Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the unit will automatically
lock the compressor out of operation. Manual r eset will
be required to restart the compressor.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb or
horizontal adapter roof curb in accordance with instructions
shipped with the curb or horizontal adapter. Accessory roof
curb and horizontal adapter roof curb and information required
to field fabricate a roof curb or horizontal adapter roof curb are
shown in Fig. 1 and 2. Install insulation, cant strips, roofing,
and counter flashing as shown. Ductwork can be secured to
roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb
or adapter roof curb is critical for a leak-proof seal.
Install gasket supplied with the roof curb or adapter roof
curb as shown in Fig. 1. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb or adapter roof curb should be level. This is necessary
to permit unit drain to function properly. Unit leveling tolerance is ±
ry Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additional information as required.
ALTERNATE UNIT SUPPORT — When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
adapter support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally spaced 4-in. x 4-in.
pads on each side.
Step 2 — Rig and Place Unit —
transportation damage. File any claim with transportation
agency. Keep unit upright, and do not drop. Use spreader bars
over unit to prevent sling or cable damage. Rollers may be used
to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ±
tion. See Fig. 3 for additional information. Unit weight is
shown in T able 1.
shown in Fig. 3. Refer to rigging instructions on unit.
POS ITIONI NG — Provide clearance around and above unit
for airflow, safety, and service access (Fig. 4 and 5).
lets near exhaust vents or other sources of contaminated air.
higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight distribu-
tion requirements.
1
/16 in. per linear ft in any direction. Refer to Accesso-
Inspect unit for
1
/16 in. per linear ft in any direc-
Four lifting holes are provided in ends of unit base rails as
Do not install unit in an indoor location. Do not locate air in-
Although unit is weatherproof, guard against water from
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Ta b 1 b
PC 111Catalog No. 535-034Printed in U.S.A.Form 50TJ-17SIPg 12-01Replaces: 50TJ-14SI
Page 2
lb density.
2
/
1
AB
.28.45.28.43
thick neoprene coated 1
″
Deg.in.Deg.in.
DIMENSIONS* (degrees and inches)
ALL
UNIT
below the unit discharge for units equipped with electric
heaters.
A 90 degree elbow must be installed on the supply ductwork
NOTE: To prevent the hazard of stagnant water build-up in the drain
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1
3. Dimensions in ( ) are in millimeters.
4.Direction of airflow.
5. Roof curb: 16 ga. (VA03-56) stl.
6.
pan of the indoor section, unit can only be pitched as shown.
PKG. NO. REF.CURB HEIGHTDESCRIPTION
High
″
(305)Standard Curb 14
″
-2
′
CRRFCURB010A001
Fig. 1 — Roof Curb Details
(610)Side Supply and Return Curb for High Installation
(610)Standard Curb for Units Requiring High Installation
″
″
-0
-0
′
′
CRRFCURB012A002
CRRFCURB011A002
2
Page 3
NOTE: For preassembled horizontal adapter roof curb part no.
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4 and 5 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner
post from packaging to protect coil from damage. Use bumper
boards for spreader bars.
5. Weights do not include optional EconoMi$er. See Fig. 4 and 5 for
EconoMi$er weight. See Table 1 for MoistureMiser weight.
6. Weights given are for aluminum evaporator and condenser coil
plate fins.
Fig. 3 — Rigging Details
UNIT
50TJ
MAXIMUM
SHIPPING WEIGHT
DIMENSIONS
AB
LbKgFt-in.mmFt-in.mm
016
15507036-11
1
/221214- 01219
020
16507486-11
1
/221213-101168
024
17007716-11
1
/221213- 71092
028
18508396-11
1
/221213- 51041
All panels must be in place when rigging.
CRRFCURB013A00, the accessory kit includes a factory-designed,
high-static, transition duct. For horizontal curb part no.
CRRFCURB012A00, a field-supplied transition duct is required.
Fig. 2 — Horizontal Adapter Roof Curb
and Roof Curb
3
Page 4
(8) on
″
16
/
5
-
′
DIM ADIM BDIM C
(D)
CORNER
(C)
CORNER
(B)
CORNER
(A)
CORNER
WEIGHT
ECONOMI$ER
WEIGHT
STD UNIT
LbKgLbKgLbKgLbKgLbKgLbKg Ft-in. mm Ft-in. mm Ft-in. mm
(1219) for proper operation of damper and
(1219) if conditions permit coil removal from the
″
″
(1219) for proper condenser coil airflow.
-0
′
″
-0
′
(2134) for coil removal. This dimension can be
(1219) for control box access.
-0
′
″
″
-0
′
reduced to 4
Rear: 7
1. Refer to print for roof curb accessory dimensions.
Rows...Fins/in.2...17
Total Face Area (sq ft)21.721.721.7
CONDENSER FANPropeller Type
Nominal Cfm10,50010,50014,20014,200
Quantity...Diameter (in.)3...223...222...302...30
Motor Hp...Rpm
Watts Input (Total)1100110034003400
EVAPORATOR COILCross-Hatched
Rows...Fins/in.2...173...153...154...15
Total Face Area (sq ft)17.517.517.517.5
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...10 x 102...10 x 102...12 x 122...12 x 122...12 x 12
Type DriveBeltBeltBeltBeltBelt
Nominal Cfm600060007200800010,000
Motor Hp3.73.057.510
Motor Nominal Rpm17251725174517451740
Maximum Continuous Bhp4.253.455.90
Motor Frame Size56H56H184T213T215T
Nominal Rpm High/Low—————
Fan r/s RangeLow-Medium Static891-11791159-1429910-10951002-12251066-1283
Motor Bearing TypeBallBallBallBallBall
Maximum Allowable Rpm15501550155015501550
Motor Pulley Pitch DiameterLow-Medium Static3.1/4.14.3/5.34.9/5.95.4/6.64.9/5.9
Min/Max (in.)High Static3.7/4.7—4.9/5.95.4/6.64.9/5.9
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)Low-Medium Static6.06.49.49.48.0
Nominal Fan Shaft Diameter (in.)1
Belt, Quantity...Type...Length (in.)Low-Medium Static1...BX...421...BX...451...BX...501...BX...532...BX...50
Pulley Center Line Distance (in.)13.5-15.513.5-15.513.3-14.814.6-15.414.6-15.4
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position66666
Factory Speed3.53.53.53.53.5
Factory Speed Setting (rpmLow-Medium Static10351296100211201182
Fan Shaft Diameter at Pulley (in.)1
HIGH-PRESSURE SWITCH (psig)
Cutout426
Reset (Auto)320
LOW-PRESSURE SWITCH (psig)
Cutout27
Reset (Auto)44
FREEZE PROTECTION THERMOSTAT (F)
Opens30 ± 5
Closes45 ± 5
OUTDOOR-AIR INLET SCREENSCleanable
Quantity...Size (in.)2...20 x 25 x 1
RETURN-AIR FILTERSThrowaway†
Quantity...Size (in.)4...20 x 20 x 2
High Static1227-1550—1069-12871193-14581332-1550
High Static5.2—8.07.96.4
High Static1...BX...42—1...BX...481...BX...502...BX...47
*Circuit 1 uses the lower por tion of condenser coil and lower portion of evap-
orator coils; and Circuit 2 uses the upper portion of both coils.
016
020024028
808080
40
2...ZR94KC
50, 50
2
81, 81
10-10
Aluminum Pre-Coated, or Copper Plate Fins
21.7
1
/2...1050
7
/
8
3
/
16
3
/
16
1
/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
7
/
8
13/
16
13/
16
†The 50TJ028 units requires 2-in. industrial-grade filters capable of handling
face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or
equivalent).
NOTE: The 50TJ016-028 units have a low-pressure switch (standard) located
on the suction side.
404040
1...ZR108KC,
1...ZR94KC
15-516-020-13
3
/8-in. Copper Tubes, Aluminum Lanced,
3...153...154...15
1
/2...10501...10751...1075
3
/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
11/
8
17/
16
17/
16
1...20 x 20 x 1
4...16 x 20 x 2
1...ZR125KC,
1...ZR108KC
8.7 [208/230, 575 v]
9.5 [460 v]
13/
8
17/
16
17/
16
1...ZR16M3,
1...ZR125KC
10.2 [208/230, 575 v]
11.8 [380, 460 v]
17/
17/
13/
8
16
16
6
Page 7
Step 3 — Field Fabricate Ductwork —
3/4" FPT DRAIN
CONNECTION
1-3/8"
DRAIN HOLES
Shaded area indicates block-off panels.
NOTE: Dimensions A, A′, and B, B′ are obtained from field-supplied
ceiling diffuser.
Fig. 8 — Concentric Duct Details
Fig. 9 — Condensate Drain Details
(50TJ016,020 Shown)
Secure all
ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
The 50TJ units with electric heat require a 1-in. clearance
for the first 24 in. of ductwork.
Outlet grilles must not lie directly below unit discharge.
NOTE: A 90-degree elbow must be provided in the ductwork
to comply with UL (Underwriters’ Laboratories) codes for use
with electric heat.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90 degree
turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then
a grille of sufficient strength and density should b e installed
to prevent objects from falling into the conditioned space.
Due to electric heater, supply duct will require 90 degree
elbow.
Step 4 — Make Unit Duct Connections —
Unit
is shipped for through-the-bottom duct connections. Ductwork
openings are shown in Fig. 6. Field-fabricated concentric ductwork may be connected as shown in Fig. 7 and 8. Attach all
ductwork to roof curb and roof curb basepans. Refer to installation instructions shipped with accessory roof curb for more
information.
Step 5 — Trap Condensate Drain —
and 9 for drain location. Plug is provided in drain hole and
must be removed when unit is operating. One
See Fig. 4, 5,
3
/4-in. halfcoupling is provided inside unit evaporator section for condensate drain connection. An 81/2 in. x 3/4-in. diameter nipple and a
2-in. x
3
3
/4-in. diameter pipe nipple are coupled to standard
/4-in. diameter elbows to provide a straight path down through
holes in unit base rails (see Fig. 10). A trap at least 4-in. deep
must be used.
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 6 — Air Distribution — Thru-the-Bottom
(50TJ020-028 Shown)
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 7 — Concentric Duct Air Distribution
(50TJ020-028 Shown)
7
Page 8
Fig. 10 — Make Electrical Connections
TB1 MAXIMUM WIRE SIZE
LEGEND
Fig. 11 — Field Power Wiring Connections
UNIT
50TJ
VOLTAGE
208/230,380460575
All
350 kcmil2/02/0
EQUIP —
Equipment
GND—
Ground
kcmil —
Thousand Circular Mils
NEC—
National Electrical Code
TB—
Terminal Block
UNIT LOW-VOLTAGE CONNECTIONS
Fig. 12 — Field Control Thermostat Wiring
Step 6 — Make Electrical Connections
FIEL D POWER SUP PLY — Unit is factory wired for voltage shown on nameplate.
When installing units, provide a disconnect, per NEC
(National Electrical Code) requirements, of adequate size
(T able 2).
All field wiring must comply with NEC and local
requirements.
Route power lines through control box access panel or unit
basepan (Fig. 4 and 5) to connections as shown on unit wiring
diagram and Fig. 11.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages
between phases must be balanced within 2% and the current
must be balanced within 10%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company immediately.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
FIELD CONTR OL WIRING — Install a Carrier-approved
accessory thermostat assembly according to the installati on instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of no. 18
A WG (American Wire Gage) colored wire from subbase terminals through conduit in unit to low-voltage connections as
shown on unit label wiring diagram and in Fig. 12.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG
insulated wire (35 C minimum). All wire larger than no. 18
AWG cannot be direct ly connected to the thermostat and will
require a junction box and splice at the thermostat.
Set heat anticipator settings as indicated in Tabl e 3. Settings
may be changed slightly to provide a greater degree of comfort
for a particular installation.
The correct power phasing is critical in the operation of the
scroll compressors. An incorrect phasing will cause the
compressor to rotate in the wrong direction. This may lead
to premature compressor failure.
Use the following formula to determine the percentage of
voltage imbalance.
Percentage of Voltage Imbalance
= 100 x
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage:
max voltage deviation from average voltage
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
A verage Voltage =
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
Percentage of Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is be-
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
380 v, 480 v, and 575 v. Heaters are rated at 240 v, 380 v, 480 v, or
600 v. If power distribution voltage to unit varies from rated heater
voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Heaters are field installed only.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percent of voltage imbalance.
% Voltage Imbalance
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
max voltage deviation from average voltage
VO LTAG E
RANGE
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) HpFLAFLA LRAkWFLAMCAMOCP†
Use the following formula to determine
average voltage
COMPRESSOR
No. 1No. 2
OFMIFM
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
3. MCA calculation for units with electric heaters over 50 kW =
(1.25 x IFM amps) + (1.00 x heater FLA).
the optional non-fused disconnect, incoming power will be
wired into the disconnect switch. Refer to Fig. 13 for wiring
for 100 and 200 amp disconnect switches. Units with an
MOCP under 100 will use the 100 amp disconnect switch.
Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control
box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Ope n the control box door and remove the handle and
shaft from shipping location.
2. Loosen the A llen bolt located on the disconnect switch.
The bolt is located on the square hole and is used to hold
the shaft in place. The shaft cannot be inserted until the
Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is specially cut and
the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two
screws provided. When the handle is in the ON position,
the handle will be vertical. When the handle is in the OFF
position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door.
The handle should fit over the end of the shaft when t he
door is closed.
8. The ha ndle must be in the OFF position to open the control box door.
OPTIONAL CONVENIENCE OUTLET — On units with
optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outlet receptacle is provided for field wiring.
Field wiring should be run through the
7
/8-in. knockout pro-
vided in the basepan near the return air opening.
Step 7 — Make Outdoor-Air Inlet Adjustments
MANUAL OUTDOOR-AIR DAMPER — All units (except
those equipped with a factory-installed economizer) have a
manual outdoor-air damper to provide ventilation air. Damper
can be preset to admit up to 25% outdoor air into return-ai r
compartment. To adjust, loosen securing screws and move
damper to desired setting. Then retighten screws to secure
damper (Fig. 14).
OPTIONAL ECONOMI$ER
EconoMi$er Motor Control Module (Fig. 15-17)
ECONSP dial to the ‘ ‘D’’ setting (Fig. 16). The control module
is located on the EconoMi$er motor. See Fig. 15 and 17.
Damper Vent Position Setting
1. Set fan switch at ON position (continuous fan operation)
and close night switch if used.
2. Set system selector switch to OFF position.
3. Turn Min Pos (%) dial slowly until dampers assume desired vent position.
Do not manually operate EconoMi$er
motor since damage to motor will result.
— Set the
NOTE: The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 13 — Optional Non-Fused Disconnect Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
11
Page 12
Table 3 — Heat Anticipator Settings
Fig. 18 — Outdoor-Air Hood Component Location
UNIT
50TJ
016-028
*Heater kW is based on heater voltage of 208 v, 240 v, 380 v, 480 v,
and 575 v.
UNIT
VOLTAGE S
208/230-3-60
380-3-60
460-3-60
575-3-60
kW*STAGE 1STAGE 2
26/34.40.66
42/56.66.40
56/75.66.66
20.40.40
35.40.66
32.40.40
55.40.66
80.66.66
50.66.66
Fig. 16 — EconoMi$er Control Module
Adjustment Potentiometers
CONTROL MODULEACTUATOR
Fig. 17 — EconoMi$er Control Module Location
Step 8 — Install Outdoor-Air Hood —
The same
type of factory-installed hood is used on units with 25% air
ventilation and units with an EconoMi$er.
NOTE: The hood top panel, upper and lower filter retainers,
hood drain pan, baffle (028), and filter support bracket are
secured opposite the condenser end of the unit. The screens,
hood side panels, remaining section of filter support bracket,
seal strip, and all other hardware are in a package located
inside the return-air filter access panel (Fig. 18).
1. Attach seal strip to upper filter retainer. See Fig. 19.
2. Assemble hood t op panel and side panels, upper filter retainer, and hood drain pan (Fig. 20).
3. Secure l ower filte r retainer and long se ction of filter support bracket to unit. See Fig. 20. Leave screws loose on
028 units.
5. Loosen sheet metal screws for base unit top panel located
above outdoor-air inlet opening, and remove screws for
hood side panels located on the sides of the outdoor-air
inlet opening.
6. Match notches in hood top panel to unit top panel screws.
Insert hood flange between unit top panel flange and unit.
Tighten screws.
7. Hold hood side pa nel flanges flat aga inst unit, and install
screws removed in Step 5.
8. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket.
9. Attach remaining short section of filter support bracket.
OUTDOOR AIR ENTHALPY SENSOR INSTALLATION — Perform the following procedure to install the outdoor air enthalpy sensor (part no. CROUTENT001A00).
1. Remove the outdoor air temperature sensor cover. See
Fig. 21. Save cover and screws.
2. Disconnect the wiring from the installed outdoor air temperature sensor. See F ig. 22.
3. Us e a
1
/4-in. nut driver to remove the 2 screws securing
the outdoor air temperature sensor to the sheet metal.
4. Mount the outdoor air enthalpy sensor in t he outdoor air
temperature sensor location using the screws removed in
Step 3.
5. Connect the outdoor air enthalpy sensor wiring harness to
the EconoMi$er control module and sensor.
6. Re-install sensor cover saved from Step 1.
RETURN AIR TEMPERATURE SENSOR OR RETURN
AIR ENTHALPY SENSOR INSTALLATION — Perform the
following procedure to install the return air temperature sensor
(part no. CRRETTMP001A00) or return air enthalpy sensor
(part no. CRRETENT001A00).
1. Attach the sensor to the mounting bracket using 2 selftapping
2. Mount the bracket to the inside of the return air opening
flange using a
1
/2-in. screws provided .
1
/4-in. nut driver and 2 no. 6 sheet metal
screws.
NOTE: The sensor must be mounted in an upright position.
3. Feed the sensor wiring through the bushing in
EconoMi$er to secure wires.
4. Route sensor wiring harness from sensor to EconoMi$er
control module. Secure wiring harness to the original harness using tie wraps.
5. Wire the sensor to the EconoMi$er control module. See
Fig. 23 and 24.
12
Page 13
SENSOR
COVER
OUTSIDE AIR SENSOR
MOUNTING
SCREW
MOUNTING SCREW
WIRING
HARNESS
SENSOR
WIRING
CONNECTIONS
Fig. 22 — Outdoor-Air Sensor Details
Fig. 21 — Outdoor-Air Sensor Location
Fig. 19 — Seal Strip Location
(Air Hood Cross-Sectional View)
BAFFLE (028 ONLY)
HOOD TOP
PANEL
NOTE: The outdoor-air hood comes with a baffle which is used on
028 units only; discard baffle for 016-024 units.
Fig. 20 — Outdoor-Air Hood Details
COMMISSION ING — The EconoMi$er saves energy when
it uses outdoor air to provide free cooling instead of mechanical air conditioning. The EconoMi$er switchover strategy determines if the outdoor air is suitable for free cooling. The
EconoMi$er chooses the switchover strategy with the most energy savings, provided that the required sensors are connected
and functioning normally.
IMPORTANT: If a sensor stops functioning normally (becomes unreliable), the EconoMi$er
switches to the next best strategy.
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
FILTER SUPPORT
BRACKET
HOOD DRAIN PAN
UPPER FILTER RETAINER
HOOD SIDE
PANELS (2)
BAFFLE
(028 ONLY)
LOWER
FILTER
RETAINER
Refer to Table 4 to determine the sensors required for each
— The differential enthalpy switchover strategy must be selected manually, if
required. To enable, press and hold the CONFIG button for 30
seconds, then release. The LED will flash twice to indicate the
change of configuration.
T o ret urn to s ingle enthalpy mode, p ress and hold t he CO NFIG button for 30 seconds. The LED will flash once to indicate
the change of configuration.
DISCHARGE AIR THERMISTOR (DAT) — The discharge
air thermistor is factory-mounted on the supply-fan housing in
the fan section of the unit. The DAT is factory-wired to the
EconoMi$er Control Module.
CO
CONTROL SETUP — If a CO2 sensor is not being
2
used, proceed to the next section. If a CO2 sensor is being used,
perform the following:
1. Determine the value at which you want the minimum
position of the dampers to begin opening to allow a
greater amount of outdoor air to enter. The range is
800 to 1,400 ppm.
2. Locate the CO
SP (PPM) potentiometer and adjust to the
2
desired set point. See Fig. 16.
13
Page 14
MECHANICAL COOLING LOCKOUT — Determine the
outdoor-air temperature at which you want the mechanical
cooling (compressors) to be disabled. Locate the mechanical
cooling lockout (MECH CLG LOCKOUT) potentiometer. To
disable this feature, turn the potentiometer counterclockwise
(CCW) to the OFF position. Otherwise, set the value between
10 and 60 F. Mechanical cooling will not operate when the outdoor air temperature is below this value. See Fig. 16.
Table 4 — EconoMi$er Switchover Control Strategy
DRY BULB CHANGEOVER SET UP — Dete rmine the dry
bulb changeover set point from Table 5. The settings are A, B,
C and D. Locate the ECON SP potentiometer and set the dry
bulb changeover set point. See Fig. 16. When the OAT is above
this set point, the damper is limited to minimum position
setting.
If a potentiometer fails, its setting will default to the values
in Ta ble 6.
ECONOMI$ER SWITCHOVER
STRATEGY
Dry BulbX
Single EnthalpyX
Differential TemperatureXX
Differential Enthalpy*XX
*Must be selected manually.
Outdoor Air TemperatureOutdoor Air EnthalpyReturn Air TemperatureReturn Air Enthalpy
Table 5 — Changeover Set Points
SETTINGSABCD
Dry Bulb (°F)73696663
Single Enthalpy* (Btu/lb)27252422
Differential Temperature*
(°F, Not Adjustable)
Differential Enthalpy*
(Btu/lb, Not Adjustable)
*Field-installed accessory.
2222
1111
SENSORS REQUIRED
Table 6 — Default Potentiometer Settings
POTENTIOMETERDEFAULT SETTING
CO2 SP (PPM)1,000
MECH CLG LOCKOUT50 F
ECON SPD
MIN POS (%)20
LEGEND
COM—
DAT—
DM—
GND—
OAH—
OAT—
POT—
RAH—
RAT—
REM—
*OAT sensor shipped with economizer option. OAH, RAT, RAH and CO
Common
Discharge Air Thermistor
Damper Motor
Ground
Outdoor-Air Enthalpy Sensor
Outdoor-Air Temperature Sensor
Potentiometer
Return-Air Enthalpy Sensor
Return-Air Temperature Sensor
Remote
Fig. 23 — Typical EconoMi$er Sensor Wiring
are field-installed accessories.
2
14
Page 15
VENTILATION AIR (Minimum Position Set Up) — If ventilation air is not required, skip this section. If ventilation air is
required, perform the following:
1. The indoor fan must be on to set the ventilation air.
Either put the thermostat in the continuous fan mode or
jumper the R and G terminals at the rooftop unit connection board.
2. Loca te the minimum position (MIN PO S) potentiometer.
Turn the potentiometer full CCW to fully close the out door air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 16.
3. Replace the filter access panel. See Fig. 18. Ensure the filter access panel is securely engaged.
4. Calculate the minimum airflow across the EconoMi$er.
a. Calculate % of outside air using the following
formula.
% Outdoor air through EconoMi$er
% Outdoor air =
Mixture T emp – Return Air Temp
Outdoor T emp – Return Air Temp
b. Multiply total CFM by percentage outdoor air, this
gives outdoor air volume in CFM.
Personal Injury Hazard.
Avoid possible injury by keep-
ing fingers away from damper blades.
Step 9 — Install All Accessories —
After all the
factory-installed options have been adjusted, install all fieldinstalled accessories. Refer to the accessory installation instructions included with each accessory .
MOTORMASTER® I CONTROL INSTALLATION
(50TJ016 and 020 Only)
Install Field-Fabricated Wind Baffles
— Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 25 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be
5
/8-in. long. Drill required screw holes for mounting baffles.
1
/4-in. diameter and
To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care
when drilling holes.
Outdoor Air Enthalpy
CROUTENT001A00
OAT
COM
OAH
+15V
RAT
COM
RAH
+15V
CO
(+)
2
CO
2
COM
DAT
COM
REM
POT
COM
LED
COM
Tan
Violet
White
Red
Tan
Violet
White
Red
T
C
O
M
PW
Minimum Position
1k ohm Potentiometer
O
U
T
T
Remote
Violet
C
O
M
T
PW
O
U
TT
Unoccupied Control
(Part num ber on the control
must be AD-DME1701-1
or AD-DME1711-1.)
Unoccupied
Contact
24 VAC must be present
on BI for the system to be
Violet
470 ohm
5watt
Resistor
unoccupied.
Return Air Enthalpy
CRRETENT001A00
CO2 Sensors:
323ZCSENCO
NOT
USED
2
1
2to10VDCat
0 to 2000 ppm
Line
20 VA
24 VAC
Voltage
20 mA LED
Remote
LED
Field-supplied WiringWiring Included
Fig. 24 — Typical EconoMi$er Sensor Wiring
15
-
Page 16
Install Motormaster I Controls
NOTE: Dimensions in ( ) are in mm.
Fig. 25 — Wind Baffle Details
— Only one Motormaster I
control is required per unit. The Motormaster I control must be
used in conjunction with the Accessory 0° F Low Ambient Kit
(purchased separately). The Motormaster I device controls outdoor fan no. 1 while outdoor fans no. 2 and 3 are sequenced off
by the Accessory 0° F Low Ambient Kit.
Accessory 0° F Low Ambient Kit —
Install the Accessory 0° F
Low Ambient Kit per instruction supplied with accessory.
Sensor Assembly —
Install the sensor assembly in the location
shown in Fig. 26.
Motor Mount —
T o ensure proper fan height, replace the existing motor mount with the new motor mount provided with
accessory.
Transformer (460 and 575-v Units Only) —
On 460 and
575-volt units a transformer is required. The transformer is
provided with the accessory and must be field-installed.
Motormaster I Control —
Recommended mounting location is
on the inside of the panel to the left of the control box. The
control should be mounted on the inside of the panel, vertically, with leads protruding from bottom of extrusion.
MOTORMASTER® III CONTROL INSTALLATION
(50TJ024 and 028 Only)
Install Field-Fabricated Wind Baffles
— Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 25 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be
5
/8-in. long. Drill required screw holes for mounting baffles.
1
/4-in. diameter and
T o avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care
when drilling holes.
Replace Outdoor Motor
— Replace outdoor fan motor no. 1
with motor included in accessory kit. Existing motor is not
Motormaster® III compatible.
Install Motormaster III Controls
— Only one Motormaster
III control is required per unit.
Sensor —
Install the sensor for thermistor input control in the
location shown in Fig. 27. Connect sensor leads to the purple
and grey control signal leads on the Motormaster III control.
Signal Selection Switch —
Remove the cover of the Motormaster III control. Set the switch to accept the thermistor sensor input signal. Set the frequency to match the unit power supply (60 Hz).
Motormaster III Control —
Recommended mounting location
is beneath the control box, mounted to the partition that separates the control box section from the indoor section.
NOTE: If unit power is supplied through the roof curb and
basepan of the unit, mount the Motormaster III control on the
corner post adjacent to the conduit running from the basepan to
the bottom of the control box.
MositureMiser dehumidification package operation can be
controlled by field installation of a Carrier-approved humidistat. To i nstall the humidistat perform the following procedure:
1. Locate humidistat o n a solid interior wall in the conditioned space. Location should be a well ventilated area
to sense average humidity .
2. Route the rmostat cable or equivalent single leads of colored wire from Humidistat terminals through conduit in
unit to the low voltage connection on the 2-pole terminal
strip (TB3) as shown in Fig. 28 and Fig. 29.
16
Page 17
SENSOR
SENSOR
LOCATION
HAIRPIN END
SENSOR
LOCATION
HAIRPIN END
LOCATION
SENSOR
LOCATION
HAIRPIN END
HAIRPIN END
50TJ016 50TJ020
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
Fig. 26 — Motormaster® I Sensor Locations
50TJ024 50TJ028
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
Fig. 27 — Motormaster III Sensor Locations
LEGEND
LLSV —
LPS—
TB—
TRAN —
Liquid Line Solenoid Valve
Low Pressure Switch
Terminal Block
Transformer
Use the following information and Start-Up Checklist on
page CL-1 to check out unit PRIOR to start-up.
Unit Preparation —
Check that unit has been installed in
accordance with these installation instructions and all applicable codes.
Internal Wiring —
Check all electrical connections in
unit control boxes; tighten as required.
Crankcase Heater (Size 028 and Units with
MoistureMiser Dehumidification Package
Only) —
and compressor is not operating.
IMPORTANT : Unit power must be on for 24 hours prior
to start-up. Otherwise, damage to compressor may
result.
Compressor Mounting —
spring mounted. Do not loosen or remove compressor holddown bolts.
Refrigerant Service Ports —
tem has a total of 3 Schrader-type service gage ports. One port
is located on the suction line, one on the compressor
line, and one on the liquid line. In addition Schrader-type
valves are located underneath the low-pressure switches. Be
sure that caps on the ports are tight.
Compressor Rotation —
the compressors are rotating in the proper direction. To determine whether or not compressors are rotating in the proper direction:
Heater is energized as long as there is power to unit
Compressors are internally
Each refrigerant sys-
discharge
It is important to be certain
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suct ion pressure should drop and th e discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Not e that the evaporator fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the incoming power leads.
4. Turn on power to the compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When compressors are rotating in the wrong direction,
the unit will have increased noise levels and will not provide
heating and cooling.
After a few minutes of reverse operation, the scroll compressor internal overload protection will open, which will activate the unit’s lockout and requires a manual reset. Reset is accomplished by turning the thermostat on and off.
Evaporator Fan —
Fan belt and variable pulleys are factory installed. Remove tape from the fan pulley. See Table 7 for
Air Quantity Limits. See Tables 8-10 for Fan Performance
data. Be sure that fans rotate in the proper direction. See
Tables 11-13 for Static Pressure information for accessories
and options. See Table 14 for fan rpm at various fan motor pulley settings. To alter fan performance, see Evaporator-Fan Performance Adjustment section, page 25.
Table 7 — Air Quantity Limits
UNIT
50TJ
016
020
024
028
Condenser Fans and Motors —
MINIMUM CFMMAXIMUM CFM
45007,500
54009,000
600010,000
700011,250
Fans and motors
are factory set. Refer to Condenser-Fan Adjustment section
(page 26) as required.
Return-Air Filters —
Check that correct filters are installed in filter tracks. See Table 1. Do not operate unit without
return-air filters.
Outdoor-Air Inlet Screens —
Outdoor-air i nlet scr eens
must be in place before operating unit.
Accessory EconoMi$er Adjustment —
Remove filter access panel. Check that outdoor-air damper blades are
closed and return-air damper blades are open.
EconoMi$er operation and adjustment is described in Base
Unit Operation and EconoMi$er Adjustment sections
(pages 23 and 27), respectively.
*Standard low-medium static drive range is 891 to 1179 rpm (for
208/230, 380 and 460 v units) or 1159 to 1429 rpm (for 575-v
units). Alternate high-static drive range is 1227 to 1550 (for 208/
230, 380, and 460 v units). The alternate high-static drive is not
available for 50TJ016 575-v units. Other rpms require a field-supplied drive.
NOTES:
1. Maximum continuous bhp is 4.25 (208/230, 380 and 460 v) or
Brake Horsepower
Factory-Installed Option
Input Watts to Motor
3.45 (575 v) and the maximum continuous watts are 3775 (208/
230, 380, and 460 v) or 3065 (575 v). Do not adjust motor rpm
such that motor maximum bhp and/or watts is exceeded at the
maximum operating cfm.
2. Static pressure losses (i.e., EconoMi$er) must be added to
external static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 11 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that
the full horsepower and watts range of the motor can be utilized
with confidence. Using your fan motors up to the watts or bhp
rating shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact
your Carrier representative for details.
*Standard low-medium static drive range for the 020 size is 910 to
1095 rpm. Standard low-medium static drive range for the 024 size
is 1002 to 1225 rpm. Alternate high-static drive range for the
020 size is 1069 to 1287. Alternate high-static drive range for the
024 size is 1193 to 1458 rpm. Other rpms require a field-supplied
drive.
NOTES:
1. Maximum continuous bhp for the 020 size is 5.90. Maximum
(208/230, 575 v) or 8640 (380, 460 v). Do not adjust motor rpm
such that motor maximum bhp and/or watts is exceeded at the
maximum operating cfm.
2. Static pressure losses (i.e., EconoMi$er) must be added to
external static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and casing
losses. See Table 12 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that
the full horsepower and watts range of the motor can be utilized
with confidence. Using your fan motors up to the watts or bhp
rating shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact
your Carrier representative for details.
20
Page 21
Table 10 — Fan Performance — 50TJ028
50TJ028 (25 TONS)*
Airflow
(Cfm)
7,000
7,500
8,000
8,500
9,000
9,500
10,000
10,500
11,000
11,250
50TJ028 (25 TONS)* (cont)
Airflow
(Cfm)
7,000
7,500
8,000
8,500
9,000
9,500
10,000
10,500
11,000
11,250
LEGEND
Bhp —
FIOP —
Watts —
*Standard low-medium static drive range is 1066 to 1283 rpm. Alter-
nate high-static drive range is 1332 to 1550. Other rpms require a
field-supplied drive.
NOTES:
1. Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (380,
460 v) and the maximum continuous watts are 9510 (208/230,
575 v) or 11,000 (380, 460 v). Do not adjust motor rpm such
that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
Brake Horsepower
Factory-Installed Option
Input Watts to Motor
Available External Static Pressure (in. wg)
2. Static pressure losses (i.e., EconoMi$er) must be added to
external static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and casing
losses. See Table 12 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that
the full horsepower and watts range of the motor can be utilized
with confidence. Using your fan motors up to the watts or bhp
rating shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact
your Carrier representative for details.
1. The static pressure must be added to external static pressure.
The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance tables to determine blower rpm and watts.
2. Heaters are rated at 240 v, 380 v, 480 v, and 600 v.
1. The static pressure must be added to external static pressure.
The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance tables to determine blower rpm and watts.
2. Heaters are rated at 240 v, 380 v, and 480 v. There are no
575-v heaters.
COOLING, UNITS WITHOUT ECONOMI$ER — When
thermostat calls for cooling, terminals G and Y1 are energized.
The indoor (evaporator) fan contactor (IFC), and compressor
contactor no. 1 (C1) are energized and evaporator-fan m otor,
compressor no. 1 and condenser fans start. The condenser-f an
motors run continuously while unit is cooling. If the thermostat
calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2
starts.
HEATING, UNITS WITHOUT ECONOMI$ER (If Accessory or Optional Heater is Installed) — Upon a call for heating through terminal W1, IFC and heater contactor no. 1 (HC1)
are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC2 is energized through W2.
COOLING UNITS WITH ECONOMI$ER — When the
OAT is above the ECON SP set point and the room thermostat
calls for Stage 1 cooling (R to G + Y1), th e indoor-fan m otors
(IFM) is energized and the EconoMi$er dampe r modulates to
minimum position. The compressor contactor and OFC are
energized to start the compressor and outdoor-fan motor
(OFM). After the thermostat is satisfied, the damper modulates
to the fully closed position when the IFM is deenergized.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
55 F supply air set point. If the supply-air temperature (SAT) is
greater than 57 F, the EconoMi$er modulates open, allowing a
greater amount of outdoor air to enter the unit. If the SA T drops
below 53 F, the outdoor air damper modulates closed to reduce
the amount of outdoor air. When the SAT is bet ween 53 and
57 F , the EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressors have a two-minute Minimum On and
Minimum Off, which are accomplished by the strategies
below.
1. If Y1 is energized, and the room thermostat calls for Y2
(2-stage thermostat), the compressor and OFC are energized. The position of the EconoMi$er damper is maintained at its current value.
2. If Y1 is energized for more than 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), the compressor and OFC are energized. The position of the EconoMi$er damper is maintained at its current value.
3. If Y 1 is energized, and com pressor no. 1 i s al ready ene rgized (see Step 2) and the room thermostat calls for Y2,
compressor no. 1 continues to operate. If Y2 remains
energized for more than 20 minutes, compressor no. 2 is
energized.
NOTE: Compressor no. 2 cannot be energized unless there is a
signal for Y2 from the space thermostat.
4. If c ompressor no. 2 is ene rgized, and the Y2 signal from
the thermostat is satisfied, compressors 1 and 2 are deenergized. Re-asserting Y2 will start compressor no. 1 and
(after a 20-minute interstage delay) compressor no. 2.
5. If compressor no. 1 is energized and the thermostat is satisfied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
FREEZE PROTECTION THERMOSTAT(S) — A freeze
protection thermostat (FPT) is located on the top and bottom of
the evaporator coil. It detects frost build-up and turns off the
compressor, allowing the coil to clear. Once frost has melted,
the compressor can be reenergized by resetting the compressor
lockout.
HEATING, UNITS WITH ECONOMI$ER (If Accessory or
Optional Heater is Installed) — When the room thermostat
calls for heat, the heating controls are energized as described in
the Heating, Units Without EconoMi$er section. The IFM is
energized and the EconoMi$er damper modulates to the minimum position. When the thermostat is satisfied, the damper
modulates closed.
UNITS WITH MOISTUREMISER DEHUMIDIFICATION
PACKAGE — When thermostat calls for cooling, terminals G
and Y1 and/or Y2 and the compressor contactor C1 and/or C2
are energized. The indoor (evaporator) fan motor (IFM), compressors, and outdoor (condenser) fan motors (OFM) start. The
OFMs run continuously while the unit is in cooling. As shipped
from the factory, both MoistureMiser dehumidification circuits
are always energized.
If MoistureMiser circuit modulation is desired, a fieldinstalled, wall-mounted humidistat is required. If the MoistureMiser humidistat is installed and calls for the MoistureMiser subcooler coil to operate, the humidistat internal
switch closes. This energizes the 3-way liquid line solenoid
valve coils (LLSV1 for circuit 1 and LLSV2 for circuit 2) of
the MoistureMiser circuits, forcing the warm liquid refrigerant
of the liquid line to enter the subcooler coils. See Fig. 30.
As the warm liquid passes through the subcooler coils, it is
exposed to the cold supply airflow coming off the evaporator
coils and the liquid is further cooled to a temperature approaching the evaporator coil leaving-air temperature. The state of the
refrigerant leaving the subcooler coils is a highly subcooled liquid refrigerant. The liquid then enters a thermostatic expansion
valve (TXV) where the liquid is dropped to the evaporator
pressure. The TXVs can throttle the pressure drop of the liquid
refrigerant and maintain proper conditions at the compressor
suction valves over a wide range of operating conditions. T he
liquid proceeds to the evaporator coil s at a temperature lower
than normal cooling operation. This lower temperature is what
increases the latent and sensible capacity of the evaporator
coils.
The 2-phase refrigerant passes through the evaporators and
is changed into a vapor. The air passing over the evaporator
coils will become colder than during normal operation as a r esult of the colder refrigerant temperatures. However, as it passes over the subcooler coils, t he a ir wi ll be warm ed, de crea sing
the sensible capacity and reducing the sensible heat of the rooftop unit.
As the refrigerant leaves the evaporator, the refrigerant
passes a subcooler control low-pressure switch (S-LPS1 for
circuit 1 or S-LPS2 for circuit 2) in the suction line. This lowpressure switch will deactivate the MoistureMiser package
when the suction pressure reaches 60 psig. The subcooler control low-pressure switch is an added safety device to protect
against evaporator coil freeze-up during low ambient operation. The subcooler control low-pressure switch will only
deactivate the 3-way liquid line solenoid valve in the M oistureMiser circuit. The compressors will continue to run as long
as there is a call for cooling, regardless of the position of the
subcooler control low-pressure switch. The 3-way solenoid
valve and the MoistureMiser package will be re activated only
when the call for cooling has been satisfied, the subcooler control low-pressure switch has closed above 80 psig, and a new
call for cooling exists. The crankcase heaters on the scroll compressors provide additional protection for the compressors due
to the additional refrigerant charge in the subcooler.
23
Page 24
Fig. 30 — MoistureMiser Operation Diagram
When the humidistat is satisfied, the humidistat internal
switch opens, cutting power to and deenergizing the LLSVs.
The refrigerant is routed back through the evapora tors and the
sub-cooler coils are removed from the refrigerant loops. When
the thermostat is satisfied, C1 and C2 are deenergized and t he
compressors, IFM, and OFMs shut off. If the thermostat
fan selector switch is in the ON position, the IFM will run
continuously .
SERVICE
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Turn off accessory
heater power switch if applicable. Electrical shock could
cause personal injury.
Cleaning —
ing and cooling season and as operating conditions require.
Remove unit top panel and/or side panels for access to unit
interior.
EVAPORATOR COIL — Clean as required with a commercial coil cleaner.
NOTE: The 50TJ028 unit has a mist eliminator screen attached
to the evaporator coil to prevent condensate runoff at high wetbulb conditions. Check periodically and clean as necessary.
Inspect unit interior at beginning of each heat-
CONDENSER COIL — Clean condenser coil annually and
as required by location and outdoor-air conditions. Inspect coil
monthly — clean as required.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer
to Ta ble 1 for type and size.
NOTE: The 50TJ028 unit requires industrial grade throwaway
filters capable of withstanding face velocities up to 625 fpm.
Ensure that replacement filters for the 50TJ028 units are rated
for 625 fpm.
OUTDOOR-AIR INLET SCREENS — Clean screens with
steam or hot water and a mild detergent. Do not use throwaway
filters in place of screens.
Lubrication
COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory. Conventional white oil
(Sontext 200LT) is used. White oil is compatible with 3GS oil,
and 3GS oil may be used if the addition of oil is required. See
compressor nameplate for original oil charge. A complete recharge should be four ounces less than the original oil charge.
When a compressor is excha nged in the field it is possible that
a major portion of the oil from the replaced compressor may
still be in the system . Whil e this wi ll no t af fe ct th e rel iabi lity of
the replacement compressor, the extra oil will add rot or drag
and increase power usage. To remove this excess oil, an access
valve may be added to the lower portion of the suction line at
24
Page 25
the inlet of the compressor. The compressor should then be run
Fig. 31 — Evaporator-Fan Pulley Alignment
and Adjustment
for 10 minutes, shut down, and the access valve opened until
no oil flows. This should be repeated twice to make sure the
proper oil level has been achieved.
FAN SHAFT BEARINGS — For size 016 units , bearings are
permanently lubricated. No field lubrication is required. For
size 020-028 units, the bearings are of the pillow block type
and have grease fittings. The bearing opposite the motor end
has an extended tube line so it can be lubricated from the motor
side. Lubricate the bearings twice annually.
T ypical lubricants are given below:
MANUFACTURERLUBRICANT
Texaco
Mobil
Sunoco
Texaco
*Preferred lubricant because it contains rust and oxidation inhibitors.
Regal AFB-2*
Mobilplex EP No. 1
Prestige 42
Multifak 2
CONDENSER AND EVAPORATOR-FAN MOTOR
BEARINGS — The condenser and evaporator-fan motors
have permanently-sealed bearings, so no field lubrication is
necessary.
Evaporator Fan Performance Adjustment
(Fig. 31-33) —
shown in T able 1.
T o change fan speeds:
1. Shut off unit power supply.
2. a. Size 016 Only: Loosen belt by loosening fan motor
mounting plate nuts.
b. Size 020-028 Only: Loosen nuts on the 2 carriage
bolts in the motor mounting base. Install jacking
bolt and plate under motor base (bolt and plate are
shipped in installer’s packet). See Fig. 33. Using
bolt and plate, raise motor to top of slide and
remove belt. Secure motor in th is pos i ti on by tig ht ening the nuts on the carriage bolts.
3. Loosen movable-pulley flange setscrew (see Fig. 31).
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.
See Tabl e 7 for air quantity limits.
5. Set movable flange at ne arest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)
6. Repla ce and tighten belts. See Belt Tension Adjustment
section on page 26.
T o align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
Fan motor pulleys are factory set for speed
Evaporator Fan Service and Replacement
50TJ016 UNITS (See Fig. 32)
NOTE: To remove belts only, follow Steps 1-6.
1. Remove filter and supply-air section panels.
2. Remove unit top panel.
3. Loosen c arriage nuts A and B holding motor mount as-
sembly to fan scroll side plates.
4. Loosen screw C.
5. Rotate m otor mount assembly (with motor attached) as
far as possible away from evaporator coil.
6. Remove belt.
7. Rotate motor mount assembly back past original position
toward evaporator coil.
8. Remove motor mounting nuts D and E (both sides).
9. Lift motor up through top of unit.
10. Reverse above procedure to reinstall motor.
11. Check and adjust belt tension as necessary.
50T J 020 -0 2 8 U NI TS (S ee Fi g. 33 ) — The 50TJ020-028
units use a fan motor mounting system that features a slide-out
motor mounting plate. To replace or service the motor, slide out
the brack et.
1. Remove t he evaporator-fan access panel and the heating
control access panel.
2. Remove the center post (located betwe en the evaporator
fan and heating control access panels) and all screws securing it.
3. Loosen nuts on the two carriage bolts in the motor mounting base.
4. Using jacking bolt under motor base, raise motor to top of
slide and remove belt. Secure motor in this position by
tightening the nuts on the carriage bolts.
5. Remove the belt drive.
6. Remove jacking bolt and tapped jacking bolt plate.
7. Remove the 2 screws that secure the motor mounting
plate to the motor support channel.
8. Remove the 3 screws from the end of the motor support
channel that interfere with the motor slide path.
9. Slide out the motor and motor mounting plate.
10. Disconnect wiring c onnections a nd remove the 4 mount ing bolts.
11. Remove the motor.
12. To install the new motor, reverse Steps 1-11.
25
Page 26
4. Tighten setscrews and replace rubber hubcap to prevent
NOTE: A 31/2-in. bolt and threaded plate are included in the
installer’s packet. They should be added to the motor support channel below the motor mounting plate to aid in raising the motor. The
plate part number is 50DP503842. The adjustment bolt is
3
/8-16 x
1
3
/4 in.-LG.
Fig. 33 — 50TJ020-028 Evaporator-Fan
Motor Section
NOTE: Dimensions are in inches.
Fig. 35 — Condenser-Fan Adjustment,
50TJ024,028
NOTE: Dimensions are in inches).
Fig. 34 — Condenser-Fan Adjustment,
50TJ016,020
hub from rusting to motor shaft.
5. Fill hub recess with permagum if rubber hubcap is
missing.
Belt Tension Adjustment —
1. Loosen fan motor bolts.
2. Adjust belt tension:
Fig. 32 — 50TJ016 Evaporator-Fan
Motor Section
To adj ust belt tension:
a. Size 016 Units: Move motor mounting plate up or
down for proper belt tension (
1
/2 in. deflection with
one finger).
b. Size 020-028 Units: Turn motor jacking bolt to move
motor mounting plate up or down for proper belt ten-
3
sion (
/8 in. deflection at midspan with one finger [9
lb force]).
3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure motor in
fixed position.
Condenser-Fan Adjustment
50TJ016,020 UNITS (Fig. 34)
1. Shut off unit power supply.
2. Remove access panel(s) closest to the fan to be adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed
across the fan orifice.
5. Tighten setscrews and replace panel(s).
6. Turn on unit power.
50TJ024,028 UNITS (Fig. 35)
1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub
screws.
3. Adjust fan height on unit, using a straightedge placed
across the fan orifice.
26
Page 27
EconoMi$er Adjustment
LED INDI CATI ON — The EconoMi$er controller features
an onboard diagnostic LED (light-emitting diode) that flashes
to indicate its status. See Table 15 for flash codes. The controller also has terminal connections (REM LED) for remotely
mounting an LED, if desired. The flash code priorities are as
follows:
1. On/Off or continuous flash
2. Critical fault
3. Non-critical fault
If any sensors are opened, shorted, or removed, the
EconoMi$er determines whether the failure is critical or noncritical and flashes the appropriate code. If a non-critical sensor
fault occurs (i.e., outdoor air humidity), the EconoMi$er auto matically reconfigures its control strategy to a more appropriate
mode. If a critical sensor fault occurs (i.e., supply air sensor),
the EconoMi$er reverts to a safe mode of operation until the
sensor problem is resolved.
MANUAL CONFIGURATION PUSHBUTTON — The
EconoMi$er controller also features an onboard button (CONFIG) to help troubleshoot the system. See Fig. 16. The button
can perform 3 different functions.
Pressing the CONFIG button for more than three seconds,
but less than ten seconds and then releasing will start the automatic test procedure. The damper will modulate fully open,
wait, and modulate closed. This process takes three minutes to
complete. Use this feature to determine if the actuator can be
commanded.
If the CONFIG button is pressed and held for ten seconds
and less than 30 seconds then released, the EconoMi$er controller reconfigures its mode of operation based on the sensors
that are connected and functioning normally, and cancels the
automatic test procedure.
If the EconoMi$er controller recognized a non-critical
sensor fault, and flashed a code (i.e., FLASH 6, outdoor air
humidity sensor fault) the FLASH CODE will be cleared, and
normal operation begins. Ensure faulty sensor is removed
before clearing faults.
If the EconoMi$er controller recognizes a critical sensor
fault, and flashes a code (i.e., FLASH 4, discharge air thermostat fault) the FLASH code will not be cleared, and the
EconoMi$er will remain in the safe operation mode. The
sensor fault must be corrected to enable EconoMi$er to revert
to normal operation.
If the CONFIG button is pressed and held for more th an
30 seconds and released, the EconoMi$er controller will enable
the enthalpy comparison strategy (with outdoor air enthalpy
and return air enthalpy sensors installed).
Power Failure —
Dampers have a spring return. In event
of power failure, dampers will return to fully closed position
until power is restored.
Do not manually operate damper
motor.
Refrigerant Charge —
Amount of refrigerant charge is
listed on unit nameplate and in Table 1. Refer to Carrier GT AC
II; Module 5; Charging, Recovery, Recycling, and Reclamation
section for charging methods and procedures. Unit panels must
be in place when unit is operating during charging procedure.
NOTE: Do not use recycled refrigerant a s it may contain contaminants.
NO CHA RGE — Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING — Using cooling charging chart
(see Fig. 36), add or remove refrigerant until conditions of the
chart are met. Note that charging chart is different from those
normally used. An accurate pressure gage and temperaturesensing device is required. Charging is accomplished by ensuring the proper amount of liquid subcooling. Measure liquid line
pressure at the liquid line service valve using pressure gage.
Connect temperature sensing device to the liquid line near the
liquid line service valve and insulate it so that outdoor ambient
temperature does not affect reading.
TO USE THE COOLING CHARGING CHART — Use the
above temperature and pressure readings, and find the intersection point on the cooling charging chart. If intersection point on
chart is above line, add refrigerant. If intersection point on
chart is below line, carefully recover some of t he charge. Recheck suction pressure as charge is adjusted. NOTE: Indoor-air
CFM must be within normal operating range of unit. All outdoor fans must be operating.
The TXV (thermostatic expansion valve) is set to maintain
between 15 and 20 degrees of superheat at the compressors.
The valves are factory set and should not require re-adjustment.
Table 15 — EconoMi$er Control Module Flash Code Identification
FLASH CODECAUSEACTION TAKEN BY ECONOMI$ER
Constant On
Constant Off
Continuous
Flash
Flash One
Flash Two
Flash Three
Flash Four
Critical Fault
Flash Five
Flash Six
Flash Seven
Flash Eight
Flash Nine
Non-Critical Fault
Flash Ten
Normal operationNormal operation.
No powerNo operation.
CONFIG button pushed and held
between 3 and 9 seconds
Control board faultSystem shutdown.
Thermostat fault (i.e., Y2 without Y1)System shutdown until corrected.
Actuator faultRevert to mechanical cooling only.
Discharge air thermistor fault
Outdoor air temperature sensor fault
Outdoor air humidity sensor faultContinue operation with dry bulb or dry bulb differential switchover.
Return air temperature sensor fault
Return air humidity sensor fault
Carbon Dioxide (CO
Onboard adjustment potentiometer faultContinue operation with default potentiometer settings.
) sensor faultContinue operation without ventilation control.
2
Outdoor air damper is stroked fully open, then closed
(automatic test procedure takes 3 minutes to complete).
Continue operation with damper at minimum position.
Revert to mechanical cooling only.
Continue operation with damper at minimum position.
Disable mechanical cooling lockout.
Continue operation with single enthalpy EconoMi$er
switchover or dry bulb EconoMi$er switchover (without
humidity sensor).
Continue operation with single enthalpy, differential dry
bulb, or dry bulb EconoMi$er switchover.
27
Page 28
BOTH CIRCUITS
REDUCE CHARGE IF BELOW CURVE
150
200
250
300
350
400
140
120
100
80
60
LIQUID TEMPERATURE AT LIQUID VALVE (DEG F)
40
50
ALL OUTDOOR FANS MUST BE OPERATING
ADD CHARGE IF ABOVE CURVE
100
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
Fig. 36 — Cooling Charging Chart
MOISTUREMISER SYSTEM CHARGING — The system
charge for units with the MoistureMiser option is greater than
that of the standard unit alone. The charge for units wit h this
option is indicated on the unit nameplate drawing. To charge
systems using the MoistureMiser Dehumidification package,
fully evacuate, recover, and re-charge the system to the nameplate specified charge level. To check or adjust refrigerant
charge on systems using the MoistureMiser Dehumidification
package, charge per the standard subcooling charts. The subcooler MUST be deenergized to use the charging charts. The
charts reference a liquid pressure (psig) and temperature at a
point between the condenser coil and the subcooler coil. A tap
is provided on the unit to measure liquid pressure entering the
subcooler (leaving the condenser).
Filter Drier —
Replace whenever refrigerant s ystem is ex-
posed to atmosphere.
Protective Devices
COMPRESSOR PROTECTION
Overcurrent
protection, except the circuit no. 1 on the 50TJ028 unit. Compressor no. 1 on the 50TJ028 unit uses an electronic module located with the compressor junction box, to provide motor protection. This electronic module monitors winding and discharge temperatures. If these temperatures reach the trip
values, the module interrupts the control line and causes the
compressor to swit ch of f.
Crankcase Heater
the optional MoistureMiser Dehumidification system are
equipped with a 70-watt crankcase heater to prevent absorption
of liquid refrigerant by oil in the crankcase when the compressor is idle. The crankcase heater is energized whenever there is
a main power to the unit and the compressor is not energized.
IMPORTANT: After prolonged shutdown or servicing,
energize the crankcase heaters for 24 hours before starting the compressors.
— Each compressor has internal line break motor
— Only the 50TJ028 unit and units with
Compressor Lockout
— If any of the safeties (high-pressure,
low-pressure, freeze protection thermostat, compressor internal
thermostat) trip, or if there is loss of power to the compr essors,
the CLO (compressor lockout) will lock the compressors off.
T o reset, manually move the thermostat setting.
EVAPORATOR FAN MOTOR PROTECTION — A manual reset, calibrated trip, magnetic circuit breaker protects
against overcurrent. Do not bypass connections or increase the
size of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
CONDENSER-FAN MOTOR PROTECTION — Each
condenser-fan motor is internally protected against
overtemperature.
HIGH- AND LOW-PRESSURE SWIT CHES — If either
switch trips, or if the compres sor overt emperatur e switch activates, that refrigerant circuit will be automatically locked out
by the CLO. To reset, manually move the thermostat setting.
FREEZE PROTECTION THERMOSTAT (FPT) — An FPT
is located on the top and bottom of the evaporator coil. It detects frost build-up and turns off the compressor, allowing the
coil to clear. Once the frost has melted, the compressor can be
reenergized.
Relief Devices —
All units have relief devices to protect
against damage from excessive pressures (e.g., fire). These devices protect the high and low side.
Control Circuit, 24-V —
This control circuit is protected against overcurrent by a 3.2-amp circuit brea ker. Breaker
can be reset. If it trips, determine cause of trouble before
resetting.
Replacement Parts —
A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.
EconoMi$er LEDs —
The EconoMi$er control module
has an LED for diagnostic purposes. The flash code identification is shown in T able 15.
Optional Hinged Access Doors —
When the optional
service package is ordered or the if the hinged access doors
option is ordered, the unit will be provided with external and
internal hinged access doors to facilitate service.
Four external hinged access doors are provided. All external
doors are provided with 2 large
1
/4 turn latches with folding
bail-type handles. (Compressor access doors have one latch.) A
single door is provided for filter and drive access. One door is
provided for control box access. The control box access door is
interlocked with the non-fused disconnect which must be in the
OFF position to open the door. Two doors are provided for access to the compressor compartment.
Two internal access doors are provided inside the filter/
drive access door. The filter access door (on the left) is secured
by 2 small
1
/4 turn latches with folding bail-type handles. This
door must be opened prior to opening the drive access door.
The drive access door is shipped with 2 sheet metal screws
holding the door closed. Upon initial opening of the door, these
screws may be removed and discarded. The door is then held
shut by the filter access door, which closes over it.
Adjustable Heat Anticipator
Breaks with Amp Turns
Contactor, Compressor
Circuit Breaker
Cooling Compensator
Crankcase Heater
Compressor Lockout
Compressor Motor
Control Relay
Discharge Air Thermistor
Damper Motor
Dummy Terminal
Enthalpy Control
Equipment
Fuse Link
Full Load Amps
Freeze Protection Thermostat
Fuse
NOTES:
1. Compressor and fan motor(s) thermally protected; 3-phase motors protected
against primary single-phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with
type 90 C wire or its equivalent.
3. TRAN1 is wired for 230 v (60 Hz) or 220 v (50 Hz) operation. If unit is 208 v, disconnect the black wires from the ORN TRAN wire and reconnect to the RED
TRAN wire, apply wirenuts to wires.
5. IFCB must trip amps is equal to or less than 140% FLA.
6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices.
7. Jumpers are omitted when unit is equipped with EconoMi$er.
8. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. Plain (no line) number signifies a normally open
contact.
Te r mi n al B lo c k
Thermostat Cooling
Thermostat Heating
Transformer
Terminal (Marked)
Terminal (Unmarked)
Te r mi n al B lo c k
Splice
Fac tory W irin g
Field Control Wiring
Option/Accessory Wiring
To indicate common potential
only; not to represent wiring.
31
Page 32
PROBLEMCAUSEREMEDY
Compressor and
condenser fan
will not start.
Compressor will not start
but condenser fan runs.
Compressor cycles
(other than normally
satisfying thermostat).
Compressor operates
continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction
pressure.
Suction pressure too low.
LEGEND
Thermostatic Expansion Valve
TXV —
TROUBLESHOOTING
Refer to Tables 16-18 for troubleshooting details.
Table 16 — Cooling Service Analysis
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or control
relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace.
Compressor motor burned out, seized, or internal over-
load open.
Defective overload.Determine cause and replace.
Compressor locked outDetermine cause for safety trip and reset lockout.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker.
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and recharge
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective overload.Determine cause and replace.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Air in system.Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Recover excess refrigerant.
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Air in system.Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks, repair, and recharge.
Restriction in liquid tube.Remove restriction.
High heat load.Check for source and eliminate.
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Field-installed filter drier restricted.Replace.
Replace component.
Determine cause. Replace compressor.
Determine cause.
to nameplate.
suction line.
2. Replace TXV if stuck open or closed.
suction line.
2. Replace TXV if stuck open or closed.
suction line.
2. Replace TXV if stuck open or closed.
necessary.
32
Page 33
Table 17 — EconoMi$er Troubleshooting
PROBLEMPOTENTIAL CAUSEREMEDY
Damper Does Not
Open
EconoMi$er
Operation Limited to
Minimum Position
Damper Position
Less than Minimum
Position Set Poi nt
Damper Does Not
Return to Minimum
Position
Damper Does Not
Close on Power Loss
LEGEND
IFM —
PL—
Indoor Fan Motor
Plug
Indoor (Evaporator) Fan is
Off
No Power to EconoMi$er
Controller
No Power to G TerminalIf IFM is on, check to ensure 24 vac is present on G Terminal of the
Controller FaultIf STATUS light is flashing one flash, the EconoMi$er controller is
Thermostat FaultIf STATUS light is flashing two flashes, the EconoMi$er controller senses that
Actuator FaultCheck the wiring between the EconoMi$er controller and the actuator.
Minimum Position Set
Incorrectly
EconoMi$er Changeover
Set Point Set Too High or
Too Low
Discharge Air
Thermistor Faulty
Outdoor Air Temperature
Sensor Faulty
Supply Air Low Limit
Strategy Controlling
Ventilation Strategy
CO
2
Controlling
Damper Travel is
Restricted
Check to ensure that 24 vac is present at Terminal C1 (Common Power)
on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at
the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
Check to ensure that 24 vac is present across Terminals 24 VAC and
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.
Hold CONFIG button between 3 and 10 seconds to verify the
actuator’s operation. (This process takes 3 minutes to complete.)
Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 5.
If STATUS light is flashing 4 flashes, Discharge Air Thermistor is
faulty. Check wiring or replace sensor.
If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
faulty. Check wiring or replace sensor.
The supply-air temperature is less than 45 F, causing the minimum
position to be decreased. Refer to the Start-Up instructions. Verify correct
setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
If a CO2 sensor is being used, and the damper position is greater than
minimum position, the ventilation control strategy is controlling. Refer to
The Start-Up instructions. EconoMi$er is operating correctly.
Check to ensure the damper is not blocked.
Table 18 — MoistureMiser Dehumidification Subcooler Service Analysis
PROBLEMCAUSEREMEDY
Subcooler will not energize
Subcooler will not deenergize
Low system capacity
No power to subcooler
control transformer.
No power from subcooler
control transformer to liquid line three way valve.
Liquid line three-way valve
will not operate.
Liquid Line three-way valve
will not close.
Low refrigerant charge or
frosted coil.
33
Check power source. Ensure all wire connections
are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Subcooler control low pressure switch open.
Cycle unit off and allow low-pressure switch
to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
1. Solenoid coil defective; replace.
2. Solenoid valve stuck closed; replace.
Valve is stuck open; replace.
1. Check charge amount. See system charging
section.
2. Evaporator coil frosted; check and replace
subcooler control low pressure switch if necessary.
Page 34
SERVICE TRAINING
Packaged Service Training
programs are an excellent way to increase your knowledge of the equipment
discussed in this manual, including:
• Unit Familia r iz ation• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based formats
and materials. All include video and/or slides, plus companion book.
Classroom Service Training
which includes “hands-on” experience with the products in our labs can
mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks. Course
descriptions and schedules are in our catalog.
CALL FOR FREE CA TALOG 1-800-962-9212
[ ] Packaged Service Training[ ] Classroom Service Training
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Ta b 1 b
PC 111Catalog No. 535-034Printed in U.S.A.Form 50TJ-17SIPg 342-01Replaces: 50TJ-14SI
Page 35
Page 36
START-UP CHECKLIST
MODEL NO.:
SERIAL NO.:
DATE:TECHNICIAN:
PRE-START-UP:
VERIFY THAT ALL P A CKIN G MATERIALS HAVE B EEN REMO VED F ROM UNI T
VERIFY INSTALLATION OF INDOOR FAN MOTOR ADJUSTMENT BOLT (016 UNITS) OR ADJUSTMENT
BOLT AND PLATE (020-028 UNITS)
VERIFY INSTALLATION OF ECONOMI$ER HOOD
VERIFY THAT CONDENSATE CONNECTION IS INST ALLED PER INSTRUCTIONS
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
CHECK THAT FILTE RS AN D SCR EEN S ARE C LEAN AN D IN P LACE
VERIFY THA T UNIT IS LEVEL
CHECK F AN WHEEL AND PROPELLER FOR LOCA TION IN HOUSING/ORIFICE, AND VERIFY SETSCREW
IS TIGHT
VERIFY THA T FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
VERIFY THAT SCROLL COMPRESSOR IS ROT ATING IN THE CORRECT DIRECTION
VERIFY THAT CRANKCASE HEATER HAS BEEN ENERGIZED FOR 24 HOURS (SIZE 028 AND UNITS WITH
OP TI ONAL MOI STU RE MIS ER DE HUMI DI FIC ATION SYSTEM ONLY)