cooling Charging Charts for 50TJM Size 28
All outdoor fans must be operating
CHARGING CHART 50TJM-28
Both Circuits
Reduce charge if below lower curve
Liquid Pressure (PSIG)
CHARGING CHART 50TJM-34
Both Circuits
110
Add charge if above upper curve
100
90
80
70
Liquid Temperature at Valve (F)
60
50
40
150 200 250 300 350 400 450 500 550 600
Liquid Pressure (PSIG)
Fig - 13 Cooling Charging Charts for 50TJM Size 34
Reduce charge if below lower curve
Page 26
Troubleshooting Guide
Power failure. Call power company.
Defective thermostat, contactor, transformer, or control
Replace component.
Incorrect or faulty wiring. Check wiring diagram and rewire correctly.
Compressor motor burned out, seized, or internal over-
Determine cause. Replace compressor.
Defective overload. Determine cause and replace.
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and
Defective compressor. Replace and determine cause.
Blocked condenser. Determine cause and correct.
Defective thermostat. Replace thermostat.
Faulty condenser-fan motor. Replace.
Dirty air filter. Replace filter.
Thermostat set too low. Reset thermostat.
Air in system.
Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted. Clean coil or remove restriction.
Dirty drier filter. Replace filter.
Refrigerant overcharged. Recover excess refrigerant.
Air in system.
Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling. Determine cause and correct.
Restriction in liquid tube. Remove restriction.
Faulty TXV.
1. Check TXV bulb mounting and secure tightly to
Dirty air filter. Replace filter.
Faulty TXV.
1. Check TXV bulb mounting and secure tightly to Insufficient evaporator airflow.
Increase air quantity. Check filter and replace if
Field-installed filter drier restricted. Replace.
Table 8 — Cooling Service Analysis
Page 26
PROBLEM CAUSE REMEDY
Compressor and condenser fan will not start.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
relay. Insufficient line voltage. Determine cause and correct.
Compressor will not start but condenser fan runs.
Compressor cycles (other than normally satisfying thermostat).
Compressor operates continuously.
Thermostat setting too high. Lower thermostat setting below room
Faulty wiring or loose connections in compressor circuit.
load open.
Compressor locked out Determine cause for safety trip and reset lockout.
One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Insufficient line voltage. Determine cause and correct.
Defective overload. Determine cause and replace.
Restriction in refrigerant system. Locate restriction and remove.
Unit undersized for load. Decrease load or increase unit size.
Low refrigerant charge. Locate leak, repair, and recharge.
temperature. Check wiring and repair or replace.
Determine cause.
recharge to nameplate.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
recharge.
Dirty condenser coil. Clean coil.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
recharge.
Low refrigerant charge. Check for leaks, repair, and recharge.
High heat load. Check for source and eliminate.
suction line.
2. Replace TXV if stuck open or closed.
Refrigerant overcharged. Recover excess refrigerant.
Low refrigerant charge. Check for leaks, repair, and recharge.
Metering device or low side restricted. Remove source of restriction.
suction line.
2. Replace TXV if stuck open or closed.
necessary.
Temperature too low in conditioned area. Reset thermostat.
Page 27
MODEL NO: DATE:
SERIAL NO: TECHNICIAN:
Notes:
VERIFY REFRIGERANT CHARGE USING CHARGING CHART IN FIG - 10 to FIG - 13 on Page 24 and 25.
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
REFRIGERANT DISCHARGE
:PSIG
:PSIG
:PSIG
:PSIG
:WB
:WB
PRESSURES:
CIRCUIT - 1
CIRCUIT - 2
REFRIGERANT SUCTION
OUTDOOR AIR:
INDOOR SECTION ENTERING AIR:
INDOOR SECTION LEAVING AIR:
: DB
: DB
: DB
(L3):
TEMPERATURES:
(BOTH CIRCUITS OPERATING)
SUPPLY VOLTAGE:
COMPRESSOR - 1 AMPS:
COMPRESSOR - 2 AMPS:
INDOOR FAN AMPS:
(L1 - L2):
(L1):
(L1):
(L1):
(L2 - L3):
(L2):
9) CORRECT FAN ROTATION HAS BEEN CONFIRMED.
10) SEALED ALL POWER AND CONTROL WIRES ENTRY INTO THE UNIT AND INSIDE THE BOX
(L3 - L1):
(L3):
(L3):
START-UP CHECKLIST
(Remove and Store in Job File)
II. PRE-START-UP (Insert checkmark in box as each item is completed)
I. PRELIMINARY INFORMATION
2) VERIFY THAT UNIT INSTALLATION IS LEVEL.
1) ALL PACKING MATERIALS HAVE BEEN REMOVED FROM THE UNIT.
(Tear Along This Line)
(L2):
(L2):
III. START - UP
ELECTRICAL:
8) ENERGIZE CRANKCASE HEATERS FOR 12 HOURS.
3) CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTION.
4) UNIT GROUNDING WIRE HAS BEEN CONNECTED.
5) POWER WIRES HAVE BEEN SIZED AND INSTALLED PROPERLY TO THE UNIT.
6) CONTROL WIRING CONNECTIONS HAVE BEEN INSTALLED PROPERLY.
7) CHECK ALL WIRING TERMINALS HAVE BEEN TIGHTENED PROPERLY.
Page 27
Page 28
Page 28
Manufacturer reserves the rights to discontinue, or change at any time, specifications or designs without notice and without inc ur r in g ob ligations Supersedes Version: 50TJM-IOM05 Version: 50 TJM-IOM06 Effective Date: 22-06-2013
Loading...