Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the unit will automatically
lock the compressor out of operation. Manual r eset will
be required to restart the compressor.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb or
horizontal adapter roof curb in accordance with instructions
shipped with the curb or horizontal adapter. Accessory roof
curb and horizontal adapter roof curb and information required
to field fabricate a roof curb or horizontal adapter roof curb are
shown in Fig. 1 and 2. Install insulation, cant strips, roofing,
and counter flashing as shown. Ductwork can be secured to
roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb
or adapter roof curb is critical for a leak-proof seal.
Install gasket supplied with the roof curb or adapter roof
curb as shown in Fig. 1. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb or adapter roof curb should be level. This is necessary
to permit unit drain to function properly. Unit leveling tolerance is ±
ry Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additional information as required.
ALTERNATE UNIT SUPPORT — When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
adapter support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally spaced 4-in. x 4-in.
pads on each side.
Step 2 — Rig and Place Unit —
transportation damage. File any claim with transportation
agency. Keep unit upright, and do not drop. Use spreader bars
over unit to prevent sling or cable damage. Rollers may be used
to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ±
tion. See Fig. 3 for additional information. Unit weight is
shown in T able 1.
shown in Fig. 3. Refer to rigging instructions on unit.
POS ITIONI NG — Provide clearance around and above unit
for airflow, safety, and service access (Fig. 4 and 5).
lets near exhaust vents or other sources of contaminated air.
higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight distribu-
tion requirements.
1
/16 in. per linear ft in any direction. Refer to Accesso-
Inspect unit for
1
/16 in. per linear ft in any direc-
Four lifting holes are provided in ends of unit base rails as
Do not install unit in an indoor location. Do not locate air in-
Although unit is weatherproof, guard against water from
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Ta b 1 b
PC 111Catalog No. 535-034Printed in U.S.A.Form 50TJ-17SIPg 12-01Replaces: 50TJ-14SI
lb density.
2
/
1
AB
.28.45.28.43
thick neoprene coated 1
″
Deg.in.Deg.in.
DIMENSIONS* (degrees and inches)
ALL
UNIT
below the unit discharge for units equipped with electric
heaters.
A 90 degree elbow must be installed on the supply ductwork
NOTE: To prevent the hazard of stagnant water build-up in the drain
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1
3. Dimensions in ( ) are in millimeters.
4.Direction of airflow.
5. Roof curb: 16 ga. (VA03-56) stl.
6.
pan of the indoor section, unit can only be pitched as shown.
PKG. NO. REF.CURB HEIGHTDESCRIPTION
High
″
(305)Standard Curb 14
″
-2
′
CRRFCURB010A001
Fig. 1 — Roof Curb Details
(610)Side Supply and Return Curb for High Installation
(610)Standard Curb for Units Requiring High Installation
″
″
-0
-0
′
′
CRRFCURB012A002
CRRFCURB011A002
2
NOTE: For preassembled horizontal adapter roof curb part no.
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4 and 5 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner
post from packaging to protect coil from damage. Use bumper
boards for spreader bars.
5. Weights do not include optional EconoMi$er. See Fig. 4 and 5 for
EconoMi$er weight. See Table 1 for MoistureMiser weight.
6. Weights given are for aluminum evaporator and condenser coil
plate fins.
Fig. 3 — Rigging Details
UNIT
50TJ
MAXIMUM
SHIPPING WEIGHT
DIMENSIONS
AB
LbKgFt-in.mmFt-in.mm
016
15507036-11
1
/221214- 01219
020
16507486-11
1
/221213-101168
024
17007716-11
1
/221213- 71092
028
18508396-11
1
/221213- 51041
All panels must be in place when rigging.
CRRFCURB013A00, the accessory kit includes a factory-designed,
high-static, transition duct. For horizontal curb part no.
CRRFCURB012A00, a field-supplied transition duct is required.
Fig. 2 — Horizontal Adapter Roof Curb
and Roof Curb
3
(8) on
″
16
/
5
-
′
DIM ADIM BDIM C
(D)
CORNER
(C)
CORNER
(B)
CORNER
(A)
CORNER
WEIGHT
ECONOMI$ER
WEIGHT
STD UNIT
LbKgLbKgLbKgLbKgLbKgLbKg Ft-in. mm Ft-in. mm Ft-in. mm
(1219) for proper operation of damper and
(1219) if conditions permit coil removal from the
″
″
(1219) for proper condenser coil airflow.
-0
′
″
-0
′
(2134) for coil removal. This dimension can be
(1219) for control box access.
-0
′
″
″
-0
′
reduced to 4
Rear: 7
1. Refer to print for roof curb accessory dimensions.
Rows...Fins/in.2...17
Total Face Area (sq ft)21.721.721.7
CONDENSER FANPropeller Type
Nominal Cfm10,50010,50014,20014,200
Quantity...Diameter (in.)3...223...222...302...30
Motor Hp...Rpm
Watts Input (Total)1100110034003400
EVAPORATOR COILCross-Hatched
Rows...Fins/in.2...173...153...154...15
Total Face Area (sq ft)17.517.517.517.5
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...10 x 102...10 x 102...12 x 122...12 x 122...12 x 12
Type DriveBeltBeltBeltBeltBelt
Nominal Cfm600060007200800010,000
Motor Hp3.73.057.510
Motor Nominal Rpm17251725174517451740
Maximum Continuous Bhp4.253.455.90
Motor Frame Size56H56H184T213T215T
Nominal Rpm High/Low—————
Fan r/s RangeLow-Medium Static891-11791159-1429910-10951002-12251066-1283
Motor Bearing TypeBallBallBallBallBall
Maximum Allowable Rpm15501550155015501550
Motor Pulley Pitch DiameterLow-Medium Static3.1/4.14.3/5.34.9/5.95.4/6.64.9/5.9
Min/Max (in.)High Static3.7/4.7—4.9/5.95.4/6.64.9/5.9
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)Low-Medium Static6.06.49.49.48.0
Nominal Fan Shaft Diameter (in.)1
Belt, Quantity...Type...Length (in.)Low-Medium Static1...BX...421...BX...451...BX...501...BX...532...BX...50
Pulley Center Line Distance (in.)13.5-15.513.5-15.513.3-14.814.6-15.414.6-15.4
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position66666
Factory Speed3.53.53.53.53.5
Factory Speed Setting (rpmLow-Medium Static10351296100211201182
Fan Shaft Diameter at Pulley (in.)1
HIGH-PRESSURE SWITCH (psig)
Cutout426
Reset (Auto)320
LOW-PRESSURE SWITCH (psig)
Cutout27
Reset (Auto)44
FREEZE PROTECTION THERMOSTAT (F)
Opens30 ± 5
Closes45 ± 5
OUTDOOR-AIR INLET SCREENSCleanable
Quantity...Size (in.)2...20 x 25 x 1
RETURN-AIR FILTERSThrowaway†
Quantity...Size (in.)4...20 x 20 x 2
High Static1227-1550—1069-12871193-14581332-1550
High Static5.2—8.07.96.4
High Static1...BX...42—1...BX...481...BX...502...BX...47
*Circuit 1 uses the lower por tion of condenser coil and lower portion of evap-
orator coils; and Circuit 2 uses the upper portion of both coils.
016
020024028
808080
40
2...ZR94KC
50, 50
2
81, 81
10-10
Aluminum Pre-Coated, or Copper Plate Fins
21.7
1
/2...1050
7
/
8
3
/
16
3
/
16
1
/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
7
/
8
13/
16
13/
16
†The 50TJ028 units requires 2-in. industrial-grade filters capable of handling
face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or
equivalent).
NOTE: The 50TJ016-028 units have a low-pressure switch (standard) located
on the suction side.
404040
1...ZR108KC,
1...ZR94KC
15-516-020-13
3
/8-in. Copper Tubes, Aluminum Lanced,
3...153...154...15
1
/2...10501...10751...1075
3
/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
11/
8
17/
16
17/
16
1...20 x 20 x 1
4...16 x 20 x 2
1...ZR125KC,
1...ZR108KC
8.7 [208/230, 575 v]
9.5 [460 v]
13/
8
17/
16
17/
16
1...ZR16M3,
1...ZR125KC
10.2 [208/230, 575 v]
11.8 [380, 460 v]
17/
17/
13/
8
16
16
6
Step 3 — Field Fabricate Ductwork —
3/4" FPT DRAIN
CONNECTION
1-3/8"
DRAIN HOLES
Shaded area indicates block-off panels.
NOTE: Dimensions A, A′, and B, B′ are obtained from field-supplied
ceiling diffuser.
Fig. 8 — Concentric Duct Details
Fig. 9 — Condensate Drain Details
(50TJ016,020 Shown)
Secure all
ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
The 50TJ units with electric heat require a 1-in. clearance
for the first 24 in. of ductwork.
Outlet grilles must not lie directly below unit discharge.
NOTE: A 90-degree elbow must be provided in the ductwork
to comply with UL (Underwriters’ Laboratories) codes for use
with electric heat.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90 degree
turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then
a grille of sufficient strength and density should b e installed
to prevent objects from falling into the conditioned space.
Due to electric heater, supply duct will require 90 degree
elbow.
Step 4 — Make Unit Duct Connections —
Unit
is shipped for through-the-bottom duct connections. Ductwork
openings are shown in Fig. 6. Field-fabricated concentric ductwork may be connected as shown in Fig. 7 and 8. Attach all
ductwork to roof curb and roof curb basepans. Refer to installation instructions shipped with accessory roof curb for more
information.
Step 5 — Trap Condensate Drain —
and 9 for drain location. Plug is provided in drain hole and
must be removed when unit is operating. One
See Fig. 4, 5,
3
/4-in. halfcoupling is provided inside unit evaporator section for condensate drain connection. An 81/2 in. x 3/4-in. diameter nipple and a
2-in. x
3
3
/4-in. diameter pipe nipple are coupled to standard
/4-in. diameter elbows to provide a straight path down through
holes in unit base rails (see Fig. 10). A trap at least 4-in. deep
must be used.
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 6 — Air Distribution — Thru-the-Bottom
(50TJ020-028 Shown)
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 7 — Concentric Duct Air Distribution
(50TJ020-028 Shown)
7
Fig. 10 — Make Electrical Connections
TB1 MAXIMUM WIRE SIZE
LEGEND
Fig. 11 — Field Power Wiring Connections
UNIT
50TJ
VOLTAGE
208/230,380460575
All
350 kcmil2/02/0
EQUIP —
Equipment
GND—
Ground
kcmil —
Thousand Circular Mils
NEC—
National Electrical Code
TB—
Terminal Block
UNIT LOW-VOLTAGE CONNECTIONS
Fig. 12 — Field Control Thermostat Wiring
Step 6 — Make Electrical Connections
FIEL D POWER SUP PLY — Unit is factory wired for voltage shown on nameplate.
When installing units, provide a disconnect, per NEC
(National Electrical Code) requirements, of adequate size
(T able 2).
All field wiring must comply with NEC and local
requirements.
Route power lines through control box access panel or unit
basepan (Fig. 4 and 5) to connections as shown on unit wiring
diagram and Fig. 11.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages
between phases must be balanced within 2% and the current
must be balanced within 10%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company immediately.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
FIELD CONTR OL WIRING — Install a Carrier-approved
accessory thermostat assembly according to the installati on instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of no. 18
A WG (American Wire Gage) colored wire from subbase terminals through conduit in unit to low-voltage connections as
shown on unit label wiring diagram and in Fig. 12.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG
insulated wire (35 C minimum). All wire larger than no. 18
AWG cannot be direct ly connected to the thermostat and will
require a junction box and splice at the thermostat.
Set heat anticipator settings as indicated in Tabl e 3. Settings
may be changed slightly to provide a greater degree of comfort
for a particular installation.
The correct power phasing is critical in the operation of the
scroll compressors. An incorrect phasing will cause the
compressor to rotate in the wrong direction. This may lead
to premature compressor failure.
Use the following formula to determine the percentage of
voltage imbalance.
Percentage of Voltage Imbalance
= 100 x
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage:
max voltage deviation from average voltage
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
A verage Voltage =
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
Percentage of Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is be-
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
380 v, 480 v, and 575 v. Heaters are rated at 240 v, 380 v, 480 v, or
600 v. If power distribution voltage to unit varies from rated heater
voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Heaters are field installed only.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percent of voltage imbalance.
% Voltage Imbalance
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
max voltage deviation from average voltage
VO LTAG E
RANGE
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) HpFLAFLA LRAkWFLAMCAMOCP†
Use the following formula to determine
average voltage
COMPRESSOR
No. 1No. 2
OFMIFM
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
3. MCA calculation for units with electric heaters over 50 kW =
(1.25 x IFM amps) + (1.00 x heater FLA).
the optional non-fused disconnect, incoming power will be
wired into the disconnect switch. Refer to Fig. 13 for wiring
for 100 and 200 amp disconnect switches. Units with an
MOCP under 100 will use the 100 amp disconnect switch.
Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control
box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Ope n the control box door and remove the handle and
shaft from shipping location.
2. Loosen the A llen bolt located on the disconnect switch.
The bolt is located on the square hole and is used to hold
the shaft in place. The shaft cannot be inserted until the
Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is specially cut and
the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two
screws provided. When the handle is in the ON position,
the handle will be vertical. When the handle is in the OFF
position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door.
The handle should fit over the end of the shaft when t he
door is closed.
8. The ha ndle must be in the OFF position to open the control box door.
OPTIONAL CONVENIENCE OUTLET — On units with
optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outlet receptacle is provided for field wiring.
Field wiring should be run through the
7
/8-in. knockout pro-
vided in the basepan near the return air opening.
Step 7 — Make Outdoor-Air Inlet Adjustments
MANUAL OUTDOOR-AIR DAMPER — All units (except
those equipped with a factory-installed economizer) have a
manual outdoor-air damper to provide ventilation air. Damper
can be preset to admit up to 25% outdoor air into return-ai r
compartment. To adjust, loosen securing screws and move
damper to desired setting. Then retighten screws to secure
damper (Fig. 14).
OPTIONAL ECONOMI$ER
EconoMi$er Motor Control Module (Fig. 15-17)
ECONSP dial to the ‘ ‘D’’ setting (Fig. 16). The control module
is located on the EconoMi$er motor. See Fig. 15 and 17.
Damper Vent Position Setting
1. Set fan switch at ON position (continuous fan operation)
and close night switch if used.
2. Set system selector switch to OFF position.
3. Turn Min Pos (%) dial slowly until dampers assume desired vent position.
Do not manually operate EconoMi$er
motor since damage to motor will result.
— Set the
NOTE: The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 13 — Optional Non-Fused Disconnect Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.