• Commercial duty motors with
permanently lubricated bearings
• Standard cooling operation at
outdoor ambient temperatures as
low as –4 C (25 F)
• Meets ASHRAE Standard 62
(Indoor Air Quality)
50TFF007
50TFF008-014
Features/Benefits
Compact, vertical discharge
units convert to horizontal
discharge, combining
installation flexibility with
efficient performance and
easy maintenance.
Easy installation and
conversion
All units are shipped in the vertical discharge configuration for fit-up to
standard roof curbs. (Two different curb
sizes fit unit sizes 007 and 008-014.)
The contractor can order and install the
roof curb early in the construction
stage, before decisions on size requirements are made.
All units feature roll-formed baserail
design with forklift slots on 3 sides and
rigging holes for easier maneuvering.
Durable packaging protects all units
during shipment and storage.
The units can be easily converted
from a vertical to a horizontal
discharge configuration by interchanging the panels supplied with the unit.
Copyright 2000 Carrier CorporationForm 50TFF-C1PD
Page 2
All units feature a non-corrosive
sloped condensate drain pan in accordance with ASHRAE (American Society of Heating, Refrigeration and Air
Conditioning Engineers) Standard 62.
Also, the sloped condensate pan on
units permits either an external side
condensate drain (outside the roof curb)
or an internal bottom drain (inside the
roof curb). Both options require fieldsupplied P-trap.
In addition, the 50TFF units have a
standard filter access door, which permits tool-less filter changes.
Field-installed electric heaters are
available in a wide range of capacities.
Single point wiring kit makes installation simple.
Simple electrical connections
Terminal boards, located in the base
unit control box, facilitate connections
to room thermostat, outdoor thermostat(s), economizer, and electric heat.
Service panels are quickly removed,
permitting easy servicing.
Thru-the-bottom service connection
capability and thru-the-curb service
connections accessory allows power
and control wiring to be routed through
the unit basepan or curb, minimizing
roof penetrations. Both power and
control connections are made on the
same side of the unit to simplify installation. In addition, color-coded wires
permit easy tracing and diagnostics.
Proven compressor reliability
Design techniques feature computerprogrammed balance between compressor, condenser, and evaporator.
Carrier-specified hermetic compressors are equipped with compressor
overcurrent and overtemperature protection to ensure dependability.
The 50TFF units have Carrier’s exclusive Acutrol™ metering device which
precisely controls refrigerant flow,
preventing slugging and flood-back,
while maintaining optimum unit
performance.
Carrier’s exclusive Acutrol metering
device precisely controls refrigerant
flow, preventing slugging and floodback, while maintaining optimum unit
performance.
Durable, dependable
construction
Designed for durability in any climate,
the weather-resistant cabinets are
manufactured using pre-painted steel.
The cabinet is constructed of galvanized steel and bonderized, and all exterior panels are coated with a prepainted baked enamel finish. The paint
finish is non-chalking, and is capable of
withstanding Federal (U.S.A.) Test
Method Standard ASTM B117
500-hour salt spray test. All internal
cabinet panels are primed, permitting
longer life and a more attractive appearance for the entire unit. In addition, the 50TFF units are designed with
a single, continuous top piece to eliminate any possible leaks. Totally enclosed condenser-fan motors and permanently lubricated bearings provide
additional unit dependability.
Integrated economizers and
outdoor air
During a first stage call for cooling, if
the outdoor-air temperature is below
the control set point, the supply-air
sensor modulates the economizer outdoor-air damper open to achieve the
set point. When second-stage cooling is
called for, the compressor is energized
in addition to the economizer. If the
outdoor-air temperature is above the
set point, the first stage of compression
is activated and the economizer stays at
minimum vent position. Economizer
operation is controlled by Accusensor™
I dry-bulb thermostat that senses
outdoor-air temperature. Accessory upgrade kits include solid-state enthalpy
control and differential enthalpy sensor.
The Durablade economizer has a reliable sliding plate damper which is easily adjusted for 100% outdoor air,
100% return air, or any proportions of
mixed air.
The 50TFF units also utilize the optional field or factory-installed
EconoMi$er. This newly designed
EconoMi$er incorporates a
parallel-opposed blade design. In
addition, the EconoMi$er has a spring
return built into the damper motor to
provide reliable close-on-power-loss.
The EconoMi$er comes equipped with
up to 100% barometric relief capability
for high outdoor airflow applications.
In addition, the EconoMi$er barometric relief damper or integrated power exhaust accessory can be utilized to
help maintain proper building pressure.
Quiet, efficient operation and
dependable performance
Compressors have vibration isolators
for extremely quiet operation. Efficient
fan and motor design permits operation at very low sound levels, and all
008-014 units are mounted on a special polycore plate.
The 50TFF008-014 units offer high
energy efficiency and lower utility costs
through part load operation using
2 stages of cooling.
Quiet and efficient operation is
provided by belt-driven evaporator fans
(standard). The belt-driven evaporatorfan motor allows adjustment to available static pressure to meet the job requirements of even the most demanding applications.
Increased operating efficiency is
achieved through computer-designed
coils featuring staggered copper tubes.
Fins are ripple-edged for strength,
lanced, and double waved for higher
heat transfer.
Carrier Apollo controls add
reliability, efficiency, and
simplification
The direct digital controls are ordered
as a factory-installed option. Designed
and manufactured exclusively by
Carrier, the controls can be used to actively monitor and control all modes of
operation, as well as to monitor
evaporator-fan status, filter status
indoor-air quality (humidity and carbon
dioxide), supply-air temperature, and
outdoor-air temperature.
The Apollo communicating control is
factory-installed into the rooftop unit
evaporator-fan section (007) or unit
control box (008-014), and comes
equipped with built-in diagnostic capabilities. Light-emitting diodes (LEDs)
simplify troubleshooting by indicating
thermostat commands for both stages
of heating and cooling, evaporator-fan
operation, and economizer operation.
The Apollo communicating control is
designed to work specifically with the
Carrier TEMP and VVT® (variable vol-
ume and temperature) thermostats.
The Apollo control combined with
Carrier thermostats incorporate a
5-minute recycle delay timer between
modes of operation to prevent short
cycling.
The standard rooftop control system
is readily adaptable to all conventional
and programmable thermostats. In addition, units with Apollo controls are
suitable for integration into building
monitor control systems if required.
This system gives the 50TFF units the
flexibility to communicate with almost
any thermostat or building control
system.
Indoor-air quality begins with
Carrier rooftops
Sloped condensate pans minimize biological growth in rooftop units in accordance with ASHRAE Standard 62.
Standard 51 mm (2-in.) filters with
optional dirty filter indicator switch provide for greater particle reduction in the
Model number nomenclature
return air. The face-split evaporator
coils improve the dehumidification capability of the standard units, and
standard enthalpy controls provided
with the optional or accessory economizers maximize building humidity
control. The 50TFF units also have an
accessory, 100% open, two-position
damper to meet all your fresh outdoor
air requirements.
For units without economizer, yearround ventilation is enhanced by a
manual outdoor-air damper (ordered as
an accessory or an option on 50TFF
units). The damper can be preset to admit up to 50% outdoor air.
Motor BkW...r/s.25...16.0.19...15.5.19...15.5.19...15.5.19...15.5
EVAPORATOR COIL
Rows...Fins/m4...5903...5903...5903...5904...590
Total Face Area (sq m)0.510.740.740.931.03
EVAPORATOR FANCentrifugal Type
Quantity...Size (mm x mm)1...254 x 2541...381 x 3811...381 x 3811...381 x 3811...381 x 381
Type DriveBeltBeltBeltBeltBeltNominal L/s11301230142017001980
Motor kW1.121.121.121.502.24
Maximum Continuous BkW1.791.791.791.792.76
Motor Frame Size5656565656Nominal r/s High/Low— ————
Fan r/s Range15.50-20.0810.33-14.6710.33-14.6711.50-15.0011.83-14.83
Motor Bearing TypeBallBallBallBallBall
Maximum Allowable r/s35.026.726.726.726.7
Motor Pulley Pitch Diameter Min/Max (mm)71/9761/8671/9771/97102/127Nominal Motor Shaft Diameter (mm)1616161622
Fan Pulley Pitch Diameter (mm)114178178178203Nominal Fan Shaft Diameter (mm)— 25252525
Belt, Quantity...Type...Length (mm)1...A...10921...A...12451...A...12451...A...12451...A...1321
Pulley Center Line Distance (mm)373-394425-489425-489403-445403-445
Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting5 5555
Factory Speed Setting (r/s)15.5010.3310.3311.5011.83
Fan Shaft Diameter at Pulley (mm)1625252525
HIGH-PRESSURE SWITCH (kPa)
Standard Compressor Internal Relief
(Differential)
Cutout2951
Reset (Auto.)2206
LOW-PRESSURE SWITCH (kPa)
Cutout48 ± 21
Reset (auto.)152 ± 48
FREEZEPROTECTION THERMOSTAT
Opens (C)–1
Closes (C)7
OUTDOOR-AIR INLET SCREENSCleanable
Quantity...Size (mm)1...508 x 610 x 25
RETURN-AIR FILTERSThrowaway
Quantity...Size (mm)2...406 x 635 x 51 4...406 x 508 x 51 4...406 x 508 x 51 4...508 x 508 x 51 4...508 x 508 x 51
LEGEND*Evaporator coil fins/condenser coil fins.
Al— Aluminum
Bhp — Brake Horsepower
BkW — Fan Input Watts x Motor Efficiency
Cu— Copper
Rows...Fins/in.4...153...153...153...154...15
Total Face Area (sq ft)5.58.08.010.011.1
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)1...10 x 101...15 x 151...15 x 151...15 x 151...15 x 15
Type DriveBeltBeltBeltBeltBeltNominal Cfm20002600260035004200
Motor Hp1
Maximum Continuous Bhp2.402.402.402.403.70
Motor Frame Size5656565656
1
/
2
Fan Rpm Range930-1205620-880620-880690-900710-890
Motor Bearing TypeBallBallBallBallBall
Maximum Allowable Rpm21001600160016001600
Motor Pulley Pitch Diameter Min/Max (in.)2.8/3.82.4/3.42.8/3.82.8/3.84.0/5.0Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)4.57.07.07.08.0
5
/
8
Nominal Fan Shaft Diameter (in.)—— —— —
Belt, Quantity...Type...Length (in.)1...A...401...A...491...A...491...A...491...A...52
Pulley Center Line Distance (in.)14.7-15.516.75-19.2516.75-19.2515.85-17.5015.85-17.50
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
8050505044
55 55 5
Factory Setting55 55 5
Factory Speed Setting (rpm)930620620690710
Fan Shaft Diameter at Pulley (in.)
5
/
8
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
(Differential)
500 ± 50450 ± 50500 ± 50
Cutout428
Reset (Auto.)320
LOW-PRESSURE SWITCH (psig)
Cutout7±3
Reset (Auto.)22 ± 7
FREEZEPROTECTION THERMOSTAT
Opens30 ± 5
Closes45 ± 5
OUTDOOR-AIR INLET SCREENSCleanableCleanable
Quantity...Size (in.)1...20 x 24 x 1
RETURN-AIR FILTERSThrowaway
Quantity...Size (in.)2...16 x 25 x 24...16 x 20 x 24...16 x 20 x 24...20 x 20 x 24...20 x 20 x 2
LEGEND*Evaporator coil fins/condenser coil fins.
Al— Aluminum
Bhp — Brake Horsepower
BkW — Fan Input Watts x Motor Efficiency
Cu— Copper
3
/8-in., Enhanced Copper Tubes, Aluminum Lanced Fins
1
/4...930
11/
5
/
2
8
1
/4...930
11/
5
/
1
/4...930
2
8
23
5
/
8
1
/4...930
7
/
8
111 1
1...20 x 25 x 1
1...16 x 25 x 1
†Requires the accessory/optional controls upgrade kit.
NOTE: The 50TFF007-014 units have a loss-of-charge/low-pressure
switch (accessory) located in the liquid line.
5
Page 6
Options and accessories
ITEMOPTION*ACCESSORY†
Apollo Communicating ControlsXDisconnect SwitchX
EconoMi$erXX
EconoMi$er with Power ExhaustX
Power Exhaust for EconoMi$erXDurablade Integrated Economizer (Includes Hood)XX
Manual Outdoor-Air DamperX
Condenser Coil GrilleX
Electric HeatX
Electronic Programmable ThermostatX25% Open Two-Position DamperX
100% Open Two-Position DamperX
Roof Curbs (Vertical and Horizontal Discharge)X
Thermostats and SubbasesX
Motormaster® I Head Pressure Control (Speed Control)X
Motormaster II Head Pressure Control (Fan Cycling)X
Time Guard® II Control CircuitX
Thru-the-Bottom Service ConnectionsX
Thru-the-Curb Service ConnectionsX
Accusensor™ II Enthalpy ControlX
Accusensor III Enthalpy SensorX
Condenser Coil Hail Guard AssemblyX
Fan/Filter StatusX
Salt Spray Protection Grille (008-014)XLogo KitX
Outdoor-Air Enthalpy Sensor (EconoMi$er)X
Return-Air Enthalpy Sensor (EconoMi$er)X
Return-Air Temperature Sensor (EconoMi$er)X
Indoor-Aair Quality (CO
*Factory installed.
†Field installed.
) Sensor (EconoMi$er)X
2
HEAD PRESSURE CONTROL
The 50TFF007-014 standard units are designed to operate in cooling at
outdoor temperatures down to –3.8 C (25 F). With accessory Motormaster control (condenser fan speed modulation) or Motormaster II control
(condenser fan cycling) units can operate at outdoor temperatures down
to –17.8 C (0° F). The head pressure controls, which mount in the condenser section, control the condenser-fan motor to maintain correct condensing temperature. Refer to product ordering or contact your local
Carrier representative for appropriate accessory combinations for
desired outdoor ambient temperature operation.
6
Motormaster II Control
(007-014)
Motormaster I Control
(007-014)
Page 7
ELECTRONIC PROGRAMMABLE THERMOSTAT
Carrier’s electronic programmable thermostat provides efficient temperature control by allowing you to program heating
and cooling setbacks and setups with provisions for weekends
and holidays. Accessory remote sensing package is also available to provide tamperproof control in high traffic spaces. Used
in conjunction with factory-installed Apollo control, this thermostat provides a 5-minute recycle timer between modes of operation for short-cycle protection.
THERMOSTAT
H
C
Zone thermostat (24 v) provides one- or 2-stage
cooling for control of unit. Matching subbases are
available with or without tamperproof switches and
automatic changeover.
TIME GUARD® II CONTROL
Time Guard II control automatically prevents compressor from restarting for at least 5 minutes after
a shutdown. Accessory prevents short cycling of
compressor if thermostat is changed rapidly. Time
Guard II control mounts in the control compartment
of unit.
DURABLADE ECONOMIZER
Exclusive Durablade economizer damper design saves
energy while providing economical and reliable cooling. A
sliding plate on the face of the economizer controls the
amount of outdoor air entering the system. Closed, it provides a leakproof seal which prevents ambient air from seeping in or conditioned air from seeping out. It can be adjusted
easily for 100% outdoor air or any proportions of mixed air.
Like the base unit, the economizer is converted easily for horizontal discharge applications.
7
Page 8
Options and accessories (cont)
MINIMUM
POSITION
OPEN
3
1
T
P
P1
T1
4
2
5
S
S
O
D
C
TR
B
REV
.B
198
818A
%
H
U
M
I
D
I
T
Y
90
70
60
30
10
D
C
B
A
60
65
70
75
55
50
85
80
D
A
M
P
E
R
D
A
M
P
E
R
C
L
O
S
E
D
O
P
E
N
OUTDOORTEMP
.
°
F
REV
.
97-3672
CW
–SETPOINTS
–CCW
C
O
N
T
A
C
T
S
S
H
O
W
N
IN
H
IG
H
E
N
T
H
A
L
P
Y
RUSHA
T24V
AC
3mA
MIN.
A
T1
1VDC
C
O
N
T
A
C
T
R
A
T
IN
G
S
:
1
.5
A
R
U
N
,
3
.5
A
IN
O
R
U
N
P
O
W
E
R
E
D
S
T
A
T
E
1
2
3
TR
T
R
1
24V
AC
ENTHALPYCONTROL
+
ACCUSENSOR™ II
CONTROL
ACCUSENSOR III
SENSOR
Accusensor economizer controls help provide efficient, economical
economizer operation. Accusensor II solid-state enthalpy control
includes the logic and one sensor to calculate both dry- and wetbulb of the outdoor air to provide an accurate enthalpy reading on. It
then decides when to energize the economizer based on this reading. A second Accusensor III sensor compares outdoor temperature
and humidity to return-air temperature and humidity and determines
the most economical mixture of air (purchased in addition to first
solid-state enthalpy sensor for differential enthalpy sensing).
FACTORY-INSTALLED APOLLO
COMMUNICATING CONTROLS
The Apollo direct digital controls are designed exclusively by
Carrier, and are used to actively monitor and control all modes of
operation as well as to monitor evaporator-fan status, filter status,
supply-air temperature, outdoor-air temperature, and indoor-air
quality. They are designed to work in conjunction with Carrier
TEMP and VVT® system thermostats.
ELECTRIC HEATER
ECONOMI$ER
ECONOMI$ER
PLUG
ACTUATOR
OUTDOOR AIR
TEMPERATURE
SENSOR
Factory-installed EconoMi$er utilizes a microprocessor-based control, gear drive damper system, low pressure drop characteristics,
built-in spring return (for close upon power loss), and an integral
barometric damper.
NOTE: EconoMi$er is only available for vertical ductwork applications and can be field or factory installed.
CONTROLLER
BAROMETRIC
RELIEF DAMPERS
GEAR-DRIVEN
DAMPER
Electric heaters are available in a wide range
of capacities for factory or field installation.
CONNECTION SIZES
A 13/8″ Dia. [35] Field Power Supply Hole
B 2″ Dia. [51] Power Supply Knockout
C 21/2″ Dia. [64] Power Supply Knockout
D7/8″ Dia. [22] Field Control Wiring Hole
E3/4″− 14 NPT Condensate Drain
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units field-supplied flanges should be attached to horizontal discharge openings, and all
ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb) 1 inch. Bottom of base rail to com-
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC.
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in Note
5a, b, and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering
material if set on base rail.
8. The vertical center of gravity is 1′-6″ [457]
up from the bottom of the base rail.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches, on horizontal discharge units with
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil as stated in Notes 5a, b, and c, a removable
fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.
8. The vertical center of gravity is 1′-71/2″ [495] for 008 and 009, 2′-0″ [610] for 012 and 014 up from the
bottom of the base rail.
CORNER
WEIGHT
(C)
electric heat 1 in. clearance to ductwork for 1 ft.
clearance is optional.
NEC.
CORNER
WEIGHT
(D)
BOTTOM POWER CHART, THESE HOLES REQ’D
FOR USE WITH ACCESSORY PACKAGES —
THREADED
*Select either3/4″ or 11/4″ for power, depending on wire
5. Attach ductwork to curb (flanges of duct
rest on curb).
D
ALT DRAIN HOLE
13/4″
[44.5]
“E”
GAS
3
/4″
[19] NPT
1
/2″
[12.7] NPT
3
/4″
[19] NPT
“F”
POWER
3
/4″ [19] NPT
1
1
/4″ [31.7]
NPT
3
/4″ [19] NPT
11/4″ [31.7]
NPT
6. Service clearance 4 ft on each side.
7.Direction of airflow.
8. Connector packages CRBTMPWR001A00
and 002A00 are for thru-the-curb connections. Packages CRBTMP003A00 and
004A00 are for thru-the-bottom connections.
8. Connector packages CRBTMPWR001A00 and
002A00 are for thru-the-curb connections.
Packages CRBTMP003A00 and 004A00 are
for thru-the-bottom connections.
Enter the 50TFF012 Cooling Capacities table on
page 18 at condenser entering temperature of
36 C, evaporator-air entering at 1520 L/s, 26.7 C
db and 20 C wb. The 50TFF012 unit will provide
cooling capacity of 30.1 kW and a sensible heat
capacity of 21.2 kW. For evaporator-air temperature other than 26.7 C edb, calculate sensible heat
capacity correction, as required, using the formula
found in the notes following the Cooling Capacities
table on page 19.
NOTE: Unit ratings are gross capacities and do not
include the effect of evaporator-fan motor (IFM)
heat. To calculate net capacities, see Step V.
III. Select electric heat:
Heating load required is 18 kW.
Enter the Electric Heating Capacities table (page 33)
for the 50TFF012 at 400-3-50. The 19.3 kW
heater at 400 v most closely satisfies the heating
required.
IV. Determine fan speed and power require-
ments at design conditions.
Before entering the Fan Performance tables, calculate the total static pressure required based on unit
components. From the given and the Pressure Drop
tables (page 33), find:
External static pressure 300 Pa
Economizer 9 Pa
Electric Heat 14 Pa
Total static pressure 323 Pa
Enter the Fan Performance table for the 50TFF012
vertical discharge unit on page 23. Find the fan r/s
and kilowatts at 323 Pa and 1520 L/s. Note that
the fan speed is 14.5 r/s and power required is
1.56 kW (interpolation required). The standard
motor will adequately handle the job requirements.
V. Determine net capacities.
Capacities are gross and do not include the effect of
evaporator-fan motor heat. Use IFM kW from Fan
Performance table on page 23.
Determine net cooling capacity as follows:
Net capacity = gross capacity – IFM kW
= 30.1 kW – 1.56 kW
= 28.5 kW
Net sensible capacity = 21.2 kW – 1.56 kW
= 19.6 kW
Determine net heating capacity as follows:
Net capacity = gross capacity + IFM heat
= 19.3 kW + 1.56 kW
= 24.9 kW
13
Page 14
Selection procedure (with 50TFF012 example) —
English
Enter the 50TFF012 Cooling Capacities table on
page 21 condenser entering temperature of 95 F,
evaporator-air entering at 3200 cfm, 80 F db and
67 F wb. The 50TFF012 unit will provide cooling
capacity of 102,500 Btuh and a sensible heat
capacity of 76,000 Btuh. For evaporator-air temperature other than 80 F edb, calculate sensible
heat capacity correction, as required, using the formula found in the notes following the Cooling
Capacities table on page 21.
NOTE: Unit ratings are gross capacities and do not
include the effect of evaporator-fan motor (IFM)
heat. To calculate net capacities, see Step V.
III. Select electric heat:
Heating load required is 62,000 Btuh.
62,000 Btuh
3413 Btuh/kW
= 18.2 kW of heat required
IV. Determine fan speed and power require-
ments at design conditions.
Before entering the Fan Performance tables, calculate the total static pressure required based on unit
components. From the given and the Pressure Drop
tables (page 33) find:
External static pressure 1.10 in. wg
Economizer 0.04 in. wg
Electric Heat 0.06 in. wg
Total static pressure 1.20 in. wg
Enter the Fan Performance table for the 50TFF012
vertical discharge unit on page 27. Find the fan rpm
and watts at 1.20 in. wg and 3200 cfm. Note that
the fan speed is 844 rpm and power required is
1430 watts. The standard motor will adequately
handle the job requirements.
V. Determine net capacities.
Capacities are gross and do not include the effect of
evaporator-fan motor heat. Use IFM Watts from Fan
Performance table on page 27.
Determine net cooling capacity as follows:
Net capacity = gross capacity – IFM Watts
= 102,500 Btuh – 1430 Watts x 3.413
= 102,500 Btuh – 4881 Btuh
= 97,619 Btuh
Net sensible capacity = 76,000 Btuh – 4881 Btuh
= 71,119 Btuh
Determine net heating capacity as follows:
Net Capacity= gross capacity + IFM heat
= 65,871 + 4881
= 70,752 Btuh
Btuh
Watts
Enter the Electric Heating Capacities table (page 33)
for the 50TFF012 at 400-3-50. The 19.3 kW
heater at 400 v most closely satisfies the heating
required.
1. Ratings are gross, and do not account for the effects of the
evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of cooling capacities as follows:
Corrected SHC
= SHC + [1.23 x 10–3x(1–BF)x(Cdb– 26.7) x L/s]
Observe the rule of sign. Above 26.7 C, SHC correction will be posi-
tive; add it to SHC. Below 26.7 C, SHC correction will be negative;
subtract it from SHC.
kW
4. Formulas:
SHC
x 1000
kW
C
ldb=Cedb
Leaving wet bulb = wet bulb temperature corresponding to enthalpy
of air leaving coil (h
h
lwb=hewb
Where h
–
1.23 x L/s
).
lwb
TC
x 1000
kW
–
1.20 x L/s
is enthalpy of air entering evaporator coil (kJ/kg).
1. Ratings are gross, and do not account for the effects of the
evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of cooling capacities as follows:
Corrected SHC
= SHC + [1.23 x 10–3x(1–BF)x(Cdb– 26.7) x L/s]
Observe the rule of sign. Above 26.7 C, SHC correction will be posi-
tive; add it to SHC. Below 26.7 C, SHC correction will be negative;
subtract it from SHC.
kW
4. Formulas:
SHC
x 1000
kW
C
ldb=Cedb
Leaving wet bulb = wet bulb temperature corresponding to enthalpy
of air leaving coil (h
h
lwb=hewb
Where h
–
1.23 x L/s
).
lwb
TC
x 1000
kW
–
1.20 x L/s
is enthalpy of air entering evaporator coil (kJ/kg).
1. Ratings are gross, and do not account for the effects of the
evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of cooling capacities as follows:
Corrected SHC
= SHC + [1.23 x 10–3x(1–BF)x(Cdb– 26.7) x L/s]
Observe the rule of sign. Above 26.7 C, SHC correction will be posi-
tive; add it to SHC. Below 26.7 C, SHC correction will be negative;
subtract it from SHC.
kW
4. Formulas:
SHC
x 1000
kW
C
ldb=Cedb
Leaving wet bulb = wet bulb temperature corresponding to enthalpy
of air leaving coil (h
h
lwb=hewb
Where h
–
1.23 x L/s
).
lwb
TC
x 1000
kW
–
1.20 x L/s
is enthalpy of air entering evaporator coil (kJ/kg).
LEGEND AND NOTES FOR COOLING CAPACITY TABLES — ENGLISH
LEGEND
BF— Bypass Factor
Edb — Entering Dry Bulb Temperature (F)
Ewb — Entering Wet Bulb Temperature (F)
kW— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh)
TC— Total Capacity (1000 Btuh)
NOTES:
1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 80 F db temperature of air entering the unit. At any
other temperature, correct the SHC read from the table of cooling capacities as follows:
Corrected SHC
=SHC+[1.10x(1–BF)x(Fdb–80)xcfm]
Observe the rule of sign. Above 80 F, SHC correction will be positive; add
it to SHC. Below 80 F, SHC correction will be negative; subtract it from
SHC.
Btuh
4. Formulas:
SHC
F
ldb=Fedb
Leaving wet bulb = wet bulb temperature corresponding to enthalpy of air
leaving coil (h
h
lwb=hewb
Where h
–
–
is enthalpy of air entering evaporator coil (kJ/kg).
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 15.50 to 20.08 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
50TFF008,009 (21.5 AND 24.3 kW)—STANDARD MOTOR (BELT DRIVE)
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
15.1 2.13 15.9 2.41 16.6 2.66 17.3 2.92——
15.5 2.36 16.3 2.64 17.0 2.91————
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
15.5 2.18 16.2 2.34 16.9 2.69 17.6 2.97
15.9 2.22 16.7 2.52 17.4 2.85
16.6 2.45
16.8 2.55
16.1 2.24 17.0 2.65
16.4 2.38 17.2 2.75
22
Page 23
FAN PERFORMANCE (SI) — VERTICAL DISCHARGE UNITS (cont)
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
18.5 3.36 19.1 3.59
18.6 3.51 19.2 3.75
18.2 3.39 18.8 3.65 19.4 3.90
18.4 3.52 19.0 3.80 19.5 4.06
18.0 3.47 18.6 3.67 19.2 3.93 19.7 4.22
18.9 3.44
LEGEND
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85Maximum Continuous kW: 3.31
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 15.50 to 20.08 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
50TFF008,009 (21.5 AND 24.3 kW)—STANDARD MOTOR (BELT DRIVE)
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
15.5 2.15 16.0 2.43 16.4 2.71
14.8 2.14 15.6 2.41 16.4 2.70————
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
15.3 2.21 16.1 2.50 16.9 2.78——
15.8 2.32 16.5 2.60 17.1 2.88
15.1 2.27 15.0 2.53
14.2 2.19
14.6 2.35
24
Page 25
FAN PERFORMANCE (SI) — HORIZONTAL DISCHARGE UNITS (cont)
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
BkW — Fan Input kW x Motor Efficiency
kW— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
18.6 3.41
18.2 3.40 18.8 3.67
17.3 3.23 17.9 3.44 18.5 3.65 19.1 3.92
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85Maximum Continuous kW: 3.31
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
18.4 3.51 19.0 3.80
18.7 3.55
25
Page 26
Performance data (cont)
FAN PERFORMANCE (ENGLISH) — VERTICAL DISCHARGE UNITS
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 930 to 1205 rpm. Other rpms may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 620 to 880 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
Bhp— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 930 to 1205 rpm. Other rpms may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 620 to 880 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
1. Boldface indicates field-supplied drive required (see Note 3).
2.indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
LEGEND*Extensive motor and electrical testing on these units ensures that the
Bhp— Brake Horsepower
BkW — kW x Motor Efficiency
full range of the motors can be utilized with confidence. Using your fan
motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
MTR— Motor
OAT— Outdoor-Air Thermostat
OFC— Outdoor-Fan Contactor
OFM— Outdoor-Fan Motor
P—Plug
PL— Plug AssemblyQT—Quadruple Terminal
R—Relay
SAT— Supply-Air Thermostat
SEN— Sensor
SW1—Switch Fully Open
SW2 — Switch Fully Closed
SW3 — Switch Min Vent Position
SW4—Switch Max Vent Position
TB— Terminal Block
TC— Thermostat-Cooling
TH— Thermostat-Heating
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
NOTES
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C
wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat:
HH07AT170, 172, 174 and P272-2783
Subbase:
HH93AZ176, 178 and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
37
Page 38
Controls
Operating sequence
Cooling, units without economizer — When thermo-
stat calls for cooling, terminals G and Y1 are energized.
The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator-fan
motor, compressor no. 1 and condenser fans start. The
liquid line solenoid valve for compressor no. 1 is deenergized to open. The condenser-fan motor runs continuously
while unit is cooling. On 50TFF008-014 units, if the thermostat calls for a second stage of cooling by energizing Y2,
compressor contactor no. 2 (C2) is energized and compressor no. 2 starts.
Heating, units without economizer (If Accessory
Heater is Installed) — Upon a call for heating through
terminal W1, IFC and heater contactor no. 1 (HC1) are
energized. On units equipped for 2 stages of heat, when
additional heat is needed, HC2 is energized through W2.
Cooling, units with Durablade economizer — When
the outdoor-air temperature is above the outdoor-air thermostat (OAT) setting and the room thermostat calls for
cooling, compressor contactor no. 1 is energized to start
compressor no. 1 and the condenser-fan motor. The
evaporator-fan motor is energized and the economizer
damper moves to the minimum position. Upon a further
call for cooling, compressor contactor no. 2 will be energized (50TFF008-014), starting compressor no. 2. After
the thermostat is satisfied, the damper moves to the fully
closed position.
When the outdoor-air temperature is below the OAT setting and the thermostat calls for cooling, the economizer
dampers move to the minimum position. If the supply-air
temperature is above 13.9 C (57 F), the damper continues
to open until it reaches the fully open position or until the
supply-air temperature drops below 13.9 C (57 F).
When the supply-air temperature falls to between
13.9 C (57 F) and 11.1 C (52 F), the damper will remain at
an intermediate open position. If the supply-air temperature falls below 11.1 C (52 F), the damper will modulate
closed until it reaches the minimum position or until the
supply-air temperature is above 11.1 C (52 F). When the
thermostat is satisfied, the damper will move to the fully
closed position.
If the outdoor air alone cannot satisfy the cooling
requirements of the conditioned space, economizer cooling is integrated with mechanical cooling, providing
second-stage cooling. Compressor no. 1 and the
condenser fan will be energized and the position of the
economizer damper will be determined by the supply-air
temperature. Compressor no. 2 (50TFF008-014) is locked
out.
When the second stage of cooling is satisfied, the compressor and condenser-fan motor will be deenergized.
The damper position will be determined by the supply-air
temperature.
When the first stage of cooling is satisfied, the damper
will move to fully closed position.
Cooling, units with EconoMi$er (50TFF007) —
When the outdoor-air temperature (OAT) is above the
ECON SP set point and the room thermostat calls for
Stage 1 cooling (R to G + Y1), the indoor (evaporator) fan
motor (IFM) is energized and the EconoMi$er damper
modulates to minimum position. The compressor contactor is energized to start the compressor and outdoor (condenser) fan motor (OFM). After the thermostat is satisfied,
the damper modulates to the fully closed position when the
IFM is deenergized.
When the OAT is below the ECON SP setting and the
room thermostat calls for Stage 1 cooling (R to G + Y1),
the EconoMi$er modulates to the minimum position when
the IFM is energized. The EconoMi$er provides Stage 1 of
cooling by modulating the return and outdoor-air dampers
to maintain a 12.8 C (55 F) supply air set point. If the
supply-air temperature (SAT) is greater than 13.9 C (57 F),
the EconoMi$er modulates open, allowing a greater
amount of outdoor air to enter the unit. If the SAT drops
below 11.7 C (53 F), the outdoor air damper modulates
closed to reduce the amount of outdoor air. When the SAT
is between 11.1 and 13.9 C (53 and 57 F), the
EconoMi$er maintains its position.
If outdoor-air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the
MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below.
NOTE: Compressor has a 2-minute Minimum On, Minimum Off, and Interstage delay timer.
1. If Y1 is energized, and the room thermostat calls for
Y2 (2-stage thermostat), the compressor and OFM
are energized. The EconoMi$er damper is maintained at its current position.
2. If Y1 is energized for more than 20 minutes, and Y2
is not energized (whether or not a 2-stage thermostat
is used), the compressor and OFM are energized.
The EconoMi$er damper is maintained at its current
position.
3. If Y1 is energized, and the compressor is already
energized (see Step 2) and the room thermostat calls
for Y2, the compressor continues to operate.
4. If compressor is energized and the thermostat is satisfied, the compressor, the OFM, and IFM are deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
Cooling, units with EconoMi$er (50TFF008-014)
— When the outdoor-air temperature (OAT) is above the
ECON SP set point and the room thermostat calls for
Stage 1 cooling (R to G + Y1), the indoor (evaporator) fan
motor (IFM) is energized and the EconoMi$er damper
modulates to minimum position. The compressor contactor is energized to start the compressor and outdoor (condenser) fan motor (OFM). After the thermostat is satisfied,
the damper modulates to the fully closed position when the
IFM is deenergized.
When the OAT is below the ECON SP setting and the
room thermostat calls for Stage 1 cooling (R to G + Y1),
the EconoMi$er modulates to the minimum position when
the IFM is energized. The EconoMi$er provides Stage 1 of
cooling by modulating the return and outdoor-air dampers
to maintain a (12.8 C) 55 F supply air set point. If the supply-air temperature (SAT) is greater than 13.9 C (57 F), the
EconoMi$er modulates open, allowing a greater amount of
outdoor air to enter the unit. If the SAT drops below
11.7 C (53 F), the outdoor air damper modulates closed to
reduce the amount of outdoor air. When the SAT is between 11.7 and 13.9 C (53 and 57 F), the EconoMi$er
maintains its position.
38
Page 39
If outdoor-air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the
MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below.
NOTE: Compressors have a 2-minute Minimum On, Minimum Off, and Interstage delay timer.
1. If Y1 is energized, and the room thermostat calls for
Y2 (2-stage thermostat), compressor no. 1 and OFM
are energized. The EconoMi$er damper is maintained at its current position.
2. If Y1 is energized for more than 20 minutes, and Y2
is not energized (whether or not a 2-stage thermostat
is used), compressor no. 1 and OFM are energized.
The EconoMi$er damper is maintained at its current
position.
3. If Y1 is energized, and compressor no. 1 is already
energized (see Step 2) and the room thermostat calls
for Y2, compressor no. 1 continues to operate. If Y2
remains energized for more than 20 minutes, compressor no. 2 is energized.
NOTE: Compressor no. 2 cannot be energized unless
there is a signal for Y2 from the space thermostat.
4. If compressor no. 2 is energized, and the Y2 signal
from the thermostat is satisfied, compressor no. 1
and 2 are deenergized. Reasserting Y2 will start compressor no. 1 and (after a 20-minute interstage delay)
compressor 2.
5. If compressor no. 1 is energized and the thermostat is
satisfied, compressor no. 1, the OFM, and IFM are
deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
Heating, units with economizer (If Accessory
Heater is Installed) — When the room thermostat calls
for heat through terminal W1, the evaporator-fan contactor and heater contactor no. 1 are energized. On units
equipped for 2 stages of heat, when additional heat is
needed, heater contactor no. 2 is energized through W2.
The economizer damper moves to the minimum position
during heating. When the thermostat is satisfied, the
damper moves to the fully closed position.
TEMP systems
A TEMP System is a network of communicating Carrier
TEMP System Thermostats and rooftop, factory-mounted
Apollo direct digital controls, each serving its own zone
and heating/cooling unit. Networking allows your building
manager to easily access each of your systems from a single location...whether they are in the same building or
located throughout town.
The TEMP System’s inherently flexible, modular base
design supports the exact number of independent, single
zone systems you require...no more, no less, no compromises.
Ideal for department stores, small office buildings, fast
food chains, schools and hotels, a TEMP System is a
cost-effective way to maintain comfortable building
environments.
TEMP SYSTEM THERMOSTAT (WITH TIMECLOCK)TEMP SYSTEM THERMOSTAT (WITHOUT TIMECLOCK)
39
Page 40
Controls (cont)
Variab le Vo lum e/ Variabl e Te mpera tur e
(VVT®) Systems
VVT Systems are dedicated to total building comfort. Carrier thermostats, zone dampers, and HVAC equipment
with factory-mounted direct digital controls continually
monitor and adjust their operation to ensure uninterrupted
and personalized comfort for all occupants.
Through the use of communicating electronic controls,
VVT Systems are able to provide the comfort of a multiple
zone system while using the installation, operating and
maintenance economics of single zone equipment...virtually putting an end to the cost vs comfort compromise.
40
Page 41
Application data
Outdoor installation — Units approved for outdoor
installation only.
Ductwork — Secure vertical discharge ductwork to roof
curb. For horizontal discharge applications, either attach
ductwork to unit, or use field-supplied flanges attached to
the horizontal discharge openings and attach all ductwork
to flanges.
Horizontal discharge — To convert from vertical discharge to horizontal discharge:
1. Remove economizer or two-position damper to gain
access to return duct opening.
2. Move the horizontal-discharge duct opening covers to
the vertical discharge openings.
3. Rotate economizer or two-position damper
90 degrees.
4. Rotate the barometric relief damper 90 degrees.
5. Install block-off plate over the opening on the access
panel.
Thru-the-curb service connections — Roof curb connections allow field power wires and control wires to enter
through the roof curb opening.
Thru-the-bottom service connections — Power connections made through the bottom of the unit must utilize
an accessory Carrier roof curb and accessory thru-the-bottom power connection accessory kit.
Thermostat — Use of 2-stage heating and cooling thermostat is recommended for all units. A 2-stage cooling
thermostat is required on units with accessory economizer
to provide integrated cooling.
Heating-to-cooling changeover — All units are automatic changeover from heating to cooling when automatic
changeover thermostat and subbase are used.
Airflow — Units are draw-thru on cooling and blow-thru
on heating.
Maximum airflow — To minimize the possibility of condensate blow-off from evaporator, airflow through units
should not exceed 67 L/s per kW (500 cfm/ton).
Minimum airflow — For cooling minimum airflow is
40 L/s per kW (300 cfm/ton). For 50TFF007-014 units
with electric heating, required minimum L/s (cfm) is 849
(1800) for 50TFF007; 1062 (2250) for 50TFF008; 1203
(2550) for 50TFF009; and 1416 (3000) for 50TFF012
and 014.
Minimum ambient cooling operating temperature
— The minimum temperature for standard units is –4 C
(25 F). With accessory Motormaster® II control, units can
operate at outdoor temperatures down to –17.8 C (0° F).
Internal unit design — Due to Carrier’s internal unit
design (draw-thru over the motor), air path, and specially
designed motors, the full kW horsepower (maximum continuous bkW and bhp) listed in the Physical Data tables and
the notes following each Fan Performance table can be utilized with confidence.
Using Carrier motors with the values listed in the Physical and Fan Performance Data tables will not result in nuisance tripping or premature motor failure. The unit
warranty will not be affected.
Apollo direct digital controls — The Apollo direct digital controls must be used with either a Carrier master or
monitor thermostat.
41
Page 42
Guide specifications
Packaged Rooftop Cooling Unit with
Electric Heat Option — Constant Volume
Application
HVAC Guide Specifications
Size Range: 17.6 to 35.9 kW (5.0 to 10.2 Tons)
Carrier Model Number: 50TFF
Part 1 — General
1.01 SYSTEM DESCRIPTION
Outdoor rooftop- or slab-mounted, electrically con-
trolled cooling unit with optional heat utilizing a hermetic compressor for cooling duty and electric
resistance coils for heating duty. Unit shall discharge
supply air vertically or horizontally as shown on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
210/240 or 360 and 270 (U.S.A.).
B. Unit shall be designed to conform to ASHRAE 15,
latest revision, and in accordance with UL 1995.
(U.S.A. Standards).
C. Roof curb shall be designed to conform to NRCA
Standards (U.S.A.).
D. Insulation and adhesive shall meet NFPA 90A
requirements (U.S.A. Standard) for flame spread and
smoke generation.
E. Unit casing shall be capable of withstanding Federal
test method (U.S.A. Standard) Standard ASTM B117
500-hour salt spray test.
F. Units shall be designed in accordance with
ISO 9001:2000, and shall be manufactured in a
facility registered to ISO 9001:2000.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit(s) shall be stored and handled per manufacturer’s
recommendations.
Part 2 — Products
2.01 EQUIPMENT (STANDARD)
A. General:
Factory-assembled, single-piece cooling unit with
optional heat. Contained within the unit enclosure
shall be all factory wiring, piping, controls, refrigerant
charge (R-22), and special features required prior to
field start-up.
B. Unit Cabinet:
Nominal Cooling
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a baked
enamel finish on all externally exposed surfaces.
2. Evaporator fan cabinet interior shall be insulated
with a minimum 13 mm (
sity neoprene coated, flexible fiberglass insulation coated on the air side.
3. Cabinet panels shall be easily removable for
servicing.
4. Holes shall be provided in the base rails for rigging shackles to facilitate overhead rigging, and
forklift slots shall be provided to facilitate
maneuvering.
5. Unit shall have a factory-installed, sloped condensate drain pan made of a non-corrosive
1
/2-in.) thick 1 lb den-
material, providing a minimum 19 mm (
connection with both vertical and horizontal
drains and shall comply with ASHRAE 62.
6. Unit shall have factory-installed filter access
panel to provide filter access with tool-less
removal.
7. Unit shall have standard thru-the-bottom power
connection capability.
C. Fans:
1. Indoor blower (evaporator fan) shall be beltdriven, double inlet, forward-curved centrifugal
type. Belt drive shall include an adjustable-pitch
motor pulley.
2. Indoor blower (evaporator-fan) shall be made
from steel with a corrosion-resistant finish and
shall be dynamically balanced.
3. Bearings shall be of the sealed, permanently
lubricated, ball-bearing type for longer life and
lower maintenance.
4. Condenser fan shall be of the direct-driven propeller type and shall discharge air vertically.
5. Condenser fan shall have aluminum blades riveted to corrosion-resistant steel spiders and shall
be dynamically balanced.
D. Compressor(s):
1. Reciprocating or scroll type fully hermetic type,
internally protected.
2. Factory rubber-mounted and internally spring
mounted for vibration isolation.
3. On independent mounting circuits (008-014).
E. Coils:
1. Condenser coils shall have aluminum plate fins
mechanically bonded to enhanced copper tubes
with all joints brazed.
2. Tube sheet openings shall be belled to prevent
tube wear.
3. Evaporator coil shall be of the full face active
design.
F. Refrigerant Components:
Refrigerant circuit components shall include:
1. Refrigerant feed system.
2. Refrigerant filter drier.
3. Service gage connections on suction, discharge,
and liquid line.
G. Filter Section:
1. Standard filter section shall consist of factoryinstalled low-velocity, throwaway 51 mm (2-in.)
thick fiberglass filters of commercially available
sizes.
2. Filter face velocity shall not exceed 1.64 m/s
(320 fpm) at nominal airflows.
3. Filter section shall use only one size filter.
4. Filters shall be accessible through an access
panel with ‘‘no-tool’’ removal.
H. Controls and Safeties:
1. Unit Controls:
Unit shall be complete with self-contained low-
voltage control circuit.
3
/4-in.)
42
Page 43
2. Standard Safeties:
a. Unit shall incorporate compressor over-
temperature and overcurrent safety devices to
shut off compressor.
b. Heating section shall be provided with the fol-
lowing minimum protections:
1) High-temperature limit switches.
2) Overcurrent protection.
3. Refrigerant Controls:
Shall contain high-pressure, loss-of-charge/
low-pressure, and freeze protection
switches.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at
46.1 C (115 F) ambient outdoor temperature,
meeting maximum load criteria of ARI Standard
210/240 or 360 (U.S.A. Standard) at ± 10%
voltage.
2. Compressor with standard controls shall be
capable of operation down to –4 C (25 F) ambient outdoor temperature.
J. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single factory-predrilled location.
K. Motors:
1. Compressor motors shall be cooled by refrigerant passing through motor windings and shall
have line break thermal and current overload
protection.
2. Indoor blower (evaporator-fan) motor shall have
permanently lubricated bearings and inherent
automatic-reset thermal overload protection.
3. Totally enclosed condenser-fan motor shall have
permanently lubricated bearings, and inherent
automatic-reset thermal overload protection.
L. Special Features:
Certain features are not applicable when the features
designated by * are specified. For assistance in
amending the specifications, your local Carrier Sales
Office should be contacted.
* 1. Direct Digital Controls:
a. Shall be available as a factory-installed option.
b. Shall actively monitor all modes of operation,
as well as evaporator-fan status, filter status,
indoor-air quality, supply-air temperature, and
outdoor-air temperature.
c. Shall work with Carrier TEMP and VVT®
systems.
d. Shall have built-in diagnostics for thermostat
commands for both staged heating and cooling, evaporator-fan operation, and economizer operation.
e. Shall be equipped with a 5-minute time delay
between modes of operation.
2. Roof Curbs: (Horizontal and Vertical)
a. Formed galvanized steel with wood nailer
strip and capable of supporting entire unit
weight.
b. Allows for installing and securing ductwork to
curb prior to mounting unit on the curb.
* 3. Integrated Economizer:
a. Integrated integral-modulating type capable
of simultaneous economizer and compressor
operation.
b. Includes all hardware and controls to provide
cooling with outdoor air.
c. Equipped with low-leakage dampers not to
exceed 3% leakage, at 249 Pa (1 in. wg) pressure differential (Durablade economizer).
d. Capable of introducing up to 100% outdoor
air in both minimum and fully open positions.
e. Equipped with a gravity relief sliding plate
damper (Durablade economizer). Damper
shall close upon unit shutoff.
f. EconoMi$er shall be equipped with a baro-
metric relief damper with up to 100% of
return air (007) or 90% of return air (008-
014) relief. Durablade economizer is
equipped with 30% of return-air relief.
g. Designed to close damper during loss-of-
power situations with emergency power supply (Durablade economizer) or spring return
built into motor (EconoMi$er).
h. Dry bulb outdoor-air thermostat (Durablade
economizer) shall be provided as standard.
Enthalpy control shall be provided as an
option.
i. Durablade economizer is a guillotine-style
damper and EconoMi$er is a parallel-blade
design.
NOTE: EconoMi$er shall also be available
with field-installed power exhaust accessory.
* 4. Manual Outdoor-Air Damper:
Manual damper package shall consist of
damper, birdscreen, and rainhood which can be
preset to admit up to 50% outdoor air for yearround ventilation.
* 5. 100% Open Two-Position Damper:
a. Two-position damper package shall include
single blade damper and motor. Admits up to
100% outdoor air.
b. Damper shall close upon indoor (evaporator)
fan shutoff.
c. Designed to close damper during loss of
power situations.
d. Equipped with barometric relief damper.
* 6. 25% Open Two-Position Damper:
a. Two-position damper package shall include
single blade damper and motor. Admits up to
25% open outdoor air.
b. Damper shall close upon indoor (evaporator)
fan shutoff.
c. Designed to close damper during loss of
power situations.
d. Equipped with barometric relief damper.
* 7. Solid-State Enthalpy Control:
a. For use with Durablade economizer
package.
b. Capable of sensing outdoor-air enthalpy
content (temperature and humidity) and
43
Page 44
Guide specifications (cont)
controlling economizer cut-in point to have
minimum heat content air passing over the
evaporator coil for most efficient system
operation.
* 8. Differential Enthalpy Sensor:
a. For use with economizer only.
b. Capable of comparing enthalpy content
(temperature and humidity) of outdoor and
indoor air and controlling economizer cutin point at the most economical level.
* 9. Electric Resistance Heaters:
a. Open wire nichrome elements with all nec-
essary safety operating controls.
b. UL (U.S.A. Standard) listed and indicated
on basic unit informative plate.
c. Available in multiples to match heating
requirements.
*10. Low-Ambient Operation (Head Pressure
Control) Package:
Consists of solid-state control and condenser-
coil temperature sensor to operate at outdoor
ambient temperatures down to –17.8 C (0° F)
by condenser-fan cycling.
*11. Thermostat and Subbase:
Provides staged cooling and heating automatic (or manual) changeover, fan control,
and indicator light.
12. Thru-The-Bottom Service Connectors:
Kit shall provide connectors to permit electri-
cal connections to be brought to the unit
through the basepan.
*13. Electronic Programmable Thermostat:
Capable of using deluxe full-featured electronic thermostat. Shall use built-in compressor cycle delay control for both heating and
cooling duty. Capable of working with
Carrier direct digital controls.
14. Condenser Coil Hail Guard Assembly:
Hail guard shall protect against damage from
hail and flying debris.
15. Condenser Coil Grille:
The grille protects the condenser coil from
damage by large objects without increasing
unit clearances.
16. Compressor Cycle Delay:
Unit shall be prevented from restarting for a
minimum of 5 minutes after shutdown.
17. Salt Spray Protection Package (008-014):
Coil guard protects coil from corrosion in
coastal areas and in areas with high sulfur
emissions.
18. Fan/Filter Status Switch:
Provides status of indoor fan (ON/OFF) or
filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used
with direct digital controls or with an indicator light at the thermostat.
19. Unit-Mounted Disconnect Switch:
Shall be factory-installed. Internally mounted,
non-fused switch provides unit power shutoff.
Shall be accessible from outside the unit.
20. Logo Kit:
Shall provide logo for field installation onto
outdoor coil grille.
21. EconoMi$er and Power Exhaust:
Package shall provide control of internal
building pressure. The system shall exhaust
up to 100% of return air.
22. Power Exhaust for Accessory EconoMi$er:
Power exhaust shall be used in conjunction
with EconoMi$er to provide the system with
the capability to exhaust up to 100% of
return air. The power exhaust is fieldinstalled accessory.
23. Outdoor-Air Enthalpy Sensor:
The outdoor-air enthlapy sensor shall be
used with the EconoMi$er device to provide
single enthalpy control. When used in conjunction with a return air enthalpy sensor,
the EconoMi$er device will provide different
enthalpy control. The sensor allows the
EconoMi$er controller to determine if outside air is suitable for free cooling.
24. Return-Air Enthalpy Sensor:
The return-air enthalpy sensor shall be used
with the EconoMi$er device. When used in
conjunction with an outdoor air enthalpy
sensor, the EconoMi$er device will provide
differential enthalpy control.
25. Return-Air Temperature Sensor:
The return-air temperature sensor shall be
used with the EconoMi$er device. When
used in conjunction with the standard
outdoor air temperature sensor, the
EconoMi$er device will provide differential
temperature control.
26. Indoor-Air Quality (CO
) Sensor:
2
a. Shall have the ability to provide demand
ventilation indoor-air quality (IAQ) control through the economizer with an IAQ
sensor.
b. The IAQ sensor shall be available in duct
mount, wall mount, and wall mount with
LED display. The set point shall have
adjustment capability.
Carrier Corporation • Syracuse, New York 132212049-00
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 b 6 b
Book 1
NewPage 44Catalog No. 005-003Printed in U.S.A.Form 50TFF-C1PD
Ta b O P2 b
Replaces: New
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.