Carrier 50TFQ008-012 User Manual

Single-Package Rooftop
Heat Pump Units
Installation, Start-Up and
Service Instructions
50TFQ008-012
CONTENTS
Page
INSTALLATION ...................................1-43
Step 1— Provide Unit Support .......................1
• ROOF CURB
• SLAB MOUNT
• ALTERNATE UNIT SUPPORT
Step 2 — Field Fabricate Ductwork ..................3
Step 3 — Install Condensate Drain Line
and External Trap .................................3
• POSITIONING
Step 5 — Make Electrical Connections ..............7
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• DEFROST BOARD
• HEAT ANTICIPATOR SETTINGS
Step 6 — Adjust Factory-Installed Options .........12
• DISCONNECT SWITCH
• CONVENIENCE OUTLET
• NOVAR CONTROLS
• MANUAL OUTDOOR-AIR DAMPER
• PREMIERLINK™ CONTROL
• OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2
• ECONOMI$ER IV STANDARD SENSORS
• ECONOMI$ER IV CONTROL MODES
Step 7 — Adjust Indoor-Fan Speed .................25
PRE-START-UP .....................................44
START-UP .......................................44-47
SERVICE ........................................47-49
INDEX ..............................................54
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit. Electrical shock could cause personal injury.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to horizontal configuration, remove side duct opening covers. Us­ing the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install the accessory roof curb in accordance with instructions shipped with the curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If electric or control power will be routed through the basepan, use the proper accessory kit listed in Fig. 1, available from your local distributor. Attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before the unit is set on the roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a water-tight seal. Install gasket supplied with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance.
The roof curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for the unit drain to function properly. Refer to Accessory Roof Curb Installation Instruc­tions for additional information as required.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
Catalog No. 04-53500019-01 Printed in U.S.A. Form 50TFQ-9SI Pg 1 9-05 Replaces: 50TFQ-7SI
Fig. 1 — Roof Curb Details
2
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 2 — Unit Leveling Tolerances
SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond the unit cabinet on all sides. Install a gravel apron in front of the outdoor coil air inlet to prevent grass and foliage from obstruct­ing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT — When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 — Field Fabricate Ductwork — On verti-
cal discharge units, secure all ducts to the roof curb and building structure. Do not connect ductwork to the unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accor­dance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applica­ble fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) should not exceed 0.35 in. wg with economizer, or 0.45 in. wg without economizer.
Step 3 — Install Condensate Drain Line and External Trap —
ed at the bottom and end of the unit. Unit discharge connec­tions do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.
When using the standard end drain connection, make sure the plug in the alternate bottom connection is tight before in­stalling the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed plug from the bottom connec­tion to the end connection. The center drain plug looks like a star connection, but can be removed with a sion. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect against freeze­up. If drain line is installed downstream from the external trap,
Condensate drain connections are locat-
1
/2-in. socket drive exten-
pitch the line away from the unit at
1
/4-in. per ft of run. Do not
use a pipe size smaller than the unit connection. See Fig. 4.
Step 4 — Rig and Place Unit — Inspect the unit for
transportation damage. File any claim with the transportation agency. Keep the unit upright and do not drop it. Spreader bars are not required if top crating is left on the unit. Rollers may be used to move the unit across a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5.
Lifting holes are provided in the base rails as shown in
Fig. 5 and 6. Refer to rigging instructions on the unit. POSITIONING — Maintain clearance around and above the
unit to provide proper airflow and service access. See Fig. 6.
Position the unit on the roof curb so that the following clear­ances are maintained: and base rails on each side and in front of the unit; 3 clearance between the roof curb and the outdoor fan end of the unit (see Fig. 1, section C-C).
Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air.
Although the unit is weatherproof, guard against water from higher level runoff and overhangs.
After the unit is in position, remove the polyethylene ship­ping wrapper and rigging skid.
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
Fig. 3 — Condensate Drain Pan (Side View)
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 4 — Condensate Drain Piping Details
1
/4-in. clearance between the roof curb
DRAIN PLUGHORIZONTAL
5
/16-in.
3
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail A. Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
All panels must be in place when rigging. Unit is not designed for handling by a fork truck. Damage to unit may result.
Fig. 5 — Rigging Details
50TFQ
008 940 426 77.42 1966.5 41.5 1054 42.12 1070 009 965 438 77.42 1966.5 41.5 1054 42.12 1070 012 1015 460 77.42 1966.5 41.5 1054 42.12 1070
WEIGHT A B C
Lb Kg in. mm in. mm in. mm
4
Table 1 — Physical Data
NOMINAL CAPACITY (tons) 7
UNIT SIZE 50TFQ 008 009 012
OPERATING WEIGHT (lb)
Unit 940 965 1015 Economizer
EconoMi$er IV 75 75 75
Roof Curb* 143 143 143
COMPRESSOR (Hermetic) Reciprocating Scroll
Quantity 222 Oil (oz) 45 ea 54 ea 54 ea
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1 5-14 8- 6 7-14 Circuit 2 5-13 8-13 8- 3
OUTDOOR COIL Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device
Rows...Fins/in. 1...17 2...17 2...17 Total Face Area (sq ft) 20.50 18.00 18.30
OUTDOOR FAN Propeller Type
Nominal Cfm 6500 6500 6500 Quantity...Diameter (in.) 2...22 2...22 2...22 Motor Hp...Rpm Watts Input (Total) 500 500 500
INDOOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device
Rows...Fins/in. 3...15 3...15 3...15 Total Face Area (sq ft) 8.0 8.0 11.1
INDOOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15
Typ e Drive Std Belt Belt Belt
Nominal Cfm 3000 3600 4000 Maximum Continuous Bhp Std 2.40 2.40 2.40
Motor Frame Size Std 56 56 56
Nominal Rpm Std ———
Fan Rpm Range Std 590- 840 685- 935 685- 935
Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 7.0
Belt, Quantity...Type...Length (in.) Std 1...A...53 1...A...48 1...A...49
Pulley Center Line Distance (in.) Std 16.75-19.25 16.75-19.25 15.85-17.50
Speed Change per Full Turn of
Moveable Pulley Flange (rpm)
Moveable Pulley Maximum Full Turns
From Closed Position
Factory Setting Std 555
Factory Speed Setting (rpm) Std 590 685 685
Fan Shaft Diameter at Pulley (in.) 111
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief (Differential) 450 ± 50 Cutout 428 Reset (Auto.) 320
LOSS-OF-CHARGE (LOW-PRESSURE) SWITCH (psig)
Cutout 7±3 Reset (Auto.) 22 ± 5
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
Alt 1...15 x 15 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 1...15 x 15
Alt Belt Belt High-Static Belt Belt Belt
Alt 2.40 2.90 High-Static 3.70 3.70 5.25
Alt 56 56 High-Static 56 56 56
Alt ——— High-Static 1725 1725 1725
Alt 685- 935 835-1085 High-Static 860-1080 860-1080 830-1130
Alt 2.8/3.8 3.4/4.4 High-Static 4.0/5.0 4.0/5.0 2.8/3.8
Alt High-Static
Alt 7.0 7.0 High-Static 8.0 8.0 5.8
Alt 1...A...49 1...A...51 High-Static 1...A...65 1...A...53 1...BX...48
Alt 16.75-19.25 15.85-17.50 High-Static 16.75-19.25 16.75-19.25 15.85-17.50 Std 50 50 50 Alt 50 50 High-Static 60 60 60 Std 555 Alt 5—5 High-Static 556
Alt 5—5 High-Static 555
Alt 685 835 High-Static 860 880 887
OUTDOOR-AIR INLET SCREENS Cleanable.
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 4...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower
1
1
/4...1100
5
/
5
/
7
/
/
2
8 8 8
81/
1
/4...1100
5
/
7
/
2
8
8
Screen quantity and size vary based on options selected.
*Weightof14-in.roofcurb.
10
1
/4...1100
5
/
7
/
7
/
8 8 8
5
Fig. 6 — Base Unit Dimensions
6
Step 5 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute)/ NFPA (National Fire Protection Association) 70 latest year and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
FIELD POWER SUPPLY — All units except 208/230-v units are factory-wired for the voltage shown on the unit name­plate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v transformer and connecting it to the 208-v1/4-in. male spade terminal from the transformer.
Refer to the unit label diagram for additional information. Pigtails are provided for field wire connections. Use factory­supplied splices or a UL (Underwriters’ Laboratories) approved copper/aluminum connector.
1
/4-in. male spade terminal on the
When installing units, provide a disconnect per the NEC.
All field wiring must comply with the NEC and local re­quirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.
Install field wiring as follows:
1. Install conduit through the side panel openings. For units without electric heat, install conduit between the discon­nect and control box.
2. Install power lines to terminal connections as shown in Fig. 7.
3. For units with electric heat, refer to Table 2 and Accessory Installation Instructions.
During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 3A and 3B). On 3-phase units, voltages between phases must be bal­anced within 2%, and the current within 10%. Use the formula shown in Tables 3A and 3B, Note 2 on page 11 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such opera­tion would invalidate any applicable Carrier warranty.
208/230-3-60
460-3-60
LEGEND
C—Contactor COMP — Compressor IFC Indoor-Fan Contactor NEC National Electrical Code TB Terminal Block
Field Wiring Factory Wiring Splice Connection (Factory-Supplied)
Fig. 7 — Power Wiring Connections
7
575-3-60
Table 2 — Electric Heating Capacities
50TFQ
UNIT SIZE
008, 009
012
*Two heater packages required to provide kW indicated.
†Use CRSINGLE008A00 for units with an electrical convenience outlet.
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240) kW new = 12.8 kW (rating at 215 v)
UNIT VOLTAGE
(60 Hz)
208/230/240
(3 phase)
460/480
(3 phase)
575
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
575
(3 phase)
2
ACCESSORY
kW
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
17.0
34.0
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
45.9/50.0*
17.0
34.0
51.0*
ELECTRIC HEATER
PART NUMBER
CRHEATER---A00
017 010 011 012
012 and 017
016 013 014 015
014 and 016
018 019
017 010
012 012 and 017 010 and 012
013
014
015 014 and 016 013 and 015
018
019 018 and 019
2
SINGLE POINT BOX
PAC KA GE N O.
CRSINGLE---A00
007 007 009 009 013
006 006 008 008 010
006 006†
012 012 015 017 017
011 014 014 016 016
011 014 016
Table 3A — Electrical Data (Units Without Electrical Convenience Outlet)
VOLTAGE
50TFQ
UNIT SIZE
008
1
(7
/2Ton s)
NOTE: Legend and Notes for Electrical Data are on page 11.
NOMINAL
V-P H-Hz
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
STD 187 254 13.4 91.0 1.4 5.8
HIGH-STATIC 187 254 13.4 91.0 1.4 10.6
STD 414 508 6.7 42.0 0.7 2.6
HIGH-STATIC 414 508 6.7 42.0 0.7 4.8
STD
HIGH-STATIC 4.8
RANGE
Min Max RLA LRA
518 632 5.4 39.0 0.7
COMPRESSOR
(each)
OFM
FLA
ELECTRIC HEAT* POWER SUPPLY
IFM
FLA
Nominal
kW**
38.8/ 38.8 40/ 40†† 41/ 41 229/229
7.8/10.4 21.7/ 25.0 65.9/ 70.0 70/ 70 66/ 69 251/254
12.0/16.0 33.3/ 38.5 80.4/ 86.9 90/ 90 79/ 85 262/268***
18.6/24.8 51.6/ 59.7 103.3/113.4 110/125 100/109 281/289***
24.0/32.0 66.6/ 77.0 122.0/135.0 125/150 117/129 296/306***
31.8/42.4 88.3/102.0 149.1/166.3 150/175 142/158 317/331*** — 43.6/ 43.6 45/ 45†† 46/ 46 273/273
7.8/10.4 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 294/298
12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 306/311***
18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 324/332***
24.0/32.0 66.6/ 77.0 126.8/139.8 150/150 123/135 339/350***
31.8/42.4 88.3/102.0 153.9/171.1 175/175 148/164 361/375*** — 19.1 20†† 20 108
13.9 16.7 40.0 40†† 39 124
16.5 19.8 43.8 45†† 43 128
27.8 33.4 60.8 70 58 141
33.0 39.7 68.7 70 66 147
41.7 50.2 81.8 90 78 158 — 21.3 25†† 23 130
13.9 16.7 42.2 45†† 42 146
16.5 19.8 46.0 50†† 45 149
27.8 33.4 63.0 70 61 163
33.0 39.7 70.9 80 68 169
41.7 50.2 84.0 90 80 180*** — 15.4 20†† 16 97
2.6
17.0 17.1 36.7 40†† 36 114
34.0 34.1 58.0 60†† 55 131 — 17.1 20†† 18 114
17.0 17.1 38.5 40†† 38 132
34.0 34.1 59.7 60†† 57 149
FLA MCA MOCP FLA LRA
DISCONNECT
SIZE†
8
Table 3A — Electrical Data (Units Without Electrical Convenience Outlet) (cont)
VO LTAGE
50TFQ
UNIT SIZE
009
(81/2Ton s)
012
(10 Tons)
NOTE: Legend and Notes for Electrical Data are on page 11.
NOMINAL
V-P H- Hz
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
STD 187 254 16.0 137.0 1.4 5.8
HIGH-STATIC 187 254 16.0 137.0 1.4 10.6
STD 414 508 8.3 69.0 0.7 2.6
HIGH-STATIC 414 508 8.3 69.0 0.7 4.8
STD
HIGH-STATIC 4.8
STD 187 254 17.2 124.0 1.4 5.8
ALT 187 254 17.2 124.0 1.4 7.5
HIGH-STATIC 187 254 17.2 124.0 1.4 15.0
STD 414 508 8.6 59.6 0.7 2.6
ALT 414 508 8.6 59.6 0.7 3.4
HIGH-STATIC 414 508 8.6 59.6 0.7 7.4
STD 518 632 6.9 49.4 0.7 2.6
ALT 518 632 6.9 49.4 0.7 3.4
HIGH-STATIC 518 632 6.9 49.4 0.7 7.4
RANGE
Min Max RLA LRA
518 632 6.4 58.0 0.7
COMPRESSOR
(each)
OFM
FLA
ELECTRIC HEAT* POWER SUPPLY
IFM
FLA
Nominal
kW**
44.6/ 44.6 45/ 45†† 47/ 47 321/321
7.8/10.4 21.7/ 25.0 71.7/ 75.9 80/ 80 72/ 75 343/346
12.0/16.0 33.3/ 38.5 86.2/ 92.7 90/100 85/ 91 354/360***
18.6/24.8 51.6/ 59.7 109.1/119.2 110/125 106/115 373/381***
24.0/32.0 66.6/ 77.0 127.9/140.9 150/150 123/135 388/398***
31.8/42.4 88.3/102.0 155.0/172.1 175/175 148/164 409/428*** — 49.4/ 49.4 50/ 50†† 52/ 52 365/365
7.8/10.4 21.7/ 25.0 76.5/ 80.7 80/ 90 77/ 81 386/390***
12.0/16.0 33.3/ 38.5 91.0/ 97.5 100/100 91/ 96 398/403***
18.6/24.8 51.6/ 59.7 113.9/124.0 125/125 112/121 416/424***
24.0/32.0 66.6/ 77.0 132.7/145.7 150/150 129/141 431/442***
31.8/42.4 88.3/102.0 159.8/176.9 175/200 154/170 453/467*** — 22.7 25†† 24 162
13.9 16.7 43.6 45†† 43 178
16.5 19.8 47.4 50†† 46 182
27.8 33.4 64.4 70 62 195
33.0 39.7 72.3 80 69 201
41.7 50.2 85.4 90 81 212*** — 24.9 25†† 26 184
13.9 16.7 45.8 50†† 45 200
16.5 19.8 49.6 50†† 49 203
27.8 33.4 66.6 70 65 217
33.0 39.7 74.5 80 72 223
41.7 50.2 87.6 90 84 234*** — 17.6 20†† 18 135
2.6
17.0 17.1 39.0 40†† 38 152
34.0 34.1 60.2 70†† 58 169 — 19.4 20†† 20 152
17.0 17.1 40.7 45†† 40 170
34.0 34.1 62.0 70 60 187 — 47.3/ 47.3 50/ 50†† 49/ 49 295/295
7.8/10.4 21.7/ 25.0 74.4/ 78.6 80/ 80 74/ 78 317/320
12.0/16.0 33.3/ 38.5 88.9/ 95.4 90/100 88/ 94 328/334***
24.0/32.0 66.6/ 77.0 130.6/143.6 150/150 126/138 362/372***
31.8/42.4 88.3/102.0 157.7/174.8 175/175 151/167 383/397***
37.6/50.0 104.4/120.3 177.8/167.6 200/175 170/188 399/415*** — 49.0/ 49.0 50/ 50†† 51/ 51 314/314
7.8/10.4 21.7/ 25.0 76.1/ 80.8 80/ 90 76/ 80 336/389***
12.0/16.0 33.3/ 38.5 90.6/ 97.1 100/100 90/ 96 347/353***
24.0/32.0 66.6/ 77.0 132.3/145.3 150/150 128/140 381/391***
31.8/42.4 88.3/102.0 159.4/176.5 175/200 153/169 402/416***
37.6/50.0 104.4/120.3 179.5/169.3 200/200 171/190 418/434*** — 56.5/ 56.5 60/ 60†† 60/ 60 362/362
7.8/10.4 21.7/ 25.0 83.6/ 87.8 90/ 90 85/ 89 384/387***
12.0/16.0 33.3/ 38.5 98.1/104.6 100/110 98/104 395/401***
24.0/32.0 66.6/ 77.0 139.8/152.8 150/175 137/149 429/439***
31.8/42.4 88.3/102.0 166.9/184.0 175/200 162/177 450/464***
37.6/50.0 104.4/120.3 187.0/176.8 200/200 180/198 466/482*** — 23.4 25†† 24 143
16.5 19.8 48.1 50†† 47 163
27.8 33.4 65.1 70 63 176
33.0 39.7 73.0 80 70 183
41.7 50.2 86.1 90 82 193***
50.0 60.1 83.5 90 93 203*** — 24.2 25†† 25 182
16.5 19.8 48.9 50†† 48 202
27.8 33.4 65.9 70 64 216
33.0 39.7 73.8 80 71 222
41.7 50.2 86.9 90 83 233***
50.0 60.1 84.3 90 94 243*** — 28.2 30†† 30 176
16.5 19.8 52.9 60†† 53 196
27.8 33.4 69.9 70 68 210
33.0 39.7 77.8 80 76 216
41.7 50.2 90.9 100 88 227***
50.0 60.1 88.3 100 99 237*** — 18.7 20†† 20 118
17.0 17.1 40.1 45†† 39 135
34.0 34.1 61.4 70 59 152
51.0 51.2 69.9 70 78 169 — 19.4 20†† 20 149
17.0 17.1 40.7 45†† 40 166
34.0 34.1 62.0 70 60 183
51.0 51.2 70.6 80 79 201*** — 22.6 25†† 24 145
17.0 17.1 43.9 45†† 44 162
34.0 34.1 65.2 70 63 179
51.0 51.2 73.8 80 83 196***
FLA MCA MOCP FLA LRA
DISCONNECT
SIZE†
9
Table 3B — Electrical Data (Units With Electrical Convenience Outlet)
VOLTAGE
50TFQ
UNIT SIZE
008
1
/2Ton s)
(7
009
1
(8
/2Ton s)
NOTE: Legend and Notes for Electrical Data are on page 11.
NOMINAL
V-P H- Hz
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
STD 187 254 13.4 91.0 1.4 5.8
HIGH-STATIC 187 254 13.4 91.0 1.4 10.6
STD 414 508 6.7 42.0 0.7 2.6
HIGH-STATIC 414 508 6.7 42.0 0.7 4.8
STD 518 632 5.4 39.0 0.7 2.6
HIGH-STATIC 518 632 5.4 39.0 0.7 4.8
STD 187 254 16.0 137.0 1.4 5.8
HIGH-STATIC 187 254 16.0 137.0 1.4 10.6
STD 414 508 8.3 69.0 0.7 2.6
HIGH-STATIC 414 508 8.3 69.0 0.7 4.8
STD 518 632 6.4 58.0 0.7 2.6
HIGH-STATIC 518 632 6.4 58.0 0.7 4.8
RANGE
Min Max RLA LRA
COMPRESSOR
(each)
OFM
FLA
ELECTRIC
IFM
FLA
HEAT*
Nominal
kW**
43.6/ 43.6 45/ 45†† 46/ 46 234/234
7.8/10.4 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 256/259
12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 267/272***
18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 285/294***
24.0/32.0 66.6/ 77.0 126.8/139.8 150/150 123/135 300/311***
31.8/42.4 88.3/102.0 153.9/171.1 175/175 148/164 322/336*** — 48.4/ 48.4 50/ 50†† 52/ 52 277/277
7.8/10.4 21.7/ 25.0 75.5/ 79.6 80/ 80 77/ 81 299/302***
12.0/16.0 33.3/ 38.5 90.0/ 96.5 90/100 90/ 96 311/316***
18.6/24.8 51.6/ 59.7 112.9/123.0 125/125 111/120 329/337***
24.0/32.0 66.6/ 77.0 131.6/144.6 150/150 128/140 344/354***
31.8/42.4 88.3/102.0 158.7/175.9 175/200 153/169 366/379*** — 21.3 25†† 23 110
13.9 16.7 42.1 45†† 42 127
16.5 19.8 46.0 50†† 45 130
27.8 33.4 63.0 70 61 143
33.0 39.7 70.9 80 68 150
41.7 50.2 84.0 90 80 160*** — 23.5 25†† 25 132
13.9 16.7 44.3 45†† 44 148
16.5 19.8 48.2 50†† 48 151
27.8 33.4 65.2 70 63 165
33.0 39.7 73.1 80 71 171
41.7 50.2 86.2 90 83 182*** — 17.1 20†† 18 99
17.0 17.1 38.5 40†† 38 116
34.0 34.1 59.7 60†† 57 133 — 18.9 20†† 20 116
17.0 17.1 40.2 45†† 40 133
34.0 34.1 61.5 70 59 150 — 49.4/ 49.4 50/ 50†† 52/ 52 326/326
7.8/10.4 21.7/ 25.0 76.5/ 80.7 80/ 90 77/ 81 348/351
12.0/16.0 33.3/ 38.5 91.0/ 97.5 100/100 91/ 96 359/364
18.6/24.8 51.6/ 59.7 113.9/124.0 125/125 112/121 377/386
24.0/32.0 66.6/ 77.0 132.7/145.7 150/150 129/141 392/403
31.8/42.4 88.3/102.0 154.8/176.9 175/200 154/170 414/428 — 54.2/ 54.2 60/ 60†† 58/ 58 369/369
7.8/10.4 21.7/ 25.0 81.3/ 85.5 90/ 90 83/ 86 391/394***
12.0/16.0 33.3/ 38.5 95.8/102.3 100/110 96/102 403/408***
18.6/24.8 51.6/ 59.7 118.7/128.8 125/150 117/126 421/429***
24.0/32.0 66.6/ 77.0 137.5/150.5 150/175 134/146 436/446***
31.8/42.4 88.3/102.0 164.6/181.7 175/200 159/175 458/471*** — 24.9 25†† 26 164
13.9 16.7 45.7 50†† 45 181
16.5 19.8 49.6 50†† 49 184
27.8 33.4 66.6 70 65 197
33.0 39.7 74.5 80 72 204
41.7 50.2 87.6 90 84 214*** — 27.1 30†† 29 186
13.9 16.7 47.9 50†† 48 202
16.5 19.8 51.8 60†† 51 205
27.8 33.4 68.8 70 67 219
33.0 39.7 76.7 80 74 225
41.7 50.2 89.8 90 86 236*** — 19.3 20†† 20 137
17.0 17.1 40.7 45†† 40 154
34.0 34.1 62.0 70 60 171 — 21.1 25†† 22 154
17.0 17.1 42.5 45†† 42 171
34.0 34.1 63.7 70 62 188
FLA MCA MOCP FLA LRA
POWER SUPPLY
DISCONNECT
SIZE†
10
50TFQ
UNIT SIZE
012
(10 Tons)
NOMINAL
V-P H-Hz
208/230-3-60
460-3-60
575-3-60
Table 3B — Electrical Data (Units With Electrical Convenience Outlet) (cont)
VO LTAGE
IFM
TYPE
STD 187 254 17.2 124.0 1.4 5.8
ALT 187 254 17.2 124.0 1.4 7.5
HIGH-STATIC 187 254 17.2 124.0 1.4 15.0
STD 414 508 8.6 59.6 0.7 2.6
ALT 414 508 8.6 59.6 0.7 3.4
HIGH-STATIC 414 508 8.6 59.6 0.7 7.4
STD 518 632 6.9 49.4 0.7 2.6
ALT 518 632 6.9 49.4 0.7 3.4
HIGH-STATIC 518 632 6.9 49.4 0.7 7.4
RANGE
Min Max RLA LRA
COMPRESSOR
(each)
OFM
FLA
ELECTRIC
IFM
FLA
HEAT*
Nominal
kW**
52.1/ 52.1 60/ 60†† 55/ 55 300/300
7.8/10.4 21.7/ 25.0 79.2/ 83.4 80/ 90 80/ 84 322/325***
12.0/16.0 33.3/ 38.5 93.7/100.2 100/110 93/ 99 333/338***
24.0/32.0 66.6/ 77.0 135.4/148.4 150/150 132/144 366/377***
31.8/42.4 88.3/102.0 162.5/179.6 175/200 157/172 388/402***
37.6/50.0 104.4/120.3 182.6/172.4 200/200 175/193 404/420*** — 53.8/ 53.8 60/ 60†† 57/ 57 319/319
7.8/10.4 21.7/ 25.0 80.9/ 85.1 90/ 90 82/ 86 341/344***
12.0/16.0 33.3/ 38.5 95.4/101.9 100/110 95/101 352/357***
24.0/32.0 66.6/ 77.0 137.1/150.1 150/175 134/145 385/396***
31.8/42.4 88.3/102.0 164.2/181.3 175/200 158/174 407/421***
37.6/50.0 104.4/120.3 184.3/174.1 200/200 177/195 423/439*** — 61.3/ 61.3 70/ 70 66/ 66 367/367
7.8/10.4 21.7/ 25.0 88.4/ 92.6 90/100 91/ 94 389/392***
12.0/16.0 33.3/ 38.5 102.9/109.4 110/110 104/110 400/405***
24.0/32.0 66.6/ 77.0 144.6/157.6 150/175 142/154 433/444***
31.8/42.4 88.3/102.0 171.7/188.8 175/200 167/183 455/459***
37.6/50.0 104.4/120.3 191.8/181.6 200/200 186/204 471/487*** — 25.5 30†† 27 145
16.5 19.8 50.3 60†† 50 165
27.8 33.4 67.3 70 65 178
33.0 39.7 75.2 80 73 185
41.7 50.2 88.3 90 85 195***
50.0 60.1 85.6 90 96 205*** — 26.3 30†† 28 185
16.5 19.8 51.1 60†† 51 204
27.8 33.4 68.1 70 66 218
33.0 39.7 76.0 80 73 224
41.7 50.2 89.1 90 86 235***
50.0 60.1 86.4 90 97 245*** — 30.3 35†† 32 179
16.5 19.8 55.1 60†† 55 198
27.8 33.4 72.1 80 71 212
33.0 39.7 80.0 80 78 218
41.7 50.2 93.1 100 90 229***
50.0 60.1 90.4 100 102 239*** — 20.5 25†† 22 120
17.0 17.1 41.8 45†† 41 137
34.0 34.1 63.1 70 61 154
51.0 51.2 71.7 80 80 171*** — 21.1 25†† 22 151
17.0 17.1 42.5 45†† 42 168
34.0 34.1 63.7 70 62 185
51.0 51.2 72.3 80 81 202*** — 24.3 25†† 26 146
17.0 17.1 45.7 50†† 46 163
34.0 34.1 66.9 70 65 180
51.0 51.2 75.5 80 85 198***
FLA MCA MOCP FLA LRA
POWER SUPPLY
DISCONNECT
SIZE†
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps
*Heaters are field installed only.
†Used to determine minimum disconnect size per NEC.
**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If
power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
††Fuse or HACR circuit breaker.
***Optional disconnect swi tch is unavailable.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
LEGEND
%Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB)457–452=5v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum devia tion is 7 v.
Determine percent of voltage imbalance.
%Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
=1.53%
average voltage
7
457
452 + 464 + 455
1371
=
3
= 457
3
11
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate the thermostat assembly on a solid wall in the conditioned space to sense aver­age temperature in accordance with the thermostat installation instructions.
NOTE: If using a Carrier electronic thermostat, set the thermo­stat configuration for “non-heat pump operation.” This family of products does not require an O terminal to energize the reversing valve.
Route the thermostat cable or equivalent single leads of colored wire from the subbase terminals to the low-voltage connections on the unit (shown in Fig. 8A and 8B) as described in Steps 1 through 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
1. If the unit is mounted on the roof curb and the accessory thru-the-curb service plate connection is used, route wire through the connection plate.
2. Pass control wires through the hole provided on the unit (see connection D in Connection Sizes table in Fig. 6).
3. Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the UL required clear­ance between the high-voltage and low-voltage wiring.
4. Connect the thermostat wires to the screw terminals of the low-voltage connector (see Fig. 8A and 8B).
NOTE: If the unit is mounted on a roof curb and electrical power will be run up “thru-the-bottom,” use accessory kit number CRBTMPWR002A01. This kit, available from your local distributor, ensures a watertight seal. Refer to the acces­sory installation instructions for information on power wiring. Refer to Fig. 6 for drilling holes in basepan.
DEFROST BOARD — The defrost board timer cycle is set to 30 minutes. To change the cycle time, turn off power to the unit and install lockout tag. Remove the wire from defrost board connected to the 30 minute quick-connect. See Fig. 10. Connect the wire to the 50 or 90 minute quick-connects on the defrost board, depending on the desired defrost time.
HEAT ANTICIPATOR SETTINGS — For units with electric heat, set heat anticipator settings as shown in Table 4.
Step 6 — Adjust Factory-Installed Options
DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch can be locked in place for safety purposes.
CONTROL
CONNECTION
BOARD
24 VAC
R
RMTOCC
G
CMPSAFE
Y2
FSD
W1
SFS
NOT USED
C
C
X
X
Fig. 8B — Low Voltage Connections
(Units with PremierLink™ Controls)
THERMOSTAT CONTROL
CONNECTION
BOARD
R
Y1
Y2
W1
W2
G
C
R
Y1
Y2
W1
W2
G
C
X
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS ON
OFF
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
A
B
Field Wiring
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
C
LEGEND
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
Fig. 8A — Low-Voltage Connections With or
Without Economizer or Two-Position Damper
DISCONNECT BOARD
DISCONNECT SWITCH (OPTIONAL)
RACEWAY
COMPRESSOR NO. 2
CONVENIENCE OUTLET
HOLE IN END PANEL
COMPRESSOR NO. 1
Fig. 9 — Typical Field Control Wiring Raceway
12
Table 4 — Heat Anticipator Settings
UNIT
50TFQ
*kW is based on 240, 480, or 575 v.
Heater
kW*
10.4, 16.0 0.3 NA NA
24.8, 32.0 0.6 0.3 0.3
42.4, 50.0 0.9 0.6 0.3 41.7, 50.0 0.6 0.3 0.3 51.0 0.6 0.3 0.3
208/230 460 575
1-Stage
Configuration
2-Stage
Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2
Heater
kW*
13.9, 16.5
27.8, 33.0
CONVENIENCE OUTLET — An optional convenience out­let provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit dis­connect is off. Adjacent unit outlets may be used for service tools. An optional “Hot Outlet” is available from the factory as a special order item.
NOVAR CONTROLS — Optional Novar controls (ETM 3051) are available for replacement or new construction jobs.
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit (for shipping).
Assembly:
1. Determine the amount of ventilation required for build­ing. Record the amount for use in Step 8.
2. Remove the filter access panel by raising the panel and swinging it outward. The panel is now disengaged from the track and can be removed. No tools are required to re­move the filter access panel. Remove the outdoor-air opening panel. Save the panels and screws. See Fig. 11.
3. Separate the hood and screen from the basepan by remov­ing the screws and brackets securing them. Save all screws and discard the brackets.
4. Replace the outdoor air opening panel.
5. Place the hood on the front of the outdoor air opening panel. See Fig. 12 for hood details. Secure the top of the hood with the 6 screws removed in Step 3. See Fig. 13.
6. Remove and save the 8 screws (4 on each side) from the sides of the manual outdoor-air damper.
7. Align the screw holes on the hood with the screw holes on the side of the manual outdoor-air damper. See Fig. 12 and 13. Secure the hood with the 8 screws from Step 6.
8. Adjust the minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 11. Slide the blade vertically until it is in the appropriate position determined by Fig. 14. Tighten the screws.
9. Remove and save the screws currently on the sides of hood. Insert the screen. Secure the screen to the hood using the screws. See Fig. 13.
10. Replace the filter access panel. Ensure that the filter access panel slides along the tracks and is securely engaged.
UNIT VOLTAGE
Configuration
1-Stage
0.3 NA NA 17.0, 34.0 0.3 NA NA
2-Stage
Heater
kW*
1-Stage
Configuration
2-Stage
Fig. 10 — Defrost Board
FILTER ACCESS PANEL
OUTDOOR AIR OPENING PANEL
SCREWS (SIDE)
MANUAL OUTDOOR-AIR ADJUSTMENT SCREWS
DAMPER BLADE
Fig. 11 — Damper Panel with Manual
Outdoor-Air Damper Installed
13
Fig. 12 — Outdoor-Air Hood Details
SCREW HOLES (TOP)
HOOD
HOOD SCREEN LOCATION (SCREEN NOT SHOWN)
Fig. 13 — Optional Manual Outdoor-Air
Damper with Hood Attached
PREMIERLINK™ CONTROL — The PremierLink control­ler is compatible with Carrier Comfort Network® (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Carrier’s diag­nostic standard tier display tools such as Navigator™ module or Scrolling Marquee can be used with the PremierLink controller.
The PremierLink controller (see Fig. 15A and 15B) requires a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). Re­fer to Fig. 16. The PremierLink control may be mounted in the control panel or an area below the control panel.
NOTE: PremierLink versions 1.3 and later are shipped in Sen­sor mode. If used with a thermostat, the PremierLink control must be configured to Thermostat mode.
The PremierLink control includes a supply-air temperature sensor (SAT) and an outdoor-air temperature sensor (OAT) as standard. An indoor-air quality (CO
) sensor can be added as
2
an option. Refer to Table 5 for sensor usage. Install the Supply Air Temperature (SAT) Sensor
—When the unit is supplied with a factory-mounted PremierLink con­trol, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factory-supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening.
The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a
1
/2-in. hole in the flange or duct. Use two field­supplied, self-drilling screws to secure the sensor probe in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure that the probe tip does not come in contact with any of the unit or heat surfaces.
Outdoor Air Temperature (OAT) Sensor
— When the unit is supplied with a factory-mounted PremierLink control, the outdoor-air temperature (OAT) sensor is factory-supplied and wired.
Install the Indoor Air Quality (CO optional indoor air quality (CO
)Sensor — Mount the
2
) sensor according to manufac-
2
turer specifications.
A separate field-supplied transformer must be used to pow-
er the CO
Wire the CO
sensor.
2
sensor to the COM and IAQI terminals of J5
2
on the PremierLink controller. Refer to the PremierLink Instal­lation, Start-up, and Configuration Instructions for detailed wiring and configuration information.
Fig. 14 — Outdoor Air Damper Position Setting
14
Table 5 — PremierLink™ Sensor Usage
APPLICATION
Dry Bulb
Temperature with
PremierLink™*
(PremierLink
requires4-20mA
Actuator)
Differential Dry Bulb
Temperature with
PremierLink* (PremierLink
requires4-20mA
Actuator)
Single Enthalpy with
PremierLink* (PremierLink
requires4-20mA
Actuator)
Differential Enthalpy
with PremierLink*
(PremierLink
requires4-20mA
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and
Outdoor Air Temperature Sensor HH79NZ017 — Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO2room sensor with override. 33ZCT56CO2 — Space temperature and CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — 50HJ540569 — Opens at 67 F, closes at 52 F, not adjustable. Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor HH79NZ017) Compressor Lockout Sensor — 50HJ540570 — Opens at 35 F, closes at 50 F.
OUTDOOR AIR
TEMPERATURE SENSOR
Included —
HH79NZ017
Included —
HH79NZ017
Included —
Not Used
Included —
Not Used
room sensor with override and set point.
2
2
RETURN AIR
TEMPERATURE SENSOR
———
Required —
33ZCT55SPT
or Equivalent
room sensor.
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
——
Required —
HH57AC077
Required —
HH57AC077
Required —
HH57AC078
Fig. 15A — PremierLink Controller
15
PREMIERLINK CONTROL
HINGED DOOR PANEL
PREMIERLINK COVER
Fig. 15B — PremierLink™ Controller (Installed)
OAT
PNK
VIO
YEL
BLU
BLK
RED
BLU
YEL
WHT
7
7
6
6
11
11
10
10
8
8
2
2
3
3
4
4
1
1
5
5
9
9
12
12
TR
SR
2
OUTDOOR AIR
ENTHALPY SENSOR
Economi$er2
4 - 20mA
RED
BRN
PNK
VIO
Power Exhaust/Energy Recycler
GRA
ORN
PNK
TR1
+
3
RED
SAT
Space Temp./ Set
Point Adjustment
Quality Sensor
Quality Sensor
GRAY
GRAY
BLK
S
RETURN AIR
ENTHALPY
SENSOR
BLK
RED
Indoor Air
Outdoor Air
CMPSAFE
TB-2
1
2
3
4
5
6
7
8
BLU
BRN
BLK
BRN
RED
BRN
BLU
ORN
TB-3
RMTOCC
1
GRN
2
Com
SFS
FSD
CCN
3
4
5
6
7
m.
BLU
WHT
PNK
RED
WHT
8
+
COMMS — Communications OAT Outdoor Air Temperature Sensor PWR Power SAT Supply Air Temperature Sensor
YEL
BLK
VIO
BRN
BRN
ORN
RED
BLU
GRA
LEGEND
BLK
PNK
BRN
BRN
GRN
YEL
BLU
WHT
PNK
BLU
GRA
GRA
PNK
BLK
ANAL OG
0-20mAIN
DISCRETE
PWR
BRN
J6
J5
J4
J1
Fig. 16 — Typical PremierLink Controls Wiring
J2
COMMS
RED
BRN
J9
0-20 mA
TB-1
1
2
Y1
3
Y2
W1
4
5
W2
6
7
8
RTU Terminal
Board
HK50AA0
39
PremierLink
J7
PP/MP
WHT
GRA
R
RED
GRA
ORN
ORN
PNK
G
WHT
C
X
Relays
J8
PNK
ORNORN
ORN
RED
16
Enthalpy Sensors and Control
— The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the economizer damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink™ controller. Locate the controller in place of an existing econo­mizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.
A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Outdoor Air Enthalpy Sensor/Enthalpy Controller (HH57AC077) — To wire the outdoor air enthalpy sensor, perform the following (see Fig. 17 and 18):
NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.
1. Use a 4-conductor, 18 or 20 AWG cable to connect the enthalpy control to the PremierLink controller and power transformer.
2. Connect the following 4 wires from the wire harness located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TR1)
on enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal
(TR) on enthalpy sensor and to pin 4 on 12-pin harness.
c. Connect the GRAY/ORN wire to J4-2 on Premier-
Link controller and to terminal (3) on enthalpy sensor.
d. Connect the GRAY/RED wire to J4-1 on Premier-
Link controller and to terminal (2) on enthalpy sensor.
NOTE: If installing in a Carrier rooftop, use the two gray wires provided from the control section to the economizer to connect PremierLink controller to terminals 2 and 3 on enthalpy sensor.
If NOT using Carrier equipment, wires may need to be field
supplied and installed. Return Air Enthalpy Sensor
— Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). The outdoor enthalpy changeover set point is set at the controller.
To wire the return air enthalpy sensor, perform the follow-
ing (see Fig. 17):
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.
2. At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.
ENTHALPY CONTROLLER
B
TR TR1
C
A
D
LED
NOTES:
1. Remove factory-installed jumper across SR and + before con­necting wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in out­door airstream.
SO
SR
+
+
3
2
1
RED BRN
BLK
RED
GRAY/ORN
GRAY/RED
WIRE HARNESS IN UNIT
(OUTDOOR
S
AIR
+
ENTHALPY
SENSOR)
S
(RETURN AIR
ENTHALPY
+
SENSOR)
Fig. 17 — Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
HH57AC077 ENTHALPY CONTROL AND
BRACKET
HH57AC078 ENTHALPY SENSOR (USED WITH ENTHALPY CONTROL FOR DIFFERENTIAL ENTHALPY OPERATION)
MOUNTING PLATE
OUTDOOR AIR ENTHALPY SENSOR
C7400A1004
+
Fig. 18 — Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
17
OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2 — See Fig. 19 for EconoMi$er IV component locations. See Fig. 20 for EconoMi$er2 component locations.
NOTE: These instructions are for installing the optional EconoMi$er IV and EconoMi$er2 only. Refer to the accessory EconoMi$er IV or EconoMi$er2 installation instructions when field installing an EconoMi$er IV or EconoMi$er2 accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 21.
2. The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 19. The optional EconoMi$er2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controller. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 22.
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter
for use in the power exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 23.
4. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws pro­vided to attach the hood sides to the unit. See Fig. 24.
5. Remove the shipping tape holding the economizer baro­metric relief damper in place.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Fig. 21 — Typical Access Panel Locations
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
ACTUATOR
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
Fig. 19 — EconoMi$er IV Component Locations
OUTDOOR AIR HOOD
ECONOMI$ER2 PLUG
HOOD SHIPPING BRACKET
x
o
B
d
o
o
H
Fig. 22 — Hood Box Removal
HOOD BOX BRACKET
SIDE PANEL
BAROMETRIC RELIEF DAMPER
GEAR DRIVEN DAMPER
Fig. 20 — EconoMi$er2 Component Locations
18
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
Fig. 23 — Indoor Coil Access Panel Relocation
6. Insert the hood divider between the hood sides. See Fig. 24 and 25. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bot­tom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 25.
TOP PANEL
INDOOR COIL ACCESS PANEL
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 23.
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 26. EconoMi$er2 wiring is shown in Fig. 27.
Barometric flow capacity is shown in Fig. 28. Outdoor air leakage is shown in Fig. 29. Return air pressure drop is shown in Fig. 30.
22 1/4
LEFT HOOD SIDE
B
24 9/16
HOOD DIVIDER
SCREW
40 3/8
Fig. 24 — Outdoor-Air Hood Construction
BAROMETRIC RELIEF
FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK
DIVIDER
OUTSIDE AIR
CLEANABLE ALUMINUM FILTER
FILTER
Fig. 25 — Filter Installation
HOOD
FILTER CLIP
LEGEND
DCV— Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT— Potentiometer RAT— Retur n-Air Temperature
Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Fig. 26 — EconoMi$er IV Wiring
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT. to the minimum position.
19
BLACK
4
3
5
NOTE 1
NOTE 3
RUN
500 OHM RESISTOR
BLUE
VIOLET
PINK
-
RED
2
8
6
7
1
+
50HJ540573
ACTUATOR ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dr y bulb sensor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
OPTIONAL CO
SENSOR4-20mA
OUTPUT
2
YELLOW
WHITE
10
11
9
12
ECONOMISER2 PLUG
Fig. 27 — EconoMi$er2 with 4 to 20 mA Control Wiring
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
Fig. 28 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.20 0.22 0.25 0. 30 0. 35 0.40 0 .45 0 .50
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 29 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0. 15 0. 20 0.25 0.30 0.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 30 — Return-Air Pressure Drop
20
ECONOMI$ER IV STANDARD SENSORS Outdoor Air Temperature (OAT) Sensor
— The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. See Fig. 19. The op­erating range of temperature measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor
— The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. See Fig. 31. This sensor is factory installed. The op­erating range of temperature measurement is 0° to 158 F. See Table 6 for sensor temperature/resistance values.
The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Table 6 — Supply Air Sensor Temperature/
Resistance Values
TEMPERATURE (F) RESISTANCE (ohms)
–58 200,250 –40 100,680 –22 53,010
–4 29,091 14 16,590 32 9,795 50 5,970 68 3,747 77 3,000
86 2,416 104 1,597 122 1,080 140 746 158 525 176 376 185 321 194 274 212 203 230 153 248 116 257 102 266 89 284 70 302 55
Table 7 — EconoMi$er IV Sensor Usage
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy HH57AC078
Differential
Enthalpy
for DCV
CO
2
Control using a
Wall-Mounted
CO
Sensor
2
CO
for DCV
2
Control using a
Duct-Mounted
Sensor
CO
2
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are
used on many different base units. As such, these kits may con­tain parts that will not be needed for installation.
†33ZCSENCO2 is an accessory CO
**33ZCASPCO2 is an accessory aspirator box required for duct-
mounted applications.
††CRCBDIOX005A00 is an accessory that contains both
33ZCSENCO2 and 33ZCASPCO2 accessories.
ECONOMI$ER IV WITH OUTDOOR AIR
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
HH57AC078
CRENTDIF004A00*
33ZCSENCO2
and
sensor.
2
and
CRCBDIOX005A00††
OR
Outdoor Dry Bulb Changeover — The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor air dampers to minimum position. If the outdoor-air temperature is below the set point, the position of the outdoor air dampers will be controlled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potenti­ometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the control. See Fig. 32. The scale on the potentiometer is A, B, C, and D. See Fig. 33 for the corresponding temperature changeover values.
Outdoor Air Lockout Sensor
— The Economi$er IV is equipped with an ambient temperature lockout switch located in the outdoor air stream which is used to lockout the compres­sors below a 42 F ambient temperature. See Fig. 19.
ECONOMI$ER IV CONTROL MODES
IMPORTANT: The optional EconoMi$er2 does not include a controller. The EconoMi$er2 is operated by a 4 to 20 mA signal from an existing field-supplied controller (such as PremierLink™ control). See Fig. 27 for wiring information.
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sen­sors. Refer to Table 7. The EconoMi$er IV is supplied from the factory with a supply air temperature sensor and an outdoor air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.
21
SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
Fig. 31 — Supply Air Sensor Location
Fig. 32 — EconoMi$er IV Controller Potentiometer
and LED Locations
19
LED ON
mA
18
17
16
15
14
13
12
11
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
C
LED OFF
65
70
LED ON
LED OFF
75
B
LED ON
A
LED OFF
100
90
95
85
80
Fig. 33 — Outside Air Temperature
Changeover Set Points
Differential Enthalpy Control
— For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sen­sors (HH57AC078 and CRENTDIF004A00), one in the out­side air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sen­sor with the accessory enthalpy sensor in the same mounting location. See Fig. 19. Mount the return air enthalpy sensor in the return air duct. See Fig. 34. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 26. The outdoor en­thalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy set­point potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
— The IAQ input can be used for demand control ventilation control based on the level of CO
measured in the space or return air duct.
2
Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiome­ters to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 37.
If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.
ECONOMI$ER IV CONTROLLER
ECONOMI$ER IV
Differential Dry Bulb Control
— For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunc­tion with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig. 34. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 26.
In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower tempera­ture airstream is used for cooling. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 32.
Outdoor Enthalpy Changeover
— For enthalpy control, ac­cessory enthalpy sensor (part number HH57AC078) is re­quired. Replace the standard outdoor dry bulb temperature sen­sor with the accessory enthalpy sensor in the same mounting location. See Fig. 19. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor­air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 35. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 19 and 36.
GROMMET
RETURN AIR SENSOR
RETURN DUCT (FIELD-PROVIDED)
Fig. 34 — Return Air Temperature or Enthalpy
Sensor Mounting Location
22
CONTROL
CURVE
4
1
2
1
A B C D
6
1
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
NT
E
2
2
2
0
2
8
1
35 (2)
HA
4
85
(29)90(32)95(35)
46
4
4
42
40
IR
8
3
Y A
6
DR
3
D
N
U
4
3
PO
R
32
E
P
TU
30
B
Y
28
P
L
26
60
(16)
55
(13)
B
50
C
(10)
45
D
(7)
40
(4)
70
(21)
0
0
1
65
(18)
A
80
(27)
75
(24)
0
9
80
70
0
6
50
0
4
100
105
(38)
IT
ID
M
U
H
VE
I
T
A
L
E
R
0
3
20
110
(41)
(43)
)
%
(
Y
0
1
N1
P1
T1
AQ1
SO+
SR+
A
B
C
D
35
40
45
50
55
60
65
70
75
80
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
85
(27)
(29)90(32)95(35)
100 (38)
105
(41)
110 (43)
HIGH LIMIT CURVE
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 35 — Enthalpy Changeover Set Points
CO SENSOR MAX RANGE SETTING
EXH
2V 10V
EXH
2V 10V
DCV
2V 10V
Free Cool
B
A
Open
Min Pos
DCV
Max
DCV
C
D
Set
Set
N
P
T
AQ
SO
SR
TR1
TR
24
24 Vac
Vac
COM
HOT
_
+
12
5
4
3
EF1
EF
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 37 — CO
2
800 ppm 900 ppm 1000 ppm 1100 ppm
2345678
Sensor Maximum Range Setting
2
Fig. 36 — EconoMi$er IV Control
23
Exhaust Set Point Adjustment
— The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modi­fied with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 32. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the damp­ers to open. This delay allows the damper to reach the appro­priate position to avoid unnecessary fan overload.
Minimum Position Control
— There is a minimum damper position potentiometer on the EconoMi$er IV controller. See Fig. 32. The minimum damper position maintains the mini­mum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper po­sition represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occu­pied ventilation.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the oc­cupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F temperature difference between the outdoor and return-air temperatures.
To determine the minimum position setting, perform the following procedure:
1. Calculate the appropriate mixed air temperature using the following formula:
OA
(T
x
O
= Outdoor-Air Temperature
T
O
)+(TRxRA)=T
100 100
M
OA = Percent of Outdoor Air T
= Return-Air Temperature
R
RA = Percent of Return Air T
= Mixed-Air Temperature
M
As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 26 and that the minimum position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated value.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a re­mote location.
To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiome­ter to the P and P1 terminals on the EconoMi$er IV controller. See Fig. 36.
Damper Movement full closed (or vice versa) takes 2
Thermostats
— Damper movement from full open to
1
/2minutes.
— The EconoMi$er IV control works with con­ventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal con­nection board located in the main control box.
Occupancy Control
— The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied timeclock function in place of the jumper between TR and N. See Fig. 26. When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.
Demand Controlled Ventilation (DCV)
— When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be cal­culated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occu­pancy, and equipment that cannot exceed the required ventila­tion rate at design conditions. Exceeding the required ventila­tion rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO level increases even though the CO2set point has not been reached. By the time the CO2level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer
2
damper in this manner, first determine the damper voltage out­put for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccu­pied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.
OA
(TOx
T
= Outdoor-Air Temperature
O
)+(TRx
100 100
RA
)=T
M
OA = Percent of Outdoor Air T
= Return-Air Temperature
R
RA = Percent of Return Air T
= Mixed-Air Temperature
M
Once base ventilation has been determined, set the mini­mum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an out­put of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum venti­lation rate of 20% (or base plus 15 cfm per person). Use Fig. 37 to determine the maximum setting of the CO
sensor. For ex-
2
ample, a 1100 ppm set point relates to a 15 cfm per person de­sign. Use the 1100 ppm curve on Fig. 37 to find the point when the CO
sensor output will be 6.7 volts. Line up the point on the
2
graph with the left side of the chart to determine that the range configuration for the CO
sensor should be 1800 ppm. The
2
EconoMi$er IV controller will output the 6.7 volts from the
2
24
sensor to the actuator when the CO2concentration in the
CO
2
space is at 1100 ppm. The DCV set point may be left at 2 volts since the CO
sensor voltage will be ignored by the
2
EconoMi$er IV controller until it rises above the 3.6 volt set­ting of the minimum position potentiometer.
Once the fully occupied damper position has been deter­mined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum posi­tion as this can result in over-ventilation to the space and poten­tial high-humidity levels.
CO
Sensor Configuration —TheCO2sensor has preset
2
standard voltage settings that can be selected anytime after the sensor is powered up. See Table 8.
Use setting 1 or 2 for Carrier equipment. See Table 8.
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 8 .
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed any-
2
time after the sensor is energized. Follow the steps below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired set­ting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV Control
— Infor­mation from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a 62AQ energy recovery unit is added to re­duce the moisture content of the fresh air being brought into the
building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to re­move the humidity loads for most commercial applications.
If normal rooftop heating and cooling operation is not ade­quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
Step 7 — Adjust Indoor-Fan Speed — Adjust the
indoor-fan speed to meet jobsite conditions.
For units with electric heat, required minimum cfm is 2250 for 50TFQ008, 2550 for 50TFQ009 and 3000 for 50TFQ012 with the following exceptions:
UNIT
50TFQ012
UNIT
VOLTAGE
208/230 42.4 Horizontal 3200 208/230 50.0 Horizontal 3200
460 50.0
575
HEATER
kW
17.0
51.0 2350
UNIT
CONFIG-
URATION
Horizontal or
Vertical
Horizontal or
Vertical
Table 9 shows indoor-fan motor data. Table 10 shows fan rpm at motor pulley settings for standard and alternate motors. Tables 11A and 11B show static pressure for accessories. Refer to Tables 12-27 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Table 1.
To change fan speeds:
1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting nuts. See Fig. 38 and 39.
3. Loosen the movable pulley flange setscrew (see Fig. 40).
4. Screw the movable flange toward the fixed flange to increase speed or away from the fixed flange to decrease speed. Increasing the fan speed increases the load on the motor. Do not exceed the maximum speed specified in Table 1.
5. Set the movable flange at nearest keyway of the pulley hub and tighten the setscrew. (See Table 1 for speed change for each full turn of the pulley flange.)
REQUIRED
MINIMUM
CFM
3200
2800
Table 8 — CO
SETTING EQUIPMENT OUTPUT
1
Interface w/Standard
2 Proportional Any
Building Control System
3 Exponential Any
4
5 Proportional 20
Economizer
6 Exponential 15
7 Exponential 20
8 Health & Safety Proportional
Parking/Air Intakes/
9
Loading Docks
LEGEND
ppm — Parts Per Million
Proportional Any
Proportional 15
Proportional
Sensor Standard Settings
2
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
25
CO
CONTROL RANGE
2
(ppm)
0-2000 1000 50
0-2000 1000 50
0-2000 1100 50
0-1100 1100 50
0- 900 900 50
0-1100 1100 50
0- 900 900 50
0-9999 5000 500
0-2000 700 50
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
To align the fan and motor pulleys:
1. Loosen the fan pulley setscrews.
2. Slide the fan pulley along the fan shaft.
3. Make angular alignment by loosening the motor from the mounting plate.
To adjust belt tension:
1. Loosen the fan motor mounting nuts.
2. Sizes 008 and 009 — Slide the motor mounting plate away from the fan scroll for proper belt tension ( deflection with 5 to 10 lb of force) and tighten the mount­ing nuts (see Fig. 38).
Size 012 — Slide the motor mounting plate downward to tighten belt tension (
1
/2-in. deflection with 5 to 10 lb of
force). Secure the motor mounting plate nuts. See Fig. 39.
3. Adjust the bolt and nut on the mounting plate to secure the motor in fixed position.
1
/2-in.
Fig. 39 — Typical Belt-Drive Motor Mounting for
Size 012
MOTOR MOUNTING
PLATE NUTS
Fig. 38 — Typical Belt-Drive Motor Mounting for
Size 008 and 009
Fig. 40 — Indoor-Fan Pulley Adjustment
Table 9 — Fan Motor Performance
UNIT
50TFQ
008
009
012
LEGEND BHP — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower range of the
motors can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
INDOOR-FAN
MOTOR
Standard,
Alternate
High Static
Standard
High Static
Standard
Alternate
High Static
UNIT
VOLTAGE
208/230
460 3.0 575 3.0
208/230
460 5.5 575 5.5
208/230
460 3.0 575 3.0
208/230
460 5.5 575 5.5
208/230
460 3.0 575 3.0
208/230
460 3.9 575 3.9
208/230
460 8.5 575 8.5
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
2.40 2120
3.70 3313
2.40 2120
3.70 3313
2.40 2120
2.90 2615
5.25 4400
MAXIMUM ACCEPTABLE
OP ER ATI NG WAT TS
MAXIMUM
AMP DRAW
6.0
11.7
6.0
11.7
6.0
8.6
17.3
26
Table 10 — Fan Rpm at Motor Pulley Settings*
UNIT
50TFQ
1
0
/
2
11
1
/
2
MOTOR PULLEY TURNS OPEN
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
008† 840 815 790 765 740 715 690 665 635 615 590 008** 935 910 885 860 835 810 785 760 735 710 685 008†† 1080 1025 1007 988 970 952 933 915 897 878 860 009† 935 910 885 860 835 810 785 760 735 710 685 009†† 1080 1025 1007 988 970 952 933 915 897 878 860 012† 935 910 885 860 835 810 785 760 735 710 685 012** 1085 1060 1035 1010 985 960 935 910 885 860 835 012†† 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates alternate drive package only.
††Indicates high-static motor and drive package.
Table 11A — Electric Heater Static Pressure* (in. wg) — 50TFQ008-012
COMPONENT
2250 2500 3000 3500 4000 4500 5000 5500 6000 6250 1 Heater Module 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.17 2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21 0.20
*The static pressure must be added to external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter­mine blower rpm and watts.
CFM
Table 11B — EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) — 50TFQ008-012
6
COMPONENT
2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250
CFM
Vertical EconoMi$er IV and EconoMi$er2 0.06 0.075 0.09 0.115 0.13 0.15 0.17 0.195 0.22 0.25 0.285 0.325 0.36 Horizontal EconoMi$er IV and EconoMi$er2 0.1 0.125 0.15 0.18 0.21 0.25 0.275 0.3 0.34 0.388
*The static pressure must be added to external static pressure. The sum and the outdoor
entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
27
Table 12 — Fan Performance, 50TFQ008 — Vertical Discharge Units; Standard Motor and Drive*
AIRFLOW
(Cfm)
2250 511 0.58 538 591 0.75 697 660 0.93 864 722 1.12 1041 779 1.32 1228 2300 519 0.61 567 597 0.78 729 666 0.97 900 727 1.16 1079 784 1.36 1268 2400 534 0.68 630 611 0.86 798 678 1.04 974 739 1.24 1158 794 1.45 1352 2500 550 0.75 698 624 0.93 872 690 1.13 1053 750 1.33 1243 805 1.55 1441 2550 557 0.79 733 631 0.98 910 697 1.17 1095 756 1.38 1287 811 1.60 1488 2600 565 0.83 770 638 1.02 950 703 1.22 1138 762 1.43 1333 816 1.65 1536 2700 581 0.91 848 652 1.11 1034 716 1.32 1228 774 1.53 1428 828 1.75 1636 2800 597 1.00 932 667 1.21 1124 729 1.42 1323 786 1.64 1529 839 1.87 1742 2900 613 1.09 1020 681 1.31 1220 743 1.53 1425 799 1.75 1636 851 1.99 1855 3000 629 1.20 1115 696 1.42 1321 756 1.64 1532 812 1.88 1749 863 2.12 1973 3100 646 1.30 1217 711 1.53 1428 770 1.76 1645 825 2.00 1869 875 2.25 2098 3200 662 1.42 1324 726 1.65 1542 784 1.89 1765 838 2.14 1994 888 2.39 2229 3300 679 1.54 1438 741 1.78 1663 798 2.03 1892 851 2.28 2126 —— — 3400 695 1.67 1558 756 1.92 1790 812 2.17 2025 3500 712 1.81 1686 772 2.06 1923 827 2.32 2165 3600 729 1.95 1820 787 2.21 2065 3700 746 2.10 1962 803 2.37 2213 3750 754 2.18 2036
AIRFLOW
(Cfm)
2250 831 1.53 1423 880 1.74 1627 927 1.97 1840 971 2.21 2061 —— — 2300 836 1.57 1465 885 1.79 1671 931 2.02 1886 975 2.26 2109 —— — 2400 846 1.67 1554 895 1.89 1764 941 2.13 1982 984 2.37 2209 —— — 2500 856 1.77 1647 905 2.00 1862 950 2.24 2085 —— — —— — 2550 862 1.82 1697 910 2.05 1913 955 2.29 2138 —— — —— — 2600 867 1.87 1747 915 2.11 1966 960 2.35 2193 —— — —— — 2700 878 1.99 1852 925 2.23 2076 —— — —— — —— — 2800 889 2.11 1963 936 2.35 2192 —— — —— — —— — 2900 900 2.23 2080 ———————————— 3000 912 2.36 2204 ———————————— 3100 ————— — —— — —— — —— — 3200 ————— — —— — —— — —— — 3300 ————— — —— — —— — —— — 3400 ————— — —— — —— — —— — 3500 ————— — —— — —— — —— — 3600 ————— — —— — —— — —— — 3700 ————— — —— — —— — —— — 3750 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
28
Table 13 — Fan Performance, 50TFQ008 — Vertical Discharge Units; Alternate Motor and Drive*
AIRFLOW
(Cfm)
2250 511 0.58 538 591 0.75 697 660 0.93 864 722 1.12 1041 779 1.32 1228 2300 519 0.61 567 597 0.78 729 666 0.97 900 727 1.16 1079 784 1.36 1268 2400 534 0.68 630 611 0.86 798 678 1.04 974 739 1.24 1158 794 1.45 1352 2500 550 0.75 698 624 0.93 872 690 1.13 1053 750 1.33 1243 805 1.55 1441 2550 557 0.79 733 631 0.98 910 697 1.17 1095 756 1.38 1287 811 1.60 1488 2600 565 0.83 770 638 1.02 950 703 1.22 1138 762 1.43 1333 816 1.65 1536 2700 581 0.91 848 652 1.11 1034 716 1.32 1228 774 1.53 1428 828 1.75 1636 2800 597 1.00 932 667 1.21 1124 729 1.42 1323 786 1.64 1529 839 1.87 1742 2900 613 1.09 1020 681 1.31 1220 743 1.53 1425 799 1.75 1636 851 1.99 1855 3000 629 1.20 1115 696 1.42 1321 756 1.64 1532 812 1.88 1749 863 2.12 1973 3100 646 1.30 1217 711 1.53 1428 770 1.76 1645 825 2.00 1869 875 2.25 2098 3200 662 1.42 1324 726 1.65 1542 784 1.89 1765 838 2.14 1994 888 2.39 2229 3300 679 1.54 1438 741 1.78 1663 798 2.03 1892 851 2.28 2126 3400 695 1.67 1558 756 1.92 1790 812 2.17 2025 3500 712 1.81 1686 772 2.06 1923 827 2.32 2165 3600 729 1.95 1820 787 2.21 2065 3700 746 2.10 1962 803 2.37 2213 3750 754 2.18 2036
AIRFLOW
(Cfm)
2250 831 1.53 1423 880 1.74 1627 927 1.97 1840 971 2.21 2061 —— — 2300 836 1.57 1465 885 1.79 1671 931 2.02 1886 975 2.26 2109 —— — 2400 846 1.67 1554 895 1.89 1764 941 2.13 1982 984 2.37 2209 —— — 2500 856 1.77 1647 905 2.00 1862 950 2.24 2085 —— — —— — 2550 862 1.82 1697 910 2.05 1913 955 2.29 2138 —— — —— — 2600 867 1.87 1747 915 2.11 1966 960 2.35 2193 —— — —— — 2700 878 1.99 1852 925 2.23 2076 2800 889 2.11 1963 936 2.35 2192 —— — —— — —— — 2900 900 2.23 2080 3000 912 2.36 2204 3100 ————— — —— — —— — —— — 3200 ————— — —— — —— — —— — 3300 ————— — —— — —— — —— — 3400 ————— — —— — —— — —— — 3500 ————— — —— — —— — —— — 3600 ————— — —— — —— — —— — 3700 ————— — —— — —— — —— — 3750 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
29
Table 14 — Fan Performance, 50TFQ008 — Vertical Discharge Units; High-Static Motor and Drive*
AIRFLOW
(Cfm)
2250 511 0.58 538 591 0.75 697 660 0.93 864 722 1.12 1041 779 1.32 1228 2300 519 0.61 567 597 0.78 729 666 0.97 900 727 1.16 1079 784 1.36 1268 2400 534 0.68 630 611 0.86 798 678 1.04 974 739 1.24 1158 794 1.45 1352 2500 550 0.75 698 624 0.93 872 690 1.13 1053 750 1.33 1243 805 1.55 1441 2550 557 0.79 733 631 0.98 910 697 1.17 1095 756 1.38 1287 811 1.60 1488 2600 565 0.83 770 638 1.02 950 703 1.22 1138 762 1.43 1333 816 1.65 1536 2700 581 0.91 848 652 1.11 1034 716 1.32 1228 774 1.53 1428 828 1.75 1636 2800 597 1.00 932 667 1.21 1124 729 1.42 1323 786 1.64 1529 839 1.87 1742 2900 613 1.09 1020 681 1.31 1220 743 1.53 1425 799 1.75 1636 851 1.99 1855 3000 629 1.20 1115 696 1.42 1321 756 1.64 1532 812 1.88 1749 863 2.12 1973 3100 646 1.30 1217 711 1.53 1428 770 1.76 1645 825 2.00 1869 875 2.25 2098 3200 662 1.42 1324 726 1.65 1542 784 1.89 1765 838 2.14 1994 888 2.39 2229 3300 679 1.54 1438 741 1.78 1663 798 2.03 1892 851 2.28 2126 901 2.54 2367 3400 695 1.67 1558 756 1.92 1790 812 2.17 2025 865 2.43 2266 913 2.69 2512 3500 712 1.81 1686 772 2.06 1923 827 2.32 2165 878 2.59 2412 926 2.86 2664 3600 729 1.95 1820 787 2.21 2065 841 2.48 2312 892 2.75 2565 940 3.03 2823 3700 746 2.10 1962 803 2.37 2213 856 2.65 2467 906 2.92 2726 953 3.21 2990 3750 754 2.18 2036 811 2.46 2290 864 2.73 2548 913 3.01 2809 960 3.30 3076
AIRFLOW
(Cfm)
2250 831 1.53 1423 880 1.74 1627 927 1.97 1840 971 2.21 2061 1013 2.46 2289 2300 836 1.57 1465 885 1.79 1671 931 2.02 1886 975 2.26 2109 1017 2.51 2340 2400 846 1.67 1554 895 1.89 1764 941 2.13 1982 984 2.37 2209 1026 2.62 2443 2500 856 1.77 1647 905 2.00 1862 950 2.24 2085 993 2.48 2315 1035 2.74 2553 2550 862 1.82 1697 910 2.05 1913 955 2.29 2138 998 2.54 2370 1039 2.80 2611 2600 867 1.87 1747 915 2.11 1966 960 2.35 2193 1003 2.60 2427 1044 2.86 2669 2700 878 1.99 1852 925 2.23 2076 970 2.47 2307 1012 2.73 2545 1053 2.99 2791 2800 889 2.11 1963 936 2.35 2192 980 2.60 2427 1022 2.86 2670 1063 3.13 2920 2900 900 2.23 2080 946 2.48 2314 990 2.74 2554 1032 3.00 2800 1072 3.28 3055 3000 912 2.36 2204 957 2.62 2442 1001 2.88 2687 1043 3.15 2938 1082 3.43 3196 3100 923 2.50 2334 969 2.76 2577 1012 3.03 2826 1053 3.31 3082 1093 3.59 3345 3200 935 2.65 2471 980 2.92 2718 1023 3.19 2973 1064 3.47 3233 3300 947 2.80 2613 992 3.07 2867 1034 3.35 3126 1074 3.64 3391 3400 960 2.96 2764 1003 3.24 3022 1045 3.52 3286 3500 972 3.13 2921 1015 3.42 3185 1057 3.70 3454 3600 985 3.31 3086 1028 3.60 3355 3700 997 3.49 3259 3750 1004 3.59 3347
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
30
Table 15 — Fan Performance, 50TFQ009 — Vertical Discharge Units; Standard Motor and Drive*
AIRFLOW
(Cfm)
2550 557 0.79 733 631 0.98 910 697 1.17 1095 756 1.38 1287 811 1.60 1488 2600 565 0.83 770 638 1.02 950 703 1.22 1138 762 1.43 1333 816 1.65 1536 2700 581 0.91 848 652 1.11 1034 716 1.32 1228 774 1.53 1428 828 1.75 1636 2800 597 1.00 932 667 1.21 1124 729 1.42 1323 786 1.64 1529 839 1.87 1742 2900 613 1.09 1020 681 1.31 1220 743 1.53 1425 799 1.75 1636 851 1.99 1855 3000 629 1.20 1115 696 1.42 1321 756 1.64 1532 812 1.88 1749 863 2.12 1973 3100 646 1.30 1217 711 1.53 1428 770 1.76 1645 825 2.00 1869 875 2.25 2098 3200 662 1.42 1324 726 1.65 1542 784 1.89 1765 838 2.14 1994 888 2.39 2229 3300 679 1.54 1438 741 1.78 1663 798 2.03 1892 851 2.28 2126 3400 695 1.67 1558 756 1.92 1790 812 2.17 2025 3500 712 1.81 1686 772 2.06 1923 827 2.32 2165 3600 729 1.95 1820 787 2.21 2065 3700 746 2.10 1962 803 2.37 2213 3750 754 2.18 2036 3800 763 2.26 2112 3900 —— ——— —————————— 4000 —— ——— —————————— 4100 —— ——— —————————— 4200 —— ——— —————————— 4250 —— ——— ——————————
AIRFLOW
(Cfm)
2550 862 1.82 1697 910 2.05 1913 955 2.29 2138 —— — —— — 2600 867 1.87 1747 915 2.11 1966 960 2.35 2193 —— — —— — 2700 878 1.99 1852 925 2.23 2076 2800 889 2.11 1963 936 2.35 2192 —— — —— — —— — 2900 900 2.23 2080 3000 912 2.36 2204 3100 ————— — —— — —— — —— — 3200 ————— — —— — —— — —— — 3300 ————— — —— — —— — —— — 3400 ————— — —— — —— — —— — 3500 ————— — —— — —— — —— — 3600 ————— — —— — —— — —— — 3700 ————— — —— — —— — —— — 3750 ————— — —— — —— — —— — 3800 ————— — —— — —— — —— — 3900 ————— — —— — —— — —— — 4000 ————— — —— — —— — —— — 4100 ————— — —— — —— — —— — 4200 ————— — —— — —— — —— — 4250 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
31
Table 16 — Fan Performance, 50TFQ009 — Vertical Discharge Units; High-Static Motor and Drive*
AIRFLOW
(Cfm)
2550 557 0.79 733 631 0.98 910 697 1.17 1095 756 1.38 1287 811 1.60 1488 2600 565 0.83 770 638 1.02 950 703 1.22 1138 762 1.43 1333 816 1.65 1536 2700 581 0.91 848 652 1.11 1034 716 1.32 1228 774 1.53 1428 828 1.75 1636 2800 597 1.00 932 667 1.21 1124 729 1.42 1323 786 1.64 1529 839 1.87 1742 2900 613 1.09 1020 681 1.31 1220 743 1.53 1425 799 1.75 1636 851 1.99 1855 3000 629 1.20 1115 696 1.42 1321 756 1.64 1532 812 1.88 1749 863 2.12 1973 3100 646 1.30 1217 711 1.53 1428 770 1.76 1645 825 2.00 1869 875 2.25 2098 3200 662 1.42 1324 726 1.65 1542 784 1.89 1765 838 2.14 1994 888 2.39 2229 3300 679 1.54 1438 741 1.78 1663 798 2.03 1892 851 2.28 2126 901 2.54 2367 3400 695 1.67 1558 756 1.92 1790 812 2.17 2025 865 2.43 2266 913 2.69 2512 3500 712 1.81 1686 772 2.06 1923 827 2.32 2165 878 2.59 2412 926 2.86 2664 3600 729 1.95 1820 787 2.21 2065 841 2.48 2312 892 2.75 2565 940 3.03 2823 3700 746 2.10 1962 803 2.37 2213 856 2.65 2467 906 2.92 2726 953 3.21 2990 3750 754 2.18 2036 811 2.46 2290 864 2.73 2548 913 3.01 2809 960 3.30 3076 3800 763 2.26 2112 819 2.54 2369 871 2.82 2630 920 3.10 2895 966 3.39 3164 3900 780 2.43 2269 835 2.72 2533 886 3.00 2800 934 3.29 3070 980 3.59 3346 4000 797 2.61 2434 851 2.90 2705 901 3.19 2978 949 3.49 3255 4100 814 2.80 2607 867 3.09 2884 916 3.39 3164 963 3.70 3447 4200 831 2.99 2788 883 3.29 3072 932 3.60 3358 4250 840 3.09 2883 891 3.40 3170
AIRFLOW
(Cfm)
2550 862 1.82 1697 910 2.05 1913 955 2.29 2138 998 2.54 2370 1039 2.80 2611 2600 867 1.87 1747 915 2.11 1966 960 2.35 2193 1003 2.60 2427 1044 2.86 2669 2700 878 1.99 1852 925 2.23 2076 970 2.47 2307 1012 2.73 2545 1053 2.99 2791 2800 889 2.11 1963 936 2.35 2192 980 2.60 2427 1022 2.86 2670 1063 3.13 2920 2900 900 2.23 2080 946 2.48 2314 990 2.74 2554 1032 3.00 2800 1072 3.28 3055 3000 912 2.36 2204 957 2.62 2442 1001 2.88 2687 1043 3.15 2938 1082 3.43 3196 3100 923 2.50 2334 969 2.76 2577 1012 3.03 2826 1053 3.31 3082 1093 3.59 3345 3200 935 2.65 2471 980 2.92 2718 1023 3.19 2973 1064 3.47 3233 3300 947 2.80 2613 992 3.07 2867 1034 3.35 3126 1074 3.64 3391 3400 960 2.96 2764 1003 3.24 3022 1045 3.52 3286 3500 972 3.13 2921 1015 3.42 3185 1057 3.70 3454 3600 985 3.31 3086 1028 3.60 3355 3700 997 3.49 3259 3750 1004 3.59 3347 3800 1010 3.69 3438 3900 ————— — —— — —— — —— — 4000 ————— — —— — —— — —— — 4100 ————— — —— — —— — —— — 4200 ————— — —— — —— — —— — 4250 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
32
Table 17 — Fan Performance, 50TFQ012 — Vertical Discharge Units; Standard Motor and Drive*
AIRFLOW
(Cfm)
3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 4400 755 1.78 1660 807 2.01 1873 856 2.23 2084 4500 770 1.89 1766 821 2.13 1984 869 2.36 2200 4600 785 2.01 1876 835 2.25 2099 4700 800 2.14 1991 849 2.38 2219 4800 815 2.26 2111 4900 829 2.40 2235 5000 —— ——— ——————————
AIRFLOW
(Cfm)
3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 —— — 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 —— — 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 —— — —— — 3700 907 2.06 1924 949 2.25 2101 —— — —— — —— — 3800 918 2.17 2025 959 2.37 2207 —— — —— — —— — 3900 929 2.28 2130 4000 940 2.40 2238 ———————————— 4100 ————— — —— — —— — —— — 4200 ————— — —— — —— — —— — 4300 ————— — —— — —— — —— — 4400 ————— — —— — —— — —— — 4500 ————— — —— — —— — —— — 4600 ————— — —— — —— — —— — 4700 ————— — —— — —— — —— — 4800 ————— — —— — —— — —— — 4900 ————— — —— — —— — —— — 5000 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
33
Table 18 — Fan Performance, 50TFQ012 — Vertical Discharge Units; Alternate Motor and Drive*
AIRFLOW
(Cfm)
3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 920 2.43 2268 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 932 2.56 2384 4400 755 1.78 1660 807 2.01 1873 856 2.23 2084 901 2.46 2295 944 2.69 2505 4500 770 1.89 1766 821 2.13 1984 869 2.36 2200 914 2.59 2415 956 2.82 2630 4600 785 2.01 1876 835 2.25 2099 882 2.49 2320 926 2.72 2541 4700 800 2.14 1991 849 2.38 2219 895 2.62 2445 939 2.86 2670 4800 815 2.26 2111 863 2.51 2344 909 2.76 2575 4900 829 2.40 2235 877 2.65 2473 5000 844 2.54 2365 891 2.80 2608
AIRFLOW
(Cfm)
3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 1036 2.47 2303 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 1045 2.58 2410 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 1017 2.52 2347 1054 2.70 2521 3700 907 2.06 1924 949 2.25 2101 989 2.44 2279 1027 2.63 2457 1063 2.83 2636 3800 918 2.17 2025 959 2.37 2207 999 2.56 2389 1036 2.76 2571 3900 929 2.28 2130 970 2.48 2316 1009 2.68 2502 1046 2.88 2690 4000 940 2.40 2238 980 2.61 2429 1019 2.81 2620 4100 951 2.52 2351 991 2.73 2547 4200 962 2.65 2468 1002 2.86 2668 4300 973 2.78 2589 4400 ————— — —— — —— — —— — 4500 ————— — —— — —— — —— — 4600 ————— — —— — —— — —— — 4700 ————— — —— — —— — —— — 4800 ————— — —— — —— — —— — 4900 ————— — —— — —— — —— — 5000 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
34
Table 19 — Fan Performance, 50TFQ012 — Vertical Discharge Units; High-Static Motor and Drive*
AIRFLOW
(Cfm)
3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 920 2.43 2268 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 932 2.56 2384 4400 755 1.78 1660 807 2.01 1873 856 2.23 2084 901 2.46 2295 944 2.69 2505 4500 770 1.89 1766 821 2.13 1984 869 2.36 2200 914 2.59 2415 956 2.82 2630 4600 785 2.01 1876 835 2.25 2099 882 2.49 2320 926 2.72 2541 968 2.96 2760 4700 800 2.14 1991 849 2.38 2219 895 2.62 2445 939 2.86 2670 980 3.10 2895 4800 815 2.26 2111 863 2.51 2344 909 2.76 2575 952 3.01 2805 993 3.25 3034 4900 829 2.40 2235 877 2.65 2473 922 2.91 2709 965 3.16 2944 1005 3.41 3178 5000 844 2.54 2365 891 2.80 2608 936 3.06 2849 978 3.31 3089 1018 3.57 3328
AIRFLOW
(Cfm)
3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 1036 2.47 2303 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 1045 2.58 2410 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 1017 2.52 2347 1054 2.70 2521 3700 907 2.06 1924 949 2.25 2101 989 2.44 2279 1027 2.63 2457 1063 2.83 2636 3800 918 2.17 2025 959 2.37 2207 999 2.56 2389 1036 2.76 2571 1073 2.95 2755 3900 929 2.28 2130 970 2.48 2316 1009 2.68 2502 1046 2.88 2690 1082 3.09 2877 4000 940 2.40 2238 980 2.61 2429 1019 2.81 2620 1056 3.02 2812 1092 3.22 3004 4100 951 2.52 2351 991 2.73 2547 1029 2.94 2743 1066 3.15 2939 1102 3.36 3136 4200 962 2.65 2468 1002 2.86 2668 1040 3.08 2869 1076 3.29 3070 1112 3.51 3271 4300 973 2.78 2589 1013 3.00 2794 1050 3.22 2999 1087 3.44 3205 1122 3.66 3411 4400 985 2.91 2715 1024 3.14 2924 1061 3.36 3134 1097 3.59 3345 1132 3.81 3555 4500 996 3.05 2845 1035 3.28 3059 1072 3.51 3274 1108 3.74 3489 1142 3.97 3704 4600 1008 3.20 2979 1046 3.43 3199 1083 3.67 3418 1118 3.90 3638 1152 4.14 3857 4700 1020 3.34 3119 1058 3.58 3343 1094 3.83 3567 1129 4.07 3792 1163 4.31 4016 4800 1032 3.50 3263 1069 3.74 3492 1105 3.99 3721 1140 4.24 3950 1174 4.48 4179 4900 1044 3.66 3413 1081 3.91 3646 1117 4.16 3880 1151 4.41 4113 1184 4.66 4347 5000 1056 3.82 3566 1093 4.08 3805 1128 4.34 4044 1162 4.59 4282 1195 4.85 4520
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
35
Table 20 — Fan Performance, 50TFQ008 — Horizontal Discharge Units; Standard Motor and Drive*
AIRFLOW
(Cfm)
2250 465 0.49 459 555 0.67 621 629 0.84 786 694 1.03 959 752 1.22 1138 2300 471 0.52 483 560 0.69 648 634 0.88 817 698 1.06 992 757 1.26 1174 2400 483 0.57 534 570 0.76 705 644 0.94 880 708 1.14 1061 765 1.34 1248 2500 495 0.63 588 581 0.82 767 653 1.02 948 717 1.22 1134 774 1.42 1327 2550 501 0.66 617 586 0.86 799 658 1.05 983 722 1.26 1173 779 1.47 1368 2600 507 0.69 647 592 0.89 832 663 1.09 1020 727 1.30 1212 784 1.51 1410 2700 519 0.76 709 603 0.97 902 674 1.18 1096 736 1.39 1294 793 1.61 1498 2800 532 0.83 775 614 1.05 976 684 1.26 1176 746 1.48 1381 802 1.71 1590 2900 544 0.91 846 625 1.13 1054 694 1.35 1261 756 1.58 1472 812 1.81 1687 3000 557 0.99 922 637 1.22 1137 705 1.45 1351 766 1.68 1568 821 1.92 1789 3100 570 1.07 1002 648 1.31 1224 716 1.55 1445 776 1.79 1669 831 2.03 1896 3200 582 1.17 1087 660 1.41 1317 727 1.66 1545 786 1.90 1774 841 2.15 2008 3300 595 1.26 1177 671 1.52 1414 738 1.77 1649 797 2.02 1885 851 2.28 2125 3400 608 1.36 1271 683 1.63 1517 749 1.89 1759 807 2.15 2002 3500 622 1.47 1372 695 1.74 1625 760 2.01 1874 818 2.28 2124 3600 635 1.58 1477 707 1.86 1738 771 2.14 1995 3700 648 1.70 1588 720 1.99 1857 783 2.27 2121 3750 655 1.77 1646 726 2.06 1918 788 2.34 2187
AIRFLOW
(Cfm)
2250 806 1.42 1326 855 1.63 1521 902 1.85 1723 946 2.07 1932 988 2.30 2148 2300 810 1.46 1363 859 1.67 1561 906 1.89 1765 950 2.12 1976 991 2.35 2194 2400 818 1.55 1443 868 1.76 1644 914 1.99 1853 958 2.22 2068 —— — 2500 827 1.64 1527 876 1.86 1733 922 2.09 1946 966 2.32 2165 —— — 2550 832 1.68 1570 880 1.91 1779 926 2.14 1994 970 2.38 2215 —— — 2600 836 1.73 1615 885 1.96 1826 931 2.19 2043 —— — —— — 2700 845 1.83 1708 893 2.06 1923 939 2.30 2146 —— — —— — 2800 854 1.94 1805 902 2.17 2026 —— — —— — —— — 2900 863 2.05 1907 911 2.29 2134 —— — —— — —— — 3000 872 2.16 2015 ———————————— 3100 882 2.28 2127 ———————————— 3200 ————— — —— — —— — —— — 3300 ————— — —— — —— — —— — 3400 ————— — —— — —— — —— — 3500 ————— — —— — —— — —— — 3600 ————— — —— — —— — —— — 3700 ————— — —— — —— — —— — 3750 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
36
Table 21 — Fan Performance, 50TFQ008 — Horizontal Discharge Units; Alternate Motor and Drive*
AIRFLOW
(Cfm)
2250 465 0.49 459 555 0.67 621 629 0.84 786 694 1.03 959 752 1.22 1138 2300 471 0.52 483 560 0.69 648 634 0.88 817 698 1.06 992 757 1.26 1174 2400 483 0.57 534 570 0.76 705 644 0.94 880 708 1.14 1061 765 1.34 1248 2500 495 0.63 588 581 0.82 767 653 1.02 948 717 1.22 1134 774 1.42 1327 2550 501 0.66 617 586 0.86 799 658 1.05 983 722 1.26 1173 779 1.47 1368 2600 507 0.69 647 592 0.89 832 663 1.09 1020 727 1.30 1212 784 1.51 1410 2700 519 0.76 709 603 0.97 902 674 1.18 1096 736 1.39 1294 793 1.61 1498 2800 532 0.83 775 614 1.05 976 684 1.26 1176 746 1.48 1381 802 1.71 1590 2900 544 0.91 846 625 1.13 1054 694 1.35 1261 756 1.58 1472 812 1.81 1687 3000 557 0.99 922 637 1.22 1137 705 1.45 1351 766 1.68 1568 821 1.92 1789 3100 570 1.07 1002 648 1.31 1224 716 1.55 1445 776 1.79 1669 831 2.03 1896 3200 582 1.17 1087 660 1.41 1317 727 1.66 1545 786 1.90 1774 841 2.15 2008 3300 595 1.26 1177 671 1.52 1414 738 1.77 1649 797 2.02 1885 851 2.28 2125 3400 608 1.36 1271 683 1.63 1517 749 1.89 1759 807 2.15 2002 3500 622 1.47 1372 695 1.74 1625 760 2.01 1874 818 2.28 2124 3600 635 1.58 1477 707 1.86 1738 771 2.14 1995 3700 648 1.70 1588 720 1.99 1857 783 2.27 2121 3750 655 1.77 1646 726 2.06 1918 788 2.34 2187
AIRFLOW
(Cfm)
2250 806 1.42 1326 855 1.63 1521 902 1.85 1723 946 2.07 1932 988 2.30 2148 2300 810 1.46 1363 859 1.67 1561 906 1.89 1765 950 2.12 1976 991 2.35 2194 2400 818 1.55 1443 868 1.76 1644 914 1.99 1853 958 2.22 2068 —— — 2500 827 1.64 1527 876 1.86 1733 922 2.09 1946 966 2.32 2165 —— — 2550 832 1.68 1570 880 1.91 1779 926 2.14 1994 970 2.38 2215 —— — 2600 836 1.73 1615 885 1.96 1826 931 2.19 2043 2700 845 1.83 1708 893 2.06 1923 939 2.30 2146 —— — —— — 2800 854 1.94 1805 902 2.17 2026 2900 863 2.05 1907 911 2.29 2134 3000 872 2.16 2015 3100 882 2.28 2127 3200 ————— — —— — —— — —— — 3300 ————— — —— — —— — —— — 3400 ————— — —— — —— — —— — 3500 ————— — —— — —— — —— — 3600 ————— — —— — —— — —— — 3700 ————— — —— — —— — —— — 3750 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
37
Table 22 — Fan Performance, 50TFQ008 — Horizontal Discharge Units; High-Static Motor and Drive*
AIRFLOW
(Cfm)
2250 465 0.49 459 555 0.67 621 629 0.84 786 694 1.03 959 752 1.22 1138 2300 471 0.52 483 560 0.69 648 634 0.88 817 698 1.06 992 757 1.26 1174 2400 483 0.57 534 570 0.76 705 644 0.94 880 708 1.14 1061 765 1.34 1248 2500 495 0.63 588 581 0.82 767 653 1.02 948 717 1.22 1134 774 1.42 1327 2550 501 0.66 617 586 0.86 799 658 1.05 983 722 1.26 1173 779 1.47 1368 2600 507 0.69 647 592 0.89 832 663 1.09 1020 727 1.30 1212 784 1.51 1410 2700 519 0.76 709 603 0.97 902 674 1.18 1096 736 1.39 1294 793 1.61 1498 2800 532 0.83 775 614 1.05 976 684 1.26 1176 746 1.48 1381 802 1.71 1590 2900 544 0.91 846 625 1.13 1054 694 1.35 1261 756 1.58 1472 812 1.81 1687 3000 557 0.99 922 637 1.22 1137 705 1.45 1351 766 1.68 1568 821 1.92 1789 3100 570 1.07 1002 648 1.31 1224 716 1.55 1445 776 1.79 1669 831 2.03 1896 3200 582 1.17 1087 660 1.41 1317 727 1.66 1545 786 1.90 1774 841 2.15 2008 3300 595 1.26 1177 671 1.52 1414 738 1.77 1649 797 2.02 1885 851 2.28 2125 3400 608 1.36 1271 683 1.63 1517 749 1.89 1759 807 2.15 2002 861 2.41 2248 3500 622 1.47 1372 695 1.74 1625 760 2.01 1874 818 2.28 2124 871 2.55 2376 3600 635 1.58 1477 707 1.86 1738 771 2.14 1995 829 2.41 2252 881 2.69 2510 3700 648 1.70 1588 720 1.99 1857 783 2.27 2121 839 2.56 2385 892 2.84 2650 3750 655 1.77 1646 726 2.06 1918 788 2.34 2187 845 2.63 2454 897 2.92 2722
AIRFLOW
(Cfm)
2250 806 1.42 1326 855 1.63 1521 902 1.85 1723 946 2.07 1932 988 2.30 2148 2300 810 1.46 1363 859 1.67 1561 906 1.89 1765 950 2.12 1976 991 2.35 2194 2400 818 1.55 1443 868 1.76 1644 914 1.99 1853 958 2.22 2068 999 2.46 2290 2500 827 1.64 1527 876 1.86 1733 922 2.09 1946 966 2.32 2165 1007 2.56 2391 2550 832 1.68 1570 880 1.91 1779 926 2.14 1994 970 2.38 2215 1011 2.62 2444 2600 836 1.73 1615 885 1.96 1826 931 2.19 2043 974 2.43 2267 1015 2.68 2497 2700 845 1.83 1708 893 2.06 1923 939 2.30 2146 982 2.55 2374 1023 2.80 2609 2800 854 1.94 1805 902 2.17 2026 948 2.42 2253 991 2.67 2486 1031 2.92 2725 2900 863 2.05 1907 911 2.29 2134 956 2.54 2366 999 2.79 2603 1040 3.05 2847 3000 872 2.16 2015 920 2.41 2246 965 2.66 2483 1008 2.92 2726 1048 3.19 2974 3100 882 2.28 2127 929 2.54 2365 974 2.80 2607 1016 3.06 2854 1057 3.33 3107 3200 891 2.41 2245 938 2.67 2488 983 2.93 2735 1025 3.20 2988 1065 3.48 3246 3300 901 2.54 2369 948 2.81 2617 992 3.08 2869 1034 3.35 3127 1074 3.64 3390 3400 911 2.68 2497 957 2.95 2751 1001 3.23 3010 1043 3.51 3273 3500 921 2.82 2632 967 3.10 2891 1011 3.38 3155 1052 3.67 3424 3600 930 2.97 2772 977 3.26 3038 1020 3.55 3307 3700 941 3.13 2918 986 3.42 3190 1030 3.72 3465 3750 946 3.21 2994 991 3.50 3268
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
38
Table 23 — Fan Performance, 50TFQ009 — Horizontal Discharge Units; Standard Motor and Drive*
AIRFLOW
(Cfm)
2550 501 0.66 617 586 0.86 799 658 1.05 983 722 1.26 1173 779 1.47 1368 2600 507 0.69 647 592 0.89 832 663 1.09 1020 727 1.30 1212 784 1.51 1410 2700 519 0.76 709 603 0.97 902 674 1.18 1096 736 1.39 1294 793 1.61 1498 2800 532 0.83 775 614 1.05 976 684 1.26 1176 746 1.48 1381 802 1.71 1590 2900 544 0.91 846 625 1.13 1054 694 1.35 1261 756 1.58 1472 812 1.81 1687 3000 557 0.99 922 637 1.22 1137 705 1.45 1351 766 1.68 1568 821 1.92 1789 3100 570 1.07 1002 648 1.31 1224 716 1.55 1445 776 1.79 1669 831 2.03 1896 3200 582 1.17 1087 660 1.41 1317 727 1.66 1545 786 1.90 1774 841 2.15 2008 3300 595 1.26 1177 671 1.52 1414 738 1.77 1649 797 2.02 1885 851 2.28 2125 3400 608 1.36 1271 683 1.63 1517 749 1.89 1759 807 2.15 2002 3500 622 1.47 1372 695 1.74 1625 760 2.01 1874 818 2.28 2124 3600 635 1.58 1477 707 1.86 1738 771 2.14 1995 3700 648 1.70 1588 720 1.99 1857 783 2.27 2121 3750 655 1.77 1646 726 2.06 1918 788 2.34 2187 3800 662 1.83 1705 732 2.13 1982 3900 675 1.96 1828 744 2.26 2112 4000 689 2.10 1957 4100 702 2.24 2092 4200 716 2.40 2234 4250 —— ——— ——————————
AIRFLOW
(Cfm)
2550 832 1.68 1570 880 1.91 1779 926 2.14 1994 970 2.38 2215 —— — 2600 836 1.73 1615 885 1.96 1826 931 2.19 2043 2700 845 1.83 1708 893 2.06 1923 939 2.30 2146 —— — —— — 2800 854 1.94 1805 902 2.17 2026 2900 863 2.05 1907 911 2.29 2134 3000 872 2.16 2015 3100 882 2.28 2127 3200 ————— — —— — —— — —— — 3300 ————— — —— — —— — —— — 3400 ————— — —— — —— — —— — 3500 ————— — —— — —— — —— — 3600 ————— — —— — —— — —— — 3700 ————— — —— — —— — —— — 3750 ————— — —— — —— — —— — 3800 ————— — —— — —— — —— — 3900 ————— — —— — —— — —— — 4000 ————— — —— — —— — —— — 4100 ————— — —— — —— — —— — 4200 ————— — —— — —— — —— — 4250 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
39
Table 24 — Fan Performance, 50TFQ009 — Horizontal Discharge Units; High-Static Motor and Drive*
AIRFLOW
(Cfm)
2550 501 0.66 617 586 0.86 799 658 1.05 983 722 1.26 1173 779 1.47 1368 2600 507 0.69 647 592 0.89 832 663 1.09 1020 727 1.30 1212 784 1.51 1410 2700 519 0.76 709 603 0.97 902 674 1.18 1096 736 1.39 1294 793 1.61 1498 2800 532 0.83 775 614 1.05 976 684 1.26 1176 746 1.48 1381 802 1.71 1590 2900 544 0.91 846 625 1.13 1054 694 1.35 1261 756 1.58 1472 812 1.81 1687 3000 557 0.99 922 637 1.22 1137 705 1.45 1351 766 1.68 1568 821 1.92 1789 3100 570 1.07 1002 648 1.31 1224 716 1.55 1445 776 1.79 1669 831 2.03 1896 3200 582 1.17 1087 660 1.41 1317 727 1.66 1545 786 1.90 1774 841 2.15 2008 3300 595 1.26 1177 671 1.52 1414 738 1.77 1649 797 2.02 1885 851 2.28 2125 3400 608 1.36 1271 683 1.63 1517 749 1.89 1759 807 2.15 2002 861 2.41 2248 3500 622 1.47 1372 695 1.74 1625 760 2.01 1874 818 2.28 2124 871 2.55 2376 3600 635 1.58 1477 707 1.86 1738 771 2.14 1995 829 2.41 2252 881 2.69 2510 3700 648 1.70 1588 720 1.99 1857 783 2.27 2121 839 2.56 2385 892 2.84 2650 3750 655 1.77 1646 726 2.06 1918 788 2.34 2187 845 2.63 2454 897 2.92 2722 3800 662 1.83 1705 732 2.13 1982 794 2.42 2253 850 2.71 2524 902 3.00 2796 3900 675 1.96 1828 744 2.26 2112 806 2.56 2392 861 2.86 2669 913 3.16 2948 4000 689 2.10 1957 757 2.41 2249 817 2.72 2536 873 3.02 2820 924 3.33 3106 4100 702 2.24 2092 769 2.57 2392 829 2.88 2686 884 3.19 2978 935 3.51 3271 4200 716 2.40 2234 782 2.73 2541 841 3.05 2843 895 3.37 3143 945 3.69 3442 4250 723 2.47 2307 788 2.81 2619 847 3.14 2924 901 3.46 3227
AIRFLOW
(Cfm)
2550 832 1.68 1570 880 1.91 1779 926 2.14 1994 970 2.38 2215 1011 2.62 2444 2600 836 1.73 1615 885 1.96 1826 931 2.19 2043 974 2.43 2267 1015 2.68 2497 2700 845 1.83 1708 893 2.06 1923 939 2.30 2146 982 2.55 2374 1023 2.80 2609 2800 854 1.94 1805 902 2.17 2026 948 2.42 2253 991 2.67 2486 1031 2.92 2725 2900 863 2.05 1907 911 2.29 2134 956 2.54 2366 999 2.79 2603 1040 3.05 2847 3000 872 2.16 2015 920 2.41 2246 965 2.66 2483 1008 2.92 2726 1048 3.19 2974 3100 882 2.28 2127 929 2.54 2365 974 2.80 2607 1016 3.06 2854 1057 3.33 3107 3200 891 2.41 2245 938 2.67 2488 983 2.93 2735 1025 3.20 2988 1065 3.48 3246 3300 901 2.54 2369 948 2.81 2617 992 3.08 2869 1034 3.35 3127 1074 3.64 3390 3400 911 2.68 2497 957 2.95 2751 1001 3.23 3010 1043 3.51 3273 3500 921 2.82 2632 967 3.10 2891 1011 3.38 3155 1052 3.67 3424 3600 930 2.97 2772 977 3.26 3038 1020 3.55 3307 3700 941 3.13 2918 986 3.42 3190 3750 946 3.21 2994 991 3.50 3268 3800 951 3.29 3071 996 3.59 3348 3900 961 3.46 3229 4000 971 3.64 3393 4100 ————— — —— — —— — —— — 4200 ————— — —— — —— — —— — 4250 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
40
Table 25 — Fan Performance, 50TFQ012 — Horizontal Discharge Units; Standard Motor and Drive*
AIRFLOW
(Cfm)
3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184 4400 710 1.59 1482 760 1.80 1677 808 2.01 1876 855 2.23 2081 4500 723 1.69 1577 773 1.90 1775 820 2.12 1978 866 2.35 2187 4600 737 1.80 1675 785 2.01 1877 832 2.24 2085 4700 751 1.91 1778 798 2.13 1984 844 2.35 2195 4800 765 2.02 1885 812 2.25 2095 4900 779 2.14 1996 825 2.37 2210 5000 793 2.26 2112
AIRFLOW
(Cfm)
3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 —— — 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 —— — 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 —— — —— — 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 —— — —— — 3800 889 2.04 1904 936 2.25 2100 —— — —— — —— — 3900 898 2.14 1995 944 2.35 2195 —— — —— — —— — 4000 907 2.24 2089 4100 916 2.35 2187 4200 ————— — —— — —— — —— — 4300 ————— — —— — —— — —— — 4400 ————— — —— — —— — —— — 4500 ————— — —— — —— — —— — 4600 ————— — —— — —— — —— — 4700 ————— — —— — —— — —— — 4800 ————— — —— — —— — —— — 4900 ————— — —— — —— — —— — 5000 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
41
Table 26 — Fan Performance, 50TFQ012 — Horizontal Discharge Units; Alternate Motor and Drive*
AIRFLOW
(Cfm)
3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184 4400 710 1.59 1482 760 1.80 1677 808 2.01 1876 855 2.23 2081 900 2.46 2290 4500 723 1.69 1577 773 1.90 1775 820 2.12 1978 866 2.35 2187 910 2.57 2400 4600 737 1.80 1675 785 2.01 1877 832 2.24 2085 877 2.46 2297 921 2.70 2514 4700 751 1.91 1778 798 2.13 1984 844 2.35 2195 889 2.59 2412 932 2.82 2633 4800 765 2.02 1885 812 2.25 2095 856 2.48 2310 900 2.71 2531 4900 779 2.14 1996 825 2.37 2210 869 2.61 2430 912 2.85 2654 5000 793 2.26 2112 838 2.50 2330 881 2.74 2554
AIRFLOW
(Cfm)
3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 1046 2.50 2331 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 1051 2.60 2422 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 1012 2.48 2314 1056 2.70 2516 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 1019 2.58 2409 1062 2.80 2615 3800 889 2.04 1904 936 2.25 2100 981 2.47 2302 1025 2.69 2507 3900 898 2.14 1995 944 2.35 2195 988 2.57 2399 1032 2.80 2608 4000 907 2.24 2089 952 2.46 2293 996 2.68 2501 4100 916 2.35 2187 960 2.57 2395 1004 2.80 2607 4200 925 2.45 2289 969 2.68 2500 4300 934 2.57 2395 978 2.80 2610 4400 944 2.69 2504 4500 954 2.81 2618 4600 ————— — —— — —— — —— — 4700 ————— — —— — —— — —— — 4800 ————— — —— — —— — —— — 4900 ————— — —— — —— — —— — 5000 ————— — —— — —— — —— —
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to page 43 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
42
Table 27 — Fan Performance, 50TFQ012 — Horizontal Discharge Units; High-Static Motor and Drive*
AIRFLOW
(Cfm)
3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184 4400 710 1.59 1482 760 1.80 1677 808 2.01 1876 855 2.23 2081 900 2.46 2290 4500 723 1.69 1577 773 1.90 1775 820 2.12 1978 866 2.35 2187 910 2.57 2400 4600 737 1.80 1675 785 2.01 1877 832 2.24 2085 877 2.46 2297 921 2.70 2514 4700 751 1.91 1778 798 2.13 1984 844 2.35 2195 889 2.59 2412 932 2.82 2633 4800 765 2.02 1885 812 2.25 2095 856 2.48 2310 900 2.71 2531 942 2.95 2756 4900 779 2.14 1996 825 2.37 2210 869 2.61 2430 912 2.85 2654 953 3.09 2883 5000 793 2.26 2112 838 2.50 2330 881 2.74 2554 923 2.98 2782 965 3.23 3014
AIRFLOW
(Cfm)
3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 1046 2.50 2331 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 1051 2.60 2422 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 1012 2.48 2314 1056 2.70 2516 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 1019 2.58 2409 1062 2.80 2615 3800 889 2.04 1904 936 2.25 2100 981 2.47 2302 1025 2.69 2507 1068 2.91 2716 3900 898 2.14 1995 944 2.35 2195 988 2.57 2399 1032 2.80 2608 1074 3.03 2821 4000 907 2.24 2089 952 2.46 2293 996 2.68 2501 1038 2.91 2713 1080 3.14 2930 4100 916 2.35 2187 960 2.57 2395 1004 2.80 2607 1046 3.03 2822 1087 3.26 3042 4200 925 2.45 2289 969 2.68 2500 1011 2.91 2716 1053 3.15 2935 1094 3.39 3159 4300 934 2.57 2395 978 2.80 2610 1020 3.03 2828 1061 3.27 3052 1101 3.52 3279 4400 944 2.69 2504 986 2.92 2723 1028 3.16 2946 1068 3.40 3173 1108 3.65 3403 4500 954 2.81 2618 996 3.05 2840 1037 3.29 3067 1076 3.54 3297 1115 3.79 3531 4600 963 2.93 2736 1005 3.18 2962 1045 3.42 3192 1085 3.67 3426 1123 3.93 3664 4700 974 3.07 2858 1014 3.31 3088 1054 3.56 3322 1093 3.82 3560 1131 4.08 3801 4800 984 3.20 2985 1024 3.45 3219 1063 3.71 3456 1102 3.96 3697 1139 4.23 3943 4900 994 3.34 3116 1034 3.60 3353 1073 3.85 3594 1111 4.12 3839 1148 4.38 4088 5000 1005 3.49 3251 1044 3.74 3492 1082 4.01 3737 1119 4.27 3986 1156 4.55 4238
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Refer to General Fan Performance Notes below.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Fan performance is based on clean filters and wet coil data.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor perfor­mance Table 9.
3. Values include losses for filters, unit casing, and wet coils. See Tables 11A and 11B for static pressure information.
4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
43
PRE-START-UP
Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protec­tive goggles when checking or servicing refrigerant system.
2. Do not operate the compressor or provide any electric power to the unit unless the compressor terminal cover is in place and secured.
3. Do not remove the compressor terminal cover until all electrical sources are disconnected.
4. Relieve all pressure from the system before touching or disturbing anything inside the compressor terminal box if a refrigerant leak is suspected around the com­pressor terminals. Use accepted methods to recover refrigerant.
5. Never attempt to repair a soldered connection while the refrigerant system is under pressure.
6. Do not use a torch to remove any component. The system contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power to the unit and tag
disconnect.
b. Relieve all pressure from the system using both
the high and low-pressure ports. Use accepted methods to recover refrigerant.
c. Cut the component connection tubing with tubing
cutter, and remove the component from the unit.
d. Carefully unsweat the remaining tubing stubs
when necessary. Oil can ignite when exposed to a torch flame.
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU­TION, and INFORMATION labels attached to or shipped with unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected wires.
b. Inspect for oil at all refrigerant tubing connections
and on the unit base. Detecting oil generally indi­cates a refrigerant leak. Leak-test all refrigerant tubing connections using an electronic leak detec­tor, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring con-
nections. Be sure that connections are completed and tight. Ensure that electrical wires do not contact refrigerant tubing.
d. Inspect the coil fins. If damaged during shipping
and handling, carefully straighten the fins with a fin comb.
4. Verify the following conditions: a. Make sure that the outdoor-fan blades are
correctly positioned in the fan orifice. Refer to Outdoor-Fan Adjustment section on page 48 for
more details. b. Make sure that an air filter(s) is in place. c. Make sure that the condensate drain trap is filled
with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
Unit Preparation —
installed in accordance with installation instructions and applicable codes.
Make sure that the unit has been
Return-Air Filters — Make sure that the correct filters
are installed in the unit (see Table 1). Do not operate the unit without return-air filters.
Outdoor-Air Inlet Screen — The outdoor-air inlet screen
must be in place before operating the unit.
Compressor Mounting — Compressors are internally
spring mounted. Do not loosen or remove the compressor hold­down bolts.
Internal Wiring — Check all electrical connections in
unit control boxes; tighten as required.
Refrigerant Service Ports — Each refrigerant system
has 3 Schrader-type service gage ports: One on the suction line, one on the cooling mode liquid line, and one on the compressor discharge line. Be sure that the caps on the ports are tight. The port on the cooling mode liquid line and one port on the discharge line have protective devices installed on them.
HIGH FLOW REFRIGERANT VALVES — Two high flow valves may be located on the hot gas tube coming out of the compressor and the suction tube going into the compressor. Large black plastic caps identify these valves with O-rings inside screwing the cap and onto a brass body. No field access to these valves is available at this time. Ensure the plastic caps remain on the valves and are tight or the possibility of refriger­ant leakage could occur.
Compressor Rotation — It is important to be certain
that the scroll compressor (size 012 only) is rotating in the proper direction. To determine whether or not the compressor is rotating in the proper direction:
1. Connect service gages to the suction and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres­sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the indoor fan is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit. Re-energize compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels. NOTE: When the compressor is rotating in the wrong
direction, the unit makes more noise and does not provide heating/cooling.
Cooling — To start the unit, turn on main power supply. Set
the system selector switch at COOL position and the fan switch at AUTO position. Adjust the thermostat to a setting below room temperature. The compressor starts on closure of the contactor.
Check the unit charge. Refer to Refrigerant Charge section
on page 48.
Reset the thermostat at a position above room temperature.
The compressor will shut off. TO SHUT OFF UNIT — Set the system selector switch at
OFF position. Resetting the thermostat at a position above room temperature shuts the unit off temporarily until the space temperature exceeds the thermostat setting.
The compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then ON position.
44
Heating — To start the unit, turn on the main power supply.
Set the thermostat at HEAT position at a setting above room
temperature, the fan at AUTO position.
The first stage of the thermostat energizes the indoor-fan motor, compressor, and outdoor fan; the second stage energizes electric heater elements, if installed. Check the heating effects at the air supply grille(s).
If the accessory electric heaters do not energize, reset limit switch (located on indoor-fan scroll) by pressing the button located between terminals on the switch.
TO SHUT OFF UNIT — Set the system selector switch at OFF position. Resetting the heating selector lever below room temperature temporarily shuts the unit off until the space temperature falls below the thermostat setting.
Safety Relief — A soft solder joint on the suction line at
the loss-of-charge/low-pressure fitting provides pressure relief under abnormal temperature and pressure conditions.
Ventilation (Continuous Fan) — Set the fan and system
selector switches at ON and OFF positions, respectively. The in­door fan operates continuously to provide constant air circulation.
Operating Sequence
COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC), reversing valve solenoid (RVS1) and compressor contactor no. 1 (C1) are energized and indoor-fan motor, compressor no. 1, and outdoor fan starts. The outdoor-fan motor(s) run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) and reversing valve sole­noid (RVS2) are energized and compressor no. 2 starts.
HEATING, UNITS WITHOUT ECONOMIZER — Upon a request for heating from the space thermostat, terminal W1 will be energized with 24 v. The IFC, outdoor-fan contactor (OFC), C1, and C2 will be energized. The reversing valves switch po­sition and the indoor fan, outdoor fan, compressor no. 1, and compressor no. 2 are energized.
If the space temperature continues to fall while W1 is ener­gized, W2 will be energized with 24 v, and the heater contac­tor(s) (HC) will be energized, which will energize the electric heater(s).
When the space thermostat is satisfied, W2 will be deener­gized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be deenergized, and the reversing valve solenoids (RVS1 and RVS2) will be energized.
COOLING, UNITS WITH ECONOMI$ER IV — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV con­trol to provide a 50 to 55 F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55 or below 50 F, the dampers will be modulated (open or close) to bring the supply-air temperature back within set point limits.
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.
Above 50 F supply-air temperature, the dampers will modu­late from 100% open to the minimum open position. From 50 F to 45 F supply-air temperature, the dampers will maintain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the damp­ers will come back open to the minimum open position once the supply-air temperature rises to 48 F.
If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be ener­gized and deenergized.
If field-installed accessory CO
sensors are connected to the
2
EconoMi$er IV control, a demand controlled ventilation strate­gy will begin to operate. As the CO
level in the zone increases
2
above the CO2set point, the minimum position of the damper will be increased proportionally. As the CO
level decreases
2
because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Damper position will follow the high­er demand condition from DCV mode or free cooling mode.
Damper movement from full closed to full open (or vice
versa) will take between 1
1
/2and 21/2minutes.
If free cooling can be used as determined from the appropri­ate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply-air temperature set point at 50 to 55 F.
As the supply-air temperature drops below the set point range of 50 to 55 F, the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperature.
HEATING, UNITS WITH ECONOMI$ER IV — When the room temperature calls for heat, the heating controls are ener­gized as described in the Heating, Units Without Economizer section. When the thermostat is satisfied, the economizer damper moves to the minimum position.
COOLING, UNITS WITH ECONOMI$ER2, PREMIER­LINK™ CONTROL AND A THERMOSTAT — When free cooling is not available, the compressors will be controlled by the PremierLink control in response to the Y1 and Y2 inputs from the thermostat.
The PremierLink control will use the following information to determine if free cooling is available:
• Indoor fan has been on for at least 30 seconds.
• The SPT, SAT, and OAT inputs must have valid readings.
• OAT must be less than 75 F.
• OAT must be less than SPT.
• Enthalpy must be LOW (may be jumpered if an enthalpy
sensor not available).
• Economizer position is NOT forced.
Pre-cooling occurs when the is no call from the thermostat except G. Pre-cooling is defined as the economizer modulates to provide 70 F supply air.
When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply­air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following three routines. The three control routines are based on OAT, where:
SASP = Supply Air Set Point
DXCTLO = Direct Expansion Cooling Lockout Set Point Routine 1
—(OAT<DXCTLO)
• Y1 energized — economizer maintains a SASP =
(SATLO1 + 3).
• Y2 energized — economizer maintains a SASP =
(SATLO2 + 3). Routine 2
—(DXCTLO<OAT<68F)
• If only Y1 energized, the economizer maintains a SASP
=(SATLO1+3).
• If SAT > SASP + 5 and economizer position > 80%,
economizer will go to minimum position for 3 minutes or
until SAT > 68 F.
• First stage of mechanical cooling will be energized.
• Integrator resets.
• Economizer opens again and controls to current SASP
after stage one on for 90 seconds.
• With Y1 and Y2 energized Economizer maintains an
SASP = SATLO2 + 3.
45
• If SAT > SASP + 5 and economizer position >80%, economizer will go to minimum position for 3 minutes or until SAT > 68 F.
• If compressor no. 1 is on then second stage of mechani­cal cooling will be energized. Otherwise the first stage will be energized.
• Integrator resets.
• Economizer opens again and controls to SASP after stage one on for 90 seconds.
Routine 3
— (OAT > 68)
• Economizer is opened 100%.
• Compressors 1 and 2 are cycled based on Y1 and Y2 using minimum on and off times and watching the sup­ply air temperature as compared to SATLO1 and SATLO2 set points.
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be ener­gized and deenergized.
If field-installed accessory CO
sensors are connected to the
2
PremierLink™ control, a PID-controlled demand ventilation strategy will begin to operate. As the CO increases above the CO
set point, the minimum position of the
2
level in the zone
2
damper will be increased proportionally. As the CO2level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.
HEATING, UNITS WITH ECONOMI$ER2, PREMIER­LINK CONTROL AND A THERMOSTAT — When the thermostat calls for heating, terminal W1 is energized. The PremierLink control will move the economizer damper to the minimum position if there is a call for G and closed if there is a call for W1 without G. In order to prevent thermostat from short cycling, the unit is locked into the heating mode for at least 10 minutes when W1 is energized.
COOLING, UNITS WITH ECONOMI$ER2, PREMIER­LINK CONTROL AND A ROOM SENSOR — When free cooling is not available, the compressors will be controlled by the PremierLink controller using a PID (proportional integral) Error reduction calculation as indicated by Fig. 41.
The PremierLink controller will use the following informa-
tion to determine if free cooling is available:
• Indoor fan has been on for at least 30 seconds.
• The SPT, SAT, and OAT inputs must have valid readings.
• OAT must be less than 75 F.
• OAT must be less than SPT.
• Enthalpy must be LOW (may be jumpered if and enthalpy sensor is not available).
• Economizer position is NOT forced. When free cooling is available, the outdoor-air damper is
positioned through the use of a Proportional Integral (PID) control process to provide a calculated supply-air temperature into the zone. The supply air will maintain the space tempera­ture between the heating and cooling set points as indicated in Fig. 42.
The PremierLink control will integrate the compressor
stages with the economizer based on similar logic as the three routines listed in the previous section. The SASP will float up and down based on the error reduction calculations that com­pare space temperature and space set point.
When outside-air temperature conditions require the econo-
mizer to close for a compressor stage-up sequence, the econo­mizer control integrator is reset to zero after the stage-up se­quence is completed. This prevents the supply-air temperature from dropping too quickly and creating a freeze condition that would make the compressor turn off prematurely.
The high space set point is used for DX (direct expansion)
cooling control, while the economizer space set point is a calculated value between the heating and cooling set points.
The economizer set point will always be at least one degree below the cooling set point, allowing for a smooth transition from mechanical cooling with economizer assist, back to economizer cooling as the cooling set point is achieved. The compressors may be used for initial cooling then the PremierLink controller will modulate the economizer using an error reduction calculation to hold the space temperature between the heating and cooling set points. See Fig. 42.
The controller uses the following conditions to determine
economizer cooling:
• Enthalpy is Low
• SAT reading is available
• OAT reading is available
• SPT reading is available
•OAT≤SPT
• Economizer Position is NOT forced If any of the above conditions are not met, the economizer
submaster reference (ECSR) is set to maximum limit and the damper moves to minimum position. The operating sequence is complete. The ECSR is recalculated every 30 seconds.
If an optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO
sensors are connected to
2
the PremierLink control, a PID-controlled demand ventilation strategy will begin to operate. As the CO
level in the zone
2
increases above the CO2set point, the minimum position of the damper will be increased proportionally. As the CO
2
level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.
TEMPERATURE CONTROL
75
74
73 72 71
70
69
SPACE TEMPERATURE
68
NOTE: PremierLink control performs smart staging of 2 stages of DX cooling and up to 3 stages of heat.
TIME
SET POINT
TEMPERATURE
Fig. 41 — DX Cooling Temperature
Control Example
TEMPERATURE CONTROL
75
74
73 72 71
70
69
SPACE TEMPERATURE
68
TIME
COOL SETPOINT
TEMPERATURE HEAT SETPOINT
Fig. 42 — Economizer Temperature
Control Example
46
HEATING, UNIT WITH ECONOMI$ER2, PREMIERLINK™ CONTROL AND A ROOM SENSOR — Every 40 seconds the controller will calculate the required heat stages (maximum of 3) to maintain supply air temperature (SAT) if the following qualifying conditions are met:
• Indoor fan has been on for at least 30 seconds.
• COOL mode is not active.
• OCCUPIED, TEMP.COMPENSATED START or HEAT mode is active.
• SAT reading is available.
• Fire shutdown mode is not active. If all of the above conditions are met, the number of heat
stages is calculated; otherwise the required number of heat stages will be set to 0.
If the PremierLink controller determines that heat stages are
required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied.
SERVICE
When servicing the unit, shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
6. Secure the sections together. Reposition the coil sections, and remove the coil corner post from between the top panel and center post. Install the coil corner post and coil center post, and replace all screws.
CONDENSATE DRAIN — Check and clean each year at the start of cooling season. In winter, keep the drain dry or protect it against freeze-up.
Cleaning —
heating and cooling season or as operating conditions require. INDOOR COIL
1. Turn off the unit power and tag disconnect. Remove the filter access panel and indoor coil access panel.
2. If an economizer or accessory two-position damper is installed, remove the economizer or two-position damper by disconnecting the economizer plug and removing the mounting screws.
3. Slide the filters out of the unit.
4. Clean the coil using a commercial coil cleaner or dish­washer detergent in a pressurized spray canister. Wash both sides of the coil and flush with clean water. For best results, backflush toward the return-air section to remove foreign material.
5. Flush the condensate pan after completion.
6. Reinstall the economizer/two-position damper and filters.
7. Reconnect the wiring.
8. Replace the access panels.
OUTDOOR COILS — Inspect the coils monthly. Clean condenser coils annually, and as required by location and outdoor-air conditions.
Clean 2-row coils as follows:
1. Turn off the unit power and tag disconnect.
2. Remove the top panel screws on the outdoor end of the unit.
3. Remove the outdoor coil corner post. See Fig. 43. To hold the top panel open, place the coil corner post between the top panel and the center post. See Fig. 44.
4. Remove the device holding the coil sections together at the return end of the outdoor coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 45.
5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
Inspect the unit interior at the beginning of each
Fig. 43 — Cleaning Outdoor Coil
Fig. 44 — Propping Up Top Panel
47
Fig. 45 — Separating Coil Sections
FILTERS — Clean or replace at the start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be the same dimensions as original filters.
OUTDOOR-AIR INLET SCREEN — Clean the screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screens.
Lubrication
COMPRESSORS — Each compressor is charged with correct amount of oil at the factory.
FAN MOTOR BEARINGS — Fan motor bearings are per- manently lubricated. No further lubrication of outdoor or indoor-fan motors is required.
Outdoor Fan Adjustment (Fig. 46)
1. Shut off the unit power supply and tag disconnect.
2. Remove the outdoor-fan assembly (grille, motor, motor cover, and fan) and loosen the fan hub setscrews.
3. Adjust the fan height as shown in Fig. 46.
4. Tighten the setscrews and replace the outdoor-fan assembly.
UNIT
VOLTAGE 208/230 V 2.75
460 V and 575 V 3.50
Fig. 46 — Outdoor Fan Adjustment
“A”
in.
Unit panels must be in place when the unit is operating
during charging procedure. NO CHARGE — Use standard evacuating techniques. After
evacuating the system, weigh in the specified amount of refrig­erant (refer to Table 1).
LOW CHARGE COOLING — Use the Cooling Charging Charts, Fig. 47-49. Vary the refrigerant until the conditions of the appropriate chart are met. Note that the charging charts are different from the type normally used. Charts are based on charging the units to the correct superheat for the various oper­ating conditions. An accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambi­ent temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHARTS — Take the out­door ambient temperature and read the suction pressure gage. Refer to the appropriate chart to determine what the suction temperature should be. If the suction temperature is high, add refrigerant. If the suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.
EXAMPLE: (Fig. 47)
Outdoor Temperature . . . . . . . . . . . .................. 85F
SuctionPressure ...............................70psig
Suction Temperature should be . . . .................. 49F
(Suction Temperature may vary ±5° F.) HEATING CHARGE — Do not attempt to adjust refrigerant
charge while the unit is operating in the heating mode. If the charge amount is believed to be incorrect, recover refrigerant and weigh in the amount listed on the unit rating plate.
Replacement Parts — A complete list of replacement
parts can be obtained from any Carrier distributor.
Blower Belt Adjustment — Inspect the blower belt
for wear, proper belt tension, and pulley alignment as condi­tions require or at the beginning of each heating and air condi­tioning season.
Refer to Step 7 — Adjust Indoor-Fan Speed on page 25 for
adjustment and alignment procedures.
High-Pressure Switch — Located on the compressor
hot gas line is a high-pressure switch, which contains a Schrader core depressor. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Table 1 .
Loss-of-Charge Switch — Located on the outdoor liq-
uid line is a low-pressure switch which functions as a loss-of­charge switch. This switch contains a Schrader core depressor. This switch opens at 7 psig and closes at 22 psig. No adjust­ment is necessary. Refer to Table 1.
Freezestat — Located on the “hair pin” end of the indoor
coil is a bimetal temperature sensing switch. This switch pro­tects the evaporator coil from freeze-up due to lack of airflow. The switch opens at 30 F and closes at 45 F. No adjustment is necessary. Refer to Table 1.
Refrigerant Charge — The amount of refrigerant charge
is listed on the unit nameplate (also refer to Table 1). Refer to Carrier Refrigerant Service Techniques Manual, Refrigerants section.
Fig. 47 — Cooling Charging Chart, 50TFQ008
48
Fig. 48 — Cooling Charging Chart, 50TFQ009
Fig. 49 — Cooling Charging Chart, 50TFQ012
TROUBLESHOOTING
Unit Troubleshooting —
fer to Fig. 50 and Table 28.
For unit troubleshooting, re-
EconoMi$er IV Troubleshooting — See Table 29
for EconoMi$er IV logic.
A functional view of the EconoMi$er IV is shown in Fig. 51. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is avail­able from Carrier to help with EconoMi$er IV training and troubleshooting.
ECONOMI$ER IV PREPARATION — This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all poten­tiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals S
8. Put 620-ohm resistor across terminals S
and +.
O
and +.
R
9. Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
and +.
O
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
DIFFERENTIAL ENTHALPY — To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Place 620-ohm resistor across S
3. Place 1.2 kilo-ohm resistor across S
and +.
O
and +. The Free
R
Cool LED should be lit.
4. Remove 620-ohm resistor across S
and +. The Free
O
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
SINGLE ENTHALPY — To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
DCV (DEMAND CONTROLLED VENTILATION) AND POWER EXHAUST — To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.
49
5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
DCV MINIMUM AND MAXIMUM POSITION — To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to mid­point. The actuator should drive to between 20 and 80% open.
4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
SUPPLY-AIR INPUT — To check supply-air input:
1. Make sure EconoMi$er IV preparation procedure has been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
ECONOMI$ER IV TROUBLESHOOTING COMPLE­TION — This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by perform­ing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous setting.
4. Set minimum position, DCV set point, and exhaust potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
and +.
R
6. Remove 1.2 kilo-ohm checkout resistor from terminals S
and +. If used, reconnect sensor from terminals SOand
O
+.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1.
50
C—Contactor, Compressor CAP Capacitor CB Circuit Breaker CLO Compressor Lockout COMP — Compressor Motor DB Defrost Board DFT Defrost Thermostat EQUIP — Equipment FPT Freeze Protection Thermostat HC Heater Contactor HPS High-Pressure Switch HR Heater Relay IFC Indoor-Fan Contactor IFM Indoor-Fan Motor IFMOVL — Indoor-Fan Motor Overload Switch LPS Low-Pressure Switch
Fig. 50 — Typical Unit Wiring Schematic (208/203-3-60 Unit Shown)
LEGEND
LSM Limit Switch (Manual Reset) MCA Minimum Circuit Amps MTR Motor OFC Outdoor-Fan Contactor OFM Outdoor-Fan Motor P—Plug PL Plug Assembly QT Quadruple Terminal SAT Supply Air Thermostat RVS Reversing Valve Solenoid TRAN Transformer
Field Splice
Marked Wire
51
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked) Factory Wiring
Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only,
not to represent wiring
Table 28 — Heating and Cooling Troubleshooting
PROBLEM CAUSE REMEDY
Compressor and Outdoor Fan Will Not Start.
Compressor Will Not Start But Outdoor Fan Runs.
Compressor Cycles (Other Than Normally Satisfying Thermostat).
Compressor Operates Continuously. Dirty air filter. Replace filter.
Excessive Head Pressure. Dirty outdoor coil. Clean coil.
Head Pressure Too Low. Low refrigerant charge. Check for leaks, repair, and recharge.
Excessive Suction Pressure. High heat load. Check for source and eliminate.
Suction Pressure Too Low. Dirty air filter (cooling) or dirty outdoor coil
Compressor No. 2 Will Not Run. Unit in economizer mode. Proper operation; no remedy necessary.
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or
control relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room
High-pressure switch tripped. See problem ‘‘Excessive Head Pressure.’’ Low-pressure switch tripped. Check for leaks, repair, and recharge. Freeze-up protection thermostat tripped. See problem ‘‘Suction Pressure Too Low.’’ Faulty wiring or loose connections in compressor
circuit. Compressor motor burned out, seized, or internal
overload open. Defective overload. Determine cause and replace. One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked outdoor coil or dirty air filter. Determine cause and correct. Defective overload. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty outdoor-fan (cooling) or indoor-fan (heating)
motor or capacitor. Restriction in refrigerant system. Locate restriction and remove.
Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and
Outdoor coil dirty or restricted. Clean coil or remove restriction. Dirty air filter. Replace filter.
Refrigerant overcharged. Remove excess refrigerant. Air in system. Recover refrigerant, evacuate system, and
Condensing air restricted or air short-cycling. Determine cause and correct.
Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction.
Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant.
(heating). Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted Remove source of restriction. Insufficient indoor airflow (cooling mode). Increase air quantity. Check filter and replace if
Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace. Outdoor ambient temperature below 25 F. Install low-ambient kit.
Replace component.
temperature.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause.
recharge to nameplate.
Replace.
recharge.
recharge.
Replace filter or clean coil.
necessary.
52
Table 29 — EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventila tion (DCV )
Below set (DCV LED Off)
Above set (DCV LED On)
*For single enthalpy control, the module compares outdoor
enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
High (Free Cooling LED Off)
Low (Free Cooling LED On)
High (Free Cooling LED Off)
Low (Free Cooling LED On)
Enthalpy*
Outdoor Return
Low On On On On Minimum position Closed
High On On On Off Modulating** (between min.
Low On On On On Modulating†† (between min.
High On On On Off Modulating*** Modulating†††
Y1 Y2
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off Minimum position Closed
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off
Compressor N Terminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
***Modulation is based on the greater of DCV and supply-air sen-
sor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air sen-
sor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).
Occupied Unoccupied
Damper
Modulating** (between closed and full-open)
Modulating†† (between closed and DCV maximum)
Fig. 51 — EconoMi$er IV Functional View
53
Access panels 18 Barometric flow capacity 20 Carrier Comfort Network 14 Charging chart, refrigerant 48, 49 Clearance 3, 6 CO2sensor
Configuration 25 Settings 23, 25
Compressor
Mounting
44
Rotation 44
Condensate drain
Cleaning 47 Location 3
Control circuit
Wiring 12
Wiring raceway 12 Convenience outlet 10, 11, 13 Defrost board 12, 13 Demand control ventilation 24
Dehumidification 25 Dimensions 2, 6 Ductwork 3 EconoMi$er2 18
Components 18
4to20mAcontrol 20
Wiring 20 EconoMi$er IV 18-25
Components 18
Damper 24
Dry bulb changeover 21
Enthalpy changeover 22
Inputs and outputs 53
Troubleshooting 49, 50
Wiring 19 Electrical connections 7 Electrical data 8-11 Electric heat 8 Enthalpy changeover set points 23 Factory-installed options 12-25
Convenience outlet 13
EconoMi$er2 18-20
EconoMi$er IV 18-25
Manual outdoor air damper 13
Novar controls 13
PremierLink™ controls 14-16 Filter
Cleaning 48
Installation 19
Size 5 Freeze protection thermostat 5, 48 Heat anticipator settings 12, 13 High flow valves 44 High pressure switch 5, 48 Horizontal units 3 Indoor air quality 14, 22 Indoor coil 5
Cleaning 47 Indoor fan motor 5
Lubrication 48
Motor data 26
Performance 28-43
Pulley adjustment 26
Pulley setting 5, 27
Speed 5 Low pressure switch 5, 48 Manual outdoor air damper 13 Mounting
Compressor 44
Unit 3 Novar controls 13
INDEX
Operating sequence
Cooling 45 EconoMi$er2 45-47 EconoMi$er IV 45
Heating 45 Outdoor air hood 14, 19 Outdoor air inlet screens 44
Cleaning 48 Outdoor coil 5
Cleaning 47 Outdoor fan 5
Adjustment 48 Physical data 5 Potentiometer 22 Power supply
Wiring 7 PremierLink controls 14-16 Pressure, drop
Electric heat 27
Return air 20
Outdoor air 20 Pre-start-up 44 Pressure switches
High pressure 5
Low pressure 5 Refrigerant
Charge 5, 48, 49
Type 5 Refrigerant service ports 44 Replacement parts 48 Return air filter 5, 44 Return air temperature sensor 22 Rigging unit 3, 4 Roof curb
Assembly 1
Dimensions 2
Connector package 2
Leveling tolerances 3
We ig ht 5 Safety considerations 1 Safety relief 45 Service 47-49 Service ports 44 Slab mount 3 Start-up 44-47 Start-up checklist CL-1 Supply-air temperature sensor 14, 21 Thermostat 12, 24 Troubleshooting 49-53 Ventilation 45 Weight
Corner 6
EconoMi$er IV 5, 6
Unit 4-6 Wiring
4to20mAcontrol 20
EconoMi$er2 20
EconoMi$er IV 19
Power connections 7
PremierLink 16
Thermostat 12
Unit 51
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
Catalog No. 04-53500019-01 Printed in U.S.A. Form 50TFQ-9SI Pg 54 9-05 Replaces: 50TFQ-7SI
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: __________________________________ SERIAL NO.: ______________________________________ DATE: ________________________________________ TECHNICIAN: _____________________________________ BUILDING LOCATION: _________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
VERIFY INSTALLATION OF ECONOMIZER HOOD (IF EQUIPPED)
III. START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 INDOOR-FAN AMPS L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE DB WB
RETURN-AIR TEMPERATURE DB WB
COOLINGSUPPLYAIR DB WB
PRESSURES (COOLING MODE)
REFRIGERANT SUCTION, CIRCUIT 1 PSIG F
REFRIGERANT SUCTION, CIRCUIT 2 PSIG F
REFRIGERANT DISCHARGE, CIRCUIT 1 PSIG F
REFRIGERANT DISCHARGE, CIRCUIT 2 PSIG F
VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION (SIZE 012 ONLY)
VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGES 48 AND 49.
GENERAL
SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS (IF EQUIPPED)
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
Catalog No. 04-53500019-01 Printed in U.S.A. Form 50TFQ-9SI Pg CL-1 9-05 Replaces: 50TFQ-7SI
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Loading...