Carrier 50TFQ008-012 User Manual

Single-Package Rooftop
Heat Pump Units
Installation, Start-Up and
Service Instructions
50TFQ008-012
CONTENTS
Page
INSTALLATION ...................................1-43
Step 1— Provide Unit Support .......................1
• ROOF CURB
• SLAB MOUNT
• ALTERNATE UNIT SUPPORT
Step 2 — Field Fabricate Ductwork ..................3
Step 3 — Install Condensate Drain Line
and External Trap .................................3
• POSITIONING
Step 5 — Make Electrical Connections ..............7
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• DEFROST BOARD
• HEAT ANTICIPATOR SETTINGS
Step 6 — Adjust Factory-Installed Options .........12
• DISCONNECT SWITCH
• CONVENIENCE OUTLET
• NOVAR CONTROLS
• MANUAL OUTDOOR-AIR DAMPER
• PREMIERLINK™ CONTROL
• OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2
• ECONOMI$ER IV STANDARD SENSORS
• ECONOMI$ER IV CONTROL MODES
Step 7 — Adjust Indoor-Fan Speed .................25
PRE-START-UP .....................................44
START-UP .......................................44-47
SERVICE ........................................47-49
INDEX ..............................................54
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit. Electrical shock could cause personal injury.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to horizontal configuration, remove side duct opening covers. Us­ing the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install the accessory roof curb in accordance with instructions shipped with the curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If electric or control power will be routed through the basepan, use the proper accessory kit listed in Fig. 1, available from your local distributor. Attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before the unit is set on the roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a water-tight seal. Install gasket supplied with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance.
The roof curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for the unit drain to function properly. Refer to Accessory Roof Curb Installation Instruc­tions for additional information as required.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
Catalog No. 04-53500019-01 Printed in U.S.A. Form 50TFQ-9SI Pg 1 9-05 Replaces: 50TFQ-7SI
Fig. 1 — Roof Curb Details
2
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 2 — Unit Leveling Tolerances
SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond the unit cabinet on all sides. Install a gravel apron in front of the outdoor coil air inlet to prevent grass and foliage from obstruct­ing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT — When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 — Field Fabricate Ductwork — On verti-
cal discharge units, secure all ducts to the roof curb and building structure. Do not connect ductwork to the unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accor­dance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applica­ble fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) should not exceed 0.35 in. wg with economizer, or 0.45 in. wg without economizer.
Step 3 — Install Condensate Drain Line and External Trap —
ed at the bottom and end of the unit. Unit discharge connec­tions do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.
When using the standard end drain connection, make sure the plug in the alternate bottom connection is tight before in­stalling the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed plug from the bottom connec­tion to the end connection. The center drain plug looks like a star connection, but can be removed with a sion. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect against freeze­up. If drain line is installed downstream from the external trap,
Condensate drain connections are locat-
1
/2-in. socket drive exten-
pitch the line away from the unit at
1
/4-in. per ft of run. Do not
use a pipe size smaller than the unit connection. See Fig. 4.
Step 4 — Rig and Place Unit — Inspect the unit for
transportation damage. File any claim with the transportation agency. Keep the unit upright and do not drop it. Spreader bars are not required if top crating is left on the unit. Rollers may be used to move the unit across a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5.
Lifting holes are provided in the base rails as shown in
Fig. 5 and 6. Refer to rigging instructions on the unit. POSITIONING — Maintain clearance around and above the
unit to provide proper airflow and service access. See Fig. 6.
Position the unit on the roof curb so that the following clear­ances are maintained: and base rails on each side and in front of the unit; 3 clearance between the roof curb and the outdoor fan end of the unit (see Fig. 1, section C-C).
Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air.
Although the unit is weatherproof, guard against water from higher level runoff and overhangs.
After the unit is in position, remove the polyethylene ship­ping wrapper and rigging skid.
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
Fig. 3 — Condensate Drain Pan (Side View)
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 4 — Condensate Drain Piping Details
1
/4-in. clearance between the roof curb
DRAIN PLUGHORIZONTAL
5
/16-in.
3
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail A. Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
All panels must be in place when rigging. Unit is not designed for handling by a fork truck. Damage to unit may result.
Fig. 5 — Rigging Details
50TFQ
008 940 426 77.42 1966.5 41.5 1054 42.12 1070 009 965 438 77.42 1966.5 41.5 1054 42.12 1070 012 1015 460 77.42 1966.5 41.5 1054 42.12 1070
WEIGHT A B C
Lb Kg in. mm in. mm in. mm
4
Table 1 — Physical Data
NOMINAL CAPACITY (tons) 7
UNIT SIZE 50TFQ 008 009 012
OPERATING WEIGHT (lb)
Unit 940 965 1015 Economizer
EconoMi$er IV 75 75 75
Roof Curb* 143 143 143
COMPRESSOR (Hermetic) Reciprocating Scroll
Quantity 222 Oil (oz) 45 ea 54 ea 54 ea
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1 5-14 8- 6 7-14 Circuit 2 5-13 8-13 8- 3
OUTDOOR COIL Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device
Rows...Fins/in. 1...17 2...17 2...17 Total Face Area (sq ft) 20.50 18.00 18.30
OUTDOOR FAN Propeller Type
Nominal Cfm 6500 6500 6500 Quantity...Diameter (in.) 2...22 2...22 2...22 Motor Hp...Rpm Watts Input (Total) 500 500 500
INDOOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device
Rows...Fins/in. 3...15 3...15 3...15 Total Face Area (sq ft) 8.0 8.0 11.1
INDOOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15
Typ e Drive Std Belt Belt Belt
Nominal Cfm 3000 3600 4000 Maximum Continuous Bhp Std 2.40 2.40 2.40
Motor Frame Size Std 56 56 56
Nominal Rpm Std ———
Fan Rpm Range Std 590- 840 685- 935 685- 935
Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 7.0
Belt, Quantity...Type...Length (in.) Std 1...A...53 1...A...48 1...A...49
Pulley Center Line Distance (in.) Std 16.75-19.25 16.75-19.25 15.85-17.50
Speed Change per Full Turn of
Moveable Pulley Flange (rpm)
Moveable Pulley Maximum Full Turns
From Closed Position
Factory Setting Std 555
Factory Speed Setting (rpm) Std 590 685 685
Fan Shaft Diameter at Pulley (in.) 111
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief (Differential) 450 ± 50 Cutout 428 Reset (Auto.) 320
LOSS-OF-CHARGE (LOW-PRESSURE) SWITCH (psig)
Cutout 7±3 Reset (Auto.) 22 ± 5
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
Alt 1...15 x 15 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 1...15 x 15
Alt Belt Belt High-Static Belt Belt Belt
Alt 2.40 2.90 High-Static 3.70 3.70 5.25
Alt 56 56 High-Static 56 56 56
Alt ——— High-Static 1725 1725 1725
Alt 685- 935 835-1085 High-Static 860-1080 860-1080 830-1130
Alt 2.8/3.8 3.4/4.4 High-Static 4.0/5.0 4.0/5.0 2.8/3.8
Alt High-Static
Alt 7.0 7.0 High-Static 8.0 8.0 5.8
Alt 1...A...49 1...A...51 High-Static 1...A...65 1...A...53 1...BX...48
Alt 16.75-19.25 15.85-17.50 High-Static 16.75-19.25 16.75-19.25 15.85-17.50 Std 50 50 50 Alt 50 50 High-Static 60 60 60 Std 555 Alt 5—5 High-Static 556
Alt 5—5 High-Static 555
Alt 685 835 High-Static 860 880 887
OUTDOOR-AIR INLET SCREENS Cleanable.
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 4...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower
1
1
/4...1100
5
/
5
/
7
/
/
2
8 8 8
81/
1
/4...1100
5
/
7
/
2
8
8
Screen quantity and size vary based on options selected.
*Weightof14-in.roofcurb.
10
1
/4...1100
5
/
7
/
7
/
8 8 8
5
Fig. 6 — Base Unit Dimensions
6
Step 5 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute)/ NFPA (National Fire Protection Association) 70 latest year and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
FIELD POWER SUPPLY — All units except 208/230-v units are factory-wired for the voltage shown on the unit name­plate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v transformer and connecting it to the 208-v1/4-in. male spade terminal from the transformer.
Refer to the unit label diagram for additional information. Pigtails are provided for field wire connections. Use factory­supplied splices or a UL (Underwriters’ Laboratories) approved copper/aluminum connector.
1
/4-in. male spade terminal on the
When installing units, provide a disconnect per the NEC.
All field wiring must comply with the NEC and local re­quirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.
Install field wiring as follows:
1. Install conduit through the side panel openings. For units without electric heat, install conduit between the discon­nect and control box.
2. Install power lines to terminal connections as shown in Fig. 7.
3. For units with electric heat, refer to Table 2 and Accessory Installation Instructions.
During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 3A and 3B). On 3-phase units, voltages between phases must be bal­anced within 2%, and the current within 10%. Use the formula shown in Tables 3A and 3B, Note 2 on page 11 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such opera­tion would invalidate any applicable Carrier warranty.
208/230-3-60
460-3-60
LEGEND
C—Contactor COMP — Compressor IFC Indoor-Fan Contactor NEC National Electrical Code TB Terminal Block
Field Wiring Factory Wiring Splice Connection (Factory-Supplied)
Fig. 7 — Power Wiring Connections
7
575-3-60
Table 2 — Electric Heating Capacities
50TFQ
UNIT SIZE
008, 009
012
*Two heater packages required to provide kW indicated.
†Use CRSINGLE008A00 for units with an electrical convenience outlet.
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240) kW new = 12.8 kW (rating at 215 v)
UNIT VOLTAGE
(60 Hz)
208/230/240
(3 phase)
460/480
(3 phase)
575
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
575
(3 phase)
2
ACCESSORY
kW
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
17.0
34.0
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
45.9/50.0*
17.0
34.0
51.0*
ELECTRIC HEATER
PART NUMBER
CRHEATER---A00
017 010 011 012
012 and 017
016 013 014 015
014 and 016
018 019
017 010
012 012 and 017 010 and 012
013
014
015 014 and 016 013 and 015
018
019 018 and 019
2
SINGLE POINT BOX
PAC KA GE N O.
CRSINGLE---A00
007 007 009 009 013
006 006 008 008 010
006 006†
012 012 015 017 017
011 014 014 016 016
011 014 016
Table 3A — Electrical Data (Units Without Electrical Convenience Outlet)
VOLTAGE
50TFQ
UNIT SIZE
008
1
(7
/2Ton s)
NOTE: Legend and Notes for Electrical Data are on page 11.
NOMINAL
V-P H-Hz
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
STD 187 254 13.4 91.0 1.4 5.8
HIGH-STATIC 187 254 13.4 91.0 1.4 10.6
STD 414 508 6.7 42.0 0.7 2.6
HIGH-STATIC 414 508 6.7 42.0 0.7 4.8
STD
HIGH-STATIC 4.8
RANGE
Min Max RLA LRA
518 632 5.4 39.0 0.7
COMPRESSOR
(each)
OFM
FLA
ELECTRIC HEAT* POWER SUPPLY
IFM
FLA
Nominal
kW**
38.8/ 38.8 40/ 40†† 41/ 41 229/229
7.8/10.4 21.7/ 25.0 65.9/ 70.0 70/ 70 66/ 69 251/254
12.0/16.0 33.3/ 38.5 80.4/ 86.9 90/ 90 79/ 85 262/268***
18.6/24.8 51.6/ 59.7 103.3/113.4 110/125 100/109 281/289***
24.0/32.0 66.6/ 77.0 122.0/135.0 125/150 117/129 296/306***
31.8/42.4 88.3/102.0 149.1/166.3 150/175 142/158 317/331*** — 43.6/ 43.6 45/ 45†† 46/ 46 273/273
7.8/10.4 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 294/298
12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 306/311***
18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 324/332***
24.0/32.0 66.6/ 77.0 126.8/139.8 150/150 123/135 339/350***
31.8/42.4 88.3/102.0 153.9/171.1 175/175 148/164 361/375*** — 19.1 20†† 20 108
13.9 16.7 40.0 40†† 39 124
16.5 19.8 43.8 45†† 43 128
27.8 33.4 60.8 70 58 141
33.0 39.7 68.7 70 66 147
41.7 50.2 81.8 90 78 158 — 21.3 25†† 23 130
13.9 16.7 42.2 45†† 42 146
16.5 19.8 46.0 50†† 45 149
27.8 33.4 63.0 70 61 163
33.0 39.7 70.9 80 68 169
41.7 50.2 84.0 90 80 180*** — 15.4 20†† 16 97
2.6
17.0 17.1 36.7 40†† 36 114
34.0 34.1 58.0 60†† 55 131 — 17.1 20†† 18 114
17.0 17.1 38.5 40†† 38 132
34.0 34.1 59.7 60†† 57 149
FLA MCA MOCP FLA LRA
DISCONNECT
SIZE†
8
Table 3A — Electrical Data (Units Without Electrical Convenience Outlet) (cont)
VO LTAGE
50TFQ
UNIT SIZE
009
(81/2Ton s)
012
(10 Tons)
NOTE: Legend and Notes for Electrical Data are on page 11.
NOMINAL
V-P H- Hz
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
STD 187 254 16.0 137.0 1.4 5.8
HIGH-STATIC 187 254 16.0 137.0 1.4 10.6
STD 414 508 8.3 69.0 0.7 2.6
HIGH-STATIC 414 508 8.3 69.0 0.7 4.8
STD
HIGH-STATIC 4.8
STD 187 254 17.2 124.0 1.4 5.8
ALT 187 254 17.2 124.0 1.4 7.5
HIGH-STATIC 187 254 17.2 124.0 1.4 15.0
STD 414 508 8.6 59.6 0.7 2.6
ALT 414 508 8.6 59.6 0.7 3.4
HIGH-STATIC 414 508 8.6 59.6 0.7 7.4
STD 518 632 6.9 49.4 0.7 2.6
ALT 518 632 6.9 49.4 0.7 3.4
HIGH-STATIC 518 632 6.9 49.4 0.7 7.4
RANGE
Min Max RLA LRA
518 632 6.4 58.0 0.7
COMPRESSOR
(each)
OFM
FLA
ELECTRIC HEAT* POWER SUPPLY
IFM
FLA
Nominal
kW**
44.6/ 44.6 45/ 45†† 47/ 47 321/321
7.8/10.4 21.7/ 25.0 71.7/ 75.9 80/ 80 72/ 75 343/346
12.0/16.0 33.3/ 38.5 86.2/ 92.7 90/100 85/ 91 354/360***
18.6/24.8 51.6/ 59.7 109.1/119.2 110/125 106/115 373/381***
24.0/32.0 66.6/ 77.0 127.9/140.9 150/150 123/135 388/398***
31.8/42.4 88.3/102.0 155.0/172.1 175/175 148/164 409/428*** — 49.4/ 49.4 50/ 50†† 52/ 52 365/365
7.8/10.4 21.7/ 25.0 76.5/ 80.7 80/ 90 77/ 81 386/390***
12.0/16.0 33.3/ 38.5 91.0/ 97.5 100/100 91/ 96 398/403***
18.6/24.8 51.6/ 59.7 113.9/124.0 125/125 112/121 416/424***
24.0/32.0 66.6/ 77.0 132.7/145.7 150/150 129/141 431/442***
31.8/42.4 88.3/102.0 159.8/176.9 175/200 154/170 453/467*** — 22.7 25†† 24 162
13.9 16.7 43.6 45†† 43 178
16.5 19.8 47.4 50†† 46 182
27.8 33.4 64.4 70 62 195
33.0 39.7 72.3 80 69 201
41.7 50.2 85.4 90 81 212*** — 24.9 25†† 26 184
13.9 16.7 45.8 50†† 45 200
16.5 19.8 49.6 50†† 49 203
27.8 33.4 66.6 70 65 217
33.0 39.7 74.5 80 72 223
41.7 50.2 87.6 90 84 234*** — 17.6 20†† 18 135
2.6
17.0 17.1 39.0 40†† 38 152
34.0 34.1 60.2 70†† 58 169 — 19.4 20†† 20 152
17.0 17.1 40.7 45†† 40 170
34.0 34.1 62.0 70 60 187 — 47.3/ 47.3 50/ 50†† 49/ 49 295/295
7.8/10.4 21.7/ 25.0 74.4/ 78.6 80/ 80 74/ 78 317/320
12.0/16.0 33.3/ 38.5 88.9/ 95.4 90/100 88/ 94 328/334***
24.0/32.0 66.6/ 77.0 130.6/143.6 150/150 126/138 362/372***
31.8/42.4 88.3/102.0 157.7/174.8 175/175 151/167 383/397***
37.6/50.0 104.4/120.3 177.8/167.6 200/175 170/188 399/415*** — 49.0/ 49.0 50/ 50†† 51/ 51 314/314
7.8/10.4 21.7/ 25.0 76.1/ 80.8 80/ 90 76/ 80 336/389***
12.0/16.0 33.3/ 38.5 90.6/ 97.1 100/100 90/ 96 347/353***
24.0/32.0 66.6/ 77.0 132.3/145.3 150/150 128/140 381/391***
31.8/42.4 88.3/102.0 159.4/176.5 175/200 153/169 402/416***
37.6/50.0 104.4/120.3 179.5/169.3 200/200 171/190 418/434*** — 56.5/ 56.5 60/ 60†† 60/ 60 362/362
7.8/10.4 21.7/ 25.0 83.6/ 87.8 90/ 90 85/ 89 384/387***
12.0/16.0 33.3/ 38.5 98.1/104.6 100/110 98/104 395/401***
24.0/32.0 66.6/ 77.0 139.8/152.8 150/175 137/149 429/439***
31.8/42.4 88.3/102.0 166.9/184.0 175/200 162/177 450/464***
37.6/50.0 104.4/120.3 187.0/176.8 200/200 180/198 466/482*** — 23.4 25†† 24 143
16.5 19.8 48.1 50†† 47 163
27.8 33.4 65.1 70 63 176
33.0 39.7 73.0 80 70 183
41.7 50.2 86.1 90 82 193***
50.0 60.1 83.5 90 93 203*** — 24.2 25†† 25 182
16.5 19.8 48.9 50†† 48 202
27.8 33.4 65.9 70 64 216
33.0 39.7 73.8 80 71 222
41.7 50.2 86.9 90 83 233***
50.0 60.1 84.3 90 94 243*** — 28.2 30†† 30 176
16.5 19.8 52.9 60†† 53 196
27.8 33.4 69.9 70 68 210
33.0 39.7 77.8 80 76 216
41.7 50.2 90.9 100 88 227***
50.0 60.1 88.3 100 99 237*** — 18.7 20†† 20 118
17.0 17.1 40.1 45†† 39 135
34.0 34.1 61.4 70 59 152
51.0 51.2 69.9 70 78 169 — 19.4 20†† 20 149
17.0 17.1 40.7 45†† 40 166
34.0 34.1 62.0 70 60 183
51.0 51.2 70.6 80 79 201*** — 22.6 25†† 24 145
17.0 17.1 43.9 45†† 44 162
34.0 34.1 65.2 70 63 179
51.0 51.2 73.8 80 83 196***
FLA MCA MOCP FLA LRA
DISCONNECT
SIZE†
9
Table 3B — Electrical Data (Units With Electrical Convenience Outlet)
VOLTAGE
50TFQ
UNIT SIZE
008
1
/2Ton s)
(7
009
1
(8
/2Ton s)
NOTE: Legend and Notes for Electrical Data are on page 11.
NOMINAL
V-P H- Hz
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
STD 187 254 13.4 91.0 1.4 5.8
HIGH-STATIC 187 254 13.4 91.0 1.4 10.6
STD 414 508 6.7 42.0 0.7 2.6
HIGH-STATIC 414 508 6.7 42.0 0.7 4.8
STD 518 632 5.4 39.0 0.7 2.6
HIGH-STATIC 518 632 5.4 39.0 0.7 4.8
STD 187 254 16.0 137.0 1.4 5.8
HIGH-STATIC 187 254 16.0 137.0 1.4 10.6
STD 414 508 8.3 69.0 0.7 2.6
HIGH-STATIC 414 508 8.3 69.0 0.7 4.8
STD 518 632 6.4 58.0 0.7 2.6
HIGH-STATIC 518 632 6.4 58.0 0.7 4.8
RANGE
Min Max RLA LRA
COMPRESSOR
(each)
OFM
FLA
ELECTRIC
IFM
FLA
HEAT*
Nominal
kW**
43.6/ 43.6 45/ 45†† 46/ 46 234/234
7.8/10.4 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 256/259
12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 267/272***
18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 285/294***
24.0/32.0 66.6/ 77.0 126.8/139.8 150/150 123/135 300/311***
31.8/42.4 88.3/102.0 153.9/171.1 175/175 148/164 322/336*** — 48.4/ 48.4 50/ 50†† 52/ 52 277/277
7.8/10.4 21.7/ 25.0 75.5/ 79.6 80/ 80 77/ 81 299/302***
12.0/16.0 33.3/ 38.5 90.0/ 96.5 90/100 90/ 96 311/316***
18.6/24.8 51.6/ 59.7 112.9/123.0 125/125 111/120 329/337***
24.0/32.0 66.6/ 77.0 131.6/144.6 150/150 128/140 344/354***
31.8/42.4 88.3/102.0 158.7/175.9 175/200 153/169 366/379*** — 21.3 25†† 23 110
13.9 16.7 42.1 45†† 42 127
16.5 19.8 46.0 50†† 45 130
27.8 33.4 63.0 70 61 143
33.0 39.7 70.9 80 68 150
41.7 50.2 84.0 90 80 160*** — 23.5 25†† 25 132
13.9 16.7 44.3 45†† 44 148
16.5 19.8 48.2 50†† 48 151
27.8 33.4 65.2 70 63 165
33.0 39.7 73.1 80 71 171
41.7 50.2 86.2 90 83 182*** — 17.1 20†† 18 99
17.0 17.1 38.5 40†† 38 116
34.0 34.1 59.7 60†† 57 133 — 18.9 20†† 20 116
17.0 17.1 40.2 45†† 40 133
34.0 34.1 61.5 70 59 150 — 49.4/ 49.4 50/ 50†† 52/ 52 326/326
7.8/10.4 21.7/ 25.0 76.5/ 80.7 80/ 90 77/ 81 348/351
12.0/16.0 33.3/ 38.5 91.0/ 97.5 100/100 91/ 96 359/364
18.6/24.8 51.6/ 59.7 113.9/124.0 125/125 112/121 377/386
24.0/32.0 66.6/ 77.0 132.7/145.7 150/150 129/141 392/403
31.8/42.4 88.3/102.0 154.8/176.9 175/200 154/170 414/428 — 54.2/ 54.2 60/ 60†† 58/ 58 369/369
7.8/10.4 21.7/ 25.0 81.3/ 85.5 90/ 90 83/ 86 391/394***
12.0/16.0 33.3/ 38.5 95.8/102.3 100/110 96/102 403/408***
18.6/24.8 51.6/ 59.7 118.7/128.8 125/150 117/126 421/429***
24.0/32.0 66.6/ 77.0 137.5/150.5 150/175 134/146 436/446***
31.8/42.4 88.3/102.0 164.6/181.7 175/200 159/175 458/471*** — 24.9 25†† 26 164
13.9 16.7 45.7 50†† 45 181
16.5 19.8 49.6 50†† 49 184
27.8 33.4 66.6 70 65 197
33.0 39.7 74.5 80 72 204
41.7 50.2 87.6 90 84 214*** — 27.1 30†† 29 186
13.9 16.7 47.9 50†† 48 202
16.5 19.8 51.8 60†† 51 205
27.8 33.4 68.8 70 67 219
33.0 39.7 76.7 80 74 225
41.7 50.2 89.8 90 86 236*** — 19.3 20†† 20 137
17.0 17.1 40.7 45†† 40 154
34.0 34.1 62.0 70 60 171 — 21.1 25†† 22 154
17.0 17.1 42.5 45†† 42 171
34.0 34.1 63.7 70 62 188
FLA MCA MOCP FLA LRA
POWER SUPPLY
DISCONNECT
SIZE†
10
50TFQ
UNIT SIZE
012
(10 Tons)
NOMINAL
V-P H-Hz
208/230-3-60
460-3-60
575-3-60
Table 3B — Electrical Data (Units With Electrical Convenience Outlet) (cont)
VO LTAGE
IFM
TYPE
STD 187 254 17.2 124.0 1.4 5.8
ALT 187 254 17.2 124.0 1.4 7.5
HIGH-STATIC 187 254 17.2 124.0 1.4 15.0
STD 414 508 8.6 59.6 0.7 2.6
ALT 414 508 8.6 59.6 0.7 3.4
HIGH-STATIC 414 508 8.6 59.6 0.7 7.4
STD 518 632 6.9 49.4 0.7 2.6
ALT 518 632 6.9 49.4 0.7 3.4
HIGH-STATIC 518 632 6.9 49.4 0.7 7.4
RANGE
Min Max RLA LRA
COMPRESSOR
(each)
OFM
FLA
ELECTRIC
IFM
FLA
HEAT*
Nominal
kW**
52.1/ 52.1 60/ 60†† 55/ 55 300/300
7.8/10.4 21.7/ 25.0 79.2/ 83.4 80/ 90 80/ 84 322/325***
12.0/16.0 33.3/ 38.5 93.7/100.2 100/110 93/ 99 333/338***
24.0/32.0 66.6/ 77.0 135.4/148.4 150/150 132/144 366/377***
31.8/42.4 88.3/102.0 162.5/179.6 175/200 157/172 388/402***
37.6/50.0 104.4/120.3 182.6/172.4 200/200 175/193 404/420*** — 53.8/ 53.8 60/ 60†† 57/ 57 319/319
7.8/10.4 21.7/ 25.0 80.9/ 85.1 90/ 90 82/ 86 341/344***
12.0/16.0 33.3/ 38.5 95.4/101.9 100/110 95/101 352/357***
24.0/32.0 66.6/ 77.0 137.1/150.1 150/175 134/145 385/396***
31.8/42.4 88.3/102.0 164.2/181.3 175/200 158/174 407/421***
37.6/50.0 104.4/120.3 184.3/174.1 200/200 177/195 423/439*** — 61.3/ 61.3 70/ 70 66/ 66 367/367
7.8/10.4 21.7/ 25.0 88.4/ 92.6 90/100 91/ 94 389/392***
12.0/16.0 33.3/ 38.5 102.9/109.4 110/110 104/110 400/405***
24.0/32.0 66.6/ 77.0 144.6/157.6 150/175 142/154 433/444***
31.8/42.4 88.3/102.0 171.7/188.8 175/200 167/183 455/459***
37.6/50.0 104.4/120.3 191.8/181.6 200/200 186/204 471/487*** — 25.5 30†† 27 145
16.5 19.8 50.3 60†† 50 165
27.8 33.4 67.3 70 65 178
33.0 39.7 75.2 80 73 185
41.7 50.2 88.3 90 85 195***
50.0 60.1 85.6 90 96 205*** — 26.3 30†† 28 185
16.5 19.8 51.1 60†† 51 204
27.8 33.4 68.1 70 66 218
33.0 39.7 76.0 80 73 224
41.7 50.2 89.1 90 86 235***
50.0 60.1 86.4 90 97 245*** — 30.3 35†† 32 179
16.5 19.8 55.1 60†† 55 198
27.8 33.4 72.1 80 71 212
33.0 39.7 80.0 80 78 218
41.7 50.2 93.1 100 90 229***
50.0 60.1 90.4 100 102 239*** — 20.5 25†† 22 120
17.0 17.1 41.8 45†† 41 137
34.0 34.1 63.1 70 61 154
51.0 51.2 71.7 80 80 171*** — 21.1 25†† 22 151
17.0 17.1 42.5 45†† 42 168
34.0 34.1 63.7 70 62 185
51.0 51.2 72.3 80 81 202*** — 24.3 25†† 26 146
17.0 17.1 45.7 50†† 46 163
34.0 34.1 66.9 70 65 180
51.0 51.2 75.5 80 85 198***
FLA MCA MOCP FLA LRA
POWER SUPPLY
DISCONNECT
SIZE†
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps
*Heaters are field installed only.
†Used to determine minimum disconnect size per NEC.
**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If
power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
††Fuse or HACR circuit breaker.
***Optional disconnect swi tch is unavailable.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
LEGEND
%Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB)457–452=5v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum devia tion is 7 v.
Determine percent of voltage imbalance.
%Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
=1.53%
average voltage
7
457
452 + 464 + 455
1371
=
3
= 457
3
11
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate the thermostat assembly on a solid wall in the conditioned space to sense aver­age temperature in accordance with the thermostat installation instructions.
NOTE: If using a Carrier electronic thermostat, set the thermo­stat configuration for “non-heat pump operation.” This family of products does not require an O terminal to energize the reversing valve.
Route the thermostat cable or equivalent single leads of colored wire from the subbase terminals to the low-voltage connections on the unit (shown in Fig. 8A and 8B) as described in Steps 1 through 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
1. If the unit is mounted on the roof curb and the accessory thru-the-curb service plate connection is used, route wire through the connection plate.
2. Pass control wires through the hole provided on the unit (see connection D in Connection Sizes table in Fig. 6).
3. Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the UL required clear­ance between the high-voltage and low-voltage wiring.
4. Connect the thermostat wires to the screw terminals of the low-voltage connector (see Fig. 8A and 8B).
NOTE: If the unit is mounted on a roof curb and electrical power will be run up “thru-the-bottom,” use accessory kit number CRBTMPWR002A01. This kit, available from your local distributor, ensures a watertight seal. Refer to the acces­sory installation instructions for information on power wiring. Refer to Fig. 6 for drilling holes in basepan.
DEFROST BOARD — The defrost board timer cycle is set to 30 minutes. To change the cycle time, turn off power to the unit and install lockout tag. Remove the wire from defrost board connected to the 30 minute quick-connect. See Fig. 10. Connect the wire to the 50 or 90 minute quick-connects on the defrost board, depending on the desired defrost time.
HEAT ANTICIPATOR SETTINGS — For units with electric heat, set heat anticipator settings as shown in Table 4.
Step 6 — Adjust Factory-Installed Options
DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch can be locked in place for safety purposes.
CONTROL
CONNECTION
BOARD
24 VAC
R
RMTOCC
G
CMPSAFE
Y2
FSD
W1
SFS
NOT USED
C
C
X
X
Fig. 8B — Low Voltage Connections
(Units with PremierLink™ Controls)
THERMOSTAT CONTROL
CONNECTION
BOARD
R
Y1
Y2
W1
W2
G
C
R
Y1
Y2
W1
W2
G
C
X
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS ON
OFF
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
A
B
Field Wiring
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
C
LEGEND
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
Fig. 8A — Low-Voltage Connections With or
Without Economizer or Two-Position Damper
DISCONNECT BOARD
DISCONNECT SWITCH (OPTIONAL)
RACEWAY
COMPRESSOR NO. 2
CONVENIENCE OUTLET
HOLE IN END PANEL
COMPRESSOR NO. 1
Fig. 9 — Typical Field Control Wiring Raceway
12
Table 4 — Heat Anticipator Settings
UNIT
50TFQ
*kW is based on 240, 480, or 575 v.
Heater
kW*
10.4, 16.0 0.3 NA NA
24.8, 32.0 0.6 0.3 0.3
42.4, 50.0 0.9 0.6 0.3 41.7, 50.0 0.6 0.3 0.3 51.0 0.6 0.3 0.3
208/230 460 575
1-Stage
Configuration
2-Stage
Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2
Heater
kW*
13.9, 16.5
27.8, 33.0
CONVENIENCE OUTLET — An optional convenience out­let provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit dis­connect is off. Adjacent unit outlets may be used for service tools. An optional “Hot Outlet” is available from the factory as a special order item.
NOVAR CONTROLS — Optional Novar controls (ETM 3051) are available for replacement or new construction jobs.
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit (for shipping).
Assembly:
1. Determine the amount of ventilation required for build­ing. Record the amount for use in Step 8.
2. Remove the filter access panel by raising the panel and swinging it outward. The panel is now disengaged from the track and can be removed. No tools are required to re­move the filter access panel. Remove the outdoor-air opening panel. Save the panels and screws. See Fig. 11.
3. Separate the hood and screen from the basepan by remov­ing the screws and brackets securing them. Save all screws and discard the brackets.
4. Replace the outdoor air opening panel.
5. Place the hood on the front of the outdoor air opening panel. See Fig. 12 for hood details. Secure the top of the hood with the 6 screws removed in Step 3. See Fig. 13.
6. Remove and save the 8 screws (4 on each side) from the sides of the manual outdoor-air damper.
7. Align the screw holes on the hood with the screw holes on the side of the manual outdoor-air damper. See Fig. 12 and 13. Secure the hood with the 8 screws from Step 6.
8. Adjust the minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 11. Slide the blade vertically until it is in the appropriate position determined by Fig. 14. Tighten the screws.
9. Remove and save the screws currently on the sides of hood. Insert the screen. Secure the screen to the hood using the screws. See Fig. 13.
10. Replace the filter access panel. Ensure that the filter access panel slides along the tracks and is securely engaged.
UNIT VOLTAGE
Configuration
1-Stage
0.3 NA NA 17.0, 34.0 0.3 NA NA
2-Stage
Heater
kW*
1-Stage
Configuration
2-Stage
Fig. 10 — Defrost Board
FILTER ACCESS PANEL
OUTDOOR AIR OPENING PANEL
SCREWS (SIDE)
MANUAL OUTDOOR-AIR ADJUSTMENT SCREWS
DAMPER BLADE
Fig. 11 — Damper Panel with Manual
Outdoor-Air Damper Installed
13
Fig. 12 — Outdoor-Air Hood Details
SCREW HOLES (TOP)
HOOD
HOOD SCREEN LOCATION (SCREEN NOT SHOWN)
Fig. 13 — Optional Manual Outdoor-Air
Damper with Hood Attached
PREMIERLINK™ CONTROL — The PremierLink control­ler is compatible with Carrier Comfort Network® (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Carrier’s diag­nostic standard tier display tools such as Navigator™ module or Scrolling Marquee can be used with the PremierLink controller.
The PremierLink controller (see Fig. 15A and 15B) requires a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). Re­fer to Fig. 16. The PremierLink control may be mounted in the control panel or an area below the control panel.
NOTE: PremierLink versions 1.3 and later are shipped in Sen­sor mode. If used with a thermostat, the PremierLink control must be configured to Thermostat mode.
The PremierLink control includes a supply-air temperature sensor (SAT) and an outdoor-air temperature sensor (OAT) as standard. An indoor-air quality (CO
) sensor can be added as
2
an option. Refer to Table 5 for sensor usage. Install the Supply Air Temperature (SAT) Sensor
—When the unit is supplied with a factory-mounted PremierLink con­trol, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factory-supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening.
The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a
1
/2-in. hole in the flange or duct. Use two field­supplied, self-drilling screws to secure the sensor probe in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure that the probe tip does not come in contact with any of the unit or heat surfaces.
Outdoor Air Temperature (OAT) Sensor
— When the unit is supplied with a factory-mounted PremierLink control, the outdoor-air temperature (OAT) sensor is factory-supplied and wired.
Install the Indoor Air Quality (CO optional indoor air quality (CO
)Sensor — Mount the
2
) sensor according to manufac-
2
turer specifications.
A separate field-supplied transformer must be used to pow-
er the CO
Wire the CO
sensor.
2
sensor to the COM and IAQI terminals of J5
2
on the PremierLink controller. Refer to the PremierLink Instal­lation, Start-up, and Configuration Instructions for detailed wiring and configuration information.
Fig. 14 — Outdoor Air Damper Position Setting
14
Table 5 — PremierLink™ Sensor Usage
APPLICATION
Dry Bulb
Temperature with
PremierLink™*
(PremierLink
requires4-20mA
Actuator)
Differential Dry Bulb
Temperature with
PremierLink* (PremierLink
requires4-20mA
Actuator)
Single Enthalpy with
PremierLink* (PremierLink
requires4-20mA
Actuator)
Differential Enthalpy
with PremierLink*
(PremierLink
requires4-20mA
Actuator)
*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and
Outdoor Air Temperature Sensor HH79NZ017 — Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO
Sensors (Optional):
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO2room sensor with override. 33ZCT56CO2 — Space temperature and CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — 50HJ540569 — Opens at 67 F, closes at 52 F, not adjustable. Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor HH79NZ017) Compressor Lockout Sensor — 50HJ540570 — Opens at 35 F, closes at 50 F.
OUTDOOR AIR
TEMPERATURE SENSOR
Included —
HH79NZ017
Included —
HH79NZ017
Included —
Not Used
Included —
Not Used
room sensor with override and set point.
2
2
RETURN AIR
TEMPERATURE SENSOR
———
Required —
33ZCT55SPT
or Equivalent
room sensor.
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
——
Required —
HH57AC077
Required —
HH57AC077
Required —
HH57AC078
Fig. 15A — PremierLink Controller
15
PREMIERLINK CONTROL
HINGED DOOR PANEL
PREMIERLINK COVER
Fig. 15B — PremierLink™ Controller (Installed)
OAT
PNK
VIO
YEL
BLU
BLK
RED
BLU
YEL
WHT
7
7
6
6
11
11
10
10
8
8
2
2
3
3
4
4
1
1
5
5
9
9
12
12
TR
SR
2
OUTDOOR AIR
ENTHALPY SENSOR
Economi$er2
4 - 20mA
RED
BRN
PNK
VIO
Power Exhaust/Energy Recycler
GRA
ORN
PNK
TR1
+
3
RED
SAT
Space Temp./ Set
Point Adjustment
Quality Sensor
Quality Sensor
GRAY
GRAY
BLK
S
RETURN AIR
ENTHALPY
SENSOR
BLK
RED
Indoor Air
Outdoor Air
CMPSAFE
TB-2
1
2
3
4
5
6
7
8
BLU
BRN
BLK
BRN
RED
BRN
BLU
ORN
TB-3
RMTOCC
1
GRN
2
Com
SFS
FSD
CCN
3
4
5
6
7
m.
BLU
WHT
PNK
RED
WHT
8
+
COMMS — Communications OAT Outdoor Air Temperature Sensor PWR Power SAT Supply Air Temperature Sensor
YEL
BLK
VIO
BRN
BRN
ORN
RED
BLU
GRA
LEGEND
BLK
PNK
BRN
BRN
GRN
YEL
BLU
WHT
PNK
BLU
GRA
GRA
PNK
BLK
ANAL OG
0-20mAIN
DISCRETE
PWR
BRN
J6
J5
J4
J1
Fig. 16 — Typical PremierLink Controls Wiring
J2
COMMS
RED
BRN
J9
0-20 mA
TB-1
1
2
Y1
3
Y2
W1
4
5
W2
6
7
8
RTU Terminal
Board
HK50AA0
39
PremierLink
J7
PP/MP
WHT
GRA
R
RED
GRA
ORN
ORN
PNK
G
WHT
C
X
Relays
J8
PNK
ORNORN
ORN
RED
16
Enthalpy Sensors and Control
— The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the economizer damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink™ controller. Locate the controller in place of an existing econo­mizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.
A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Outdoor Air Enthalpy Sensor/Enthalpy Controller (HH57AC077) — To wire the outdoor air enthalpy sensor, perform the following (see Fig. 17 and 18):
NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.
1. Use a 4-conductor, 18 or 20 AWG cable to connect the enthalpy control to the PremierLink controller and power transformer.
2. Connect the following 4 wires from the wire harness located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TR1)
on enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal
(TR) on enthalpy sensor and to pin 4 on 12-pin harness.
c. Connect the GRAY/ORN wire to J4-2 on Premier-
Link controller and to terminal (3) on enthalpy sensor.
d. Connect the GRAY/RED wire to J4-1 on Premier-
Link controller and to terminal (2) on enthalpy sensor.
NOTE: If installing in a Carrier rooftop, use the two gray wires provided from the control section to the economizer to connect PremierLink controller to terminals 2 and 3 on enthalpy sensor.
If NOT using Carrier equipment, wires may need to be field
supplied and installed. Return Air Enthalpy Sensor
— Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). The outdoor enthalpy changeover set point is set at the controller.
To wire the return air enthalpy sensor, perform the follow-
ing (see Fig. 17):
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.
2. At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.
ENTHALPY CONTROLLER
B
TR TR1
C
A
D
LED
NOTES:
1. Remove factory-installed jumper across SR and + before con­necting wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in out­door airstream.
SO
SR
+
+
3
2
1
RED BRN
BLK
RED
GRAY/ORN
GRAY/RED
WIRE HARNESS IN UNIT
(OUTDOOR
S
AIR
+
ENTHALPY
SENSOR)
S
(RETURN AIR
ENTHALPY
+
SENSOR)
Fig. 17 — Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
HH57AC077 ENTHALPY CONTROL AND
BRACKET
HH57AC078 ENTHALPY SENSOR (USED WITH ENTHALPY CONTROL FOR DIFFERENTIAL ENTHALPY OPERATION)
MOUNTING PLATE
OUTDOOR AIR ENTHALPY SENSOR
C7400A1004
+
Fig. 18 — Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
17
Loading...
+ 39 hidden pages